    Type M1 00

    Energy Meter

    Type M 100

    Energy Meter

    T & DProtection & Control

  • 8/3/2019 m100enbr_ef

    2/122

    Features

    Active and reactive energy

    metering

    Single phase or three phase

    connection

    Balanced or unbalanced load

    One or two line LCD display

    (one line per counter)

    Pulsed outputs available

    (1 or 2, as an option)

    Setting of CT primary value

    Compact design

    Introduction

    The M100 energy meter usesnumerical technology to achievehigh accuracy over a wide dynamicmeasuring range. It measuresenergy for single or three phasesystems. Housed in a DIN standard96mm by 96mm case, the M100 iscompact, rugged and ideal forpanel mounting in powerdistribution and power monitoringapplications.

    Application

    M100 applications include;

    Energy measurement to

    IEC 61036 Class 1.0

    Replacement/ upgrade of existingenergy meters

    Energy metering for building

    management or power

    management systems using

    pulsed outputs

    The M100 is intended for use onsystems where energy monitoring isrequired, being capable ofproviding display of one or twometering quantities, each of whichcan be specified for active orreactive power, and for import orexport measurement. Options alsoprovide pulsed outputs for 1 or 2measurements. In this application,the M100 provides a more compactsolution than electromagneticdevices.

    Type M 100 Energy Meter

    Functions

    One or two parameters, accordingto the model ordered, selected from:

    Import active energyWhtotalimport

    Export active energyWhtotalexport

    Import reactive energy

    VArhtotalimport

    Export reactive energyVArhtotalexport

    Configuration

    It is possible to modify the followingparameters, using the optional

    external pushbutton:Current transformer primary value

    Reset of energy meters

    Fig 1.: M100

  • 8/3/2019 m100enbr_ef

    3/123

    Fig 2.:Typical diagram - singlephase connection

    1

    3

    2

    k l

    LK

    11

    u v

    U V

    A

    N

    Load

    Notes: Connect two wire auxiliary supply terminals marked supply if fitted.

    Out 1/ Out 2 are volt-free contact pulse outputs, if fitted.

    Out 1 Out 2 Supply

    1

    3

    2 5 8

    u v

    U V

    k l

    LK

    u v

    U V

    Notes: Connect two wire auxiliary supply to terminals marked ' supply' i f fitted.

    Out 1/ Out 2 are volt-free contact pulse outputs, if fitted.

    A

    C

    B

    Load

    Out 1 Out 2 Supply

    11

    1

    3

    2

    u v

    U V

    k l

    K L

    Notes: Connect two wire auxiliary supply to terminals marked ' supply' if fitted.

    Out 1/ Out 2 are volt-free contact pulse outputs, i f fitted.

    A

    N

    B

    C

    Load

    Out 1 Out 2 Supply

    Fig 3.:

    Typical diagram - three phase,three wire balanced load

    Fig 4.:Typical diagram - three phase,four wire balanced load

  • 8/3/2019 m100enbr_ef

    4/124

    Figure 5:Typical diagram - three phase,three wire unbalanced load

    1

    3

    2 8

    9

    5

    7

    u v u v

    U V U V

    k l

    K L

    k l

    K L

    Notes: Connect two wire auxiliary supply to terminals marked ' supply' i f fitted.

    Out 1/ Out 2 are volt-free contact pulse outputs, if fi tted.

    A

    C

    B

    Load

    SupplyOut 1Out 2

    A

    N

    1

    3

    4

    96

    2

    7

    5

    11

    8

    B

    C

    K L

    k l

    k l

    k lK L

    K L

    11u

    x

    u

    x

    u

    x

    X

    U

    X

    U

    X

    U

    Notes: Connect two wire auxiliary supply to terminals marked 'supply' if fitted.

    Out 1/ Out 2 are volt-free contact pulse outputs, i f fitted.

    Load

    Out 1O ut 2 Supply

    DC

    100ms

    Out

    R>100R

    0V

    24V

    Pulse receptorPower supply

    Figure 6:Typical diagram - three phase,four wire unbalanced load

    Figure 7:Connections for pulse output

  • 8/3/2019 m100enbr_ef

    5/125

    Ha rdw are Description

    The M100 is housed in a DIN case

    with maximum dimensions of 96mm by

    96mm by 96mm.

    M100 variants are available for single

    phase systems or 3 phase 3 or 4 wire

    systems, with balanced or unbalanced

    loads.The front panel contains a 1 or 2 line

    alphanumeric liquid crystal display of

    16 characters per line, with a

    character size of 4.86mm by 2.96mm.

    Measuring circuit connections on the

    rear are by means of individual M4

    screw clamp terminals, auxiliary and

    pulsed output connections using M2.5

    terminal blocks. A copy of the relevant

    DIN circuit diagram is printed on a

    label on the device.

    User Interface

    If the external pushbutton option has

    been selected, the configurable

    features of the M100 can be accessed

    through a menu-driven system. The

    menu is arranged as shown below:

    Active and reactive energy are

    displayed when the device is

    switched on.

    Procedure for resetting

    channel 1

    Press the setting button once and hold.

    The above display is shown.The display will show the far right digitcount down from 5 to 0 and thenreturn to the normal working display.The counter should have reset to zero.If the setting button is released beforezero count is reached the counter willnot reset.

    Procedure for resettingchannel 2

    Press the setting button twice and

    hold.

    The above display is shown.

    The display will show the far rightdigit count down from 5 to 0 andthen return to the normal workingdisplay. The counter should havereset to zero. If the setting button isreleased before zero count isreached the counter will not reset.

    Procedure for changing theCT ratio

    1. Press the setting button threetimes and hold until the CT ratiois displayed.

    2. Press the setting button once.Rolling characters, +,, b, Eshould appear in the bottomright hand corner of the display.

    3. Hold the setting button in until Eis displayed, then release. SETwill appear under the CT ratioand an underscore will appearunder the first digit as shownbelow.

    (a) To increase the digits byone, press and hold thesetting button until a + isdisplayed and release. Todecrease the digits hold thesetting button until a isdisplayed and release.Repeat step (a) until thecorrect reading isdisplayed.

    (b) To change to the next digithold the setting button untilE is displayed andrelease. Repeatsteps 1 and 2 until thecorrect CT ratio is set.

    4. W hen changing the CT primarysettings the last digit set shouldbe the far right digit as shownbelow.

    5. Once this digit has been set,press the setting button andrelease when E is displayed.

    6. This will enter the new settinginto the unit. If you finish on anyother digit, the unit will defaultback to the original setting.

    7. If the device is left in the CTsetting mode it willautomatically change to thenormal working display after30 seconds, defaulting to thelatest fully programmed value(ie. any incomplete changeswill be lost).

    * 123456789 Wh000001234 varh

    1* RESET* 5

    2* RESET* 5 CT=00000/ 5

    SET

    CT=00000/ 5SET

  • 8/3/2019 m100enbr_ef

    6/126

    Technical Data

    Accuracy

    Active and reactive energy

    IEC 61036 Class 1.0

    Voltage input

    Standard rated voltages (Vn)

    63.5V, 110V, 230V, 400V

    Optional rated voltage

    50V to 440V

    Voltage measuring range with

    separate auxiliary supply

    0.1 to 1.5Vn

    Self-powered

    0.8 to 1.2Vn

    Burden with auxiliary supply

  • 8/3/2019 m100enbr_ef

    7/127

    Case

    The M100 is housed in a 96mm x

    96mm x 91mm plastic case in

    compliance with UL 94-V0. See

    Figure 8.

    96mm

    96mm 5mm 91mm*

    92mm (+0.8 , 0)

    92mm (+0.8 , 0)

    * includes terminals/ panel fixing

    Terminal 1

    M4Terminals

    Figure 8: Case outline

  • 8/3/2019 m100enbr_ef

    8/128

    Numeric instrumentation

    Panel mounted energy meter

    Application

    Panel mounted energy meter 1

    Connection options

    Single phase 1

    3 phase 4 wire, balanced 2

    3 phase 3 wire, balanced 3

    3 phase 3 wire, unbalanced 4

    3 phase 4 wire, unbalanced 5

    Display options

    Wh only 1

    VArh only 2

    Wh/ VArh 3

    Wh/ W h 4

    VArh/ VArh 5

    CT secondary

    1A 1

    5A 5

    VT secondary63.5V B

    110V E

    230V V

    400V 4

    Frequency

    50 60Hz X

    Auxiliary rating

    63.5 B

    110V E

    230V V

    No. of pulsed outputs

    None 0

    One 1

    Two 2

    External reset facility

    Not fitted 0

    Fitted 1

    M 1

    Informa tion Required w ith Order

  • 8/3/2019 m100enbr_ef

    9/129

    Display 1

    Display 2

    Active energy meter AReactive energy meter R

    Import energy meter I

    Export energy meter E

    Lagging VArs as positive +

    Lagging VArs as negative

    Ex tra informa tion required w ith order

    CT ratio

    VT ratio

    Relay 1 Relay 2

    W h or varh

    Import or export

    Energy per pulse

    Effect of CT primary rating on energy per pulse for 5A secondary

    Table 1

    Notes on ordering

    The standard devices on offer reflect the new normalised European voltage, eg. 230V L-N will work on a 220V or

    240V system. Therefore, if for example a 220V unit is requested, a nominal 230V unit will be supplied.

    NB. The unit of measurement displayed changes according to the change in CT ratio. The energy per pulse is related

    to the displayed value. See Table 1 below for default settings.

    If pulse outputs are required:

  • 8/3/2019 m100enbr_ef

    10/1210

    ALSTOM T&D Protection & Control Business conta ct a ddresses

    Central and South America

    ALSTOM INTERNATIONAL (PERU)Edificio Las NacionesAvenida Central 643 - Piso 1San Isidro - Lima 27 - PERU

    Tel: +51 1 221 7954 / 1208Fax: +51 1 221 [email protected]

    Brazil

    ALSTOM T&D LtdProteco e Control

    Avenida Interlagos 4211CEP-04661-300 So PauloSo Paulo - BRAZIL

    Tel: +55 (0)11 3491 70 00Fax: +55 (0)11 3491 73 0 0pcb-nsa.brazi [email protected]

    South America

    ALSTOM ARGENTINA SAProteccin y ControlAv. Leandro N. Alem 896 - Piso 51001 Buenos Aires - ARGENTINA

    Tel: +54 11 4891 9600 / 9666Fax: +54 11 4311 [email protected]

    A

    T

    W estern Europeand Africa

    United Kingdom and Northen EuropeALSTOM T&D P&C LtdSt Leonards Works - StaffordST17 4LX - UNITED KINGDOM

    Tel: +44 (0)1785 223251Fax: +44 (0)1785 [email protected]

    France, Belgium and Luxembourg,

    Mediterranean and AfricaALSTOM T&D P&C SA

    venue de Figuires34975 Lattes Cedex - FRAN CE

    el: +33 (0)4 67 20 54 54Fax: +33 (0)4 67 20 54 [email protected]

    Italy

    ALSTOM FIR S.p.AViale Giulio Cesare, 2924124 -Bergamo - ITALY

    Tel: +39 035 5791611Fax: +39 035 5791662pcb-wea.i [email protected]

    Spain and Portugal

    ALSTOM T&D, S.A.Paseo de la Castellana, 25728046 Madrid - SPAIN

    Tel: +34 91 334 59 43Fax: +34 91 334 59 [email protected]

    Germanyand Eastern Europe

    Germany and SwitzerlandRussian Speaking Countries

    ALSTOM ENERGIETECHNIK GmbHBereich Schutz- undSchaltanlagenleittechnikLyoner Strae 44-48D 60528 Frankfurt/ Main - GERMAN Y

    Tel: +49 69 66 32 33 33Fax: +49 69 66 32 25 [email protected]

    South East EuropeALSTOM AUSTRIA AGHietzinger Kai 169A1130-Vienna - AUSTRIA

    Tel: +43 1 87893 726Fax: +43 1 87893 [email protected]

    Central EuropeALSTOM T&D SAuI. Strzegomska 23/ 2758-160 Swiebodzi ce - POLAN D

    Tel: +48 74 854 84 10Fax: +48 74 854 85 [email protected]

    M iddle East Asia a nd Pacific

    Middle East AsiaALSTOM T&D P&C Ltd12th Floor, Cresent TowerBuhaira Corniche - PO Box 25448Sharjah - UNITED ARAB EMIRATESTel: +971 6 556 3971Fax: +971 6 556 [email protected]

    India and South AsiaALSTOM INDIA LtdProtection & Control Division19/ 1 GST Road Pallavaram W orks

    Chennai (Madras) 600 043 - INDIATel: +91 44 236 8621Fax: +9144 236 7276pcb-map. [email protected]

    South East AsiaALSTOM T&D P&C Ltd31 Kaki Bukit Road 3#02-05, TechlinkSingapore 417818 - SINGAPORE

    Tel: +65 843 3130Fax: +65 846 [email protected]

    China and North East Asia

    ALSTOM T&D P&C

    Room 910-912, 9th floorNew Kowloon plaza38 Tai kok Tsui roadKowloon, Hong Kong - CHINA

    Tel: +852 2833 6265Fax: +852 2834 [email protected]

    Australia and Pacific IslandsALSTOM AUSTRALIA LtdProtection & Control DivisionPO Box 22, 25 Princes RoadRegents Park, N SW 2143 SydneyAUSTRALIATel: +61 29 645 0777

    Fax: +61 29 743 [email protected]

    PCB Head Office

    ALSTOM T&D P&CLe Sextant3, avenue Andr Malraux923 00 Levallois-Perret - FRAN CE

    Tel: +33 (0)1 41 49 20 00

    Fax: +33 (0)1 41 49 24 [email protected]

    North and South America

    USA, Panama and Caribbean

    Canada

    ALSTOM CANADA Inc.845 Harrington CourtBurlingtonOntario L7N 3P3 - CANADA

    Mexico

    ALSTOM T&D SA DE CVAlce Blanco 13-ANaucalpan de JuarezCP 53370 Mexico City - MEXICO

    Tel: +52 5 358 27 22Fax: +52 5 358 83 93

    [email protected]

    Tel: +1 905 333 3667Fax: +1 905 333 [email protected]

    ALSTOM T&D BITRONICS Inc.261 Brodhead RoadBethlehem, PA18017-8698 - USATel: +1 610 865 2444Fax: +1 610 865 0340

    South AfricaALSTOM MEASUREMENTSPO Box 24Primrose 1416Gauteng, SOUTH AFRICATel: +27 11 820 5111Fax: +27 11 820 [email protected]

    International Contact Centre

    On line 24 hours a day

    Tel: +44 (0)1785 25 00 70Fax: +44 (0)1785 27 24 51

    www.tde.alstom.com/ p-c/ en/ contcent.htm

    ALSTOM T&D ShanghaiPower Automation Co. Ltd1/ B Building - No. 499 Kangyi RoadPudong KangqiaoIndustrial Development ZoneShanghai 201315 - CHINATel : + 86 (21) 5812 8822Fax : + 86 (21) 5812 883 3

  • 8/3/2019 m100enbr_ef

    11/1211

    Your contact:

    Notes:

  • 8/3/2019 m100enbr_ef

    12/12

    ublicati

    on:M100/EN

    BR/Ef

    2 0 0 2

    A L S T O M

    - 0 1 0 2 0 1

    F l a s h E s p a c e

    TRANSM ISSION & DISTRIBUTION Protection & Control, Le Sextant, 3 avenue Andr Malraux, 92 30 0 Levallois-Perret. France

    Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 Email: [email protected] Internet: www.tde.alstom.com

    Contact Centre on line 24 hours a day : +44 (0) 1785 2 7 2 4 5 1

    ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.

    MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.

    Our po licy is one of continuous development. Accordingly the design of o ur products may change at any time. W hilst every effort is made to produce up to date literature, this brochure

    should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product