maintenance sheet c. wiring diagram and check point of the ... · pdf filecheck if the...
TRANSCRIPT
Maintenance sheet 68A166
B. Error codes031: Incorrect DIPswitch setting ・Check the DIPswitch settings on the PCB. Refer to Section D.
101: Warning for the “991” error code ・Check the gas type of the house (and/or the bulding). ・Check if there is any blockage in the intake air and/or exhaust. Refer to the “Vent termination clearances” of the installation manual. ・If the water heater is installed as a direct-vent system, check whether there is enough distance between the intake air terminal and the exhaust terminal. Refer to the “Vent termination clearances” of the installation manual. ・Check if the total vent length. Refer to the "Venting instructions" of the Installation manual. ・Check the altitude/elevation of area of where the water heater installed. Refer to the “High-altitude function” of the Section D. And change the DIPswitch settings. ・Check if there is grease and/or dirt in the burner (Part #101) and the fan motor (Part #103), especially if the water heater has been installed in a contaminated area. ・Check if there is dust and lint in heat exchanger. ・Check the manifold pressure of the water heater. Refer to installation manual.111: Ignition failure 1. Check gas supply and inlet gas pressure. 2. Check if the Hi-limit switch (Part #412) is properly functioning. 3. Check for connection/breakage of wires (Part #413, 708, 709, 710, 712), and/or soot on the flame rod (Part #108). And then if O.H.C.F (Part #413) is breakage, Consult the manufacturer. 4. Check if there is a buzzing spark ignition sound coming from the burner (Part #101) when water heater prepares for combustion. 5. Listen for the double “clunk” sound coming from the gas valve assembly (Part #102) when water heater goes into combustion. 6. (Only no sparking and/or kick sound) Check voltage on each wire to gas valves assembly (Part #102) and/or the igniter (Part #711). Refer to the “Appendix A” in Section C. *No sparking sound >>>>> Refer to the #1 at “Appendix A” in Section C. *No kick sound >>>>> Refer to the #2 at “Appendix A” in Section C. 7. Check if there is leaking from heat exchanger (Part #401) 8. Check if there is dust and lint in nozzles of the manifold (Part #102). 9. Check current on the flame rod (Part #108). Refer to the #3 at “Appendix A” in Section C. 121: Loss of flame 1. Check gas supply and inlet gas pressure. 2. Check if the Hi-limit switch (Part #412) is properly functioning. 3. Check for connection/breakage of wires (Part #413, 708, 709, 712), burn marks on the computer board (Part #701), and/or soot on the flame rod (Part #108). And then if O.H.C.F (Part #413) is breakage, Consult the manufacturer. 4. Check if there is leakage from heat exchanger (Part #401). 5. Check if there is dust and lint in nozzles of the manifold (Part #102). 6. Check current on the flame rod (Part #108). Refer to the #3 at “Appendix A” in Section C.311,321,331,341*: Disconnected/short-circuited thermistor ・Check for connection/breakage of wires and/or debris on thermistor (Part #407, 408, 411, 715, 718). ・Check thermistor resistance. Refer to the “Appendix D” in Section C.391: Air-fuel Ratio Rod failure ・Check for connection/breakage of wires (Part #709) and/or soot on the frame rod (Part #108).441: Flow sensor failure (Only Easy-Link system) ・Check for connection/breakage of wires and/or debris on the flow sensor impeller (Part #402).
510,551: Abnormal Main and Solenoid Gas Valve ・Check for connection/breakage of wires (Part #708) and/or burn marks on the computer board (Part #701). ・Reset power supply of the water heater. ・ Check voltage of each valve on the gas valves assembly (Part #102). Refer to the “Appendix C” in Section C.611: Fan motor fault ・Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or burn marks on the computer board (Part #701). ・Check for frozen/corrosion of connectors of the fan motor (Part #103). ・Check voltage between blue wire and each wire of the fan motor (Part #103). Refer to the “Appendix B” in Section C.651: Flow adjustment valve fault (Only Easy-Link system) ・Inspect the flow adjustment valve (Part #402), for connection/breakage of wires, locked motor drive due to scale buildup, and/or water leakage. ・Check voltage between black wire and red wire. Refer to the “Appendix F” in Section C.661: Bypass valve fault ・Inspect the bypass valve (Part #403), for connection/breakage of wires, locked motor drive due to scale buildup, and/or water leakage. ・Check voltage between brown wire and red wire. Refer to the “Appendix F” in Section C.701,711: Computer board fault ・Check for connection/breakage of wires (Part #714), and check resistance between white wire and red wire. Refer to the “Appendix A” in Section C.721: False flame detection 1. Clean the flame rod (Part #108). 2. Check if there is leaking from heat exchanger (Part #401).741: Miscommunication between water heater and remote controller 1. Check the model type of the remote controller. Model No. 9008172005 (TM-RE40) is the correct one. 2. Inspect the connections between the water heater and remote controller. Refer to the “Remote controller connections” of the Installation manual. 3. Check the power supply of the water heater. 4. If this error code appears only the green LED on the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to the “Appendix E” in Section C. 5. If this error code appears only remote controller, replace the PCB (Part #701). 6. If this error code appears both the PCB (Part #701) and the remote controller, replace the remote controller.751*: Miscommunication between water heater and temperature controller 1. Check the power supply of the water heater. 2. If this error code appears only the green LED on the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to the “Appendix E” in Section C. 3. If this error code appears only temperature controller, replace the PCB (Part #701). 4. If this error code appears both the PCB (Part #701) and the temperature controller, replace the temperature controller.761: Miscommunication between Parent unit and Child units for Easy-link system ・Check if the connections between the parent unit and the child units are correct. Refer to “Easy-Link system” section in the Installation manual.941*: Abnormal exhaust temperature (Only 540 (T-H3) Direct Vent Indoor) ・Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or burn marks on the computer board (Part #701). ・Check exhaust thermistor resistance. Refer to the "Appendix D" in Section C.991: Imperfect combustion ・Refer to the “101” error code in this section.
C. Wiring Diagram and check point of the Water heater
Appendix A (For error code 111)
Check these points during ignition stage. # 1. Refer to check point “B” on the wiring diagram above. Check voltage between purple wires. (Normal: 108 to 132 VAC) This Check point is normal? Yes >> Replace the igniter. (Part #711) No >> Go to Next. # 2. Refer to check point “C” and “H1” on the wiring diagram above. Check the voltages below: C: Between blue wire and light blue wire (#3). (Normal: 93 to 120 VDC) C: Between blue wire and orange wire (#53). (Normal: 93 to 120 VDC) H1: Check the voltage between white wire and red wire. (Normal: 1 to 15 VDC) These check points are normal? Yes >> Replace the gas valves assembly. (Part #102) No >> Replace the PCB. (Part #701) # 3. Check current thought the yellow flame rod wire (Part #709). (Normal: more than 5 μA) This check point is normal during operation? Yes >> Replace the PCB. (Part #701) No >> Replace the flame rod. (Part #108)
Appendix B (For error code 611) Refer to check point “G” in the diagram to the left and the following. • Check voltage between red wire and blue wire. (Normal: 132 to 192 VDC) • Check voltage between yellow wire and blue wire. (Normal: 13 to 17 VDC) • Check voltage between orange wire and blue wire. (Normal: 2.0 to 6.5 VDC) All check points are normal? Yes >> Replace the fan motor. (Part #103) No >> Replace the PCB. (Part #701)
Appendix C (For error code 510 and 551) Refer to check point “C” in the diagram to the left and followings. Check voltage on the each valve on the gas valves assembly. • Between blue wire and light blue wire (#3). (Normal: 93 to 120 VDC) • Between blue wire and green wire (#9). (Normal: 93 to 120 VDC) • Between blue wire and orange wire (#53). (Normal: 93 to 120 VDC) • Between blue wire and red wire (#73). (Normal: 93 to 120 VDC) All check points are normal? Yes >> Replace the gas valves assembly. (Part #102) No >> Replace the PCB. (Part #701)
Appendix D (For error code 311, 321, 331, 341, and 941) • Outlet thermistor (Find the marking of No.113 on the connector) Check point “E1” • Inlet thermistor (Find the marking of No.42 on the connector) Check point “E2” • Heat exchanger thermistor (Find the marking of No.12 on the connector) Check point “E3” Check resistance between black wire and black wire.
• Exhaust thermistor Check point “K1” Check resistance between white wire and white wire.
All check points are normal? Yes >> Replace the PCB. (Part #701) No >> Replace the wrong thermistor. (Part #407, 408, 411, 718)
Appendix E (For error code 741 and 751) Error code 741: Refer to check point “F” on the wiring diagram above. Error code 751 : Refer to check point “L” on the wiring diagram above. Check voltage on the remote controller and/or temperature controller on the PCB. • Between black wire and white wire. (Normal: 11 to 25 VDC) This check point is normal? Yes >> Replace the remote controller and/or temperature controller. No >> Replace the PCB. (Part #701)
If the error code is indicated on green LED (Refer to the Section C) on the PCB (Part #701) of the water heater (and/or the remote controller), refer to Section B.<< It takes long time to get hot water at the fixtures >> ・The time it takes to deliver hot water from the water heater to your fixtures depends on the length of piping between the two. The longer the distance or the bigger the pipes, the longer it will take to get hot water. ・If you would like to receive hot water to your fixtures quicker, you may want to consider a hot water recirculation system.<< The water is not hot enough or turns cold and stays cold >> ・Compare the flow and temperature. Refer to the “Output temperature chart” of the installation manual. ・Check cross plumbing between cold water lines and hot water lines. ・Check if the gas supply valve fully open, the gas line sized properly and the gas supplies pressure enough. Refer to the “Gas supply and gas pipe sizing” of the installation manual. ・Check the set temperature, and change the set temperature with the remote controller or the DIPswitch setting. Refer to Section D. ・Refer to “Water circuit” in this section.<<The water is too hot>> ・Check the set temperature, lower setting temperature.<<The hot water is not available when a fixture is opened>> ・Refer to the “Power supply circuit” and “Water circuit” in this section.<<Fluctuation in hot water temperature>> ・Check if the filter on the cold water inlet cleaned. (Part #406) ・Check if the gas line sized properly and the supply gas pressure sufficient. ・Check for cross connection between cold water lines and hot water lines. ・Refer to “Water circuit” in this section.<<Unit does not ignite when water goes through the water heater>> ・Refer to the “Power supply circuit” and “Water circuit” in this section. ・If you use the remote controller, turn the power button on and then the STAND BY LED will light up. ・Check if the filter on the cold water inlet cleaned. (Part #406) ・Refer to “Water circuit” in this section.
A. Troubleshooting <<The fan motor still spinning after operation has stopped>> ・This is normal. After operation has stopped, the fan motor keeps running from 15 to 70 seconds in order to re-ignite quickly, as well as purge all the exhaust gas out of the flue.<<Abnormal sound from water heater>> ・An abnormal sound from the water heaters is caused by not enough air supply or wrong installations. The water heater needs more combustion air. Refer to the “101” error code in the section B.<<Power supply circuit>> 1. If the remote controller installed, press the “ON/OFF” button of the remote controller, and make sure that the STAND BY LED next to the “ON/OFF” button of the remote controller is lit. Restart the water heater. 2. Check if that the green LED on the PCB (Part #701) of the water heater is lit. If so, the power supply circuit of the water heater is under normal condition. Next, refer to the “Water circuit” in this section. 3. Check the fuse on the surge box (Part #703), and if it has a brown spot, need to replace it. 4. Check the power supply, and make sure that the water heater has 120 VAC. 5. If the green LED on the PCB (Part #701) isn’t lit, some electrical parts can be broken. Consult the manufacturer.<<Water circuit>> 1. If you set the remote controller, turn the power button on and then the STAND BY LED will light up. 2. Open all hot water faucets, and make sure that there is enough water flow. This water heater needs at least 0.5 GPM water flow (at the default set temperature) to operate. 3. Check for reverse connection and cross connection. 4. Check if the filter on the cold water inlet cleaned. (Part #406) 5. Check if there is no debris or obstruction on the fixtures. 6. Check if water ways in the water heater are frozen. If so, unfreeze them. And refer to installation manual to protect your water heater from freezing. 7. Check if the inlet water pressure is higher than 40 psi. And if it’s lower than 40 psi, need to increase the pressure. 8. Check for connections and breakage of wires (Part #402). 9. Check if the motor drive of the flow adjustment valve (Part #402) is locked due to scale buildup, and/or water leakage. Consult the manufacturer.
Temperature°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance kΩ 15.4 12.6 10.3 8.5 7.0 5.9
ATH3W: WHITER: RED
BK: BLACK
P: PURPLE
LB: LIGHT BLUEBL: BLUE
G: GREENY: YELLOW
O: ORANGE BR: BROWN
Temperature°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance kΩ 19.5 15.9 13.0 10.7 8.9 7.4
D. DIPswitch Settings on the computer board of the water heater
<Lower bank of DIPswitches>
Temperature set120 °F (49 °C)
DEFAULT
140 °F (60 °C)
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 62 3 4 5 6
Easy-Link system
Parent Unit
Child Unit(DEFAULT)
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
Single unit is the same as the child unit.
Lower bank
Upper bank
Appendix F (For error code 651 and 661) Error code 651 : Refer to check point “J” on the wiring diagram above. Check voltage between black wire and red wire. (Normal: 7 to 16 VDC) Error code 661 : Refer to check point “J1” on the wiring diagram above. Check voltage between brown wire and red wire. (Normal: 3 to 11 VDC) This check point is normal? Yes >> Error code 651: Replace the Flow adjustment valve. (Part #402) / Error code 661: Replace the Bypass valve. (Part #403) No >> Replace the PCB. (Part #701)
High-altitude functionIndoor models Outdoor models
DEFAULT DEFAULT
Up to 2,500 ft Up to 2,000 ft
Up to 5,000 ft Up to 4,000 ft
Up to 7,500 ft Up to 6,000 ft
Over 10,100 ft: Over 6,000 ft:Consult themanufacturer
FM speed is increased automatically.
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
*The 341, 751 and 941 error codes are applied to the 540 (T-H3) Direct Vent Indoor model only.
<Upper bank of DIPswitches>
Locate the bank of DIPswitches at the bottom left of the computer board of the unit.Change the DIPswitch settings when the power supply is turned off.The dark square is the direction the DIPswitch should be set to. DEFAULT is the factory setting.
C
87
65
43
21 ON
65
43
21 ON
RW
G Y
PCB
W
120 VACG
Ground
SWGround
BKWG BK
W
Surge box
7353
93
BLBL
RBKRW BK
BKBK
BKBKBK
WBK
WBK
Hi-limit switch for exhaust
Exhaust thermistorWW W
W
HeaterY
Y
Thermostat
BK
O
Ground
Flame rod
AFR rod
BKWVent Indoor
Only
540 Direct
W BLR BK Temperature controller
BK
BKW
MAX buttonMIN button
Increase buttonDecrease button
Green LED
DIPswitches
Bypass Vavle
R
W
BR
YBL
GasPropor-tional Valve
RY O
BL
WFM
IGIgniter rod PP
exchanger Heatthermistor Inlet thermistorOutlet thermistor
Remote controller
Parent
12
FlowSensor
FlowAdjust- ment
Valve
HeaterHeater
540 Outdoor Only
Heater
Y
YHeater
Y
Y
HeaterHeater
540 Direct Vent Indoor Only
Hi-swichlimit
O.H.C.F
MV
SV1
SV2
SV3
BLBL BL
BL
LBG O
R
BL
Vent Indoor Only
540 Direct
A1A2
B1
GA
B
C2C1
H2
I
F
J
E1E2E3
H1
K1K2
J1D1D2L
Set DIPswitches shown in the table above depending on the vent length.
Vent settings (Direct vent Indoor models only)
3" ventings 5 to 20 ft (DEFAULT) 21 to 40 ft 41 to 70 ft
4" ventings 5 to 50 ft (DEFAULT) 51 to 100 ft N/A
OFF
ON 1 2 3 4 5 6 7 8
OFF
ON 1 2 3 4 5 6 7 8
OFF
ON 1 2 3 4 5 6 7 8
*Factory setting
Gas type*
Propane
Natural Gas
OFF
ON 1 2 3 4 5
OFF
ON 1 2 3 4 5
Model type*Direct ventIndoor model
Outdoor model
OFF
ON 1 2 3 4 5 6
OFF
ON 1 2 3 4 5 6
E. Components Diagram / Parts List
Case assembly
Item # Part # Description540 models T-H3 models
001 N/AN/A
EK159EK164
Case assembly for Indoor modelsCase assembly for Outdoor models
002 319143-507319143-508
EK158EK174
Front cover for Indoor modelsFront cover for Outdoor models
003004005006007
319143-509N/A
319143-510319143-511319143-512
EK170EK162EK190EK171EK161
Intake air port assemblyBracket
Junction boxPower suuply code assembly
Back guard panel008009
319143-513319143-018
EK160EKH23
Chamber fixing plateCondensate drain port
050051052053054
319143-025319143-325319143-026319143-060319143-326
EW000EW001EW002EW003EW004
Screw M4×12 (W/Washer)Screw M4×10 (W/Washer)
Screw M4×10 (Coated)Screw M4x10
Hex head screw M4×12 (W/Washer)055056057058059
319143-063N/A
319143-201319143-087319143-328
EW005EW018EKK31EW00AEW009
Hex head screw M4x8Pan screw M4x20
Tap tight screw M4x12 FEZNScrew M3x6Screw M4x6
060061062063064065
319143-438N/A
319143-059319143-048
N/A319143-330
EKK37EK191
EW00DEM167EK230EW00B
Screw M4x12Screw M3x6Screw M4x8
Wire clamp 60Screw M4x10
Screw M3x6 SUS3101102
319143-514319143-515319143-516
EK192EK181EK182
Burner assemblyManifold with gas valve assembly LP Manifold with gas valve assembly NA
Item # Part # Description540 models T-H3 models
103 319143-443319143-043
EK109EKK25
Fan motor for Indoor modelsFan motor for Outdoor models
104105106107108
319143-031319143-282319143-033319143-034319143-517
EKK2XEM381EKK2VEKK2WEK193
Burner gasketFan damper for Indoor models
Burner windowRod holder gasket
Flame rod109110111112
319143-037319143-036319143-038319143-518319143-519
EKK0FEKK32EKN61EK183EK169
Igniter rodRod holder
Rod capBurner damper LPBurner damper NA
113114115116117
319143-044319143-045319143-032319143-042319143-520
EKK2YEKK2KEKK0GEKK2DEX019
Manifold gasket AManifold gasket B
Burner holder gasketPressure port
Combustion chamber tube118119120121
319143-455319143-342319143-521319143-522
EK117EX00DEK194EK163
Gas inletGas inlet ringIgniter plate
Surge box plate150151152153
319143-350319143-057319143-523319143-524
EZP18EK042EK157EK177
O-ring P18 NBR (Black)O-ring P20 NBR (Black)
Silicon ring for Outdoor modelsExhaust port for Outdoor models
401
402403404
319143-527319143-528319143-463319143-464319143-193
EK200EK206EK129EKD58EKK1U
Heat exchanger assembly for Indoor models Heat exchanger assembly for Outdoor models
Flow adjustment valve / Flow sensorBypass valveWater inlet
Temperature remote controller
724
Water intlet section
402460456
461
458 404417
407454
405
457
406
D
052059
Water outlet section
410455
408458 454
462
C
052
409 417 Item # Part # Description540 models T-H3 models
405406407408409410
319143-197319143-198319143-465319143-190319143-530319143-199
EKK2BEKK2CEK137EKK1AEK208EKK2E
Inlet drain plugInlet water filterInlet thermistor
Outlet thermistorWater outlet
Outlet drain plug411412413414415
319143-096319143-095319143-149319143-531319143-532319143-533
EKK2TEKN34EK333EK209EK210EK211
Heat exchanger thermistorHi-Limit switch
Overheat-cut-off fusePipe heater
Inlet heater for Indoor modelsInlet heater for Outdoor models
416417
319143-534319143-468
EK231EK105
Drain tubeInlet heater
450451452453454
319143-088319143-125319143-066319143-146319143-082
EKK27EK031EKK26EK029EZM04
Pipe heater fixing plateHeater fixing plate 16Fuse fixing plate 18Fuse fixing plate 14
O-ring P4 FKM455456457458459
319143-080319143-100319143-091319143-083319143-097
EZM06EZM14EZM15EZM16EKH30
O-ring P6 FKMO-ring P14 FKMO-ring P15 FKMO-ring P16 FKMFastener “4-11”
460461462463464
319143-105319143-226319143-205319143-112319143-535
EKK24EM192EKK39EX12KEK217
Fastener “14-22”Fastener “16A”
Fastener “16-25A”Fastener “6-15”
Flat heater465466467468469
319143-536319143-538319143-539319143-540319143-541
EK218EK220EK222EK226EK228
Drain pipeCold pipe
Stainless heat exchanger out pipeHeader connection
Drain port470471472473
319143-106319143-111319143-104319143-542
EX13HEX13LEKH6GEK229
Thermistor fixing plateExhaust thermistor gasketHi-limit switch for exhaust
Gasket701702703704
319143-545319143-334320273-128319143-427319143-546
EK176EX00BEK280EK146EK143
Computer board Rubber grommet
Surge box120 VAC wire for Indoor models
120 VAC wire for Outdoor models706707708709710
319143-141319143-491319143-492319143-493319143-494
EKK4VEK165EK168EK166EK172
120 VAC Power ON-OFF switchRemote controller wire
Gas valve wire Flame rod wire
EH-IG wire 711712713
714715
319143-479319143-495319143-496319143-497319143-498319143-499
EK153EK195EK184EK185EK167EK179
IgniterHigh voltage igniter cable
Switch wire with thermostat for Indoor modelsSwitch wire with thermostat for Outdoor models
Proportional gas valve wire 24V cables
716717718719
319143-191319143-500319143-131319143-484
EKK1MEX13CEKH6EEK152
Computer board coverCable clamp for Indoor modelsExhaust thermistor assembly
Remote fixing plate721722723
319143-501319143-502319143-503
EK180EK173EK178
Exhaust Hi-limit switch wireTemperature controller for Indoor models
Fixing plate724 319143-485 ER014 Temperature remote controller
Outdoor modelsIndoor models
052052
003
007
002
050
006
704
005
052
702
704
008
052
050
052
717702
713
004
002
001
001
004
Surge box
703
706063709053
703
121
713Burner assembly
Water way assembly
B
E
E
459454
411
F
412
058
F
413
452
450414
451
414
401
416
009
464C
453
468
468
052
455
463
455
469
052
463
462
467
064462
462
473
473
465
471
064
153
152
053
718470
415
472
A
451
414466
451
D
415
056
723
722
Temperature contoller Indoor models
101104
115
106107
108
110
109 111 712112062
053
053
709
053
401
103
105
065
054
113114
102
708
119
151
118055
051
150
057055
120
711 063
117
053
116
062
121
714719
707
712
117
Burner assembly
Manifold Assembly
Computer board assembly
701
714
403
715
721 707 722715
402
402
103
713
708710
709
716
403
456
460
458
462
B
A
Bypass section
Maintenance sheet 68B166
B. Error codes031: Incorrect DIPswitch setting ・Check the DIPswitch settings on the PCB. Refer to Section D.
101: Warning for the “991” error code ・Check the gas type of the house (and/or the bulding). ・Check if there is any blockage in the intake air and/or exhaust. Refer to the “Vent termination clearances” of the installation manual. ・If the water heater is installed as a direct-vent system, check whether there is enough distance between the intake air terminal and the exhaust terminal. Refer to the “Vent termination clearances” of the installation manual. ・Check if the total vent length. Refer to the "Venting instructions" of the Installation manual. ・Check the altitude/elevation of area of where the water heater installed. Refer to the “High-altitude function” of the Section D. And change the DIPswitch settings. ・Check if there is grease and/or dirt in the burner (Part #101) and the fan motor (Part #103), especially if the water heater has been installed in a contaminated area. ・Check if there is dust and lint in heat exchanger. ・Check the manifold pressure of the water heater. Refer to installation manual.
111: Ignition failure 1. Check gas supply and inlet gas pressure. 2. Check if the Hi-limit switch (Part #412) is properly functioning. 3. Check for connection/breakage of wires (Part #413, 708, 709, 710, 712), and/or soot on the flame rod (Part #108). And then if O.H.C.F (Part #413) is breakage, Consult the manufacturer. 4. Check if there is a buzzing spark ignition sound coming from the burner (Part #101) when water heater prepares for combustion. 5. Listen for the double “clunk” sound coming from the gas valve assembly (Part #102) when water heater goes into combustion. 6. (Only no sparking and/or kick sound) Check voltage on each wire to gas valves assembly (Part #102) and/or the igniter (Part #711). Refer to the “Appendix A” in Section C. *No sparking sound >>>>> Refer to the #1 at “Appendix A” in Section C. *No kick sound >>>>> Refer to the #2 at “Appendix A” in Section C. 7. Check if there is leaking from heat exchanger (Part #401) 8. Check if there is dust and lint in nozzles of the manifold (Part #102). 9. Check current on the flame rod (Part #108). Refer to the #3 at “Appendix A” in Section C.
121: Loss of flame 1. Check gas supply and inlet gas pressure. 2. Check if the Hi-limit switch (Part #412) is properly functioning. 3. Check for connection/breakage of wires (Part #413, 708, 709, 712), burn marks on the computer board (Part #701), and/or soot on the flame rod (Part #108). And then if O.H.C.F (Part #413) is breakage, Consult the manufacturer. 4. Check if there is leakage from heat exchanger (Part #401). 5. Check if there is dust and lint in nozzles of the manifold (Part #102). 6. Check current on the flame rod (Part #108). Refer to the #3 at “Appendix A” in Section C.
311,321,341*: Disconnected/short-circuited thermistor ・Check for connection/breakage of wires and/or debris on thermistor (Part #407, 408, 715, 718). ・Check thermistor resistance. Refer to the “Appendix D” in Section C.
391: Air-fuel Ratio Rod failure ・Check for connection/breakage of wires (Part #709) and/or soot on the frame rod (Part #108).510,551: Abnormal Main and Solenoid Gas Valve ・Check for connection/breakage of wires (Part #708) and/or burn marks on the computer board (Part #701). ・Reset power supply of the water heater. ・ Check voltage of each valve on the gas valves assembly (Part #102). Refer to the “Appendix C” in Section C.611: Fan motor fault ・Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or burn marks on the computer board (Part #701). ・Check for frozen/corrosion of connectors of the fan motor (Part #103). ・Check voltage between blue wire and each wire of the fan motor (Part #103). Refer to the “Appendix B” in Section C.701,711: Computer board fault ・Check for connection/breakage of wires (Part #714), and check resistance between white wire and red wire. Refer to the “Appendix A” in Section C.721: False flame detection 1. Clean the flame rod (Part #108). 2. For indoor models, check if condensate drain is installed on the vent collar of the water heater. 3. Check if there is leaking from heat exchanger (Part #401).741: Miscommunication between water heater and remote controller 1. Check the model type of the remote controller. Model No. 9008172005 (TM-RE40) is the correct one. 2. Inspect the connections between the water heater and remote controller. Refer to the “Remote controller connections” of the Installation manual. 3. Check the power supply of the water heater. 4. If this error code appears only the green LED on the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to the “Appendix E” in Section C. 5. If this error code appears only remote controller, replace the PCB (Part #701). 6. If this error code appears both the PCB (Part #701) and the remote controller, replace the remote controller.751*: Miscommunication between water heater and temperature controller 1. Check the power supply of the water heater. 2. If this error code appears only the green LED on the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to the “Appendix E” in Section C. 3. If this error code appears only temperature controller, replace the PCB (Part #701). 4. If this error code appears both the PCB (Part #701) and the temperature controller, replace the temperature controller.941*: Abnormal exhaust temperature (Only 240 (T-H3J) and 340 (T-H3S) Direct Vent Indoor) ・Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or burn marks on the computer board (Part #701). ・Check exhaust thermistor resistance. Refer to the "Appendix D" in Section C.991: Imperfect combustion ・Refer to the “101” error code in this section.
C. Wiring Diagram and check point of the Water heater
Appendix A (For error code 111)
Check these points during ignition stage. # 1. Refer to check point “B” on the wiring diagram above. Check voltage between purple wires. (Normal: 108 to 132 VAC) This Check point is normal? Yes >> Replace the igniter. (Part #711) No >> Go to Next. # 2. Refer to check point “C” and “H1” on the wiring diagram above. Check the voltages below: C: Between blue wire and light blue wire (#3). (Normal: 93 to 120 VDC) C: Between blue wire and orange wire (#53). (Normal: 93 to 120 VDC) H1: Check the voltage between white wire and red wire. (Normal: 1 to 15 VDC) These check points are normal? Yes >> Replace the gas valves assembly. (Part #102) No >> Replace the PCB. (Part #701) # 3. Check current thought the yellow flame rod wire (Part #709). (Normal: more than 5 μA) This check point is normal during operation? Yes >> Replace the PCB. (Part #701) No >> Replace the flame rod. (Part #108)
Appendix B (For error code 611)
Refer to check point “G” in the diagram to the left and the following. • Check voltage between red wire and blue wire. (Normal: 132 to 192 VDC) • Check voltage between yellow wire and blue wire. (Normal: 13 to 17 VDC) • Check voltage between orange wire and blue wire. (Normal: 2.0 to 6.5 VDC) All check points are normal? Yes >> Replace the fan motor. (Part #103) No >> Replace the PCB. (Part #701)
Appendix C (For error code 510 and 551)
Refer to check point “C” in the diagram to the left and followings. Check voltage on the each valve on the gas valves assembly. • Between blue wire and light blue wire (#3). (Normal: 93 to 120 VDC) • Between blue wire and green wire (#9). (Normal: 93 to 120 VDC) • Between blue wire and orange wire (#53). (Normal: 93 to 120 VDC) • Between blue wire and red wire (#73). (Normal: 93 to 120 VDC) All check points are normal? Yes >> Replace the gas valves assembly. (Part #102) No >> Replace the PCB. (Part #701)
Appendix D (For error code 311, 321, 341, and 941)
• Outlet thermistor (Find the marking of No.113 on the connector) Check point “E1” • Inlet thermistor (Find the marking of No.42 on the connector) Check point “E2” Check resistance between black wire and black wire.
• Exhaust thermistor Check point “K1” Check resistance between white wire and white wire.
All check points are normal? Yes >> Replace the PCB. (Part #701) No >> Replace the wrong thermistor. (Part #407, 408, 718)
If the error code is indicated on green LED (Refer to the Section C) on the PCB (Part #701) of the water heater (and/or the remote controller), refer to Section B.<< It takes long time to get hot water at the fixtures >> ・The time it takes to deliver hot water from the water heater to your fixtures depends on the length of piping between the two. The longer the distance or the bigger the pipes, the longer it will take to get hot water. ・If you would like to receive hot water to your fixtures quicker, you may want to consider a hot water recirculation system.<< The water is not hot enough or turns cold and stays cold >> ・Compare the flow and temperature. Refer to the “Output temperature chart” of the installation manual. ・Check cross plumbing between cold water lines and hot water lines. ・Check if the gas supply valve fully open, the gas line sized properly and the gas supplies pressure enough. Refer to the “Gas supply and gas pipe sizing” of the installation manual. ・Check the set temperature, and change the set temperature with the remote controller or the DIPswitch setting. Refer to Section D. ・Refer to “Water circuit” in this section.<<The water is too hot>> ・Check the set temperature, lower setting temperature.<<The hot water is not available when a fixture is opened>> ・Refer to the “Power supply circuit” and “Water circuit” in this section.<<Fluctuation in hot water temperature>> ・Check if the filter on the cold water inlet cleaned. (Part #406) ・Check if the gas line sized properly and the supply gas pressure sufficient. ・Check for cross connection between cold water lines and hot water lines. ・Refer to “Water circuit” in this section.<<Unit does not ignite when water goes through the water heater>> ・Refer to the “Power supply circuit” and “Water circuit” in this section. ・If you use the remote controller, turn the power button on and then the STAND BY LED will light up. ・Check if the filter on the cold water inlet cleaned. (Part #406) ・Refer to “Water circuit” in this section.
A. Troubleshooting <<The fan motor still spinning after operation has stopped>> ・This is normal. After operation has stopped, the fan motor keeps running from 15 to 70 seconds in order to re-ignite quickly, as well as purge all the exhaust gas out of the flue.<<Abnormal sound from water heater>> ・An abnormal sound from the water heaters is caused by not enough air supply or wrong installations. The water heater needs more combustion air. Refer to the “101” error code in the section B.<<Power supply circuit>> 1. If the remote controller installed, press the “ON/OFF” button of the remote controller, and make sure that the STAND BY LED next to the “ON/OFF” button of the remote controller is lit. Restart the water heater. 2. Check if that the green LED on the PCB (Part #701) of the water heater is lit. If so, the power supply circuit of the water heater is under normal condition. Next, refer to the “Water circuit” in this section. 3. Check the fuse on the surge box (Part #703), and if it has a brown spot, need to replace it. 4. Check the power supply, and make sure that the water heater has 120 VAC. 5. If the green LED on the PCB (Part #701) isn’t lit, some electrical parts can be broken. Consult the manufacturer.<<Water circuit>> 1. If you set the remote controller, turn the power button on and then the STAND BY LED will light up. 2. Open all hot water faucets, and make sure that there is enough water flow. This water heater needs at least 0.5 GPM water flow (at the default set temperature) to operate. 3. Check for reverse connection and cross connection. 4. Check if the filter on the cold water inlet cleaned. (Part #406) 5. Check if there is no debris or obstruction on the fixtures. 6. Check if water ways in the water heater are frozen. If so, unfreeze them. And refer to installation manual to protect your water heater from freezing. 7. Check if the inlet water pressure is higher than 40 psi. And if it’s lower than 40 psi, need to increase the pressure. 8. Check for connections and breakage of wires (Part #402). 9. Check if the motor drive of the flow adjustment valve (Part #402) is locked due to scale buildup, and/or water leakage. Consult the manufacturer.
Temperature°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance kΩ 15.4 12.6 10.3 8.5 7.0 5.9
ATH3J, ATH3S
Model type*
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10Outdoor models
Direct ventIndoor models
D. DIPswitch Settings on the computer board of the water heaterLocate the bank of DIPswitches at the bottom left of the computer board of the unit.Change the DIPswitch settings when the power supply is turned off.The dark square is the direction the DIPswitch should be set to. DEFAULT is the factory setting.
Temperature set
120 °F (49 °C)DEFAULT
140 °F (60 °C)
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
W: WHITER: RED
BK: BLACK
P: PURPLE
LB: LIGHT BLUEBL: BLUE
G: GREENY: YELLOW
O: ORANGE BR: BROWN
DIPswitches
987654321 10
OFF
Remote controller
RBK
R WBK
Ground
GO
WY BL
O
R
PCB
W
120 VACG
Ground
SWGround
W BKG
Igniter rodP
7353
93
OR
GLBBL
O.H.C.FBL
Hi-limit
SwitchBL
GasPropor-tional Valve
WR
BL
BLBLBL
P
BK
BKW
BKBK
Outlet thermistorInlet thermistor
Surge box
Hi-limit switch for exhaust
Exhaust thermistor
WW
W
W BK
WBL RBKTemperature controller
Heater
HeaterHeater
240/340 Outdoor Only
Heater
BK
DIPswitches
Y
Y
YY
YY
WWW
Y
Flame rod
AFR rod
BKW
Thermostat
HeaterHeater
Heater
240/340 Direct Vent Indoor Only
Decrease buttonIncrease button
MIN buttonMAX button
Green LED
SV3
SV2
SV1
MV
IG
FlowAdjust-ment Valve
FlowSensor
FM
Indoor Only
240/340 Direct Vent
Vent Indoor Only
240/340 Direct
B
CC2C1
GA
A1A2
B1
F
JH2
E1H1
E2
IK2K1
Temperature°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance kΩ 19.5 15.9 13.0 10.7 8.9 7.4
Gas type*
PropaneOFF
ON1 2 3 4 5 6 7 8 9 10
Natural Gas OFF
ON1 2 3 4 5 6 7 8 9 10
*Factory setting
*The 341, 751 and 941 error codes are applied to the 240 (T-H3J) and 340 (T-H3S) Direct Vent Indoor model only.
L
Set DIPswitches shown in the table above depending on the vent length.
Vent settings (Direct vent Indoor models only)
3" ventings 5 to 20 ft (DEFAULT) 21 to 40 ft 41 to 70 ft
4" ventings 5 to 50 ft (DEFAULT) 51 to 100 ft N/A
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
High-altitude functionIndoor models Outdoor models
DEFAULT DEFAULT
Up to 2,500 ft Up to 2,000 ft
Up to 5,000 ft Up to 4,000 ft
Up to 7,500 ft Up to 6,000 ft
Up to 10,100 ft Over 6,000 ft: Consult the manufacturer
FM speed is increased automatically.
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
OFF
ON1 2 3 4 5 6 7
Appendix E (For error code 741 and 751) Error code 741: Refer to check point “F” on the wiring diagram above. Error code 751 : Refer to check point “L” on the wiring diagram above. Check voltage on the remote controller and/or temperature controller on the PCB. • Between black wire and white wire. (Normal: 11 to 25 VDC) This check point is normal? Yes >> Replace the remote controller and/or temperature controller. No >> Replace the PCB. (Part #701)
E. Components Diagram / Parts List
Case assembly
Item #Part #
Description240 / 340 models
T-H3J / T-H3S models
001 N/AN/A
EK159EK164
Case assembly for Indoor modelsCase assembly for Outdoor models
002 319143-505319143-506
EK187EK188
Front cover for Indoor modelsFront cover for Outdoor models
003004005006007
319143-509N/A
319143-510319143-511319143-512
EK170EK162EK190EK171EK161
Intake air port assemblyBracket
Junction boxPower suuply code assembly
Back guard panel008009
319143-513319143-018
EK160EKH23
Chamber fixing plateCondensate drain port
050051052053054
319143-025319143-325319143-026319143-060319143-326
EW000EW001EW002EW003EW004
Screw M4×12 (W/Washer)Screw M4×10 (W/Washer)
Screw M4×10 (Coated)Screw M4x10
Hex head screw M4×12 (W/Washer)055056057058059
319143-063N/A
319143-201319143-087319143-328
EW005EW018EKK31EW00AEW009
Hex head screw M4x8Pan screw M4x20
Tap tight screw M4x12 FEZNScrew M3x6Screw M4x6
060061062063064065
319143-438N/A
319143-059319143-048
N/A319143-330
EKK37EK191
EW00DEM167EK230EW00B
Screw M4x12Screw M3x6Screw M4x8
Wire clamp 60Screw M4x10
Screw M3x6 SUS3
Item #Part #
Description240 / 340 models
T-H3J / T-H3S models
101102
103
319143-514319143-515319143-516319143-443319143-043
EK192EK181EK182EK109EKK25
Burner assemblyManifold with gas valve assembly LP Manifold with gas valve assembly NA
Fan motor for Indoor modelsFan motor for Outdoor models
104105106107108
319143-031319143-282319143-033319143-034319143-157
EKK2XEM381EKK2VEKK2WEK193
Burner gasketFan damper for Indoor models
Burner windowRod holder gasket
Flame rod109110111112
319143-037319143-036319143-038319143-518319143-519
EKK0FEKK32EKN61EK183EK169
Igniter rodRod holder
Rod capBurner damper LPBurner damper NA
113114115116117
319143-044319143-045319143-032319143-042319143-520
EKK2YEKK2KEKK0GEKK2DEX019
Manifold gasket AManifold gasket B
Burner holder gasketPressure port
Combustion chamber tube118119120121
319143-455319143-342319143-521319143-522
EK117EX00DEK194EK163
Gas inletGas inlet ringIgniter plate
Surge box plate150151152153
319143-350319143-057319143-523319143-524
EZP18EK042EK157EK177
O-ring P18 NBR (Black)O-ring P20 NBR (Black)
Silicon ring for Outdoor modelsExhaust port for Outdoor models
Water intlet section
402460456
461
458 404417
407454
405
457
406
D
052059
Water outlet section
410455
408458 454
462
C
052
409 417
Item #Part #
Description240 / 340 models
T-H3J / T-H3S models
401
402404405
319143-525319143-526319143-463319143-193319143-197
EK198EK199EK129EKK1UEKK2B
Heat exchanger assembly for Indoor models Heat exchanger assembly for Outdoor models
Flow adjustment valve / Flow sensorWater inlet
Inlet drain plug406407408409410
319143-198319143-214319143-529319143-530319143-199
EKK2CEKK4JEK207EK208EKK2E
Inlet water filterInlet thermistor
Outlet thermistorWater outlet
Outlet drain plug412413414415
319143-228319143-149319143-531319143-532319143-533
EM212EK333EK209EK210EK211
Hi-Limit switchOverheat-cut-off fuse
Pipe heaterInlet heater for Indoor models
Inlet heater for Outdoor models416417
319143-534319143-468
EK231EK105
Drain tubeInlet heater
450451452453454
319143-088319143-125319143-066319143-146319143-082
EKK27EK031EKK26EK029EZM04
Pipe heater fixing plateHeater fixing plate 16Fuse fixing plate 18Fuse fixing plate 14
O-ring P4 FKM455456457458459
319143-080319143-100319143-091319143-083319143-097
EZM06EZM14EZM15EZM16EKH30
O-ring P6 FKMO-ring P14 FKMO-ring P15 FKMO-ring P16 FKMFastener “4-11”
460461462463464
319143-105319143-226319143-205319143-112319143-535
EKK24EM192EKK39EX12KEK217
Fastener “14-22”Fastener “16A”
Fastener “16-25A”Fastener “6-15”
Flat heater465466467468469
319143-536319143-537319143-539319143-540319143-541
EK218EK219EK222EK226EK228
Drain pipeCold pipe
Stainless heat exchanger out pipeHeader connection
Drain port470471472473
319143-106319143-111319143-104319143-542
EX13HEX13LEKH6GEK229
Thermistor fixing plateExhaust thermistor gasketHi-limit switch for exhaust
Gasket701
702703704
319143-543319143-544319143-334320273-128319143-427319143-546
EK186EK175EX00BEK280EK146EK143
Computer board for 240 (T-H3J) models Computer board for 340 (T-H3S) models
Rubber grommetSurge box
120 VAC wire for Indoor models120 VAC wire for Outdoor models
706707708709710
319143-141319143-490319143-492319143-493319143-494
EKK4VEK189EK168EK166EK172
120 VAC Power ON-OFF switchRemote controller wire
Gas valve wire Flame rod wire
EH-IG wire 711712713
714
319143-479319143-495319143-496319143-497319143-498
EK153EK195EK184EK185EK167
IgniterHigh voltage igniter cable
Switch wire with thermostat for Indoor modelsSwitch wire with thermostat for Outdoor models
Proportional gas valve wire 716717718721
319143-191319143-500319143-131319143-501
EKK1MEX13CEKH6EEK180
Computer board coverCable clamp for Indoor modelsExhaust thermistor assemblyExhaust Hi-limit switch wire
722723
319143-502319143-503
EK173EK178
Temperature controller for Indoor modelsFixing plate
724 319143-485 ER014 Temperature remote controller
Outdoor modelsIndoor models
052052
003
007
002
050
006
704
005
052
702
704
008
052
050
052
717702
713
004
002
001
001
004
Computer board assembly701
713
103
709
402
708
714
721
407
408
716
722 402707
710
061
Burner assembly
Water way assembly
E
E
F
412
058
F
413
452
450414
451
414
451
414
401
416
009
464C
453
468
468
052
455
463
455
469
052
463
462
467
064462
462
473
473
466
451
471
064
D
153
152
053
718470
415
472
415
465
101104
115
106107
108
110
109 111 712112062
053
053
709
053
401
103
105
065
054
113114
102
708
119
151
118055
051
150
057055
120
711 063
117
053
116
062
121
714712
117
Burner assembly
Manifold Assembly
056
723
722
Temperature contoller Indoor models
Temperature remote controller
724
Surge box
703
706063709053
703
121
713
Maintenance sheet MC02
C. Maintenance informationHow to check the maintenance information 1. Press the “MODE” button on the computer board of the multi- unit controller. And then the first 2-digit number “_0” displayed on 7-seg LED that indicates the multi-unit controller. The first 2-digit number means unit number. Press the “MODE” button to select the unit number. The unit number changes at ”0→1→2→3→・・・→20→0→1→2 ・・・”. (In this case, the multi-unit controller is connected to 20 units). 2. Press the “SET” button to fix the unit number. 3. Press the “MODE” button to select the mode number. The mode number changes at “1→2→3→・・・→9→10→11→ ・・・→32→1→2→・・・" 4. Press the “SET” button to fix the maintenance number and then the Maintenance number and then the maintenance data will be displayed on 7-segLED.
NOTE Refer to the installation manual of the water heater for error codes. The and means the multi-unit controller and water heater in the text.
031 : Incorrect DIPswitch setting ・Check the DIPswitch settings on the computer board.101 : Warning for the “991” error code111 : Ignition failure121 : Loss of flame311,321,331,341 : Disconnected/short-circuited thermistor391 : Air-fuel ratio rod failure441 : Flow sensor failure ・Check the flow sensor in the water heaters. Check the water supply for the water heaters.510 : Abnormal main gas valve551 : Abnormal gas solenoid valve
A. Troubleshooting 611 : Fan motor fault631 : Abnormal external pump ・Check the recirculation pump.651 : Flow adjustment valve fault661 : Bypass valve fault681 : Abnormal external fan motor ・Check the external fan motor.701 : Computer board fault721 : False flame detection741 : Miscommunication between multi-unit controller and temperature remote controller ・Check the communication cable between the multi-unit controller and the remote controller.751 : Miscommunication between multi-unit controller and temperature controller of the water heater ・Check the communication cable between the multi-unit controller and the temperature controller of the water heater.761 : Miscommunication in multi unit system ・Check the communication cable between the multi-unit controller and the water heaters.991 : Imperfect combustion
81A005
D. Wiring Diagram and check point of the multi-unit controller
B. DIPswitch Settings on the computer board of the multi-unit controller• Change the DIPswitch settings when
the power supply is turning off.• The dark square is the direction the
DIPswitch should be set to.• DO NOT adjust the right bank of
DIPswitches.
E. Components diagram / parts list
Item # DescriptionPart #
9008300005 model
TM-MC02 model
001002003
BracketJunction boxRubber bush
319143-184N/A
319143-334
EKJ09EM430EX00B
050051052
Screw M4×12 (W/Washer)Screw M4×10 (Coated)Screw M4x10
319143-025319143-026319143-060
EW000EW002EW003
701702703704705
Computer boardSurge box120 VAC wirePCB fixing plateCable strap
320273-550320273-128320273-551320273-552
N/A
EK232EK280EK235EK238EW022
A: Temperature remote controller terminals. Check voltage on the remote controller terminals. (Normal range: 14 to 16 VDC)
B: Water heater terminals. Check voltage on the terminals for water heaters. (Normal range: 14 to 16 VDC)
Freeze protection for re-circulation system
3 4 5 6ON 21
Factory setting
ON 3 4 5 621
001
050
050051
052
051
701
703
704
705
702
052051
051
051
051
003052
002
051
NOTE: *These components are NOT included with the multi-unit controller and are external to the unit. They must be acquired separately.
6ON
1 2 3 4 5 6
In each port510U (T-D2U) : Max 5 units540 (T-H3) : Max 5 units
Lamp buzzer
Power supplyfor Relay andLamp buzzer24 VDC or 24 VAC
BL:Black G:Green
W:White
"SET" button"ERROR CALL" button
"ALARM RESET" button
7-Seg LED
Unit# LED
Timer controlterminals
"MODE" button
"PRIORITY SET"button
"PUMP TEST" button"BYPASS REMOTECONTROL" button
Bank of DIPswitches
"MULTI SYSTEM ALARM"lamp
Re-circulation pump
Power supply forrelays 120 VAC
pump120VAC240VAC
Fan motorcontrol terminals
Pump controlterminals
To 9008172005 (TM-RE40)
Temperature remotecontroller terminals
1 2 3 4 5 6
Alarm terminals
120 VAC
Surge box
WBL
WBL
G
Ground
120 VAC
Externalfan motor
Power supply forrelays 120 VAC
external fan moter120 VAC240 VAC
To Water heaters
Draft switch terminals
MNCNO5432 654321 1O
N
*
*
*
*
Timer Switch
Draft switch
Terminals forwater heaters
*
Power supply forprogram timer120 VAC240 VAC
Power supply for
Power supply for
A
BCD
E
Mode number Whole multi-unit system information (#0) Information for water heaters (#1 to #20)
1 Total system flow rate 0 to 9999 (x 0.1 GPM) Total operation time 0 to 9,999 (× 10 hours)
2 BTU requirement for the multi-system 0 to 9999 (×kBTU/h) The number of operation
cycle0 to 9,999 (× 100 times)
3The number of water heaters connected with multi-unit controller
0 to 20 (units) Fan motor speed 0 to 9,999 rpm
4 Priority water heater 0 to 20 (unit #) Inlet temperature32 to 212 (°F).Over 212 °F = E5,Under 32 °F = E0
5 Quantity of operational water heaters 0 to 20 (units) Heat exchanger temperature
6 Set temperature 100 to 185 °F Outlet temperature
7 Operation time during current rotation 0 to 999 (minutes) Air-Fuel ratio rod current 0 to 9,999 (× 0.1 μA)
8 ON/OFF cycles during current rotation 0 to 999 (times) Flow rate 0 to 999 (× 0.1 GPM)
9 N/A Energization time of the water heater
0 to 9,999 (× 10 hours)
10 Delete units number - Integrating flow of the water heater
0 to 9,999 (× 1,000 gallons)
11 N/A Error code history: displays most recent error code
12 Inlet temperature of the priority water heater 0 to 999 °F Error code history: displays 2nd most recent
error code
13 Outlet temperature of the priority water heater 0 to 999 °F Error code history: displays 3rd most recent error code
14 N/A Clears memory in error code history*
15 Integrating flow of the multi unit system
0 to 9999 (× 100,000 gallons)
Integrating output of the water heater 0 to 999 MBTU/h
16 Energization time of multi-unit controller
0 to 9,999 (× 10 hours) Air-fuel ratio stage 0 to 16,
normal condition=6
17 to 19 N/A Refer to the installation manual of the water heater
20 Operation time of the recirculation pump
0 to 9,999 (× 10 hours)
Ratio of hot water and cold water 0 to 999 (%)
21 to 32 N/A Refer to the installation manual of the water heater
Description of mode numbers in “Diagnostic Mode”
1 2 3 4 5 6ON
1 2 3 4 5 6ON
1 2 3 4 5
6 7 8 9 10
11 12 13 14 15
16 17 18 19 20
UNIT No.
7-Seg LEDs “MODE” button
“SET” button
D: External fan motor control terminals. When the error code appears, the terminals get 0 Ω. When the no error code appears, the terminals get Ω.8
E: Alarm terminals. When the error code appears, the terminals get 0 Ω. When the no error code appears, the terminals get Ω.8
1 2 3 4 5 6
↑
1 2 3 4 5 6
↑
ON
ON
Left bank of DIPswitchesWHWHWH
MC
MC
WHWH
WHWH
WH
WH
MC
MCWH
WHWH
WH
MC
MC
WH
Pump control mode
Re-circulation controlNormal control (DEFAULT)
Type A Type BON 3 4 5 621ON 3 4 5 6213 4 5 6ON 21
C: Pump control terminals. When the re-circulation pump needs to be work, the terminals get 0 Ω. When the re-circulation pump needs not to be work, the terminals get Ω.8
MC WH