m4-cgm general purpose application controllers installation...

26
M4-CGM General Purpose Application Controllers Installation Guide Application The CGM09090 General Purpose Application MS/ TP Controller (CGM) are equipment controllers that run pre-engineered and user-programmable applications, and provides the inputs and outputs required to monitor and control a wide variety of HVAC and other facility equipment. CGM controllers operate on an RS-485 BACnet® MS/TP Bus as BACnet Advanced Application Controllers (B-AACs) and integrate into Johnson Controls® and third- party BACnet systems. CGM equipment controllers include an integral real- time clock, which enables the controllers to monitor and control schedules, calendars, and trends, and operate for extended periods of time as stand-alone controllers when offline from the Metasys® system network. Communications Protocols The CGM controllers can communicate using BACnet MS/TP, N2, or wireless Zigbee®. By default, the CGM controllers communicate using the BACnet MS/TP protocol. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls. The CGM controllers can be used as functional replacements for legacy N2 controllers. The N2- capable MS/TP equipment controller models provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. For installation and commissioning support, and tips for efficient and safe replacement, refer to the Modernization Guide for Legacy N2 Controllers (LIT-12012005) and the controller- specific documentation. For information about mapping N2 Objects in controllers with switchable communications protocols, refer to the N2 Compatibility Options chapter of the Controller Tool Help (LIT-12011147). To configure CGM controllers to communicate using the N2 communications protocol, see Configuring N2 communications. The CGM controller can also be installed in a wireless application using aZFR/ZFR Pro Wireless Field Bus Router. To configure these controllers to communicate using the wireless communications protocol, see Configuring wireless communications. North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense. Canada This Class (A) digital apparatus meets all the requirements of the Canadian Interference- Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. Installation Observe the following guidelines when installing a CGM Controller: To minimize vibration and shock damage to the controller, transport the controller in the original container. Verify that all parts shipped with the controller. Do not drop the controller or subject it to physical shock. *241014301698B* Part No. 24-10143-01698 Rev. B 2019-10-18 (For factory use only) M4-CGM09090

Upload: others

Post on 25-May-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

M4-CGM General Purpose ApplicationControllers Installation Guide

ApplicationThe CGM09090 General Purpose Application MS/TP Controller (CGM) are equipment controllersthat run pre-engineered and user-programmableapplications, and provides the inputs and outputsrequired to monitor and control a wide variety ofHVAC and other facility equipment. CGM controllersoperate on an RS-485 BACnet® MS/TP Bus asBACnet Advanced Application Controllers (B-AACs)and integrate into Johnson Controls® and third-party BACnet systems.CGM equipment controllers include an integral real-time clock, which enables the controllers to monitorand control schedules, calendars, and trends, andoperate for extended periods of time as stand-alonecontrollers when offline from the Metasys® systemnetwork.

Communications ProtocolsThe CGM controllers can communicate using BACnetMS/TP, N2, or wireless Zigbee®. By default, theCGM controllers communicate using the BACnetMS/TP protocol. The BACnet protocol is a standardfor ANSI, ASHRAE, and the International StandardsOrganization (ISO) for building controls.The CGM controllers can be used as functionalreplacements for legacy N2 controllers. The N2-capable MS/TP equipment controller modelsprovide a cost-effective upgrade and modernizationpath for customers with existing N2 controllers.For installation and commissioning support,and tips for efficient and safe replacement,refer to the Modernization Guide for Legacy N2Controllers (LIT-12012005) and the controller-specific documentation. For information aboutmapping N2 Objects in controllers with switchablecommunications protocols, refer to the N2Compatibility Options chapter of the Controller ToolHelp (LIT-12011147).To configure CGM controllers to communicate usingthe N2 communications protocol, see ConfiguringN2 communications.The CGM controller can also be installed in awireless application using aZFR/ZFR Pro WirelessField Bus Router. To configure these controllers tocommunicate using the wireless communicationsprotocol, see Configuring wireless communications.

North American EmissionsCompliance

United States

This equipment has been tested and found tocomply with the limits for a Class A digital devicepursuant to Part 15 of the FCC Rules. These limitsare designed to provide reasonable protectionagainst harmful interference when this equipmentis operated in a commercial environment. Thisequipment generates, uses, and can radiate radiofrequency energy and, if not installed and used inaccordance with the instruction manual, may causeharmful interference to radio communications.Operation of this equipment in a residential areamay cause harmful interference, in which case theusers will be required to correct the interference attheir own expense.

Canada

This Class (A) digital apparatus meets all therequirements of the Canadian Interference-Causing Equipment Regulations.

Cet appareil numérique de la Classe (A) respectetoutes les exigences du Règlement sur le matérielbrouilleur du Canada.

InstallationObserve the following guidelines when installing aCGM Controller:• To minimize vibration and shock damage to the

controller, transport the controller in the originalcontainer.

• Verify that all parts shipped with the controller.

• Do not drop the controller or subject it to physicalshock.

*241014301698B*

Part No. 24-10143-01698 Rev. B

2019-10-18

(For factory use only)

M4-CGM09090

Page 2: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Parts included• One CGM controller with removable terminal

blocks (Input/Output, Power, FC, and SA bus areremovable)

• One installation instructions sheet

Materials and special tools needed• Three fasteners appropriate for the mounting

surface (M4 screws or #8 screws)

• One 20 cm (8 in.) or longer piece of 35 mm DINrail and appropriate hardware for DIN rail mount(only)

• Small straight-blade screwdriver for securingwires in the terminal blocks

CGM09090 physical featuresThe following figure displays the physical featuresof the CGM controllers, and the accompanying tableprovides a description of the physical features and areference to further information where required.

Figure 1: CGM09090 Physical Features

Table 1: CGM09090 physical featuresPhysical Feature: Description and References

1 Binary Outputs (BO) Terminal Block: Black terminals; 24VAC Triac (see Table 5)

2Configurable Outputs (CO) Terminal Block: Blackterminals; can be defined as Voltage Analog Output (0-10VDC) or Binary Output (24 VAC Triac) (see Table 5)

3Analog Output (AO) Terminal Block: Black terminals;can be defined as Voltage Analog Output (0-10 VDC) orCurrent Analog Output (4-20 mA) (see Table 5)

4 Device Address Rotary Switch Block: Decimal Addressing(see Setting the device address)

5 Supply Power Terminal Block: Gray terminals; 24 VAC,Class 2 (see Supply power terminal block)

Table 1: CGM09090 physical featuresPhysical Feature: Description and References

6 Cover Lift Tab (see Removing the controller cover)

7 Sensor Actuator (SA) Bus Terminal Block: Orange terminal(see SA bus terminal block)

8 Field Controller (FC) Bus Terminal Block: Blue terminal(see FC bus terminal block (or N2 protocol as required))

9 End-of-Line (EOL) Switch (see Setting the End-of-Line(EOL) switch)

10Universal Serial Bus (USB) 2.0 host type A Port

Note: The USB feature is not currently supported.

11Binary Input (BI) Terminal Block: White terminals; dryContact Maintained or Pulse Counter/Accumulator Mode(see Table 5)

12

Universal Inputs (UI) Terminal Block: White terminals; canbe defined as Voltage Analog Input (0-10 VDC), CurrentAnalog Input (4-20 mA), Resistive Analog Inputs (0-600kohm), or Dry Contact Binary Input (see Table 5)

13 FC Bus Port RJ-12 6-pin Modular Jack (see FC bus port)14 LED Status Indicators (see Table 11)

15 Sensor (SA Bus) Port: RJ-12 6-Pin Modular Jack (see SA Busport)

MountingObserve the following guidelines when mounting aCGM controller:• Ensure the mounting surface can support the

controller, DIN rail, and any user-suppliedenclosure.

• Mount the controller horizontally on 35 mm DINrail whenever possible.

• Mount the controller in the proper mountingposition.

• Mount the controller on a hard, even surfacewhenever possible in wall-mount applications.

• Use shims or washers to mount the controllersecurely and evenly on the mounting surface.

• Mount the controller in an area free of corrosivevapors and observe the Ambient Conditionsrequirements in Table 14.

• Provide for sufficient space around the controllerfor cable and wire connections for easy coverremoval and good ventilation through thecontroller (50 mm [2 in.] minimum on the top,bottom, and front of the controller).

• Do not mount the controller on surfaces prone tovibration, such as duct work.

M4-CGM General Purpose Application Controllers Installation Guide2

Page 3: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

• Do not mount the controller in areas whereelectromagnetic emissions from otherdevices or wiring can interfere with controllercommunication.

On panel or enclosure mount applications, observethe following additional guidelines :• Mount the controller so that the enclosure walls

do not obstruct cover removal or ventilationthrough the controller.

• Mount the controller so that the powertransformer and other devices do not radiateexcessive heat to the controller.

• Do not install the controller in an airtightenclosure.

Figure 2: Controller mounting position

Mounting features and dimensionsSee the Figure 3 for mounting dimensions inmillimeters. Figure 3 also illustrates the DIN railchannel and the mounting clips in an extendedposition.

Figure 3: Back of controller

DIN rail mount applicationsTo mount a CGM controller horizontally on a 35mm DIN rail (recommended method), complete thefollowing steps:

1. Securely mount a 20 cm (8 in.) or longer sectionof 35 mm DIN rail horizontal and centered in thedesired space so that the controller mounts inthe horizontal position.

2. Pull the two bottom mounting clips outwardfrom the controller to the extended position(Figure 3).

3. Hang the controller on the DIN rail by the hooksat the top of the (DIN rail) channel on the backof the controller (Figure 3), and position thecontroller snugly against the DIN rail.

4. Push the bottom mounting clips inward (up) tosecure the controller on the DIN rail.

To remove the controller from the DIN rail,pull the bottom mounting clips out to theextended position and carefully lift the con-troller off the DIN rail.

Wall mount applicationsTo mount a CGM controller directly on a wall orother flat vertical surface, complete the followingsteps:

1. Pull the two bottom mounting clips outwardand ensure they are locked in the extendedposition as shown in Figure 3.

M4-CGM General Purpose Application Controllers Installation Guide 3

Page 4: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

2. Mark the mounting hole locations on the wallusing the dimensions in one of the mountpositions shown in Figure 2. Or hold thecontroller up to the wall or surface in a propermount position and mark the hole locationsthrough the mounting clips.

3. Drill holes in the wall or surface at the markedlocations, and insert appropriate wall anchors inthe holes (if necessary).

4. Hold the controller in place, and insert thescrews through the mounting clips and into theholes (or anchors). Carefully tighten all of thescrews.

Important: Do not over-tighten themounting screws. Over-tightening thescrews may damage the mounting clips.

WiringObserve the following guidelines when wiring a CGMcontroller:

 CAUTION

Risk of Electric Shock:Disconnect the power supply before making electricalconnections to avoid electric shock.

 ATTENTION

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation avant de réaliser tout rac-cordement électrique afin d'éviter tout risque dedécharge électrique.

 CAUTION

Risk of Property Damage:Do not apply power to the system before checking allwiring connections. Short circuited or improperly con-nected wires may result in permanent damage to theequipment.

 ATTENTION

Mise En Garde: Risque de dégâts matériels:Ne pas mettre le système sous tension avant d'avoirvérifié tous les raccords de câblage. Des fils for-mant un court-circuit ou connectés de façon incor-recte risquent d'endommager irrémédiablementl'équipement.

Important: Do not exceed the controllerelectrical ratings. Exceeding controller electricalratings can result in permanent damage to thecontroller and void any warranty.

Important: Use copper conductors only. Makeall wiring in accordance with local, national, andregional regulations.

Important: Electrostatic discharge can damagecontroller components. Use proper electrostaticdischarge precautions during installation,setup, and servicing to avoid damaging thecontroller.

For detailed information about configuring andwiring an MS/TP Bus, FC bus, and SA bus, refer tothe MS/TP Communications Bus Technical Bulletin(LIT-12011034). For detailed information about wiringan N2 network, refer to the N2 Communications BusTechnical Bulletin (LIT-636018).

Terminal blocks and bus portsSee CGM09090 physical features for terminal blockand bus port locations on the CGM controller.Observe the following guidelines when wiring a CGMcontroller.

Input and Output terminal blocksOn the CGM controller models, the input andoutput terminal blocks are removable. All of theinput terminal blocks are mounted on the bottomof the controller, and the output terminal blocksare mounted on the top of the controller. Forinformation about removing a terminal block, seeRemoving a terminal block. For more informationabout I/O terminal functions, requirements, andratings, see Terminal wiring guidelines, functions,ratings, and requirements.

M4-CGM General Purpose Application Controllers Installation Guide4

Page 5: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

FC bus terminal block (or N2 protocol asrequired)The FC bus terminal block is a blue, removable, 4-terminal plug that fits into a board-mounted pinheader.Use a 3-wire twisted, shielded cable, as shown inFigure 4, to wire the removable FC bus terminalblock plugs on the controller, and other controllers,in a daisy-chain configuration. For more informationabout FC Bus terminal functions, requirements, andratings, see Table 7.

Figure 4: FC Bus terminal block wiring

Table 2: FC bus configurationDescription

1 Wiring for a terminating device on the FC bus2 FC bus terminal block plugs3 Wiring for a daisy-chained device on an FC bus segment4 Connects to the next device on the FC bus5 Isolated Shield connection terminal

Note: The FC bus Shield (SHLD) terminal isisolated and can be used to connect (daisychain) the shields for FC bus wiring.

SA bus terminal blockThe SA Bus terminal block is an orange, removable,4-terminal plug that fits into a board-mounted jack.Use a 4-wire twisted, shielded cable, as shown inFigure 5, to wire the removable SA Bus terminalblock plugs on the controller, and other SA busdevices, in a daisy-chain configuration. SeeTerminal wiring guidelines, functions, ratings, andrequirements for more information.

Figure 5: SA Bus Terminal Block Wiring

Table 3: SA bus configurationDescription

1 Wiring for a terminating device on SA bus2 SA bus terminal block plugs3 Wiring for a daisy chained device on SA bus

4

Cable shield connectionNote: Connect the shields to ensure they arecontinuous the entire length with only one groundlocation.

5 Connects to the next device on the SA bus

Note: The POWER terminal supplies 15 VDC.The POWER terminal can be used to connect(daisy chain) the 15 VDC power leads on the SAbus.

Note: Do not use the modular SA Bus port andthe terminal block SA Bus simultaneously. Onlyuse one of these connections at a time.

Note: The CGM controller is the EOL for the SABus.

FC bus portThe FC bus port on the front of the controller isan RJ-12, 6-position modular jack that providesa connection for the Mobile Access Portal (MAP)Gateway, or the ZFR/ZFR Pro Wireless Field BusRouter.The FC bus port is connected internally to the FC busterminal block. See Table 7 for more information.The FC bus port pin assignment is shown in Figure 6.

M4-CGM General Purpose Application Controllers Installation Guide 5

Page 6: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Note: The MAP Gateway serves as areplacement for the BTCVT, which is no longeravailable for purchase, but continues to besupported.

Figure 6: Pin number assignments for FC bus andSA bus ports on equipment controllers

SA Bus portThe Sensor (SA Bus) port on the front of thecontroller is an RJ-12, 6-position modular jack thatprovides a connection for the MAP Gateway, BTCVT,the VAV Balancing Tool, the DIS1710 local controllerdisplay, specified network sensors, or other SABus devices with RJ-12 plugs. When the CGM isconfigured for N2 network communication, youmust download and commission the controller usingthe SA Bus port.

Note: The MAP Gateway serves as areplacement for the BTCVT, which is no longeravailable for purchase, but continues to besupported.

The Sensor port is connected internally to the SA busterminal block. See Table 7 for more information.The Sensor port pin assignment is shown in Figure 6.

Supply power terminal blockThe 24 VAC supply power terminal block is a gray,removable, 2-pin terminal plug that fits into a board-mounted jack on the top right of the controller.Wire the 24 VAC supply power wires from thetransformer to the HOT and COM terminals onthe terminal plug as shown in Figure 7. For moreinformation about the Supply Power Terminal Block,see Table 7.

Figure 7: 24 VAC supply power terminal blockwiring

Table 4: Supply power terminal block wiringDescription

1 Supply power terminal block2 Supply power terminal header

3 Wires from Johnson Controls 24 VAC, class 2 powertransformer

4 24 VAC (Orange wire)5 COM (Brown wire)

Note: The HOT and COM labels are shownbased on the order when looking from the frontof the controller.

Note: The supply power wire colors maybe different on transformers from othermanufacturers. Refer to the transformermanufacturer’s instructions and the projectinstallation drawings for wiring details.

Important: Connect 24 VAC supply powerto the equipment controller and all othernetwork devices so that transformer phasing isuniform across the network devices. Poweringnetwork devices with uniform 24 VAC supplypower phasing reduces noise, interference,and ground loop problems. The equipmentcontroller does not require an earth groundconnection.

Important: Power wires must be less than 30meters between controller and transformer

Terminal wiring guidelines, functions,ratings, and requirementsThis section provides further guidelines on input andoutput wiring, maximum cable length versus loadcurrent, and SA Bus and supply power wiring.For information about removing a terminal blockfrom the controller, see Removing a terminal block.

M4-CGM General Purpose Application Controllers Installation Guide6

Page 7: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Input and Output wiring guidelinesTable 5 provides information and guidelines aboutthe functions, ratings, and requirements for thecontroller input and output terminals, and Table 6also references guidelines for determining properwire sizes and cable lengths.In addition to the wiring guidelines in Table 5,observe these guidelines when wiring controllerinputs and outputs:• Run all low-voltage wiring and cables separate

from high-voltage wiring.

• All input and output cables, regardless of wire sizeor number of wires, should consist of stranded,insulated, and twisted copper wires.

• Shielded cable is not required for input or outputcables.

• Shielded cable is recommended for inputand output cables that are exposed to highelectromagnetic or radio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)typically do not require an offset in the softwaresetup. Cable runs over 30 m (100 ft) may requirean offset in the input/output software setup.

I/O terminal blocks, ratings and requirementsTable 5: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal Block label Terminallabel Function, ratings, requirements Determine wire size and

maximum cable length

+15 V15 VDC Power Source for active (3-wire) input devicesconnected to the Universal INn terminals.Provides 100 mA total current

Same as (Universal) INnNote: Use 3-wire cable fordevices that source powerfrom the +15V terminal.

Analog Input - Voltage Mode (0–10 VDC)10 VDC maximum input voltageInternal 10k ohm Pull-down

See Guideline A in Table 6

Analog Input - Current Mode (4–20 mA)Internal 100 ohm load impedance

Note: Current loop jumpers are fail-safe to maintain aclosed 4 to 20 mA current loop, even when the power tothe controller is interrupted or off. See UI current loopjumpers.

See Guideline B in Table 6.

Analog Input - Resistive Mode (0–600k ohm)Internal 12 V. 15k ohm pull upQualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel[Johnson Controls® sensor], 1k Platinum, and A99B SiliconTemperature Sensor) Negative Temperature Coefficient (NTC)Sensor

See Guideline A in Table 6.

INn

Binary Input - Dry Contact Maintained Mode1 second minimum pulse widthInternal 12 V. 15k ohm pull up

See Guideline A in Table 6.

UNIVERSAL(Inputs)

ICOMnUniversal Input Common for all Universal Input terminals

Note: All Universal ICOMn terminals share a common,which is isolated from all other commons.

Same as (Universal) INn

M4-CGM General Purpose Application Controllers Installation Guide 7

Page 8: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 5: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal Block label Terminallabel Function, ratings, requirements Determine wire size and

maximum cable lengthBinary Input - Dry Contact Maintained Mode0.01 second minimum pulse widthInternal 18 V. 3k ohm pull up

INn Binary Input - Pulse Counter/Accumulator Mode0.01 second minimum pulse width(50 Hz at 50% duty cycle)Internal 18 V. 3k ohm pull up

BINARY(Inputs)

ICOMn

Binary Input Common for all Binary Input (IN) terminalsNote: All Binary ICOMn terminals share a common,which is isolated from all other commons, except theConfigurable Output (CO) common (OCOMn) when theCO is defined as an Analog Output.

See Guideline A in Table 6.

Analog Output - Voltage Mode (0–10 VDC)10 VDC maximum output voltage10 mA maximum output currentRequired an external load of 1,000 ohm or more.

See Guideline A in Table 6.

OUTn

Binary Output - 24 VAC Triac (External Power Source only)Connects OUTn to OCOMn when activated.External Power Source Requirements:30 VAC maximum output voltage0.5 A maximum output current1.3 A at 25% duty cycleMaximum 6 cycles/hour with M9220BGx-340 mA minimum load current

See Guideline C in Table 6.CONFIGURABLE(Outputs)

OCOMn

Analog Output Signal Common All Configurable Outputs(COs) defined as Analog Outputs (AOs) share a common,which is isolated from all other commons except the BinaryInput common.Binary Output Signal Common All Configurable Outputs(COs) defined as Binary Outputs are isolated from all othercommons, including other CO commons.

Same as (Configurable) OUTn.

Analog Output - Voltage Mode (0–10 VDC)10 VDC maximum output voltage10 mA maximum output currentRequired an external load of 1,000 ohm or more.

Note: The Analog Output (AO) operates in the VoltageMode when connected to devices with impedancesgreater than 1,000 ohm. Devices that drop below 1,000ohm may not operate as intended for Voltage Modeapplications.

OUTn

Analog Output - Current Mode (4–20 mA)Requires and external load between 0 and 300 ohm.

Note: The Analog Output (AO) operates in the CurrentMode when connected to devices with impedances lessthan 300 ohm. Devices with impedances greater than300 may not operate as intended for Current Modeapplications.

ANALOG(Outputs)

OCOMn

Analog Output Signal Common for all Analog OUT terminals.Note: All Analog Output Common terminals (OCOMn)share a common, which is isolated from all othercommons.

See Guideline C in Table 6.

M4-CGM General Purpose Application Controllers Installation Guide8

Page 9: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 5: I/O terminal blocks, functions, ratings, requirements, and cables

Terminal Block label Terminallabel Function, ratings, requirements Determine wire size and

maximum cable length

OUTn

Binary Output - 24 VAC Triac (External Power Source)Connects OUTn to OCOMn when activated.External Power Source Requirements:30 VAC maximum output voltage0.5 A maximum output current1.3 A at 25% duty cycleMaximum 6 cycles/hour with M9220BGx-340 mA minimum load current

BINARY(Output)

OCOMn

Binary Output Common (for OUTn terminal)Note: Each Binary Output Common terminal (OCOMn) isisolated from all other commons, including other BinaryOutput Common terminals.

See Guideline C in Table 6.

Cable and wire length guidelinesTable 6 defines cable length guidelines for the various wire sizes that may be used for wiring low-voltage(<30 V) input and outputs. The required wire sizes and lengths for high-voltage (>30 V) Relay Outputs aredetermined by the load connected to the relay, and local, national or regional electrical codes.Table 6: Cable length guidelines

Guideline Wire size/Gauge and type Maximum cable length andtype Assumptions

1.0 mm (18 AWG) stranded copper 457 m (1,500 ft) twisted wire0.8 mm (20 AWG) stranded copper297 m (975 ft) twisted wire 297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper183 m (600 ft) twisted wire 183 m (600 ft) twisted wireA

0.5mm (24 AWG) stranded copper107 m (350 ft) twisted wire 107 m (350 ft) twisted wire

100 mV maximum voltage dropDepending on the cable lengthand the connected input oroutput device, you may haveto define an offset in the setupsoftware for the input or outputpoint.

1.0 mm (18 AWG) stranded copper 229 m (750 ft) twisted wire0.8 mm (20 AWG) stranded copper297 m (975 ft) twisted wire 137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper183 m (600 ft) twisted wire 91 m (300 ft) twisted wireB

0.5 mm (24 AWG) stranded copper107 m (350 ft) twisted wire 61 m (200 ft) twisted wire

100 mV maximum voltage dropDepending on the cable lengthand the connected input oroutput device, you may haveto define an offset in the setupsoftware for the input or outputpoint.

CSee Figure 8 to select wire size/gauge.Use stranded copper wire.

See Figure 8 to determine cablelength.Use twisted wire cable.

N/A

M4-CGM General Purpose Application Controllers Installation Guide 9

Page 10: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Maximum cable length versus loadcurrentUse the following figure to estimate the maximumcable length relative to the wire size and the loadcurrent (in mA) when wiring inputs and outputs.

Note: Figure 8 applies to low-voltage (<30 V)inputs and outputs only.

Figure 8: Maximum wire length for low-voltage (<30 V) Inputs and Outputs by current and wire size

Communications bus and supply powerwiring guidelinesTable 7 provides information about the functions,ratings, and requirements for the communicationbus and supply power terminals. The table alsoprovides guidelines for wire sizes, cable types,and cable lengths for wiring the controller'scommunication buses and supply power.

Important: Refer to the N2 Modernization Guidefor Legacy N2 Controllers (LIT-12012005) forguidelines when you use this device on an N2bus.

In addition to the guidelines in Table 7, observe thefollowing guidelines when you wire an FC or SA busand the 24 VAC supply power:• Run all low-voltage wiring and cables separate

from high-voltage wiring.

• All FC and SA bus cables, regardless of wire size,should be twisted, insulated, stranded copperwire.

• Shielded cable is strongly recommended for all FCand SA bus cables.

• Refer to the MS/TP Communications BusTechnical Bulletin (LIT-12011034) for detailedinformation regarding wire size and cable lengthrequirements for FC and SA buses.

M4-CGM General Purpose Application Controllers Installation Guide10

Page 11: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Communications bus and supply power terminal blocks, ratings, and requirementsTable 7: Communications bus and supply power terminal blocks, functions, ratings, requirements, andcablesTerminal block/Port label

Terminallabels Function, electrical ratings/Requirements Recommended cable type11

+-

FC Bus Communications

COM Signal Reference (Common) for Bus communicationsFC BUS22

SHLD Isolated terminal

0.6 mm (22 AWG) stranded, 3-wiretwisted, shielded cable recommended

FC BUS (Port)2 FC Bus

RJ-12 6-Position Modular Connector provides:FC Bus CommunicationsFC Bus Signal Reference and 15 VDC Common15 VDC, 180 mA, Power for Bluetooth CommissioningConverter (BTCVT) or ZFR or ZFR Pro Wireless Router33

Bluetooth Commissioning Converterretractable cable or 24 AWG 3-pairCAT 3 Cable <30.5 m (100 ft)

+-

SA Bus Communications

COM SA Bus Signal Reference and 15 VDC CommonSA BUS2

SA PWR15 VDC Supply Power for Devices on the SA Bus(Maximum total current draw for SA Bus is 240 mA.)

0.6 mm (22 AWG) stranded, 4-wire(2 twisted-pairs), shielded cablerecommended.

Note: The + and - wire are onetwisted pair, and the COM andSA PWR are the second twistedpair of wires.

SA BUS (Port)2 SA BUS

RJ-12 6-Position Modular Connector provides:SA Bus CommunicationsSA Bus Signal Reference and 15 VDC Common15 VDC Power for devices on the SA bus and BTCVT

24 AWG 3-pair CAT3 cable <30.5 m(100 ft)

HOT24 VAC Power Supply - HotSupplies 20–30 VAC (Nominal 24 VAC)

24~COM

24 VAC Power Supply Common (Isolated from all otherCommon terminals on controller)14 VA

0.8 mm to 1.0 mm(18 AWG) 2-wire< 30 m (100 ft)

1 See Input and Output wiring guidelines to determine wire size and cable lengths for cables other than the recommended cables.2 The FC bus and SA bus wiring recommendations in this table are for MS/TP Bus communications at 38.4k baud. For more

information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).3 The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.

M4-CGM General Purpose Application Controllers Installation Guide 11

Page 12: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Termination diagramsA set of Johnson Controls termination diagrams provides details for wiring inputs and outputs to thecontrollers. See the figures in this section for the applicable termination diagrams.Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

TemperatureSensor UI

Voltage Input -External Source UI

Voltage Input -Internal Source UI

Voltage Input(Self-Powered) UI

M4-CGM General Purpose Application Controllers Installation Guide12

Page 13: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

Current Input -External Source(Isolated)

UI

Current Input -Internal Source (2-wire)

UI

Current Input -Internal Source (3wire)

UI

Current Input -External Source (inLoop)

UI

Feedback fromEPP-1000 UI

M4-CGM General Purpose Application Controllers Installation Guide 13

Page 14: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

Dry Contact(Binary Input) UI or BI

0–10 VDC Outputto Actuator(External Source)

AO

0–10 VDC Outputto Actuator(Internal Source)

AO

Current Output AO

24 VAC TriacOutput (SwitchLow, ExternalSource)

AO

M4-CGM General Purpose Application Controllers Installation Guide14

Page 15: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

Analog Output(Current) AO

4–20 mA Output toActuator AO

4–20 mA Output toActuator AO

IncrementalControl toActuator (SwitchLow, ExternallySourced)

BO

24 VAC BinaryOutput (SwitchLow, ExternallySourced)

BO

M4-CGM General Purpose Application Controllers Installation Guide 15

Page 16: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

24 VAC BinaryOutput (SwitchHigh, ExternallySourced)

BO

IncrementalControl toActuator (SwitchHigh, ExternallySourced)

BO

Network Stat withPhone Jack (FixedAddress = 199)

SA Bus

Note: The bottom jack (J2) on the TE-700 and TE-6x00 Series Sensors is not usable as a zonebus or an SAB connection.

Network Statwith TerminalsAddressable

SA Bus

M4-CGM General Purpose Application Controllers Installation Guide16

Page 17: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 8: Termination detailsType of fielddevice

Type of Input/Output Termination diagrams

Network Stat withTerminals (FixedAddress = 199)

SA Bus

Setup and adjustmentsImportant: Electrostatic discharge candamage controller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

Configuring N2 communicationsN2-capable controllers support the full range ofpossible N2 device addresses provided by the N2protocol standard (1-254).To configure a controller to communicate using theN2 protocol, complete the following steps:

1. Disconnect the 24 VAC supply from thecontroller.

2. Set the address switches to the desired N2address. For details about setting a deviceaddress, see Setting the device address.

3. Reconnect the 24 VAC supply to the controller.

4. Using an SA bus connection, download thefirmware and controller application fileconfigured for N2 to the controller.

Switching the CommunicationsProtocol from N2 to MS/TPFor N2 sites that are converting to BACnet MS/TP,you can switch the communications protocol of N2-configured MS/TP controllers back to BACnet MS/TP.To switch the CGM controller operating in N2mode back into BACnet MS/TP mode, complete thefollowing steps:

1. Disconnect the 24 VAC supply from thecontroller.

2. Set the address switches to the desired BACnetMS/TP address. For details about setting adevice address, see Setting the device address.

3. Reconnect the 24 VAC supply to the controller.

4. Using an SA Bus connection, download acontroller application file configured for BACnetMS/TP to the controller.

Configuring wirelesscommunicationsTo configure a controller for use with the ZFR/ZFRPro Series Wireless Field Bus system, complete thefollowing steps:

1. Disconnect the 24 VAC supply from thecontroller.

2. Wire the input/output terminals and SA bus.

Note: In wireless network applications,do not connect any wires to the FC busterminal block. (Connect the FC/SAterminal block on an IOM to an SA busonly.)

3. Important: Before the CGM controller ispowered on, connect the ZFR/ZFR Pro WirelessField Bus Router to the FC bus port (RJ-12modular jack) on the front of the controller.

M4-CGM General Purpose Application Controllers Installation Guide 17

Page 18: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

4. Ensure that the controller's rotary switches areset to the correct device address. For detailsabout setting a device address, see Setting thedevice address.

5. Reconnect the 24 VAC supply to the controller.

For more information about the ZFR ProWireless Field Bus system, refer to theWNC1800/ZFR182x Pro Series Wireless FieldBus System Product Bulletin (LIT-12012320).For more information about the ZFR 1800Wireless Field Bus system, refer to theZFR1800 Series Wireless Field Bus SystemProduct Bulletin (LIT-12011336).

Setting the device addressMetasys equipment controllers are master deviceson MS/TP (FC or SA) buses. Before you operatecontrollers on a bus, you must set a valid andunique device address for each controller on thebus. You set the CGM device address by setting thepositions of the Device Address rotary switches atthe top of the controller.The following table describes the valid rotaryswitch device addresses for communications busapplications.Table 9: Switch device addressesFC Bus CommunicationMode Valid Device Address Range

Wired MS/TPcommunication

4-127Note: Addresses 0-3 arereserved and not for use onequipment controllers.

Zigbee wirelesscommunication

4-127Note: Addresses 0-3 arereserved and not for use onequipment controllers.

N2 communication

1-254Note: Addresses 0 and 255 arereserved and not for use onequipment controllers.

Note: The controller auto-detects if thecommunication protocol is wired MS/TP, ZigbeeWireless, or N2 on the FC Bus.

The device address is a decimal address that isset using three rotary switches. The numbersare ordered from left to right, most significantbit (MSB) to least significant bit (LSB) when thecontroller is oriented as shown in CGM09090physical features. In the following figure, the

switches are set to 1 2 3, designating thiscontroller's device address as 123.

Figure 9: Device address rotary switch block

The device address must match the deviceaddress defined in the Controller ConfigurationTool (CCT) under Define Hardware > NetworkSettings.

To set the device addresses on CGM controllers,complete the following steps:

1. Set a unique and sequential device address foreach of the equipment controllers connectedon the FC or SA Bus, starting with deviceaddress 4.

2. To ensure the best bus performance, setsequential device addresses with no gaps inthe device address range (4, 5, 6, 7, 8, 9, andso on). The equipment controllers do not needto be physically connected on the bus in theirnumerical device address order.

3. Write each controller's device address on thewhite label below the device address rotaryswitch block on the controller's cover.

Refer to the MS/TP Communications BusTechnical Bulletin (LIT-12011034) for moreinformation about controller deviceaddresses and how to set them on MS/TPbuses.

Removing a terminal blockTo remove the terminal block from the circuit board,complete the following steps:

Note: You need a flat blade screwdriver toremove the terminal block.

M4-CGM General Purpose Application Controllers Installation Guide18

Page 19: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

1. To prevent any possibility of damage from anaccidental short, remove power from thecontroller.

2. Underneath the terminal block, in the small gapbetween the bottom of the terminal block andthe circuit board, insert the flat blade of thescrewdriver.

Figure 10: Terminal block

3. To detach the left-hand side of the terminalblock, position the flat blade underneath theterminal block to the left, and push down thescrewdriver handle. When you do this, you areusing the screwdriver as a lever to pry up theterminal block.

4. To detach the right-hand side of the terminalblock, position the flat blade underneath theterminal block to the right, and push down thescrewdriver handle.

5. If necessary, repeat steps 3 and 4 until theterminal block is removed.

Removing the controller coverImportant: Electrostatic discharge candamage controller components. Use properelectrostatic discharge precautions duringinstallation, setup, and servicing to avoiddamaging the controller.

Important: Disconnect all power sourcesto the controller before removing cover andchanging the position of any jumper or the EOLswitch on the controller. Failure to disconnectpower before changing a jumper or EOL switchposition can result in damage to the controllerand void any warranties.

The controller cover is held in place by fourplastic latches that extend from the base andsnap into slots on the inside of the housingcover.

To remove the controller cover, complete thefollowing steps:

1. Place your fingertips under the two cover lifttabs (CGM09090 physical features) on the sidesof the housing cover and gently pry the top ofthe cover away from the base to release thecover from the two upper latches.

2. Pivot the top of the cover further to release itfrom the lower two latches.

3. Replace the cover by placing it squarely overthe base, and then gently and evenly push thecover on to the latches until they snap into thelatched position.

Cover removed, EOL switch, and currentjumpers

Figure 11: CGM with cover removed showing EOLswitch and jumper positions

Setting the End-of-Line (EOL) switchEach CGM controller has an EOL switch, which, whenset to ON (up), sets the controller as a terminatingdevice on the bus. See Figure 11 for the EOL switchlocation. The default EOL switch position is OFF(down).

Figure 12: End-of-Line switch positions

To set the EOL switch on a controller, complete thefollowing steps:

M4-CGM General Purpose Application Controllers Installation Guide 19

Page 20: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

1. Determine the physical location of thecontroller on the FC bus.

2. Determine if the controller must be set as aterminating device on the bus.

Note: For detailed information aboutEOL termination rules and EOL switchsettings on FC buses, refer to the MS/TP Communications Bus Technical Bulletin(LIT-12011034).

3. If the controller is a terminating device onthe FC bus, set the EOL switch to ON. If thecontroller is not a terminating device on thebus, set the EOL switch to Off.

When a controller is connected to powerwith its EOL switch set to ON, the amberEOL LED on the controller cover is illumi-nated.

Setting the input jumpers

 CAUTION

Risk of Electric Shock:Disconnect supply power to the field controller beforeattempting to adjust the Binary Output Source PowerSelection Jumpers. Failure to disconnect the supplypower may result in electric shock.

 ATTENTION

Mise En Garde: Risque de décharge électrique:Débrancher l'alimentation de l'controller avant toutréglage du Binary Output Source Power SelectionJumpers. Le non-respect de cette précaution risquede provoquer une décharge électrique.

UI current loop jumpersThe UI current loop fail-safe jumpers are on thecircuit board under the controller cover near the UIterminals (Figure 11). When a UI is defined (in thesystem software) as a 4-20 mA Analog Input and theUI’s current loop jumper is in the Disabled (default)position (Figure 13), the internal 100 ohm loadresister is disconnected and the 4-20mA currentloop is open.

Figure 13: Exchange enable and default settings

Setting the current loop jumper to the Enabledposition, (Figure 13) connects an internal 100 ohmresistor across the UI terminals, which maintains the4-20 mA current loop circuit even when power to thecontroller is interrupted or off.

Important: Current Loop jumpers must be inthe Disabled (default) position for all UIs thatare not set up to operate as 4-20 mA analoginputs.

The following table identifies the current loopswitches associated with each UI on the CGMcontroller.Table 10: CGM UI Inputs and jumper labelsUniversal Inputlabel Jumper label on circuit board

IN1 J13IN2 J14IN3 J15IN4 J16IN5 J17IN6 J18IN7 J19

Setting up a local displayCGM models do not have an integral display, butcan be connected to a DIS1710 Local ControllerDisplay. For detailed information about settingup and operating a remotely connected DIS1710display, refer to the DIS1710 Local Controller DisplayTechnical Bulletin (LIT-12011270) .

Input/Output Wiring ValidationThe CGM controllers ship with a default state thatcan assist in validating the wiring of the input andoutput terminals prior to download of an applicationfile. When the controller is powered on in this state,the Fault LED will flash in a pattern of two quickblinks and then a long pause (see Table 11).To make use of this feature, ensure the rotaryswitches are set to the desired address and wire theinput and output terminals. Apply power to the CGM

M4-CGM General Purpose Application Controllers Installation Guide20

Page 21: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

controller and connect to the device with either aMAP Gateway or MS-DIS1710-0 Local Display to viewthe points in the controller. The CGM controller willreport an Operational status even though there isno true application loaded. CCT will not be able tocommission or upload the device as a result untila true application is downloaded. The applicationname displayed will be the address of the controllerfollowed by the model of the controller and “DefaultState”.For example, a CGM09090 controller whose rotaryswitches are set to 8 would have the default stateapplication name of “8-CGM09090 Default State”.The default state creates I/O points for allconnections on the input and output terminals.It assumes all Universal Inputs (UIs) are Nickeltemperature sensors. All Configurable Outputs(COs) are treated as Binary Outputs (BOs) with aninitial value of 0. The default state also takes inputfrom a Network Sensor at address 199. If there isno connected Network Sensor, the startup of thisdefault state will be delayed by 30 seconds as thecontroller attempts to establish connection with thesensor.

Commissioning equipmentcontrollersYou commission MS/TP equipment controllers withthe CCT software using either MAP Gateway , aBTCVT, a ZFR wireless dongle, or in passthroughmode when connected to an NAE or NCE. Fordetailed information about commissioningfield controllers, refer to Controller Tool Help(LIT-12011147).

Note: You can use the Bluetooth connectionto Transfer to Computer (Upload) andcommission the controller, but you cannot usethe Bluetooth connection to Transfer to Device(Download).

Note: The MAP Gateway serves as areplacement for the BTCVT, which is no longeravailable for purchase, but continues to besupported.

Troubleshooting equipmentcontrollersObserve the Status LEDs on the front of theequipment controller. Table 11 provides LEDstatus indicator information for troubleshootingthe controller. To troubleshoot an integral orlocal controller display, refer to the DIS1710 LocalController Display Technical Bulletin (LIT-12011666).

M4-CGM General Purpose Application Controllers Installation Guide 21

Page 22: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

LED status and statesTable 11: Status LEDs and description of LED statesLED label LED color Normal LED state Description of LED states

POWER Green On SteadyOff Steady = No Supply Power or the controller’s polyswitch/resettable fuse isopen. Check Output wiring for short circuits and cycle power to controller.On Steady = Power Connected

FAULT Red Off Steady

2 blinks followed by long pause = Controller powered on in default state. For moreinformation about this default state, see Input/Output Wiring Validation.Off Steady = No FaultsOn Steady = Device Fault; no application loaded; Main Code download required, ifcontroller is in Boot mode, or a firmware mismatch exists between the CGM andthe ZFR1811 Wireless Field Bus Router.Blink - 2 Hz = Download or Startup in progress, not ready for normal operationRapid blink = SA Bus communications issue

SA BUS Green Blink - 2 HzBlink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (N/A - auto baud not supported)On Steady = Communication lost, waiting to join communication ring

FC BUS Green Blink - 2 HzBlink - 2 Hz = Data Transmission (normal communication)Off Steady = No Data Transmission (auto baud in progress)On Steady = Communication lost, waiting to join communication ring

EOL AmberOff (Except onterminatingdevices)

On Steady = EOL switch in ON positionOff Steady = EOL switch in Off position

Repair informationIf an equipment controller fails to operate withinits specifications, replace the controller. For areplacement controller, contact your JohnsonControls representative.

M4-CGM General Purpose Application Controllers Installation Guide22

Page 23: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Ordering information andaccessoriesThe following tables provide the product code number and description for the CGM models and accessories.Table 12: CGM Series ordering informationProduct code number Description

M4-CGM09090-0General Purpose Application ControllerIncludes: MS/TP (and N2) communication; 18 points (7 UI, 2 BI, 4 CO, 2 AO, 3 BO); real-time clock; 32-bitmicroprocessor; 24VAC input

Table 13: CGM Controller accessories (order separately)Product Code Number Description

IOM Series ControllersRefer to the Metasys® System Field Equipment Controllers and Related ProductsProduct Bulletin (LIT-12011042) for a complete list of available IOM SeriesControllers.

TL-CCT-0 License enabling Metasys Controller Configuration Tool (CCT) software for oneuser

MS-FCP-0 License enabling Metasys Equipment Controller Firmware Package Files requiredfor CCT

Mobile Access Portal (MAP) Gateway

Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify theappropriate product for your region.

Note: The MAP Gateway serves as a replacement for the BTCVT, which is nolonger available for purchase, but continues to be supported.

MS-DIS1710-0 Local Controller Display

NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specificsensor model descriptions.

AS-CBLTSTAT-0 Cable adapter for connection to 8-pin TE-6700 Series sensorsNS-WALLPLATE-0 Network Sensor Wall Plate

WRZ Series Wireless Room Sensors Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653) forspecific sensor model descriptions.

WRZ-7860-0 Refer to the WRZ-7860 Receiver for One-to-One Wireless Room Sensing ProductBulletin (LIT-12011640) for a list of available products.

WRZ-SST-120 Refer to the WRZ-SST-120 Wireless Sensing System Tool Installation Instructions(LIT-24-10563-55) for usage instructions.

WNC1800/ZFR182x Pro Wireless Field Bus System Refer to the WNC1800/ZFR182x Pro Series Wireless Field Bus System Product Bulletin(LIT-12012320) for a list of available products.

ZFR1800 Series Wireless Field Bus System Refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336)for a list of available products.

ZFR-USBHA-0

ZFR USB Dongle provides a wireless connection through CCT to allow wirelesscommissioning of the wirelessly enabled CGM, CVM, FAC, FEC, VMA16, and IOMcontrollers. It also allows use of the ZFR Checkout Tool (ZCT) in CCT.

Note: The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZFR USB dongle.For additional information about the ZFR-USBHA-0 ZFR dongle, refer to theZCT Checkout Tool Help LIT-12012292 or the WNC1800_ZFR182x Pro SeriesWireless Field Bus System Technical Bulletin (LIT-12012356).

Y64T15-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount,72.2 cm (30 in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2

Y65A13-0 Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AS),20.32 cm (8 in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2

Y65T31-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount(Y65AR+), 20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2

Y65T42-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount(Y65SP+), 20.32 cm (8 in.), Primary Leads and Secondary Screw Terminals, Class 2

M4-CGM General Purpose Application Controllers Installation Guide 23

Page 24: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 13: CGM Controller accessories (order separately)Product Code Number Description

MS-FIT100-0

The Field Inspection Tool or (FIT) is a portable handheld device with a userinterface that is used to test and troubleshoot the BACnet protocol MS/TP RS-485communications bus that connects supervisory controllers and equipmentcontrollers to field point interfaces.The FIT can be used to check out the wiring of the MS/TP RS-485 bus as wellas verify proper communications of supervisory controllers and equipmentcontrollers connected to the bus. The FIT can be used on both the FC Bus and SABus.

TL-BRTRP-0 Portable BACnet/IP to MS/TP Router

M4-CGM General Purpose Application Controllers Installation Guide24

Page 25: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Technical specificationsTable 14: Technical specifications

Product Code NumbersM4-CGM09090-0 General Purpose Application ControllerIncludes: MS/TP (and N2) communication; 18 points (7 UI, 2 BI, 4 CO, 2 AO, 3 BO); real-time clock; 32-bit microprocessor; 24VAC input

Power Requirement 24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2(North America), Safety Extra-Low Voltage (SELV) (Europe)

Power Consumption

14 VA maximumNote: The USB feature is not currently supported.

Note: The VA rating does not include any power supplied to the peripheral devicesconnected to Binary Outputs (BOs) or Configurable Outputs (COs), which canconsume up to 12 VA for each BO or CO; for a possible total consumption of anadditional 84 VA (maximum).

Power Source +15 VDC power source terminals provide 100 mA total current. Quantity 2 located inUniversal IN terminals - for active (3-wire) input devices

Ambient ConditionsOperating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensingStorage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing

Network Engines All network engine model types

Communications Protocol BACnet MS/TP; N2. Wireless also supported (at FC Bus and for Sensors) with additionalhardware.

Device Addressing for BACnet MS/TP Decimal address set via three rotary switches; valid controller device addresses 4-127Device Addressing for N2 Decimal address set via three rotary switches: valid controller device addresses 1-254

Communications Bus

BACnet MS/TP (default); N23-wire FC Bus between the supervisory controller and equipment controllers4-wire SA Bus between equipment controller, network sensors and other sensor/actuatordevices, includes a lead to source 15 VDC supply power (from equipment controller) tobus devices.

Processor RX64M Renesas® 32-Bit microcontrollerMemory 16 MB flash memory and 8 MB SDRAM

Real-Time Clock Backup Power Supply Super capacitor maintains power to the onboard real-time clock for a minimum of 72hours when supply power to the controller is disconnected.

Input and Output Capabilities

Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohms, or Binary Dry ContactBinary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator ModeConfigurable Outputs Defined as 0-10 VDC or 24 VAC Triac BOAnalog Outputs: Defined as 0–10 VDC or 4–20 mABinary Outputs: Defined as 24 VAC Triac (external power source only)

Universal Input (UI) Resolution/ AnalogOutput (AO) Accuracy

Input: 24-bit Analog to Digital converterOutput: +/- 200 mV accuracy in 0–10 VDC applications

TerminationsInput/Output: Pluggable Screw Terminal BlocksSA/FC Bus and Supply Power: 4-Wire and 2-Wire Pluggable Screw Terminal BlocksSA/FC Bus Port: RJ-12 6-Pin Modular Jacks

Mounting Horizontal on single 35 mm DIN rail mount (recommended), or screw mount on flatsurface with three integral mounting clips on controller

HousingEnclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishingProtection Class: IP20 (IEC529)

Dimensions (Height x Width x Depth)

150 mm x 190 mm x 44.5 mm (5-7/8 in. x 7-1/2 in. x 2-1/8 in.) including terminals andmounting clips

Note: Mounting space requires an additional 50 mm (2 in.) space on top,bottom, and front face of controller for easy cover removal, ventilation, and wireterminations.

Weight 0.5 kg (1.1 lb)

M4-CGM General Purpose Application Controllers Installation Guide 25

Page 26: M4-CGM General Purpose Application Controllers Installation Guidecgproducts.johnsoncontrols.com/MET_PDF/241014301698.pdf · capable MS/TP equipment controller models provide a cost-effective

Table 14: Technical specificationsUnited States: UL Listed, File E107041, CCN PAZX, UL 916, Energy ManagementEquipmentFCC Compliant to CFR47, Part 15, Subpart B, Class ACanada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No. 205, Signal EquipmentIndustry Canada Compliant, ICES-003Europe: Johnson Controls declares that this product is in compliance with the essentialrequirements and other relevant provisions of the EMC Directive nd RoHS Directive.Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant

Compliance

BACnet International: BACnet Testing Laboratories™ (BTL) Protocol Revision 15 Listedand Certified BACnet Advanced Application Controller (B-AAC), based on ANSI/ASHRAE135-2016

The performance specifications are nominal and conform to acceptable industry standard. For application atconditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not beliable for damages resulting from misapplication or misuse of its products.

Product warrantyThis product is covered by a limitedwarranty, details of which can be found atwww.johnsoncontrols.com/buildingswarranty.

Single point of contactAPAC Europe NA/SAJOHNSON CONTROLS

C/O CONTROLS PRODUCTMANAGEMENT

NO. 32 CHANGJIJANG RD NEWDISTRICT

WUXI JIANGSU PROVINCE 214028

CHINA

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision andare subject to change without notice.

www.johnsoncontrols.com