lightning protection · 2015. 8. 18. · ffflflflflflffff˙ 19 lpi® stormaster ese key benefits...

9
LIGHTNING PROTECTION INTERNATIONAL PTY LTD www.lpi.com.au 19 LPI® Stormaster ESE Key Benefits Complies to standard NF C 17-102 Tested in high voltage laboratory Easy to install Cost effective Product Description The LPI Stormaster ESE range of terminals provides a safe and efficient system for the protection of your facility from direct lightning strikes. The LPI Stormaster ESE terminal captures the lightning energy at a preferred point. The energy is conveyed to ground via a downconductor(s). When the energy enters the dedicated lightning earth, it is safely dissipated without risk to personnel and equipment. The Stormaster ESE range of terminals have been fully tested in accordance with NF C 17-102 in a high voltage laboratory. Stormaster ESE Principles The Stormaster Early Streamer Emission air terminal uses the naturally occurring electrical field to complete the timely release of an upward leader. This process provides for a safe and efficient method of controlling dangerous lightning energy at a preferred point. As a thunder storm gathers overhead the ambient electrical field surrounding the Stormaster ESE begins to rise in voltage. Upon the approach of a down leader towards the protected area there is a rapid increase in the electric field which initiates the triggering of an upward streamer from the Stormaster ESE terminal. The concept of earlier streamer emission allows for a larger or enhanced area of protection to be provided by the Stormaster ESE in comparison to a conventional rod. With the release of the upward streamer from the finial tip earlier than other competing structural points, the Stormaster ESE terminal becomes a preferred point for the capture of the lightning discharge within the protected area. Certified Performance As one of the leading companies in the field of lightning protection, LPI has invested heavily in field and laboratory testing as part of its on-going commitment to research and development. Throughout the product development of the Stormaster ESE terminals the proto-type models were subjected to intense testing under high voltage conditions. Following further refinements the Stormaster terminals were subjected to final testing by an independently accredited test laboratory which completed testing in full compliance with the French National Standard NF C 17-102. The final testing on the Stormaster ESE terminals showed effective performance as defined in the French National Standard. LIGHTNING PROTECTION IMPORTANT: Stormaster ESE terminal to be a minimum of 2 metres above the highest point of the building. Recommended clearance height = 5 metres LPI GROUND RESISTANCE IMPROVEMENT POWDER ORDERING CODE: GRIP-10 LPI STORMASTER ESE AIR TERMINAL ORDERING CODE: STORMASTER-ESE-60 STORMASTER-ESE-50 STORMASTER-ESE-30 STORMASTER-ESE-15 LPI UPPER TERMINATION KIT ORDERING CODE: UTERMKIT-Mk2 LPI SUPPORT MAST ORDERING CODE: FRP-2M FRP-3M FRP-4M LPI INLINE COUPLING ORDERING CODE: ILCOUPLING LPI GUY KIT ORDERING CODE: GUYKIT-4M GUYKIT-4M-SS GUYKIT-7M GUYKIT-7M-SS LPI CABLE TIES ORDERING CODE: SS-CABTIE-STD SS-CABTIES-L LPI LOWER MAST ASSEMBLY WITH BASE ORDERING CODE: ALUMB-3M ALUMB-4M ALUMB-5M ALUMB-6M LPI HIGH VOLTAGE SHIELDED CABLE ORDERING CODE: HVSC-PM LPI HIGH VOLTAGE SHIELDED CABLE LPI SADDLES AND FIXINGS ORDERING CODE: SAD FIX LPI LIGHTNING STRIKE RECORDER ORDERING CODE: LSR1 LPI LOWER TERMINATION KIT ORDERING CODE: LTERMKIT LPI INSPECTION PIT ORDERING CODE: EPIT-P EPIT-D LPI EARTHING SYSTEM TYPICAL PRODUCTS REQUIRED FOR RADIAL LP EARTH: 4 X CBER1214 4 X RTC253 1 X EPIT-P 1 X GRIP-10 30 X FL6T253C Early Streamer Emission Air Terminals

Upload: others

Post on 18-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au 19

LPI® Stormaster ESEKey Benefits

∆ Complies to standard NF C 17-102

∆ Tested in high voltage laboratory

∆ Easy to install

∆ Cost effective

Product DescriptionThe LPI Stormaster ESE range of terminals provides a safe and efficient system for the protection of your facility from direct lightning strikes. The LPI Stormaster ESE terminal captures the lightning energy at a preferred point. The energy is conveyed to ground via a downconductor(s). When the energy enters the dedicated lightning earth, it is safely dissipated without risk to personnel and equipment.

The Stormaster ESE range of terminals have been fully tested in accordance with NF C 17-102 in a high voltage laboratory.

Stormaster ESE Principles The Stormaster Early Streamer Emission air terminal uses the naturally occurring electrical field to complete the timely release of an upward leader. This process provides for a safe and efficient method of controlling dangerous lightning energy at a preferred point.

As a thunder storm gathers overhead the ambient electrical field surrounding the Stormaster ESE begins to rise in voltage. Upon the approach of a down leader towards the protected area there is a rapid increase in the electric field which initiates the triggering of an upward streamer from the Stormaster ESE terminal. The concept of earlier streamer emission allows for a larger or enhanced area of protection to be provided by the Stormaster ESE in comparison to a conventional rod.

With the release of the upward streamer from the finial tip earlier than other competing structural points, the Stormaster ESE terminal becomes a preferred point for the capture of the lightning discharge within the protected area.

Certified PerformanceAs one of the leading companies in the field of lightning protection, LPI has invested heavily in field and laboratory testing as part of its on-going commitment to research and development.

Throughout the product development of the Stormaster ESE terminals the proto-type models were subjected to intense testing under high voltage conditions. Following further refinements the Stormaster terminals were subjected to final testing by an independently accredited test laboratory which completed testing in full compliance with the French National Standard NF C 17-102. The final testing on the Stormaster ESE terminals showed effective performance as defined in the French National Standard.

LIGHTNING PROTECTION

IMPORTANT:Stormaster ESE terminal to be a minimum of 2metres above thehighest point of the building. Recommendedclearance height= 5 metres

LPI GROUNDRESISTANCEIMPROVEMENTPOWDERORDERING CODE:GRIP-10

LPI STORMASTER ESE AIR TERMINALORDERING CODE: STORMASTER-ESE-60 STORMASTER-ESE-50 STORMASTER-ESE-30 STORMASTER-ESE-15

LPI UPPER TERMINATION KITORDERING CODE: UTERMKIT-Mk2

LPI SUPPORT MASTORDERING CODE: FRP-2M FRP-3M FRP-4M

LPI INLINE COUPLINGORDERING CODE: ILCOUPLING

LPI GUY KIT ORDERING CODE: GUYKIT-4M GUYKIT-4M-SS GUYKIT-7M GUYKIT-7M-SS LPI CABLE TIESORDERING CODE: SS-CABTIE-STD SS-CABTIES-L

LPI LOWER MAST ASSEMBLY WITH BASEORDERING CODE: ALUMB-3M ALUMB-4M ALUMB-5M ALUMB-6M

LPI HIGH VOLTAGE SHIELDED CABLEORDERING CODE: HVSC-PM

LPI HIGH VOLTAGE SHIELDED CABLE

LPI SADDLES AND FIXINGSORDERING CODE: SAD FIX

LPI LIGHTNING STRIKE RECORDERORDERING CODE: LSR1

LPI LOWER TERMINATION KITORDERING CODE: LTERMKIT

LPI INSPECTION PITORDERING CODE: EPIT-P EPIT-D

LPI EARTHING SYSTEMTYPICAL PRODUCTS REQUIREDFOR RADIAL LP EARTH:4 X CBER12144 X RTC2531 X EPIT-P1 X GRIP-1030 X FL6T253C

Early Streamer Emission Air Terminals

Page 2: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au20

Early Streamer Emission Air Terminals

LIGHTNING PROTECTION

LPI® STORMASTER ESE TERMINAL

MAST ASSEMBLY WITH GI ADAPTOR

SUITABLE MOUNTING SADDLES

BASE OF MAST PIPE

COMPRESSION LUG

PVC COVERED COPPER CABLE

MOUNTING BOLT &STAINLESS STEEL WASHER

EXISTING STRUCTURE

LPI® SADDLES FOR CANTILEVERING MAST

IMPORTANT:One third of the mast heightmust be securely fixed to the structure.Stormaster ESE Terminal to be a minimum of 2 metres above the highest point of the building. Recommended clearance height = 5 metres.

THREADED GI ADAPTOR (FEMALE THREAD 2 INCH BSP)

Research and DevelopmentThe company has an ongoing commitment to Research and Development.

LPI personnel and its associates have been involved in a number of field trials throughout lightning prone regions of the world. This experience has extended throughout such countries as Australia, Indonesia, Sri Lanka the USA and South Korea.

Stormaster GI Version

Page 3: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au 21

Early Streamer Emission Air Terminals

LPI® Stormaster ESE Terminals

LIGHTNING PROTECTION

Stormaster ESE Air Terminal

Description: Stormaster-ESE-15

Sphere Dimensions: 106mm (Diameter), 344mm (Height)

Panel Material: Anodised Aluminium

Terminal Colour: Gold

Weight: 1.80kg

Insulation Material: UV Rated Evoprene

Down Conductor Connection: Lug connection GI connection

Description: Stormaster-ESE-30

Sphere Dimensions: 106mm (Diameter), 344mm (Height)

Panel Material: Anodised Aluminium

Terminal Colour: Gold

Weight: 1.80kg

Insulation Material: UV Rated Evoprene

Down Conductor Connection: Lug connection GI connection

Description: Stormaster-ESE-50

Sphere Dimensions: 106mm (Diameter), 344mm (Height)

Panel Material: Anodised Aluminium

Terminal Colour: Gold

Weight: 1.80kg

Insulation Material: UV Rated Evoprene

Down Conductor Connection: Lug connection GI connection

Description: Stormaster-ESE-60

Sphere Dimensions: 155mm (Diameter), 406mm (Height)

Panel Material: Anodised Aluminium

Terminal Colour: Gold

Weight: 2.80kg

Insulation Material: UV Rated Evoprene

Down Conductor Connection: Lug connection GI connection

Ordering Code STORMASTER-ESE-15 STORMASTER-ESE-15 W/O CONNECTOR

Ordering Code STORMASTER-ESE-30 STORMASTER-ESE-30 W/O CONNECTOR

Ordering Code STORMASTER-ESE-50 STORMASTER-ESE-50 W/O CONNECTOR

Ordering Code STORMASTER-ESE-60 STORMASTER-ESE-60 W/O CONNECTOR

All Stormaster models are available in Stainless Steel, contact LPI for full details.

Page 4: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au22

LIGHTNING PROTECTION

LPI® Upper Termination KitLPI®‘s Upper Termination Kit is designed for use with the LPI HVSC down-conductor. The LPI High Voltage Shielded Cable is an insulated downconductor used to safely convey lightning currents from an air terminal to a dedicated lightning earth termination, while avoiding galvanic conduction to the structure being protected. The Upper Termination Kit provides all accessories for the High Voltage termination of the HVSC downconductor to the Stormaster ESE Terminal. The LPI® UTERMKIT-MK2 has been tested in compliance with IEC 600601, 2nd Edition, 1989-11.

LPI® FRP Support MastLPI®‘s Fibreglass reinforced pole (FRP) mast is an insulated and water resistant mounting pole which is designed to provide the necessary electrical isolation and mounting strength at the position where the high voltage upper termination between the High Voltage Shielded Cable (HVSC) downconductor and LPI Stormaster terminal is completed.

Mounting Accessories

Upper Termination KitOrdering Code UTERMKIT-MK2

Description: Upper Termination Kit Mark 2

Maximum Voltage: 280kV 1.2/50μs impulse

Operating Temperatures: - 20°C to + 85°C

Pack Dimensions: 70mm x 70mm x 1250mm

Weight: 0.75kg

Contents: Instruction, Semi-conducting tape, Crimp Lug, Heat Shrink Tube, Insulated Friction Cutting Tool, Insulation Tape

FRP Support MastDescription Fibreglass Reinforced Pole (FRP)

Colour: Black

Material : Fibreglass

Construction Type: Pre-Impregnated Reinforced Epoxy Resin Laminate (Flame Retardant)

Resin Tensile Strength: 70 MPa

Resin Tensile Modulus: 2.9 GPa

Resin Tensile Strain: 2.7%

Resin Poisson Ratio: 0.35

FRP Support MastOrdering Weight DimensionsCodeFRP-2M 2.7kg Length 2000mm, Outer diameter 68mm, Inner diameter 60mm

FRP-3M 4.0kg Length 3000mm, Outer diameter 68mm, Inner diameter 60mm

FRP-4M 5.3kg Length 4000mm, Outer diameter 68mm, Inner diameter 60mm

Page 5: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au 23

LIGHTNING PROTECTION

Mounting Accessories

LPI® Inline CouplingLPI®’s Inline Coupling is a purpose designed coupling which allows for the clamping of the FRP mast to the Aluminium lower mast. The inline coupling provides 3 Guy anchoring points and provides an exit point for the HVSC.

LPI® Guy KitLPI®‘s non conductive guy kits are provided in variable lengths to suit specific mast and terminal heights. The purpose designed guying kits are designed for anchoring from a guy ring or an inline coupling.

Inline CouplingOrdering code ILCOUPLING

Description: Inline Coupling

Material: Cast Aluminium

Dimension: 550mm x 150mm x 120 mm

Weight: 2.5 kg

Anchoring Points: 3

Max. Clamping Torque: 55kg/cm

Guy KitOrdering Code GUYKIT-4M GUYKIT-7M

Description: Stainless Steel fittings and non conductive synthetic guy wire kits

Material: Dyneema® is a UHMwPE fibre, which is non conductive, UV stabilised, moisture resistant and chemically inert

Application: Designed to provide additional stabilizing/securing of mast arrangement where deemed necessary

Diameter: 4mm

Tensile yield strength: 543kg

Weight: 0.5kg 0.8kg

Guy KitOrdering Code GUYKIT-4M-SS GUYKIT-7M-SS

Description: Stainless Steel guy wire kits

Material: Stainless Steel, Grade 316

Application: Designed to provide additional stabilizing/securing of mast arrangement from the inline coupling only

Diameter: 3.2mm

Tensile yield strength: 450kg

Weight: 0.75kg 1.2kg

Page 6: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au24

LIGHTNING PROTECTION

Guy RingLPI®‘s Guy Ring provides 3 guy points for mounting between the top section of the FRP mast and the Stormaster ESE Terminal.

LPI® Lower Mast AssemblyLPI uses Aluminium Mast’s as the lower mast assembly due to it’s high strength and light weight characteristics.

LPI® Cantilevering SaddlesPurpose designed stainless steel saddles for cantilevering Aluminium mast of 69.9mm outer diameter to flat vertical surface.

Guy Ring

Ordering Code Guy Ring

Material: Cast Aluminium

Dimension: 110mm x 110mm x 10 mm

Weight: 0.12kg

Guy Hole Diameter: 10mm

Lower Mast Assembly

Description Aluminium Mast

Colour: Silver

Material: Aluminium

Inside Diameter: 61.9mm

Outside Diameter: 69.9mm

Lower Mast AssemblyLength 3 Metre 4 Metre 5 Metre 6 Metre

Weight: 7kg, 9kg, 11.7kg, 14.4kg, 8kg (with base) 10kg (with base) 12.7kg (with base) 15.4kg (with base)

Ordering Code (without base): ALUM-3M ALUM-4M ALUM-5M ALUM-6M

Ordering Code (with base): ALUMB-3M ALUMB-4M ALUMB-5M ALUMB-6M

Ordering Code (with GI Male Adaptor): ALUM3M-MGI ALUMB4M-MGI ALUMB5M-MGI ALUMB6M-MGI

Cantilevering SaddlesOrdering Code CANTSAD

Description: 70mm Saddles for mounting of Aluminium Mast (3 per set)

Material: Stainless Steel

Weight: 180g per saddle, 540g per set

Dimension: 130mm (L) x 70mm (W) x1.2mm (D)

Hole Fixing Diameter: 8mm

Mounting Accessories

Page 7: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au 25

LIGHTNING PROTECTION

Offset BracketLPI‘s Offset Brackets are designed for the off-set cantilevering of aluminium support masts.

U-BoltLPI®’s U-Bolt set is specifically designed to allow for the secure clamping of aluminium or FRP mast to tower section or handle rail.

High Voltage Shielded CableLPI®‘s High Voltage Shielded Cable (HVSC) is a high integrity low impedance cable, which is designed to convey lightning energy to ground with minimal risk of side flashing or structure electrification. The design of the HVSC incorporates carefully selected dielectric components to ensure optimum performance under high impulse conditions. This design provides a low inductance per unit length with low surge impedance. LPI®‘s HVSC has been tested in compliance to IEC test standard: IEC 60-1:1989 and IEC 600601, 2nd Edition,1989-11.

High Voltage Shielded Cable

Offset Bracket

Description Offset Bracket

Colour: Silver

Material: Stainless Steel, 316

Nominal Clamping OD: 70 mm

Ordering Code HVSC-PM or HVSC-500M

Description: High Voltage Shielded Cable

Concentric conductor: Nominal cross sectional area 50mm2

Sheath Thickness: 3.3mm +/-0.3mm

Overall Diameter: 37mm +/-0.8mm

Weight of Cable: 2.050 kg per metre

DC Resistance of conductor at 20ºC: Max. 0.387 Ohm/km

DC Resistance of screen at 20ºC: Max. 0.492 Ohm/km

Insulation resistance at 20ºC: Min. 1,830 M Ohm-km

Maximum Voltage: 280kV 1.2/50μs impulse

U-Bolt

Ordering Code U-Bolt

Description: U-Bolt, 2 per set

Material: U-bolt:Stainless Steel, Plate:Aluminium

Weight: 375g per U-bolt, 750g per set

Dimension: 80mm Diameter, 170mm Length

Core

Lightning Downconductor(HVSC)

Cross Section

Sheath

Binding

OuterConductor

Insulation

Binding

InnerConductor

Mounting Accessories

Page 8: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au26

LIGHTNING PROTECTION

Cable TiesLPI®‘s Cable Ties are designed for securing the HVSC downconductor to structures and mast assembly.

Cable SockLPI®‘s Cable Sock is designed for the mounting support of the HVSC Downconductor when installing a free standing mast arrangement.

Saddles and FixingsLPI®‘s Saddles and fixings are specially designed for securing of HVSC downconductor to structures.

Saddles and Fixings

Ordering Code SAD FIX

Description: Saddles and Fixings

Material: Stainless Steel, Grade 304

Dimension: 90mm Length, 1.2mm Thickness

Fixing hole diameter: 7mm

Weight: 25g

Cable Sock

Ordering Code Cable Sock

Description: Cable sock for HVSC support

Material: Two-ply galvanised steel wire strand

To grip cable diameter (mm): 28-40

Grip Length (mm): 600

Max. Pull approx. (kn): 24

Cable Ties

Ordering Code SS-CABTIE-STD SS-CABTIES-L

Description: Cable Ties

Material: Stainless Steel

Length: 360mm 520mm

Width: 7.9mm 7.9mm

Beam Clamp and Cable SupportLPI® Beam Clamp and Cable Support are specifically designed for the securing of the HVSC downconductor to tower legs.

Beam Clamp and Cable Support

Ordering Code BCHVSC

Description: Beam Clamp and HVSC Clamp

Material: Stainless steel, Polymer

Dimension: 60mm x 60mm x 50mm

Fixing hole diameter: 38mm

Weight: 180g

Mounting Accessories

Page 9: LIGHTNING PROTECTION · 2015. 8. 18. · ffflflflflflffff˙ 19 LPI® Stormaster ESE Key Benefits ∆ Complies to standard NF C 17-102 ∆ Tested in high voltage laboratory ∆ Easy

L I G H T N I N G P R O T E C T I O N I N T E R N A T I O N A L P T Y L T D www.lpi .com.au 27

LIGHTNING PROTECTION

Lightning Strike RecorderLPI®‘s Lightning Strike Recorder (LSR1) is a lightning strike counter. The LSR1 is simply mounted at any location along the downconductor route. It’s purpose is to record the number of strikes captured by the lightning terminal.

Lightning Strike Recorder

Ordering Code LSR1

Description: Lightning Strike Recorder

Current sensitivity: 1500A 8/20μs impulse

Operating range: Min. 1500A and Max. 220kA 8/20μs

Display: Mechanical 6 digits display (not re-settable).

Dimension: 80mm (B) x 82mm (H) x 65mm (D)

Weight: 0.4 kg

Mounting: Adjustable cable ties to accommodate a cable up to 40 mm dia. cable or 50mm x 5mm flat tape

Construction: Polycarbonate enclosure

Colour: Light Grey

Environment: IP 67 (IEC 529)

Operating Temperature: -15C to 65C

Lower Termination KitLPI®‘s Lower Termination Kit provides accessories and tools for the termination of the HVSC lower end to the dedicated lightning earth.

Lower Termination Kit

Ordering Code LTERMKIT

Description: Lower Termination Kit

Pack Dimensions: 270mm (B) x 100mm (H) x 40mm (D)

Weight: 585g

Contents: 1 x 95mm crimp lug

1 x waterproofing tape

1 x earth rod clamp

2 x warning labels

1 x insulation friction cutting tool

Mounting Accessories