long line check valve accessory for ... - utcccs-cdn.com · check valve accessory must be mounted...

4
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53380009-01 Printed in U.S.A. Form 38AP-5SI Pg 1 5-10 Replaces: New Installation Instructions Part No.: 38AP-900---011, 38AP-900---012, 38AP-900---013 SAFETY CONSIDERATIONS When installing this accessory, observe precautions in the literature and on any labels attached to the equipment, and all other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling and installing this accessory. INTRODUCTION An accessory long line check valve must be installed for: 1. Any 025-030 size dual circuit unit where the evapora- tor is located higher than the condensing unit and the linear line length exceeds 55 ft (16.8 m). 2. Any size dual or single circuit unit with linear line length of 100 ft (30.5 m) or more. The kit consists of a liquid line check valve and a bypass check valve to prevent charge migration to compressor. INSTALLATION The long line check valve accessory must be mounted in the liquid line near the condensing unit. The valve is brazed into the liquid line. Fitting adapters may be required to connect the check valve to the liquid line. The valve may be mounted in any orientation, horizontally or vertically. See Fig. 1 for dimen- sions. Figure 2 shows the location of the check valves on a rooftop installation. Figure 3 shows the location of the check valves on a ground level installation. ACCESSORY USAGE WARNING To avoid the possibility of electrical shock, open and tag all disconnects before installing this equipment. Failure to do so could result in severe personal injury. CAUTION For all units with liquid lines of 100 ft (30.5 m) or more or any 025-030 size dual circuit unit application where evapo- rator is located higher than the condensing unit and liquid lines exceed 55 feet (16.8 m), a long line check valve must be installed to prevent compressor failure. The long line check valve accessory must be mounted in the liquid line as close as possible to the condensing unit. UNIT SIZE CIRCUIT TYPE CHECK VALVE SIZE (in. ODF) ACCESSORY USAGE (QUANTITY) — PART NO. 38AP-900--- 011 012 013 38APD/S025 Dual 5/8 + 5/8 2 Single 5/8 1 38APD/S027 Dual 5/8 + 5/8 2 Single 5/8 1 38APD/S030 Dual 5/8 + 5/8 2 Single 7/8 1 38APD/S040 Dual 5/8 + 5/8 2 Single 7/8 1 38APD/S050 Dual 5/8 + 5/8 2 Single 7/8 1 38APD060 Dual 5/8 + 7/8 1 1 38APS065 Single 7/8 1 38APD070 Dual 7/8 + 7/8 2 38APD080 Dual 7/8 + 7/8 2 38APD090 Dual 7/8 + 7/8 2 38APD100 Dual 7/8 + 7/8 2 38APD115 Dual 7/8 + 7/8 2 38APD130 Dual 7/8 + 1 1/8 1 1 38APS025-065 38APD025-130 Long Line Check Valve Accessory 50/60 Hz

Upload: dangnguyet

Post on 24-Apr-2018

219 views

Category:

Documents


5 download

TRANSCRIPT

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53380009-01 Printed in U.S.A. Form 38AP-5SI Pg 1 5-10 Replaces: New

Installation InstructionsPart No.: 38AP-900---011, 38AP-900---012, 38AP-900---013

SAFETY CONSIDERATIONSWhen installing this accessory, observe precautions in the

literature and on any labels attached to the equipment, and allother safety precautions that may apply.• Follow all safety codes.• Wear safety glasses and work gloves.• Use care in handling and installing this accessory.

INTRODUCTIONAn accessory long line check valve must be installed for:

1. Any 025-030 size dual circuit unit where the evapora-tor is located higher than the condensing unit and thelinear line length exceeds 55 ft (16.8 m).

2. Any size dual or single circuit unit with linear linelength of 100 ft (30.5 m) or more.

The kit consists of a liquid line check valve and a bypasscheck valve to prevent charge migration to compressor.

INSTALLATION

The long line check valve accessory must be mounted in theliquid line near the condensing unit. The valve is brazed intothe liquid line. Fitting adapters may be required to connect thecheck valve to the liquid line. The valve may be mounted inany orientation, horizontally or vertically. See Fig. 1 for dimen-sions. Figure 2 shows the location of the check valves on arooftop installation. Figure 3 shows the location of the checkvalves on a ground level installation.

ACCESSORY USAGE

WARNING

To avoid the possibility of electrical shock, open and tag alldisconnects before installing this equipment. Failure to doso could result in severe personal injury.

CAUTION

For all units with liquid lines of 100 ft (30.5 m) or more orany 025-030 size dual circuit unit application where evapo-rator is located higher than the condensing unit and liquidlines exceed 55 feet (16.8 m), a long line check valve mustbe installed to prevent compressor failure. The long linecheck valve accessory must be mounted in the liquid lineas close as possible to the condensing unit.

UNITSIZE

CIRCUITTYPE

CHECK VALVE SIZE

(in. ODF)

ACCESSORY USAGE (QUANTITY) — PART NO. 38AP-900---

011 012 013

38APD/S025Dual 5/8 + 5/8 2 — —

Single 5/8 1 — —

38APD/S027Dual 5/8 + 5/8 2 — —

Single 5/8 1 — —

38APD/S030Dual 5/8 + 5/8 2 — —

Single 7/8 — 1 —

38APD/S040Dual 5/8 + 5/8 2 — —

Single 7/8 — 1 —

38APD/S050Dual 5/8 + 5/8 2 — —

Single 7/8 — 1 —

38APD060 Dual 5/8 + 7/8 1 1 —

38APS065 Single 7/8 — 1 —

38APD070 Dual 7/8 + 7/8 — 2 —

38APD080 Dual 7/8 + 7/8 — 2 —

38APD090 Dual 7/8 + 7/8 — 2 —

38APD100 Dual 7/8 + 7/8 — 2 —

38APD115 Dual 7/8 + 7/8 — 2 —

38APD130 Dual 7/8 + 1 1/8 — 1 1

38APS025-06538APD025-130

Long Line Check Valve Accessory50/60 Hz

2

3.715

TYP

20.000

ENSURE FLOW ARROWSARE AS DEPICTED

BYPASS CHECK VALVE

LIQUID LINE CHECK VALVE

(508)

(94)

DIRECTIONOF FLOW

Fig. 1 — Long Line Check Valve Accessory Dimensions (Part No. 38AP-900---011 Shown)

NOTE: Dimensions are in inches. Dimensions in () are in millimeters.

3

40RU

3 FT MAX FOR SHORT RISER

a38-7098_gs

LEGEND

*Field supplied.†If double suction riser is required for pipingsystem, size short riser (3 ft [0.9 m] maximum)according to base unit installation instructions.

**Field supplied. See base unti installationinstructions for refrigerant specialties partnumbers.

LLSV — Liquid Line Solenoid ValveNEC — National Electrical CodeTXV — Thermostatic Expansion Valve

PipingDouble Riser Piping (if required)

NOTES:1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System

Design Manual for details. 2. All wiring must comply with the applicable local and national codes.3. Wiring and piping shown are general points-of-connection guides only and are not

intended for, or to include all details for, a specific installation.4. Install field-supplied disconnect switch in accordance with all local and national electrical

codes.5. Liquid line solenoid valves (solenoid drop control) are not required but are recommended

to prevent refrigerant migration to the compressor.6. Factory-supplied accumulator not shown.7. Dual-circuit piping shown. Single-circuit piping is similar but would only have one suction

line and one liquid line.8. A field-supplied (min. 5% up to 15%) bleed port TXV is required for every application.9. Sight glass, LLSV, and filter drier are field supplied.

10. Long line length check valves are required for liquid line installation on all linear linelength applications of more than 100 ft (30.5 m). For any 025-030 size dual-circuit unitapplication where evaporator is located higher than the condensing unit, check valvesare required for linear line length above 55 ft (16.8 m).

Fig. 2 — Accessory Location — 38AP Unit Rooftop Installation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53380009-01 Printed in U.S.A. Form 38AP-5SI Pg 4 5-10 Replaces: New

Copyright 2010 Carrier Corporation

a38-7099_gs

NOTES:1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System

Design Manual for details. 2. All wiring must comply with the applicable local and national codes.3. Wiring and piping shown are general points-of-connection guides only and are not

intended for, or to include all details for, a specific installation.4. Install field-supplied disconnect switch in accordance with all local and national electrical

codes.5. Liquid line solenoid valves (solenoid drop control) are not required but are recom-

mended to prevent refrigerant migration to the compressor.6. Factory-supplied accumulator not shown.7. Dual-circuit piping shown. Single-circuit piping is similar but would only have one suction

line and one liquid line.8. A field-supplied (min. 5% up to 15%) bleed port TXV is required for every application.9. Sight glass, LLSV, and filter drier are field supplied.10.Long line length check valves are required for liquid line installation on all linear line

length applications of more than 100 ft (30.5 m). For any 025-030 size dual-circuit unitapplication where evaporator is located higher than the condensing unit, check valvesare required for linear line length above 55 ft (16.8 m).

LEGEND

*Field supplied.†Field supplied. See base unit installationinstructions for refrigerant specialties partnumbers.

LLSV — Liquid Line Solenoid ValveNEC — National Electrical CodeTXV — Thermostatic Expansion Valve

Piping

Fig. 3 — Accessory Location — 38AP Unit Ground Level Installation