6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 1
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.1: 132 kV Switchyards
132 kV Disconnector with Earthing Switch
manufacturer
applicable standard IEC 62271-102
type outdoor type
type of operation center break
highest system voltage kV 145
rated normal current A 1250
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated short time current (1s) kA 31,5
rated short-circuit making current kApeak 80
power supply V 110 DC/230 AC
minimum creepage distance mm 6525
132 kV Busbar Disconnector
applicable standard IEC 62271-102
type outdoor type
type of operation two column rotary
highest system voltage kV 145
rated normal current A 1250
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated short time current (1s) kA 31,5
rated short-circuit making current kApeak 80
power supply V 110 DC/230 AC
![Page 2: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/2.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 2
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.1: 132 kV Switchyards
132 kV Circuit Breaker
manufacturer
applicable standard IEC 62271
type of circuit breaker outdoor type
type of arc quenching medium SF6
highest system voltage kV 145
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated normal current A A 1250
rated short-circuit breaking current kA 31.5
rated peak withstand current kApeak 80
number of tripping coils 2
number of closing coils 1
rated operating sequence (three phase auto reclosing) 0 - 0.3 s – CO - 1 min – CO
maximum breaking time msec. 60
minimum creepage distance mm 6525
power supply V 110 DC/230 AC
first-pole-to-clear factor 1.3
drive - 1 pole
type of drive - spring type
![Page 3: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/3.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 3
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.1: 132 kV Switchyards
132 kV Current Transformer
manufacturer
applicable standard IEC 60044-1
type
highest system voltage kV 145
rated short time current (1s) kA 31,5
rated primary currents:
for line feeders A 600/1200
for 45 MVA transformer feeders A 100/200
number of cores
for measuring purpose 1
for protection purposes 3
rated secondary currents:
for measuring A 1
for protection A 1/1/1
rated burden 30
for measuring core VA 15
for protection core VA 60
accuracy class
for measuring - 0.5 M 5
for protection - 5 P 20
minimum creepage distance mm 6525
![Page 4: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/4.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 4
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.1: 132 kV Switchyards
132 kV Capacitive Voltage Transformer
manufacturer
applicable standard IEC 60 044-5
type Outdoor type
rated primary voltage kV 132/√3
rated secondary voltages (independent)
kV 0.11/√3
kV 0.11/3
rated output VA/VA 150/150
accuracy class:
for measuring 0.5
for protection 5 P
minimum creepage distance mm 6525
132 kV Gapless Zinc-Oxide Lightning Arrester
manufacturer
applicable standard IEC 600 99/4
type Outdoor type
rated continuous voltage kV rms 120
rated discharge current kA 10
rated frequency Hz 50
arrester classification heavy duty
minimum creepage distance mm 6525
Lightning Arrester Discharge Counter
type Outdoor type
counter indication Digital
protection class IP54
number per 3 arresters 1
![Page 5: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/5.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 5
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.1: 132 kV Switchyards
Busbar Conductors
type / material 2 x AAAC 400
rated current (with max. allowed 30 K temperature rise above max. ambient temperature)
A 1250
branch connections 1 x AAAC 400
![Page 6: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/6.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 6
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Electrical Characteristic
type -
nominal voltage kV 132
rated voltage kV 145
rated frequency Hz 50
Basic Data
manufacturer place of manufacture manufacturer reference/designation
-
- -
lightning impulse withstand voltage kV(peak) 650
power frequency withstand voltage kV(rms) 275
peak withstand current kA(peak) 80
short time withstand current (1sec) kA(rms) 31.5
total thermal losses at full load kW
maximum guaranteed gas loss from any compartment % per annum
< 1
protection class of switchgear cubicles - IP 52
safety requirements as per 1.5.3 of B1 - Yes
single-phase enclosure as per 1.5.7 of B1 - Yes
material of encapsulation: - yes
aluminum alloy - Yes/no
or
stainless steel - Yes/no
Manufacture and tests shall comply with but shall be not limited to the following IEC standards as well as provisions in sections A7 and B1 of this tender:
bus bars IEC 60517, 60094 - Yes
circuit breakers IEC 62271-100 - Yes
current transformers IEC 60044-1 - Yes
voltage transformers IEC 60044-2 - Yes
surge arrestors IEC 60099-4, 99-1, 99-3 - Yes
![Page 7: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/7.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 7
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Main dimensions (per feeder)
manufacturer place of manufacture manufacturer reference/designation
- - -
height x width x depth m
weight of feeder t
weight of heaviest single part t
Busbars
manufacturer place of manufacture manufacturer reference/designation
- - -
rated current A 2000
cross-section of busbar conductor mm2
busbar material - aluminum
single-phase enclosure -
material of encapsulation - yes
aluminum alloy Yes/no
or
stainless steel Yes/no
diameter of busbar duct housing mm
rated pressure of SF6 gas at 40°C Kpa
maximum and minimum admissible pressure of SF6 gas at 40°C
Kpa
volume of largest busbar compartment m3
puncturing time msec 500
configuration - single bus (with bus coupler)
![Page 8: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/8.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 8
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Feeders (outgoing, incoming)
manufacturer place of manufacture manufacturer reference/designation
-
- -
rated current A
cross-section of bus-duct conductor mm2
volume of largest feeder compartment m3
Circuit Breakers
manufacturer place of manufacture manufacturer reference/designation
- - -
type -
single-phase enclosure -
material of encapsulation: - Yes
aluminum alloy - Yes/no
or
stainless steel - Yes/no
rated voltage kV
rated breaker current:
transformer feeder A 1250
line feeder A 1250
coupling feeder A 2000
rated short-circuit breaking current (1 sec) kA 31.5
peak making current kA 80
rated cable charging breaking current A
rated small inductive breaking currents A
rated lightning impulse withstand voltage phase to earth across isolating distance
kV(peak) kV(peak)
![Page 9: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/9.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 9
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
rated switching impulse withstand voltage phase to earth across isolating distance
kV(peak) kV(peak)
rated power frequency withstand voltage phase to earth across isolating distance
kV(rms) kV(rms)
rated
total breaking time Msec ′50
total making time Msec ′80
volume of breaker compartment M3
rated pressure of SF6 gas at 40°C Kpa
maximum and minimum admissible pressure of SF6 gas at 40°C
Kpa
rated operating sequence for OHL feeder - 0-0.3s-CO-1min-CO
first pole to clear factor - 1.5
auto reclosing facilities for line feeder bays - Single and 3 phase
Driving Mechanism
manufacturer place of manufacture manufacturer reference/designation
- - -
type
spring - Yes/no
or
hydraulic - Yes/no
rating of drive motor W
auto-reclose, single-phase/three-phase -
auto-reclose sequence -
![Page 10: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/10.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 10
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Compressor or Oil Pump
manufacturer place of manufacture manufacturer reference/designation
- - -
type -
rated pressure bar
rated flow 1/min
rated power kW
Disconnector
manufacturer place of manufacture manufacturer reference/designation
- - -
standard - IEC 62271, 60265 part 2,
IEC 60517
type -
rated current (full load transfer capability from one bus to another without load reduction or interruption)
A 1250
rated lightning impulse withstand voltage phase to earth across isolating distance
kV(peak) kV(peak)
650 750
rated switching impulse withstand voltage phase to earth across isolating distance
kV(peak) kV(peak)
rated power frequency withstand voltage phase to earth across isolating distance
kV(rms) kV(rms)
rating of drive motor W
motor drive supply (AC or DC) -
closing/opening time sec / sec
![Page 11: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/11.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 11
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Maintenance Earthing Switch
manufacturer place of manufacture manufacturer reference/designation
- - -
standard - IEC 62271-102, 60517
type -
driving mechanism -
motor drive supply (AC or DC) -
short time current withstand (1 sec) kA (sec) 31.5
peak current withstand kA
closing / opening time
sec/sec
High Speed Earthing Switch
manufacturer place of manufacture manufacturer reference/designation
- - -
standard - IEC 62271-102, 60517
type -
driving mechanism -
motor drive supply (AC or DC) -
rated peak current withstand kA
rated short time withstand current (1 sec) kA (sec) 31.5
closing / opening time
sec/sec
Current Transformer
manufacturer place of manufacture manufacturer reference/designation
- - -
type - Toroidal, GIS enclosed
rated primary current A Single line diagram
number of primary windings n 2/1
![Page 12: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/12.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 12
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
rated secondary current A 1
number of secondary windings for measuring for protection
n n
1 5
accuracy class for metering and billing - 0.2
accuracy class for protection - 5P20, class X
Ratio
Cable Bay
power rating (min. burden) (to be justified by successful tenderer)
VA 30
Ratings:
measuring: core 4 A 1000-500/1
protection: core 1 core 2 core 3 core 5 core 6
A A A A A
1000-500/1 1000-500/1 1000-500/1
2000/1 2000/1
Accuracy Class:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
Cl Cl Cl Cl Cl Cl
X X
5P20 0.2 X X
Rated Output:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
VA VA VA VA VA VA
Saturation Factor:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
n n n n n n
dynamic current x IN
thermal current x IN
![Page 13: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/13.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 13
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Ratings:
Transformer Bay
measuring: core 3 A 400-200/1
protection: core 1 core 2 core 4 core 5 core 6
A A A A A
400-200/1 400-200/1 400-200/1
2000/1 2000/1
Accuracy Class:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
Cl Cl Cl Cl Cl Cl
X X
5P20 0.2 X X
Rated Output:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
VA VA VA VA VA VA
Saturation Factor:
protection 1 protection 2 protection 3 measuring 4 / billing protection 5 protection 6
n n n n n n
dynamic current x IN
thermal current x IN
Transformer Bay Outgoing Feeder
HV Neutral CT:
protection: core 1 core 2
A A
400-200/1 400-200/1
Accuracy Class:
protection 1 protection 2
Cl Cl
5P20 X
![Page 14: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/14.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 14
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Rated Output:
protection 1 protection 2
VA VA
Saturation Factor:
protection 1 protection 2
n n
dynamic current x IN
thermal current x IN
LV Neutral CT:
protection: core 1 core 2
A A
1600-800/1 1600-800/1
Accuracy Class:
protection 1 protection 2
Cl Cl
5P15 X
Rated Output:
protection 1 protection 2
VA VA
Saturation Factor:
protection 1 protection 2
n n
dynamic current x IN
thermal current x IN
Bus Section CT No. 1:
Protection: core 1 core 2
A A
2000/1 2000-1000/1
Accuracy Class:
protection 1 protection 2
Cl Cl
X 5P20
Rated Output:
measuring 1 protection 2
VA VA
![Page 15: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/15.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 15
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.2 132 gas insulated switchgear
Bus Section CT No. 2:
protection: core 1 A 2000/1
Accuracy Class:
protection 1 Cl X
Rated Output:
protection 2 VA
Voltage Transformer
manufacturer place of manufacture manufacturer reference/designation
- - -
type - Inductive, SF6 gas insulated,
enclosed
burden (min) VA
rated primary voltage kV
3132
rated secondary voltage kV 3
110.0 & 3110.0
measuring V
protection V
Accuracy Class
measuring / billing Cl 0.2
protection Cl 3P
Rated Output:
measuring VA
protection VA
![Page 16: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/16.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 16
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.3: 33 kV Indoor switchgear
33 kV Indoor Switchgear
manufacturer
type - Metalclad
insulation SF6
enclosure - triple pole primary
application standard IEC 60298
nominal system voltage kV 33
highest value of system operating voltage kV 36
range of highest voltage for equipment (IEC 60071-1)) - A
rated frequency Hz 50
rated short-circuit current, 1 sec. kArms 31,5
rated lightning impulse withstand voltage kVpeak 170
rated power frequency short duration withstand voltage kVrms 70
symmetrical breaking current kA 25
short circuit making current kApeak 80
rated current
busbar and bus coupler
- for Dhamar,Haouban, Sheban A 1250
- for Al Arish, Mansoura A 2500
outgoing feeders
- for Dhamar,Haouban, Sheban A 630
- for Al Arish, Mansoura A 1600
incoming feeder from transformer
- for Dhamar,Haouban, Sheban A 1250
- for Al Arish, Mansoura A 2500
protection class – high voltage live parts
- low voltage compartment
-
-
IP 65
IP 41
circuit breaker type - Vacuum or SF6
rated operating cycle of circuit breaker - 0-0.3 s-C0-1 min.-C0
![Page 17: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/17.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 17
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.3: 33 kV Indoor switchgear
rated short-circuit current, 1 sec of circuit breaker kA rms 31,5
rated peak withstand current kA peak 63
rated voltage of cb drive V 110 DC
type of earthing switch - positively making type
type of current transformers - inductive, cast-resin insulated
ratings primary winding:
- for , Haouban, Sheban
for line bays A 400/200
for transformer bays 45 MVA A 800/400
For transformer incomer 60MVA A 1200/600
- for Al Arish, Mansoura
for line bays A 1600/800
for transformer bays 90 MVA A 1600/800
ratings secondary winding A
- for Dhamar, Haouban, Sheban
for measuring A 1
for protection A 1/1
- for Al Arish, Mansoura
for measuring A 1
for protection A 1/1
accuracy class
- for Dhamar,Haouban, Sheban
for measuring - 0.5 M 5
for protection - 5 P 20
- for Al Arish, Mansoura
for measuring - 0.2
for protection - 5 P 20
burden VA 30
type of voltage transformers - cast-resin insulated
![Page 18: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/18.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 18
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
rated primary voltage kV 33/√3
B1.3.3: 33 kV Indoor switchgear
rated secondary voltages (independent)
V 110/√3
V 110/3
rated output VA/VA 100/100
accuracy class:
- for Dhamar,Haouban, Sheban
for measuring 1.0 M
for protection 5 P
- for Al Arish, Mansoura
for measuring 0.2
for protection 3 P
![Page 19: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/19.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 19
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
A. 132/33 kV Power transformers for Haouban and Sheban Substation
manufacturer
type - 3-phase oil immersed
applicable standards - IEC 60076, 60354
rated power
for ONAN operation
for Sheban
for Haouban
MVA
MVA
45
60
rated voltage kV/kV 132/33
highest system voltage kV/kV 145/36
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 275
for secondary kVrms 70
rated lightning impulse withstand voltage
for primary kVpeak 650
for secondary kVpeak 170
vector group - YnD1
impedance voltage at principal tapping % 9.5
voltage regulation - on-load tap changer
tap positions - +4/-12
range of voltage regulation % +5/- 15
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) dB (A) 55
max. no-load current % In 0.2
max. ambient temperature °C 50
![Page 20: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/20.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 20
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
temperature rise at rated power over 50°C maximum ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
Bushings
insulation - graded/not graded
terminal arrangement
for primary outdoor condenser bushings
for secondary Air filled cable connection box
with outdoor bushings
rated creepage distance of bushings
for HV mm 6525
for LV mm 1620
approximate total weight to
approximate transport weight to
On-load Tap Changer
manufacturer
type - resistor
rated current A 350
rated short-time current ( 1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000
![Page 21: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/21.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 21
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
Guarantee Values for 132/33 kV, 45MVA Transformers
no load losses kW --
load losses at principal tap kW
losses of auxiliaries (fans, pumps, etc.) kW
Guarantee Values for 132/33 kV, 60 MVA Transformers
no load losses kW --
load losses at principal tap kW
losses of auxiliaries (fans, pumps, etc.) kW
![Page 22: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/22.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 22
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
B. 33/0.4 kV Station Earthing and Auxiliary Transformers
manufacturer
type - 3-phase hermetically
sealed
applicable standard - IEC 60076
rated apparent power kVA 400
rated voltage HV/LV kV 33/0.4
rated frequency Hz 50
vector group Znyn 11
impedance voltage % 6
off-load tap changer regulation - +/- 2x2,5%
type of cooling - ONAN
rated power frequency withstand voltage kV 70
rated lightning impulse withstand voltage kVpeak 170
max. noise level (acc. to. IEC 60551) dB (A) 55
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
approximate weight kg
Guarantee values for 33/0.4 kV station auxiliary transformers
no load losses
load losses at principal tap
![Page 23: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/23.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 23
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
C. 132/33/11 kV Power Transformers for Al Arish and Mansoura Substation
manufacturer
type - 3-phase oil immersed
applicable standards - IEC 60076, 60354
rated power maximum continuous ONAF operation MVA 90
rated power minimum continuous ONAN operation MVA 63
rated voltage kV/kV 132/33/11
highest system voltage kV/kV 145/36/12
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 275
for secondary kVrms 70
rated lightning impulse withstand voltage
for primary kVpeak 650
for secondary kVpeak 170
vector group - Ynyn0d11
impedance voltage at principal tapping % 10
voltage regulation - on-load tap changer
tap positions - +4/-12
range of voltage regulation % +5/- 15
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) ONAN / ONAF dB (A) 55 / 65
max. no-load current % In 0.2
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum ambient temperature
![Page 24: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/24.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 24
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
Bushings
insulation - graded/not graded
terminal arrangement
for primary outdoor condenser bushings
for secondary Air filled cable connection box
with outdoor bushings
rated creepage distance of bushings
for HV mm 6525
for LV mm 1620
approximate total weight to
approximate transport weight to
On-load Tap Changer
manufacturer
type - resistor
rated current A 400
rated short-time current (1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000
![Page 25: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/25.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 25
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
Guarantee Values for 132/33/11 kV, 90MVA Transformer
no load losses kW --
load losses at principal tap
ONAN operation kW --
ONAF operation kW --
losses of auxiliaries (fans, pumps, etc.)
ONAN operation kW --
ONAF operation kW --
![Page 26: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/26.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 26
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
D. 33/11 kV Distribution Transformers for Al Arish Substation
manufacturer
type - 3-phase oil immersed
applicable standards - IEC 60076, 60354
rated power maximum continuous ONAF operation MVA 20
rated power minimum continuous ONAN operation MVA 15
rated voltage kV/kV 33/11
highest system voltage kV/kV 36/12
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 70
for secondary kVrms 28
rated lightning impulse withstand voltage
for primary kVpeak 170
for secondary kVpeak 95
vector group - DYN11
impedance voltage at principal tapping % 11.7
voltage regulation - on-load tap changer
tap positions - +8/-8
range of voltage regulation % +10/-10
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) ONAN / ONAF dB (A) 55 / 65
max. no-load current % In 0.2
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum ambient temperature
![Page 27: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/27.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 27
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
Bushings
insulation - graded/not graded
terminal arrangement
for primary Air filled cable connection box
with outdoor bushings
for secondary Air filled cable connection box
with outdoor bushings
rated creepage distance of bushings
for HV mm 1620
for LV mm 540
approximate total weight to
approximate transport weight to
On-load tap changer
manufacturer
type - resistor
rated current A 350
rated short-time current (1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000
![Page 28: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/28.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 28
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
Guarantee Values for 33/11 kV Distribution Transformers for Al Arish Substation
no load losses kW --
load losses at principal tap
ONAN operation kW --
ONAF operation kW --
losses of auxiliaries (fans, pumps, etc.)
ONAN operation kW --
ONAF operation kW --
![Page 29: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/29.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 29
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.4: Power and station service transformers
E. 11/0.4 kV Station Auxiliary Transformer
manufacturer
type - 3-phase hermetically
sealed
applicable standard - IEC 60076
rated apparent power kVA 400
rated voltage HV/LV kV 11/0.4
rated frequency Hz 50
vector group Znyn 11
impedance voltage % 6
off-load tap changer regulation - +/- 2x2,5%
type of cooling - ONAN
rated power frequency withstand voltage kV 28
rated lightning impulse withstand voltage kVpeak 95
max. noise level (acc. to. IEC 60551) dB (A) 55
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
approximate weight kg
Guarantee values for 11/0.4 kV station auxiliary transformers
no load losses
load losses at principal tap
![Page 30: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/30.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 30
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.5: 33 kV Capacitor banks
manufacturer
type -
standards IEC 60871-1
kind of installation - indoor
protection degree IP 00
rated voltage kV 36
rating
steps
Mvar
-
25
insulation level
- lightning impulse
- power frequency withstand voltage
kV
kV
170
70
temperature class (1h) °C 50
connection -
YY
with diff. relay in each phase
number of elements connected in series and/or parallel per unit capacitor
-
number of unit capacitor connected per bank -
rated power of unit capacitor kVar
rated voltage of unit capacitor kV
nominal capacitance and max. permitted tolerance for each unit capacitor
µF/%
impregnating medium
- type
- specification reference
-
-
non PCB
total weight of complete unit capacitor incl. all fitting and impregnating medium
kg
total losses per kVar
overall dimensions of unit
- height
- depth
- width
mm
mm
mm
![Page 31: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/31.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 31
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.5: 33 kV Capacitor banks
overall dimensions of bank
- height
- depth
- width
mm
mm
mm
number of terminals of each unit capacitor -
creepage distance mm/kV 31
discharge time of capacitor unit from rated voltage to 75 V
min max. 10
material of capacitor unit container - Stainless steel
![Page 32: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/32.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 32
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.6: 132 kV and 33 kV Power cables and terminations
132 kV Power Cables, Single-Core
manufacturer
applicable standards IEC 60840
type - XLPE
specified voltage U0/U kV 76/132
highest system voltage kV 145
rated frequency Hz 50
power frequency withstand voltage kV 275
impulse withstand voltage kV 650
conductor cross section mm² 1000
conductor material - annealed copper
rated short circuit current (1 sec.)
conductor kA 143.0
screen kA 33.0
current carrying capacity
buried in soil at 40°C ground temperature A
laid in concrete channel at 54°C A
Conductor to screen capacitance µF/km
Charging current A/km
reference diameter of cable mm 83
cross-section of screen (copper screen wire) mm² 225
min. thickness of insulation mm 15
thickness of outer sheath mm
weight of cable per m kg 13.7
bending radius (single core cables) mm approx. 15 x d
132 kV Sealing Ends
manufacturer
material of insulator Composite
type test acc. to IEC 60840
rated power frequency withstand voltage (1 min/20°C) kV 275
![Page 33: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/33.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 33
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.6: 132 kV and 33 kV Power cables and terminations
impulse withstand voltage kV 650
minimum creepage distance mm 6600
132 kV Sealing Ends for GIS- Termination
manufacturer -
type test acc. to IEC 60840
rated power frequency withstand voltage (1 min/20°C) kV 275
impulse withstand voltage kV 650
type of termination - Dry type
dimension acc. to. - IEC 60859
33 kV Power Cables, Single-Core
manufacturer
applicable standards IEC 60502
type - XLPE
specified voltage U0/U kV 19/33
highest system voltage kV 36
rated frequency Hz 50
power frequency withstand voltage kV 70
impulse withstand voltage kV 170
conductor cross section mm² 630
mm² 95
conductor material - annealed copper
rated short circuit current (1 sec.)
conductor
for 630 mm² kA 90.0
for 95 mm² kA 13.6
screen
for 630 mm² kA 10.2
for 95 mm² kA 10.2
current carrying capacity
![Page 34: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/34.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 34
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.6: 132 kV and 33 kV Power cables and terminations
buried in soil at 40°C ground temperature
for 630 mm² A
for 95 mm² A
laid in concrete channel at 54°C
for 630 mm² A
for 95 mm² A
reference diameter of cable
for 630 mm² mm 58
cross-section of screen
for 630 mm² mm² 35
for 95 mm² mm² 25
min. thickness of insulation mm 8
thickness of outer sheath mm
weight of cable per m
for 630 mm² kg 8.0
for 95 mm² kg 2.0
bending radius (single core cables) mm approx. 15 x d
33 kV Sealing Ends
manufacturer
material of insulator polymeric
type test carried out yes/no
rated power frequency withstand voltage kV 70
impulse withstand voltage kV 170
minimum creepage distance mm 1650
![Page 35: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/35.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 35
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
1. Distance protection for 132 kV OHL feeder
(incl. fault locator function)
manufacturer
type
ratings
rating CT secondary A
rating VT secondary Hz
overcurrent capacity
permanent X IN
10 sec XI N
1 sec XI N
burdens (per phase)
current circuit VA
voltage circuit
ambient temperature
within specified accuracy °C
within operation capacity
DC supply
rated voltage V
main burden W
energizing circuit
minimum actuating impedance Ohm
number of actuating elements
range of actuating impedance
forwards direction Ohm/
reverse direction phase
range of actuating current (3 x I0) X IN
accuracy %
resetting ration
![Page 36: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/36.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 36
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
Distance measuring circuit
type of measuring
umber of measuring elements
impedance range
a) resistance - min. Ohm/Ph
- max. Ohm/Ph
b) impedance -min. Ohm/Ph
- max. Ohm/Ph
directional sensitivity for
asymmetrical faults mV
triple-pole faults mV
tripping times
min. ms
max. ms
setting range of earth impedance/zero sequence line impedance
amplitude
angle
accuracy
setting range
basic step
2nd step
3rd step
4th step
reversal of direction
Ancillaries
single multi-phase automatic reclosing capability
PLC interfaces
power swing blocking
switch-on to fault
fuse failure supervising device
![Page 37: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/37.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 37
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
Output Contacts
for indication
• max. service voltage
• max. making current (1 s)
• continuous current
• making power at 110 V DC
V DC
A
A
W
for tripping
• number
• max. service voltage V DC
• max. making current A
• continuous current A
• making power at 110 V DC W
• rupture power at 110 V DC L/R < 40 ms W
Constructional Features
protection class
mounting mode
Main Characteristics of Fault Locating Function
setting range (secondary ohms)
accuracy of measurement for fault currents with & without DC transient (% of line length)
variation of accuracy with resistance of point of fault
minimum time between start of fault locator & fault
extinction to achieve accuracy in 1.2 & 1.3 above
state method of rendout
state data storage time if applicable (hours)
References
![Page 38: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/38.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 38
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
2. Back-up Protection for 132 kV OHL Feeder – Overcurrent Protection Relay (50, 51)
manufacturer
type -
ratings -
current A
DC voltage V
main characteristics
current setting range (from-to) X IN
measuring accuracy %
reset ratio
pick-up time (from-to) ms
time error
3. Back-up Protection for 132 kV OHL Feeder – Directional Sensitive Earthfault Relay (67 N)
manufacturer
type
Ratings
current A
voltage V
frequency Hz
DC voltage V
Main Characteristics
current setting range (earth fault) X IN
measuring accuracy %
reset ratio
pick-up time ms
![Page 39: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/39.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 39
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
directional element
measuring angle
angle error
sensitivity
pick-up time
time-lag characteristics
time error
4. Autoreclosing Relay for 132 kV & 33 kV OHLs (79)
manufacturer
type
main characteristics
number of shots
one-phase cycle
three-phase cycle
dead time for 3-phase cycle sec.
reclaim time sec.
5. Overcurrent Protection (50, 51, 50N, 51N) for OHL
manufacturer
relay type
tripping current range from - to xIIn
tripping time range from - to msec
6. Overvoltage Protection (59)
manufacturer
relay type
setting range undervoltage stage 1 V
setting range undervoltage stage 2 V
setting range time delay stage 1 S
setting range time delay stage 2 S
tolerances %
![Page 40: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/40.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 40
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
7. Undervoltage Protection (27)
manufacturer
relay type
setting range undervoltage stage 1 v
setting range undervoltage stage 2 v
setting range time delay stage 1 s
setting range time delay stage 2 s
tolerances
8. Synchrocheck Relay (25)
manufacturer
relay type
operation modes
voltages
∆U measurement
∆φ measurement
9. Load Unbalance Protection
manufacturer
relay type
setting range current stage 1 v
setting range current stage 2 v
setting range time delay stage 1 s
setting range time delay stage 2 S
10. Transformer Differential Protection (87) for Two-and Three-Winding Transformers
manufacturer
type
![Page 41: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/41.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 41
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
Ratings
secondary current A
rated frequency Hz
DC supply V
Main Characteristics
range of operating coil settings % of C.T. rating
range of bias coil settings
recommended operating coil setting
recommended bias coil setting
number of bias coils
minimum sensitivity
earth faults % of C.T. rating
phase faults % of C.T. rating
maximum trough fault at which the protective equipment is stable with recommended settings:
earth faults % of C.T. rating
phase faults % of C.T. rating
maximum time delay between initiation of fault and energizing of breaker trip circuit
3 x IN 10xIN (ms)
11. Transformer Overcurrent Protection (50/51, 51N) for Two-and Three-Winding Transformers
manufacturer
relay type
tripping current range from - to x IN
tripping time range from - to msec
![Page 42: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/42.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 42
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.7: Protection equipment
12. Transformer Restricted Earth Fault Protection (87N) for Two-and Three-Winding Transformers
manufacturer
relay type
tripping current range from – to X IN
tripping time range from – to msec
14. Busbar Protection
manufacturer
type
Ratings
AC current A
frequency Hz
AC supply V
DC supply VDC
Settings
CT supervision
operating time ms
Scheme burdens
DC burden W
AC burden Ohm
Contact rating
make and carry for 0.2 sec. VA
break
![Page 43: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/43.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 43
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
1. Substation Digital Control System
automatic time synchronization at all nodes of the network
Yes
fault indication LEDs on modules and alarm messages on monitors
Yes
basic functions: logic, sequence control, data processing, including code conversion, text and alarm signal editing and function units for binary processes
Yes
cycle times, selectable (for each control module) ms <10
programming language: elements for logic, control loops, arithmetic
Yes
minimum number of I/0 channels per computer (analogue in/digital in/digital out)
(see rel. chapter )
spare % 25
LCU Processing Unit
manufacturer
type
microprocessing with 32 bit Yes
system software in PROM Yes
application software in battery-buffered RAM or EPROM/Flash-PROM
Yes
LAN
type
protocol
transmission medium
transmission rate MBit/s
Printers (Color)
number of printers
manufacturer/type
noise
dB (A)
![Page 44: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/44.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 44
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
resolution dpi
• format DIN
• pages/min.
Printers (Laser, b/w)
• number of printers
• manufacturer/type
• noise dB (A)
• resolution dpi 600 x 600
• format DIN
• pages/min. ≥ 12
Operator workstation
• redundant configuration no
• hardware
• manufacturer
• type
• CPU
• data word
• coprocessor
• working memory MB
• hard disk
• type
• capacity MB
• external memory
• type
• capacity MB
• access ms
• data rate MB/s
![Page 45: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/45.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 45
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
•
• noise dB (A)
• mouse, type
• monitors
• manufacturer/type
• number of monitors
• TFT screen size inch 19
• pixels x 1280 x 1024
• refresh rate Hz
• TCO standard
• noise dB (A)
4. Service and analysis station
• hardware
• manufacturer
• type
• CPU
• data word
• coprocessor
• working memory MB
• hard disk
• type
• capacity MB
•
• external memory
• type
• capacity MB
• access ms
• data rate MB/s
• noise dB (A)
![Page 46: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/46.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 46
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
• mouse, type
• monitors
• manufacturer/type
• number of monitors
• TFT screen size inch 19
• pixels x 1280 x 1024
• refresh rate Hz
• TCO standard
• noise dB (A)
Service Aid Laptop
manufacturer
type
processor type
performance MHz
RAM Mbyte
hard disk drive GByte
5. Clock System
manufacturer
synchronization source
synchronization interval
6. Metering Equipment
V-meter
manufacturer -
type -
size mm x mm
scale degree
accuracy class -
![Page 47: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/47.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 47
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
power consumption kO/V
operating principle kOhm/V
electro-mechanical -
electronic -
A-meter
manufacturer -
type -
size mm x mm
scale degree
accuracy class -
power consumption kO/V
operating principle kOhm/V
electro-mechanical -
electronic -
W-meter
manufacturer -
type -
size -
scale degree
accuracy class -
power consumption mV
operating principle -
electro-mechanical -
electronic -
VAR-meter
manufacturer -
![Page 48: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/48.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 48
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.8: Substation control and monitoring system
type -
size mm x mm
scale degree
accuracy class -
power consumption mV
operating principle -
electro-mechanical -
electronic -
Wh-meter
manufacturer -
type -
size -
accuracy class -
power consumption VA
operating principle -
electro-mechanical -
electronic
VARh-meter
manufacturer -
type -
size mm x mm
accuracy class -
power consumption VA
operating principle -
electro-mechanical -
electronic -
![Page 49: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/49.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 49
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
Optical Line terminal (OLT/STM-1)
- functions ITU-T Rec. G.783
- PDH to SDH electrical interface ITU-T Rec. G.703
- mux structure ITU-T Rec. G.707
- timing, synchronisation ITU-T Rec.
G.783, G.811, G.812, G.813
- jitter and wander for SDH mux ITU-T Rec. G.783
- jitter and wander for SDH line ITU-T Rec. G.958
- craft interface ITU-T Rec. G.773
- optical safety ITU-T Rec. G.958
- min receive power @ BER 10-10
power supply: rated V DC 48
range V DC 40 - 60
Primary Multiplexer
- comply with ITU-T Rec. G.737
- add/drop kbps 64 or multiple of 2.4 kbps
- Bit rate kbps 2048 +/- 50 ppm
- PCM requirements ITU-T Rec. G.711
- frame structure ITU-T Rec.G.732
- encoding law ITU-T Rec. G.711
- performance at voice frequencies ITU-T Rec. G.714
alarms
- power failure
- loss of incoming signals 2048 kbps
![Page 50: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/50.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 50
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
- loss of frame alignment
- alarm indication from remote mux
Optical Fibre Underground Cable (OPUG)
manufacturer
type
stainless steel tube mm / mm
steel stranding N x mm
steel section mmsp
cross section St mm2
cross section ACS mm2
cross section AA mm2
overall diameter mm
calculated breaking load kN
nominal weight kg/km
modulus of elasticity kN / sqmm
load bearing cross section mmsq
coefficient of thermal exp. 10E-6/K
creep yeald promille
ultimate Tensil strength kN
rated Tensil strength kN
everyday stress N/mm2
short circuit capacity I2t kA2S
DC resistance Ohms/ km
weight of OPGW kg / km
number of fibres No 24
![Page 51: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/51.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 51
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
fibre excess length promille
core diameter µm 9.0 to 11.5 3% tolerance
mode field diameter
@ 1310 nm µm 8 – 9.5
@ 1550 nm µm 9.5 – 11.5
optical cladding diameter µm 125 +/- 2
core clad concentricity < 2 %
coating diameter µm 250 +/- 15
coating concentricity < 0.7 %
cable attenuation @ 1310 nm dB/km <= 0.35
cable attenuation @ 1550 nm dB/km <= 0.25
splice attenuation @ 1310 nm dB <= 0.15
splice attenuation @ 1550 nm dB <= 0.25
total dispersion @ 1310 nm ps/ km.nm 3.5
total dispersion @ 1550 nm ps/ km.nm 18.0
core numerical aperture <= 0.23
life span year > = 30
PLC Terminal Equipment (digital and analogue)
manufacturer
type
number of speech channels per link (analogue) min. 1
![Page 52: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/52.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 52
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
“ “ ditto (analogue, for 8 kHz bandwidth) min. 3
“ “ ditto (digital) min. 8
number of data channels per link (analogue) min. 4
“ “ ditto (digital) min. 8
compatibility with existing analogue PLC equipment yes
S/N ratio for complete link (without compandors) dB >35
line attenuation dB
carrier frequency range kHz 40 - 500
gross channel bandwidth kHz 4 / 8
usable AF bandwidth Hz 300 - 3600
max. usable data transmission rate kBit/s 76.8
RF output power W PEP
spurious emission suppression dB
selectivity of receiver dB
automatic gain control yes
RF level range dB
number of teleprotection commands
protection class of equipment racks, cubicles
EMC standards:
• EN 50081-2, class A yes
• EN 50082-2
Power supply:
• Supply voltage VDC 48 ± 20%
• Power consumption W
Ambient conditions: yes
(according to IEC 721-3)
![Page 53: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/53.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 53
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
PLC Teleprotection Equipment
For digital signals:
manufacturer
type
number of simultaneous commands 4
command initiated by potential-free contact yes
test voltages according to IEC 255-4
• isolation kV/DC 0.5 2 /1 min.
• pulse 1.2/50 µsec. kV 1
For analogue signals:
manufacturer
type
test voltages according to IEC 255-4
• isolation (0.5 J, 1 min) kV/DC 2
• pulse 1.2/50 µsec. kV 1
Fibre Equipment Teleprotection Interface
electromagnetic compatibility test voltages according to IEC 255-4
• isolation (0.5 J, 1 min.) kV/DC 2
• pulse 1.2/50 µsec. kV 1
no. of simultaneous commands
no. of analogue signals
Line Matching Units
manufacturer - -
equipment type - -
![Page 54: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/54.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 54
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.9: Telecommunications and telephone systems
equipment site impedance Ω
line site impedance Ω
nominal peak envelope power W
Line Traps 132 kV
manufacturer -
type -
rated inductance m H 0.5/0.315/0.2
power frequency inductance m H
rated continuous current A 1250
rated short time current kA 31.5
• duration s 1
Telephone Set
manufacturer
type
no. of standard sets
![Page 55: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/55.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 55
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.10: 0.4 kV AC Installations
0.4 kV AC Installations
applicable standards IEC 60439, 60947
type - fixed units
rated voltage V 400
frequency Hz 50
rated short-circuit current for 1 second kA 25
test voltage V 2500
type of circuit breaker driving mechanism - hand-operated
secondary current of current transformer A 5
protection class - IP 41
400 V Main Switchgear
manufacturer -
type of switchgear -
rated voltage kV
rated current of busbar (45 °C ambient) A
rated frequency Hz
rest voltage V
max. asym. 3-phase short circuit withstand current kApeak
short-time current (1 sec) kA
overall dimensions (H x W x D) mm
weight kg
Circuit Breaker
type -
rated current A
rated short circuit breaking current kA
short-time current (1 sec) kA
![Page 56: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/56.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 56
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.10: 0.4 kV AC Installations
max. asym. 3-phase short-circuit withstand current kApeak
total opening time ms
Current Transformer
type -
current ratio A
dynamic current x IN
400 V Sub-distribution
manufacturer -
type of switchgear -
rated voltage kV
rated current of busbar (45°C ambient) A
rated frequency Hz
test voltage V
max. asym. 3-phase short circuit withstand current Apeak
short-time current (1 sec) kA
![Page 57: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/57.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 57
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.11: Direct current installations
110 V DC Equipment
applicable standards IEC 60439, 60947
type of distribution board fix mounted components
busbar P and N insulated
rated voltage DC V 110
test voltage V 1500
type of load break switch/circuit breaker - hand-operated
protection class - IP 41
min. insulation resistance kΩ 110
battery type - NiCd
nominal voltage per cell V 1.2
number of cells - 92
applicable standard IEC 60623
rated voltage V 110
type of operation parallel stand-by
rated capacity (for 10 hours discharge time) Ah 400
battery charger type - thyristor controlled
input voltage (three-phase) V 400 ± 10%
frequency Hz 50 ± 2%
rated DC voltage V 110
maximum DC voltage V 132
residual ripple % < 5
type of cooling - self-ventilating
protection class of cubicle - IP 41
![Page 58: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/58.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 58
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.11: Direct current installations
110 V DC Distribution
manufacturer -
type -
dimensions (height x width x depth) mm
metal cabinets with single busbar system and fixed equipment
-
rated current A
short-circuit withstand current A
busbar cross-section mm²
Circuit Breaker
type -
rated current DC A
Fuse -
type -
rated current DC A
rated breaking current DC A
110 V Battery Charger
manufacturer -
type -
mounted in metal cabinet -
rated voltage DC V
rated current DC A
rated capacity kVA
rated input voltage V
rated current consumption A
efficiency -
charging characteristics -
constant voltage range from - to V
continuous charging voltage per cell and tolerance V + %
![Page 59: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/59.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 59
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.12: LV Power and control cables
0.4 kV Power Cables, Four-Core
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed copper
insulation material -
110 and 48 V DC Cables
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed copper
insulation material -
Control Cables
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed copper
insulation material -
type of screen -
Instrument Cables
manufacturer -
cable type -
![Page 60: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/60.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 60
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.12: LV Power and control cables
rated voltage kV
test voltage kV
conductor material - annealed copper
insulation material -
type of screen -
Signaling Cables
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed copper
type of screen -
![Page 61: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/61.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 61
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.13: Earthing system, power and lighting installations
1. Earthing and Lightning Protection System
applicable standards - IEEE 80, IEC 60621/61024
VDE0185:
manufacturer
type
size of standard copper conductor mm2 70
mode of connection - by compression
diameter of round copper rods for lightning protection mm 8
size of stranded copper for earthing conductors mm2
diameter of round copper for lightning protection conductors
mm
diameter of reinforcement bar (round iron) mm
material of conductor supports of lightning protection system
-
material of nuts and bolts on points for remain detachment
-
mode of connection of copper conductors in ground and PVC single-core cable to the reinforcement bar in concrete
-
2. Power and Lighting Installation
0.4 kV Sub-distributions Boards
manufacturer -
type of switchgear - fixed
plug-in units/fixed units -
rated voltage V 400/250
rated frequency - 50
test voltage V 2500
![Page 62: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/62.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 62
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.13: Earthing system, power and lighting installations
rated current of busbar (45°C ambient) A
max. asym. 3-phase short circuit withstand current kApeak
short-time current (1 sec.) kA
degree of protection IP41/IP54
Lighting
manufacturer -
indoor lighting (type) -
outdoor lighting (type) -
Lighting Fixtures
indoor fluorescent W 1 x 58/2 x 58
indoor halogen W 1 x 250/1 x 400
outdoor high-pressure mercury W 400
Power and Domestic Sockets
manufacturer -
power sockets (type) -
domestic sockets (type) -
![Page 63: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/63.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 63
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.16: Overhead cranes
Manufacturer -
Place of manufacture -
Manufacturer reference / designation - Test load for the crane and lifting gears in % of the nominal carrying capacity % 125
Carrying capacity, approx. (to be adapted by the Bidder, according to the heaviest part to be lifted) t
Weight of the heaviest part to be lifted t
Lifting height, approx. m
Hoisting speed, fast/creep approx. m/min. 4/0.4
Crab traversing speed, fast/creep approx. m/min. 20/5
Crane bridge traveling speed m/min. 20/5
Fast/creep approx.
Span approx. m
Length of runway – full building length m yes
Standards for design and calculation of the crane - yes/no
BS 466,2373 class 2
Or equivalent standard applied -
General Guarantees The Contractor shall guarantee the following values and characteristics of the crane.
Faultless operation of the crane installation
Travel and lifting speeds including the inching speed with a tolerance of each nominal speed at nominal load.
% ±15
The lifting capacity with a permitted overload capacity (test load) of at least nominal lifting capacity.
% 25
Max. deflecting of the crane bridge of span at nominal load
- 1/800
Special Guarantees
Lifting capacity t
Deflecting of crane girder at nominal load and with crab in center position
mm
![Page 64: Lot 2b_B1 Data Sheets, Rev, 300807](https://reader034.vdocument.in/reader034/viewer/2022051312/547754bb5906b53a068b4693/html5/thumbnails/64.jpg)
6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 64
Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Connection
Unit Data
Technical Data required offered
B1.3.16: Overhead cranes
Traveling speeds fast/creep m/min.
Hoisting speeds fast/creep m/min.
Max. power demand kW