maulaca

448
March 5, 2015 Field diagnostics and diagnostic monitoring of HV insulation at generators, motors, transformers and cables (part I)

Upload: leanhhai1080

Post on 14-Nov-2015

37 views

Category:

Documents


20 download

DESCRIPTION

gssg

TRANSCRIPT

  • March 5, 2015

    Field diagnostics and diagnostic monitoring of HV insulation at generators, motors, transformers and cables (part I)

  • Page 2

    Topics

    Page 2

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Meta-Trends

    1. HV asset fleet / installed base becomes older

    2. Knowledge is a limited resource

    3. HV assets are designed with lower margins than the generation before

    4. Cost pressure

    Page 3 OMICRON

    Introduction

  • Page: 4March 10, 2015

    but on the other hand ...

  • Blackouts

    Page: 5March 10, 2015

    millions ofpeople affected location date

    July 2012 India blackout 620 India 30 July 2012-31 July 2012

    January 2001 India blackout 230 India 2 January 2001

    November 2014 Bangladesh blackout 150 Bangladesh 1 November 2014

    2015 Pakistan blackout 140 Pakistan 26 January 2015

    2005 JavaBali blackout 100 Indonesia 18 Aug 2005

    1999 Southern Brazil blackout 97 Brazil 11 March 1999

    2009 Brazil and Paraguay blackout 87 Brazil, Paraguay 1011 Nov 2009

    Northeast blackout of 2003 55 United States, Canada 1415 Aug 2003

    2003 Italy blackout 55 Italy, Switzerland, Austria, Slovenia, Croatia 28 Sep 2003

    Thailand Nation-wide blackout of 1978 40 Thailand 18 Mar 1978

    Northeast blackout of 1965 30 United States, Canada 9 Nov 1965

  • What to do ?

    maintenance

  • Page 7

    Topics

    Page 7

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Historical stages of maintenance practices

    No maintenance (run to failure)

    Preventive (time based)

    Predictive (condition based)

  • Condition and Time based maintenance

    Time

    Insu

    latio

    n st

    reng

    th New condition

    Operating stress

    Time based maintenance

    Diagnostic levelCondition based maintenance

    Condition based maintenance requires reliable diagnostic tools

  • Equipment, that can be easily replaced within a

    month

    Critical equipment that should be repaired or replaced within 1 year

    Critical Equipment with long term delivery time

    (>1 year)

    Run to Failure

    Predictive Maintenance

    Real Time Monitoring

    Non critical equipment, that can be replaced

    within few months

    Preventive Maintenance

    Eas

    e of

    repa

    ir/re

    plac

    emen

    tC

    ost for unforeseen shut down

    Reliability Centred Maintenance

  • Reliability Centred Maintenance

  • Reliability Centred Maintenance

    Reliability cantered

    Maintenance RCM

    Preventive Maintenance

    PM

    Condition Based

    MaintenanceCBM

    Real Time Monitoring

    RTM

    Predictive Maintenance

    PdM

    Run to Failure

    RTF

  • Page 13

    Topics

    Page 13

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Measurement is a process of making a quantitative assessment of an unknown quantity.

    Monitoring is the systematic observation of repeated processes or systems in order to draw conclusions through the comparison of results.

    The comparison of repeated measurements is defacto monitoring.

    Challenges:Boundary conditions, comparability, measurement uncertainty, repeatability

    Page 14 OMICRON

    Measurement vs. Monitoring

  • Why conduct monitoring when design, type, series and commissioning tests are performed?

    > Design, type and serial tests are conducted prior to asset installation

    > Possible damage via transport, assembly and installation that could lead to eventual failure

    > These tests do not assess online condition when asset is in service

    A commissioning test is:

    > Limited in time

    > Often limited to specific stress factors, but not all

    > A snapshot in time, not continuous

    Example: Cable after laying test: 1h @ 1.1 Un, no load, no temperature stress

    Page 15 OMICRON

    Measurement vs. Monitoring

  • Monitoring enables measurement comparisons to be made in the presence of all operational stress factors (3-phase , asymmetries, couplings, loads, vibrations, temperatures, etc..) during real operation conditions over longer periods of time.

    Monitoring helps to predict severe failure to extend reliable operation of equipment throughout its service life.

    Page 16 OMICRON

    Measurement vs. Monitoring

  • Page 17 OMICRON

    Measurement vs. Monitoring

  • > Periodic offline diagnostic measurements> Allows the variation of different measurement parameters > Does not take place under normal operating conditions> Execution is highly dependent on human interaction > Provides only a snapshot of condition state

    > Periodic online monitoring (temporary monitoring)> Does not allow the variation of different measurement parameters> Takes place under operating conditions (load, temperature, vibration) > Execution required a minor degree of human interaction > Provides a snapshot of condition state over a specified period of time

    > Permanent monitoring (continuous monitoring)> Does not allow the variation of different measurement parameters> Takes place under operating conditions (load, temperature, vibration) > Execution does not require human interaction after setup> Provides continuous (on-going) condition assessment

    Page 18 OMICRON

    Measurement vs. Monitoring

  • > Continuous or periodic monitoring of HV equipment is an essential tool for effective maintenance management

    > Monitoring answers questions about the present condition of the equipment and its future performance

    > The large amount of real-time data gathered by monitoring systems can be used for precise insulation condition assessment

    > Effective comparison of historical data is enabled via an easy-to-use and extendable database solution

    > Exact knowledge of insulation state at any time saves money, as maintenance schedules can be specifically optimized and the service life of assets can be extended

    Page 19 OMICRON

    Diagnostic monitoring

  • > Involves no operational variables > Provides information to evaluate the aging condition of equipment> Allows assessment of future developments in the aging process > Supports decision making for ongoing maintenance or the replacement

    of components > is a "planning tool (asset management)

    Page 20 OMICRON

    Diagnostic monitoring

  • Page 21 OMICRON

    What we would like to discuss today...

  • Page 22 OMICRON

    aging of HV assets means in general aging of HV insulation systems...

    therefore we like to discuss today

    > measurement methods / diagnostically methods to determine health indicating parameters of HV insulations

    > monitoring of diagnostically parameters YES

    > monitoring of operational parameter NO

    What we would like to discuss today...

  • Page 23

    Topics

    Page 23

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Seite 24 OMICRON

    Field Diagnostics & diagnostic monitoring of rotating machines

    Copyright "Siemens Pressebild

  • Seite 25 OMICRON

    Field Diagnostics & diagnostic monitoring of rotating machines

  • Page 26

    Topics

    Page 26

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Seite 27 OMICRON

    Life Time expectation

    Opinions & Statements:

    > 20 ... 30 years (till rewinding) ?

    > economically 15 years (depreciation) ?

    > operated at determined temperature limit 20.000 hours (= 2.3 years)

    all above may be correct what we learn: prediction is difficult ... impossible, therefore diagnostically methods or monitoring is needed

  • Seite 28 OMICRON

    Life Time expectation

    Insulation design evolution the last 100 years

    Glew C.N.:The Next Generation A Review of the Factors influencing the Output of an Electrical Machine in the New Millenium., INSUCON/ISOTEC 98, p. 231-242

  • Seite 29 OMICRON

    Generator

  • Page 30

    Topics

    Page 30

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Seite 31 OMICRON

    Faults & Aging

    Faults

    Source: Brtsch et al. "Insulation Failure Mechanisms of Power Generators", DEIS July/August 2008

    CIGRE 2009 / Survey of Hydro Generator Failures

  • Seite 32 OMICRON

    Faults & Aging

    Insulation of Stator Winding generalCoil Type Winding Roebel Bar Type winding

  • Seite 33 OMICRON

    Faults & Aging

    Insulation of Stator Winding general

  • Seite 34 OMICRON

    Faults & Aging

    Stator slot

  • Seite 35 OMICRON

    Faults & Aging

    Insulation of Stator Winding general

    A. Covering TapeB. Spacer, Coil-End BracinC. Groundwall Insulation, Mica TapesD. Grading/ Silicon Carbide Coating

    E. Slot Semi conductive CoatingF. Inner Semicon. coatingG. Turn InsulationH. Slot Wedge / SealI. Stator Core

  • Seite 36 OMICRON

    Faults & Aging

    Insulation of Stator Winding general

    Slot Semiconductive Coating prevent PDfrom occurring in any air gap that might bepresent between the coil/ bar surface andthe stator core. Carbon-loaded paint or tape

    End winding Grading potential grading,silicon carbide, extends only fewcentimetre beyond the end of each slot.

  • Seite 37 OMICRON

    Faults & Aging

    Insulation of Stator Winding general

    Standards

    IEC 60034 Rotating electrical machinesIEC 60034-18 Functional evaluation of insulating systemsIEC 60034-18-31 Test procedures for form-wound windings Thermal evaluation and classification of

    insulating systems used on machines up to and including 50 MVA and 15 kVIEC 60034-18-33 Test procedures for form-wound windings Multifactor functional evaluation; Endurance

    under combined thermal and electrical stresses of insulating systems used in machines up to and including 50 MVA and 15 kV

    IEC 60034-18-34 Test procedures for form-wound windings - Thermomechanical cycle endurance evaluationIEC 60085 Thermal evaluation and classification of electrical insulationIEC 60216 Guide for the determination of thermal endurance properties electrical insulating

    materialsIEC 60371 Specification for insulating materials based on micaIEC 60270 High-voltage test techniques Partial discharge measurement, Version 2000, 3rd Edition IEC 60034-27 TS, Ed.1, Rotating electrical machines Part 27: Off-line partial discharge measurements

    on the stator winding insulation of rotating electrical machines, Version 2006 IEEE 1434-2000 IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery,

    Version 2000

  • Seite 38 OMICRON

    Faults & AgingBroken Solder Connection

  • Seite 39 OMICRON

    Faults & AgingInsulation with Cavity

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 40 OMICRON

    Faults & AgingDischarge Propagation Path

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 41 OMICRON

    Faults & AgingLoose coils in the slot, semi conductive coating abrasion

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 42 OMICRON

    Faults & AgingDelamination within Mica-Insulation

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 43 OMICRON

    Faults & AgingDelamination within Mica-Insulation

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 44 OMICRON

    Faults & Aging40 years old Insulation

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 45 OMICRON

    Faults & AgingSemi conductive/ grading coating overlap failure

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 46 OMICRON

    Faults & AgingPartial Discharge at the End-Winding

    Sou

    rce:

    Br

    tsch

    et a

    l. "In

    sula

    tion

    Failu

    re M

    echa

    nism

    s of

    Pow

    er G

    ener

    ator

    s", D

    EIS

    Jul

    y/A

    ugus

    t 200

    8

  • Seite 47 OMICRON

    Faults & AgingPartial Discharge at the End-Winding

    Sou

    rce:

    VA

    TEC

    H, A

    US

    TRIA

  • Seite 48 OMICRON

    Faults & Aging

    Insulation faults are mainly caused by aging and overloads

    thermal> overload> extreme high and low ambient temperatures> Cooling air deficiency / wrong installation height above sea level; Management

    errors for large generators (iron and copper different expansion coefficients)

    ambient (chemical)> Moisture + (water with nitrogen oxides under PD influence generates nitric acid)> Oxidation by aggressive environment

    electrical> Overvoltages, transients or permanent stress

    mechanically> pollution> misalignment> Vibrations / relaxations> Exposure by foreign object damage> Forces caused by short-circuits & faulty synchronization actions

  • Seite 49 OMICRON

    Faults & Aging

    Highest and lowest temperature Increase of Current through Overload

    Rated Voltage Test Voltage Over Voltage

    water, ice aggressive and reactive chemicals abrasive particles: metal parts, ash,

    carbon, lubricants

    Oscillation in slot section mechanical forces in enwinding section Different thermal expansion

    T

    E

    A

    M

  • Page 50

    Topics

    Page 50

    > Introduction

    > Maintenance

    > Measurement, Diagnostics and Diagnostic Monitoring

    > Rotating Machines (Generators / Motors)

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities Insulation Resistance

    Polarization Index

    C / tan (power factor)

    Partial discharge

  • Seite 51 OMICRON

    Life Time expectation & Aging

    Diagnosis and Monitoring can not avoid faults, but it helps to plan and minimize the cost

    A suddenly popped up insulation damage is not repaired on average less than 6 to 8 weeks (open end) - if all goes perfect.

    A well-planned repair of a machine takes 2-3 weeks till re-commissioning (depending on the size of the machine)

  • Seite 52 OMICRON

    Measurement & monitoring parameters /quantities

    > Visual inspection

    > Insulation Resistance

    > Polarization Index

    > Partial Discharge

    > Capacitance

    > TanDelta / Power Factor Tip Up

  • Seite 53 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    Insulation Resistance (IR) and Polarization Index (PI) are two universally accepted diagnostic tests for insulation tests. These have been in use for more than 75 years.

    The IR test measures the resistance of the electrical insulation between the copper conductors and the core of the stator or rotor. Ideally the value of this resistance is infinite since the purpose of the insulation is to block current flow between the copper and the core. But in practice, it is not possible.However, the resistance should have a high value to avoid any appreciable leakage current. Lower value of IR indicates that the insulation has deteriorated.

  • Seite 54 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    In insulation resistance test, a high DC voltage is applied across, conductor and ground. The voltage is applied across the insulator. Due to this applied high DC voltage there will be a current through the electrical insulator. Insulators are dielectric in nature (capacitance). Due to that, initially there will be a charging current. After some time when the insulator is totally charged, the capacitive changing current becomes zero and then only resistive conductive current presents in the insulator. That is why it is always recommended to do insulation resistance test at least for 1 minute as it is proved that charging current totally becomes zero after 1 minute.

    Sou

    rce:

    ele

    ctric

    al-e

    ngin

    eerin

    g-po

    rtal.c

    om

  • Seite 55 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    Effect of Temperature on IR

    Unfortunately, just measuring IR has proved to be unreliable, since it is not tenable over time and strongly dependent on temperature. A 10C increase in temperature can reduce IR by 2 to 10 times. When readings of temperature and insulation resistance are plotted on ordinary equally divided co-ordination, a curved characteristics is obtained. On the other hand if graph paper is used on which the insulation scale is laid out in logarithmic division, the graph becomes a straight line. Further, the effect of temperature is different for each insulation material and type of contamination. Although some temperature correction graphs and formulae are given in the IEEE-43 and some other books, they are acknowledged as being unreliable for extrapolation by more than 10C. The result is that every time IR is measured at different temperatures, one gets a completely different IR. This makes it impossible to define a scientifically acceptable IR value over a wide range of temperatures

  • Seite 56 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    Effect of Temperature on IR

    Unfortunately, just measuring IR has proved to be unreliable, since it is not tenable over time and strongly dependent on temperature. A 10C increase in temperature can reduce IR by 2 to 10 times. When readings of temperature and insulation resistance are plotted on ordinary equally divided co-ordination, a curved characteristics is obtained. On the other hand if graph paper is used on which the insulation scale is laid out in logarithmic division, the graph becomes a straight line. Further, the effect of temperature is different for each insulation material and type of contamination. Although some temperature correction graphs and formulae are given in the IEEE-43 and some other books, they are acknowledged as being unreliable for extrapolation by more than 10C. The result is that every time IR is measured at different temperatures, one gets a completely different IR. This makes it impossible to define a scientifically acceptable IR value over a wide range of temperatures

  • Seite 57 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    Sou

    rce:

    ele

    ctric

    al-e

    ngin

    eerin

    g-po

    rtal.c

    om

  • Seite 58 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    PI is a variation of the IR test. It is the ratio of IR measured after voltage has been applied for 10 minutes (R10) to the IR measured after one minute (R1), i.e.

    PI = R10 / R1

    PI was developed to make interpretation of results less sensitive to temperature. PI is the ratio of two IR at two different times. Temperature of the winding does not rise during the test period of 10 minutes. So it is fairly assumed that both R10 and R1 are measured at same winding temperature. Then the temperature correction factor will be same for both cases and will be cancelled during the calculation of Pl. Thus PI is relatively insensitive to temperature.

    Interpretation of Polarisation Index results

    PI Condition of item under test

    4.0 Excellent

  • Seite 59 OMICRON

    Measurement & monitoring parameters /quantities

    Insulation Resistance / Polarization Index

    U-VWE 60 s 25.9809 nA

    Measurement Time Current

    U-VWE 600s 3.7637 nA

    PI = 25.98 / 3.76 = 6.9

  • Polarization and frequency

    > Due to different polarization methods the dielectric constant (r) and the dissipation factor (tan()) are frequency dependent

    thermal losses light absorption (optics)

    polarization losses tan()

    dielectric constant

    frequencyHz kHz MHz GHz

    nr

    nmmm mm

    electrical engineering

    optics

    wavelength

    IR light UV x-rays

    losses caused by reloading of partial capacitances

    dipoles follow the field with delay

    grid gets into resonance

    atoms get excited

    orientation polarization

    grid polarization

    atom polarization

    r = n

    1

    0

    refraction index n

    boundary layer polarization

  • Conductivity

    > Caused by current flowing through the insolation

    > Mostly caused by moving electrons> In liquids also caused by ion movement> In most insolation materials the water

    concentration determines the conductivity

    > Surface currents should be suppressed or relatively small

    > Causes losses at all measuring frequencies> Determines the losses at very low frequencies,

    below 0.1Hz

    +

    insulation

    current through

    insolation

    surface current

  • Partial discharge (PD) losses

    > PD in the Insulation can cause additional losses

    > PD act as a current though the insulation

    > PD losses only occur above the inception voltage

    > With a higher voltage PD losses are higher due to higher PD intensity

    > A precise PD detection is not possible> Only high PD activity leads to a visible increase

    of the tangent()> This mostly happens far above the inception

    voltage> PD sensitive insulations can get seriously

    damaged at this PD level (e.g. PE)> Use a PD measurement system for PD

    detection (e.g. the Omicron MPD600)

    insulationcavity

    with PD

  • Vacuum capacity

    > Capacity of a test object which has as dielectric vacuum

    > For the most objects it is only an ideal concept

    > Has no losses

    > Dielectric constant is 1

    > Gas insolation is close to the vacuum insolation

    vacuum

    +

  • Polarization, conductivity and vacuum capacity

    > The electric representation of an insolation consists of:

    > An ideal capacity for the vacuum field

    > Different polarizations, here shown as one

    > A electric conduction through the dielectric

    > This can be modeled as an equivalent circuit

    Image Source: Andreas Kchler, Hochspannungstechnik, Heidelberg, 2009

    vacuum E-field

    polarization conductivity

    equivalent circuit

  • Equivalent circuit

    > The equivalent circuit can be summarized to two elements:

    > A capacitor

    > A resistor

    > This gives the equivalent circuit for the tangent() measurement

    > As parallel circuit> A series circuit is also possible

    Image source Top Image: Andreas Kchler, Hochspannungstechnik, Heidelberg, 2009

  • What is the dissipation/loss factor tangent()?

    > When using the equivalent circuit diagram of the test object, the tangent() is the relation between the resistive current (IR) and the capacitive current (IC)

    >

    > But IR and IC are not directly measureable

    IC IR

    test object

    Itest

  • What is the dissipation factor tangent()?

    > In the complex plane the angle delta can be seen between the test object current (Itest) and the capacitive current (IC)

    > Using sinusoidal currents this gives a phase difference between the test object current (Itest) and the capacitive current (IC)

    ICIR

    Itest

    U

    t

    i(t)

    capacitive current

    test object current

    = phase difference

  • Difficulties measuring tangent()

    > A good ground connection is essential> Low inductance and resistance> Good connection to the grounding point> Star shaped grounding of all used devices

    > Use short connection cables

    > Very good insolation against stray currents needed> Test object isolation to the ground (best use PTFE or PE)> High voltage to test object (use guard electrode if possible)

    > All contacts in the measuring circuit have to be as good as possible

  • Typical tangent() values at 50Hz for different insolation materials

    Insolation material Typical tangent()(50Hz)*

    Polyethylene (PE and XLPE) 8*10-5 - 4*10-4

    PTFE / Teflon ~1*10-4

    Polyvinyl chloride (PVC) ~2*10-2

    Cast resin (filling and humidity dependent) 5*10-3 - 2*10-1

    Oil impregnated paper (0,1%-10% humidity) 2*10-3 - 1Mineral oil (humidity dependent) 1*10-3 - 8*10-2

    Silicone oil ~2*10-4

    Mica Lower than 1*10-3

    Glass ~1*10-4

    Pressboard ~3*10-3* Source: Andreas Kchler - Hochspannungstechnik

  • Dielectric losses, conductivity and temperature

    > In most insulation materials the conductivity increases with the temperature> This gives a higher dissipation factor> Under certain conditions this can lead to a thermal break down

    > The losses due to polarization may sink with higher temperatures due to better dipole movement

    > This gives a lower dissipation factor

    > In combination this mostly gives a rising dissipation factor with rising temperature, but other results may also occur

  • Seite 71 OMICRON

    Measurement & monitoring parameters /quantities

    TanDelta Dissipation Factor Power Factor Gtan

    PF)Factor(Powercos

    DF)Factoron(Dissipatitan

    SPQP

    M

    G

    Insulation R C

    IR

    IC

    S Q

    P

    Icos

  • Seite 72 OMICRON

    Measurement & monitoring parameters /quantities

    Dielectric Losses

    Conductive Losses Polarization Losses

    .....

  • Seite 73 OMICRON

    Measurement & monitoring parameters /quantities

    Dielectric Losses

    > Conductive losses> Movement of conductive particles

    > carbon in oil> Movement of ions and electrons

    > leakage current through the insulation or on the surface of a bushing> Partial discharge

    > Polarization losses> Interfacial polarization> Polarization of dipoles in insulation material (rotation/suspension)

    > Increased moisture causes more dipoles and hence more losses

  • Seite 74 OMICRON

    Measurement & monitoring parameters /quantities

    tanDelta = f(f)

    tan

    f [Hz]

    Sum

    Polarization Losses

    Conductive Losses

  • Seite 75 OMICRON

    Measurement & monitoring parameters /quantities

    tanDelta = f(f)

    Freq/Hz0.0001 0.010 0.10 1.0 10.0

    0.005

    0.010

    0.020

    0.050

    0.100

    0.200

    0.500

    1.000

    2.000

    10000.001

    5.000DF

    New Moderate Aged

    0.12

    0.0024

    50H

    z0.0036

  • Measuring Principle

    25 mm

    2.5 km

    Reference path: tan G = 10-5

    G

  • Seite 77 OMICRON

    Measurement & monitoring parameters /quantities

    Capacitance and TanD

    tan G =conductor (tan GC)polarization (tan GP)losses caused by PD (tan GPD)

    tan G = tan GC + tan GP + tan GPD

    tan G = f (U)

    Tip-Up Test IEEE 286 Tan-Delta Test IEC 60894

  • Seite 78 OMICRON

    Measurement & monitoring parameters /quantities

    Power factor / dissipation factor (tan delta) tip-up test at 50 Hz / 60 HzDetermination of stator winding condition typical curves for aged and new rotating machines

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    Del

    ta ta

    n de

    ltaV V

    Aged rotating machine

    New rotating machine

    New rotating machine

    Aged rotating machine

    The tip-up test and the delta tan delta diagram show the same thing.The delta tan delta diagram is frequency independent.

  • Seite 79 OMICRON

    Measurement & monitoring parameters /quantities

    Power factor / dissipation factor (tan delta) tip-up test with variable frequency

    Power factor / dissipation factor (V) at 62 HzPower factor / dissipation factor (f) at 2 kV

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    n fa

    ctor

    (tan

    del

    ta)

    f VPow

    er fa

    ctor

    / di

    ssip

    atio

    n fa

    ctor

    (tan

    del

    ta)

  • What is partial discharge ?

    > Partial discharge (PD) is a localized dielectric breakdown of a small portion of a solid or liquid electrical insulation system under high voltage stress.

    > Definition from IEC 60270 Specification: Localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor.

  • Important units

    Charge Q [1Coulomb] = [1As]:

    Charge in movement = CURRENT!!!

    The more electrons per TIME interval, the higher is the current

    Current = Charge per Time[A] = [Coulomb] per [s][A] = [Coulomb] / [s]

    Charge = Current times TimeCharge = Current x Time

    +

    nucleus1st orbit

    2nd orbit

    electron-

    -

    -

    q =

  • Charge How to measure?

    > Time Domain Integration q =

    q

  • SI prefixes

    kilo Volts [kV]

    milli Ampere [mA]micro Farad [F]nano Coulomb [nC]pico Coulomb [pC]

    Most used prefixes:

  • Types of PD

    > Internal PD> Void discharges, electrical treeing

    > External PD> Corona> Surface discharges

    Solid insulation

    Outer semicon

    Solid insulation

    Inner semicon

    Image Source: Andreas Kchler Hochspannungstechnik

  • External PD

    Surface discharge Corona discharge

  • Internal PD

    Internal discharge in laminated material

    Treeing

    Cavity / void discharge

  • PD classification

    Semicon layer protrusion(stress concentration at the tip)

    Void (field strength doubling)

    Lines ofelectrical field

    En = 2

  • Breakdown theory in solid materials

    1. Intrinsic breakdown (pure electrical breakdown)

    > emerges in insulations stressed temporarily with surge voltage

    2. Thermal breakdown

    > thermal instability of the insulation caused by high temperature

    3. Partial discharge breakdown (erosion breakdown)> as a result of aging processes in electrical high stressed insulation areas > mostly caused by manufacturing

  • Main differences in comparison to breakdowns in air

    > Failure is destroyed by the breakdown channel

    > Breakdown in solid insulations are dependent of:

    > purity of different solid materials (e.g. compounding of cables)

    > technological influences during manufacturing and contacting

    > surface and boundary issues

    > temperature, humidity and pressure inside the solid

  • Thermal breakdown

    > dielectric losses are caused by conductivity and polarization phenomena

    > material heats up (conductivity raises exponential with temperature)

    > higher losses

    Electrical insulationsare at the same timethermal insulations

    tan()

    conductivity losses

    polarization losses

  • Thermal breakdown schematic process

    Dielectric losses cause a warming in the insulation

    > highest temperature occurs in the center plane

    > not enough heat can be conducted

    > heating effects increase

    > thermal hot spot

    hot spot

  • Thermal breakdown schematic process

    > conductivity rises in heated area

    > increasing e-field at the channel ends

    > growth of channel to the electrodes

    > breakdown

  • Partial discharge breakdown

    > PD occurs as a consequence of :

    > local heating (creation of voids)

    > abrasion

    > delamination

    > mechanical stress (vibration)

    > defects in the material

    > water treeing

    > high electric field strength

  • Partial discharge breakdown (treeing)

    > The thinner the insulation, the faster follows on a channel growing a breakdown

    A larger thickness of the insulation

    increases the treeing time

    > The channel building time is much higher than the channel starting time.

  • PD sources in solid insulations

    cracks cleaving voids cavity delamination of fibers

  • PD treeing

    Acrylic glass Epoxy resin

    PD treeing stopped

  • AC frequency influences the electrical treeing

    Prof. Dr. Ing. Daniel Pepper, Dissertation, Berlin, 2004

  • Partial discharge breakdown (treeing)

    > PD tree reacts as pushed forward potential

    > PD treeing is not a steady process:

    1. treeing in a channel ends because of high pressure due to products of decomposition

    2. high conductivity delays the growth of trees

    3. free space charges lower the electric field locally

    Eg

    Eg: global electric field

    + +

  • How to analyze PD

    > Well known approaches:

    > PRPD

    > Trend

    > Q(U)

    > PSA (Pulse Sequence Analysis)

    > TDR and STDR (PD localization)

    > OMICRONs new approaches:

    > Frequency based pulse discrimination (3CFRD/3FREQ)

    > Cross-talk evaluation (3PARD)

  • Phase resolved partial discharge PRPD

    PRPD correlation between PD pulses and voltage phasePD nature might be identified

  • Phase resolved partial discharge PRPD

    Am

    plitu

    de

    1 2 3 4...

    5 50

    Time (ms)

    Am

    plitu

    de

    Time

    Trigger TriggerTriggerTriggerTriggerTrigger

    > How is a PRPD created?

    1020

  • Further ways of PD analysis Trend

    Charge vs. time

    Applied voltage vs. time PD repetition rate vs. applied voltage

    PD repetition rate vs. time

  • Further ways of PD analysis Q(U)

    > Charge over Test Voltage

  • Further ways of PD analysis 3CFRD (3 Center Frequency Ratio Diagram)> Pulse Shape Analysis: 3CFRD or Time/Frequency map

    T/W map

  • Influence of inverse gating on external disturbances

    External disturbance PD Noise

  • Further ways of PD analysis 3PARD> Analysis of synchronous signal cross talk by using the

    3 Phase Amplitude Ratio Diagram

    500pC

    850pC

    900pC

  • Further ways of PD analysis 3PARD> Analysis of signal cross talk

    Left Phase

    Center Phase

    Right Phase

    500pC

    850pC

    900pC

  • Further ways of PD analysis 3PARD

    Noise PD source 1 PD source 2

  • Further ways of PD analysis PD location> TDR: Time Domain

    Reflectometry

    > LOC: Statistical TDR

    > Dual End:

    Measure 2 PD pulse components directly without using reflections

  • Corona discharges on high voltage potential

  • Corona discharges on ground potential

  • Corona discharges on ground potential with multiple reflections (HV cable)

    origin

    reflection

  • Corona during online measurement

  • Ut(t)

    tt

    U1(t)

    Partial discharge mechanism Void

  • Void discharges in solid dielectric material

    some single cavities

  • Void discharges in solid dielectric material

    Bigger cavities

  • Some single voids

  • Void discharges in XLPE cable Early stage (1/3)

  • Void discharges in XLPE cable Developing fault (2/3)

  • Void discharges in XLPE cable Developing fault (3/3)

  • Cable PD Defective outer semicon layer

  • Bubble in oil

    Pattern is disappearing and re-appearing from time to time.

  • Spike on ground potential in oil

  • Surface discharges

  • Surface discharges Significant differences in amplitude

  • Contact PD

    When the bad contact becomes better, the contact PD can disappear.

  • Floating potential

  • Delamination on outer semicon layer

  • Hopping particle

  • Hopping particles

  • Hopping particles

  • Bushing (RBP) Early stages (88kV)

  • Bushing (RBP) Early stages (126kV)

  • Bushing (RBP) 156kV

  • Voltage transformer Inner PD

  • PD patterns and classification

    Source: J. Fuhr, Procedure for Identification and Localization of PD, IEEE Transactions 2005

  • PD patterns and classification

    Source: J. Fuhr, Procedure for Identification and Localization of PD, IEEE Transactions 2005

  • PD patterns and classification

    CIGRE WG 21.03

    Recognition of Discharges

  • Inception / extinction voltage

    U/Umax

    noise level

    PDEV PDIV

    Specified threshold for PDIV and PDEV

    PD magnitude as a function of the normalized test voltage Qm = f (U/Umax)

  • Full bandwidth

    oscilloscope signal time domain o

    m bar indicator frequency domain

  • Low-pass

  • High-pass

  • Band-pass

    > key element of the PD measuring system

  • Time domain vs frequency domain power quality

  • Time domain vs frequency domain

  • Time domain vs frequency domain

    > easier to display

    50 Hz: 1 V500 Hz: 0.1 V

  • Time Domain vs Frequency Domain

    50 Hz: 1 V150 Hz: 0.3 V

  • Time domain vs frequency domain

    50 Hz: 1 V150 Hz: 0.3 V250 Hz: 0.1 V350 Hz: 0.03 V450 Hz: 0.01 V

  • Time domain vs frequency domain

    > the dirac pulse consists of all thinkable frequency components N x 50 Hz: 1V

  • The DIRAC pulse

    The area below the curve is 1.

    time (t) frequency (f)

    A (f) = 1, for all f

    amplitude (A)

  • Time domain vs frequency domain: i(t) and A(f) and charge

    t

    i

    fA

    area = q = 10pC

    cut-off frequency

    area = q = 10pC

    area = q = 10pC

    area = q = 10pC

    all spectral curves show the same amplitude

    charge = q = 10pC

  • Time domain vs frequency domain: i(t) and A(f) and charge

    frequency f = 0Hz

    The spectral amplitude @ 0Hz (f< fcut-off)

    represents the impulse charge q!

    f

    A

    charge = q = 10pC

  • PD pulse: time domain vs frequency domain

    ideal PD-impulse:

    a) time domain display of current i(t) T1 time to the maximum of the current (imax)T2 time to the declining half of imax

    b) normalized amplitude density F()/F(0)1) T1/T2 = 1 s/5 s2) T1/T2 = 5 ns/50 ns3) T1/T2 = 5 ns/15 ns

    a)

    T1

    i (t)

    imax

    imax/2

    T2t

    b)

    0103 104 105 106 107 109Hz

    0,5

    1,5

    F()

    F(0)

    1

    2

    3

  • Partial discharge breakdown

    > PD occurs as a consequence of :

    > local heating (creation of voids)

    > abrasion

    > delamination

    > mechanical stress (vibration)

    > defects in the material

    > water treeing

    > high electric field strength

  • This one...

  • Introduction

    > ...For many years, the measurement of PD has been employed as a sensitive means of assessing the quality ... and localize sources of PD in used electrical winding insulation ...

    > ... Compared with other dielectric tests (i.e. the measurement of dissipation factor or insulation resistance) the differentiating character of partial discharge measurements allows localized weak points of the insulation system to be identified...

  • Introduction

    > ...The PD testing ... is also used when inspecting the quality of new assembled ... stator windings, new ... components (e.g. form-wound coils and bars, HV bushings, etc..) and fully impregnated stators...

    > ...PD can provide information on> points of weakness in the insulation system> ageing processes> further measures and intervals between overhauls

  • Introduction

    > Partial discharge testing of stator windings can be divided into two broad groups:

    a. Off-line measurements, in which the stator winding is isolated from the power system and a separate power supply is employed to energize the winding;

    b. On-line measurements, in which the rotating machine is operating normally and connected to the power system.

    > Both of these approaches have advantages and disadvantages...

    Annex Aand

    IEC 60034-27-2

  • Introduction LIMITATIONS

    > ... different types of PD measuring instruments will inevitably produce different results ...

    > ... PD measurements will only be comparable under certain conditions ...

    > ... absolute limits for the windings of rotating machines, for example as acceptance criteria for production or operation, are difficult to define ...

    > Pulse propagation phenomena> Difficulties with calibration> Individual frequency response characteristics> Type of PD source> Location within the stator

  • Introduction LIMITATIONS

    > ... Empirical limits verified in practice can be used as a basis for evaluating test results ...

    > ... PD trend evaluation and comparisons with machines of similar design and similar insulation system measured under similar conditions, using the same measurement equipment

    > ... not all insulation-related problems in stator windings can be detectedby measuring PD (e.g. insulation failures involving continuous leakage currents due to conductive paths between different elements of the insulation or pulseless discharge phenomena) ...

  • 1 Scope

    > Measuring techniques and instruments,

    > The arrangement of test circuits,

    > Normalization and testing procedures,

    > Noise reduction,

    > The documentation of test results,

    > The interpretation of test results

    > Test with AC ... bars or form wound coils with (without) conductive slot coating...

    > Voltage rating >= 6kV

  • 2 Normative references

    > IEC 60060-1, High-voltage test techniques Part 1: General definitions and test requirements

    > IEC 60060-2, High-voltage test techniques Part 2: Measuring systems

    > IEC 60270:2000, Partial discharge measurements

  • 3 Definitions

    > ... general terms and definitions for partial discharge measurements given in IEC 60270 apply...

    > Offline measurement > Measurement taken with the rotating machine at standstill, the machine being

    disconnected from the power system > Test voltage is ... from a separate voltage source.

    > Online measurement > Measurement taken with the rotating machine in normal operation

  • 3 Definitions (Coating)

    > Stress control coating > Paint or tape on the surface of the groundwall insulation that extends beyond

    the conductive slot portion coating in high-voltage stator bars and coils

    > The stress control coating reduces the electric field stress along the winding overhang to below a critical value that would initiate PD on the surface. The stress control coating overlaps the conductive slot portion coating to provide electrical contact between them.

    > Conductive slot coating > Conductive paint or tape layer in intimate contact with the groundwall insulation

    in the slot portion of the coil side, often called semiconductive coating

    > This coating provides good electrical contact to the stator core.

  • 3 Definitions (PD types)

    > Slot discharges > Discharges that occur between the outer surface of the slot

    portion of a coil or bar and the grounded core laminations

    > Internal discharges > Discharges that occur within the insulation system

    > Surface discharges > Discharges that occur on the surface of the insulation or on

    the surface of winding components in the winding overhang or the active part of the machine winding

  • 3 Definitions (Evaluation)

    > Pulse height distribution > The number of pulses within a series of equally-spaced windows of pulse

    magnitude during a predefined measuring time

    > Pulse phase distribution > The number of pulses within a series of equally-spaced windows of phase

    during a predefined measuring time

    > Partial discharge pattern > PD distribution map of PD magnitude vs a.c. cycle phase position, for

    visualization of the PD behaviour during a predefined measuring time, in which specific PD parameters are used for graphical representation

  • 3 Definitions (Evaluation)

    > Pulse height distribution

    > Pulse phase distribution

    > Partial discharge pattern

  • 3 Definitions (Hardware)

    > Coupling device > Usually an active or passive four-terminal network that

    converts the input currents to output voltage signals

    > These signals are transmitted to the measuring instrument by a transmission system. The frequency response of the coupling device is normally chosen at least so as to efficiently prevent the test voltage frequency and its harmonics from reaching the measuring instrument.

    > PD coupling unit > A high voltage coupling capacitor

    of low inductance design and a low voltage coupling device in series

  • 3 Definitions (Numeric measures)

    > Largest repeatedly occurring PD magnitude Qm > The largest magnitude recorded by a measuring system which has the pulse

    train response in accordance with 4.3.3 of IEC 60270, or the magnitude associated with a PD pulse repetition rate of 10 pulses per second (pps), which can be directly inferred from a pulse height distribution.

  • 3 Definitions (Numeric measures)

    > Normalized quantity number NQN > Normalized area under a straight line fitted to the pulse counts in each

    magnitude window of a pulse height analysis, in which the pulse counts are expressed as a logarithm of the pulses per second and the pulse magnitude window is a linear scale.

  • 4 Nature of PD in rotating machines4.1 Basics of PD> ... where the dielectric properties of insulating materials are inhomogeneous ...

    > ... local electrical over-stressing ...

    > ... local, partial breakdown ...

    > ... PD in general requires a gas volume to develop ...> Gas filled voids embedded in the insulation,> Voids adjacent to conductors> At insulation interfaces

    > ... numerous PD pulses during one cycle of the applied voltage ...

    > ... Stator winding insulation ... for HV machines will normally have some PD .., but are inherently resistant to partial discharges due to their inorganic mica components...

    > ... PD in these machines is usually more a symptom of insulation deficiencies ...

    > .. PD ... may also directly attack the insulation and thus influence the ageing process...

    > ... The time to failure may not correlate with PD levels ...

  • 4 Nature of PD in rotating machines

    4.2 Types of PD> ... For a given machine, the various PD sources may be identified and distinguished

    in many cases by their characteristic PD behaviour...

    > Internal discharges> Internal voids> Internal delamination> Delamination between conductors and insulation> Slot discharges> End-winding surface discharges> Conductive particles

  • 4 Nature of PD in rotating machines

  • A - Small voids on edgeB - Delamination: conductor main insulationC - Delamination of tape layersD - Treeing in layersE - Broken strandsF - Micro voidsG - Slot discharge, semicon paint abrasionH - Discharges in Cooling DuctI - Delamination of Insulation in ElbowJ - End winding surface discharge - contaminationK - Insufficient Spacing, Tracking and SparkingL - Connection area between slot corona protection and end winding corona protection

    4 Nature of PD in rotating machines

  • 4 Nature of PD in rotating machines

  • 4.3 Pulse propagation in windings > ... PD current ... is a transient pulse with a rise time of only a few

    nanoseconds ...

    > ... high frequency spectrum ...

    > ... stator windings represent objects with distributed elements in which travelling wave, complex capacitive and inductive coupling, and resonance phenomena occur ...

    > ... attenuation, distortion, reflection and cross-coupling ...

    > ... transmission function from the PD source to ... sensor is unknown and depends on the specific design of the machine ... Therefore, the energy at the source of the PD, which can be taken as a measure of the erosion of the insulation, cannot be measured directly ...

    4 Nature of PD in rotating machines

  • PD pulse propagation

    Two frequency components of the PD signals in a stator winding

    Damping, reflection, attenuation

    Amplitude of the pulse depends on:

    > Calibration

    > Ratio CK / CA

    > Center frequency

    > Propagation path

  • 4 Nature of PD in rotating machines

    4.3 Pulse propagation in windings > ... the individual high frequency

    transmission behaviour of a stator winding produces PD signals at the terminals that are a characteristicof the machine being tested and of the location of the PD source ...

    > ... very high frequency components of PD signals are subject to ...attenuation ... and ... might not be detectable at the terminals of the test object ...

  • 5 Measuring techniques and instruments

    5.2 Influence of frequency response of measurement system> ... measurement in the lower frequency range ensures good sensitivity

    not only for partial discharges in bars/coils close to the sensor but also for those that originate from further away in the winding. However, the lower frequency range is more subjected to noise and disturbances ...

    > ... measurement in the very high frequency range may acquire only a very small proportion of the total PD energy, which results in sensitivity to signals originating only very close to the sensor. However, this frequency range may be less susceptible to noise and disturbance. ...

    > ... For off-line PD testing to obtain appropriate sensitivity to PD from the whole winding it is advisable to use wide band PD measuring systems. The lower cut-off frequency should be in the range of several tens of kHz in accordance with IEC 60270. ...

  • 5 Measuring techniques and instruments

    5.3 Effects of PD coupling units> ... HV capacitor, coupling device, transmission system and input

    impedance of the measurement system represent a high-pass filter. Therefore, increased input impedance or higher capacitance values lead to an increased sensitivity...

  • 5 Measuring techniques and instruments

    5.4 Wide-band and narrow band measuring systems

    Superposition errors!

    f >100kHz ... 1MHz

  • 6 Visualization of measurements

    6.2 Data presentation> PD magnitude [pC or mV]

    > r.m.s. value of test voltage

    > Inception voltage Ui (PDIV)

    > Extinction voltage Ue (PDEV)

    > Curve Qm = f(U)

    U/Umax

    Noise level

    PDEV PDIV

    Specified threshold for PDIV and PDEV

  • 6 Visualization of measurements

    6.3 Additional means of PD data representation

    > ... Additional quantities ... like integrated charge, discharge current, quadratic rate, PD power, and PD energy ...

    > ... pulse height distribution, pulse phase distribution, phase resolved pulse height distribution, oscillograms of pulse trains, PD distribution maps, etc.... CIGRE technical brochure 226 ...

    Part V: Generator Stator Insulation

  • 6 Visualization of measurements

    > 6.3.2. PRPD pattern> ... a 2-dimensional PD distribution map (-q-n pattern) is employed for

    visualization ...

  • 7 Test circuits

    > HV power supply conforming to IEC 60060-1 and IEC 60060-2; > A voltage measuring device; > A suitable PD coupling unit; > A connection cable from the measuring impedance to the PD device with

    sufficiently low damping characteristics and good shielding; > A partial-discharge measuring system; > High-voltage connections.

    > ... sufficiently PD free...

    Example: IEC 60060-1

    IEC 60060-2: Measuring systems

  • 7 Test circuits

    > ... sufficiently PD free...

    > ... To ensure that the test circuit does not influence the measurement of partial discharges from the test object, the arrangement should first be tested up to the maximum test voltage in accordance with the test procedure given in 9.1.6. The noise level produced by the complete test circuit at maximum required test voltage shall not exceed 100 pC when using the normalization procedure in accordance with Clause 8...

    > ... The whole test circuit should be of a low-inductance arrangement. It is essential that ground loops are avoided. Low inductance leads are recommended as ground connections...

  • 7 Test circuits

    MI

    Z

    CC

    CD

    Ck

    Ca

    Zmi

    U~

  • 7 Test circuits

    MI

    Z

    CC

    CD

    Ck

    Ca

    Zmi

    U~

  • 7 Test circuits Complete winding

    > ... HV source and the PD coupling unit should be connected to oppositewinding terminals whenever possible, to utilize the advantage of the damping effect of the winding phases to suppress conducted interference from the power supply...

    > ... The PD coupling unit should be installed as close to the winding terminals as possible...

    > ... The stator core should normally be grounded...

  • 7 Test circuits Complete winding

    > Single winding energized, also measuring at the grounded windings

  • 7 Test circuits Complete winding

    Single winding energized, also measuring at the grounded windings (ground connection at far end).

  • PD measurement on stator winding

  • Online measurement with permanent couplers

  • 7 Test circuits Complete winding

    Phases not to be separated

    Double length as filter

    Phases not to be separatedPhases not to be separated

  • 8 Normalization of measurements

    > ... Due to pulse propagation, resonance and mutual cross coupling in machine windings, mentioned in 4.3, calibration is not possible...

    > ... The aim of normalization is to ratio out various influences of the test circuit, for example power supply connections, stray capacitance, coupling capacitance and test object capacitance...

    > ... Normalization is to ensure that the PD measuring system provides sufficient sensitivity to measure a specified value of PD magnitude correctly, as it appears at the machine terminals during the measurement, and to show that the PD detection system used, is responding in a repeatable fashion...

    > ... comparisons between measurements on objects having the same design, taken with the same PD device...

    > ... Normalization of the test circuit should be performed by injecting short-duration current pulses of known magnitude by means of a reference pulse generator (calibrator) ...

  • 9 Test procedures

    > Tests on complete windings

    > Individual phases

    > Individual winding components

    > DUT disconnected from all external power supplies> Bus work> Surge arrestors> Surge capacitors> Excitation systems

    > Test lead contact should always be at the machine terminals

    > Same arrangement of all circuit components

    > Same normalization procedure

  • 9 Test procedures Equipment

    > ... The waveform of the applied voltage should have Upp/Urms = 2 SQR(2) , 5% ...

    > ... it is acceptable to perform PD tests at lower frequencies ... or at higher frequencies, 0.1Hz ... 400Hz

    > ... PD results obtained from very-low frequency tests might significantly differ from that at power frequency and thus direct comparison might not be possible ...

  • 9 Test procedures Preparation

    > ... stator should be inspected for cleanliness ...

    > ... sufficient air clearance between ...connections and ... cables ...

    > ... check the insulation resistance before starting the PD test ... >100M ... [Mainly dirt, as dirt may influence PD behaviour]

    > ... conductive slot coating should be in contact with ground potential throughout its whole length ... [for winding components]

    > CONDITIONING!> ... PD will typically decrease during the first minutes ...> ... 5 min at the maximum test voltage is recommended ...> ... voltage may then be re-applied to start the partial discharge measurements

    ...

  • 9 Test procedures Conditioning

    Paschens Law

  • 9 Test procedures Test voltages

    > ... steps (e.g. U = 0,2 Umax) or ... continuous ramping (< 1 kV/s) up to ... Umax. ...

    > ... dwell time on each step of at least 10s is recommended ...

  • 9.1.6 PD test procedure

    > ... level of background noise...should be obtained to ensure that the test arrangement has sufficiently low noise and PD up to the maximum testvoltage...

    > ... replacing the test object by an appropriate discharge free capacitor ...

    > ... Disturbances ... can be reduced or ... eliminated by appropriate measures ...

    > ... localize such disturbance signals ...

    > ... temperature detectors (RTDs) are anchored to the grounded stator frame ...

    > ... the same connection point for the PD coupler, the test object and the measuring equipment should be used ...

    > ... test arrangement as compact as possible ...

  • 9.1.6.3 PD testing

    > ... each voltage step, or during continuous ramping, the PD data ... should be recorded and processed ...

    > ... Qm = f(U) curve ...

    > PDIV

    > PDEV

    > ... distribution of pulse magnitudes, phase resolved distributions or specific PD patterns ... at various levels during test voltage increase and decrease ...

    > ... Any comments or observations during the test should be recorded ...

    > ... an appropriate sequence of standard measurements and ... extended measurements ... should be taken ...

  • 9.2 PD location and ID

    > ... Following the per-phase test... energize simultaneously all three phases of the winding ... [ No PD from end winding]

    > ... subdivide the winding ...

    > ... Electromagnetic probes ...> scanning of stator slots > machine end-winding> conduit boxes> cable routing> termination boards> stand-off insulators, etc.

    > ... probes can disrupt the electric field ...

    > ... additional safety requirements ...

  • 10 Interpretation

    > ... it has to be decided whether there are ... defects and ... what they imply regarding the performance of the insulation system, whether any supplementary tests are needed and the planning and/or implementation of any essential corrective maintenance. ...

    > ... significant variations in the amounts of partial discharges depending on the individual properties of the machine being tested. As a result, a directcomparison of different types of machine in terms of absolute values is notpossible. ...

    > ... Neither is it possible to establish any absolute limits for complete windings ...

  • 10 Interpretation

    > ... the PD site, which produces the highest PD magnitude is not necessarily the location in the winding being at most risk ...

    > ... PD magnitude as a function of test voltage provides a simple and effective means of characterizing typical dominating PD sources ...

    > ... Interpretation is always comparative ...

    > ... meaningful interpretation for complete windings ...> Trending Qm on the same stator over time> Comparing Qm from several stators with the same design> Comparing Qm between different phases of one stator

    > ... the higher the PDIV and PDEV ... the less insulation deficiencies ...

  • 10 Interpretation

    Trend in PD in a machine over time

    > ... Initial fingerprint ... when the winding is new ...

    > ... If the winding deteriorates ... Qm will usually increase over time ...

    > ... Compare the PD quantities ... between windings ...

    > Limitations> ... a new stator may have relatively high PD that decreases after the first 5000

    to 10000 equivalent operating hours ...> ... same voltage, temperature and similar humidity conditions ...> ... variations of Qm of a certain percentage, for example 25 %, are normal

    ...

    > Why?: ... That is, for example, Qm for the winding at the specified test voltage is lower than 95 % of the mean Qm magnitudes achieved by the manufacturer on the same windings they have made in the past....

  • 10.3 Pattern recognition

    > ... When using the -q-n patterns, it may be possible to separate various PD sources from each other, to assess the related risk and to trend them separately ...

    > ... weight their risk separately ...

    > Observe the trend behaviour of each PD source

    > Localize the various PD phenomena

    > Provide rough information concerning location for pinpointing

    > Assess the insulation condition, depending on PD source and PD location.

  • 3CFRD

    Disturbance PD Noise

  • PRPD pattern shows multiple sources

    L2

    L1 L3

  • Separation of sources by 3PARD

    3PARD = Three Phase Amplitude Relation Diagram

  • Inner PD source in L1 in 3PARD

    Inner PD Source L1>L2>L3

    L1

    L2 L1

    L2

    L3

    3PARD

    timeframe 1 s

    Inner PD Source in L1

    L3

  • Outer noise in 3PARD

    L2

    L3

    3PARD

    Outer Noise

    L1

    L1

    L2

    L3

    timeframe 1 s

    Outer Noise L1 L2 L3

  • 213

    PD measurement on Stator Winding and calibrationLocalization: difficult

    2

    ttVelocitySignalLD 12 2

    ttVelocitySignalLD

    1.1unit2.1unit

    rr

    0cVelocitySignalPH

    TDR TDD

  • March 5, 2015

    Field diagnostics and diagnostic monitoring of HV insulation at generators, motors, transformers and cables (part II)

  • Page 2

    Topics

    Page 2

    > Transformer

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities

    > HV Cables

    Lifetime expectations

    Faults and Aging

    Measurement & monitoring parameters /quantities

  • Seite 3 OMICRON

    Field Diagnostics & diagnostic monitoring of transformers

  • Seite 4 OMICRON

    Life Time expectation

    When a Transformer is operated under ANSI / IEEE basic loading conditions (ANSI C57.96), its normal life expectancy is about 20 years. The ANSI / IEEE basic loading conditions for Transformer are:

    i. The Transformer is continuously loaded at rated kVA (kilo Volt Ampere) and rated Voltages (Transformer must be operated at the rated Voltage and kVA)

    ii. The average temperature of the ambient air during any 24-hour period is equal to 30C (86 F) and at no time exceeds 40C (104 F).

    iii. The height where the transformer is installed, does not above 3300 feet or 1000 meters

  • Seite 5 OMICRON

    Transformer Breakdowns

  • Seite 6 OMICRON

    Faults in Transformers

    Win

    ding

    Cor

    e Bus

    hing

    Vess

    el &

    Oil

    Acc

    esso

    ries

    Tap

    Cha

    nger

    Source: Cigre_WG 12-05 An international survey on failures in large power transformers in service, Electra No. 88, 1983

  • Condition and Time based maintenance

    Time

    Insu

    latio

    n st

    reng

    th New condition

    Operating stress

    Time based maintenance

    Diagnostic levelCondition based maintenance

    Condition based maintenance requires reliable diagnostic tools

  • Seite 8 OMICRON

    Possible Impacts by lack of maintenance

    Life of the Transformer

    Baseline data not recorded Problems during warranty period not detected OLTC contacts wear Oil oxidation begins Fan and Pump bearing wear Visible effects of weathering and UV Oil decay products affect paper insulation Miss opportunity to intercept accelerated ageing Oxidation and hydrolysis enters accelerated ageing state OLTC and bushing failure rates increase Dielectric withstand diminishes Expensive failure (bushing, OLTC)

  • Seite 9 OMICRON

    Overview: Transformer Measurements

  • Maintenance Intervals

    Action Task Interval Remark

    Light Regular IntensiveVisit 6 m 1 m 1 d In service

    Detailed inspection (visual)

    1 y 3 m 2 w In service

    DGA 2 y 1 y 3 m Task interval may differ with monitoring

    Oil Test 6 y 2 y 1 y

    Cooling system cleaning

    Conditional Conditional Any interval Outage may be required

    Accessories verification

    12 y or conditional

    6-8 y 1-2 y Outage required

    Electrical basic tests Conditional Conditional Any interval Outage required

    Insulation tests (DF) Conditional 6-8 y 2-4 y Outage required

    OLTC inspection 12 y 6-8 y 4 y

  • Seite 11 OMICRON

    Overview: Transformer MeasurementsType of ProblemMagnetic Circuit Integrity

    Magnetic Circuit Insulation

    Winding Geometry

    Winding/Bushing/OLTC Continuity

    Winding/Bushing Insulation

    Winding Turn to Turn Insulation

    Diagnostic Technique

    Bas

    ic E

    lect

    rical

    Winding Ratio x

    Winding Resistance x

    Magnetisation Current x x

    Capacitance and DF/PF x x x x

    Leakage Reactance x

    Insulation Resistance x x

    Core Ground Test x

    Adv

    ance

    d El

    ectr

    ical

    Frequency Response of Stray Losses x x

    Frequency Response Analysis x x x x

    Polarisation/Depolarisation x

    Frequency Domain Spectroscopy x

    Recovery Voltage Method x

    Electrical Detection of PD x x

    Acoustical detection of PD x x

    UHF Detection of PD x x

    Dissolved Gas Analysis x x x x x

  • Assessment and Interpretation

    Indication RBP OIP RIP

    increase of capacitance oil in cracksor partial breakdowns partial breakdowns partial breakdowns

    high dissipation factor

    partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;

    partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;

    partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;

    dissipation factor is decreasing withincreasing voltage

    bad potential connections;partial breakdowns

    bad potential connections;partial breakdowns

    bad potential connections;partial breakdowns

    dissipation factor isstrongly increasing with increasing temperature

    high moisture in the insulation;high degree of ageing

    high moisture in the insulation;high degree of ageing

    high moisture in the insulation;high degree of ageing

    partial discharges normal, if constant

    Discharges produce gasses;Errosion of the cellulose;production of x-wax

    partial breakdowns;cracks or voids after electrical or mechanical stress;

  • Seite 13 OMICRON

    Overview: Transformer Measurements

    > Turns Ratio

    > Exciting Current

    > Winding Resistance (Dynamic and Static)

    > Short Circuit Impedance (+FRSL)

    > C & DF (Winding, Bushing and Oil sample)

    > Moisture Determination in liquid and solid insulation

    > Frequency Response Analysis Partial Discharge

  • 0nF

    5nF

    10nF

    15nF

    20nF

    25nF

    30nF

    0V

    2000V

    4000V

    6000V

    8000V

    1000

    0V

    1200

    0V

    1400

    0V

    H(V) HL(V) L(V)

    0.2%

    0.25%

    0.3%

    0.35%

    0.4%

    0.45%

    0.5%

    0V

    2000V

    4000V

    6000V

    8000V

    1000

    0V

    1200

    0V

    1400

    0V

    H(V) HL(V) L(V)

    OMICRON

    Tan delta(voltage sweep)

    Capacitance (voltage sweep)

    Cap

    acita

    nce

    V

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    n fa

    ctor

    (tan

    del

    ta)

    V

    Transformer power and dissipation factor (tan delta) + insulation capacitancePower transformer diagnosis

    Automated testing with test templates and reporting with ExcelTM

  • 0%

    0.1%

    0.2%

    0.3%

    0.4%

    0.5%

    0.6%

    0.7%

    0Hz

    50H

    z

    100

    Hz

    150

    Hz

    200

    Hz

    250

    Hz

    300

    Hz

    350

    Hz

    400

    Hz

    450

    Hz

    H(f) HL(f) L(f)

    OMICRON

    0%

    0.1%

    0.2%

    0.3%

    0.4%

    0.5%

    0.6%

    0Hz

    50H

    z

    100

    Hz

    150

    Hz

    200

    Hz

    250

    Hz

    300

    Hz

    350

    Hz

    400

    Hz

    450

    Hzff

    New transformer Transformer with aged oil

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    Increased power factor / dissipation factor especially

    at low frequencies

    H(f) HL(f) L(f)

    Transformer power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz

    Advanced diagnostics

    Additional diagnostics revealed through frequency sweep from 15 Hz to 400 Hz.

  • OMICRON

    Transformer power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz

    Advanced diagnostics

    Advantages

    > Faster and more reliable assessment of transformer and bushing conditions (aging)

    > Shows additional details not obtainable from single power factor measurements:

    > Determines whether moisture contamination is in the cellulose or if the oil is contaminated or otherwise compromised.

    > Effective discrimination between a deteriorated power factor test result that warrants more frequent monitoring and one that requires immediate remediation.

    > Faster fault localization

  • 0.24%0.25%0.26%0.27%0.28%0.29%

    0.3%0.31%0.32%

    0 V

    2000

    V

    4000

    V

    6000

    V

    8000

    V

    1000

    0 V

    1200

    0 V

    1400

    0 V

    A B C

    0.5%

    0.6%

    0.7%

    0.8%

    0.9%

    1%

    1.1%

    0V

    2000V

    4000V

    6000V

    8000V

    1000

    0V

    1200

    0V

    1400

    0V

    A B C

    New bushing Bad bushing

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    V

    OMICRON

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    V

    Inmost layer was not connected to the HV conductor properly.

    Bushing power and dissipation factor (tan delta) + insulation capacitancePower transformer diagnosis

  • 0.25%

    0.35%

    0.45%

    0.55%

    0.65%

    0.75%

    0.85%

    0Hz 100Hz 200Hz 300Hz 400Hz 500Hz

    f

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta) only fNOM values

    Aged bushing

    Medium-aged bushing

    New bushing

    OMICRON

    Condenser type bushing (220 kV RIP)

    Bushing power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz

    Advanced diagnostics

    Additional diagnostics revealed through frequency sweep from 15 Hz to 400 Hz.

  • OMICRON

    0.4 %

    0.45 %

    0.5 %

    0.55 %

    0.6 %

    0 H

    z

    50 H

    z

    100

    Hz

    150

    Hz

    200

    Hz

    250

    Hz

    300

    Hz

    350

    Hz

    400

    Hz

    450

    Hz

    1 2 3 4 5 6

    f

    Pow

    er fa

    ctor

    / di

    ssip

    atio

    nfa

    ctor

    (tan

    del

    ta)

    Oil-impregnated bushings (OIP)

    Bushing power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz

    Advanced diagnostics

    Looking at the whole frequency range shows that four bushings have aged considerably. At lower frequencies there is an

    extreme increase in the dissipation factor (tan delta).

  • OMICRON

    Insulating fluids (oil test cell) power and dissipation factor (tan delta)Power transformer diagnosis

    Testing the insulation condition of oil

  • Exciting current per tap changer position

    0.001 A

    0.0015 A

    0.002 A

    0.0025 A

    0.003 A

    0.0035 A

    0.004 A

    0.0045 A

    0 5 10 15 20 25 30

    A B C

    OMICRON

    Tap changer position

    Exci

    ting

    curr

    ent

    Exciting current and phase angle per tap

    Exciting current per tapPower transformer diagnosis

  • OMICRON

    OLTCPosition

    DETCPosition

    Phase AI out [mA]

    WattLoss [W]

    Reactance(+/-jX)[k]

    Phase BI out[mA]

    WattLoss[W]

    Reactance(+/-jX)[k]

    Phase CI out [mA]

    WattLoss [W]

    Reactance(+/-jX)[k]

    PatternRating

    1 0 61,56 573,22 67,62 42,81 396,23 88,42 59,00 540,12 67,43 NONE

    2 0 62,62 569,87 66,09 44,31 410,38 86,00 61,12 559,15 66,15 NONE

    3 0 64,79 588,69 64,45 45,79 422,97 83,65 63,23 577,36 64,53 NONE

    4 0 67,05 608,41 62,72 47,44 438,60 81,21 65,46 596,85 62,81 NONE

    5 0 70,51 625,79 60,10 49,08 452,48 78,84 67,80 617,27 61,04 NONE

    6 0 71,89 651,07 59,04 50,92 469,99 76,44 70,24 638,84 59,23 NONE

    7 0 74,44 673,86 57,11 52,74 486,24 73,79 72,79 661,55 57,33 NONE

    8 0 77,18 698,20 55,26 54,69 503,53 71,31 75,56 685,89 55,56 NONE

    9 0 80,07 724,07 53,37 56,78 522,56 68,86 78,47 711,65 53,72 NONE

    10 0 82,97 750,83 51,35 58,97 542,90 66,22 81,55 739,10 51,88 NONE

    11 0 86,33 780,10 49,64 61,28 564,43 63,40 84,81 768,08 50,05 NONE

    0 mA

    20 mA

    40 mA

    60 mA

    80 mA

    100 mA

    1 2 3 4 5 6 7 8 9 10 11

    A

    B

    C

    Tap changer position

    Exci

    ting

    curr

    ent

    0 W

    200 W

    400 W

    600 W

    800 W

    1000 W

    1 2 3 4 5 6 7 8 9 10 11

    A

    B

    C

    Tap changer position

    Wat

    t los

    ses

    Measurement and report table

    Exciting current per tapPower transformer diagnosis

  • OMICRON

    12

    13

    14

    15

    16

    17

    000 005 010 015 020

    A

    B

    C

    Rat

    io

    Tap

    Settings: transformer ratio per tap

    Transformer turns ratio (TTR) per tapPower transformer diagnosis

  • -0.08 %

    -0.06 %

    -0.04 %

    -0.02 %

    0.00 %

    0.02 %

    0.04 %

    0 5 10 15 20

    A

    B

    C

    0.002 A

    0.004 A

    0.006 A

    0.008 A

    0.01 A

    0 5 10 15 20

    ABC

    TRRatio: A

    Date/Time: 02.05.2008 13:22

    Overload: NO

    Assessment: n/a

    Range: AC 2kV

    Nominal values:

    Frequency: 50,0Hz

    V test: 1000,0V

    Tap V prim. Nom.Vsec.nom.

    Ratio nom. V prim. Vsec. Ratio I prim.

    001 449610,0/3V 15750,0V 16,4814:1 999,59V 0,0 60,636585V 0,0 16,4849:1 -0,02% 0,004566A -40,71

    002 444890,0/3V 15750,0V 16,3084:1 999,74V 0,0 61,285938V 0,01 16,3127:1 -0,03% 0,004625A -41,18

    003 440170,0/3V 15750,0V 16,1354:1 999,79V 0,0 61,947819V 0,0 16,1392:1 -0,02% 0,004721A -41,48

    004 435440,0/3V 15750,0V 15,962:1 999,85V 0,0 62,622185V 0,0 15,9664:1 -0,03% 0,004791A -41,86

    005 430720,0/3V 15750,0V 15,789:1 999,83V 0,0 63,309776V -0,01 15,7927:1 -0,02% 0,004902A -42,1

    006 426000,0/3V 15750,0V 15,616:1 999,81V 0,0 64,010597V -0,01 15,6194:1 -0,02% 0,005008A -42,35

    007 421280,0/3V 15750,0V 15,4429:1 999,78V 0,0 64,727524V -0,01 15,446:1 -0,02% 0,005097A -42,77

    008 416560,0/3V 15750,0V 15,2699:1 999,89V 0,0 65,464005V -0,01 15,2739:1 -0,03% 0,005211A -42,96

    009 411830,0/3V 15750,0V 15,0965:1 999,6V 0,0 66,197601V -0,01 15,1002:1 -0,02% 0,005334A -42,71

    010 407110,0/3V 15750,0V 14,9235:1 999,78V 0,0 66,981621V 0,01 14,9262:1 -0,02% 0,005422A -43,33

    011 402390,0/3V 15750,0V 14,7505:1 999,73V 0,0 67,760643V 0,0 14,7538:1 -0,02% 0,00568A -45,03

    012 397670,0/3V 15750,0V 14,5775:1 999,83V 0,0 68,570297V 0,0 14,5811:1 -0,02% 0,005816A -45,37

    013 392950,0/3V 15750,0V 14,4044:1 999,78V 0,0 69,396141V -0,02 14,4069:1 -0,02% 0,005939A -45,7

    014 388230,0/3V 15750,0V 14,2314:1 999,74V 0,0 70,235367V 0,0 14,2341:1 -0,02% 0,006073A -45,83

    015 383500,0/3V 15750,0V 14,058:1 999,79V 0,0 71,101517V 0,0 14,0614:1 -0,02% 0,006229A -46,1

    016 378780,0/3V 15750,0V 13,885:1 999,72V 0,0 71,986328V 0,0 13,8876:1 -0,02% 0,006361A -46,33

    017 374060,0/3V 15750,0V 13,712:1 999,78V 0,0 72,902046V -0,01 13,714:1 -0,01% 0,00651A -46,59

    018 369340,0/3V 15750,0V 13,539:1 999,79V 0,0 73,832764V -0,01 13,5413:1 -0,02% 0,006659A -46,73

    019 364620,0/3V 15750,0V 13,3659:1 999,75V 0,0 74,779701V -0,01 13,3693:1 -0,02% 0,006823A -46,88

    Taps

    OMICRON

    Rat

    io d

    evia

    tion

    Exci

    ting

    curr

    ent

    Taps

    Transformer turns ratio (TTR) per tapPower transformer diagnosis

    Transformer in good condition

  • OMICRON

    > Tremendous time-saver: removes the need to change test connections between tests

    > Automatically operates the tap changer

    > Quickly discharges the transformer

    > Increases safety by reducing the risk of accidents

    > Minimizes the likelihood of measurement errors

    > Automated ratio and winding resistance tests

    > Manual operation mode: allows measurements for special applications (e.g. auto transformer tests)

    Transformer turns ratio (TTR) per tapPower transformer diagnosis

    Automated measurement with switch box CP SB1

  • OMICRON

    Leakage reactance / short circuit impedancePower transformer diagnosis

    Determination of winding or core deformation due to high fault currents

  • OMICRON

    Equivalent circuit diagram: effective resistance and reactance

    Forces

    10 kV winding 220 kV windingLeakage flux

    Leakage reactance / short circuit impedancePower transformer diagnosis

    Forces in a transformer, especially in case of a short circuit, can damage windings and the core.

  • Factory Test with W-Meter 3-Phase Measurement

    SN [kVA] Pk [kW] f [Hz] Tap Position: UHV [kV] ULV [kV] uk [%] Uk [kV]

    6500 34.5 50 1 51.7 27.2 6.250 1.9

    Three Phase Equivalent Test CPC 100 Measurement

    f [Hz] V1 AC [V] I AC [A] Z [] Phi [] R [] X [] L [mH]A-B 50 55.224 1.049 25.7019 85.01 2.2370 25.6044 81.50B-C 50 54.675 1.048 25.8922 85.24 2.1470 25.8030 82.13A-C 50 54.464 1.048 25.2547 84.96 2.2196 25.1570 80.08

    Average Impedance

    f [Hz] uk [%] Z [] Phi [] R [] X [] xk [%] L [mH]Factory Test Values: 50 6.250 25.7009 85.13 2.1826 25.6080 6.227 81.51Measured Values: 50 6.229 25.6162 85.07 2.2012 25.5215 6.206 81.24

    Difference to Factory Test [%] -0.33 -0.33 -0.07 0.85 -0.34 -0.34 -0.34

    Per-Phase Test CPC 100 Measurement

    f [Hz] V1 AC [V] I AC [A] Z [] Phi [] R [] X [] L [mH]A-B 50 25.061 1.010 24.5892 84.37 2.4102 24.4708 77.89B-C 50 25.337 1.011 24.8397 84.54 2.3641 24.7270 78.71A-C 50 25.485 1.010 24.9888 84.44 2.4224 24.8711 79.17

    Average Impedance24.8059 2.3989 24.6896 78.5896

    Maximum delta of Average [%] 0.87 1.45 0.89 0.89

    OMICRON

    Factory test data

    Measurement in accordance to IEEE Std C57.12.90

    Factory test and measurement comparison

    Per-phase test

    Leakage reactance / short circuit impedancePower transformer diagnosis

  • OMICRON

    Frequency

    Mea

    sure

    d re

    sist

    ance

    Frequency response of stray losses (FRSL)Advanced diagnostics

    This test is automatically performed with the leakage reactance / short circuit impedance test.

    R is frequency-dependent due to eddy losses (induced currents) in the windings which will increase with the frequency.

  • OMICRON

    B

    HV winding

    LV winding

    Losses through induced currents

    Frequency response of stray losses (FRSL)Advanced diagnostics

    Parallel strands without twisting

  • OMICRON

    B

    HV winding

    LV winding

    Induced currents are compensated

    Parallel strands with twisting

    Frequency response of stray losses (FRSL)Advanced diagnostics

    Parallel strands with twisting compensate the induced currents.

  • OMICRON

    B

    HV winding

    LV winding

    Additional losses through induced currents

    Frequency response of stray losses (FRSL)Advanced diagnostics

    If the twisted strands are shorted additional losses will occur due to induced currents.

  • 0

    1

    2

    3

    4

    5

    0Hz 100Hz 200Hz 300Hz 400Hz

    ZkAB ZkBC ZkAC

    18.8mH

    19.2mH

    19.6mH

    20mH

    20.4mH

    0Hz 100Hz 200Hz 300Hz 400Hz

    ZkAB ZkBC ZkAC

    f

    Three phase equivalent

    f

    R L

    Three phase equivalent

    OMICRON

    Frequency response of stray losses (FRSL)Advanced diagnostics

    The deviation of the resistance Rk,AC indicates short circuit parallel strands in the left diagram.

  • OMICRON

    Tap changer

    Connection clampsTap selector

    DC winding resistancePower transformer diagnosis

    Measurement of winding resistance and internal contacts

  • OMICRON

    0.14

    0.15

    0.16

    0.17

    0.18

    0.19

    0 5 10 15 20 25 30

    Rmeas

    0.14

    0.15

    0.16

    0.17

    0.18

    0.19

    0 5 10 15 20 25 30

    Rref Rmeas

    Tap changer in good condition

    Taps

    Defective contacts in the tap selector

    Win

    ding

    resi

    stan

    ce

    Win

    ding

    resi

    stan

    ce

    Taps

    DC winding resistancePower transformer diagnosis

    Measurement example

    The contacts which were used in taps1, 3, 5, 23, 25, and 27 were defective.

  • OMICRON

    Transformer demagnetizationPower transformer diagnosis

    Influence of remanence

    0.0A

    0.002A

    0.004A

    0.006A

    0.008A

    0.01A

    0.012A

    0.014A

    0.016A

    0.018A

    0.02A U with remanenceV with remanenceW with remanenceU without remanenceV without remanenceW without remanence

    Initial FRA verificationAfter DC testAfter demagnetization

    Exciting current Frequency response anaylsis

  • OMICRON

    Dynamic LTC diagnostics with CP SB1 (OLTC test)Advanced diagnostics

  • 4.7 A

    4.8 A

    4.9 A

    5.0 A

    5.1 A

    -0.05 s 0 s 0.05 s 0.1 s 0.15 s 0.2 s 0.25 s 0.3 s 0.35 s

    OMICRON

    Ripple

    Slope

    Transient current during switching process

    Time

    Cur

    rentDiverter switch switches to the

    first commutating or transition resistor

    Both commutating resistors are in parallel

    Final contact of the diverter contact B is reached

    Current control of the CPC 100 regulates the current to the nominal test current again

    Dynamic LTC diagnostics with CP SB1 (OLTC test)Advanced diagnostics

    The transient switch is recorded and graphically displayed to find faults in the OLTC,