Revisions to Fire Safety Provisions :“Selangor Uniform Building

(amendment)(no2) By-Laws 2012”

1) Open Structures and corridors2) Fire Appliance Access

3) Travel Distances4) Single Staircase

Ar Chong Lee SiongAPAM MIFireE MIArbs

10 December 2014

Page 2: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

I : Small Residential

II : Institutional

III : Other Residential

V : Shop

VII : Place of Assembly

PURPOSE GROUP

Page 3: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

OPEN STRUCTURE

(1)Total surface area of openings is to be no less than 40% of the total perimeter wall area enclosing the floor or compartment

(2)The opening is to be shaped and located in such a way that total length in plan of the opening(s) is to be no less than 50% of the perimeter of the floor or compartment

“ Openings” is to be opened to outside, unenclosed space or permitted airwells. Any individual opening having a surface area less than 600mm2 or area width of opening is less than 25mm is not to be regarded as an opening for this purpose.

Page 4: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

OPEN STRUCTURES

50m

25m

5m

Example:Total perimeter length (25m + 50m ) x 2 = 150m

minimum 50% = 75mTotal perimeter wall area 150m x 5m = 750m2

minimum 40% = 300m2

Total length of openings : 25m + 50m = 75mTotal area of openings : 75m x 4m = 300m2Total length of openings : 50m + 50m = 100mTotal area of openings : 100m x 3m = 300m2Total length of openings (25m + 50m)x2 = 150mTotal area of openings : 150m x 2m = 300m2

Page 5: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

OPEN CORRIDOR

(1)Total surface area of opening(s) is to be no less than 25% of the total perimeter wall area enclosing the balcony (corridor)

(2)The opening(s) is to be shaped and located in such a way that total length in plan of the opening(s) is to be no less than 50% of the perimeter of the floor or compartment

“ Openings” is to be opened to outside, unenclosed space or permitted airwells. Any individual opening having a surface area less than 600mm2 or area width of opening is less than 25mm is not to be regarded as an opening for this purpose.

Page 6: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

OPEN CORRIDORExample (corridor)Total perimeter length (24m + 2m ) x 2 = 52m

minimum 50% = 26mTotal perimeter wall area 52m x 3m = 156m2

minimum 25% = 39m2

Total length of openings 24m + 2m + 2m= 28mTotal area of openings : 28m x 1.5m = 42m2

Permitted Airwells(UBBL 40)

6m

3m

6m 6m6m

3m

2m

Page 7: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 8: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 9: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 10: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

A : HRB : SpkrC : GasExD : PrHy

10th SCHEDULE

HOTELS

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

Page 11: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 12: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

FIRE APPLIANCE ACCESSUBBL 140

ACCESS WAYAn area for the entry, maneuvering and parking of Fire Appliances during fire fighting and rescue operations

ACCESS ROADA road capable of accommodating the passage of Fire Appliances to enter an Access Way

ACCESS OPENINGSDoorways or openings that allows fast and safe entry of Fire Fighting and Rescue personnel into a building during fire fighting and rescue operations

Page 13: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Pressurised Hydrant System

Page 14: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Sprinkler System

Page 15: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Dry Riser system

Page 16: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Wet Riser System

Page 17: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

External source of water•Hydrants•Lakes, Ponds, Pools, rivers

•Fire Tenders

Fire Fighting Applianceon ‘Access Way’

Internal Systems• Sprinklers• Hose reels• Dry/Wet Risers

Breaching Inlet• Sprinklers• Risers

Page 18: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

ACCESS WAY• Minimum 6m width• 30 tonnes load• Gradient <= 1:15• No overhead obstructionsACCESS ROAD

• (Suggested) minimum width 4m

• Gradient <= 1: 8.3• Minimum overhead

clearance 4.5m

ACCESS OPENING• Located fronting

Access Way• (suggested) width >=

required exit width

Required portion of building fronting the Access Way

Edge of Access Way• Minimum 2m• Maximum 10m

Required portion of building fronting the Access Way

ACCESS WAY

ACCESS ROAD• (Suggested)

minimum width 4m• Gradient <= 1: 8.3• Minimum overhead

clearance 4.5m

Page 19: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Fire Fighting Access Lobbies

Emergency Power Generators

Fire Pumps

Breeching Inlets

Hydrant

Hydrant

Maximum 30mHydrant to Breeching Inlet

Maximum 90mHydrant to Hydrant

Page 20: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

EXITS and TRAVEL DISTANCE

• Final exit

• ‘Alternative exits’

• Storey exit

• Horizontal exit

• Exit route

Page 21: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Final exit

Exit route

horizontal exit

storey exit

Travel distance

Travel distanceTravel distance

Final exit

Page 22: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

TRAVEL DISTANCE• UBBL 165

• 7th Schedule

• Dead end • initial travel distance before a point where an alternative path becomes

available

• Direct distance• Stipulates that travel distance must be measured along the actual path of

travel

• Open plan• Where an actual path of travel cannot be determined, the direct distance

can be measured as a straight line direct to the exit. Permitted travel distance is then reduced to 2/3.

Page 23: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

7th Schedule : Maximum Travel Distance

6 60 9

0 30 45 10 45 10

22.5 45

0 61

30 45 60

NR 22.5 22.5 NR

NR NR NRNR 22.5 30

30 45

UBBL 1984 provisions shown in RED

Page 24: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

7th Schedule : Occupant Load and capacity of exits

22

100 60 60 60 45

------OFFICE

------SHOP

UBBL 1984 provisions shown in RED

Page 25: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Evacuation : multiple areas

Final exitsUBBL 165 (B)Max 15m2 and < 6 pax

Travel distance measured from door if room is less than 15m2 and with less than 6 occupants

Page 26: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Clause 194 (b) : single staircase for shop house

<=12m

Shop

House/office

Single staircase

Houseonly

<= 6m

1) House only on upper floor

2) No more than 2 storeys

3) Height of first floor no more than 6m above ground level

Clause 166 and 167 (not less than two exits) shall apply for other building types

Page 27: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

THANK YOU

Ar Chong Lee Siong

APAM MIFireE MMIArbs

Page 28: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Horizontal exits

12 3

Page 29: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Horizontal exits

1

2 2

Page 30: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Vehicles in use by JBPM :

•Motorcycle•Terrain buggy•Rapid Fire Rescue Tender•Fire Rescue Tender•Turntable ladder•Hydraulic platform•Hazmat

Page 31: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Rapid response motorcycles

Page 32: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Terrain buggy

Page 33: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Rapid Fire Rescue Tender

Page 34: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Fire Rescue Tender (medium)

Page 35: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Fire Rescue Tender (light)

Page 36: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

HAZMAT tender

Page 37: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Turntable ladders

Page 38: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Pump tanker

Page 39: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

Hydraulic platforms

Page 40: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 41: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 42: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No

?

Page 43: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 44: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 45: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 46: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 47: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No
Page 48: Major Revisions to Fire Safety Provisions in the Selangor Uniform Building Amendment No