© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tc Document Number: F-15479-13 www.schneider-electric.com schneider-electric.com | 1 Installation Instructions MP-3/4xx Series, MP-2/4xxx Series Reversible and Proportional Electric Actuators Application The MP series actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilating, air conditioning, and similar applications. Hazardous location models offer a sturdy cast aluminum case with bolted cover. They have two 3/4" pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for ease of installation. These factory enclosure and actuator assemblies are Underwriters Laboratories Listed. Features Proportional actuators with built-in feedback potentiometers Spring return and non-spring return models available 24 Vac, 120 Vac, and 240 Vac models are available Actuator has a rugged die cast aluminum housing with two 1/2” conduit openings. Hazardous location actuator housing has two 3/4" pipe taped openings for rigid metal conduit connection Oil-immersed motor and gear train Typical Spring Return Typical Non-Spring Return * Refer to Table-5 to identify specific models that are in compliance with CE requirements. Typical MP6 (Hazardous Locations) Typical -6xx Suffix (CP-8301-xxx or CP-8391-91x Installed)

Upload: others

Post on 18-Dec-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M-34 Series, M-24 Series General ... - Schneider Electric

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

www.schneider-electric.com

schneider-electric.com | 1Installation Instructions

MP-3/4xx Series, MP-2/4xxx SeriesReversible and Proportional Electric Actuators

Printed in U.S.A. 6/12 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

ApplicationThe MP series actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilating, airconditioning, and similar applications.

Hazardous location models offer a sturdy castaluminum case with bolted cover. They have two 3/4"pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for easeof installation. These factory enclosure and actuatorassemblies are Underwriters Laboratories Listed.

Features• Proportional actuators with built-in feedback

potentiometers• Spring return and non-spring return models

available• 24 Vac, 120 Vac, and 240 Vac models are available• Actuator has a rugged die cast aluminum housing

with two 1/2” conduit openings.• Hazardous location actuator housing has two 3/4"

pipe taped openings for rigid metal conduitconnection

• Oil-immersed motor and gear train

Applicable Literature• Valve Selection Guide, F-26094• AV-29x Valve Linkage for Hazardous Location Gear

Train Actuators General Instructions, F-27441.• Apparatus for Hazardous Locations EN-56-2,

F-18451.• AV-390 Series, Valve Linkage for Gear Train

Actuators, General Instructions, F-24376• Material Safety Data Sheet MSDS-4• AM-363 Gasket Cover Kit General Instructions,

F-25598• CP-8301 Solid State Actuator Drive General

Instructions, F-14940• CP-8391-716 Electronic Actuator Drive General

Instructions, F-21220• CP-8391-910 Series 4 to 20 mA Electronic Actuator

Drive General Instructions, F-22453• AE-504 Solid State Paralleling Relay General

Instructions, F-16524

Typical Spring Return

Typical Non-Spring Return

* Refer to Table-5 to identify specific models that are incompliance with CE requirements.

Typical MP6(Hazardous Locations)

Typical -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed)

MP-3xx Series, MP-4xx Series, MP-2xxx Series, and

MP-4xxx SeriesReversible and Proportional Electric Actuators

General Instructions

Printed in U.S.A. 6/12 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

ApplicationThe MP series actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilating, airconditioning, and similar applications.

Hazardous location models offer a sturdy castaluminum case with bolted cover. They have two 3/4"pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for easeof installation. These factory enclosure and actuatorassemblies are Underwriters Laboratories Listed.

Features• Proportional actuators with built-in feedback

potentiometers• Spring return and non-spring return models

available• 24 Vac, 120 Vac, and 240 Vac models are available• Actuator has a rugged die cast aluminum housing

with two 1/2” conduit openings.• Hazardous location actuator housing has two 3/4"

pipe taped openings for rigid metal conduitconnection

• Oil-immersed motor and gear train

Applicable Literature• Valve Selection Guide, F-26094• AV-29x Valve Linkage for Hazardous Location Gear

Train Actuators General Instructions, F-27441.• Apparatus for Hazardous Locations EN-56-2,

F-18451.• AV-390 Series, Valve Linkage for Gear Train

Actuators, General Instructions, F-24376• Material Safety Data Sheet MSDS-4• AM-363 Gasket Cover Kit General Instructions,

F-25598• CP-8301 Solid State Actuator Drive General

Instructions, F-14940• CP-8391-716 Electronic Actuator Drive General

Instructions, F-21220• CP-8391-910 Series 4 to 20 mA Electronic Actuator

Drive General Instructions, F-22453• AE-504 Solid State Paralleling Relay General

Instructions, F-16524

Typical Spring Return

Typical Non-Spring Return

* Refer to Table-5 to identify specific models that are incompliance with CE requirements.

Typical MP6(Hazardous Locations)

Typical -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed)

MP-3xx Series, MP-4xx Series, MP-2xxx Series, and

MP-4xxx SeriesReversible and Proportional Electric Actuators

General Instructions

Page 2: M-34 Series, M-24 Series General ... - Schneider Electric

2 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-132 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

SPECIFICATIONS

Actuator InputsInput Control Signals: Refer to the actuator selection tables beginning on page 3 for input control signal capability versus specific actuator models.

Floating, Requires one Single Pole Double Throw (SPDT) switch with floating (center off) position rated at 0.9 amps @ 24 Vac or two Single Pole Single Throw (SPST) switches rated at 0.9 amps @ 24 Vac.Two-Position,

SPDT Requires snap acting switch rated at 0.9 amps @ 24 Vac.SPST Can be used with certain spring return actuators. Switch must be rated to handle actuator power requirements.

Barber-Colman Microtherm, Proportional Electrical system with the following typical controllers: PP-22x series, TP-1xx series, TP-2xx series, TP-3xx series, TP-4xx series, TP-1xxx series, and TP-1xxxx series.

Standard Control of a single actuator.Sequencing Control of two actuators in sequence.Five-Position Used typically for adjustable minimum position (five positions) of an economizer actuator.

Slidewire and Paralleling, Requires AE-504 paralleling relay. Refer to AE-504 Solid State Paralleling Relay General Instructions F-16524. AE-504 accepts 100 Ω to 1000 Ω slidewires.Voltage Vdc, Requires CP-8301-xxx series of solid state actuator drives. Refer to CP-8301 Solid State Actuator Drive General Instructions F-14940. Refer to the actuator selection tables beginning on page 3.Current mAdc, Requires CP-8391-xxx series of solid state actuator drives. Refer to the actuator selection tables beginning on page 3.

Power Requirements: Refer to the actuator selection tables beginning on page 3 to determine power requirements.Connections:

MP-3xx, 4xx, 2xxx, 4xxx, Coded screw terminals.Models with “-600” Suffix, Coded screw terminals except for input signal which are color coded pigtails.

Actuator OutputsTorque: Refer to the actuator selection tables beginning on page 3 to determine the actuator torque rating.Nominal Damper Area: Actuator selection should be made in accordance with the damper manufacturer’s specifications.

Stroke (Degrees of Rotation), Refer to the actuator selection tables beginning on page 3 for information on degrees of rotation.Auxiliary Switch, Refer to the actuator selection tables beginning on page 3 for the models that include an auxiliary switch. Refer to Table-7 for ratings.

Spring Return: Refer to the actuator selection tables beginning on page 3 for models that are spring return.

EnvironmentAmbient Temperature Limits:

Shipping and Storage, -40 to 160 °F (-40 to 71 °C).Operating, -40 to 136 °F (-40 to 58 °C).

Humidity: 5 to 95% RH, non-condensing.Locations: NEMA 1.

NEMA 4 for non-spring return actuators with AM-363. Optional hazardous locations models.

Agency Listings:US Standard UL 873, Underwriters Laboratories (File #E9429 XAPX, Temperature Indicating and Regulating Equipment).Canadian Standard C22.2 No. 24: Underwriters Laboratories (File #E429 Category XAPX7, Temperature Indicating and Regulating Equipment).European Community, EMC Directive (2004/108/EC). Low Voltage Directive (2006/95/EC). Refer to Table-5 to identify specific models that are in compliance with CE requirements.Hazardous Location Models, UL file #E29291. Designed for use in hazardous

IMAGE OR IMAGES

IMAGE OR IMAGES

Page 3: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 3Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 3

loca

tions

N.E

.C.,

Cla

ss 1

, Gro

ups

C a

nd D

, and

Cla

ss 2

, Gro

ups

E, F

, and

G.

Tem

pera

ture

cod

e T6

for h

azar

dous

hou

sing

. Act

uato

rs in

the

actu

ator

sel

ectio

n ta

bles

bel

ow w

ith “-

600”

suf

fix h

ave

the

CP-

8301

-120

fact

ory

inst

alle

d. A

ll C

P-83

01s

have

a fi

xed

span

of 3

Vdc

to d

rive

the

actu

ator

full

stro

ke a

nd a

sta

rt po

int a

djus

tabl

e fro

m 2

to 1

2V

dc (f

acto

ry s

et 6

Vdc

).

The

CP-

8391

-91x

ser

ies

have

a fi

xed

rang

e of

4 to

20

mAd

c to

driv

e th

e ac

tuat

or fu

ll st

roke

. Ref

er to

CP-

8391

-910

Ser

ies

4 to

20

mA

Ele

ctro

nic

Act

uato

r Driv

e G

ener

al In

stru

ctio

ns F

-224

53. T

he C

P-83

91-7

16 h

as a

n ad

just

able

spa

n of

4 to

16

mAd

c (fa

ctor

y se

t for

16)

and

adj

usta

ble

star

t po

int o

f 2 to

16

mAd

c (fa

ctor

y se

t for

4).

The

inpu

t sig

nal o

n C

P-83

91-7

16 is

opt

ical

ly is

olat

ed. R

efer

to C

P-83

91-7

16 E

lect

roni

c A

ctua

tor D

rive

Gen

eral

Inst

ruct

ions

F-2

1220

.

Tabl

e-1

MP-

2xxx

Ser

ies

Mod

el C

hart

.

Tabl

e-2

MP-

3xx

Serie

s M

odel

Cha

rt.

Act

uato

rPa

rtN

umbe

r

Inte

rnal

Wiri

ng(S

eeFi

gure

)

Inpu

t Con

trol

Sig

nal E

xter

nal W

iring

(and

requ

ired

Inte

rfac

e M

odul

e th

at m

ust b

e pu

rcha

sed

sepa

rate

ly)

(See

Fig

ure)

Pow

er R

equi

rem

ents

Out

put S

haft

Aux

.Sw

itch

Bui

lt-in

Tran

s-fo

rmer

b2-

Posi

tion

SPST

Sprin

gR

etur

n

2-Po

sitio

nor

Floa

ting

SPD

T

Bar

ber-

Col

man

Mic

roth

erm

a

(Pro

port

iona

l Ele

ctric

)13

5 to

1,00

Slid

ewire

Volta

ge V

dcC

urre

nt m

Adc

Volts

Hz.

Am

psTo

rque

Lb.-i

n.(N

-m)

Tim

ing

Seco

nds

(No

Load

)D

egre

es o

fR

otat

ion

Sprin

gR

etur

nSt

anda

rdSe

quen

cing

of T

wo

Act

uato

rs

5-Po

sitio

n(A

dj. M

inPo

sitio

n)

MP-

2113

-500

Figu

re-2

7–

Figu

re-5

Figu

re-7

––

Figu

re-1

4 (A

E-50

4)Fi

gure

-17

(CP

-830

1-02

4)Fi

gure

-19

(CP-

8391

-913

)24

602.

250

(5.6

)25

180

(non

Adj

.)N

oSP

DT

MP

-215

0-50

0Fi

gure

-29

–Fi

gure

-6–

––

Figu

re-1

5 (A

E-50

4)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21c o

r Fi

gure

-23d

120

600.

550

(5.6

)25

180

(non

-Adj

.)N

oSP

DT

Yes

Act

uato

rPa

rtN

umbe

r

Inte

rnal

Wiri

ng(S

eeFi

gure

)

Inpu

t Con

trol

Sig

nal E

xter

nal W

iring

(and

requ

ired

Inte

rfac

e M

odul

e th

at m

ust b

e pu

rcha

sed

sepa

rate

ly)

(See

Fig

ure)

Pow

er

Req

uire

men

tsO

utpu

t Sha

ft

Aux

.Sw

itch

Bui

lt-in

Tran

s-fo

rmer

b2-

Posi

tion

SPST

Sprin

gR

etur

n

2-Po

sitio

nor

Floa

ting

SPD

T

Bar

ber-

Col

man

Mic

roth

erm

a

(Pro

port

iona

l Ele

ctric

)13

5 to

1,00

Slid

ewire

Volta

ge V

dcC

urre

nt m

Adc

Volts

Hz.

Am

psTo

rque

Lb.-i

n.(N

-m)

Tim

ing

Seco

nds

(No

Load

)D

egre

es o

fR

otat

ion

Sprin

gR

etur

nSt

anda

rdSe

quen

cing

of T

wo

Act

uato

rs

5-Po

sitio

n(A

dj. M

inPo

sitio

n)

MP-

361

Figu

re-2

4Fi

gure

-3Fi

gure

-5Fi

gure

-7–

–Fi

gure

-14

(AE

-504

)Fi

gure

-17

(CP

-830

1-02

4)Fi

gure

-19

(CP

-839

1-91

3)24

602.

550

(5.6

)90

180

(Adj

.e )C

WS

PD

T–

MP-

367

Figu

re-3

2–

––

Figu

re-1

1–

––

–24

602.

550

(5.6

)90

180

(Adj

.e )C

WSP

ST

MP-

371

Figu

re-2

4Fi

gure

-3Fi

gure

-5Fi

gure

-7–

–Fi

gure

-14

(AE

-504

)

Figu

re-1

7 (C

P-8

301-

024)

Figu

re-1

9 (C

P-8

391-

913)

2460

2.5

50 (5

.6)

9018

0 (n

onAd

j.)C

CW

SP

DT

MP-

377

Figu

re-3

2–

––

Figu

re-1

1–

––

–24

602.

550

(5.6

)90

180

(non

Adj.)

CC

WSP

ST

MP-

379

Figu

re-3

0–

––

–Fi

gure

-12

––

–24

602.

550

(5.6

)90

180

(non

Adj.)

CC

WN

one

MP-

381

Figu

re-2

4–

Figu

re-5

––

–Fi

gure

-14

(AE

-504

)Fi

gure

-17

(CP

-830

1-02

4)Fi

gure

-19

(CP

-839

1-91

3)24

602.

222

0 (2

4.9)

130

180

(Adj

.e )N

oS

PD

T–

MP-

382

Figu

re-2

4–

Figu

re-5

––

–Fi

gure

-14

(AE

-504

)Fi

gure

-17

(CP

-830

1-02

4)Fi

gure

-19

(CP

-839

1-91

3)24

602.

222

0 (2

4.9)

130

to

1300

(Adj

.)18

0 (A

dj.e )

No

SP

DT

MP-

387

Figu

re-3

2–

––

Figu

re-1

1–

––

–24

602.

222

0 (2

4.9)

130

180

(Adj

.e )N

oSP

ST

MP-

389

Figu

re-3

0–

––

–Fi

gure

-12

––

–24

602.

222

0 (2

4.9)

130

180

(Adj

.e )N

oN

one

aTy

pica

l Bar

ber-

Col

man

Mic

roth

erm

Con

trolle

rs: P

P-2

2x S

erie

s; T

P-1x

x Se

ries;

TP-

4xx

Ser

ies;

TP

-101

x S

erie

s; T

P-1

03x

Serie

s; a

nd T

P-1

xxxx

Ser

ies.

bU

nits

with

a “-

2-x”

suf

fix, e

.g. M

P-xx

xx-x

xx-2

-x, i

nclu

de a

bui

lt-in

tran

sfor

mer

(use

d fo

r Bar

ber-

Col

man

Mic

roth

erm

or w

ith A

E-50

4) w

ith s

econ

dary

lead

s w

ired

exte

rnal

ly to

term

inal

s 7

and

8 of

the

actu

ator

. Red

(24

Vac)

to te

rmin

al

8 an

d Bl

ue (1

2Va

c) to

term

inal

7. W

hen

thes

e ac

tuat

ors

are

used

with

con

trolle

rs o

ther

than

Bar

ber-

Col

man

Mic

roth

erm

or A

E-5

04, d

isco

nnec

t the

Red

and

Blu

e le

ads

and

tape

off.

Not

e: M

odel

s pr

ior t

o “-2

-x” s

uffix

had

tra

nsfo

rmer

wire

d di

rect

ly to

pot

entio

met

er. T

o di

scon

nect

the

trans

form

er, r

emov

e th

e ba

ck p

late

of t

he a

ctua

tor,

disc

onne

ct a

nd ta

pe th

e tra

nsfo

rmer

lead

s.c

Req

uire

s C

P-8

391-

910.

dR

equi

res

CP

-839

1-71

6.e

Rot

atio

n ad

just

able

45

to 3

20°.

Cau

tion:

On

actu

ator

s w

ith p

ropo

rtion

al in

put s

igna

ls c

hang

ing

the

rota

tion

will

affe

ct th

e co

ntro

l, si

nce

the

inte

rnal

feed

back

pot

entio

met

er’s

trav

el is

fixe

d.f

MP

-371

mod

els

with

the

“-621

” suf

fix a

re o

bsol

ete.

Page 4: M-34 Series, M-24 Series General ... - Schneider Electric

4 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

4 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Tabl

e-3

MP-

4xx

Serie

s M

odel

Cha

rt.

Act

uato

rPa

rtN

umbe

r

Inte

rnal

Wiri

ng(S

eeFi

gure

)

Inpu

t Con

trol

Sig

nal E

xter

nal W

iring

(and

requ

ired

Inte

rfac

e M

odul

e th

at m

ust b

e pu

rcha

sed

sepa

rate

ly)

(See

Fig

ure)

Pow

er

Req

uire

men

tsO

utpu

t Sha

ft

Aux

.Sw

itch

Bui

lt-in

Tran

s-fo

rmer

b2-

Posi

tion

SPST

Sprin

gR

etur

n

2-Po

sitio

nor

Floa

ting

SPD

T

Bar

ber-

Col

man

Mic

roth

erm

a

(Pro

port

iona

l Ele

ctric

)13

5 to

1,00

0 Ω

Slid

ewire

Volta

ge V

dcC

urre

nt

mA

dcVo

ltsH

z.A

mps

Torq

ueLb

. -in.

(N-m

)

Tim

ing

Seco

nds

(No

Load

)D

egre

es o

fR

otat

ion

Sprin

gR

etur

nSt

anda

rdSe

quen

c-in

gof

Tw

oA

ctua

tors

5-Po

sitio

n(A

dj. M

inPo

sitio

n)

MP

-421

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6560

(6.8

)25

180

(Adj

.e )N

oSP

DT

MP

-422

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6560

(6.8

)25

to 2

50(A

dj.)

180

(Adj

.e )N

oSP

DT

MP

-423

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6560

(6.8

)13

90 (A

dj.e )

No

SPD

T–

MP

-424

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6560

(6.8

)13

to 1

30(A

dj.)

90 (A

dj.e )

No

SPD

T–

MP

-451

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6522

0 (2

4.9)

8018

0 (A

dj.e )

No

SPD

T–

MP

-452

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6522

0 (2

4.9)

80 to

800

(Adj

.)18

0 (A

dj.e )

No

SPD

T–

MP

-453

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6522

0 (2

4.9)

4090

(Adj

.e )N

oSP

DT

MP

-454

Figu

re-2

5–

Figu

re-6

––

––

Figu

re-1

6 (C

P-8

301-

120)

Figu

re-2

0 c o

r Fi

gure

-22d

120

600.

6522

0 (2

4.9)

40 to

400

(Adj

.)90

(Adj

.e )N

oSP

DT

MP-

461-

600

Figu

re-2

5–

1.5

––

––

Figu

re-1

6f–

120

600.6

50 (5

.6)

9018

0 (A

dj.e )

CW

SPD

T–

MP

-465

Figu

re-2

6Fi

gure

-4Fi

gure

-6Fi

gure

-9–

–Fi

gure

-15

(AE

-504

)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21

c or

Figu

re-2

3d12

060

0.6

50 (5

.6)

9018

0 (A

dj.e )

CW

SPD

TYe

s

MP

-470

Figu

re-3

1–

––

–Fi

gure

-13

––

–12

060

0.6

50 (5

.6)

9018

0 (n

on-A

dj.)

CC

WN

one

Yes

MP-

471-

600

Figu

re-2

5–

––

––

–Fi

gure

-16f

–12

060

0.6

50 (5

.6)

9018

0 (n

on-A

dj.)

CC

WSP

DT

MP

-475

Figu

re-2

6Fi

gure

-4Fi

gure

-6Fi

gure

-9–

–Fi

gure

-15

(AE

-504

)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21 c

or

Figu

re-2

3d12

060

0.6

50 (5

.6)

9018

0 (n

on-A

dj.)

CC

WSP

DT

Yes

MP

-480

Figu

re-3

1–

––

–Fi

gure

-13

––

–12

060

0.6

220

(24.

9)13

018

0 (A

dj.e )

No

Non

eYe

s

MP-

481-

600

Figu

re-2

5–

––

––

–Fi

gure

-16f

–12

060

0.6

220

(24.

9)13

018

0 (A

dj.e )

No

SPD

T–

MP

-483

Figu

re-2

6–

Figu

re-6

––

–Fi

gure

-15

(AE

-504

)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21 c

or

Figu

re-2

3d12

060

0.6

220

(24.

9)65

90 (A

dj.e )

No

SPD

TYe

s

MP

-485

Figu

re-2

6–

Figu

re-6

––

–Fi

gure

-15

(AE

-504

)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21 c

or

Figu

re-2

3d12

060

0.6

220

(24.

9)13

018

0 (A

dj.e )

No

SPD

TYe

s

MP

-486

Figu

re-2

6–

Figu

re-6

––

–Fi

gure

-15

(AE

-504

)Fi

gure

-18

(CP

-830

1-12

0)Fi

gure

-21 c

or

Figu

re-2

3d12

060

0.6

220

(24.

9)13

0 to

130

0(A

dj.)

180

(Adj

.e )N

oSP

DT

Yes

MP

-495

gFi

gure

-26

–Fi

gure

-6–

––

Figu

re-1

5 (A

E-5

04)

Figu

re-1

8 (C

P-8

301-

120)

Figu

re-2

1 c o

r Fi

gure

-23d

120

600.

9545

0 (5

0.9)

130

180

(Adj

.e )N

oSP

DT

Yes

Foot

note

s fo

r thi

s ta

ble

are

liste

d on

the

follo

win

g pa

ge.

Page 5: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 5Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 5

Tabl

e-4

MP-

4xxx

Ser

ies

Mod

el C

hart

.

Tabl

e-5

Act

uato

r Par

t Num

bers

that

are

Com

plia

nt w

ith C

E

Act

uato

rPa

rtN

umbe

r

Inte

rnal

Wiri

ng(S

eeFi

gure

)

Inpu

t Con

trol

Sig

nal E

xter

nal W

iring

(and

requ

ired

Inte

rfac

e M

odul

e th

at m

ust b

e pu

rcha

sed

sepa

rate

ly)

(See

Fig

ure)

Pow

er

Req

uire

men

tsO

utpu

t Sha

ft

Aux

.Sw

itch

Bui

lt-in

Tran

s-fo

rmer

b2-

Posi

tion

SPST

Sprin

gR

etur

n

2-Po

sitio

nor

Floa

ting

SPD

T

Bar

ber-

Col

man

Mic

roth

erm

a

(Pro

port

iona

l Ele

ctric

)13

5 to

1,00

0 Ω

Slid

ewire

Volta

ge V

dcC

urre

nt

mA

dcVo

ltsH

z.A

mps

Torq

ueLb

.-in.

(N-m

)

Tim

ing

Seco

nds

(No

Load

)D

egre

es o

fR

otat

ion

Sprin

gR

etur

nSt

anda

rdSe

quen

cing

of T

wo

Act

uato

rs

5-Po

sitio

n(A

dj. M

inPo

sitio

n)

MP

5-46

51Fi

gure

-26

Figu

re-4

Figu

re-6

––

–Fi

gure

-15

(AE-

504)

Figu

re-1

8(C

P-8

301-

240)

Fig

ure-

21c o

r Fi

gure

-23d

240

500.

2550

(5.6

)10

818

0 (A

dj.f )

CW

SPD

TYe

s

MP-

4701

Figu

re-3

1–

––

–Fi

gure

-13

––

–24

060

0.25

50 (5

.6)

9018

0 (n

on-A

dj.)

CC

WN

one

Yes

MP

5-47

51Fi

gure

-26

Figu

re-4

Figu

re-6

––

–Fi

gure

-15

(AE-

504)

Figu

re-1

8 (C

P-8

301-

240)

Figu

re-2

1cor

Fi

gure

-23d

240

500.

2550

(5.6

)10

818

0 (n

on-A

dj.)

CC

WS

PDT

Yes

MP-

4851

Figu

re-2

6–

Figu

re-6

––

–Fi

gure

-15

(AE-

504)

Figu

re-1

8 (C

P-8

301-

240)

Figu

re-2

1c or

Fi

gure

-23d

240

600.

2522

0 (2

4.9)

130

180

(Adj

.f )N

oS

PDT

Yes

MP

5-48

51Fi

gure

-26

–Fi

gure

-6–

––

Figu

re-1

5(A

E-50

4)Fi

gure

-18

(CP

-830

1-24

0)Fi

gure

-21c

or

Figu

re-2

3d24

050

0.25

220

(24.

9)15

618

0 (A

dj.f )

No

SPD

TYe

s

aTy

pica

l Bar

ber-C

olm

an M

icro

ther

m C

ontro

llers

: PP

-22x

Ser

ies;

TP

-1xx

Ser

ies;

TP

-4xx

Ser

ies;

TP

-101

x Se

ries;

TP-

103x

Ser

ies;

and

TP

-1xx

xx S

erie

s.b

Uni

ts w

ith a

“-2-

x” s

uffix

, e.g

. MP-

xxxx

-xxx

-2-x

, inc

lude

a b

uilt-

in tr

ansf

orm

er (u

sed

for B

arbe

r-C

olm

an M

icro

ther

m o

r with

AE

-504

) with

sec

onda

ry le

ads

wire

d ex

tern

ally

to te

rmin

als

7 an

d 8

of th

e ac

tuat

or. R

ed (2

4 Va

c) to

te

rmin

al 8

and

Blu

e (1

2 Va

c) to

term

inal

7. W

hen

thes

e ac

tuat

ors

are

used

with

con

trolle

rs o

ther

than

Bar

ber-

Col

man

Mic

roth

erm

or A

E-5

04, d

isco

nnec

t the

Red

and

Blu

e le

ads

and

tape

off.

Not

e: M

odel

s pr

ior t

o “-2

-x” s

uffix

had

tra

nsfo

rmer

wire

d di

rect

ly to

pot

entio

met

er. T

o di

scon

nect

the

trans

form

er, r

emov

e th

e ba

ck p

late

of t

he a

ctua

tor,

disc

onne

ct a

nd ta

pe th

e tra

nsfo

rmer

lead

s.c

Req

uire

s C

P-83

91-9

10.

dR

equi

res

CP-

8391

-716

.e

Rot

atio

n ad

just

able

45

to 3

20°.

Cau

tion:

On

actu

ator

s w

ith p

ropo

rtion

al in

put s

igna

ls c

hang

ing

the

rota

tion

will

affe

ct th

e co

ntro

l, si

nce

the

inte

rnal

feed

back

pot

entio

met

er’s

trav

el is

fixe

d.f

Inte

gral

sol

id s

tate

driv

e ac

cept

s 2-

15 V

dc v

olta

ge.

gM

P-4

95 is

not

rate

d fo

r UL

or C

SA

MP

-361

-0-0

-2

MP

-363

-0-0

-2

MP

-367

-0-0

-2

MP

-371

-0-0

-2

MP

-377

-0-0

-2

MP

-379

-0-0

-2

MP

-381

-0-0

-2

MP

-382

-0-0

-2

MP

-383

-0-0

-2

MP

-387

-0-0

-2

MP

-389

-0-0

-2

MP

-481

-600

-0-2

MP

-481

-691

-0-2

MP

-481

-692

-0-2

Page 6: M-34 Series, M-24 Series General ... - Schneider Electric

6 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

6 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Table-6 Actuator Part Numbers for Hazardous Location Applications.

Table-7 Auxiliary Switch Ratings.

Standard ActuatorPart Numbers

Hazardous Location Actuator AssembliesPart Numbersa b c

Damper Actuators Valve Actuatorsd

MP-381 — MP6-381

MP-421 — MP6-421

MP-423 MP6-423 —

MP-453 MP6-453 —

MP-483 MP6-483 —

MP-485 — MP6-485

MP-361 — MP6-361

MP-367 — MP6-367

MP-371 — MP6-371

MP-377 — MP6-377

MP-379 — MP6-379

MP-465 — MP6-465

MP-470 — MP6-470

MP-475 — MP6-475

MP5-4651 — MP7-4651

MP5-4751 — MP7-4751a Class 1, Groups C & D, and Class 2, Groups E, F, and G hazardous locations; refer to EN-56-2.b Models for hazardous locations are only available as factory-built enclosure/actuator assemblies.c See standard actuator part number wiring diagrams for wiring terminations.d Hazardous location valve actuators can also be used for hazardous location damper applications.

Switch Electrical Rating 120 Vac 240 VacRunning 5.8 amps 2.9 amps

Locked Rotor 34.8 amps 17.4 amps

Non-Inductive 12 6

Page 7: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 7Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 7

Figure-1 Part Number System for MP-2xxx-xxx-x-x Series Actuators.

Note: This figure is for information only. Do not use it for ordering or selecting product.

5 -50 Hz6 -Includes 60 Hz Hazardous Location Housing7 -50 Hz Hazardous Location Housing

0 - No Transformer Unless Noted in Base Part Number

2 - Internal Transformer3 - Old Engineering Revision

A - Old Actuator (Eng. Revision)Ax10 - Old Actuator Equals - 110 as an ExampleAV5 - Old Actuator Equals - 205 as an Example1xx - Specials100 - AM-363 Installed2xx - Unit Ventilator Specials304 - AE-504 Installed321 - AM 321 Installed332 - AM-332 Installed341 - AM-341 Installed500 - Aux. Switch600 - CP-8301-620 (CP-8301-120) Installed (120 Vac), No Aux. Switch

CP-8301-624 (CP-8301-024) Installed (24 Vac), No Aux. Switch CP-8301-640 (CP-8301-240) Installed (240 Vac), No Aux. Switch

601 - CP-8301-620 (CP-8301-120) Installed (120 Vac), Aux. Switch CP-8301-624 (CP-8301-024) Installed (24 Vac), Aux. Switch CP-8301-640 (CP-8301-240) Installed (240 Vac), Aux. Switch

7xx - OEM Specials

Voltage0 - 120 Vac1 - 240 Vac2 - 208 Vac3 - 24 Vac

1 - 180°, No Transformer3 - 90°, No Transformer5 - 180°, Transformer

1800:1 Gear Train50 Lb.-In. Torque25 Sec./180° @ 60 HzNo Load Timing

MPx-21xx-xxx-x-xMechanical Stops

Motor (Actuator)

Proportional

Page 8: M-34 Series, M-24 Series General ... - Schneider Electric

8 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

8 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Figure-2 Part Number System for MP-3xx, MP-4xx, or MP-4xxx Series Actuators.

Note: This figure is for information only. Do not use it for ordering or selecting product.

Gear Train (Torque/Timing* for 180°)1 - 1025:1 (35 Lb.-In./13 Sec.)2 - 1960:1 (60 Lb.-In./25 Sec.)3 - 2980:1 (85 Lb.-In./35 Sec.)4 - 4018:1 (130 Lb.-In./50 Sec.)5 - 6760:1 (220 Lb.-In./80 Sec.)6 - 6760:1 Spring Return CW (50 Lb.-In./90 Sec.)7 - 6760:1 Spring Return CCW (50 Lb.-In./90 Sec.)8 - 10292:1 (220 Lb.-In./130 Sec.)9 - 10413:1 (450 Lb.-In./130 Sec.)*No Load @ 60 Hz.

1 - 180°, Fixed Speed2 - 180°, Adj. Speed3 - 90°, Fixed Speed4 - 90°, Adj. Speed5 - 180°, Fixed Speed, Transformer6 - 180°, Adj. Speed, Transformer7 - 180°, Fixed Speed, Sequencing8 - 180°, Adj. Speed, 5-Position9 - 180°, Fixed Speed, 5-Position0 - 180°, Fixed Speed, 5-Position, Transformer

A - Old Actuator (Eng. Revision)Ax10 - Old Actuator Equals - 110 as an ExampleAV5 - Old Actuator Equals - 205 as an Example1xx - Specials100 - AM-363 Installed, Not Available on

Spring Return Actuators2xx - Unit Ventilator Specials304 - AE-504 Installed321 - AM-321 Installed332 - AM-332 Installed341 - AM-341 Installed600 - CP-8301-620 (CP-8301-120) Installed (120 Vac)

CP-8301-624 (CP-8301-024) Installed (24 Vac) CP-8301-640 (CP-8301-240) Installed (240 Vac)

7xx - OEM Specials

Voltage3xx -24 Vac4xx -120 Vac4xx1 -240 Vac4xx2 -208 Vac

MPx-xxxx-xxx-x-x

0 - No Transformer Unless Noted in Base Part Number

1 - Leeds Northrup Capacitor Start Motor with Internal Capacitor

2 - Internal Transformer3 - Old Engineering Revision

5 -50 Hz6 -Includes 60 Hz Hazardous Location Housing7 -50 Hz Hazardous Location Housing

Motor (Actuator)

Proportional

Page 9: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 9Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 9

ACCESSORIESDamper linkage accessoriesAM-111 Crank arm for 5/16" (7.9 mm) diameter damper shaftAM-112 Crank arm for 3/8" (9.5 mm) diameter damper shaftAM-113 Crank arm for actuator or 1/2" (12.7 mm) diameter damper shaftAM-115 Crank arm for 7/16" (11.1 mm) diameter damper shaftAM-116 Splined crank arm for actuatorAM-122 Linkage connector, straight typeAM-123 Damper clipAM-125 5/16" x 20" (7.9 mm x 0.5 m) damper rodAM-125-048 5/16" x 48" (7.9 mm x 1.2 m) damper rodAM-132 Ball joint connectorAM-161 Damper linkage kitAM-161-1 Damper linkage kitAM-301 90 degree mounting bracketMiscellaneous actuator accessoriesAM-321 Two step switch kitAM-332 Potentiometer kitAM-341 Four step switch kitAM-342 Two step switch and potentiometer kitAM-363 NEMA 4 gasket kit for non-spring return actuators onlyValve linkage for 50 lb.-in. minimum, 180° actuatorAV-329 Valve linkage for 2-1/2" and 3" VB-9323AV-391 Valve linkage for 15 to 50 mm and 1/2" to 2” VB-72xx or VB-73xx (also valve

linkage for obsolete 1/2” to 1-1/4" VB-92xx or VB-93xx)AV-392 Valve linkage for obsolete 1-1/2" and 2" VB-92xx or VB-93xxAV-395 Valve linkage for 65 and 80 mm VB-9215 or VB-9315, and 2-1/2" to 4" VB-9213 or

VB-9313Valve linkage for 130 lb.-in. minimum, 180° actuatorAV-330 Valve linkage for 2-1/2" and 3" VB-9323AV-352 Valve linkage for 2-1/2" to 6" VB-921x or VB-931x, 4" to 6" VB-9323AV-393 Valve linkage for 15 to 50 mm and 1/2” to 2” VB-72xx or VB-73xx (also valve

linkage for obsolete 1/2" to 1-1/4" VB-92xx or VB-93xx)AV-394 Valve linkage for obsolete 1-1/2" and 2" VB-92xx or VB-93xxAV-396 Valve linkage for 65 and 80 mm VB-9215 or VB-9315, and 2-1/2" to 4" VB-921x or

VB-931xValve Linkage for 50 lb.-in. MP6-xxx and MP7-xxx Hazardous Location ActuatorsAV-291 Valve linkage for ½ to 2" VB-7xxx valves assembled with hazardous location

actuator assemblies.AV-295 Valve linkage for 2½ to 3" VB-9xxx valves assembled with hazardous location

actuator assemblies.Valve Linkage for 220 lb.-in. MP6-xxx and MP7-xxx Hazardous Location ActuatorsAV-293 Valve linkage for ½ to 2" VB-7xxx valves assembled with hazardous location

actuator assembliesAV-296 Valve linkage for 2½ to 3" VB-9xxx valves assembled with hazardous location

actuator assemblies

Page 10: M-34 Series, M-24 Series General ... - Schneider Electric

10 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

10 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

TYPICAL APPLICATIONS (wiring diagrams)

List of FiguresFigure-3 External Wiring for SPST Control of MP-361 and MP-371, 24 Vac

Actuators.page 11

Figure-4 External Wiring for SPST Control of MP-465, MP-475, MP5-4651, and MP5-4751 Line Voltage Actuators.

page 11

Figure-5 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of 24 Vac Actuators MP-361, MP-371, MP-381, MP-382 and MP-2113-500.

page 12

Figure-6 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of Line Voltage Actuators.

page 12

Figure-7 Barber-Colman Microtherm Controller with 24 Vac Actuators – Standard Wiring Diagram.

Page 13

Figure-8 Barber-Colman Microtherm Controller with 24 Vac Actuators – Reversed (Cooling) Wiring Diagram.

page 13

Figure-9 External Wiring of Barber-Colman Microtherm Controller with Line Voltage Actuator – Standard Wiring.

page 14

Figure-10 External Wiring of Barber-Colman Microtherm Controller with Line Voltage Actuator – Reversed (Cooling) Wiring.

page 14

Figure-11 External Wiring for Barber-Colman Microtherm Controller with 24 Vac Sequencing Actuators.

page 15

Figure-12 External Wiring for Barber-Colman Microtherm Controller with Five-Position 24 Vac Actuators.

page 16

Figure-13 External Wiring for Barber-Colman Microtherm Controller with Five-Position Line Voltage Actuator.

page 17

Figure-14 External Wiring for Slidewire Controller with 24 Vac Actuators. page 18

Figure-15 External Wiring for Slidewire Controller with Line Voltage Actuator. page 18

Figure-16 External Wiring for CP-8301-120, Vdc Interface with Line Voltage Actuators without Internal Transformer.

page 19

Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators. page 20

Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line Voltage Actuators with Internal Transformer.

page 21

Figure-19 External Wiring for CP-8391-913, 4 to 20 mAdc Interface with 24 Vac Actuators.

page 22

Figure-20 External Wiring for CP-8391-910, 4 to 20 mAdc Interface with Line Voltage Actuators without Internal Transformer.

page 22

Figure-21 External Wiring for CP-8391-910 and CP-8391-911, 4 to 20 mAdc Interface with Line Voltage Actuators with Internal Transformer.

page 23

Figure-22 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators without Internal Transformer.

page 23

Figure-23 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators with Internal Transformer.

page 24

Figure-24 Internal Wiring for 24 Vac Actuator. page 24

Figure-25 Internal Wiring for Line Voltage Actuators. page 25

Figure-26 Internal Wiring for Line Voltage Actuator with Built-in Transformer. page 25

Figure-27 Internal Wiring for 24 Vac Actuator without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops).

page 26

Figure-28 Internal Wiring for Line Voltage Actuators without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops.)

page 26

Figure-29 Internal Wiring for Line Voltage Actuators without Limit Switches and Built-in Transformer (Actuator is Stall Type with Built-in Mechanical Stops).

page 27

Figure-30 Internal Wiring for 24 Vac Five-Position Actuators. page 27

Figure-31 Internal Wiring for LIne Voltage Five-Position Actuators. page 28

Figure-32 Internal Wiring for 24 Vac Sequencing Actuators. page 28

Page 11: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 11Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 11

Figure-3 External Wiring for SPST Control of MP-361 and MP-371, 24 Vac Actuators.

Figure-4 External Wiring for SPST Control of MP-465, MP-475, MP5-4651, and MP5-4751 Line Voltage Actuators.

4 5 6 7

3 8

2 H

1 GX

Green Wires

SPST Control Switch(Rated to Handle Power

Requirements of Actuator)

To 24 VacPower Supply

Add Jumper

4 5 6 7

3 8

2 H

1 GX

Green Wires

SPST Control Switch(Rated to Handle Power

Requirements of Actuator)

To 24 VacPower Supply

Add Jumper

CaseGround Screw

CaseGround Screw

MP-361 Actuator drives CCW when 24 Vac is applied and spring returns CW with no power.

MP-371 Actuator drives CW when 24 Vac is applied and spring returns CCW with no power.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

SPST Control Switch(Rated to Handle Power

Requirements of Actuator)

To ACPower Supply

Add Jumper

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

SPST Control Switch(Rated to Handle Power

Requirements of Actuator)

To ACPower Supply

Add Jumper

CaseGround Screw

CaseGround Screw

Typical Actuators: MP-465 and MP5-4651 Actuator drives CCW when Power is applied and spring returns CW with no power.

Typical Actuators: MP-475 and MP5-4751 Actuator drives CW when Power is applied and spring returns CCW with no power.

Page 12: M-34 Series, M-24 Series General ... - Schneider Electric

12 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

12 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators: MP-361, MP-371, MP-381, MP-382, and MP-2113-500.

Note: Each pole of a switch or a relay can control only one actuator.

Figure-5 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of 24 Vac Actuators MP-361, MP-371,MP-381, MP-382, and MP-2113-500

Typical Actuators: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-4553, MP-454, MP-465, MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.

Note: Each pole of a switch or a relay can control only one actuator.

Figure-6 External Wiring for SPDT (Snap Acting or Floating) Switch for Control of Line Voltage Actuators.

4 5 6 7

8

H

1 G

Green WiresTo 24 Vac

Power Supply

WhiteBlue

Red

CaseGround Screw

SPDT Snap Acting orFloating Switch ratedfor.9 Amps @ 24 Vac

1 The use of a snap acting switch will result in a two-position control actuator.

2 With actuator terminal X shorted to terminal 2, actuator drives CW. With actuator terminal X shorted to terminal 3, actuator drives CCW. With actuator terminal X open to both terminals 2 and 3, actuator maintains position.

Typical DDCControllers

DO1

DO2

COM

COM

To SPDT Switchor

From 3

From 3

From 2

From X

From 2

CYZR-818Arc Suppressor

Purchased Separately

3

2

X

orDDC Controller

2

1

From X

Typical DDCControllers

DO1

DO2

COM

COM

From 3

From 3

From 2

From X

From 2

From X

4 5 6 7

8

L1

1 L2

Green WiresTo AC

Power Supply

WhiteBlue

Red

CaseGround Screw

SPDT Snap Acting orFloating Switch ratedfor.9 Amps @ 24 Vac

1 The use of a snap acting switch will result in a two-position control actuator.

2 With actuator terminal X shorted to terminal 2, actuator drives CW. With actuator terminal X shorted to terminal 3, actuator drives CCW. With actuator terminal X open to both terminals 2 and 3, actuator maintains position.

Typical DDCControllers

DO1

DO2

COM

COM

To SPDT Switchor

From 3

From 3

From 2

From X

From X

CYZR-818Arc Suppressor

Purchased Separately

3

2

X

orDDC Controller

2

1

From 2

Page 13: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 13Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 13

Typical Actuators: MP-361, MP-371, MP-381, MP-382, and MP-2113-500.

Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of Switch to R and B.

1 =Feedback from actuator (24 Vac with actuator full Counterclockwise rotation (CCW) to 12 Vac at Clockwise rotation (CW) end).

R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).

B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).

Typical Cooling Barber-Colman Microtherm: TP-1031.C =Common of switch to R and B.

1 =Feedback from Actuator (24 Vac with actuator full CCW to 12 Vac at CW end).

R =Closes on temperature rise and drives the actuator CCW (opens valve).

B =Closes on temperature drop and drives the actuator CW (closes valve).

Figure-7 Barber-Colman Microtherm Controller with 24 Vac Actuators – Standard Wiring Diagram.

Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of Switch to R and B.

1 =Feedback from Actuator (12 Vac with Actuator full CCW to 24 Vac at CW end).

R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).

B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).

Figure-8 Barber-Colman Microtherm Controller with 24 Vac Actuators – Reversed (Cooling) Wiring Diagram.

4 5 6 7

3 8

2 H

1 GX

Green WiresTo 24 Vac

Power Supply

CaseGround Screw

C

2

R

1

B

CaseGroundScrew

AddJumper

Add Resistor(Supplied With Actuator)

100

4 5 6 7

3 8

2 H

1 GX

Green WiresTo 24 Vac

Power Supply

CaseGround Screw

C

2

R

1

B

CaseGroundScrew

AddJumper

Add Resistor(Supplied With Actuator)

100

Page 14: M-34 Series, M-24 Series General ... - Schneider Electric

14 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-1314 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.

Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.Standard Wiring:

C=Common of Switch to R and B.

1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).

R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).

B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).

Typical Cooling Barber-Colman Microtherm: TP-1031.C =Common of switch to R and B.

1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).

R =Closes on temperature rise and drives the actuator CCW (opens valve).

B =Closes on temperature drop and drives the actuator CW (closes valve).

Figure-9 External Wiring of Barber-Colman Microtherm Controller with Line VoltageActuator – Standard Wiring.

Typical Actuators: MP-465, MP-475, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-2151-500, MP5-4651, MP5-4751, MP-4851, and MP5-4851.

Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.Reversed Wiring:

C =Common of switch to R and B.

1 =Feedback from actuator (12 Vac with actuator full CCW to 24 Vac at CW end).

R =Closes on temperature (pressure) drop and drives the actuator CW (closes valve).

B =Closes on temperature (pressure) rise and drives the actuator CCW (opens valve).

Figure-10 External Wiring of Barber-Colman Microtherm Controller with Line Voltage Actuator – Reversed (Cooling) Wiring.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire To ACPower Supply

CaseGround Screw

C

2

R

1

B

Blue

Red

ActuatorTransformerLeads

4 5 6 7

3 8

2 L1

1 L2X

Green Wire To ACPower Supply

CaseGround Screw

C

2

R

1

B

Red

Blue

NOTE: ActuatorTransformer LeadsMust Be Reversed

Page 15: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 15Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 15

Typical Actuators: MP-367, MP-377, and MP-387.

Typical Barber-Colman Microtherm Controllers: PP-22x Series, TP-2xx Series, TP-3xx Series, TP-4xx Series, and TP-101x Series.C =Common of switch to R and B.

1 =Feedback from actuators (24 Vac with both actuators full CCW to 12 Vac both full CW).

R =Closes on temperature (pressure) drop and drives the actuator CCW (opens valve).

B =Closes on temperature (pressure) rise and drives the actuator CW (closes valve).

Sequence of OperationOn a temperature rise, the controller completes a circuit through B to terminal 2 of actuator number one, causing CW rotation. When actuator number one reaches the CW end of travel, it transfers the control circuit to actuator number two, causing it to rotate CW. Conversely, on a temperature drop, first actuator number two, then actuator number one rotates to CCW end of travel.

Figure-11 External Wiring for Barber-Colman Microtherm Controller with 24 Vac Sequencing Actuators.

4 5 6 7

3 8

2 H

1 Gx

Green WiresTo 24 Vac

Power Supply

CaseGround Screw

C

2

R

1

B4 5 6 7

3 8

2 H

1 GX

Green Wires

CaseGround Screw

AddJumper

Add Resistor(Supplied With Actuator)

Splice

100

AddJumper

Actuator Number 1Typical Actuators: MP-367,MP-377, and MP-387

RemoveJumper

Actuator Number 2Typical Actuators: MP-367,MP-377, and MP-387

Page 16: M-34 Series, M-24 Series General ... - Schneider Electric

16 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

16 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Barber-Colman Microtherm Controllers: TP-2xx Series, TP-3xx Series, and TP-4xx Series.C =Common of switch to R and B.

1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).

R =Closes on temperature drop and drives the actuator CCW (closes damper).

B =Closes on temperature rise and drives the actuator CW (opens damper).

Cycle of OperationWith the fan running:

1. Rotates actuator to CCW end (damper closed).

2. Allows actuator to modulate between 33% from CCW end to CW (damper open).

3. Allows actuator to modulate between 50% from CCW end to CW (damper open).

4. Allows actuator to modulate between 67% from CCW end to CW (damper open).

5. Rotates actuator to CW end (damper open).

When the fan is off, the damper is closed.

Figure-12 External Wiring for Barber-Colman Microtherm Controller with Five-Position 24 Vac Actuators.

4 5 6 7

3 8

2 H

1 GX

Green WiresTo 24 Vac

Power Supply

CaseGround Screw

C

2

R

1

B

AddJumper

CaseGroundScrew

100

SPDT Relay

To Load ofFan MotorStarter. TheCoil VoltageSame asFan Motor.

Typical Actuators:MP-379 and MP-389

Five-Position Switch

1Close

3 2

5Open

4

Add Resistor(Supplied with Actuator)

Page 17: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 17Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 17

Typical Barber-Colman Microtherm Controllers: TP-2xx Series, TP-3xx Series, and TP-4xx Series.C =Common of switch to R and B.

1 =Feedback from actuator (24 Vac with actuator full CCW to 12 Vac at CW end).

R =Closes on temperature drop and drives the actuator CCW (closes damper).

B =Closes on temperature rise and drives the actuator CW (opens damper).

Cycle of OperationWith the fan running:

1. Rotates actuator to CCW end (damper closed).

2. Allows actuator to modulate between 33% from CCW end to CW (damper open).

3. Allows actuator to modulate between 50% from CCW end to CW (damper open).

4. Allows actuator to modulate between 67% from CCW end to CW (damper open).

5. Rotates actuator to CW end (damper open).

When the fan is off, the damper is closed.

Figure-13 External Wiring for Barber-Colman Microtherm Controller with Five-Position Line Voltage Actuator.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire To ACPower Supply

CaseGround Screw

C

2

R

1

B

Blue

SPDT Relay

To Load ofFan MotorStarter. TheCoil VoltageSame asFan Motor.

Typical Actuators:MP-470, MP-480, and MP-4701

Five-Position Switch

1Close

3 2

5Open

4

Red

ActuatorTransformer Leads

Page 18: M-34 Series, M-24 Series General ... - Schneider Electric

18 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

18 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators which require AE-504 purchased separately: MP-361, MP-371, MP-382, and MP-2113-500.

Figure-14 External Wiring for Slidewire Controller with 24 Vac Actuators.

Typical Actuators which require AE-504 purchased separately: MP-465, MP-475, MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.

Figure-15 External Wiring for Slidewire Controller with Line Voltage Actuator.

4 5 6 7

3 8

2 H

1 GX

Green

To 24 VacPower Supply

CaseGround Screw

AddJumper

CCW CW

COM

Br / Yel

Black

680

680

50Blue / Blk

Red / BlkBrown

AE-504Paralleling Relay

Yel / Blk

Controlling potentiometer: 135 Ω 1.5 watts min.: 1,000 Ω 3 watts min., or AM-332 Actuator Potentiometer Kit.

Wires

1

1 Direction in which actuator will drive.

2 Install two 680 Ω resistors and one 50 Ωresistor. Supplied AE-504.

1

2

4 5 6 7

3 8

2 L1

1 L2X

Green WireTo AC

Power Supply

CaseGround Screw

ActuatorTransformer

CCW CW

COM

Br / Yel

Black

680

680

Blue / Blk

Red / BlkBrown

AE-504Paralleling Relay

Yel / Blk

BlueRed Leads

Controlling potentiometer: 135 Ω 1.5 watts min.: 1,000 Ω 3 watts min., or AM-332 Actuator Potentiometer Kit.

*DirectionActuatorWill Drive

1

21 Direction in which actuator will drive.

2 Install two 680 Ω resistors. Supplied AE-504.

1

Page 19: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 19Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 19

Typical Actuators which require CP-8301-120 purchased separately: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-454.

Typical Actuators with CP-8301-120 factory installed and wired: MP-461-600, MP-471-600, MP-481-600, MP-2110-601.

Note: CP-8301-120 is marked CP-8301-620 on factory assemblies.

Figure-16 External Wiring for CP-8301-120, Vdc Interface with Line VoltageActuators without Internal Transformer.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

CP-8301-120Solid State

Actuator Drive(Vdc InputSignal with3 Vdc FixedSpan and

2 to 12 VdcAdjustableStart Point

Blue (-, Common)

Yellow (+, Input Signal)

Red (+20 Vdc,50 mA Power Supply)

Yellow / BlackBlue / BlackRed / Black

Brown

Brown / White

Brown / Black

Black

White

To ACPower Supply

1

2

1

Red

Yellow

Blue

+20

OP

COM

TypicalControllers

Yellow

Blue

AO

COM

SH

Typical DDCControllers

3

CP-8102SLC-8xxxTP-8xxx

To Controller(Below)

Green / Yellow

1The Blue wire on the CP-8301-120 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and the case ground screw.

2The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.

Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 actuator drive.

Connect Green/Yellow wire from CP actuator drive to case ground screw.

3

4

Page 20: M-34 Series, M-24 Series General ... - Schneider Electric

20 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

20 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators which require CP-8301-024 purchased separately: MP-361, MP-371, MP-381, MP-382, MP-2113-500.

Figure-17 External Wiring for CP-8301-024, Vdc Interface with 24 Vac Actuators.

4 5 6 7

3 8

2 H

1 GX

Green Wires

CaseGround Screw

Yellow / BlackBlue / BlackRed / Black

Brown

Brown / White

Brown / Black

Black / Blue

Black

To 24 VacPower Supply

1

The Blue wire on the CP-8301-024 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal X and the case ground screw.

The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads and reverse the Brown/Black and Brown/White leads.

Whenever it is not connected, tape off the red power supply lead from the CP-8301-024 actuator drive.

Connect Green/Yellow ground wire from CP actuator drive to case ground screw.

1

2

2

CP-8301-024Solid State

Actuator Drive(Vdc InputSignal with3 Vdc FixedSpan and

2 to 12 VdcAdjustableStart Point

Blue (-, Common)

Yellow (+, Input Signal)

Red (+20 Vdc,50 mA Power Supply)

1

Red

Yellow

Blue

+20

OP

COM

TypicalControllers

Yellow

Blue

AO

COM

SH

Typical DDCControllers

3

CP-8102SLC-8xxxTP-8xxx

To Controller(Below)

Green / Yellow

4

3

Page 21: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 21Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 21

Typical Actuators which require CP-8301-120 purchased separately: MP-465, MP-475, MP-483, MP-485, MP-486, MP495, MP-2130-500, MP-2150-500.

Typical Actuators which require CP-8301-240 purchased separately: MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.

Figure-18 External Wiring for CP-8301-120 and CP-8301-240, Vdc Interface with Line VoltageActuators with Internal Transformer.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

Yellow / BlackBlue / BlackRed / Black

Brown

Brown / WhiteBrown / Black

Black

To ACPower Supply

White (CP-8301-120, 120 Vac)White / Black (CP-8301-240, 240 Vac)

TapeRed

Blue

1

3

The Blue wire on the CP-8301-120 and CP-8301-240 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal X and the case ground scree.

The actuator rotates clockwise on an increasing Vdc input signal between Blue (-, Common) and Yellow (+). To rotate the actuator counterclockwise on an increase in input signal, reverse the Blue/Black and Red/Black leads, and reverse the Brown/Black and Brown/White leads.

Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.

Whenever it is not connected, tape off the red power supply lead from the CP-8301-120 or CP-8301-240 actuator drive.

Connect Green/Yellow ground wire from CP actuator drive to case ground screw.

2

Blue (-, Common)

Yellow (+, Input Signal)

Red (+20 Vdc,50 mA Power Supply)

1

CP-8301-120(120 Vac)

CP-8301-240(240 Vac)Solid State

Actuator Drive(Vdc Input Signalwith 3 Vdc Fixed

Span and2 to 12 Vdc

Adjustable StartPoint

3

Yellow

Blue

AO

COM

SH

Typical DDCControllers

4

To Controller(Below)

5

4

2

1

Green / Yellow

Page 22: M-34 Series, M-24 Series General ... - Schneider Electric

22 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-1322 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators which require CP-8391-913 purchased separately: MP-361, MP-371, MP-381, MP-382, MP-2113-500.

Figure-19 External Wiring for CP-8391-913, 4 to 20 mAdc Interface with 24 Vac Actuators.

Typical Actuators which require CP-8391-910 purchased separately: MP-421, MP-422, MP-424, MP-451, MP-452, MP-453, MP-454.

Figure-20 External Wiring for CP-8391-910, 4 to 20 mAdc Interface with Line Voltage Actuators without Internal Transformer.

4 5 6 7

3 8

2 H

1 GX

Green Wires

CaseGround Screw

Blue (-)4 to 20 mAdc

Controller Input

Yellow / BlackBlue / BlackRed / Black

Brown

Brown / White

Brown / BlackCP-8391-913Solid State

Actuator Drive(4 to 20 mAdcNonadjustable

Range)Black

To 24 VacPower Supply

Orange (+)

Black / Blue

1

2

1

Green / Yellow

The Blue wire on the CP-8391-913 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.

The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.

Connect the Green/Yellow ground wire from CP actuator drive to case ground screw.

1

2

3

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

Blue (-)4 to 20 mAdc

Controller Input

Yellow / Black

Blue / Black

Red / BlackBrown

Brown / White

Brown / BlackCP-8391-910

Solid StateActuator Drive(4 to 20 mAdcNonadjustable

Range)Black

To 120 VacPower Supply

Orange (+)

White

1

2

1

Green / Yellow

1The Blue wire on the CP-8391-910 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.

2The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.

3 Connect the Green/Yellow ground wire from the CP actuator drive to case ground screw.

Page 23: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 23Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13 F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 23

Typical Actuators which require CP-8391-910 purchased separately: MP-465, MP-475, MP483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500.

Figure-21 External Wiring for CP-8391-910 and CP-8391-911, 4 to 20 mAdc Interface with Line Voltage Actuators with Internal Transformer.

Typical Actuators which require CP-8391-716 purchased separately: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454.

Figure-22 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators without Internal Transformer.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

Blue (-)4 to 20 mAdc

Controller Input

Yellow / BlackBlue / BlackRed / Black

Brown

Brown / White

Brown / Black

CP-8391-910(120 Vac)

Solid StateActuator Drive(4 to 20 mAdcNonadjustable

Range)

Black

To ACPower Supply

Orange (+)

TapeRed

Blue

White

1

2

1

The Blue wire on the CP-8391-910 is grounded. To unground the Blue wire, remove the Green jumper wire between terminal x and case ground screw.

The actuator rotates clockwise on an increasing mAdc input signal between Blue (-) and Orange (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and Red/Black leads and reverse Brown/Black and Brown/White leads.

Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.

Connect Green/Yellow ground wire from CP actuator drive to case ground screw.

1

3

Green / Yellow

2

3

4

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

Black (-)To mAdc

Controller Input

Red / YellowWhite / BlueBlack / Blue

Brown

Orange

Yellow

CP-8391-716Solid State

Actuator Drive(mAdc Input;

Span Adj. 4 to 16Factory Set 16,

Start PointAdj. 2 to 16

Factory Set 4)

Blue (120 Vac)

To 120 VacPower Supply

Red (+)

Black / White (240 Vac)Tape

Violet (Com)

1

1 The actuator rotates clockwise on an increasing mAdc input signal between Black (-) and Red (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Blue/Black and White/Blue leads and reverse Orange and Yellow leads.

Page 24: M-34 Series, M-24 Series General ... - Schneider Electric

24 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

24 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical 120 Vac Actuators which require CP-8391-716 purchased separately: MP-465, MP-475. MP-483, MP-485, MP-486, MP-495, MP-2130-500, MP-2150-500.

Typical 240 Vac Actuators which require CP-8391-716 purchased separately: MP5-2151-500, MP5-4651, MP5-4751, MP-4851, MP5-4851.

Figure-23 External Wiring for CP-8391-716, mAdc Interface with Line Voltage Actuators with Internal Transformer.

Typical Actuators: MP-361, MP-371, MP-381, and MP-382.

Figure-24 Internal Wiring for 24 Vac Actuator.

4 5 6 7

3 8

2 L1

1 L2X

Green Wire

CaseGround Screw

Black (-)To mAdc

Controller Input

Red / YellowWhite / BlueBlack / Blue

Brown

Orange

Yellow

CP-8391-716Solid State

Actuator Drive(mAdc Input;

Span Adj. 4 to 16Factory Set 16,

Start PointAdj. 2 to 16

Factory Set 4)

Blue (120 Vac)Black / White (240 Vac)

Tape Unused Wire

To ACPower Supply

Red (+)

TapeRed

Blue

Violet (Com)

1

1 The actuator rotates clockwise on an increasing mAdc input signal between Black (-) and Red (+). To rotate the actuator counterclockwise on an increase in input signal, reverse Black/Blue and White/Blue leads and reverse Orange and Yellow leads.

2 Remove Red and Blue actuator transformer leads from actuator terminals 7 and 8 and tape the leads off. On older actuators, remove back cover of actuator and cut and tape the leads from the transformer to the feedback transformer.

2

H

8

7

6

5

4

3

2

1

X

GFieldCoil

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

Potentiometer

CCW

CW

Limit Switches

AuxiliarySwitch

CaseScrew

GreenWire Green Case

Ground Screw

Green

CaseScrew

2

2Wire

1

1 Used for field grounding.

2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.

Page 25: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 25Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13 F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 25

Typical Actuators: MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454, MP-461-600, MP-471-600, and MP-481-600.

Figure-25 Internal Wiring for Line Voltage Actuators.

Typical Actuators: MP-465, MP-475, MP-483, MP-486, MP-495, MP5-4651, MP5-4751, MP-4851, and MP5-4851.

Figure-26 Internal Wiring for Line Voltage Actuator with Built-in Transformer.

L1

8

7

6

5

4

3

2

1

X

L2

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

Potentiometer

CCW

CW

Limit Switches

AuxiliarySwitch

CaseScrew

GreenWire

Green CaseGround Screw

Field Coil

2 1

1 Used for field grounding.

2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.

L1

8

7

6

5

4

3

2

1

X

L2

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

PotentiometerCCW

CW

Limit Switches

AuxiliarySwitch

CaseScrew

GreenWire

InternalTransformer

0 Vac

Blue12 Vac

24 Vac

Red

FieldCoil

Green CaseGround Screw2 1

1 Used for field grounding.

2 External green jumper from terminal x to case ground is only available on current MP-xxx-xxx-x-2 models.

3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.

3

3

Page 26: M-34 Series, M-24 Series General ... - Schneider Electric

26 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

26 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuator: MP-2113-500.

Figure-27 Internal Wiring for 24 Vac Actuator without Limit Switches (Actuator is Stall Type with Built-in Mechanical Stops).

Typical Actuator: MP-2110-600.

Figure-28 Internal Wiring for Line Voltage Actuators without Limit Switches (Actuator is Stall Type with Built-inMechanical Stops.)

H

8

7

6

5

4

3

2

1

X

G

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

Potentiometer

CCW

CW

AuxiliarySwitch

CaseScrew

GreenWire

FieldCoil

Green CaseGround Screw

Case ScrewGreen

2

1

1 Used for field grounding.

2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.

Wire

2

L1

8

7

6

5

4

3

2

1

X

L2

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

Potentiometer

CCW

CW

AuxiliarySwitch

CaseScrew

GreenWire

Green CaseGround Screw

Field Coil

1

1 Used for field grounding.

2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.

2

Page 27: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 27Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 27

Typical Actuators: MP-2130-500, MP-2150-500, MP5-2151-500.

Figure-29 Internal Wiring for Line Voltage Actuators without Limit Switches and Built-in Transformer(Actuator is Stall Type with Built-in Mechanical Stops).

Typical Actuators: MP-379 and MP-389.

Figure-30 Internal Wiring for 24 Vac Five-Position Actuators.

L1

8

7

6

5

4

3

2

1

X

L2

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

PotentiometerCCW

CW

AuxiliarySwitch

CaseScrew

GreenWire

InternalTransformer

0 Vac

Blue

12 Vac

24 Vac

Red

FieldCoil

Green CaseGround Screw

21

1 Used for field grounding.

2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.

3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.

3

3

H

8

7

6

5

4

3

2

1

X

G

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

Potentiometer

CCW

CW

CaseScrew

GreenWire

FieldCoil

Limit Switches

Green CaseGround Screw

Case Screw

GreenWire

1

1 Used for field grounding.

2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.

2

2

Page 28: M-34 Series, M-24 Series General ... - Schneider Electric

28 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

28 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Typical Actuators: MP-470, MP-480, and MP-4701.

Figure-31 Internal Wiring for LIne Voltage Five-Position Actuators.

Typical Actuators: MP-367, MP-377, and MP-387.

Figure-32 Internal Wiring for 24 Vac Sequencing Actuators.

L1

8

7

6

5

4

3

2

1

X

L2

Motor

CW CCW

CWCCW

ShadingCoils

100 ΩInternal

PotentiometerCCW

CW

CaseScrew

GreenWire

InternalTransformer

0 Vac

Blue

12 Vac

24 Vac

Red

FieldCoil

Limit Switches

Green CaseGround Screw2 1

1 Used for field grounding.

2 External green jumper from terminal X to case ground is only available on current MP-xxx-xxx-x-2 models.

3 On models prior to current MP-xxx-xxx-2-x the Red and Blue transformer leads were wired directly to potentiometer.

3

3

H

8

7

6

5

4

3

2

1

X

G

Motor

CW CCW

CWCCW

ShadingCoils

50 ΩInternal

Potentiometer

CCW

CW

AuxiliarySwitch

CaseScrew

GreenWire

FieldCoil

Limit Switches

Green CaseGround Screw

Case ScrewGreenWire

1

1 Used for field grounding.

2 External green jumpers from terminals X and G to case ground is only available on current MP-xxx-xxx-x-2 models.

2

2

Page 29: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 29Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 29

Figure-33 Internal View of a Typical Actuator.

Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

INSTALLATION

Inspection

Requirements • Wiring diagrams• Tools (not provided):

– Digital volt-ohm meter (DVM)– Appropriate screwdriver(s) for cover, and mounting screws– Appropriate drill and drill bit for mounting screws– Appropriate wrenches for adjustment of damper and valve linkages

• Appropriate accessories• Mounting screws (not provided)• Wire nuts (not provided)• Training: Installer must be a qualified, experienced technician

Warning:• Disconnect the power supply (line power) before installation to prevent electrical shock

and equipment damage.• Make all connections in accordance with the wiring diagram and in accordance with

national and local electrical codes. Use copper conductors only.

Caution:• Do not exceed the ratings of the device(s).• Do not apply power to the unit unless the damper linkage and/or the valve assembly

have been installed.• Avoid locations where excessive moisture, corrosive fumes, or vibration is present.• Do not install insulation on any part of the actuator.

TerminalBlockLimit & Aux.

Switch Block

DriveDisc

CamsMotor &

Pinion Assy.

GearTrain

LimitSwitches

Aux. SwitchAdj. Disk

PotentiometerWiper Arm

Feed-ThroughTerminal Block

PotentiometerResistance Card

SpeedAdjustment(Optional)

Page 30: M-34 Series, M-24 Series General ... - Schneider Electric

30 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

30 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

European CommunityRefer to Table-5 to identify applicable models.

Warning: This is a Class A (European Classification) product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

MOUNTINGPreferred mounting is with the actuator in an upright position in a weather protected area.

Note: The MP-21xx series requires upright mounting. The adjustable speed actuators cannot be mounted upside down, with the output shaft up or with speed adjustment screw pointing up.

It is recommended that valve actuators be mounted above the centerline of the valve body. When selecting a location, allow sufficient room for accessories and for service of the product.

Direction of Actuator RotationAll references to the direction of actuator rotation are based on looking at the front of the actuator, where the splined output shaft extends from the front case of the actuator.

Linkage Assembly Damper

Caution: The damper must not stop the actuator before it has reached its electrical limit of travel or permanent damage can occur to the actuator.

1. During installation of the linkage assembly, the actuator should be powered and be able to be controlled manually.

2. Mount the actuator in an appropriate position near the damper. Refer to Figure-35.Actuators must be linked to the damper so that it can complete its full stroke. Damperrod that is too long is not rigid enough for good control and damper rod that is too shortmakes it difficult to adjust the linkage.

3. Attach a balljoint to the actuator and damper crank arms at the correct position in thecrank arm slot depending on the application. Refer to Figure-34, Table-8, and Table-9for application settings. The use of 180° rotation damper actuators provides the bestclose-off at the end of stroke and the best controllability (turn down ratio).

4. Typically the damper should be linked for an angular rotation of less than 90° thatprovides the required flow (typically 60°). This provides the optimum close-off andcontrollability.

Table-8 Balljoint Position on Actuator and Damper Crank Arms with 180 Degree Rotation Actuators.

Desired Damper Rotation Balljoint Position on Actuator Crank Arm

Balljoint Position on Damper Crank Arm

90° Prick Point (2-1/4") End of Slot (3-1/8")

80° 2" End of Slot (3-1/8")

70° 1-3/4" 3"

60° 1-1/2" 3"

Page 31: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 31Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 31

Table-9 Balljoint Positioning Actuator and Damper Crank Arms with 90 Degree Rotation Actuators.

Figure-34 Proper Balljoint Position on Crank Arm.

5. With the actuator powered, manually position the actuator to the position that is requiredfor the closed position of the damper. Rotate the damper to its midstroke position.Referring to Figure-36, install the crank arms on the damper shaft and the actuator sothat crank arms are parallel. The crank arm on damper shaft should be secured to theshaft and the crank arm on the actuator should be free to rotate.

6. Attach the push rod to the ball joint connectors on both crank arms and tighten the balljoint screws only thumb tight.

7. Rotate by hand the crank arm on the actuator to drive the linkage and the damper shaftthrough its full stroke to ensure proper damper action.

8. Return the damper to its closed position and tighten to secure the actuator crank arm.

9. While pushing the damper closed, tighten the ball joint screws to secure the damperrod.

10. Run the actuator back and forth through its full stroke and check for proper damper andlinkage operation. Adjust the linkage if required.

Caution: If the crank arm does not provide proper travel, reset the linkage. Never attempt to turn the actuator shaft with a wrench or a crank; this may damage the actuator.

Figure-35 Typical Actuator Mounting Positions.

Desired Damper Rotation Balljoint Position Actuator Crank Arm

Balljoint Position Damper Crank Arm

90° End of Slot (3-1/8") End of Slot (3-1/8")

80° 2-3/4" 3"

70° 2-1/2" 3"

60° Prick Point (2-1/4") End of Slot (3-1/8")

1 2 3

Prick Point

Slot Provides AdjustmentFrom 7/8" to 3-1/8"

Page 32: M-34 Series, M-24 Series General ... - Schneider Electric

32 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

32 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Figure-36 Typical Damper Linking with 180 Degree or 90 Degree Rotation Actuator.

ValveFor the correct installation of valve linkages, refer to the ACCESSORIES section for form numbers of the appropriate linkage instruction sheets.

90° RotationDamper

Install Ball Jointat Prick Pointon Crank Arm

180° RotationActuator

Typical of Actuator and Damper Rotating in Same Direction

Install Ball Jointat End of Crank Arm

Install Ball Jointat Prick Pointon Crank Arm

180° RotationActuator

90° RotationDamper

= Ball Joint

= Crank Arm Open Position

= Crank Arm Mid-Position

= Crank Arm Closed Position

in Different Directions

Install Ball Jointat End of Crank Arm

Typical of Actuator and Damper Rotating

90° RotationDamper

90° RotationActuator

Typical of Actuator and Damper Rotating in Same Direction

Install Ball Jointat End of Crank Arm

90° RotationActuator

90° RotationDamper

= Ball Joint

= Crank Arm Open Position

= Crank Arm Mid-Position

= Crank Arm Closed Position

Typical of Actuator and Damper Rotatingin Different Directions

Install Ball Jointat End of Crank Arm

180 Degree Rotation Actuator 90 Degree Rotation Actuator

Page 33: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 33Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 33

WIRINGThe wiring connectors are made to coded screw terminals. Actuators with “-600” suffixes also have 6" (152 mm) color coded leads for control circuit.

Hazardous Location Models

Hazardous Location Models Make all electrical connections to the assembly in accordance with the job wiring diagram, the National Electric Code Article 500, and in compliance with the local electrical codes.

Two 3/4" pipe tapped openings are provided in the housing for rigid conduit connections. It is recommended to insert a chase nipple from inside of the housing to prevent threads from cutting or damaging wiring.

When wiring, take care to lay all leads in the wiring channel located just under the housing cover to protect the leads from any sharp edges which may be in the vicinity.

The housing and the edge of the cover are stamped with the letter "O." When replacing the cover, the letters must be aligned with each other.

Warning:• The cover-to-housing orientation must be maintained in order to preserve the integrity

of the seal. Failure to observe this warning can result in injury or death.• Do not scrape, scratch, or use abrasives on the machined surfaces.• Ensure the surfaces are clean.• Use only the approved compounds listed in the note below.• If an additional device, such as a drive, is to be installed it must be mounted in the safe

area or enclosed in a separate hazardous location housing.

1. Remove twelve cover screws and cover. Place cover, machined surface up, in aprotected location to avoid damage to machined surfaces.

2. Make all wiring connections to actuator taking care to lay all leads in the wiring channelprovided.

3. Before enclosing the actuator, wipe machined surfaces of housing clean with a lint freecloth and apply one of the UL approved compounds. See Note below.

4. Secure cover tight against the enclosure in the same position before removal with thetwelve screws provided.

5. Refer to Figure-3 thorough Figure-32 for correct model and application wiring.

Note: Underwriters Laboratories has sanctioned the use of the following compounds on hazardous location ground joints: Crouse-Hinds type OSL lubricant, Crouse-Hinds type STL lubricant, or "No-OXID" oil, grade "D."

Two 1/2" conduit knockouts are provided on the actuator case.

Page 34: M-34 Series, M-24 Series General ... - Schneider Electric

34 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

34 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Power Wiring All actuators include a barrier that separates the power wiring compartment from the low voltage wiring compartment. Refer to Table-10 for allowable circuit class for the two wiring compartments.

Table-10 Actuator Circuit Class.

Refer to Table-11 for selection of proper gage wire for the length of wire run (one run has two wires).

Table-11 Power Wire Selection.

When multiple 24 Vac actuators are powered from the same transformer, the actuators must be in phase. Connect the same transformer lead to the “G” terminal on all actuators and same transformer lead to the “H” terminal on all actuators.

Typical Part Numbers Actuator Description

Power Wiring Compartment Low Voltage Wiring Compartment

Terminals (Function) Circuit Class for Power Wiring Compartment Terminals (Function)

Circuit Class for Low

Voltage Wiring Compartment

MP-361, MP-371, MP-381, MP-382,

MP-2113-500

Low Voltage Proportional

H&G (24 Vac Power) 1, 5, and 6

(Auxiliary Switch)

1.May be Class 2 circuit ifauxiliary switch is wired to24 Vac or is not used.

2.Must be Class 1 circuit ifauxiliary switch is wired to line voltage.

X, 2, and 3 (Control Circuit)

4, 7, and 8 (Potentiometer)

May be Class 2 Circuit.

MP-421, MP-422, MP-423, MP-424, MP-451, MP-452, MP-453, MP-454,

MP-461-600, MP-465, MP-471-600, MP-475, MP-481-600, MP-483,

MP-485, MP-486, MP-495, MP-2150-500, MP5-4651, MP5-4751, MP-4851, MP5-4851

Line Voltage Proportional

L1 and L2 (Line Voltage Power)

1, 5, and 6 (Auxiliary Switch)

Must be Class 1 circuit.

X, 2, and 3 (Control Circuit)

4, 7, and 8 (Potentiometer)

May be Class 2 Circuit.

MP-367, MP-377, MP-387

Low Voltage Sequencing

H&G (24 Vac Power) 1, 5, and 6

(Control Switches)May be Class 2 Circuit.

X, 2, and 3 (Control Circuit)

4, 7, and 8 (Potentiometer)

May be Class 2 Circuit.

MP-379, MP-389 Low Voltage Five-Position

H&G (24 Vac Power) 6, 7, and 8

(Potentiometer)May be Class 2 Circuit. X, 1, 2, 3, 4, 5

(Control Circuit)May be Class 2

Circuit.

MP-470, MP-480, MP-4701

Line Voltage Five-Position

H&G (24 Vac Power) 6, 7, and 8

(Potentiometer)Must be Class 1 Circuit. X, 1, 2, 3, 4, 5

(Control Circuit)May be Class 2

Circuit.

Actuator Series Voltage Wire Size(AWG)

MaximumRun ft. (m)

MP-36x, MP-37x 24 Vac141210

115 (35)180 (55)285 (87)

MP-38x 24 Vac141210

130 (40)205 (62)325 (99)

MP-42xMP-445-304

MP-45x120 Vac

141210

810 (247)1275 (388)2040 (622)

MP-46xMP-47xMP-48x

120 Vac141210

1050 (320)1660 (506)2650 (808)

MP-4xx1 240 Vac 14 3340 (1018)

Page 35: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 35Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 35

Control Wiring Refer to Figure-3 through Figure-23 for typical wiring of the actuators. Refer to the actuator selection tables beginning on page 3, for an index of External Wiring Figures versus actuator models and control signals. The requirements for the field control wiring are shown below.

SPST Control SignalRefer to Figure-3 and Figure-4. Since the SPST switch is controlling the power to the actuator, the control wiring is limited to the power wiring shown above.

SPDT Control SignalRefer to Figure-5 and Figure-6. Use 18 gage wire for runs up to 1,000 ft. (305 m) between the actuator and the SPDT switch. Use larger gage wires on longer runs.

Barber-Colman Microtherm ControlRefer to External Wiring Figure-7 through Figure-13. Use 18 gage wire for runs up to 1,000 ft. (305 m) between the actuator and the Barber-Colman Microtherm controller. Use larger gage wires on longer runs.

135 to 1000 Ω Slidewire ControlRefer to External Wiring Figure-14 and Figure-15. Use 18 gage three-conductor twisted leads (part number W-103 or equal) for runs up to 500 ft. (152 m) between the actuator and the slidewire controller. Use larger gage wires for longer runs.

Voltage Vdc ControlRefer to External Wiring Figure-16 through Figure-18. Use 18 gage three-conductor twisted leads (part number W-103 or equal) for runs up to 1,000 ft. (305 m) between the actuator and the Vdc controller. Use larger gage wires for longer runs.

Caution: Use 18 gage three-conductor shielded cable (twisted) when it is necessary to install the control leads in the same conduit with power wiring, or when high RFI/EMI generating devices are near. Do not connect the shield to earth ground or any leads or terminals.

Current mAdc ControlRefer to External Wiring Figure-19 through Figure-23. Use 18 gage two-conductor twisted leads (part number W-102 or equal) for runs up to 500 ft. (152 m) between the actuator and the slidewire controller. Use larger gage wires for longer runs.

Direct Digital Control (DDC)DDC controllers may be used to control these actuators according to one of the methods described below.

SPST Control

Refer to External Wiring Figure-5 and Figure-6. Requires two digital output points programmed as a drive open, drive closed configuration. The digital output must be rated for switching 0.9 amp at 24 Vac.

Voltage Vdc Control

Refer to External Wiring Figure-16, Figure-17, and Figure-18. Requires an analog output from the DDC controller, programmed to provide the desired voltage range. Also requires a CP-8301-120 electronic actuator drive between the DDC controller and the actuator.

Current mAdc Control

Refer to External Wiring Figure-19, Figure-20, and Figure-21. Requires an analog output from the DDC controller, programmed to provide the desired current range (usually 4 to 20 mA). Also requires a CP-8391-913 electronic actuator drive between the DDC controller and the actuator.

Page 36: M-34 Series, M-24 Series General ... - Schneider Electric

36 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

36 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

ADJUSTMENTS

Limit Switch Adjustment

The counterclockwise limit switch on certain actuators provides adjustable travel of 45° to 320° rotation. The actuator selection tables beginning on page 3 identify the models that have adjustable travel limits. To adjust travel refer to Figure-37 and Figure-38 while following the steps shown below.

Note: The feedback potentiometers in the actuator have a fixed rotation (typically either 90° or 180°). Therefore, adjusting the travel of the actuator could affect the feedback to the controller. The potentiometer has a slip clutch and will not be damaged by adjusting the actuator travel. If the actuator travels beyond the limit of the potentiometer, the wiper arm on the potentiometer will cease to rotate. The wiper arm will instantly start moving in the opposite direction as soon as the actuator reverses direction.

1. Remove the top cover from the actuator and disconnect the field wiring from terminals,X, 2, and 3 of the actuator.

2. The actuator should be powered and driven to its CW limit by shorting terminal X toterminal 2. Refer to Figure-37.

Figure-37 Actuator Output Shaft Position (Front View).

3. The access hole for the travel adjustment is located in the top plate of the actuatordirectly ahead of terminal block in the front of the actuator (where output shaft extendsfrom actuator). Refer to Figure-38.

Short Tooth onShaft at 9:00

Short Tooth onShaft at 3:00

Full CW Position Full CCW Position*

180° Rotation Actuator

90° Rotation Actuator

Full CW Position Full CCW Position*

Short Tooth onShaft at 6:00

Short Tooth onShaft at 9:00

*On Certain Models the CCW TravelLimit is Adjustable from 45 to 320°

Page 37: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 37Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 37

4. Insert a screwdriver through the access hole and engage the notched cam nearest thefront of the actuator.

Figure-38 Limit Switch Adjustment.

5. Turning the cam CW (as seen from the front of the actuator) increases the length of theactuator rotation. Each click of the cam represents about a 3° change in actuatorrotation.

6. After adjusting the cam, check the rotation of the actuator by shorting actuator terminalx to terminal 3 to drive the actuator to its new CCW limit setting.

7. If the travel is not what is desired, repeat steps 2 through 6 until desired results areobtained.

Auxiliary Switch Adjustment

Refer to the actuator selection tables beginning on page 3 for the actuators that include an auxiliary switch. The adjustable SPDT auxiliary switch is actuated by the cam nearest the back of the actuator. It is factory set to switch near the CW end of actuator rotation. Terminal 1, the common of the switch, is made to terminal 5, from the CCW end of rotation until the switch point, then terminal 1 is made to terminal 6 for rest of the stroke.

Note: The auxiliary switch is made from terminal 1 to terminal 5 when the switch follower is on the low part of the cam, and from terminal 1 to terminal 6 when the switch follower is on the lobe of the cam.

To adjust the switch point of the auxiliary switch, follow the steps shown below.

Note: If the actuator travel has been increased beyond 180°, the auxiliary switch may, depending on its switch point, operate twice in the actuator stroke.

1. Remove the top cover of the actuator.

2. The actuator should be powered and positioned to desired point in actuator stroke forthe auxiliary switch to operate.

3. The access hole for the auxiliary switch adjustment is located in top plate of the actuator directly ahead of the terminal block in the back of the actuator. Refer to Figure-39.Actuators manufactured after 1976 have plastic funnel shield inserted in the accesshole.

Caution: Disconnect the power to the actuator at the power terminals (H and G or L1 and L2) plus the auxiliary switch terminals (1, 5, and 6). More than one disconnect may be required.

AccessHole

Page 38: M-34 Series, M-24 Series General ... - Schneider Electric

38 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

38 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

4. Insert a screwdriver through the plastic funnel shield, if present, and through the access hole, engaging the screwdriver with the gear-like plastic disc.

Figure-39 Auxiliary Switch Adjustment (Rear View with Top and Back Coversof Actuator Removed).

5. Turning the disc CW (as viewed from the front of the actuator) causes the switch tooperate nearer to the CCW end of actuator rotation. Each click of the cam representsabout a 3° change in the switch point.

6. Adjust the disc so that the switch just operates.

Speed Adjustment The actuator selection tables beginning on page 3 list the actuators that are adjustable speed. The timing of the adjustable speed actuators is varied by a slotted adjustment screw on the lower left side of the front housing. Refer to Figure-40. Turning the screw CW decreases the speed. Total timing can be increased to about ten times the normal. Take care not to turn the adjustment screw too far CW as this will stall, but not damage, the actuator. If stalling occurs, turn the screw CCW until the actuator resumes operation. The total adjustment is normally 3-1/2 turns on the adjustment screw.

Figure-40 Speed Adjustment Location.

TerminalBlockLimit & Aux.

Switch Block

DriveDisc

CamsMotor &

Pinion Assy.

GearTrain

LimitSwitches

Aux. SwitchAdj. Disk

PotentiometerWiper Arm

Feed-ThroughTerminal Block

PotentiometerResistance Card

SpeedAdjustment(Optional)

Page 39: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 39Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 39

CHECKOUTAfter the entire system has been installed and the actuator has been powered up, the following checks can be made for proper system operation.

GO, NO GO Test Slidewire Controller with 24 Vac ActuatorsRefer to Figure-14.

1. Disconnect field wiring from Brown lead of AE-504 and terminals 7 and 8 of the actuator.

2. Apply 24 Vac power to terminals H and G of the actuator.

3. Short the Brown lead of AE-504 to terminal 7 of actuator and the actuator should rotateCW to its limit.

4. Short the Brown lead of AE-504 to terminal 8 of actuator and the actuator should rotateCCW to its limit.

5. If the unit passes steps 3 and 4, the actuator and the AE-504 are good. If the unit doesnot pass steps 4 and 5, proceed to step 6.

6. Unhook the AE-504 leads from actuator terminals X, 2, and 3.

7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

If the unit passes steps 7 and 8, the actuator is good and AE-504 is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the AE-504 may be good.

Slidewire Controller with Line Voltage Actuator Refer to Figure-15.

1. Disconnect field wiring from Brown lead of AE-504 and terminals 7 and 8 of the actuator.

2. Apply proper AC power to terminals L1 and L2 of the actuator.

3. Short the Brown lead of AE-504 to terminal 7 of actuator and the actuator should rotateCW to its limit.

4. Short the Brown lead of AE-504 to terminal 8 of actuator and the actuator should rotateCCW to its limit.

5. If the unit passes steps 3 and 4, the actuator and the AE-504 are good. If the unit doesnot pass steps 4 and 5, proceed to step 6.

6. Unhook the AE-504 leads from actuator terminals X, 2, and 3.

7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

If the unit passes steps 7 and 8, the actuator is good and AE-504 is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the AE-504 may be good.

CP-8301-120, Vdc Interface with Line Voltage Actuators without Internal Transformer Refer to Figure-16.

1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.

2. Apply 120 Vac power to terminals L1 and L2 of the actuator.

3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW toits limit, unless rewired to rotate CCW on an increase in input signal.

4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW toits limit, unless rewired to rotate CCW on an increase in input signal.

5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unitdoes not pass steps 3 and 4, proceed to step 6.

6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.

7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

Page 40: M-34 Series, M-24 Series General ... - Schneider Electric

40 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

40 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.

CP-8301-024, Vdc Interface with 24 Vac Actuators Refer to Figure-17.

1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.

2. Apply 24 Vac power to terminals H and G of the actuator.

3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW toits limit, unless rewired to rotate CCW on an increase in input signal.

4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW toits limit, unless rewired to rotate CCW on an increase in input signal.

5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unitdoes not pass steps 3 and 4, proceed to step 6.

6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.

7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.

CP-8301-120 and CP-8301-240, Vdc Interface with Line Voltage Actuators with Internal Transformer Refer to Figure-18.

1. Disconnect field wiring from Red, Yellow, and Blue leads of CP-8301-xxx.

2. Apply AC power to terminals L1 and L2 of the actuator.

3. Short the Yellow and Red leads of CP-8301-xxx and the actuator should rotate CW toits limit, unless rewired to rotate CCW on an increase in input signal.

4. Short the Yellow and Blue leads of CP-8301-xxx and the actuator should rotate CCW toits limit, unless rewired to rotate CCW on an increase in input signal.

5. If the unit passes steps 3 and 4, the actuator and the CP-8301-xxx are good. If the unitdoes not pass steps 3 and 4, proceed to step 6.

6. Unhook the CP-8301-xxx leads from actuator terminals X, 2, and 3.

7. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

8. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

If the unit passes steps 7 and 8, the actuator is good and CP-8301-xxx is defective. If the unit does not pass steps 7 and 8, the actuator is defective and the CP-8301-xxx may be good.

CP-8391-xxx Series mAdc Interface Refer to Figure-19 through Figure-23.

1. Unhook the CP-8391-xxx leads from actuator terminals X, 2, and 3.

2. Refer to specific actuator for power hook-ups.

3. Short actuator terminal X to 2 and the actuator should rotate CW to its limit.

4. Short actuator terminal X to 3 and the actuator should rotate CCW to its limit.

5. If the unit passes steps 3 and 4, the actuator is good.

Page 41: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 41Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 41

Positioning the Actuator with the Controller

If the sensed media is within the controller’s setpoint range, the actuator can be positioned by adjusting the controller setpoint up and down. Check for proper operation of the actuator (valve or damper) while the actuator is being stroked.

Theory of OperationActuator variations are shown in Figure-24 through Figure-32. Refer to the actuator selection tables beginning on page 3 to determine which Internal Wiring Figure applies to a certain actuator.

The actuators are powered by shaded pole motors that are of the induction type, using what is commonly know as a squirrel cage rotor. These motors, like all single phase induction motors, must be provided with some means of starting. This is accomplished by the shading coils in the poles of the motor and hence the name “Shaded Pole.” However, unlike most single phase induction motors, the shading coils are also essential for running.

The field coil produces a magnetic field in the iron core (stator) and in the rotor. When actuator terminal x is shorted to a terminal attached to CW shading coils, it causes a lag in part of the field which provides the equivalent of a rotating field. This rotating field induces a voltage and current in the rotor bars, and the attraction between the rotating field and these current carrying bars pulls the rotor around with the field in a CW direction. When actuator terminal x is shorted to a terminal attached to CCW shading coils, it operates the same except it drives the actuator CCW. A voltage of 24 to 30 Vac with current of 9 amps is induced in the shading coils in much the same manner as the secondary of a transformer.

Page 42: M-34 Series, M-24 Series General ... - Schneider Electric

42 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

42 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

REPLACEMENT PARTSTable-12 Potentiometer Kit.

Table-13 Additional Potentiometer Kits.

MAINTENANCERegular maintenance of the total system is recommended to assure sustained, optimum performance.

The actuators require a minimum of maintenance since the motor and gear train are submerged in oil for continuous lubrication and cooling.

TROUBLESHOOTINGRefer to Section “GO, NO GO Test” on page 39.

REPAIRNone. Replace an inoperable actuator with a functional unit.

Actuator Potentiometer Kit

Part No. DescriptionMP-xx0x-0-0-1MP-xx0x-0-2-1 ADDA-902-2 100 Ω, 180°

MP-xx1x-0-0-1 ADDA-902-2 100 Ω, 180°

MP-xx2x-0-0-1 ADDA-902-2 100 Ω, 180°

MP-xx3x-0-0-1MP-xx3x-0-2-1 ADDA-902-5 100 Ω, 90°

MP-xx4x-0-0-1MP-xx4x-0-2-1 ADDA-902-5 100 Ω, 90°

MP-xx5x-0-0-1MP-xx5x-0-2-1 ADDA-902-2 100 Ω, 180°

MP-xx6x-0-0-1MP-xx6x-0-2-1 ADDA-902-2 100 Ω, 180°

MP-xx7x-0-0-1 ADDA-902-4 50 Ω, 180°

MP-xx8x-0-0-1MP-xx8x-0-2-1 ADDA-902-2 100 Ω, 180°

MP-xx9x-0-0-1 ADDA-902-2 100 Ω, 180°

Potentiometer KitsPart No. Description

ADDA-902-6 500 Ω, 90°

ADDA-902-8 1000 Ω, 90°

ADDA-902-9 500 Ω, 180°

ADDA-902-10 1000 Ω, 180°

Page 43: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 43Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 43

DIMENSIONAL DATA

Figure-41 Dimensional Drawing for MP-3xx, MP-4xx, MP-2xxx, and MP-4xxx.

2-3/8"(60 mm)

4-3/4"(121 mm)

5-3/8"(136 mm)

17/64" (6.7 mm)Dia. Holes

2"(51 mm)

1-5/8"(41 mm)

2-1/4"(57 mm)

1-7/16"(36 mm)

1-1/2"(38 mm)

15/16"(24 mm)

4"(102 mm)

1-13/16"(46 mm)

6-5/16"(160 mm)8-1/8"

(206 mm)

3-7/8"(97 mm)

7"(178 mm)

1/2" Conduit Knockouts(Two Each Side)

Spring ReturnOnly

4-3/16"(106 mm)

Page 44: M-34 Series, M-24 Series General ... - Schneider Electric

44 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

44 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

Figure-42 Dimensional Drawing for MP-3xx, MP-4xx, MP-2xxx, and MP-4xxx with -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed) or with AE-504 Installed.

2-3/8"(60 mm)

4-3/4"(121 mm)

3-1/8"(79 mm)

17/64" (6.7 mm)Dia. Holes

2"(51 mm)

1-5/8"(41 mm)

2-1/4"(57 mm)

1-7/16"(36 mm)

1-1/2"(38 mm)

15/16"(24 mm)

4"(102 mm)

1-13/16"(46 mm)

6-5/16"(160 mm)

8-1/8"(206 mm)

3-7/8"(97 mm)

7"(178 mm)

Spring ReturnOnly

4-3/16"(106 mm)

4-1/8"(105 mm)

5-3/8"(136 mm)

Two 1/2" ConduitKnockouts

6-13/16"(173 mm)

2"(51 mm)

1/4"(6 mm)

4-13/16"(122 mm)

2-9/16"(65 mm)

3-7/8"(96 mm)

7"(178 mm)

3-1/8"(79 mm)

(A)

Model Dimension A (Width)MP-xxxx With AE-504 Installed

6-11/16 in.(170 mm)

MP-xxxx-6xx Equipped with CP-8301-xxx or CP-8391-91x

7-1/2 in.(191 mm)

CP-8301-xxxor

CP-8391-91x

Page 45: M-34 Series, M-24 Series General ... - Schneider Electric

schneider-electric.com | 45Installation Instructions

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. December, 2017 tcDocument Number: F-15479-13

F-15479-12 © Copyright 2012 Schneider Electric All Rights Reserved. 45

Figure-43 Dimensional Drawing for Hazardous Location Damper Actuators.

Figure-44 Dimensional Drawing for Hazardous Location Valve Actuators.

4-1/2(114)

15/16(24)

4-7/32(107)

8-1/4(209)

1/2 (13)Dia. Shaft

Dimensions are in inches (mm).

4-13/32(112)

9(228)

1/4 (6)

2-15/16(51)

2-1/8(54)

3/4 (19) Pipe TapOn Each Side

9(229)

9-9/16(243)

10-5/8(270)

1-1/2(40)

On reversible spring returnactuators only.

7(178)

4-1/4(108)

8-1/4(209)

Dimensions are in inches (mm).

4-13/32(112)

9(228)

1/4 (6)4-1/2(114)

2-15/16(51)

2-1/8(54)

3/4 (19) Pipe TapOn Each Side

9(229)

10-13/16(275)

1/8(3)

1-1/2(40)

On reversible spring returnactuators only.

Page 46: M-34 Series, M-24 Series General ... - Schneider Electric

46 | schneider-electric.com Installation Instructions

December, 2017 tc © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Document Number: F-15479-13

Printed in U.S.A. 6/12 © Copyright 2012 Schneider Electric All Rights Reserved. F-15479-12

ApplicationThe MP series actuators are used for two-position, floating, and proportional control of dampers, valves, and program switches in heating, ventilating, airconditioning, and similar applications.

Hazardous location models offer a sturdy castaluminum case with bolted cover. They have two 3/4"pipe tapped openings for joints with rigid metal conduit. All wiring is brought out to separate terminals for easeof installation. These factory enclosure and actuatorassemblies are Underwriters Laboratories Listed.

Features• Proportional actuators with built-in feedback

potentiometers• Spring return and non-spring return models

available• 24 Vac, 120 Vac, and 240 Vac models are available• Actuator has a rugged die cast aluminum housing

with two 1/2” conduit openings.• Hazardous location actuator housing has two 3/4"

pipe taped openings for rigid metal conduitconnection

• Oil-immersed motor and gear train

Applicable Literature• Valve Selection Guide, F-26094• AV-29x Valve Linkage for Hazardous Location Gear

Train Actuators General Instructions, F-27441.• Apparatus for Hazardous Locations EN-56-2,

F-18451.• AV-390 Series, Valve Linkage for Gear Train

Actuators, General Instructions, F-24376• Material Safety Data Sheet MSDS-4• AM-363 Gasket Cover Kit General Instructions,

F-25598• CP-8301 Solid State Actuator Drive General

Instructions, F-14940• CP-8391-716 Electronic Actuator Drive General

Instructions, F-21220• CP-8391-910 Series 4 to 20 mA Electronic Actuator

Drive General Instructions, F-22453• AE-504 Solid State Paralleling Relay General

Instructions, F-16524

Typical Spring Return

Typical Non-Spring Return

* Refer to Table-5 to identify specific models that are incompliance with CE requirements.

Typical MP6(Hazardous Locations)

Typical -6xx Suffix(CP-8301-xxx or CP-8391-91x Installed)

MP-3xx Series, MP-4xx Series, MP-2xxx Series, and

MP-4xxx SeriesReversible and Proportional Electric Actuators

General Instructions