load capacities of threaded hanger rods are indicated in the table below
DESCRIPTION
load for hanger rodTRANSCRIPT
Load capacities of threaded hanger rods are indicated in the table below:Nominal Rod Diameter(inches)Root Area of Thread(in2)Maximum Load 1)
(lbs)(kg)
3/80.07600270
1/20.131100500
5/80.201800820
3/40.3027001220
7/80.4238001720
10.5549002220
1 1/80.6962002810
1 1/40.8980003630
1 1/21.29116005260
1 3/41.74147006670
22.30207009390
2 1/43.022720012340
2 1/23.723350015200
35.625060022960
3 1/46.726050027440
3 1/27.927130032340
410.69540043270
4 1/213.712300055780
517.215400069900
1) The maximum loads in the table above are based on allowable tensile stress of 12 kpsi - reduced by 25% to 9 kpsi allowable stress.Note that hangers supporting steam, water, air or gas piping systems should be able to carry the weight of piping, insulation, valves and other equipment - and water for hydrostatic pressure testing - without exceeding 80% of the supporting hangers yield strength (not exceeding 16 kpsi for steel of unknown properties)