massachusetts water resources authority - mwra - … 87 linear feet of 16-inch-diameter, cast-iron...

46

Upload: doantuyen

Post on 11-Jun-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress
Page 2: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Page 3: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

0

2

4

6

8

10

12

14

0

100

200

300

400

500

600

700

800

J A S O N D J F M A M J

Inches (Water E

quivalent) M

GD

Plant Flow & Precipitation

Total Plant Flow, MGD 12 Yr Avg Flow, MGD Total Precipitation, inches rain 12 Yr Avg Precipitation, inches rain

Deer Island Operations

3

Page 4: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Deer Island Yearly Maintenance Metrics

4

0.0

5.0

10.0

15.0

20.0

FY04

FY05

FY06

FY07

FY08

FY09

FY10

FY11

FY12

FY13

FY14

Rep

lace

men

t Ass

et V

alue

in M

illio

ns S

/Tec

hnic

ian

Replacement Asset Value / Maintenance Technician

Best in Class Target = $8 to $10 Million

Page 5: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Water Distribution System Pipelines

0

50

100

150

200

250

300

J A S O N D J F M A M J

Miles Surveyed for Leaks

Monthly Cumulative Target

Page 6: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

0

250

500

750

1000

1250

1500

July August September October November December January February March April May June

# of

val

ves

Main Line Valves Exercised

Target = 92 valves monthly or 1,100 annually

Water Distribution System Valves

6

Type of Valve Inventory

#

Operable Percentage

FY14 to Date FY14 Targets Main Line Valves 2,092 97.7% 95%

Blow-Off Valves 1,206 95.1% 95% Air Release Valves 1,335 93.1% 95%

Control Valves 48 100.0% 95%

Page 7: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

0

20

40

60

80

100

120

J A S O N D J F M A M J

# of

Sip

hon

Bar

rels

Inverted Siphon Cleaning

Monthly Cleaning

YTD Actual

Target = 3 monthly or 36 / 33% of the system annually

Wastewater Pipeline and Structure Inspections and Maintenance

7

0

5

10

15

20

25

30

35

40

J A S O N D J F M A M J M

iles

Pipeline Cleaning

Hydraulic Cleaning Mechanical Cleaning

YTD Actual

Target = 3 miles monthly or 36 miles annually

Page 8: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Renewable Energy at MWRA

8

J A S O N D J F M A M J

Savi

ngs

and

Rev

enue

, $

Savings and Revenue Totals for Renewable Energy Production, FY14

Solar Wind Hydro Steam

J A S O N D J F M A M J

Ren

ewab

le E

nerg

y C

ertif

icat

es V

alue

, $ Renewable Energy Certificates (RECs) Values, FY14

Steam Hydro Wind Solar

Page 9: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Workforce Management

9

1150

1170

1190

1210

1230

1250

J A S O N D J F M A M J

Filled Position Tracking

Target Filled

Pr/Trns Hires Total

FY11 48 (62%) 30 (38%) 78

FY12 42 (61%) 27 (39%) 69

FY13 82 (64%) 47 (36%) 129

FY14 111 (69%) 51 (31%) 162

69% 31%

Positions Filled by Hires/Promotions FY14-YTD

Promotions / Transfers (111)

Hires (51)

Page 10: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress
Page 11: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Presentation to the

Board of Directors

Existing and Future Combined Heat and Power (CHP)

at DITP

September 17, 2014

Massachusetts Water Resources Authority

Page 12: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

130,000,000  

135,000,000  

140,000,000  

145,000,000  

150,000,000  

155,000,000  

160,000,000  

165,000,000  

170,000,000  

175,000,000  

FY03   FY04   FY05   FY06   FY07   FY08   FY09   FY10   FY11   FY12   FY13   FY14  

Total  DITP  Annual  Power  Demand,  kWh  

DITP – A Significant Energy User

12

Staff efforts have helped reduced plant electrical demand by 10% •  Process Optimization •  Installation of new energy efficient equipment

Page 13: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

DITP – Green Energy Production (FY14)

13

Maximizing On-Site Green Energy Production is a priority for MWRA •  23% of DITP’s total electricity demand met by green energy

•  60% of DITP’s energy needs (heat + power) met by Digester Gas (62.5% for all)

Generation Assets:

• Digas – STG/BPSTG – 25.1 M kWh – 17.4%

• Hydro Power – 5.89 M kWh – 4.1%

• Wind Power – 1.48 M kWh – 1.0%

• Solar – 0.86 M kWh – 0.6%

0  

5,000,000  

10,000,000  

15,000,000  

20,000,000  

25,000,000  

30,000,000  

35,000,000  

40,000,000  

FY03   FY04   FY05   FY06   FY07   FY08   FY09   FY10   FY11   FY12   FY13   FY14  

Total  On-­‐Site  Renewable  Electrical  Energy  Produc@on,  kWh  

Renewable  energy  from  Digas   Renewable  Energy  from  other  sources  

Page 14: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

•  Anaerobic Digestion: –  240 dtpd solid in, 100 dtpd to FRSA for pellet conversion –  Digas generated on average is 60% methane

•  OSTPP: Bottom-Cycle Generation –  Digas – 95% utilized –  95% of heat demand met by Digas ($17.6 million annually) (remainder by Fuel Oil) –  25.1 M kWh generation from Steam Turbine ($2.4 million annually)

DITP – Digester Gas Generation & Use (FY14)

14

On-site Thermal Power Plant

Anaerobic Digester Complex Digas Generation

Page 15: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

•  Bottom Cycle Generation –  Heat First – 60% efficient

•  Generate Steam then Hot Water

–  Power Second – 9% efficient •  Generate Electricity from Steam

•  New BPSTG / Steam Bypass Valve improves steam to electricity conversion process by extracting more heat per unit steam

Combined Heat & Power Process – Currently Used by DITP

15

Page 16: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

•  New BPSTG / Steam Bypass Valve improve steam to electricity conversion process

–  18% improvement (10.6% efficiency overall) –  +1.3 MW increase in generation from steam generators –  Sustainable May - November –  Should see an increase of +4.5 M kWh / year –  ~30 M kWh total/year from steam (25.1 M kWh currently)

Combined Heat & Power Process – Improved Performance

16

y  =  0.0706x  -­‐  0.6165   R²  =  0.97744   y  =  0.0729x  -­‐  1.9051   R²  =  0.99959  

1.5  

2.0  

2.5  

3.0  

3.5  

4.0  

4.5  

5.0  

50.0   55.0   60.0   65.0   70.0   75.0   80.0   85.0   90.0  

STG  Pow

er  Outpu

t  (M

W)  

STG  Power  Output  vs.  Steam  Flow  (STG  Boiler  101  with  BP-­‐STG)  

OperaKng  in  a  vacuum   Not  operaKng  in  a  vacuum  

Steam  Flow  (KLB/HR)  

Page 17: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

17

•  Develop engineering and economics for new CHP

•  Compare and recommend more efficient generation technologies

•  Internal Combustion Engines

•  Gas Turbines

•  Develop Simple Payback Analysis / Economic benefits

•  Evaluate implementation options

CHP Study Objectives – CDM Smith Residuals Technology Assessment

Page 18: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Internal Combustion Engines versus Gas Turbines

18

•  Exhaust emissions (NOx, CO) – GT ↓ •  Space required (Capacity) – GT ↓ •  Capital and operating costs – GT ↓ •  Energy efficiency (Electricity and Heat) ↔ •  Flexibility – GT ↑

Page 19: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

CHP Technology Change

19

CHP Benefit from Co Digestion •  Expected 29-42% increase in biogas •  Results in more electrical output •  Heat demand increase 5-10% •  Electrical demand increase <2%

CHP Technology Change •  Change from Bottom to Top cycle generation •  Improve efficiency •  Increased electrical production •  Better use of all digas - summer months •  Continue to meet plant heating needs

Page 20: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Cost Benefit Analysis – Simple Payback

20

Parameter OSTPP with

1 Gas Turbine*

OSTPP with 1 Gas Turbine*

With Co-digestion

3 Gas Turbines* 3 Gas Turbines*

With Co-digestion

Capital Cost $24.9 M $24.9 M $75.0 M $75.0 M

Annual O&M Cost $2.2 M/yr $2.2 M/yr $1.6 M/yr $1.6 M/yr

Annual Electrical Savings $5.2 M/yr $7.0 M/yr $11.4 M/yr $14.7 M/yr

Net Annual Savings $3.0 M/yr $4.8 M/yr $9.8 M/yr $13.1 M/yr

Simple Payback Period 8 years 5 years 8 years 6 years

Payback Without and With Co-Digestion

•  Single Gas Turbine capacity: 4.6 MW •  Payback does not include potential funding for green energy projects to pay for the capital.

Page 21: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Potential Energy Benefit with CHP

21

•  23% green generation* (18% w/digas) •  75% purchased electricity

•  Can reverse energy profile •  More sustainable •  77% green generation* (72% w/digas) •  21% purchased electricity

CHP with 3 Gas Turbines – Co-Digestion

Existing Thermal Plant

*Note: 1.5% generation by CTG backup power.

Page 22: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

•  Gas Turbine CHP is recommended technology

•  Staff will move forward with design to –  Confirm economics –  Investigate additional equipment needed –  Review economics with and without co-digestion –  Confirm full implementation approach –  Develop specific gas system changes –  Develop plans and specs for bidding new CHP

Recommendation

22

Page 23: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress
Page 24: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Presentation to the

Board of Directors

Struvite , Scum, Sludge, and Grit Removal Contract

September 17, 2014

Page 25: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Struvite Removal

25

Cause  •  Struvite  forms  a  pipe  scale  and  consists  of  phosphate,  ammonia,  and  magnesium  

•  Struvite  coats  digested  sludge  pipelines  •  Digester  overflow  box  piping  •  Centrifuge  piping  

•  Difficult  to  remove    PrevenKon  •  Ferric  chloride  added  to  control    RemediaKon  •  Specialized  equipment  and  services  in  confined  spaces  needed  for  removal  

Page 26: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Scum, Sludge and Grit Removal

26

•  Removal  of  severe  blockages  beyond  in  house  capability  in:  

•  Gravity  thickeners  •  Primary  clarifiers  

•  Influent  channels  •  Scum  receiving  wells  

•  Vactor  trucks  and  boxes  used  •  Off  site  material  disposal    

Page 27: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress
Page 28: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Presentation to the

Board of Directors

Deer Island Clarifier Rehabilitation Contract 7394

September 17, 2014

Page 29: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Deer Island Stacked Clarifiers

Page 30: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Condition of Concrete

Page 31: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress
Page 32: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Presentation to the

Board of Directors

Beacon Street Line: Water Pipeline Repair

Contract 7474

September 17, 2014

Page 33: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Beacon Street Line - Brookline

33

•  48-inch cement mortar lined cast-iron pipe

•  Constructed in the 1870sIt is part of MWRA’s Boston Low Service System

•  A significant portion of it is located underneath the MBTA’s Beacon Street Green Line tracks

•  The Beacon Street Line provides important the Longwood Medical area

Page 34: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Beacon Street Line - Brookline

Page 35: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Beacon Street Line - Brookline

Page 36: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Location of Access Pits

CFRP  InstallaKon  

Page 37: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Presentation to the

Board of Directors

Spot Pond Water Storage Facility Contract 6457, Change Order 7

September 17, 2014

Page 38: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Spot Pond Tank and Ravine Road Piping

Page 39: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Remove Ledge to Install 36-Inch Pipelines and Valve Vaults at Ravine Road

Page 40: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Remove 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe

Page 41: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Current Progress

Page 42: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Massachusetts Water Resources Authority

Presentation to the

Board of Directors

Gillis Pump Station Short-Term Improvements Contract 7260, Change Order 3

September 17, 2014

Page 43: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Additional Valve Work

Page 44: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Ledge Croppings Inside Excavated Pit

Page 45: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress

Selector Switch for Three VFD Bypasses

Page 46: Massachusetts Water Resources Authority - MWRA - … 87 Linear Feet of 16-Inch-Diameter, Cast-Iron Water Main and Replace with Restrained-Joint, Ductile-Iron Pipe Current Progress