POWER SUPPLY SYSTEM

Single Phase Power Shelves

With

ES-48V/25A and NSCSU

CUSTOMER DOCUMENTATION

Page 2: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Single Phase ES-48V/25A Series

Power System

Installation, Operation and Maintenance Manual

JUNE – 08 REV-2 2

Page 3: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Contents

1. GENERAL ..………………..51.1 Using this Manual …..……………….51.2 Safety Notice …..……………….51.3 Environmental …..……………….6

2. INTRODUCTION AND FEATURES ..………………..72.1 Introduction …..……………….72.2 Features …..……………….72.3 Shelf Outlook …..……………….82.4 Shelf Dimension …..……………….92.5 Maintenance Bypass Switch …..……………….8

3. GENERAL SPECIFICATIONS …..………………113.1 System General Specifications …..………………113.2 System Configuration …..………………12

4. SAFETY INSTRUCTIONS …..………………134.1 General Instructions …..………………134.2 Special Instructions …..………………15

5. NEW SMART CONTROL & SUPERVISORY UNIT (NSCSU)

…..……………….16

5.1 Software Interface …..……………….165.2 System Management …..……………….165.3 Remote Management …..……………….175.4 System Control & Parameter

Adjustment …..……………….17

6. Local and Remote Monitoring & Control

…..……………….32

6.1 Description …..……………….326.2 System Requirements …..……………….326.3 Configuration and Monitoring …..……………….336.4 Remote Monitoring System …..……………….39

7. RECTIFIER .……..……………407.1 Description .……..……………40

8. SYSTEM ALARMS & TROUBLE SHOOTING

…..……………….44

8.1 AC Fail/AC High Voltage / AC Low Voltage Alarm Description

…..……………….44

8.2 DC Output Voltage High/Low (HV/LV) …..……………….458.3 DC Circuit Breaker Trip Alarm …..……………….45

JUNE – 08 REV-2 3

Page 4: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual8.4 Over-Temperature Alarm …..……………….468.5 NSCSU Fail …..……………….478.5 Rectifier Fail Alarm …..……………….47

9 INSTALLATION …..……………….489.1 Tools Required …..……………….489.2 Preliminary Inspection …..……………….489.3 Shelf Mounting …..……………….489.4 Module Installation …..……………….489.5 Shelf Wiring …..……………….489.6 Frame Grounding …..……………….48

10. MAINTENANCE …..……………….4910.1 Cleaning and Maintenance …..……………….4910.2 Removing and Replacing a Rectifier

Module …..……………….49

10.3 Float Voltage Adjusting …..……………….5010.4 Equalize Voltage Adjusting …..……………….5010.5 Replacing a Rectifier Cooling Fan …..……………….50

JUNE – 08 REV-2 4

Page 5: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

1. GENERAL

1.1 Using this Manual

This manual contains specifications and instructions to properly install and maintain the Delta MCS-1400 power shelf. Component specifications and drawings and contained in this manual.

Included in this manual is the operation and maintenance of the New Smart Control & Supervisory Unit (NSCSU), ES-48V Switch Mode Rectifier (SMR), system status and alarms, troubleshooting and system maintenance.

Step by step procedures required for installation and turn-up are detailed. All equipment parameter settings, adjustments and confirmation as well as system monitoring, operations and maintenance procedures are included.

Warnings are printed in bold lettering and alert the installation or maintenance craftsperson of a potential hazard to either or the craftsperson if the warning advisement is not followed.

1.2 Safety Notice

Delta products are not liable for any hazards incurred by not following proper safety procedures, Installation, Operation and maintenance personnel should always follow these safety rules:

Do not install or remove any SMR with the AC breaker ON. The AC breaker must be switched to the OFF (0) position prior to inserting a module into a shelf to avoid any damage to the rectifier.

Before switching ON the system, the AC input frequency and voltage must be verified. AC breaker rating and type should be adequate and other environmental conditions as noted in the specifications should meet.

The system has passed stringent system testing prior to shipment. To avoid electrical shock, the MCS system requires a single ground point permanently connected to earth ground.

An AC breaker must be provided for adequate isolation between the system input and commercial AC main.

The environment should be dust free and controlled by an HV AC system. The area must be free of any flammable vapors or fluids.

To avoid electrical hazard, the covers must not be removed on any component including the NSCSU, MCS rectifier etc.

Circuit breakers must be replaced with approved circuit breakers, meeting the original design specification.

JUNE – 08 REV-2 5

Page 6: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

All AC connections must be made per the latest issue of the National Electrical Code and must also confirm to all local codes.

1.3 Environmental

Input Voltage : 230V AC single phase / 400V AC Three phase.Input frequency : 45 – 65 Hz.Operating Temperature : 0 - 50˚ CHumidity : 0% - 95% RH (Non - Condensing)Floor Load Density : 600 Kg/M2

Recommended Clearance : Minimum 4 inches from side walls and 6 inches from rear wall.

JUNE – 08 REV-2 6

Page 7: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

2. INTRODUCTION AND FEATURES

2.1 Introduction

Delta MCS 1400 power shelf is designed to meet the demands of today’s and tomorrow’s wireless and wire-line network applications. It combines a compact, modular design and intelligent power features.

A typical Delta MCS 1400 power shelf, consisting of compact rack enclosures, 1400W rectifier modules and related power distribution units, is under the control of New Smart Control and Supervisory Unit (NSCSU). All system functions and management can be operated via the user friendly LCD interface. Meanwhile, with the Delta power system management software, the remote power system management function is also available via internet, intranet or telephone line,

Delta's MCS 1400 power shelf employ state-of-the-art design to ensure high reliability and performance. All components pass stringent reliability testing. The MCS-1400 series power module is UL and cUL approved and manufactured in our modern ISO 9001 and TL 9000 certified facility.

2.2 Features

User friendly (LCD) operation interface (128*64 dots display)

Wide input voltage range, 90~300 VAC good for unstable utility environment.

Module design, front access for simple installation and maintenance.

Compact design, saves valuable floor space.

1400W output high efficiency, hot pluggable rectifier module.

Temperature Compensation Float Voltage Control for VRLA Batteries.

Front Access for Simplified Operation and Maintenance.

54V/125 ~ 200A (Identify 1~2 specific strength/features for the shelf).

Intelligent remote system monitoring and control (RMS software function)

Comprehensive AC, DC, battery, power distribution management function.

High power density saves valuable floor space.

JUNE – 08 REV-2 7

Page 8: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

2.3 Shelf outlook2.3.1 19” Shelf

2.3.2 23” Shelf

JUNE – 08 REV-2 8

Page 9: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

2.4 Shelf Dimension

2.4.1 19” Shelf

JUNE – 08 REV-2 9

Page 10: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

2.4.2 23” Shelf

JUNE – 08 REV-2 10

Page 11: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

JUNE – 08 REV-2 11

Page 12: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Maintenance Bypass Switch

2.5 For Maintenance purpose system is having maintenance bypass switch inside the Class-B surge arrestor box. Upward position indicates that system is in OFF position & downward is to turn on the Switch.

3. GENERAL SPECIFICATIONS

3.1 System General Specifications

Item Specification/Function

AC InputSingle phase two wire / Three phase four wire:

230V/ 400 V AC, 50Hz

Shelf Capacity-48V/25 ~ 125A (1 ~ 5 rectifiers), 19” shelf

-48V/25 ~ 150A (1 ~ 6 rectifiers), 23” shelf

System Capacity-48V/200A (Max. 2 shelves), 19” shelf

-48V/200A (Max. 2 shelves), 23” shelf

Contactor Rating 125 Amp (all three Contactors)

Rectifier Rectifier module: -48V/25A

New Smart Control & Supervisory Unit

LCD Display: 128*64characters

LED Indicator: 3

CommunicationWeb Server + Local Access or

Dial-up Modem + Web Server

Remote Monitoring and Control

RS232/RS485

By RMS software (Use RS232/RS485 Interface)

Operating Temperature +32 ˚F~+122˚F (0℃~+50℃)Storage Temperature -40˚F~+158˚F (-40℃~+70℃) Humidity 0~95% Relative Humidity, Non-CondensingAltitude -500~+10,000 Feet (-152~3048m)Acoustic 55 dB @ 1 meter

Note! The system capacity, quantity of rectifier, Power distribution, qty. and rate of breaker

JUNE – 08 REV-2 12

Page 13: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

are all based on contract. {Please see the System Drawings in the rear pocket of this booklet}

3.2 System Configuration

3.2.1 19” Shelf

Item Specification/Function

Dimensions (WxDxH) 19.02 in. x 14.12 in. x 6.04 in. / 483.2mm x 358.6mm x 153.5mm

Rack 5 rectifier positions per shelf, Max. 2 shelves (10 rectifiers)

3.2.2 23” Shelf

Item Specification/Function

Dimensions (WxDxH) 23.00in. x 14.11 in. x 6.04 in. / 584.2mm x 358.3mm x 153.5mm

Rack 6 rectifier positions per shelf, Max. 2 shelves (12 rectifiers)

JUNE – 08 REV-2 13

Page 14: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

4. SAFETY INSTRUCTIONS

Warning - Please read the following instructions carefully. Ignoring these instructions may result in a loss of life or a health hazard for users working with the equipment and/or in damage to the equipment itself. These safety instructions are an extension of any national laws governing health and safety at work and the applicable EN, DIN, SEV, VDE and CEI standards and any regulations of the statutory authorities. The manufacturer cannot be held responsible for any danger or damage resulting from incorrect operation or usage of the equipment, failure to observe the instructions in the user’s documentation and/or failure to observe the safety instructions.

4.1 General Instructions

No user replaceable or serviceable parts inside- In case of any service aspect please contact service provider. Operation of and work on the equipment or parts thereof may only be performed by professional persons (qualified technicians) with appropriate experience who have been successfully trained by the manufacturer/ distributor (= authorized person)

The weight of the components (specified on the front of the unit) requires that physically able-bodied persons be employed for installing / assembling the equipment or parts thereof.

If work on the equipment or parts thereof is necessary with the equipment under present voltage, another qualified technicians or a supervisor must be present in addition to the electrician performing the work. The supervisor should be capable of providing first aid in case of electrical hazard. Providing the electrician with an emergency switch or disconnection strap, so-called "dead man’s switch", is not sufficient protection.

Work on the equipment may only be carried out using insulated safety tools and appropriate protective clothing (shoes, gloves, safety spectacles, etc).

JUNE – 08 REV-2 14

Page 15: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

There is an increased risk of an accident and electrical hazard when working on compact equipment (different components mounted in a single cabinet, e.g. rectifier/inverter modules, DC distribution and battery connection), due to the close proximity of the various different components. Work should therefore be carried out with an extra attention to safety, and appropriate insulating covers over the live electrical parts must be provided for protection against accidental contact.

If the power supply equipment is not fitted with a disconnecting switch or equivalent device unit, for isolating it from the AC mains or any other hazardous voltage source, the operator of the power supply equipment is responsible for fitting the mains distribution board, battery system or other supplying equipment with appropriate disconnection switch conforming to the relevant regulations.

Removing or inserting components from or into the equipment may result in changes to the performance of the equipment. The operator is therefore responsible for the consequences of any change in the hardware configuration that are made without an agreement with the manufacturer or his local representative.

The operator of the equipment is responsible for ensuring that personnel concerned with the equipment (authorised persons) are provided with safety training when the equipment is installed or when starting their employment and at regular 6-monthly intervals thereafter.

The operator of the equipment is responsible for ensuring that the rooms in which the equipment is set up and in which the batteries are used are treated as electrical equipment rooms, which are only accessible to qualified personnel (authorised persons).

The operator of the equipment is responsible for ensuring that the equipment is installed in suitable rooms, if necessary with air-conditioning. If forced cooling (fan ventilation) is used, there must be adequate airflow in the room, as well as heating/cooling.

The units or individual parts of the equipment may only be opened by qualified employees (authorised persons) of the equipment operator, who have attended a special repair training course held by the manufacturer or his local representative.

The operator of the equipment is responsible for ensuring that the rectifier/ inverter/distributor rack is securely locked and not accessible to unauthorised persons.

Installation and dismantling of the equipment or parts thereof, as well as the laying of the connection cables may only be carried out by persons trained by the manufacturer/distributor (authorised persons).

JUNE – 08 REV-2 15

Page 16: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

The installation instructions and specifications in this user manual are a part of these safety instructions. The order of installation and the specified limit values must be adhered to in order to guarantee that the equipment is correctly installed and operated.

The environment should be dust free and controlled by an HV AC system. The area must be free of any flammable vapours or fluids.

To avoid electrical hazard, the covers must not be removed on any component.

All AC connections must be made as per the latest issue of the National Electrical Code and must also confirm to all local codes.

4.2 Special Instructions

Before switching `ON` the system, the AC input frequency and voltage must be verified, AC break rating and type should be adequate, and other environmental conditions as noted in the specifications should meet.

Localised areas of high temperature (> 70 C) may occur within the rectifier/ inverter/distributor rack. Adequate precautions against accidental burns must be taken.

Fuses should only be gripped using the tools provided for this purpose (Load-break switch handles, etc.).

Ensure adequate insulation from ground potential (earth) when working on the rack or changing fuses.

The power system may have dual energy supply by means of primary and secondary energy sources, and operator is responsible to secure the proper precautions by separating or disconnecting the sources for maintenance or service purposes.

Some of the potentiometers for adjusting equipment components are mounted under the unit covers and can only be accessed through the ventilation slots of these components. Take care when making adjustments, and use appropriate tools (e.g. an insulated screwdriver for trimming), otherwise sensitive components may be damaged.

Only suitable measuring devices (e.g. high-impedance multimeter) may be connected to the voltage and current measurement sockets.

JUNE – 08 REV-2 16

Page 17: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Incorrect operation of the equipment or parts thereof may alter the operating state of the system, trigger false alarms or discharge the batteries connected to the system. Ensure that the settings conform to the specifications, the system configuration and the limit values that you require.

Make sure that the voltage values for all components are set correctly. Incorrect voltage settings may lead to an increase in the battery voltage and the consequent danger of explosion.

Ensure that the alarm limit values (trigger thresholds) are set correctly. Incorrect settings may trigger false alarms and cause the rectifier/inverter modules to switch off.

All temporary manipulations of the equipment or parts thereof that are carried out (e.g. for test purposes) must be reset manually. Automatic reset facilities are not provided.

5. NEW SMART CONTROL & SUPERVISORY UNIT (NSCSU)

5.1 Software Interface

Power system controller : Delta New Smart Control & Supervisory Unit (NSCSU)

Display : LCD 128 x 64 dots display

LED (Major, Minor, EQU)Push button : 4 push buttons on the NSCSU LCD display.

They are used to control the power system.Language : English / Chinese

JUNE – 08 REV-2 17

Page 18: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

5.2 System Management

Monitoring : AC input information

DC information

Rectifier information

Battery Information

DC load information

Environment detection

Parameter Setting : System output parameter setting

Alarm threhold setting

Alarm configuration setting

System relay setting

Others : Remote management

Event log

Efficiency management

Battery discharge test function

5.3 Remote Management

Method : RS-232/485 cable (9 pin), Internet/Intranet, SNMP

SW Interface: (Optional) : Delta Remote Management Software

Network Management Software

Internet Browser

Hardware Interface: (Optional) : RS-232/RJ 45

5.4 System Control & Parameter Adjustment

A 128*64 characters LCD Display is on the NSCSU for display system status as the following:

Main page: DCV, DCI, System status, Alarm

Buttons A BACK; B ↑; C ↓; D ENTER

5.4.1 System Real Time Operation Status

The system status is displayed on the front of the NSCSU. The Main page is always displayed during normal operation.

Main page:DCV 54.0V

JUNE – 08 REV-2 18

Page 19: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

DCI 0ASys. Sta FLAlarm Existing

DCV: System output DC Voltage

DCI: Total system output current

Sys Sta: System status

Alarm Existing: “Alarm Existing” will display if alarm had occurred

5.4.2 Sys InfoSys SettingCurr. Alarm

RectifierBatteryEvent LogCurr. SettingAC & Temp.Date & Version

5.4.3 Rectifier Information

Rectifier Info01 0.0A OK02 0.0A OK03 0.0A OK

---

24 0.0A OKTotal 24 Rectifiers can be displayed

Rectifier Alarm Info

01

02

-

-

30

JUNE – 08 REV-2 19

Press Enter

Press Enter

Page 20: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Press Enter

No. Version CHSUM

01 1.0 36B5H

02 1.0 36B5H

-

-

30 1.0 36B5H

5.4.4 Battery InformationRectifierBatteryEvent LogCurr. SettingAC & Temp.Date & Version

Battery 1Charging…Current 0.0ATemp….. °C

Battery 2Charging…Current 0.0ATemp….. °C

Battery 3No existence

5.4.5 Event InformationRectifierBatteryEvent LogCurr. SettingAC & Temp.

JUNE – 08 REV-2 20

Press Enter

Page 21: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Date & Version

00 XXXX AlarmMM/DD HH:MM:SS

02 XXXX AlarmMM/DD HH:MM:SS

---100 XXXX Alarm

MM/DD HH:MM:SSNote: Total 100 events can be displayed

5.4.6 Current Setting Information

RectifierBatteryEvent LogCurr. SettingAC & Temp.Date & Version

Press Enter

DC SettingAlarm Setting Batt. SettingOther Setting

Press Enter

DC SettingEQU VLT 55.2VFL VLT 54.0VSMR CL 26.2A

5.4.7 Alarm SettingDC SettingAlarm Setting Batt. SettingOther Setting

Press Enter

Alarm SettingHV 56.0VLV 45.6V

JUNE – 08 REV-2 21

Press Enter

Page 22: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

HVSD 56.5VACH 300VAVL 90VHT 55°CLT -15°CHTSD 75°CLTSD -40°CTST ALM ONBATT OTP 50°CLVDS1 44.4VLVDS2 44.4VLVDS3 44.6VBatt UnB ON

5.4.8 Battery Setting

DC SettingAlarm Setting Batt. SettingOther Setting

Press Enter

i. B- ParameterBatt. ChargeT-COMPBDT SettingB-EQU Setting

Press Enter

Batt. CapacityBatt.1 xxx AHBatt.2 xxx AHBatt.3 xxx AHStop EQU…Max. Time 8HrMin. Curr. 0.03CExtra Time 0Hr

B- Parameter(B) Batt. Charge

T-COMPBDT SettingB-EQU Setting

Press Enter

On Mains

JUNE – 08 REV-2 22

Page 23: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

On Standby

Press Enter

Charge & CLBatt.1 0.10CBatt.2 0.10CBatt.3 0.10C

On MainsOn Standby

Press Enter

Charge & CLBatt.1 0.05CBatt.2 0.05CBatt.3 0.05C

B- ParameterBatt. Charge

(C) T-COMPBDT SettingB-EQU Setting

Press Enter

T- COMP ENABLEMode: LinearLinearNon Linear

Press EnterCoef 3.0mV/°CUpper 55.8VLower 52.8VT-START 27°C

T- COMP ENABLEMode: Linear

LinearNon Linear

Press Enter

T0,V0: 0,56.8T1,V1: 15,54.4T2,V2: 35,54.4T3,V3: 60,51.6

B- Parameter

JUNE – 08 REV-2 23

Page 24: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Batt. ChargeT-COMP

(D) BDT SettingB-EQU Setting

Press Enter

Periodic BDTStatus ONNext Batt TestYY/MM/DD HH:MMBDT1 0.10CEnd VLT 45.0VBDT Time 2Hr

B- ParameterBatt. ChargeT-COMPBDT Setting

(E) B-EQU Setting

Press Enter

Periodic B-EQUStatus ONNext EQUYY/MM/DD HH:MMPeriodic B-EQUPeriod. 6MDate 1DTime 0Hr

5.4.9 Other Settings

DC SettingAlarm Setting Batt. SettingOther Setting

Press Enter

Eficnt Func OFF

5.4.10 AC & Temperature Information

RectifierBatteryEvent LogCurr. SettingAC & Temp.Date & Version

JUNE – 08 REV-2 24

Page 25: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Press Enter

ACVACV1 xxxVACV2 xxxVACV3 xxxVAmbient Temp xx °C

5.4.11 Date & Version

RectifierBatteryEvent LogCurr. SettingAC & Temp.Date & Version

Press Enter

Current DateYYYY/MM/DDCurrent TimeHH:MM:SSSW Version1.03ChecksumFB44H

5.4.12 System Settings

Sys InfoSys SettingCurr. Alarm

Press Enter

5.4.13 DCV Settings

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator

JUNE – 08 REV-2 25

Page 26: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance ManualAlarm Reset Temp. Unit

Press Enter

DC SettingEQU VLT 55.2V (48.0V- 56.0V)FL VLT 54.0V (48.0V- 56.0V)SMR CL 26.2.0A (5.0A-250.0A)

5.4.14 Alarm settings

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Alarm SettingHV ON Enter – (Enable/Disable)/SETTPOINT (56.0V) - Range (55.0-57.5V)LV ON Enter – (Enable/Disable)/SETTPOINT (45.6V) - Range (44.0-50.0V)HVSD Enter - SETTPOINT (56.5V) - Range (56.0-59.5V)ACH ON Enter – (Enable/Disable)/SETTPOINT (300V) - Range (230-500V)ACL ON Enter – (Enable/Disable)/SETTPOINT (90V) - Range (85-500V)HT ON Enter – (Enable/Disable)/SETTPOINT (55) - Range (35°C -75°C)LT ON Enter – (Enable/Disable)/SETTPOINT (-15°C) - Range (-40°C- +10°C)HTSD Enter - SETTPOINT (75°C) - Range (45°C -75°C)Batt OTPON Enter – (Enable/Disable)/SETTPOINT (50°C) - Range (30°C- +50°C)LVDS1 Enter - SETTPOINT (44.4V) - Range (0.0-48.0V)LVDS2 Enter - SETTPOINT (44.4V) - Range (0.0-48.0V)LVDS3 Enter - SETTPOINT (44.6V) - Range (0.0-48.0V)LVDS Recover Enter- SETTPOINT (46.0V) - Range (46.0-52.0V)Batt Tst ON Enter – (Enable/Disable)Batt UnB ON Enter – (Enable/Disable)/SETTPOINT (1.0V) - Range (0.5V-4.0V)Over Load ON Enter – (Enable/Disable)/SETTPOINT (200A) - Range (50A-3000A)

5.4.15 Batt. Setting

DCV SettingAlarm SettingBatt. SettingPasswordDate Setting

JUNE – 08 REV-2 26

Page 27: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance ManualLanguageEfficiency MgtGeneratorAlarm Reset Temp. Unit

Press Enter

Battery Parameter Setting-

B- Parameter Batt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 ControlLVDS3 Control

Press Enter

B-Parameter

Capacity EnterBatt 1 & 2 SETTPOINT (400AH) - Range (0AH-6000AH)Batt 3 SETTPOINT (0AH) - Range (0AH-6000AH)EQU Stop Enter

Max Time SETTPOINT (8Hr) - Range (1r-24Hr)Min Curr SETTPOINT (0.03C) - Range (0.01C -0.06C)Extra Time SETTPOINT (0Hr) - Range (0 -12Hr)

EQU Enable EnterBatt Cap ON Enter (ON/OFF)/SETTPOINT (50%) - Range (30-90%)AC Time ON Enter (ON/OFF)/SETTPOINT (0Hr) - Range (0r-24Hr)Batt VLT ON Enter (ON/OFF)/SETTPOINT (46.0V) - Range (42-54V)

B- ParameterBatt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 ControlLVDS3 Control

Press Enter

Battery Charge Setting-

JUNE – 08 REV-2 27

Page 28: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance ManualOn MainsOn Standby

Press EnterCharge & CLBatt.1 0.10C Enter - Range (0.02C-0.20C)Batt.2 0.10C Enter - Range (0.02C-0.20C)Batt.3 0.10C Enter - Range (0.02C-0.20C)

On MainsOn Standby

Press Enter Charge & CLBatt.1 0.05C Enter - Range (0.02C-0.10C)Batt.2 0.05C Enter - Range (0.02C-0.10C)Batt.3 0.05C Enter - Range (0.02C-0.10C)

B- ParameterBatt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 ControlLVDS3 Control

Press Enter

Battery T-Comp Setting-

Enable/Disbale EnterChoose T-COMPLinearNon- LinearParameter Enter

Coef 3.0mV/°C Enter Range (0.1mV/°C - 4.0mV/°C) Upper 55.8V Enter Range (53V – 56.0V)Lower 52.8V Enter Range (50V – 53.0V)T-START 27°C Enter Range (15°C - 35°C)

B- ParameterBatt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 Control

JUNE – 08 REV-2 28

Page 29: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance ManualLVDS3 Control

Press Enter

Manual BDTPeriodic BDTNext BDT HH:MM

YYYY/MM/DD

Battery Discharge Test Setting-

Press Enter

Manual BDTStatus: OFFSetting Enter

BDT1 0.10C Enter Range (0.05C-0.5C)End VLT 45.0V Enter Range (42.0-52.0V)BDT Time 2Hr Enter Range ( 1Hr- 2Hr)

Start MBDT

Manual BDTPeriodic BDT Status: ON

Setting

Enter

BDT1 0.10C Enter Range (0.05C-0.5C)End VLT 45.0V Enter Range (42.0-52.0V)BDT Time 2Hr Enter Range ( 1Hr- 2Hr) Fre. 6M Enter Range ( 1- 12Month)Date 1D Enter Range ( 1-31Days)Time 0Hr. Enter Range (0- 23 Hr)

Stop PBDT Enter (Start/Stop)

B- ParameterBatt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 ControlLVDS3 Control

JUNE – 08 REV-2 29

Page 30: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Press Enter

Battery Equalization Setting-

B-EQU SettingManual B-EQU Enter

Status: OFFStart MB-EQU

Periodic B-EQUStatus: ONSetting Enter

Fre. 6M Enter Range (1- 12Month)Date 1D Enter Range (1-31Days)Time 0Hr. Enter Range (0- 23 Hr)

Stop PB-EQU Enter (Stop/Start)Next BDT HH:MMYYYY/MM/DD

B- ParameterBatt. ChargeT- COMPBDT SettingB-EQU SettingLVDS1 ControlLVDS2 ControlLVDS3 Control

Battery LVD Setting-LVDS1 Control Enter- CLOSE/OPENLVDS2 Control Enter CLOSE/OPENLVDS3 Control Enter CLOSE/OPEN

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

JUNE – 08 REV-2 30

Page 31: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Password Setting-

PasswordON/OFF

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit Press Enter

Date & Time Setting-

YYYY/MM/DDHH:MM

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Language Setting-

EnglishChineese

DCV SettingAlarm SettingBatt. SettingPasswordDate Setting

JUNE – 08 REV-2 31

Page 32: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance ManualLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Efficiency Management Setting-

Efficnt Mgt.Status Enter ON/OFF

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Generator Setting-

Generator Status Disable

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Alarm Reset-

Reset BuzzerReset Com-FailReset BT-Fail

JUNE – 08 REV-2 32

Page 33: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

DCV SettingAlarm SettingBatt. SettingPasswordDate SettingLanguageEfficiency MgtGenerator Alarm Reset Temp. Unit

Press Enter

Temp Unit-

Fahrenheit*Celcius

Sys InfoSys SettingCurr. Alarm

Press Enter

Major AlamDCL Alarm-------------

List of All Active Alarms

JUNE – 08 REV-2 33

Page 34: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

6. Local and Remote Monitoring & Control

6.1 Description

The Remote Site Monitoring software allows maintenance personnel to access the MCS 1400 single phase systems NSCSU without having to be in front of the power system. Using a window based PC and the RS232 interface port on the power systems NSCSU the personnel can gain access to the system.

6.2 System Requirements

RS 232/485 Cross Cable. (Configuration as per attached Drawing).

CD with the application Software (GUI).

Personnel computer.

6.3 Configuration and Monitoring

In order to provide user friendly RMS GUI configuration, a CD containing the software is provided along with the system.

JUNE – 08 REV-2 34

Page 35: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

1) Copy the GUI software from the attached CD.

2) Open the GUI file Remote site.

3) Now a screen (Remote Site) appears on the desktop. Select COMM Port 1 on the upper right corner of this screen and then the user is able to access the parameters as shown in the Fig Below.

6.3.1 Alarm Urgent

The Alarm Urgent Screen shows the Alarm status of the system as shown in the figure:

a. Mains ON/Battery Discharging.

b. System Over Load

c. Load Voltage High

d. Rack Fan Fail.

6.3.2 Alarm Non-Urgent

The Alarm Non-Urgent Screen shows the following alarms as shown in the Figure.

Mains High

JUNE – 08 REV-2 35

Page 36: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Mains Low

Rectifier Alarms (over volt, under volt, over load, fan fail and rectifier fail)

6.3.3 Parameter Monitoring

The parameter Monitoring Screen shows about the Power Plant status, Load, Mains, System Output Voltage, System Load, Load sharing Performance, Rectifier Information and Battery Information.

6.3.4 Parameter Control

JUNE – 08 REV-2 36

Page 37: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

The Parameter Control Screen shows the information about Mains Voltage, System Over Load, System Float Voltage, System Charge Voltage, System Load Voltage and Battery path Current Limits, settings and user can change the settings accordingly.

6.3.5 System Detail

The System Detail Screen shows the details about System Make, Date of Commissioning, Ultimate capacity, Equipped Capacity, Rectifier No, Rectifier Rating, Rectifier Work No, Rectifier Fail No, Battery Detail and Number of Batteries Connected.

JUNE – 08 REV-2 37

Page 38: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual6.3.6 BHM (Optional)

The BHM Screen shows the information about the following parameters:

a. Alarm Urgent

b. Alarm Non Urgent

c. Parameter Monitoring

JUNE – 08 REV-2 38

Page 39: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

d. Parameter Control

JUNE – 08 REV-2 39

Page 40: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manuale. System Detail

6.3.7 Command Line

Through Command Line the user can send the complete packet and get the information about system & batteries parameters by using 5th, 6th and 7th bites accordingly.

JUNE – 08 REV-2 40

Page 41: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

6.3.8 Report

The Report screen shows the information about the Report save mode. There are two save modes. Auto - Set the time interval and get the report at define interval. Manual - Press the save button and get the report.

6.4 Remote Monitoring System

JUNE – 08 REV-2 41

Page 42: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

The Remote Monitor System Screen displays a visual real time condition of how the system is functioning. This screen contains all of the information, which can be seen on the main page display.The indications listed on the screen include:

AC input voltage DC Output Voltage DC Output Current Current Time Total Current Battery state: Float, Equalize or Discharge Ambient temperature

It shows the information about the Rectifiers, Battery, Parameter, alarms, Events, Calibrate, and Configuration. The System can be controlled by using these parameters.

7. Rectifier

JUNE – 08 REV-2 42

Page 43: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

7.1 Description

The Switch Mode Rectifiers (SMR) modules are rated at 25 Amps at -48 VDC. The modular design provides the flexibility to configure and expand the system as the load demand increases. Each MCS-1400 module is hot swappable with front access for ease of maintenance without system shutdown providing uninterrupted service.

The MCS-1400 series module is active power factor corrected to great than 0.99 PF (THD5%) for maximum AC utilization. Each module is equipped with AC breakers located at the front of the module to allow for easy identification when maintenance is required.

7.1.1 Specifications

7.1.1.1 Input

Specification Value

Input Voltage

- Norminal voltage

- Input voltage range

- 230V, single phase

- 90 ~ 300V; 1400W operation

Input Current 18 Amps at 90 VAC input, rated power

Line Frequency 48 to 52 Hz

Power Factor>0.99, at norminal line, Full Load

>0.95, at 300V, 50% Load

THD

≦5%, Full load, nominal line, rated output voltage

IEC1000-3-2:limits for harmonic current emissions.

≦10%, At 300Vac(45~55Hz), 50% load

Efficiency>91%, At nominal input, output , full rated load

>85%, Other specified input output conditions and load between 50% to 100%

Inrush Current18 Amps (at cold start), Full load, nominal line, rated output voltage. Ignore the first inrush current caused by X-CAP

Start Time Delay (Walk-In)3 to 10 seconds (at cold start), Full load, nominal line, rated output voltage.

Protection Fuse (25A)

JUNE – 08 REV-2 43

Page 44: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

7.1.2 Output

Specifications Value

DC Output Voltage

Nominal output voltage Output voltage range

- 54V

- 44.4V ~ 56V

Rated Output Current - 25A

Current Limit 26.25A (25A * 105% ± 1%)

Dynamic Response

Overshoot

Recovery time

Overshoot

Recovery time

- ≦±5% of rated output voltage, Load change100% ~ 25% ~ 100%

- <10ms, Recover to rated output voltage

-≦±5% of rated output voltage, Change AC from 90Vac to 300Vac

- <20ms, Recover to rated output voltage

Load Regulation- ≦±0.5%<Delta Spec.> :

V: Maximum And Minimum Voltage; VH: Half Load Voltage

At rated output voltage, 0-100% load

Noise

- Audio band

- Peak to peak ripple voltage

- Acoustic

- ≦24 dBrnc- ≦32 dBrnc(<0.82mV)<Note> dBmp + 2.5 = 20 Log (V/0.7746)CCITT Connect battery No battery connection

- ≦200 mV, Oscilloscope band set to 60 MHz

-- ≦55dBA, at 1 meter in front of SMR

Current Sharing ≦±10% of rated output current , Load 50%~100%

Dynamic Response10% to 90% Load Change Overshoot 5% Rated Output Voltage Recovery Time <1 ms to 1% Rated Output Voltage

JUNE – 08 REV-2 44

Page 45: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

7.1.3 Indicators

Item Specification/Function Standard/Comment

Line

Function

Component type

Color

On condition

Off condition

AC line ON

LED

Green

Line exceeds 50V (Typical)

No line or line under 30V (Typical)

The LED lights when AC line is normal.

R.F.

Function

Component type

Color

On condition

Off condition

Rectifier Failed

LED

Red

Rectifier Fail

Rectifier Normal

C.L.

Function

Component type

Color

On condition

Off condition

Current Limited

LED

Red

Output current is limited.

Output current under of rated load. Output current is not limited.

The LED lights when the output current exceeds rated load.

The current limited point can be programmed by NSCSU.

HV/LV/FF

Function

Component type

Color

On condition

Off condition

High Voltage/Low Voltage/Fan Fail

LED

RED

HV: DC voltage exceeds –56V

LV: DC voltage under –40V

FF: Fan Fail

Rectifier Normal

HV:The LED Continuous light

LV:The LED flashing witching freq 1Hz

FF:The LED flashing switching freq 2Hz

I+, I-

Function - Output Current Test Points

The I+, I- will send a voltage value, which can be transferred, to output current. 0.1V = 1A.

JUNE – 08 REV-2 45

Page 46: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

7.1.4 Standard and Environmental

EMI Suppression: FCC Class A, CISPR 22 Class A

EMC Immunity: 10V/m, IEC 1000-4-3, IEC 801-3 Level 3

Voltage Fluctuation Flicker

EN 61000-3-3, EN 60555-3

Fast Transient (EFT):

4KV, EN 61000-4-4 Level 4, IEC 1000-4-4, IEC 801-4 level 4

Lightning/Surge 6KV, IEC 1000-4-5 Level 4,

Test Condition: 1. Combination wave 1.2/50us, 8/20us, 2, 3KA2. Ring wave 100KHz, 500A

ESD15KV Air Discharge, 8KV Contact Discharge, EN 61000-4-2 Level 4, IEC 1000-4-2, IEC 801-2 level 4

Conducted Susceptibility

10V/m, IEC 1000-4-6 Level 3

Safety Mark UL/CUL UL 60950, TUV/CE EN 60950

Operation Temperature

-5˚C ~ +70˚C (23˚F ~ +158˚F), Constant current 1400W at 230Vac

-5˚C ~ +55˚C (23˚F ~+131˚F), Constant current 1400W at 90Vac

Storage Temperature

-50˚C~ 75˚C (-58˚F ~ +167˚F)

Operation Humidity 0 ~ 95% Relative Humidity (Non-Condensing)

Storage Humidity 0 ~ 95% Relative Humidity (Non-Condensing)

Altitude -152m~3048m (-500~10000 Feet)

MTBF >465K hours, At 25℃, rated load

Cooling Fan Life > 7 years(70000hr)

7.1.5 Physical

Dimensions

(W x H x D)3.3 in. x 5.2 in. x 10.35 in. / 83.6 x 132 x 263mm

Weight 7.26lbs / 3.1Kg

JUNE – 08 REV-2 46

Page 47: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

8. SYSTEMS ALARM AND TROUBLE SHOOTING

8.1 AC Fail/AC High Voltage / AC Low Voltage Alarm Description.

There are three (3) AC alarm conditions that are monitored by the system: AC Fail, AC High Voltage and AC Low Voltage. AC fail occurs when AC current is not present at the AC Distribution box. AC high Voltage (ACH) is a factory set parameter and can be adjusted by setting parameter High Voltage Alarm (ACH) to the desired voltage. All three alarms result in the system shutting down rectifiers until either AC is restored, or the AC voltage returns to levels within the parameter threshold settings (AC High Voltage and AC Low Voltage).

8.1.1 AC Fail, AC Input High (ACH) and AC Input Low (ACL) Alarm Conditions.

8.1.1.1 AC Fail: Major Alarm

When the NSCSU senses the absence of AC current at the AC Distribution box located in the rear of the DC Distribution Cabinet, the NSCSU will initiate a major alarm and “AC DN” will be displayed on the main page. ACL and AC DN alarm is indicated on the NSCSU. Battery is in discharge status. The alarm will be re-set to normal condition when AC is restored. During an AC Fail condition, the NSCSU is powered by the reserve from batteries.

8.1.1.2 AC Input High (ACH): Minor Alarm -AC Input High Alarm

When the NSCSU senses the input AC Voltage exceeding parameter alarm, the NSCSU will initiate an AC High Alarm, displayed on the NSCSU. The system will shut down the rectifiers. The NSCSU will continue to monitor the AC input voltage. The ACH alarm will re-set to the normal operation when AC input voltage decreases within the threshold parameter setting. SMR restart after input voltage return to nominal line voltage range.

8.1.1.3 AC Voltage Low (ACL) Minor Alarm-AC Input Low Alarm

The AC Voltage Low Alarm occurs when the AC input voltage falls below the threshold set in parameter. When the ACL condition is sensed, an ACL alarm is displayed on the NSCSU. The NSCSU will shut down the rectifiers. The NSCSU will continue to monitor the AC input voltage. The ACL alarm will re-set to the normal operation when AC input voltage increases within the threshold parameter setting. SMR restart after input voltage return to nominal line voltage range.

8.1.2 AC Fail Trouble shooting

During an AC Fail condition, the CSU is powered by reserve batteries and the rectifiers are shut down. When AC is restored, observe the battery charge current. It may be necessary to decrease the current limit to the charge current range during equalize if a deep discharge situation has occurred.

JUNE – 08 REV-2 47

Page 48: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

8.1.3 AC High Voltage (ACH) Trouble shooting

Verify the AC input voltage at the AC service pane. If the AC input voltage is higher than the threshold setting, the NSCSU will take the rectifiers of line. The AC circuit breaker at the AC service panel should be tripped until the AC utility is repaired and the AC input is within input specifications.

Verify the AC distribution voltage is higher than the setting value. If not, the system will continue to operate and the NSCSU may be faulty. The NSCSU should be swapped with a spare; the High Voltage (HV1) parameter set to the desired high voltage threshold setting, and verified that the HV1 alarm is cleared. Follow established repair/return policy to have the faulty NSCSU repaired by Delta Products.Warning Do not increase the threshold setting past normal operating input

voltages. Operating rectifiers in a High Input Voltage condition can result in seriously damaging the rectifier modules.

8.2 DC Output Voltage High/Low (HV1/LV1)

8.2.1 DC Output Voltage High Alarm-HV-1 Minor Alarm.

This alarm condition exists when the DC output voltage is higher than the parameter alarm setting. The alarm will re-set to the normal condition when the voltage is decreased below the threshold parameter setting. The output voltage can be adjusted via the NSCSU.

8.2.2 DC Output Low Alarm-LV-1 Minor Alarm

This alarm condition exists when the DC output voltage is lower than the parameter alarm setting. The alarm will clear when the DC output voltage increases. The output voltage can be adjusted via the NSCSU.

8.2.3 DC Voltage High/Low Trouble Shooting

Verify the output of each rectifier. If the rectifier output is not within tolerance, swap the rectifier with a spare module, and return the faulty unit to Delta Products for repair. If the output of each rectifier is within tolerance, check the parameters to ensure the correct settings.

8.3 DC Circuit Breaker Trip Alarm

When a DC load circuit breaker is tripped, the NSCSU will go into alarm.

1. Press the alarm button and the NSCSU will display “Breaker Fail”.2. Open the DC Distribution Cabinet Door.3. Check the DC Circuit Breaker Distribution panel indicator for an illuminated read

LED.4. The tripped circuit breaker shall indicate by the illuminated red LED.5. Re-set the tripped circuit breaker.6. The red LED indicator should turn off and the CSU alarm should clear.

JUNE – 08 REV-2 48

Page 49: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

8.3.1 Circuit Breaker Fail Condition Trouble Shooting

If the circuit breaker continues to fail:

a. Check the DC branch load (fed by the DC circuit breaker) to ensure the circuit breaker is the correct size.

b. If the branch load exceeds the circuit breaker rating, the circuit breaker must be changed to a higher rating.

c. Swap with a spare circuit breaker with a higher rating.

8.4 Over-Temperature Alarm

8.4.1 Over-Temperature-Ambient

This alarm is generated when the threshold temperature set in parameter alarm setting TA is exceeded and also controls the Temperature Compensation Voltage Control. The NSCSU senses the temperature via sensor TA and generates an Ambient Over Temperature Alarm setting.

8.4.2 Over Temperature - Ambient Troubleshooting

1. Verify that the ambient temperature has exceeded the parameter setting by checking the thermostat reading in the hut or equipment room and comparing the reading to the NSCSU Reading.

2. The NSCSU will decrease the float/equalize voltage for each degree over the 25˚C or 77˚F threshold.

3. If the TA parameter setting has been exceeded, increase the air conditioning.

4. If the TA threshold is exceeded, it is recommended to turn off the AC Main feeding the Rectifiers until the ambient temperature has decreased below the threshold temperature.

5. If the sensor is defective, turn the Temperature Compensation off.

Warning Operating the system at excessive temperatures can damage the rectifiers.

8.4.3 Over Temperature - Battery Alarm

This alarm is generated when the threshold temperature set in parameter TB-1 or TB-2 (if equipped with 2 battery strings) is exceeded. The NSCSU senses the temperature via sensor TB-1 or TB-2 and generates a Battery Over Temperature Alarm-TB-1 or TB-2.

8.4.4 Over Temperature-Battery Troubleshooting

1. Check the ambient temperature and verify it is within the TA parameter threshold.

2. If the TA and TB-1 & 2 thresholds are not exceeded, check the thermostat reading in the room and comparing the reading to the NSCSU reading. If the TB-1 or TB-2 sensor is defective, replace the sensor.

JUNE – 08 REV-2 49

Page 50: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Note! It is recommended that if the system is in the equalize mode, switch the status to float to reduce the battery temperature.

8.5 NSCSU Fail

8.5.1 Fail Status

During a NSCSU failure condition, the NSCSU fail LED will light, and the rectifiers status will change from equalize to float, or remain in the float condition.

8.5.2 Troubleshooting

1. Check the input fuse on the back of the NSCSU, replace if blown.

2. Check the DC input connectors for proper connections.

3. Replace with a spare and send the faulty unit to Delta Products for repair.

8.6 Rectifier Fail Alarm

When a rectifier fails, the alarm information is sent to the NSCSU and the rectifier is shut down. The rectifier should be swapped out with a spare unit and the faulty unit returned for repair. Refer to the section 10.2 for removing and replacing a rectifier.

Warning Do not open the rectifier module. There are no serviceable parts. Call for an RMA number for repair and return.

JUNE – 08 REV-2 50

Page 51: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

9. INSTALLATION

9.1 Tools RequiredThe following tools are recommended for the power shelf installation:

Phillips No. 3 screw driver Insulated slotted screw driver - blade size 1/4” Insulated slotted screw driver - blade size 1/8” Tweaker - Slotted screw driver blade size .09”×.02” Insulated side cutters Metric Socket Wrenches with Extensions Torque Wrench Thomas & Betts, Type TBM8-750M-1

9.2 Preliminary Inspection

Prior to removing the system from the crate, note any damage to the crate. Remove the power shelf from the crate and inspect it for any dents or damage. If any damage is noted, contact the carrier immediately.

9.3 Shelf Mounting

Mount the rack of system with a distance no less than 12 inches from the rear of the rectifier shelf to a wall. This will provide adequate ventilation for the rectifiers. The front of the system should be clear of all obstruction and allow room for proper ventilation, installation and maintenance. The relay rack should be mounted to the superstructure and floor per customer provided equipment engineering drawings.

9.4 Module Installation

In order to minimize the weight of system, all rectifier modules can be removed from the rack and re-installed after the rack has been mounted.

Install rectifier modules into the shelf.

Warning Do not force the module into the slot. If it does not slide in and connect easily, remove and re-seat the unit.

Secure each rectifier module to the shelf by tightening the captive screw located at the right side front of the module.

9.5 Shelf Wiring

The system comes fully assembled and all the connections are made at the factory. There is no internal, shelf or module wiring required.

9.6 Frame Grounding

JUNE – 08 REV-2 51

Page 52: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

The frame ground must be connected to a permanent earth ground connection. Feed the frame ground lead through the knock out at the rear of the right hand side of the DC distribution cabinet and connect to the frame ground lug. Recommended Lead Wire: AWG#8

Warning Do not connect this terminal to AC power system neutral.

10. MAINTENANCE

10.1 Cleaning and Maintenance

10.1.1 General

Special maintenance is not necessary for this system, unless the system is being operated in a severely harsh environment (dusty environment). The front panels and the cover of the DC Distribution cabinet was treated with a special coating, do not use organic cleanser or volatile solvent or corrosion damage may occur. For daily cleaning, brush the dust from the cover and panel. If necessary, use a gentle cleanser or a lightly dampened lint free cloth to remove any dirt or smudges.

10.1.2 Periodic Maintenance

Periodic maintenance is not required for normal operation. If necessary, wipe remove dust from the front of the MCS 1400 using a lint free, soft cloth an gently wipe the front of the Distribution cabinet door, the NSCSU and rectifiers. If necessary, use a gentle detergent to clean.

Warning Do not use spray cleanser to clean the equipment. Using a spray cleanser directly on the equipment can result in serious equipment damage.

Check the DC Bus for heat discoloration. If the bus has any heat discoloration, notify to the Customer Service.

10.2 Removing and Replacing a Rectifier Module

10.2.1 Removing a Rectifier

Warning Do not touch the DC output Bus when pulling out the SMR module.

1. Loosen the captive retaining screws located on the right and bottom of the front panel.

2. Pull out the SMR module slowly from the shelf, using one hand to support the rear half of the SMR and remove the rectifier from the shelf.

10.2.2 Replacing a Rectifier

JUNE – 08 REV-2 52

Page 53: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

Install the rectifier module, holding the handle with one hand and using the other to support the rear half of the rectifier module. Place the rectifier on the shelf making sure the rail is on the tack.

Warning Do not force the module into the slot. If it does not slide in and connect easily, remove and re-set the unit.

1. Lock the rectifier into position by screwing in the captive retaining screw located at the right and the bottom of the rectifier front panel.

2. On the front of the rectifier: Verify the Current Limit is set at the same value as the other rectifiers in the system.

3. Begin by accessing into the parameter menu. Turn off the mode of temperature compensation and Voltage compensation. Then the float and equalize voltage can start adjusting

10.3 Float Voltage Adjusting

Verify the required float voltage setting per the battery manufacturer specification. If the factory setting differs from the battery manufacturer recommended setting, all the rectifiers and the NSCSU Float Voltage parameter must be adjusted to the new setting. Use NSCSU to adjust the FLO voltage.

10.4 Equalize Voltage Adjusting

Verify the required equalize charge voltage setting per the battery manufacturer specification. If the factory setting differs from the battery manufacturer recommended setting, all the rectifiers and the NSCSU Equalize Voltage parameter must be adjusted to the new setting. Use NSCSU to adjust the EQU voltage.

10.5 Replacing a Rectifier Cooling Fan

Under a fan fail condition, the rectifier will automatically go into alarm and shut down. It is recommended that a maintenance craftsperson change the fans on-site.

1. Follow Rectifier Removal procedure,

2. Remove the front panel and screw.

3. Loosen and remove the four fan screws.

4. Remove the faulty fan from the rectifier.

5. Position the new fan on the rectifier.

Warning Ensure the fan is positioned correctly to avoid possible fan or rectifier damage.

6. Replace and tighten the fan mounting screws.

JUNE – 08 REV-2 53

Page 54: Manual-MCS1400-48V-25A-NSCSU - January 08.doc

ES-48V/25A- Single Phase System Installation, Operation & Maintenance Manual

7. Plug the fan lead connector into the connector slot.

8. Replacing a rectifier to complete the fan replacement procedure.

11. Dip Switch Settings

11.1 DIP Switch Selection

Shelf No. SF1(1-6)

SF2(1-6)

SF3(1-3)

Shelf 1 (Upper Shelf)SMR1-SMR5

1,3,4,6-ON2,5-OFF

1,3,4,6-ON2,5-OFF

1,3-ON2-OFF

Shelf 2(Upper Shelf)

SMR6-SMR10

1,4-ON2,3,5,6-OFF

1,4-ON2,3,5,6-OFF

1-ON2,3-OFF

JUNE – 08 REV-2 54