Lighting / Electrical Breadth
As a Lighting/Electrical breadth study, an analysis of one lighting space was
performed and the space was redesigned. The space which was selected to be analyzed
and redesigned was the ground floor computer classroom. In this analysis, an alternative
approach to the lighting design of the selected space was performed using a computer
lighting design program called Lightscape. In addition to this rendering of the redesigned
lighting system’s performance, the redesign was assessed in terms of allowable power
density according to the ASHRAE 90.1 standard.
Furniture Layout and Floor Plan of Ground Floor Computer Classroom:
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-33-
Existing Lighting Conditions:
The computer classroom on the ground floor has the dimensions, 43’-3”x31’-
2”x8’-0”. The lighting system in this room consists of 4 rows of 20 evenly spaced 2x4
recessed lensed troffers. These 277 V fixtures utilize 3- 32 Watt T8 lamps. They operate
with electronic ballasts and have two different switching zones.
Design Criteria According to the IESNA Lighting Handbook, a space with VDT usage should
have a horizontal illuminance of at least 50 footcandles on the work plane, and a
horizontal illuminance of at least 5 footcandles. The IESNA lighting handbook also
outlines important design considerations for this type of a space. It was considered very
important to control glare in a space like this, as it could detract from the viewing
capabilities of the VDT users in the space. This design consideration has been addressed
in this redesign by changing the existing 2x4 lensed troffers to new Indirect/Direct
pendants. These pendants provide a direct component, but provide most of their
illumination indirectly, thus eliminating much of the glare associated with lighting in
VDT usage. It is also very important to consider the source/task/eye geometry of the
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-34-
lighting in this space. This means that it was vital to space fixtures out of an offending
zone for the VDT user so that glare was further eliminated. It was also very important to
keep the illuminances of the room surfaces uniform, therefore eliminating any patterns or
distortions that may be seen in reflections on a VDT screen. This could be done by
spacing the fixtures evenly throughout the space. Daylighting is typically important in
VDT usage spaces, but was not an issue with this space since there are no windows into
the space.
Fixture used in redesign
The classica ID fixture has been selected for this application because it provides
20%-30% downlight for task lighting and the rest as indirect light in order to eliminate
glare in a VDT space. This lamp is four feet long and contains 3 T8 fluorescent lamps, 32
Watts each. It operates at 277 V, and has an electronic ballast.
Light Loss Factors The room cavity ratio was calculated below: RCR= 5h (l+w)/ (l*w) RCR= 5*8’ (43.25’+31.1666’)/ (43.25*31.1666) = 2.199 The maintenance category for the luminaire selected for this redesign was II, the
cleaning interval was assumed to be 12 months, and the space was considered clean.
Therefore, the luminaire dirt depreciation in this case would be (0.94)*(0.068)=0.06392,
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-35-
meaning that the expected dirt depreciation was approximately 6.392%. The ballast factor
for this lamp is approximately 0.8. The RSDD for this space is 0.9012. The LLD for this
particular lamp is 2715/2950=0.92. Therefore, the total Light Loss Factor for this fixture
is: 0.7215
Power Density of existing vs Redesign system As it turned out, the power density for both of the designs are the same. Since
both fixtures use the same T8 lamps, and the layouts both have 20 fixtures each, the
power density was: 1720 Watts/2950 ft^2= 1.276 Watts per square foot for each design.
This power density was within the allowable amount for this space as defined in the
ASHRAE standard 90.1.
Performance Results of Redesign system using Lightscape:
Room Layout in Lightscape:
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-36-
Rendering from front of room:
Illuminance Values From front of room
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-37-
Lightscape Rendering from back of room:
Close-Up renderings of Computer Desk Stations:
Daniel Chwastyk F.W. Olin Center Structural Option Union College, NY
-38-
Illuminance Values at Typical Computer Workstations:
Conclusions and Recommendations: The results of the analysis of this redesign showed that the use of these new
fixtures meets all requirements for the illumination and power density of the space. The
use of these fixtures would help eliminate glare from the VDT screens better than the use
of the existing 2x4 troffers in the room. It would therefore be recommended to use this
indirect/direct type of fixture for the lighting design of this space.