manuel innovations sirius - appareils à...

100
Manuel Appareillage industriel Innovations SIRIUS Appareils à semiconducteurs SIRIUS 3RF34 Édition Answers for industry. 08/2014

Upload: leanh

Post on 15-Sep-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

GerätehandbuchManuel

Appareillage industrielInnovations SIRIUSAppareils à semiconducteurs SIRIUS 3RF34

Édition

Answers for industry.

08/2014

Innovations SIRIUS -

Appareils à semiconducteurs SIRIUS 3RF34

___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________

___________________ ___________________ ___________________ ___________________ ___________________ ___________________ ___________________

Appareillage industriel

Appareils à semiconducteurs Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel

08/2014 A5E03656507230A/RS-AA/002

Introduction 1

Normes 2

Description du produit 3

Combinaison des produits 4

Fonctions 5

Configuration / Etude 6

Etude de la mise en œuvre 7

Montage 8

Raccordement 9

Questions fréquemment posées (Foire aux Questions)

10

Accessoires 11

Caractéristiques techniques 12

Schémas électriques 13

Types de coordination A

Bibliographie B

Croquis cotés (cotes en mm) C

Formulaire de correction D

Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG ALLEMAGNE

3ZX1012-0RF34-5AD1 Ⓟ 08/2014 Sous réserve de modifications

Copyright © Siemens AG 2011 - 2014. Tous droits réservés

Mentions légales Signalétique d'avertissement

Ce manuel donne des consignes que vous devez respecter pour votre propre sécurité et pour éviter des dommages matériels. Les avertissements servant à votre sécurité personnelle sont accompagnés d'un triangle de danger, les avertissements concernant uniquement des dommages matériels sont dépourvus de ce triangle. Les avertissements sont représentés ci-après par ordre décroissant de niveau de risque.

DANGER signifie que la non-application des mesures de sécurité appropriées entraîne la mort ou des blessures graves.

ATTENTION signifie que la non-application des mesures de sécurité appropriées peut entraîner la mort ou des blessures graves.

PRUDENCE signifie que la non-application des mesures de sécurité appropriées peut entraîner des blessures légères.

IMPORTANT signifie que la non-application des mesures de sécurité appropriées peut entraîner un dommage matériel.

En présence de plusieurs niveaux de risque, c'est toujours l'avertissement correspondant au niveau le plus élevé qui est reproduit. Si un avertissement avec triangle de danger prévient des risques de dommages corporels, le même avertissement peut aussi contenir un avis de mise en garde contre des dommages matériels.

Personnes qualifiées L’appareil/le système décrit dans cette documentation ne doit être manipulé que par du personnel qualifié pour chaque tâche spécifique. La documentation relative à cette tâche doit être observée, en particulier les consignes de sécurité et avertissements. Les personnes qualifiées sont, en raison de leur formation et de leur expérience, en mesure de reconnaître les risques liés au maniement de ce produit / système et de les éviter.

Utilisation des produits Siemens conforme à leur destination Tenez compte des points suivants:

ATTENTION Les produits Siemens ne doivent être utilisés que pour les cas d'application prévus dans le catalogue et dans la documentation technique correspondante. S'ils sont utilisés en liaison avec des produits et composants d'autres marques, ceux-ci doivent être recommandés ou agréés par Siemens. Le fonctionnement correct et sûr des produits suppose un transport, un entreposage, une mise en place, un montage, une mise en service, une utilisation et une maintenance dans les règles de l'art. Il faut respecter les conditions d'environnement admissibles ainsi que les indications dans les documentations afférentes.

Marques de fabrique Toutes les désignations repérées par ® sont des marques déposées de Siemens AG. Les autres désignations dans ce document peuvent être des marques dont l'utilisation par des tiers à leurs propres fins peut enfreindre les droits de leurs propriétaires respectifs.

Exclusion de responsabilité Nous avons vérifié la conformité du contenu du présent document avec le matériel et le logiciel qui y sont décrits. Ne pouvant toutefois exclure toute divergence, nous ne pouvons pas nous porter garants de la conformité intégrale. Si l'usage de ce manuel devait révéler des erreurs, nous en tiendrons compte et apporterons les corrections nécessaires dès la prochaine édition.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 5

Sommaire

1 Introduction ............................................................................................................................................. 9

2 Normes ................................................................................................................................................. 11

2.1 Normes ................................................................................................................................... 13

3 Description du produit ........................................................................................................................... 15

3.1 Modèles d'appareils ................................................................................................................ 15

3.2 Champs d'application .............................................................................................................. 17

3.3 Environnement d'utilisation ..................................................................................................... 18

3.4 Appareils à semiconducteurs .................................................................................................. 19

3.5 Marquages sur l'appareil ......................................................................................................... 21

3.6 Avantages des appareils à semiconducteurs ......................................................................... 24

4 Combinaison des produits ..................................................................................................................... 25

5 Fonctions .............................................................................................................................................. 27

5.1 Commande des appareils à semiconducteurs ....................................................................... 28

6 Configuration / Etude ............................................................................................................................ 29

6.1 Choix des appareils à semiconducteurs ................................................................................. 29

6.2 Configurateur de système pour Innovations SIRIUS .............................................................. 30

6.3 Configuration : choix de contacteurs à semiconducteurs pour moteurs ................................. 30

6.4 Protection contre les courts-circuits ........................................................................................ 34 6.4.1 Montages du départ-moteur conformes à CEI ....................................................................... 34 6.4.1.1 Contacteurs à semiconducteurs 3RF34 - Types de coordination 1 et 2 selon CEI

(montage avec fusibles) .......................................................................................................... 34 6.4.1.2 Contacteurs-inverseurs à semiconducteurs 3RF34 - Types de coordination 1 et 2

selon CEI (montage avec fusibles) ......................................................................................... 36 6.4.2 Montages du départ-moteur selon UL .................................................................................... 38 6.4.2.1 Indications SCCR sur le courant de court-circuit .................................................................... 38 6.4.2.2 Fusibles ................................................................................................................................... 38

7 Etude de la mise en œuvre ................................................................................................................... 43

7.1 Domaines d'utilisation ............................................................................................................. 44 7.1.1 Commande de moteurs .......................................................................................................... 44 7.1.2 Utilisation dans une installation photovoltaïque ...................................................................... 44

8 Montage ............................................................................................................................................... 45

8.1 Instructions de montage.......................................................................................................... 45

8.2 Fixation par vis ........................................................................................................................ 47

8.3 Fixation sur rail DIN symétrique (fixation par encliquetage) et dépose .................................. 47

Sommaire

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 6 Manuel, 08/2014, A5E03656507230A/RS-AA/002

9 Raccordement ...................................................................................................................................... 49

9.1 Contacteur à semiconducteurs .............................................................................................. 50

9.2 Contacteur-inverseur à semiconducteurs %% ....................................................................... 50

9.3 Sections de conducteur ......................................................................................................... 51 9.3.1 Sections pour raccordement par bornes à vis ....................................................................... 51 9.3.2 Sections pour raccordement par bornes à ressort ................................................................. 52

10 Questions fréquemment posées (Foire aux Questions) ......................................................................... 53

11 Accessoires .......................................................................................................................................... 55

11.1 Vue d'ensemble des accessoires .......................................................................................... 55

11.2 Arrêt d'isolation ...................................................................................................................... 55 11.2.1 Description ............................................................................................................................. 55

11.3 Bloc de connexion au disjoncteur .......................................................................................... 56 11.3.1 Description ............................................................................................................................. 56 11.3.2 Montage / démontage ............................................................................................................ 57

11.4 Adaptateur de connexion au relais de surcharge .................................................................. 58 11.4.1 Description ............................................................................................................................. 58 11.4.2 Montage / démontage ............................................................................................................ 58

12 Caractéristiques techniques .................................................................................................................. 59

12.1 Caractéristiques générales .................................................................................................... 59

12.2 Sections de raccordement pour contacteurs à semiconducteurs .......................................... 61

12.3 Sections de raccordement pour contacteurs-inverseurs à semiconducteurs ........................ 62

12.4 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à vis .......................................... 63

12.5 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à ressort.................................... 64

12.6 Contacteurs à semiconducteurs - Montage sans fusibles avec disjoncteur CLASS 10 ........ 65

12.7 Contacteurs à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30 ..... 66

12.8 Contacteurs à semiconducteurs, circuit principal et commande biphasée ............................ 67

12.9 Contacteurs à semiconducteurs avec circuit de commande ................................................. 67

12.10 Contacteur-inverseur à semiconducteurs avec intégration de quatre circuits en un schéma inverseur ................................................................................................................... 68

12.11 Contacteur-inverseur - montage sans fusibles avec disjoncteur CLASS 10 ......................... 69

12.12 Contacteur-inverseur à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30 ................................................................................................................... 70

12.13 Contacteur-inverseur à semiconducteurs, circuit principal et commande biphasée ............. 70

12.14 Contacteur-inverseur à semiconducteurs avec circuit de commande ................................... 71

12.15 Courbes - fréquence de manœuvre / charge ......................................................................... 72 12.15.1 Courbes caractéristiques pour le contacteur à semiconducteurs .......................................... 72 12.15.2 Courbes caractéristiques pour le contacteur-inverseur à semiconducteurs .......................... 77

13 Schémas électriques ............................................................................................................................. 83

Sommaire

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 7

A Types de coordination ........................................................................................................................... 87

B Bibliographie ......................................................................................................................................... 89

B.1 Littérature ................................................................................................................................ 89

B.2 Manuels des Innovations SIRIUS ........................................................................................... 90

B.3 Informations complémentaires ................................................................................................ 92

C Croquis cotés (cotes en mm) ................................................................................................................. 93

C.1 Appareils à semiconducteurs .................................................................................................. 93

C.2 Bloc de connexion au disjoncteur ........................................................................................... 94

D Formulaire de correction ....................................................................................................................... 95

Index..................................................................................................................................................... 97

Sommaire

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 8 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 9

Introduction 1

Objet du manuel Le présent manuel décrit les appareils à semiconducteurs 3RF34 et fournit les informations suivantes :

● Informations sur l'intégration des appareils à semiconducteurs dans l'environnement système

● Informations sur les constituants matériels nécessaires

● Informations sur le montage, le raccordement et la configuration des appareils à semiconducteurs

● Informations techniques (dessins cotés, schémas des appareils, etc.)

Les informations contenues dans le présent manuel permettent de configurer et de mettre en service les appareils à semiconducteurs.

Connaissances de base requises La compréhension du manuel requiert des connaissances générales dans le domaine de l'automatisation et de l'appareillage basse tension.

Domaine de validité du manuel Le présent manuel s'applique aux appareils à semiconducteurs considérés. Il contient une description des appareils valables à la date d'édition.

Autres documents Pour le montage et le raccordement des appareils à semiconducteurs, vous avez besoin des instructions de service des appareils à semiconducteurs utilisés.

Une liste des instructions de service et des manuels des Innovations SIRIUS figure en annexe "Littérature (Page 89)".

Recyclage et mise au rebut Les appareils considérés contiennent peu de substances polluantes et sont donc recyclables. Adressez-vous à une entreprise certifiée dans la mise au rebut de déchets électroniques pour un recyclage et une mise au rebut de votre appareil qui soient respectueux de l'environnement.

Introduction

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 10 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Mise à jour continuelle des informations Vous obtiendrez davantage d'assistance au numéro suivant :

Assistance technique :

Téléphone : +49 (911) 895-5900 (8h00 - 17h00 HEC)

Fax : +49 (911) 895-5907

ou sur Internet :

Courriel : (mailto:[email protected])

Internet : (www.siemens.com/industrial-controls/technical-assistance)

Feuille de correction Une feuille de correction est à votre disposition à la fin de ce manuel. Vous pouvez y inscrire vos suggestions pour améliorer, compléter et corriger le manuel et nous la renvoyer. Vous nous aiderez ainsi à améliorer l'édition suivante.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 11

Normes 2

Utilisation conforme

Remarque Parasites en zone résidentielle

Ce produit a été construit comme appareil de classe A. Son utilisation en zone résidentielle pourrait provoquer des parasites.

Dans ce cas, il est permis d'exiger de l'utilisateur qu'il prenne des mesures d'affaiblissement supplémentaires.

Mesures de sécurité

PRUDENCE

Court-circuit entre phases par surtension dans les contacteurs-inverseurs à semiconducteurs

Les appareils de connexion du départ-moteur peuvent, en cas de court-circuit, mettre les personnes en danger et endommager l'installation.

Dans les montages avec fusibles, il faut changer l'organe de protection après un court-circuit.

Pour réduire le risque de court-circuit entre phases par surtension, il est recommandé de raccorder une varistance de type 3TX7 462-3L entre L1 et L3. Une réalisation avec fusible et protection des semiconducteurs protègera contre les courts-circuits.

Remarque Court-circuit entre phases en mode automatique des contacteurs-inverseurs à semiconducteurs

En cas d'application de la tension principale et de mise en circuit simultanée de la tension de commande, il peut arriver que le circuit de protection RC intégré réagisse. Selon le type de commande, il est alors possible que deux thyristors du schéma inverseur soient passants et produisent ainsi un court-circuit entre phases.

Pour évitersûrement ce comportement, il convient de n'actionner les entrées de commande qu'au terme d'une temporisation de 40 ms après l'application de la tension principale.

Normes

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 12 Manuel, 08/2014, A5E03656507230A/RS-AA/002

IMPORTANT

Perturbations CEM des contacteurs-inverseurs à semiconducteurs

Les moteurs triphasés couplés en étoile (particulièrement si <1 kW) avec des contacteurs électromécaniques peuvent causer des perturbations CEM très fortes. Ceci peut provoquer des dysfonctionnements des contacteurs-inverseurs à semiconducteurs situés dans cet environnement.

Il faut prévoir des circuits de protection CEM sur les sources des perturbations.

Normes 2.1 Normes

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 13

2.1 Normes

Normes et homologations ● CEI 60947-4-2

● UL 508, CSA pour l'Amérique du Nord 1)

● Marquage CE pour l'Europe

● Autorisation C-Tick pour l'Australie

● CCC pour la Chine 1) Please note: Use overvoltage protection device; max. cut-off-voltage 6000 V; min. energy handling capability 100J.

Normes appliquées Le produit est conforme aux normes suivantes :

Tableau 2- 1 Normes appliquées (produit)

Champ d'application Norme Norme pour l'appareil NF CEI 60947-4-2 Repérage des bornes DIN EN 50011 Degré de protection IP20 DIN CEI 0529 Résistance aux vibrations NF CEI 60068-2-6 Résistance aux chocs NF CEI 60068-2-27 Norme CEM NF CEI 60947-4-2; NF CEI 61000-4-2;

NF CEI 61000-4-6; NF CEI 61000-4-4; NF CEI 61000-4-5

Résistance aux conditions climatiques NF CEI 60068-2-61 (séquence d'essais), NF CEI 60068-2-30 (chaleur humide), NF CEI 60068-2-2 (chaleur sèche), NF CEI 60068-2-1 (froid), NF CEI 60068-2-14 (variations de température)

Voir aussi Les normes figurant dans l'annexe du catalogue IC 10 "Appareillage industriel SIRIUS" sont d'application générale. Pour les innovations du système modulaire SIRIUS, vous trouverez les principales normes au chapitre "Manuels des Innovations SIRIUS (Page 90)" de l'annexe "Bibliographie" du manuel "Innovations SIRIUS - Vue d'ensemble du système".

Normes 2.1 Normes

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 14 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 15

Description du produit 3 3.1 Modèles d'appareils

Les appareils à semiconducteurs sont mis en œuvre le plus souvent dans des applications monophasées devant répondre aux exigences suivantes :

● très hautes fréquences de manœuvre (> 1000 manœuvres par heure)

● charges ohmiques

Pour la manœuvre fréquente de charges ohmiques, le système modulaire SIRIUS offre des contacteurs et des relais à semiconducteurs monophasés et triphasés. Pour la commande de charges moteur, le système propose des contacteurs et des contacteurs-inverseurs à semiconducteurs triphasés. Des modules fonctionnels standardisés pour différentes applications complètent la gamme des appareils à semiconducteurs SIRIUS.

Les modèles de contacteurs et de contacteurs-inverseurs à semiconducteurs présentés dans ce manuel sont prévus spécialement pour l'emploi sur moteurs triphasés jusqu'à 7,5 kW.

Pour plus d'informations, reportez-vous aux renvois dans l'annexe "Informations complémentaires (Page 92)".

Vue d'ensemble Ces appareils à semiconducteurs à commande biphasée et à manœuvre instantanée se présentent sous boîtier isolant en deux largeurs :

● Largeur 45 mm

– jusqu'à 5,2 A comme contacteur à semiconducteurs (contacteur moteur) ou

– jusqu'à 5,4 A comme contacteur-inverseur à semiconducteurs

● Largeur 90 mm

– jusqu'à 16 A comme contacteur à semiconducteurs ou

– jusqu'à 7,4 A comme contacteur-inverseur à semiconducteurs

Ils permettent d'exploiter des moteurs jusqu'à 7,5 kW.

Les contacteurs et contacteurs-inverseurs à semiconducteurs à bornes à vis peuvent être raccordés directement à un disjoncteur à l'aide d'un bloc de connexion 3RA2921-1BA00. Le montage direct d'un relais électronique de surcharge 3RB30 / 3RB31 est également possible et dans quelques cas celui d'un relais de surveillance du courant 3RR2. Ceci permet de réaliser en gagnant du temps des départs moteur à manœuvre fréquente, avec ou sans fusibles.

Description du produit 3.1 Modèles d'appareils

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 16 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Modèles Le tableau ci-dessous énumère les différents modèles de contacteurs à semiconducteurs à manœuvre instantanée 3RF34 pour la commande de moteurs.

Tableau 3- 1 Modèles des appareils à semiconducteurs

Caractéristique Réalisation Variante Contacteur à semiconducteurs Contacteur-inverseur à semiconducteurs Description Appareils complets en boîtier isolé pour

enclenchement et coupure fréquentes de moteurs triphasés.

Montage compact du schéma inverseur pour enclenchement et coupure fréquentes de moteurs triphasés avec changement constant du sens de marche

Numéros de référence 3RF34..-.BB.. 3RF34..-.BD.. Taille S0 Largeur (puissance du moteur1) / courant assigné d'emploi maxi)

• 45 mm (moteurs jusqu'à 2,2 kW, 5,2 A) • 90 mm (moteurs jusqu'à 7,5 kW, 16 A)

• 45 mm (moteurs jusqu'à 2,2 kW, 5,4 A) • 90 mm (moteurs jusqu'à 3,0 kW, 7,4 A)

Nombre de pôles 3 3 Connectique Raccordement par bornes à vis et par

bornes à ressort Raccordement par bornes à vis

Tension assignée d'emploi jusqu'à 600 V jusqu'à 480 V Tension assignée d'alimentation de commande

24 V CC et 110 à 230 V CA

Retard de manœuvre Retard à la fermeture Retard à la coupure

1 ms (24 V CC), 5 ms (110 … 230 V CA) 1 ms (24 V CC), 30 ms (110 … 230 V CA) une demi-onde maxi en plus

5 ms (24 V CC),20 ms (110 … 230 V CA) 5 ms (24 V CC), 10 ms (110 … 230 V CA) une demi-onde maxi en plus

Temps de verrouillage 60 … 100 ms (24 V CC), 50 … 100 ms (110 … 230 V CA) Boîtier IsolE (mise à la terre inutile) Bornes de commande Raccordement par bornes à vis et par

bornes à ressort ; borne amovible pour le câblage du circuit auxiliaire (2 contacts)

Raccordement par bornes à vis ; borne amovible pour le câblage du circuit auxiliaire (3 contacts)

1) Les puissances indiquées s'appliquent à une tension réseau de 400 V.

Description du produit 3.2 Champs d'application

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 17

3.2 Champs d'application

Appareils à semiconducteurs pour la commande de moteurs Les contacteurs à semiconducteurs pour la commande de moteurs sans usure et sans bruit sont prévus pour l'enclenchement et la coupure fréquentes de moteurs triphasés jusqu'à 7,5 kW ainsi que pour l'inversion du sens de marche jusqu'à 3,0 kW. Ces appareils sont construits en isolation totale et peuvent être montés directement sur les disjoncteurs et les relais de surcharge ou sur les relais de surveillance du courant SIRIUS, ce qui permet leur intégration très simple dans des départs moteur.

Ces contacteurs à semiconducteurs triphasés sont équipés d'une commande biphasée qui convient particulièrement aux circuits moteur typiques sans liaison au conducteur neutre.

L'intégration dans un même boîtier de quatre circuits en un schéma inverseur fait du contacteur-inverseur à semiconducteurs une solution particulièrement compacte. Par rapport aux systèmes classiques qui requièrent deux contacteurs, les contacteurs-inverseurs triphasés à semiconducteurs permettent d'économiser jusqu'à 50 % en largeur. Les appareils en 45 mm de largeur couvrent les moteurs jusqu'à 2,2 kW et en 90 mm de largeur jusqu'à 3 kW.

Grâce à leur intégration dans le système modulaire SIRIUS, ils peuvent être reliés sans difficulté à un disjoncteur SIRIUS au moyen d'un bloc de connexion ou encore à un relais électronique de surcharge 3RB30 / 3RB31 ou à un relais de surveillance du courant 3RR2. Ceci permet le montage simple et rapide de départs moteur avec ou sans fusibles.

Caractéristiques principales :

● Boîtier isolé avec radiateur intégré

● Degré de protection IP20

● Pied de montage intégré pour encliquetage sur un rail DIN symétrique ou pour montage sur une plaque support.

● Connectique variées

● Connecteur de commande enfichable

● Indication de la tension de commande par LED

Voir aussi Pour plus d'informations... reportez-vous... sur les blocs de connexion au chapitre Description (Page 56) sur le relais de surcharge au chapitre Manuels des Innovations SIRIUS

(Page 90) de l'annexe "Bibliographie" du manuel "Relais de surveillance 3UG4 / 3RR2"

sur le relais de surveillance du courant

Description du produit 3.3 Environnement d'utilisation

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 18 Manuel, 08/2014, A5E03656507230A/RS-AA/002

3.3 Environnement d'utilisation

Conditions générales d'emploi Le tableau ci-après indique les conditions générales dans lesquelles il est permis d'exploiter le produit.

Tableau 3- 2 Conditions générales d'emploi

Conditions d'emploi Valeur Degré de protection IP20 Température ambiante en service - 25 ... 60 °C Altitude d'implantation 0 ... 1000 m ;

pour > 1000 m, s'adresser au Support technique (www.siemens.com/industrial-controls/technical-assistance)

Résistance aux chocs 15 g / 11 ms ; selon CEI 60068-2-27 Résistance aux vibrations 2 g ; selon CEI 60068-2-6 Conditions CEM selon CEI 60947-4-2, CEI 61000-4-2, CEI 61000-4-4,

CEI 61000-4-5 et CEI 61000-4-6 Résistance d'isolement 50 / 60 Hz 4000 Vrms

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les conditions d'emploi des appareils à semiconducteurs

Caractéristiques techniques (Page 59)

Conformément à la norme produit CEI 60947-4-2, les appareils à semiconducteurs sont conçus pour des moteurs avec un courant de démarrage I/Ie < 8.

Pour les moteurs à courant de démarrage plus élevé (typiquement I/Ie > 8), réduire le courant assigné d'emploi selon le tableau ci-dessous :

Appareils à semiconducteurs IeAC53a [A] à 40 °C

Contacteurs à semiconducteurs Contacteur-inverseur à semiconducteurs

3RF3405-.BB..

3RF3410-.BB..

3RF3412-.BB..

3RF3416-.BB..

3RF34 03-.BD.4

3RF34 05-.BD.4

3RF34 10-.BD.4

rapport max. du courant de démarrage <= 8 x Ie 5,2 9,2 12,5 16,0 3,8 5,4 7,4 8,5 x Ie 4,9 8,7 11,8 15,1 3,6 5,1 7,0 9 x Ie 4,6 8,2 11,1 14,2 3,4 4,8 6,6 9,5 x Ie 4,4 7,7 10,5 13,5 3,2 4,5 6,2 10 x Ie 4,2 7,4 10,0 12,8 3,0 4,3 5,9

Description du produit 3.4 Appareils à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 19

3.4 Appareils à semiconducteurs

Eléments de commande et équipement

Contacteur à semiconducteurs

Elément de

commande / Equipement Fonction

1 Contacteur à semiconducteurs Enclenchement et coupure fréquentes de moteurs triphasés 2 Raccordement par bornes à

vis / par bornes à ressort Bornes de circuit principal, alimentation / côté réseau

3 LED La LED est allumée quand la tension de commande est appliquée.

4 Connecteur de commande enfichable (2 bornes)

Bornes amovibles pour le circuit de commande

5 Raccordement par bornes à vis / par bornes à ressort

Bornes de circuit principal, départ du moteur / côté charge

Figure 3-1 Vue d'ensemble d'un contacteur à semiconducteurs - raccordement par bornes à vis et par bornes à ressort

Description du produit 3.4 Appareils à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 20 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Contacteur-inverseur à semiconducteurs

Elément de

commande / Equipement Fonction

1 Contacteur à semiconducteurs Enclenchement et coupure fréquentes de moteurs triphasés 2 Raccordement par bornes à vis Bornes de circuit principal, alimentation / côté réseau 3 LED LED jaune de gauche allumée en commande pour marche

vers la gauche (tension de commande aux bornes A1 et A2). LED jaune de droite allumée en commande pour marche vers la droite (tension de commande aux bornes A3 et A2).

4 Connecteur de commande enfichable (3 bornes)

Bornes amovibles pour le circuit de commande

5 Raccordement par bornes à vis Bornes de circuit principal, départ du moteur / côté charge

Figure 3-2 Vue d'ensemble d'un contacteur-inverseur à semiconducteurs - raccordement par bornes à vis

Description du produit 3.5 Marquages sur l'appareil

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 21

3.5 Marquages sur l'appareil

Marquages sur l'appareil

1 Repérage des bornes de circuit principal, alimentation / côté réseau 2 SIRIUS (famille d'appareils) 3 Date de fabrication / version 4 Repérage des bornes de circuit principal, départ du moteur / côté charge 5 Numéro de référence 6 Repérage des bornes du circuit de commande et tension de commande

(voir aussi les figures suivantes "Détail du marquage des contacteurs à semiconducteurs") 7 Schéma électrique

Figure 3-3 Marquage des contacteurs à semiconducteurs avec bornes à vis

Description du produit 3.5 Marquages sur l'appareil

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 22 Manuel, 08/2014, A5E03656507230A/RS-AA/002

1 Repérage des bornes de circuit principal, alimentation / côté réseau 2 SIRIUS (famille d'appareils) 3 Date de fabrication / version 4 Repérage des bornes de circuit principal, départ du moteur / côté charge 5 Numéro de référence 6 Repérage des bornes du circuit de commande et tension de commande

(voir aussi les figures suivantes "Détail du marquage des contacteurs à semiconducteurs") 7 Schéma électrique

Figure 3-4 Marquage des contacteurs à semiconducteurs avec bornes à ressort

Figure 3-5 Détail du marquage des contacteurs à semiconducteurs avec tension de commande CA

Figure 3-6 Détail du marquage des contacteurs à semiconducteurs avec tension de commande CC

Description du produit 3.5 Marquages sur l'appareil

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 23

1 Repérage des bornes de circuit principal, alimentation / côté réseau 2 SIRIUS (famille d'appareils) 3 Date de fabrication / version 4 Repérage des bornes de circuit principal, départ du moteur / côté charge 5 Numéro de référence 6 Repérage des bornes du circuit de commande et tension de commande

(voir aussi les figures suivantes "Détail du marquage des contacteurs-inverseurs à semiconducteurs")

7 Schéma électrique

Figure 3-7 Marquage des contacteurs-inverseurs à semiconducteurs avec bornes à vis

Figure 3-8 Détail du marquage des contacteurs-inverseurs à semiconducteurs avec tension de

commande CA

Figure 3-9 Détail du marquage des contacteurs-inverseurs à semiconducteurs avec tension de

commande CC

Description du produit 3.6 Avantages des appareils à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 24 Manuel, 08/2014, A5E03656507230A/RS-AA/002

3.6 Avantages des appareils à semiconducteurs

Avantages techniques / intérêt pour le client

Tableau 3- 3 Avantages des appareils à semiconducteurs

Points forts techniques Avantages pour le client Avantages majeurs Bornes amovibles pour le câblage du circuit auxiliaire

évite les erreurs de câblage lors du remplacement de l'appareil

Interverrouillage électrique intégré Economise des frais et évite les erreurs Contacteur moteur entièrement disponible avec bornes à ressort

Améliore la sécurité de fonctionnement et accélère le câblage

Manœuvre sans usure La grande durée de vie évite un remplacement cyclique dans les applications à haute fréquence de manœuvre. L'installation est en service plus longtemps.

Autres avantages Bornes à vis avec des sections pratiques Choix de câbles souple et selon l'application Blocs de connexion du disjoncteur à l'appareil de connexion

Montage rapide et sans erreur pour raccordement par bornes à vis

Manœuvre silencieuse Utilisation dans des bâtiments grâce au nuisances sonores réduites

Essais homogènes des ensembles pour le montage avec et sans fusibles

Sûreté de l'étude

Homologations complètes Mise en œuvre dans le monde entier Outil unique et couples de serrage identiques pour tous les appareils

Montage simple et rapide

Quelques variantes de puissance seulement jusqu'à 7,5 kW

Etude facile

Modèles avec plage étendue de tension 110 à 230 V CA

Réduction des frais de stockage car moins de variantes chez le client

Mise à disposition complète des données CAx Etude simple et exempte d'erreurs Fiches techniques en 10 langues par numéro de référence

Toutes les caractéristiques techniques sont disponibles et maintenues à jour en 10 langues.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 25

Combinaison des produits 4

Les produits de la gamme Innovations du système modulaire SIRIUS sont assortis les uns aux autres électriquement et mécaniquement et sont donc simples et rapides à assembler.

Les appareils à semiconducteurs 3RF34 à bornes à vis peuvent être combinés avec les appareils suivants :

● Disjoncteurs 3RV20 (avec bloc de connexion 3RA2921-1BA00)

● Relais électroniques de surcharge 3RB3

● Relais de surveillance du courant 3RR2

Voir aussi Pour plus d'informations... reportez-vous... sur les ensembles d'appareillage avec des appareils à semiconducteurs

à l'aide à la configuration (en anglais) "Configurer les Innovations SIRIUS - Données pour départs-moteur en montage avec fusibles et sans fusibles" (nº de référence : 3ZX1012-0RA21-1AC0)

Combinaison des produits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 26 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 27

Fonctions 5

Performances Les performances des appareils à semiconducteurs dépendent pour une grande part des semiconducteurs utilisés et du montage interne. Dans les contacteurs à semiconducteurs et dans les relais à semiconducteurs SIRIUS, seuls des thyristors sont mis en œuvre au lieu des triacs moins puissants. Deux caractéristiques essentielles des thyristors sont la tension de blocage et l'intégrale de destruction.

Tension de blocage Les thyristors à tension de blocage élevée peuvent être exploités sans problème dans les réseaux présentant des tensions perturbatrices importantes. Dans la plupart des cas, les mesures de protection séparées telles que le montage d'une varistance ne sont pas nécessaires.

Les appareils à semiconducteurs SIRIUS contiennent par ex. des thyristors avec une tension de blocage de 800 V pour l'emploi dans des réseaux jusqu'à 230 V. Pour les réseaux avec des tensions plus élevées, on a recours à des thyristors allant jusqu'à 1600 V.

Intégrale de destruction L'indication de l'intégrale de destruction (I²t) sert entre autres à dimensionner la protection contre les courts-circuits. Un semiconducteur de puissance ne pourra être protégé contre la destruction par court-circuit au moyen d'un organe de protection assorti à l'application que s'il est de taille suffisante avec une grande valeur correspondante pour I²t. Mais les appareils à semiconducteurs SIRIUS se distinguent aussi par des thyristors assortis de manière optimale (valeur de I²t) aux courants assignés. Les courants assignés selon EN 60947-4-2 qui sont indiqués sur les appareils sont confirmés par des tests très complets.

Fonctions 5.1 Commande des appareils à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 28 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Durée de vie améliorée Par rapport aux appareils de connexion classiques, les appareils à semiconducteurs présentent une durée de vie de manœuvre extrêmement longue.

Tableau 5- 1 Comparaison entre appareils de connexion classiques et appareils à semiconducteurs

Caractéristique Appareils de connexion classiques

Appareils à semiconducteurs

Durée de vie de manœuvre 1 à 3 millions de cycles de manœuvre

Plus de 100 millions de cycles de manœuvre

Puissance dissipée Faible Forte Puissance de commande Forte Faible résistance aux chocs / aux secousses

Moyenne Très élevée

Nuisances sonores Moyenne Néant Séparation galvanique Oui Néant Arc électrique parasite Oui Néant

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les performances des appareils à semiconducteurs

Caractéristiques techniques (Page 59)

5.1 Commande des appareils à semiconducteurs

Contacteurs à semiconducteurs Les contacteurs à semiconducteurs sont mis en œuvre pour l'enclenchement fréquent de moteurs. L'application de la tension de commande aux bornes A1 / A2 donne l'ordre d'enclenchement au contacteur à semiconducteurs. Les semiconducteurs de la partie puissance sont commandés après un bref temps de retard.

Contacteurs-inverseurs à semiconducteurs Les contacteurs-inverseurs à semiconducteurs sont prévus pour l'inversion fréquente du sens de marche des moteurs. Selon l'entrée de commande qui est actionnée, deux paires de semiconducteurs de la partie puissance sont amorcées. Quand les deux entrées sont amorcées en même temps, l'appareil se verrouille et le courant ne circule pas. Le changement d'un sens de marche à l'autre est verrouillé pendant 50 à 100 ms environ.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 29

Configuration / Etude 6 6.1 Choix des appareils à semiconducteurs

Choix des contacteurs à semiconducteurs Le choix des contacteurs à semiconducteurs s'effectue sur la base des données concernant le réseau, la charge et les conditions ambiantes.

Nous recommandons de procéder comme suit :

● Déterminer le courant assigné, la charge et la tension réseau.

● Choisir le contacteur à semiconducteurs avec un courant assigné plus élevé ou au moins égal à la charge.

● Vérifier la fréquence de manœuvre maximale admissible sur la base des courbes caractéristiques. Pour cela, il faut connaître le courant de démarrage du moteur, sa durée de démarrage et sa charge en fonctionnement.

● Quand la fréquence de manœuvre admissible est inférieure à la fréquence souhaitée, elle ne peut être augmentée que par surdimensionnement du moteur.

● Une autre solution consiste à saisir les données concernant le réseau, le moteur, l'application et les conditions ambiantes dans l'outil "Choix des contacteurs à semiconducteurs pour la commande de moteurs (https://eb.automation.siemens.com/spicecad/dc-web-app/main/index.jsf)" pour effectuer sur Internet le dimensionnement correct de l'appareil.

Départs-moteur Il n'y a pas de montage typique pour un départ-moteur avec des relais à semiconducteurs ou des contacteurs à semiconducteurs , la multitude de techniques de raccordement et de tensions de commande offre plutôt des possibilités d'utilisation universelles. Les relais à semiconducteurs et les contacteurs à semiconducteurs SIRIUS peuvent être montés au choix dans des départs avec fusibles ou sans fusibles.

Voir aussi Pour plus d'informations... reportez-vous... sur les départs-moteurs testés à l'aide à la configuration (en anglais) "Configurer les

Innovations SIRIUS - Données pour départs-moteur en montage avec fusibles et sans fusibles" (nº de référence : 3ZX1012-0RA21-1AC0)

sur la fréquence de manœuvre maximale admissible

au chapitre "Caractéristiques techniques (Page 59)"

Configuration / Etude 6.2 Configurateur de système pour Innovations SIRIUS

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 30 Manuel, 08/2014, A5E03656507230A/RS-AA/002

6.2 Configurateur de système pour Innovations SIRIUS

Voir aussi Le "Configurateur de système pour Innovations SIRIUS" vous est mis à disposition sur Internet comme aide à la configuration. Vous pouvez y combiner tous les produits nécessaires et réaliser des projets virtuels complets avant la configuration proprement dite.

Vous trouverez le "Configurateur de système pour Innovations SIRIUS" sur Internet (www.siemens.com/industrial-controls/configurators).

6.3 Configuration : choix de contacteurs à semiconducteurs pour moteurs

Description du programme Choix des appareils à semiconducteurs avec le programme "Choix des contacteurs à semiconducteurs pour la commande de moteurs".

L'outil "Choix de contacteurs à semiconducteurs pour moteurs" sert à déterminer vite et facilement la taille correcte des appareils à semiconducteurs. La charge de l'appareil de connexion est calculée sur la base des détails concernant le moteur, le cycle de charge et les conditions ambiantes, et le type approprié est choisi. Le champ de résultat affiche le numéro de référence dans son entier.

Ce programme est accessible par les liens suivants :

● Configurateur (https://mall.automation.siemens.com/WW/guest/bizLogic/bizGotoConfig.asp?ConfigID=4&ConfigType=3RF2&lang=fr) (choix de contacteurs à semiconducteurs pour moteurs)

● Choix des contacteurs à semiconducteurs pour la commande de moteurs (https://eb.automation.siemens.com/spicecad/dc-web-app/main/index.jsf)

Remarque Dimensionnement du moteur et des appareils de protection correspondants.

Il incombe à l'utilisateur de dimensionner correctement le moteur et les appareils de protection correspondants. Avec une fréquence de manœuvre élevée, il est recommandé d'utiliser une protection moteur par thermistance. Le cas échEant, il est possible que des disjoncteurs ou des relais de surcharge ne conviennent pas pour protéger le moteur de la surcharge.

Configuration / Etude 6.3 Configuration : choix de contacteurs à semiconducteurs pour moteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 31

Figure 6-1 Interface graphique du programme : "Choix de contacteurs à semiconducteurs pour moteurs"

Marche à suivre : Pour commencer, il faut indiquer le mode de fonctionnement. Lorsque vous choisissez entre "Démarrage direct" et "Démarrage-inversion", le calcul est activé pour la première fois. Les autres indications peuvent être faites dans n'importe quel ordre, le calcul est lancé de nouveau après chaque saisie. Quelques indications entraînent des restrictions pour les autres paramètres, ceci est signalé par des messages s'affichant dans le champ "Etat". Quand les données saisies provoquent des erreurs, ceci est signalé également dans le champ "Etat". Une fois les données saisies corrigées et le calcul correct efffectué, le numéro de référence d'un appareil adéquat s'affiche dans le champ "Résultat". On peut alors le copier pour passer la commande dans le Mall (http://www.siemens.com/automation/mall).

Un nouveau choix du "Mode de fonctionnement" remet l'outil complètement à zéro, le bouton "Langue" permet de passer à l'une des langues suivantes : allemand, anglais, espagnol, italien, portugais.

Configuration / Etude 6.3 Configuration : choix de contacteurs à semiconducteurs pour moteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 32 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Explications des paramètres ● "Mode de fonctionnement"

Choix entre contacteur moteur et contacteur-inverseur

● "Lieu d'utilisation" Choix de l'environnement d'application, c.-à-d. d'un montage conforme aux normes CEI ou selon les règles UL.

● "Protection" La protection contre les courts-circuits des appareils à semiconducteurs, soit avec des disjoncteurs, soit avec des fusibles, a une influence sur le courant assigné.

● "Unité de température" La température peut être saisie au choix en degrés Celsius ou en degrés Fahrenheit.

● "Température ambiante" Il s'agit de la température ambiante au lieu de montage. Au-dessus de 40 °C / 104 °F, des restrictions s'appliquent au courant assigné des appareils.

● "Tension de commande" Le choix de la tension de commande détermine le type d'appareil.

● "Altitude d'implantation" Il s'agit de l'altitude au lieu de montage. Au-delà de 1000 m au-dessus du niveau de la mer, des restrictions s'appliquent au courant assigné des appareils.

● Paramètres réseau

– "Tension réseau" Le choix de la tension réseau détermine le modèle de l'appareil.

– "Fréquence réseau" Cette donnée est nécessaire pour calculer correctement la charge électrique.

Configuration / Etude 6.3 Configuration : choix de contacteurs à semiconducteurs pour moteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 33

● Paramètres moteur

– "Courant assigné du moteur" Il figure sur la plaque signalétique du moteur.

– "Courant d'emploi du moteur" Il s'agit du courant effectivement consommé pendant le fonctionnement, à déterminer par une mesure le cas échEant. On peut aussi estimer cette valeur sur la base des données de charge.

– "Facteur du courant de démarrage du moteur" Cette valeur figure dans les caractéristiques techniques du moteur, elle détermine de façon décisive la charge électrique de l'appareil de connexion pendant le démarrage.

– "Temps de démarrage" C'est le temps requis par le moteur pour un démarrage.

● "Type de saisie du cycle de charge" Un cycle de charge se compose de la phase de démarrage, la phase de fonctionnement et la phase de pause. La durée du cycle de charge est la somme de ces phases. On peut choisir entre deux méthodes pour saisir le cycle de charge : soit saisir la fréquence de manœuvre et le facteur de marche, soit indiquer le temps de fonctionnement et le temps de pause.

– "Fréquence de manœuvre" C'est le nombre de cycles de charge en une heure ; pour les contacteurs-inverseurs, chaque cycle de charge compte, qu'il soit en marche vers la gauche ou en marche vers la droite.

– "Facteur de marche" Rapport entre la somme du temps de démarrage et du temps de fonctionnement et la durée totale du cycle de charge.

– "Temps de fonctionnement" Durée pendant laquelle le courant d'emploi du moteur circule.

– "Temps de pause" Durée de la phase hors courant.

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 34 Manuel, 08/2014, A5E03656507230A/RS-AA/002

6.4 Protection contre les courts-circuits

6.4.1 Montages du départ-moteur conformes à CEI

6.4.1.1 Contacteurs à semiconducteurs 3RF34 - Types de coordination 1 et 2 selon CEI (montage avec fusibles)

Combiner des contacteurs à semiconducteurs 3RF34 du type de coordination 1 (type 1) à des relais de surcharge 3RB3

Les contacteurs à semiconducteurs 3RF34 peuvent être combinés aux relais de surcharge 3RB3 suivants conformément au type de coordination 1 (type 1) :

Tableau 6- 1 Numéros de référence des relais de surcharge 3RB3

Relais de surcharge Contacteur à semiconducteurs Cartouches fusibles maxi admissibles à 400 V ; classe de service gG

Référence de commande

Plage de réglage Numéro de référence

Courant assigné

Référence de commande

Courant assigné

3RB3.2.-N.. 0,32 … 1,25 A 3RF3405-xBByz 4 A 3NW6210-1 3NA6810-6

25 A 3RB3.2.-P.. 1 … 4 A 3RF3405-xBByz 4 A 3RB3.2.-S.. 3 … 12 A 3RF3405-xBByz 4 A 3RB3.2.-N.. 0,32 … 1,25 A 3RF3410-xBByz 7,8 A 3NW6217-1

3NA6817-6 40 A

3RB3.2.-P.. 1 … 4 A 3RF3410-xBByz 7,8 A 3RB3.2.-S.. 3 … 12 A 3RF3410-xBByz 7,8 A 3RB3.2.-Q.. 6 … 25 A 3RF3410-xBByz 7,8 A 3RB3.2.-N.. 0,32 … 1,25 A 3RF3412-xBByz 9,5 A 3NW6117-1

3NA6817-6 40 A

3RB3.2.-P.. 1 … 4 A 3RF3412-xBByz 9,5 A 3RB3.2.-S.. 3 … 12 A 3RF3412-xBByz 9,5 A 3RB3.2.-Q.. 6 … 25 A 3RF3412-xBByz 9,5 A 3RB3.2.-N.. 0,32 … 1,25 A 3RF3416-xBByz 11 A 3NW6117-1

3NA6817-6 40 A

3RB3.2.-P.. 1 … 4 A 3RF3416-xBByz 11 A 3RB3.2.-S.. 3 … 12 A 3RF3416-xBByz 11 A 3RB3.2.-Q.. 6 … 25 A 3RF3416-xBByz 11 A

Tableau 6- 2 Compléments du numéro de référence :

x = connectique

1 = bornes à vis 2 = bornes à ressort

y = tension de commande

0 = 24 V CC selon EN 61131-2 2 = 110 ... 230 V CA

z = tension assignée de commande

4 = 48 à 480 V 6 = 48 à 600 V

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 35

Combiner des contacteurs à semiconducteurs 3RF34 du type de coordination 2 (type 2) à des relais de surcharge 3RB3

Les contacteurs à semiconducteurs 3RF34 peuvent être combinés aux relais de surcharge 3RB3 suivants conformément au type de coordination 2 (type 2) :

Tableau 6- 3 Numéros de référence des relais de surcharge 3RB3

Relais de surcharge Contacteur à semiconducteurs Cartouches fusibles maxi admissibles à 400 V Référence de commande

Plage de réglage

Référence de commande

Courant assigné

Référence de commande

Courant assigné

Classe de service

3RB3.2.-N.. 0,32 … 1,25 A 3RF3405-xBByz 4 A 3NA3801-6 5SB2 31

6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3405-xBByz 4 A 3NC1020 20 A aR 3RB3.2.-S.. 3 … 12 A 3RF3405-xBByz 4 A 3NC1020 20 A aR 3RB3.2.-N.. 0,32 … 1,25 A 3RF3410-xBByz 7,8 A 3NA3801-6

5SB2 31 6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3410-xBByz 7,8 A 3NE1802-0 3NE8020-1 3NW6205-1

40 A 80 A 16 A

gR aR aR

3RB3.2.-S.. 3 … 12 A 3RF3410-xBByz 7,8 A 3NE1802-0 3NE8020-1 3NW6205-1

40 A 80 A 16 A

gR aR aR

3RB3.2.-Q.. 6 … 25 A 3RF3410-xBByz 7,8 A 3NE1802-0 3NE8020-1 3NW6205-1

40 A 80 A 16 A

gR aR aR

3RB3.2.-N.. 0,32 … 1,25 A 3RF3412-xBByz 9,5 A 3NA3801-6 5SB2 31

6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3412-xBByz 9,5 A 3NA3807-6 5SB2 71

20 A gG

3RB3.2.-S.. 3 … 12 A 3RF3412-xBByz 9,5 A 3NE1818-0 3NC2200

63 A 100 A

gR aR

3RB3.2.-Q.. 6 … 25 A 3RF3412-xBByz 9,5 A 3NE1818-0 3NC2200

63 A 100 A

gR aR

3RB3.2.-N.. 0,32 … 1,25 A 3RF3416-xBByz 11 A 3NA3801-6 5SB2 31

6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3416-xBByz 11 A 3NA3807-6 5SB2 71

20 A gG

3RB3.2.-S.. 3 … 12 A 3RF3416-xBByz 11 A 3NA3812 32 A gG 3RB3.2.-Q.. 6 … 25 A 3RF3416-xBByz 11 A 3NA3812 32 A gG

Tableau 6- 4 Compléments du numéro de référence :

x = connectique

1 = bornes à vis 2 = bornes à ressort

y = tension de commande

0 = 24 V CC selon EN 61131-2 2 = 110 ... 230 V CA

z = tension assignée de commande

4 = 48 à 480 V 6 = 48 à 600 V

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 36 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Remarque

Montage sans fusibles (coordination des disjoncteurs) : voir Caractéristiques techniques (Page 59).

6.4.1.2 Contacteurs-inverseurs à semiconducteurs 3RF34 - Types de coordination 1 et 2 selon CEI (montage avec fusibles)

Combiner des contacteurs-inverseurs à semiconducteurs 3RF34 du type de coordination 1 (type 1) à des relais de surcharge 3RB3

Les contacteurs-inverseurs à semiconducteurs 3RF34 peuvent être combinés aux relais de surcharge 3RB3 suivants conformément au type de coordination 1 (type 1) :

Tableau 6- 5 Numéros de référence des relais de surcharge 3RB3

Relais de surcharge Contacteur-inverseur à semiconducteurs

Cartouches fusibles maxi admissibles à 400 V, classe de service gG

Référence de commande

Plage de réglage

Référence de commande

Courant assigné

Référence de commande

Courant assigné

3RB3.2.-N.. 0,32 … 1,25 A 3RF3403-xBDyz 3,8 A 3NW6210-1 3NA6810-6

25 A 3RB3.2.-P.. 1 … 4 A 3RF3403-xBDyz 3,8 A 3RB3.2.-S.. 3 … 12 A 3RF3403-xBDyz 3,8 A 3RB3.2.-N.. 0,32 … 1,25 A 3RF3405-xBDyz 5,4 A 3NW6217-1

3NA6817-6 40 A

3RB3.2.-P.. 1 … 4 A 3RF3405-xBDyz 5,4 A 3RB3.2.-S.. 3 … 12 A 3RF3405-xBDyz 5,4 A 3RB3.2.-N.. 0,32 … 1,25 A 3RF3410-xBDyz 7,4 A 3NW6117-1

3NA6817-6 40 A

3RB3.2.-P.. 1 … 4 A 3RF3410-xBDyz 7,4 A 3RB3.2.-S.. 3 … 12 A 3RF3410-xBDyz 7,4 A 3RB3.2.-Q.. 6 … 25 A 3RF3410-xBDyz 7,4 A

Tableau 6- 6 Compléments du numéro de référence :

x = connectique

1 = bornes à vis 2 = bornes à ressort

y = tension de commande

0 = 24 V CC selon EN 61131-2 2 = 110 ... 230 V CA

z = tension assignée de commande

4 = 48 à 480 V 6 = 48 à 600 V

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 37

Combiner des contacteurs-inverseurs à semiconducteurs 3RF34 du type de coordination 2 (type 2) à des relais de surcharge 3RB3

Les contacteurs-inverseurs à semiconducteurs 3RF34 peuvent être combinés aux relais de surcharge 3RB3 suivants conformément au type de coordination 2 (type 2) :

Tableau 6- 7 Numéros de référence des relais de surcharge 3RB3

Relais de surcharge Contacteur-inverseur à semiconducteurs

Cartouches fusibles maxi admissibles à 400 V

Référence de commande

Plage de réglage

Référence de commande

Courant assigné

Référence de commande

Courant assigné

Classe de service

3RB3.2.-N.. 0,32 … 1,25 A 3RF3403-xBDyz 3,8 A 3NA3801-6 5SB2 31

6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3403-xBDyz 3,8 A 3NC1020 20 A aR 3RB3.2.-S.. 3 … 12 A 3RF3403-xBDyz 3,8 A 3NC1020 20 A aR 3RB3.2.-N.. 0,32 … 1,25 A 3RF3405-xBDyz 5,4 A 3NA3801-6

5SB2 31 6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3405-xBDyz 5,4 A 3NE1802-0 3NE8020-1

40 A 80 A

gR aR

3RB3.2.-S.. 3 … 12 A 3RF3405-xBDyz 5,4 A 3NE1802-0 3NE8020-1

40 A 80 A

gR aR

3RB3.2.-N.. 0,32 … 1,25 A 3RF3410-xBDyz 7,4 A 3NA3801-6 5SB2 31

6 A gG

3RB3.2.-P.. 1 … 4 A 3RF3410-xBDyz 7,4 A 3NE1802-0 3NE8020-1

40 A 80 A

gR aR

3RB3.2.-S.. 3 … 12 A 3RF3410-xBDyz 7,4 A 3NE1802-0 3NE8020-1

40 A 80 A

gR aR

3RB3.2.-Q.. 6 … 25 A 3RF3410-xBDyz 7,4 A 3NE1802-0 3NE8020-1

40 A 80 A

gR aR

Tableau 6- 8 Compléments du numéro de référence :

x = connectique

1 = bornes à vis 2 = bornes à ressort

y = tension de commande

0 = 24 V CC selon EN 61131-2 2 = 110 ... 230 V CA

z = tension assignée de commande

4 = 48 à 480 V 6 = 48 à 600 V

Remarque

Montage sans fusibles (coordination des disjoncteurs) : voir Caractéristiques techniques (Page 59)

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 38 Manuel, 08/2014, A5E03656507230A/RS-AA/002

6.4.2 Montages du départ-moteur selon UL

6.4.2.1 Indications SCCR sur le courant de court-circuit

Indications SCCR sur le courant de court-circuit ● La valeur SCCR (Short Circuit Current Rating) indique le courant de court-circuit maximal

admissible pour un appareil de connexion. Une valeur plus élevée ne peut être obtenue qu'avec des appareils de protection tels que fusibles ou disjoncteurs.

● Cette indication est nécessaire pour monter des armoires électriques selon UL 508A. L'appareil de connexion ou l'ensemble d'appareillage avec la valeur la plus basse détermine la valeur pour toute l'armoire. Si cette valeur est basse, il en résultera un gros travail d'ingénierie pour alimenter l'armoire en tension.

● Les appareils à semiconducteurs 3RF3 ont une valeur de court-circuit standard de 5 kA selon UL 508.

● En outre, on a fait des tests avec une valeur de court-circuit de 65 kA (High Capacity Short Circuit Current Ratings). Les combinaisons possibles avec des fusibles Class CC et Class J ainsi qu'avec certains disjoncteurs ont été consignées dans les rapports UL.

6.4.2.2 Fusibles

Fusibles pour contacteurs à semiconducteurs

Tableau 6- 9 Fusibles pour la protection contre les courants de court-circuit de forte intensité

Fusibles 3RF34 Taille maxi [A] Classe Type Courant [kA] Tension [V]

3RF3405-.BB 25 J TD 65 480 3RF3405-.BB 45 J TD 65 600 3RF3410-.BB 45 J TD 65 480 3RF3410-.BB 45 J TD 65 600 3RF3412-.BB 45 J TD 65 480 3RF3412-.BB 50 J TD 65 600 3RF3416-.BB 50 J TD 65 480 3RF3416-.BB 50 J TD 65 600

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 39

Fusibles pour contacteurs-inverseurs à semiconducteurs

Tableau 6- 10 Fusibles pour la protection contre les courants de court-circuit de forte intensité

Fusibles 3RF34 Taille maxi [A] Classe Type Courant [kA] Tension [V]

3RF3403-.BD 45 J TD 65 480 3RF3405-.BD 45 J TD 65 480 3RF3410-.BD 45 J TD 65 480

Disjoncteurs pour la protection contre les courants de court-circuit de forte intensité

Tableau 6- 11 Disjoncteurs pour contacteurs à semiconducteurs

Fusibles 3RF34 Taille maxi [A] Type Courant [kA] Tension [V]

3RF3405-.BB 4 3RV1721 50 480 3RF3405-.BB 4 3RV1721 10 600 3RF3410-.BB 8 3RV1721 5 600 3RF3412-.BB 8 3RV1721 5 600 3RF3416-.BB 8 3RV1721 5 600 3RF3416-.BB 10 3RV1721 5 600

Tableau 6- 12 Disjoncteurs pour contacteurs-inverseurs à semiconducteurs

Fusibles 3RF34 Taille maxi [A] Type Courant [kA] Tension [V]

3RF3403-.BD 4 3RV1721 50 480 3RF3405-.BD 5 3RV1721 30 480 3RF3410-.BD 8 3RV1721 5 480

Remarque Courants de court-circuit

Les courants de court-circuit peuvent causer des dégâts.

Pour les assemblages d'appareils à semi-conducteur et relais de surcharge, l'appareil dont la valeur assignée est la plus faible est déterminant pour le dimensionnement de la protection de court-circuit.

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 40 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Fusibles de protection des semiconducteurs Une autre solution consiste à utiliser des fusibles SITOR au lieu des fusibles UL. Les rapports UL ont été complétés également sur ce point. La protection des semiconducteurs est bien meilleure dans ce cas (comparable au type de coordination 2).

Pour les applications UL, il faut savoir que : les fusibles SITOR ne sont pas un organe de protection des départs, mais seulement des "special purpose fuses".

Tableau 6- 13 Protection par fusibles de protection des semiconducteurs

Fusible

3RF34 Taille maxi [A] Type Courant [kA] Tension [V] 3RF3405-.BB 16 3NE1813-0 65 480 3RF3405-.BB 32 3NE4101 65 480 3RF3405-.BB 25 3NE8715-1 65 480 3RF3405-.BB 25 3NE8015-1 65 480 3RF3405-.BB 35 3NE1803-0 65 600 3RF3405-.BB 50 3NE4117 65 600 3RF3405-.BB 50 3NE8717-1 65 600 3RF3405-.BB 63 3NE8018-1 65 600 3RF3410-.BB 35 3NE1803-0 65 600 3RF3410-.BB 50 3NE4117 65 600 3RF3410-.BB 50 3NE8717-1 65 600 3RF3410-.BB 63 3NE8018-1 65 600 3RF3412-.BB 63 3NE1818-0 65 480 3RF3412-.BB 50 3NE1817-0 65 600 3RF3412-.BB 50 3NE4117 65 600 3RF3412-.BB 50 3NE8717-1 65 600 3RF3412-.BB 63 3NE8018-1 65 600 3RF3412-.BB 80 3NE1020-2 65 600 3RF3416-.BB 63 3NE1818-0 65 480 3RF3416-.BB 50 3NE1817-0 65 600 3RF3416-.BB 50 3NE4117 65 600 3RF3416-.BB 50 3NE8717-1 65 600 3RF3416-.BB 63 3NE8018-1 65 600 3RF3416-.BB 80 3NE1020-2 65 600 3RF3403-.BD 35 3NE1803-0 65 480 3RF3403-.BD 50 3NE4117 65 480 3RF3403-.BD 50 3NE8717-1 65 480 3RF3403-.BD 63 3NE8018-1 65 480 3RF3405-.BD 35 3NE1803-0 65 480 3RF3405-.BD 50 3NE4117 65 480 3RF3405-.BD 50 3NE8717-1 65 480

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 41

Fusible

3RF34 Taille maxi [A] Type Courant [kA] Tension [V] 3RF3405-.BD 63 3NE8018-1 65 480 3RF3410-.BD 35 3NE1803-0 65 480 3RF3410-.BD 50 3NE4117 65 480 3RF3410-.BD 50 3NE8717-1 65 480 3RF3410-.BD 63 3NE8018-1 65 480

Configuration / Etude 6.4 Protection contre les courts-circuits

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 42 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 43

Etude de la mise en œuvre 7

Remarques sur l'intégration dans les départs-moteur Les appareils à semiconducteurs SIRIUS sont très faciles à intégrer dans les départs-moteur en raison de leur connectique et de leur construction industrielles.

Mais il faut prêter une attention particulière aux conditions de montage et aux conditions ambiantes, car elles ont une influence considérable sur les performances des appareils. Selon le modèle, il faut tenir compte de certaines restrictions. Vous trouverez des indications détaillées sur les écartements minimum au chapitre Caractéristiques techniques (Page 59) et dans les fiches techniques des produits.

Malgré la robustesse des semiconducteurs utilisés dans la partie puissance, les appareils à semiconducteurs sont sensibles aux courts.circuits dans le départ-moteur. Il faut donc prendre des mesures particulières contre la destruction, selon le type de montage.

De façon générale, il est recommandé d'utiliser des fusibles SITOR de protection des semiconducteurs. Ces fusibles assurent une protection contre la destruction par court-circuit, même quand les contacteurs à semiconducteurs sont exploités à fond.

En alternative, la protection peut être assurée aussi par des fusibles standard ou par des disjoncteurs quand la charge est plus faible. Cette protection est obtenue par le surdimensionnement approprié des appareils à semiconducteurs. Le chapitre sur les caractéristiques techniques et les fiches techniques des produits donnent des indications sur la protection des semiconducteurs ainsi que sur l'utilisation des appareils SIRIUS avec des organes de protection classiques.

Les contacteurs moteur et les contacteurs-inverseurs à semiconducteurs sont faciles à combiner avec les disjoncteurs 3RV, les relais électroniques de surcharge 3RB3 et les relais de surveillance du courant 3RR2 tirés du système modulaire SIRIUS. Ceci permet de monter simplement des départs moteur avec et sans fusibles qui tiennent peu de place.

Remarque

L'exploitation de moteurs triphasés couplés en étoile (particulièrement avec des puissances <1 kW) avec des contacteurs électromécaniques peut causer des perturbations CEM très fortes. Ces perturbations, qui excèdent les valeurs limites admissibles, peuvent provoquer des dysfonctionnements des appareils à semiconducteurs exploités dans cet environnement.

En cas de fortes perturbations CEM, il est recommandé d'équiper de circuits de protection CEM les moteurs jusqu'à 5,5 kW commandés par des contacteurs électromécaniques 3RT20 1.. Le meilleur filtrage est obtenu par des modules d'antiparasitage RC triphasés, comme par ex. 3RT29 16-1PA1 jusqu'à 400 V. Vous trouverez des modules appropriés pour les contacteurs dans le chapitre "Contacteurs et associations de contacteurs" sous "Accessoires". Il ne faut pas recourir aux modules d'antiparasitage à varistance, car ils ne filtrent pas suffisamment les transitoires rapides.

Etude de la mise en œuvre 7.1 Domaines d'utilisation

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 44 Manuel, 08/2014, A5E03656507230A/RS-AA/002

7.1 Domaines d'utilisation

7.1.1 Commande de moteurs Les contacteurs pour la commande de moteurs sont "à manœuvre instantanée" ; cette méthode est particulièrement adaptée aux charges inductives. L'extension du point de manœuvre à l'ensemble de la courbe sinusoïdale de la tension réseau réduit les défauts à un minimum.

7.1.2 Utilisation dans une installation photovoltaïque

Avantages de l'utilisation de contacteurs-inverseurs à semiconducteurs dans une installation photovoltaïque

● Commande des moteurs d'orientation des panneaux solaires

● Durabilité et compacité

● Encombrements réduits ; durée de vie nettement supérieure par rapport aux contacteurs traditionnels

● Câblage minimal

Pour des raisons thermiques et de coûts, on a renoncé à une solution avec convertisseurs de fréquence.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 45

Montage 8 8.1 Instructions de montage

Possibilités de montage Les appareils à semiconducteurs sont fixés

● par encliquetage sur un rail DIN symétrique ou

● par vissage sur une plaque de montage.

Ecartements minimum

Figure 8-1 Ecartements en montage séparé (cotes en mm)

Figure 8-2 Ecartements en montage accolé (cotes en mm)

Montage 8.1 Instructions de montage

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 46 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Position de montage

Figure 8-3 Position de montage

Disposition des trous

Figure 8-4 Disposition des trous pour fixation par vis (cotes en mm)

Remarque

Le plan de perçage est valable pour les appareils d'une largeur de 90 mm. Pour les appareils d'une largeur de 45 mm, deux trous suffisent.

Montage 8.2 Fixation par vis

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 47

8.2 Fixation par vis

Fixation par vis

Tableau 8- 1 Fixation (appareils à semiconducteurs)

Etape Marche à suivre Figure 1 Fixer le contacteur à semiconducteurs dans

les trous prévus à cet effet avec deux vis M4 (couple de serrage maximal 1,5 Nm) serrées en diagonale, rondelles et rondelles élastiques.

8.3 Fixation sur rail DIN symétrique (fixation par encliquetage) et dépose

Fixation sur rail DIN symétrique

Tableau 8- 2 Fixation (appareils à semiconducteurs)

Etape Marche à suivre Figure 1 Posez l'appareil sur l'arête supérieure

du rail et appuyez-le vers le bas jusqu'à ce qu'il s'encliquette sur l'arête inférieure du rail.

Montage 8.3 Fixation sur rail DIN symétrique (fixation par encliquetage) et dépose

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 48 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 49

Raccordement 9

Connectique Les appareils à semiconducteurs SIRIUS présentent plusieurs possibilités de raccordement. Les types de raccordement suivants sont disponibles :

Raccordement par bornes à vis C'est la technique classique pour l'appareillage industriel. Les bornes ouvertes et les vis plus-moins ne sont que deux des points forts de cette connectique. On peut raccorder dans une seule borne soit deux conducteurs de section allant jusqu'à 6 mm² soit un conducteur de 10 mm².

Raccordement par bornes à ressort Cette technique innovante se passe de toute vis. On obtient ainsi des résistances très élevées aux vibrations. On peut raccorder deux conducteurs de section allant jusqu'à 2,5 mm² par borne.

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les sections de raccordement pour les appareils à semiconducteurs

• Sections de raccordement pour contacteurs à semiconducteurs (Page 61)

• Sections de raccordement pour contacteurs-inverseurs à semiconducteurs (Page 62)

Raccordement 9.1 Contacteur à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 50 Manuel, 08/2014, A5E03656507230A/RS-AA/002

9.1 Contacteur à semiconducteurs

Bornes de raccordement

Tableau 9- 1 Contacteur à semiconducteurs

Borne Déignation L1, L2, L3 Bornes du circuit principal, alimentation / côté réseau T1, T2, T3 Bornes du circuit principal, départ du moteur / côté charge A1∼ Tension d'alimentation de commande, commande CA A2∼ Tension d'alimentation de commande, commande CA A1+ Tension d'alimentation de commande, commande CC (plus) A2- Tension d'alimentation de commande, commande CC (moins)

9.2 Contacteur-inverseur à semiconducteurs %%

Bornes de raccordement

Tableau 9- 2 Contacteur-inverseur à semiconducteurs

Borne Déignation L1, L2, L3 Bornes de circuit principal, alimentation / côté réseau T1, T2, T3 Bornes de circuit principal, départ du moteur / côté charge A1∼ Tension d'alimentation de commande, commande CA A2∼ Tension d'alimentation de commande, commande CA, potentiel de référence pour

A1 / A3 A3∼ Tension d'alimentation de commande, commande CA A1+ Tension d'alimentation de commande, commande CC (plus) A2- Tension d'alimentation de commande, commande CC (moins), potentiel de

référence pour A1 / A3 A3+ Tension d'alimentation de commande, commande CC (plus)

Raccordement 9.3 Sections de conducteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 51

9.3 Sections de conducteur

Sections de raccordement En raison du système modulaire de SIRIUS, les sections de raccordement sont les mêmes pour tous les appareils d'une taille.

9.3.1 Sections pour raccordement par bornes à vis

Sections pour raccordement par bornes à vis Les tableaux suivants donnent les sections de conducteur autorisées pour les raccordements principaux et les raccordements auxiliaires de taille S0 effectués par bornes à vis.

Tableau 9- 3 Conducteur principal de taille S0 avec vis combinée M4

Contacteurs et contacteurs-inverseurs à semiconducteurs Outil

Pozidriv de taille PZ 2, Ø 5 … 6 mm

Couple de serrage 2,0 ... 2,5 Nm Ame massive

2 x (1,5 … 2,5) mm2 2 x (1,5 … 6) mm2

Ame souple avec embout (DIN 46 228 T1)

2 x (1 ... 2,5) mm² 2 x (2,5 ... 6) mm²

Ame souple sans embout

1 x 10 mm2

AWG 2 x (14 … 10) 1) un seul conducteur peut être serré dans le support pour installation séparée.

Tableau 9- 4 Conducteur auxiliaire de taille S0 avec vis combinées M3

Contacteurs et contacteurs-inverseurs à semiconducteurs Outil

Pozidriv de taille PZ 2, Ø 5 … 6 mm

Couple de serrage 0,5 … 0,6 Nm Section de raccordement avec embout (DIN 46 228 T1)

2 x (0,5 ... 2,5) mm²

Section de raccordement sans embout

2 x (0,5 ... 1,0) mm²

AWG 20 … 12

Raccordement 9.3 Sections de conducteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 52 Manuel, 08/2014, A5E03656507230A/RS-AA/002

9.3.2 Sections pour raccordement par bornes à ressort

Sections pour raccordement par bornes à ressort Les tableaux suivants donnent les sections de conducteur autorisées pour les raccordements principaux et les raccordements auxiliaires de taille S0 effectués par bornes à ressort.

Tableau 9- 5 Conducteur principal de taille S0

Contacteurs à semiconducteurs *) Outil

Ø 3,5 x 0,5 (8WA2880 / 8WA2803) Ø3,0 x 0,5 (3RA2808-1A)

Ame massive

2 x (0,5 ... 2,5) mm²

Ame souple sans embout

2 x (0,5 ... 1,5) mm²

Ame souple avec embout (DIN 46 228 T1)

2 x (0,5 ... 2,5) mm²

AWG 2 x (18 à 14) *) Les contacteurs-inverseurs à semiconducteurs sont uniquement disponibles avec des bornes à vis.

Tableau 9- 6 Conducteur auxiliaire de taille S0

Contacteurs à semiconducteurs *) Outil

-

Section de raccordement sans embout

-

Section de raccordement avec embout

0,5 ... 2,5 mm²

AWG 20 … 12 *) Les contacteurs-inverseurs à semiconducteurs sont uniquement disponibles avec des bornes à vis.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 53

Questions fréquemment posées (Foire aux Questions) 10

Déannage / FAQ

Tableau 10- 1 Questions / réponses / solutions

Questions fréquemment posées Réponses / solutions Les appareils à semiconducteurs assurent-ils la séparation galvanique du circuit principal ?

Non, les appareils à semiconducteurs ne séparent pas galvaniquement. Un courant de fuite d'intensité minime (env. 10 mA) circule toujours à l'état coupé. Pour effectuer des travaux de maintenance du côté charge, il faut utiliser un appareil de connexion supplémentaire possédant des propriétés de sectionneur.

On veut commander deux moteurs avec un convertisseur de fréquence. Il s'agit de commuter entre le moteur 1 et le moteur 2 avec une fréquence de manœuvre élevée. Des contacteurs à semiconducteurs sont-ils les appareils appropriés ?

Les contacteurs à semiconducteurs ne conviennent pas pour commuter des charges dans des circuits comportant des convertisseurs de fréquence ou des appareils pour démarrage progressif. La forme non sinusoïdale de la courbe de tension détruirait des constituants importants des contacteurs à semiconducteurs.

Un montage des circuits en parallèle est-il permis pour augmenter les valeurs limites admissibles ?

Un montage des circuits en parallèle n'est pas permis, car des pertes de tension au passage très différentes dans les thyristors provoqueraient une charge fortement asymétrique des circuits. Le circuit avec la résistance de passage la plus faible s'en trouverait surchargé thermiquement.

Les caractéristiques techniques des contacteurs à semiconducteurs 3RF34 mentionnent des courants de charge minimum. Que se passe-t-il quand ils sont dépassés par le bas ?

Le courant de charge minimum est de 0,1 A pour les appareils à semiconducteurs 3RF3405-.BB.4. Elle est de 0,5 A pour toutes les autres variantes. Quand le courant passe en-dessous de cette valeur, il peut arriver que le contacteur coupe dans chaque demi-onde avant le passage par zéro du courant (le courant est discontinu, cela est comparable à une commande par angle de phase). Pour cette raison, il ne faut pas tomber en-dessous de la valeur minimale. Solution proposée : montage en parallèle d'une résistance ohmique apparente (par ex. charge ohmique) pour augmenter l'intensité du courant de charge.

Existe-t-il des contacts auxiliaires pour les contacteurs à semiconducteurs ?

On nous demande souvent comment réaliser un retour de signal pour l'état de manœuvre à l'adresse de l'automate. Pour des raisons physiques, les appareils à semiconducteurs ne disposent pas de blocs de contacts auxiliaires couplés avec le circuit principal et il n'est donc pas possible de signaler directement l'état de manœuvre. L'état de l'appareil de connexion ou plus exactement du moteur peut être signalé à l'automate par les modules de surveillance du courant 3RR2. Les relais de surveillance du courant 3RR2 peuvent être vissés comme extension sur les contacteurs à semiconducteurs pour assurer la surveillance de charge. Ces relais surveillent la charge raccordée. Ils permettent donc de répéter à l'automate l'état du départ-moteur tout entier.

Questions fréquemment posées (Foire aux Questions)

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 54 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 55

Accessoires 11 11.1 Vue d'ensemble des accessoires

Pour obtenir la plus grande souplesse possible, les accessoires peuvent être montés sur les appareils à semiconducteurs au besoin, facilement et sans outil.

Tableau 11- 1 Accessoires pour les appareils à semiconducteurs

Accessoires Contacteur à semiconducteurs

Contacteur-inverseur à semiconducteurs

Jeu de barres triphasé isolé pour raccorder trois contacteurs à semiconducteurs par bornes à ressort

✓ –

Jeu de barres triphasé isolé pour raccorder quatre contacteurs à semiconducteurs par bornes à ressort

✓ –

Arrêt d'isolation 3RT2916-4JA02 pour raccordement par bornes à ressort

✓ –

Adaptateur pour jeu de barres pour système 40 mm ✓ ✓ Adaptateur pour jeu de barres pour système 60 mm ✓ ✓ Bloc de connexion au disjoncteur ✓ ✓ Adaptateur de connexion au relais de surcharge ✓ ✓

11.2 Arrêt d'isolation

11.2.1 Description L'arrêt d'isolation 3RT2916-4JA02 est prévu pour les contacteurs à semiconducteurs raccordés par bornes à ressort et il retient sûrement l'isolation du conducteur pour une section allant jusqu'à 1 mm2. Une barre d'arrêt d'isolation comporte 5 paires de bornes de raccordement. Comme le montre la figure ci-dessous, elle s'enfiche dans les entrées de câble à ressort (jusqu'à 2,5 mm2 maxi de section).

Figure 11-1 Arrêt d'isolation 3RT2916-4AJ02

Accessoires 11.3 Bloc de connexion au disjoncteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 56 Manuel, 08/2014, A5E03656507230A/RS-AA/002

11.3 Bloc de connexion au disjoncteur

11.3.1 Description La mise en œuvre de départs-moteur nécessite des blocs de connexion qui assurent la liaison électrique et mécanique entre contacteur à semiconducteurs et disjoncteur. Le bloc de connexion pour montage du disjoncteur 3RV2 est facile à monter sur les contacteurs.

Figure 11-2 Bloc de connexion au disjoncteur 3RA2921-1BA00

Voir aussi Pour plus d'informations... reportez-vous... sur les blocs de connexion au chapitre "Manuels des Innovations SIRIUS

(Page 90)" de l'annexe "Bibliographie" du manuel "Innovations SIRIUS - Départs-moteur SIRIUS 3RA21 / 22"

sur le montage du contacteur à semiconducteurs et du disjoncteur

au chapitre "Montage / démontage (Page 57)"

Accessoires 11.3 Bloc de connexion au disjoncteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 57

11.3.2 Montage / démontage

Pour monter / démonter le bloc de connexion au disjoncteur Avant de pouvoir encliqueter un disjoncteur sur le contacteur à semiconducteurs ou sur le contacteur-inverseur à semiconducteurs, il faut monter un bloc de connexion entre les deux appareils. La construction isolée des appareils rend une mise à la terre superflue.

Un montage accolé permet de monter plusieurs appareils latéralement. On peut fixer les appareils par des vis ou les encliqueter sur un rail DIN symétrique.

La figure ci-dessous montre à l'aide d'un exemple comment monter le bloc de connexion sur un contacteur à semiconducteurs.

1 Disjoncteurs 2 Bloc de connexion 3 Contacteur à semiconducteurs

Figure 11-3 Montage : disjoncteur, bloc de connexion, contacteur à semiconducteurs

Accessoires 11.4 Adaptateur de connexion au relais de surcharge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 58 Manuel, 08/2014, A5E03656507230A/RS-AA/002

11.4 Adaptateur de connexion au relais de surcharge

11.4.1 Description La mise en œuvre de départs-moteur nécessite des adaptateurs de connexion qui assurent la liaison électrique et mécanique entre contacteur à semiconducteurs et relais de surcharge.

L'adaptateur de connexion s'encliquète sur le boîtier du contacteur 3RF34 et reçoit les crochets de fixation des relais de surcharge 3RB3 ou des relais de surveillance de courant 3RR2 en montage direct.

Figure 11-4 Adaptateur de connexion 3RF3900-0QA88 pour connexion au relais de surcharge

11.4.2 Montage / démontage

Pour monter / démonter l'adaptateur de connexion au relais de surcharge Avant de pouvoir encliqueter un relais de surcharge sur le contacteur à semiconducteurs ou sur le contacteur-inverseur à semiconducteurs, il faut monter un adaptateur de connexion entre les deux appareils. La construction isolée des appareils rend une mise à la terre superflue.

Un montage accolé permet de monter plusieurs appareils latéralement. On peut fixer les appareils par des vis ou les encliqueter sur un rail DIN symétrique.

La figure ci-dessous montre à l'aide d'un exemple comment monter l'adaptateur de connexion sur un contacteur à semiconducteurs.

① Contacteurs à semiconducteurs

② Adaptateur de connexion

Montage : relais de surcharge, adaptateur de connexion, contacteur à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 59

Caractéristiques techniques 12 12.1 Caractéristiques générales

Tableau 12- 1 Appareils à semiconducteurs - caractéristiques générales

Caractéristiques générales Température ambiante en service, déclassement à partir de 40 °C °C - 25 ... + 60 à l'entreposage °C - 55 ... + 80 Altitude d'implantation m 0 ...1000;

pour > 1000 m, s'adresser au Support technique (www.siemens.com/industrial-controls/technical-assistance)

Résistance aux chocs selon DIN CEI 60068-2-27 g/ms 15/11 Résistance aux vibrations selon DIN CEI 60068-2-6 g 2 Degré de protection IP20 Compatibilité électromagnétique (CEM)

• Emission selon NF CEI 60947-4-2

- tension perturbatrice due aux câbles Classe A pour les environnements industriels1) - tension perturbatrice rayonnée à haute

fréquence Classe A pour les environnements industriels

• Immunité2)

- décharges électrostatiques selon NF CEI 61000-4-2 (correspond au niveau de sévérité 3)

kV Décharge par contact : 4 ; décharge à l'air : 8 ; critère de comportement 2

- perturbations conduites, induites par les champs radioélectriques selon NF CEI 61000-4-6

MHz 0,15 ... 80 ; 140 dBμV, critère de comportement 1

- champs électromagnétiques rayonnés aux fréquences radioélectriques selon NF CEI 61000-4-3

MHz 80 ... 3000, niveau de test 10 V/m ; critère de comportement 1

- transitoires électriques rapides en salves selon NF CEI 61000-4-4

kV 2 / 5,0 kHz ; critère de comportement 1

- ondes de choc selon NF CEI 61000-4-53) kV conducteur - conducteur de protection : 2 ; conducteur - conducteur : 1 ; critère de comportement 2

Type de raccordement

• Contacteur à semiconducteurs Raccordement par bornes à vis et par bornes à ressort

• Contacteur-inverseur à semiconducteurs Raccordement par bornes à vis

Caractéristiques techniques 12.1 Caractéristiques générales

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 60 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Caractéristiques générales Position de montage autorisée

Résistance d'isolement pour 50/60 Hz (circuit principal/de commande vers le sol)

V rms 4000

1) Ces produits ont été construits comme appareils de classe A. Leur utilisation en zone résidentielle pourrait provoquer des parasites. Dans ce cas, il est permis d'exiger de l'utilisateur qu'il prenne des mesures d'affaiblissement supplémentaires.

2) L'exploitation de moteurs triphasés couplés en étoile (particulièrement si <1 kW) avec des contacteurs électromécaniques peut causer des perturbations CEM très fortes. Ceci peut provoquer des dysfonctionnements des contacteurs-inverseurs à semiconducteurs situés dans cet environnement. Il faut prévoir des circuits de protection CEM sur les sources des perturbations. Le catalogue IC10 propose des circuits de protection appropriés dans son chapitre 6.

3) Pour les contacteurs-inverseurs à semiconducteurs : pour pouvoir tenir les valeurs, il faut utiliser un limiteur de surtension 3TX7 462-3L (voir catalogue IC10) entre les phases L1 et L3, autant que possible à proximité du contacteur-inverseur.

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur l'environnement d'utilisation des appareils à semiconducteurs

Environnement d'utilisation (Page 18)

Caractéristiques techniques 12.2 Sections de raccordement pour contacteurs à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 61

12.2 Sections de raccordement pour contacteurs à semiconducteurs

Sections de raccordement pour contacteurs à semiconducteurs

Tableau 12- 2 Raccordement des contacts principaux par bornes à vis ou par bornes à ressort

Raccordement, contacts principaux Bornes à vis Bornes à ressort Section de raccordement

• Ame massive mm² 2 x (1,5 ... 2,5), 2 x (1,5 ... 6) 2 x (0,5 ... 2,5)

• Ame souple avec embout mm² 2 x (1,5 ... 2,5), 2 x (1,5 ... 6) 2 x (0,5 ... 1,5)

• Ame souple sans embout mm² 1 x 10 2 x (0,5 ... 2,5)

• Ame massive ou multibrin AWG 2 x (14 ... 10) 2 x (18 ... 14)

Longueur à dénuder mm 10 10 Vis de raccordement M4 — Couple de serrage Nm 2 ... 2,5 — D 5...6 mm / PZ 2 Ib in 18 ... 22 —

Tableau 12- 3 Raccordement des contacts auxiliaires et des contacts de commande par bornes à vis ou par bornes à ressort

Raccordement, contacts auxiliaires et contacts de commande

Bornes à vis Bornes à ressort

Section de raccordement avec embout mm² 1 x (0,5 ... 2,5), 0,5 ... 2,5 Section de raccordement sans embout mm² 2 x (0,5 ... 1,0) AWG 20 ... 12 20 ... 12 Longueur à dénuder mm 7 10 Vis de raccordement M3 — Couple de serrage Nm 0,5 ... 0,6 — D 3,5 / PZ 1 Ib in 4,5 ... 5,3 —

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les techniques de raccordement et le repérage des bornes de raccordement

Raccordement (Page 49)

Caractéristiques techniques 12.3 Sections de raccordement pour contacteurs-inverseurs à semiconducteurs

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 62 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.3 Sections de raccordement pour contacteurs-inverseurs à semiconducteurs

Sections de raccordement pour contacteurs-inverseurs à semiconducteurs

Tableau 12- 4 Raccordement des contacts principaux par bornes à vis

Raccordement, contacts principaux Raccordement par bornes à vis Section de raccordement

• Ame massive mm² 2 x (1,5 ... 2,5), 2 x (1,5 ... 6)

• Ame souple avec embout mm² 2 x (1,5 ... 2,5), 2 x (1,5 ... 6)

• Ame souple sans embout mm² 1 x 10

• Ame massive ou multibrin AWG 2 x (14 ... 10)

Longueur à dénuder mm 10 Vis de raccordement M4 Couple de serrage Nm 2 ... 2,5 D 5...6 mm / PZ 2 Ib.in 18 ... 22

Tableau 12- 5 Raccordement des contacts auxiliaires et des contacts de commande par bornes à vis

Raccordement, contacts auxiliaires et contacts de commande

Raccordement par bornes à vis

Section de raccordement avec embout mm² 1 x (0,5 ... 2,5) Section de raccordement sans embout mm² 2 x (0,5 ... 1,0) AWG 20 ... 12 Longueur à dénuder mm 7 Vis de raccordement M3 Couple de serrage Nm 0,5 ... 0,6 D 3,5 / PZ 1 Ib.in 4,5 ... 5,3

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les techniques de raccordement et le repérage des bornes de raccordement

Raccordement (Page 49)

Caractéristiques techniques 12.4 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à vis

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 63

12.4 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à vis

Contacteurs à semiconducteurs, à manœuvre instantanée et commande biphasée

Tableau 12- 6 Tension assignée d'emploi Ue 48 ... 480 V

3RF3405-1BB04

3RF3410-1BB04

3RF3412-1BB04

3RF3416-1BB04

Type de raccordement Bornes à vis Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 7 Tension assignée d'emploi Ue 48 ... 480 V

3RF3405-1BB24

3RF3410-1BB24

3RF3412-1BB24

3RF3416-1BB24

Type de raccordement Bornes à vis Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 110 ... 230 V CA Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 8 Tension assignée d'emploi Ue 48 ... 600 V, tension de blocage 1600 V

3RF3405-1BB06

3RF3410-1BB06

3RF3412-1BB06

3RF3416-1BB06

Type de raccordement Bornes à vis Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 9 Tension assignée d'emploi Ue 48 ... 600 V, tension de blocage 1600 V

3RF3405-1BB26

3RF3410-1BB26

3RF3412-1BB26

3RF3416-1BB26

Type de raccordement Bornes à vis Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 110 ... 230 V CA Poids environ kg 0,250 0,380 0,380 0,380

Caractéristiques techniques 12.5 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à ressort

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 64 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.5 Contacteurs à semiconducteurs 3RF34, triphasés, bornes à ressort

Contacteurs à semiconducteurs, à manœuvre instantanée et commande biphasée

Tableau 12- 10 Tension assignée d'emploi Ue 48 ... 480 V

3RF3405-2BB04

3RF3410-2BB04

3RF3412-2BB04

3RF3416-2BB04

Type de raccordement Bornes à ressort Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 11 Tension assignée d'emploi Ue 48 ... 480 V

3RF3405-2BB24

3RF3410-2BB24

3RF3412-2BB24

3RF3416-2BB24

Type de raccordement Bornes à ressort Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 110 ... 230 V CA Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 12 Tension assignée d'emploi Ue 48 ... 600 V, tension de blocage 1600 V

3RF3405-2BB06

3RF3410-2BB06

3RF3412-2BB06

3RF3416-2BB06

Type de raccordement Bornes à ressort Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 Poids environ kg 0,250 0,380 0,380 0,380

Tableau 12- 13 Tension assignée d'emploi Ue 48 ... 600 V, tension de blocage 1600 V

3RF3405-2BB26

3RF3410-2BB26

3RF3412-2BB26

3RF3416-2BB26

Type de raccordement Bornes à ressort Courant assigné d'emploi Ie A 5,2 9,2 12,5 16 Puissance assignée pour Ie et Ue 400 V kW 2,2 4,0 5,5 7,5 Tension assignée d'alimentation de commande Us V 110 ... 230 V CA Poids environ kg 0,250 0,380 0,380 0,380

Caractéristiques techniques 12.6 Contacteurs à semiconducteurs - Montage sans fusibles avec disjoncteur CLASS 10

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 65

Voir aussi Pour plus d'informations... reportez-vous au chapitre... sur les techniques de raccordement et le repérage des bornes de raccordement

Raccordement (Page 49)

pour le déclassement du courant d'emploi en fonction des courants de démarrage élevés.

Environnement d'utilisation (Page 18)

12.6 Contacteurs à semiconducteurs - Montage sans fusibles avec disjoncteur CLASS 10

Montage sans fusibles avec disjoncteur CLASS 10

Tableau 12- 14 Circuit principal

Nº de référence 3RF3405-.BB.. 3RF3410-.BB.. 3RF3412-.BB.. 3RF3416-.BB.. Courant assigné d'emploi IAC-53 1) selon CEI 60947-4-2 à 40 °C A 5,2 (4,5) 2) 9,2 12,5 16 à 50°C A 4,6 (4,0) 2) 8,4 11,5 14 à 60 °C A 4,2 (3,5) 2 7,6 10,5 12,5 Puissance dissipée pour IAC-53 à 40 °C

W 10 (8) 2) 16 22 28

Protection contre les courts-circuits avec type de coordination "1" à la tension d'emploi Ue jusqu'à 440 V Disjoncteurs Type 3RV2011-1GA10 3RV2011-1JA10 3RV2011-1KA10 3RV2011-4AA10 Iq kA 50 5 5 3 1) Use overvoltage protection device; max cut-off-voltage 6000 V; min energy handling capability 100 J

2) Les valeurs réduites entre parenthèses sont valables pour un disjoncteur monté directement avec un montage accolé.

Caractéristiques techniques 12.7 Contacteurs à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 66 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.7 Contacteurs à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30

Montage avec fusibles et relais de surcharge 3RB30 monté directement

Tableau 12- 15 Circuit principal

Nº de référence 3RF3405-.BB.4 3RF3405-.BB.6 3RF3410-.BB.. Courant assigné d'emploi IAC-53 1) selon CEI 60947-4-2 à 40 °C A 4 (3,5) 2) 4 (3,5) 2) 7,8 UL/CSA à 50 °C A 3,6 (3,2) 2) 3,6 (3,2) 2) 7 à 60 °C A 3,2 (2,9) 2 3,2 (2,9) 2 6,2 Puissance dissipée pour IAC-53 à 40 °C W 7 (6) 2) 7 (6) 2) 13 Courant de charge minimal A 0,1 0,5 0,5 Courant de fuite maxi mA 10 10 10 Valeur de crête assignée admissible du courant Itsm

A 200 600 600

Valeur I2t A2s 200 1800 1800

Tableau 12- 16 Circuit principal

Nº de référence 3RF3412-.BB.4 3RF3412-.BB.6 3RF3416-.BB.. Courant assigné d'emploi IAC-53 1) selon CEI 60947-4-2 à 40 °C A 9,5 9,5 11 UL/CSA à 50 °C A 8,5 8,5 10 à 60 °C A 7,6 7,6 9 Puissance dissipée pour IAC-53 à 40 °C W 16 16 18 Courant de charge minimal A 0,5 0,5 0,5 Courant de fuite maxi mA 10 10 10 Valeur de crête assignée admissible du courant Itsm

A 1200 1150 1150

Valeur I2t A2s 7200 6600 6600 1) Use overvoltage protection device; max cut-off-voltage 6000 V; min energy handling capability 100 J

2) Les valeurs réduites entre parenthèses sont valables pour un disjoncteur monté directement avec un montage accolé.

Caractéristiques techniques 12.8 Contacteurs à semiconducteurs, circuit principal et commande biphasée

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 67

12.8 Contacteurs à semiconducteurs, circuit principal et commande biphasée

Contacteur à semiconducteurs, commande biphasée

Tableau 12- 17 Circuit principal

Nº de référence 3RF34..- BB.4 3RF34..- BB.6 Phases commandées biphasé biphasé Tension assignée d'emploi Ue Plage de travail V 40 ... 506 40 ... 660 Fréquence assignée Hz 50 / 60 ± 10 % 50 / 60 ± 10 % Tension assignée d'isolement Us V 600 600 Tension assignée de tenue aux chocs Uimp kV 6 6 Tension de blocage V 1200 1600 Vitesse de croissance de la tension V/μs 1000 1000

12.9 Contacteurs à semiconducteurs avec circuit de commande

Contacteur à semiconducteurs avec circuit de commande

Tableau 12- 18 Circuit de commande A1 - A2

Nº de référence 3RF34..- BB0. 3RF34..- BB2. Type de commande Commande CC Commande CA Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 110 ... 230 V CA Tension assignée d'alimentation de commande maxi Us

V 30 V CC 253 V CA

Fréquence assignée de la tension d'alimentation de commande

Hz — 50 / 60 ± 10 %

Courant de commande normal mA 20 15 Tension d'appel V 15 90 Tension de retombée V 5 < 40 Temps de manœuvre

• Retard à la fermeture ms 1 5

• Retard à la coupure ms 1 + une demi-onde maxi 30 + une demi-onde maxi

Caractéristiques techniques 12.10 Contacteur-inverseur à semiconducteurs avec intégration de quatre circuits en un schéma inverseur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 68 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.10 Contacteur-inverseur à semiconducteurs avec intégration de quatre circuits en un schéma inverseur

Contacteur-inverseur à semiconducteurs, à manœuvre instantanée, commande biphasée et bornes à vis

Tableau 12- 19 Tension assignée d'emploi Ue 48 ... 480 V

Nº de référence 3RF34 03-1BD04 3RF34 05-1BD04 3RF34 10-1BD04 Courant assigné d'emploi Ie A 3,8 5,4 7,4 Puissance assignée pour Ie et Ue 400 V kW 1,5 2,2 3,0 Tension assignée d'alimentation de commande Us

V 24 V CC selon EN 61131-2

Poids par PE, environ kg 0,280 0,280 0,410

Tableau 12- 20 Tension assignée d'emploi Ue 48 ... 480 V

Nº de référence 3RF34 03-1BD24 3RF34 05-1BD24 3RF34 10-1BD24 Courant assigné d'emploi Ie A 3,8 5,4 7,4 Puissance assignée pour Ie et Ue 400 V kW 1,5 2,2 3,0 Tension assignée d'alimentation de commande Us

V 110 ... 230 V CA

Poids par PE, environ kg 0,280 0,280 0,410

Voir aussi Pour plus d'informations... reportez-vous au chapitre... pour le déclassement du courant d'emploi en fonction des courants de démarrage élevés.

Environnement d'utilisation (Page 18)

Caractéristiques techniques 12.11 Contacteur-inverseur - montage sans fusibles avec disjoncteur CLASS 10

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 69

12.11 Contacteur-inverseur - montage sans fusibles avec disjoncteur CLASS 10

Montage sans fusibles avec disjoncteur CLASS 10

Tableau 12- 21 Circuit principal

Nº de référence 3RF34 03-.BD.4 3RF34 05-.BD.4 3RF34 10-.BD.4 Courant assigné d'emploi IAC-531) selon CEI 60947-4-2 à 40 °C A 3,8 (3,4) 5,4 (4,8) 7,4 UL/CSA à 50 °C A 3,5 (3,1) 5 (4,3) 6,8 à 60 °C A 3,2 (2,8) 4,6 (3,8) 6,2 Puissance dissipée pour IAC-53 à 40 °C W 7 (6) 9 (8) 13 Protection contre les courts-circuits avec type de coordination "1" à la tension d'emploi Ue jusqu'à 440 V Disjoncteurs Type 3RV20 11-1FA10 3RV20 11-1GA10 3RV20 11-1JA10 Iq kA 50 50 10 1) Les valeurs réduites entre parenthèses sont valables pour un disjoncteur monté directement avec un montage accolé.

2) Pour réduire le risque de court-circuit entre phases par surtension, il est recommandé de raccorder une varistance de type 3TX7 462-3L entre L1 et L3, autant que possible à proximité de l'appareil de connexion. Une réalisation avec protection des semiconducteurs protègera contre les courts-circuits.

Caractéristiques techniques 12.12 Contacteur-inverseur à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 70 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.12 Contacteur-inverseur à semiconducteurs - montage avec fusibles et relais de surcharge 3RB30

Montage avec fusibles et relais de surcharge 3RB30 monté directement

Tableau 12- 22 Circuit principal

Nº de référence 3RF34 03-.BD.4 3RF34 05-.BD.4 3RF34 10-.BD.4 Courant assigné d'emploi IAC-531) selon CEI 60947-4-2 à 40 °C A 3,8 (3,4) 5,4 (4,8) 7,4 UL/CSA à 50 °C A 3,5 (3,1) 5 (4,3) 6,8 à 60 °C A 3,2 (2,8) 4,6 (3,8) 6,2 Puissance dissipée pour IAC-53 à 40 °C W 7 (6) 9 (8) 13 Courant de charge minimal A 0,5 0,5 0,5 Courant de fuite maxi mA 10 10 10 Valeur de crête assignée admissible du courant Itsm

A 600 600 600

Valeur I2t A2s 1800 1800 1800 1) Les valeurs réduites entre parenthèses sont valables pour un disjoncteur monté directement avec un montage accolé.

2) Pour réduire le risque de court-circuit entre phases par surtension, il est recommandé de raccorder une varistance de type 3TX7 462-3L entre L1 et L3, autant que possible à proximité de l'appareil de connexion. Une réalisation avec protection des semiconducteurs protègera contre les courts-circuits.

12.13 Contacteur-inverseur à semiconducteurs, circuit principal et commande biphasée

Contacteur-inverseur à semiconducteurs, commande biphasée

Tableau 12- 23 Circuit principal

Nº de référence 3RF34..- BD.4 Phases commandées biphasé Tension assignée d'emploi Plage de travail Ue V 40 ... 506 Fréquence assignée Hz 50 / 60 ± 10 % Tension assignée d'isolement Us V 600 Tension assignée de tenue aux chocs Uimp kV 6 Tension de blocage V 1200 Vitesse de croissance de la tension V/μs 1000

Caractéristiques techniques 12.14 Contacteur-inverseur à semiconducteurs avec circuit de commande

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 71

12.14 Contacteur-inverseur à semiconducteurs avec circuit de commande

Contacteur-inverseur à semiconducteurs avec circuit de commande

Tableau 12- 24 Circuit de commande A1 - A2

Nº de référence 3RF34..- BD0. 3RF34..- BD2. Type de commande Commande CC Commande CA Tension assignée d'alimentation de commande Us V 24 V CC selon EN 61131-2 110 ... 230 V CA Tension assignée d'alimentation de commande maxi Us

V 30 V CC 253 V CA

Fréquence assignée de la tension d'alimentation de commande

Hz — 50 / 60 ± 10 %

Courant de commande normal mA 20 15 Tension d'appel V 15 90 Tension de retombée V 5 < 40 Temps de manœuvre

• Retard à la fermeture ms 5 20

• Retard à la coupure ms 5 + une demi-onde maxi 10 + une demi-onde maxi

• Temps de verrouillage ms 60 - 100 50 - 100

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 72 Manuel, 08/2014, A5E03656507230A/RS-AA/002

12.15 Courbes - fréquence de manœuvre / charge

12.15.1 Courbes caractéristiques pour le contacteur à semiconducteurs

Courbe de la fréquence de manœuvre pour le contacteur à semiconducteurs Données de fonctionnement du moteur

Ia Courant de démarrage direct du moteur Ie Courant assigné d'emploi du moteur Ib Courant d'emploi du moteur ta Temps de démarrage du moteur tb Temps de fonctionnement tp Temps de pause tFM Facteur de marche ts Cycle de manœuvre

Figure 12-1 Courbes de la fréquence de manœuvre - diagramme de charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 73

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-2 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est 4 à 7,2 fois celle du courant assigné et à pleine charge 1)

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 74 Manuel, 08/2014, A5E03656507230A/RS-AA/002

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-3 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est 4 à 7,2 fois celle du courant assigné et 60 % de charge 1)

1) Les lignes en pointillEs valent pour les courants de forte intensité en fonctionnement avec disjoncteur !

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 75

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-4 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est jusqu'à 4 fois celle du courant assigné et à pleine charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 76 Manuel, 08/2014, A5E03656507230A/RS-AA/002

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-5 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est jusqu'à 4 fois celle du courant assigné et 60 % de charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 77

12.15.2 Courbes caractéristiques pour le contacteur-inverseur à semiconducteurs

Courbe de la fréquence de manœuvre pour le contacteur-inverseur à semiconducteurs Données de fonctionnement du moteur

Ia Courant de démarrage direct Ie Courant assigné d'emploi Ib Courant d'emploi ta Temps de démarrage ta Temps de fonctionnement tp Temps de pause tFM Facteur de marche ts Cycle de manœuvre

Figure 12-6 Courbes de la fréquence de manœuvre - diagramme de charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 78 Manuel, 08/2014, A5E03656507230A/RS-AA/002

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-7 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est 4 à 7,2 fois celle du courant assigné et à pleine charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 79

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-8 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est 4 à 7,2 fois celle du courant assigné et 60 % de charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 80 Manuel, 08/2014, A5E03656507230A/RS-AA/002

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-9 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est jusqu'à 4 fois celle du courant assigné et à pleine charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 81

1 ta = 0,05 s 2 ta = 0,1 s 3 ta = 0,2 s 4 ta = 0,4 s 5 ta = 0,8 s 6 ta = 1,6 s 7 ta = 3,2 s

Figure 12-10 Fréquence de manœuvre maximale admissible z en fonction du temps de démarrage ta et du facteur de marche tFM pour moteurs avec un courant de démarrage dont l'intensité est jusqu'à 4 fois celle du courant assigné et à 60 % de charge

Caractéristiques techniques 12.15 Courbes - fréquence de manœuvre / charge

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 82 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 83

Schémas électriques 13

Schémas des appareils Vous trouverez les schémas des Innovations SIRIUS sur Internet dans la banque d'images (www.siemens.com/industrial-controls/bilddb).

Pour cela, tapez le numéro de référence de l'appareil dans le champ "Order number" et sélectionnez le type d'objet "Circuit diagram" dans la liste déroulante.

Figure 13-1 Banque d'images

Schémas électriques

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 84 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Appareils à semiconducteurs 3RF34 3RF34..-.BB2.

Figure 13-2 Contacteur à semiconducteurs, triphasé, tension de commande CA

3RF34..-.BD2.

Figure 13-3 Contacteur-inverseur à semiconducteurs, triphasé, tension de commande CA

3RF34..-.BB0.

Figure 13-4 Contacteur à semiconducteurs, triphasé, tension de commande CC

3RF34..-.BD0.

Figure 13-5 Contacteur-inverseur à semiconducteurs, triphasé, tension de commande CC

Schémas électriques

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 85

Exemples de schéma électrique Les figures ci-après montrent des exemples de schéma électrique pour les contacteurs à semiconducteurs et les contacteurs-inverseurs à semiconducteurs.

Exemple de schéma électrique pour le contacteur moteur à semiconducteurs

F1 - 3 Fusibles du circuit principal (spéciaux pour protection de semiconducteurs recommandés) F4 Fusible du circuit de commande Q1 Contacteur moteur à semiconducteurs 3RF34 M1 Moteur R1 Varistance 3TX7 462-3L (recommandée pour obtenir l'immunité "Ondes de choc" !) S1 Commutateur "Marche"

Figure 13-6 Exemple de schéma électrique : départ moteur avec fusibles et contacteur moteur à semiconducteurs avec circuit de commande CC

Schémas électriques

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 86 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Exemple de schéma électrique pour le contacteur-inverseur à semiconducteurs

F1 - 3 Fusibles du circuit principal (spéciaux pour protection de semiconducteurs recommandés) F4 Fusible du circuit de commande Q1 Contacteur-inverseur à semiconducteurs 3RF34 M1 Moteur R1 Varistance 3TX7 462-3L (recommandée pour obtenir l'immunité "Ondes de choc" !) S1 Commutateur "Gauche" : S2 Commutateur "Droite"

Figure 13-7 Exemple de schéma électrique : départ moteur avec fusibles et contacteur-inverseur à semiconducteurs avec circuit de commande CA

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 87

Types de coordination A

Types de coordination La norme EN 60947-4-1 (VDE 0660 partie 102) ou CEI 60947-4-1 distingue deux types de coordination (type of coordination), désignés par type de coordination "1" et type de coordination "2". Le court-circuit est maîtrisé de manière sûre avec ces deux types de coordination. Les seules différences concernent le degré d'endommagement de l'appareil après un court-circuit.

Type de coordination 1 Après une coupure en court-circuit, il est admis que le départ-moteur ne puisse plus fonctionner. La détérioration du contacteur et du déclencheur de surcharge est admissible.

Type de coordination 2 Aucune détérioration du déclencheur de surcharge ni d'un autre constituant ne doit se présenter après une coupure sur court-circuit. Le départ-moteur peut être remis en service sans remplacement de pièces. Seule la soudure des contacts du contacteur est admissible s'il est possible de les séparer facilement sans déformation notable.

Types de coordination

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 88 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 89

Bibliographie B B.1 Littérature

Informations complémentaires Vous trouverez des informations complémentaires sur les appareils à semiconducteurs 3RF34 sur Internet (http://support.automation.siemens.com/WW/view/fr/20368269/133300).

Veuillez observer en complément de ce manuel les instructions de service et les manuels des accessoires. Vous pouvez télécharger la documentation correspondante depuis Internet (www.siemens.com/industrial-controls/manuals). Pour cela, introduisez le numéro de référence de la documentation en question dans le champ de recherche.

Instructions de service Titre Numéro de référence Contacteurs / contacteurs-inverseurs à semiconducteurs SIRIUS (3RF34..-.BB.. et 3RF34..-.BD..)

3ZX1012-0RF34-2AA1

Bibliographie B.2 Manuels des Innovations SIRIUS

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 90 Manuel, 08/2014, A5E03656507230A/RS-AA/002

B.2 Manuels des Innovations SIRIUS

Manuels des Innovations SIRIUS Vous pouvez télécharger les manuels des Innovations SIRIUS sur Internet (www.siemens.com/industrial-controls/manuals).

Pour cela, introduisez le numéro de référence de la documentation en question dans le champ de recherche.

Pour trouver des informations sur... reportez-vous au...

• Innovations SIRIUS - Vue d'ensemble du système

• Manuel "Innovations SIRIUS - Vue d'ensemble du système" (numéro de référence : 3ZX1012-0RA01-5AB1)

• Contacteurs et associations de contacteurs 3RT2, 3RH2 et 3RA23 / 24

• Manuel "Innovations SIRIUS - Contacteurs / associations de contacteurs SIRIUS 3RT2" (numéro de référence : 3ZX1012-0RT20-5AB1)

• Appareils à semiconducteurs 3RF34 • Manuel "Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34" (numéro de référence : 3ZX1012-0RF34-5AB1)

• Démarreurs progressifs 3RW • Manuel "Démarreurs progressifs SIRIUS 3RW30 / 3RW40" (http://support.automation.siemens.com/WW/view/en/38752095) (numéro de référence : 3ZX1012-0RW30-1AC1)

• Manuel "Démarreurs progressifs SIRIUS 3RW44" (http://support.automation.siemens.com/WW/view/fr/21772518) (numéro de référence : 3ZX1012-0RW44-1AD1)

• Disjoncteurs 3RV2 • Manuel "Innovations SIRIUS - Disjoncteurs SIRIUS 3RV2" (numéro de référence : 3ZX1012-0RV20-5AB1)

• Relais de surcharge 3RU2, 3RB30 / 31 • Manuel "Innovations SIRIUS - Relais de surcharge SIRIUS 3RU2 / 3RB3" (numéro de référence : 3ZX1012-0RU20-5AB1)

• Relais de surcharge électronique 3RB24 • Manuel "Relais de surcharge électronique 3RB24 pour IO-Link" (numéro de référence : 3ZX1012-0RB24-0AB0)

• Relais de surveillance 3UG4 / relais de surveillance de courant 3RR2

• Manuel "Relais de surveillance 3UG4 / 3RR2" (numéro de référence : 3ZX1012-0UG40-0AB0)

• Relais de surveillance de température 3RS1 / 3RS2

• Manuel "Relais de surveillance de température 3RS1 / 3RS2" (numéro de référence : 3ZX1012-0RS10-1AB1)

Bibliographie B.2 Manuels des Innovations SIRIUS

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 91

Pour trouver des informations sur... reportez-vous au...

• Relais de surveillance 3UG48 • Manuel "Relais de surveillance 3UG48 pour IO-Link" (numéro de référence : 3ZX1012-0UG48-0AB1)

• Relais de surveillance de température 3RS14 / 3RS15

• Manuel "Relais de surveillance de température 3RS14 / 3RS15 pour IO-Link" (numéro de référence : 3ZX1012-0RS14-0AB0)

• Départs-moteur 3RA21 / 22 • Manuel "Innovations SIRIUS - Départs-moteur SIRIUS 3RA21 / 3RA22" (numéro de référence : 3ZX1012-0RA21-5AB1)

• Départs-moteur compacts 3RA6 • Manuel "Départ-moteur compact SIRIUS 3RA6" (http://support.automation.siemens.com/WW/view/fr/27865747) (numéro de référence : 3RA6991-0A)

• Modules fonctionnels 3RA28 pour montage sur contacteurs

• Manuel "Innovations SIRIUS - Modules fonctionnels SIRIUS 3RA28 pour montage sur contacteurs 3RT2" (numéro de référence : 3ZX1012-0RA28-5AB1)

• Modules fonctionnels 3RA27 pour intégration à l'automatisme

• Manuel "Modules fonctionnels pour AS-Interface" (http://support.automation.siemens.com/WW/view/fr/39318922) (numéro de référence : 3ZX1012-0RA27-0AD0)

• Manuel "Modules fonctionnels pour IO-Link" (http://support.automation.siemens.com/WW/view/fr/39319600) (numéro de référence : 3ZX1012-0RA27-1AD1)

• Module électronique 4SI SIRIUS (3RK1005-0LB00-0AA0)

• Manuel "Module électronique 4SI SIRIUS (3RK1005-0LB00-0AA0)" (numéro de référence :3ZX1012-0LB00-0AA0)

Bibliographie B.3 Informations complémentaires

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 92 Manuel, 08/2014, A5E03656507230A/RS-AA/002

B.3 Informations complémentaires

Informations complémentaires Siemens met des informations complémentaires à votre disposition sur Internet sous les liens suivants.

● Documentation produit Vous trouverez la liste des manuels / instructions de service, caractéristiques et certificats disponibles pour les produits sur Internet (www.siemens.com/industrial-controls/support).

● Information produit Vous trouverez des catalogues et des brochures informatives dans notre Centre d'information et de téléchargement (www.siemens.com/industrial-controls/infomaterial).

● Système de commande en ligne Vous trouverez le système de commande en ligne avec les données les plus récentes sur notre Plateforme d'informations et de commande (www.siemens.com/industrial-controls/mall).

● Support technique Siemens répond à toutes vos demandes de renseignement techniques sur des produits et des systèmes, avant comme après la livraison. Vous pouvez contacter le portail Service & Support sur Internet (www.siemens.com/industrial-controls/technical-assistance). Vous pouvez aussi poser votre question directement à un conseiller en envoyant une demande de support.

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 93

Croquis cotés (cotes en mm) C

Remarque

Toutes les cotes sont données en mm.

C.1 Appareils à semiconducteurs

Contacteur à semiconducteurs

Figure C-1 Contacteur à semiconducteurs

Contacteur-inverseur à semiconducteurs

Figure C-2 Contacteur-inverseur à semiconducteurs

Croquis cotés (cotes en mm) C.2 Bloc de connexion au disjoncteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 94 Manuel, 08/2014, A5E03656507230A/RS-AA/002

C.2 Bloc de connexion au disjoncteur

Accessoires

Bloc de connexion 3RA2921-1BA00 au disjoncteur 3RV20

Figure C-3 Bloc de connexion au disjoncteur

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 95

Formulaire de correction D

Formulaire de correction Avez-vous trouvé des erreurs en lisant ce manuel ? Nous vous remercions de bien vouloir nous faire part de ces erreurs dans le formulaire ci-joint. Nous vous remercions également de toute suggestion ou proposition d'amélioration.

Fax-réponse Expéditeur (prière de remplir) : Destinataire : SIEMENS AG I IA CE MK&ST 3 D-92220 Amberg

Name Société / service Adresse

_________________________________________________________________________________

Fax : +49 (0)9621-80-3337

Titre du manuel :

Tableau D- 1 Erreurs, suggestions ou propositions d'amélioration

Formulaire de correction

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 96 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 Manuel, 08/2014, A5E03656507230A/RS-AA/002 97

Index

A Accessoires

Appareils à semiconducteurs, 55 Accessoires - appareils à semiconducteurs

Arrêt d'isolation, 55 Bloc de connexion au disjoncteur, 56, 57

Appareils à semiconducteurs Manœuvre instantanée, 15, 16, 44

Arrêt d'isolation Appareils à semiconducteurs, 55

Assistance technique, 10 Avantages

Appareils à semiconducteurs, 24

B Bibliographie, 89 Bloc de connexion au disjoncteur

Appareils à semiconducteurs, 56, 57

C Champs d'application

Appareils à semiconducteurs, 17 Charge inductive

Appareils à semiconducteurs, 44 Choix

Appareils à semiconducteurs, 29 Choix à l'aide d'un outil - paramètres

Appareils à semiconducteurs, 32, 33 Commande

Contacteur à semiconducteurs, 28 Contacteur-inverseur à semiconducteurs, 28

Configurateur de système pour Innovations SIRIUS, 30 Connaissances de base, 9 Connectique

Appareils à semiconducteurs, 16, 49 Consignes de sécurité

Appareils à semiconducteurs, 11 Contacteurs à semiconducteurs, 15, 16, 17, 57 Contacteurs-inverseurs à semiconducteurs, 15, 16, 17, 57 Corrections, 10 Courant de court-circuit

Appareils à semiconducteurs, 39

Courbes - fréquence de manœuvre / charge Contacteur à semiconducteurs, 72 Contacteur-inverseur à semiconducteurs, 77

D Déarts-moteur

Appareils à semiconducteurs, 43 Démarrage direct

Appareils à semiconducteurs, 31 Démarrage-inversion

Appareils à semiconducteurs, 31 Départs-moteur

Appareils à semiconducteurs, 29 Dimensionnement du moteur

Appareils à semiconducteurs, 30 Domaine de validité

Manuel, 9 Durée de vie

Appareils à semiconducteurs, 28

E Ecartement minimal

Appareils à semiconducteurs, 45 Equipement

Contacteur à semiconducteurs, 19 Contacteur-inverseur à semiconducteurs, 20

Exemples de schéma électrique Appareils à semiconducteurs, 85, 85, 86

F Fixation par encliquetage

Appareils à semiconducteurs, 45, 47 Fixation par vis

Appareils à semiconducteurs, 45, 47 Formulaire de correction, 95 Fusibles

Appareils à semiconducteurs, 38 Fusibles de protection des semiconducteurs SITOR

Appareils à semiconducteurs, 40, 43

I Innovations, 90

Index

Innovations SIRIUS - Appareils à semiconducteurs SIRIUS 3RF34 98 Manuel, 08/2014, A5E03656507230A/RS-AA/002

Installation photovoltaïque Appareils à semiconducteurs, 44

Instructions de service, 89 Intégrale de destruction

Appareils à semiconducteurs, 27

M Manœuvre

Charge de moteur, 44 Charge moteur, 15, 17, 30 Charge ohmique, 15

Modèles d'appareils Appareils à semiconducteurs, 15

N Normes

Appareils à semiconducteurs, 13

O Outil

Choix des appareils à semiconducteurs, 30, 32, 33

P Perturbations CEM

Appareils à semiconducteurs, 43 Position de montage

Appareils à semiconducteurs, 46 Protection contre les courts-circuits

Appareils à semiconducteurs, 34 Contacteur à semiconducteurs, 34, 35 Contacteur-inverseur à semiconducteurs, 36, 37

R Raccordement par bornes à ressort, 52 Raccordement par bornes à vis, 51 Recyclage, 9, 9 Repérage des bornes

Contacteur à semiconducteurs, 50 Contacteur-inverseur à semiconducteurs, 50

S Schémas des appareils, 83, 83

Appareils à semiconducteurs, 84

Sections de raccordement, 51 Sélection à l'aide d'un outil

Appareils à semiconducteurs, 30

T Température ambiante

Appareils à semiconducteurs, 18 Tension de blocage

Appareils à semiconducteurs, 27 Types de coordination, 87

U UL

Appareils à semiconducteurs, 38, 40

Siemens AGIndustry SectorPostfach 23 5590713 FUERTHALLEMAGNE

Sous réserve de modifications 3ZX1012-0RF34-5AD1

© Siemens AG 2011

Service après-vente & AssistanceTélécharger simplement les catalogues et le matériel d‘information :www.siemens.com/sirius/infomaterial

Newsletter - toujours au courant :www.siemens.com/sirius/newsletter

e-business dans la galerie marchande Industry Mall :www.siemens.com/sirius/mall

Assistance en ligne :www.siemens.com/sirius/support

Pour des questions techniques, adressez-vous à :Technical AssistanceTel.: +49 (911) 895-5900Courriel : [email protected]/sirius/technical-assistance

Industrial ControlsSIRIUS

www.siemens.com/automation