  • ANUPPUR THERMAL POWER PROJECT PHASE-I (2X600MW)

    AT ANUPPUR, MADHYA PRADESH (INDIA)

    Owner: MB POWER (MADHYA PRADESH) LTD. 235-B, OKHLA INDUSTRIAL ESTATE, PHASE-III

    NEW DELHI 110 020

    Owners Consultant:

    EPCContractor: LANCO INFRATECH LTD. (EPC DIVISION)

    PLOT NO. 404-405, UDYOG VIHAR PHASE-III GURGAON, HARYANA, INDIA

    Vendor:

    KEC INTERNATIONAL LIMITED

    Document Title: Technical Data Sheet

    LITL Document No.: LITL-020-ELV-320-S-71933-R3

    Vendor Doc. No.

    JB / GVC 12-07-2013

    12-07-2013

    TCE.5657B-EL-CO-700-601

  • LANCO INFRATECH LTD. (EPC DIVISION) PLOT NO. 404-405, UDYOG VIHAR PHASE-III

    GURGAON, HARYANA (INDIA)

    ANUPPUR THERMAL POWER PROJECT PHASE-I (2X600MW)

    AT ANUPPUR, MADHYA PRADESH (INDIA)

    LITL Document No.

    R3

    REVNO.

    DATE STATUS INTLS SGN INTLS SGN INTLS SGN INTLS SGN

    PRPD. BY CHKD. BY APPR. BY ISSUE

    AUTHORISATION

    (This document is a property of LIT Ltd. This is not transferable and shall not be used for any purpose other than for which it is supplied)

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India India

    3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS A2XFY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 3C x 16 Sq.mm 3C x 35 Sq.mm 3C x 70 Sq.mm

    6 No. of core 3 3 3

    7 Rated voltage 1100 V 1100 V 1100 V

    8

    Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C

    62 104 158

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    65 102 146

    9

    Short circuit withstand capacity and duration for one second

    a. Conductor 1.51 3.31 6.61

    9 Conductor

    a.

    Material H4 Grade Aluminium (

    Class-2 ) to IS: 8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS: 8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    b.

    No. of strand/Approx diameter of each strand

    7/1.72 7/2.52 19/2.14

    c. Shape of Conductor Sector Sector Sector

    d. Diameter of conductor 4.1 6.1 8.6

    e.

    Nominal cross section areain sq. mm.

    16 35 70

    f. Max. D. C. resistance at 20 deg. C

    1.91 0.868 0.443

    g. Conductor temperature 90 90 90

    h. S/C conductor temprature 250 250 250

    10 Insulation

    a.

    Material Cross Linked

    Polyethylene(XLPE) as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE)

    as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE)

    as per IS:7098/I/1988

    b. Nominal thickness (in mm) 0.70 0.90 1.10

    c. Minimum thickness(in mm) 0.53 0.71 0.89

    d. Identification of cores Red,Yellow & Blue Red,Yellow & Blue Red,Yellow & Blue

    e. Insulation temperature 90 90 90

    f.

    Type of extrusion & curing process

    Sioplas single Extrusion & Hot Water

    Curing

    Sioplas single Extrusion & Hot

    Water Curing

    Sioplas single Extrusion & Hot

    Water Curing

    g. Diameter over insulation 5.5 7.9 10.8

    11 Inner sheath

    a. Min. thichkness 0.30 0.30 0.40

  • b. Wrapped or Extruded Extruded Extruded Extruded

    c. Colour Black Black Black

    d. Approx. dia. Over inner sheath

    13.0 17.9 24.0

    e.

    Material and Type of inner sheath (if required)

    PVC Type `ST2' to IS:5831/84

    PVC Type `ST2' to IS:5831/84

    PVC Type `ST2' to IS:5831/84

    f. Filler material

    Gaps can be filled by PVC during the extruded PVC

    innersheathing wherever applicable.

    Gaps can be filled by PVC during the extruded PVC

    innersheathing wherever applicable.

    Gaps can be filled by PVC during the extruded PVC

    innersheathing wherever applicable.

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS" PVC

    Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as

    per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as

    per IS:5831/84 b. Material

    c. Colour Black Black Black

    d.

    Min. thickness of Outer

    sheath 1.24 1.40 1.56

    e. Tolerance on diameter

    2 mm

    2 mm

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Flat Strip as per IS:3975

    Galvanised Steel Flat Strip as per IS:3975

    Galvanised Steel Flat Strip as per IS:3975

    b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8 4.0 x 0.8

    c. Whether galvanized:(Yes/No)

    Yes Yes Yes

    d.

    Diameter of cable over armouring mm):

    15.0 19.9 25.9

    e. Armour coverage area (%) 90% 90% 90%

    f.

    Maximum DC resistance at

    20C (ohm/km) 4.77 4.16 3.12

    g. No of wires/Strips required 8 11 15

    14

    Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC

    1.91 0.868 0.443

    b. A.C resistance at 90degC 2.44 1.11 0.567

    c. Reactance at 50Hz(App) 0.0815 0.0794 0.0752

    d. Capacitance (App) 0.401 0.464 0.490

    e. Impedance(App) 2.4414 1.1128 0.572

    15 Finished Cable

    a.

    Diameter over laid up core (Calculated)

    12.7 18.4 25.1

    b.

    Diameter under armor in mm (Claculated)

    13.3 19.0 25.9

    c.

    Diameter over armor in mm (Calculated)

    14.9 20.6 27.5

    16 Max. Pulling force 3 kg/mm of

    Aluminium area 3 kg/mm of

    Aluminium area 3 kg/mm of

    Aluminium area

    17 Cable Drum

    a. Material Wooden Wooden Wooden

    b. Dimension of drum(App) 950 x 300 x 650 1400 x 600 x 650 1200 x 575 x 650

    c. Shipping Weight(App) 608 1088 886.5

  • d. Drum Weight(Without cable) (App)

    105 270 220

    e. Cable pulling eye yes/No No No No

    18 Recommended bending radius

    12 times Overall diameter

    12 times Overall diameter

    12 times Overall diameter

    19 Derating Factor Refer Catalogue Refer Catalogue Refer Catalogue

    20 Group rating factor Refer Catalogue Refer Catalogue Refer Catalogue

    21

    Overall dia. of cable (in

    mm)(

    2mm tolerance) 18 24 30

    22

    Weight per 1000 metre (in

    Kg.) 503 818 1333

    23 Standard drum length offered

    1000 1000 500

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29% Min. 29% Min. 29%

    25a.

    Minimum temperature

    index(C) Min. 2500C Min. 2500C Min. 2500C

    25b. Maximum smoke density rating(%)

    Max. 60% Max. 60% Max. 60%

    25c Maximum acid gas generation(%)

    20% Max. 20% Max. 20% Max.

    25d. Flammability test As per IEC-60332-

    1/SS-424-1475 As per IEC-60332-

    1/SS-424-1475 As per IEC-60332-

    1/SS-424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    27 Marking on Drums As per IS:7098

    part(1)/88 As per IS:7098

    part(1)/88 As per IS:7098

    part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India India

    3 Type Designation A2XWaY:FRLS A2XWaY:FRLS A2XWaY:FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 1C x 16 Sq.mm 1C x 35 Sq.mm 1C x 70 Sq.mm

    6 No. of core 1 1 1

    7 Rated voltage 1100 V 1100 V 1100 V

    8

    Continuous current rating for max. conductor temperature:

    a.

    When laid in air at an ambient Temp. of 50 deg. C 65 109 169

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    68 102 148

    9

    Short circuit withstand capacity and duration for one second

    a. Conductor 1.51 3.31 6.61

    9 Conductor

    a.

    Material

    H4 Grade Aluminium ( Class-

    2 ) to IS: 8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    b.

    No. of strand/Approx diameter of each strand

    7/1.72 7/2.52 19/2.14

    c. Shape of Conductor Compacted Circular Compacted Circular Compacted Circular

    d. Diameter of conductor 5.0 6.8 9.6

    e.

    Nominal cross section areain sq. mm.

    16 35 70

    f. Max. D. C. resistance at 20 deg. C

    1.91 0.868 0.443

    g. Conductor temperature 90 90 90

    h. S/C conductor temprature

    250 250 250

    10 Insulation

    a.

    Material

    Cross Linked Polyethylene(XLPE)

    as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE)

    as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE) as per IS:7098/I/1988

    b. Nominal thickness (in mm)

    1.00 1.20 1.40

    c. Minimum thickness(in mm)

    0.80 0.98 1.16

    d. Identification of cores Black Black Black

    e. Insulation temperature 90 90 90

    f.

    Type of extrusion & curing process

    Sioplas single Extrusion & Hot

    Water Curing

    Sioplas single Extrusion & Hot

    Water Curing

    Sioplas single Extrusion & Hot Water Curing

  • g. Diameter over insulation 7.0 9.2 12.4

    11 Inner sheath

    a. Min. thichkness N.A N.A N.A

    b. Wrapped or Extruded N.A N.A N.A

    c. Colour N.A N.A N.A

    d. Approx. dia. Over inner sheath

    N.A N.A N.A

    e.

    Material and Type of inner sheath (if required)

    N.A N.A N.A

    f. Filler material N.A N.A N.A

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS"

    PVC Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as

    per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as per

    IS:5831/84 b. Material

    c. Colour Black Black Black

    d.

    Min. thickness of Outer

    sheath 1.24 1.24 1.24

    e. Tolerance on diameter

    2 mm

    2 mm

    2 mm

    13 Armour

    a. Material & shape : Hard Drawn

    Aluminium Round Wire as per IS:8130

    Hard Drawn Aluminium Round Wire as per IS:8130

    Hard Drawn Aluminium Round Wire as per

    IS:8130

    b. Diameter of wire : 1.4 1.4 1.4

    c. Whether galvanized:(Yes/No)

    N.A N.A N.A

    d.

    Diameter of cable over armouring mm):

    10.2 12.3 15.4

    e. Armour coverage area (%)

    90% 90% 90%

    f.

    Maximum DC resistance at 20C (ohm/km) 1.35 0.76 0.99

    g. No of wires/Strips required

    14.0 19.0 25.0

    14

    Electrical Parameter at maximum Operating

    temperature

    a. Max. DC resistance at 20degC

    1.91 0.868 0.443

    b. A.C resistance at 90degC 2.44 1.11 0.567

    c. Reactance at 50Hz(App) 0.101 0.097 0.091

    d. Capacitance (App) 0.371 0.45 0.512

    e. Impedance(App) 2.4421 1.1142 0.5743

    15 Finished Cable

    a.

    Diameter over laid up core (Calculated)

    N.A N.A N.A

    b.

    Diameter under armor in mm (Claculated)

    6.5 9.1 12.2

    c.

    Diameter over armor in mm (Calculated)

    9.3 11.9 15

    16 Max. Pulling force 3 kg/mm of

    Aluminium area 3 kg/mm of

    Aluminium area 3 kg/mm of Aluminium

    area

    17 Cable Drum

    a. Material Wooden Wooden Wooden

  • b. Dimension of drum(App) 950 x 300 x 650 950 x 300 x 650 950 x 300 x 650

    c. Shipping Weight(App) 316 408 559

    d. Drum Weight(Without cable) (App)

    105 105 105

    e. Cable pulling eye yes/No No No No

    18 Recommended bending radius

    15 times Overall diameter

    15 times Overall diameter

    15 times Overall diameter

    19 Derating Factor Refer Catalogue Refer Catalogue Refer Catalogue

    20 Group rating factor Refer Catalogue Refer Catalogue Refer Catalogue

    21

    Overall dia. of cable (in mm)(

    2mm tolerance) 13 16 19

    22 Weight per 1000 metre (in Kg.)

    211 303 454

    23 Standard drum length offered

    1000 1000 1000

    24 FRLS Properties on outer

    25 Oxygen index in room (%)

    Min. 29% Min. 29% Min. 29%

    25a.

    Minimum temperature

    index(C) Min. 2500C Min. 2500C Min. 2500C

    25b. Maximum smoke density rating(%)

    Max. 60% Max. 60% Max. 60%

    25c Maximum acid gas generation(%)

    20% Max. 20% Max. 20% Max.

    25d. Flammability test As per IEC-60332-

    1/SS-424-1475 As per IEC-60332-

    1/SS-424-1475 As per IEC-60332-1/SS-

    424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    " KEC INTL. LTD., 'RPG-

    CABLES' , 1100V, ELECTRIC CABLE, NO.

    OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER LTD"

    YEAR."

    27 Marking on Drums As per IS:7098

    part(1)/88 As per IS:7098

    part(1)/88 As per IS:7098

    part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India

    3 Type Designation A2XFaY:FRLS A2XFaY:FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 1C x 300 Sq.mm 1C x 630 Sq.mm

    6 No. of core 1 1

    7 Rated voltage 1100 V 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C 457 732

    b.

    When buried in soil having thermal Resistivity of 150

    deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    337 499

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 28.34 59.52

    9 Conductor

    a.

    Material

    H4 Grade Aluminium (

    Class-2 ) to IS: 8130/1984

    H4 Grade Aluminium (

    Class-2 ) to IS: 8130/1984

    b. No. of strand/Approx diameter of each strand 37/3.18 55/3.84

    c. Shape of Conductor

    Compacted Circular

    Compacted Circular

    d. Diameter of conductor 20.0 29.4

    e. Nominal cross section area in sq. mm. 300 630

    f. Max. D. C. resistance at 20 deg. C 0.100 0.0469

    g. Conductor temperature 90 90

    h. S/C conductor temprature 250 250

    10 Insulation

    a.

    Material

    Cross Linked

    Polyethylene(XLPE) as per

    IS:7098/I/1988

    Cross Linked

    Polyethylene(XLPE) as per

    IS:7098/I/1988

    b. Nominal thickness (in mm) 2.10 2.80

    c. Minimum thickness(in mm) 1.79 2.42

    d. Identification of cores Black Black

    e. Insulation temperature 90 90

    f.

    Type of extrusion & curing process Sioplas single

    Extrusion & Hot Water Curing

    Sioplas single Extrusion & Hot

    Water Curing

    f. Diameter over insulation 24.2 35.0

    11 Inner sheath

    a. Min. thichkness N.A N.A

    b. Wrapped or Extruded N.A N.A

  • c. Colour N.A N.A

    d. Approx. dia. Over inner sheath N.A N.A

    e. Material and Type of inner sheath (if required) N.A N.A

    f. Filler material N.A N.A

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS"

    PVC Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2'

    as per IS:5831/84 b. Material

    c. Colour Black Black

    d. Min. thickness of Outer sheath 1.56 1.72

    e. Tolerance on diameter

    2 mm

    2 mm

    13 Armour

    a. Material & shape :

    Hard Drawn Aluminium Flat

    Strip as per IS:8130

    Hard Drawn Aluminium Flat

    Strip as per IS:8130

    b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8

    c. Whether galvanized:(Yes/No) N.A N.A

    d. Diameter of cable over armouring mm): 26.4 37.4

    e. Armour coverage area (%) 90% 90%

    f. Maximum DC resistance at 20C (ohm/km) 0.74 0.51

    g. No of wires/Strips required 16 23

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 0.10 0.0469

    b. A.C resistance at 90degC 0.128 0.06

    c. Reactance at 50Hz(App) 0.0857 0.0843

    d. Capacitance (App) 0.693 0.766

    e. Impedance(App) 0.154 0.1034

    15 Finished Cable

    a. Diameter over laid up core (Calculated) N.A N.A

    b. Diameter under armor in mm (Claculated) 23.7 33.9

    c. Diameter over armor in mm (Calculated) 25.3 35.5

    16 Max. Pulling force 3 kg/mm of

    Aluminium area 3 kg/mm of

    Aluminium area

    17 Cable Drum

    a. Material Wooden Wooden

    b. Dimension of drum(App) 1200 x 575 x 650 1500 x 700 x 800

    c. Shipping Weight(App) 859 1538

    d. Drum Weight(Without cable) (App) 220 300

    e. Cable pulling eye yes/No No No

    18 Recommended bending radius

    15 times Overall diameter

    15 times Overall diameter

    19 Derating Factor Refer Catalogue Refer Catalogue

  • 20 Group rating factor Refer Catalogue Refer Catalogue

    21 Overall dia. of cable (in mm)(

    2mm tolerance) 30 42

    22 Weight per 1000 metre (in Kg.) 1277 2475

    23 Standard drum length offered 500 500

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29% Min. 29%

    25a. Minimum temperature index(C) Min. 2500C Min. 2500C

    25b. Maximum smoke density rating(%)

    Max. 60% Max. 60%

    25c Maximum acid gas generation(%) 20% Max. 20% Max.

    25d.

    Flammability test As per IEC-

    60332-1/SS-424-1475

    As per IEC-60332-1/SS-424-

    1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC

    CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER LTD",

    YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC

    CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER LTD",

    YEAR."

    27 Marking on Drums As per IS:7098

    part(1)/88 As per IS:7098

    part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India

    3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 3C x 150 Sq.mm 3C x 240 Sq.mm

    6 No. of core 3 3

    7 Rated voltage 1100 V 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C

    261 357

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth

    of 1000 mm in ground amb. Temp. of 40 deg. C.

    222 291

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 14.17 22.68

    9 Conductor

    a.

    Material H4 Grade Aluminium

    ( Class-2 ) to IS: 8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    b.

    No. of strand/Approx diameter of each strand

    19/3.18 36/2.94

    c. Shape of Conductor Sector Sector

    d. Diameter of conductor 12.0 15.4

    e. Nominal cross section areain sq. mm. 150 240

    f. Max. D. C. resistance at 20 deg. C 0.206 0.125

    g. Conductor temperature 90 90

    h. S/C conductor temprature 250 250

    10 Insulation

    a.

    Material Cross Linked

    Polyethylene(XLPE) as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE) as per

    IS:7098/I/1988

    b. Nominal thickness (in mm) 1.40 1.70

    c. Minimum thickness(in mm) 1.16 1.43

    d. Identification of cores Red,Yellow & Blue Red,Yellow & Blue

    e. Insulation temperature 90 90

    f.

    Type of extrusion & curing process Sioplas single

    Extrusion & Hot Water Curing

    Sioplas single Extrusion & Hot Water Curing

    g. Diameter over insulation 14.8 18.8

    11 Inner sheath

    a. Min. thichkness 0.50 0.60

    b. Wrapped or Extruded Extruded Extruded

    c. Colour Black Black

  • d. Approx. dia. Over inner sheath 32.9 41.5

    e.

    Material and Type of inner sheath (if required)

    PVC Type `ST2' to IS:5831/84

    PVC Type `ST2' to IS:5831/84

    f. Filler material

    Gaps can be filled by PVC during the extruded PVC

    innersheathing wherever applicable.

    Gaps can be filled by PVC during the extruded PVC innersheathing wherever

    applicable.

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS"

    PVC Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as per

    IS:5831/84 b. Material

    c. Colour Black Black

    d. Min. thickness of Outer sheath 1.72 2.04

    e. Tolerance on diameter

    2 mm

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Flat Strip as per IS:3975

    Galvanised Steel Flat Strip as per IS:3975

    b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8

    c. Whether galvanized:(Yes/No) Yes Yes

    d.

    Diameter of cable over armouring mm):

    34.8 43.5

    e. Armour coverage area (%) 90% 90%

    f.

    Maximum DC resistance at 20C (ohm/km)

    2.19 1.78

    g. No of wires/Strips required 21 27

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 0.206 0.125

    b. A.C resistance at 90degC 0.264 0.16

    c. Reactance at 50Hz(App) 0.0732 0.0719

    d. Capacitance (App) 0.569 0.594

    e. Impedance(App) 0.274 0.1754

    15 Finished Cable

    a. Diameter over laid up core (Calculated) 35.9 45.1

    b.

    Diameter under armor in mm (Claculated)

    36.9 46.3

    c.

    Diameter over armor in mm (Calculated)

    38.5 47.9

    16 Max. Pulling force 3 kg/mm of

    Aluminium area 3 kg/mm of Aluminium

    area

    17 Cable Drum

    a. Material Wooden Wooden

    b. Dimension of drum(App) 1500 x 700 x 800 1800 x 700 x 800

    c. Shipping Weight(App) 1479 2287

    d. Drum Weight(Without cable) (App) 300 500

    e. Cable pulling eye yes/No No No

    18 Recommended bending radius 12 times Overall

    diameter 12 times Overall diameter

  • 19 Derating Factor Refer Catalogue Refer Catalogue

    20 Group rating factor Refer Catalogue Refer Catalogue

    21

    Overall dia. of cable (in mm)(

    2mm

    tolerance) 39 49

    22 Weight per 1000 metre (in Kg.) 2358 3574

    23 Standard drum length offered 500 500

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29% Min. 29%

    25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25

    b. Maximum smoke density rating(%) Max. 60% Max. 60%

    25c Maximum acid gas generation(%)

    20% Max. 20% Max.

    25d.

    Flammability test As per IEC-60332-

    1/SS-424-1475 As per IEC-60332-1/SS-

    424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI Mark, "MB POWER

    LTD" YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V,

    ELECTRIC CABLE, NO. OF CORES X SIZE

    Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB POWER LTD" YEAR."

    27 Marking on Drums As per IS:7098

    part(1)/88 As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India

    3 Type Designation A2XFY(P):FRLS A2XFY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 3.5C x 35 Sq.mm 3.5C x 70Sq.mm

    6 No. of core 3.5 3.5

    7 Rated voltage 1100 V 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C

    104 158

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a

    depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    102 146

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 3.31 6.61

    9 Conductor

    a.

    Material H4 Grade Aluminium (

    Class-2 ) to IS: 8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS: 8130/1984

    b.

    No. of strand/Approx diameter of each strand

    7/2.52 19/2.14

    c. Shape of Conductor Sector Sector

    d. Diameter of conductor 6.8 9.6

    e. Nominal cross section areain sq. mm. 35 70

    f. Max. D. C. resistance at 20 deg. C 0.868 0.443

    g. Conductor temperature 90 90

    h. S/C conductor temprature 250 250

    10 Insulation

    a.

    Material Cross Linked

    Polyethylene(XLPE) as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE) as per

    IS:7098/I/1988

    b. Nominal thickness (in mm) 0.90 1.10

    c. Minimum thickness(in mm) 0.71 0.89

    d. Identification of cores Red,Yellow,Blue & Black Red,Yellow,Blue & Black

    e. Insulation temperature 90 90

    f.

    Type of extrusion & curing process Sioplas single Extrusion

    & Hot Water Curing Sioplas single Extrusion &

    Hot Water Curing

    g. Diameter over insulation 8.6 11.8

    11 Inner sheath

    a. Min. thichkness 0.30 0.40

    b. Wrapped or Extruded Extruded Extruded

    c. Colour Black Black

  • d. Approx. dia. Over inner sheath 20.3 27.5

    e.

    Material and Type of inner sheath (if required)

    PVC Type `ST2' to IS:5831/84

    PVC Type `ST2' to IS:5831/84

    f. Filler material

    Gaps can be filled by PVC during the extruded

    PVC innersheathing wherever applicable.

    Gaps can be filled by PVC during the extruded PVC innersheathing wherever

    applicable.

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS" PVC

    Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84

    b. Material

    c. Colour Black Black

    d. Min. thickness of Outer sheath 1.40 1.56

    e. Tolerance on diameter

    2 mm

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Flat Strip as per IS:3975

    Galvanised Steel Flat Strip as per IS:3975

    b. Diameter of wire : 4.0 x 0.8 4.0 x 0.8

    c. Whether galvanized:(Yes/No) Yes Yes

    d.

    Diameter of cable over armouring mm):

    22.3 29.5

    e. Armour coverage area (%) 90% 90%

    f.

    Maximum DC resistance at 20C (ohm/km)

    3.6 2.7

    g. No of wires/Strips required 12 17

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 0.868 0.443

    b. A.C resistance at 90degC 1.11 0.567

    c. Reactance at 50Hz(App) 0.0794 0.0752

    d. Capacitance (App) 0.464 0.49

    e. Impedance(App) 1.1128 0.572

    15 Finished Cable

    a. Diameter over laid up core (Calculated) 19.0 26.2

    b.

    Diameter under armor in mm (Claculated)

    19.6 27.0

    c.

    Diameter over armor in mm (Calculated)

    21.2 28.6

    16 Max. Pulling force 3 kg/mm of Aluminium

    area 3 kg/mm of Aluminium

    area

    17 Cable Drum

    a. Material Wooden Wooden

    b. Dimension of drum(App) 1400 x 600 x 650 1400 x 600 x 650

    c. Shipping Weight(App) 1220 1035.5

    d. Drum Weight(Without cable) (App) 270 270

    e. Cable pulling eye yes/No No No

    18 Recommended bending radius 12 times Overall

    diameter 12 times Overall diameter

  • 19 Derating Factor Refer Catalogue Refer Catalogue

    20 Group rating factor Refer Catalogue Refer Catalogue

    21

    Overall dia. of cable (in mm)(

    2mm

    tolerance) 26 33

    22 Weight per 1000 metre (in Kg.) 950 1531

    23 Standard drum length offered 1000 500

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29% Min. 29%

    25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25

    b. Maximum smoke density rating(%) Max. 60% Max. 60%

    25c Maximum acid gas generation(%)

    20% Max. 20% Max.

    25d.

    Flammability test As per IEC-60332-1/SS-

    424-1475 As per IEC-60332-1/SS-

    424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V,

    ELECTRIC CABLE, NO. OF CORES X SIZE

    Sq.mm.,Type of Insulation,FRLS,ISI

    Mark, "MB POWER LTD" YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V,

    ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark,

    "MB POWER LTD" YEAR."

    27 Marking on Drums As per IS:7098

    part(1)/88 As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India

    3 Type Designation A2XFY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88

    5 Cable size 4C x 16Sq.mm

    6 No. of core 4

    7 Rated voltage 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C 62

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    65

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 1.51

    9 Conductor

    a.

    Material H4 Grade Aluminium ( Class-2 ) to

    IS: 8130/1984

    b. No. of strand/Approx diameter of each strand 7/1.72

    c. Shape of Conductor Sector

    d. Diameter of conductor 4.6

    e. Nominal cross section areain sq. mm. 16

    f. Max. D. C. resistance at 20 deg. C 1.91

    g. Conductor temperature 90

    h. S/C conductor temprature 250

    10 Insulation

    a.

    Material Cross Linked Polyethylene(XLPE)

    as per IS:7098/I/1988

    b. Nominal thickness (in mm) 0.70

    c. Minimum thickness(in mm) 0.53

    d. Identification of cores Red,Yellow,Blue & Black

    e. Insulation temperature 90

    f.

    Type of extrusion & curing process Sioplas single Extrusion & Hot

    Water Curing

    g. Diameter over insulation 6.0

    11 Inner sheath

    a. Min. thichkness 0.30

    b. Wrapped or Extruded Extruded

    c. Colour Black

  • d. Approx. dia. Over inner sheath 14.9

    e. Material and Type of inner sheath (if required) PVC Type `ST2' to IS:5831/84

    f. Filler material Gaps can be filled by PVC during the extruded PVC innersheathing

    wherever applicable.

    12 Outer sheath

    a. Type of Outer sheath

    Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84

    b. Material

    c. Colour Black

    d. Min. thickness of Outer sheath 1.40

    e. Tolerance on diameter

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Flat Strip as per

    IS:3975

    b. Diameter of wire : 4.0 x 0.8

    c. Whether galvanized:(Yes/No) Yes

    d. Diameter of cable over armouring mm): 16.9

    e. Armour coverage area (%) 90%

    f. Maximum DC resistance at 20C (ohm/km) 4.32

    g. No of wires/Strips required 9

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 1.91

    b. A.C resistance at 90degC 2.44

    c. Reactance at 50Hz(App) 0.0815

    d. Capacitance (App) 0.401

    e. Impedance(App) 2.4414

    15 Finished Cable

    a. Diameter over laid up core (Calculated) 14.3

    b. Diameter under armor in mm (Claculated) 14.9

    c. Diameter over armor in mm (Calculated) 16.5

    16 Max. Pulling force 3 kg/mm of Aluminium area

    17 Cable Drum

    a. Material Wooden

    b. Dimension of drum(App) 1200 x 575 x 650

    c. Shipping Weight(App) 837

    d. Drum Weight(Without cable) (App) 220

    e. Cable pulling eye yes/No No

    18 Recommended bending radius 12 times Overall diameter

  • 19 Derating Factor Refer Catalogue

    20 Group rating factor Refer Catalogue

    21 Overall dia. of cable (in mm)(

    2mm tolerance) 21

    22 Weight per 1000 metre (in Kg.) 617

    23 Standard drum length offered 1000

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29%

    25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%

    25c Maximum acid gas generation(%) 20% Max.

    25d. Flammability test As per IEC-60332-1/SS-424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF

    CORES X SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB

    POWER LTD" YEAR."

    27 Marking on Drums As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make

    KEC International Ltd 'RPG-Cables'

    KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India India

    3 Type Designation Str. A2XWY(P):FRLS Str. A2XWY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88 IS:7098 pt(1)/88

    5 Cable size 3C x 10Sq.mm 4C x 10Sq.mm

    6 No. of core 3 4

    7 Rated voltage 1100 V 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C

    59 59

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth

    of 1000 mm in ground amb. Temp. of 40 deg. C.

    80 80

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 0.94 0.94

    9 Conductor

    a. Material

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    b.

    No. of strand/Approx diameter of each

    strand 7/1.35 7/1.35

    c. Shape of Conductor Circular Circular

    d. Diameter of conductor 4.1 4.1

    e. Nominal cross section areain sq. mm. 10 10

    f. Max. D. C. resistance at 20 deg. C 3.08 3.08

    g. Conductor temperature 90 90

    h. S/C conductor temprature 250 250

    10 Insulation

    a.

    Material Cross Linked

    Polyethylene(XLPE) as per IS:7098/I/1988

    Cross Linked Polyethylene(XLPE) as per IS:7098/I/1988

    b. Nominal thickness (in mm) 0.70 0.70

    c. Minimum thickness(in mm) 0.53 0.53

    d. Identification of cores Red, Yellow & Blue

    Red, Yellow, Blue & Black

    e. Insulation temperature 90 90

    f. Type of extrusion & curing process

    Sioplas single Extrusion & Hot Water Curing

    Sioplas single Extrusion & Hot Water

    Curing

    g. Diameter over insulation 5.5 5.5

    11 Inner sheath

    a. Min. thichkness 0.30 0.30

    b. Wrapped or Extruded Extruded Extruded

    c. Colour Black Black

  • d. Approx. dia. Over inner sheath 13.4 15.0

    e.

    Material and Type of inner sheath (if required)

    PVC Type `ST2' to IS:5831/84

    PVC Type `ST2' to IS:5831/84

    f. Filler material

    Gaps can be filled by PVC during the extruded PVC innersheathing wherever

    applicable.

    Gaps can be filled by PVC during the extruded PVC

    innersheathing wherever applicable.

    12 Outer sheath

    a. Type of Outer sheath Extruded "FRLS" PVC

    Type 'ST2' as per IS:5831/84

    Extruded "FRLS" PVC Type 'ST2' as per

    IS:5831/84 b. Material

    c. Colour Black Black

    d. Min. thickness of Outer sheath 1.24 1.40

    e. Tolerance on diameter

    2 mm

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Round

    Wire as per IS:3975

    Galvanised Steel Round Wire as per

    IS:3975

    b. Diameter of wire : 1.4 1.4

    c. Whether galvanized:(Yes/No) Yes Yes

    d.

    Diameter of cable over armouring mm):

    16.2 17.8

    e. Armour coverage area (%) 90% 90%

    f. Maximum DC resistance at 20C (ohm/km) 3.57 3.20

    g. Approx. No of wires/Strips required 26 29

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 3.08 3.08

    b. A.C resistance at 90degC 3.94 3.94

    c. Reactance at 50Hz(App) 0.0852 0.0852

    d. Capacitance (App) 0.347 0.347

    e. Impedance(App) 3.9409 3.9409

    15 Finished Cable

    a. Diameter over laid up core (Calculated) 10.8 12.1

    b.

    Diameter under armor in mm (Claculated)

    11.4 12.7

    c.

    Diameter over armor in mm (Calculated)

    14.2 15.5

    16 Max. Pulling force 3 kg/mm of Al. area 3 kg/mm of Al. area

    17 Cable Drum

    a. Material Wooden Wooden

    b. Dimension of drum(App) 1000 x 300 x 600 1200 x 575 x 650

    c. Shipping Weight(App) 817 1027

    d. Drum Weight(Without cable) (App) 130 220

    e. Cable pulling eye yes/No No No

    18 Recommended bending radius 12 times Overall diameter

    12 times Overall diameter

    19 Derating Factor Refer Catalogue Refer Catalogue

  • 20 Group rating factor Refer Catalogue Refer Catalogue

    21

    Overall dia. of cable (in mm)(

    2mm

    tolerance) 19 21

    22 Weight per 1000 metre (in Kg.) 687 807

    23 Standard drum length offered 1000 1000

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29% Min. 29%

    25a. Minimum temperature index(C) Min. 2500C Min. 2500C 25b. Maximum smoke density rating(%) Max. 60% Max. 60%

    25c Maximum acid gas generation(%) 20% Max. 20% Max.

    25d. Flammability test As per IEC-60332-1/SS-

    424-1475 As per IEC-60332-

    1/SS-424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V,

    ELECTRIC CABLE, NO. OF CORES X SIZE

    Sq.mm.,Type of Insulation,FRLS,ISI Mark,

    YEAR."

    " KEC INTL. LTD., 'RPG-CABLES' ,

    1100V, ELECTRIC CABLE, NO. OF CORES X SIZE Sq.mm.,Type of

    Insulation,FRLS,ISI

    Mark, YEAR."

    27 Marking on Drums As per IS:7098 part(1)/88

    As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India

    3 Type Designation Str. 2XWY(P):FRLS

    4 Applicable Standard IS:7098 pt(1)/88

    5 Cable size 2C x 2.5 Sq.mm

    6 No. of core 2

    7 Rated voltage 1100 V

    8

    Continuous current rating for max. conductor

    temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C 35

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    38

    9

    Short circuit withstand capacity and duration for

    one second

    a. Conductor 0.36

    9 Conductor

    a.

    Material Annealed Stranded Copper ( Class-2 ) to

    IS:8130/84

    b. No. of strand/Approx diameter of each strand 7/0.67

    c. Shape of Conductor Circular

    d. Diameter of conductor 2.0

    e. Nominal cross section areain sq. mm. 2.5

    f. Max. D. C. resistance at 20 deg. C 7.41

    g. Conductor temperature 90

    h. S/C conductor temprature 250

    10 Insulation

    a.

    Material Cross Linked Polyethylene(XLPE) as per

    IS:7098/I/1988

    b. Nominal thickness (in mm) 0.70

    c. Minimum thickness(in mm) 0.53

    d. Identification of cores Red & Black

    e. Insulation temperature 90

    f.

    Type of extrusion & curing process Sioplas single Extrusion & Hot Water Curing

    g. Diameter over insulation 3.4

    11 Inner sheath

    a. Min. thichkness 0.30

    b. Wrapped or Extruded Extruded

  • c. Colour Black

    d. Approx. dia. Over inner sheath 8.4

    e. Material and Type of inner sheath (if required) PVC Type `ST2' to IS:5831/84

    f. Filler material Gaps can be filled by PVC during the

    extruded PVC inner sheathing wherever applicable.

    12 Outer sheath

    a. Type of Outer sheath

    Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84

    b. Material

    c. Colour Black

    d. Min. thickness of Outer sheath 1.24

    e. Tolerance on diameter

    2 mm

    13 Armour

    a. Material & shape : Galvanised Steel Round Wire as per IS:3975

    b. Diameter of wire : 1.4

    c. Whether galvanized:(Yes/No) Yes

    d. Diameter of cable over armouring mm): 11.2

    e. Armour coverage area (%) 90%

    f. Maximum DC resistance at 20C (ohm/km) 6.07

    g. No of wires/Strips required 15

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 7.41

    b. A.C resistance at 90degC 9.48

    c. Reactance at 50Hz(App) 0.1007

    d. Capacitance (App) 0.071

    e. Impedance(App) 9.4805

    15 Finished Cable

    a. Diameter over laid up core (Calculated) 6.4

    b. Diameter under armor in mm (Claculated) 7.0

    c. Diameter over armor in mm (Calculated) 9.8

    16 Max. Pulling force 5 kg/mm of Copper area

    17 Cable Drum

    a. Material Wooden

    b. Dimension of drum(App) 950 x 300 x 650

    c. Shipping Weight(App) 508

    d. Drum Weight(Without cable) (App) 105

    e. Cable pulling eye yes/No No

    18 Recommended bending radius 12 times Overall diameter

  • 19 Derating Factor Refer Catalogue

    20 Group rating factor Refer Catalogue

    21 Overall dia. of cable (in mm)(

    2mm tolerance) 14

    22 Weight per 1000 metre (in Kg.) 403

    23 Standard drum length offered 1000

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29%

    25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%

    25c Maximum acid gas generation(%) 20% Max.

    25d. Flammability test As per IEC-60332-1/SS-424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF CORES X SIZE

    Sq.mm.,Type of Insulation,FRLS,ISI Mark,"MB POWER LTD" YEAR."

    27 Marking on Drums As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps

  • GUARANTEED TECHNICAL PARTICULARS

    1 Make KEC International Ltd 'RPG-Cables'

    2 Country of Manufacturer India

    3 Type Designation A2XFaY:FRLS

    4 Applicable Standard IS:7098 pt(1)/88

    5 Cable size 1C x 120 Sq.mm

    6 No. of core 1

    7 Rated voltage 1100 V

    8 Continuous current rating for max. conductor temperature:

    a. When laid in air at an ambient Temp. of 50 deg. C 245

    b.

    When buried in soil having thermal Resistivity of 150 deg. C Cm/W at a depth of 1000 mm in ground amb. Temp. of 40 deg. C.

    206

    9 Short circuit withstand capacity and duration for one second

    a. Conductor 11.34

    9 Conductor

    a.

    Material H4 Grade Aluminium ( Class-2 ) to IS:

    8130/1984

    b. No. of strand/Approx diameter of each strand 19/2.94

    c. Shape of Conductor Compacted Circular

    d. Diameter of conductor 12.8

    e. Nominal cross section area in sq. mm. 120

    f. Max. D. C. resistance at 20 deg. C 0.253

    g. Conductor temperature 90

    h. S/C conductor temprature 250

    10 Insulation

    a.

    Material Cross Linked Polyethylene(XLPE) as per

    IS:7098/I/1988

    b. Nominal thickness (in mm) 1.50

    c. Minimum thickness(in mm) 1.25

    d. Identification of cores Black

    e. Insulation temperature 90

    f.

    Type of extrusion & curing process Sioplas single Extrusion & Hot Water

    Curing

    f. Diameter over insulation 15.8

    11 Inner sheath

    a. Min. thichkness N.A

    b. Wrapped or Extruded N.A

    c. Colour N.A

  • d. Approx. dia. Over inner sheath N.A

    e. Material and Type of inner sheath (if required) N.A

    f. Filler material N.A

    12 Outer sheath

    a. Type of Outer sheath

    Extruded "FRLS" PVC Type 'ST2' as per IS:5831/84

    b. Material

    c. Colour Black

    d. Min. thickness of Outer sheath 1.40

    e. Tolerance on diameter

    2 mm

    13 Armour

    a. Material & shape : Hard Drawn Aluminium Flat Strip as per

    IS:8130

    b. Diameter of wire : 4.0 x 0.8

    c. Whether galvanized:(Yes/No) N.A

    d. Diameter of cable over armouring mm): 18.0

    e. Armour coverage area (%) 90%

    f. Maximum DC resistance at 20C (ohm/km) 1.18

    g. No of wires/Strips required 10

    14 Electrical Parameter at maximum Operating temperature

    a. Max. DC resistance at 20degC 0.253

    b. A.C resistance at 90degC 0.324

    c. Reactance at 50Hz(App) 0.0879

    d. Capacitance (App) 0.641

    e. Impedance(App) 0.3357

    15 Finished Cable

    a. Diameter over laid up core (Calculated) N.A

    b. Diameter under armor in mm (Claculated) 15.4

    c. Diameter over armor in mm (Calculated) 17

    16 Max. Pulling force 3 kg/mm of Aluminium area

    17 Cable Drum

    a. Material Wooden

    b. Dimension of drum(App) 1200 x 575 x 650

    c. Shipping Weight(App) 821

    d. Drum Weight(Without cable) (App) 220

    e. Cable pulling eye yes/No No

    18 Recommended bending radius 15 times Overall diameter

    19 Derating Factor Refer Catalogue

    20 Group rating factor Refer Catalogue

  • 21 Overall dia. of cable (in mm)(

    2mm tolerance) 22

    22 Weight per 1000 metre (in Kg.) 601

    23 Standard drum length offered 1000

    24 FRLS Properties on outer

    25 Oxygen index in room (%) Min. 29%

    25a. Minimum temperature index(C) Min. 2500C 25b. Maximum smoke density rating(%) Max. 60%

    25c Maximum acid gas generation(%) 20% Max.

    25d. Flammability test As per IEC-60332-1/SS-424-1475

    26 Embossing on outer Sheath

    " KEC INTL. LTD., 'RPG-CABLES' , 1100V, ELECTRIC CABLE, NO. OF CORES X

    SIZE Sq.mm.,Type of Insulation,FRLS,ISI Mark, "MB POWER LTD", YEAR."

    27 Marking on Drums As per IS:7098 part(1)/88

    28 Type of end sealing PVC End Caps