manual de metodologÍa sistema de aire acondicionado
TRANSCRIPT
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 1 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
MANUAL DE METODOLOGÍA SISTEMA DE AIRE ACONDICIONADO
Elaborado por:
SGS
01.10.2020
Revisado por:
ESI
TT.MM.20JJ
Confirmado por:
ESI
TT.MM.20JJ
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 2 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
ÍNDICE
1 OBJETO .......................................................................................................................................................... 3 2 ALCANCE DEL MANUAL ............................................................................................................................... 3 3 DEFINICIONES / ABREVIATURAS UTILIZADAS EN ESTE DOCUMENTO ................................................. 4 4 REFERENCIAS ............................................................................................................................................... 5 5 RESPONSABILIDADES ................................................................................................................................. 5 6 PARÁMETROS Y SU DETERMINACIÓN ....................................................................................................... 7 7 METODOLOGÍA PARA LA MEDICIÓN DE LA EFICIENCIA ENERGÉTICA EN SISTEMAS ELÉCTRICOS: MEDIDAS Y ANÁLISIS ............................................................................................................................................ 8 8 SISTEMAS DE AIRE ACONDICIONADO ..................................................................................................... 10 8.1 ABREVIATURAS .................................................................................................................................. 10 8.2 NORMATIVA APLICABLE .................................................................................................................... 11
Normativa Europea aplicable ..................................................................................................... 11 Normativa española aplicable .................................................................................................... 12
8.3 METODOLOGÍA DE CÁLCULO ...................................................................................................................... 13 8.4 METODOLOGÍA DE LAS MEDICIONES: ANTES DE LA MEJORA .............................................................. 14
Documentación del proyecto ...................................................................................................... 14 Informe de mediciones ............................................................................................................... 15
VALIDACIÓN DEL PROYECTO DE INSTALACIÓN .............................................................................................. 18 8.5 18 8.6 METODOLOGÍA DE MEDICIONES: VALIDACIÓN ANUAL ..................................................................................... 20 9 HISTÓRICO ................................................................................................................................................... 21 10 ANEXO I ........................................................................................................................................................ 22
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 3 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
1 OBJETO
Este manual tiene como objeto la elaboración de un procedimiento práctico para evaluar equipos
eléctricos y térmicos de uso muy frecuente en el sector industrial como son los motores eléctricos,
compresores de aire, equipos de climatización, etc. y determinar los ahorros potenciales de
reemplazar equipos ineficientes por equipos de alta eficiencia con mejoras tecnológicas que reduzcan
su consumo de energía.
El propósito final de este manual es evaluar los proveedores de tecnología (TP) y proyectos adscritos
al Seguro de Ahorro de Energía (ESI).
2 ALCANCE DEL MANUAL
Este manual complementa el Procedimiento general de ESI Europe y sus requisitos, describiendo
los pasos que el Cliente, el Proveedor de la tecnología (TP) y la Entidad de validación (VE) deben
seguir para validar las diferentes tecnologías:
• Propuesta de proyecto: Esta validación se centra en evaluar el valor de Ahorro de Energía
prometido (EScommited) en función de la situación específica del proyecto, calculado por el TP.
• Instalación: El proceso de validación de la instalación incluye una visita al lugar donde se ha
instalado la mejora para verificar por parte de la VE, que se trata de la tecnología previamente
propuesta y que la instalación cumple con todos los requisitos necesarios para el desarrollo
del proyecto.
• Ahorro anual: La validación del ahorro anual consiste en verificar el Ahorro Energético Real
del proyecto (ESactual).
Cada proyecto contendrá los siguientes puntos:
1. Abreviaturas / Definiciones utilizadas en la documentación.
2. Normativa aplicable: Regulaciones internacionales, nacionales o locales para el sistema
aplicable.
3. Descripción de la Metodología. Descripción general de los cálculos.
4. Metodología de medición antes de la mejora: revisión de la documentación del proyecto y las
mediciones necesarias para la validación de la propuesta de proyecto.
5. Validación de la instalación del proyecto: revisión de la documentación necesaria para la
validación de la instalación.
6. Metodología de mediciones anuales: validación anual. Medidas necesarias para la validación
del ahorro anual.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 4 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
3 DEFINICIONES / ABREVIATURAS UTILIZADAS EN ESTE DOCUMENTO
Las siguientes definiciones deben ser consideradas en este documento
ESI Seguro de ahorro energético
Before retrofit technology Indicator (𝐼𝑏𝑟) Indicador basado en mediciones realizadas por el TP (o datalogger) antes de la mejora de la instalación.
After retrofit technology Indicator (𝐼𝑎𝑟) Indicador basado en mediciones reales del consumo de energía registradas en el datalogger después de la mejora de la instalación.
Committed Energy Savings (ESCommitted) Valor porcentual que representa el ahorro de energía prometido para cada proyecto, calculado por el TP para cada tecnología utilizando la metodología ESI. Este valor se incluirá en el contrato ESI.
Actual Energy Savings (ESActual)
Valor porcentual calculado utilizando los datos reales del consumo de energía registrados en el datalogger después de la mejora de la instalación y considerando los factores de operación según el contrato ESI.
Operation factors
Los factores de operación del proyecto definen el consumo energético estimado de una tecnología en el momento de firmar el contrato ESI. Estos factores se utilizan para el cálculo del ahorro de energía prometido (ESCommitted) y el ahorro de energía real (ESActual).
APECA Asociación de Contratación de Rendimiento Energético de Australasia
ASHRAE Sociedad Estadounidense de Ingenieros de Calefacción, Refrigeración y Aire Acondicionado
FENERCOM Fundación de la Energía de la Comunidad de Madrid
EEI Índice de Eficiencia Energética
NIST Instituto Nacional de Estándares y Tecnología de EE.UU.
TP Proveedor de tecnología
VE Entidad de validación
CL Cliente
BR Antes de la mejora: antes de que se realice la mejora en la instalación. Ya sea por una modernización de la instalación o por el reemplazo de un equipo más eficiente.
AR Después de la mejora: después de que se realice la mejora en la instalación. Ya sea por una modernización de la instalación o por el reemplazo de un equipo más eficiente.
PPV Validación de la propuesta de proyecto
PIV Validación de la instalación del proyecto
PAV Validación anual del proyecto
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 5 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
4 REFERENCIAS
Para este procedimiento se han tenido en cuenta los siguientes documentos de referencia:
• Protocolo internacional de medición y verificación del desempeño (IPMVP) -Volumen 1: Conceptos y
opciones para determinar los ahorros de energía y agua.
• APECA (2004), Guía de buenas prácticas para la medición y verificación del ahorro energético.
Gobierno de Australia.
• FENERCOM (2011), “Guía para la evaluación y seguimiento de ahorros en contratos de Servicios
energéticos”. Comunidad del Madrid 2011
• ASHRAE (2014) Directriz 14-2014 MEDICIÓN DE AHORRO DE ENERGÍA, DEMANDA Y AGUA
• "Atlas de las Radiaciones Solares en España a partir de datos del Climate SAF EUMETSAT", publicado
en 2012 por la Agencia Estatal de Meteorología.
5 RESPONSABILIDADES
Las responsabilidades de cada parte, con respecto a este procedimiento, se describen a continuación. Como
regla general, el TP y VE contarán con miembros con responsabilidad y autoridad suficientes para llevar a cabo
estas funciones:
- Tener antecedentes, experiencia y habilidades reconocidas para realizar las actividades de evaluación, análisis de datos y preparación de informes.
- Estar familiarizado con las prácticas de operación y mantenimiento del equipo seleccionado.
Validación Etapas
Responsabilidades Subsección
TP CL VE
Project Proposal validation (PPV) (Validación de la propuesta de proyecto)
• Realizar mediciones con equipos calibrados en la instalación antes de la mejora de la instalación.1
• Calcular los ahorros estimados “prometidos” del proyecto (EScommitted)
• Firmar contrato ESI
• Proporcionar acceso al TP para realizar mediciones
• Proporcionar información del proyecto al TP
• Proporcionar factores de operación del proyecto al TP
• Firmar contrato ESI
• Validar la documentación del proyecto
• Validar los registros de las mediciones.
• Validar cálculos de ahorro
• Proporcionar un resultado de Ahorro energético estimado “prometido” (ESCommitted) para el proyecto adscrito al programa ESI.
4. Metodología de mediciones: Antes de la mejora (br).2
1 Los instrumentos utilizados para las mediciones se calibrarán según los procedimientos desarrollados por el Instituto Nacional de Estándares y Tecnología (NIST). Siempre que sea posible, deben utilizarse patrones primarios y equipo de calibración rastreable por NIST de no menos de tercer orden. El período de recalibración / verificación del equipo no debe exceder los 12 meses. 2 Para calcular el ahorro energético es importante conocer el estado real de la instalación. Este se determinará por medio de mediciones realizadas en la instalación antes de la mejora. Las mediciones anteriores y posteriores a la mejora deberán realizarse en las mismas condiciones. Con estas mediciones se obtendrán valores más precisos para los diferentes ahorros energéticos.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 6 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
Validación Etapas
Responsabilidades Subsección
TP CL VE
Project installation validation (PIV) (Validación del proyecto de instalación)
• Instalación del equipo
• Instalación del data-logger
• Documento de instalación del equipo y del data-logger
• Informar a la VE una vez se haya realizado la mejora en la instalación.
• Asegurar el acceso a la instalación después de la realización del trabajo.
• Validación de la instalación mediante una inspección visual del equipo instalado durante una visita a la instalación.
• Validar el funcionamiento de los equipos instalados en el momento de la visita
• Validar e identificar la existencia de un datalogger en la instalación.
• Reiniciar el datalogger para comenzar el primer año de medición después de la mejora.
5 . Validación del Proyecto de instalación.
Project Annual validation (PAV) (Validación del proyecto anual)
• Proporcionar a la VE junto con el CL, los datos anuales registrados por el datalogger.
• Asegurarse de la re-calibración del data-logger.
• Colaborar con el TP para la recopilación de datos del datalogger.
• Calcular el ESActual (Ahorro Energético Real) basado en los datos proporcionados por el datalogger.
• Si es neceario, calcular la compensación económica.
6 . Metodología de mediciones y Validación anual.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 7 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
6 PARÁMETROS Y SU DETERMINACIÓN
Las unidades de medida utilizadas serán preferentemente las unidades SI. Si debido al uso común o la mejor
comprensión, se aplican unidades imperiales, estos valores también deberán expresarse en las unidades SI.
Las unidades de medida se acordarán al establecer los parámetros de evaluación y así se expresará en el
informe de evaluación.
Para asegurar resultados válidos, el equipo de medición debe calibrarse, verificarse o ambos según los
intervalos especificados en el manual del equipo o antes de su uso. La calibración se realizará según los
estándares de medición trazables nacionales o internacionales; cuando no existan tales estándares, se
registrarán las bases seguidas para la calibración o verificación.
Todos los instrumentos utilizados para la medición, incluidos los instalados de forma permanente, deben tener
un registro de la calibración más reciente. La precisión y los detalles de calibración de todos los dispositivos
deben detallarse en el informe.
Los registros de verificación o calibración de los equipos de medida se conservarán durante un período mínimo
de 2 años por el TP y se presentarán en caso de arbitraje. (Datalogger del consumo de energía, potenciómetro,
caudalímetro de aire, etc.).
Será instalado obligatoriamente un datalogger en la instalación después de la mejora. Este guardará como
mínimo, un registro de mediciones de las siguientes magnitudes:
- Consumo de energía acumulado (kWh)
- Potencia media (kW)
- Horas de funcionamiento acumuladas (h)
En caso de la necesidad de utilización de un dispositivo portátil para realizar mediciones in situ, éste contará
con las siguientes características:
Equipo de medida portátil Parámetros Propiedades
Analizador de redes eléctricas
- Consumo de energía
acumulado (kWh)
- Potencia media (kW)
- Tiempo de
funcionamiento (h)
- El período de recalibración / verificación del
equipo no debe exceder los 12 meses.
- La instrumentación utilizada en las mediciones
se calibrará según procedimientos
desarrollados por el Instituto Nacional de
Estándares y Tecnología (NIST)
- El certificado de calibración estará disponible
durante todo el periodo de medición.
- El certificado de calibración se adjuntará al informe de mediciones.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 8 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
7 METODOLOGÍA PARA LA MEDICIÓN DE LA EFICIENCIA ENERGÉTICA EN SISTEMAS ELÉCTRICOS: MEDIDAS Y ANÁLISIS
A continuación, se detallarán las diferentes tecnologías bajo el alcance del modelo de Seguro de
Ahorro Energético (ESI). Las etapas necesarias para el registro de la tecnología ofrecida por el TP
dentro del modelo ESI y la validación de los proyectos son las siguientes:
Validación - Etapas Subsección Contenido
Validación de la propuesta de Proyecto
6. Metodología de las
mediciones: Antes de la
mejora (br)
• Mediciones antes de la mejora
• Cálculo del EScommited (Ahorro Energéttico
prometido) después de la mejora.
Validación del Proyecto de instalación
7. Validación del Proyecto de
instalación. • Revisión de la documentación
• Visita in situ
• Instalación del Energy datalogger
Validación del Proyecto anual
8. Validación anual • Medidas del Energy datalogger
• Cáculo del ESactual (Ahorro Energético Real)
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 9 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
Para todas las tecnologías se definirán los siguientes indicadores. Esta definición debe basarse en
mediciones o cálculos:
- Medido: valores obtenidos a partir de medidas directas o ficha técnica del equipo.
- Calculado: valores obtenidos de un cálculo.
Indicador Nombre Etapa Unidad Descripción para el caso
base Medido/calculado Responsable
AHORROS
𝐸𝑆𝑐𝑜𝑚𝑚𝑖𝑡𝑡𝑒𝑑
Committed energy savings
(Ahorro Energético
Prometido)
PPV % No aplica Calculado TP
𝐸𝑆𝑎𝑐𝑡𝑢𝑎𝑙
Actual energy savings
(Ahorro Energético Real)
PAV % No aplica Calculado VE
INDICADORES
𝐼𝑏𝑟
Indicator before retrofit
(Indicador antes de la mejora)
PPV -- No aplica Calculado TP
𝐼𝑎𝑟
Indicator after retrofit
(Indicador después de la mejora)
PPV -- No aplica Calculado TP
𝐼𝑎𝑟(𝑦𝑒𝑎𝑟 𝑛)
Indicator after n year
(Indicador después la mejora – año n)
PAV -- No aplica Calculado TP
FACTORES DE OPERACIÓN
ℎ𝑠𝑖𝑔𝑛𝑒𝑑
Yearly Signed operating hours
(Horas de
funcionamiento anuales firmadas)
PPV-PAV
h/año No aplica Estipulado en el
contrato CL
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 10 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8 SISTEMAS DE AIRE ACONDICIONADO
8
8.1 ABREVIATURAS Los términos utilizados en esta sección se describen a continuación:
Valor Nombre Etapa Unidad Medido/ Calculado Responsable
CONCEPTOS GENERALES
𝑆𝐸𝐸𝑅 Seasonal Energy Efficiency Ratio-Heating
PPV -- Medido (*) TP
𝑆𝐶𝑂𝑃 Seasonal Energy Efficiency
Ratio-Cooling PPV --
Medido (*) TP
𝐶𝑂𝑃 Energy Efficiency Ratio-Cooling PPV -- Medido (*) TP
𝐸𝑅𝑅 Energy Efficiency Ratio-Heating PPV -- Medido (*) TP
ANTES DE LA MEJORA
𝐶𝑏𝑟 Energy consumption for 6
months-br PPV kWh Calculado TP
𝑃𝑏𝑟 Calculated input power
according to the signed hours-br PPV kW Calculado TP
DESPUÉS DE LA MEJORA
𝑃𝑎𝑟 Averaged input power between cooling input power and heating
input power-ar PPV kW Calculado TP
𝑃𝑎𝑟 (𝑐𝑜𝑜𝑙𝑖𝑛𝑔) Real input power for cooling season-ar
PPV kW Calculado/ Medido TP
𝑃𝑎𝑟 (ℎ𝑒𝑎𝑡𝑖𝑛𝑔) Real input power for heating
season - ar PPV kW Calculado/ Medido TP
DESPUÉS DE LA MEJORA - AÑO “N”
𝐶𝑎𝑟 (𝑦𝑒𝑎𝑟 𝑛) Yearly energy consumption
according to mandatory datalogger -ar (year n)
PAV kWh Medido VE
𝑃𝑎𝑟 (𝑦𝑒𝑎𝑟 𝑛) Weighted output power
according to the signed hours- ar (year n)
PAV kW Calculado VE
Medido (*): Datos proporcionados por el fabricante.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 11 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8.2 NORMATIVA APLICABLE Las tecnologías propuestas por el TP deberán cumplir la normativa de aplicación vigente en el país donde se
localiza el proyecto:
NORMA EUROPEA:
La Directiva 2010/30 / UE del Parlamento Europeo y del Consejo obliga a la Comisión a adoptar actos
delegados en relación con el etiquetado energético de productos relacionados con la energía que representen
un potencial de ahorro energético significativo, por lo tanto, en relación con el etiquetado energético de
acondicionadores de aire, ha adoptado el reglamento 626/2011.
NORMA ESPAÑOLA:
Reglamento de instalaciones térmicas en edificios (RITE) en su versión consolidada de 2013
NORMATIVA EUROPEA APLICABLE
La Directiva 2010/30 / UE del Parlamento Europeo y del Consejo obliga a la Comisión a adoptar actos
delegados en relación con el etiquetado energético de productos relacionados con la energía que representen
un potencial de ahorro energético significativo, por lo tanto, en relación con el etiquetado energético de
acondicionadores de aire, ha adoptado el reglamento 626/2011.
Este reglamento establece los requisitos para el etiquetado y suministro de información adicional sobre los
productos referentes a acondicionadores de aire conectados a la red con una potencia frigorífica nominal, o
calefacción si el producto no tiene una función frigorífica de 12 kW como máximo.
No se aplicará a:
• Electrodomésticos que utilizan fuentes de energía no eléctricas.
• Acondicionadores de aire en los que el condensador o el evaporador, o ambos, no utilizan aire como
medio de transferencia de calor.
Los equipos con potencia nominal superior a 12 KW deben tener incorporados los valores de etiquetado
energético (COP / SCOP) determinados por la legislación europea vigente, en su caso, o por las entidades
certificadoras europeas.
REGLAMENTO (UE) 2016/2281 DE LA COMISIÓN de 30 de noviembre de 2016 por el que se aplica la
Directiva 2009/125 / CE del Parlamento Europeo y del Consejo por la que se establece un marco para el
establecimiento de requisitos de diseño ecológico para productos relacionados con la energía, con respecto a
los requisitos de diseño ecológico para el calentamiento del aire productos, productos de refrigeración,
enfriadores de proceso de alta temperatura y unidades fan coil.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 12 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
NORMATIVA ESPAÑOLA APLICABLE
En España, el Reglamento de instalaciones térmicas en edificios (RITE) en su versión consolidada de 2013
indica en su instrucción técnica relativa a la eficiencia energética:
• Los equipos de hasta 12 kW de potencia nominal útil, deben tener incorporados los valores de
etiquetado energético (COP / SCOP) correspondientes a la legislación europea vigente.
• Los equipos con una potencia nominal superior a 12 KW deben tener incorporados los valores de
etiquetado energético (COP / SCOP) determinados por la legislación europea vigente, donde exista, o
por los organismos de certificación europeos.
• Los fabricantes proporcionarán tablas de funcionamiento de los equipos a diferentes temperaturas
para facilitar la evaluación y el rendimiento energético de la instalación.
Para otros sistemas de climatización, fuera del alcance de esta norma (Potencia nominal mayor a 12kW),
será necesario un estudio individualizado de la instalación.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 13 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8.3 METODOLOGÍA DE CÁLCULO Los ahorros de energía se determinarán midiendo la capacidad o eficiencia energética de un sistema antes y
después de la mejora, y multiplicando esa diferencia por un factor estipulado (horas de funcionamiento).
Before retrofit
𝐶𝑏𝑟 (𝑘𝑊ℎ) = 𝐸𝑛𝑒𝑟𝑔𝑦 𝑐𝑜𝑚𝑠𝑢𝑝𝑡𝑖𝑜𝑛 𝑓𝑜𝑟 6 𝑚𝑜𝑛𝑡ℎ𝑠 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 𝑏𝑦 𝑡ℎ𝑒 𝑐𝑙𝑖𝑒𝑛𝑡 (𝑏𝑒𝑓𝑜𝑟𝑒 𝑟𝑒𝑡𝑟𝑜𝑓𝑖𝑡 𝑑𝑎𝑡𝑎𝑙𝑜𝑔𝑔𝑒𝑟)
𝐼𝑏𝑟 = 𝑃𝑏𝑟(𝑘𝑊) =𝐶𝑏𝑟(𝑘𝑊ℎ)
ℎ𝑠𝑖𝑔𝑛𝑒𝑑
After retrofit
𝑃𝑎𝑟(𝑘𝑊) =𝑃𝑎𝑟(𝑐𝑜𝑜𝑙𝑖𝑛𝑔)(𝑘𝑊) + 𝑃𝑎𝑟(ℎ𝑒𝑎𝑡𝑖𝑛𝑔)(𝑘𝑊)
2
𝑬𝑺𝒄𝒐𝒎𝒎𝒊𝒕𝒆𝒅(%) = (𝑰𝒃𝒓 − 𝑰𝒂𝒓
𝑰𝒃𝒓
) ∗ 𝟏𝟎𝟎
After retrofit (year n)
𝑰𝒂𝒓 (𝒚𝒆𝒂𝒓 𝒏) = 𝑃𝑎𝑟(𝑦𝑒𝑎𝑟 𝑛)(𝑘𝑊) =𝐶𝑎𝑟 (𝑦𝑒𝑎𝑟 𝑛)(𝑘𝑊ℎ)
ℎ𝑠𝑖𝑔𝑛𝑒𝑑
𝑬𝑺𝒂𝒄𝒕𝒖𝒂𝒍(%) = (𝑰𝒃𝒓−𝑰𝒂𝒓(𝒚𝒆𝒂𝒓 𝒏)
𝑰𝒃𝒓) ∗ 𝟏𝟎𝟎
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 14 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8.4 METODOLOGÍA DE LAS MEDICIONES: ANTES DE LA MEJORA Para la validación de la Propuesta del proyecto, la VE deberá revisar la documentación del proyecto y el informe
de mediciones proporcionado por el TP.
DOCUMENTACIÓN DEL PROYECTO
La documentación del proyecto para la validación de la propuesta de proyecto deberá incluir al menos lo
siguiente:
- Detalles generales del proyecto:
▪ Una representación esquemática de la instalación bajo medición.
▪ Diagrama unifilar de la instalación en el ámbito del proyecto
- Antes de la mejora:
▪ Ficha técnica de la unidad antigua: Tipo, Marca, Potencia, Etiquetado.
▪ Número de equipos a reemplazar (factor de operación)
▪ Número de horas de uso (factor estimado de operación)
- Después de la mejora:
▪ Ficha técnica de la nueva tecnología propuesta: Tipo, Marca, Potencia, Etiquetado.
▪ Número de equipos a instalar (factor de operación)
- Datalogger
▪ Características: rango, precisión, parámetros, certificados de calibración/verificación
▪ Últimos certificados de calibración / verificación. La última verificación / calibración se habrá
realizado como máximo 12 meses antes de su uso para este proyecto.
▪ Datos de consumo energético de los últimos 6 meses (mínimo)
▪ Esquema, mostrando claramente, dónde se encuentra el datalogger de energía existente
en la instalación.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 15 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
INFORME DE MEDICIONES
La VE revisará el informe de mediciones según esta metodología. Significa que el TP deberá realizar y registrar
la medición del consumo del sistema "antes de la mejora" de acuerdo con los siguientes pasos.
El consumo del sistema de aire acondicionado depende de muchos factores externos, como la temperatura
interior y exterior, la ocupación y las horas de funcionamiento, que son muy difíciles de estimar y, en
consecuencia, de simular. Por este motivo, será requisito obligatorio que el cliente haya instalado
previamente un datalogger de energía en el sistema de climatización (al menos 6 meses antes de la
mejora).
In case of a new installation, the technology provided must select a similar project or technology with similar
features in order to use the methodology described in the following points. If there isn´t a similar project, it shall
be established reference values that could be assumed as valid for the proposed base scenario.
The energy datalogger shall cover the consumed energy of the air conditioning system under the scope of the
project during the last 6 months including cold and hot seasons.
The measurement procedure shall be the following:
1) The duration of the measurements will be minimum 6 months. TP shall ensure that the period is
representative of the normal operation conditions. It will be checked following client instructions
(schedule, load…) TP/CL shall use air conditioning system at normal conditions for 12 months
(minimum)
2) The TP shall note the following data from the energy datalogger:
a. Measurement start date: (dd/mm/yyyy)
b. Measurements start time: (hh:mm)
c. Measurement finish date: (dd/mm/yyyy)
d. Measurements finish time: (hh:mm)
e. Energy consumption from the Energy datalogger (kWh)
TP/CL shall take photographs (with date and time) of the energy datalogger screen, showing clearly the
different parameters noted.
Para el caso de una nueva instalación, el TP debe consultar un proyecto o tecnología con características
similares para poder utilizar la metodología descrita en los siguientes puntos. De no existir un proyecto similar,
se establecerán valores de referencia que se puedan asumir como válidos para el escenario base propuesto.
El datalogger medirá y registrará la energía consumida del sistema de aire acondicionado en el alcance del
proyecto durante los últimos 6 meses, incluidas las temporadas de frío y calor.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 16 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
El procedimiento de medición será el siguiente:
1) La duración de las mediciones será mínimo de 6 meses. El TP se asegurará de que el
período sea representativo de las condiciones normales de funcionamiento. Se comprobará
siguiendo las instrucciones del cliente (horario, carga, etc). El TP / CL utilizará el sistema de aire
acondicionado en condiciones normales durante 12 meses (mínimo).
2) El TP deberá registrar los siguientes datos del datalogger:
a. Fecha de inicio de la medición: (dd / mm / aaaa)
b. Hora de inicio de las mediciones: (hh: mm)
C. Fecha de finalización de la medición: (dd / mm / aaaa)
d. Tiempo de finalización de las medidas: (hh: mm)
e. Consumo de energía registrado en el datalogger (kWh)
El TP / CL tomará fotografías (con fecha y hora) de la pantalla del datalogger, mostrando
claramente los diferentes parámetros anotados.
3) El TP calculará la potencia ponderada durante 6 meses siguiendo la esta fórmula:
𝑰𝒃𝒓 = 𝑃𝑏𝑟(𝑘𝑊) =𝐶𝑏𝑟(𝑘𝑊ℎ)
ℎ𝑠𝑖𝑔𝑛𝑒𝑑
𝐶𝑏𝑟 (𝑘𝑊ℎ) = 𝐸𝑛𝑒𝑟𝑔𝑦 𝑐𝑜𝑚𝑠𝑢𝑝𝑡𝑖𝑜𝑛 𝑓𝑜𝑟 6 𝑚𝑜𝑛𝑡ℎ𝑠 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 𝑏𝑦 𝑡ℎ𝑒 𝑐𝑙𝑖𝑒𝑛𝑡 (𝑏𝑒𝑓𝑜𝑟𝑒 𝑟𝑒𝑡𝑟𝑜𝑓𝑖𝑡 𝑑𝑎𝑡𝑎𝑙𝑜𝑔𝑔𝑒𝑟)
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 17 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
4) La VE validará los indicadores y consumos calculados acorde a esta metodología:
Para calcular la potencia de entrada del equipo post-mejora será necesario recopilar los datos
de la potencia de refrigeración y calefacción. Los siguientes datos se pueden obtener de la ficha
técnica del equipo (potencia de refrigeración y calefacción).
𝑰𝒂𝒓 = 𝑃𝑎𝑟(𝑘𝑊) =𝑃𝑎𝑟(𝑐𝑜𝑜𝑙𝑖𝑛𝑔)(𝑘𝑊) + 𝑃𝑎𝑟(ℎ𝑒𝑎𝑡𝑖𝑛𝑔)(𝑘𝑊)
2
Para este equipo, el Ahorro Energético estimado prometido, 𝑬𝑺𝒄𝒐𝒎𝒎𝒊𝒕𝒆𝒅(%) , se calcula con la
siguiente fórmula:
𝑬𝑺𝒄𝒐𝒎𝒎𝒊𝒕𝒆𝒅(%) = (𝑰𝒃𝒓 − 𝑰𝒂𝒓
𝑰𝒃𝒓
) ∗ 𝟏𝟎𝟎
Para proyectos, fuera del alcance, será necesario un estudio individual. Si no es posible seguir la
metodología, será necesario definir un método alternativo basado en mediciones estacionales de EER
(refrigeración) o COP (calefacción) con métodos externos, para estimar estimate the 𝑬𝑺𝒄𝒐𝒎𝒎𝒊𝒕𝒆𝒅(%).
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 18 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8.5 VALIDACIÓN DEL PROYECTO DE INSTALACIÓN
VE shall verify the project documentation of the new equipment provided by the TP: The required documentation
for the installation validation will be at least the following:
- General projects details: General project differences between the Project Proposal and the finalized
project, (if any)
- After retrofit status
▪ Data sheet of final new unit: (brand, type, voltage, intensity, cooling and heating power, EER,
COP)
▪ Final number of equipment to replace:
▪ Delivery receipt for the new equipment.
- Energy datalogger
▪ Features: range, accuracy, parameters, calibrations/verifications certificates)
▪ Last calibration/verification certificates.
▪ Electricity diagram which shows clearly that the energy datalogger only considers the
equipment under the scope of the project.
VE shall note the current measurement from the energy datalogger installed on site. The options are the
following:
a) Reset the energy datalogger (if is possible)
b) If option A isn´t possible, note the following parameters from the energy datalogger and take photographs
of the different screens.:
a. Accumulated consumption 𝐴𝐶𝑎𝑟 (𝑦𝑒𝑎𝑟 𝑛−1)(𝑘𝑊ℎ)
b. Measurement date: (dd/mm/yyyy)
c. Measurements time: (hh:mm)
These reset point/s will be the reference start point for the annual validations.
El VE deberá verificar la documentación del proyecto del nuevo equipo proporcionada por el CE: La
documentación requerida para la validación de la instalación incluirá como mínimo lo siguiente:
- Detalles generales del proyecto: diferencias generales del proyecto entre la propuesta de proyecto
y el proyecto finalizado (si corresponde).
- Instalación después de la mejora:
▪ Ficha técnica de la nueva unidad final: (marca, tipo, voltaje, intensidad, potencia de
refrigeración y calefacción, EER, COP)
▪ Número final de equipos a reemplazar.
▪ Recibo de entrega del nuevo equipo.
- Datalogger
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 19 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
▪ Características: rango, precisión, parámetros, certificados de calibraciones / verificaciones
▪ Últimos certificados de calibración / verificación.
▪ Diagrama de electricidad que muestre claramente que el datalogger de energía solo
considera los equipos bajo el alcance del proyecto.
El VE deberá registrar la medición de corriente del datalogger instalado en el nuevo equipo. Las opciones son
las siguientes:
a) Reiniciar el datalogger (si es posible)
b) Si la opción A no es posible, tenga en cuenta los siguientes parámetros del datalogger y tome fotografías
de las diferentes pantallas:
▪ Consumo acumulado: Car (año n=1) (kWh)
▪ Fecha de medición: (dd / mm / aaaa)
▪ Tiempo de medidas: (hh: mm)
Estos datos de reinicio serán el punto de partida de referencia para las mediciones de las validaciones
anuales.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 20 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
8.6 METODOLOGÍA DE MEDICIONES: VALIDACIÓN ANUAL
Se debe instalar un datalogger en el momento de la instalación del nuevo equipo. La información del
consumo de energía registrada en el datalogger cubrirá solo los nuevos equipos dentro del alcance del
proyecto.
Para calcular los diferentes indicadores, los factores de operación serán los mismos antes y después de la
instalación de la mejora.
La metodología de mediciones anuales debe ser la siguiente:
1) La duración de las mediciones serán los últimos 6 meses posteriores a la instalación del nuevo
sistema de climatización. La fecha de inicio de referencia será el día en que se realizó la validación del
proyecto de instalación. (Ver sección 8.5)
2) El TP deberá registrar los siguientes datos del datalogger:
a. Fecha de finalización de la medición: (dd / mm / aaaa)
b. Tiempo de finalización de las medidas: (hh: mm)
C. Consumo de energía registrado en el datalogger (kWh)
El TP / CL tomará fotografías (con fecha y hora) de la pantalla del datalogger, mostrando claramente
los diferentes parámetros anotados.
3) El TP calculará el consumo de energía durante el último año como la diferencia entre dos años
consecutivos:
𝑰𝒂𝒓 (𝒚𝒆𝒂𝒓 𝒏) = 𝑃𝑎𝑟(𝑦𝑒𝑎𝑟 𝑛)(𝑘𝑊) =𝐶𝑎𝑟 (𝑦𝑒𝑎𝑟 𝑛)(𝑘𝑊ℎ)
ℎ𝑠𝑖𝑔𝑛𝑒𝑑
4) La VE validará los cálculos de los indicadores y consumos realizados acorde a esta metodología.
A continuación, el TP calculará el Ahorro energético real, 𝑬𝑺𝒂𝒄𝒕𝒖𝒂𝒍(%), utilizando los datos de consumo
energético obtenidos por el datalogger instalado en el nuevo equipo.
𝑬𝑺𝒂𝒄𝒕𝒖𝒂𝒍(%) = (𝑰𝒃𝒓−𝑰𝒂𝒓(𝒚𝒆𝒂𝒓 𝒏)
𝑰𝒃𝒓) ∗ 𝟏𝟎𝟎
Para proyectos fuera del alcance, será necesario un estudio detallado del proyecto. El Ahorro energético
real, 𝑬𝑺𝒂𝒄𝒕𝒖𝒂𝒍(%), se calculará como la diferencia entre los consumos antes y después de la mejora.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 21 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
9 HISTÓRICO
9
Version replaces Key changes:
0 1 First version
-
The changes has been highlighted using this format
This history includes only the last 3 revisions.
ESI Europe Methodoly Handbook SISTEMA DE AIRE ACONDICIONADO
Número : VA XXX XXX
Versión : 01
Página : Pag. 22 / 22
Owner : BASE
BASE Only valid at the time of printing: Printing date: 18.01.2021
10 ANEXO I
Tabla 01: Clasificación de eficiencia energética de las unidades de aire acondicionado. Fuente: Directiva 2010/30 / UE (Sistema de aire acondicionado)
Índcice de eficiencia energética Rendimiento refrigeración Rendimiento calefacción
A+++ SEER ≥ 8,50 SCOP ≥ 5,10
A++ 6,10 ≤ SEER < 8,50 4,60 ≤ SCOP < 5,10
A+ 5,60 ≤ SEER < 6,10 4,00 ≤ SCOP < 4,60
A 5,10 ≤ SEER < 5,60 3,40 ≤ SCOP < 4,00
B 4,60 ≤ SEER < 5,10 3,10 ≤ SCOP < 3,40
C 4,10 ≤ SEER < 4,60 2,80 ≤ SCOP < 3,10
D 3,60 ≤ SEER < 4,10 2,50 ≤ SCOP < 2,80
E 3,10 ≤ SEER < 3,60 2,20 ≤ SCOP < 2,50
F 2,60 ≤ SEER < 3,10 1,90 ≤ SCOP < 2,20
G SEER < 2,60 SCOP < 1,90