Page 1: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

LoadCentre KQ+Distribution boards

Simply safer

SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:15 pm Page 1

Page 2: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

Square D - The right connection

Square D – Serving Your NeedsTo help electrical contractors Square D provide:■ An extensive range of easy to install products.

■ Readily available products from our national network of authorised distributors.

■ Distributor staff training to help develop product knowledge and the ability to promptly resolve queries.

■ A team of sales engineers to support distributors and electrical contractors.

■ A ready assembled product service for applications requiring either non-standard products or completely assembled products to reduce site installation time.

SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2

Page 3: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

LoadCentre KQ+ product selectorKQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories

Standard A boards No. SP ways

KQ125A6 6KQ125A8 8KQ125A12 12KQ125A16 16KQ125A24 24

Split load A boards No. SP ways

KQ125A4SL6 4+6KQ125A5SL5 5+5KQ125A4SL8 4+8KQ125A6SL6 6+6

For A type distribution boardsKQK Barrel lock and 2 keysSQODNBP Blanking plate (5 poles)QOEPLA MCB padlock attachmentQOPL Padlock for QOEPLAKQ6SPFK 6 way A board flush kitKQ8SPFK 8 way A board flush kitKQ12SPFK 12 way A board flush kitKQ16SPFK 16 way A board flush kitKQ24SPFK 24 way A board flush kitKQAE16 DIN rail extension enclosureKQ1100L 1P outgoing terminal blockKQDC Replacement door catch

125A Standard No. TPB boards waysKQ125B12 4KQ125B18 6KQ125B24 8KQ125B36 12KQ125B48 16KQ125B54 18KQ125B72 24

125A Split load No. TPB boards waysKQ125B24SL12 8+4KQ125B18SL18 6+6KQ125B12SL24 4+8

125A Extra service No. TPB boards waysKQ125B24ES 8+13 modsKQ125B36ES 12+13 mods

125A B board incoming devicesKQ125L4 125A 4P term blockKQ125SW3L 125A 3P+N switch discKQ124SW4 125A 4P switch discRSD80034 80A 30mARSD100034 100A 30mARSD100304 100A 300mARSD100304S 100A 300mA TD

250A Standard No. TPB boards waysKQ250B12 4KQ250B18 6KQ250B24 8KQ250B36 12KQ250B48 16KQ250B54 18KQ250B72 24

250A Extra service No. TPB boards waysKQ250B24ES 8+13 modsKQ250B36ES 12+13 mods

250A B board incoming devicesKQ250L4P 250A 4P term blockKQ160SW3L 160A 3P+N switch discKQ200SW3L 200A 3P+N switch discKQ250SW3L 250A 3P+N switch discKQ160SW4 160A 4P switch discKQ200SW4 200A 4P switch discKQ250SW4 250A 4P switch discKQ160MCCB3L 160A 3P+N MCCBKQ200MCCB3L 200A 3P+N MCCBKQ250MCCB3L 250A 3P+N MCCBKQ250MCCB3L 250A 3P+N MCCBKQ160RCD 160A 4P RCCB

For B type distribution boardsQOJ Joining kitKQDBL Barrel lock and 2 keysW29370 MCCB padlock attachmentW29242 MCCB <= 95mm2 cable

clamps x 3W29259 MCCB <= 185mm2 cable

clamps x 3KQ125SPP Single phasing kit for

125A boardsKQ250SPP Single phasing kit for

250A boardsSQODNBP Blanking plate (5 poles)QOEPLA Padlocking attachmentQOPL PadlockWALLET Circuit directory and walletKQ4TPFK Flush kit for 450mm

enclosuresKQ5TPFK Flush kit for 540mm

enclosuresKQ6TPFK Flush kit for 675mm

enclosuresKQ8TPFK Flush kit for 810mm

enclosuresKQ10TPFK Flush kit for 1080mm

enclosuresKQAE16 DIN rail extension boxKQ1100L Single pole outgoing lug unitKQSGPKO Spare gland plate

with knockoutsKQSGPKO Spare gland plate (plain)KQSEB12T Spare/clean earth 12

terminalsKQSEB24T Spare/clean earth 24

terminals

Main incomers for A type boardsKQ125L2 125A 2P term blockKQ125SW2 125A 2P switch discRSD63032 63A 30mA RCCBRSD63102 63A 100mA RCCBRSD63302 63A 300mA RCCBRSD100032 100A 30mA RCCBRSD100102 100A 100mA RCCB

Plug-On secondary RCCB for split load A boardsSQOE063030 63A 30mASQOE063100 63A 100mASQOE100030 100A 30mASQOE100100 100A100mASQOE100100S 100A 100mA TDSQOE100300 100A 300mA

KQ125SW3L KQ6TPFKKQ125B12

SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 3

Page 4: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

KQ+ MCB's (10kA) KQ+ RCBO's (10kA) DIN mounted control products

B curve1 poleKQ10B103 3AKQ10B106 6AKQ10B110 10AKQ10B116 16AKQ10B120 20AKQ10B125 25AKQ10B132 32AKQ10B140 40AKQ10B150 50AKQ10B163 63A

C curve1 pole 2 pole 3 poleKQ10C106 KQ10C206 KQ10C306 6AKQ10C110 KQ10C210 KQ10C310 10AKQ10C116 KQ10C216 KQ10C316 16AKQ10C120 KQ10C220 KQ10C320 20AKQ10C125 KQ10C225 KQ10C325 25AKQ10C132 KQ10C232 KQ10C332 32AKQ10C140 KQ10C240 KQ10C340 40AKQ10C150 KQ10C250 KQ10C350 50AKQ10C163 KQ10C263 KQ10C363 63A

D curve1 pole 2 pole 3 poleKQ10D106 KQ10D206 KQ10D306 6AKQ10D110 KQ10D210 KQ10D310 10AKQ10D116 KQ10D216 KQ10D316 16AKQ10D120 KQ10D220 KQ10D320 20AKQ10D125 KQ10D225 KQ10D325 25AKQ10D132 KQ10D232 KQ10D332 32AKQ10D140 KQ10D240 KQ10D340 40AKQ10D150 KQ10D250 KQ10D350 50AKQ10D163 KQ10D263 KQ10D363 63A

CCN225 2P 25A contactorCCN240 2P 40A contactorCCN340 3P 40A contactorCCN363 3P 63A contactorCCN425 4P 25A contactorCCN440 4P 40A contactorCCN4100 4P 100A contactorCEM01 Multi function meterCPD360 Presence detectorCPIR PIR detectorCPT9 Multi function time switchCPT9MC Memory cartridge

for CPT9CPT11 1c 7 day electronic

time switchCPT21 2c 7 day electronic

time switchCRT1 Room thermostatCSA115 1P+N surge arrestor 15kACSA140 1P+N surge arrestor 40kACSA315 3P+N surge arrestor 15kACSA340 3P+N surge arrestor 40kACSA15C 15kA surge arrestor

cartridgeCSA40C 40kA surge arrestor

cartridgeCSANC Surge arrestor neutral

cartridgeCTR1 Time delay ON relayCTS24 1ch 24hr time switchCIR116 1P 16A impulse relayCIR216 2P 16A impulse relayCCR110 1P 10A changeover relayCDT116 1P 16A stair case timerCBL8 8V AC bellCBX8 240-8V bell transformerCBZ8 8V AC buzzerCLS110 1P 10A light sensitive

switchF27062 1/2 mod spacerKQ10C380 MCB 3P 80A TypeCKQ10C3100 MCB 3P 100A TypeC

10mA (230/240V)KQE106C01 6AKQE110C01 10AKQE116C01 16AKQE120C01 20AKQE132C01 32AKQE145C01 45A

30mA (230/240V)KQE106C03 6AKQE110C03 10AKQE116C03 16AKQE120C03 20AKQE132C03 32AKQE145C03 45A

100mA (230/240V)KQE106C10 6AKQE110C10 10AKQE116C10 16AKQE120C10 20AKQE132C10 32AKQE145C10 45A

KQ10B106 KQE132C03 CCN340

SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 4

Page 5: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

ContentsSection 1 – LoadCentre KQ+ distribution boards

■ LoadCentre KQ+ Single phase A type distribution boards - 125A.

■ LoadCentre KQ+ Single phase A type distribution board incoming devicesand accessories.

■ LoadCentre KQ+ Three phase B type distribution boards - 125A.

■ LoadCentre KQ+ Three phase B type distribution board incomers - 125A.

■ LoadCentre KQ+ Three phase B type distribution boards - 250A.

■ LoadCentre KQ+ Three phase B type distribution board incomers - 160A,200A and 250A.

Page

10

Section 2 – LoadCentre KQ+ circuit protection devices

■ LoadCentre KQ+ Miniature circuit breakers.

■ LoadCentre KQ+ Residual Current Circuit Breakers with integral overcurrent protection (RCBO’s).

■ LoadCentre KQ+ DIN rail mounted control and command devices.

■ Residual Current Circuit Breakers and DIN rail enclosures.

18Section 3 - LoadCentre KQ+ extension enclosures & interiors

■ LoadCentre KQ+ Interiors & cover assemblies.

■ LoadCentre KQ+ enclosures. 24Section 4 - Technical data

■ KQ+ MCB discrimination and cascading.

■ KQ+ MCB temperature derating.

■ KQ+ circuit breaker ratings for infrequent start motor loads.

■ Protection of lamp circuits.

■ Control and command devices - operational information.

28Section 5 – Dimensional information

■ LoadCentre KQ+ distribution boards.

■ LoadCentre KQ+ cover assemblies & interiors. 38Section 6 – Standard Plus

■ Fully assembled and custom built distribution, panel and switchboards. 44Section 7 – Other Square D products

■ Qwikline II consumer units, Twinbreak & Quadbreak fusegear, I-Line panelboards and Clearstart control gear. 48

Section 8 – Index

■ Alphanumeric part number index. 52

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:15 pm Page 6

Page 6: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

7

Easy Installation■ Even faster plug on system for MCB’s and

RCBO’s. 50% fewer connections to make.

■ A new integral cable way is provided forcontrol cables, making installation easier.

■ A new split earth and neutral bar designmeans all terminals are easily accessiblefrom either side of the distribution board.

■ Common enclosure sizes and a range ofextension boxes simplify group mounting ofboards.

■ Removable gland plates (one plain and onewith knockouts) provide quick and safecable entry.

LoadCentre KQ+ Distribution boards - benefits

Safety■ IP2X factory fitted busbar assembly with non removable

insulating barriers, provide protection against accidental direct contact. This is particularly useful if work such as testing and commissioning is required on an energised enclosure.

■ Neutral terminal bar cover provides additional shielding of liveparts. This is secured by screw fixing to prevent accidental disturbance in order to maintain safety levels.

■ Distribution boards and devices are 3rd party type tested to 20kA (MCCB incomer), to BS EN 60439.

High Performance■ Two frame sizes - 125A B boards and 250A B boards with up to

72 outgoing SP ways. LoadCentre KQ+ is designed to cater for the most demanding of installations.

■ Boards accept 10kA MCB’s and RCBO’s.

■ 20kA conditional short circuit rating.

■ Range of three and four pole incoming devices.

■ 25mm2 earth and neutral terminals as standard.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:15 pm Page 7

Page 7: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

8

LoadCentre KQ+ Distribution boards - benefits

Easy Installation - continued■ Improved symmetrical layout and increased enclosure size

provides more wiring space, avoids cable bunching.

■ Incoming devices are an integral feature of all distribution boards. No extension boxes, joining kits or special tools are needed to fitincoming devices.

■ A new modified standards design and production facility meansSquare D can now engineer bespoke products to meet your specificneeds. Typical applications so far have included: boards to meet theexact colour scheme of the buildings interior or a customers corporateimage, new combinations of split load consumer units and distributionboards with enclosure dimensions to accommodate electrical cupboards with restricted access.

■ A new improved incomer design means the time taken to fit incomingdevices is reduced by up to 70%.

Extensive Choice ■ Over 500 distribution board and incomer combinations to choose from.

■ Standard distribution boards, with high flexibility.

■ Split load distribution boards. These are ideal for applications requiringtwo types of earth fault protection from one supply.

Versatility■ Interchangeable incoming devices can

easily be upgraded to meet the changingneeds of an application.

■ Control devices such as contactors, timeclocks and impulse relays can be mountedin any unused outgoing way.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:15 pm Page 8

Page 8: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

9

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:15 pm Page 9

Page 9: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

10

Section 1Page

11Standard 125A SP&N boards Split load 125A A type boards

12Standard SP&N incoming devicesSplit load SP&N incoming devicesSP&N flush mounting kitsSP&N accessories

13Standard 125A TP&N B boardsSplit load 125A TP&N B boardsExtra service 125A TP&N B boards

1480 - 125A TP&N incoming devicesTP&N type B flush mounting kitsTP&N type B accessories

15Standard TP&N B boards: 250AExtra service TP&N B boards: 250A

16160A, 200A, 250A, TP&N type B incoming devicesTP&N type B flush mounting kitsTP&N type B accessories

LoadCentre KQ+ distribution boards

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:15 pm Page 10

Page 10: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

11

LoadCentre KQ+ Single phase A type distribution boards - 125A

KQ125A6 6 270 266 127 KQ6SPFKKQ125A8 8 270 321 127 KQ8SPFKKQ125A12 12 270 376 127 KQ12SPFKKQ125A16 16 270 456 127 KQ16SPFKKQ125A24 24 500 376 127 KQ24SPFK

Notes* 2 incoming devices required for split load units. e.g. Switch and RCCB’s.Secondary incomer is a plug on device - see opposite page. All devices are supplied separately.

Standard type (excluding incomers)

■ Manufactured and tested to BS EN 60439parts 1 and 3.

■ Maximum busbar rating 125A.

■ Voltage rating 230/240V AC.

■ External IP3X protection to BS EN 60529.

■ Internal IP2XB protection to BS EN 60529provided by permanent, non removable, factory fitted barriers.

■ Shielded neutral bars.

■ Cable knockouts on all sides for speed ofinstallation.

■ Removable pan assembly for easier drillingand fixing

■ Earth bar capacity 25mm2.

■ Neutral bar capacity 25mm2.

■ Wide range of bolt on incomers, Plug-On outgoers.

■ All A boards accept DIN control products eg. contactors, time clocks, in any unusedoutgoing way without adaptation.

■ Flush mounting option.

Split load boards are designed for use with earth protection devices (RCD’s) on the secondary sideand provide the user added protection against earth leakage while maintaining continuity of supplyon the primary side.

Reference No. of SP Dimensions mm Compatibleno. ways Height Width Depth Flush kit

KQ125A4SL6 4 6 270 376 127 KQ12SPFKKQ125A5SL5 5 5 270 376 127 KQ12SPFKKQ125A4SL8 4 8 270 456 127 KQ16SPFKKQ125A6SL6 6 6 270 456 127 KQ16SPFK

Split Load type* (excluding incomers)Reference No. of ways Dimensions mm Compatibleno. Unprotected SP Protected RCD Height Width Depth Flush kit

KQ125A6SL6*

KQ125A6

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:16 pm Page 11

Page 11: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

12

LoadCentre KQ+ Single phase A type distribution boardincoming devices and accessories

KQ125L2 Terminal block 125A 2 - 50KQ125SW2 Switch disconnector 125A 2 BS EN 60947-3 50RSD63032 RCCB 63A, 30mA 2 BS EN 61008 35RSD63102 RCCB 63A, 100mA 2 BS EN 61008 35RSD63302 RCCB 63A, 300mA 2 BS EN 61008 35RSD100032 RCCB 100A, 30mA 2 BS EN 61008 50RSD100102 RCCB 100A, 100mA 2 BS EN 61008 50

Type A LoadCentre KQ+ DIN incoming devicesReference Device type Current No. of Standard Cableno. rating poles approval capacity mm2

SQOE063030 RCCB 63A 30mA 2 BS EN 61008 35SQOE063100 RCCB 63A 100mA 2 BS EN 61008 35SQOE100030 RCCB 100A 30mA 2 BS EN 61008 50SQOE100100S RCCB 100A 100mA TD 2 BS EN 61008 50SQOE100100 RCCB 100A 100mA 2 BS EN 61008 50SQOE100300 RCCB 100A 300mA 2 BS EN 61008 50

Plug on RCCB secondary incomers for split load A boardsReference Device type Current No. of Standard Cableno. rating poles approval capacity mm2

KQK Barrel lock & 2 keys new square door catchKQDBL Barrel lock & 2 keys old round door catchSQODNBP Blanking plate (5 poles)QOEPLA MCB padlock attachment (pack of 5)QOPL Padlock for use with QOEPLAKQ6SPFK 6 way A board flush kitKQ8SPFK 8 way A board flush kitKQ12SPFK 12 way A board flush kitKQ16SPFK 16 way A board flush kitKQ24SPFK 24 way A board flush kitKQAE16 A type din rail extension enclosure (16 SP ways available)KQ1100L 100A lug unit single poleKQDC Replacement door catch

125A A board accessoriesReference Device typeno.

NoteFor a wider range of RCD incomers see the RSD range on page 22

KQ125L2 KQ125SW2 RSD10032

SQOE63100

KQ6SPFK

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:16 pm Page 12

Page 12: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

13

LoadCentre KQ+ Three phase B type distribution boards - 125A

KQ125B12 4 450 456 127 KQ4TPFKKQ125B18 6 540 456 127 KQ5TPFKKQ125B24 8 675 456 127 KQ6TPFKKQ125B36 12 675 456 127 KQ6TPFKKQ125B48 16 810 456 127 KQ8TPFKKQ125B54 18 1080 456 127 KQ10TPFKKQ125B72 24 1080 456 127 KQ10TPFK

Standard type (excluding incomers)

■ Manufactured and tested to BS EN 60439parts 1 and 3.

■ Maximum busbar rating 125A.

■ Voltage Rating 400/415V AC.

■ External IP3X protection to BS EN 60529.

■ Internal IP2XB protection to BS EN 60529,provided by permanent, non removable, factory fitted barriers.

■ Fully shielded neutral bars.

■ Earth and neutral bar cable capacity 25mm2.

■ All incoming devices fit integral to the board,no extension boxes required.

■ All incoming connections are the samelength ie. 4 pole configuration.

■ Range of integral incomers for all applications including lugs, switches andRCD’s.

■ Outgoing MCB's available up to 63A B, C orD curves.

■ 18mm RCBO available, minimising use ofoutgoing ways.

■ Plug On outgoers for speed of installationand guaranteed connection.

■ All B boards accept DIN control products(timers, contactors) in any unused outgoingway without adaptation.

■ New control wiring cable way provided.

Reference No. of TP Dimensions mm Compatibleno. ways Height Width Depth Flush kit

Notes2 incoming devices required for split load units e.g. switch and RCD or 2 x RCD's

KQ125B24SL12 8 4 810 456 127 KQ8TPFKKQ125B18SL18 6 6 810 456 127 KQ8TPFKKQ125B12SL24 4 8 810 456 127 KQ8TPFK

Split load type (excluding incomer) Reference No. of ways Dimensions mm Compatibleno. Unprotected TP Protected RCD Height Width Depth Flush kit

NotesExtra service distribution boards are specifically designed for applicationsusing numerous control products and MCB’s and RCBO’s, these dedicatedunits eliminate the need for extension boxes, speed up and economiseinstallations,while automatically providing a professional finish.The dedicated DIN space will accommodate up to 235 mm (thirteen 18mm modules) of control products.

KQ125B24ES 8 13 675 456 127 KQ6TPFKKQ125B36ES 12 13 810 456 127 KQ8TPFK

Extra service units (excluding incomer) B board with dedicated top extension box for control products

Reference No. of 18mm Dimensions mm Compatibleno. ways modules Height Width Depth Flush kit

KQ125B12

KQ125B12SL24

KQ125B24ES

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:16 pm Page 13

Page 13: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

KQK Barrel lock & 2 keys for new square door catchKQK33 Spare keys for aboveKQDBL Barrel lock & 2 keys for old round door catchQOJ Joining kit (mechanical)W29370 MCCB locking attachmentKQ125SPP 125A single phasing kit for use with RCD & switch incomersSQODNBP Blanking plate (5 poles)QOEPLA MCB padlock attachment (pack of 5)QOPL Padlock for use with QOEPLAWALLET Circuit directory & wallet (pack of 10)KQ4TPFK Flush kit for 450mm enclosuresKQ5TPFK Flush kit for 540mm enclosuresKQ6TPFK Flush kit for 675mm enclosuresKQ8TPFK Flush kit for 810mm enclosuresKQ10TPFK Flush kit for 1080mm enclosuresKQAE16 A type 16 way extension enclosure DIN rail onlyKQ1100L 100A lug unit single poleKQSGPKO Spare gland plate with knockoutsKQSGP Spare gland plateKQSEB12T Spare/clean earth 12 terminalsKQSEB24T Spare/clean earth 24 terminalsKQ72BL Spare way label 72 ways

14

LoadCentre KQ+ Three phase B type distribution boards - 125A

KQ125L4 Terminal block 125A 4 – 50KQ125SW4 Switch disconnector 125A 4 BS EN 60947-3 50KQ125SW3L Switch disconnector 125A 3+N lug BS EN 60947-3 50RSD80034 RCCB 80A 30mA 4 BS EN 61008 35RSD100304 RCCB 100A 300mA 4 BS EN 61008 50RSD100304S RCCB 100A 300mA TD 4 BS EN 61008 50

125A type B LoadCentre KQ+ incoming devicesReference Device type Current No. of Standard Cableno. rating poles approval capacity mm2

NoteFor a wider range of RCD incomers see the RSD range on page 22

B board accessoriesReference Device typeno.

Description Multi function metering kit for KQ+ 3 phase B type distribution boardsFunction This metering kit is designed to be field installable to any Square D

LoadCentre KQ+ B type distribution board allowing the contractor to provide a full metering facility without the need to purchase a special bespoke board. One kit for all ratings.

Format This kit comprises an extension box to be fixed to the bottom of the KQ+ distribution board. All fixings are supplied. All components except three single pole MCB’s are supplied fully fitted and wired. The MCB’s are supplied but require to be fitted on the distribution stack and connected to prepared tails.

Components CEM01 multi function meterThree current transformersThree single pole MCB’s

Current rating The kit is rated at 250A and is suitable for all ratings of incomerVoltage rating 415V nominal, 455V maximum. 3 phase 4 wire 50-60 HzOutput Pulse output contact is available. Contact rated at 27V 20mA ac or dc.Dimensions Width 456

Height 270Depth 127

Metering kitReference KQMET250no.

KQ125L4

KQ125SW3L

QOJ

CEM01 as fitted to KQMET250

KQ6TPFK

RSD100034

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:17 pm Page 14

Page 14: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

15

LoadCentre KQ+ Three phase B type distribution boards - 250A

KQ250B12 4 810 456 127 KQ8TPFKKQ250B18 6 810 456 127 KQ8TPFKKQ250B24 8 810 456 127 KQ8TPFKKQ250B36 12 1080 456 127 KQ10TPFKKQ250B48 16 1080 456 127 KQ10TPFKKQ250B54 18 1080 456 127 KQ10TPFKKQ250B72 24 1080 456 127 Consult

Square D

Standard type (excluding incomers)

■ Manufactured and tested to BS EN 60439parts 1 & 3.

■ Maximum busbar rating 250A.

■ Voltage Rating 400/415V AC.

■ External IP3X protection to BS EN 60529.

■ Internal IP2XB protection to BS EN 60529,provided by permanent, non removable, factory fitted barriers.

■ Neutral bar shields supplied as standard.

■ Earth and neutral bar cable capacity 25mm2.

■ All incoming devices fit integral to the board,no extension boxes required.

■ Integral incomers for all applications including lugs, switch, MCCB’s and RCD’s.

■ All incoming connections are the samelength ie. 4 pole configuration.

■ Outgoing MCB's available up to 63A B, C or D curves.

■ 18mm RCBO available, maximising use ofoutgoing ways.

■ Plug On outgoers for speed of installationand guaranteed connections.

■ All B boards accept DIN control productstimers, contactors in any unused outgoingway without adaptation.

■ New control wiring cable way provided.

Reference No. of TP Dimensions mm Compatibleno. ways Height Width Depth Flush kit

KQ250B24ES 8 13 1080 456 127 KQ10TPFKKQ250B36ES 12 13 1080 456 127 KQ10TPFK

Extra service units (excluding incomer) B board with integral DIN rail for control products

Reference No. of TP 18mm Dimensions mm Compatibleno. ways modules Height Width Depth Flush kit

NotesExtra Service KQ+ distribution boards are specifically designed for usewhere numerous control products are required adjacent to MCB’s andRCBO’s.These dedicated units eliminate extension boxes and speed up installationand reduce wiring time and cost.They also provide an extremely professional finish to an otherwise complex and potentially untidy application. The dedicated DIN space willaccommodate up to 235mm (thirteen 18mm modules) of control products.

KQ250B12

KQ250B24ES

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:17 pm Page 15

Page 15: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

16

LoadCentre KQ+ Three phase B type distribution board interchangeable incomers - 160A, 200A, 250A

KQ250L4P Terminal block 250A 4 –KQ160SW3L Switch disconnector 160A 3+N BS EN 60947-3KQ200SW3L Switch disconnector 200A 3+N BS EN 60947-3KQ250SW3L Switch disconnector 250A 3+N BS EN 60947-3KQ160SW4 Switch disconnector 160A 4 BS EN 60947-3KQ200SW4 Switch disconnector 200A 4 BS EN 60947-3KQ250SW4 Switch disconnector 250A 4 BS EN 60947-3KQ160MCCB3L MCCB 160A 3+N BS EN 60947-2KQ200MCCB3L MCCB 200A 3+N BS EN 60947-2KQ250MCCB3L MCCB 250A 3+N BS EN 60947-2KQ160RCD RCCB 160A I∆n 30mA -10A 4 BS EN 61008

250A type B LoadCentre incoming devicesReference Device type Current No. of Standardno. rating poles approval

KQ250SPP 250A single phasing kitQOJ Joining kit (mechanical)KQK Barrel lock & 2 keys for new square door catchKQK33 Spare keys for aboveKQDBL Barrel lock & 2 keys for old round door catchW29370 MCCB locking attachmentSQODNBP Blanking plate (5 poles)QOEPLA MCB padlock attachment (pack of 5)QOPL Padlock for use with QOEPLAWALLET Circuit directory & wallet (pack of 10)KQ4TPFK Flush kit for 450mm enclosuresKQ5TPFK Flush kit for 540mm enclosuresKQ6TPFK Flush kit for 675mm enclosuresKQ8TPFK Flush kit for 810mm enclosuresKQ10TPFK Flush kit for 1080mm enclosuresKQAE16 A type 16 way extension enclosure DIN rail onlyKQ1100L 100A lug unit single poleKQSGPKO Spare gland plate with knockoutsKQSGP Spare gland plateKQSEB12T Spare/clean earth 12 terminalsKQSEB24T Spare/clean earth 24 terminalsW29242 MCCB< = 95mm2 cable clamps x 3W29259 MCCB< = 185mm2 cable clamps x 3KQ72BL Spare way label 72 ways

B board accessoriesReference Device typeno.

Connected by

solid conductor

or crimped

cable lug to

maximum

diameter on

stand

L ≤25mmd ≤10mmØ >8mm

KQ250SW4

KQ200MCCB3L

Description Multi function metering kit for KQ+ 3 phase B type distribution boardsFunction This metering kit is designed to be field installable to any Square D

LoadCentre KQ+ B type distribution board allowing the contractor to provide a full metering facility without the need to purchase a special bespoke board. One kit for all ratings.

Format This kit comprises an extension box to be fixed to the bottom of the KQ+distribution board. All fixings are supplied. All components except three single pole MCB’s are supplied fully fitted and wired. The MCB’s are supplied but require to be fitted on the distribution stack and connected to prepared tails.

Components CEM01 multi function meterThree current transformersThree single pole MCB’s

Current rating The kit is rated at 250A and is suitable for all ratings of incomerVoltage rating 415V nominal, 455V maximum. 3 phase 4 wire 50-60 HzOutput Pulse output contact is available. Contact rated at 27V 20mA ac or dc.Dimensions Width 456

Height 450Depth 127

Metering kitReference KQMET250no.

KQMET250

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:17 pm Page 16

Page 16: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

17

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 17

Page 17: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

18

Section 2Page

19Single pole MCB’s Two pole MCB’sThree pole MCB’s

20Single pole RCBO’s 10mASingle pole RCBO’s 30mASingle pole RCBO’s 100mA

21Contactors 2 & 4 pole 25-63A,Time switchesImpulse relays Changeover relays

222 pole RCD’s 25-100A4 pole RCD’s 25-100ADIN enclosures

LoadCentre KQ+ circuit protection devices

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 18

Page 18: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

19

KQ10C240

LoadCentre KQ+ KQ+ miniature circuit breakers (MCB’s)

KQ10B103 - - 3A 25mm2 15A 12AKQ10B106 - - 6A 25mm2 30A 24AKQ10B110 - - 10A 25mm2 50A 40AKQ10B116 - - 16A 25mm2 80A 65AKQ10B120 - - 20A 25mm2 100A 80AKQ10B125 - - 25A 25mm2 125A 105AKQ10B132 - - 32A 35mm2 160A 134AKQ10B140 - - 40A 35mm2 200A 160AKQ10B150 - - 50A 35mm2 250A 200AKQ10B163 - - 63A 35mm2 315A 267A

Type B (magnetic setting 3 - 5 In) For resistive and light reactive loads, e.g. heating, incandescent lighting etc

■ Manufactured and tested to BS EN 60898

■ 10kA breaking capacity.

■ Let through energy classification of 3 (lowestlet through energy best cable protection classification).

■ Positive contact indication. (guaranteedon/off indication).

■ Trip free mechanism operates even whenthe toggle is locked.

■ Lockable in the ON or OFF position.

■ Speed of Connection of plug on devices - 50% fewer connections to make.

■ For use in LoadCentre KQ+ A and B boards.

■ All MCB's have their part number clearlyprinted on the front face for ease of identification.

Reference no. Current Terminal Current required1 pole 2 pole 3 pole rating capacity to disconnect

(Icn*) 0.4s 5s

KQ10C106 KQ10C206 KQ10C306 6A 25mm2 60A 24AKQ10C110 KQ10C210 KQ10C310 10A 25mm2 100A 40AKQ10C116 KQ10C216 KQ10C316 16A 25mm2 160A 65AKQ10C120 KQ10C220 KQ10C320 20A 25mm2 200A 80AKQ10C125 KQ10C225 KQ10C325 25A 25mm2 250A 105AKQ10C132 KQ10C232 KQ10C332 32A 35mm2 320A 134AKQ10C140 KQ10C240 KQ10C340 40A 35mm2 400A 160AKQ10C150 KQ10C250 KQ10C350 50A 35mm2 500A 200AKQ10C163 KQ10C263 KQ10C363 63A 35mm2 630A 267A

Type C (magnetic setting 5 - 10 In) For moderately light reactive loads, e.g. fluorescent lighting

Reference no. Current Terminal Current required1 pole 2 pole 3 pole rating capacity to disconnect

(Icn*) 0.4s 5s

KQ10D106 KQ10D206 KQ10D306 6A 25mm2 84A 24AKQ10D110 KQ10D210 KQ10D310 10A 25mm2 140A 40AKQ10D116 KQ10D216 KQ10D316 16A 25mm2 224A 65AKQ10D120 KQ10D220 KQ10D320 20A 25mm2 280A 80AKQ10D125 KQ10D225 KQ10D325 25A 25mm2 350A 105AKQ10D132 KQ10D232 KQ10D332 32A 35mm2 448A 134AKQ10D140 KQ10D240 KQ10D340 40A 35mm2 560A 160AKQ10D150 KQ10D250 KQ10D350 50A 35mm2 700A 200AKQ10D163 KQ10D263 KQ10D363 63A 35mm2 882A 267A

Type D (magnetic setting 10 - 14 In) For highly reactive loads, e.g. motors, pumps and transformers

Reference no. Current Terminal Current required1 pole 2 pole 3 pole rating capacity to disconnect

(Icn*) 0.4s 5s

NoteBreaking capacity to BS EN 60898 = 10kA (lcn)*lcs = 75% lcn.Breaking capacity to BS EN 60947-2 = 15 kA 1P, 30kA 2&3P (lcu)lcs = 75% lcu.

KQ10B106

KQ10C340

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 19

Page 19: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

20

LoadCentre KQ+ Residual current circuit breakers with integral overcurrent protection (RCBO’s)■ Manufactured and tested to BS EN 61009.

■ 10kA breaking capacity.

■ Let through energy classification of 3 (lowest let through energy best cable protection classification).

■ Positive contact indication (guaranteed on/off indication).

■ Trip free MCB mechanism.

■ Lockable in on or off position.

■ Automatic trip on loss of neutral.

■ Automatic protection against reverse polarity.

■ Type C tripping characteristics (5In to 10In).

■ 6 – 45A; 10, 30 & 100mA sensitivities.

■ AC class sensitivity.

■ For use in LoadCentre A and B boards.

■ One single pole way occupied in a distribution board.

■ Cable capacity 16mm2.

■ Speed of connection of plug on devices.

■ Assured system integrity, no other devices fit KQ+ boards.

■ All RCBO’s have part numbers marked onthe front of device.

ApplicationsRCBO’s are available with various earth leakage sensitivities to suit numerous applications including 10mA devices for protection of sensitive machine/equipment, 30mA devices which are generally used for personnel protection and 100mA deviceswhich provide protection against risk of fire.RCBO’s should be carefully selected for the relevant application.

KQE106C01 6 10mA 16mm2

KQE110C01 10 10mA 16mm2

KQE116C01 16 10mA 16mm2

KQE120C01 20 10mA 16mm2

KQE132C01 32 10mA 16mm2

KQE145C01 45 10mA 16mm2

KQE106C03 6 30mA 16mm2

KQE110C03 10 30mA 16mm2

KQE116C03 16 30mA 16mm2

KQE120C03 20 30mA 16mm2

KQE132C03 32 30mA 16mm2

KQE145C03 45 30mA 16mm2

KQE106C10 6 100mA 16mm2

KQE110C10 10 100mA 16mm2

KQE116C10 16 100mA 16mm2

KQE120C10 20 100mA 16mm2

KQE132C10 32 100mA 16mm2

KQE145C10 45 100mA 16mm2

Residual current circuit breakersReference Current rating Residual tripping Terminalno. (A) current capacity

KQE132C03

KQ125A6

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 20

Page 20: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

21

KQ10C3100 MCB 3P 100A Type C 50 4 1/2KQ10C380 MCB 3P 80A Type C 50 4 1/2

DIN rail mounted 100A MCB Suitable for use in extension enclosures or extra service units

Reference no. Description Terminal Modular ways capacity occupied 17.5mm

LoadCentre KQ+ DIN rail mounted control and command devices

CBL8 Bell 8V ac Audible alarm 1CBX8 Transformer 240/8V 8VA Bell circuits 2CBZ8 Buzzer 8V ac Audible alarm 1CCN225 Contactor 2 pole 25A Switching large single phase loads 1CCN240 Contactor 2 pole 40A Switching large single phase loads 2CCN340 Contactor 3 pole 40A Switching 3 phase loads 3CCN363 Contactor 3 pole 63A Switching 3 phase loads 4CCN4100 Contactor 4 pole 100A Distribution board incomer 6CCN425 Contactor 4 pole 25A Switching 3 phase loads 2CCN440 Contactor 4 pole 40A Switching 3 phase loads 3CCR110 Changeover relay 10A Switching small loads 1CDT116 Delay OFF timer 1-7 min timer for stairs & corridor lighting 1CEM01 Multi function meter Metering KWh 6CIR116 Impulse relay 1 pole 16A Lighting switching 1CIR216 Impulse relay 2 pole 16A Lighting switching 1CLS110 Light sensitive switch Lighting during low light levels 3.5CPD360 Presence detector Detecting persons in the area -CPIR PIR detector Movement detection -CPS9 Contactor spacer Spacing contactors in boards 0.5CPT11 7 day elect. time switch, 1 channel 7 day programmable time switch 2.5CPT21 7 day elect. time switch, 2 channel 7 day programmable time switch 2.5CPLST110 Astronomic time switch Lighting control 2.5CTR1 Time delay ON relay Delay switch on 1CTS24 24 hour time switch 24 hour regular switching 1CPT9 Multi function time switch Time switch with conditional functions 5CPT9MC Memory cartridge for CPT9 - -KQMET250 KQ+ metering kit KQ+ B type distribution boards -RSD4IP54 Insulated enclosure, 4 modules IP54 enclosure with door -SDEN3 Metal enclosure, 3 modules IP30 enclosure, sealable -SDEN4 Metal enclosure, 4 modules IP30 enclosure, sealable -SDEN5 Metal enclosure, 5 modules IP30 enclosure, sealable -SDEN4P Insulated enclosure, 4 modules IP40 enclosure with door -SDEN6P Insulated enclosure, 6 modules IP40 enclosure with door -SDEN8P Insulated enclosure, 8 modules IP40 enclosure with door -

Control and command devicesReference no. Description Application Modular size

All KQ+ A and B type LoadCentres accept DIN railmounted control devices in any unused MCB way

NoteWhen installing several CCN contactors, side by side in an enclosure, include a 1/2 module spacer(CPS9) between every two units. This also applies to adjacent MCB's.

NoteFor further information about control and command products and applications, please refer to theControl and Command Catalogue.

For high density control applications a range of extra serviceboards are available, each one providing 13 module spaces forcontrol products.For stand alone control applications a range of insulated or metalenclosures are available.

CIR116

CCN340

KQ125B24ES

KQ10C3100

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 21

Page 21: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

22

■ Comply with BS EN 61008.Specification for residual current operated circuit breakers.

■ Rated voltage 240/415V AC 50/60 Hz.

■ Test button enables RCCB to be testedperiodically.

■ Suitable for use as supplementary protection on final sub circuits eg. equipment outside equipotentialzone or items requiring 2/4 pole protection i.e.switched neutral applications

RSD25032 25A RCCB 30mA trip 2 pole 35 81 36 75 0.227RSD25302 25A RCCB 300mA trip 2 pole 35 81 36 75 0.227RSD40032 40A RCCB 30mA trip 2 pole 35 81 36 75 0.227RSD40102 40A RCCB 100mA trip 2 pole 35 81 36 75 0.227RSD40302 40A RCCB 300mA trip 2 pole 35 81 36 75 0.227RSD63032 63A RCCB 30mA trip 2 pole 35 81 36 75 0.227RSD63102 63A RCCB 100mA trip 2 pole 35 81 36 75 0.227RSD63302 63A RCCB 300mA trip 2 pole 35 81 36 75 0.227RSD80032 80A RCCB 30mA trip 2 pole 50 81 36 75 0.227RSD100032 100A RCCB 30mA trip 2 pole 50 81 36 75 0.227RSD100102 100A RCCB 100mA trip 2 pole 50 81 36 75 0.227RSD100302 100A RCCB 300mA trip 2 pole 50 81 36 75 0.227RSD25304 25A RCCB 300mA trip 4 pole 35 81 72 75 0.428RSD25034 25A RCCB 30mA trip 4 pole 35 81 72 75 0.428RSD25104 25A RCCB 100mA trip 4 pole 35 81 72 75 0.428RSD40034 40A RCCB 30mA trip 4 pole 35 81 72 75 0.428RSD40104 40A RCCB 100mA trip 4 pole 35 81 72 75 0.428RSD40304 40A RCCB 300mA trip 4 pole 35 81 72 75 0.428RSD63034 63A RCCB 30mA trip 4 pole 35 81 72 75 0.428RSD63104 63A RCCB 100mA trip 4 pole 35 81 72 75 0.428RSD63304 63A RCCB 300mA trip 4 pole 35 81 72 75 0.428RSD80034 80A RCCB 30mA trip 4 pole 35 81 72 75 0.500RSD100304 100A RCCB 300mA trip 4 pole 50 81 72 75 0.500RSD100304S 100A RCCB 300mA trip 4 pole 50 81 72 75 0.500

Residual current circuit breakersReference no. Description Terminal Dimensions mm Weight

capacity Height Width Depth Kgmm

RSD2IP54 2 x 18mm Module IP54 protection 150 50 60 0.1RSD4IP54 4 x 18mm Module IP54 protection 200 110 112 0.35

Individual RCCB insulated enclosuresReference no. Description Dimensions mm Weight

Height Width Depth Kg

All RSD residual current circuit breakers are suitable foruse as main incomers in KQ+ distribution boards

LoadCentre KQ+ Residual current circuit breakers (RCCB’s)and DIN rail mounted enclosures

For short circuit back-up protection, maximum fuse rating:-RSD 25A Fuse to BS88 Type T 40A or BS1361 type RH 30ARSD 40A Fuse to BS88 Type T 50A or BS1361 type RH 40ARSD 63A Fuse to BS88 Type T 63A or BS1361 type RH 60ARSD 80A Fuse to BS88 Type T 80A or BS1361 type RH 80ARSD 100A Fuse to BS88 Type T 100A or BS1361 type RH 100A

RSD insulated enclosures are also suitable forany DIN rail mounted product including timeclocks, timers, contactors, switches andrelays.

RSD80302

RSD80304 RSD4IP54

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:18 pm Page 22

Page 22: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

23

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:19 pm Page 23

Page 23: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

24

Section 3Page

25125A SP interiors125A SP interior cover assemblies125A & 250A TP interiors125A & 250A TP interior cover assemblies

26KQ plain enclosures KQ BLK enclosuresKQ DIN enclosures

LoadCentre KQ+ extension enclosures and interiors

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:19 pm Page 24

Page 24: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

25

NoteAll incoming devices from page 2 are compatible with KQ+ interiors (except plug on SQO type).For compatible MCB’s and RCBO’s see pages 9 and 10.“CD” Cover assemblies include doors and door furniture and are suitable for use as replacements forstandard distribution board covers.

LoadCentre KQ+ Interiors and cover assemblies

KQ125INTA6 KQ125INTCD6 KQ125INTAC6 6 125AKQ125INTA8 KQ125INTCD8 KQ125INTAC8 8 125AKQ125INTA12 KQ125INTCD12 KQ125INTAC12 12 125AKQ125INTA16 KQ125INTCD16 KQ125INTAC16 16 125A

Single phase

■ Manufactured and tested to BS EN 60439parts 3 & BS5486 part 12.

■ Maximum busbar rating 125A.

■ Voltage rating 230/240V SP&N.

■ Internal IP2XB protection to BS EN 60529provided by non removable, factory fittedbarriers.

■ Neutral terminal bar shields.

■ Earth bar capacity 25mm2.

■ Neutral bar capacity 25mm2.

■ Wide range of bolt on incomers, Plug-Onoutgoers.

■ All A type interiors accept control productseg. contactors, time clocks, in any unusedoutgoing way without adaptation.

■ Manufactured and tested to BS EN 60439parts 1 and 3.

■ Maximum busbar rating 125A or 250A.

■ Voltage Rating 400/415V AC.

■ Internal IP2XB protection to BS EN 60529,provided by permanent, factory fitted, non removable barriers.

■ Neutral terminal bar fully shielded.

■ Neutral bar cable capacity 25mm2.

■ All TP&N interiors accept control products(timers, contactors) in any unused outgoingway without adaptation.

■ Includes earth terminal bars.

Reference no. Door & cover Cover No. of RatingInterior assembly assembly SP ways

NoteAll incoming devices from page 4 are compatible with KQ+ TP&N 125A interiors.For compatible MCB’s and RCBO’s see pages 9 & 10Cover assemblies are also suitable for use as replacements for standard distribution board covers.

KQ125TBP12 KQ125BCP12 4 KQ250TBP12 KQ250BCP12KQ125TBP18 KQ125BCP18 6 KQ250TBP18 KQ250BCP18KQ125TBP24 KQ125BCP24 8 KQ250TBP24 KQ250BCP24KQ125TBP36 KQ125BCP36 12 KQ250TBP36 KQ250BCP36KQ125TBP48 KQ125BCP48 16 KQ250TBP48 KQ250BCP48KQ125TBP54 KQ125BCP54 18 KQ250TBP54 KQ250BCP54KQ125TBP72 KQ125BCP72 24 KQ250TBP72 KQ250BCP72

Three phase 125AReference no. No. ofInterior Cover assembly TP ways Interior Cover assembly*

Three phase 250A

* BCP type pan assemblies are not suitable for use with distribution boards and interiors manufactured prior to May 2002. Consult Square D for further details.

KQ125INTA6

KQ125INTAC6

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:19 pm Page 25

Page 25: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

26

LoadCentre KQ+ Extension enclosuresKQ+ enclosures are available for applications wherematching extension boxes are required to house systemextensions or stand alone control systems.There are three configurations, plain enclosures, plainenclosures with door, enclosures with two, three or fourrows of DIN rail, door and front cover assembly.

KQBLK12 450 456 127KQBLK18 540 456 127KQBLK2436 675 456 127KQBLK4854 810 456 127KQBLK25054 1080 456 127

Steel enclosures with plain coverReference Dimensions mmno. Height Width Depth

KQBLK12D 450 456 127KQBLK18D 540 456 127KQBLK2436D 675 456 127KQBLK4854D 810 456 127KQBLK25054D 1080 456 127

Steel enclosures with plain cover & doorReference Dimensions mmno. Height Width Depth

KQDA12 450 456 127 2 36KQDA18 540 456 127 2 36KQDA2436 675 456 127 3 54KQDA4854 810 456 127 4 72KQDA25054 1080 456 127 4 72

Steel enclosures with 2 or 3 rows of DIN rails and a front cover assembly and doorReference Dimensions mm No. of Total no. ofno. Height Width Depth rows SP modules

NotesKQ+ enclosures can be joined to KQ+ TP&N distribution boards by using the QOJ joining kit.

Group mounting of distribution boards and extension enclosures.Self assembly or ready assembled.

KQBLK12

KQBLK12D

KQDA12

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:20 pm Page 26

Page 26: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

27

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:20 pm Page 27

Page 27: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

28

Section 4Page

29KQ+ MCB discrimination and cascading tables

30KQ+ MCB service currents and temperature derating tables

31 & 32KQ+ MCB ratings for motor applications

33 & 34KQ+ MCB lighting applications

35 & 36Control and command devicesOperational information

LoadCentre KQ+ technical data

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:20 pm Page 28

Page 28: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

29

LoadCentre KQ+ MCB discrimination and cascading

Ref CD CN CN CH CHRating 100A 100A 250A 100A 250A

Ref Rating Icu 25kA 36kA 36kA 50kA 50kASQO/KQ 63A 6 & 10kA 25 25 30 40 30

Cascading chartDownstream Upstreambreaker breaker

(A2 s/1000)≤6 4 7 9 10 1110 6 12 17 19 2416 7 16 23 30 37.520 7 16 23 30 37.525 7 16 23 30 37.532 10 23 32.5 42.5 5540 10 23 32.5 42.5 5550 13 28 35 55 7063 13 28 35 55 70

KQ+ 1P devices @ 230.240v B, C & D curveRating Fault level (kA)(A) 2 4 6 8 10

Discrimination is the co-ordination of circuitbreakers such that when a fault occurs in a network it is cleared by the breaker immediatelyupstream of the fault. No breaker furtherupstream operates. Thus the number of circuitsaffected by the fault is minimised.

In many cases full discrimination is achieved up to the breaking capacity of the breaker disconnecting the fault. This is indicated by 'F' inthe table below. In other cases discrimination isachieved up to a lesser current as indicatedbelow in amps.

I line CD/CN/CH breaker with Thermal magnetic trip units CN/CH DH SMAL SPAF

16 25 32 40 50 63 80 100 125 160 200 250 160 250 400 630 1000 2000

KQ/SQO=<10 200 300 300 500 500 500 630 800 F F F F F F F F

16 300 300 500 500 500 630 800 F F F F F F F F

20 500 500 630 800 F F F F F F F F

25 500 500 630 800 F F F F F F F F

32 500 630 800 F F F F F F F F

40 500 630 800 F F F F F F F F

50 800 F F F F F F F F

63 800 F F F F F F F F

Downstream Upstream Electronicbreaker breaker breakers

Dis

crim

inat

ion

isac

hiev

ed u

p to

the

Mag

netic

set

ting

of t

heU

pstr

eam

bre

aker

F = Full discrimination

I2t let through values for KQ+ MCB's/RCBO’s

(A2 s/1000)≤6 4 8 8.5 9.5 1010 6 12 16 19 2216 7 15 22 29 3520 7 15 22 29 3525 7 15 22 29 3532 10 21 32.5 35 5040 10 21 32.5 35 5050 12 26 40 55 6863 12 26 40 55 68

KQ+ 2 & 3P devices @ 400.415v C & D curveRating Fault level (kA)(A) 2 4 6 8 10

Square D KQ+ (and SQO) MCB's have an energy let through classification of “3”, this is the highest current limiting classification to BS EN 60898.

Compared with the protection offered by lower performance devices, MCB's having a class of“3” may be used to protect cables having asmaller cross section area. This eases installation and reduces cost.

To provide adequate short circuit protection for a conductor, the I2t value of the MCB shouldalways be less than the K2S2 value of the conductor (as stated in BS7671).

Discrimination

Cascading permits the installation of a circuitbreaker having a breaking capacity lower thanthe prospective at its point of installation. Theupstream breaker, which must have the requiredbreaking capacity, limits the fault current to thatwhich may safely be interrupted by thedownstream breaker.

In the case of a high fault current both breakersmay operate.For example: A KQ+ breaker rated at 10kA maybe used at a point in the network having aprospective fault current of 40kA provided that itis protected by a CH breaker (50kA).

Cascading chart

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:20 pm Page 29

Page 29: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

30

3 3.2 3 2.8 2.6 2.36 6.3 6 5.6 5.2 4.610 10.5 10 9.4 8.6 7.616 16.8 16 15.0 13.8 12.220 21.0 20 18.8 17.2 15.225 26.3 25 23.5 21.5 19.032 33.6 32 30.1 27.5 24.340 42.0 40 37.6 34.4 30.450 52.5 50 46.5 43.0 38.063 66.2 63 58.0 52.9 46.6

Circuit breakers type KQ+KQ+ 2 & 3P devices @ 200.415v C & D curve

Current rating Ambient temperature deg C(A) 20 30 40 50 60

LoadCentre KQ+ Temperature derating

Circuit breakers complying with BS EN 60898 shall be capable of operating under the following standard conditions:

Standard conditions for operation in service

Circuit breakers listed in the service currenttable may be used at temperatures from –30°C to +60°C.

The table indicates the maximum current to beused as a function of the ambient temperature.

Figures in bold type are the nominal current rating at calibrated temperature.

This avoids the necessity to derate for normalambient temperatures likely to be encounteredwhen circuit breakers are grouped together in anenclosure.

Temperature derating of circuit breakers

■ The ambient air temperature does notexceed +40°C and its average over a period of 24 hours does not exceed +35°C.

■ The lower limit of the ambient air temperature is -15°C.

■ Circuit breakers intended to be used in ambient air temperatures above +40°C (particularly in tropical countries) or below -5°C shall either be specially designed or be used according to the information given in the manufacturer’s catalogue.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 4:20 pm Page 30

Page 30: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

31

LoadCentre KQ+ Circuit breaker ratings for infrequent start motor loadsThree phase circuit breaker ratings for infrequent start motor loads

Circuit breakers are not generally intended toprovide close current protection for motors.

Normally they are used in conjunction with arecognised motor over current protective device.

Under these conditions the circuit breaker willprotect the cable to the motor whilst the motorsown protective device will protect the motoritself.

The comparison between full load current andkW rating, is based upon an average efficiencyand power factor for each motor rating.

The circuit breaker ratings used to protect the cable to the motor are based upon DOL starting = Up to 4kW, 7 x full load current for 4.5 seconds 4.1kW to 30kW, 7 x full load current for 6 seconds

Reduced voltage starting = Up to 18.5kW, 3.5 x full load current for 10 seconds 19kW to 30kW, 4 x full load current for 18 seconds

KQ10C306 6 3 1.6 4 1.9KQ10C310 10 5 2.7 6 3.2KQ10C316 16 7 3.3 10 5.1KQ10C320 20 8 4.1 13 6.3KQ10C325 25 10 5.1 16 7.9KQ10C332 32 13 6.5 20 10.1KQ10C340 40 16 8.2 25 12.7KQ10C350 50 20 10.2 32 15.9KQ10C363 63 26 12.9 36 18.0

KQ10D306 6 3 1.6 4 1.9KQ10D310 10 5 2.7 6 3.2KQ10D316 16 7 3.3 10 5.1KQ10D320 20 8 4.1 13 6.3KQ10D325 25 10 5.1 16 7.9KQ10D332 32 13 6.5 20 10.1KQ10D340 40 16 8.2 25 12.7KQ10D350 50 20 10.2 32 15.9KQ10D363 63 26 12.9 36 18.0

Circuit breaker ratings for infrequent start motor loadsReference no. MCB D.O.L. starting Reduced voltage starting

current Full load kW Full load kW rating current @415V AC current @415V AC

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 31

Page 31: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

32

LoadCentre KQ+ Circuit breaker ratings for infrequent start motor loads

DOL starting = Up to 4kW, 7 x full load current for 4.5 seconds 4.1 to 10kW, 7 x full load current for 6 seconds

KQ10C106 6 3 0.3KQ10C110 10 5 0.5KQ10C116 16 7 0.8KQ10C120 20 9 1.0KQ10C125 25 11 1.3KQ10C132 32 15 1.6KQ10C140 40 18 2.0KQ10C150 50 23 2.5KQ10C163 63 29 3.2

KQ10D106 6 3 0.3KQ10D110 10 5 0.5KQ10D116 16 7 0.8KQ10D120 20 9 1.0KQ10D125 25 11 1.3KQ10D132 32 15 1.6KQ10D140 40 18 2.0KQ10D150 50 23 2.5KQ10D163 63 29 3.2

Circuit breaker ratings for infrequent start motor loadsReference no. Current D.O.L. starting

rating Full load kW (A) current @415V AC

Single phase circuit breaker ratings for infrequent start motor loads

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 32

Page 32: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

33

LoadCentre KQ+ Protection of lamp circuitsThe following table gives recommended circuitbreaker ratings for use in circuits with dischargelamps. Ratings are based on the time currentcharacteristic of KQ+ type C and D circuit breakers.

During start up of discharge lamps, surge current may be in the order of:-

25 x circuit start current for the first 3 milliseconds.

7 x circuit start current for the following 2 seconds.

Circuits with long cable runs may reduce theactual inrush current due to voltage drop to alevel which is lower than the maximum of 25 xstart up current.

This could effect the choice of circuit breakerrating used in circuits where the number oflamps exceed 3, a reduced surge current factoris therefore applied.

Consideration must be given to the number oflamp fittings used in each circuit as this mayentail the use of unusually large cable.

Circuits with large numbers of lamp fittings maycause some inconvenience in the event of afault, as due regard for safety in the workingenvironment must be considered in the event ofthe lighting being extinguished.

Low pressure Sodium (SOX) Circuit breaker rating (A)18 0.14 0.15 6 6 6 6 6 6 6 6 6 635 0.22 0.2 6 6 6 6 6 6 6 6 6 650 0.3 0.3 6 6 6 6 6 6 6 6 6 690 0.5 0.3 6 6 6 6 6 6 6 6 6 10135 0.7 0.6 6 6 6 6 6 10 10 10 10 10180 1.0 0.7 6 6 6 6 10 10 10 16 16 16

High pressure Sodium (SON) Circuit breaker rating (A)50 0.3 0.35 6 6 6 6 6 6 6 6 6 670 0.4 0.55 6 6 6 6 6 6 6 6 6 6100 0.52 0.7 6 6 6 6 6 6 10 10 10 10150 0.8 1.0 6 6 6 6 10 10 10 10 10 16250 1.3 1.5 6 6 10 10 16 16 16 16 16 20400 2.15 3.0 6 10 16 16 20 20 25 25 25 321000 5.4 6.0 16 20 32 40 40 50 50 50

Mercury Fluorescent (HPL/MBF) Circuit breaker rating (A)50 0.3 0.32 6 6 6 6 6 6 6 6 6 680 0.4 0.5 6 6 6 6 6 6 6 6 6 6125 0.7 1.1 6 6 6 6 6 6 6 10 10 10250 1.33 2.2 6 6 10 10 10 16 16 16 16 20400 2.2 4.0 6 10 16 16 20 20 20 25 25 321000 5.0 9.0 16 20 32 40 40 50 50 - - -

Type D circuit breaker ratingLamp Circuit current Number of lamps in circuitwattage each lamp(W) run A start A 1 2 3 4 5 6 7 8 9 10

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 33

Page 33: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

34

LoadCentre KQ+ Protection of lamp circuits

Low pressure Sodium (SOX) Circuit breaker rating (A)18 0.14 0.15 6 6 6 6 6 6 6 6 6 635 0.22 0.2 6 6 6 6 6 6 6 6 6 650 0.3 0.3 6 6 6 6 6 6 6 6 6 1090 0.5 0.3 6 6 6 6 6 10 16 16 16 10135 0.7 0.6 6 6 6 10 10 10 16 16 16 16180 1.0 0.7 6 6 10 10 16 16 16 16 16 16High pressure Sodium (SON) Circuit breaker rating (A)50 0.3 0.35 6 6 6 6 6 6 6 6 6 670 0.4 0.55 6 6 6 6 6 6 10 10 10 10100 0.52 0.7 6 6 6 10 10 10 10 10 16 16150 0.8 1.0 6 6 10 10 10 16 16 16 16 16250 1.3 1.5 6 10 16 16 16 20 20 20 25 25400 2.15 3.0 10 16 20 25 25 32 32 32 32 321000 5.4 6.0 16 32 40 50 – – – – – –Mercury Fluorescent (HPL/MBF) Circuit breaker rating (A)50 0.3 0.32 6 6 6 6 6 6 6 6 6 680 0.4 0.5 6 6 6 6 6 6 10 10 10 10125 0.7 1.1 6 6 6 10 10 10 16 16 16 16250 1.33 2.2 6 10 16 16 16 20 20 20 25 25400 2.2 4.0 6 16 20 25 32 32 40 40 40 401000 5.0 9.0 16 32 40 50 – – – – – –

Type C circuit breaker ratingLamp Circuit current Number of lamps in circuitwattage each lamp(W) run A start A 1 2 3 4 5 6 7 8 9 10

Type C or D circuit breaker rating (A)20 0.15 – 6 6 6 6 6 6 6 6 6 640 0.25 – 6 6 6 6 6 6 6 6 6 658 0.35 – 6 6 6 6 6 6 6 6 6 665 0.39 – 6 6 6 6 6 6 6 6 6 670 0.42 – 6 6 6 6 6 6 6 6 6 680 0.48 – 6 6 6 6 6 6 6 6 6 10110 0.66 – 6 6 6 6 6 6 10 10 10 10

Standard fluorescent type TLamp Circuit current Number of lamps in circuitwattage each lamp(W) run A start A 1 2 3 4 5 6 7 8 9 10

For circuits that supply fluorescent lamps, the protective device rating can be calculated on the basis of steady circuit current ofeach lamp and control gear.

Standard fluorescent type T

For circuits that supply fluorescent lamps that incorporate high frequency ballast, refer to Square D Technical Department forapplication details.

High frequency ballast type lamps

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 34

Page 34: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

35

LoadCentre KQ+ Control and command devices - operational information

20 0.15 13 87 174 26 173 346 41 273 54640 0.25 13 52 104 26 104 208 41 164 32858 0.35 13 37 74 26 75 150 41 118 23665 0.39 13 33 66 26 67 134 41 105 21070 0.42 13 31 62 26 62 124 41 98 19680 0.48 13 27 54 26 54 108 41 85 170110 0.66 13 20 40 26 39 78 41 62 124

Fluorescent lamps with starters (corrected)

Determination of contactor rating – lighting loads.

Based on 230 / 240 V AC rated fittings.

■ 2 Pole contactor used on a single phase twowire system.

■ 3 & 4 Pole contactor used on a three phasefour wire system.

Lamp Circuit 25A contactor 40A contactor 63A contactorwattage current load 2P 4P Load 2P 4P Load 2P 3P(W) A A lamp no. max. A lamp no. max. A lamp no. max.

20 0.09 13 144 288 26 289 578 41 456 91260 0.27 13 48 90 26 96 192 41 152 30475 0.34 13 39 78 26 77 154 41 121 242100 0.45 13 29 58 26 58 116 41 91 182150 0.68 13 19 38 26 39 78 41 61 122200 0.90 13 14 28 26 29 58 41 46 92300 1.35 13 10 20 26 19 38 41 30 60500 2.25 13 6 12 26 12 24 41 18 36750 3.38 13 4 8 26 8 16 41 12 241000 4.50 13 3 6 26 6 12 41 9 18

Incandescent and halogen lampsLamp Circuit 25A contactor 40A contactor 63A contactorwattage current load 2P 4P Load 2P 4P Load 2P 3P(W) A A lamp no. max. A lamp no. max. A lamp no. max.

50 0.30 13 43 - 26 87 - 41 137 -80 0.45 13 29 - 26 58 - 41 91 -125 0.67 13 19 - 26 39 - 41 61 -250 1.30 13 10 - 26 20 - 41 32 -400 2.30 13 6 - 26 11 - 41 18 -700 3.00 13 4 - 26 9 - 41 14 -1000 5.50 13 2 - 26 5 - 41 7 -

High pressure mercury vapour lamps (hpl/mbf)Lamp Circuit 25A contactor 40A contactor 63A contactorwattage current load 2P 4P Load 2P 4P Load 2P 3P(W) A A lamp no. max. A lamp no. max. A lamp no. max.

35 0.30 13 43 86 26 87 174 41 137 -55 0.40 13 33 66 26 65 130 41 103 -90 0.60 13 22 44 26 43 86 41 68 -135 0.90 13 14 28 26 29 58 41 46 -

Low pressure sodium lamps (SOX)Lamp Circuit 25A contactor 40A contactor 63A contactorwattage current load 2P 4P Load 2P 4P Load 2P 3P(W) A A lamp no. max. A lamp no. max. A lamp no. max.

150 0.84 13 15 30 26 31 62 41 49 98250 1.40 13 9 18 26 19 38 41 29 58400 2.20 13 6 12 26 12 24 41 19 38700 3.90 13 3 6 26 7 14 41 11 221000 5.50 13 2 4 26 5 10 41 7 14

High pressure sodium lamps (SON)Lamp Circuit 25A contactor 40A contactor 63A contactorwattage current load 2P 4P Load 2P 4P Load 2P 3P(W) A A lamp no. max. A lamp no. max. A lamp no. max.

Contactors – Type CCN

Installation recommendations

■ Contactor and relay controls must be bouncefree.

■ When several contactorsare mounted side by sidea half module spacermust be fitted betweenevery two contactors.

■ It is advisable to mountelectronic units at thebottom of modular enclosures and to separate them from electro-mechanicaldevices by a space equalto one module or by twoF27062 half modulespacers.

■ For applications wherethe temperature insidethe enclosure is likely toexceed 40°C refer to:

Square D – Technical Department

01902 303467

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 35

Page 35: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

36

LoadCentre KQ+ Control and command devices - operational information

20 0.09 8 8940 0.18 8 4460 0.27 8 3075 0.34 8 24100 0.45 8 18150 0.68 8 12200 0.90 8 9300 1.35 8 6500 2.25 8 4750 3.38 8 21000 4.50 8 2

Incandescent and halogen lamps

Determination of relay rating - lighting loads.

Lamp Lamp Line 1 polewattage current current @ 240V AC(W) A A lamp no. max

18 0.8 8 10036 0.19 8 4242 0.21 8 3858 0.26 8 3170 0.30 8 27

Fluorescent lampsLamp Lamp Line 1 polewattage current current @ 240V AC(W) A A lamp no. max

35 0.23 8 3555 0.36 8 2290 0.49 8 16135 0.73 8 11180 1.00 8 8

Low pressure sodium lamps (SOX)Lamp Lamp Line 1 polewattage current current @ 240V AC(W) A A lamp no. max

150 0.83 8 9250 1.38 8 6400 2.20 8 4700 3.85 8 21000 5.50 8 1

High pressure sodium lamps (SON)Lamp Lamp Line 1 polewattage current current @ 240V AC(W) A A lamp no. max

50 0.30 8 2780 0.44 8 18125 0.69 8 12250 1.31 8 6400 2.30 8 3700 3.85 8 21000 5.50 8 1

High pressure mercury vapour lamps (hpl/mbf)Lamp Lamp Line 1 polewattage current current @ 240V AC(W) A A lamp no. max

Impulse relay – type CIR 16A

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 36

Page 36: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

37

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 37

Page 37: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

38

Section 5Page

39SP type A board SP type A board flush kit

40SP interiors & covers

41TP type B board TP type B board flush kit

42TP type B interiors

43TP type B cover assembly

LoadCentre KQ+ dimensional information

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 38

Page 38: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

39

LoadCentre KQ+ Distribution board dimensions (mm)

N L WAY

1WAY

2WAY

3WAY

4WAY

5WAY

6WAY

7WAY

8WAY

9WAY

10WAY

11WAY

12WAY

13WAY

14WAY

15WAY

16

INCOMER

DIM B

DIM D DIM E

DIM A

216

5.2

8

126.7

7.4

5.2

96.4

8

8

7

DIM C

6.5 Ø

13 Ø

370*600 272

*502

49

DIM F

* 24 way dimensions

A board flush kits

KQ125A6 266 260 140 270 264KQ125A8 321 315 195 270 264KQ125A12 376 370 250 270 264KQ125A16 456 450 330 270 264*KQ125A24 376 370 250 500 494KQ125A4SL6 376 370 250 270 264KQ125A5SL5 376 370 250 270 264KQ125A4SL8 456 450 330 270 264KQ125A6SL6 456 450 330 270 264KQAE16 456 450 330 270 264

Dimensions mmReference no. Dimensions mm

DIM A DIM B DIM C DIM D DIM E

KQ6SPFK 366KQ8SPFK 421KQ12SPFK 476KQ16SPFK 556KQ24SPFK 476

Dimensions mmReferenceno. DIM F

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 39

Page 39: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

40

LoadCentre KQ+ Interior and cover dimensions (mm)

KQ125INTAC6 190.8 178.1 - - 188 145KQ125INTAC8 226.8 214.1 - - 188 181KQ125INTAC12 298.8 286.1 - - 188 253KQ125INTAC16 370.8 358.1 - - 188 325KQ125INTCD6 - - 193.2 158.9 270 145KQ125INTCD8 - - 229.2 194.9 270 181KQ125INTCD12 - - 301.2 266.9 270 253KQ125INTCD16 - - 373.2 338.9 270 325

Dimensions mmReference no. Dimensions mm

DIM A DIM B DIM C DIM D DIM E DIM F

N L WAY

1WAY

2WAY

3WAY

4WAY

5WAY

6WAY

7WAY

8WAY

9WAY

10WAY

11WAY

12WAY

13WAY

14WAY

15WAY

16

INCOMER

DIM B

DIM C

DIM D

DIM F

145.5

DIM E

102

102

4 holes 4.5 Ø

All “INTC”Internal covers are 20.6mm deep

DIM A

46

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 40

Page 40: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

41

LoadCentre KQ+ Distribution board dimensions (mm)

DIM C

548.5

456.44.4

8.4

70.4

DIM B

330

70.4

8.4 8.4

70.4127.5

3.2

3.2

62

8.4

70.44.4

DIM A

DIM D

45.3

45.3

KQ125B12 449 340 KQ250B12 808.80 700KQ125B18 539 430 KQ250B18 808.80 700KQ125B24 674 565 KQ250B24 808.80 700KQ125B36 674 565 KQ250B36 1078.80 970KQ125B48 809 700 KQ250B48 1078.80 970KQ125B54 1079 970 KQ250B54 1078.80 970

Dimensions mmReference no. Reference no.

DIM A DIM B DIM A DIM B

KQ4TPFK 542 451KQ5TPFK 632 541KQ6TPFK 767 676KQ8TPFK 902 811KQ10TPFK 1172 1081

Dimensions mmReferenceno. DIM C DIM D

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 41

Page 41: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

42

LoadCentre KQ+ Interior dimensions (mm)

KQ125TBP12 298 378 200KQ125TBP18 352 432 250KQ125TBP24 406 486 300KQ125TBP36 514 594 400KQ125TBP48 622 702 525KQ125TBP54 678 756 575

Dimensions mmReferenceno. DIM A DIM B DIM C

KQ250TBP12 298 378 200KQ250TBP18 352 432 250KQ250TBP24 406 486 300KQ250TBP36 514 594 400KQ250TBP48 622 702 525KQ250TBP54 678 756 575

Dimensions mmReferenceno. DIM A DIM B DIM C

L3L3L2L2

L1L1NN

NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVALNEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL

NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL

N 7 8 9 10 11 12

N 1 2 3 4 5 6

1 2 3 4 5 6 7 8 9 10 11 12

L3L3

L2L2

L1

L1

L2

L2

L3

L3

L1

L1

L2

L2

L3

L3

DIM C

DIM A

94.97

45

443.80

162.62

DIM B

109.50

85.26

22.50

L3L3L2L2

L1L1NN

NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVALNEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL

NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL NEUTRAL COVER ISOLATE SUPPLY BEFORE REMOVAL

N 7 8 9 10 11 12

N 1 2 3 4 5 6

1 2 3 4 5 6 7 8 9 10 11 12

L3L3

L2L2

L1

L1

L2

L2

L3

L3

L1

L1

L2

L2

L3

L3

DIM C

DIM A

94.97

45

443.80

162.62

DIM B

109.50

85.26

22.50

to inside of cover

to inside of cover

125A interiors

250A interiors

(To cover cut-out centre)

(To cover cut-out centre)

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 42

Page 42: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

43

LoadCentre KQ+ Distribution board dimensions (mm)

73

90.3

38.3

46

81.24

46 46

456

DIMA

DIMB

81

4.62

129 56.75

27

36.5

456

DIMA

DIMB

125A covers TP&N

250A cover TP&N

4 109 4506 163 5408 217 67412 325 67416 433 81018 487 1080

Dimensions mmNo. ofways DIM A DIM B

4 109 8106 163 8108 217 81012 325 108016 433 108018 487 1080

Dimensions mmNo. ofways DIM A DIM B

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 43

Page 43: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

44

Section 6Page

45 & 46Fully assembled and custom built distribution, panel and switchboards

Standard plus

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:10 pm Page 44

Page 44: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

45

Standard PlusAdditional resource for your business.Standard Plus gives additional resource to yourbusiness by providing both fully assembled andcustom built distribution and panelboards andForm3Fast switchboards.

Ease and speed of installation are the main benefits of Standard Plus.

In addition it also means:■ Less installation time. All products are supplied fully

assembled and delivered to site.

■ Tailor made solutions. Standard Plus panelboardsand distribution boards can be designed and constructed specifically to your requirements.

■ Less installation space. The neat and compactnature of Standard Plus products means they can bereadily installed in confined spaces.

■ Total project assistance. Square D can provide fullydetailed drawings and test certificates for allStandard Plus products.

■ Fast quotations. Square D guarantees a quick24-hour response to quotation requests.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:11 pm Page 45

Page 45: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

46

Delivering the goodsStandard Plus - Delivered within 2 weeks.The assembly of standard boards:■ LoadCentre KQ+ type A SP&N boards.

■ LoadCentre KQ+ TP&N boards.

■ I Line MCCB panelboards.

■ I Line Fuse Switch panelboards.

All complete with incoming and outgoing devices and traffolyte labels (if required).

Standard Plus - Delivered within 3 weeks.More sophisticated boards, namely those requiring both assembly andmodification can be delivered within 3 weeks of an order being placed.Typically the products include:

■ LoadCentre KQ+ distribution boards joined together.

■ I Line Panelboards joined together.

■ Combined I Line Panelboards and LoadCentre KQ+ distributionboards.

■ I Line panelboards or LoadCentre KQ+ distribution boards incorporatingcontrol equipment.

■ LoadCentre KQ+ TP&N boards fitted with incoming contactor devices.

Standard Plus - Delivered within 4 weeks.More complex installations may require assembly of Square D productsplus the incorporation of other equipment within one composite enclosure.The additional equipment could include:

■ Power factor correction equipment.

■ Change over contactors.

■ Automatic source changeover systems.

■ Protective devices such as earth fault relays.

■ Instrumentation.

■ Facilities for building management systems.

All Standard Plus products are manufactured and tested to BS EN60439-1and in accordance with ISO 9001 procedures before leaving the Square D production facility.

Square D guarantee to deliver these products to site within 4 weeks of an order being placed.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:11 pm Page 46

Page 46: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

47

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:11 pm Page 47

Page 47: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

48

Section 7Page

44Qwikline II consumer unitsTwinbreak & Quadbreak fusegear

50I-Line panelboards

Other Square D products

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:11 pm Page 48

Page 48: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

49

Qwikline II Universal Consumer units

■ Insulated and metal consumer units 2 to 24 SP ways, Standard,split bus, dual and multi tariff supply options.

■ Accept plug on 6kA MCB’s, RCBO’s and control devices.

■ Totally encapsulated busbar system providing complete fingersafety to IP2X.

A range of switch disconnector fuses and switch disconnectors supplied completefor individual mounting or for mounting to busbar chambers.

Twinbreak and Quadbreak Fusegear

Other Square D products

Quadbreak :Full AC 23 ratings (to 630A)

■ 63A to 630A switch disconnector fuses(supplied with fuses).

■ 63A to 630A switch disconnectors supplied with isolator links.

■ 200A to 800A busbar chambers.

Twinbreak :Full AC 23 ratings (to 100A) AC22 to160A

■ 20A to 100A switch disconnector fuses.

■ 20A to 160A switch disconnectors.

■ 160 busbar chambers.

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 49

Page 49: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

50

I-Line Panelboards

Choice of either MCCB or fuse switch panelboards.

MCCB panelboards :■ Four sizes with incoming devices from 250A to 2000A.

■ Outgoing plug-on single pole and triple MCCB devices, 16A to 1250A.

■ Full compliment of accessories, cable extension boxes, plinths, side extension boxes,instrumentation kits and blanking plates.

Fuse switch panelboards :■ Four sizes with incoming devices from 400A to 2000A.

■ Outgoing plug-on fuse combination of units from 32A to 400A.

Other Square D products

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 50

Page 50: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

51

AB

C

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 51

Page 51: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

52

Section 8Page

53Alphanumeric index

Alphanumeric part number index

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 52

Page 52: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

DIN mounted control product - 8V AC bell

DIN mounted control product - 240-8V bell transformer

DIN mounted control product - 8V AC buzzer

DIN mounted control product - 2P 25A contactor

DIN mounted control product - 2P 40A contactor

DIN mounted control product - 3P 40A contactor

DIN mounted control product - 3P 63A contactor

Contactor 4P 100A

DIN mounted control product - 4P 25A contactor

DIN mounted control product - 4P 40A contactor

DIN mounted control product - 1P 10A changeover relay

DIN mounted control product - 1P 16A staircase timer

DIN mounted multi function meter

DIN mounted control product - 1P 16A impulse relay

DIN mounted control product - 2P 16A impulse relay

Light sensitive switch

Presence detector

PIR movement detection

Contactor spacer

DIN mounted control product - 1ch 7 day electronic time switch

DIN mounted control product - 2ch 7 day electronic time switch

Multi function time switch

Memory cartridge for CPT9

Room thermostat

Programmable thermostat

Surge arrester 15kA 1P+N

Surge arrester 15kA 3P+N

Surge arrester 40kA 1P+N

Surge arrester 15kA cartridge

Surge arrester 40kA 3P+N

Surge arrester 40kA cartridge

Surge arrester neutral cartridge

Time delay ON relay

DIN mounted control product - 1ch 24hr time switch

DIN mounted control product - mod spacer

CBL8

CBXB

CBZ8

CCN225

CCN240

CCN340

CCN363

CCN4100

CCN425

CCN440

CCR110

CDT116

CEM01

CIR116

CIR216

CLS1100

CPD360

CPIR

CPS9

CPT11

CPT21

CPT9

CPT9MC

CRT1

CRT2

CSA115

CSA135

CSA140

CSA15C

CSA340

CSA40C

CSANC

CTR1

CTS24

F27062

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

21

53

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 53

Page 53: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

KQ10B103

KQ10B106

KQ10B110

KQ10B116

KQ10B120

KQ10B125

KQ10B132

KQ10B140

KQ10B150

KQ10B163

KQ10C106

KQ10C110

KQ10C116

KQ10C120

KQ10C125

KQ10C132

KQ10C140

KQ10C150

KQ10C163

KQ10C206

KQ10C210

KQ10C216

KQ10C220

KQ10C225

KQ10C232

KQ10C240

KQ10C250

KQ10C263

KQ10C306

KQ10C310

KQ10C316

KQ10C320

KQ10C325

KQ10C332

KQ10C340

MCB (10kA) B curve SP 3A

MCB (10 kA) B curve SP 6A

MCB (10 kA) B curve SP 10A

MCB (10 kA) B curve SP 16A

MCB (10 kA) B curve SP 20A

MCB (10 kA) B curve SP 25A

MCB (10 kA) B curve SP 32A

MCB (10 kA) B curve SP 40A

MCB (10 kA a) B curve SP 50A

MCB (10 kA) B curve SP 63A

MCB (10 kA) C curve SP 6A

MCB (10 kA) C curve SP 10A

MCB (10 kA) C curve SP 16A

MCB (10 kA) C curve SP 20A

MCB (10 kA) C curve SP 25A

MCB (10 kA) C curve SP 32A

MCB (10 kA) C curve SP 40A

MCB (10 kA) C curve SP 50A

MCB (10 kA) C curve SP 63A

MCB (10 kA) C curve DP 6A

MCB (10 kA) C curve DP 10A

MCB (10 kA) C curve DP 16A

MCB (10 kA) C curve DP 20A

MCB (10 kA) C curve DP 25A

MCB (10 kA) C curve DP 32A

MCB (10 kA) C curve DP 40A

MCB (10 kA) C curve DP 50A

MCB (10 kA) C curve DP 63A

MCB (10 kA) C curve TP 6A

MCB (10 kA) C curve TP 10A

MCB (10 kA) C curve TP 16A

MCB (10 kA) C curve TP 20A

MCB (10 kA) C curve TP 25A

MCB (10 kA) C curve TP 32A

MCB (10 kA) C curve TP 40A

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

54

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 54

Page 54: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

19

14

14

11

11

11

11

MCB (10 kA) C curve TP 50A

MCB (10 kA) C curve TP 63A

MCB (10 kA) D curve SP 6A

MCB (10 kA) D curve SP 10A

MCB (10 kA) D curve SP 16A

MCB (10 kA) D curve SP 20A

MCB (10 kA) D curve SP 25A

MCB (10 kA) D curve SP 32A

MCB (10 kA) D curve SP 40A

MCB (10 kA) D curve SP 50A

MCB (10 kA) D curve SP 63A

MCB (10 kA) D curve DP 6A

MCB (10 kA) D curve DP 10A

MCB (10 kA) D curve DP 16A

MCB (10 kA) D curve DP 20A

MCB (10 kA) D curve DP 25A

MCB (10 kA) D curve DP 32A

MCB (10 kA) D curve DP 40A

MCB (10 kA) D curve DP 50A

MCB (10 kA) D curve DP 63A

MCB (10 kA) D curve TP 6A

MCB (10 kA) D curve TP 10A

MCB (10 kA) D curve TP 16A

MCB (10 kA) D curve TP 20A

MCB (10 kA) D curve TP 25A

MCB (10 kA) D curve TP 32A

MCB (10 kA) D curve TP 40A

MCB (10 kA) D curve TP 50A

MCB (10 kA) D curve TP 63A

Accessories B Boards - Flush kit for 1080mm enclosures

Accessories A Boards - 1P outgoing terminal block

Standard A Board 12 SP ways

Standard A Board 16 SP ways

Standard A Board 24 SP ways

Split Load A Board 4+6 SP ways

KQ10C350

KQ10C363

KQ10D106

KQ10D110

KQ10D116

KQ10D120

KQ10D125

KQ10D132

KQ10D140

KQ10D150

KQ10D163

KQ10D206

KQ10D210

KQ10D216

KQ10D220

KQ10D225

KQ10D232

KQ10D240

KQ10D250

KQ10D263

KQ10D306

KQ10D310

KQ10D316

KQ10D320

KQ10D325

KQ10D332

KQ10D340

KQ10D350

KQ10D363

KQ10TPFK

KQ1100L

KQ125A12

KQ125A16

KQ125A24

KQ125A4SL6

55

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 55

Page 55: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

KQ125A4SL8

KQ125A5SL5

KQ125A6

KQ125A6SL6

KQ125A8

KQ125B12

KQ125B12SL24

KQ125B18

KQ125B18SL18

KQ125B24

KQ125B24ES

KQ125B24SL12

KQ125B36

KQ125B36ES

KQ125B48

KQ125B54

KQ125B72

KQ125BCP12

KQ125BCP18

KQ125BCP24

KQ125BCP36

KQ125BCP48

KQ125BCP54

KQ125INTA12

KQ125INTA16

KQ125INTA6

KQ125INTA8

KQ125INTAC12

KQ125INTAC16

KQ125INTAC6

KQ125INTAC8

KQ125INTCD12

KQ125INTCD16

KQ125INTCD6

KQ125INTCD8

Split Load A Board 4+8 SP ways

Split Load A Board 5+5 SP ways

Standard A Board 6 SP ways

Split Load A Board 6+6 SP ways

Standard A Board 8 SP ways

125A Standard B Board 4 TP ways

125A Split Load B Boards 4+8 TP ways

125A Standard B Board 6 TP ways

125A Split Load B Boards 6+6 TP ways

125A Standard B Board 8 TP ways

125A Extra Service B Boards 8+13 mods TP ways

125A Split Load B Boards 8+4 TP ways

125A Standard B Board 12 TP ways

125A Extra Service B Boards 12+13 mods TP ways

125A Standard B Board 16 TP ways

125A Standard B Board 18 TP ways

125A Standard B Board 24 TP ways

Door assembly - three phase - 125A

Door assembly - three phase - 125A

Door assembly - three phase - 125A

Door assembly - three phase - 125A

Door assembly - three phase - 125A

Door assembly - three phase - 125A

Interior reference number - single phase

Interior reference number - single phase

Interior reference number - single phase

Interior reference number - single phase

Cover assembly - single phase

Cover assembly - single phase

Cover assembly - single phase

Cover assembly - single phase

Door and cover assembly - single phase

Door and cover assembly - single phase

Door and cover assembly - single phase

Door and cover assembly - single phase

11

11

11

11

11

13

13

13

13

13

13

13

13

13

13

13

13

25

25

25

25

25

25

25

25

25

25

40

40

40

40

40

40

40

40

56

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 56

Page 56: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

12

14

12

42

42

42

42

42

42

12

16

16

16

16

12

16

39

16

12

15

15

15

15

15

15

15

15

15

25

25

25

25

25

25

16

KQ125L2

KQ125SPP

KQ125SW2

KQ125TBP12

KQ125TBP18

KQ125TBP24

KQ125TBP36

KQ125TBP48

KQ125TBP54

KQ12SPFK

KQ160MCCB3L

KQ160RCD

KQ160SW3L

KQ160SW4

KQ16SPFK

KQ200MCCB3L

KQ200SW3L

KQ200SW4

KQ24SPFK

KQ250B12

KQ250B18

KQ250B24

KQ250B24ES

KQ250B36

KQ250B36ES

KQ250B48

KQ250B54

KQ250B72

KQ250BCP12

KQ250BCP18

KQ250BCP24

KQ250BCP36

KQ250BCP48

KQ250BCP54

KQ250L4P

57

LoadCentre KQ+ Product indexPart Number Description Page Number

Incoming device A Board 125A 2P term block

Accessories B Boards - single phasing kit for 125A

Incoming device A Board 125A 2P switch disc

Interior reference number - three phase - 125A

Interior reference number - three phase - 125A

Interior reference number - three phase - 125A

Interior reference number - three phase - 125A

Interior reference number - three phase - 125A

Interior reference number - three phase - 125A

Accessories A Boards - 12 way A Board flush kit

Incoming device 250A B Board - 160A 3P+N MCCB

Incoming device 250A B Board - 160A 4P RCCB

Incoming device 250A B Board - 160A 3P+N switch disc

Incoming device 250A B Board - 160A 4P switch disc

Accessories A Boards - 6 way A Board flush kit

Incoming device 250A B Board - 200A 3P+N MCCB

Incoming device 250A B Board - 200A 3P+N switch disc

Incoming device 250A B Board - 200A 4P switch disc

Accessories A Boards - 24 way A Board flush kit

250A Standard B Board 4 TP ways

250A Standard B Board 6 TP ways

250A Standard B Board 8 TP ways

250A Extra Service B Boards 8+13 mods TP ways

250A Standard B Board 12 TP ways

250A Extra Service B Boards 12+13 mods TP ways

250A Standard B Board 16 TP ways

250A Standard B Board 18 TP ways

250A Standard B Board 24 TP ways

Cover assembly - three phase - 250A

Cover assembly - three phase - 250A

Cover assembly - three phase - 250A

Cover assembly - three phase - 250A

Cover assembly - three phase - 250A

Cover assembly - three phase - 250A

250A 4P terminal block

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 57

Page 57: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

KQ250MCCB3L

KQ250SPP

KQ250SW3L

KQ250SW4

KQ250TBP12

KQ250TBP18

KQ250TBP24

KQ250TBP36

KQ250TBP48

KQ250TBP54

KQ4TPFK

KQ5TPFK

KQ6SPFK

KQ6TPFK

KQ8SPFK

KQ8TPFK

KQAE16

KQBLK12

KQBLK12D

KQBLK18

KQBLK18D

KQBLK2436

KQBLK2436D

KQBLK25054

KQBLK25054D

KQBLK4854

KQBLK4854D

KQDA12

KQDA18

KQDA2436

KQDA25054

KQDA4854

KQDBL

KQDC

KQE106C01

Incoming device 250A B Board - 250A 3P+N MCCB

Accessories B Boards - single phasing kit for 250A

Incoming device 250A B Board - 250A 3P+N switch disc

Incoming device 250A B Board - 250A 4P switch disc

Interior reference number - three phase - 250A

Interior reference number - three phase - 250A

Interior reference number - three phase - 250A

Interior reference number - three phase - 250A

Interior reference number - three phase - 250A

Interior reference number - three phase - 250A

Accessories B Boards - flush kit for 450mm enclosures

Accessories B Boards - flush kit for 540mm enclosures

Accessories A Boards - 6 way A Board flush kit

Accessories B Boards - flush kit for 675mm enclosures

Accessories A Boards - 8 way A Board flush kit

Accessories B Boards - flush kit for 810mm enclosures

Accessories A Boards - DIN rail extension enclosure

Extension enclosures steel/plain cover

Extension enclosures steel/plain cover & door

Extension enclosures steel/plain cover

Extension enclosures steel/plain cover & door

Extension enclosures steel/plain cover

Extension enclosures steel/plain cover & door

Extension enclosures steel/plain cover

Extension enclosures steel/plain cover & door

Extension enclosures steel/plain cover

Extension enclosures steel/plain cover & door

Enclosures steel/cover/door & 2 or 3 rows of DIN rail

Enclosures steel/cover/door & 2 or 3 rows of DIN rail

Enclosures steel/cover/door & 2 or 3 rows of DIN rail

Enclosures steel/cover/door & 2 or 3 rows of DIN rail

Enclosures steel/cover/door & 2 or 3 rows of DIN rail

Accessories A Boards - barrel lock and 2 Keys

Accessories A Boards - replacement door catch

RCBO (10 kA) 10mA (230/240V) 6A

16

16

16

16

25

25

25

25

25

25

14

14

12

14

12

14

12

26

26

26

26

26

26

26

26

26

26

26

26

26

26

26

14

12

20

58

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 58

Page 58: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

14

14

14

14

14

14

14

22

22

14

14

22

22

22

22

22

22

22

RCBO (10 kA) 30mA (230/240V) 6A

RCBO (10 kA) 100mA (230/240V) 6A

RCBO (10 kA) 10mA (230/240V) 10A

RCBO (10 kA) 30mA (230/240V) 10A

RCBO (10 kA) 100mA (230/240V) 10A

RCBO (10 kA) 10mA (230/240V) 16A

RCBO (10 kA) 30mA (230/240V) 16A

RCBO (10 kA) 100mA (230/240V) 16A

RCBO (10 kA) 10mA (230/240V) 20A

RCBO (10 kA) 30mA (230/240V) 20A

RCBO (10 kA) 100mA (230/240V) 20A

RCBO (10 kA) 10mA (230/240V) 32A

RCBO (10 kA) 30mA (230/240V) 32A

RCBO (10 kA) 100mA (230/240V) 32A

RCBO (10 kA) 10mA (230/240V) 45A

RCBO (10 kA) 30mA (230/240V) 45A

RCBO (10 kA) 100mA (230/240V) 45A

KW metering kit

Accessories B Boards - spare/clean earth 12 terminals

Accessories B Boards - spare/clean earth 24 terminals

Accessories B Boards - spare gland plate (plain)

Accessories B Boards - MCB padlocking attachment (pack of 5)

Accessories B Boards - joining kits

Accessories A Boards - padlock for QOEPLA

100A RCCB 30mA trip DP

100A RCCB 100mA trip DP

100A RCCB 300mA trip 4P

100A RCCB 300mA trip 4P

25A RCCB 30mA trip DP

25A RCCB 30mA trip 4P

25A RCCB 100mA trip 4P

25A RCCB 300mA trip DP

25A RCCB 300mA trip 4P

40A RCCB 30mA trip DP

40A RCCB 30mA trip 4P

KQE106C03

KQE106C10

KQE110C01

KQE110C03

KQE110C10

KQE116C01

KQE116C03

KQE116C10

KQE120C01

KQE120C03

KQE120C10

KQE132C01

KQE132C03

KQE132C10

KQE145C01

KQE145C03

KQE145C10

KQMET250

KQSEB12T

KQSEB24T

KQSGPKO

QOEPLA

QOJ

QOPL

RSD100032

RSD100102

RSD100304

RSD100304S

RSD25032

RSD25034

RSD25104

RSD25302

RSD25304

RSD40032

RSD40034

59

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 59

Page 59: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

RSD40102

RSD40104

RSD40302

RSD40304

RSD41P54

RSD63032

RSD63034

RSD63102

RSD63104

RSD63302

RSD63304

RSD80032

RSD80034

SDEN3

SDEN4

SDEN4P

SDEN5

SDEN6P

SDEN8P

SQODNBP

SQOE063030

SQOE063100

SQOE100030

SQOE100100

SQOE100100S

SQOE100300

W29242

W29259

W29370

WALLET

40A RCCB 100mA trip DP

40A RCCB 100mA trip 4P

40A RCCB 300mA trip DP

40A RCCB 300mA trip 4P

Insulated enclosure

63A RCCB 30mA trip DP

63A RCCB 30mA trip 4P

63A RCCB 100A trip DP

63A RCCB 100mA trip 4P

63A RCCB 300mA trip DP

63A RCCB 300mA trip 4P

80A RCCB 30mA trip DP

80A RCCB 30mA trip 4P

Metal enclosure, 3 modules

Metal enclosure, 4 modules

Insulated enclosure, 4 modules

Metal enclosure, 5 modules

Insulated enclosure, 6 modules

Insulated enclosure, 8 modules

Accessories A Boards - blanking plate (5 poles)

Secondary RCCB for SL A Board 125A 4 P term block

Secondary RCCB for SL A Board 125A 3P+N switch disc

Secondary RCCB for SL A Board 125A 4P switch disc

Secondary RCCB for SL A Board 80A 30mA

Secondary RCCB for SL A Board 100A 30mA

Secondary RCCB for SL A Board 100A 300mA TD

Accessories B Boards - MCCB<=95mm2 cable clamps x 3

Accessories B Boards - MCCB<=185mm2 cable clamps x 3

Accessories B Boards - MCCB padlock attachment

Accessories B Boards - circuit directory and wallet

22

22

22

22

22

22

22

22

22

22

22

22

22

16

12

12

21

21

21

12

12

12

12

12

12

12

16

16

16

16

60

LoadCentre KQ+ Product indexPart Number Description Page Number

SQ.D5131. V2 LoadCentreKQ(Text) 20/9/04 5:12 pm Page 60

Page 60: LoadCentre KQ+...SQ.D5131.V2 LoadCentreKQ(Cover) 20/9/04 5:16 pm Page 2 LoadCentre KQ+ product selector KQ+ Distribution boards KQ+ Incoming devices KQ+ Accessories Standard A boards

Square D, Stafford Park 5, Telford, ShropshireTF3 3BL. Tel: 0870 608 8 608 Fax: 0870 608 8 606.www.squared.co.uk

SQD5131.V2 Sep 2004