WET STAND PIPE DRY STAND PIPE COMBINATION STAND PIPE SPRINKLER FIRE WATER SUPPLY REFRIGERANT LIQUID REFRIGERANT DISCHARGE REFRIGERANT SUCTION HUMIDIFICATION GLYCOL HEATING RETURN GLYCOL HEATING SUPPLY HOT WATER RETURN ( HEATING) HOT WATER SUPPLY (HEATING) FUEL OIL VENT FUEL OIL RETURN FUEL OIL SUPPLY FUEL OIL GAUGE FUEL OIL DISCHARGE NATURAL GAS CONDENSATE DRAIN DRAIN VENT (PLUMBING) STORM DRAINAGE SANITARY DRAINAGE HOT WATER RETURN (DOMESTIC) HOT WATER (DOMESTIC) COLD WATER (DOMESTIC) LEGEND EXISTING ITEM TO DEMOLISH EXISTING ITEM TO REMAIN ELBOW, TURNED UP ELBOW, TURNED DOWN REDUCER, CONCENTRIC ELBOW, 90 DEGREES ELBOW, 45 DEGREES CAP THERMOMETER GAGE, PRESSURE WITH COCK REDUCER, ECCENTRIC MANUAL AIR VENT AUTOMATIC AIR VENT AIR ELIMINATOR JOINT, EXPANSION ANCHOR GUIDE, ALIGNMENT SLEEVE, PIPE PUMP RISE, PIPE DROP, PIPE COCK FLANGE, BLIND VALVE, CONTROL 3 WAY ELECTRIC VALVE, CONTROL 3 WAY PNEUMATIC VALVE, CONTROL 2 WAY PNEUMATIC THERMOMETER WELL STRAINER, BLOW OFF STRAINER DIFFUSER, PUMP SUCTION VALVE, SOLENOID / THERMOSTATIC VALVE, TRIPLE DUTY CONNECTION, FLEXIBLE ARROW, FLOW DIRECTION VALVE, FLOW CONTROL VALVE, FLOAT VALVE, LOCK SHIELD VALVE, PLUG VALVE, NEEDLE VALVE, GLOBE VALVE, BUTTERFLY VALVE, ANGLE VALVE, BALL VALVE, GATE UNION TEE TEE, OUTLET UP TEE, OUTLET DOWN VALVE, CHECK TRAP, STEAM FLOAT & THERMOSTATIC TRAP, STEAM FLOAT TRAP, STEAM VALVE, SAFETY/RELIEF VALVE, SAFETY VALVE, QUICK OPENING VALVE, PRESSURE REDUCING OUTLET, GAS, OXY, VAC, N20 CLEANOUT, WALL FIRE ALARM CONTROL PANEL CONNECTION, FIRE DEPT SIAMESE BELL, FIRE ALARM SPRINKLER, AUTOMATIC SPRINKLER HEAD, SIDEWALL SPRINKLER HEAD, PENDANT SPRINKLER HEAD, UPRIGHT VALVE, OUTSIDE SCREW & YOKE VALVE, DRY PIPE VALVE, ALARM CHECK VALVE, POST INDICATOR VALVE, TAMPER DETECTION SWITCH DRAIN, FLOOR CLEANOUT, FLOOR HVAC CONTROL PANEL HYDRANT, WALL HYDRANT, FIRE DETECTOR, GAS DETECTOR, HEAT DETECTOR, SMOKE STANDPIPE, DRY STATION STANDPIPE, WET STATION GONG, WATER MOTOR ALARM HORN / SPEAKER EXTINGUISHER, DRY CHEM MANUAL ACTIVATION EXTINGUISHER, DRY CHEM AUTO ACTIVATION EXTINGUISHER, DRY CHEMICAL DRAIN, ROOF ABBREVIATIONS A AMP, AMPERES, AIR (COMPRESSED) DIFF DIFFERENCE, DELTA INCL INCLUDING, INCLUSIVE RPM REVOLUTIONS PER MINUTE ABS ABSOLUTE DIM DIMENSION INSUL INSULATION, INSULATED RS ROOF SUMP, REFRIGERANT SUCTION AC ALT. CURRENT, AIR COMPRESSOR DISC DISCONNECT INT INTERIOR, INTERNAL S SOUTH, SOLENOID ACU AIR CONDITIONING UNIT DISCH DISCHARGE INV INVERT SA SUPPLY AIR, SOUND ATTENUATOR AD ACCESS DOOR DIV DIVISION IPS IRON PIPE SIZE SAN SANITARY DRAIN/SEWER ADDL ADDITIONAL DN DOWN ISD IONIZATION SMOKE DETECTOR SCFM (STANDARD) CUBIC FEET PER MINUTE ADDM ADDENDUM DOM DOMESTIC JC JANITOR’S CLOSET SCHED SCHEDULE ADDN ADDITION DS DOWNSPOUT, DISCONNECT KW KILOWATTS SCW SOFT COLD WATER ADJ ADJUSTABLE DT DRAIN TILE L LENGTH, LONG, LOUVER SD SMOKE DAMPER A-E ARCHITECT-ENGINEER DWC DRINKING WATER COOLER LAB LABORATORY SDA SUPPLY DIFFUSER TYPE A AF AIR FOIL DWG DRAWING LAT LEAVING AIR TEMPERATURE SE STATIC FAN EFFICIENCY, SOUTHEAST AFF ABOVE FINISHED FLOOR DWR DRINKING WATER RETURN LAV LAVATORY SECT SECTION AFS AIR FLOW SWITCH DWS DRINKING WATER SUPPLY LB/LBS POUND POUNDS SENS SENSIBLE AHU AIR HANDLING UNIT DX DIRECT EXPANSION LP LOW PRESSURE, LIGHTING PANEL SF SERVICE FACTOR ALT ALTERNATE, ALTITUDE EA EXHAUST AIR, EACH LR LONG RADIUS SGA SUPPLY GRILLE TYPE A AMB AMBIENT EAT ENTERING AIR TEMPERATURE LWT LEAVING WATER TEMPERATURE SH SHOWER, SENSIBLE HEAT AMS AIR MEASURING STATION ECC ECCENTRIC M METER, MOTOR SHT SHEET ANSI AMERICAN NAT. STANDARDS INSTITUTE ECON ECONOMIZER MAN MANUAL SIM SIMILAR APD AIR PRESSURE DROP EEW EMERGENCY EYE WASH MATL MATERIAL SM SHEET METAL APPROX APPROXIMATE EF EXHAUST FAN MAX MAXIMUM SP STATIC PRESSURE ARCH ARCHITECT, ARCHITECTURAL EFF EFFICIENCY MBH 1000 BRITISH THERMAL UNITS / HOUR SPEC SPECIFICATION AS AUTOMATIC SPRINKLER EGA EHAUST GRILLE TYPE A MC MOTOR CONTROL SPR SPRINKLER ASME AM. SOCIETY OF MECHANICAL ENGINEERS EL ELEVATION MCC MOTOR CONTROL CENTER SQ SQUARE ASR AUTOMATIC SPRINKLER RISER ELEC ELECTRIC, ELECTRONIC MECH MECHANICAL SR SUPPLY RISER ASTM AM. SOCIETY FOR TESTING MATERIALS ELEV ELEVATOR MEZZ MEZZANINE SSTL STAINLESS STEEL ATM ATMOSPHERE ELL ELBOW MFG MANUFACTURING ST STORM AUTO AUTOMATIC EMS ENERGY MANAGEMENT SYSTEM MFR MANUFACTURER STA STATION AUX AUXILIARY ENCL ENCLOSURE, ENCLOSED MH MANHOLE STD STANDARD AV AIR VENT (AUTOMATIC) ENT ENTERING MIN MINIMUM, MINUTE STL STEEL AW ACID WASTE EQ EQUAL MISC MISCELLANEOUS STM STEAM B BOILER, BRINE SUPPLY EQUIP EQUIPMENT MM MILLIMETER STOR STORAGE BDD BACKDRAFT DAMPER EVAP EVAPORATOR MU MAKE UP STR STRAINER BET BETWEEN EWT ENTERING WATER TEMPERATURE MV AIR VENT (MANUAL) STRUCT STRUCTURAL BF BARRIER FREE EX EXISTING N NORTH SUCT SUCTION BFP BACK FLOW PREVENTER EXH EXHAUST NA NOT APPLICABLE SW SWITCH BHP BRAKE HORSEPOWER EXP EXPANSION NATL NATIONAL SYS SYSTEM BI BACKWARD INCLINED / BINARY INPUT F FAHRENHEIT, FAN NC NORMALLY CLOSED, NOISE CRITERIA T THERMOSTAT, TIME, TANK BLDG BUILDING FA FACE AREA NEC NATIONAL ELECTRICAL CODE TAB TESTING, ADJUSTING & BALANCING BOD BOTTOM OF DUCT FC FORWARD CURVED NEMA NAT. ELECT MANUFACTURERS ASSOC. TB THRUST BLOCK BOP BOTTOM OF PIPE FD FLOOR DRAIN, FIRE DAMPER NFPA NAT. FIRE PROTECTION ASSOCIATION TCV TEMPERATURE CONTROL VALVE BTU BRITISH THERMAL UNIT FEC FIRE EXTINGUISHER CABINET NIC NOT IN CONTRACT TD TEMPERATURE DIFFERENCE BTUH BRITISH THERMAL UNIT PER HOUR FEX FIRE EXTINGUISHER NO NORMALLY OPEN TDH TOTAL DYNAMIC HEAD C/C CENTER TO CENTER FH FUME HOOD NO. NUMBER TEMP TEMPERATURE, TEMPORARY CAV CONSTANT AIR VOLUME FHC FIRE HOSE CABINET NRS NON RISING STEM TG TRANSFER GRILLE CB CATCH BASIN FLA FULL LOAD AMPS NTS NOT TO SCALE TOT TOTAL CC COOLING COIL FLEX FLEXIBLE OA OUTSIDE AIR TP TEMPRATURE AND PRESSURE CFH CUBIC FEET PER HOUR FLR FLOOR OC ON CENTER TSP TOTAL STATIC PRESSURE CFM CUBIC FEET PER MINUTE FM FACTORY MUTUAL OD OUTSIDE DIAMETER TSTAT THERMOSTAT CH CHILLER FP FIRE PROTECTION OS&Y OUTSIDE SCREW AND YOKE TU TERMINAL UNIT CHWR CHILLED WATER RETURN FPM FEET PER MINUTE OSHA OCCUPATIONAL SAFETY & HEALTH ACT TX THERMOSTATIC EXPANSION CHWS CHILLED WATER SUPPLY FRP FIBERGLASS REINFORCED PLASTIC OV OUTLET VELOCITY TYP TYPICAL CI CAST IRON FS FLOW SWITCH, FREEZESTAT P PUMP UC UNDERCUT CIRC CIRCLE, CIRCULAR, CIRCULATION FSD FIRE & SMOKE DAMPER PD PRESSURE DROP UG UNDERGROUND CL CENTER LINE FT FOOT, FEET PERF PERFORATED UH UNIT HEATER CLG CEILING FVEL FACE VELOCITY PERM PERMANENT UL UNDERWRITERS LABORATORIES CO CLEANOUT G GRAM, GAS (NATURAL) PH PHASE UPS UNINTERRUPTABLE POWER SYSTEM COEF COEFFICIENT GA GAGE, GAUGE PHC PREHEAT COIL UR URINAL COL COLUMN GAL GALLON PIV POST INDICATOR VALVE V VENT, VALVE, VOLT CONC CONCRETE GALV GALVANIZED PLBG PLUMBING VA VALVE, VOLT-AMPERE COND CONDENSATE, CONDENSER GEN GENERAL PNL PANEL VAC VACUUM CONN CONNECTION GI GALVANIZED IRON PP POWER PANEL VAR VARIABLE CONT CONTINUATION, CONTINUOUS, CONTROL GPD GALLONS PER DAY PPH POUNDS PER HOUR VAV VARIABLE AIR VOLUME CONTR CONTRACTOR GPH GALLONS PER HOUR PREFAB PREFABRICATED VB VACUUM BREAKER COORD COORDINATE GPM GALLONS PER MINUTE PREP PREPARATION VD VOLUME DAMPER CPVC CHOLORINATED POLYVINYL CHLORIDE GR GRADE, GRAINS PRESS PRESSURE VEL VELOCITY CTR CENTER H HIGH, HEIGHT, HUMIDIFIER, HUMIDISTAT PROJ PROJECT, PROJECTION VENT VENTILATING, VENTILATION CU COPPER, CUBIC HB HOSE BIBB PROP PROPERTY VERT VERTICAL CU FT CUBIC FEET HC HEATING COIL PRV PRESSURE REDUCING VALVE VEST VESTIBULE CUH CABINET UNIT HEATER HD HEAVY-DUTY, HEAD, HEAT DETECTOR PS PRESSURE SWITCH VOL VOLUME Cv COEFFICIENT, VALVE FLOW HEX HEAT EXCHANGER, HEXAGON PSI POUNDS PER SQUARE INCH VOLT VOLTAGE CW COLD WATER, CLOCKWISE HG MERCURY PVC POLYVINYL CHLORIDE VSD VARIABLE SPEED DRIVE CWR CONDENSER WATER RETURN HO HUB OUTLET R RADIUS, RISE VTR VENT THROUGH ROOF CWS CONDENSER WATER SUPPLY HORIZ HORIZONTAL, HORIZONTALLY R22 REFRIGERANT R22 W WEST, WIDE, WIDTH, WATT D DRAIN, DAMPER, DROP HP HORSEPOWER, HIGH PRESSURE RA RETURN AIR W&V WASTE AND VENT DB DRY BULB, DECIBEL HR HOUR RD ROOF DRAIN, REFIRGERANT DISCHARGE W/ WITH DBT DRY BULB TEMPERATURE HRU HEAT RECOVERY UNIT RECIRC RECIRCULATION W/O WITHOUT DC DIRECT CURRENT HTG HEATING REF REFERENCE WB WET BULB DDC DIRECT DIGITAL CONTROL HTR HEATER REFRIG REFRIGERANT, REFRIGERATION WBT WET BULB TEMPERATURE DEG DEGREE HUM HUMIDITY, HUMIDIFIER REQD REQUIRED WC WATER CLOSET DEGF DEGREES FAHRENHEIT HVY HEAVY RET RETURN WF WASH FOUNTAIN DEMO DEMOLISH, DEMOLITION HW HOT WATER REV REVISION, REVOLUTION WG WATER GAUGE DEPT DEPARTMENT HWR HOT WATER RECIRCULATION RF RETURN FAN WH WALL HYDRANT DET DETAIL HZ HERTZ FREQUENCY RGA RETURN GRILLE TYPE A WPD WATER PRESSURE DROP DF DRINKING FOUNTAIN I/O INPUT/OUTPUT RH RIGHT HAND, RELATIVE HUMIDITY WT WEIGHT DG DOOR GRILLE ID INSIDE DIAMETER, IDENTIFICATION RL REFRIGERANT LIQUID Y YARD DI DISTILLED WATER / DIGITAL INPUT IE INVERT ELEVATION RM ROOM YH YARD HYDRANT DIA DIAMETER IN. INCH, INCHES RO REVERSE OSMOSIS, ROUGH OPENING CONTROLS & ELECTRICAL HVAC GRILLE, CEILING RETURN/EXHAUST DIFFUSER, CEILING SUPPLY ROUND DAMPER, SMOKE DAMPER, FIRE DAMPER, ELECTRIC OPERATED HEATER, ELECTRIC DUCT DIFFUSER, CEILING LINEAR/SLOT FAN, LOUVERED ROOF FAN, ROOF EXHAUST DIFFUSER, CEILING SUPPLY SQUARE UNIT, TERMINAL DUAL DUCT DUCT, ACOUSTIC LINED LOUVER ELBOW, RADIUS/SQUARE W/ VANES DUCT, SUPPLY DUCT, EXHAUST / RETURN DIRECTION, FLOW CONNECTION, FLEXIBLE GRILLE, WALL SUPPLY DROP, DUCT DIFF, SPLY TYP B, 8" NECK, 250 CFM SIZE, DUCT 12" WIDE X 10" DEEP DAMPER, PNEUMATIC OPERATED RISE, DUCT UNIT, TERMINAL VAV RH UNIT, TERMINAL VAV W/ ATTENUATOR UNIT, TERMINAL VAV NO ATTENUATOR DOOR, ACCESS ATTENUATOR, SOUND DAMPER, BACK DRAFT FLEXIBLE DUCT DUCT BRANCH, STANDARD GRILLE, WALL RETURN /EXHAUST DIFFUSER/GRILLE THROW DIRECTION LOUVER L-1, 24" X 12", 750 CFM HUMIDISTAT SENSOR, HUMIDITY TEMPERATURE SENSOR THERMOSTAT SWITCH, PRESSURE SWITCH, FLOW MOTOR CONTROL POWER PANEL LIGHTING PANEL TELEPHONE OUTLET METER, WATT HOUR TRANSFORMER FUSE CIRCUIT BREAKER RECEPTACLE, DUPLEX BOX, JUNCTION SWITCH DISCONNECT, FUSED DISCONNECT, UNFUSED MOTOR / ACTUATOR ELECTRIC FAN, CENTRIFUGAL FAN, AXIAL / PROPELLER DAMPER, COMBINATION FIRE/SMOKE SF SUPPLY FAN, SAFETY FACTOR PIPE FITTING & FP METER SENSOR, PRESSURE SENSOR, LIGHT (PHOTO CELL) SENSOR, CO2 SENSOR, LEVEL CONTROLLER RELAY AI ANALOG INPUT AO ANALOG OUTPUT BO BINARY OUTPUT DO DIGITAL OUTPUT PREVENTER, BACKFLOW FPWH FREEZE PROOF WALL HYDRANT CTE CONNECT TO EXISTING PROJECT No. DRAWN BY DATE CAD FILE SHEET ISSUE DATE (Y-M-D) No. ISSUED FOR CLIENT SCALE 374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected] Passa Associates Inc. WWW.PASSA.CA PROJECT ARCHITECTS Please note that all information included in these drawing files is protected by copyright. Unauthorized use of these files without the written permission of Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects is responsible only for information shown on a mechanical reproduction of these drawings that have been signed and stamped by an architect with signing authority employed by the firm. If you require further information please contact our office at the numbers listed. A R C H I T E C T S ISSUE DATE (Y-M-D) No. ISSUED FOR 2606 WINDSOR CAMPUS 720 OUELLETTE AVE., WINDSOR ON. AUG. 09, 2021 UNIVERSITY OF OTTAWA 75 LAURIER AVE. E., OTTAWA, ON. 2021-06-25 1 PROGRESS 2021-06-30 2 PERMIT 2021-07-14 3 FINAL REVIEW 2021-07-27 4 PROGRESS 2021-08-09 5 PERMIT & TENDER JACE #21-023 M1 LEGENDS, ABBREVIATIONS & MECHANICAL DRAWING LIST NA 2021-08-09 21-023

Upload: others

Post on 03-Oct-2021

23 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M1 - LEGENDS M1

WET STAND PIPE

DRY STAND PIPE

COMBINATION STAND PIPE

SPRINKLER

FIRE WATER SUPPLY

REFRIGERANT LIQUID

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

HUMIDIFICATION

GLYCOL HEATING RETURN

GLYCOL HEATING SUPPLY

HOT WATER RETURN ( HEATING)

HOT WATER SUPPLY (HEATING)

FUEL OIL VENT

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAUGE

FUEL OIL DISCHARGE

NATURAL GAS

CONDENSATE DRAIN

DRAIN

VENT (PLUMBING)

STORM DRAINAGE

SANITARY DRAINAGE

HOT WATER RETURN (DOMESTIC)

HOT WATER (DOMESTIC)

COLD WATER (DOMESTIC)

LEGEND

EXISTING ITEM TO DEMOLISH

EXISTING ITEM TO REMAIN

ELBOW, TURNED UP

ELBOW, TURNED DOWN

REDUCER, CONCENTRIC

ELBOW, 90 DEGREES

ELBOW, 45 DEGREES

CAP

THERMOMETER

GAGE, PRESSURE WITH COCK

REDUCER, ECCENTRIC

MANUAL AIR VENT

AUTOMATIC AIR VENT

AIR ELIMINATOR

JOINT, EXPANSION

ANCHOR

GUIDE, ALIGNMENT

SLEEVE, PIPE

PUMP

RISE, PIPE

DROP, PIPE

COCK

FLANGE, BLIND

VALVE, CONTROL 3 WAY ELECTRIC

VALVE, CONTROL 3 WAY PNEUMATIC

VALVE, CONTROL 2 WAY PNEUMATIC

THERMOMETER WELL

STRAINER, BLOW OFF

STRAINER

DIFFUSER, PUMP SUCTION

VALVE, SOLENOID / THERMOSTATIC

VALVE, TRIPLE DUTY

CONNECTION, FLEXIBLE

ARROW, FLOW DIRECTION

VALVE, FLOW CONTROL

VALVE, FLOAT

VALVE, LOCK SHIELD

VALVE, PLUG

VALVE, NEEDLE

VALVE, GLOBE

VALVE, BUTTERFLY

VALVE, ANGLE

VALVE, BALL

VALVE, GATE

UNION

TEE

TEE, OUTLET UP

TEE, OUTLET DOWN

VALVE, CHECK

TRAP, STEAM FLOAT & THERMOSTATIC

TRAP, STEAM FLOAT

TRAP, STEAM

VALVE, SAFETY/RELIEF

VALVE, SAFETY

VALVE, QUICK OPENING

VALVE, PRESSURE REDUCING

OUTLET, GAS, OXY, VAC, N20

CLEANOUT, WALL

FIRE ALARM CONTROL PANEL

CONNECTION, FIRE DEPT SIAMESE

BELL, FIRE ALARM

SPRINKLER, AUTOMATIC

SPRINKLER HEAD, SIDEWALL

SPRINKLER HEAD, PENDANT

SPRINKLER HEAD, UPRIGHT

VALVE, OUTSIDE SCREW & YOKE

VALVE, DRY PIPE

VALVE, ALARM CHECK

VALVE, POST INDICATOR

VALVE, TAMPER DETECTION SWITCH

DRAIN, FLOOR

CLEANOUT, FLOOR

HVAC CONTROL PANEL

HYDRANT, WALL

HYDRANT, FIRE

DETECTOR, GAS

DETECTOR, HEAT

DETECTOR, SMOKE

STANDPIPE, DRY STATION

STANDPIPE, WET STATION

GONG, WATER MOTOR ALARM

HORN / SPEAKER

EXTINGUISHER, DRY CHEM MANUAL ACTIVATION

EXTINGUISHER, DRY CHEM AUTO ACTIVATION

EXTINGUISHER, DRY CHEMICAL

DRAIN, ROOF

ABBREVIATIONSA AMP, AMPERES, AIR (COMPRESSED) DIFF DIFFERENCE, DELTA INCL INCLUDING, INCLUSIVE RPM REVOLUTIONS PER MINUTE

ABS ABSOLUTE DIM DIMENSION INSUL INSULATION, INSULATED RS ROOF SUMP, REFRIGERANT SUCTION

AC ALT. CURRENT, AIR COMPRESSOR DISC DISCONNECT INT INTERIOR, INTERNAL S SOUTH, SOLENOID

ACU AIR CONDITIONING UNIT DISCH DISCHARGE INV INVERT SA SUPPLY AIR, SOUND ATTENUATOR

AD ACCESS DOOR DIV DIVISION IPS IRON PIPE SIZE SAN SANITARY DRAIN/SEWER

ADDL ADDITIONAL DN DOWN ISD IONIZATION SMOKE DETECTOR SCFM (STANDARD) CUBIC FEET PER MINUTE

ADDM ADDENDUM

DOM DOMESTIC

JC JANITOR’S CLOSET SCHED SCHEDULE

ADDN ADDITION

DS DOWNSPOUT, DISCONNECT

KW KILOWATTS SCW SOFT COLD WATER

ADJ ADJUSTABLE

DT DRAIN TILE

L LENGTH, LONG, LOUVER SD SMOKE DAMPER

A-E ARCHITECT-ENGINEER

DWC DRINKING WATER COOLER

LAB LABORATORY SDA SUPPLY DIFFUSER TYPE A

AF AIR FOIL

DWG DRAWING

LAT LEAVING AIR TEMPERATURE SE STATIC FAN EFFICIENCY, SOUTHEAST

AFF ABOVE FINISHED FLOOR

DWR DRINKING WATER RETURN

LAV LAVATORY SECT SECTION

AFS AIR FLOW SWITCH

DWS DRINKING WATER SUPPLY

LB/LBS POUND POUNDS SENS SENSIBLE

AHU AIR HANDLING UNIT

DX DIRECT EXPANSION

LP LOW PRESSURE, LIGHTING PANEL

SF SERVICE FACTOR

ALT ALTERNATE, ALTITUDE EA EXHAUST AIR, EACH

LR LONG RADIUS

SGA SUPPLY GRILLE TYPE A

AMB AMBIENT EAT ENTERING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

SH SHOWER, SENSIBLE HEAT

AMS AIR MEASURING STATION ECC ECCENTRIC

M METER, MOTOR

SHT SHEET

ANSI AMERICAN NAT. STANDARDS INSTITUTE ECON ECONOMIZER

MAN MANUAL

SIM SIMILAR

APD AIR PRESSURE DROP

EEW EMERGENCY EYE WASH

MATL MATERIAL

SM SHEET METAL

APPROX APPROXIMATE

EF EXHAUST FAN

MAX MAXIMUM

SP STATIC PRESSURE

ARCH ARCHITECT, ARCHITECTURAL

EFF EFFICIENCY

MBH 1000 BRITISH THERMAL UNITS / HOUR

SPEC SPECIFICATION

AS AUTOMATIC SPRINKLER

EGA EHAUST GRILLE TYPE A

MC MOTOR CONTROL

SPR SPRINKLER

ASME AM. SOCIETY OF MECHANICAL ENGINEERS

EL ELEVATION

MCC MOTOR CONTROL CENTER

SQ SQUARE

ASR AUTOMATIC SPRINKLER RISER

ELEC ELECTRIC, ELECTRONIC

MECH MECHANICAL

SR SUPPLY RISER

ASTM AM. SOCIETY FOR TESTING MATERIALS

ELEV ELEVATOR

MEZZ MEZZANINE

SSTL STAINLESS STEEL

ATM ATMOSPHERE

ELL ELBOW

MFG MANUFACTURING

ST STORM

AUTO AUTOMATIC

EMS ENERGY MANAGEMENT SYSTEM

MFR MANUFACTURER

STA STATION

AUX AUXILIARY

ENCL ENCLOSURE, ENCLOSED

MH MANHOLE

STD STANDARD

AV AIR VENT (AUTOMATIC)

ENT ENTERING

MIN MINIMUM, MINUTE

STL STEEL

AW ACID WASTE

EQ EQUAL

MISC MISCELLANEOUS

STM STEAM

B BOILER, BRINE SUPPLY

EQUIP EQUIPMENT

MM MILLIMETER

STOR STORAGE

BDD BACKDRAFT DAMPER

EVAP EVAPORATOR

MU MAKE UP

STR STRAINER

BET BETWEEN

EWT ENTERING WATER TEMPERATURE

MV AIR VENT (MANUAL)

STRUCT STRUCTURAL

BF BARRIER FREE

EX EXISTING

N NORTH

SUCT SUCTION

BFP BACK FLOW PREVENTER

EXH EXHAUST

NA NOT APPLICABLE

SW SWITCH

BHP BRAKE HORSEPOWER

EXP EXPANSION

NATL NATIONAL

SYS SYSTEM

BI BACKWARD INCLINED / BINARY INPUT

F FAHRENHEIT, FAN

NC NORMALLY CLOSED, NOISE CRITERIA

T THERMOSTAT, TIME, TANK

BLDG BUILDING

FA FACE AREA

NEC NATIONAL ELECTRICAL CODE

TAB TESTING, ADJUSTING & BALANCING

BOD BOTTOM OF DUCT

FC FORWARD CURVED

NEMA NAT. ELECT MANUFACTURERS ASSOC.

TB THRUST BLOCK

BOP BOTTOM OF PIPE

FD FLOOR DRAIN, FIRE DAMPER

NFPA NAT. FIRE PROTECTION ASSOCIATION

TCV TEMPERATURE CONTROL VALVE

BTU BRITISH THERMAL UNIT

FEC FIRE EXTINGUISHER CABINET

NIC NOT IN CONTRACT

TD TEMPERATURE DIFFERENCE

BTUH BRITISH THERMAL UNIT PER HOUR

FEX FIRE EXTINGUISHER

NO NORMALLY OPEN

TDH TOTAL DYNAMIC HEAD

C/C CENTER TO CENTER

FH FUME HOOD

NO. NUMBER

TEMP TEMPERATURE, TEMPORARY

CAV CONSTANT AIR VOLUME

FHC FIRE HOSE CABINET

NRS NON RISING STEM

TG TRANSFER GRILLE

CB CATCH BASIN

FLA FULL LOAD AMPS

NTS NOT TO SCALE

TOT TOTAL

CC COOLING COIL

FLEX FLEXIBLE

OA OUTSIDE AIR

TP TEMPRATURE AND PRESSURE

CFH CUBIC FEET PER HOUR

FLR FLOOR

OC ON CENTER

TSP TOTAL STATIC PRESSURE

CFM CUBIC FEET PER MINUTE

FM FACTORY MUTUAL

OD OUTSIDE DIAMETER

TSTAT THERMOSTAT

CH CHILLER

FP FIRE PROTECTION

OS&Y OUTSIDE SCREW AND YOKE

TU TERMINAL UNIT

CHWR CHILLED WATER RETURN

FPM FEET PER MINUTE

OSHA OCCUPATIONAL SAFETY & HEALTH ACT

TX THERMOSTATIC EXPANSION

CHWS CHILLED WATER SUPPLY

FRP FIBERGLASS REINFORCED PLASTIC

OV OUTLET VELOCITY

TYP TYPICAL

CI CAST IRON

FS FLOW SWITCH, FREEZESTAT

P PUMP

UC UNDERCUT

CIRC CIRCLE, CIRCULAR, CIRCULATION

FSD FIRE & SMOKE DAMPER

PD PRESSURE DROP

UG UNDERGROUND

CL CENTER LINE

FT FOOT, FEET

PERF PERFORATED

UH UNIT HEATER

CLG CEILING

FVEL FACE VELOCITY

PERM PERMANENT

UL UNDERWRITERS LABORATORIES

CO CLEANOUT

G GRAM, GAS (NATURAL)

PH PHASE

UPS UNINTERRUPTABLE POWER SYSTEM

COEF COEFFICIENT

GA GAGE, GAUGE

PHC PREHEAT COIL

UR URINAL

COL COLUMN

GAL GALLON

PIV POST INDICATOR VALVE

V VENT, VALVE, VOLT

CONC CONCRETE

GALV GALVANIZED

PLBG PLUMBING

VA VALVE, VOLT-AMPERE

COND CONDENSATE, CONDENSER

GEN GENERAL

PNL PANEL

VAC VACUUM

CONN CONNECTION

GI GALVANIZED IRON

PP POWER PANEL

VAR VARIABLE

CONT CONTINUATION, CONTINUOUS, CONTROL

GPD GALLONS PER DAY

PPH POUNDS PER HOUR

VAV VARIABLE AIR VOLUME

CONTR CONTRACTOR

GPH GALLONS PER HOUR

PREFAB PREFABRICATED

VB VACUUM BREAKER

COORD COORDINATE

GPM GALLONS PER MINUTE

PREP PREPARATION

VD VOLUME DAMPER

CPVC CHOLORINATED POLYVINYL CHLORIDE

GR GRADE, GRAINS

PRESS PRESSURE

VEL VELOCITY

CTR CENTER

H HIGH, HEIGHT, HUMIDIFIER, HUMIDISTAT

PROJ PROJECT, PROJECTION

VENT VENTILATING, VENTILATION

CU COPPER, CUBIC

HB HOSE BIBB

PROP PROPERTY

VERT VERTICAL

CU FT CUBIC FEET

HC HEATING COIL

PRV PRESSURE REDUCING VALVE

VEST VESTIBULE

CUH CABINET UNIT HEATER

HD HEAVY-DUTY, HEAD, HEAT DETECTOR

PS PRESSURE SWITCH

VOL VOLUME

Cv COEFFICIENT, VALVE FLOW

HEX HEAT EXCHANGER, HEXAGON

PSI POUNDS PER SQUARE INCH

VOLT VOLTAGE

CW COLD WATER, CLOCKWISE

HG MERCURY

PVC POLYVINYL CHLORIDE

VSD VARIABLE SPEED DRIVE

CWR CONDENSER WATER RETURN

HO HUB OUTLET

R RADIUS, RISE

VTR VENT THROUGH ROOF

CWS CONDENSER WATER SUPPLY

HORIZ HORIZONTAL, HORIZONTALLY

R22 REFRIGERANT R22

W WEST, WIDE, WIDTH, WATT

D DRAIN, DAMPER, DROP

HP HORSEPOWER, HIGH PRESSURE

RA RETURN AIR

W&V WASTE AND VENT

DB DRY BULB, DECIBEL

HR HOUR

RD ROOF DRAIN, REFIRGERANT DISCHARGE

W/ WITH

DBT DRY BULB TEMPERATURE

HRU HEAT RECOVERY UNIT

RECIRC RECIRCULATION

W/O WITHOUT

DC DIRECT CURRENT

HTG HEATING

REF REFERENCE

WB WET BULB

DDC DIRECT DIGITAL CONTROL

HTR HEATER

REFRIG REFRIGERANT, REFRIGERATION

WBT WET BULB TEMPERATURE

DEG DEGREE

HUM HUMIDITY, HUMIDIFIER

REQD REQUIRED

WC WATER CLOSET

DEGF DEGREES FAHRENHEIT

HVY HEAVY

RET RETURN

WF WASH FOUNTAIN

DEMO DEMOLISH, DEMOLITION

HW HOT WATER

REV REVISION, REVOLUTION

WG WATER GAUGE

DEPT DEPARTMENT

HWR HOT WATER RECIRCULATION

RF RETURN FAN

WH WALL HYDRANT

DET DETAIL

HZ HERTZ FREQUENCY

RGA RETURN GRILLE TYPE A

WPD WATER PRESSURE DROP

DF DRINKING FOUNTAIN

I/O INPUT/OUTPUT

RH RIGHT HAND, RELATIVE HUMIDITY

WT WEIGHT

DG DOOR GRILLE

ID INSIDE DIAMETER, IDENTIFICATION

RL REFRIGERANT LIQUID

Y YARD

DI DISTILLED WATER / DIGITAL INPUT

IE INVERT ELEVATION

RM ROOM

YH YARD HYDRANT

DIA DIAMETER

IN. INCH, INCHES

RO REVERSE OSMOSIS, ROUGH OPENING

CONTROLS & ELECTRICAL

HVAC

GRILLE, CEILING RETURN/EXHAUST

DIFFUSER, CEILING SUPPLY ROUND

DAMPER, SMOKE

DAMPER, FIRE

DAMPER, ELECTRIC OPERATED

HEATER, ELECTRIC DUCT

DIFFUSER, CEILING LINEAR/SLOT

FAN, LOUVERED ROOF

FAN, ROOF EXHAUST

DIFFUSER, CEILING SUPPLY SQUARE

UNIT, TERMINAL DUAL DUCT

DUCT, ACOUSTIC LINED

LOUVER

ELBOW, RADIUS/SQUARE W/ VANES

DUCT, SUPPLY

DUCT, EXHAUST / RETURN

DIRECTION, FLOW

CONNECTION, FLEXIBLE

GRILLE, WALL SUPPLY

DROP, DUCT

DIFF, SPLY TYP B, 8" NECK, 250 CFM

SIZE, DUCT 12" WIDE X 10" DEEP

DAMPER, PNEUMATIC OPERATED

RISE, DUCT

UNIT, TERMINAL VAV RH

UNIT, TERMINAL VAV W/ ATTENUATOR

UNIT, TERMINAL VAV NO ATTENUATOR

DOOR, ACCESS

ATTENUATOR, SOUND

DAMPER, BACK DRAFT

FLEXIBLE DUCT

DUCT BRANCH, STANDARD

GRILLE, WALL RETURN /EXHAUST

DIFFUSER/GRILLE THROW DIRECTION

LOUVER L-1, 24" X 12", 750 CFM

HUMIDISTAT

SENSOR, HUMIDITY

TEMPERATURE SENSOR

THERMOSTAT

SWITCH, PRESSURE

SWITCH, FLOW

MOTOR CONTROL

POWER PANEL

LIGHTING PANEL

TELEPHONE OUTLET

METER, WATT HOUR

TRANSFORMER

FUSE

CIRCUIT BREAKER

RECEPTACLE, DUPLEX

BOX, JUNCTION

SWITCH

DISCONNECT, FUSED

DISCONNECT, UNFUSED

MOTOR / ACTUATOR ELECTRIC

FAN, CENTRIFUGAL

FAN, AXIAL / PROPELLER

DAMPER, COMBINATION FIRE/SMOKE

SF SUPPLY FAN, SAFETY FACTOR

PIPE FITTING & FP

METER

SENSOR, PRESSURE

SENSOR, LIGHT (PHOTO CELL)

SENSOR, CO2

SENSOR, LEVEL

CONTROLLER

RELAY

AI ANALOG INPUT

AO ANALOG OUTPUT

BO BINARY OUTPUT

DO DIGITAL OUTPUT

PREVENTER, BACKFLOW

FPWH FREEZE PROOF WALL HYDRANT

CTE CONNECT TO EXISTING

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023 M1

LEGENDS, ABBREVIATIONS & MECHANICAL DRAWING LIST

NA

2021-08-0921-023

Page 2: M1 - LEGENDS M1

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023 M2

MECHANICAL SPECIFICATIONS

1/8" - 1'-0"

MECHANICAL SPECIFICATIONS

SECTION 15000 - GENERAL SPECIFICATIONS

1.0 GENERAL

1.1 THIS GENERAL SPECIFICATION APPLIES TO ALL MECHANICAL WORK INCLUDING

HVAC, PLUMBING, FIRE PROTECTION AND CONTROLS. SEE THE RESPECTIVE

SECTIONS.

1.2 ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, ORDINANCES,

STANDARDS, GOOD PRACTICE, MANUFACTURER'S RECOMMENDATIONS & PRODUCT

LISTING CONDITIONS FOR NEW, RENOVATON AND/OR DEMOLITION WORK. THIS

INCLUDES BUT NOT LIMITED TO ASHRAE, SMACNA, NFPA, IMC, IPC, IFGC, IFC, UL/ULC,

FM, OWNERS INSURANCE REQUIREMENTS & LOCAL CODES, REGULATIONS & BYLAWS.

SHOULD A CONFLICT OCCUR BETWEEN DRAWINGS, SPECIFICATIONS, CODES,

REGULATIONS, ORDINANCES, STANDARDS, GOOD PRACTICE, MANUFACTURER'S

RECOMMENDATIONS & PRODUCT LISTING CONDITIONS THE MOST STRINGENT

REQUIREMENTS SHALL PREVAIL.

1.3 QUALIFICATIONS: EXECUTE WORK ONLY WITH SKILLED TRADESMEN EMPLOYED

BY A QUALIFIED TRADE CONTRACTORS IN ONTARIO REGULARLY ENGAGED IN THE

INSTALLATION OF THEIR RESPECTIVE SYSTEMS.

1.4 INSTALLATION SHALL BE COMPLETE AND FULLY FUNCTIONAL. PROVIDE ALL

MATERIALS, EQUIPMENT, ACCESSORIES, CONSUMABLES, LABOR, SUPERVISION,

TOOLS, SERVICES, ETC. AS REQUIRED.

1.5 PROVIDE THE FOLLOWING SYSTEMS AS PART OF THIS CONTRACT: HVAC,

PLUMBING, FIRE PROTECTION WET SPRINKLERS, FIRE EXTINGUISHERS AND

ASSOCIATED CONTROLS.

1.6 PROVIDE A SCHEDULE WITHIN 5 WORKING DAYS OF AWARD OF CONTRACT.

SCHEDULE TO INCLUDE TIME FOR CONTRACTOR COMMISSIONING CLEARLY

INDICATED. PROVIDE A BILLING BREAKDOWN FOR REVIEW PRIOR TO FIRST DRAW

SUBMISSION.

1.7 ARRANGE FOR ALL PERMITS, APPROVALS, EXAMINATION, TESTS AND INSPECTION

SERVICES. PAY ALL REQUIRED FEES & CHARGES. PROVIDE ALL THE NECESSARY

APPLICATIONS, DOCUMENTATION, DRAWINGS AND SPECIFICATIONS. NO WORK SHALL

COMMENCE UNTIL ALL REQUIRED PERMITS, APPROVALS, ETC. ARE OBTAINED FROM

AUTHORITIES HAVING JURISDICTION.

1.8 EXAMINE ALL DRAWINGS AND SPECIFICATIONS AND REPORT ALL CONFLICTS,

DISCREPANCIES TO THE CONSULTANT FOR CLARIFICATION AND /OR CORRECTION.

1.9 DRAWINGS: DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL

ARRANGEMENT OF MECHANICAL SYSTEMS AND WORK INCLUDED. DO NOT SCALE

DRAWINGS. OBTAIN DIMENSIONS FROM ENGINEER'S PLANS, MANUFACTURER'S SHOP

DRAWINGS AND ONSITE INSPECTIONS.

1.10 ELECTRICAL WORK: ALL WIRING AND CONDUIT FOR POWER AND CONTROL SHALL

BE BY ELECTRICAL DIVISION, EXCEPT FOR WIRING, CONDUIT AND CONNECTIONS

BELOW 50V WHICH ARE RELATED TO AUTOMATIC CONTROL SYSTEMS SHALL BE BY

CONTROLS CONTRACTOR.

1.11 SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR ALL EQUIPMENT. THE SHOP

DRAWINGS SHALL INDICATE THE MANUFACTURER, MODEL, AND PHYSICAL,

ELECTRICAL, MECHANICAL, AND PERFORMANCE CHARACTERISTICS.

1.12 PROTECT WORK AND STRUCTURE FROM DAMAGE, WEATHER, TEMPERATURE

AND HUMIDITY EXTREMES.

1.13 PROVIDE SCHEDULE 40 PIPE SLEEVES AT PENETRATIONS THROUGH MASONRY

AND CONCRETE, OR FIRE RATED ASSEMBLIES.

1.14 PROVIDE FIRE STOPPING MATERIAL AT PENETRATIONS THROUGH FIRE RATED

ASSEMBLIES TO MAINTAIN FIRE RATING INTEGRITY.

1.15 PROVIDE ACCESS FOR SERVICING EQUIPMENT AS RECOMMENDED BY THE

MANUFACTURER.

1.16 INSTALL EQUIPMENT, DUCTS AND PIPES PARALLEL TO OR PERPENDICULAR TO

BUILDING LINES.

1.17PROVIDE SPACE, UNIONS AND FLANGES FOR EASE OF MAINTENANCE,

DISASSEMBLY AND REMOVAL OF EQUIPMENT.

1.18 PIPE EQUIPMENT DRAINS TO FLOOR DRAINS, JANITOR / SERVICE SINKS, ETC AS

APPLICABLE.

1.19 PIPE PAINTING AND IDENTIFICATION SHALL COMPLY WITH STANDARDS. IDENTIFY

PIPES AT EVERY BRANCH AND AT EVERY EQUIPMENT. USE PLASTIC COATED CLOTH

MATERIAL WITH COLORS AND IDENTIFICATION AND WATER PROOF ADHESIVE.

1.20 RECORD ALL DEVIATIONS FROM THE CONSTRUCTION DRAWINGS. ON PROJECT

COMPLETION, PROVIDE REPRODUCIBLE “AS BUILT” DRAWINGS SHOWING WORK AS

ACTUALLY INSTALLED.

1.21 CONDUCT TESTS IN ACCORDANCE WITH APPLICABLE CODES ANS STANDARDS.

1.22 PROVIDE 3 COPIES OPERATING AND MAINTENANCE MANUALS FOR HVAC,

PLUMBING, FIRE PROTECTION, AND CONTROL EQUIPMENT/SYSTEMS. INCLUDE: “AS

BUILT” DRAWINGS, SHOP DRAWINGS, PRODUCT DATA, OPERATING & MAINTENANCE

INSTRUCTIONS, TROUBLE SHOOTING, PART LISTS, T & B REPORT, WARRANTIES,

WIRING AND CONTROL DIAGRAMS. O&M TO BE INDEXED AND PDF TO BE OCR

SEARCHABLE. SUBMIT TO CONSULTANT AND OWNER 10 DAYS PRIOR TO REQUESTING

SUBSTANTIAL COMPLETION.

1.23 DEMONSTRATE AND INSTRUCT CLIENT'S PERSONNEL IN OPERATING,

CONTROLLING, ADJUSTING, TROUBLE SHOOTING, AND SERVICING ALL SYSTEMS AND

EQUIPMENT. INSTRUCTIONS SHALL BE HELD DURING REGULAR WORK HOURS PRIOR

TO ACCEPTANCE. TOTAL TIME SHALL NOT BE LESS THAN 2 HOURS.

1.24 FURNISH A GUARANTEE COVERING ALL EQUIPMENT, COMPONENTS,

ACCESSORIES AND SYSTEMS FOR MINIMUM OF ONE YEAR FROM THE DATE OF

ACCEPTANCE.

1.25 START-UP AND COMMISSIONING: PROVIDE START-UP, TESTING AND

COMMISSIONING. PROVIDE TECHNICAL SERVICE REPORT OF TEST RESULTS. THIS

INCLUDES A DEFICIENCY LIST. CONTRACTOR IS RESPONSIBLE TO ENSURE ALL

EQUIPMENT FUNCTIONS AS PER DESIGN DOCUMENTS. CONTRACTOR TO NOTIFY

CONSULTANT 5 DAYS PRIOR TO START OF CONTRACTOR COMMISSIONING FOR

OPTIONAL WITNESSING. CONTRACTOR TO MAINTAIN A DEFICIENCY LIST THAT

INCORPORATES ALL DEFICIENCIES NOTED FROM ALL PARTIES. PRINTOUT OF BAS

GRAPHICS TO BE PROVIDED TO CONSULTANT FOR REVIEW.

1.26 DEMOLITION & RENOVATIONS:

1.26.1 REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL SCOPE OF DEMOLITION.

COORDINATE WITH ARCHITECTURAL, STRUCTURAL & ELECTRICAL DEMOLITION.

1.26.2 DRAWINGS ARE BASED ON FIELD OBSERVATIONS & EXISTING RECORD

DRAWINGS. NOT EVERY MECHANICAL EQUIPMENT, COMPONENT, ACCESSORY,

DEVICE, PIPE, DUCT, SERVICE, UTILITY HAVE BEEN SHOWN. EXISTING SYSTEMS

SHOWN ON THE DRAWINGS MAY DIFFER FROM ACTUAL

1.26.3 THE DRAWINGS INDICATE ONLY AFFECTED EQUIPMENT IN THE DESIGNATED

DEMOLITION AREAS OF THIS PROJECT. EXCEPT FOR ITEMS DESIGNATED TO REMAIN,

REMOVE ALL NECESSARY ITEMS REQUIRED BY THIS DEMOLITION WHETHER SHOWN

OR NOT.

1.26.4 PRIOR TO BID/TENDER, EXAMINE ENTIRE DEMOLITION SCOPE/AREAS, ALL

DRAWINGS & SPECIFICATIONS INCLUDING EQUIPMENT LOCATIONS, AREAS OF

SERVICE, EXISTING EQUIPMENT / SERVICES TO REMAIN, PIPE/DUCT RUNS, ETC. TO

UNDERSTAND THE ENTIRE DEMOLITION SCOPE. REPORT ALL CONFLICTS,

DISCREPANCIES TO THE CONSULTANT FOR CLARIFICATION & /OR CORRECTION. NO

ALLOWANCE SHALL BE MADE FOR FAILURE TO DO SO.

1.26.5 PRIOR TO DEMOLITION & REMOVAL, SURVEY BUILDING & SITE TO COMFIRM NO

SERVICES / UTILITIES DESIGNATED FOR DEMOLITION WILL INTERRUPT SERVICES

OUTSIDE OF DEMOLITION AREA. IF CERTAIN SERVICES WILL BE DISRUPTED, REROUTE

SERVICES PRIOR TO DEMOLITION TO ENSURE CONTINUED SERVICE.

1.26.6 PRIOR TO DEMOLITION OF HVAC, PLUMBING, FIRE PROTECTION EQUIPMENT,

CONTROLS, COMPONENTS, SYSTEMS, ETC. ENSURE THAT THESE ARE NOT NEEDED &

WILL NOT BE USED FOR THE NEW WORK.

1.26.7 LIMIT DEMOLITION WORK TO THE DESIGNATED EQUIPMENT, APPLIANCES,

COMPONENTS, AREAS, ETC. REMOVE ALL DEMOLISHED ITEMS COMPLETE INCLUDING

ASSOCIATED PIPING, DUCTS, EQUIPMENT, INSULATION, SUPPORTS, COMPONENTS,

ACCESSORIES, CONTROLS, EQUIPMENT PADS, ETC. ASSOCIATED WITH DEMOLISHED

ITEMS UP TO DEMOLITION AREA LIMITS & SERVICES / UTILITIES TO REMAIN. VALVE,

CAP & TERMINATE UTILITIES, SERVICES, ETC.

1.26.8 NO SERVICES, UTILITIES, EQUIPMENT, APPLIANCES, PIPES, DUCTS, ETC. WITHIN

THE DEMOLITION AREAS THAT ARE NO LONGER NEEDED OR USED SHALL BE

ABANDONED IN PLACE. ALL UNNECESSARY SERVICES, UTILITIES, EQUIPMENT,

APPLIANCES, PIPES, DUCTS, ETC. SHALL BE COMPLETELY DEMOLISHED WITHIN THE

DESIGNATED DEMOLITION AREAS UNLESS INDICATED OTHERWISE.

1.26.9 CONTROLS, PIPES, SERVICES, UTILITIES, ETC. LOCATED IN WALLS, OR WALL

SURFACES, BEING DEMOLISHED SHALL BE COMPLETELY REMOVED BACK TO THEIR

RESPECTIVE SOURCES WHICH ARE TO REMAIN. CAP UTILITIES & SERVICES AT POINT

OF DEMOLITION.

1.26.10 ALL MECHANICAL EQUIPMENT & DEVICES (I.E. CONTROLS, THERMOSTATS,

SWITCHES, PIPES, DUCTS, ETC.) SHOWN TO BE REMOVED FROM A WALL WHICH IS TO

REMAIN, SHALL HAVE THESE MECHANICAL ITEMS ABANDONED WITHIN THE WALLS OR

COMPLETELY REMOVED / DEMOLISHED OTHERWISE. FURNISH & INSTALL A BLANK

COVERPLATE AS NEEDED.

1.26.11 DO NOT DISABLE OR DISRUPT BUILDING FIRE OR LIFE SAFETY SYSTEMS

WITHOUT PRIOR WRITTEN NOTICE TO & APPROVAL OF OWNER, GENERAL, ARCHITECT

& AUTHORITIES.

1.26.12 REMOVE DESIGNATED BUILDING MATERIALS, EQUIPMENT, TANKS, PIPING,

FIXTURES & CONSTRUCTION COMPLETE WITH ALL COMPONENTS, ACCESSORIES, ETC.

1.26.13 COORDINATE & SCHEDULE WORK WITH OWNER, GENERAL, ARCHITECT &

OTHER TRADES TO MINIMIZE CONFLICTS, DELAYS, INTERFERANCE & DISRUPTION OF

EXISTING SERVICES, OPERATIONS & ADJACENT BUILDING AREAS. PREVENT SPREAD

OF DUST, ODOURS, & NOISE TO PERMIT CONTINUED USE & OCCUPANCY. PERFORM

NOISY, MALODOROUS, DUSTY, &/OR DISRUPTIVE WORK ON DAYS & TIMES AGREED

WITH OWNER.

1.26.14 DEMOLISH IN AN ORDERLY & CAREFUL MANNER. PROTECT EXISTING

STRUCTURE. KEEP PROJECT SITE IN A CLEAN & ORDERLY MANNER. REMOVE TRASH

AT REGULAR INTERVALS TO PREVENT BUILDUP OF RUBBISH.

1.26.15 EXISTING ITEMS DESIGNATED FOR RELOCATION SHALL BE REMOVED,

CLEANED, CHECKED & REINSTALLED AS INDICATED ON PLANS. REPORT

DEFICIENCIES TO THE CONSULTANT.

1.26.16 AT THE OWNER'S DISCRETION, EXISTING ITEMS DESIGNATED FOR REMOVAL

SHALL BE REMOVED & STORED IN THE OWNER'S STORAGE FACILITIES OR REMOVED

FROM THE OWNER'S PREMISES & DISPOSED PROPERLY BY THE CONTRACTOR. DO

NOT BURN OR BURY MATERIALS ON SITE. REMOVE MATERIALS AS WORK

PROGRESSES. REMOVE TEMPORARY WORK. UPON COMPLETION, LEAVE AREAS IN

CLEAN CONDITION.

2.0 PRODUCTS

2.1 CONDENSATE DRAIN PIPES SHALL BE COPPER TUBE TYPE DWV TO ASTM B306.

FITTINGS SHALL BE WROUGHT COPPER TO CSA B125 SOLDERED JOINTS AND CAST

BRASS TO CSA B125. SOLDER SHALL BE TIN-LEAD 50:50 TO ASTM B32 TYPE 50A.

2.2 HANGERS & SUPPORTS - HANGERS SHALL BE IN ACCORDANCE WITH ANSI B31.1.

HORIZONTAL PIPE HANGERS SHALL BE CLEVIS TYPE CARBON STEEL WITH BLACK

FINISH. FINISH SHALL BE COPPER OR PLASTIC FOR DIRECT SUPPORT COPPER TUBE

OR PIPE. RODS SHALL BE BLACK CARBON STEEL THREADED RODS WITH LOCK NUTS,

AND PROTECTION SADDLES (FOR INSULATED PIPES).

2.3 INSULATION SHALL BE FIBERGLASS, NON-COMBUSTIBLE WITH VAPOR BARRIER

JACKET AND FIRE RETARDANT ADHESIVE. FLAME SPREAD AND SMOKE DEVELOPED

RATINGS SHALL NOT EXCEED 25/50 BASED ON THE STANDARDS OF FIRE HAZARD

CLASSIFICATION FOR BUILDING MATERIALS.

2.4 PIPE INSULATION FOR CONDENSATE LINES SHALL BE 1” THICK RIGID FIBER SLEEVE

WITH FACTORY APPLIED ALL SERVICE VAPOR BARRIER JACKET AND SELF ADHESIVE

TAPE.

2.5 PIPE INSULATION FOR REFRIGERATION SYSTEMS SHALL BE FLEXIBLE

ELASTOMERIC, CLOSED-CELL, SPONGE- OR EXPANDED-RUBBER MATERIALS,

COMPLYING WITH ASTM C 534, TYPE I, 2 INCHES THICK, INDOORS AND OUTDOORS.

ACCEPTABLE PRODUCT: ARMACELL LLC; AP ARMAFLEX.

2.6 VALVES, FITTINGS & FLANGE INSULATION SHALL BE MOLDED AND FABRICATED

INSULATION SEGMENTS OF A THICKNESS EQUAL TO THAT OF THE PIPE.

2.7 INSULATION:

2.7.1INSULATION SHALL BE PROVIDED PER ASHRAE 90.1 - 2010 & AS SPECIFIED

HEREIN. FIRE AND SMOKE RATING IN ACCORDANCE WITH CAN/ULC-S102, MAXIMUM

FLAME SPREAD / SMOKE DEVELOPED RATING: 25/50.

2.7.2 INSULATION: MINERAL FIBRE SPECIFIED FOR GLASS FIBRE, ROCK WOOL, SLAG

WOOL, THERMAL CONDUCTIVITY ("K" FACTOR) < SPECIFIED VALUES AT 24 DEGREES C

MEAN TEMPERATURE WHEN TESTED IN ACCORDANCE WITH ASTM C335.

2.7.3 PIPE INSULATION: APPLY INSULATION TO MECHANICAL EQUIPMENT & SYSTEMS.

2.7.3.1 RIGID MOULDED MINERAL FIBRE WITH FACTORY APPLIED VAPOUR RETARDER

JACKET, MINERAL FIBRE, JACKET, MAXIMUM "K" FACTOR TO ASTM C547 CAN/ULC-S702.

2.7.3.2 MINERAL FIBRE BLANKET FACED WITH FACTORY APPLIED VAPOUR RETARDER

JACKET MINERAL FIBRE ASTM C547, JACKET, MAXIMUM "K" FACTOR TO ASTM C547

CAN/ULC-S702.

2.7.3.3 FLEXIBLE UNICELLULAR TUBULAR ELASTOMER WITH VAPOUR RETARDER

JACKET, CERTIFIED BY MANUFACTURER: FREE OF POTENTIAL STRESS CORROSION

CRACKING CORRODANTS.

2.7.4 DUCT INSULATION:

2.7.4.1 RIGID MINERAL FIBRE BOARD TO ASTM C612, WITH FACTORY APPLIED VAPOUR

RETARDER JACKET TO CGSB 51-GP-52MA.

2.7.4.2 MINERAL FIBRE BLANKET TO ASTM C553 FACED WITH FACTORY APPLIED

VAPOUR RETARDER JACKET TO CGSB 51-GP-52MA, MINERAL FIBRE: TO ASTM C553,

JACKET: TO CGSB 51-GP-52MA, MAXIMUM "K" FACTOR: TO ASTM C553.

2.7.4.3 TAPE: SELF-ADHESIVE, ALUMINUM, PLAIN REINFORCED, 75 50MM WIDE

MINIMUM.

2.7.4.CONTACT ADHESIVE: QUICK-SETTING, MAXIMUM VOC LIMIT 250 50 200G/L TO

SCAQMD RULE 1168 GSES GS-36.

2.8 EQUIPMENT INSULATION:

2.8.1 RIGID MOULDED MINERAL FIBRE WITH FACTORY APPLIED VAPOUR RETARDER

JACKET. MINERAL FIBRE: ASTM C547. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K"

FACTOR: ASTM C547.

2.8.2 RIGID MINERAL FIBRE BOARD FACED WITH FACTORY APPLIED VAPOUR

RETARDER JACKET. MINERAL FIBRE: ASTM C612. JACKET: TO CGSB 51-GP-52MA.

MAXIMUM "K" FACTOR: ASTM C612.

2.8.3 MINERAL FIBRE BLANKET FACED WITH FACTORY APPLIED VAPOUR RETARDER

JACKET. MINERAL FIBRE: ASTM C553. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K"

FACTOR: ASTM C553.

2.8.4 FLEXIBLE UNICELLULAR TUBULAR ELASTOMER. INSULATION: WITH VAPOUR

RETARDER JACKET. JACKET: TO CGSB 51-GP-52MA. MAXIMUM "K" FACTOR.

CERTIFIED BY MANUFACTURER FREE OF POTENTIAL STRESS CORROSION CRACKING

CORRODENTS.

3.0 EXECUTION

3.1 PROVIDE DRAIN PIPES FROM EQUIPMENT AND/OR FIXTURES TO FLOOR DRAINS AS

REQUIRED.

3.2 ALL EQUIPMENT CONNECTIONS SHALL HAVE ISOLATION VALVES AND UNIONS OR

FLANGED CONNECTIONS.

3.3 VALVE SIZES SHALL BE THE SAME LINE SIZE UNLESS NOTED OTHERWISE.

PROVIDE ISOLATING VALVES IN EACH BRANCH FROM THE MAIN LINE AND WHERE

SHOWN. PROVIDE ISOLATING VALVES FOR ALL EQUIPMENT.

3.4 PROVIDE SHOCK ABSORBERS UPSTREAM OF ALL SOLENOID VALVES, FLUSH

VALVES AND/OR OTHER QUICK CLOSING VALVES.

3.5 PROVIDE VACUUM BREAKERS AND BACKFLOW PREVENTERS WHERE REQUIRED BY

CODE.

3.6 ALL PIPE, FITTINGS, FIXTURES AND EQUIPMENT SHALL BE RIGIDLY SUPPORTED.

ALL FASTENINGS TO BUILDING STRUCTURE SHALL BE FIRMLY MADE WITHOUT

DAMAGE TO BUILDING STRUCTURE.

3.7 PIPES SHALL BE CONCEALED IN WALLS, CEILINGS, CHASES, PIPE SHAFTS, ETC.

EXCEPT IN MECHANICAL ROOMS, SERVICE ROOMS AND AS INDICATED OTHERWISE.

3.8 PROVIDE DIELECTRIC UNIONS BETWEEN PIPES OF DISSIMILAR MATERIAL.

3.9 PROVIDE CHROME PLATED ESCUTCHEONS AT ALL POINTS WHERE PIPES PASS

THROUGH FINISHED WALLS, CEILINGS OR FLOORS.

3.10 SUPPORT CAST IRON PIPES AT 1.5 M MAXIMUM INTERVALS; COPPER PIPES AT 2.4

M MAXIMUM INTERVALS; STEEL PIPE AT 3 M MAXIMUM INTERVALS.

SECTION 15200 - FIRE PROTECTION

1.0 GENERAL

1.01 SEE SECTION 15000 ABOVE.

2.0 PRODUCTS

2.1 ALL FIRE PROTECTION PRODUCTS, COMPONENTS, PARTS, ASSEMBLIES,

ACCESSORIES, ETC. SHALL BE SUITABLE FOR THE INTENDED APPLICATION, MEETING

APPLICABLE CODES & STANDARDS INDICATED, SHALL BE APPROVED AND BEAR THE

ULC, UL, FM LISTING / LABEL.

2.2 FIRE EXTINGUISHERS:

2.2.1 MULTI-PURPOSE DRY CHEMICAL: MULTI-PURPOSE (ABC) TYPE, DRY CHEMICAL,

SIZE:10 LB. (4.54 KG), RATING: MINIMUM 6A:80BC, NATIONAL FIRE EQUIPMENT

ABC-100WWD.

2.2.2 CARBON DIOXIDE CO2: CARBON DIOXIDE CO2 (BC), SIZE: 10 LB. (4.54 KG),

RATING:MINIMUM 10B:C, BRACKET: VB-2 (20976) NATIONAL FIRE EQUIPMENT BADGER

10 BV-C (24208).

2.3 SPRINKLER PIPING:

2.3.1 STEEL PIPE: ASTM A53; JOINED WITH THREADED FITTINGS OR CUT GROOVE PIPE

AND FITTINGS: SCHEDULE 40 FOR SIZES 6" (150MM) DIAMETER AND SMALLER,

SCHEDULE 30 FOR SIZES 8" (200MM) DIAMETER AND LARGER.

2.3.2 STEEL FITTINGS: ASME B16.9, WROUGHT STEEL, BUTTWELDED; CAST IRON

FITTINGS: ASME B16.1, FLANGES AND FLANGED FITTINGS; MALLEABLE IRON FITTINGS:

ASME B16.3, THREADED FITTINGS.

2.3.3 MECHANICAL GROOVED COUPLINGS: MALLEABLE IRON HOUSING CLAMPS TO

ENGAGE AND LOCK, "C" SHAPED ELASTOMERIC SEALING GASKET, STEEL BOLTS,

NUTS, AND WASHERS; GALVANIZED FOR GALVANIZED PIPE.

2.3.4 MECHANICAL FORMED FITTINGS: CARBON STEEL HOUSING WITH INTEGRAL PIPE

STOP AND O-RING POCKED AND O-RING, UNIFORMLY COMPRESSED INTO PERMANENT

MECHANICAL ENGAGEMENT ONTO PIPE.

2.4 SPRINKLERS:

2.4.1 SUSPENDED CEILING: SEMI-RECESSED PENDANT TYPE WITH MATCHING PUSH

ON ESCUTCHEON PLATE, ULC LISTED. SPRINKLER & ESCUTCHEON PLATE FINISH:

(COLOR SELECTION BY ARCHITECT) CHROME PLATED. FUSIBLE LINK: GLASS BULB

TYPE TEMPERATURE RATED FOR SPECIFIC AREA HAZARD.

2.4.2 EXPOSED AREA TYPE: STANDARD UPRIGHT TYPE WITH GUARD, ULC LISTED.

FINISH: BRASS.FUSIBLE LINK: GLASS BULB TYPE TEMPERATURE RATED FOR SPECIFIC

AREA HAZARD.

2.4.4 GUARDS: FINISH TO MATCH SPRINKLER FINISH.

2.4.5 SPRINKLERS, EXCUTHEONS, COVER, ACCESSORIES, FINISH, ETC. TO MATCH.

2.4.6 PROVIDE SPRINKLERS PER ABOVE UNLESS NOTED OTHERWISE. COORDINATE

WITH ARCHITECTURAL DOCUMENTS.

3.0 EXECUTION

3.1 FURNISH AND INSTALL FIRE EXTINGUISHERS & AUTOMATIC WET SPRINKLERS

THROUGHOUT ALL AREAS OF THE BUILDING AS INDICATED UNLESS SPECIFICALLY

EXEMPTED BY APPLICABLE CODES & STANDARDS.

3.2 FIRE PROTECTION SYSTEM SHALL BE DESIGNED & INSTALLED IN ACCORDANCE

WITH APPLICABLE CODES & STANDARDS.

3.3 REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING CODE DETAILS –

CONSTRUCTION TYPE, CONSTRUCTION MATERIALS, AREAS, ELEVATIONS, SPRINKLER

& STANDPIPE REQUIREMENTS, ETC.

3.4 PERFORM FIRE HYDRANT FLOW TEST WITNESSED AUTHORITIES. FLOW TEST

INFORMATION SHALL BE USED FOR SPRINKLER DESIGN AND HYDRAULIC

CALCULATIONS. SUBMIT TO CONSULTANT AND OWNER FOR REVIEW AND COMMENT.

3.5 PREPARE SUBMITTAL DOUMENTS (PLANS, SPECIFICATIONS, LAYOUTS, DETAILS,

DIAGRAMS, CALCULATIONS, EQUIPMENT INFORMATION/CUTSHEETS, ETC.)

CONFORMING TO APPLICABLE CODES & STANDARDS INDICATED ABOVE.

CALCULATIONS, EQUIPMENT SELECTIONS, SIZING, ETC. SHALL BE BASED ON ACTUAL

EQUIPMENT / COMPONENTS USED, LAYOUT / INSTALLATION, FLOW TEST RESULTS,

MEASUREMENT LOCATIONS, DESIGN AREAS, DESIGN DENSITIES, & HOSE

ALLOWANCES INDICATED. DOCUMENTS SHALL INDICATE THE CODES, STANDARDS,

EDITIONS, ETC. USED IN THE PREPARATIONS OF THE DOCUMENTS AND COMPLIANCE

WITH THOSE CODES & STANDARDS. SUBMITTAL DOCUMENTS SHALL BE SIGNED &

STAMPED / SEALED BY FIRE PROTECTION ENGINEER OF RECORD PRIOR TO

SUBMISSION. CONTRACTOR & HIS ENGINEER OF RECORD SHALL BE RESPONSIBLE

FOR THE COMPLETE & FULLY FUNCTIONAL FIRE PROTECTION SYSTEM DESIGN,

ENGINEERING & INSTALLATION.

3.6 PROVIDE SUBMITTAL DOCUMENTS TO CONSULTANT / ENGINEER AFTER SUBMITTAL

DOCUMENTS HAVE BEEN SUBMITTED, REVIEWED, CORRECTED, UPDATED AND

APPROVED BY AUTHORITIES HAVING JURISDICTION.

3.7 SPRINKLER MINIMUM AREA & DESIGN WATER FLOW DENSITY SHALL BE AS

FOLLOWS:

LIGHT HAZARD: 1500 SQFT 0.1 GPM/SQFT

ORDINARY GROUP 11500 SQFT 0.15 GPM/SQFT

ORDINARY GROUP 21500 SQFT 0.2 GPM/SQFT

EXTRA HAZARD GROUP 12500 SQFT 0.3 GPM/SQFT

EXTRA HAZARD GROUP 22500 SQFT 0.4 GPM/SQFT

3.8 HOSE STREAM ALLOWANCE & WATER SUPPLY DURATION SHALL BE AS FOLLOWS:

LIGHT HAZARD 100 GPM 30 MINUTES

ORDINARY HAZARD 250 GPM 60-90 MINUTES

EXTRA HAZARD 500 GPM 90-120 MINUTES

3.9 PIPING INSTALLATION

3.10 ALL SPRINKLERS SHALL HAVE DEFLECTORS INSTALLED BELOW ROOF AND/OR

CEILING ASSEMBLIES BETWEEN 1" TO 22" MAXIMUM DEPENDING ON THE TYPE OF

ROOF AND/OR CEILING CONSTRUCTION CLASSIFICATION.

3.11 INSTALL AUTOMATIC SPRINKLERS BELOW DUCTWORK, HORIZONTAL OVERHEAD

DOORS AND OTHER OBSTRUCTIONS 48" IN WIDTH AND LARGER. THIS INCLUDES

MULTIPLE DUCTS, PIPES, CONDUITS, ETC. LOCATED SUCH THAT TOGETHER A 48"

OBSTRUCTION IS FORMED. PROVIDE SPRINKLERS ABOVE AND BELOW THE

HORIZONTAL DOORS UNLESS NOTED OTHERWISE.

3.12 LOCATE SPRINKLERS AT CENTER OF ACOUSTIC TILE / GRID CEILINGS WHENEVER

POSSIBLE. SPRINKLER HEAD LOCATIONS MAY CHANGE FOR COORDINATION WITH

EXISTING CONDITIONS & OTHER TRADES.

3.13 PIPES 1" TO 4" SHALL BE SUPPORTED WITH 3/8" ALL THREAD ROD AND 3/8"

HANGER ASSEMBLIES. 5" TO 6" PIPE TO BE SUPPORTED WITH 1/2" ALL THREAD ROD

AND 1/2" HANGER ASSEMBLIES.

3.14 BEFORE ANY SPRINKLER PIPING IS CONCEALED, NOTIFY THE FIRE DEPARTMENT

FOR INSPECTION 48 HOURS IN ADVANCE.

3.15 CONDUCT PIPING SYSTEM FLUSHING, HYDROSTATIC SYSTEM TEST & MAIN DRAIN

TEST. HYDROSTATIC TEST OVERHEAD PIPING @ 200 PSI FOR 2 HOURS. NOTIFY FIRE

DEPARTMENT 48 HOURS IN ADVANCE. CORRECT DEFFICIENCIES ENCOUNTERED

UNTIL ALL SYSTEM TESTS ARE PASSED. PERFORM ALL TESTING IN THE PRESENCE OF

THE AUTHORITIES. SUBMIT ALL TEST RESULTS TO THE CONSULTANT. SUBMIT

INSPECTOR'S TEST REPORT ON COMPLETION.

3.16 PROVIDE A CERTIFICATE STATING THAT THE FIRE PROTECTION SYSTEM WAS

INSTALLED IN FULL COMPLIANCE WITH APPLICABLE CODES & STANDARDS INDICATED

ABOVE AND THAT ALL APPLICABLE TESTS HAVE PERFORMED AND PASSED AT THE

CLOSURE OF THE PROJECT.

3.17 SUBMIT AS-BUILT DRAWINGS AND FINAL HYDRAULIC CALCULATIONS

REPRESENTING THE SYSTEM AS INSTALLED TO THE FIRE DEPARTMENT FOR FINAL

REVIEW AND ACCEPTANCE.

3.18 PROVIDE CONTRACTOR'S MATERIAL AND TEST CERTIFICATES WITH O & M

MANUALS.

SECTION 15400 - PLUMBING

1.0 GENERAL

1.1 SEE SECTION 15000 ABOVE.

2.0 PRODUCTS

2.1 PLUMBING FIXTURES:

2.1.1 ALL PLUMBING FIXTURES & EQUIPMENT SHALL MEET THE LATEST SAFETY &

WATER EFFICIENCY REQUIREMENTS OF THE APPLICABLE CODES & STANDARDS.

2.1.2 DF1: WATER FOUNTAIN: BI-LEVEL TYPE, SURFACE MOUNTED, STAINLESS STEEL

CONSTRUCTION, 115 V/ 60HZ , ADA COMPLIANT WITH A TOUCHLESS ACTIVATED

WATER FILLING STATION, GREEN TICKER DISPLAYING COUNT OF PLASTIC BOTTLES

SAVED, INTEGRATED WATER COOLING SYSTEM, ANTI-MICROBIAL FLEXI-GUARD

BUBBLER. ACCEPTABLE PRODUCT PRODUCT: ELKAY EZH2O BOTTLE FILLING STATION

EZSTL8WS(S)K OR APPROVED EQUAL.

2.1.3 S1: KITCHEN SINK: STAINLESS STEEL, TYPE 304 (18/10), NO. 4 SATIN FINISHED,

SINGLE COMPARTMENT, SELF-RIMMING DROP SINK (16.75” L X16.75” W X 8“ D) WITH

FAUCET LEDGE, 18 GAUGE (1.2 MM) WITH NO OVERFLOW, UNDERCOAT, 3 ½’’ CUP

STRAINER, 1 ½’’ BRASS TAILPIECE. ACCEPTABLE PRODUCT: FRANKE LBS6808 OR

APPROVED EQUAL. FAUCET: SINGLE HOLE, SINGLE LEVER, CHROME PLATED, 9 ½’’

CENTER TO CENTER INTEGRAL CAST BRASS SPOUT, 1.5 GPM (5.7 L/S) MAX.,

NON-AERATING OUTLET, CERAMIC CARTRIDGE, USER ADJUSTABLE TEMPERATURE

CONTROL MIXER, TEMPERATURE LIMITER, RATED OPERATING PRESSURE: 20-125 PSI,

RATED OPERATING TEMPERATURE: 40-140°F, ADA COMPLIANT. ACCEPTABLE

PRODUCT: CHICAGO FAUCET 430-ABCP OR APPROVED EQUAL. MCGUIRE LFH170BV

FAUCET SUPPLIES, CHROME PLATED FINISH POLISHED BRASS, COMMERCIAL DUTY 1/4

TURN BALL VALVE ANGLE STOPS, 13 MM (1/2") I.D. INLET X 127 MM (5") HORIZONTAL

EXTENSION TUBES, COMBINATION V.P. LOOSE KEY HANDLES, ESCUTCHEON AND

FLEXIBLE COPPER RISERS, 8912CB P-TRAP, CHROME PLATED FINISH, HEAVY CAST

BRASS ADJUSTABLE BODY WITH SLIP NUT, 38 MM (1-1/2") SIZE, WITH CLEANOUT, BOX

FLANGE AND SEAMLESS TUBULAR WALL BEND.

2.2 PLUMBING EQUIPMENT:

2.2.1 WATER HAMMER ARRESTOR: STAINLESS STEEL OR COPPER CONSTRUCTION,

PISTON OR BELLOW STYPE: TO PDI-WH201.

2.2.2 BACKFLOW PREVENTER: TO CSA-B64 SERIES, APPLICATION DOUBLE CHECK

VALVE ASSEMBLY AS INDICATED, REDUCED PRESSURE PRINCIPLE TYPE BACK FLOW

PREVENTER WITH INTERMEDIATE VACUUM BREAKER ATMOSPHERIC VENT.

2.2.3 STRAINERS: 860KPA, Y TYPE WITH 20 MESH, MONEL, BRONZE OR STAINLESS

STEEL REMOVABLE SCREEN. NPS 2 AND UNDER, BRONZE BODY, SCREWED ENDS,

WITH BRASS CAP. NPS 2 1/2 AND OVER, CAST IRON BODY, FLANGED ENDS, WITH

BOLTED CAP.

2.2.4 WH1 POINT OF USE ELECTRIC MINI STORAGE TANK WATER HEATER: COMPACT

DESIGN ETL TESTED TO UL 174 & NSF 372 WITH ENAMELED GLASS LINED SINGLE WELD

TANK, WATER CONNECTIONS, T&P VALVE, STATUS INDICATOR LIGHT, ADJUSTABLE

THERMOSTAT (50°-140°F), 6-YEAR WARRANTY, FLOOR / WALL MOUNT / BRACKET,

STANDARD 120 VOLT POWER CORD & PLUG. ACCEPTABLE PRODUCT: RHEEM

MINI-TANK PROE OR APPROVED EQUAL.

2021-08-0921-023

Page 3: M1 - LEGENDS M1

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023 M3

MECHANICAL SPECIFICATIONS

1/8" - 1'-0"

2.3 PLUMBING PIPING

2.3.1 SANITARY DRAINAGE PIPING – BURIED: 2" (50 MM) AND SMALLER DIAMETER,

HARD TEMPER COPPER PIPE, TYPE L; 3" (75 MM) AND LARGER DIAMETER, CAST IRON

SOIL PIPE, NO-HUB MECHANICAL JOINT WITH NEOPRENE GASKETS AND STAINLESS

STEEL PIPE CLAMPS.

2.3.2 SANITARY DRAINAGE PIPING - ABOVE GRADE: 2" (50 MM) AND SMALLER

DIAMETER, HARD TEMPER COPPER TUBE, TYPE DWV, SOLDERED, WITH WROUGHT

COPPER OR COPPER DRAINAGE FITTINGS OR CAST BRASS DRAINAGE FITTINGS; 3" (75

MM) AND LARGER DIAMETER, CAST IRON SOIL PIPE, NO-HUB MECHANICAL JOINT WITH

NEOPRENE GASKETS AND STAINLESS STEEL PIPE CLAMPS WITH CAST IRON

DRAINAGE FITTINGS.

2.3.3 VENT PIPING – BURIED: 2" (50 MM) AND SMALLER DIAMETER, HARD TEMPER

COPPER PIPE, TYPE L, TO ASTM B42-87, WITH WROUGHT COPPER OR COPPER ALLOY

SOLDER JOINT TO ANSI B16.29-73 OR CAST BRASS SOLDER JOINT TO CSA B158.1-1976.

2.3.4 VENT PIPING - ABOVE GRADE: 2" (50 MM) AND SMALLER DIAMETER, HARD

TEMPER COPPER TUBE, TYPE DWV 3" (75 MM) AND LARGER DIAMETER, CAST IRON

SOIL PIPE, NO HUB MECHANICAL JOINT WITH CAST IRON DRAINAGE FITTINGS

2.3.5 STORM - HUBLESS CAST-IRON PIPE AND FITTINGS TO ASTM A 888 OR CISPI 301.

SHIELDED COUPLINGS TO ASTM C 1277 METAL SHIELD OR HOUSING,

CORROSION-RESISTANT FASTENERS, RUBBER SLEEVE, CENTER PIPE STOP.

2.3.6 WATER PIPING - ABOVE GRADE: COPPER TUBING 3" (75MM) AND SMALLER TYPE L,

HARD DRAWN FITTINGS: CAST COPPER ALLOY OR WROUGHT COPPER AND BRONZE.

2.3.7 ISOLATING VALVES: UP TO AND INCLUDING 2" (50 MM): MANUFACTURER: KITZ

69AMLL, CONSTRUCTION: MSS SP-110, 1034 KPA (150 PSIG) 600 WOG, FORGED BRASS,

TWO PIECE BODY, STAINLESS STEEL BALL AND STEM, FULL PORT, VIRGIN PTFE SEATS

AND STEM PACKING OR DOUBLE "O" RING, BLOW-OUT PROOF STEM, LEVER HANDLE,

STEM EXTENSIONS FOR INSULATED PIPING, SOLDER ENDS.

SECTION 15600 – HEATING, VENTILATING & AIR CONDITIONING

1.0 GENERAL

1.1 SEE SECTION 15000 ABOVE.

2.0 PRODUCTS

2.1 DUCTWORK & ACCESSORIES:

2.1.1 DUCT LEAKAGE: PER SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL.

2.1.2 SEAL CLASSIFICATION: 125 PA MAX: UNSEALED, 500 PA MAX: SMACNA SEAL

CLASS C. CLASS C: TRANSVERSE JOINTS AND CONNECTIONS MADE AIR TIGHT WITH

TAPE SEALANT GASKETS OR COMBINATION THEREOF. LONGITUDINAL SEAMS

UNSEALED.

2.1.3 SEALANT: ADHESIVES AND SEALANTS: VOC LIMIT 30 70 250G/L MAXIMUM TO

SCAQMD RULE 1168 GS-36. SEALANT: OIL RESISTANT, WATER BORNE, POLYMER TYPE

FLAME RESISTANT CLEAR DUCT SEALANT. TEMPERATURE RANGE OF MINUS

30DEGREES C TO PLUS 93DEGREES C.

2.1.4 FITTINGS: FABRICATION TO SMACNA.

2.1.4.1 RADIUSED ELBOWS: RECTANGULAR: STANDARD RADIUS SHORT RADIUS WITH

SINGLE THICKNESS TURNING VANES, CENTRELINE RADIUS: 1.5 TIMES WIDTH OF

DUCT. ROUND: SMOOTH RADIUS FIVE PIECE, CENTRELINE RADIUS: 1.5TIMES

DIAMETER.

2.1.4.2 MITRED ELBOWS, RECTANGULAR: TO 400MM: WITH SINGLE DOUBLE

THICKNESS TURNING VANES. OVER 400MM: WITH DOUBLE THICKNESS TURNING

VANES.

2.1.4.3 BRANCHES: RECTANGULAR MAIN AND BRANCH: WITH 45 DEGREES ENTRY ON

BRANCH RADIUS ON BRANCH 1.5 TIMES WIDTH OF DUCT. ROUND MAIN AND BRANCH:

ENTER MAIN DUCT AT 45 DEGREES WITH CONICAL CONNECTION. PROVIDE VOLUME

CONTROL DAMPER IN BRANCH DUCT NEAR CONNECTION TO MAIN DUCT. MAIN DUCT

BRANCHES: WITH SPLITTER DAMPER.

2.1.4.4 TRANSITIONS: DIVERGING: 20DEGREES MAXIMUM INCLUDED ANGLE.

CONVERGING: 30DEGREES MAXIMUM INCLUDED ANGLE.

2.1.4.5 OFFSETS: AS INDICATED SHORT FULL RADIUSED ELBOWS. OBSTRUCTION

DEFLECTORS: MAINTAIN FULL CROSS-SECTIONAL AREA. MAXIMUM INCLUDED

ANGLES: AS FOR TRANSITIONS.

2.2 FIRE STOPPING: RETAINING ANGLES AROUND DUCT, ON BOTH SIDES OF FIRE

SEPARATION. FIRE STOPPING MATERIAL AND INSTALLATION MUST NOT DISTORT

DUCT.

2.3 HANGERS AND SUPPORTS: STRAP HANGERS: OF SAME MATERIAL AS DUCT BUT

NEXT SHEET METAL THICKNESS HEAVIER THAN DUCT. MAXIMUM SIZE DUCT

SUPPORTED BY STRAP HANGER: 500 MM. HANGER CONFIGURATION: TO SMACNA &

ASHRAE. HANGERS: GALVANIZED BLACK STEEL ANGLE WITH BLACK GALVANIZED

STEEL RODS TO ASHRAE & SMACNA. UPPER HANGER ATTACHMENTS: FOR

CONCRETE: MANUFACTURED CONCRETE INSERTS. FOR STEEL JOIST:

MANUFACTURED JOIST CLAMP STEEL PLATE WASHER. FOR STEEL BEAMS:

MANUFACTURED BEAM CLAMPS.

2.4 DUCT MATERIAL:

2.4.1 GALVANIZED STEEL: LOCK FORMING QUALITY: TO ASTM A653/A653M, Z90ZINC

COATING. THICKNESS, FABRICATION AND REINFORCEMENT: TO SMACNA ASHRAE.

JOINTS: TO SMACNA PROPRIETARY MANUFACTURED DUCT JOINT ASHRAE.

PROPRIETARY MANUFACTURED FLANGED DUCT JOINT TO BE CONSIDERED TO BE A

CLASS A SEAL.

2.4.2 DUCTS AND FITTINGS SHALL BE FABRICATED FROM GALVANIZED SHEET STEEL,

LOCK FORMING QUALITY TO ASTM A525 WITH Z275 ZINC COATING. DUCT

CONSTRUCTION SHALL BE PER SMACNA FOR 2 INCHES W.C. PRESSURE CLASS WITH

MAXIMUM LEAKAGE RATE OF 5%. DUCT CONNECTIONS AND TRANSVERSE JOINTS

SHALL BE SEALED WITH SEALANT AND TAPE.

2.4.3 DUCT MATERIAL THICKNESS SHALL BE AS FOLLOWS:

MAXIMUM SIZE OR DIAMETERTHICKNESS

UP TO 300 MM 26 U.S. STANDARD GAUGE

301 TO 750 MM 24 U.S. STANDARD GAUGE

2.4.4 FLEXIBLE DUCT: INSULATED, UL-181/ETL CLASS I AIR DUCT, NFPA 90A COMPLIANT,

LOW TO MEDIUM PRESSURE APPLICATION, ALUMINUM FOIL, FIBREGLASS AND

ALUMINIZED POLYESTER LAYERS, CORROSION RESISTANT GALVANIZED STEEL HELIX,

FIRE RETARDANT REINFORCED VAPOUR BARRIER, FIBERGLASS INSULATION BLANKET,

FACTORY WRAPPED, 5 FEET MAXIMUM LENGTH. FLEXMASTER 5B OR APPROVED

EQUAL.

2.4.5 FLEXIBLE CONNECTIONS SHALL BE FIRE RESISTANT, SELF EXTINGUISHING,

NEOPRENE COATED GLASS FABRIC WITH GALVANIZED SHEET METAL FRAME.

2.4.6 VOLUME DAMPERS (SINGLE BLADE UP TO 12 INCHES DEEP) SHALL BE SAME

MATERIAL AS DUCT, NEXT GAUGE HEAVIER THAN DUCT, V GROVE STIFFENED,

LOCKING QUADRANT, SHAFT EXTENSION, BRONZE END BEARINGS, CHANNEL FRAME

AND ANGLE STOP. DAMPERS FOR DUCTS GREATER THAN 12 INCHES DEEP SHALL BE

PARALLEL BLADE, PIN IN BRONZE BUSHING, LOCKING QUADRANT, SHAFT EXTENSION,

ANGLE STOP, CHANNEL FRAME INTERCONNECTED. BLADES UP TO 30 INCHES IN

LENGTH SHALL HAVE A MAXIMUM WIDTH OF 10 INCHES, BLADES LONGER THAN 30

INCHES SHALL HAVE A MAXIMUM WIDTH OF 12 INCHES. KERR HUNT OR APPROVED

EQUAL.

2.4.6 MULTI LEAF CONTROL DAMPERS SHALL BE OPPOSED OR PARALLEL BLADE,

STRUCTURALLY FORMED STEEL, INTERLOCKING BLADES, EXTRUDED VINYL SEALS,

STAINLESS STEEL SPRING SIDE SEALS, STRUCTURALLY FORMED AND WELDED

GALVANIZED STEEL FRAME, PRESSURE FIT SELF LUBRICATED BRONZE BEARINGS,

PLATED STEEL TIE RODS, BRASS PIVOTS, PLATED STEEL BRACKETS AND CONTROL

ROD. JOHNSON CONTROLS, HONEYWELL, OR SIEMENS.

2.4.7 DAMPER MOTORS SHALL BE 2 POSITION OR MODULATING, 24 VAC, SPRING

RETURN, NORMALLY OPEN/CLOSED AS APPLICABLE. JOHNSON CONTROLS, BELIMO,

HONEYWELL, SIEMENS.

2.4.10 FIRE DAMPERS SHALL BE FACTORY FABRICATED GALVANIZED STEEL, CHANNEL

FRAME, CURTAIN TYPE, LOW RESISTANCE TYPE B, INTERLOCKING BLADES, 160

DEGREES F FUSIBLE LINK, UL LISTED AND LABELED FOR 1 ½ HOUR RATING. FUSIBLE

LINKS FOR 105 DEGREES F, 182 DEGREES F OR 285 DEGREES F, SHALL BE PROVIDED

AS INDICATED ON DRAWINGS. RUSKIN, CONTROLLED AIR OR APPROVED EQUAL.

2.4.8 TURNING VANES SHALL BE FACTORY OF SHOP FABRICATED SINGLE THICKNESS

WITH TRAILING EDGE.

2.4.9 ACCESS DOORS SHALL BE SANDWICH CONSTRUCTION OF SAME MATERIAL AS

DUCT, ONE SHEET METAL THICKNESS HEAVIER, MINIMUM 0.0236 INCH THICK WITH

SHEET METAL ANGLE FRAME, 1-1/2 IN. RIGID FIBER GLASS INSULATION, AND

NEOPRENE OR FOAM RUBBER GASKETS.

2.5 DIFFUSERS, GRILLES & REGISTERS

2.5.1 CEILING DIFFUSERS: ADJUSTABLE, SQUARE CONE STEEL CONSTRUCTION, 24

INCHES X 24 INCHES FACE, ROUND INLET, OFF WHITE BAKED ENAMEL FINISH,

MOUNTING TYPE TO MATCH CEILING. FINISH SHALL BE AS SELECTED BY ARCHITECT.

EH PRICE SCDA OR APPROVED EQUAL.

2.5.2 RETURN/EXHAUST GRILLES SHALL BE ½ IN X ½ IN X ½ IN ALUMINUM GRID EGG

CRATE CORE, ALUMINUM BORDER AND FRAME, T BAR LAY IN TYPE, OFF WHITE BAKED

ENAMEL FINISH. SEE DRAWINGS FOR SIZE AND TYPE. E. H. PRICE 80 SERIES OR

APPROVED EQUAL.

2.5.3 TRANSFER GRILLE: HEAVY DUTY EXTRUDED ALUMINUM CONSTRUCTION, LARGE

FREE AREA, COMPLETELY SIGHTPROOF OR LIGHTPROOF CORE, AND RUGGED

MANDREL TUBE CONSTRUCTION OF HEAVY GAUGE EXTRUDED ALUMINUM AS

REQUIRED FOR SEVERE USE APPLICATIONS. FINISH SELECTION BY ARCHITECT.

ACCEPTABLE MANUFACTURER: PRICE MODEL ATG / ATGH SERIES.

2.5.4 HOODED WALL CAP: FOR OUTSIDE WALL APPLICATIONS, STEEL CONSTRUCTION

WITH BLACK ENAMEL FINISH, BUILT-IN BIRDSCREEN, DAMPER, SQUARE OR

RECTANGULAR CONNECTIONS. PERFORMANCE SHALL NOT EXCEED 0.1” STATIC

PRESSURE DROP AT DESIGN FLOW RATE. ACCEPTABLE PRODUCT: GREENHECK

MODEL WC OR APPROVED EQUAL.

2.6 CROSS TALK SILENCER: CONSTRUCTED TO ASHRAE & SMACNA STANDARDS

(PRESSURE & VELOCITY CLASSIFICATION OF THE AIR DISTRIBUTION SYSTEM) WITH 22

GAUGE SOLID STEEL CASING, 26 GAUGE SOLID STEEL INTERNAL NOSES AT IN-LET

AND OUTLET, ¾ INCH DUAL DENSITY ABSORPTIVE FIBERGLASS ACOUSTIC MEDIA

(SHOT-FREE INORGANIC GLASS FI-BER WITH LONG, RESILIENT FIBERS, BONDED WITH

THERMOSETTING RESIN) WITH BUTTON LOCK, PITTSBURGH LOCK, AND WELDS &

COMPLIANCE TO ASTM STANDARD E477, UL 181, ASTM C1071, ASTM E84, NFPA 255 OR

UL 723. ACCEPTA-BLE PRODUCT: EH PRICE XTL, XTZ, XTU OR APPROVED EQUAL.

2.7 TERMINAL UNIT (FAN POWERED): PRESSURE INDEPENDENT UNIT WITH

ZINC-COATED STEEL HOUSING, MECHANICALLY SEALED, LEAK-RESISTANT

CONSTRUCTION, 22 OR 20 GAUGE CONSTRUCTION, 2 IN. COLLAR, 3/4 IN. [19] THICK,

MIN. 1.5 LB DENSITY FIBERGLASS INTERNAL INSULATION, RECIRCULATING FAN,

BOTTOM ACCESS PANEL, ECM MOTORS (60 CYCLE, SINGLE PHASE, 115, 208, 240, 277

VAC LUBRICATED, PERMANENT SPLIT CAPACITOR TYPE), VIBRATION ISOLATORS,

SOLID STATE SPEED CONTROLLER, SCR TO AHRI 880, UL1995, CSA NO. 236, UL 181

AND NFPA-90A. ACCEPTABLE PROD-UCT: PRICE FPC, TITUS, KRUEGER, CARNES.

2.8 FANS

2.8.1 PERFORMANCE REQUIREMENTS: BASED ON TESTS PERFORMED IN

ACCORDANCE WITH ANSI/AMCA STANDARD 210, UNIT TO BEAR AMCA CERTIFIED

RATING SEAL. STATICALLY AND DYNAMICALLY BALANCED. CONSTRUCTED TO

ANSI/AMCA STANDARD 99. SOUND RATINGS: TO ANSI/AMCA STANDARD 301, TESTED

TO ANSI/AMCA STANDARD 300. UNIT SHALL BEAR AMCA CERTIFIED SOUND RATING

SEAL. PANASONIC.

2.8.2 BEARINGS: HEAVY DUTY GREASE LUBRICATED BALL OR ROLLER BEARINGS,

SEALED LIFETIME, BALL, OILITE BEARINGS, SELF ALIGNING TYPE WITH OIL RETAINING,

DUST EXCLUDING SEALS AND A CERTIFIED MINIMUM RATED LIFE OF 80,000

100,000HOURS.

2.8.3 CEILING FANS: CEILING MOUNTED EXHAUST FANS, CENTRIFUGAL DIRECT DRIVE,

FAN HOUSING OF HEAVY-GAUGE GALVANIZED STEEL, LINED WITH 1/2 INCH (13 MM)

ACOUSTICAL INSULATION, OUTLET DUCT COLLAR, BACKDRAFT DAMPER, HORIZONTAL

OR VERTICAL DISCHARGE, DESIGNER GRILLE, MOTOR DISCONNECT PLUG-IN TYPE,

MOTOR VIBRATION ISOLATORS, FAN WHEEL FORWARD-CURVED CENTRIFUGAL,

DYNAMICALLY BALANCED, AMCA CERTIFIED RATINGS SOUND AND AIR PERFORMANCE

SEAL, UL/CUL LISTED. PERFORMANCE: 155 CFM, 0.375" ESP, 1400 RPM, 115VAC, 54.2

WATTS. ACCEPTABLE MANUFACTURE: GREENHECK MODELS SP-A190 OR EQUAL

FROM PENN BARRY, PANASONIC, BROAN, NUTONE.

2.9 CONTROLS:

2.9.1 THE CONTRACTOR SHALL PROVIDE A COMPLETE BUILDING DDC CONTROL

SYSTEM TO COMPLY WITH SEQUENCES OF OPERATIONS OUTLINED HEREIN. PROVIDE

SENSORS, RELAYS, CONTROL WIRING, CONTROL POWER WIRING FROM DEDICATED

J-BOX (J-BOX BY E.C.), TRANSFORMERS, ENCLOSURES, MOUNTING HARDWARE, AND

CT'S AS REQUIRED TO MONITOR, ADJUST, AND COMMUNICATE THE SEQUENCES

INDICATED. SUBMIT BAS SCREEN SHOTS OF THE GRAPHICS TO THE CONSULTANT

FOR REVIEW AS PART OF THE COMMISSIONING PROCESS.

2.9.2 PROVIDE A GLOBAL CONTROL SYSTEM THAT CAN COMMUNICATE WITH ALL

EQUIPMENT. THE SYSTEM SHALL BE VIEWABLE AND EDITABLE FROM A COMPUTER

USING INTERNET WEB BROWSER COMMUNICATING EITHER DIRECTLY OR REMOTELY

WITH THE BAS MAIN CONTROL PANEL.

2.9.3 DIRECT DIGITAL CONTROL (DDC) TECHNOLOGY SHALL BE USED TO PROVIDE

THE FUNCTIONS NECESSARY FOR CONTROL OF MECHANICAL SYSTEMS.

2.9.4 THE CONTROL SYSTEM SHALL BE DESIGNED SUCH THAT IN THE EVENT OF A

NETWORK COMMUNICATION FAILURE, OR THE LOSS OF ANY OTHER CONTROLLER,

THE SCHEDULE SYSTEM SHALL CONTINUE TO INDEPENDENTLY OPERATE UNDER

LOCAL CONTROL.

2.9.5 OWNER SHALL PROVIDE WAN/LAN CONNECTION TO THE BUILDING

AUTOMATION SYSTEM.

2.9.6 UNIT LEVEL CONTROLLERS SHALL USE BACNET MSTP PROTOCOL.

CONTROLLERS SHALL BE BACNET BTL CERTIFIED.

2.9.7 THE SYSTEM MUST BE PROVIDED, INSTALLED, WIRED AND PROGRAM BY THE

MANUFACTURER'S LOCAL FACTORY OFFICE OR APPROVED CONTRACTOR.

2.9.8 PROVIDE ONE YEAR PARTS AND LABOR WARRANTY OF THE BAS.

2.9.9 PROVIDE PORTABLE UN-INTERRUPTIBLE POWER SUPPLY (APC BACK-UPS

1500VA, OR EQUAL) TO POWER CONTROL SYSTEM IF REQUIRED BY OWNER.

2.9.10 PROVIDE 4 HOURS OF OWNER'S TRAINING AT JOBSITE ON THE BUILDING

AUTOMATION SYSTEM OPERATION.

2.9.11 ALL CONTROL SETPOINTS SHALL BE ADJUSTABLE, INDICATED TEMPERATURE

SETPOINTS SHOULD BE USED FOR ORIGINAL SYSTEM SET-UP. ANY CHANGES IN

SETPOINT SETTINGS REQUIRED FOR INTENDED SYSTEM OPERATION SHALL BE

INDICATED ON AS-BUILT DRAWINGS.

2.9.12 DUCT SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE

ALARM SYSTEM BY ELECTRICAL OR OWNER APPROVED CONTRACTOR. ELECTRICAL

OR APPROVED CONTRACTOR SHALL INSTALL DETECTOR IN DUCT AND WIRE UNIT

FROM FIRE ALARM SYSTEM (DRY CONTACTS) FOR UNIT SHUT-DOWN UPON

ACTIVATION.

2.9.13 LOCATE VERASYS SMART BUILDING CONTROL HUB FOR BAS IN MECHANICAL

ROOM OR IT CLOSET. COORDINATE EXACT LOCATION OF PANELS WITH ALL OTHER

TRADES AND BUILDING OWNER PRIOR TO INSTALLATION. PROVIDE PORTABLE UPS IF

REQUIRED BY OWNER.

2.9.14 THE SEQUENCE OF OPERATION DOES NOT COMPLETELY DEFINE THE SCOPE

OF WORK FOR CONTROLS. THE CONTROLS SUBMITTAL SHALL FULLY DEVELOP THE

SEQUENCE OF OPERATIONS FOR ALL SYSTEMS IDENTIFIED AND SHALL PRESENT ALL

SETPOINTS, CONTROL PARAMETERS, AND ALARM POINTS. INCORPORATE STANDARD

FEATURES SUCH AS MINIMUM RUN TIME DELAYS AND DEAD BANDS FROM SETPOINTS

TO PREVENT EQUIPMENT FROM SHORT CYCLING WHEN NEAR SETPOINTS. THESE

BASIC FEATURES THAT ARE NECESSARY AND ARE PART OF A COMPLETE CONTROLS

INSTALLATION SHALL BE INCLUDED IN THE SCOPE OF SERVICES FOR DELIVERABLES

AT NO ADDITIONAL COSTS TO THE OWNER.

2.9.15 ALL CONTROL AND POWER WIRING SHALL BE PLENUM-RATED WITH A MINIMUM

FIRE SPREAD RATING OF 25 AND A MINIMUM SMOKE DEVELOPED RATING OF 50 PER

ASTM E84. ANY EXPOSED WIRING SHALL BE MOUNTED IN ELECTRO-MAGNETIC TUBING

(EMT) OR SUSPENDED BY UL APPROVED DATA CABLE HOOKS.

2.9.16 MOTORIZED DAMPER POSITIONING FOR OUTSIDE AIR, EXHAUST, AND RETURN

AIR SHALL BE COMPLETELY PROGRAMMABLE WITH POSITION DETERMINED DURING

TEST AND BALANCE WITH SETTINGS CONTAINED WITHIN THE BAS SYSTEM.

2.9.17 THE SYSTEM SHALL HAVE THE FOLLOWING FUNCTIONS: TIME OF DAY

SCHEDULING INCLUDING OPTIMAL START/STOP, HOLIDAY AND EXCEPTION

SCHEDULES, DATA LOGGING AND TRENDING, USER SECURITY LEVEL ASSIGMENT,

SYSTEM AND ALARMS REPORTS, ALARM REPORTING VIA TEXT MESSAGE OR EMAIL,

FLOOR PLANS, SYSTEM, EQUIPMENT GRAPHICS IN A STATIC DISPLAY FORMAT, ALARM

E-MAIL ROUTING, GLOBAL NAVIGATION ICONS TO MANAGE ALARMS AND USER

CREDENTIALS, ALL SETPOINTS, ALARMS, TRENDING, AND MONITORING FUNCTIONS

SHALL BE AVAILABLE OVER WEBPAGE.

2.9.18 CONTROLS SHALL BE PROVIDED BY JOHNSON CONTROLS. ALERTON, CARRIER,

HONEYWELL, SIEMENS, OR TRANE SHALL BE CONSIDERED AS ALTERNATES.

REGARDLESS OF VENDOR, DDC SYSTEM SHALL BE OPEN PROTOCOL, WITH ALL

LICENSES INCLUDED. WHERE ALTERNATES ARE PROPOSED, CONTRACT PRICE

REDUCTIONS SHALL BE INDICATED IN TENDER / BID.

2.10 ENERGY RECOVERY VENTILATOR: BOLT ON ACCESSORY VENTILATOR FOR EXIST.

RTU CONSTRUCTED OF G90 GALVANIZED MATERIAL WITH POWDERED ENAMEL PAINT

FINISH, INSULATED CABINET PANELS, POWER OPENINGS, TEST PORTS, MULTIPLE

SPEED INDIVIDUALLY CONTROLLED CENTRIFUGAL INTAKE & EXHAUST AIR BLOWERS,

SILICA GEL DESICCANT ENTHALPY ENERGY RECOVERY WHEEL (ARI 1060 & UL LISTED),

BALANCING DAMPERS, BAROMETRIC RELIEF, SUPPORT LEGS, FILTERS & SINGLE

POINT POWER CONNECTION, 2200 - 2800 CFM, 208/230-3-60 ELECTRICAL, DUAL POINT

POWER. OPTIONS INCLUDED: EQUIPMENT SUPPORT, ROOF CURB, LOW AMBIENT KIT,

MOTORIZED INTAKE DAMPER, STOP-START-JOG CONTROLS & PRESSURE SENSOR.

ACCEPTABLE PRODUCT: YORK / JCI V SERIES OR APPROVED EQUAL.

3.0 EXECUTION

3.1 DUCT SIZE CHANGES SHALL HAVE THE SAME FRICTION DROP PER 100 FT AS THE

DUCT SHOWN ON DRAWINGS. DUCT ASPECT RATIO SHALL NOT EXCEED 4 TO 1.

CONSULT ENGINEER BEFORE CHANGING DUCT SIZE OR LOCATION.

3.2 PROVIDE FLEXIBLE DUCT CONNECTIONS AT SUCTION AND DISCHARGE

CONNECTIONS TO FANS AND AIR CONDITIONING UNITS.

3.3 SEAL DUCT CONNECTIONS AND TRAVERSE JOINTS WITH SEALANT.

3.4 PROVIDE FIRE DAMPERS WITH STEEL ANGLES AROUND PERIMETER AND ACCESS

DOORS.

3.5 FIVE DAYS PRIOR TO CLOSING CEILING, NOTIFY CONSULTANT AND PROJECT

MANNER FOR A SITE INSPECTION. FAILURE TO DO SO CAN RESULT IN CONTRACTOR

RE-OPENING AND RE-CLOSING CEILING TILES AT THEIR EXPENSE TO PERMIT THIS

INSPECTION.

3.6 INSULATE ALL DUCTS AND PLENUMS HANDLING OUTSIDE AIR WITH 2 INCHES (50

MM) FIBERGLASS FOIL FACED VAPOR SEAL DUCT INSULATION 31 DENSITY. EXHAUST

DUCTS SHALL BE INSULATED WITH 2 IN. (50 MM) FIBERGLASS FOIL FACED VAPOR SEAL

INSULATION UP TO 7 FEET (2 METERS) FROM OUTSIDE WALL.

3.6 TESTING ADJUSTING & BALANCING:

3.6.1 TESTING AND BALANCING SHALL CONFORM TO AABC, NEBB, AND/OR SMACNA

STANDARDS FOR THE ADJUSTMENT OF AIR SYSTEMS USING TAB STANDARD

PROVISIONS: CHECKLISTS, REPORT FORMS, FIRM AND SPECIALIST QUALIFICATIONS

AND CALIBRATION OF TAB INSTRUMENTS.

3.6.2 PERFORM TAB TO TEST TO VERIFY PROPER AND SAFE OPERATION, DETERMINE

ACTUAL POINT OF PERFORMANCE, EVALUATE QUALITATIVE AND QUANTITATIVE

PERFORMANCE OF EQUIPMENT, SYSTEMS AND CONTROLS AT DESIGN, AVERAGE AND

LOW LOADS USING ACTUAL OR SIMULATED LOADS. ADJUST AND REGULATE

EQUIPMENT AND SYSTEMS TO MEET SPECIFIED PERFORMANCE REQUIREMENTS AND

TO ACHIEVE SPECIFIED INTERACTION WITH OTHER RELATED SYSTEMS UNDER

NORMAL AND EMERGENCY LOADS AND OPERATING CONDITIONS. BALANCE SYSTEMS

AND EQUIPMENT TO REGULATE FLOW RATES TO MATCH LOAD REQUIREMENTS OVER

FULL OPERATING RANGES.

3.6.3 START-UP: PERFORM STARTUP FOLLOWING START-UP PROCEDURES PER

EQUIPMENT MANUFACTURER.

3.6.4 START TAB WHEN BUILDING IS ESSENTIALLY COMPLETED AND ENCLOSED,

MECHANICAL SYSTEMS INSTALLED COMPLETE, PRESSURE TESTED, ETC. AND

OPERATIONAL.

3.6.5 DO TAB TO FOLLOWING TOLERANCES OF DESIGN VALUES: HVAC SYSTEMS: HVAC

SYSTEMS: PLUS 5%, MINUS 5%. REPORTED RESULTS SUBJECT TO VERIFICATION BY

CONSULTANT. PROVIDE PERSONNEL AND INSTRUMENTATION TO VERIFY UP TO 30%

OF REPORTED RESULTS. PAY COSTS TO REPEAT TAB AS REQUIRED TO

SATISFACTION OF CONSULTANT. TAB CONSIDERED COMPLETE WHEN FINAL TAB

REPORT RECEIVED AND APPROVED BY CONSULTANT.

3.6.7 AIR SYSTEM MEASUREMENTS: AIR VELOCITIES, TOTAL/STATIC PRESSURES,

FLOW RATES, PRESSURE DROPS (OR LOSS), TEMPERATURES (DRY BULB, WET BULB,

DEWPOINT), DUCT CROSS-SECTIONAL AREAS, RPMS, ELECTRICAL POWER, VOLTAGE,

NOISE, VIBRATION, ETC. AT INLET AND OUTLET OF DAMPERS, FILTERS, COILS, FANS,

ACUS, CONTROLLED DEVICES, MAIN DUCTS, MAIN BRANCHES, SUB-BRANCHES,

RUN-OUTS (GRILLES, REGISTERS OR DIFFUSERS).

3.6.8 TEST FOR PROPER OPERATION OF ALL SMOKE AND FIRE DAMPERS, SENSORS,

DETECTORS.

3.6.9 PARTICIPATE IN SYSTEMS CHECKS TWICE DURING WARRANTY PERIOD - #1

APPROXIMATELY 3 MONTHS AFTER ACCEPTANCE AND #2 WITHIN 1 MONTH OF

TERMINATION OF WARRANTY PERIOD.

3.6.10 PROVIDE 3 COPIES OF A WRITTEN REPORT INDICATING ALL MEASUREMENTS

AND A LETTER CERTIFYING THAT ALL SYSTEMS AND EQUIPMENT HAVE BEEN TESTED

AND BALANCED AS REQUIRED. TESTING & BALANCING REPORTS SHALL INCLUDE A

COPY OF THE ENGINEERS HVAC DUCT / PIPING LAYOUT IDENTIFYING EACH ITEM /

EQUIPMENT / POINTS IN THE SYSTEM WHERE ALL THE MEASUREMENTS WERE TAKEN.

3.6.11 PROVIDE A PRELIMINARY TAB REPORT TO CONSULTANT AND OWNER WITHIN 5

DAYS OF SITE MEASUREMENT AND A FINAL REPORT AFTER PRELIMINARY REPORT

HAS BEEN REVIEWED BY CONSULTANT AND OWNER.

3.6.12 TAB REPORT TO CLEARLY STATE MINIMUM AND MAXIMUM CONDITIONS.

PROVIDE A PLAN VIEW WITH ALL TEST LOCATIONS IDENTIFIED. TAB CONTRACTOR

REPORT TO CLEARLY INDICATE DEFICIENCIES RELATED TO DIFFUSERS, DAMPERS,

VAVS, FANS THAT ARE NOT OPERATING IN A MANNER TO PERMIT MEASUREMENTS TO

MEET DESIGN CONDITIONS.

3.6.13 PRIOR TO HVAC DEMOLITION, MODIFICATIONS & RENOVATIONS OF EXISTING

EQUIPMENT & SYSTEMS, MEASURE THE SUPPLY, RETURN, EXHAUST & OUTSIDE AIR

FLOW RATES AT EACH DIFFUSER, GRILLE, REGISTER, FAN, AHU, ACU, LOU-VER, ETC.

AFFECTED BY THE RENOVATIONS. THIS INCLUDES HVAC 3, 4 & 7. MEASURE TOTAL &

EXTERNAL STATIC PRESSURES, RPM, BHP, VOLTAGE, AMP DRAW, ETC. AT EACH

SUPPLY, RETURN, EXHAUST & OUTSIDE AIR CONNECTIONS OF EACH FAN, AHU, ACU,

EF, RF, ETC. SUBMIT PRE DEMOLITION BALANCING REPORT TO ENGINEER FOR

ANALYSIS TO DETERMINE FINAL BALANCING VALUES. UPON COMPLETION OF THE

HVAC SYSTEM MODIFICATIONS & RENOVATIONS, TAB EXISTING & NEW EQUIPMENT,

TERMINAL UNITS, DIFFUSERS, GRILLES, REGISTERS, FANS, AHUS, ETC. TO VALUES

DETERMINED BY ENGINEER AFTER REVIEW & ANALYSIS OF PRE DEMOLITION

BALANCING REPORT.

3.6.14 IN BALANCING HVAC SYSTEMS, ADJUST FAN SPEED AS NECESSARY VIA

EXISTING UNIT VFD. WHERE NO VFD IS AVAILABLE, CHANGE BELTS & SHEAVES AS

REQUIRED. FINALLY, INLET OR DISCHARGE DAMPERS MAY BE USED AS LAST RESORT.

WHERE REDUCTION IN AIRFLOW IS NO LONGER POSSIBLE DUE TO RTU MINIMUM

FLOW RATE, BYPASS DUCTS MAY BE ADJUSTED OPEN TO ACHIEVE THE REQUIRED

MINIMUM FLOW RATE. MAKE DRIVE SPEED ADJUSTMENTS OR REPLACE SHEAVES AS

REQUIRED TO ATTAIN DESIGN CONDITIONS. FURNISH NEW OR EXCHANGE FURNISHED

SHEAVES WITH UNIT MANUFACTURER, AT NO CHANGE IN CONTRACT PRICE.

3.6.15 ACCEPTABLE TAB AGENCIES: MEMBERS OF NEBB AND / OR AABC.

3.7 SEQUENCE OF OPERATION

3.7.1 A COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM (BAS) SHALL BE

INSTALLED IN ACCORDANCE WITH THE SEQUENCE OF OPERATIONS, POINTS LIST, AND

NOTES.

3.7.2 MECHANICAL CONTRACTOR SHALL COORDINATE ALL BAS INTEGRATION

REQUIREMENTS WITH EQUIPMENT VENDORS AND CONTROLS CONTRACTOR PRIOR TO

PURCHASING EQUIPMENT AND PROVIDE ALL EQUIPMENT WITH COMMUNICATION /

INTERFACE CARDS AS REQUIRED FOR SYSTEM INTEGRATION.

3.7.3 ROOFTOP UNIT: ROOFTOP UNITS (RTU) SHALL BE STOPPED / STARTED ON A

TIME OF DAY SCHEDULE THROUGH THE BAS. THIS SCHEDULE SHALL BE MODIFIED BY

A START STOP OPTIMIZATION PROGRAM. START / STOP OPTIMIZATION SHALL BE

CAPABLE OF BEING DISABLED. UPON PROOF OF AIR FLOW THRU THE SUPPLY FAN,

THE NORMALLY CLOSED OUTSIDE AIR DAMPER SHALL BE ENABLED. A DISCHARGE

AIR TEMPERATURE SENSOR SHALL STAGE COMPRESSORS ON, AS REQUIRED TO

MAINTAIN SUPPLY AIR TEMPERATURE.

13.7.4 SUPPLY AIR TEMPERATURE RESET: SUPPLY AIR TEMPERATURE SHALL VARY

LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES. STATE THE HIGH & LOW

TEMPERATURES (ADJ) IN CONTROL DRAWINGS. THE INITIAL SETPOINT FOR THE

DISCHARGE AIR SUPPLY TEMPERATURE SHALL BE 55° F. SUPPLY AIR TEMPERATURE

SETPOINT SHALL HAVE A HIGH LIMIT OF 62° REGARDLESS OF OUTSIDE AIR

TEMPERATURE, WHEN ANY ZONE ON THE RTU HAS A CALL FOR COOLING.

3.7.5 SUPPLY DUCT STATIC PRESSURE SENSOR: SENSOR SHALL MODULATE THE

BYPASS DAMPERS TO MAINTAIN THE SETPOINT ESTABLISHED DURING FINAL TESTING

AND BALANCING. THE PRELIMINARY SETPOINT SHALL BE 0.6” (ADJ.) STATIC PRESSURE.

THIS SETPOINT SHALL BE RESET BASED ON THE ZONE REQUIRING THE MOST

PRESSURE; I.E., THE SETPOINT IS RESET LOWER UNTIL ONE TERMINAL BOX DAMPER

IS NEARLY WIDE OPEN.

3.7.6 SUPPLY FAN: WHILE IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL

OPERATE CONTINUOUSLY. WHILE IN THE UNOCCUPIED MODE, THE UNIT SUPPLY FAN

SHALL CYCLE WITH HEATING AND COOLING LOADS, UPON A CALL FOR HEATING OR

COOLING TO MEET UNOCCUPIED SETPOINTS, THE UNIT FAN SHALL BE STARTED AND

THE UNIT SHALL OPERATE AS DESCRIBED BELOW AS REQUIRED BY THE SPACE

TEMPERATURE. THE STAGED HEATER OR COMPRESSORS SHALL ALSO BE STARTED

AS REQUIRED TO SATISFY SETPOINTS.

3.7.7 UNOCCUPIED HEATING MODE WITH STAGED HEAT: WHILE THERE IS A CALL

FOR HEATING IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL RUN TO SUPPLY

HEATING AIRFLOW. THE MOTORIZED OUTSIDE AIR DAMPER SHALL REMAIN FULLY

CLOSED, AND THE RETURN AIR DAMPER SHALL OPEN TO 100%. THE GAS-FIRED

HEATER SHALL OPERATE IN STAGES TO MAINTAIN A UNIT DISCHARGE AIR

TEMPERATURE OF 85 DEGREES F (ADJ.) UNTIL ALL ZONES ARE SATISFIED. VAV

TERMINAL PRIMARY AIR DAMPERS SHALL OPEN TO A PREDETERMINED POSITION. THE

UNIT SHALL OPERATE FOR A MINIMUM OF 15 MINUTES OR AS REQUIRED TO SATISFY

UNOCCUPIED SETPOINT. WHEN OCCUPIED, STAGED HEATING SHALL INCREASE RTU

SUPPLY AIR TEMPERATURE. WHEN HOT AIR IS SENSES IN THE SUPPLY DUCT, THE

VAV TERMINAL UNIT SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE.

3.7.8 DEMAND CONTROL VENTILATION: OUTSIDE AIR INTAKE SHALL BE PROVIDED

WITH A MOTORIZED DAMPER. ON UNIT START, THE OUTSIDE AIR INTAKE DAMPER

SHALL REMAIN CLOSED UNTIL THE RETURN AIR TEMPERATURE IS ABOVE 65° F (ADJ)

AND BELOW 75° F. (ADJ). ONCE RETURN AIR TEMPERATURE IS SATISFIED, THE

OUTSIDE AIR DAMPER SHALL OPEN TO THE OCCUPIED MINIMUM SETPOINT. THE

OUTSIDE AIR INTAKE DAMPER SHALL BE CLOSED WHILE UNIT IS IN THE UNOCCUPIED

MODE. BAS SHALL BE CAPABLE OF OPENING AND CLOSING ALL DAMPERS.

3.7.9 CO2 SENSOR: CO2 SENSOR MOUNTED IN THE RETURN DUCT SHALL MODULATE

THE OUTSIDE AIR DAMPER BASED ON CO2 LEVELS IN THE SPACE. DAMPER SHALL

MODULATE OPEN FROM THE OCCUPIED MINIMUM SETPOINT OF 800 PPM TO DESIGN

MAXIMUM AT 1200 PPM.

.7.10 CO2 ZONING: A SPACE CO2 SENSOR IN THE ZONES SHALL INCREMENTALLY

OPEN THE MINIMUM VAV BOX DAMPER POSITION FOR ITS RELATED ZONE DAMPER.

3.7.11 AIRSIDE ECONOMIZER COOLING CYCLE: DURING THE OCCUPIED PERIOD, WHEN

THE OUTSIDE AIR TEMPERATURE IS BELOW 70° F (ADJ.) AND THE OUTDOOR ENTHALPY

IS BELOW THE RETURN AIR ENTHALPY (OPTIONAL), THE ECONOMIZER CYCLE SHALL

BE ENABLED. UNDER THOSE CONDITIONS, THE OUTDOOR AIR DAMPER AND RETURN

AIR DAMPER SHALL MODULATE AS REQUIRED TO MAINTAIN THE DISCHARGE AIR

TEMPERATURE SETPOINT WHILE THE UNIT IS IN COOLING MODE.

3.7.12 ECONOMIZER RELIEF DAMPERS: UNIT MOUNTED RELIEF SHALL RELIEVE

EXCESS RETURN AIR WHEN IN ECONOMIZER OPERATION.

3.7.13 HUMIDITY CONTROL: HUMIDITY CONTROL SHALL BE A FUNCTION WITHIN THE

UNIT. HUMIDITY LEVELS SHALL BE MAINTAINED BETWEEN 35-55% RH AS MEASURED

VIA A DUCT MOUNTED SENSOR.

3.7.14 SMOKE DETECTION & RTU SHUTDOWN: UPON DETECTION OF SMOKE IN THE

AIR HANDLING SYSTEM BY THE DUCT-MOUNTED RETURN AIR SMOKE DETECTOR, AN

ALARM CONDITION SHALL BE SENT TO THE BUILDING FIRE ALARM SYSTEM AND ALL

AIR HANDLING UNITS SHALL BE SHUTDOWN BY THE BUILDING FIRE ALARM SYSTEM.

3.7.15 ZONE TEMPERATURE SENSORS / THERMOSTATS: ZONE TEMPERATURE

SENSORS / THERMOSTATS SHALL BE PROVIDED WHERE INDICATED ON THE

DRAWINGS. THERMOSTATS SHALL HAVE MANUAL ADJUSTMENT, AND SHALL BE

INITIALLY SET IN THE OCCUPIED MODE FOR COOLING TO 76° AND HEATING TO 71°.

THERMOSTATS SHALL HAVE A 5° (ADJ.) DEADBAND RANGE IN WHICH THEY ARE

SATISFIED. MANUAL ADJUSTMENT SHALL HAVE THE CAPABILITY TO ADJUST THE

HEATING AND COOLING SETPOINTS BY 3° (ADJ.) IN EACH DIRECTION, BUT MAINTAIN A

MINIMUM 5° SPREAD BETWEEN THE HEATING AND COOLING SETPOINT. UNOCCUPIED

SETTINGS SHALL BE 85° COOLING AND 60° HEATING. COORDINATE FINAL SETPOINTS,

SETBACK, SCHEDULING, MORNING WARM-UP, COOL-DOWN, ETC WITH OWNER DURING

OWNER. THERMOSTATS SHALL HAVE AN OVERRIDE FUNCTION THAT WILL PLACE THE

UNIT IN OCCUPIED MODE FOR A PERIOD OF TWO HOURS (ADJ.). THE OVERRIDE SHALL

ACTIVATE THE SYSTEM AHU AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.

3.7.16 HEATING / COOLING SELECTION: ALL SENSORS / THERMOSTATS CONNECTED

TO THE RTU SHALL ALL BE MONITORED AND USED TO DETERMINE THE RTU

OPERATION IN COOLING OR HEATING MODE. RTU OPERATION IN HEATING & COOLING

WILL DETERMINE VAV BOX MODULATION IN HEATING OR COOLING MODE. IF A ZONE IS

HOT & RTU IS IN COOLING MODE, VAV DAMPER MODULATES OPEN TO SATISFY

COOLING SETPOINT. ON A DROP IN TEMPERATURE BUT STILL IN COOLING MODE, VAV

DAMPER MODULATES CLOSED. IF A ZONE IS COLD & RTU IS IN HEATING MODE, VAV

DAMPER MODULATES OPEN TO SATISFY HEATING SETPOINT. ON A RISE IN

TEMPERATURE BUT STILL IN HEATING MODE, VAV DAMPER MODULATES CLOSED.

3.7.17 VAV BOXES: THE FAN POWERED VARIABLE VOLUME (VAV) TERMINAL UNITS

SHALL BE CONTROLLED INDEPENDENT OF SYSTEM PRESSURE FLUCTUATIONS BY AN

APPLICATION SPECIFIC DDC CONTROLLER UTILIZING ELECTRIC ACTUATION. DURING

OCCUPIED AND UNOCCUPIED OPERATION, A TEMPERATURE SENSOR SHALL BE

UTILIZED TO MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A RISE IN SPACE

TEMPERATURE ABOVE SETPOINT IN COOLING MODE, THE VOLUME DAMPER SHALL

MODULATE OPEN AS REQUIRED TO MAINTAIN SPACE TEMPERATURE. UPON A DROP IN

SPACE TEMPERATURE BELOW SETPOINT IN COOLING MODE, THE VOLUME DAMPER

SHALL MODULATE CLOSED UNTIL THE MINIMUM DAMPER POSITION IS REACHED. UPON

CONTINUED DROP IN SPACE TEMPERATURE BELOW HEATING SETPOINT SETPOINT &

WITH HOT AIR SUPPLIED BY THE RTU, THE VAV BOX SHALL MODULATE OPEN UNTIL

FULL OPEN.

3.7.18 NORMAL NON ECONOMIZER MODE:

3.7.18.1 SPACE THERMOSTAT SENDS A SIGNAL TO THE RTU FOR COOLING, HEATING

OR FAN ONLY OPERATION. ERV IS INTERLOCKED & ACTIVATED SIMULTANEOUSLY

WITH THE RTU SUPPLY BLOWER. THE ERV INTAKE & EXHAUST BLOWERS & ERV

WHEEL MOTORS ARE ACTIVATED & REMAIN ENERGIZED AS LONG AS THE RTU SUPPLY

BLOWER IS ENERGIZED. MOTORIZED FRESH AIR DAMPER OF THE ERV OPENS WHEN

THE ERV IS ENERGIZED.

3.7.18.2 LOW AMBIENT MODE: IF TEMPERATURE SENSED BY LOW AMBIENT SENSOR

LEAVING EXHAUST SIDE OF WHEEL DROPS BELOW SET POINT (ADJ.), MOTORIZED

FRESH AIR DAMPER WILL CLOSE AND THE INTAKE BLOWER WILL DE-ENERGIZE.

EXHAUST AIR BLOWER & WHEEL ROTATION MOTOR WILL CONTINUE TO OPERATE.

WHEN THE TEMPERATURE SENSOR HAS A SIXTEEN-DEGREE RISE, THE WHEEL IS

DEFROSTED AND THE MOTORIZED DAMPER WILL OPEN & THE FRESH AIR BLOWER

WILL REACTIVATE.

ECONOMIZER OPERATION (PIVOTING MODELS): SPACE THERMOSTAT SENDS A SIGNAL

TO RTU FOR COOLING OPERATION. RTU OUTDOOR AIR SENSOR SENSES OUTDOOR

AIR & DETERMINES IT IS APPROPRIATE FOR ECONOMIZER OPERATION. AS

ECONOMIZER OUTSIDE AIR DAMPERS OPEN, ERV ECONOMIZER END SWITCH IS

ACTIVATED & SENDS SIGNAL TO THE ERV THAT THE SYSTEM IS IN ECONOMIZER MODE.

INTAKE BLOWER, EXHAUST BLOWER & ERV WHEEL MOTOR ALL DEACTIVATE FOR UP

TO TWO MINUTES. MOTORIZED FRESH AIR DAMPER CLOSES. ERV ENTHALPY WHEEL

PIVOTS OUT OF AIR STREAM & BYPASS DAMPERS OF THE INTAKE BLOWER OPEN.

AFTER A TIME DELAY FOR THE WHEEL TO PIVOT OUT OF THE AIRSTREAM & BYPASS

DAMPERS TO OPEN, MOTORIZED FRESH AIR DAMPER OPENS TO ALLOW FOR FULL

ECONOMIZER OPERATION. THE EXHAUST BLOWER IS REACTIVATED TO PROVIDE

POWER EXHAUST FOR THE SYSTEM.

2021-08-0921-023

Page 4: M1 - LEGENDS M1

PHASE 1(GROUP D)

PHASE 2(GROUP A2)

E

1

2

3

4

5

6

DCBA

EX. SUMP& PUMP, TO

REMAIN

EX. 4"Ø SAN RISERS,

TO REMAIN

EX. LAVEX. ABANDONED DHW

HEATER, TO REMAIN

EX. ABANDONED DHW

HEATER

EX. ABANDONED DHW

HEATER

EX. 6"Ø F

EX. CAPPED TEE

EX. SPRINKLER RISER,

VALVE, & PRESS.

MAINTENANCE PUMP

EX. SPRINKLER LINES

TO SPRINKLER HEADS

EX. SPRINKLER LINES

TO SPRINKLER HEADS

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.

EX. ABANDONED

COMPRESSOR, TO

REMAIN

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.M BFP

EX. 4"Ø DCW SERVICE

1"Ø

EX. 1"Ø METER

EX. BFP

EX. 1 1/2"Ø CW TO

FIXTURES

EX. ELECTRICAL

PANEL, TYP

EX. ELECTRICAL

PANEL, TYP

EX. ABANDONED ACU

EX. ELECTRICAL

PANEL, TYP

EX. FD

EX. FD

EX. 6"Ø SAN?

EX. FFD

EX. FD

EX. CO

2 1/2"Ø3"Ø3"Ø4"Ø

4"Ø

2 1/2"Ø

2 1/2"Ø

2"Ø2"Ø

EX. 3"Ø SANEX. 3"Ø SAN & V

5"Ø5"Ø

2"Ø

2 1/2"Ø

2"Ø

OPENED PIPE

BOTH ENDS

EX. 6"Ø, RELOCATE

EX. 6"Ø INS

DN

FD3

FD2 FD2

NOT IN

SCOPE

FD2

FD2

FD2

E

1

2

3

4

5

6

DCBA

JS W/ DRAINS,

DEMOLISH

EX. SPRINKLER DRAIN,

TO REMAIN

EX. FDC, TO REMAIN

FD1

FD1

EX. SPRINKLER

HEADS, TYP

EX. PLUMB SAN, V, CW,

DHW, DEMOLISH

EX. 2"Ø PIPE

EX. 1"Ø D

EX. 1 1/2"Ø D,

DEMOLISH

EX. PLUMB SAN, V, CW,

DHW, DEMOLISH

EX. SAN, V, CW, DHW, & NG,

DEMOLISH

EX. SAN & DRINK

DISPENSER,

DEMOLISH

EX. 6"Ø F RISER,

RELOCATE

NOT IN

SCOPE

EX. SAN, V, DRAIN TO

SINK, RELOCATE &

EXTEND TO BASEMENT

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023

SCALE:

BASEMENT FLOOR PLAN - PLUMBING AND FIRE PROTECTION DEMOLITION1/8"=1'-0" SCALE:

FLOOR PLAN - PLUMBING AND FIRE PROTECTION DEMOLITION1/8"=1'-0"

M4

FLOOR PLANS - PLUMBING AND FIRE PROTECTION DEMOLITION

1/8" - 1'-0"

FIRE PROTECTION DEMOLITION NOTES:

FD1 REMOVE EX. SPRINKLER PIPING THAT WILL NOT ACCOMODATE THE NEW

LAYOUT SHOWN IN M6.

FD2 EX. SPRINKLER LINE LAYOUT & SIZES APPROXIMATE TO BE

CONFIRMED BY SPRINKLER DESIGNER, ENGINEER & CONTRACTOR.

FD3 TEST & INSPECT EX. SPRINKLER SYSTEM TO ENSURE PROPER FUNCTION

& SUITABILITY FOR NEW SERVICE. REPORT DEFFICIENCIES IDENTIFIED TO

ARCH & ENGINEER.

2021-08-0921-023

Page 5: M1 - LEGENDS M1

PHASE 1(GROUP D)

PHASE 2(GROUP A2)

E

1

2

3

4

5

6

DCBA

EX. SAN, V, DRAINS TO

NEW DRAIN

EX. SUMP & PUMP,

TO REMAIN

EX. 4"Ø SAN RISERS,

TO REMAIN

EX. LAVEX. ABANDONED DHW

HEATER, TO REMAIN

EX. ABANDONED DHW

HEATER

EX. ABANDONED DHW

HEATER

EX. 6"Ø F

EX. CAPPED TEE

EX. SPRINKLER RISER,

VALVE, & PRESS.

MAINTENANCE PUMP

EX. SPRINKLER LINES

TO SPRINKLER HEADS

EX. SPRINKLER LINES

TO SPRINKLER HEADS

EX. FIXTURES TO

REMAIN, TYP.

EX. ABANDONED

COMPRESSOR, TO

REMAIN

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.

EX. FIXTURES TO

REMAIN, TYP.M BFP

EX. 4"Ø DCW SERVICE

1"Ø

EX. 1"Ø METER

EX. BFP

EX. 1 1/2"Ø CW TO

FIXTURES

EX. ELECTRICAL

PANEL, TYP

EX. ELECTRICAL

PANEL, TYP

EX. ABANDONED ACU

EX. ELECTRICAL

PANEL, TYP

EX. FD

EX. FD

EX. 6"Ø SAN?

EX. FFD

EX. FD

EX. CO

2 1/2"Ø3"Ø3"Ø4"Ø

4"Ø2 1/2"Ø

2 1/2"Ø

2"Ø2"Ø

EX. 3"Ø SAN

EX. 3"Ø SAN & V

5"Ø5"Ø

2"Ø

2 1/2"Ø

2"Ø

EX. ABANDONED PIPE

EX. 6"Ø INS

DN

RELOCATED 6"Ø F

RISER

CONN TO EX. 1 1/2"Ø

COPPER CW LINE

3/4"Ø CW

1/2"Ø CW

1/2"Ø CW

1/2"Ø CW

CO

1 1/2"Ø SAN

CONN TO EX. 3"Ø SAN

@ FLOOR, TYP

1 1/2"Ø SAN & 1/2"Ø

CW UP TO SINK

1 1/2"Ø SAN & 1/2"Ø

CW UP TO SINK

1 1/2"Ø SAN & 1/2"Ø CW

UP TO DRINKING

FOUNTAIN

CONN TO EX.

3"Ø SAN , TYP

CONN TO EX.

FEX

FEX

FEX

FP2

FP2

FP2

CONN TO EX.

CLASSROOM 3

103

CLASSROOM 1

104

CLASSROOM 2102

RESOURCECENTRE

101

KITCHENETTE

105

LOUNGE

106

BUSINESSCENTRE

107

OFFICE 1108 STORAGE

112

OFFICE 2

109

P.T. STAFF110

MEETING RM.111

CORRIDOR

113

VESTIBULE

114

STAIR

115

E

1

2

3

4

5

6

DCBA

S1 (NEW)

1 1/2"Ø SAN & 1/2"Ø CW,

TO BELOW FLOOR

FP1

EX. SPRINKLER

HEADS, TYP

FP1

RELOCATED 6"Ø F

RISER

EX. SPRINKLER

HEADS, TYP

EX. SPRINKLER

HEADS, TYP

FP1

FP1

FP1

S1 (NEW)1 1/2"Ø SAN & 1/2"Ø CW,

TO BELOW FLOOR

CONN TO EX.

JOIST SPACE

GROUND FLOOR &

JOIST SPACE

SPRINKLERS

INSTANTANEOUS

WATER HEATER

HW1

NOT IN

SCOPE

EX. SPRINKLER DRAIN,

TO REMAIN

EX. 2"Ø PIPE

EX. 1"Ø D

EX. FDC, TO REMAIN

EX. SPRINKLER

HEADS, TYP

RELOCATED SAN, V,

DRAIN TO BASEMENT

FEX

FEX

FP2

FP2

DF1 (NEW)

1 1/2"Ø SAN & 1/2"Ø CW,

TO BELOW FLOOR

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023

SCALE:

BASEMENT FLOOR PLAN - PLUMBING AND FIRE PROTECTION1/8"=1'-0" SCALE:

FLOOR PLAN - PLUMBING AND FIRE PROTECTION1/8"=1'-0"

M5

FLOOR PLANS - PLUMBING AND FIRE PROTECTION

1/8" - 1'-0"

FIRE PROTECTION NOTES:

FP1 RECONFIGURE EX. SPRINKLER SYSTEM TO MATCH NEW LAYOUT. PROVIDE NEW BRANCH PIPING,

CONNECTIONS, HEADS, ETC. AS REQUIRED TO SATISFY NEW SPACE LAYOUT.

FP2 FEX 2A, TYPICAL FOR MAIN FLOOR UNLESS NOTED OTHERWISE.

2021-08-0921-023

Page 6: M1 - LEGENDS M1

E

1

2

3

4

5

6

DCBA

EX. EWH,

TO REMAIN

EX. 24X24 RA GRILLE

EX. 24X24 RA UP TO HVAC-5

EX. SA FROM HVAC-5 ON ROOF

EX. 24X24 RA GRILLE

EX. 24X24 RA UP TO HVAC-4

EX. SA FROM

HVAC-4 ON ROOF

EX. 24X24 RA

UP TO HVAC-3

EX. SA FROM

HVAC-3 ON ROOF

EX. 20X24 UP TO HVAC-2

EX. 48X20 SA FROM

HVAC-1 ON ROOF

EX. 24X24 RA UP TO HVAC-2

EX. 24X12 SA FROM

HVAC-7 ON ROOF

EX. EXH CAP

EX. 24X24 RA UP

TO HVAC-6

EX. SA FROM HVAC-6 ON ROOF

EX. 14X14 EXH UP TO ROOF, DEMOLISH

EX. 5"Ø EXH

TO ROOF

EX. 50X22 RA GRILLE

EX. 24X24 RA

GRILLE

8"Ø

SA DIFF.

24X18 GRILLE

EX. 24X14 UP

TO ROOF, TO REMAIN

HVAC DEMOLITION NOTES:

1 GRILLE IN EXISTING CEILING, DEMOLISH.

2 EXISTING DUCT UP THRU EXISTING CEILING, DEMOLISH.

3 DIFFUSER IN CEILING, DEMOLISH.

4 GRILLE IN EXISTING CEILING, DEMOLISH.

5 GRILLE IN BULKHEAD ABOVE NEW CEILING, DEMOLISH.

6 ABANDONED & BLOCKED EF

7 EX. DUCT IN BULKHEAD, DEMOLISH DUCT & BULKHEAD, COORDINATE WITH ARCH.

12"Ø UP

24X4 24X4

EX. 24X24 RA TO

HVAC-7

EX. 30X30 DAMPER

4"Ø SA

4"Ø RA

EX. 48X72 GRILLE

1

3

4 1

2

3

5

5

1 2

6

1

4

1

12Ø

12

Ø

12Ø

12

x12

12Ø

20

x12

24x124Ø

24x12

10Ø

24

x10

6Ø6Ø

4Ø4Ø

10x4

12Ø

20

x12

10Ø

10x1

0

10Ø

14x1

2

10Ø

10

Ø

12Ø

10Ø

10Ø

6Ø 6Ø

10Ø

10Ø

10Ø

10Ø

10Ø

10Ø 8Ø

24

x10

24

x12

10Ø

10

Ø

4Ø4Ø

4Ø 4Ø

12Ø

12

Ø

10x6

24

x12

12

x81

2x8

12

x8

10Ø

4Ø6Ø

10Ø

24x1

02

4x1

2

10x10

18x18

20x20

20x20

20x2020x20

20x20

18x1818x18

EX. NG SERVICE & METER

CAP DUCTS,

TYP.

CAP DUCTS,

TYP.

CAP DUCTS,

TYP.

CAP DUCTS,

TYP.

CAP UNUSED

DUCT CONNECTIONS,

TYP.

EX. DUCTS, DEMOLISH, TYP.

VESTIBULE

10Ø

10Ø 12Ø

24

x12

12Ø

24x1

2

EX. 20X6, DEMOLISH.

3 3

3

3

EX. EF, DEMOLISHEX. TRANSFER DUCT,

DEMOLISH

EX. WALL HEATER,

REPLACE

12x1

2

12

x12

12x1

2

8Ø8Ø

18

x12

20

x12 6Ø

20x12

10

Ø8

Ø

48x20

48x20

SA DUCT OFFSET

EX. RA DUCT DEMOLISH

EX. RA FROM

HVAC-1 ON ROOF

7

7

20x20

EX. EF

32x12

32x12 24x12

20

x40

NOT IN

SCOPE

E

1

2

3

4

5

6

DCBA

EX. HVAC-1

EX. HVAC-4 EX. HVAC-5

EX. HVAC-3EX. HVAC-6

EX. HVAC-7

EX. HVAC-2

EX. CHIMNEY

EX. EF3

EX. EF2

EX. EF1

EX. EXH. DUCT, TO REMAIN

EX. GOOSENECK, TO REMAIN

EX. EF4

EX. EF5

EX. 1 1/2"Ø NG

EX. 1"Ø NG

EX. 2"Ø NG

EX. 2 1/2"Ø NG

EX. 3"Ø NG

EX. 2"Ø NG

EX. 1"Ø NG

EX. 1 1/2"Ø NG

EX. 1"Ø NG

EX. GOOSENECK

EX. ROOF HATCH

EX. NG SERVICE & METER

HVAC DEMOLITION NOTES:

1 EX. RTU, REBANLANCE TO MATCH NEW FLOW RATES

DUE TO DEMOLISHED OUTLETS

1

1

1

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023

SCALE:

FLOOR PLAN - HVAC DEMOLITION1/8"=1'-0"

SCALE:

ROOF PLAN - HVAC DEMOLITION1/8"=1'-0"

M6

FLOOR AND ROOF PLAN - HVAC DEMOLITION

1/8" - 1'-0"

2021-08-0921-023

Page 7: M1 - LEGENDS M1

E

1

2

3

4

5

6

DCBA

EX. EWH,

TO REMAIN

EX. EF

EX. 24X24 RA GRILLE

EX. 24X24 RA UP TO HVAC-5EX. SA FROM HVAC-5 ON ROOF

EX. 24X24 RA GRILLE

24X24 RA UP TO HVAC-4

EX. SA FROM

HVAC-4 ON ROOF

EX. SA FROM

HVAC-3 ON ROOF

EX. 20X24 SA

FROM HVAC-2

24X24 RA UP

TO HVAC-2

EX. 24X12 SA FROM

HVAC-7 ON ROOF

EXH CAP

EX. 24X24 RA UP TO HVAC-6EX. SA FROM

HVAC-6 ON ROOF

5"Ø EXH

TO ROOF

EX. 24X24 RA

GRILLE

HVAC NOTES:

1 REBALANCE EX. DIFFUSERS, GRILLES, REGISTERS TO VALUES INDICATED. TYP.

2 REBALANCE DIFFUSERS / GRILLES FOR RTUS 3, 4 & 7 TO MATCH AIR FLOW RATES

INDICATED ON PLANS & SCHEDULES FROM PREVIOUS TAB REPORT.

3 TAB TO ADJUST DIFFUSERS THROWS TO VERTICAL FOR MAX. VELOCITY AT 7 FEET

ABOVE FIN. FLOOR = APPROX. 50 FPM IN COOLING & 20 FPM IN HEATING. TYP FOR

NEW 11'-10" HIGH CEILINGS IN RENOVATION AREAS.

EX. 24X24 RA TO

HVAC-7

EX. 30X30 DAMPER

4"Ø SA

4"Ø RA

10

Ø

10Ø

24

x12

10Ø

10Ø8Ø

10Ø

10Ø

12Ø

10

Ø10Ø

6Ø10x4

12

Ø

12

Ø

4Ø4Ø

10Ø

10Ø

10Ø

10Ø

4Ø 4Ø

24

x10

20x20

20x20

20x20

20x20

20x2020x20

4Ø24x12

SDJ-8250

SDJ-6100

SDJ-8300

SDJ-8300

SDJ-8310

SDJ-10390

SDB-8300

SDJ-8245

SDJ-12500

SDJ-12500

SDJ-8275

SDJ-8275

SDJ-8275

SDJ-8275

SDJ-8275

SDJ-695

SDJ-6125

SDJ-8315

SDJ-10390

SDJ-10380

SDJ-10380

RGA-22X221150

SDJ-10380

SDJ-10385

SDJ-10385

RGA-22X221150

SDJ-8245

HVAC-1

SDJ-8250

RGA-22X221375

HVAC-2

HVAC-2

HVAC-2

HVAC-2

HVAC-1 HVAC-1

RGA-22X221000

SDJ-8315

RGA-22X22500

RGA-22X22600

RGA-22X22390

RGA-22X22300

RGA-22X22245

RGA-22X22120

RGA-22X22125

RGA-22X22490

RGA-22X22310

HVAC-1

EX. NG SERVICE & METER

BELL MOUTH

RETURN, TYP.

EF101

CONNECT TO EX. 24X14 DUCT

UP TO GOOSENECK ON ROOF

CTE

CTE

CTE

CTE

CTE

12Ø

EX. 24X24 RA

UP TO HVAC-3

CLASSROOM 3

103

CLASSROOM 1

104

CLASSROOM 2102

RESOURCECENTRE

101

KITCHENETTE

105

LOUNGE106

BUSINESSCENTRE

107

OFFICE 1108

STORAGE112

OFFICE 2109

P.T. STAFF110

MEETING RM.

111

CORRIDOR113

CTE CTE

CROSSTALK

SILENCER, TYP

3

RGA-22X22235

NEW WALL HEATERS,

5.0 KW EACH, TYP.

VAV2-2

VAV1-3

VAV1-4

EX. RA FROM

HVAC-1 ON ROOF

EX. 48X20 SA FROM

HVAC-1 ON ROOF

200REB

107REB

137REB

92REB

309REB

86REB

145REB

258REB

234REB

0REB

80REB

40REB

46REB

221REB

704REB

166REB

158REB

292REB

212REB

183REB

12x12

REB

xREB

282REB

241REB

234REB

3

3

3

3

3

3

3

3

3

3

1

2

10Ø

2

2

2

2

2

2

2

2

2

2

VAV1-2

VAV2-1

VAV2-3VAV2-4

VAV2-3

VAV1-1

VAV1-5

CTE

8Ø20x12

10Ø

10

Ø

24x12

10Ø

10Ø

12Ø

10Ø

10Ø

12

Ø1

12Ø

12Ø

12

Ø

12Ø 12Ø

12Ø

14

Ø

32Ø

16Ø

14

Ø

14Ø

10Ø

10

Ø1

10

Ø

14Ø

16Ø

10

Ø

12Ø

10Ø

12

Ø

12Ø

12

Ø12

Ø

12Ø

32Ø

16Ø

16

Ø

16

Ø

40REB

296REB

120REB

75REB

35REB

14

x14

14

x14

22x14

ACOUSTIC

LINING, TYP

ACOUSTIC

LINING, TYP

XTS5

XTS2

XTS2

XTS3

XTS3

XTS3

TRANSFER

DUCT, TYP

XTS5

XTS5

12Ø

16

Ø18

x18

24x20

2

2

12

Ø

12Ø

12Ø

12Ø

20

x12

12

Ø

12Ø

6x6

20

x12

24x12

NEW VD, BALANCE BYPASS

AS REQD FOR RTU MIN

NEW VD, BALANCE

BYPASS AS REQD

FOR RTU MIN

10Ø8Ø

8Ø 10Ø

8Ø 4Ø

24

x12

24

x10

8Ø 12

x81

2x8

12

x8

10Ø

10

Ø1

10Ø 12Ø

12Ø

24

x12

12Ø

24x1

2

48x20

CTE12Ø

40

x20

40x20

ACOUSTIC

LINING, TYP

NOT IN

SCOPE

EX. HVAC-1

EX. HVAC-4 EX. HVAC-5

EX. HVAC-3EX. HVAC-6

EX. HVAC-7

EX. HVAC-2

EX. CHIMNEY

EX. EXH. DUCT

EX. 1 1/2"Ø NG

EX. 1"Ø NG

EX. 2"Ø NG

EX. 2 1/2"Ø NG

EX. 3"Ø NG

EX. 2"Ø NG

EX. 1"Ø NG

EX. 1 1/2"Ø NG

EX. 1"Ø NG

EX. GOOSENECK

EX. ROOF HATCH

EX. NG SERVICE & METER

EX. GOOSENECK

HVAC NOTES:

1 EX. RTU, REBANLANCE TO MATCH NEW FLOW RATES

2 PROVIDE YORK MODEL OPTIONAL BOLT ON ERV PER SPECS.

1

1

1

1

1

2

EX. EF3

EX. EF2

EX. EF1

EX. EF4

EX. EF5

E

1

2

3

4

5

6

DCBA

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023

SCALE:

FLOOR PLAN - HVAC1/8"=1'-0" SCALE:

ROOF PLAN - HVAC1/8"=1'-0"

M7

FLOOR AND ROOF PLAN - HVAC

1/8" - 1'-0"

2021-08-0921-023

Page 8: M1 - LEGENDS M1

PROJECT No.

DRAWN BY

DATE

CAD FILE

SHEET

ISSUE DATE (Y-M-D) No. ISSUED FOR

CLIENT

SCALE

374 OUELLETTE AVENUE, SUITE 802, WINDSOR, ON, CANADA N9A 1A8, T (519)252-0775, F 252-8559 , E [email protected]

Passa Associates Inc. WWW.PASSA.CA

PROJECT

ARCHITECTS

Please note that all information included in these drawing files is protected by

copyright. Unauthorized use of these files without the written permission of

Passa Associates Inc. Architects is prohibited. Passa Associates Inc. Architects

is responsible only for information shown on a mechanical reproduction of these

drawings that have been signed and stamped by an architect with signing

authority employed by the firm.

If you require further information please contact our office at the numbers listed.

A R C H I T E C T SISSUE DATE (Y-M-D) No. ISSUED FOR

2606WINDSOR CAMPUS720 OUELLETTE AVE., WINDSOR ON.

AUG. 09, 2021

UNIVERSITY OF OTTAWA75 LAURIER AVE. E., OTTAWA, ON.

2021-06-25 1 PROGRESS

2021-06-30 2 PERMIT

2021-07-14 3 FINAL REVIEW

2021-07-27 4 PROGRESS

2021-08-09 5 PERMIT & TENDER

JACE #21-023 M8

DETAILS, DIAGRAMS, & SCHEDULES

AS NOTED

STANDARD CLEVIS PIPE HANGER,

GALVANIZED OR ELECTRO-PLATED

FED. SPEC. WW-H-171E, TYPE I,

OR MSS SP-69, TYPE I

5/8 " ROD, STEEL,

GALVANIZED OR

ELECTRO-PLATED

(THREADED ROD

5/8 " HEX. NUTS WITH

OR ELECTRO-PLATED

BOLT CASING

NEW INSULATION PROTECTION SHIELD,

FED. SPEC. WW-H-171E TYPE 41

AND MSS SP-69 TYPE 40

CONCRETE EXPANSION

FLAT WASHERS, GALVANIZED

NOT ALLOWDED)

CEILING HUNG CLEVIS HANGER

FOR INSULATED PIPE

FLOW

CONCRETE SURFACE OR FLOOR

COVERING AS REQUIRED

CLEANOUT COVER

CSK SCREW

CLEANOUT PLUG

FINISHED FLOOR

CAULKING FERRULE

FLOOR CLEANOUT-FINISHED ROOMSSCALE: NONE

SCALE: NONE

MAY EXTEND ASWASTE OR VENT

FOR WALL CONST.REF. ARCH. DWGS.

POLISHED S.S.ACCESS COVER

CLEANOUT TEE

WASTE LINE LENGTH TO SUIT 1/8" BEND AND END

OF LINE CLEANOUT

WASTE LINE

CLEANOUTPLUG

COUNTERSUNKSCREW

FLOW

WALL CLEANOUT-FINISHED ROOMSSCALE: NONE

DIMENSIONS

BRANCH DUCT

EQUAL TO REQ'D

WIDTH, BUT MIN. 4"

1/4 BRANCH DUCT

AND BOTTOM

1" MIN. ON TOP

MAIN DUCT

AROUND

SEAL ALL

AND BOTTOM

1" MIN. ON TOP

MAIN DUCT

AROUND

SEAL ALL

ELBOW RINGS

ADJUSTABLE

AIRFLOW

SUPPLY

BRANCH DUCT DIA.

EQUAL TO REQ'D

45°45°

BRANCH TAKE OFF FITTINGSCALE: NONE

CONTROL DIAGRAM

SCALE: NONE

THERMOSTAT /

ZONE CONTROLLER

ZONE DAMPER, TYP.

ACTUATOR, TYP

BYPASS DAMPER

SUPPLY AIR SENSOR

RETURN AIR SENSOR

SENSOR / TRANSDUCER

STATIC PRESSURE

OUTDOOR AIR SENSOR

RTU, TYP.

OSA

SUPPLY AIR DUCT

ROOFTOP CONTROLLER

RETURN AIR DUCT

DIRECT EXP.

DDC

CONTROLLER

LOCAL

GRAPHICAL

INTERFACE

(GUI)

NOTE: SEE FLOOR PLANS FOR ACTUAL NUMBER OF ZONES PER RTU.

2021-08-0921-023