management of sf6 emissions from t&d hv equipment in the
TRANSCRIPT
![Page 1: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/1.jpg)
---
Management of SF6 Emissionsfrom T&D HV equipment
in the European Union
The updated inventory methodology
J-L. BESSEDE, J. M. INCHAUSTI, H. KNOBLOCH, S. THEOLEYRE, T. ENDRE
on behalf of CAPIEL
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 2: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/2.jpg)
Content
• Introduction – CAPIEL/Kyoto protocol/SF6 Issue
• SF6 in Electrical equipment in Europe – SF6 emmissions reduction strategies – Standards, etc…, Voluntary agreements
• CAPIEL Inventories – Inventory methodology (1998/2000)– Updated Inventory methodology (2005)
• Conclusion
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 3: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/3.jpg)
What is CAPIEL ?
• Co-ordinating Committee for the Associations of Manufacturers of Industrial Electrical Switchgear Controlgear in the European Union
• Members : National associations from : Belgium, Denmark, Germany, Greece, Spain, France, Ireland, Italy, Luxembourg, the Netherlands, Austria, Portugal, Finland, Sweden, U.K.
• Total turnover : 18.25 billion € (export 25 %)
• Employees : around 118.000 in Europe
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 4: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/4.jpg)
Kyoto Summit (1997) : Greenhouse Gases emissions reductions
3rd Int. Conf. on SF6 and the Environment December 1-3, 2004, Scottsdale, AZ
PFCs, HFCs, SF6
Reduction
Entry intoEntry into force in 2005force in 2005
Life Time (Year)
GW
P (C
O2
Equ
ival
ent,
Val
ue o
f 100
Yea
r)
![Page 5: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/5.jpg)
3rd 6 and the Environment
Emission in the World (1998) 22.726 Billion Ton CO2 equivalent
EU : 8 % Reduction
Compared withThat in 1990
Green-house gasses (equiv. CO2) Emissions in the World
≈
Int. Conf. on SFDecember 1-3, 2004, Scottsdale, AZ
![Page 6: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/6.jpg)
Reduction Strategy for Green-House Gasses Emissions -Europe
3rd Int. Conf. on SF6 and the Environment December 1-3, 2004, Scottsdale, AZ
GH
G E
mis
sion
s(1
995
leve
l=10
0)
Abatement
Recycling
Year
Alternative Process
Assumed rate of increase without any measures:
10% + /year
Assumed rate of increase without any measures:
10% + /yearReduction Target>8%
(Basis of Comparison: 1995)
![Page 7: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/7.jpg)
Content
• Introduction – CAPIEL/Kyoto protocol/SF6 Issue
• SF6 in Electrical equipment in Europe– SF6 emmissions reduction strategies – Standards, etc…, Voluntary agreements
• CAPIEL Inventories – Inventory methodology (1998/2000)– Updated Inventory methodology (2005)
• Conclusion 3rd
6 and the EnvironmentInt. Conf. on SFDecember 1-3, 2004, Scottsdale, AZ
![Page 8: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/8.jpg)
SF6 From the Electrical Industry
• World SF6-emissions from electricity Sector less than 0,1% of man made GW
• European Electricity Sector contributes only about 0,01 % .
• European Union is preparing an F-Gasses regulationPossible restrictions in the SF6 use even in the electrical industry
• European switchgear manufacturers & users aware that SF6 is a persistent gas.
• Voluntary actions announced by CAPIEL and EURELECTRIC in 2001 to contribute to the European Climate Change Program (ECCP).
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 9: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/9.jpg)
3rd 6 and the Environment
SF6 Situation in the EU 15
Int. Conf. on SFDecember 1-3, 2004, Scottsdale, AZ
and switchgear technology:
(1995 and 2000)
![Page 10: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/10.jpg)
SF6 Emissions from HV Switchgear - Manufacture in Europe*
[ ]
0 10 20 30 40 50 60 70 80 90
100
*Italy, UK, France, Spain,
63 t
Emission metric tons
Manuf. HV+MV
Netherlands and Germany
- 70%
1995
**
1996
1997
1998
1999
2000
2001
2002
2003
Emission rate was reduced from 9 to 3,3% of consumption
2003
w/o
act
ions
3rd
6 and the Environment CAPIEL
Int. Conf. on SFDecember 1-3, 2004, Scottsdale, AZ
Source: Reporting data by
![Page 11: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/11.jpg)
SF6 Emission Reduction in the Switchgear Industry
• Avoid unnecessary transport & Promote re-use of SF6
• Ensure re-use in/via relevant standards: IEC 60480 already revised – IEC 60376 under revision
IEC 61634 (to be revised) - IEC 62271series
• Promote appropriate handling, ensuring low emissions of SF6 Cigre "Practical SF6 Handling Instructions" – Ed. 2 Cigre "SF6 recycling guide, Re-Use of SF6 in electrical power equipment and final disposal", 1997, 46p. Cigre "SF6 Tightness Guide", to be published.
• Voluntary agreements (Government/Industry) on SF6
Germany, Italy, France, Switzerland, Norway
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 12: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/12.jpg)
Voluntary actions - Emission reduction on HV Switchgear*
•manufacturer •user •Permanent improvements in switchgear design for minimal leakage and simplified handling in service 2
•Reduction of emission during manufacture 2 •Improved filling procedures on site 2 2 •Better monitoring in service (for larger equipment) 2
•Use of “sealed-for-life” techniques for in particular smaller equipment
2 2
•Target older existing equipment with known leakage problem for repair/replacement
2
•Improved maintenance procedures 2
•Improved end-of-life recovery and recycling 2 * EU 15
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 13: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/13.jpg)
Voluntary actions - Emission reduction on HV Switchgear*
• Increased awareness of complete staff, handling SF6
• Implementation of the Re-Use system with gas-producer
• Inventory of all relevant data
• Integration of handling guide into standard training program
• State of the art handling equipment ( < 10 mbar) and piping
• Installation of self-closing couplings for pipes
• Installation of self-closing valve technology within piping system
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 14: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/14.jpg)
Voluntary actions - Emission reduction on HV Switchgear*
• Implementation of integral-leakage detection systems with highest sensitivity into standard quality system for hermetically sealed mv switchgear; detection of far less than 0,1% leakage rate
• Introduction of welded containment for MV switchgear
• Replacement of SF6 by Helium for leakage detection
• Installation of recovery stations for returned switchgear
• Installation of facility to separate SF6 from air for internal re-use in HV
Source: ZVEI3rd Int. Conf. on SF6 and the Environment December 1-3, 2004, Scottsdale, AZ
![Page 15: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/15.jpg)
Emission reduction on HV Switchgear* manufacture
( ) 350 323 214 239 ( )
( ) 329 356 (
(
( ) )
FRANCE Estimates Inventory 1 1995 1996 1997 1998 1999 2000 2001 2002 2003
Annual Consumption tons 336 341 210 216 202,7 Emissions in the Country tons 17,5 17,4 13,4 13,2 12,5 13,1 12,4 11,5 10
GERMANY Inventory 1 1995 2003
Annual Consumption tonsEmissions in the Country tons) 20,3 5,4 SWEEDEN Inventory 1
1995 2003 Annual Consumption (tons) 269 390 Emissions in the Country tons) 4,9 1,9
NORWAY Inventory 1 2000 2003
Annual Consumption tons 29 37 Emissions in the Country (tons 2,4 1,2
Source : ECOFYS/CAPIEL Study 2004
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 16: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/16.jpg)
Content• Introduction
– CAPIEL/Kyoto protocol/SF6 Issue
• SF6 in Electrical equipment in Europe– SF6 emmissions reduction strategies – Standards, etc…, Voluntary agreements
• CAPIEL Inventories – Inventory methodology (1998/2000)– Updated Inventory methodology (2005)
• Conclusion
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 17: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/17.jpg)
CAPIEL Inventory Methodology (1998/2000)• Completely based on mass balance method
• SF6 Input -SF6 Output +/-Delta Stock = SF6 Emission
• Implementation : CAPIEL Countries (8)
• SF6 content on name-plates
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 18: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/18.jpg)
CAPIEL Updated Inventory Methodology (2005)Reasons for evolution :
• Difficulty in practical implementation and some discrepancies could appear
• Need to asses banked quantities and related emissions
• Mass balance sometimes difficult to apply
• Figures could not be aggregated at European level
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 19: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/19.jpg)
CAPIEL Updated Inventory Methodology (2005)Main changes :
• Banked quantities :Figure of a reference year + yearly installed/remove quantities
• Emissions : Give choice between mass balance/emission factor as best appropriate
• Implemented in EU 29
• Figures to be aggregated at European level
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 20: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/20.jpg)
3rd Int. Conf. on SF6 and the EnvironmentDecember 1-3, 2004, Scottsdale, AZ
Revised
Emission factors shown represent best practice experience and need to be Confirmed or defined on
Inventory Methodology (sealed pressure systems*; 1kv to 52kv)
*according to IEC 60694 IEC=International Electro technical Commission
country/facility level
![Page 21: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/21.jpg)
3rd Int. Conf. on SF6 and the EnvironmentDecember 1-3, 2004, Scottsdale, AZ
Revised
Emission factors shown represent best practice experience and need to be Confirmed or defined on
Inventory Methodology (closed pressure systems*; above 52kv)
*according to IEC 60694 IEC=International Electro technical Commission
country/facility level
![Page 22: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/22.jpg)
Content
• Introduction – CAPIEL/Kyoto protocol/SF6 Issue
• SF6 in Electrical equipment in Europe – SF6 emmissions reduction strategies – Standards, etc…, Voluntary agreements
• CAPIEL Inventories – Inventory methodology (1998/2000)– Updated Inventory methodology (2005)
• Conclusion
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ
![Page 23: Management of SF6 Emissions from T&D HV equipment in the](https://reader031.vdocument.in/reader031/viewer/2022012421/617581f3f0824d31b03176fe/html5/thumbnails/23.jpg)
Conclusions
• The CAPIEL Inventory Methodology first developed in co-operation with EURELECTRIC
• The Inventory Methodology is updated to stick to reality and intends to be extended to EU29 within CAPIEL (i.e. electrical switchgear manuf.)
However : • National inventories already ran successfully (i.e. DE, CH, FR…)
• Emissions are already reduced thanks to industry’s voluntary actions
3rd 6 and the EnvironmentInt. Conf. on SF
December 1-3, 2004, Scottsdale, AZ