LT-6098 FR-320NetK Rev. 0 June 2015 Page 1 FR-320K Addendum for FR-320K Installation LT-6098 FR-320NetK Installation Attention: This specific application requires a setup not listed in either the LT-951 FR-320 Series or the LT- 894 FleX-Net™ Installation and Operation Manuals. This document takes precedence over both LT-951 and LT-894 wherever there is a conflict. Introduction This addendum describes how to implement a FR-320 Releasing panel into a FleX-Net™ system panel.The FR-320K adds releasing capability to the FleX-Net™ system without the need for a separate external cabinet. About the FR-320NetK Intelligent Network Fire Alarm and Release Control System The FR-320K panel adds releasing capability to Mircom's FleX-Net™ MNS. Based upon Mircom's already UL listed FR-320 Releasing panel and FleX-Net™ systems, this system permits pre-release, abort, manual release, and reset control. The FR-320K's chassis permits easy mounting to the Mircom's BBX-FXMNS cabinet. The FR-320K includes all necessary items to connect the FR-320 releasing panel to the Mircom's FleX-Net™ system. The FleX-Net™ and FR-320K panels have independent power arrangements. Each panel has its own AC supply and battery setup. The connection between the FR-320K and the FleX-Net™ panels is by isolated relays. The FR-320K uses the FR-320 pre-programmed mode #2 to enable activation features via the FleX-Net™ initiating device circuits. In this configuration, the Mass Notification System (MNS) capability is not present at this panel node. Note: The releasing devices used must be wired locally to this panel. Overall Features: Provides additional releasing capability to FleX-Net™ MNS system Built-in Addressable loop which supports Classic Loop Interface Protocol (CLIPS) and Advanced Protocol (AP) addressable devices Tamper resistant enclosures with password protected features for enhanced access control Local and remote placement of controls and indicators Visible notification and strobes support Large LCD displays Fire Alarm Control Panel Interface (FACI) Building Management System Interface (BMSI) Fire Alarm Control: •Base system is equipped with one Intelligent Signaling Line Circuit (SLC). Expandable up to 21 SLCs

Upload: others

Post on 25-Apr-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 1

FR-320K

Addendum for FR-320K Installation

LT-6098 FR-320NetK InstallationAttention: This specific application requires a setup not listed in either the LT-951 FR-320 Series or the LT-

894 FleX-Net™ Installation and Operation Manuals. This document takes precedence over bothLT-951 and LT-894 wherever there is a conflict.

Introduction

This addendum describes how to implement a FR-320 Releasing panel into a FleX-Net™ system panel.The FR-320K adds releasing capability to the FleX-Net™ system without the need for a separate external cabinet.

About the FR-320NetK Intelligent Network Fire Alarm and Release Control System

The FR-320K panel adds releasing capability to Mircom's FleX-Net™ MNS. Based upon Mircom's already UL listed FR-320 Releasing panel and FleX-Net™ systems, this system permits pre-release, abort, manual release, and reset control.

The FR-320K's chassis permits easy mounting to the Mircom's BBX-FXMNS cabinet. The FR-320K includes all necessary items to connect the FR-320 releasing panel to the Mircom's FleX-Net™ system.

The FleX-Net™ and FR-320K panels have independent power arrangements. Each panel has its own AC supply and battery setup. The connection between the FR-320K and the FleX-Net™ panels is by isolated relays.

The FR-320K uses the FR-320 pre-programmed mode #2 to enable activation features via the FleX-Net™ initiating device circuits. In this configuration, the Mass Notification System (MNS) capability is not present at this panel node.

Note: The releasing devices used must be wired locally to this panel.

Overall Features:

• Provides additional releasing capability to FleX-Net™ MNS system

• Built-in Addressable loop which supports Classic Loop Interface Protocol (CLIPS) and Advanced Protocol (AP) addressable devices

• Tamper resistant enclosures with password protected features for enhanced access control

• Local and remote placement of controls and indicators

• Visible notification and strobes support

• Large LCD displays

• Fire Alarm Control Panel Interface (FACI)

• Building Management System Interface (BMSI)

• Fire Alarm Control:

•Base system is equipped with one Intelligent Signaling Line Circuit (SLC). Expandable up to 21 SLCs

Page 2: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 2 LT-6098 FR-320NetK Rev. 0 June 2015

•Each SLC is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Style 6 or 7 Class A) or Style 4 (Class B)•Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each•Built-in Ethernet port•Remote diagnostics via a built-in web server

• Network Features:

•Up to 63 nodes•Fully integrated digital network audio and control over a single pair of copper wire or fibre optic cable•Supports over 5,000 points per node•Supports over 250,000 points on a single network•Peer-to-peer network communications

• Releasing Features:

• Each initiating circuit is pre-configured as: Alarm, Supervisory (Latching or non-latching), Water-Flow, Manual Release Switch, Abort Switch, or Manual Release/Abort combination, depending upon the selected pre-programmed configuration. There are two LEDs per circuit, one for Trouble (amber), and one dual color (amber/red) LED for Supervisory (amber) and Alarm (red)•Basic unit has 4 power limited class B (style Y) output circuits. Output circuits 1 & 2 are indicating circuits while output circuits 3 & 4 are releasing circuits (circuit 4 can work as an indicating circuit in some situations.) Each indicating circuit process type is pre-configured and can be silenceable•The signal rates depend on the selected pre-programmed configuration.•A pushbutton associated with each initiating, indicating, and releasing circuit can individually bypass the circuit•Configurable Signal Silence Inhibit and Auto Signal Silence Timers•Subsequent Alarm, Supervisory, and Trouble operation•Relay Contacts for Common Alarm, Common Supervisory, Common Trouble, and Auxiliary Alarm Relay (disconnectable)•RS-485 Interface for RA-1000 Series Remote Multiplex Annunciators and Smart relay Module•Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.•Extensive transient protection•Easy configuration of the panel using LCD service tool (CFG-300)•Releasing circuit protection from false alarm by disconnecting the battery if the voltage falls below 19V

Page 3: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 3

FR-320NetK includes:

BBX-FXMNS FleX-Net™ Backbox

FR-320K FR-320 Main Board and Agent Releasing Kit for FleX-Net™

FX-2000MNS FleX-Net™ Main Board and Chassis

RM-1008A Relay Adder Module

RM-306 Relay Adder Module

DM-1008A Detection Adder Module

SGM-1004A Four Indicating Circuit Module

DSPL-420 Main Display for FX-2000MNS

RAX-1048TZDS Zone Display for FX-2000MNS

MGD-32 Master Graphic Annunciator

RAM-1016TZDS Main Remote LED Annunciator

CH-1181 TR-063 Transformer support for FXMNS box

CH-1183 FR-320 Main PCB Support Plate for FXMNS backbox

CH-1184 RAM-1016TZDS Adaptor Plate

TR-061 FR-320 Transformer

TR-063 FX-2000MNS Transformer

Page 4: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 4 LT-6098 FR-320NetK Rev. 0 June 2015

Physical Installation

Tools needed:

• Hexnut driver

• Phillips screwdriver

Chassis Mounting

Using the CH-1183 support plate, anchor the FR-320K to the FXMNS back box in the area above the FX-2000MNS board. Otherwise, physical installation is as listed in each component’s manual.

Figure 1 Chassis Mounting

Board Mounting

Mount all other boards in as illustrated. Otherwise, physical installation is as listed in each component’s Installation and Operation manuals:

• LT-894 FleX-Net™

• LT-951 FR-320

• LT-847 MGD-32

FR-320Board

FR-320Batteries

FR-320Transformer

FX-2000NBatteries

FX-2000NAC transformer

FX-2000NBoard

BBX-FXMNSBackbox

CH-1181 Support Plate

FR-320K

CH-1183 Support Plate

RM-306Board

DM-1008ABoard

RM-1008ABoard SGM-1004A

Board

Page 5: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 5

Figure 2 Board Mounting Positions in the BBX-FXMNS Backbox

Interior of Inner Door Interior of Backbox

FR-320K

RM-306

FX-2000MNS

DM-1008A RM-1008A

SGM-1004A

RAM-1016TZDS

MGD-32

RAX-1048TZDS

DSPL-420

Page 6: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 6 LT-6098 FR-320NetK Rev. 0 June 2015

Electrical Power Consumption

The FR-320K has its own AC transformer and battery hookups, independent from the other FleX-Net™ components.

Table 1 FR-320K Specifications

FR-320K Fire Control Panel Chassis

General Digital Signal Processor (DSP) based design. Fully configurable using frontpanel LCD display with Password Access.

Indicating (NAC) Circuits

2 supervised style Y (Class B) indicating circuits, configured as strobes oraudibles. Terminals are labeled SIG 1 and SIG 2.

Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit

Initiating Circuits 6 supervised style B (Class B) initiating circuits, configurable. Terminals arelabeled DET. Compatibility ID A.

Power limited / 19VDC reg. / 3mA for detectors /110MVpp AC ripple / 45mA max(alarm short)

Releasing Circuit Terminals are labeled SIG 3 and SIG 4

21.1 VDC@ 1 A max per circuit, 1.7A max combined

Current Consumption Standby: 183mA

Alarm: 318mA

Supervised Auxiliary Power (non resettable)

Power limited / 21.1VDC regulated / 300mA max

RS-485 Connection For Remote Annunciators. Terminals are labeled RS485. Line impedance is 120ohms.

Electrical ratings AC line voltage 120 VAC 60Hz 1.2A / 240 VAC 50 Hz 0.6 A, 10Aslow blow fuse on secondary of transformer

Power Supply Rating 6.5A AC maximum @ secondary of transformer

Max power allowed • 4A

• 1.7A (aux power unfiltered if used)

• 0.5A (aux power filtered if used)

• 0.3A (resettable auxiliary power if used)

• 1.7A (for releasing circuits)

If no auxiliaries are used the max power is 4A for the indicating and the releasingcircuits

Auxiliary relays (resistive loads)

Must be connected to a listed power limited source of supply. Terminals are labelled ALARM, TROUBLE, SUPV and AUX.

Common Alarm Form C, 1 A max, 28 VDC

Common Supv Form C, 1 A max, 28 VDC

Common Trouble Form C, 1 A max, 28 VDC

Aux Relay Form C, 1 A max, 28 VDC

Page 7: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 7

See the LT-951 FR-320 Installation Manual for more information.

Field Wiring

Adding the FR-320K to the FleX-Net™ system is straight forward as both boards are located in the same backbox. This reduces the need for extra conduit and running long cables.

1. For general wiring options (i.e. ribbon cables), refer to these installation and operation manuals:

• LT-894 FleX-Net™

• LT-951 FR-320

• LT-847 MGD-32

• LT-617 RAM-1016TZDS

2.Use the following diagrams to wire up the FR-320K:

Unfiltered supply (full wave rectified)

Power limited / Unregulated / Special Application

1.7A Max, 21.3 VDC to 42.00 VDC

Minimum Load 5mA

Battery Type 24VDC Gel Cell/Sealed lead acid – 10AH to 26AH

Charging capability 10AH~26AH

Current Consumption standby: 200 mA

alarm: 350 mA

Protection 10A on board (F1) slow blow micro fuse

Compliance Type of Service A, M, WF, SS

Type of Signaling Non-Coded

Applicable Standards NFPA 12, 12A, 12B, 12, 15, 16,70,72,2001, UL-864Rev. 9

Table 1 FR-320K Specifications (Continued)

FR-320K Fire Control Panel Chassis

Page 8: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 8 LT-6098 FR-320NetK Rev. 0 June 2015

2.1 Wiring for FR-320K panel

Figure 3 FR-320K Panel

S-+ NCNO C NCNO C NCNO C NCNO C

JW2

JW1

-+ -+ -+ -+ -+ -+

DET 1 DET 2 DET 3 DET 4 DET 5 DET 6

-+ -+ -+ -+ -+ -+

SIG 1 SIG 2 SIG 3 SIG 4 AUX 4-WIRE SPLY

COM

-CO

M+

TRB

TRL

UN

FLTD

SPL

Y

RTI P

ORT

JW5

JW6

JW4

TO P

R-30

0 M

OD

ULE

TO

RM-3

06 R

ELA

Y M

ODUL

E

RS-485 AUX. RELAY ALARM RELAY SUPERVISORY RELAY

TROUBLE RELAY

POW

ERSI

GN

AL

JW7

For f

ront

pan

el p

rogr

amm

ing

use

CFG

-300

confi

gura

tion

tool

not

UL

-864

or U

LC-S

527

lis

ted

. Ple

ase

refe

r to

Doc

umen

t LT-

922

for d

etai

ls.

Initiating zones 1 to 6 Indicating/Releasing zones 1 to 4

P3P4

SYST

EMRE

SET

AC O

NX M ?

GRO

UN

D F

AULT

CPU

FA

IL

ABO

RT

RELE

ASE

COM

MO

N AL

ARM

COM

MO

N S

UPV

REM

OTE

TRO

UBLE

COM

MO

N TR

OUB

LE

BATT

ERY T

ROUB

LE

SIG

NA

LSI

LEN

CE

AUXI

LIA

RYD

ISCO

NN

ECT

LAM

PTE

ST

BUZZ

ER

SILE

NCE

RAC2

(ZO

NE

4)

RAC1

(ZO

NE

3)

NAC

2(Z

ON

E 2)

NAC

1(Z

ON

E 1)

IAC6

(ZO

NE

1)

IAC5

(ZO

NE

5)

IAC4

(ZO

NE

4)

IAC3

(ZO

NE

3)

IAC2

(ZO

NE

2)

IAC1

(ZO

NE

1)

PRE

RELE

ASE

JW5

JW4

Sole

noid

EO

L m

odul

eM

P-32

0R/W

From

RM

-100

8A,

Rela

y 2

and

6

Sole

noid

EO

L m

odul

eM

P-32

0R/W

WAR

NIN

G: E

OL

has t

o be

clo

se n

ippl

e

con

nect

ed to

the

sole

noid

coi

l.

Sole

noid

Coi

l

Sole

noid

Coi

l

From

RM

-100

8A, R

elay

3 a

nd 7

From

RM

-100

8A, R

elay

4 a

nd 8

To

DM

-100

8A IN

8

To

MG

D-3

2RS

-485

Inpu

t

To M

GD

-32

24VD

C IN

PUT

To

DM

-100

8A IN

4

+ - + -

+ -

Rly

2 N

O

Rly

6 C Rly

3 N

ORl

y 7

CRl

y 4

NO

Rly

8 C

STYL

E Y

WIR

ING

STYL

E Y

WIR

ING

IND

ICAT

ING

CIRC

UIT

-1

IND

ICAT

ING

CIRC

UIT

-2

Lege

nd:

BELL

STRO

BE

HO

RN3.

9K 1

/2 W

ATT

ELR

Page 9: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 9

2.2 Wiring for FX-2000MNS

Figure 4 FX-2000MNS Panel

F1

JW6

MAI

N FI

RE A

LARM

BO

ARD

FIEL

D W

IRIN

G T

ERM

INAL

S

P3

P18

P2P1

P16

P15

P10

P11

P4

J1

P9

P7

P5 P6

P8

+ BR

-

+BA

T -

P14

P19

JW1

JW4

JW5

JW2

SW2

18

ON

To A

ddre

ssab

le se

nsor

s an

d m

odul

esre

fer t

o Fl

eX-N

etLT

-894

Man

ual

NAC

0IN

DICA

TIO

N

NAC

1

NAC

2

NAC

3

(PO

WER

-LIM

ITED

)CI

RCUI

T 1

(PO

WER

-LIM

ITED

)

(PO

WER

-LIM

ITED

)

(PO

WER

-LIM

ITED

)

(PO

WER

-LIM

ITED

)

INDI

CATI

ON

CIRC

UIT

2

4-W

IRE

+PO

WER

SUPP

LY- +

AUX.

PO

WER

-

TRB

RTI

INTE

RFAC

ETR

L

2 POOL

B A

+ - + - + -+ - + + - -

INDI

CATI

ON

CIRC

UIT

1

INDI

CATI

ON

CIRC

UIT

2

+ -+ - + + - -

COM

-

NO

NC

COM

NO

NC

COM

NO

NC

+

S

SP4

P3

RS4

85TR

OU

BLE

ALAR

MSU

PV.

CO

MM

ON

TR

OU

BLE

CO

NTA

CTS

24 V

DC

, 1 A

MP

RES

ISTI

VE L

OAD

AUXI

LIAR

Y C

OM

MO

NSU

PERV

ISO

RYC

ON

TAC

TS24

VD

C, 1

AM

PR

ESIS

TIVE

LO

AD

AUXI

LIAR

Y C

OM

MO

NAL

ARM

CO

NTA

CTS

24 V

DC

, 1 A

MP

RES

ISTI

VE L

OAD

SIG

GN

Dor

CO

M(-)

MUS

T BE

CO

NN

ECTE

D TO

A L

ISTE

D P

OW

ER L

IMIT

ED S

UPPL

Y SO

URCE

E+TS

2

I+ _NA

C Ex

tern

al

Pow

er C

onne

ctio

n

Page 10: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 10 LT-6098 FR-320NetK Rev. 0 June 2015

2.3 Wiring for MGD-32

Figure 5 MGD-32 Annunciator Chassis

From RM-1008A Module

Rly 1 NO

Rly 5 C

+

-

S

S

-

+

-+

-+

Note: All circuits are power limited andmust use type FPL, FPLR, or FPLP powerlimited cable.

RS-485 and 24V DC Power Wiring

24 VDC power from FR-320 panel (Twisted Pair)

24 VDC Power to RAM-1016TZDS Module (Twisted Pair)

RS-485 to RAM-1016TZDS Module(Twisted Pair)

RS-485 from FR-320 panel (Twisted Pair)

Page 11: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 11

2.4 Wiring for RAM-1016TZDS

Figure 6 RAM-1016TZDS Main Remote LED Annunciator

+

24 VDCINPUT

-

S

S

-

+

-+

-+

P11

RS-485INPUT

RS-485OUTPUT

24 VDCOUTPUT

24 VDC OUTPUT POWER FROM MGD-32 Module

RS-485 OUTPUT FROM MGD-32 Module

+

-

+

-

Page 12: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 12 LT-6098 FR-320NetK Rev. 0 June 2015

2.5 Wiring for RM-1008A

Figure 7 RM-1008A 8 Relay Adder Module

AUX RELAY 1~8CONTACTS28 VDC, 1 AMPRESISTIVE LOAD

AU

X R

ELAY

5C

ON

TAC

TS28

VD

C, 1

AM

PRE

SIST

IVE

LOA

D

AU

X R

ELAY

6C

ON

TAC

TS28

VD

C, 1

AM

PRE

SIST

IVE

LOA

D

AU

X R

ELAY

7C

ON

TAC

TS28

VD

C, 1

AM

PRE

SIST

IVE

LOA

D

AU

X R

ELAY

8C

ON

TAC

TS28

VD

C, 1

AM

PRE

SIST

IVE

LOA

D

RLY

1RL

Y 5

RLY

6

RLY

7

RLY

8

RLY

2

RLY

3

RLY

4

CO

M

CO

M

CO

M

NC

CO

M

NC

NC

NC

NO

NC

CO

M

NO

NC

CO

M

NO

CO

M

NC

NO

CO

M

NC

NO

NO

NO

NO

To DET1 on FR-320 panel

To DET5 on FR-320 panel

To DET6 on FR-320 panel

Det 1-Det 1+

Det 5+Det 5-

Det 6+Det 6 -

Relay 1 NO

Relay 5 C

Relay 6 C

Relay 2 NO

Relay 3 NO

Relay 7 C

Relay 8 C

Relay 4 NO

Relay 7 NC

Relay 8 NC

Relay 5 NC

To System Rese t on MGD-32 module

System Reset

COM

Page 13: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 13

2.6 Wiring for RM-306

Figure 8 RM-306 Six Relay Adder Module

P1

To DM-1008A Relay INI7

INI7-INI7+

Page 14: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 14 LT-6098 FR-320NetK Rev. 0 June 2015

2.7 Wiring for DM-1008A

Figure 9 DM-1008A Module

INI 1

+

INI 1

-

INI 2

+

INI 2

-

INI 3

+

INI 3

-

INI 4

+

INI 4

-

INI 2

STYL

E B/

D

INI 1

STYL

E B/

D

STYL

E B

(CLA

SS B

)W

IRIN

G

SUPE

RVIS

ED IN

ITIA

TIN

G C

IRCU

IT #

1(A

LARM

ZO

NE)

(PO

WER

LIM

ITED

)

INI 5

+

INI 5

-

INI 6

+

INI 6

-

INI 7

+

INI 7

-

INI 8

+

INI 8

-

INI 4

STYL

E B/

D

INI 3

STYL

E B/

D From

FR-

320

Trou

ble

Rela

y

Not

e: In

itiat

ing

circ

uits

of t

he D

M-1

008A

sho

uld

be S

tyle

B (C

lass

B) b

y de

faul

t . If

Sty

le D

(Cla

ss A

) use

d, th

e Fl

eX-N

et C

onfig

urat

or m

ust b

e se

t to

NO

T us

e Cr

oss-

zone

Det

ectio

n Zo

nes.

3.9K

1/2

WAT

T EL

R

OR

ELRX

-300

/R

3.9K

1/2

WAT

T EL

R

OR

ELRX

-300

/R

STYL

E B

(CLA

SS B

)W

IRIN

G

SUPE

RVIS

ED IN

ITIA

TIN

G C

IRCU

IT #

2(A

LARM

ZO

NE)

(PO

WER

LIM

ITED

)

HEA

T D

ETEC

TOR

Lege

nd:

SMO

KE D

ETEC

TOR

3.9K

1/2

W E

LR L

ISTE

D S

5434

MO

DEL

MP-

300

MAN

UFA

CTU

RED

BY

MIR

COM

PULL

STA

TIO

N

MAN

UAL

REL

EASE

SW

ITCH

Use

MS-

403,

404

USE

ONL

Y NO

CO

NTA

CT

ABO

RT S

WIT

CHCO

NNEC

T A

UL/

ULC

LIS

TED

ABO

RT S

TATI

ON

ACCE

PTAB

LE T

O

THE

AHJ,

CO

MPL

YING

WIT

H TH

E FO

LLO

WIN

G SP

ECIF

ICAT

IONS

MAX

IMUM

IM

PEDE

NCE

=1.

4K O

HM

S RA

TED

CURR

ENT

= 4

5mA

RATE

D VO

LTAG

E= 2

4V

From

RM

-306

Rel

ay A

dder

Mod

ule

Rela

y 3

From

FR-

320

Supe

rvis

ory

Rela

yN

O

C NO

C

NO

C

Page 15: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

LT-6098 FR-320NetK Rev. 0 June 2015 Page 15

Pre- Programmed Mode

Pre-programmed Mode 2 is the FR-320K default program setting which includes new features.

Note: Cross Zone smokes detectors must not use verified alarm.

For more information, see LT-951 FR-320 Installation Manual.

Table 2 Mode 2 Agent Release, Single Hazard, Combined Release

Note: WF or Water Flow is not available.

Zone Configuration

The FleX-Net™ monitors the Detection Zones via relay control. Connect either Detection Zone 1 or 2, but not both.

• Detection Zone -1: Alarm (Hazard Area 1)

• Detection Zone -2: Alarm (Hazard Area 1)

• Detection Zone -5: Abort Switch

• Detection Zone -6: Manual Release

The FR-320K activates the Notification and Releasing Appliance Circuits.

• NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch active

• NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit (optional)

• RAC-1: Releasing Circuit (Hazard Area 1)

• RAC-2: Releasing Circuit (Hazard Area 1)

Hazard Configuration• Default Release Timer Value: 60 seconds

Detection Zones PhantomZones

Release Timers

Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2 RT1 Exp RT2 Exp

Alm Alm WF Sup AB MR Z1+Z2 Z3+Z4

Out1 Signal Steady X X X

Out2 Signal Escalating X

Out3 Rel. Releasing X X

Out4 Rel. Releasing X X

RLS TMR 1 Started X X

RLS Tmr 1 Stopped X

RLS Tmr 1 Canceled X X

RLS Tmr 1 Restarted X X

RLS Tmr 2 Started

RLS Tmr 2 Interrupted

RLS Tmr 2 Canceled

Page 16: LT-6098 FR-320NetK Installation - Mircom · LT-6098 FR-320NetK Installation ... See the LT-951 FR-320 Installation Manual for more information. Field Wiring Adding the FR-320K to

Page 16 LT-6098 FR-320NetK Rev. 0 June 2015

• Default Manual Release Delay: 0 seconds

• Default Abort Delay Type: Standard UL

• Default Soak Timer Value: 0 seconds

NAC Configuration• Default Escalating NAC code of Hazard Area State:

•Hazard Idle: Off•Hazard Alert: Temporal•Hazard Alarm: Temporal•Hazard Release: Steady

• Default NAC code of Supervisory Signal is 20 BPM

How the FR-320K Panel Works in this Mode

The following is an example of how the FleX-Net™ and FR-320K system can work, based on Preprogrammed Mode 2. Full setup options are available via the FleX-Net™ Configurator software.

• Activation of either Z-1 or Z-2 turns NAC-1 on steady

• Activation of either Z-1 or Z-2 changes the Hazard Area 1 state from Idle into Alarm directly. NAC-1 turns on steady. NAC-2 turns on Temporal. Release Timer-1 is started

• Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn on steady

• Activation of Z-6 starts Manual-release Timer 1 (MDT-1) and overrides the abort function in any situation. NAC-1 turns on steady. NAC-2 turns on Temporal. Upon the expiration of MDT-1, RAC-1 and RAC-2 turn on.

• During Hazard Alarm state, if Z-5 is pressed, Release Timer-1 is stopped, reset, and then restarted. If Z-5 is held for up to 50 seconds then the release device will actuate in 60 seconds after first pressing the abort switch. However, if Z-5 is held for longer than 50 seconds then the release device will actuate in 10 seconds.

Compatible Solenoids

The following table lists the solenoids with the FR-320K.

Manufacturer and Series Part Number Extended Description

Parker 73212BN4TNLVNOC322C2 Valve Solenoid

Siemens 500-697913BG Valve Solenoid

ASCO8210G207 Valve Solenoid

T8210A107 Valve Solenoid

BSCO 510006 Actuator

TSP 17842 Actuator

Kidde-Fenwal 486500-01 Actuator

TLX Technologies PA0036 Actuator