PLUMBING DESIGN CALCULATIONS
MOIZFP PROJECT NO. R9808/2170 1
TABLE OF CONTENTS
No of pages
REFERENCES 1
ABBREVIATIONS 1
FIXTURE COUNT 2
ELECTRIC WATER HEATER SIZING 22
SIZING OF POTABLE, IRRIGATION AND NON-POTABLE WATER PUMP 3
SIZING OF FIRE&POTABLE, NON-POTABLE AND IRRIGATION WATER TANK 2
SIZING OF FIRE PUMP 1
SIZING OF SEWAGE HOLDING TANK 1
HYDRAULIC CALCULATIONS & SIZING POTABLE WATER SYSTEM 1
HYDRAULIC CALCULATIONS & SIZING NON-POTABLE WATER SYSTEM 1
ISOMETRIC DIAGRAM & SIZING (POTABLE & NON-POTABLE WATER SYSTEM) 2
IRRIGATION SYSTEM PIPE SIZING 1
SOIL PIPE SIZING 1
WASTE PIPE SIZING 1
ROOF DRAINAGE PIPE SIZING 10
PLUMBING DESIGN CALCULATIONS
MOIZFP PROJECT NO. R9808/2170 1
REFERENCES
1- SASO - SAUDI ARABIAN STANDARD ORGANIZATION
2- ANSI - AMERICAN NATIONAL STANDARD INSTITUTE
3- UPC - UNIFORM PLUMBING CODE
4- NPC - NATIONAL PLUMBING CODE
5- UBC - UNIFORM BUILDING CODE
6- ASTM - AMERICAN SOCIETY FOR TESTING AND MATERIAL
7- ASHRAE - AMERICAN SOCIETY OF HEATING REFRIGERATION
AND AIR CONDITIONING ENGINEERS
8- PRACTICAL PLUMBING DESIGN GUIDE
PLUMBING DESIGN CALCULATIONS
3
GAS DEMAND
BUILDING NO. 2
1.) DESIGN DATA:
NO. OF LABORATORY OUTLET = 104
LOAD PER OUTLET = 5000 BTU/HR
SIMULTANEOUS USED FACTOR = 50%
HEATING VALUE = 2516 BTU/FT3
AVERAGE DAILY TIME USED = 1.5 HRS.
2.) CALCULATIONS:
TOTAL LOAD
(104 OUTLETS x 5000 BTU/FT3) = 520,000 BTU/FT3
CONSUMPTION
520,000 = 206.6772655008 FT3/HR
2516
CONSUMPTION WITH USE FACTOR
206.677 FT3/HR @ 50% = 103.3386327504 FT3/HR
TOTAL LPG CONSUMPTION
103.33 FT3/HR X 1.5 HRS. = 155.0079491256 FT3
SAY 160 CUBIC FEET
ADOPT PIPE SIZE OF 50MM DIA.
PLUMBING DESIGN CALCULATIONS
Page 4
SIZING OF CENTRALIZED LPG TANK
DESIGN BASIS:
LABORATORY OUTLET= 5000 BTU/HR
KITCHEN OUTLET OUTLET= 35000 BTU/HR
A) TABULATION OF DAILY CONSUMPTION:
OUTLET RATING TOTAL TOTAL
BUILDING 2 = 104.00 5000.00 520000 780000 BTU
BUILDING 5 = 752.00 5000.00 3760000 5640000 BTU
BUILDING 7 = 320.00 5000.00 1600000 2400000 BTU
BUILDING 8 = 485.00 5000.00 2425000 3637500 BTU
BUILDING 9 = 234.00 5000.00 1170000 1755000 BTU
BUILDING 10 = 115.00 5000.00 575000 862500 BTU
BUILDING 11 = 706.00 5000.00 3530000 5295000 BTU
BUILDING 32 = 24.00 35000.00 840000 2100000 BTU
13900000 21690000
B) SIZING OF LPG TANK:
TOTAL BTU RATING = 21690000 BTU
(INCL.DAILY AVERAGE USE)
LPG HEATING VALUE = 91,547 BTU/HR
REQUIRED DAILY STORAGE = 236.92748 GALLONS
LPG TANK CAPACITY = 7107.8244 GALLONS (WATER CAPACITY)
(30 DAYS STORAGE)
USE 8 NOS. OF 1000 GALLONS CAPACITY (GASCO STANDARD TANK)
PLUMBING DESIGN CALCULATIONS
Page 5
PLUMBING DESIGN CALCULATIONS
Page 6
PLUMBING DESIGN CALCULATIONS
Page 7
PLUMBING DESIGN CALCULATIONS
8
HEAD LOSSES CALCULATION
FROM NODE 1 TO 3
A.) DESIGN BASIS:
Pipe sizes are based on Table 4-26-Data for sizing Gas piping
(See attachment-Plumbing Design Guide from Building Sytem Design)
B.) TABULATIONS:
Node pipe dia. Pipe Length Pipe Length Load Hf hf (total friction loss)no. (mm) m ft cfh per 100 ft kPa1 0 0 0 - - 0.002 75 885 2902 160 0.005 0.153 100 507 1663 1120 0.01 0.17
B.) PRESSURE CALCULATIONS:
PIPE FRICTION LOSS = 0.31 inch water col.
LET; FITTING LOSSES = 0.034 10% of total head losses
STATIC HEAD LOSS = 0.1 inch water col.
TOTAL HEAD LOSS = 0.45 inch water col.
HEAD LOSSES CALCULATION