lwc-300/301 operator manual · lwc-300/301 operation manual doc-0361 rev c 9© 2018 droplet...
TRANSCRIPT
LWC-300/301
Liquid Water Content Sensor
Operator’s Manual
DOC-0361, Revision C
2400 Trade Centre Avenue
Longmont, CO 80503 USA
A L L R I G H T S R E S E R V E D
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
i i
C O N T E N T S
1.0 General Introduction ......................................................................................... 4
1.1 Software License ................................................................................................................... 4
1.2 Warranty ............................................................................................................................... 4
2.0 Product Introduction ......................................................................................... 4
2.1 General Specifications ........................................................................................................... 6
2.2 Electrical Specifications ......................................................................................................... 6
2.3 Sensing Element Specifications ............................................................................................. 6
2.4 Physical Specifications ........................................................................................................... 6
2.5 Operating Limits .................................................................................................................... 7
3.0 Theory of Operation .......................................................................................... 7
4.0 Installation ........................................................................................................ 8
4.1 Sensor Strut ........................................................................................................................... 8
4.2 Electronic Control Box ........................................................................................................... 8
4.3 System Power ........................................................................................................................ 8
4.4 Anti-Ice Power ....................................................................................................................... 9
5.0 Operation Instructions ...................................................................................... 9
5.1 Ground Testing before use .................................................................................................... 9
5.2 Flight Operations ................................................................................................................... 9
6.0 Servicing or Replacing the LWC Sensor ............................................................. 10
6.1 Testing the LWC sensor card ............................................................................................... 11
7.0 LWC Calculations and Formulas ........................................................................ 13
8.0 Setting Wire Temperature Estimation............................................................... 14
9.0 Data Interpretation .......................................................................................... 14
Appendix A: References ................................................................................................. 15
Appendix B: Wiring Diagrams ........................................................................................ 16
Appendix C: Connections for NI-DAQ Option .................................................................. 19
Appendix D: Mounting Guides ....................................................................................... 20
Appendix E: Min/Max Resistance @ Temp ..................................................................... 21
LWC-300/301 Operation Manual
DOC-0235 Rev C i i i © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
Appendix F: Revisions to Manual .................................................................................. 22
F i g u r e s
Figure 1: Liquid Water Content Sensor Strut (Left) and Control Box (Right) ............................. 5
Figure 2: LWC-300 Circuitry Used to Control Master Coil Temperature .................................... 7
Figure 3: Sensor Strut, Sensor Cable, and Control Box ............................................................. 8
Figure 4: Removing the LWC-301 cover for access to the LWC Sensor card ............................ 10
Figure 5:Removing the LWC Sensor Card .............................................................................. 10
Figure 6: Testing details of the sensor card ........................................................................... 11
Figure 7:Reinserting the sensor card after service ................................................................. 11
Figure 8: Check alignment and seal with O-ring grease ......................................................... 12
Figure 9: Re-assembly of the strut after service .................................................................... 12
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
4
1.0 General Introduction
In no event will Droplet Measurement Technologies, LLC (DMT) be liable for direct, indirect, special,
incidental or consequential damages resulting from any defect or omissions in this manual.
DMT reserves the right to make changes to this manual and the products it describes at any time,
without notice or obligation. Revised editions are found on the manufacturer’s website.
All DMT product names and the Droplet Measurement Technologies Logo are trademarks of Droplet
Measurement Technologies, LLC.
All other brand and product names are trademarks, or registered trademarks, of their respective owners.
1.1 Software License
DMT licenses its software only upon the condition that you accept all of the terms contained in this
license agreement.
This software is provided by DMT “as is” and any express or implied warranties, including, but not limited
to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. Under
no circumstances and under no legal theory, whether in tort, contract, or otherwise, shall DMT or its
developers be liable for any direct, indirect, incidental, special, exemplary, or consequential damages
(including damages for work stoppage; computer failure or malfunction; loss of goodwill; loss of use, data
or profits; or for any and all other damages and losses). Some states do not allow the limitation or
exclusion of implied warranties and you may be entitled to additional rights in those states.
1.2 Warranty
The seller warrants that the equipment supplied will be free from defects in material and workmanship
for a period of eighteen months from date of shipment or 12 months from the date of either installation
or first use whichever comes first. When returning the equipment to DMT for warranty or service
procedures, the equipment owner will pay for shipping to DMT, while DMT will pay the return shipping
expense. Consumable components, such as tubing, filters, pump diaphragms, and Nafion humidifiers and
dehumidifiers are not covered by this warranty.
2.0 Product Introduction
The LWC-300/301 is the DMT implementation of an instrument originally developed by Warren
King at the Australian CSIRO (see Appendix A: References). It is used for measurement of cloud
liquid water content. This sensor, oftentimes referred to as the "King Probe", is used primarily for
the study of cloud micro-physical processes, aircraft icing, aircraft icing certifications, and cloud
seeding.
The LWC-300 operates under the principle that liquid water content can be calculated from
measuring the heat released when water droplets are vaporized. A heated cylinder is exposed to
the airstream and intercepts oncoming droplets. The electronics maintain this sensor at a constant
LWC-300/301 Operation Manual
DOC-0361 Rev C 5 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
temperature (approximately 150o C) and monitors the power required to regulate the temperature
as droplets vaporize. This power is directly related to the amount of heat taken away by convection
plus the heat of vaporization. The convective heat losses are known empirically and vary with
airspeed, ambient temperature and ambient pressure. The liquid water content is calculated from
total power requirements minus convective power losses.
The system consists of a sensing coil held in the external air stream by a heated strut (see Error!
Not a valid bookmark self-reference., left) and an electronic control box with digital signal
processor (Error! Not a valid bookmark self-reference., right). Customers who have purchased the
optional Particle Analysis and Display System (PADS) also receive a computer with PADS software
installed. The electronic control box uses a serial RS-422 protocol to deliver Analog, Digital, or a
simultaneous delivery of both Analog and Digital via a 10-pin connector to communicate with the
PADS software, which displays the amount of power consumed in keeping the wire at the constant
temperature, the calculated LWC, and several housekeeping parameters.
Figure 1: Liquid Water Content Sensor Strut (Left) and Control Box (Right)
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
6
2.1 General Specifications
Measured Parameters: Liquid Water Content
Measured LWC Rangei 0 – 3 g/m3
Output Type Serial, RS-422, 115,200 baud rate, 8-N-1
Air Speed Range 0 – 200 m/sec
Calibration: Not required
Special Features • Interchangeable circuit card sensor
• DSP control
Serial Output Rate 1hz or 10hz
Control Frequency Response >25 Hz
Recorded Parameters See DOC-0290 Rev-A, PADS LWC-300 Manual.pdf
2.2 Electrical Specifications
Operating Power: 28 VDC, 7.5 A maximum
Anti-ice Power: 28 VDC, 8 A
2.3 Sensing Element Specifications
Master Coil length: 2.0 cm
Master Coil diameter: 0.18 cm
Effective wire temperature: 150°C
NOTE: The PADS system is preconfigured with these constant values in place.
2.4 Physical Specifications
Weight:
• Control Box: .5 kg / 1 lb
• Sensor Strut: .6 kg / 1.25 lb
Dimensions:
• Sensor strut: 11.5 cm W x 6.4cm L x 19.5 cm H (4.5” W x 2.5” L x 7.625” H)
• Electronic box: 12.1 cm W x 12.1 cm L x 6.7 cm H (4.75” W x 4.75” L x 2.625” H)
• Electronics box mounting plate: 9.7 cm W x 15.3 cm L x 0.3 cm H (3.8” W x 6.0“ L x 0.1” H)
i Measured range depends on airspeed, temperature, and pressure. 0 – 3 g/m3 is typical.
LWC-300/301 Operation Manual
DOC-0361 Rev C 7 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
2.5 Operating Limits
Altitude: 0 to 12,200 m / 0 to 40,000 ft
Temperature: -40 to +40 °C / -40 to +104 °F
Humidity: 0 – 100%
3.0 Theory of Operation
The hot-wire LWC sensor coil is maintained at approximately 150o C, and acts as a variable resistor
in one arm of a Wheatstone Bridge circuit. The resistance of the sensor wire decreases as the wire
temperature decreases. Temperature decreases can be caused by vaporization of water droplets,
or convective heat losses due to the air density that flows past the sensor. The resistance of the
Master Coil is directly proportional to its temperature. The DSP control circuit maintains the sensor
at constant temperature by maintaining it at a constant resistance. A Wheatstone Bridge is formed
of four resistances, of which the Master Coil LWC sensor is one. The LWC 300 has three fixed
resistors that form the other legs (see Figure 2). To determine current flow through the LWC
sensor, voltage drop across a 0.5Ω resistor is measured and multiplied x2. The voltage at the top of
the Wheatstone Bridge times the current, gives the power required to maintain a constant
resistance (temperature) of the Master Sensing Coil.
The 1K potentiometer and the 8.45K resistor supplies a “Set Point” voltage relative to changes in
the Switching Power Supply’s DC level. This Set Point voltage is used in the control algorithm and
generates an “Error” voltage. When the bridge circuit is in balance, an Error of 1.46V will be logged.
If not in balance, the pulse-width modulated control signal will increase or decrease the duty cycle
as needed.
Figure 2: LWC-300 Circuitry Used to Control Master Coil Temperature
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
8
4.0 Installation
4.1 Sensor Strut
The sensor strut should be mounted on the aircraft with the sensing coil facing forward into the air
stream. The preferable location is on the underside of the wing, away from any obstruction
upstream and an area where there is no prop wash or the possibility of water shedding from
propellers or other surfaces. Mounting on the fuselage of large aircraft should be avoided unless an
extension strut is used to insure the sensing wire is out of the boundary layer, far away from areas
where there may be “shadowing” or disturbed airflow that would bias the measurements. Refer to
Appendix E “Mounting Guides” for dimensions of the strut and control box mount holes.
Consider the aircraft’s research speed and angle-of-attack when selecting a location and
orientation. The sensing strut may require a "skin-doubler” to insure a stable mount. Consult an
aircraft structural engineer before the final location is selected.
CAUTION! Keep the sensor strut and control box away from any transmitting antennas and cables.
These can cause RFI noise problems in electronic control circuits or aircraft communication radios.
Figure 3: Sensor Strut, Sensor Cable, and Control Box
4.2 Electronic Control Box
The control box should be mounted within 1 meter of the Sensor Strut. The factory-supplied cable
should be used to inter-connect the Sensor Strut and the Control Box. See Appendix-C for cable and
wiring details.
4.3 System Power
The 28 VDC system power should be protected with a 10 Amp circuit breaker. The LWC-300/301
can be operated on the ground and not burn out or damage the sensing coil.
DATA POWER
LWC-300/301 Operation Manual
DOC-0361 Rev C 9 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
4.4 Anti-Ice Power
NOTE: The strut will become hot and can be damaged if left activated for extended periods.
The 28 VDC Anti-Ice power should be protected with a 10 Amp circuit breaker. The Anti-Ice power
should be applied just after takeoff and deactivated before landing. If possible, direct the anti-ice
power through a 10A relay which is activated by the aircraft weight-on-wheels switch. If not, pull
the anti-ice circuit breaker when the aircraft is on the ground. The anti-ice system can be tested on
the ground for periods of 15 seconds or less, one can feel the strut warming within that time.
5.0 Operation Instructions
5.1 Ground Testing before use
The LWC system should be tested before flight (1) after initial installation, (2) if a sensor has been
replaced, or (3) if a problem with the system is suspected. See Section 5 for instructions on how to
access the LWC Card. One way to achieve operational validation, direct the output air of a Shop-Vac
onto the sensor coil. This will give sufficient airflow to operate the sensor. At system power-up,
“Start Sampling,” and “Enable Hotwire”. PADS will display a power spike as the sensor reaches
operating temperature. A hand water-sprayer can then be used to add mist to the air flow. PADS
will display the power required to maintain the sensor at operating temperature as the spray cools
the sensor or if air velocity is increased. The “Fixed LWC” display will be accurate if you have
matched the TAS, ambient pressure/temperature with the Shop-Vac and surrounding conditions.
5.2 Flight Operations
System power is typically applied after engine start, Anti-Ice power should be applied after takeoff.
Always deactivate Anti-ice power before landing to preserve your unit.
A “Slave Coil Status” indicator light is displayed at the top of the LWC-300 software tab. A green
light indicates operational Slave Coils. A red light indicates that the Slave Coils have failed. Without
functioning slave coils, the master coil element will have heat loss transversely out of the ends of
the Master Coil. This will negatively influence measurement quality. If Slave Coils have failed, the
sensor PCB should be replaced at first opportunity. View this monitor at the end of each flight to
ensure that the Slave Coil is operational throughout the flight.
Failure of the Master Coil would be indicated by a near-zero power and negative LWC estimation. If
the Master Coil or Slave Coils have failed, replace the sensor with a fresh sensor card before the
next flight (See Section 5).
NOTE: When using Dual mode (Analog +Digital) cable assembly (ASSY-1899), the LWC 300/301
requires serial communication with PADS to begin operating and provide analog output.
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
1 0
6.0 Servicing or Replacing the LWC Sensor
The LWC sensor card is consumable component and will eventually wear out. The sensor life can be
shortened by debris on the runway, bug or bird strikes, hail impacts, or the abrasive nature of flying
through ice crystals. The LWC-300/301 comes with one sensor card installed and 2 spare cards.
1. Using a static dissipative wrist-strap and a 3/32” hex key, unscrew the seven screws that
hold the LWC strut side-plate in place (Figure 4 left).
Figure 4: Removing the LWC-301 cover for access to the LWC Sensor card
2. Open the two sides of the LWC strut. Be careful to not pull the two halves far apart, or the
connecting heater wires (Figure 4 right) could be damaged.
3. Remove the LWC sensor by pulling it out of its edge-card socket (Figure 5). Be careful not to
damage or displace the LWC Strut sealing gaskets that are located under the card.
Figure 5: Removing the LWC Sensor Card
Heater wires
SEALING GASKET
3/32”
Hex key
LWC-300/301 Operation Manual
DOC-0361 Rev C 1 1 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
6.1 Testing the LWC sensor card
Figure 6: Testing details of the sensor card
4. After removing the card, test using an Ohm meter across the specified contacts (Figure 6).
Replace the sensor card if any of the values are below or above specified numbers.
5. Reinstall the card. The card is symmetrical, so it does not matter which side faces up. The
sensor card must be inserted into the socket so that the hole in the card aligns with the
strut screw hole as shown in (Figure 7).
Figure 7: Reinserting the sensor card after service
Slave Coil 1Ω Master Coil 2Ω Slave Coil 1Ω
Socket
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
1 2
6. Apply a thin layer of O-ring grease every time the unit is re-assembled to both O-rings
(arrows) to help prevent water ingestion. (Figure 8).
Figure 8: Check alignment and seal with O-ring grease
7. Make sure the heater wires don’t get pinched when assembling the two halves of the unit.
Carefully screw down the seven screws that secure the LWC strut (Figure 9).
Figure 9: Re-assembly of the strut after service
LWC-300/301 Operation Manual
DOC-0361 Rev C 1 3 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
7.0 LWC Calculations and Formulas
The power dissipated by the sensing wire is the total of the convective, radiative and latent heat of
vaporization losses, i.e.
Pt = Pd + Pr + Pw
The convective heat losses, Pd, result from the air that flows past the heated sensor. The radiative
heat losses are negligible compared to the convective losses and are not included in the overall
heat balance equation. The latent heat losses are a result of water droplets that strike or pass near
the sensor and are vaporized. The convective heat loss term has been empirically derived
(Zukauskas and Ziugzda, 1985) and is related to the Reynolds number and Prandtl number by
Pd = A0πk(Ts - Ta)RexPRy
where k is the thermal conductivity of the air, Ts is the sensor temperature, Ta is the air
temperature, Re is the Reynold's number, Pr is the Prandtl number and A0, x and y are constants for
a heated cylinder at high Reynold's number. The Reynold’s number is expressed as
Re = v
VP
where ρ, V, P and are the air density, velocity, pressure and viscosity, respectively, and d is the
diameter of the sensor. The Prandtl number is the thermal conductivity divided by the viscosity.
The density, viscosity, and thermal conductivity are all functions of temperature. The temperature
used to calculate these quantities is referred to as the film temperature and is normally computed
as the arithmetic average between the sensor temperature and the environmental air temperature.
The heat loss that results from vaporizing droplets is computed as follows:
Pw = ldvw [LV+c(Tb - Ta)]
where l is the sensor length, w is the liquid water content, Lv is the latent heat of vaporization, c is
the specific heat of water, and Tb is the boiling point of water. When the total power is measured,
the liquid water content is calculated as
w = ( ) abv
d
TTclldv −+
−
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
1 4
8.0 Setting Wire Temperature Estimation
The temperature of the sensor wire is difficult to measure directly. The temperature of the sensor
is set at the factory to be approximately 150 °C by using a 60m/s wind tunnel. Each sensor has a
slightly different resistance causing a slightly different effective temperature. The sensor wire
temperature is more accurately determined from actual flight data. Assuming that air speed,
pressure altitude, and ambient temperature are accurately known, and being used by PADS, the
only remaining unknown is the sensor wire temperature. Sensor wire temperature affects the
Reynold’s number, the Prandtl number, and thermal conductivity in the dry air power (DAP) and
LWC calculation. In principle, if the sensor wire temperature is correctly selected in the software,
then the derived LWC value will be equal to zero when in clear dry air. Under the main LWC-300
tab, go to the Tools tab, and you will see an Effective Wire Temperature parameter. Adjust this
value until the LWC, Using Calculated DAP (LWC tab) reads close to zero.
The software setting for the effective sensor wire temperature is very important to the LWC
calculation. If the temperature is too low, the calculated dry air power loss will be too low and the
calculated LWC will be greater than zero in clear air. Likewise, assuming too hot of a temperature
will cause an overestimation of the dry air power term, leading to negative LWC values in clear air.
The best technique is to fly the sensor in clear air over the range of air speeds and temperatures
that the sensor is expected to encounter during normal operation. During these flights, try a
number of different settings for the wire temperature parameter. Select the setting that causes the
smallest possible zero offset under all conditions. Once the optimum sensor wire temperature is
determined, save the configuration file to preserve the new setting for future flights.
9.0 Data Interpretation
The LWC-300/301 sensor is limited by collection efficiency considerations on the small droplet end
of the spectrum and by vaporization time on the large end. The sensor has a diameter of
approximately 1.8 mm and small water droplets, less than 10 µm, will not impact with 100%
efficiency as they follow the airflow around the sensor. These losses are typically about 5% for 10
µm droplets but increase to greater than 20% for diameters less than 5 µm. Since the largest
fraction of the water mass is carried in droplets greater than 10 µm it is not usually necessary to
compensate for the smaller droplet size. In developing clouds, however, near cloud base where
droplets are still quite small, or in cloud edges where entrainment and evaporation is occurring, the
underestimation of liquid water content can be significant.
On the large droplet side, the LWC-300/301 begins to underestimate the liquid water contained in
drops larger than 50µm as a result of incomplete evaporation as these larger droplets impact,
shatter, and water is carried away by the airstream before sufficient heat has been transferred to
vaporize them.
LWC-300/301 Operation Manual
DOC-0361 Rev C 1 5 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
Appendix A: References
• King, W.D., D.A. Parkin, and R.J. Handsworth, 1978: A hot-wire liquid water device having fully
calculable response characteristics, J. Appl. Met., 17, 1809-1813.
• Zukauskas, A. And J. Ziugzda, 1985: Heat Transfer of a Cylinder in a Crossflow, G.F. Hewitt,
Editor, Hemisphere Publishing Corp., Washington D.C., 208 pp.
• DOC-0476 - DB9F PIN Removal and Re-install
• DOC-0290 – PADS Hotwire LWC Module
• DOC – 0342 PADS Appendix C Module
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
1 6
Appendix B: Wiring Diagrams
LWC-300/301 Operation Manual
DOC-0361 Rev C 1 7 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
1 8
LWC-300/301 Operation Manual
DOC-0361 Rev C 1 9 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
Appendix C: Connections for NI-DAQ Option
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
2 0
Appendix D: Mounting Guides
LWC-300/301 Operation Manual
DOC-0361 Rev C 2 1 © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
Appendix E: Min/Max Resistance @ Temp
DOC-0361 Rev C © 2018 DROPLET MEASUREMENT TECHNOLOGIES LLC
2 2
Appendix F: Revisions to Manual
Rev. Date Rev. No. Summary Section
8/21/13 A Updated DOC-0354 for LWC-300 Throughout
10/1/14 A-2 Updated block diagram, Theory of Operation, and
wiring diagram
Throughout
2/20/18 B Updated Wiring diagrams, Reference DOC-0476 Appendices
3/27/18 C “LWC-300/301” New Photos, with and without NIDaq Throughout