linear fittings fluorescent fitting evn - zones 2 & 22 · abb dts - light fittings, boxes &...
TRANSCRIPT
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15 3/15
3
Linear fittingsFluorescent fittingEVN - Zones 2 & 22
Certifications
Approved to: EN60079-0, 60079-15, 60079-31
EC Type examination Directive 94/9/EC
certificate to: Ex II 3 G
Ex nR IIC T4 Gc for -40°C to + 60°C
Ex nR IIC T5 Gc for -40°C to + 35°C
Ex II 3 D
Ex tc IIIC T135°C Dc IP66 for -40°C to + 60°C
Ex tc IIIC T100°C Dc IP66 for -40°C to + 35°C
Glow wire test: 960ºC EN60598-2-22
Ambient -20°C to +55ºC EVN,
temperature range: -10°C to +50ºC EVN EM & EVN EMA
IP test: IP66 IEC 60529 (2001)
Impact protection index: IK09 according to IEC 62262
Standards
Features – Double central locking for ingress protection – All components mounted on hinged and removable gear
tray which gives easy access for maintenance – Including accessories (cable gland, plugs & fixing brackets) – Option: Automatic switch off on opening for safe
maintenance
Specifications
– Main body constructed of glass reinforced polyester for high impact strength
– UV protected polycarbonate diffuser to resist harsh environments
– Rated voltage 110- 260Vac/Vdc 50-60Hz – Wiring configuration: 5 wires – 3xEntries M20 – 2x Emergency versions (Type: “EM” version 3h battery
duration or “EMA” with 3h with automatic test and blackstart capabilities)
3/16 ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15
3
Linear fittingsFluorescent fittingEVN - Zones 2 & 22
Lamps Fluorescent Lamp (order separately)T8 bi-pin tube, lampholder G13, diameter 26mm - white industry 4000°k.
Photometric curveSee page 6/10
Rated voltagesElectronic ballast: 110- 260Vac/Vdc50-60Hz.
Power factor0.98.
Terminal block (screws) 6mm²(rigid wire), 4mm² (flexible wire) Terminals supplied L1, L2, L3, N, PE (looping possible with one additional cable gland)
Cable entriesThree entries M20 For non- armoured cable: included two M20 nylon plugs (EX-M20) and one M20 nylon cable gland, diameter 6-12mm (EXCGM20S)For armoured cable: included continuity plate - two M20 nylon plugs (EX-M20) and one M20 nickel plated brass cable gland, diameter 6-12/ 8.5-16mm (EXN04MMC1)
HousingFiberglass reinforced polyester housing for high impact strength, UV protected polycar-bonate diffuser to resist harsh environments,Painted steel gear tray & Stainless steel 316L insert
Fixing (included)V015 - 2x Two zinc-plated steel brackets for ceiling mounting
Technical information
Light Current External dimensions mm
Type Wiring Configuration Rating W A 230V A B C Weight kg
5 wires: Equipped with 1 cable gland & 2 plugs
EVN120-0000 5 wires 1 x 18 0.09 785 432 400 4.40
EVN140-0000 5 wires 1 x 36 0.17 1370 900 700 7.60
EVN165-0000 5 wires 1 x 58 0.26 1670 900 700 9.20
EVN220-0000 5 wires 2 x 18 0.17 785 432 400 4.40
EVN240-0000 5 wires 2 x 36 0.33 1370 900 700 7.60
EVN265-0000 5 wires 2 x 58 0.50 1670 900 700 9.20
EVN120-D000 5 wires & continuity plate 1 x 18 0.09 785 432 400 4.40
EVN140-D000 5 wires & continuity plate 1 x 36 0.17 1370 900 700 7.60
EVN165-D000 5 wires & continuity plate 1 x 58 0.26 1670 900 700 9.20
EVN220-D000 5 wires & continuity plate 2 x 18 0.17 785 432 400 4.40
EVN240-D000 5 wires & continuity plate 2 x 36 0.33 1370 900 700 7.60
EVN265-D000 5 wires & continuity plate 2 x 58 0.50 1670 900 700 9.20
5 wires through: Equipped with 2 cable glands & 1 plug
EVN120-B000 5 wires through 1 x 18 0.09 785 432 400 4.40
EVN140-B000 5 wires through 1 x 36 0.17 1370 900 700 7.60
EVN165-B000 5 wires through 1 x 58 0.26 1670 900 700 9.20
EVN220-B000 5 wires through 2 x 18 0.17 785 432 400 4.40
EVN240-B000 5 wires through 2 x 36 0.33 1370 900 700 7.60
EVN265-B000 5 wires through 2 x 58 0.50 1670 900 700 9.20
EVN120-E000 5 wires through & 2 continuity plates 1 x 18 0.09 785 432 400 4.40
EVN140-E000 5 wires through & 2 continuity plates 1 x 36 0.17 1370 900 700 7.60
EVN165-E000 5 wires through & 2 continuity plates 1 x 58 0.26 1670 900 700 9.20
EVN220-E000 5 wires through & 2 continuity plates 2 x 18 0.17 785 432 400 4.40
EVN240-E000 5 wires through & 2 continuity plates 2 x 36 0.33 1370 900 700 7.60
EVN265-E000 5 wires through & 2 continuity plates 2 x 58 0.50 1670 900 700 9.20
Technical specifications
DTS
Description
Approved by
Checked by
Processing
Drawn by
Material
Class
CUSTOMER
Scale
Tol.
Rev
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
DTS
Description
Approved by
Checked by
Processing
Drawn by
Material
Class
CUSTOMER
Scale
Tol.
Rev
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
EVN
5 wires: Equipped with 1 cable gland & 2 plugs 5 wires: Equipped with 1 cable gland & 2 plugs
5 wires through: Equipped with 2 cable glands & 1 plug 5 wires through: Equipped with 2 cable glands & 1 plug 5 wires through: Equipped with 2 cable glands & 1 plug 5 wires through: Equipped with 2 cable glands & 1 plug 5 wires through: Equipped with 2 cable glands & 1 plug
A
CB
DTS
Description
Approved by
Checked by
Processing
Drawn by
Material
Class
CUSTOMER
Scale
Tol.
Rev
CE PLAN NE PEUT ETRE COMMUNIQUE OU REPRODUIT MEME PARTIELLEMENT SANS L'AUTORISATION DE DTS
2 x M8 hole 20mm depth
137
mm
170 mm
Dimensional drawing
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15 3/17
3
Light Current External dimensions mm
Type Wiring Configuration Rating W Battery h A 230V A B C Weight kg
3 wires: Equipped with 1 cable gland & 2 plugs
EVN120EM-0000 3 wires 1 x 18 3h 0.09 785 432 400 5.80
EVN140EM-0000 3 wires 1 x 36 3h 0.17 1370 900 700 9.00
EVN165EM-0000 3 wires 1 x 58 3h 0.26 1670 900 700 10.60
EVN220EM-0000 3 wires 2 x 18 3h 0.17 785 432 400 5.80
EVN240EM-0000 3 wires 2 x 36 3h 0.33 1370 900 700 9.00
EVN265EM-0000 3 wires 2 x 58 3h 0.50 1670 900 700 10.60
EVN120EM-D000 3 wires & continuity plate 1 x 18 3h 0.09 785 432 400 5.80
EVN140EM-D000 3 wires & continuity plate 1 x 36 3h 0.17 1370 900 700 9.00
EVN165EM-D000 3 wires & continuity plate 1 x 58 3h 0.26 1670 900 700 10.60
EVN220EM-D000 3 wires & continuity plate 2 x 18 3h 0.17 785 432 400 5.80
EVN240EM-D000 3 wires & continuity plate 2 x 36 3h 0.33 1370 900 700 9.00
EVN265EM-D000 3 wires & continuity plate 2 x 58 3h 0.50 1670 900 700 10.60
* For dimensional drawing please refer to page 3/16
Linear fittingsEmergency fluorescent fitting - 3hEVN EM - Zones 2 & 22
Technical specifications
Emergency function diagrams
LampsFluorescent Lamp (order separately)T8 bi-pin tube, lampholder G13, diameter 26mm - white industry 4000°K
Rated voltagesElectronic ballast: 220-240 Vac/Vdc 50/60Hz
Power factor0.98.
BatteryBattery NiCd 7,2VLumen output in emergency mode (1 lamp lit)2 hours: 40% for EVN120, EVN220,33% for EVN140, EVN240, 10% for EVN165, EVN2653 hours: 24% for EVN120, EVN220, 18% for EVN140, EVN240, 8% for EVN165, EVN265Monitored by one LED
Terminal blockTerminal block (screws plug in terminal block)4mm²(rigid wire), 2,5mm² (flexible wire)Terminals supplied L1, L2, L3, LS, N, PE (looping possible with one additional cable gland)
Cable entriesThree entries M20 For non- armoured cable: included two M20 nylon plugs (EX-M20) and one M20 nylon cable gland, diameter 6-12mm (EXCGM20S)For armoured cable: included continuity plate - two M20 nylon plugs (EX-M20) and one M20 nickel plated brass cable gland, diameter 6-12/ 8,5-16mm (EXN04MMC1)
HousingFiberglass reinforced polyester housing for high impact strength, UV protected polycar-bonate diffuser to resist harsh environmentsStainless steel 316L insertPainted steel geartray
FixingV015 - 2x Two zinc-plated steel brackets for ceiling mounting
Electrical Features
Wiring provided by DTS - Maintained Mode Switch between LS/L1 - Non Maintained Mode *
Mains Supply Tube Battery
ON Lit Charged
OFF Only emergency tube lit Discharged
Mains Supply Tube Battery
ON OFF Charged
OFF Only emergency tube lit Discharged
* This table corresponds to the position 0 “open”. If the switch is on position 1 “close”, refer to the table on the left
EVS EM A terminals wiring diagram
1
0
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
EVS EM A terminals wiring diagram
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
1
0
3/18 ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15
3
Light Nominal External dimensions mm
Type Wiring Configuration Rating W Battery h Current A A B C Weight kg
5 wires: Equipped with 1 cable gland & 2 plugs
EVN120EMA-0000 5 wires 1 x 18 3h 0.09 785 432 400 5.80
EVN140EMA-0000 5 wires 1 x 36 3h 0.17 1370 900 700 9.00
EVN220EMA-0000 5 wires 2 x 18 3h 0.17 785 432 400 5.80
EVN240EMA-0000 5 wires 2 x 36 3h 0.33 1370 900 700 9.00
EVN120EMA-D000 5 wires & continuity plate 1 x 18 3h 0.09 785 432 400 5.80
EVN140EMA-D000 5 wires & continuity plate 1 x 36 3h 0.17 1370 900 700 9.00
EVN220EMA-D000 5 wires & continuity plate 2 x 18 3h 0.17 785 432 400 5.80
EVN240EMA-D000 5 wires & continuity plate 2 x 36 3h 0.33 1370 900 700 9.00
* For dimensional drawing please refer to page 3/16
Linear fittingsEmergency Fluorescent fitting with automatic test & blackstart capabilities - 3h. EVN EMA - Zones 2 & 22
Technical specifications
Mains Supply Tube Battery
ON OFF Charged
OFF Only emergency Discharged
tube lit
Mains Supply Tube Battery
ON Lit Charged
OFF Only emergency Discharged
tube lit
LampFluorescent Lamp (order separately)T8 bi-pin tube, lampholder G13, diameter 26mm - white industry 4000°K
Rated voltagesElectronic ballast: 220-240Vac/Vdc 50/60Hz
Power factor0.98.
BatteryBattery NiCd 6V 4Ah for EVN120, EVN220Battery NiCd 6V 7Ah for EVN140, EVN240Lumen output in emergency mode (1 lamp lit)3 hours: 40% for EVN120, EVN2203 hours: 33% for EVN140, EVN240Monitored by two LED
Terminal block (spring)Jumped bar x2 terminal blocks4mm²(rigid wire), 2,5mm² (flexible wire)Terminals supplied L1, L2, L3, LS, N, E, BS (loo-ping possible with one additional cable gland)
Cable entriesThree entries M20 For non- armoured cable: included two M20 nylon plugs (EX-M20) and one M20 nylon cable gland, diameter 6-12mm (EXCGM20S)For armoured cable: included continuity plate - two M20 nylon plugs (EX-M20) and one M20 nickel plated brass cable gland, diameter 6-12/ 8,5-16mm (EXN04MMC1)
HousingFiberglass reinforced polyester housing for high impact strength, UV protected polycarbo-nate diffuser to resist harsh environments,2 x M8 Stainless steel 316L insertPainted steel geartray
Fixing (included)V015 - 2x Two zinc-plated steel brackets for ceiling mounting
Electrical Features
Switch between BS terminals
Switch between LS/L1 - Non Maintained Mode Battery charge - dailyEmergency lamp during 1min - weeklyBattery charge capacity during 1hr - quaterlyClear system test displayBattery charge monitored by 2 LED
EVS EM A terminals wiring diagram
1
0
1
0
1
0
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsBs Bs NN
E L3 EL2L1L1LsLsBs Bs NN
EVS EM A terminals wiring diagram
1
0
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
EVS EM A terminals wiring diagram
1
0
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
EVS EM A terminals wiring diagram
1
0
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
EVS EM A terminals wiring diagram
Closed loop option
Switched option
Switched option
E L3 EL2L1L1LsLsNN
E L3 EL2L1L1LsLsNNBs Bs
Bs Bs
1
0
Mains supply Tube Battery
ON Lit Disconnected - not charged
OFF OFF Disconnected - not charged
Healthy(test OK)
Emergency or Indicator
Lamp Fault(must bereplaced)
Test inProgress
(waiting endof test)
Fault(replacebattery)
Emergency function diagrams Preventive maintenance mode
Emergency function diagram - Blackstart mode
Wiring provided by DTS - Maintained Mode
The EMA product contains 2 blackstart terminals. The blackstart mode consists in disconnecting the battery and
so switching off the fitting. This mode is mainly used during maintenance. As soon as the maintenance is done, the
main power ON and the blackstart terminals connected, the emergency fitting is ready to be used as the battery is not
discharged.
This table corresponds to the position 0 “open”.If the switch is on position 1 “close”, please refer to the above tables.
ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15 3/19
3
Linear fittingsAccessoriesEVN - Zones 2 & 22
Lamps
Bi-pin T8 fluorescent lamps
Mounting bracket clip
Type Specifications
V014 2x Rapid ceiling mounting with stainless steel clip
ø920 30
60¡maxi
30
2
10070
2 x ø9
ø36ø20
M 8
18
,60
25
M8
100
41ø9
~70α
25 ø9
25160200
2 Ø 8.5
Fixing Accessories
Hinged bracket
Type Specifications
V023 2x Steel hinged brackets plastic coated
ø920 30
60¡maxi
30
2
10070
2 x ø9
ø36ø20
M 8
18
,60
25
M8
100
41ø9
~70α
25 ø9
25160200
2 Ø 8.5
Hook
Type Specifications
V024 2x Zinc plated steel ceiling suspension hook
20
M
Fixing bracket and flange
Type Specifications
V018 2x zinc plated steel pole mounted brackets for ø1”¼ & 1”½
V019 2x zinc plated steel pole mounted brackets for ø2”
V021 2x Stainless steel 316L pole mounted brackets for ø1”¼ & 1”½
V022 2x Stainless steel 316L pole mounted brackets ø2”
ø920 30
60¡maxi
30
2
10070
2 x ø9
ø36ø20
M 8
18
,60
25
M8
100
41ø9
~70α
25 ø9
25160200
2 Ø 8.5
Brackets
Type Specifications
V015 2 x pair of zinc plated steel for ceiling mounting (Included with product)
V016 2 x stainless steel 316L brackets for ceiling mounting
ø920 30
60¡maxi
30
2
10070
2 x ø9
ø36ø20
M 8
18,60
25
M8
100
41ø9
~70α
25 ø9
25160200
2 Ø 8.5
Type Power W Lumen output lm Lampholder
TL18W 18 1250 G13
TL36W 36 3350 G13
TL58W 58 5200 G13
Specifications:
G13 - ø 26mm
Colour temperature: White industry 4000°K
CRI: > 80
lm/W: 65 to 93
Average operating life: 12,000 hours
3/20 ABB DTS - Light fittings, boxes & custom built control panels for hazardous areas | LIT-140 UK 01/15
3
Linear fittingsSpare partsEVN - Zones 2 & 22
V001
V004
V008N
12
H
G
F
E
D
C
B
A
J
K
L
M
N
P
Q
R
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
1110987654321 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
EVD 140 - 240 (toutes config.)MASSE:
A0
FEUILLE 1 SUR 1ECHELLE:1:5
No. DE PLAN
TITRE:
REVISIONNE PAS CHANGER L'ECHELLE
MATERIAU:
DATESIGNATURENOM
CASSER LESANGLES VIFS
FINITION:SAUF INDICATION CONTRAIRE:LES COTES SONT EN MILLIMETRESETAT DE SURFACE:TOLERANCES: LINEAIRES: ANGULAIRES:
QUAL.
FAB.
APPR.
VERIF.
AUTEUR
Type Specifications
V00120W 20W diffuser with gasket for EV. range
V00140W 40W diffuser with gasket for EV. range
V00165W 65W diffuser with gasket for EV. range
V0041X20WE Gear tray 1X18W with electronic ballast 110-260V 50-60Hz for EVN120
V0041X40WE Gear tray 1X36W with electronic ballast 110-260V 50-60Hz for EVN140
V0041X65WE Gear tray 1X58W with electronic ballast 110-260V 50-60Hz for EVN165
V0042X20WE Gear tray 2X18W with electronic ballast 110-260V 50-60Hz for EVN220
V0042X40WE Gear tray 2x36W with electronic ballast 220- 240V 50-60Hz for EVN240
V0042X65WE Gear tray 2x58W with electronic ballast 220- 240V 50-60Hz for EVN265
V0041X20WEM Emergency gear tray 1x18W with electronic ballast 220-240V 50-60Hz for EVN120EM
V0041X40WEM Emergency gear tray 1x36W with electronic ballast 220-240V 50-60Hz for EVN140EM
V0041X65WEM Emergency gear tray 1x58W with electronic ballast 220-240V 50-60Hz for EVN165EM
V0042X20WEM Emergency gear tray 2x18W with electronic ballast 220-240V 50-60Hz for EVN220EM
V0042X40WEM Emergency gear tray 2x36W with electronic ballast 220-240V 50-60Hz for EVN240EM
V0042X65WEM Emergency gear tray 2x58W with electronic ballast 220-240V 50-60Hz for EVN265EM
V0041X20WEMA Emergency gear tray + auto test 1X18W with electronic ballast 220-240V 50-60Hz for EVN120EMA
V0041X40WEMA Emergency gear tray + auto test 1X36W with electronic ballast 220-240V 50-60Hz for EVN140EMA
V0042X20WEMA Emergency gear tray + auto test 2X18W with electronic ballast 220-240V 50-60Hz for EVN220EMA
V0042X40WEMA Emergency gear tray + auto test 2X36W with electronic ballast 220-240V 50-60Hz for EVN240EMA
V008N Bi-pin G13 lampholder
V02520x40W Brass continuity plate for EV. 120, EV. 220, EV. 140, EV. 240
V02565W Brass continuity plate for EV. 165, EV. 265
EXCGM20S-01 Kit M20 Exe IIC nylon cable gland for non armoured cable diameter 6-12,0 and locknut
EXN04MMC1-01 Kit M20 Ex-d IIC Ex-e II Ex-td double compression nickel plated cable gland for armoured cable diameter inner 6-12 outer 8,5-16, locknut, sealing gasket
Spare parts