    WiringStandardsandGuidelinesLongwoodUniversity

    Thisdocumentanditsreferencesareintendedtoassistthearchitect/designerand

    theinstallerinthebaseguidelinesandstandardsutilizedatLongwoodUniversity

    tocompleteaneffectiveandefficientwiringinfrastructure.

    2009

    MarkKendrick,DirectorCTS

    LongwoodUniversity

    1/12/2009

  • 8/4/2019 Longwood Wiring Standards

    2/38

    2

    CHARGE

    TheDivisionofCommunicationsandTechnologyServiceshastheresponsibilityforplanning,developing,managingandmaintainingthemost

    effective,efficientandeconomicalcommunicationsnetworksystem.Initsroleasasystemintegratorofnetworks,theDivisionsupportsallUniversityneedsbyapprovingandcoordinatingallvoice,dataandvideocommunicationssystemspolicies.Withtheconvergenceofvoice,data

    andvideotechnologies,theDivisioniscommittedtoaseamlesscommunicationsservicesnetwork.

    Inrecentyears,thefocusoncommunicationssystemplanning,operationsandprocurementforvoice,dataandvideocommunicationshave

    movedincreasinglyintotheforefrontoftheattentionofUniversityadministratorsanddepartmentdirectors.Communicationssystemsarenow

    seenasatoolforimprovingemployeeproductivity,facilitatingtheeducationprocessandreducingoperatingcosts.Byproviding

    communicationsandapplicationscompatibilitybetweenacquiredcommunicationssystemsandrelatedservices,theUniversitywillmeetits

    goalofachievingatotallyintegratedinformationsystemsenvironment.

    CommunicationsandTechnologyServiceswillcontinuetomaintainasophisticatedandcomprehensivecommunicationsinfrastructurethrough

    whichtheUniversitycommunitycanshareaccesstocostlytechnologyresources,andthereforeminimizeexpensiveandunnecessary

    duplication.TheDivisionwilldevelopandexpandnetworksystemstoenhanceandfacilitatethegrowthoftheinfrastructurebyproviding

    leadershipandcoordinationfortheplanning,development,acquisitionandutilizationofnewtechnologies.

    Thereare13numberedsectionstothisdocument:

    2SERVICEENTRANCEANDTERMINATIONOUTSIDEPLANT

    3TELECOMMUNICATIONSROOMSANDCABLETERMINATION

    4VOICEANDDATAOUTLETSINSIDEPLANTWIRINGANDRACEWAYS

    5TELEVISIONCABLEANDOUTLETS

    6PROTECTION,GROUNDINGANDBONDING

    7INSPECTIONANDTESTING

    8FIRESTOPPING

    9LOCALAREANETWORKS

    10FIBEROPTICTECHNOLOGY

    11MISCELLANEOUSANDSPECIALSITUATIONS

    12CODES,STANDARDSANDREGULATIONS

    13GLOSSARYANDACRONYMS

    Thisdocumentisintendedtobeaguidelineforthedesignerandtheinstaller.Therearemanyvariablesthataffectthedesignandconstruction

    ofabuilding,butwiththecoordinationofthedesignerandtheITdepartmentatLongwoodUniversityeachbuildingwillbeasuccess.

  • 8/4/2019 Longwood Wiring Standards

    3/38

    3

    2SERVICEENTRANCEANDTERMINATIONOUTSIDEPLANT

    GENERAL............................................................................................................................3

    INTRODUCTION.................................................................................................................3

    CABLE.................................................................................................................................3

    GENERAL............................................................................................................................3

    LABELING............................................................................................................................4

    AERIAL.................................................................................................................................4

    CONDUIT.............................................................................................................................4

    GENERAL.............................................................................................................................4

    REQUIREMENTS..................................................................................................................4

    UNDERGROUND..................................................................................................................4

    TUNNELS.............................................................................................................................4

    CONDENSATIONTRAPS.....................................................................................................5

    TYPES.................................................................................................................................5

    MANHOLES.........................................................................................................................6

  • 8/4/2019 Longwood Wiring Standards

    4/38

    4

    2SERVICEENTRANCEANDTERMINATIONOUTSIDEPLANT

    GENERAL

    INTRODUCTIONThissectionprovidesthenecessaryguidelinestoinstallserviceentrancestobuildingsandinformationfortheterminationof

    cablesenteringbuildings.Topicsaddressedvoice,dataandvideoandcurrentCATV.

    Alloutsideplantvoice,data,andvideocabling,conduitandmanholesshallbedesignedand/orapprovedbytheUniversitysDivisionof

    CommunicationsandTechnologyServices.

    LongwoodUniversityFacilitiesManagementisresponsiblefortheEnergyManagementSystemandcampusFireAlarmSystem.

    CABLE

    GENERAL

    PriorapprovalandcoordinationwithCommunicationsSystems,Facilities,andotherconcernedpartiesisnecessarywhenthesituationrequires

    pullingcablethroughaconduitoccupiedbyanothercable.

    Allcablesassociatedwiththecampustelecommunicationsnetwork(telephone,data,LAN,WAN,campusTV,CATVandfiberoptics)shallbe

    connectedanddisconnectedbyCommunicationsSystems.

    Onlythosecablesspecified,willbeinstalledinanyfacility.

    Thereshallbenocablewithvoltageshigherthan48voltsincommunicationsductbanks.Electricalfeedersforsumppumps,lightsandoutlets

    mustbeinstalledaccordingtotheNationalElectricalCoderequirementsforwetlocations.Allconduitsmustbeextendedinthemanhole.

    Theseconduitsmustbeclearlytagged.

    Allcablesenteringabuildingshallbeterminatedonprotectionblocks.Onlygasandsolidstateprotectorsshallbeused.

    Damagesincurredtoanycablearetheresponsibilityofthepartyinvolved.AlldamagesshallbereportedimmediatelytoCommunications

    SystemsandFacilitiesManagers.

    LABELING

    Allcablesineachmanholeshallbeidentifiedbytheownerofthecable,cablenumber,cabletype,numberofpairsandtheterminationpoint.

    Labelsshallinclude,forexample:CommunicationsSystems,Cable05,SS100,101200,B58.Thetagshallbemadeofaluminumorstainless

    steel.

    Wheneverpossible,allabandonedcableshallberemovedfromtunnels,manholesandconduit.Ifitisnotfeasibletoremoveabandonedcable,

    itshallbeclearlytaggedasabandoned,withappropriatelabelingasabove,andshallbereportedtoCommunicationsSystemsandFacilities

    Managers.

    AERIAL

    Mostuniversitylowvoltagecablingisunderground.NoaerialwiringshallbedoneoncampusunlessapprovedbyCommunicationsSystems,

    FacilitiesManager,andCapitalPlanning.

    2SERVICEENTRANCEANDTERMINATIONOUTSIDEPLANT

    CONDUIT

  • 8/4/2019 Longwood Wiring Standards

    5/38

    5

    GENERAL

    ConduitsizingandquantitiesbetweenbuildingsshallbedeterminedbytheDivisionofCommunicationsSystemsandwillbecommunicatedto

    CapitalPlanningforinclusionintheproject.Minimumrequirementsareoutlinedinthefollowingstatements:

    Allcampusbuildingsshallbeconnectedtothenearestmanholeornewmanholeifoneistobeinstalled.

    Damagesincurredtoanyconduitaretheresponsibilityofthepartyinvolved.AlldamagesshallbereportedtoCommunicationsSystemsand

    FacilitiesManagersimmediately.

    REQUIREMENTS

    Allnewfacilitiesorrenovationswillberequiredtomeetminimumrequirements.Minimumvoice,data,andvideoconduitrequiredforeach

    buildingshallbe4conduits.

    Two(2)ofwhichshallbe2Schedule40,PVC.

    Two(2),fourinch,Schedule40,PVC.

    Nomorethantheequivalentoftwo90degreelongsweepsallowedinarun,includingoffsets.

    Apullwireshallbeinstalledandtiedoffineachconduit.Pullwiresusedinoutsidefacilitiesshallbenylonandusedtopullheavierropeas

    neededtoinstallcable.Pullwireshallbeinstalledwithnewcabletoallowfutureinstalls.Pullwiresusedinsidefacilitiesshallbenylon.

    UNDERGROUND

    Allundergroundconduitsandducts,rigidorPVC,addedtoaprojectshallbeaddedingroupsof2,4,6,8,10,12ormore.Communicationsduct

    shallbe66.6percentfour(4)inchSchedule40.Undernocircumstancesaresingleundergroundconduitrunsacceptable.

    Allundergroundconduit,ductbankandracewaysshallbesteelreinforced,concrete(3500psiminimum)encasedPVCordirectburiedthreaded

    rigidsteel.Additionalreinforcementistobeusedwhencrossingroadways.

    Allcommunicationsductsshallbeaminimumof12inchesfrompowerductbanksorcables.Allcommunicationsductsshallalsobeaminimum

    of24inchesfromsteampipesandcondensationlinesifcrossingperpendicular.

    Whencommunicationductsrunparalleltosteamlinesaminimumofasix(6)footseparationisrequiredtoavoidconductionofheat.Allother

    ductseparationsmustcomplywiththeNationalElectricCode.

    UNDERGROUNDRigidsteelconduit,encasedinreinforcedconcrete,shallbeusedinanylocationsubjecttoabuse,suchasunderslabsor

    foundations.

    Allnecessaryprecautionsshallbetakenduringconstructiontopreventthelodgingofdirt,plasterortrashinallconduit,tubing,fittingsand

    boxes.Allconduitinfloors,concreteorbelowgrade,shallbeswabbedfreeofdebrisandmoisturebeforewiresarepulled.

    AlldiggingsandexcavationonLongwoodPropertyshallbeapprovedbyFacilitiesManagerandCommunicationsSystems.

    TUNNELS

    Whereconduitorductsareintunnels,theyshallbekeptatleast24inchesfromparallelrunsofflues,steampipes,hotgaspipes,hotwater

    pipesoranyotherutilitylinewhichishotduringnormaloperationofthefacilityitserves.Unlesswrittenexceptionisprovidedbythe

    University,allconduitsectionscrossingsteamlinesshallberigidandshallbeprovidedwithameansofinsulationfromthesteamlines.

    CONDENSATION

  • 8/4/2019 Longwood Wiring Standards

    6/38

    6

    Ductbanksshallbepitchedtodraintomanholes.

    TRAPS

    Allconduit,tubing,raceways,ductsandductbanksshallbeinstalledinsuchmannertoinsureagainstcollectionoftrappedcondensation.

    Racewayrunsshallbearrangedtobevoidoftraps.

    Whenconduitpassesthroughexteriorconcretewallsofanyfacility,theentranceshallbewatertight.Providepipesleevesintheconcretewith

    1/2inchminimumentranceseal.

    Allconduitshallhavewatertightconnectionsandbeslopedproperlysotheywilldrainintothemanholeandawayfromthebuildingentrance.

    TYPES

    Gaspipeandwaterpipesshallnotbeusedforconduitunderanycircumstances.

    Twotypesofconduitareacceptedforundergroundconduitsystems.

    RigidgalvanizedsteelconduitwiththreadedfittingsThisconduitshallbeinstalledwithreinforcedconcretecasing.Ifnotconcreteencased,

    thisconduitshallbepaintedwithtwocoatsofcoaltarbasepaintorhaveepoxycoatingappliedbymanufacturer.

    Schedule40PVCconduitThisconduitshallbeinstalledwithreinforcedconcretecasing.NoPVCconduitisacceptablewithoutreinforced

    concrete.

    Rigidsteelconduitsinstalledundergroundshallbefieldwrappedwith0.01inchthickpipewrappingplastictapeappliedwitha50percent

    overlap,orshallhaveafactoryappliedplasticresin,epoxyortwocoatsofafieldappliedasphalttarspecificallymadeforthispurpose.Where

    theasphalttarcoatingmethodisused,thecontractorshallnotifytheUniversityCapitalPlanningManagerpriortobackfillingsothatthe

    Universitymayinspectthecoatingandapprovebeforetheconduitiscovered.

    Paintingshallextendtosix(6)inchesabovegroundlevelwhereconduitisinstalledbyapoleorsidestructureorinsidepedestal.

    Theductenvelopeshallberectangularinthecrosssectionandbeaminimumconcretethicknessofthree(3)inchesaroundanyconduit.The

    ductenvelopeshallbesizedandplacedasshownonconstructiondocuments.

    Aminimumoffour(4),#4,steelreinforcingrodsshallbeinstalledinallductbankenvelopes.Whereconduitentersabuildingoramanholethe

    rebarsmustbedoweledintotheexistingstructuretopreventshearingoftheconduitsincaseofsettlement.

    Whereaconnectionismadetoanexistingmanholeorbuildingtheenvelopeshallbedoweledintotheexistingencasementstoprevent

    shearingduetosettling.

    Allconduitandductsmustbeterminatedwithbellendsatthemanhole,facilityorotherterminationpoint.Wheretrenchwallsareunstableor

    thetrenchwidthiswiderthantheenvelope,theenvelopeshallbeformedasrequired.

    Ductspacersshallbeprovidedatamaximumofsevenfeetintervals.Conduitshallbeanchoredatthree(3)footsix(6)inchintervalsandat

    eachspacertopreventductfloatingduringconcreteinstallation.

    Eachductrunshallbedonewithacontinuousconcretepour.BrokenpoursarenotallowedwithoutwrittenexceptionfromtheUniversity,and

    provided#4rebarorlargerisextendedtwelve(12)inchesbeyondtheendoftheenvelopeattheendofeachday'spourandatallstubouts.

    MANHOLES

    GENERAL

  • 8/4/2019 Longwood Wiring Standards

    7/38

    7

    TheUniversityusesQuazitboxesinvarioussizestoaccommodatetheconduitseitherassplicepointsorpassthrough.Currentpartnumbers

    are:TopPG3060HH00,BoxPG3060BA36.

    Standards.

    Boxesshallbeinstalledtoallowthetopoftheboxtobeatgradelevelwiththesurroundinglandscape.

    TheBoxesshallnotbestackedmorethantwodeep.Thebottomsixinchesshallbefilledwithgravel,#56insize,andnotexceedpastthetopsixinchesoftheconduit.

    Boxesshallnotbeinstalledinlocationswhereheavytrafficcoulddamagethetop.

    Themaximumdepthofallmanholesshallbeten(10)feetfromthebottomunlessotherwise

    approvedbyCommunicationsSystems.

  • 8/4/2019 Longwood Wiring Standards

    8/38

    8

    3TELECOMMUNICATIONSROOMSANDCABLETERMINATION

    OVERVIEW..........................................................................................................................8

    DEFINITION........................................................................................................................8

    SPACE.................................................................................................................................8

    GENERAL............................................................................................................................8

    REQUIREMENTS.................................................................................................................8

    GENERAL............................................................................................................................8

    ENVIRONMENT..................................................................................................................8

    ELECTRICAL........................................................................................................................8

    GROUNDING.....................................................................................................................9

    LABELING..........................................................................................................................9

    CABLE...............................................................................................................................9

    GENERAL...........................................................................................................................9

    RACKSANDPANELS..........................................................................................................10

    GENERAL...........................................................................................................................10

    WIREDRESS.......................................................................................................................10

    RACKANDPATCHPANEL...................................................................................................10

    PUNCHDOWN....................................................................................................................11

  • 8/4/2019 Longwood Wiring Standards

    9/38

    9

    3TELECOMMUNICATIONSROOMSANDCABLETERMINATION

    OVERVIEW

    DEFINITION

    Telecommunicationroomsarespecialpurposeroomsthathousetelecommunicationsequipment.

    Theseequipmentroomshavestringentrequirementsduetothenature,sizeandcomplexityoftheequipmenthousedintheroom.

    SPACE

    Theminimumdimensionforacommunicationswalkinroomis100squarefeetor150squarefeetwhentheroomistobesharedwith

    computers,telephoneswitches,andequipmentracks,suchasaPBXorlargekeysystem.Otherexceptionsmayapply;Communications

    Systemsshallbecontactedforfinalfootageapproval.

    GENERAL

    Anapprovedfireextinguishermustbeprovidedjustoutsidethedoorofeachcloset.AllworkshallcomplywiththeNationalElectricalCode,

    CommonwealthofVaBuildingCodesandLongwoodUniversityCommunicationsSystemsGuidelinesandCapitalPlanningDesignand

    ConstructionStandards.

    Telecommunicationsroomsvaryaccordingtothesizeofthebuilding,numberoffloors,tenancycharacteristicsandtelecommunications

    servicesrequired.Considerationtothefutureneedsofthefacilityandtheendusersisanecessity.

    Electricalpanelsarestrictlyprohibitedincommunicationsrooms.

    A50percentgrowthfactorshallbebuiltinandprovidedineachriserunlessotherwisespecified,consequentlyanycableorconduitworkthat

    pertainstotelecommunicationsmustbedesignedand/orapprovedbyCommunicationsSystems.

    Tofacilitatetheproperinstallation,routingandplacementofcables,wires,premiseequipmentandterminalfields,communicationroomsshall

    belocatedoneachfloor,inthemiddleofthebuildinginsteadofeitherendandstackedoneabovetheother,unlessotherwiseinstructedby

    CommunicationsSystems.Architectsmustpayextraattentiontoroomlocationstoovercomedistancelimitations.Thetotaldistanceofthe

    conduitpath,fromoutlettothecommunicationsroomshallnotexceed275feetincludingterminationloss.

    An"AsBuilt"drawingshallbesubmittedwitheachjobuponacceptance.

    Allcommunicationsroomdoorsaretobekeyedalike.Locksshallbespringlock(selflocking).Allcommunicationsroomswillutilizeaccess

    controlkeycards.

    Doorwaysshallbedesignedwithminimummeasurementsof3feetby6feet8inchesandshallopenoutwardintothecorridor.

    Floorsshallbesealedconcreteortile,carpetisprohibited.

    Telecommunicationroomsshallbelocatedaboveanythreatofflooding.Roomslocatedinbasementsshallhavefloordrainswithpositive

    drainageotherwisesumppumpsmustbeprovided.

    Firetreatedplywood,3/4inchthick,mustbemechanicallyfastenedtoaminimumofonewallandpaintedwithtwo(2)coatsoffireresistant

    paintofaneutralcolor.Thefiretreatedplywoodistobeginatfour(4)inchesAFFandendat8feet,4inchesAFF.

    Therecommendedceilingheightis8feet,6inches.Avoidfalseceilings,ifpossible.

    Installsleevesbetweenstackedcommunicationsrooms,withsleevesextended4(four)inchesAFFand4(four)inchesbelowtheceilingofthe

    room.

  • 8/4/2019 Longwood Wiring Standards

    10/38

    10

    ENVIRONMENTAllcommunicationsroomsshallbeenvironmentallycontrolledtomaintaintheroomenvironmentatatemperaturerangeof65

    to75degreesFahrenheit,withamaximumrelativehumiditylevelof50percent,24hoursaday,7daysaweek.Communicationsroomsshallbe

    conditionedwithafreshairexchangeofthree(3)airchangesperhour.IfHVACmustbeshutdownthenanexhaustmustbeprovidedto

    removeheat.

    Noplumbing,HVAC,orelectricalconduitshallpassthroughorbedirectlyabovethecommunicationsroom.Thespaceabovetheceilingis

    neededforbroadbandamplifiersand/orassortedequipment.

    ELECTRICALLightingshallbefour(4)feetfluorescentandprovideaminimumof100FC/SFandconnectedtotheemergencygeneratorwhen

    available.

    Multiple,fourplex,ACoutletsmustbeprovidedtopowertelephonekeysystems,computerinterfacesandothertelecommunications

    requirements.Outletsmustbeflushwhencutthroughplywood.Alloutletsshallbeconnectedtoadedicatedcircuitbreaker.Eachdedicated

    electricalcircuitshallbe20amp,110V,60Hz'stype.Allcircuitsmustbetiedtoanemergencygenerator.

    Allbreakerboxesaretobelabeledandidentifiedtoavoidbeingturnedoffinerror.

    *Someequipmentwillrequireadditionalamperage,thiswillneedtobeverifiedduringthedesignstage.

    GROUNDING

    Allcommunicationsroomsshallhaveagroundingbarwhichshallbetwelve(12)inchesbyone(1)inchwithpredrilled1/4inchholes.Thisbar

    shallbeattachedtothemainbuildinggroundingsystemwithawirenotsmallerthan#2AWGcopper.

    Eachdistributionpointshallbegroundedtothemainbuildingground,NECrequirementshallbefollowed.

    Thereshallbeagroundingbarateachdistributionpanel.Thegroundbarshallbeconnectedtobuildinggroundwithamaximumresistanceof

    0.5ohmsorless.

    LABELING

    Communications,computerandtelevisionconduitistobeclearlyidentified,ateveryjunctionbox,viaapaintedsectionorbyuseofconduit

    stickersindicatingeachconduitrun;Blue=telephone,Green=computer,Yellow=television,Orange=fiberoptic.

    AllIntermediateDistributionFrames,BuildingDistributionFramesandconnectingblocksmustbeproperlyidentifiedbydestination.

    Allrisercablesshallbeproperlymarked.Markeristobeaflatpieceofaluminumorstainlesssteel.Thismarkingshallbepermanentand

    indicate:

    TheOrigination(Cableitisfeedingfrom).

    TheDestination(Telecommunicationsroomitisfeeding).

    Allvoiceanddatacablepairsinrisercablesortheentrancecablemustbeterminatedonaconnectingblockandidentified.

    CABLE

    GENERAL

    A50percentgrowthfactorshallbebuiltinandprovidedforunlessotherwisespecified;consequentlyanycableworkthatpertainsto

    telecommunicationsmustbedesignedand/orapprovedbyCommunicationsSystems.

    Eachtelephoneanddatacableshallhaveaminimumoffour(4)pairs;insomecasesalargercablemayberequired.CommunicationsSystems

    willinformthecontractorinsuchcases.

  • 8/4/2019 Longwood Wiring Standards

    11/38

    11

    Plenumcommunicationscablemayberunexposedaboveceilings,providedthiscablingissupportedindependentofotherutilities,suchas

    conduits,pipes,ceilingsupportsystems,andnotlaiddirectlyontheceilingpanels.UseofPlenumcablemustbeapprovedbyCommunications

    Systems.

    AllcablesfromtheBDFmustbe100percentterminatedineachIDFifapplicableandapprovedbyCommunicationsSystems.

    Tofacilitatefuturecableinstallationsanewpullstring,tiedoffatbothends,shallbeinstalledinconduitsimultaneouslywiththepullinof

    cable.

    Ingeneralallcommunicationwiresshallbecopper,#24AWGminimum,Level5forvoice,level6fordata,howeveruserneedsshalldictatethe

    cabletypeandlevel.ThetypeandlevelofwirerequiredmustbeobtainedfromCommunicationsSystems.TheUniversityisutilizingtheAMP

    productlineasthestandardforcampus.

    RACKSANDPANELS

    GENERAL

    Undernocircumstancesshallelectricaloranyotherutilitypanelbelocatedinthecommunicationsroom.Allwallsaretobeusedforblocksand

    terminations.

    Eachdistributionpanelshallhavea3/4inchfiretreatedplywoodbackboardwhichhasbeenpaintedwithtwo(2)coatsoffireresistantpaintof

    aneutralcolor.Thebackboardwillfacilitateinstallationofterminalblocksandassociatedwiring.Eachdistributionpointshallbeidentifiedasabuildingentranceand/orafloorservicepanel.

    Junctionboxesaretobeprovidedonanyconduitrunlongerthan100feet.

    AllvoiceterminationsattheBDF(BuildingDistributionFrame)willbeonstandardraised66M150typeconnectingblocks.Allterminationsat

    theIDF(IntermediateDistributionFrame)willberaised66M150typeconnectingblocks.

    WIREDRESS

    VOICESTATIONWIRESOrganizeandlabelthecablesinnumericroomnumberorder.Forexample;withmultipleoutletslabelclockwiseas

    youentertheroom;A,B,Cor1,2,3.

    Individuallybundleandroutetheunshieldedvoicepairgroupstoeachofthevoicepunchdownblockcolumns,locatedonthewiringsurface

    labeled"Voice".

    TYPEIANDTYPEIISTATIONWIRESDropfromcommunicationsroomcabletraybehindpatchpanelrack.Organizeandlabelthecablesin

    numericroomnumberorder.WhenusingTypeII,separateshieldedandunshieldedpairs6inchesbelowcabletray.Insurethattheshielding

    braiddoesnotcontactthecabletray.IndividuallybundleandroutetheTypeIIunshieldedtwistedpairstothepunchdownblockcolumns,

    locateddirectlybehindtherackorinarackpatchpanel.

    RACKANDPATCHPANEL

    Mountan8footNewtonrack,partnumber4008B9(EIAstandardorequivalent),intheindicatedposition.Positiontheracktomaintaina

    minimumofthree(3)feetclearancefromthefrontoftheracktothefrontfacingroomwallandthree(3)feetclearancefromtherearofthe

    racktotherearfacingroomwall.Ifarowofracksistobeinstalledinacommunicationsroom,maintainaminimumoftwo(2)footclearance

    fromtherightmostorleftmostracktotheopposingwall.AnchorrackstothefinishedfloorwithaNewtonrackmountingkit.Groundtherack

    tothecommunicationsroomgroundingbussbarwith#6AWGcopperwire.

    Mountthepatchpanel(withgroundingtower)inthetopmostrackposition.Layoutthepatchpanelinascendingroomnumberorderfromtop

    lefttobottomright.

    Routetheshieldedpairsthroughthepatchpanelwireguidesandthroughthegroundingtowershield,fasteningclampsenroutetothe

    connectoronthefaceofthepatchpanel.

  • 8/4/2019 Longwood Wiring Standards

    12/38

    12

  • 8/4/2019 Longwood Wiring Standards

    13/38

    13

    3TELECOMMUNICATIONSROOMSANDCABLETERMINATION

    RACKSANDPANELS,CONTINUED

    PUNCHDOWN

    Laydownallstationwirepairsinnumericroomnumberorderfromlowestroomnumberatthetopleftmostpositiontothehighestroom

    numberatthebottomrightposition.UseSiemonsblockmountingbrackets,partnumber89B,witheveryinstalledblock.Routeallcablestobe

    puncheddowntotheseblocksunderthemountingbracket.Fastenthemountingbracketstotheplywoodwiringsurfacewith#10screwsx3/4

    inch.

    Voice4PairUseSiemons,partnumber66MI50,white50pair66blockswith#89Bmountingbrackets.Locatethepunchblocksonthe

    plywoodwiringsurfaceintheareadesignatedasVoiceStationWires.Useoneblockwidthspacingbetweenadjacentrowsofblocksandlay

    downamaximumoffourblocksinacolumn.Punchdownthefour(4)unshieldedpairsontheblockasindicatedontheaccompanyingdiagram.

    Data4PairAlldatawiringterminatesdirectlytothepatchpanels.

    ReferanyquestionsspecificallynotaddressedinthisdocumenttoCommunicationsSystems.

  • 8/4/2019 Longwood Wiring Standards

    14/38

    14

    4VOICEANDDATAOUTLETSINSIDEPLANTWIRINGANDRACEWAYS

    ContentsSUBJECTPAGE

    GENERAL.............................................................................................................................13

    OVERVIEW..........................................................................................................................13

    LABELING............................................................................................................................13

    WIRING...............................................................................................................................13

    OUTLETLOCATION.............................................................................................................14

    LOCATIONSANDQUANTITIES.............................................................................................14

    OUTLETINSTALLATION.......................................................................................................14

    MOUNTING.........................................................................................................................14

    CONDUIT.............................................................................................................................15

    GENERAL.............................................................................................................................15

    CONDUITCAPACITY.............................................................................................................15

    LADDERTRAYS....................................................................................................................16

    GENERAL............................................................................................................................16

    MOUNTING.........................................................................................................................16

  • 8/4/2019 Longwood Wiring Standards

    15/38

    15

    4VOICEANDDATAOUTLETSINSIDEPLANTWIRINGANDRACEWAYS

    GENERALOVERVIEW

    AlltelephoneanddatastationwiringshallbecontinuouswirefromtheIDFtothecommunicationoutlet.

    Thedepartment'spresentandfuturerequirementswilldeterminetheneedsofmultiplejackoutlets.Finalapprovalforthelayoutofjack

    outletsshallrestwithCommunicationsSystems.Duringtheprogrammingstageinformationwillbeprovidedtotheconsultantforinclusionin

    theproject.

    ThefollowingterminationdevicesareacceptableAMP.ConsultCommunicationsSystemsforfinalapprovalofalternatedevices.

    AllvoiceoutletsshallterminateinUSOCRJ11(X)six(8)conductormodularjackassembliesandextrapairsshallbemarkedasspareatits

    locationontheterminalblock.

    WirecolorcodingshallbeperAT&T258andWesternElectricspecifications.

    Thetotalwirepathlengthfromtheoutlettothecommunicationsroommustnotexceed275feetinanycase.Thisisimportanttomeet

    EthernetrequirementsofIEEE802.3.

    LABELING

    Eachendofallcablesandallpairswillbelabeledattheirterminationlocations.

    Alljacksshallbemarkedatthepointofmanufacturerwithengravedlettersand/orsymbolsindicatingthatthetopjackisvoiceandthatthe

    bottomjackisdata.Horizontalmountedjackpositionsshallbedataontheleftandvoiceontheright.Alljackswillbemarkedalphabetically

    andbeginclockwisearoundtheroom,e.g.throughthemainentrancetotheleft,jacksshallread102A,102B,etc..

    Allmodularjackassembliesmustbelabeledandidentified.

    Allcommunicationoutletsnotinuse,eitherwiredorempty,musthaveablankplatecoveringtheoutletandthewireshallbetaggedand

    identifiedwiththelocationoftheoriginatingIDForBDF.Whenacontractorprovidesthewiring,an"AsBuilt"drawingwithallroomjacks

    identifiedmustbeprovided.

    WIRING

    Thefollowingcableandwiring,becauseoftheirdurabilityandreliabilityamongcertifiedbrands,arerecommendedforuseattheLongwood

    University.OnlywiththeapprovalofCommunicationsSystemscananalternativeorequivalentbeused.Asampleoftheequivalentcableor

    wiremustaccompanytherequest.

    Voice4PairUseonlyAMPLevel5wire,grayincolor.

    Data4PairUseonlyAMPLevel6wire,blueincolor.

  • 8/4/2019 Longwood Wiring Standards

    16/38

    16

    4VOICEANDDATAOUTLETSINSIDEPLANTWIRINGANDRACEWAYS

    OUTLETLOCATION

    LOCATIONSUnlessotherwisespecified,thefollowingnumberofoutletsshallbeinstalledinthefollowinglocationANDquantities,depending

    onthefunctionforthatparticularoffice/room.

    QUANTITIES

    Faculty/AdministrativeOffices:Eachofficeshallhavetwo(2)communicationoutletsperdesignatedoccupant.

    Clerical/StaffOffices:Two(2)communicationoutlets,one(1)atthelocationofeachdeskandone(1)additionaloutletforafacsimileor

    printer.Eachadditionalstaffmemberinthesameareawillrequireadditionaloutlets.

    ConferenceRooms:Aminimumoffour(4)communicationoutletsperroom.One(1)outletshallbelocatedoneachwall.Roomswithmore

    than500squarefeetshallhaveadditionaloutletsequallyspacedoneachwall.Theseoutletsarenottobelocatedonentryorwindowwalls.

    Someareasmayrequiretheconferencetabletobewired.

    Laboratories/GraduateStudentOffices:Two(2)wiredcommunicationsoutletsforeveryoccupant.Additionaloutletrequirementswillbe

    determinedbasedonsizeandinthedesignphaseoftheproject.

    Classrooms/LectureHalls/Auditoriums:One(1)tofour(4)communicationoutletsdependingonroomandstudentoccupancysize.

    NOTE:*Threeoutletsinthefrontofroomattheinstructionpodium.Wirelessconnectionportswillneedtobeaboveceilinggrid.Numberof

    portsrequiredwilldependonoccupancy.Standardis1portpertwentyoccupants.

    ResidenceHalls:One(1)communicationoutletperoccupantofeachroom.Thelocationwillbedeterminedduringdesignstagesofthe

    project.

    StorageAreas:One(1)communicationoutletperroom.Two(2)outletsforroomsover500squarefeetandone(1)additionaloutletforeach

    additional2000squarefeet.

    JanitorClosets:Someclosetsmayrequirecommunicationsoutletsfortelephones,computersortimereportingdevices.

    OUTLETINSTALLATION

    MOUNTING

    UseadualgangoutletboxsimilartoSteelCity,partnumber721713/4.Whenmountingtheoutletboxinasteelstuddedwall,useaback

    brace.

    UseonlySteelCityplasterrings,partnumber72C13,(singlegang)or72C17(doublegang).Itisabsolutelycriticalthattheinsideopeningarea

    matchtheoutletinstallationenclosure.

    Theplasterringsmustbelevelandpositionedflushwiththefinishedsurface.

    Forwalltelephoneonlyoutletsuseasinglegangplasterring.

    Outletsaretobemountedatstandardindustryheightsandpositions,unlessotherwisespecifiedbyCommunicationsSystems.Standard

    mountingheightofcommunicationoutlets:

    Desk18inches,AFF.(Dualgangplasterring)

    Wall60inches,AFF.(Singlegangplasterringonly)

  • 8/4/2019 Longwood Wiring Standards

    17/38

    17

    Handicappedwallmount48inches,AFF.(Singlegangplasterringonly)

    CATVisnormallyinstalledattheheightofTVmounting.Useonlyasinglegangplasterring.

    Note:ElectricaloutletsshallbeprovidedforTVandprojectiondevices.

    CONDUIT

    GENERAL

    AllconduitworkshallmeetthespecificationsofNationalElectricalCodeconduitinstallations.

    Allvoice,dataandvideowiringinsideroomsshallbeprotectedbymetallicconduitorothermeanssuchaswiremoldortroughsinthefloor.

    PVCconduitandplasticmoldingarenotacceptableexceptincausticenvironments.Aluminumisnotacceptableincausticenvironments.EMT

    conduitshallbeusedforallinteriorwiring.Allconduitistobeconcealed.

    Nomorethananequivalentofthree(3)90degreebendsareallowedinarunbetweenjunctionboxesorpullboxes.

    Theuseofplenumcableinsteadofconduitshallbedeterminedonacasebycasebasis.CommunicationsSystemsmustbecontactedfor

    approval.

    AllEMTfittingsshallbecompressiontype.SetscrewtypefittingsareNOTacceptableonconduitlessthan21/2inchesindiameter.

    Inmajorrenovationandnewconstructionprojects,thecontractshallincludeprovisionsforinstallationoffour(4)riserconduits(4inches

    minimumdiameter)fromtheBDFtoeachIDF.Apullstringandappropriatejunctionpullboxshallalsobeprovidedineachconduitrunto

    facilitatefutureinstallationofcable(s).

    Allconduitinslabshallbeaminimumof11/4inchesgalvanizedsteelwiththreadedfittings.

    AllexceptionsshallbedeterminedduringthedesignstageoftheprojectandshallbesubjecttotheapprovalofCommunicationsSystems.

    Allsleevesmustprotrudefour(4)inchesAFFandbelowandbecappedatbothends.

    CoordinatewithCommunicationsSystemsforthenumberofconduitsenteringthefacility.

    Nohorizontalconduitrunshallbemorethan100feetbetweenpullboxes,perNECrequirements.

    Conduitfortelephoneorcomputeroutletsshallbeterminatedinadualgangbox.SteelCity,partnumbers521511,721511,52C17or72C

    17forone(1)inchwithdualgangplasterringand521513/4,721513/4,52C13or72C13,for3/4inchwithsinglegangplasticring.

    Allcommunicationsoutletsshallbeone(1)inchconduit,withanabsoluteminimumofbends,fromtheoutlettothecabletray,wirewayor

    homerundirectlytothecommunicationsroom.A3/4inchconduitisacceptableforsinglewallphoneoutlets.Pullboxesmustbeinstalledevery

    270degreesor100feetoftheconduitrun.Useonlycompressionfittingsateveryjoint.

    Inthecaseofaconduitterminatinginacabletray,theconduitmustbemechanicallyfastenedtothesideofthecabletrayandtheconduit

    endatthetraymustbeterminatedinagroundingbushingandwirebondedtothetray.Note:Ametalstrapisnotacceptableasameansof

    groundingtheconduittoacabletray.

    Inthecaseofconduitterminatinginthecommunicationsroom,theconduitmustbeterminatedwithagroundingbushingandwirebonded

    totheroomgroundbusbar.

    CONDUITCAPACITY

    Conduitcapacitywillbedependentonnumberandtypeofcablesutilized.Cablejackethasvaryingthicknesswhichwillminimizethenumber

    ofcablesinstalled.

  • 8/4/2019 Longwood Wiring Standards

    18/38

    18

    LADDERTRAYS

    GENERAL

    Allladdertraysshallbedesignedtoaccommodatevoice,video,anddatacabling;consequentlyanycableworkthatpertainsto

    telecommunicationsmustbedesignedand/orapprovedbyCommunicationsSystems.

    Theminimumdimensionsforaladdertrayshallbe12incheswideand4inchesdeep.

    Contractdocumentsshallshowcrosssectionofthecommunicationwirewayorcabletray.Thedrawingmustshowreferencetootherutilities

    inthebuilding.

    Considerationmaybegivenforinstallationofothertypesofcablesinaladdertraytopreventinterferenceonunshieldedcables.Locationof

    suchinstallationshallbeapprovedbyCommunicationsSystems.

    Laddertray(cabletray)orwirewayistobesupportedwithallthreadrodsinatrapezeformasdiagrammed.Supportsforcabletrayslarger

    than12inchesinwidtharetobeinstalledatamaximumdistanceoffive(5)feetapartoraccordingtothemanufacturersspecifications,

    whicheverismorestringent.Supportsforcabletrays12inchesorlessmaybefartherapartbutmustmeetthemanufacturersinstallation

    requirements.Asinglesupportisnotacceptable.

    CommunicationsSystemswillnotinstallanycableorperformanyworkuntilallinstallationsaremadetocomplywithspecifications.

    MOUNTING

    Cabletraysmustbeaminimumofone(1)footfromtheceilingandaminimumofeight(8)feetAFF.Traysaretobeloopedtheentire

    parameteroftheroom.

    Installsweepingfactory90'sforallturns.Useendoftraytermination'swherewiredropsdowntowallstopreventabrasionsandcutsfrom

    metaltrayedges.Useatrapezecabletraymountingmethodsuspendedby1/2inchallthread.Fastenallthreadtoceilinganchors,allowingno

    bendsinallthread.Supportthecabletrayinthismannerateverysectiontosectionjunctionandatfive(5)feettosix(6)feetintervals(mid

    span)betweenjoints.Innocaseshallthetraybecloserthaneighteen(18)inchesfromthestructuralceiling,ductsorpipes,consideringall

    otherpossibleobstructions.Aminimumoftwo(2)feetdistancefromlighting,especiallyfluorescentlighting,isrequired.

  • 8/4/2019 Longwood Wiring Standards

    19/38

    19

    5TELEVISIONCABLEANDOUTLETS

    ContentsSUBJECTPAGE

    OVERVIEW.........................................................................................................................18

    GENERAL............................................................................................................................18

    LABELING............................................................................................................................18

    CABLE.................................................................................................................................18

    OUTLETS..............................................................................................................................18

    VIDEO/PROJECTIONDEVICES,CABLINGANDOUTLETS.......................................................18

    GENERAL.............................................................................................................................18

  • 8/4/2019 Longwood Wiring Standards

    20/38

    20

    5TELEVISIONCABLEANDOUTLETSOVERVIEW

    GENERAL

    Forfurtherdetailedspecificationsregardingtelevisioncables,contacttheDepartmentofInstructionalTelecommunications.

    LABELINGTelevisioncablesaretobeclearlyidentifiedviaapaintedsectionorbyuseofconduitstickersindicatingeachconduitrun;Yellow=

    television.

    CABLETelevisionoutletcableshallbeRG6/Utypequadshieldedcoaxial75ohm,Belden,partnumber1189Aorequivalent.

    TelevisionrisercablesinmultistorybuildingsorbuildingswithfirstfloorIDF'sshallbe75ohm'sandcabledesignmustbeobtained.Asarule

    theminimumacceptablerisercableistype500coaxialcable.ObtainallcablesizesfromCommunicationsSystems.

    Allcableshallberunwithinconduits.

    Eachoutletshallbehomeruntothenearestcommunicationsroom.

    VIDEO/PROJECTIONDEVICES,CABLINGANDOUTLETS

    GENERAL

    CommunicationsSystemsorInstructionalTelecommunicationsshallprovidethespecificationsandcablepartsforprojectiondevicesand/or

    monitors.

    Projectiondevicesareeitherceilingortabletypemounts.Ineachcasetheconduitmustbeconnectedtothefrontoftheclassroomatthe

    podiumorinstructorstation.

  • 8/4/2019 Longwood Wiring Standards

    21/38

    21

    6PROTECTION,GROUNDINGANDBONDING

    ContentsSUBJECTPAGE

    LIGHTNINGPROTECTION..................................................................................................20

    GENERAL...........................................................................................................................20

    MATERIALS.......................................................................................................................20

    GROUNDING.....................................................................................................................20

    GENERAL..........................................................................................................................20

    BONDING.........................................................................................................................20

    GENERAL...........................................................................................................................20

    DRAWINGS........................................................................................................................20

  • 8/4/2019 Longwood Wiring Standards

    22/38

    22

    6PROTECTION,GROUNDINGANDBONDING

    LIGHTNINGPROTECTION

    GENERAL

    Lightningprotectionoftelecommunicationsfacilitiesisessential.Whilefederalandstatestandardsmustbeadheredto,localconditionsmay

    requireadditionalinvestigationsand/ormodificationstomeetsite,equipment,environmentalorsafetyrequirements.

    NECArticles250"Grounding"and800"CommunicationsCircuits"covergeneralrequirementsforgrounding,bondingandprotectingelectrical

    andcommunicationscircuits.NFPA78"LightningProtection"addresseszoneprotectionandotheritemswhicharebeneficial.

    Allcablingandwiring(includinggrounding)withinthebuildingandentrancefacilitieswithprotectionfromlightningandpowerfailurevia

    groundingandbondingwillbeaccomplishedundertheconstructioncontract.

    MATERIALS

    Thethreemostfrequentlyusedlightningprotectorsarelistedbelow.ContactCommunicationsSystemsforadeterminationofthemost

    appropriateprotectionforthecondition.

    AT&TProtectionHousingAT&T,partnumber189ECT1100,thelastthree(3)digitsvarydependingonpairsize,i.e.,100=100pair

    protector.TheprotectionmoduleshallbeCookElectric,partnumber303855.

    KroneProtectionHousingKrone,partnumber6637144014/25for100pairprotection,includesprotectionmodules.Krone,partnumber

    6637148018/25for200pairprotection,includesprotectionmodules.

    UseCookElectric,partnumber500LCGXforsingledropsof6pairorless.

    GROUNDING

    GENERAL

    Allgroundingshallusesinglepointschemesfromthebuildingmaintransformer,withaminimumof#2AWGsolidcopperwirewhichhasbeen

    testedtoamaximumof0.5ohms.

    Allshieldsshallbebondedtoacommonground.

    AllrisercablemustbeshieldedandproperlygroundedtothebuildinggroundthroughgroundingfacilitiesprovidedattheBDF.

    AllTypeIIstationcablemustbegroundedattheIDFbyusingaproperlysizedgroundwire(#10orlarger)whichisgroundedattheBDFwitha

    connectiontothebuildingearthground.

    TheshieldoftherisercableisnotapropergroundfortheIDF.

    BONDING

    GENERALBondingistobedurable,strongandoflowimpedancetoassureelectricalcontinuity.

    Allconduitterminatingtocabletraysandwirewaysshallbemechanicallyfastened,equippedwithgroundbushingsandwirebondedtothe

    tray.Thecabletrayorwirewayshallbegroundedtothemainbuildinggroundingsystemwithawirenotsmallerthan#2AWGcopper.

    Aresistanceof.001ohmorlessindicatesahighqualityjunction(BICSI).

    ReferanyquestionsspecificallynotaddressedinthisdocumenttoCommunicationsSystems.

  • 8/4/2019 Longwood Wiring Standards

    23/38

    23

    7INSPECTIONANDTESTING

    ContentsSUBJECTPAGE

    INSPECTIONOFWORK.......................................................................................................22

    GENERAL............................................................................................................................22

    TESTING..............................................................................................................................22

    GENERAL............................................................................................................................22

    LOCALAREANETWORK......................................................................................................22

  • 8/4/2019 Longwood Wiring Standards

    24/38

    24

    7INSPECTIONANDTESTING

    INSPECTIONOFWORK

    GENERAL

    CommunicationsSystemsdesigneesshallhaveaccesstoconstructionsites.

    ToenableCommunicationsSystemstoinspecttelecommunicationsfacilitieswork,thecontractormust:

    Provideaprogressschedulewiththeinstallationoftelephoneracewaysandspacesshownasaseparateitem.

    ImmediatelynotifyCommunicationsSystemsofanychangeinarchitecturaldrawingsand/orplansaffectingtelecommunications.

    Provideproperaccessandfacilitiesforinspections.

    NotifyCommunicationsSystemswhenanyworkisreadyforinspection.

    AllundergroundworkmustbeinspectedandapprovedbyCommunicationsSystemsbeforethesiteiscoveredwithdirtor

    concrete.Failuretohavetheworkinspectedshallresultinuncoveringtheareaatthecontractor'expense.

    ThecontractorshallprovideafinalcheckoutcertificationletterandinspectionreportstoCommunicationsSystemsonalltelecommunications

    work.

    TESTING

    GENERAL

    ThecontractorshallsubmittoCommunicationsSystems,adetailedtestproceduretobeusedforeveryproject.Allcablesshallbetestedfor

    length,attenuation,impedance,groundsshorts,continuityofcommunicationsconductorsandshields.

    Uponcompletion,testresultsshallbesubmittedtoCommunicationsSystemsforfinalapprovalandacceptanceandmadepartofthe

    document.Thecontractorshallguarantee100percentgoodpairsonallcables.

    Communicationswillperformnecessarytestingbeforeacceptingajob.Failureduringtestingwillresultinnewcableinstallationatthe

    contractorsexpense.

    LOCALAREANETWORK

    AllLocalAreaNetworkscablesmustbetestedtoconformwith10BaseTstandards.Alltestsshallbeperformedattherateof10Megabitsand

    willbetestedforthefollowing:

    Continuity

    Length

    Loss

    Resistance

    Crosstalk

    Noise

    RMS

    Impulse

  • 8/4/2019 Longwood Wiring Standards

    25/38

    25

    ActiveHub

    NetworkMonitor

    TestresultsaretobeprovidedtoCommunicationsSystemspriortoacceptanceofthebuilding.

  • 8/4/2019 Longwood Wiring Standards

    26/38

    26

    8FIRESTOPPING

    ContentsSUBJECTPAGE

    OVERVIEW.........................................................................................................................25

    GENERAL............................................................................................................................25

  • 8/4/2019 Longwood Wiring Standards

    27/38

    27

    8FIRESTOPPING

    OVERVIEW

    GENERAL

    ProvidefireproofsealsinaccordancewiththeNationalFireProtectionAssociation(NFPA)andtheNationalElectricCode(NEC),Article30021.

    FirestopallpenetrationsinaccordancewiththecurrenteditionoftheNationalElectricalCode.

    Firetreatedplywood,3/4inchthickwhichhasbeenpaintedwithtwo(2)coatsoffireresistantpaintofaneutralcolor,mustbemechanically

    fastenedtothewallofeachroom.Thefiretreatedplywoodistobeginatfour(4)inchesAFFandendat8feet,4inchesAFF.

  • 8/4/2019 Longwood Wiring Standards

    28/38

    28

    9LOCALAREANETWORKS

    ContentsSUBJECTPAGE

    OVERVIEW.........................................................................................................................27

    GENERAL............................................................................................................................27

    DETERMININGREQUIREMENTS........................................................................................27

    WIRINGTYPE.....................................................................................................................27

  • 8/4/2019 Longwood Wiring Standards

    29/38

    29

    9LOCALAREANETWORKS

    OVERVIEW

    GENERAL

    Allconnectionsmustbeclearlylabeledatbothends.

    Useaone(1)inchhomerunconduitfromtheoutlettothecabletray,wirewayordirectlytothecommunicationsroom,withpullboxesevery

    100feet.Inthecaseofanoutlet'sconduitterminatinginacabletray,theconduitmustbemechanicallyfastenedtothesideofthecabletray

    andtheconduitendatthetraymustbeterminatedinagroundingbushingandwirebondedtothetray.

    Thetotalwirepathlengthfromtheoutlettothecommunicationsroom,includinglossduetotermination's,mustnotexceed275feetfromthe

    IDFinanycase.

    DETERMININGREQUIREMENTS

    ConsultCommunicationsSystemsDataCommunicationsandLocalAreaTechnicalReferencebooksfordetails.

    WIRINGTYPE

    AMPcategory6ewiringisutilizedfordatadrops.WirejacketmaybeplenumornonplenumdependinguponHVACtype.Terminationwillbe

    AMPjackswith568bstandards.

  • 8/4/2019 Longwood Wiring Standards

    30/38

    30

    10FIBEROPTICTECHNOLOGY

    ContentsSUBJECTPAGE

    OVERVIEW........................................................................................................................29

    GENERAL............................................................................................................................29

    INSTALLATION...................................................................................................................29

  • 8/4/2019 Longwood Wiring Standards

    31/38

    31

    10FIBEROPTICTECHNOLOGY

    OVERVIEW

    GENERAL

    AllfiberopticplanningandinstallationshallbeapprovedbyCommunicationsSystems.Wheninstallingfiberopticcable,itshallbepulledina

    protectivelinerinsidetheconduitandprotectedinsidethemanhole,toallowfutureuseofconduitandalsopreventdamagetothecable.The

    linercouldbeextended,howeverthismayvaryduetocircumstances.

    Allnewoutsideplantconduitshallincludeatleasttwo(2)conduitsleevedforFiberOpticsoruseTeleDuct.Properpartsaretobeused,

    consultCommunicationsSystems.Innerductsareonlyusedonexistingfacilities.

    Allcablethatistobeconnectedordisconnectedfromthecampustelecommunicationsnetwork;telephone,data,video,toinclude,LocalArea

    Network,WideAreaNetwork,CATVcableandfiberoptics,shallbedonebyCommunicationsSystems.

    ContactCommunicationsSystemsforthetypeoffiberopticcabletobeused.

    INSTALLATIONAllfiberopticcablesshallbeterminatedviaaSTConnectorandproperlyconnectedtothedistributionpointsinafiberpanel.

    Jumperorpatchcordsaretobeusedtoconnectdifferentpairsofcablestogetherforcontinuationofservice.

  • 8/4/2019 Longwood Wiring Standards

    32/38

    32

    11MISCELLANEOUSANDSPECIALSITUATIONS

    ContentsSUBJECTPAGE

    HANDICAPPEDACCESS......................................................................................................31

    GENERAL............................................................................................................................31

    PUBLICPAYPHONES..........................................................................................................31

    MATERIALS..........................................................................................................................31

    SWIMMINGPOOLS..............................................................................................................31

  • 8/4/2019 Longwood Wiring Standards

    33/38

    33

    11MISCELLANEOUSANDSPECIALSITUATIONS

    HANDICAPPEDACCESS

    GENERAL

    Allconduitoutletsforhousephones,corridorphones,courtesyphonesandpayphonesaretomeetheightandlocationrequirementsinthe

    AmericanwithDisabilitiesActforhandicappedaccess.Thisstandardonlyreferstotelecommunicationrequirements.Allotherutilitiesarethe

    responsibilityofthedepartmentinvolved.

    PUBLICPAYPHONES

    TT,TextTelephones(formallyTDD),mustbeaccessibletohandicappedindividuals.

    Theheightofthecoinslotshallbe48inchesforallinstallations.

    Ifatotalnumberoffour(4)ormorepublicpaytelephones(includingbothinteriorandexteriorphones)isprovidedatasite,andatleastone

    (1)isinaninteriorlocation,thenatleastoneinteriorpublictexttelephoneshallbeprovided.

    MATERIALS

    SWIMMINGPOOLS

    PVCconduitandplasticmoldingarenotacceptableexceptincausticenvironmentssuchasswimmingpools.Aluminumisnotacceptablein

    causticenvironments.

    Whenpoolsidetelephoneserviceisdesiredandthereisnobuildingneartohangattachmentson,installapedestalandruna11/4inchconduit

    tothelocation.Iftheconduitlengthislongerthan100feet,installapullboxaccordingtoNEC.

  • 8/4/2019 Longwood Wiring Standards

    34/38

    34

    12CODES,STANDARDSANDREGULATIONS

    ContentsSUBJECTPAGE

    OVERVIEW.........................................................................................................................33

    GENERAL............................................................................................................................33

    AGENCIES............................................................................................................................33

  • 8/4/2019 Longwood Wiring Standards

    35/38

    35

    12CODES,STANDARDSANDREGULATIONS

    OVERVIEW

    GENERAL

    Todesignfacilitiesforaneffectivetelecommunicationssystem,thedesignerandinstallermustbefamiliarwithnationalandlocalregulations.

    Boththedesignerandthecontractormustbefamiliarwithandadheretothestandardsofthetelecommunicationsandbuildingindustries.

    AGENCIES

    Thefollowingagenciesandtheircodes,standardsandregulationsshallgovernalltelecommunicationsworkperformedattheUniversity.

    ANSIAmericanNationalStandardsInstitute

    BICSIBuildingIndustryConsultingServiceInternational

    BOCABuildingOfficialsandCodeAdministrators(StandardBuildingCode)

    EIAElectronicIndustriesAssociation

    FCCFederalCommunicationsCommission

    ICBOInternationalConferenceofBuildingOfficials(UniformBuildingCode)

    IEEEInstituteofElectricalandElectronicEngineers,Inc.

    NBCNationalBuildingCode

    NFPANationalFireProtectionAssociation

    NECNationalElectricalCode

    TIATelecommunicationsIndustryAssociation

    ULUnderwritersLaboratories

    LongwoodUniversityWiringandCablingGuidelines

    CommonwealthofVirginiaCommunicationsStandards

  • 8/4/2019 Longwood Wiring Standards

    36/38

    36

    13GLOSSARYANDACRONYMS

    ContentsSUBJECTPAGE

    GLOSSARYANDACRONYMS..............................................................................................35

  • 8/4/2019 Longwood Wiring Standards

    37/38

    37

    13GLOSSARYANDACRONYMS

    AFFAboveFinishedFloor

    AWGAmericanWireGage

    BDFBuildingDistributionFrame

    CDFCombinedDistributionFrame

    COMMUNICATIONSSYSTEMSCommunicationsandTechnologyServices

    DOWELEDDrilledholeforrebar

    ECLTypeoftokenringconnector

    EMTElectricalMetallicTubing

    FCFootcandle

    HVACHeating,VentilationandAirConditioning

    HzHertz

    IBMInternationalBusinessMachines

    IDFIntermediateDistributionFrame

    LANLocalAreaNetwork

    OHMUnitofresistance

    PBXPrivateBranchExchange

    PVCTypeofconduit

    SFSquarefoot

    TTTextTelephone(formallyTDD)

    WANWideAreaNetwork