Line Differential

Protection IED

Page 2: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

GR-200 seriesThe GRtransmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on dem

Powerful and wide application In addition to protection & control, GRadvantage of developments in information & communications technology.

APPLICATION

GRL200 line differential protection is IED platform and has been designed to provide phaseusing digital telecommunicationsuserrequirements in addition to offering excellent performance, the high quality and operational peace of mind.

- Complete EHV/HV Transmission Line Protection package

- Communications

200 seriesThe GR-200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demowerful and wide application In addition to protection & control, GRadvantage of developments in information & communications technology.

APPLICATION

GRL200 line differential protection is IED platform and has been designed to provide phaseusing digital telecommunicationsuser-friendly IED requirements in addition to offering excellent performance, the high quality and operational peace of mind.

Complete EHV/HV Transmission Line Protection package

・ Overhead lines ・ Line differential protection for up to ・ Integrated Distance, Directional OC/EF and other voltage/current protections・ Single or parallel lines・ Lines with heavy load current・ Short or long distance lines・ Lines with weak or no・ Single/three/multiphase tripping facilitating all auto

Communications

・ Line differential and teleprotection, direct optical and Ethernet packet

・ Within substation IEC62439/PRP

200 series - 200 Series is Toshiba’s next generation of protection and control IED’s, designed for

transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software co

Meeting your needs - Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demowerful and wide application In addition to protection & control, GRadvantage of developments in information & communications technology.

APPLICATION

GRL200 line differential protection is IED platform and has been designed to provide phaseusing digital telecommunications

friendly IED will provide you with the flexibility to meet your application and engineering requirements in addition to offering excellent performance, the high quality and operational

Complete EHV/HV Transmission Line Protection package

Overhead lines or underground cables Line differential protection for up to Integrated Distance, Directional OC/EF and other voltage/current protectionsSingle or parallel lines Lines with heavy load currentShort or long distance linesLines with weak or no inSingle/three/multiphase tripping facilitating all auto

Communications

Line differential and teleprotection, direct optical and Ethernet packet-based communicationsWithin substation automation system, IEC 61850IEC62439/PRP

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive hardware and modular software combinations facilitating an ap

Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements.Future upgrade paths and minor modifications are readily achievable on demowerful and wide application - In addition to protection & control, GR-200 has been designed to meet the challenges and take advantage of developments in information & communications technology.

GRL200 line differential protection is implemented on Toshiba’s next generation GRIED platform and has been designed to provide phaseusing digital telecommunications, together with

will provide you with the flexibility to meet your application and engineering requirements in addition to offering excellent performance, the high quality and operational

Complete EHV/HV Transmission Line Protection package

or underground cables Line differential protection for up to 3Integrated Distance, Directional OC/EF and other voltage/current protections

Lines with heavy load current Short or long distance lines

in-feed Single/three/multiphase tripping facilitating all auto

Line differential and teleprotection, direct optical based communications

automation system, IEC 61850

2

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

mbinations facilitating an ap

Extensive hardware and modular software combinations provide the flexibility to meet your application and engineering requirements. Future upgrade paths and minor modifications are readily achievable on dem

200 has been designed to meet the challenges and take

advantage of developments in information & communications technology.

implemented on Toshiba’s next generation GRIED platform and has been designed to provide phase

, together with control applications. This powerful and will provide you with the flexibility to meet your application and engineering

requirements in addition to offering excellent performance, the high quality and operational

Complete EHV/HV Transmission Line Protection package

or underground cables 3 terminals

Integrated Distance, Directional OC/EF and other voltage/current protections

Single/three/multiphase tripping facilitating all auto

Line differential and teleprotection, direct optical fibbased communications

automation system, IEC 61850

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

mbinations facilitating an application oriented

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on dem

200 has been designed to meet the challenges and take advantage of developments in information & communications technology.

implemented on Toshiba’s next generation GRIED platform and has been designed to provide phase-segregated current differential protection

control applications. This powerful and will provide you with the flexibility to meet your application and engineering

requirements in addition to offering excellent performance, the high quality and operational

Complete EHV/HV Transmission Line Protection package

Integrated Distance, Directional OC/EF and other voltage/current protections

Single/three/multiphase tripping facilitating all auto-reclose schemes

fiber, ITU-T X.21,

automation system, IEC 61850-8-1 [Station bus], IEC 60870

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

plication oriented

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on dem

200 has been designed to meet the challenges and take advantage of developments in information & communications technology.

implemented on Toshiba’s next generation GRsegregated current differential protection

control applications. This powerful and will provide you with the flexibility to meet your application and engineering

requirements in addition to offering excellent performance, the high quality and operational

Integrated Distance, Directional OC/EF and other voltage/current protections

reclose schemes

X.21, ITU-T G.703, IEEE Std. C37.94

1 [Station bus], IEC 60870

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable energy systems and railway applications. Flexible adaptation is enabled using extensive

plication oriented solution.

Extensive hardware and modular software combinations provide the flexibility to meet your

Future upgrade paths and minor modifications are readily achievable on demand.

200 has been designed to meet the challenges and take

implemented on Toshiba’s next generation GR-200 Series segregated current differential protection

control applications. This powerful and will provide you with the flexibility to meet your application and engineering

requirements in addition to offering excellent performance, the high quality and operational

703, IEEE Std. C37.94

1 [Station bus], IEC 60870-5-103

200 Series is Toshiba’s next generation of protection and control IED’s, designed for transmission/distribution networks and providing a platform for distributed and renewable

Extensive hardware and modular software combinations provide the flexibility to meet your

200 has been designed to meet the challenges and take

200 Series segregated current differential protection

will provide you with the flexibility to meet your application and engineering requirements in addition to offering excellent performance, the high quality and operational

703, IEEE Std. C37.94

103 and

Page 3: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

FEATURES

• ApplicationGRL200network- Overhead lines or underground cables- Two - Lines with weak or no- Single or parallel lines- Lines with heavy load current- Short or long distance lines

• Functionality- Eight settings group- Automatic supervision- Metering and recording functions

- Time synchronization by external clock

IRIG

• Communication- System interface

100BASE100BASE

- Multi protocol 61850

FUNCTIONS• Protection- Phase- Zero

protection for - Charging current compensation- Distance protection with

zone- Backup

earth fault command protection - Non

Overcurrent backup protection- Non

phase sequence - Thermal overload protection- Broken conductor detection- Circuit breaker failure protection- Switch- Stub fault protection for one

b- Phase to

under/overvoltage protection- U- Out

EATURES

Application GRL200 can be applied in various EHV/HV network configurations.

Overhead lines or underground cablesTwo to three-Lines with weak or noSingle or parallel linesLines with heavy load currentShort or long distance lines

Functionality Eight settings groupAutomatic supervisionMetering and recording functions

Time synchronization by external clock

IRIG-B or system network

CommunicationSystem interface 100BASE-TX/1000BASE100BASE-FX, 1000BASEMulti protocol 61850 and IEC62439/

UNCTIONS Protection

Phase-segregated differential protectionZero-sequence current differential protection for Charging current compensationDistance protection with zones Backup non-directional earth fault command protection Non-directional and directional Overcurrent backup protectionNon-directional phase sequence Thermal overload protectionBroken conductor detectionCircuit breaker failure protectionSwitch-on-to-Stub fault protection for onebreaker systemPhase to neutral and phase to phase under/overvoltage protectionUnder/overfrequency protectionOut-of-step protection

can be applied in various EHV/HV configurations.

Overhead lines or underground cables-terminal lines

Lines with weak or no-infeedSingle or parallel lines Lines with heavy load currentShort or long distance lines

Eight settings groups Automatic supervision Metering and recording functions

Time synchronization by external clock

system network

Communication System interface - RS485, Fiber optic,

TX/1000BASE-FX, 1000BASE

Multi protocol - IEC 60870and IEC62439/PRP

segregated differential protectionsequence current differential

protection for high resistance earth faultsCharging current compensationDistance protection with four

directional and directional earth fault command protection

directional and directional Overcurrent backup protection

directional and directional negative phase sequence overcurrent protectionThermal overload protectionBroken conductor detectionCircuit breaker failure protection

-fault (SOTF) protectionStub fault protection for one

system neutral and phase to phase

under/overvoltage protectionnder/overfrequency protection

step protection

can be applied in various EHV/HV

Overhead lines or underground cablesterminal lines

infeed

Lines with heavy load current Short or long distance lines

Metering and recording functions Time synchronization by external clock using

RS485, Fiber optic, -T,

FX, 1000BASE-LX 60870-5-103, IEC

PRP

segregated differential protectionsequence current differential

high resistance earth faultsCharging current compensation

four independent

and directional earth fault command protection

directional and directional Overcurrent backup protection

and directional negative overcurrent protection

Thermal overload protection Broken conductor detection Circuit breaker failure protection

fault (SOTF) protection Stub fault protection for one-and-a-half

neutral and phase to phase under/overvoltage protection

nder/overfrequency protection

3

can be applied in various EHV/HV

Overhead lines or underground cables

using

RS485, Fiber optic,

IEC

• Security-

• Flexibility-

- -

- -

• Human Machine Interface- - - -

- -

segregated differential protection

high resistance earth faults

independent

and directional

and directional negative overcurrent protection

half

neutral and phase to phase

- - - -

• Control-

- - - -

• Monitoring- - - -

- - -

Security Password protectionFlexibility Various models and hardware options for

flexible applicationrequirement and controlled object

Combined 1A / 5A current inputs Multi range DC power supply: 24 to 60V /

60 to 110 V / 110 to 250V Configurable Programmable control, trip and alarm

logic with PLC tool softwareHuman Machine Interface Graphical LCD and Configurable 7 function keys USB port for local PC co Direct control buttons for open/close (O/I)

and control authority (43R/L) Help key for supporting operation Monitoring terminals for

Power swing blocking function Inrush Current Detector Direct transfer trip Fail-safe overcurrent schemeControl Single-shot (single

phase / multiphase) autoreclose

Synchronism voltage Circuit breaker and isolator Switchgear interlock check Programmable automatic sequence

control • Monitoring and Metering

VT failure detection CT failure detection Relay address monitoring Status and condition monitoring of

primary apparatus Switchgear operation monitoring Plausibility check Measurement of I, V, P, Q, PF, f, Wh and

varh

protection

Various models and hardware options for flexible application depending on system requirement and controlled objectCombined 1A / 5A current inputsMulti range DC power supply: 24 to 60V / 60 to 110 V / 110 to 250VConfigurable binary inputs and outputsProgrammable control, trip and alarm

with PLC tool softwareHuman Machine Interface

Graphical LCD and 26 LEDsConfigurable 7 function keys

port for local PC coDirect control buttons for open/close (O/I)

control authority (43R/L)Help key for supporting operation

onitoring terminals for

Power swing blocking functionInrush Current Detector

ect transfer trip safe overcurrent scheme

shot (single / three/ multi-phase) or

phase) autoreclose ronism voltage check

Circuit breaker and isolatorSwitchgear interlock check

grammable automatic sequence

and MeteringVT failure detection

failure detection Relay address monitoringStatus and condition monitoring of primary apparatus Switchgear operation monitoringPlausibility check Measurement of I, V, P, Q, PF, f, Wh and

Various models and hardware options for depending on system

requirement and controlled object Combined 1A / 5A current inputs Multi range DC power supply: 24 to 60V / 60 to 110 V / 110 to 250V

binary inputs and outputsProgrammable control, trip and alarm

with PLC tool software Human Machine Interface

LEDs Configurable 7 function keys

port for local PC connection Direct control buttons for open/close (O/I)

control authority (43R/L) Help key for supporting operation

onitoring terminals for testing

Power swing blocking function Inrush Current Detector

safe overcurrent scheme

three / single + multi-shot (three

check Circuit breaker and isolator control Switchgear interlock check

grammable automatic sequence

and Metering

Relay address monitoring Status and condition monitoring of

Switchgear operation monitoring

Measurement of I, V, P, Q, PF, f, Wh and

Various models and hardware options for depending on system

Multi range DC power supply: 24 to 60V /

binary inputs and outputs Programmable control, trip and alarm

Direct control buttons for open/close (O/I)

three shot (three

grammable automatic sequence

Measurement of I, V, P, Q, PF, f, Wh and

Page 4: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

4

- Current and voltage circuit supervision - Trip circuit supervision - Fault locator

• HMI function - Selection of HMI: Standard LCD / large

LCD / Separate large LCD - Large LCD supports Single line diagram

indication and touch-type operation. - 24 configurable tri-state LEDs selectable

red/green/yellow - 7 Programmable function keys for user

demand operation • Recording - Fault record - Event record

- Disturbance record • Communication - IEC 60870-5-103 / IEC 61850 - IEC62439 PRP

• General functions - Eight settings groups - Automatic supervision - Metering and recording functions - Time synchronization by external clock

using IRIG-B or system network - Password protection for settings and

selection of local / remote control - Checking internal circuit manually. - Checking internal circuit using monitoring

jacks.

Page 5: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

5

APPLICATIONS

PROTECTION

Phase-segregated Current Differential

Protection

GRL200 provides high-speed phase-segregated

current differential protection for both phase-to-phase

faults and phase-to-earth faults. The

phase-segregated current differential protection

exhibits high selectivity and sensitivity for all types of

faults. It applies a percentage ratio differential

characteristic as shown in Figure 1.

Ir

DIFI1

Id

Id: Differential current (|IA + IB + IC|) Ir: Restraining current (|IA| + |IB| + |IC|) DIFI1: Setting of small current region DIFI2: Setting of large current region ik: Minimum operating current

Large current region characteristic

0

Operating zone

IA

A B

IB IC

C

Small current region characteristic

DIFI2

ik

Figure 1 Percentage ratio differential element

The characteristic is composed of a small current

region and a large current region. When the fault

current is large, a large ratio is employed in the large

current region of the characteristic, providing stability

in the case of external faults accompanied by CT

saturation.

Since a high level of sensitivity can be attained with

the current differential relay, it can also detect high

impedance faults provided that the load current is not

too large.

Zero-sequence Current Differential Protection

for High Impedance Earth Faults

Zero-sequence current differential protection can

detect high impedance earth faults even with heavy

load current. It applies the percentage ratio differential

characteristic shown in Figure 2. As the restraining

current is the scalar sum of the zero-sequence current

at each terminal, the relay sensitivity is not affected by

load current. When the zero-sequence current

differential protection operates, it performs

time-delayed three- phase tripping.

Ir

DIFGI

Id

Id: Differential current (|IA + IB + IC|) Ir: Restraining current (|IA| + |IB| + |IC|) DIFGI: Setting value ik: Minimum operating current

0

Operating zone

IA

A B

IB IC

C

ik

Figure 2 Zero-phase current differential element

Charging Current Compensation

When current differential protection is applied to

underground cables or long-distance overhead lines,

the charging current should be taken into account. It

appears as an erroneous differential current in the

no-fault condition and under external fault conditions.

Charging current can be included within the relay

setting, but the fault detection sensitivity for an internal

fault is reduced as a consequence.

To suppress the effect of the charging current while at

the same time maintaining its high fault detection

sensitivity, GRL200 has a charging current

compensation function which derives the charging

current component from the phase current.

The amplitude of the charging current varies with that

of the line voltage. If the value of charging current

(DIFIC) at the rated line voltage is input, GRL200

calculates and compensates for the charging current

at the measured line voltage.

Thus, instead of the phase current Ia, a compensated

current I = Ia - DIFIC is used for protection at all

terminals.

Dual Communication

Dual communication mode can be applied to

protection of two-terminal lines. Using dual

communication mode, it is possible to maintain

Page 6: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

6

continuous operation of the current differential

protection in the event of failure of one of the

communication channels.

GRL200 GRL200

CH1

CH2

CH1

CH2

Figure 3 Dual Communication

Countermeasure for Through-Fault Current

As shown in Figure 4, for an external fault on a

one-and-a-half breaker system, a large fault current IA

flows through CT1A and CT2A. If the saturation levels

of CT1A and CT2A are different, an erroneous

differential current may occur between IA1 and IA2 as

a result of CT saturation.

This may cause terminal B to operate incorrectly if it is

a weak infeed terminal and the restraining current is

small.

To cope with the through-fault current, GRL200 can be

set to output tripping commands under the condition

that the differential protection operates at both

terminals. As the remote current is sent by the result

of DIF or each value of CT1 and CT2, GRL200

provide appropriate measurement on basis of CT’s

configuration.

IA1

IA2 CT2A

CT1A

IB1

IB2

CT2B

CT1B

IB1+IB2

IA1, IA2

IB1, IB2

IA1+IA2

IB IA

Communication

Terminal A Terminal B

Fault

IA1+IA2

IB1+IB2 or

Figure 4 Through-fault current on one-and-a-half breaker system

Stub Protection

Stub protection operates for a fault in a stub zone on a

breaker-and-a-half breaker system. With the auxiliary

contact of the line disconnector open, only the local

terminal current is used as the operating quantity by

setting the remote terminal current data to zero.

Transfer Trip Function

GRL200 provides a transfer trip function which

receives a trip signal from the remote terminal and

outputs a trip command. Two transfer trip commands

are provided. The sending signal is configured by PLC

function. If the sending signal is assigned on a per

phase basis by PLC, single-phase tripping is

available.

Out-of-Step Protection

By transmitting the phase information of the local

voltage to the remote terminal, the out-of-step

protection can measure the phase difference between

the terminals of a transmission line as illustrated in

Figure 5. It detects an out-of-step condition when the

difference in the phase angle exceeds 180°, and trips

both terminals.

The out-of-step protection can detect an out-of-step

condition even with a high rate of slip.

VL: Local terminal voltage VB: Remote terminal voltage

0

βzone

αzone

VR

VL

Figure 5 Out-of-step protection element

Non-directional and Directional Overcurrent and Earth Fault Protection

GRL200 provides non-directional and directional

overcurrent protections with inverse time and definite

time characteristics for both phase faults and earth

faults.

Inverse time overcurrent protection consists of an

IDMT (inverse definite minimum time) element. IDMT

is available in conformity with the IEC 60255-151

standard which encompasses both the IEC and

IEEE/ANSI standard characteristics. Alternatively, a

user-configurable curve may be created.

The IDMT element has a programmable reset feature,

selectable for instantaneous, definite time or

dependent time operation. This feature can be used to

protect against intermittent fault conditions, or to

grade correctly with electromechanical overcurrent

Page 7: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

7

relays.

Definite time overcurrent protection is enabled by the

instantaneous overcurrent element and pickup-delay

timer.

Tripping by each element can be disabled by scheme

switches, and overcurrent backup protection can be

blocked by a binary input signal.

GRL200 can also provide non-directional and

directional earth fault protection. Protection

functionality is the same as for the phase fault

elements.

The directional earth fault elements have a user

selectable minimum voltage threshold.

GRL200 can provide directional earth fault command

protection by using two-stage directional earth fault

elements, of which one is for tripping and the other is

for blocking or for current reversal detection.

Non-Directional and Directional Sensitive Earth Fault Protection

GRL200 provides non-directional and directional earth

fault protection with more sensitive settings for use in

applications where the fault current magnitude may be

very low.

The sensitive earth fault element includes a digital

filter which rejects all harmonics other than the

fundamental power system frequency.

The sensitive earth fault quantity is measured directly, using a dedicated core balance earth fault CT.

Non-directional and Directional Negative Phase Sequence Overcurrent Protection

Negative phase sequence overcurrent (OCN)

protection can be used in applications where certain

fault conditions may not be detected by the normal

phase and earth overcurrent protections, for example,

in the case of a relay applied on the delta side of a

delta-star transformer, to detect an earth fault on the

star side. Alternatively, OCN can be used to protect a

three phase motor against the severe overheating

which results from operating with an unbalanced

supply.

The negative phase sequence overcurrent elements

can be directionalised by polarising against the

negative phase sequence voltage.

Breaker Failure Protection

When an overcurrent element remains in operation

longer than a pre-determined length of time following

the output of a trip signal the associated circuit

breaker is judged to have failed and adjacent circuit

breakers can be tripped as a back-up measure.

Two independent timers are available, one of which

can be used to control the RETRIP of the original

circuit breaker(s). The second timer is used to control

the back-tripping of adjacent circuit breakers.

For high-speed protection, an overcurrent element

with high-speed reset time is used to prevent a

spurious re-trip or back-trip following a successful trip

or re-trip action.

Broken Conductor Detection

The unbalance condition caused by an open circuited

conductor is detected by the broken conductor

detection function. An unbalance threshold with

programmable definite time delay is provided.

Thermal Overload Protection

The thermal overload feature provides protection for

cables and other plant against the effects of prolonged

operation under excess load conditions. A thermal

replica algorithm is applied to create a model for the

thermal characteristics of the protected plant. The

characteristics are exponential functions according to

functional standard IEC 60255-149 and take into

account the I2R losses due to the specific operational

current and the simultaneous cooling effect of the

coolant. In this way the tripping time during an

overload condition takes the prior level of load current

into consideration. An alarm can be set to operate

before the tripping condition is reached.

Thermal image:

I2 - Ip2

I2 - (k IB)2

where

t: Operating time

τ: Thermal time constant

I: Overload current

IB: Thermal overload current setting

K: Constant

Ip: Specified load current before the overload

occurs

t =τln

Page 8: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

GR

phase

voltage input.

definite time operation

provides four

GR

for phase

undervoltage protection

input. The undervoltage protection is provided with an

undervoltage blocking function

undervoltage tripping in the case of a dead line.

GRL200

and frequency rate

These protections provide independent

protection stages. The over/under

protection is programmable for either

over

associated DTL timer. The frequency rate

protection calculates the gradient of frequency

(df/dt).

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from

magnetising inrush current during transformer

energisation. Inrush current detector

Overvoltage Protection

GRL200 provides overvoltage protections for

phase-to-phase voltage input and phase

voltage input.

definite time operation

provides four

Figure

Under voltage Protection

GRL200 provides two

for phase-to-

undervoltage protection

input. The undervoltage protection is provided with an

undervoltage blocking function

undervoltage tripping in the case of a dead line.

Under/Overfrequency Protection

GRL200 provides over/under frequency

and frequency rate

These protections provide independent

protection stages. The over/under

protection is programmable for either

over-frequency operation, a

associated DTL timer. The frequency rate

protection calculates the gradient of frequency

(df/dt).

Inrush Current Detector

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from

magnetising inrush current during transformer

energisation. Inrush current detector

Overvoltage Inv erse Time Curves

0.100

1.000

10.000

100.000

1000.000

1 1.5

Applied Voltage (x Vs)

Ope

rati

ng T

ime

(se

cs)

( VsV

t =

Overvoltage Protection

00 provides overvoltage protections for

phase voltage input and phase

voltage input. All stages can be set for inverse time or

definite time operation. In total, t

provides four independent overvoltage

Figure 7 Inverse time characteristics

voltage Protection

00 provides two-stage

to-phase voltage

undervoltage protection for

input. The undervoltage protection is provided with an

undervoltage blocking function

undervoltage tripping in the case of a dead line.

Under/Overfrequency Protection

provides over/under frequency

and frequency rate-of-change protection.

These protections provide independent

protection stages. The over/under

protection is programmable for either

frequency operation, a

associated DTL timer. The frequency rate

protection calculates the gradient of frequency

Inrush Current Detector

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from

magnetising inrush current during transformer

energisation. Inrush current detector

Overvoltage Inv erse Time Curves

2 2.5 3

Applied Voltage (x Vs)

TMS = 1

TMS = 2

TMS = 5

TMS = 10

) xTMS

Vs 1

1

Overvoltage Protection

00 provides overvoltage protections for

phase voltage input and phase

can be set for inverse time or

In total, therefore, GR

dependent overvoltage

time characteristics

voltage Protection

stage undervoltage protection

voltage input

for phase-to

input. The undervoltage protection is provided with an

undervoltage blocking function

undervoltage tripping in the case of a dead line.

Under/Overfrequency Protection

provides over/under frequency

change protection.

These protections provide independent

protection stages. The over/under frequency

protection is programmable for either under

frequency operation, and each has an

associated DTL timer. The frequency rate

protection calculates the gradient of frequency

Inrush Current Detector

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from

magnetising inrush current during transformer

energisation. Inrush current detector

Undervoltage Inverse Time Curves

1.000

10.000

100.000

1000.000

0 0.2

Applied Voltage (x Vs)

Op

era

ting

Tim

e (s

ecs

)

TMS = 10

TMS = 5

TMS = 2

TMS = 1

( VsV

t−

=1

1

00 provides overvoltage protections for both

phase voltage input and phase-to-neutral

can be set for inverse time or

herefore, GRL

dependent overvoltage thresholds.

time characteristics

undervoltage protection

and two-stage

to-neutral voltage

input. The undervoltage protection is provided with an

undervoltage blocking function to prevent

undervoltage tripping in the case of a dead line.

Under/Overfrequency Protection

provides over/under frequency protection

change protection.

These protections provide independent frequency

frequency

under- or

nd each has an

associated DTL timer. The frequency rate-of-change

protection calculates the gradient of frequency change

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from

magnetising inrush current during transformer

energisation. Inrush current detector (ICD) detects

Undervoltage Inverse Time Curves

0.4 0.6 0.8 1

Applied Voltage (x Vs)

)xTMS

Vs

8

both

neutral

can be set for inverse time or

L200

thresholds.

undervoltage protection

stage

voltage

input. The undervoltage protection is provided with an

prevent

protection

frequency

change

change

The inrush current detector is used to prevent an

incorrect operation of overcurrent protections from a

magnetising inrush current during transformer

detects

second harmonic inrush current during transformer

energisation.

GRL

realizing a complete

single package

protection

shown in the Figure

zone

second harmonic inrush current during transformer

energisation.

Distance Protection

GRL200 provides

realizing a complete

single package

protection zones

shown in the Figure

zones are provided for phase

Figure 8

(c) Non directional zone

second harmonic inrush current during transformer

Distance Protection

provides a distance protection scheme

realizing a complete line protection capability within a

single package It provides

zones, the characteristics

shown in the Figure 8 and 9

provided for phase

8 Quadrilateral Characteristics

(a) Forward zone

(b) Reverse zone

(c) Non directional zone

(a) Forward zone

second harmonic inrush current during transformer

distance protection scheme

line protection capability within a

It provides six independent

he characteristics

9. Individual measurement

provided for phase-fault and earth

Quadrilateral Characteristics

(a) Forward zone

(b) Reverse zone

(c) Non directional zone

(a) Forward zone

second harmonic inrush current during transformer

distance protection scheme, so

line protection capability within a

independent distance

of which are

. Individual measurement

fault and earth-fault.

Quadrilateral Characteristics

second harmonic inrush current during transformer

, so

line protection capability within a

distance

are

. Individual measurement

Page 9: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

GRL

elements

prevent unwanted operation

a

a phase overcurrent element, OCD

change detection element,

undervoltage

undervoltage

detection element

current change detection element.

Control

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

line de

disperse and the air de

and de

performed. GR

schemes, single

autoreclose.

GR

of the following high

Figure

OC/UV and EF

GRL200 provides OC, OCD

elements as

prevent unwanted operation

communication failure

a phase overcurrent element, OCD

change detection element,

undervoltage

undervoltage

detection element

current change detection element.

Control

Autoreclose

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

line de-energization. After

disperse and the air de

and de-ionizing the fault arc, reclosi

performed. GR

schemes, single

autoreclose.

GRL200’s autoreclose function can be initiated

of the following high

Figure 9 Mho-based

and EF Guard

00 provides OC, OCD

additional fault detection criteria

prevent unwanted operation

communication failure should go undetected

a phase overcurrent element, OCD

change detection element,

undervoltage element, UVS is phase to phase

undervoltage element, UVD is phase voltage

detection element and EFD is a zero

current change detection element.

Autoreclose

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

energization. After

disperse and the air de-ionizes.

ionizing the fault arc, reclosi

performed. GRL200 provides two autoreclose

schemes, single-shot autoreclose and multi

autoreclose function can be initiated

of the following high-speed protection

(b) Reverse zone

(c) Non directional zone

based Characteristics

Guard Schemes

00 provides OC, OCD, UV, UVS, UVD

additional fault detection criteria

prevent unwanted operation in the unlikely event that

should go undetected

a phase overcurrent element, OCD is a phase current

change detection element, UV is a phase

, UVS is phase to phase

, UVD is phase voltage

and EFD is a zero

current change detection element.

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

energization. After a short time

ionizes. After clearing the fault

ionizing the fault arc, reclosi

00 provides two autoreclose

shot autoreclose and multi

autoreclose function can be initiated

speed protections

(b) Reverse zone

(c) Non directional zone

Characteristics

, UV, UVS, UVD and EFD

additional fault detection criteria

in the unlikely event that

should go undetected. OC is

is a phase current

UV is a phase

, UVS is phase to phase

, UVD is phase voltage change

and EFD is a zero-sequence

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

a short time, the hot gases

After clearing the fault

ionizing the fault arc, reclosing can be

00 provides two autoreclose

shot autoreclose and multi-shot

autoreclose function can be initiated by any

s.

9

and EFD

additional fault detection criteria to

in the unlikely event that

. OC is

is a phase current

UV is a phase

, UVS is phase to phase

change

sequence

Most faults on HV and EHV overhead transmission

lines are transient faults, which are removed following

, the hot gases

After clearing the fault

ng can be

00 provides two autoreclose

shot

by any

- -

Single

reclose modes

three

autoreclose

In the

phase is tripped, and then reclosed if a single

earth fault occurs.

In the

are tripped, and then reclosed regardless of the fault

mode, whether

fault

In the

single

and the three phases are reclosed if three phases are

tripped.

Multi

double

phases are tripped and reclosed when the terminals of

double

dead time through at least two or three different

phases.

In a m

can be selected.

the

autoreclose

If reclosing by the first shot fails, three

and reclosing

For the

voltage and synchronism check are necessary.

characteristics of the synchronism check element are

shown in Figure

A detected slip cycle is determined by the following

equation:

where,

f:

θ:

TSYN:

Protection using telecommunication Distance zone

Single- shot autoreclose

Single-shot reclosing can provide any of three

reclose modes

three-phase autoreclose, single

autoreclose and mu

the single-phase autoreclose mode, only

phase is tripped, and then reclosed if a single

earth fault occurs.

the three-phase autoreclose mode,

are tripped, and then reclosed regardless of the fault

mode, whether

fault has occurred

the single- and three

single-phase is reclosed if a single

and the three phases are reclosed if three phases are

tripped.

Multi-phase autoreclose

double-circuit lines. In this mode, only the faulted

phases are tripped and reclosed when the terminals of

double-circuit lines are interconnected

dead time through at least two or three different

phases.

Multi-s hot

a multi-shot autoreclose, two

can be selected.

the five autoreclose modes available in the single

autoreclose scheme

If reclosing by the first shot fails, three

and reclosing is applied for the second to

Synchronism Check

For the correct operation of three

voltage and synchronism check are necessary.

haracteristics of the synchronism check element are

shown in Figure

A detected slip cycle is determined by the following

equation:

where,

slip cycle

synchronism check angle setting

TSYN: synchronism check timer setting

f = 180°Х

Protection using telecommunicationone is set to zone

shot autoreclose

shot reclosing can provide any of three

reclose modes; single

phase autoreclose, single

and multi-phase autoreclose

phase autoreclose mode, only

phase is tripped, and then reclosed if a single

earth fault occurs.

phase autoreclose mode,

are tripped, and then reclosed regardless of the fault

mode, whether a single-phas

has occurred.

and three-phase autoreclose

phase is reclosed if a single

and the three phases are reclosed if three phases are

phase autoreclose mode

circuit lines. In this mode, only the faulted

phases are tripped and reclosed when the terminals of

circuit lines are interconnected

dead time through at least two or three different

hot autoreclose

shot autoreclose, two

can be selected. The first shot is selected from any of

autoreclose modes available in the single

scheme.

If reclosing by the first shot fails, three

is applied for the second to

Synchronism Check

operation of three

voltage and synchronism check are necessary.

haracteristics of the synchronism check element are

shown in Figure 10.

A detected slip cycle is determined by the following

slip cycle

synchronism check angle setting

synchronism check timer setting

°ХTSYN

θ

Protection using telecommunicationis set to zone 1 extension

shot autoreclose

shot reclosing can provide any of three

single-phase autoreclose,

phase autoreclose, single-and three

phase autoreclose

phase autoreclose mode, only

phase is tripped, and then reclosed if a single

phase autoreclose mode, all

are tripped, and then reclosed regardless of the fault

phase fault or

phase autoreclose

phase is reclosed if a single-phase is tripped

and the three phases are reclosed if three phases are

mode can be appli

circuit lines. In this mode, only the faulted

phases are tripped and reclosed when the terminals of

circuit lines are interconnected

dead time through at least two or three different

utoreclose

shot autoreclose, two- to five-

he first shot is selected from any of

autoreclose modes available in the single

If reclosing by the first shot fails, three-

is applied for the second to

operation of three-phase autoreclose,

voltage and synchronism check are necessary.

haracteristics of the synchronism check element are

A detected slip cycle is determined by the following

synchronism check angle setting

synchronism check timer setting

Protection using telecommunication 1 extension

shot reclosing can provide any of three auto

phase autoreclose,

and three-phase

phase autoreclose.

phase autoreclose mode, only a faulted

phase is tripped, and then reclosed if a single-phase

all three phases

are tripped, and then reclosed regardless of the fault

e fault or a multi-phase

phase autoreclose mode, the

phase is tripped

and the three phases are reclosed if three phases are

can be applied to

circuit lines. In this mode, only the faulted

phases are tripped and reclosed when the terminals of

circuit lines are interconnected during the

dead time through at least two or three different

-shot reclosing

he first shot is selected from any of

autoreclose modes available in the single-shot

phase tripping

is applied for the second to fifth shots.

phase autoreclose,

voltage and synchronism check are necessary. The

haracteristics of the synchronism check element are

A detected slip cycle is determined by the following

synchronism check angle setting

synchronism check timer setting

auto-

phase autoreclose,

phase

faulted

phase

three phases

are tripped, and then reclosed regardless of the fault

phase

mode, the

phase is tripped

and the three phases are reclosed if three phases are

ed to

circuit lines. In this mode, only the faulted

phases are tripped and reclosed when the terminals of

during the

dead time through at least two or three different

shot reclosing

he first shot is selected from any of

shot

phase tripping

shots.

phase autoreclose,

The

haracteristics of the synchronism check element are

A detected slip cycle is determined by the following

Page 10: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

10

Figure 10 Synchronism check element

One-and-a-half Breaker Scheme

GRL200 performs two-breaker autoreclose in a

one-and- a-half breaker scheme.

Only single-shot autoreclose is available in a one-and-

a-half breaker scheme. Single-phase autoreclose,

three-phase autoreclose or single and three-phase

autoreclose can be applied to the two circuit breakers.

Interfaces with Telecommunication Systems

Current data sampled at the local terminal is

transmitted to the remote terminal(s) via the

telecommunication system.

GRL200 can be provided with the following

interface(s) and linked to a dedicated optical fibre

communication circuit or multiplexed communication

circuit (multiplexer) shown in Figure 11.

Figure 11 Telecommunication system

Switchgear Control

GRL200 provides functions for local control of

switchgear from the HMI. Two-stepped operation

(select-control) is applied for the control of circuit

breakers, isolator switches and earthing switches.

Also, switchgear control commands from the station

level can be performed through GRL200 within the

application of a substation automation control system.

Interlock check

The interlocking function blocks the operation of

primary switching devices, for instance when an

isolator switch is under load, in order to prevent

equipment damage and/or accidental human injury.

Each switchgear control function has interlocking

modules included for different switchyard

arrangements, where each function handles

interlocking for one bay. The interlocking function is

distributed to each IED and is not dependent on any

central function.

VL : Line voltage VB: Busbar voltage θ: Synchronism check angle

θ

θ

0 deg

Operating zone

VL

VB

OV

UV

θ

θ

b) Optical interface using multiplexer

GRL200 Opt.

I/F

a) Optical interface

GRL200 Opt.

I/F

Optical Fibre Bit rate 2048kbps

IF unit GIF200

Opt. Fibre < 2km IEEE C37.94 Bit rate: 2048kbps

CCITT-G.703. ITUT-X.21 Bit rate: 64kbps

GRL200 Opt.

I/F

Multi- plexer

Opt. Fibre < 2km IEEE C37.94 Bit rate: 2048kbps

Multi- plexer

c) Optical interface using multiplexer

Page 11: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

HMI

GR--

The s

interfaces

stored data

Display (LCD) and operation keys.--

The large LCD panel incorporates a t

for control and navigation-

MONITORING

The following power system data is

continuously

relay fascia-

The accuracy of

P, Q at rated

measur

RECORDING

Continuous event

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

Up to 1,024 time

HMI FUNCTION

Front Panel

GRL200 provide- Standard LCD- Large LCD

available)

The standard LCD panel

interfaces listed below

stored data

Display (LCD) and operation keys.- 21 character, - Support of English language

The large LCD panel incorporates a t

for control and navigation- 40 character,

MONITORING

Metering

The following power system data is

continuously and

relay fascia, and on a local or remotely connected PC- Measured

active- and

The accuracy of

P, Q at rated

measurement

RECORDING

Event Record

Continuous event

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

Up to 1,024 time

FUNCTION

Front Panel

200 provides the following front panelStandard LCD Large LCD (optional separate LCD type is also

)

tandard LCD panel

listed below. Setting the

are possible

Display (LCD) and operation keys.character, 8 line LCD with back light

Support of English language

The large LCD panel incorporates a t

for control and navigation character, 40 line LCD with back light

Figure 12

MONITORING

Metering

The following power system data is

and can be displayed on

and on a local or remotely connected PCeasured analog voltages, currents, frequency,

and reactive-power

The accuracy of analog measure

P, Q at rated input and

ement.

RECORDING

Event Record

Continuous event-logging is useful for mon

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

Up to 1,024 time-tagged events are stored with 1ms

the following front panel

(optional separate LCD type is also

tandard LCD panel incorporates the

. Setting the relay and view

are possible using the

Display (LCD) and operation keys. line LCD with back light

Support of English language

The large LCD panel incorporates a touch type screen

purposes. line LCD with back light

gure 12 - HMI Panel

The following power system data is

displayed on

and on a local or remotely connected PCvoltages, currents, frequency,

power

analog measurement

input and ±0.03Hz

logging is useful for mon

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

tagged events are stored with 1ms

the following front panel options

(optional separate LCD type is also

incorporates the user

relay and view

using the Liquid Crystal

line LCD with back light

ouch type screen

line LCD with back light

HMI Panel

The following power system data is measured

displayed on the LCD on the

and on a local or remotely connected PCvoltages, currents, frequency,

ment is ±0.5% for I

0.03Hz for frequency

logging is useful for monitoring of

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

tagged events are stored with 1ms

11

options.

(optional separate LCD type is also

user

relay and viewing

Liquid Crystal

ouch type screen

The local human machine interface includes

which

The local human

to understand

indications.-

-

-

-

The user can communicate with

PC via the

series

the user can view

real

measured

on the

and on a local or remotely connected PC. voltages, currents, frequency,

0.5% for I, V,

for frequency

The open or closed status of each switchgear

and

and control equipment

Both

used to monitor switchgear status. If an unusual

status is

generated.

itoring of

the system from an overview perspective and is a

complement to specific disturbance recorder functions.

tagged events are stored with 1ms

resolution.

Information about the pre

currents an

trip event confirmation. The most recent 8 time

The local human machine interface includes

which can display the single line diagram for the bay.

The local human

to understand

indications. Status indication LEDs

and 24 configurable LEDs) 7 Function

group change and screen jump operation is configurable by

Test terminals which can monitor three different signals from the front panel without connection the rear terminals.

USB port

Local PC c

The user can communicate with

PC via the USB

series engineering tool

the user can view

real-time measurements.

Status Monitoring

The open or closed status of each switchgear

and failure information concerning power apparatus

and control equipment

Both normally open and normally closed contacts are

used to monitor switchgear status. If an unusual

status is detected, a switchgear abnormality alarm is

generated.

resolution.

Fault records

Information about the pre

currents and voltages are recorded and displayed for

trip event confirmation. The most recent 8 time

The local human machine interface includes

can display the single line diagram for the bay.

The local human machine interface is simple and

to understand with the

Status indication LEDsconfigurable LEDs)

7 Function keys for control, monitoring, setting group change and screen jump

ration is configurable by terminals which can monitor three different

signals from the front panel without connection the rear terminals.

Local PC c onnection

The user can communicate with

USB port on the front panel. Using

engineering tool software

the user can view, change

time measurements.

Status Monitoring

The open or closed status of each switchgear

failure information concerning power apparatus

and control equipment can be

normally open and normally closed contacts are

used to monitor switchgear status. If an unusual

detected, a switchgear abnormality alarm is

Fault records

Information about the pre-

d voltages are recorded and displayed for

trip event confirmation. The most recent 8 time

The local human machine interface includes

can display the single line diagram for the bay.

machine interface is simple and

with the following

Status indication LEDs (IN SERVICE, configurable LEDs)

for control, monitoring, setting group change and screen jump functions

ration is configurable by the userterminals which can monitor three different

signals from the front panel without connection

The user can communicate with GRL200

port on the front panel. Using

software (called

change settings

The open or closed status of each switchgear

failure information concerning power apparatus

can be monitored

normally open and normally closed contacts are

used to monitor switchgear status. If an unusual

detected, a switchgear abnormality alarm is

-fault and fault values for

d voltages are recorded and displayed for

trip event confirmation. The most recent 8 time

The local human machine interface includes an LCD

can display the single line diagram for the bay.

machine interface is simple and easy

facilities and

(IN SERVICE, ERROR

for control, monitoring, setting functions of which

the user terminals which can monitor three different

signals from the front panel without connection

GRL200 from a local

port on the front panel. Using GR-200

(called GR-TIEMS

and monitor

The open or closed status of each switchgear device

failure information concerning power apparatus

monitored by GRL200

normally open and normally closed contacts are

used to monitor switchgear status. If an unusual

detected, a switchgear abnormality alarm is

fault and fault values for

d voltages are recorded and displayed for

trip event confirmation. The most recent 8 time-tagged

an LCD

can display the single line diagram for the bay.

easy

and

ERROR

for control, monitoring, setting of which

terminals which can monitor three different signals from the front panel without connection to

from a local

200

TIEMS),

monitor

device

failure information concerning power apparatus

by GRL200.

normally open and normally closed contacts are

used to monitor switchgear status. If an unusual

detected, a switchgear abnormality alarm is

fault and fault values for

d voltages are recorded and displayed for

tagged

Page 12: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

12

faults with 1ms resolution are stored. Fault record

items are as follows. - Date and time - Faulted phase - Tripping phase - Operating mode - Pre-fault and post-fault current and voltage data

(phase, phase to phase, symmetrical components)

- Autoreclose operation - Fault location

Fault location is initiated by relay tripping signals. It can also be started on receipt of a start signal from external relays.

Fault location is indicated in km, mile and % for

the whole length of the protected line. The fault

location is highly accurate for parallel lines due to

the implementation of zero-sequence mutual

impedance compensation.

The result of the fault location is stored as fault

record data.

Disturbance records

The Disturbance Recorder function supplies fast,

complete and reliable information for disturbances in

the power system. It facilitates understanding of

system behavior and performance of related primary

and secondary equipment during and after a

disturbance.

The Disturbance Recorder acquires sampled data

from all selected analogue input and binary signals.

The data is stored in COMTRADE format.

COMMUNICATION

Station bus

Ethernet port(s) for the substation communication

standards IEC 61850 is provided for the station bus.

GRL200 also support Ethernet redundancy scheme

protocols defined in the IEC 62439-3 standard: PRP.

Serial communication

Serial ports (RS485 and fiber optic) for communicating

with legacy equipment or protection relays over IEC

60870-5-103 protocol are provided. The GRL200 can

function as a protocol converter to connect to SAS.

GENERAL FUNCTION

Self supervision

Automatic self-supervision of internal circuits and

software is provided. In the event of a failure being

detected, the ALARM LED on the front panel is

illuminated, the ‘UNIT FAILURE’ binary output

operates, and the date and time of the failure is

recorded in the event record.

Time synchronization

Current time can be provided with time

synchronization via the station bus by SNTP (Simple

Network Time Protocol) with the IEC 61850 protocol.

IRIG-B port is also available as an option.

Setting groups

8 settings groups are provided, allowing the user to

set one group for normal conditions, while the other

groups may be set to cover alternative operating

conditions.

Password protection

Password protection is available for the execution of

setting changes, executing control, clearing records

and switching between local/remote control.

Simulation and test

GRL200 provides simulation and test functions to

check control functions without modification to wiring

provided by a dummy circuit breaker (virtual

equipment), and the capability to test communication

signals by forced signal status change.

The simulation and test can work in the Test mode

only.

TOOLS & ACCESSORY

Page 13: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

The PC interface GR

GRL200 and other Toshiba GR

a local

stored data,

screen, to configure sequential logics and

purposes.

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

records stored in GRL2

disturbance record

measure

version of the engineering tool can provide additional

and powerful analysis tool

support functions.

The PC interface GR

GRL200 and other Toshiba GR

a local personal

stored data,

screen, to configure sequential logics and

purposes.

REMOTE SETTING AND MONITORING

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

records stored in GRL2

disturbance record

measured and analyzed in detail.

version of the engineering tool can provide additional

and powerful analysis tool

support functions.

Figure

The PC interface GR-TIEMS allows users to access

GRL200 and other Toshiba GR

personal computer (PC) to view on

to change settings, to edit

screen, to configure sequential logics and

REMOTE SETTING AND MONITORING

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

records stored in GRL2

disturbance records can be displayed, edited,

and analyzed in detail.

version of the engineering tool can provide additional

and powerful analysis tool

support functions.

Figure 13 PC Display of

TIEMS allows users to access

GRL200 and other Toshiba GR-200 series IEDs from

computer (PC) to view on

change settings, to edit

screen, to configure sequential logics and

REMOTE SETTING AND MONITORING

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

records stored in GRL200. Waveform data in the

can be displayed, edited,

and analyzed in detail.

version of the engineering tool can provide additional

and powerful analysis tools and setting calculation

PC Display of GR

TIEMS allows users to access

200 series IEDs from

computer (PC) to view on-line or

change settings, to edit the LCD

screen, to configure sequential logics and for other

REMOTE SETTING AND MONITORING

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

00. Waveform data in the

can be displayed, edited,

and analyzed in detail. An advanced

version of the engineering tool can provide additional

and setting calculation

GR-TIEMS

13

TIEMS allows users to access

200 series IEDs from

line or

LCD

other

The engineering tool supports functions to change

settings and to view and analyze fault and disturbance

00. Waveform data in the

can be displayed, edited,

dvanced

version of the engineering tool can provide additional

and setting calculation

The user

displayed on the LCD of G

software.

The

configure

operation. Configurable binary inputs, binary outputs

and LEDs are

logic editor.

LCD CONFIGURATION

he user can configur

displayed on the LCD of G

software.

Figure 14 PC Display of

PROGRAMMABLE LOGIC EDIT

The programmable

configure flexible

operation. Configurable binary inputs, binary outputs

and LEDs are also

logic editor. This complies with

Figure

LCD CONFIGURATION

can configure and customize

displayed on the LCD of G

PC Display of

PROGRAMMABLE LOGIC EDIT

programmable logic capability allows

flexible logic for customized

operation. Configurable binary inputs, binary outputs

also programmed by

This complies with

Figure 15 PC display of PLC editor

LCD CONFIGURATION

and customize the

displayed on the LCD of GRL200 using

PC Display of MIMIC configuration

PROGRAMMABLE LOGIC EDIT OR

logic capability allows

customized application and

operation. Configurable binary inputs, binary outputs

programmed by the programmable

This complies with IEC61131

PC display of PLC editor

the MIMIC data

using GR-TIEMS

MIMIC configuration

OR

logic capability allows the user

application and

operation. Configurable binary inputs, binary outputs

programmable

IEC61131-3 standard.

PC display of PLC editor

MIMIC data

TIEMS

to

application and

operation. Configurable binary inputs, binary outputs

programmable

standard.

Page 14: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

14

TECHNICAL DATA Analog Inputs

Rated current In 1A or 5A (selectable)

Rated voltage Vn 100V to 120V

Rated Frequency 50Hz or 60Hz (specified when order)

Overload Rating

Current inputs 4 times rated current continuous

5 times rated current for 3 mins

6 times rated current for 2 mins

30 times rated current for 10 sec 100 times rated current for 1 second

250 times rated current for one power cycle (20 or 16.6ms)

Voltage inputs 2 times rated voltage continuous

2.5 times rated voltage for 1 second

Burden

Phase current inputs ≤ 0.1VA at In = 1A, ≤ 0.2VA at In = 5A

Earth current inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A

Sensitive earth fault inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A

Voltage inputs ≤ 0.1VA at Vn

Power Supply

Rated auxiliary voltage 24/48/60Vdc (Operative range: 19.2 – 72Vdc),

48/125Vdc (Operative range: 38.4 – 150Vdc),

110/250Vdc or 100/220Vac (Operative range: 88 – 300Vdc or 80 – 230Vac)

<Notes>

1) Binary inputs are intended for use with DC power source only.

2) The power supply supervision function is intended for use with DC power source only. It should be disabled when AC power supply is applied in order to prevent spurious alarms.

Superimposed AC ripple on DC supply ≤ 15%

Supply interruption ≤ 20ms at 110Vdc

Restart time < 5ms

Power consumption ≤ 15W (quiescent) ≤ 25W (maximum)

Binary Inputs

Input circuit DC voltage 24/48/60Vdc (Operating range: 19.2 – 72Vdc), 48/125Vdc (Operating range: 38.4 – 150Vdc), 110/125/220/250Vdc (Operating range: 88 – 300Vdc)

Note: Threshold setting is available to BI2 and BIO4(Setting range: 14V to 154V)

Capacitive discharge immunity 10µF charged to maximum supply voltage and discharged into the input terminals, according to ENA TS 48-4 with an external resistor

Maximum permitted voltage 72Vdc for 24/48/60Vdc rating,

300Vdc for 110/250Vdc rating

Power consumption ≤ 0.5W per input at 220Vdc

Binary Outputs

Fast operating contacts

Make and carry

Break

Operating time

5A continuously

30A, 290Vdc for 0.2s (L/R=5ms)

0.15A, 290Vdc (L/R=40ms)

Typically 3 ms

Page 15: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

15

Semi-fast operating contacts

Make and carry

Break

Operating time

8A continuously

30A, 240Vdc for 1s (L/R=5ms)

0.1A, 250Vdc (L/R=40ms) 0.2A, 125Vdc (L/R=40ms) Typically 6 ms

Auxiliary contacts

Make and carry

Break

Operating time

8A continuously

30A, 240Vdc for 1s (L/R=5ms)

0.1A, 250Vdc (L/R=40ms) 0.2A, 125Vdc (L/R=40ms)

Typically 8 ms

Hybrid contacts (10 A breaking)

Make and carry

Break

Operating time

8A continuously

10A, 220Vdc for 0.5s (L/R=5ms)

10A, 220Vdc (L/R=20ms)

10A, 110Vdc (L/R=40ms)

1 ms

Durability ≥ 10,000 operations (loaded contact)

≥ 100,000 operations (unloaded contact)

Measuring input capability

Full scale

Standard current input

Sensitive current input

Voltage input

Sampling rate

Frequency response

≥ 60A (1A rating) or 300A (5A rating)

≥ 3A (1A rating) or 15 A (5A rating)

≥ 200V

48 samples / cycle

< 5% deviation over range 16.7Hz to 600Hz

Mechanical Design

Installation Flush mounting

Weight Approx. 12kg (1/2 size), 15kg (3/4 size), 25kg (1/1 size)

Case color 2.5Y7.5/1 (approximation to Munsell value)

LED

Number 26 (Fixed for “In service” and “ERROR”)

Color Red / Yellow / Green (configurable) except “In service (green)” and “Error (red)”

Function keys

Number 7

Local Interface

USB Type B

Maximum cable length 2m (max.)

Terminal Block

CT/VT input M3.5 Ring terminal

Binary input, Binary output Compression plug type terminal

System Interface (rear port)

100BASE-TX/1000BASE-T For IEC 61850-8-1 and GR-TIEMS

Cable type CAT5e STP cable

- enhanced category 5 with Shielded Twisted Pair cable

Connector type RJ-45

100BASE-FX For IEC 61850-8-1

Cable type Multimode fibre, 50/125μm or 62.5/125μm

Connector type SC duplex

Wave length 1300nm

Page 16: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

16

1000BASE-LX For IEC 61850-8-1

Cable type Single-mode fibre

Connector type LC duplex

Wave length 1310nm

RS485 For IEC 60870-5-103

Cable type Shielded twisted pair cable

Connector type Push-in spring terminal (PCB connector)

Fiber optical (for serial communication) For IEC 60870-5-103

Cable type Multimode fibre, 50/120μm or 62.5/125μm

Connector type ST

Wave length 820nm

IRIG-B (for time synchronization)

Cable type Shielded twisted pair cable

Connector type Push-in spring terminal (PCB connector)

Telecommunication Interface for Protection Signalli ng

Optical interface (2 km class)

Type of fibre

Connector type

Wave length

Optical transmitter

Optical receiver

Graded-index multi-mode 50/125µm or 62.5/125µm

ST type

820nm

LED, more than −19dBm(50/125µm), −16dBm(62.5/125µm)

PIN diode, less than −24dBm

Optical interface (30 km class)

Type of fibre

Connector type

Wave length

Optical transmitter

Optical receiver

Single mode 10/125µm

Duplex LC

1310nm

Laser, more than −13dBm

PIN diode, less than −30dBm

Optical interface (80 km class)

Type of fibre

Connector type

Wave length

Optical transmitter

Optical receiver

DSF 8/125µm

Duplex LC

1550nm

Laser, more than −5dBm

PIN diode, less than −34dBm

Page 17: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

17

ENVIRONMENTAL PERFORMANCE Atmospheric Environment

Temperature IEC 60068-2-1/2

IEC 60068-2-14

Operating range: -10°C to +55°C.

Storage / Transit: -25°C to +70°C.

Cyclic temperature test as per IEC 60068-2-14

Humidity IEC 60068-2-30

IEC 60068-2-78

56 days at 40°C and 93% relative humidity.

Cyclic temperature with humidity test as per IEC 60068-2-30

Enclosure Protection IEC 60529 IP52 - Dust and Dripping Water Proof

IP20 for rear panel

Mechanical Environment

Vibration IEC 60255-21-1 Response - Class 1

Endurance - Class 1

Shock and Bump IEC 60255-21-2 Shock Response Class 1

Shock Withstand Class 1

Bump Class 1

Seismic IEC 60255-21-3 Class 1

Electrical Environment

Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between all terminals and earth.

2kVrms for 1 minute between independent circuits.

1kVrms for 1 minute across normally open contacts.

High Voltage Impulse IEC 60255-27

IEEE C37.90 Three positive and three negative impulses

of 5kV (peak), 1.2/50µs, 0.5J between all

terminals and between all terminals and

earth.

Voltage Dips, Interruptions, Variations and Ripple on DC supply

IEC 60255-11,

IEC 61000-4-29,

IEC 61000-4-17

IEC 60255-26 Ed 3

1. Voltage dips:

0 % residual voltage for 20 ms

40 % residual voltage for 200 ms

70 % residual voltage for 500 ms

2. Voltage interruptions:

0 % residual voltage for 5 s

3. Ripple:

15 % of rated d.c. value, 100 / 120 Hz

4. Gradual shut-down / start-up:

60 s shut-down ramp, 5 min power off, 60s start-up ramp

5. Reversal of d.c. power supply polarity:

1 min

Capacitive Discharge ENA TS 48-4 10µF charged to maximum supply voltage and discharged into the input terminals with an external resistance

Page 18: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

18

Electromagnetic Environment

High Frequency Disturbance /

Damped Oscillatory Wave

IEC 60255-22-1 Class 3,

IEC 61000-4-18

IEC 60255-26 Ed 3

1 MHz burst in common / differential modes

Auxiliary supply and I/O ports: 2.5 kV / 1 kV

Communications ports: 1 kV / 0 kV

Electrostatic Discharge IEC 60255-22-2 Class 4,

IEC 61000-4-2

IEEE C37.90.3-2001

IEC 60255-26 Ed 3

Contact: 2, 4, 6, 8kV

Air: 2, 4, 8, 15kV

Radiated RF Electromagnetic Disturbance

IEC 60255-22-3,

IEC 61000-4-3 Level 3

IEC 60255-26 Ed 3

Sweep test ranges: 80 MHz to 1 GHz and 1.4 GHz to 2.7 GHz.

Spot tests at 80, 160, 380, 450, 900, 1850 and 2150 MHz.

Field strength: 10 V/m

IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of 25MHz to 1GHz.

Fast Transient

Disturbance

IEC 60255-22-4

IEC 61000-4-4

IEC 60255-26 Ed 3

5 kHz, 5/50ns disturbance

Auxiliary supply and input / output ports: 4 kV

Communications ports: 2 kV

Surge Immunity IEC 60255-22-5

IEC 61000-4-5

IEC 60255-26 Ed 3

1.2/50µms surge in common/differential

modes:

Auxiliary supply and input / output ports: 4, 2,

1, 0.5 kV / 1, 0.5 kV

Communications ports: up to 1, 0.5 kV / 0 kV

Surge Withstand IEEE C37.90.1-2002 3kV, 1MHz damped oscillatory wave

4kV, 5/50ns fast transient

Conducted RF

Electromagnetic

Disturbance

IEC 60255-22-6

IEC 61000-4-6

IEC 60255-26 Ed 3

Sweep test range: 150 kHz to 80MHz

Spot tests at 27 and 68 MHz.

Voltage level: 10 V r.m.s

Power Frequency

Disturbance

IEC 60255-22-7

IEC 61000-4-16

IEC 60255-26 Ed 3

50/60 Hz disturbance for 10 s in common /

differential modes

Binary input ports: 300 V / 150 V

Power Frequency

Magnetic Field

IEC 61000-4-8 Class 4

IEC 60255-26 Ed 3

Field applied at 50/60Hz with strengths of:

30A/m continuously,

300A/m for 1 second.

Conducted and

Radiated Emissions

IEC 60255-25

EN 55022 Class A,

EN 61000-6-4

IEC 60255-26 Ed 3

Conducted emissions:

0.15 to 0.50MHz: <79dB (peak) or <66dB

(mean)

0.50 to 30MHz: <73dB (peak) or <60dB

(mean)

Radiated emissions

30 to 230 MHz: < 40 dB(uV/m)

230 to 1000 MHz: < 47 dB(uV/m)

Measured at a distance of 10 m

Page 19: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

19

European Commission Directives

2014/30/EU Compliance with the European Commission

Electromagnetic Compatibility Directive is

demonstrated according to EN 60255-26:2013.

2014/35/EU Compliance with the European Commission Low

Voltage Directive for electrical safety is

demonstrated according EN 60255-27:2014.

Performance and Functional Standards

Category Standards

General

Common requirements IEC 60255-1

Data Exchange IEC 60255-24 / IEEE C37.111 (COMTRADE)

IEEE C37.239 (COMFEDE)

Product Safety IEC 60255-27

Interface Converter GIF200

Ratings Power supply: 24Vdc - 250Vdc

(Operative range: 19.2 - 300Vdc)

Burden: less than 8W

Interface Communication interface: Operative Range: Wavelength: Connector type: Fibre type:

ITU-T G.703 (64kbps, co-directional) ITU-T G.703 (64kbps, contra-directional or centralized clock) less than 2km 820nm ST 62.5/125µm GI fibre

Atmospheric Environment Temperature Humidity Enclosure Protection

IEC60068-2-1/2 IEC60068-2-78 IEC60529

Operating range: -10°C to +55°C. Storage / Transit: -25°C to +70°C. 56 days at 40°C and 93% relative humidity. IP20

Page 20: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

20

FUNCTIONAL DATA

Phase-segregated Current Differential Protection

DIFI1 (Small current region) 0.10 to 2.00A in 0.01A steps (1A rating) 0.50 to 10.00A in 0.01A steps (5A rating)

DIFI2 (Large current region) 0.6 to 60.0A in 0.1A steps (1A rating) 3.0 to 300.0A in 0.1A steps (5A rating)

DIFL-Slop1 (Small current region) 10 to 50 % DIFL-Slop2 (Large current region) 50 to 100 % Time setting for DIF 0.00 to 100.00s in 0.01s steps Reference voltage 100 to 120V in 1V step

Operating time Less than 1 cycle at 300% of DIFI1 Resetting time Less than 110 ms (for tripping output)

Less than 40 ms (for signal output)

Zero-sequence Current Differential Protection for h igh-resistance earth

DIFGI 0.05 to 1.00A in 0.01A steps (1A rating) 0.25 to 5.00A in 0.01A steps (5A rating)

DIFG-Slop 10 to 50 %

Timer 0.00 to 300.00s in 0.01s steps

Operating time less than 45ms

Resetting time less than 100ms

Charging Current Compensation

DIFL-IcC 0.00 to 1.00A in 0.01A steps (1A rating) 0.00 to 5.00A in 0.01A steps (5A rating)

Differential Current Supervision DIFSV 0.05 to 2.00A in 0.01A steps (1A rating)

0.25 to 10.00A in 0.01A steps (5A rating)

Timer 0 to 300s in 1s steps

DIF Guard characteristic

Overcurrent threshold 0.02 to 50.00A in 0.01A steps (1A rating) 0.10 to 250.00A in 0.01A steps (5A rating)

Rate of Overcurrent change threshold 0.05 to 0.20A in 0.01A steps (1A rating) 0.25 to 1.00A in 0.01A steps (5A rating)

Phase sequence Undervoltage threshold 5.0 to 130.0V in 0.1V steps Phase to Phase Undervoltage threshold 5.0 to 130.0V in 0.1V steps Rate of voltage change threshold 1 to 20V in 1steps

DIFG Guard characteristic

Rate of Earth fault change threshold 0.02 to 50.00A in 0.01A steps (1A rating) 0.10 to 250.00A in 0.01A steps (5A rating)

Phase Fault Distance Measuring Element

Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach (Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR)

0.10 to 500.00Ω in 0.01Ω steps (1A rating)

0.01 to 100.00Ω in 0.01Ω steps (5A rating)

Characteristic angle

Z*-Mho.Angle and Z*-R.Angle (Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR)

30° to 90° in 1° steps

Z*- DirX.Angle and Z*-DirR.Angle (Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR)

0° to 60° in 1° steps

ZSF-X.GrAngle1 and ZSR-X.GrAngle1 0° to 45°in 1° steps

ZSF-X.GrAngle2 and ZSR-X.GrAngle2 45° to 90° in 1° steps

Earth Fault Distance Measuring Element

Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach (Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)

0.10 to 500.00Ω in 0.01Ω steps (1A rating)

0.01 to 100.00Ω in 0.01Ω steps (5A rating)

Characteristic angle

Z*-Mho.Angle and Z*-R.Angle (Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)

30° to 90° in 1° steps

Page 21: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

21

Z*- DirX.Angle and Z*-DirR.Angle (Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)

0° to 60° in 1° steps

ZGF-X.GrAngle1 and ZGR-X.GrAngle1 0° to 45°in 1° steps

ZGF-X.GrAngle2 and ZGR-X.GrAngle2 45° to 90° in 1° steps

Timer Setting

Time setting of Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G

0.00 to 100.00s in 0.01steps

Overcurrent Element for Guard

Overcurrent elements Z*_OCFS for supervision distance measuring elements (Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G)

0.02 to 5.00A in 0.01A steps (1A rating )

0.10 to 25.00A in 0.01A steps (5A rating)

Command Protection Distance Scheme

Time for current reverse block 0.00 to 10.00s in 0.01s steps

Coordination time for BOP scheme 0 to 50ms in 1ms steps

Delayed drop-off timer 0.00 to 1.00s in 0.01s steps

Command Protection Earth Fault Scheme

Time for delay trip 0.00 - 0.30s in 0.01s steps

Time for current reverse block 0.00 to 10.00s in 0.01s steps

Coordination time for BOP scheme 0 to 50ms in 1ms steps

delayed drop-off timer 0.00 to 1.00s in 0.01s steps

Power Swing Block

Detection zone (PSBGS)

Detection timer (TPSBS)

2.50 to 75.00Ω in 0.01Ω steps (1A rating)

0.50 to 15.00Ω in 0.01Ω steps (5A rating) Load Encroachment

Minimum load resistance (LESR, LESL) 0.10 to 500.00Ω in 0.01Ω steps (1A rating)

0.01 to 100.00Ω in 0.01Ω steps (5A rating) Maximum load angle (LESR-Angle, LESL-Angle) 5° to 75° in 1° steps

Charging Current Compensation

Charging current compensation for distance relay

0.00 to 1.00A in 0.01A steps (1A rating)

0.00 to 5.00A in 0.01A steps (5A rating)

Rated voltage for charging current compensation

100 to 120V in 1V steps

Minimum Operating Current

Current 0.08A fixed (1A relay)

0.4A fixed (5A relay)

Earth fault current 0.10 to 1.00A in 0.01A steps(1A rating)

0.50 to 5.00A in 0.01A steps (5A rating)

Switch-on-to-fault Protection

Overcurrent threshold 0.02 to.5.00A in 0.01A steps (1A rating)

0.10 to 15.00A in 0.01A steps (5A rating)

Stub Protection

Overcurrent threshold 0.02 to 5.00A in 0.01A steps (1A rating)

0.10 to 15.00A in 0.01A steps (5A rating)

Out-of-step Protection (Out of step tripping (volta ge phase comparison)

Out-of-step trip OFF / TRIP / BO(separated from other trip signals)

Out-of-step Protection (impedance locus)

Resistive reach (at Right side) 15.00 to 150.00Ω in 0.01Ω steps (1A rating)

3.000 to 30.000Ω in 0.01Ω steps (5A rating)

Resistive reach (at Left side) 5.00 to 50.00Ω in 0.01Ω steps (1A rating)

1.000 to 10.000Ω in 0.01Ω steps (5A rating)

Resistive reach (at Forward) 5.00 to 250.00Ω in 0.01Ω steps (1A rating)

Page 22: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

22

1.000 to 50.000Ω in 0.001Ω steps (5A rating)

Resistive reach (at Backward) 1.0 to 50.00Ω in 0.01Ω steps (1A rating)

0.200 to 10.000Ω in 0.001Ω steps(5A rating)

Detection time 0.01 to 1.00s in 0.01s steps

Breaker Failure (BF) Protection

Overcurrent element 0.1 to 2.0A in 0.1A steps (1A rating) 0.5 to 10.0A in 0.1A steps (5A rating)

BF timer for retry-trip of failed breaker 50 to 500ms in 1ms steps

BF timer for related breaker trip 50 to 500ms in 1ms steps

Non-directional and Directional Overcurrent Protect ion

1st, 2nd, 3rd, 4th Definite time overcurrent threshold

0.02 to 50.00A in 0.01A steps (1A rating)

0.10 to 250.00A in 0.01A steps (5A rating)

1st, 2nd, 3rd, 4th Inverse time overcurrent threshold

0.02 to 5.00A in 0.01A steps (1A rating)

0.10 to 25.00A in 0.01A steps (5A rating)

Direction characteristic Non Directional / Forward / Backward

Polarising voltage 1.0 V (fixed)

Characteristic angle 0 to 180 deg in 1 deg steps

Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO2 / US-CO8 / Original

Drop-out/pick-up ratio 10 to 100% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps

Reset type Definite Time or Dependent Time

Reset definite delay 0.00 to 300.00s in 0.01s steps

Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

Non-directional and Directional Earth Fault Protect ion

1st, 2nd, 3rd, 4th Definite time earth fault threshold 0.02 to 50.00A in 0.01A steps (1A rating)

0.10 to 250.00A in 0.01A steps (5A rating)

1st, 2nd, 3rd, 4th Inverse time earth fault threshold 0.02 to 5.00A in 0.01A steps (1A rating)

0.10 to 25.00A in 0.01A steps (5A rating)

Direction characteristic Non Directional / Forward / Backward

Characteristic angle 0 to 180° in 1° steps (3I0 lags for −3V0)

Polarising voltage (3V0) 0.5 to 100.0V in 0.1V steps

Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO2 / US-CO8 / Original

Drop-out/pick-up ratio 10 to 100% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps

Reset type Definite Time or Dependent Time

Reset definite delay 0.00 to 300.00s in 0.01s steps

Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

Non-directional and Directional Negative Sequence P hase Overcurrent (NOC) Protection

1st, 2nd, 3rd, 4th Definite time NOC threshold 0.02 to 50.00A in 0.01A steps (1A rating)

0.10 to 250.00A in 0.01A steps (5A rating)

1st, 2nd, 3rd, 4th Inverse time NOC threshold 0.02 to 5.00A in 0.01A steps (1A rating)

0.10 to 25.00A in 0.01A steps (5A rating)

Direction characteristic Non Directional / Forward / Backward

Characteristic angle 0 to 180° in 1° steps (3I0 lags for −3V0)

Polarising voltage 0.5 to 25.0V in 0.1V steps

Delay type DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-VI / IEEE-EI / US-CO2 / US-CO8 / Original

Drop-out/pick-up ratio 10 to 100% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

Page 23: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

23

IDMTL Time Multiplier Setting TMS 0.010 to 50.000 in 0.001 steps

Reset type Definite Time or Dependent Time

Reset definite delay 0.00 to 300.00s in 0.01s steps

Reset Time Multiplier Setting RTMS 0.010 to 50.000 in 0.001 steps

Inrush Current Detection

Second harmonic detection 10 to 50% in 1% steps

Inrush current thresholds 0.10 to 5.00A in 0.01A steps (1A rating)

0.5 to 25.0A in 0.1A steps (5A rating)

Thermal overload Protection

Thermal setting (THM = k.IFLC) 0.40 – 2.00A in 0.01A steps (1A rating)

2.0 – 10.0A in 0.1A steps (5A rating)

Time constant (τ) 0.5 – 500.0mins in 0.1min steps

Thermal alarm OFF, 50% to 100% in 1% steps

Pre-load current setting 0.00 – 1.00A in 0.01A steps (1A rating)

0.0 – 5.0A in 0.1A steps (5A rating)

Broken Conductor Detection

Broken conductor threshold 0.10 to 1.00 in 0.01 steps DTL delay 0.00 to 300.00s in 0.01s steps Phase Overvoltage Protection

1st, 2nd overvoltage threshold 1.0 to 220.0V in 0.1V steps

Delay type DTL, IDMT, Original

Drop-out/pick-up ratio 10 to 100% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 100.000 in 0.001 steps

Reset delay 0.0 to 300.0s in 0.1s steps

Phase to Phase Overvoltage Protection

1st, 2nd overvoltage threshold 1.0 to 220.0V in 0.1V steps

Delay type DTL, IDMT, Original

Drop-out/pick-up ratio 10 to 100% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 100.000 in 0.001 steps

Reset delay 0.0 to 300.0s in 0.1s steps

Phase Undervoltage Protection

1st, 2nd undervoltage threshold 5.0 to 130.0V in 0.1V steps

Delay type DTL, IDMT, Original

Drop-out/pick-up ratio 100 to 120% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 100.000 in 0.001 steps

Reset delay 0.0 to 300.0s in 0.1s steps

Undervoltage block threshold 5.0 to 20.0V in 0.1V steps

Undervoltage block delay 0.00 to 300.00s in 0.01s steps

Phase to Phase Undervoltage Protection

1st, 2nd undervoltage threshold 5.0 to 130.0V in 0.1V steps

Delay type DTL, IDMT, Original

Drop-out/pick-up ratio 100 to 120% in 1% steps

DTL delay 0.00 to 300.00s in 0.01s steps

IDMTL Time Multiplier Setting TMS 0.010 to 100.000 in 0.001 steps

Reset delay 0.0 to 300.0s in 0.1s steps

Undervoltage block threshold 5.0 to 20.0V in 0.1V steps

Undervoltage block delay 0.00 to 300.00s in 0.01s steps

Under/Over Frequency Protection

Page 24: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

24

1st - 4th under/overfrequency threshold (Fnom − 10.00Hz) – (Fnom + 10.00Hz) in 0.01Hz steps Fnom: nominal frequency

DTL delay: 0.00 – 300.00s in 0.01s steps

Frequency UV Block 40.0 – 100.0V in 0.1V steps

Autoreclosing

Number of shots 1 to 5 shots

Dead time for single-phase autoreclose 0.01 to 300.00s in 0.01s steps

Dead time for three-phase autoreclose 0.01 to 300.00s in 0.01s steps

Multi-shot dead line time 0.01 to 300.00s in 0.01s steps

Reclaim time 0.0 to 600.0s in 0.1s steps

Pulse width of reclosing signal output 0.01 to 10.00s in 0.01s steps

Autoreclose reset time 0.01 to 310.00s in 0.01s steps

Reset time for developing fault 0.01 to 300.00s in 0.01s steps

Follower breaker autoreclose delay time 0.01 to 300.00s in 0.01s steps

Voltage and Synchronism Check

Synchronism check angle 0° to 75° in 1° steps

UV element 10 to 150V in 1V steps

OV element 10 to 150V in 1V steps

Busbar or line dead check 10 to 150V in 1V steps

Busbar or line live check 10 to 150V in 1V steps

Synchronism check time 0.01 to 100.00s in 0.01s steps

Voltage check time 0.01 to 100.00s in 0.01s steps

Voltage Transformer Failure Supervision

Undervoltage element (phase-to-phase) 50 to 100V in 1V steps

Undervoltage element (phase-to-earth) 10 to 60V in 1V steps

Current change detection element 0.1A fixed (1A rating)

0.5A fixed (5A rating)

Residual voltage element 20V fixed

Residual current element Common use with earth fault detection element

Fault Locator

Line reactance and resistance setting 0.0 to 999.9Ω in 0.1Ω steps (1A rating) 0.00 to 199.99Ω in 0.01Ω steps (5A rating)

Line length 0.0 to 399.9km in 0.1km steps

Correction factor of impedance between lines 80 to 120% in 1% steps

Correction factor of impedance between in each phase

80 to 120% in 1% steps

Accuracy ±0.4km (up to 20km, without fault at near end)

±2% (up to 399.9km, without fault at near end)

Minimum measuring cycles 2.5 cycles

Metering Function

AC Current Accuracy ± 0.5% (at rating)

AC Voltage Accuracy ± 0.5% (at rating)

Energy (Wh, varh) Accuracy ± 1.0% (at rating)

Power (P, Q) Accuracy ± 1.0% (at rating when power quantities being fed)

Frequency Accuracy ± 0.03Hz

GPS Time Synchronisation

Protocol SNTP

Page 25: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

25

ORDERING INFORMATION 1. Line Differential protection relay [Hardware selection]

7 8 9 A B C D E F G H J K L

Configurations G R L 2 0 0 - - - - - 0 - 0

Application of power system

Function for single breaker scheme (CTx5,VT5) 1

Function for one and a half breaker scheme(CTx9, VTx5) 2

System Frequency

50Hz 1

60Hz 2

AC Rating for Phase Currents

1A 1

5A 2

DC Rating

110-250 Vdc or 100-220Vac (See (*1)) 1

48-125 Vdc 2

24/48/60 Vdc 3

Outline

Standard LCD, 1/2 x 19’’ rack for flush mounting 2

Standard LCD, 3/4 x 19’’ rack for flush mounting 3

Standard LCD, 1/1 x 19’’ rack for flush/rack mounting 4

Large LCD, 1/2 x 19’’ rack for flush mounting 6

Large LCD, 3/4 x 19’’ rack for flush mounting 7

Large LCD, 1/1 x 19’’ rack for flush/rack mounting 8

Standard LCD, 1/2 x 19’’ rack for rack mounting (See (*2)) F

Standard LCD, 3/4 x 19’’ rack for rack mounting (See (*2)) G

Large LCD, 1/2 x 19’’ rack for rack mounting (See (*2)) J

Large LCD, 3/4 x 19’’ rack for rack mounting (See (*2)) K

BI/BO Module

Refer to Number of BI/BO Table

Communication for Protection (1)

1CH 1

2CH 2

Communication for Protection (2)

Refer to communication Table

Number of Serial and/or Ethernet Communication and/ or Time Synch Port(s)

Refer to Communication port Table

Function Block (linked with software selection)

See function table of software selection

Note: (*1) Binary inputs are intended for use with DC power source only.

The power supply supervision function is intended for use with DC power source only. It should be disabled when AC power supply is applied in order to prevent spurious alarms.

(*2) For 19” rack panel mounting, accessories of joint kits are available. (See Figure 23) Please contact with our sales staffs when you require user configurable models that are not indicated in the ordering sheet above.

Page 26: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

26

[Software selection]

7 M G N E F P 9 Q

Configurations G R L 2 0 0 - 0 - -

Application of power system

Assignment on position “7”

Function Block

Refer to Function Table Communication for Remote / Time Synch. (1)

Assignment on position “E”

Communication for Remote / Time Synch. (2)

Assignment on position “F”

Protocol

IEC60870-5-103 + IEC61850 (Hot-Stand-by) 1

IEC61850 (Hot-Stand-by) 2

IEC61850 (PRP) (When position E = L – N)

3

Outline

Assignment on position “9”

Language

English E

Note: Software selection codes “1” to “7”, “E”, “F” and “9” are common with hardware selection codes.

Page 27: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

27

Number of BI/BO

BI/BO 1 x I/O module (For all case sizes)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hyb

rid B

O

DC

-AO

7 - - - - 6 4 - - 11 1xBIO1 12 - - - - 3 2 - - 12 1xBIO2 8 - - - 6 - 2 - - 13 1xBIO3 - 6 - - - - 2 6 - 14 1xBIO4

18 - - - - - - - - 15 1xBI1 - 12 - - - - - - - 16 1xBI2 - - 32 - - - - - - 17 1xBI3

Other Configuration ZZ To be specified at ordering

BI/BO 2 x I/O module (For all case sizes)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

- - 32 - - 6 12 - - 21 1xBI3+1xBO1 7 - 32 - - 6 4 - - 22 1xBI3+1xBIO1

12 - 32 - - 3 2 - - 23 1xBI3+1xBIO2 18 - - - - 6 12 - - 24 1xBI1+1xBO1 25 - - - - 6 4 - - 25 1xBI1+1xBIO1 30 - - - - 3 2 - - 26 1xBI1+1xBIO2 8 - - - 6 6 14 - - 27 1xBO1+1xBIO3

15 - - - 6 6 6 - - 28 1xBIO1+1xBIO3 7 - - - - 12 16 - - 29 1xBO1+1xBIO1

16 - - 12 - 4 - - 2A 2xBIO3 - - 32 - - - - 16 - 2B 1xBI3+1xBO2 - 12 - - - 6 12 - - 2C 1xBI2 +1xBO1 - - 32 10 - - - - - 2D 1xBI3+1xDCAI2

Other Configuration ZZ To be specified at ordering

Page 28: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

28

BI/BO 3 x I/O module (For all case sizes)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

15 - - - 6 12 18 - - 31 1xBO1+1xBIO1+1xBIO3 20 - - - 6 9 16 - - 32 1xBO1+1xBIO2+1xBIO3 23 - - - 12 6 8 - - 33 1xBIO1+2xBIO3 26 - - - 6 6 14 - - 34 1xBI1+1xBO1+1xBIO3 8 - 32 - 6 6 14 - - 35 1xBI3+1xBO1+1xBIO3

24 - - - 18 - 6 - - 36 3xBIO3 25 - - - - 12 16 - - 37 1xBI1+1xBO1+1xBIO1 36 - - - - 6 12 - - 39 2xBI1+1xBO1 - 24 - - - 6 12 - - 3A 2xBI2+1xBO1

18 6 - - - 6 14 6 - 3B 1xBI1+1xBO1+1xBIO4 7 - 32 - - 6 4 16 - 3C 1xBI3+1xBIO1+1xBO2 7 - 32 - - 12 16 - - 3D 1xBI3+1xBO1+1xBIO1 - - 32 - - 6 12 16 - 3E 1xBI3+1xBO1+1xBO2

16 - - - 12 6 16 - - 3G 1xBO1+2xBIO3 - 6 32 - - 6 14 6 - 3H 1xBI3+1xBO1+1xBIO4

26 - - - 6 6 14 - - 3J 1xBO1+1xBIO3+1xBI1 (*1) - - 64 - - 6 12 - - 3K 2xBI3+1xBO1

14 - 32 - - 12 8 - - 3L 1xBI3+2xBIO1 - - 96 - - - - - - 3M 3xBI3 8 12 - - 6 6 14 - - 3N 1xBI2+1xBO1+1xBIO3 - - 32 - - 12 24 - - 3P 1xBI3 + 2xBO1

36 - - - - - - 16 - 3Q 2xBI1 + 1xBO2 - - - 30 - - - - - 3R 3xDCAI2

Other Configuration ZZ To be specified at ordering Note: (*1) module arrangement is different from 34

Page 29: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

29

BI/BO 4 x I/O modules (For case sizes 3/4 and 1/1 -Set code position “9” to “3”, “4”, “7”, “8”, “G”, or “K”)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

26 - - - 6 12 26 - - 41 1xBI1+2xBO1+1xBIO3 32 - - - 24 - 8 - - 42 4xBIO3 8 - 32 - 6 12 26 - - 43 1xBI3+2xBO1+1xBIO3 - - 64 - - 12 24 - - 44 2xBI3+2xBO1

54 - - - - 6 12 - - 46 3xBI1+1xBO1

20 - 32 - 6 9 16 - - 47 1xBI3+1xBO1+1xBIO2 +1xBIO3

26 - - - 6 12 26 - - 48 1xBO1+1xBI1+1xBO1 +1xBIO3 (*2)

20 6 15 28 49 2xBO1+1xBIO2+1xBIO3 34 - - - 12 6 16 - - 4B 1xBI1+1xBO1+2xBIO3 - - 64 - - - - 32 - 4C 2xBI3+2xBO2

21 - 32 - - 18 12 - - 4D 1xBI3+3xBIO1 - - 128 - - - - - - 4E 4xBI3 7 96 6 4 4F 3xBI3+1xBIO1 8 24 - - 6 6 14 - - 4G 2xBI2 +1xBO1 +1xBIO3 - - 32 - - 18 36 - - 4H 1xBI3 + 3xBO1

26 12 - - 6 6 14 - - 4J 1xBI1 + 1xBI2 + 1xBO1 + 1xBIO3

24 - 32 - - 12 16 - - 4K 1xBI3+1xBO1+2xBIO2 15 - - - 6 18 30 - - 4L 2xBO1+1xBIO1+1xBIO3 7 - - - - 24 40 - - 4M 3xBO1+1xBIO1

36 - - - - 12 24 - - 4N 2xBI1+2xBO1 8 - 64 - 6 6 14 - - 4P 2xBI3+1xBO1+1xBIO3

36 - - - - 6 12 16 - 4Q 2xBI1+1xBO1+1xBO2

Other Configuration ZZ To be specified at ordering Note: (*2) module arrangement is different from 41.

Page 30: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

30

BI/BO 5 x I/O modules (For case sizes 3/4 and 1/1 -Set code position “9” to “3”, “4”, “7”, “8”, “G”, or “K”)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

33 - - - 6 6 6 32 - 51 1xBI1+1xBIO1+1xBIO3 +2xBO2

44 - - - 6 12 26 - - 52 2xBI1+2xBO1+1xBIO3 25 - 96 - - 6 4 - - 53 1xBI1+3xBI3+1xBIO1 8 - 96 - 6 6 14 - - 54 3xBI3+1xBO1+1xBIO3

62 - - - 6 6 14 - - 56 3xBI1+1xBO1+1xBIO3 54 6 - - - 6 14 6 - 57 3xBI1+1xBO1+1xBIO4

20 - 32 - 6 9 16 - - 5A 1xBI3+1xDCAI2+1xBO1 +1xBIO2+1xBIO3

- - 96 - - 12 24 - - 5B 3xBI3+2xBO1 - - 128 - - 6 12 - - 5E 4xBI3+1xBO1 - - 160 - - - - - - 5F 5xBI3

44 12 - - 6 6 14 - - 5G 2xBI1+1xBI2+1xBO1 +1xBIO3

15 - - - 6 24 42 - - 5H 3xBO1+1xBIO1+1xBIO3 - - 64 - - 18 36 - - 5J 2xBI3+3xBO1 - - - - - 30 60 - - 5L 5xBO1

Other Configuration ZZ To be specified at ordering

BI/BO 6 x I/O modules (For case sizes 3/4 and 1/1 -Set code position “9” to “3”, “4”, “7”, “8”, “G”, or “K”)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

51 - - - 6 18 30 - - 61 2xBI1+2xBO1+1xBIO1 +1xBIO3

8 - 96 - 6 12 26 - - 62 3xBI3+2xBO1+1xBIO3 - - 128 - - 12 24 - - 63 4xBI3+2xBO1 8 - 128 - 6 6 14 - - 64 4xBI3+1xBO1+1xBIO3

52 - - - 12 - 4 32 - 69 2xBI1+2xBIO3+2xBO2 52 - - - 12 12 28 - - 6A 2xBI1+2xBO1+2xBIO3 36 - - - - 24 48 - - 6B 2xBI1+4xBO1 36 - 64 - - 12 24 - - 6C 2xBI1+2xBI3+2xBO1 44 - - - 6 18 38 - - 6D 2xBI1+3xBO1+1xBIO3 - - 160 - - 6 12 - - 6E 5xBI3+1xBO1 7 - 160 - - 6 4 - - 6F 5xBI3+1xBIO1

Other Configuration ZZ To be specified at ordering

Page 31: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

31

BI/BO 7 x I/O modules (For case size 1/1 -Set code position “9” to “4” or “8”)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

80 - - - 6 12 26 - - 71 4xBI1+2xBO1+1xBIO3 72 6 - - - 12 26 6 - 72 4xBI1+2xBO1+1xBIO4 8 - 96 - 6 18 38 - - 73 3xBI3+3xBO1+1xBIO3 - 6 96 - - 18 38 6 - 74 3xBI3+3xBO1+1xBIO4 - 60 - - - 6 12 16 - 78 5xBI2+1xBO1+1xBO2 - - 160 - - 12 24 - - 79 5xBI3+2xBO1

54 - 64 - - 12 24 - - 7B 3xBI1 + 2xBI3 + 2xBO1 - - 128 - - 18 36 - - 7D 4xBI3+3xBO1 7 - 160 - - 12 16 - - 7E 5xBI3+1xBO1+1xBIO1 - - 192 - - 6 12 - - 7F 6xBI3+1xBO1 7 - 192 - - 6 4 - - 7G 6xBI3+1xBIO1 - - 224 - - - - - - 7H 7xBI3

Other Configuration ZZ To be specified at ordering

BI/BO 8 x I/O modules (For case size 1/1 -Set code position “9” to “4” or “8”)

Number of BI/BO Ordering No.

(Position “A” to “B”)

Configuration

Inde

pend

ent

BI

Inde

pend

ent

BI (

varia

ble)

Com

mon

B

I

DC

-AI

Fas

t-B

O

Sem

i-fas

t BO

BO

Hea

vy d

uty

BO

DC

-AO

- - 160 - - 18 36 - - 83 5xBI3+3xBO1 - 60 - - - 6 12 32 - 87 5xBI2+1xBO1+2xBO2 8 - 128 - 6 18 38 - - 88 4xBI3+3xBO1+1xBIO3 - - 256 - - - - - - 8C 8xBI3 7 - 224 - - 6 4 - - 8G 7xBI3+1xBIO1 - - 192 - - 12 24 - - 8H 6xBI3+2xBO1 7 - 192 - - 12 16 - - 8J 6xBI3+1xBO1+1xBIO1

Other Configuration ZZ To be specified at ordering

Please contact with our sales staffs when you require “other configuration (Ordering number: ZZ)” that is not indicated in the ordering code above.

Page 32: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

32

Communication 1CH Communication for Protection (Position “C” is set to “1”)

Communication Type Ordering No.

(Position “D”)

Protection signal GI 2km Class (C37.94) 1

Protection signal SM 30km Class 2

Protection signal DSF 80km Class 3

2CH Communication for Protection (Position “C” is set to “2”)

Communication Type Ordering No.

(Position “D”)

Protection signal GI 2km Class (C37.94) x2ch 1

Protection signal SM 30km Class x2ch 2

Protection signal DSF 80km Class x2ch 3

Protection signal GI 2km Class (C37.94) x1ch Protection signal SM 30km Class x1ch

4

Protection signal GI 2km Class (C37.94) x1ch Protection signal DSF 80km Class x1ch

5

Protection signal SM 30km Class x1ch Protection signal DSF 80km Class x1ch

6

Page 33: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

33

Communication port Table Serial and/or Ethernet and/or Time Synch port

Ordering No. (Position “E”

to “F”) Remark

IEC 60870-5-103 IE C

61 85 0- 8- 1

IRIG

-B

Con

nect

ion

term

inal

fo

r ex

tern

al I/

O u

nit

(GIO

200)

RS

485

Fib

er o

ptic

(f

or s

eria

l)

100B

ase-

FX

100B

ase-

TX

/ 10

00B

ase-

T

1000

Bas

e-LX

1 14 1 1J 1 1K 1 1 34 1 1 3J 1 1 3K 2 46

1 1 4C 1 1 4G 2 4L 2 4M

1 1 4N 1 1 4Q 1 1 4S 1 1 4U 2 1 66

1 1 1 6C 1 1 1 6G 2 1 6L 2 1 6M

1 1 1 6N 1 1 1 6Q 1 1 1 6S 1 1 1 6U

1 2 7D 1 2 7H

1 2 7P 1 2 7R 1 2 7T 1 2 7V 2 L6 for PRP

1 2 LD for PRP 1 2 LH for PRP 2 LL for PRP 2 LM for PRP

1 2 LP for PRP 1 2 LR for PRP 1 2 LT for PRP 1 2 LV for PRP 2 1 N6 for PRP

1 2 1 ND for PRP (*1) 1 2 1 NH for PRP (*1) 2 1 NL for PRP 2 1 NM for PRP

1 2 1 NP for PRP (*1) 1 2 1 NR for PRP (*1) 1 2 1 NT for PRP (*1)

Page 34: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

34

Serial and/or Ethernet and/or Time Synch port

Ordering No. (Position “E”

to “F”) Remark

IEC 60870-5-103 IE C

61 85 0- 8- 1

IRIG

-B

Con

nect

ion

term

inal

fo

r ex

tern

al I/

O u

nit

(GIO

200)

RS

485

Fib

er o

ptic

(f

or s

eria

l)

100B

ase-

FX

100B

ase-

TX

/ 10

00B

ase-

T

1000

Bas

e-LX

1 2 1 NV for PRP (*1) Note: (*1) Selectable, when position “C” is “1 (=1CH)”

Page 35: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

35

FUNCTION TABLE

Function Block Protection function Ordering No. (Position “ G & N”)

33 34 35 37

DIFL

87 Phase-segregated current differential protection

50 FS Fail safe OC 27 FS Fail safe UV CCC Charging current compensation CTF CT failure detection by Id 87R Remote differential trip THC Through-fault current countermeasure

50STUB Stub protection

DIFG

87N Zero phase current differential protection

50N/51N FS Fail safe EF

CCC Charging current compensation 87R Remote differential trip THC Through-fault current countermeasure

50STUB Stub protection

DTT DTT Direct transfer trip function(*1)

DISTANCE_ZS (6zone)

21 Distance protection(for phase fault) with 6zone 68 Power swing block

50SOTF Switch on to fault protection

DISTANCE_ZG (6zone)

21N Distance protection(for earth fault) with 6zone 68 Power swing block

50SOTF Switch on to fault protection DEFCAR 85-67N Directional earth fault carrier command protection DISCAR 85-21 Distance carrier command protection SOTF-OC 50SOTF Switch on to fault protection

OC 50/67 Non-directional / directional definite time

over-current protection

51/67 Non-directional / directional inverse time over-current protection

EF 50N/67N Non-directional / directional definite time earth fault

over-current protection

51N/67N Non-directional / directional inverse time earth fault over-current protection

OCN 46/67 Non-Directional / directional Negative sequence phase over-current protection

THM 49 Thermal overload protection

BCD 46BC Broken conductor protection

CBF 50BF Circuit breaker failure protection

OV 59 Phase over-voltage protection

OVS 59 Phase-phase over-voltage protection

UV 27 Phase under-voltage protection UVS 27 Phase-phase under-voltage protection

Bas

ic1

Bas

ic2

Bas

ic1

with

con

trol

Bas

ic3

with

Inte

gral

com

mun

icat

ion

Page 36: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

36

Function Block Protection function Ordering No. (Position “ G & T”)

33 34 35 37

FRQ 81 Frequency protection OSTV 56V Out of step tripping by voltage(*1) ICD ICD Inrush current detection function FS FS Fail-safe function VTF VTF VTF detection function CTF CTF CTF detection function FL-Z 21FL Fault locator FL-A FL Fault locator TRC 94 Trip circuit ARC 79 Autoreclosing function SYNC 25 Voltage check for autoreclosing

General Control LEDR LED reset GCNT Counter function for the general MDCTRL Mode control function

Control and monitor

SPOS Single position device function

DPSY Double position controller with synchronizing

SOTFSW Software switch controller

OPTIM Operation time reset

TOTALTIM

Total time measurement

SYNDIF Synchronizing check for different network

INTERLOCK Software interlock

DPOS Double position device function

TPOS Three position device function

GENBI Event detection function for general BIs

ASEQ Automatic sequence control function

Bas

ic1

Bas

ic2

Bas

ic1

with

con

trol

Bas

ic3

with

Inte

gral

com

mun

icat

ion

Page 37: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

37

2. Interface Converter

Configurations G I F 2 0 0 -

Electrical interface protocol

ITU-T G.703 (64kbps, co-directional) 0 1

ITU-T G.703 (64kbps, contra-directional or centralized clock) 0 2

Page 38: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

38

DIMENSION AND PANEL CUT-OUT (1/2 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 16 – Dimension and Panel Cut-out – 1/2 x 19’’ case size

(when compression plug type terminals are applied)

(38)

Page 39: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

39

DIMENSION AND PANEL CUT-OUT (3/4 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 17 – Dimension and Panel Cut-out – 3/4 x 19’’ case size for flush mounting type

(when compression plug type terminals are applied)

(38)

Page 40: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

40

DIMENSION AND PANEL CUT-OUT (1/1 size)

(Panel cut-out)

Note: For a rack mount unit, there are holes for joint kits assembling on top and bottom of the unit.

Figure 18 – Dimension and Panel Cut-out – 1/1 x 19” case size for flush mounting type (when compression plug type terminals are applied)

(38)

Page 41: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

DIMENSION AND PANEL CUT

Figure

DIMENSION AND PANEL CUT

Figure 19 – Outline of Interface Converter GIF200

DIMENSION AND PANEL CUT

Outline of Interface Converter GIF200

DIMENSION AND PANEL CUT -OUT (

Outline of Interface Converter GIF200

41

OUT (Interface Converter

Outline of Interface Converter GIF200

Interface Converter

Interface Converter )

Page 42: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

42

19” RACK MOUNTING JOINT KITS ATTACHMENT

<Panel mounting kits – only for compressed terminal type racks>

Name Code

Joint kits for single 1/2 x 19” size rack EP-204

Joint kits for two 1/2 x 19” size racks EP-205

Joint kits for single 3/4 x 19” size rack EP-206

EP-204 (single 1/2 x 19” size rack) EP-205 (two 1/2 x 19” size racks)

Figure 20 – Joint kits example for 19” rack panel mounting

Page 43: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

43

CONNECTIONS DIAGRAM

BI1 A

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

27

28 BI13

(+)

(-)

29

30 BI14

(+)

(-)

31

32 BI15

(+)

(-)

35

36 BI17

(+)

(-)

33

34 BI16

(+)

(-)

37

38 BI18

(+)

(-)

BI2 A

1

2 BI1

(+)

(-)

5

6 BI2

(+)

(-)

7

8 BI3

(+)

(-)

11

12 BI4

(+)

(-)

13

14 BI5

(+)

(-)

21

22 BI7

(+)

(-)

17

18 BI6

(+)

(-)

25

26 BI8

(+)

(-)

27

28 BI9

(+)

(-)

31

32 BI10

(+)

(-)

33

34 BI11

(+)

(-)

37

38 BI12

(+)

(-)

BI3 A

35

36

(-)

(-)

37

38

(-)

(-)

1 (+) BI1

2 (+) BI2

3 (+) BI3

4 (+) BI4

5 (+) BI5

6 (+) BI6

7 (+) BI7

8 (+) BI8

9 (+) BI9

10 (+) BI10

11 (+) BI11

12 (+) BI12

13 (+) BI13

14 (+) BI14

15 (+) BI15

16 (+) BI16

17 (+) BI17

18 (+) BI18

21 (+) BI19

22 (+) BI20

23 (+) BI21

24 (+) BI22

25 (+) BI23

26 (+) BI24

27 (+) BI25

28 (+) BI26

29 (+) BI27

30 (+) BI28

31 (+) BI29

32 (+) BI30

33 (+) BI31

34 (+) BI32

BO1 A

BO10(*4)

21

22

BO1(*2)

1

2

BO2(*2)

3

4

BO3(*2)

5

6

BO4(*2)

7

8

BO5(*2)

9

10

BO6(*2)

11

12

BO7(*4)

13

14

BO8(*4)

15

16

BO9(*4)

17

18

BO11(*4)

23

24

BO12(*4)

25

26

BO13(*4)

27

28

BO14(*4)

29

30

BO15(*4)

31

32

BO16(*4)

33

34

BO17(*4)

35

36

BO18(*4)

37

38

BO2 A

BO1(*3)

1

2

(+)

(-)

BO2(*3)

3

4

(+)

(-)

BO3(*3)

5

6

(+)

(-)

BO4(*3)

7

8

(+)

(-)

BO5(*3)

9

10

(+)

(-)

BO6(*3)

11

12

(+)

(-)

BO7(*3)

13

14

(+)

(-)

BO8(*3)

15

16

(+)

(-)

BO9(*3)

17

18

(+)

(-)

BO10(*3)

21

22

(+)

(-)

BO11(*3)

23

24

(+)

(-)

BO12(*3)

25

26

(+)

(-)

BO13(*3)

27

28

(+)

(-)

BO14(*3)

29

30

(+)

(-)

BO15(*3)

31

32

(+)

(-)

BO16(*3)

33

34

(+)

(-)

BIO1A

BO1(*2)

15

16

BO2(*2)

17

18

BO3(*2)

21

22

BO4(*2)

23

24

BO5(*2)

25

26

BO6(*2)

27

28

BO7(*4)

29

30

BO8(*4)

31

32

BO9(*4)

33

34

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

36

38

35

37

BO10(*5)

(*1) Fast BO (*2) Semi-fast BO (*3) Hybrid BO (*4) Normal BO (*5) Form-C BO

Figure 21 – Binary input board and binary output module for compression plug ty pe

Page 44: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

44

CONNECTIONS DIAGRAM

BIO2 A

BO1(*2)

27

28

BO2(*2)

29

30

BO3(*2)

31

32

BO4(*4)

33

34

36

38

35

37

BO5(*5)

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

17

18 BI9

(+)

(-)

21

22 BI10

(+)

(-)

23

24 BI11

(+)

(-)

25

26 BI12

(+)

(-)

BIO3A

BO1(*1)

21

22

BO2(*1)

23

24

BO3(*1)

25

26

BO4(*1)

27

28

BO5(*1)

29

30

BO6(*1)

31

32

BO7(*4)

33

34

36

38

35

37

BO8(*5)

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

13

14 BI7

(+)

(-)

11

12 BI6

(+)

(-)

15

16 BI8

(+)

(-)

BIO4A

BO7(*4)

33

34

36

38

35

37

BO8(*5)

1

2 BI1

(+)

(-)

3

4 BI2

(+)

(-)

5

6 BI3

(+)

(-)

7

8 BI4

(+)

(-)

9

10 BI5

(+)

(-)

11

12 BI6

(+)

(-)

BO1(*3)

17

18

(+)

(-)

BO2(*3)

21

22

(+)

(-)

BO3(*3)

23

24

(+)

(-)

BO4(*3)

25

26

(+)

(-)

BO5(*3)

27

28

(+)

(-)

BO6(*3)

29

30

(+)

(-)

PWS1 A

29

30

31

32

38

DC/DC

(+)

(-)

35

37

36

3

1

2

4

FAIL1

9

7

8

10

FAIL2

(*1) Fast BO (*2) Semi-fast BO (*3) Hybrid BO (*4) Normal BO (*5) Form-C BO

Figure 22 – Combined binary input and output module and DC power supply module for

compression plug type

Page 45: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

45

CONNECTIONS DIAGRAM

CT/VT module

VCT11B

30

Vb

3

4

Vc

5

6

Vs/Ve

7

8

Vs2/Ve

9

10

Ie2

25

26

Ia

11

12

Ib

13

14

Ic

15

16

Ie

17

18

Ia2

19

20

Ib2

21

22

Ic2

23

24

Iem

27

28

Va

1

2

GRZ/GRL (1.0)

VCT12B

Va

1

2

30

Vb

3

4

Vc

5

6

Vs/Ve

7

8

Vs2/Ve

9

10

Ia

11

12

Ib

13

14

Ic

15

16

Ie

17

18

Iem

27

28

GRZ/GRL (1.0)

Module no. 11 Module no. 12

(CT x 9 + VT x 5) (CT x 5 + VT x 5)

Figure 23 – CT/VT module

Page 46: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

46

EXTERNAL CONNECTIONS DIAGRAM

Figure 24 – Typical external connection diagram (PCT: No.12, IO: BI1, BO1 and BIO3)

BUS

VCT1-11

14

13 12

17

16

15

18

3

1

5

7

6

8

BUS VT1/2

CT

CB

VT

BUS VT1

9

10

A1

Semi-fast BO

DD FAIL.

B14

(-)

(+) +5Vdc

0V

B18

E

B17

B15

B16

DC

SUPPLY

CASE EARTH

DC-DC

RELAY FAIL.

≥1

BI1

BI10

BI11

BI2

BI8

BI12

BI9

BI5

BI6

BI7

BI3

BI4

BI13

BI14

BI15

BI16

BI17

BI18

30

BI1

VCT12

Programmable BI

Ethernet LAN I/F

(option) RJ45

Optical I/F (option)

2

4

BUS VT2

B1

A2

B2

A3

B3

A4

B4

A11

B11

A12

B12

A13

B13

A14

B14

A15

B15

A16

B16

A17

B17

A18

B18

A9

B9

A10

B10

A5

B5

A6

B6

A7

B7

A8

B8

PWS B2

B1

RELAY FAILURE 1 FAIL

B4

B3

B6

B5

RELAY FAILURE 2 FAIL

B8

B7

RS485 I/F

(option)

COM-B

COM-A

COM-0V

IRIG-B (option)

COM-B

COM-A

COM-0V

COM

Semi-fast BO

Semi-fast BO

Semi-fast BO

Semi-fast BO

A1

B1 BO1

A2

B2 BO2

A3

B3 BO3

A4

B4 BO4

A5

B5 BO5

A6

B6 BO6 Semi-fast BO

A7

B7 BO7

A8

B8 BO8

A9

B9 BO9

A10

B10 BO10

A11

B11 BO11

A12

B12 BO12

A13

B13 BO13

A14

B14 BO14

A15

B15 BO15

A16

B16 BO16

A17

B17 BO17

A18

B18 BO18

BO1

BIO3

A1

BI1 B1

A2

BI2 B2

A3

BI3 B3

A4

BI4 B4

A5

BI5 B5

A6

BI6 B6

A7

BI7 B7

A8

BI8 B8

Fast BO

Fast BO

Fast BO

Fast BO

Fast BO

Fast BO

A9

B9 BO1

A10

B10 BO2

A11

B11 BO3

A12

B12 BO4

A13

B13 BO5

A14

B14 BO6

A16

B16 BO7

A17

B18

BO8

A18

B17

3I0 from adjacent line

27

28

Page 47: Line Differential Protection IED - toshiba.co.jp · Line differential and teleprotection, direct optical and Ethernet packet Within substation ... protection in the event of failure

72-34,

Tel +81http://www.toshiba

, Horikawa-choTel +81-44-331-1462http://www.toshiba

cho, Saiwai-Ku, 1462 Fax +81-

http://www.toshiba-relays.com

Ku, Kawasaki-44-548-9540

Kawasaki 212-8585, Japan

9540

, Japan

・The information given in this catalog is subject to change without notice.・The information given in this catalog is as of ・The information given in this catalog is pre

applications of our products. No responsibility is assumed by TOSHIBA for any infringements of patents result from its use. No licensany patent or patent rights of TOSHIBA or others.

・TOSHIBA products should not be embedded to the downstream products which are prohregulations.

- Toshiba does not take any loss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the products.

The information given in this catalog is subject to change without notice.The information given in this catalog is as of The information given in this catalog is preapplications of our products. No responsibility is assumed by TOSHIBA for any infringements of patents result from its use. No licensany patent or patent rights of TOSHIBA or others.TOSHIBA products should not be embedded to the downstream products which are prohibited to be produced and sold, under any law and regulations. oshiba does not take any

loss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the products.

The information given in this catalog is subject to change without notice.The information given in this catalog is as of The information given in this catalog is preapplications of our products. No responsibility is assumed by TOSHIBA for any infringements of patents or other rights of the third parties which may result from its use. No license is granted by implication or otherwise under any patent or patent rights of TOSHIBA or others.TOSHIBA products should not be embedded to the downstream products

ibited to be produced and sold, under any law and

oshiba does not take any responsibilityloss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the

The information given in this catalog is subject to change without notice.The information given in this catalog is as of 25 OctoberThe information given in this catalog is presented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

or other rights of the third parties which may e is granted by implication or otherwise under

any patent or patent rights of TOSHIBA or others. TOSHIBA products should not be embedded to the downstream products

ibited to be produced and sold, under any law and

responsibility for incidental damage (including loss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the

GKP

The information given in this catalog is subject to change without notice.October 2017.

sented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

or other rights of the third parties which may e is granted by implication or otherwise under

TOSHIBA products should not be embedded to the downstream products

ibited to be produced and sold, under any law and

for incidental damage (including loss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the

GKP-99-15017 Rev1

©C

opyri

gh

t 2017 T

osh

iba E

ner

gy S

yst

ems

& S

olu

tion

s C

orp

orati

on. A

ll r

igh

ts r

eser

ved

.

The information given in this catalog is subject to change without notice.

sented only as a guide for the applications of our products. No responsibility is assumed by TOSHIBA for

or other rights of the third parties which may e is granted by implication or otherwise under

TOSHIBA products should not be embedded to the downstream products ibited to be produced and sold, under any law and

for incidental damage (including loss of business profit, business interruption, loss of business information and other pecuniary damage) arising out of the use or disability to use the

Rev1.2