Major Changes in the 2017National Electrical Safety Code® (NESC®)
forPart 1-Electric Supply Stations
October 18, 2016 San Antonio, Texas
Marne and Associates, Inc.Experts in Electrical Code619 S.W. Higgins, Suite C
Missoula, MT 59803(406) 544-8997
www.marneassociates.comDavid J. Marne, P.E.
![Page 2: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/2.jpg)
Overview¾ 2017 National Electrical Safety Code (NESC)
– Over 700 proposed changes were submitted to the NESC subcommittees.
– The accepted changes affect approximately 215 of the 354 pages in the NESC.
– Changes range from new rules and requirements to minor modifications of existing rules. (Not every change will be discussed.)
– NESC 2017 Edition was published August 1, 2016.– McGraw-Hill’s 2017 NESC Handbook was published October 1,
2016.– The Figures and Photos in this presentation are from McGraw-
Hill’s NESC 2017 Handbook and are used with permission of Marne and Associates, Inc. and the McGraw-Hill Companies, Inc. © 2017. Do not duplicate.
2
![Page 3: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/3.jpg)
2017 National Electrical Safety Code (NESC) Changes
¾ No Changes (General Overview)
¾ Level 1 (Minor Change)
¾ Level 2 (Moderate Change)
¾ Level 3 (Major Change)
3
![Page 4: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/4.jpg)
2017 National Electrical Safety Code (NESC) Changes
¾ NESC Change Bars
4
![Page 5: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/5.jpg)
Part 1- Electric Supply Stations
5
![Page 6: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/6.jpg)
6
Part 1- Electric Supply StationsQ: What separates Part 1-Electric Supply Stations from Part 2-Overhead Lines and Part 3-Underground Lines???
A: The Fence!!!
![Page 7: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/7.jpg)
Safety sign locations on an electric supply station with and without a roof
7
Change: RULE 110A.Modified rule wording for safety sign requirements on fenced substations and added rule wording for safety sign requirements on a substation with a roof.
![Page 8: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/8.jpg)
Safe sign locations on an electric supply station with and without a roof
8
Change: RULE 110A.Modified rule wording for safety sign requirements on fenced substations and added rule wording for safety sign requirements on a substation with a roof.
![Page 9: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/9.jpg)
Barrier height requirements
9
Change: RULE 110A.Minor edits to the formatting and wording.
Remember! Dimensions are “Not Less Than” values and must be maintained.
![Page 10: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/10.jpg)
Neighboring fence requirements
10
Change: RULE 110A.New rule wording addressing neighboring fences adjacent to substation fences.
![Page 11: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/11.jpg)
Neighboring fence requirements
¾ Photo submitted with NESC CP 4572 by Allen Clapp
11
![Page 12: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/12.jpg)
Example of how to apply the safety clearance zone to a chain-link fence per NESC Table 110-1 and NESC Fig. 110-1
12
substation fence (safety clearance zone). Altitude of 3300’ or less.
¾ Example: 12.47/7.2 kV, 3∅, 4W live part clearance from a chain-link substation fence (safety clearance zone). Altitude of 3300’ or less.
Change: RULE 110A2a and Table 110-1. Added a requirement to apply appropriate atmospheric correction factors to the clearance values for altitudes above 3300 feet.
![Page 13: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/13.jpg)
Example of how to apply the safety clearance zone to a chain-link fence per NESC Table 110-1 and NESC Fig. 110-1
13
![Page 14: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/14.jpg)
Example of how to apply the safety clearance zone to an impenetrable fence per NESC Table 110-1 and NESC Fig. 110-2
¾ Example:12.47/7.2 kV, 3∅, 4W live part clearance from an impenetrable fence (safety clearance zone). Altitude of 3300’ or less.
Change: RULE 110A2b.New rule wording addressing both penetrable and impenetrable portions of a fence.
14
![Page 15: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/15.jpg)
Fire-extinguishing equipment
15
Change: Rule 114 was deleted.
![Page 16: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/16.jpg)
Example of how to apply vertical clearances per NESC Table 124-1, NESC Fig. 124-1 and Rule 124A3
¾ Example:34.5/19.9 kV, 3∅, 4W primary 12.47/7.2 kV, 3∅, 4W, secondary Altitude of 3300’ or lessVertical clearance:35 kV between phases for primary.15 kV (110 kV BIL) between phases for secondary.Vertical clearance per NESC Table 124-1, Column 2
Change: RULE 124A1.Added a requirement to apply appropriateatmospheric correction factors to the clearance values for altitudes above 3300’.
16
![Page 17: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/17.jpg)
Example of how to apply vertical clearances per NESC Table 124-1, NESC Fig. 124-1, and Rule 124A3
17
![Page 18: Major Changes in the 2017 National Electrical Safety Code (NESC … · 2019-09-09 · Overview ¾ 2017 National Electrical Safety Code (NESC) – Over 700 proposed changes were submitted](https://reader034.vdocument.in/reader034/viewer/2022042022/5e79dee272aa3f61bb724afa/html5/thumbnails/18.jpg)
18
The Best Merger in the
Utility Industry!
Training and Books: www.marneassociates.com