master spec home and pool inspection services · decision to correct a hazard or any deficiency...

27
Home Inspection Report Master Spec Home and Pool Inspection Services 1110 Anywhere Ln. Dallas, TX 75216

Upload: others

Post on 04-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

Home Inspection Report

Master Spec Home and Pool Inspection Services

1110 Anywhere Ln. Dallas, TX 75216

Page 2: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

PROPERTY INSPECTION REPORT

Prepared For: Mr. & Mrs. Happy Homebuyer

Concerning: 1110 Anywhere Ln. Dallas, TX 75216

Inspection Date: 2/15/2018

By: Inspector Name: Jason Woodliff License Number: 21033 Date: 5-14-14

Phone: 214-536-9300 E-Mail: [email protected]

PURPOSE, LIMITATIONS AND INSPECTOR / CLIENT RESPONSIBILITIES

This property inspection report may include an inspection agreement (contract), addenda, and other information related to property conditions. If any item or comment is unclear, you should ask the inspector to clarify the findings. It is important that you carefully read ALL of this information.

This inspection is subject to the rules ("Rules") of the Texas Real Estate Commission ("TREC"), which can be found at www.trec.texas.gov.

The TREC Standards of Practice (Sections 535.227-535.233 of the Rules) are the minimum standards for inspections by TREC-licensed inspectors. An inspection addresses only those components and conditions that are present, visible, and accessible at the time of the inspection. While there may be other parts, components or systems present, only those items specifically noted as being inspected were inspected. The inspector is NOT required to turn on decommissioned equipment, systems, utility services or apply an open flame or light a pilot to operate any appliance. The inspector is NOT required to climb over obstacles, move furnishings or stored items. The inspection report may address issues that are code-based or may refer to a particular code; however, this is NOT a code compliance inspection and does NOT verify compliance with manufacturer's installation instructions. The inspection does NOT imply insurability or warrantability of the structure or its components. Although some safety issues may be addressed in this report, this inspection is NOT a safety/code inspection, and the inspector is NOT required to identify all potential hazards.

In this report, the inspector shall indicate, by checking the appropriate boxes on the form, whether each item was inspected, not inspected, not present or deficient and explain the findings in the corresponding section in the body of the report form. The inspector must check the Deficient (D) box if a condition exists that adversely and materially affects the performance of a system or component or constitutes a hazard to life, limb or property as specified by the TREC Standards of Practice. General deficiencies include inoperability, material distress, water penetration, damage, deterioration, missing components, and unsuitable installation. Comments may be provided by the inspector whether or not an item is deemed deficient. The inspector is not required to prioritize or emphasize the importance of one deficiency over another.

Some items reported may be considered life-safety upgrades to the property. For more information, refer to Texas Real Estate Consumer Notice Concerning Recognized Hazards or Deficiencies below.

THIS PROPERTY INSPECTION IS NOT A TECHNICALLY EXHAUSTIVE INSPECTION OF THE STRUCTURE, SYSTEMS OR COMPONENTS. The inspection may not reveal all deficiencies. A real estate inspection helps to reduce some of the risk involved in purchasing a home, but it cannot eliminate these risks, nor can the inspection anticipate future events or changes in performance due to changes in use or occupancy. It is recommended that you obtain as much information as is available about this property, including any sellers disclosures, previous inspection reports, engineering reports, building/remodeling permits, and reports performed for or by relocation companies, municipal inspection departments, lenders, insurers, and appraisers. You should also attempt to determine whether repairs, renovation, remodeling, additions, or other such activities have taken place at this property. It is not the inspector's responsibility to confirm that information obtained from these sources is complete or accurate or that this inspection is consistent with the opinions expressed in previous or future reports.

ITEMS IDENTIFIED IN THE REPORT DO NOT OBLIGATE ANY PARTY TO MAKE REPAIRS OR TAKE OTHER ACTIONS, NOR IS THE PURCHASER REQUIRED TO REQUEST THAT THE SELLER TAKE ANY ACTION. When a deficiency is reported, it is the client's responsibility to obtain further evaluations and/or cost estimates from qualified service professionals. Any such follow-up should take place prior to the expiration of any time limitations such as option periods.

Master Spec Home and Pool Inspection Services

Promulgated by the Texas Real Estate Commission (TREC) P.O. Box 12188, Austin, TX 78711-2188 (512)936-3000(http://www.trec.texas.gov).

Page 1 of 26REI 7-5 (Revised 05/4/2015)

Page 3: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

Evaluations by qualified tradesmen may lead to the discovery of additional deficiencies which may involve additional repair costs. Failure to address deficiencies or comments noted in this report may lead to further damage of the structure or systems and add to the original repair costs. The inspector is not required to provide follow-up services to verify that proper repairs have been made.

Property conditions change with time and use. For example, mechanical devices can fail at any time, plumbing gaskets and seals may crack if the appliance or plumbing fixture is not used often, roof leaks can occur at any time regardless of the apparent condition of the roof, and the performance of the structure and the systems may change due to changes in use or occupancy, effects of weather, etc. These changes or repairs made to the structure after the inspection may render information contained herein obsolete or invalid. This report is provided for the specific benefit of the client named above and is based on observations at the time of the inspection. If you did not hire the inspector yourself, reliance on this report may provide incomplete or outdated information. Repairs, professional opinions or additional inspection reports may affect the meaning of the information in this report. It is recommended that you hire a licensed inspector to perform an inspection to meet your specific needs and to provide you with current information concerning this property.

TEXAS REAL ESTATE CONSUMER NOTICE CONCERNING HAZARDS OR DEFICIENCIES

Each year, Texans sustain property damage and are injured by accidents in the home. While some accidents may not be avoidable, many other accidents, injuries, and deaths may be avoided through the identification and repair of certain hazardous conditions. Examples of such hazards include: * malfunctioning, improperly installed, or missing ground fault circuit protection (GFCI) devices for electrical receptacles in garages, bathrooms, kitchens, and exterior areas; * malfunctioning arc fault protection (AFCI) devices; * ordinary glass in locations where modern construction techniques call for safety glass; * malfunctioning or lack of fire safety features such as smoke alarms, fire-rated doors in certain locations, and functional emergency escape and rescue openings in bedrooms; * malfunctioning carbon monoxide alarms; * excessive spacing between balusters on stairways and porches; * improperly installed appliances; * improperly installed or defective safety devices; * lack of electrical bonding and grounding; and * lack of bonding on gas piping, including corrugated stainless steel tubing (CSST).

To ensure that consumers are informed of hazards such as these, the Texas Real Estate Commission (TREC) has adopted Standards of Practice requiring licensed inspectors to report these conditions as "Deficient" when performing an inspection for a buyer or seller, if they can be reasonably determined.

These conditions may not have violated building codes or common practices at the time of the construction of the home, or they may have been "grandfathered" because they were present prior to the adoption of codes prohibiting such conditions. While the TREC Standards of Practice do not require inspectors to perform a code compliance inspection, TREC considers the potential for injury or property loss from the hazards addressed in the Standards of Practice to be significant enough to warrant this notice.

Contract forms developed by TREC for use by its real estate licensees also inform the buyer of the right to have the home inspected and can provide an option clause permitting the buyer to terminate the contract within a specified time. Neither the Standards of Practice nor the TREC contract forms require a seller to remedy conditions revealed by an inspection. The decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale or purchase of the home.

INFORMATION INCLUDED UNDER "ADDITIONAL INFORMATION PROVIDED BY INSPECTOR", OR PROVIDED ASAN ATTACHMENT WITH THE STANDARD FORM, IS NOT REQUIRED BY THE COMMISSION AND MAY CONTAIN CONTRACTUAL TERMS BETWEEN THE INSPECTOR AND YOU, AS THE CLIENT. THE COMMISSION DOES NOT REGULATE CONTRACTUAL TERMS BETWEEN PARTIES. IF YOU DO NOT UNDERSTAND THE EFFECT OF ANY CONTRACTUAL TERM CONTAINED IN THIS SECTION OR ANY ATTACHMENTS, CONSULT AN ATTORNEY.

ADDITIONAL INFORMATION PROVIDED BY INSPECTOR

This report has been prepared for the sole and exclusive use of the client indicated above and is limited to an impartial opinion which is not a warranty, that the items inspected are defect-free or that concealed defects may exist as of the date of this inspection or which may have existed in the past or may exist in the future. The report is limited to the components of the property which were visible to the inspector at the time of inspection and his opinion of their condition at the time of inspection. The digital photos in this report are a sampling of the conditions and should not be considered to show all of the conditions or deficiencies observed. The photos are intended to illustrate some, but not all the defects and to clarify the written information in the report. This is not a code-compliance inspection, but the report may contain some references to the International Residential Code and National Electric Code, as support for the inspector's opinion.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Page 2 of 26REI 7-5 (Revised 05/4/2015)

Page 4: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

ADDITIONAL INFORMATION: (continued) Property Description: One-Story, wood framed, single family residence, brick/stone/siding exterior, pier and beam foundation, composition roof. For Reference: The front of the property faces north. Conditions at time of inspection: Partly Cloudy, 70-75 degrees F.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 3 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 5: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

I. STRUCTURAL SYSTEMS

A. Foundations Type of Foundation: Pier and Beam Comments: The foundation is currently providing adequate support for the structure, but issues were observed in the crawlspace which could lead to future structural deficiencies. Spalling was noted on several piers, and they are not fully supporting the beam above it. One of the piers is leaning. One of the beams under the front bedroom area is twisted and is not properly supported at the end, as it does not extend into the foundation wall. The sill plate is significantly rotted on the east side and at the front of the house. The sill plate has been replaced in other areas. Water-damaged subflooring was observed. Recommend a qualified foundation contractor for further evaluation. There is no access to the crawlspace at the rear of the house.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 4 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 6: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

A. Foundations (continued)

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 5 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 7: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

A. Foundations (continued)

B. Grading and Drainage - Comments: A slight negative grade was observed on the west side of the house. The grade should be made to slope away from the structure. Common industry practice requires a downward slope of 6" in the first 10' away from the house. A splash guard is missing at the rear of the house.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 6 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 8: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

C. Roof Covering Materials Type of Roof Covering: Composition Viewed from: Walking on the roof Comments: Many unused nails were left on the roof. Recommend removing these, as they may wash down and become a hazard. Scuff marks were observed at multiple areas. This normally occurs during installation. Leaves and debris have accumulated behind the chimney, which could cause premature deterioration of the roof in this area. Recommend improvement.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 7 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 9: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

C. Roof Covering Materials (continued)

D. Roof Structures and Attics Viewed from: Attic Approximate Average Depth of Insulation: 6"-8" Comments: Not all areas of the attic are visible. There is no access to the attic space above the master area. Much of the attic framing has been reinforced, although 1 rafter is cracked and is not reinforced. The attic space is not equipped with a solid, unobstructed pathway to HVAC equipment, as required. This is noteworthy because the air filter is located on the unit in the attic space.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 8 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 10: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

D. Roof Structures and Attics (continued)

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 9 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 11: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

D. Roof Structures and Attics (continued)

E. Walls (Interior and Exterior) - Comments: A waviness was noted in the interior walls. This is a cosmetic issue related to installation, not a structural issue.

F. Ceilings and Floors - Comments: No deficiencies observed. G. Doors (Interior and Exterior) - Comments: Both secondary bedroom doorframes are out of square, and neither door latches. The lock on the middle bedroom door is not functioning.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 10 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 12: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

G. Doors (Interior and Exterior) (continued)

H. Windows - Comments: All the windows were checked and all were found to open, close and latch properly at time of inspection. I. Stairways (Interior and Exterior) - Comments: Not present. J. Fireplaces and Chimneys - Comments: The chimney is capped, but it appears the covering is only secured by a rock.

K. Porches, Balconies, Decks, and Carports - Comments: No deficiencies observed.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 11 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 13: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

II. ELECTRICAL SYSTEMS

A. Service Entrance and Panels - Comments: This home is equipped with Arc Fault Circuit Interrupters in all habitable rooms, as required. AFCI devices are designed to protect against fires caused by electrical arcing faults in the home's wiring. Arc faults can be created by damaged, deteriorated or worn electrical plugs or cords. AFCI breakers cannot be tested when a home is occupied, as it may cause damage to the occupant's electronic devices. Since this home is vacant, the AFCI breakers were tested and all were found to be functioning properly at time of inspection.

B. Branch Circuits, Connected Devices, and Fixtures Type of Wiring: Copper Comments: All smoke alarms were checked and were found to be functioning properly. Each bedroom has a smoke alarm and the hallways adjacent to each bedroom have a smoke alarm, as required. All receptacles were checked and were found to be functioning properly at time of inspection. No carbon monoxide detector was found. Even though this house is "all electric", a carbon monoxide detector is recommended, as a safety precaution. The microwave is on the same circuit as the GFCI counter receptacles. It should be on its own dedicated circuit. The bathroom lights and exhaust fans are on the same circuit as the bathroom GFCI receptacles. When the bathroom GFCI receptacles are tripped, the lights/fans shut off also, which is not proper. Recommend a licensed electrician for further evaluation. The back porch lights are not functioning. The front coach lights are not sealed at the top or on the sides to prevent moisture intrusion. The pull chains are mislabeled on the ceiling fans in the secondary bedrooms.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 12 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 14: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

A. Heating Equipment Type of Systems: Forced Air Energy Sources: Electric Comments: The system was functioning properly at time of inspection.

B. Cooling Equipment Type of Systems: Forced Air Comments: The system was functioning properly at time of inspection. Return air- 60 degrees F Supply air- 40 degrees F The temperature differential should ideally be between 14-22 degrees F. As information, this condenser unit is a 4 ton unit and was manufactured in 2017. Average life expectancy is 10-15 years.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 13 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 15: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

C. Duct Systems, Chases, and Vents - Comments: When the heat was running, the air temperature at the supply vent in the master bathroom was 20-30 degrees F less than the supply air temperature at all the other vents in the house. As information, the filter is located on the unit in the attic space.

IV. PLUMBING SYSTEM

A. Plumbing Supply, Distribution Systems and Fixtures Location of water meter: Front of the house, by the street Location of main water supply valve: Front of the house, outside the front living room windows Static water pressure reading: 42 PSI Comments: The static water pressure is 42 PSI. Ideal water pressure is between 40-80 PSI. The hot/cold are reversed at the master bathroom sink.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 14 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 16: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

B. Drains, Wastes, and Vents - Comments: The stopper in the hall bath sink is disconnected.

C. Water Heating Equipment Energy Sources: Electric Capacity: 50 gallons Comments: The unit was functioning properly at time of inspection. As information, this unit was manufactured in 2017. The average life expectancy of an electric water heater is 5-12 years. There is a drain pan under the unit, which is plumbed to the exterior of the house, as required. The temperature at the fixtures was 117 degrees F, which is ideal.

D. Hydro-Massage Therapy Equipment - Comments: Not present.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 15 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 17: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

V. APPLIANCES

A. Dishwashers - Comments: Functioning properly at time of inspection. The unit was only run in "normal" operating mode. B. Food Waste Disposers - Comments: Functioning properly at time of inspection. C. Range Hood and Exhaust Systems - Comments: Functioning properly at time of inspection. D. Ranges, Cooktops, and Ovens - Comments: Functioning properly at time of inspection. The unit was only checked in "normal" operating mode. The anti-tip brackets are not installed.

E. Microwave Ovens - Comments: Functioning properly at time of inspection. The unit was only run in "normal" operating mode. F. Mechanical Exhaust Vents and Bathroom Heaters - Comments: All the units were functioning properly at time of inspection. G. Garage Door Operators - Comments: Not present. H. Dryer Exhaust Systems - Comments: The dryer vent has a screened termination. It should have a baffle at the termination point, as lint may become clogged in the screen.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 16 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 18: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

VI. OPTIONAL SYSTEMS

A. Landscape Irrigation (Sprinkler) Systems - Comments: B. Swimming Pools, Spas, Hot Tubs, And Equipment Type of Construction: Comments: C. Outbuildings - Comments: D. Private Water Wells (A coliform analysis is recommended) Type of Pump: Type of Storage Equipment: Comments: E. Private Sewage Disposal (Septic) Systems Type of System: Location of Drain Field: Comments:

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

I=Inspected NI=Not Inspected NP=Not Present D=Deficient

I NI NP D

REI 7-5 (Revised 05/4/2015)Page 17 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 19: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

I. STRUCTURAL SYSTEMS

A. Foundations The foundation is currently providing adequate support for the structure, but issues were observed in the crawlspace which could lead to future structural deficiencies. Spalling was noted on several piers, and they are not fully supporting the beam above it. One of the piers is leaning. One of the beams under the front bedroom area is twisted and is not properly supported at the end, as it does not extend into the foundation wall. The sill plate is significantly rotted on the east side and at the front of the house. The sill plate has been replaced in other areas. Water-damaged subflooring was observed. Recommend a qualified foundation contractor for further evaluation. There is no access to the crawlspace at the rear of the house. Type of Foundation(s): Pier and Beam

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary

REI 7-5 (Revised 05/4/2015)Page 18 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 20: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

A. Foundations (continued)

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 19 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 21: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

A. Foundations (continued)

B. Grading and Drainage A slight negative grade was observed on the west side of the house. The grade should be made to slope away from the structure. Common industry practice requires a downward slope of 6" in the first 10' away from the house. A splash guard is missing at the rear of the house.

C. Roof Covering Materials Many unused nails were left on the roof. Recommend removing these, as they may wash down and become a hazard. Scuff marks were observed at multiple areas. This normally occurs during installation. Leaves and debris have accumulated behind the chimney, which could cause premature deterioration of the roof in this area. Recommend improvement. Types(s) of Roof Covering: Composition Viewed From: Walking on the roof

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 20 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 22: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

C. Roof Covering Materials (continued)

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 21 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 23: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

C. Roof Covering Materials (continued)

D. Roof Structures and Attics Not all areas of the attic are visible. There is no access to the attic space above the master area. Much of the attic framing has been reinforced, although 1 rafter is cracked and is not reinforced. The attic space is not equipped with a solid, unobstructed pathway to HVAC equipment, as required. This is noteworthy because the air filter is located on the unit in the attic space. Viewed From: Attic Approximate Average Depth of Insulation: 6"-8"

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 22 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 24: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

D. Roof Structures and Attics (continued)

G. Doors (Interior and Exterior) Both secondary bedroom doorframes are out of square, and neither door latches. The lock on the middle bedroom door is not functioning.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 23 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 25: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

G. Doors (Interior and Exterior) (continued)

J. Fireplaces and Chimneys The chimney is capped, but it appears the covering is only secured by a rock.

II. ELECTRICAL SYSTEMS

B. Branch Circuits, Connected Devices, and Fixtures All smoke alarms were checked and were found to be functioning properly. Each bedroom has a smoke alarm and the hallways adjacent to each bedroom have a smoke alarm, as required. All receptacles were checked and were found to be functioning properly at time of inspection. No carbon monoxide detector was found. Even though this house is "all electric", a carbon monoxide detector is recommended, as a safety precaution. The microwave is on the same circuit as the GFCI counter receptacles. It should be on its own dedicated circuit. The bathroom lights and exhaust fans are on the same circuit as the bathroom GFCI receptacles. When the bathroom GFCI receptacles are tripped, the lights/fans shut off also, which is not proper.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 24 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 26: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

B. Branch Circuits, Connected Devices, and Fixtures (continued) Recommend a licensed electrician for further evaluation. The back porch lights are not functioning. The front coach lights are not sealed at the top or on the sides to prevent moisture intrusion. The pull chains are mislabeled on the ceiling fans in the secondary bedrooms. Type of Wiring: Copper

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

C. Duct Systems, Chases, and Vents When the heat was running, the air temperature at the supply vent in the master bathroom was 20-30 degrees F less than the supply air temperature at all the other vents in the house. As information, the filter is located on the unit in the attic space.

IV. PLUMBING SYSTEM

A. Plumbing Supply, Distribution Systems and Fixtures The static water pressure is 42 PSI. Ideal water pressure is between 40-80 PSI. The hot/cold are reversed at the master bathroom sink. Location of water meter: Front of the house, by the street Location of main water supply valve: Front of the house, outside the front living room windows Static water pressure reading: 42 PSI

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 25 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services

Page 27: Master Spec Home and Pool Inspection Services · decision to correct a hazard or any deficiency identified in an inspection report is left to the parties to the contract for the sale

A. Plumbing Supply, Distribution Systems and Fixtures (continued)

B. Drains, Wastes, and Vents The stopper in the hall bath sink is disconnected.

V. APPLIANCES

D. Ranges, Cooktops, and Ovens Functioning properly at time of inspection. The unit was only checked in "normal" operating mode. The anti-tip brackets are not installed.

H. Dryer Exhaust Systems The dryer vent has a screened termination. It should have a baffle at the termination point, as lint may become clogged in the screen.

Report Identification: ______________________________________________________________________1110 Anywhere Ln. - Dallas, TX 75216

Summary (continued)

REI 7-5 (Revised 05/4/2015)Page 26 of 26

Client: Mr. & Mrs. Happy Homebuyer

Palm-Tech Inspector, Copyright © 1998-2018, PDmB, Inc.Master Spec Home and Pool Inspection Services