maulaca
DESCRIPTION
gssgTRANSCRIPT
-
March 5, 2015
Field diagnostics and diagnostic monitoring of HV insulation at generators, motors, transformers and cables (part I)
-
Page 2
Topics
Page 2
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Meta-Trends
1. HV asset fleet / installed base becomes older
2. Knowledge is a limited resource
3. HV assets are designed with lower margins than the generation before
4. Cost pressure
Page 3 OMICRON
Introduction
-
Page: 4March 10, 2015
but on the other hand ...
-
Blackouts
Page: 5March 10, 2015
millions ofpeople affected location date
July 2012 India blackout 620 India 30 July 2012-31 July 2012
January 2001 India blackout 230 India 2 January 2001
November 2014 Bangladesh blackout 150 Bangladesh 1 November 2014
2015 Pakistan blackout 140 Pakistan 26 January 2015
2005 JavaBali blackout 100 Indonesia 18 Aug 2005
1999 Southern Brazil blackout 97 Brazil 11 March 1999
2009 Brazil and Paraguay blackout 87 Brazil, Paraguay 1011 Nov 2009
Northeast blackout of 2003 55 United States, Canada 1415 Aug 2003
2003 Italy blackout 55 Italy, Switzerland, Austria, Slovenia, Croatia 28 Sep 2003
Thailand Nation-wide blackout of 1978 40 Thailand 18 Mar 1978
Northeast blackout of 1965 30 United States, Canada 9 Nov 1965
-
What to do ?
maintenance
-
Page 7
Topics
Page 7
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Historical stages of maintenance practices
No maintenance (run to failure)
Preventive (time based)
Predictive (condition based)
-
Condition and Time based maintenance
Time
Insu
latio
n st
reng
th New condition
Operating stress
Time based maintenance
Diagnostic levelCondition based maintenance
Condition based maintenance requires reliable diagnostic tools
-
Equipment, that can be easily replaced within a
month
Critical equipment that should be repaired or replaced within 1 year
Critical Equipment with long term delivery time
(>1 year)
Run to Failure
Predictive Maintenance
Real Time Monitoring
Non critical equipment, that can be replaced
within few months
Preventive Maintenance
Eas
e of
repa
ir/re
plac
emen
tC
ost for unforeseen shut down
Reliability Centred Maintenance
-
Reliability Centred Maintenance
-
Reliability Centred Maintenance
Reliability cantered
Maintenance RCM
Preventive Maintenance
PM
Condition Based
MaintenanceCBM
Real Time Monitoring
RTM
Predictive Maintenance
PdM
Run to Failure
RTF
-
Page 13
Topics
Page 13
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Measurement is a process of making a quantitative assessment of an unknown quantity.
Monitoring is the systematic observation of repeated processes or systems in order to draw conclusions through the comparison of results.
The comparison of repeated measurements is defacto monitoring.
Challenges:Boundary conditions, comparability, measurement uncertainty, repeatability
Page 14 OMICRON
Measurement vs. Monitoring
-
Why conduct monitoring when design, type, series and commissioning tests are performed?
> Design, type and serial tests are conducted prior to asset installation
> Possible damage via transport, assembly and installation that could lead to eventual failure
> These tests do not assess online condition when asset is in service
A commissioning test is:
> Limited in time
> Often limited to specific stress factors, but not all
> A snapshot in time, not continuous
Example: Cable after laying test: 1h @ 1.1 Un, no load, no temperature stress
Page 15 OMICRON
Measurement vs. Monitoring
-
Monitoring enables measurement comparisons to be made in the presence of all operational stress factors (3-phase , asymmetries, couplings, loads, vibrations, temperatures, etc..) during real operation conditions over longer periods of time.
Monitoring helps to predict severe failure to extend reliable operation of equipment throughout its service life.
Page 16 OMICRON
Measurement vs. Monitoring
-
Page 17 OMICRON
Measurement vs. Monitoring
-
> Periodic offline diagnostic measurements> Allows the variation of different measurement parameters > Does not take place under normal operating conditions> Execution is highly dependent on human interaction > Provides only a snapshot of condition state
> Periodic online monitoring (temporary monitoring)> Does not allow the variation of different measurement parameters> Takes place under operating conditions (load, temperature, vibration) > Execution required a minor degree of human interaction > Provides a snapshot of condition state over a specified period of time
> Permanent monitoring (continuous monitoring)> Does not allow the variation of different measurement parameters> Takes place under operating conditions (load, temperature, vibration) > Execution does not require human interaction after setup> Provides continuous (on-going) condition assessment
Page 18 OMICRON
Measurement vs. Monitoring
-
> Continuous or periodic monitoring of HV equipment is an essential tool for effective maintenance management
> Monitoring answers questions about the present condition of the equipment and its future performance
> The large amount of real-time data gathered by monitoring systems can be used for precise insulation condition assessment
> Effective comparison of historical data is enabled via an easy-to-use and extendable database solution
> Exact knowledge of insulation state at any time saves money, as maintenance schedules can be specifically optimized and the service life of assets can be extended
Page 19 OMICRON
Diagnostic monitoring
-
> Involves no operational variables > Provides information to evaluate the aging condition of equipment> Allows assessment of future developments in the aging process > Supports decision making for ongoing maintenance or the replacement
of components > is a "planning tool (asset management)
Page 20 OMICRON
Diagnostic monitoring
-
Page 21 OMICRON
What we would like to discuss today...
-
Page 22 OMICRON
aging of HV assets means in general aging of HV insulation systems...
therefore we like to discuss today
> measurement methods / diagnostically methods to determine health indicating parameters of HV insulations
> monitoring of diagnostically parameters YES
> monitoring of operational parameter NO
What we would like to discuss today...
-
Page 23
Topics
Page 23
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Seite 24 OMICRON
Field Diagnostics & diagnostic monitoring of rotating machines
Copyright "Siemens Pressebild
-
Seite 25 OMICRON
Field Diagnostics & diagnostic monitoring of rotating machines
-
Page 26
Topics
Page 26
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Seite 27 OMICRON
Life Time expectation
Opinions & Statements:
> 20 ... 30 years (till rewinding) ?
> economically 15 years (depreciation) ?
> operated at determined temperature limit 20.000 hours (= 2.3 years)
all above may be correct what we learn: prediction is difficult ... impossible, therefore diagnostically methods or monitoring is needed
-
Seite 28 OMICRON
Life Time expectation
Insulation design evolution the last 100 years
Glew C.N.:The Next Generation A Review of the Factors influencing the Output of an Electrical Machine in the New Millenium., INSUCON/ISOTEC 98, p. 231-242
-
Seite 29 OMICRON
Generator
-
Page 30
Topics
Page 30
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Seite 31 OMICRON
Faults & Aging
Faults
Source: Brtsch et al. "Insulation Failure Mechanisms of Power Generators", DEIS July/August 2008
CIGRE 2009 / Survey of Hydro Generator Failures
-
Seite 32 OMICRON
Faults & Aging
Insulation of Stator Winding generalCoil Type Winding Roebel Bar Type winding
-
Seite 33 OMICRON
Faults & Aging
Insulation of Stator Winding general
-
Seite 34 OMICRON
Faults & Aging
Stator slot
-
Seite 35 OMICRON
Faults & Aging
Insulation of Stator Winding general
A. Covering TapeB. Spacer, Coil-End BracinC. Groundwall Insulation, Mica TapesD. Grading/ Silicon Carbide Coating
E. Slot Semi conductive CoatingF. Inner Semicon. coatingG. Turn InsulationH. Slot Wedge / SealI. Stator Core
-
Seite 36 OMICRON
Faults & Aging
Insulation of Stator Winding general
Slot Semiconductive Coating prevent PDfrom occurring in any air gap that might bepresent between the coil/ bar surface andthe stator core. Carbon-loaded paint or tape
End winding Grading potential grading,silicon carbide, extends only fewcentimetre beyond the end of each slot.
-
Seite 37 OMICRON
Faults & Aging
Insulation of Stator Winding general
Standards
IEC 60034 Rotating electrical machinesIEC 60034-18 Functional evaluation of insulating systemsIEC 60034-18-31 Test procedures for form-wound windings Thermal evaluation and classification of
insulating systems used on machines up to and including 50 MVA and 15 kVIEC 60034-18-33 Test procedures for form-wound windings Multifactor functional evaluation; Endurance
under combined thermal and electrical stresses of insulating systems used in machines up to and including 50 MVA and 15 kV
IEC 60034-18-34 Test procedures for form-wound windings - Thermomechanical cycle endurance evaluationIEC 60085 Thermal evaluation and classification of electrical insulationIEC 60216 Guide for the determination of thermal endurance properties electrical insulating
materialsIEC 60371 Specification for insulating materials based on micaIEC 60270 High-voltage test techniques Partial discharge measurement, Version 2000, 3rd Edition IEC 60034-27 TS, Ed.1, Rotating electrical machines Part 27: Off-line partial discharge measurements
on the stator winding insulation of rotating electrical machines, Version 2006 IEEE 1434-2000 IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery,
Version 2000
-
Seite 38 OMICRON
Faults & AgingBroken Solder Connection
-
Seite 39 OMICRON
Faults & AgingInsulation with Cavity
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 40 OMICRON
Faults & AgingDischarge Propagation Path
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 41 OMICRON
Faults & AgingLoose coils in the slot, semi conductive coating abrasion
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 42 OMICRON
Faults & AgingDelamination within Mica-Insulation
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 43 OMICRON
Faults & AgingDelamination within Mica-Insulation
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 44 OMICRON
Faults & Aging40 years old Insulation
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 45 OMICRON
Faults & AgingSemi conductive/ grading coating overlap failure
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 46 OMICRON
Faults & AgingPartial Discharge at the End-Winding
Sou
rce:
Br
tsch
et a
l. "In
sula
tion
Failu
re M
echa
nism
s of
Pow
er G
ener
ator
s", D
EIS
Jul
y/A
ugus
t 200
8
-
Seite 47 OMICRON
Faults & AgingPartial Discharge at the End-Winding
Sou
rce:
VA
TEC
H, A
US
TRIA
-
Seite 48 OMICRON
Faults & Aging
Insulation faults are mainly caused by aging and overloads
thermal> overload> extreme high and low ambient temperatures> Cooling air deficiency / wrong installation height above sea level; Management
errors for large generators (iron and copper different expansion coefficients)
ambient (chemical)> Moisture + (water with nitrogen oxides under PD influence generates nitric acid)> Oxidation by aggressive environment
electrical> Overvoltages, transients or permanent stress
mechanically> pollution> misalignment> Vibrations / relaxations> Exposure by foreign object damage> Forces caused by short-circuits & faulty synchronization actions
-
Seite 49 OMICRON
Faults & Aging
Highest and lowest temperature Increase of Current through Overload
Rated Voltage Test Voltage Over Voltage
water, ice aggressive and reactive chemicals abrasive particles: metal parts, ash,
carbon, lubricants
Oscillation in slot section mechanical forces in enwinding section Different thermal expansion
T
E
A
M
-
Page 50
Topics
Page 50
> Introduction
> Maintenance
> Measurement, Diagnostics and Diagnostic Monitoring
> Rotating Machines (Generators / Motors)
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities Insulation Resistance
Polarization Index
C / tan (power factor)
Partial discharge
-
Seite 51 OMICRON
Life Time expectation & Aging
Diagnosis and Monitoring can not avoid faults, but it helps to plan and minimize the cost
A suddenly popped up insulation damage is not repaired on average less than 6 to 8 weeks (open end) - if all goes perfect.
A well-planned repair of a machine takes 2-3 weeks till re-commissioning (depending on the size of the machine)
-
Seite 52 OMICRON
Measurement & monitoring parameters /quantities
> Visual inspection
> Insulation Resistance
> Polarization Index
> Partial Discharge
> Capacitance
> TanDelta / Power Factor Tip Up
-
Seite 53 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
Insulation Resistance (IR) and Polarization Index (PI) are two universally accepted diagnostic tests for insulation tests. These have been in use for more than 75 years.
The IR test measures the resistance of the electrical insulation between the copper conductors and the core of the stator or rotor. Ideally the value of this resistance is infinite since the purpose of the insulation is to block current flow between the copper and the core. But in practice, it is not possible.However, the resistance should have a high value to avoid any appreciable leakage current. Lower value of IR indicates that the insulation has deteriorated.
-
Seite 54 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
In insulation resistance test, a high DC voltage is applied across, conductor and ground. The voltage is applied across the insulator. Due to this applied high DC voltage there will be a current through the electrical insulator. Insulators are dielectric in nature (capacitance). Due to that, initially there will be a charging current. After some time when the insulator is totally charged, the capacitive changing current becomes zero and then only resistive conductive current presents in the insulator. That is why it is always recommended to do insulation resistance test at least for 1 minute as it is proved that charging current totally becomes zero after 1 minute.
Sou
rce:
ele
ctric
al-e
ngin
eerin
g-po
rtal.c
om
-
Seite 55 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
Effect of Temperature on IR
Unfortunately, just measuring IR has proved to be unreliable, since it is not tenable over time and strongly dependent on temperature. A 10C increase in temperature can reduce IR by 2 to 10 times. When readings of temperature and insulation resistance are plotted on ordinary equally divided co-ordination, a curved characteristics is obtained. On the other hand if graph paper is used on which the insulation scale is laid out in logarithmic division, the graph becomes a straight line. Further, the effect of temperature is different for each insulation material and type of contamination. Although some temperature correction graphs and formulae are given in the IEEE-43 and some other books, they are acknowledged as being unreliable for extrapolation by more than 10C. The result is that every time IR is measured at different temperatures, one gets a completely different IR. This makes it impossible to define a scientifically acceptable IR value over a wide range of temperatures
-
Seite 56 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
Effect of Temperature on IR
Unfortunately, just measuring IR has proved to be unreliable, since it is not tenable over time and strongly dependent on temperature. A 10C increase in temperature can reduce IR by 2 to 10 times. When readings of temperature and insulation resistance are plotted on ordinary equally divided co-ordination, a curved characteristics is obtained. On the other hand if graph paper is used on which the insulation scale is laid out in logarithmic division, the graph becomes a straight line. Further, the effect of temperature is different for each insulation material and type of contamination. Although some temperature correction graphs and formulae are given in the IEEE-43 and some other books, they are acknowledged as being unreliable for extrapolation by more than 10C. The result is that every time IR is measured at different temperatures, one gets a completely different IR. This makes it impossible to define a scientifically acceptable IR value over a wide range of temperatures
-
Seite 57 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
Sou
rce:
ele
ctric
al-e
ngin
eerin
g-po
rtal.c
om
-
Seite 58 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
PI is a variation of the IR test. It is the ratio of IR measured after voltage has been applied for 10 minutes (R10) to the IR measured after one minute (R1), i.e.
PI = R10 / R1
PI was developed to make interpretation of results less sensitive to temperature. PI is the ratio of two IR at two different times. Temperature of the winding does not rise during the test period of 10 minutes. So it is fairly assumed that both R10 and R1 are measured at same winding temperature. Then the temperature correction factor will be same for both cases and will be cancelled during the calculation of Pl. Thus PI is relatively insensitive to temperature.
Interpretation of Polarisation Index results
PI Condition of item under test
4.0 Excellent
-
Seite 59 OMICRON
Measurement & monitoring parameters /quantities
Insulation Resistance / Polarization Index
U-VWE 60 s 25.9809 nA
Measurement Time Current
U-VWE 600s 3.7637 nA
PI = 25.98 / 3.76 = 6.9
-
Polarization and frequency
> Due to different polarization methods the dielectric constant (r) and the dissipation factor (tan()) are frequency dependent
thermal losses light absorption (optics)
polarization losses tan()
dielectric constant
frequencyHz kHz MHz GHz
nr
nmmm mm
electrical engineering
optics
wavelength
IR light UV x-rays
losses caused by reloading of partial capacitances
dipoles follow the field with delay
grid gets into resonance
atoms get excited
orientation polarization
grid polarization
atom polarization
r = n
1
0
refraction index n
boundary layer polarization
-
Conductivity
> Caused by current flowing through the insolation
> Mostly caused by moving electrons> In liquids also caused by ion movement> In most insolation materials the water
concentration determines the conductivity
> Surface currents should be suppressed or relatively small
> Causes losses at all measuring frequencies> Determines the losses at very low frequencies,
below 0.1Hz
+
insulation
current through
insolation
surface current
-
Partial discharge (PD) losses
> PD in the Insulation can cause additional losses
> PD act as a current though the insulation
> PD losses only occur above the inception voltage
> With a higher voltage PD losses are higher due to higher PD intensity
> A precise PD detection is not possible> Only high PD activity leads to a visible increase
of the tangent()> This mostly happens far above the inception
voltage> PD sensitive insulations can get seriously
damaged at this PD level (e.g. PE)> Use a PD measurement system for PD
detection (e.g. the Omicron MPD600)
insulationcavity
with PD
-
Vacuum capacity
> Capacity of a test object which has as dielectric vacuum
> For the most objects it is only an ideal concept
> Has no losses
> Dielectric constant is 1
> Gas insolation is close to the vacuum insolation
vacuum
+
-
Polarization, conductivity and vacuum capacity
> The electric representation of an insolation consists of:
> An ideal capacity for the vacuum field
> Different polarizations, here shown as one
> A electric conduction through the dielectric
> This can be modeled as an equivalent circuit
Image Source: Andreas Kchler, Hochspannungstechnik, Heidelberg, 2009
vacuum E-field
polarization conductivity
equivalent circuit
-
Equivalent circuit
> The equivalent circuit can be summarized to two elements:
> A capacitor
> A resistor
> This gives the equivalent circuit for the tangent() measurement
> As parallel circuit> A series circuit is also possible
Image source Top Image: Andreas Kchler, Hochspannungstechnik, Heidelberg, 2009
-
What is the dissipation/loss factor tangent()?
> When using the equivalent circuit diagram of the test object, the tangent() is the relation between the resistive current (IR) and the capacitive current (IC)
>
> But IR and IC are not directly measureable
IC IR
test object
Itest
-
What is the dissipation factor tangent()?
> In the complex plane the angle delta can be seen between the test object current (Itest) and the capacitive current (IC)
> Using sinusoidal currents this gives a phase difference between the test object current (Itest) and the capacitive current (IC)
ICIR
Itest
U
t
i(t)
capacitive current
test object current
= phase difference
-
Difficulties measuring tangent()
> A good ground connection is essential> Low inductance and resistance> Good connection to the grounding point> Star shaped grounding of all used devices
> Use short connection cables
> Very good insolation against stray currents needed> Test object isolation to the ground (best use PTFE or PE)> High voltage to test object (use guard electrode if possible)
> All contacts in the measuring circuit have to be as good as possible
-
Typical tangent() values at 50Hz for different insolation materials
Insolation material Typical tangent()(50Hz)*
Polyethylene (PE and XLPE) 8*10-5 - 4*10-4
PTFE / Teflon ~1*10-4
Polyvinyl chloride (PVC) ~2*10-2
Cast resin (filling and humidity dependent) 5*10-3 - 2*10-1
Oil impregnated paper (0,1%-10% humidity) 2*10-3 - 1Mineral oil (humidity dependent) 1*10-3 - 8*10-2
Silicone oil ~2*10-4
Mica Lower than 1*10-3
Glass ~1*10-4
Pressboard ~3*10-3* Source: Andreas Kchler - Hochspannungstechnik
-
Dielectric losses, conductivity and temperature
> In most insulation materials the conductivity increases with the temperature> This gives a higher dissipation factor> Under certain conditions this can lead to a thermal break down
> The losses due to polarization may sink with higher temperatures due to better dipole movement
> This gives a lower dissipation factor
> In combination this mostly gives a rising dissipation factor with rising temperature, but other results may also occur
-
Seite 71 OMICRON
Measurement & monitoring parameters /quantities
TanDelta Dissipation Factor Power Factor Gtan
PF)Factor(Powercos
DF)Factoron(Dissipatitan
SPQP
M
G
Insulation R C
IR
IC
S Q
P
Icos
-
Seite 72 OMICRON
Measurement & monitoring parameters /quantities
Dielectric Losses
Conductive Losses Polarization Losses
.....
-
Seite 73 OMICRON
Measurement & monitoring parameters /quantities
Dielectric Losses
> Conductive losses> Movement of conductive particles
> carbon in oil> Movement of ions and electrons
> leakage current through the insulation or on the surface of a bushing> Partial discharge
> Polarization losses> Interfacial polarization> Polarization of dipoles in insulation material (rotation/suspension)
> Increased moisture causes more dipoles and hence more losses
-
Seite 74 OMICRON
Measurement & monitoring parameters /quantities
tanDelta = f(f)
tan
f [Hz]
Sum
Polarization Losses
Conductive Losses
-
Seite 75 OMICRON
Measurement & monitoring parameters /quantities
tanDelta = f(f)
Freq/Hz0.0001 0.010 0.10 1.0 10.0
0.005
0.010
0.020
0.050
0.100
0.200
0.500
1.000
2.000
10000.001
5.000DF
New Moderate Aged
0.12
0.0024
50H
z0.0036
-
Measuring Principle
25 mm
2.5 km
Reference path: tan G = 10-5
G
-
Seite 77 OMICRON
Measurement & monitoring parameters /quantities
Capacitance and TanD
tan G =conductor (tan GC)polarization (tan GP)losses caused by PD (tan GPD)
tan G = tan GC + tan GP + tan GPD
tan G = f (U)
Tip-Up Test IEEE 286 Tan-Delta Test IEC 60894
-
Seite 78 OMICRON
Measurement & monitoring parameters /quantities
Power factor / dissipation factor (tan delta) tip-up test at 50 Hz / 60 HzDetermination of stator winding condition typical curves for aged and new rotating machines
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
Del
ta ta
n de
ltaV V
Aged rotating machine
New rotating machine
New rotating machine
Aged rotating machine
The tip-up test and the delta tan delta diagram show the same thing.The delta tan delta diagram is frequency independent.
-
Seite 79 OMICRON
Measurement & monitoring parameters /quantities
Power factor / dissipation factor (tan delta) tip-up test with variable frequency
Power factor / dissipation factor (V) at 62 HzPower factor / dissipation factor (f) at 2 kV
Pow
er fa
ctor
/ di
ssip
atio
n fa
ctor
(tan
del
ta)
f VPow
er fa
ctor
/ di
ssip
atio
n fa
ctor
(tan
del
ta)
-
What is partial discharge ?
> Partial discharge (PD) is a localized dielectric breakdown of a small portion of a solid or liquid electrical insulation system under high voltage stress.
> Definition from IEC 60270 Specification: Localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor.
-
Important units
Charge Q [1Coulomb] = [1As]:
Charge in movement = CURRENT!!!
The more electrons per TIME interval, the higher is the current
Current = Charge per Time[A] = [Coulomb] per [s][A] = [Coulomb] / [s]
Charge = Current times TimeCharge = Current x Time
+
nucleus1st orbit
2nd orbit
electron-
-
-
q =
-
Charge How to measure?
> Time Domain Integration q =
q
-
SI prefixes
kilo Volts [kV]
milli Ampere [mA]micro Farad [F]nano Coulomb [nC]pico Coulomb [pC]
Most used prefixes:
-
Types of PD
> Internal PD> Void discharges, electrical treeing
> External PD> Corona> Surface discharges
Solid insulation
Outer semicon
Solid insulation
Inner semicon
Image Source: Andreas Kchler Hochspannungstechnik
-
External PD
Surface discharge Corona discharge
-
Internal PD
Internal discharge in laminated material
Treeing
Cavity / void discharge
-
PD classification
Semicon layer protrusion(stress concentration at the tip)
Void (field strength doubling)
Lines ofelectrical field
En = 2
-
Breakdown theory in solid materials
1. Intrinsic breakdown (pure electrical breakdown)
> emerges in insulations stressed temporarily with surge voltage
2. Thermal breakdown
> thermal instability of the insulation caused by high temperature
3. Partial discharge breakdown (erosion breakdown)> as a result of aging processes in electrical high stressed insulation areas > mostly caused by manufacturing
-
Main differences in comparison to breakdowns in air
> Failure is destroyed by the breakdown channel
> Breakdown in solid insulations are dependent of:
> purity of different solid materials (e.g. compounding of cables)
> technological influences during manufacturing and contacting
> surface and boundary issues
> temperature, humidity and pressure inside the solid
-
Thermal breakdown
> dielectric losses are caused by conductivity and polarization phenomena
> material heats up (conductivity raises exponential with temperature)
> higher losses
Electrical insulationsare at the same timethermal insulations
tan()
conductivity losses
polarization losses
-
Thermal breakdown schematic process
Dielectric losses cause a warming in the insulation
> highest temperature occurs in the center plane
> not enough heat can be conducted
> heating effects increase
> thermal hot spot
hot spot
-
Thermal breakdown schematic process
> conductivity rises in heated area
> increasing e-field at the channel ends
> growth of channel to the electrodes
> breakdown
-
Partial discharge breakdown
> PD occurs as a consequence of :
> local heating (creation of voids)
> abrasion
> delamination
> mechanical stress (vibration)
> defects in the material
> water treeing
> high electric field strength
-
Partial discharge breakdown (treeing)
> The thinner the insulation, the faster follows on a channel growing a breakdown
A larger thickness of the insulation
increases the treeing time
> The channel building time is much higher than the channel starting time.
-
PD sources in solid insulations
cracks cleaving voids cavity delamination of fibers
-
PD treeing
Acrylic glass Epoxy resin
PD treeing stopped
-
AC frequency influences the electrical treeing
Prof. Dr. Ing. Daniel Pepper, Dissertation, Berlin, 2004
-
Partial discharge breakdown (treeing)
> PD tree reacts as pushed forward potential
> PD treeing is not a steady process:
1. treeing in a channel ends because of high pressure due to products of decomposition
2. high conductivity delays the growth of trees
3. free space charges lower the electric field locally
Eg
Eg: global electric field
+ +
-
How to analyze PD
> Well known approaches:
> PRPD
> Trend
> Q(U)
> PSA (Pulse Sequence Analysis)
> TDR and STDR (PD localization)
> OMICRONs new approaches:
> Frequency based pulse discrimination (3CFRD/3FREQ)
> Cross-talk evaluation (3PARD)
-
Phase resolved partial discharge PRPD
PRPD correlation between PD pulses and voltage phasePD nature might be identified
-
Phase resolved partial discharge PRPD
Am
plitu
de
1 2 3 4...
5 50
Time (ms)
Am
plitu
de
Time
Trigger TriggerTriggerTriggerTriggerTrigger
> How is a PRPD created?
1020
-
Further ways of PD analysis Trend
Charge vs. time
Applied voltage vs. time PD repetition rate vs. applied voltage
PD repetition rate vs. time
-
Further ways of PD analysis Q(U)
> Charge over Test Voltage
-
Further ways of PD analysis 3CFRD (3 Center Frequency Ratio Diagram)> Pulse Shape Analysis: 3CFRD or Time/Frequency map
T/W map
-
Influence of inverse gating on external disturbances
External disturbance PD Noise
-
Further ways of PD analysis 3PARD> Analysis of synchronous signal cross talk by using the
3 Phase Amplitude Ratio Diagram
500pC
850pC
900pC
-
Further ways of PD analysis 3PARD> Analysis of signal cross talk
Left Phase
Center Phase
Right Phase
500pC
850pC
900pC
-
Further ways of PD analysis 3PARD
Noise PD source 1 PD source 2
-
Further ways of PD analysis PD location> TDR: Time Domain
Reflectometry
> LOC: Statistical TDR
> Dual End:
Measure 2 PD pulse components directly without using reflections
-
Corona discharges on high voltage potential
-
Corona discharges on ground potential
-
Corona discharges on ground potential with multiple reflections (HV cable)
origin
reflection
-
Corona during online measurement
-
Ut(t)
tt
U1(t)
Partial discharge mechanism Void
-
Void discharges in solid dielectric material
some single cavities
-
Void discharges in solid dielectric material
Bigger cavities
-
Some single voids
-
Void discharges in XLPE cable Early stage (1/3)
-
Void discharges in XLPE cable Developing fault (2/3)
-
Void discharges in XLPE cable Developing fault (3/3)
-
Cable PD Defective outer semicon layer
-
Bubble in oil
Pattern is disappearing and re-appearing from time to time.
-
Spike on ground potential in oil
-
Surface discharges
-
Surface discharges Significant differences in amplitude
-
Contact PD
When the bad contact becomes better, the contact PD can disappear.
-
Floating potential
-
Delamination on outer semicon layer
-
Hopping particle
-
Hopping particles
-
Hopping particles
-
Bushing (RBP) Early stages (88kV)
-
Bushing (RBP) Early stages (126kV)
-
Bushing (RBP) 156kV
-
Voltage transformer Inner PD
-
PD patterns and classification
Source: J. Fuhr, Procedure for Identification and Localization of PD, IEEE Transactions 2005
-
PD patterns and classification
Source: J. Fuhr, Procedure for Identification and Localization of PD, IEEE Transactions 2005
-
PD patterns and classification
CIGRE WG 21.03
Recognition of Discharges
-
Inception / extinction voltage
U/Umax
noise level
PDEV PDIV
Specified threshold for PDIV and PDEV
PD magnitude as a function of the normalized test voltage Qm = f (U/Umax)
-
Full bandwidth
oscilloscope signal time domain o
m bar indicator frequency domain
-
Low-pass
-
High-pass
-
Band-pass
> key element of the PD measuring system
-
Time domain vs frequency domain power quality
-
Time domain vs frequency domain
-
Time domain vs frequency domain
> easier to display
50 Hz: 1 V500 Hz: 0.1 V
-
Time Domain vs Frequency Domain
50 Hz: 1 V150 Hz: 0.3 V
-
Time domain vs frequency domain
50 Hz: 1 V150 Hz: 0.3 V250 Hz: 0.1 V350 Hz: 0.03 V450 Hz: 0.01 V
-
Time domain vs frequency domain
> the dirac pulse consists of all thinkable frequency components N x 50 Hz: 1V
-
The DIRAC pulse
The area below the curve is 1.
time (t) frequency (f)
A (f) = 1, for all f
amplitude (A)
-
Time domain vs frequency domain: i(t) and A(f) and charge
t
i
fA
area = q = 10pC
cut-off frequency
area = q = 10pC
area = q = 10pC
area = q = 10pC
all spectral curves show the same amplitude
charge = q = 10pC
-
Time domain vs frequency domain: i(t) and A(f) and charge
frequency f = 0Hz
The spectral amplitude @ 0Hz (f< fcut-off)
represents the impulse charge q!
f
A
charge = q = 10pC
-
PD pulse: time domain vs frequency domain
ideal PD-impulse:
a) time domain display of current i(t) T1 time to the maximum of the current (imax)T2 time to the declining half of imax
b) normalized amplitude density F()/F(0)1) T1/T2 = 1 s/5 s2) T1/T2 = 5 ns/50 ns3) T1/T2 = 5 ns/15 ns
a)
T1
i (t)
imax
imax/2
T2t
b)
0103 104 105 106 107 109Hz
0,5
1,5
F()
F(0)
1
2
3
-
Partial discharge breakdown
> PD occurs as a consequence of :
> local heating (creation of voids)
> abrasion
> delamination
> mechanical stress (vibration)
> defects in the material
> water treeing
> high electric field strength
-
This one...
-
Introduction
> ...For many years, the measurement of PD has been employed as a sensitive means of assessing the quality ... and localize sources of PD in used electrical winding insulation ...
> ... Compared with other dielectric tests (i.e. the measurement of dissipation factor or insulation resistance) the differentiating character of partial discharge measurements allows localized weak points of the insulation system to be identified...
-
Introduction
> ...The PD testing ... is also used when inspecting the quality of new assembled ... stator windings, new ... components (e.g. form-wound coils and bars, HV bushings, etc..) and fully impregnated stators...
> ...PD can provide information on> points of weakness in the insulation system> ageing processes> further measures and intervals between overhauls
-
Introduction
> Partial discharge testing of stator windings can be divided into two broad groups:
a. Off-line measurements, in which the stator winding is isolated from the power system and a separate power supply is employed to energize the winding;
b. On-line measurements, in which the rotating machine is operating normally and connected to the power system.
> Both of these approaches have advantages and disadvantages...
Annex Aand
IEC 60034-27-2
-
Introduction LIMITATIONS
> ... different types of PD measuring instruments will inevitably produce different results ...
> ... PD measurements will only be comparable under certain conditions ...
> ... absolute limits for the windings of rotating machines, for example as acceptance criteria for production or operation, are difficult to define ...
> Pulse propagation phenomena> Difficulties with calibration> Individual frequency response characteristics> Type of PD source> Location within the stator
-
Introduction LIMITATIONS
> ... Empirical limits verified in practice can be used as a basis for evaluating test results ...
> ... PD trend evaluation and comparisons with machines of similar design and similar insulation system measured under similar conditions, using the same measurement equipment
> ... not all insulation-related problems in stator windings can be detectedby measuring PD (e.g. insulation failures involving continuous leakage currents due to conductive paths between different elements of the insulation or pulseless discharge phenomena) ...
-
1 Scope
> Measuring techniques and instruments,
> The arrangement of test circuits,
> Normalization and testing procedures,
> Noise reduction,
> The documentation of test results,
> The interpretation of test results
> Test with AC ... bars or form wound coils with (without) conductive slot coating...
> Voltage rating >= 6kV
-
2 Normative references
> IEC 60060-1, High-voltage test techniques Part 1: General definitions and test requirements
> IEC 60060-2, High-voltage test techniques Part 2: Measuring systems
> IEC 60270:2000, Partial discharge measurements
-
3 Definitions
> ... general terms and definitions for partial discharge measurements given in IEC 60270 apply...
> Offline measurement > Measurement taken with the rotating machine at standstill, the machine being
disconnected from the power system > Test voltage is ... from a separate voltage source.
> Online measurement > Measurement taken with the rotating machine in normal operation
-
3 Definitions (Coating)
> Stress control coating > Paint or tape on the surface of the groundwall insulation that extends beyond
the conductive slot portion coating in high-voltage stator bars and coils
> The stress control coating reduces the electric field stress along the winding overhang to below a critical value that would initiate PD on the surface. The stress control coating overlaps the conductive slot portion coating to provide electrical contact between them.
> Conductive slot coating > Conductive paint or tape layer in intimate contact with the groundwall insulation
in the slot portion of the coil side, often called semiconductive coating
> This coating provides good electrical contact to the stator core.
-
3 Definitions (PD types)
> Slot discharges > Discharges that occur between the outer surface of the slot
portion of a coil or bar and the grounded core laminations
> Internal discharges > Discharges that occur within the insulation system
> Surface discharges > Discharges that occur on the surface of the insulation or on
the surface of winding components in the winding overhang or the active part of the machine winding
-
3 Definitions (Evaluation)
> Pulse height distribution > The number of pulses within a series of equally-spaced windows of pulse
magnitude during a predefined measuring time
> Pulse phase distribution > The number of pulses within a series of equally-spaced windows of phase
during a predefined measuring time
> Partial discharge pattern > PD distribution map of PD magnitude vs a.c. cycle phase position, for
visualization of the PD behaviour during a predefined measuring time, in which specific PD parameters are used for graphical representation
-
3 Definitions (Evaluation)
> Pulse height distribution
> Pulse phase distribution
> Partial discharge pattern
-
3 Definitions (Hardware)
> Coupling device > Usually an active or passive four-terminal network that
converts the input currents to output voltage signals
> These signals are transmitted to the measuring instrument by a transmission system. The frequency response of the coupling device is normally chosen at least so as to efficiently prevent the test voltage frequency and its harmonics from reaching the measuring instrument.
> PD coupling unit > A high voltage coupling capacitor
of low inductance design and a low voltage coupling device in series
-
3 Definitions (Numeric measures)
> Largest repeatedly occurring PD magnitude Qm > The largest magnitude recorded by a measuring system which has the pulse
train response in accordance with 4.3.3 of IEC 60270, or the magnitude associated with a PD pulse repetition rate of 10 pulses per second (pps), which can be directly inferred from a pulse height distribution.
-
3 Definitions (Numeric measures)
> Normalized quantity number NQN > Normalized area under a straight line fitted to the pulse counts in each
magnitude window of a pulse height analysis, in which the pulse counts are expressed as a logarithm of the pulses per second and the pulse magnitude window is a linear scale.
-
4 Nature of PD in rotating machines4.1 Basics of PD> ... where the dielectric properties of insulating materials are inhomogeneous ...
> ... local electrical over-stressing ...
> ... local, partial breakdown ...
> ... PD in general requires a gas volume to develop ...> Gas filled voids embedded in the insulation,> Voids adjacent to conductors> At insulation interfaces
> ... numerous PD pulses during one cycle of the applied voltage ...
> ... Stator winding insulation ... for HV machines will normally have some PD .., but are inherently resistant to partial discharges due to their inorganic mica components...
> ... PD in these machines is usually more a symptom of insulation deficiencies ...
> .. PD ... may also directly attack the insulation and thus influence the ageing process...
> ... The time to failure may not correlate with PD levels ...
-
4 Nature of PD in rotating machines
4.2 Types of PD> ... For a given machine, the various PD sources may be identified and distinguished
in many cases by their characteristic PD behaviour...
> Internal discharges> Internal voids> Internal delamination> Delamination between conductors and insulation> Slot discharges> End-winding surface discharges> Conductive particles
-
4 Nature of PD in rotating machines
-
A - Small voids on edgeB - Delamination: conductor main insulationC - Delamination of tape layersD - Treeing in layersE - Broken strandsF - Micro voidsG - Slot discharge, semicon paint abrasionH - Discharges in Cooling DuctI - Delamination of Insulation in ElbowJ - End winding surface discharge - contaminationK - Insufficient Spacing, Tracking and SparkingL - Connection area between slot corona protection and end winding corona protection
4 Nature of PD in rotating machines
-
4 Nature of PD in rotating machines
-
4.3 Pulse propagation in windings > ... PD current ... is a transient pulse with a rise time of only a few
nanoseconds ...
> ... high frequency spectrum ...
> ... stator windings represent objects with distributed elements in which travelling wave, complex capacitive and inductive coupling, and resonance phenomena occur ...
> ... attenuation, distortion, reflection and cross-coupling ...
> ... transmission function from the PD source to ... sensor is unknown and depends on the specific design of the machine ... Therefore, the energy at the source of the PD, which can be taken as a measure of the erosion of the insulation, cannot be measured directly ...
4 Nature of PD in rotating machines
-
PD pulse propagation
Two frequency components of the PD signals in a stator winding
Damping, reflection, attenuation
Amplitude of the pulse depends on:
> Calibration
> Ratio CK / CA
> Center frequency
> Propagation path
-
4 Nature of PD in rotating machines
4.3 Pulse propagation in windings > ... the individual high frequency
transmission behaviour of a stator winding produces PD signals at the terminals that are a characteristicof the machine being tested and of the location of the PD source ...
> ... very high frequency components of PD signals are subject to ...attenuation ... and ... might not be detectable at the terminals of the test object ...
-
5 Measuring techniques and instruments
5.2 Influence of frequency response of measurement system> ... measurement in the lower frequency range ensures good sensitivity
not only for partial discharges in bars/coils close to the sensor but also for those that originate from further away in the winding. However, the lower frequency range is more subjected to noise and disturbances ...
> ... measurement in the very high frequency range may acquire only a very small proportion of the total PD energy, which results in sensitivity to signals originating only very close to the sensor. However, this frequency range may be less susceptible to noise and disturbance. ...
> ... For off-line PD testing to obtain appropriate sensitivity to PD from the whole winding it is advisable to use wide band PD measuring systems. The lower cut-off frequency should be in the range of several tens of kHz in accordance with IEC 60270. ...
-
5 Measuring techniques and instruments
5.3 Effects of PD coupling units> ... HV capacitor, coupling device, transmission system and input
impedance of the measurement system represent a high-pass filter. Therefore, increased input impedance or higher capacitance values lead to an increased sensitivity...
-
5 Measuring techniques and instruments
5.4 Wide-band and narrow band measuring systems
Superposition errors!
f >100kHz ... 1MHz
-
6 Visualization of measurements
6.2 Data presentation> PD magnitude [pC or mV]
> r.m.s. value of test voltage
> Inception voltage Ui (PDIV)
> Extinction voltage Ue (PDEV)
> Curve Qm = f(U)
U/Umax
Noise level
PDEV PDIV
Specified threshold for PDIV and PDEV
-
6 Visualization of measurements
6.3 Additional means of PD data representation
> ... Additional quantities ... like integrated charge, discharge current, quadratic rate, PD power, and PD energy ...
> ... pulse height distribution, pulse phase distribution, phase resolved pulse height distribution, oscillograms of pulse trains, PD distribution maps, etc.... CIGRE technical brochure 226 ...
Part V: Generator Stator Insulation
-
6 Visualization of measurements
> 6.3.2. PRPD pattern> ... a 2-dimensional PD distribution map (-q-n pattern) is employed for
visualization ...
-
7 Test circuits
> HV power supply conforming to IEC 60060-1 and IEC 60060-2; > A voltage measuring device; > A suitable PD coupling unit; > A connection cable from the measuring impedance to the PD device with
sufficiently low damping characteristics and good shielding; > A partial-discharge measuring system; > High-voltage connections.
> ... sufficiently PD free...
Example: IEC 60060-1
IEC 60060-2: Measuring systems
-
7 Test circuits
> ... sufficiently PD free...
> ... To ensure that the test circuit does not influence the measurement of partial discharges from the test object, the arrangement should first be tested up to the maximum test voltage in accordance with the test procedure given in 9.1.6. The noise level produced by the complete test circuit at maximum required test voltage shall not exceed 100 pC when using the normalization procedure in accordance with Clause 8...
> ... The whole test circuit should be of a low-inductance arrangement. It is essential that ground loops are avoided. Low inductance leads are recommended as ground connections...
-
7 Test circuits
MI
Z
CC
CD
Ck
Ca
Zmi
U~
-
7 Test circuits
MI
Z
CC
CD
Ck
Ca
Zmi
U~
-
7 Test circuits Complete winding
> ... HV source and the PD coupling unit should be connected to oppositewinding terminals whenever possible, to utilize the advantage of the damping effect of the winding phases to suppress conducted interference from the power supply...
> ... The PD coupling unit should be installed as close to the winding terminals as possible...
> ... The stator core should normally be grounded...
-
7 Test circuits Complete winding
> Single winding energized, also measuring at the grounded windings
-
7 Test circuits Complete winding
Single winding energized, also measuring at the grounded windings (ground connection at far end).
-
PD measurement on stator winding
-
Online measurement with permanent couplers
-
7 Test circuits Complete winding
Phases not to be separated
Double length as filter
Phases not to be separatedPhases not to be separated
-
8 Normalization of measurements
> ... Due to pulse propagation, resonance and mutual cross coupling in machine windings, mentioned in 4.3, calibration is not possible...
> ... The aim of normalization is to ratio out various influences of the test circuit, for example power supply connections, stray capacitance, coupling capacitance and test object capacitance...
> ... Normalization is to ensure that the PD measuring system provides sufficient sensitivity to measure a specified value of PD magnitude correctly, as it appears at the machine terminals during the measurement, and to show that the PD detection system used, is responding in a repeatable fashion...
> ... comparisons between measurements on objects having the same design, taken with the same PD device...
> ... Normalization of the test circuit should be performed by injecting short-duration current pulses of known magnitude by means of a reference pulse generator (calibrator) ...
-
9 Test procedures
> Tests on complete windings
> Individual phases
> Individual winding components
> DUT disconnected from all external power supplies> Bus work> Surge arrestors> Surge capacitors> Excitation systems
> Test lead contact should always be at the machine terminals
> Same arrangement of all circuit components
> Same normalization procedure
-
9 Test procedures Equipment
> ... The waveform of the applied voltage should have Upp/Urms = 2 SQR(2) , 5% ...
> ... it is acceptable to perform PD tests at lower frequencies ... or at higher frequencies, 0.1Hz ... 400Hz
> ... PD results obtained from very-low frequency tests might significantly differ from that at power frequency and thus direct comparison might not be possible ...
-
9 Test procedures Preparation
> ... stator should be inspected for cleanliness ...
> ... sufficient air clearance between ...connections and ... cables ...
> ... check the insulation resistance before starting the PD test ... >100M ... [Mainly dirt, as dirt may influence PD behaviour]
> ... conductive slot coating should be in contact with ground potential throughout its whole length ... [for winding components]
> CONDITIONING!> ... PD will typically decrease during the first minutes ...> ... 5 min at the maximum test voltage is recommended ...> ... voltage may then be re-applied to start the partial discharge measurements
...
-
9 Test procedures Conditioning
Paschens Law
-
9 Test procedures Test voltages
> ... steps (e.g. U = 0,2 Umax) or ... continuous ramping (< 1 kV/s) up to ... Umax. ...
> ... dwell time on each step of at least 10s is recommended ...
-
9.1.6 PD test procedure
> ... level of background noise...should be obtained to ensure that the test arrangement has sufficiently low noise and PD up to the maximum testvoltage...
> ... replacing the test object by an appropriate discharge free capacitor ...
> ... Disturbances ... can be reduced or ... eliminated by appropriate measures ...
> ... localize such disturbance signals ...
> ... temperature detectors (RTDs) are anchored to the grounded stator frame ...
> ... the same connection point for the PD coupler, the test object and the measuring equipment should be used ...
> ... test arrangement as compact as possible ...
-
9.1.6.3 PD testing
> ... each voltage step, or during continuous ramping, the PD data ... should be recorded and processed ...
> ... Qm = f(U) curve ...
> PDIV
> PDEV
> ... distribution of pulse magnitudes, phase resolved distributions or specific PD patterns ... at various levels during test voltage increase and decrease ...
> ... Any comments or observations during the test should be recorded ...
> ... an appropriate sequence of standard measurements and ... extended measurements ... should be taken ...
-
9.2 PD location and ID
> ... Following the per-phase test... energize simultaneously all three phases of the winding ... [ No PD from end winding]
> ... subdivide the winding ...
> ... Electromagnetic probes ...> scanning of stator slots > machine end-winding> conduit boxes> cable routing> termination boards> stand-off insulators, etc.
> ... probes can disrupt the electric field ...
> ... additional safety requirements ...
-
10 Interpretation
> ... it has to be decided whether there are ... defects and ... what they imply regarding the performance of the insulation system, whether any supplementary tests are needed and the planning and/or implementation of any essential corrective maintenance. ...
> ... significant variations in the amounts of partial discharges depending on the individual properties of the machine being tested. As a result, a directcomparison of different types of machine in terms of absolute values is notpossible. ...
> ... Neither is it possible to establish any absolute limits for complete windings ...
-
10 Interpretation
> ... the PD site, which produces the highest PD magnitude is not necessarily the location in the winding being at most risk ...
> ... PD magnitude as a function of test voltage provides a simple and effective means of characterizing typical dominating PD sources ...
> ... Interpretation is always comparative ...
> ... meaningful interpretation for complete windings ...> Trending Qm on the same stator over time> Comparing Qm from several stators with the same design> Comparing Qm between different phases of one stator
> ... the higher the PDIV and PDEV ... the less insulation deficiencies ...
-
10 Interpretation
Trend in PD in a machine over time
> ... Initial fingerprint ... when the winding is new ...
> ... If the winding deteriorates ... Qm will usually increase over time ...
> ... Compare the PD quantities ... between windings ...
> Limitations> ... a new stator may have relatively high PD that decreases after the first 5000
to 10000 equivalent operating hours ...> ... same voltage, temperature and similar humidity conditions ...> ... variations of Qm of a certain percentage, for example 25 %, are normal
...
> Why?: ... That is, for example, Qm for the winding at the specified test voltage is lower than 95 % of the mean Qm magnitudes achieved by the manufacturer on the same windings they have made in the past....
-
10.3 Pattern recognition
> ... When using the -q-n patterns, it may be possible to separate various PD sources from each other, to assess the related risk and to trend them separately ...
> ... weight their risk separately ...
> Observe the trend behaviour of each PD source
> Localize the various PD phenomena
> Provide rough information concerning location for pinpointing
> Assess the insulation condition, depending on PD source and PD location.
-
3CFRD
Disturbance PD Noise
-
PRPD pattern shows multiple sources
L2
L1 L3
-
Separation of sources by 3PARD
3PARD = Three Phase Amplitude Relation Diagram
-
Inner PD source in L1 in 3PARD
Inner PD Source L1>L2>L3
L1
L2 L1
L2
L3
3PARD
timeframe 1 s
Inner PD Source in L1
L3
-
Outer noise in 3PARD
L2
L3
3PARD
Outer Noise
L1
L1
L2
L3
timeframe 1 s
Outer Noise L1 L2 L3
-
213
PD measurement on Stator Winding and calibrationLocalization: difficult
2
ttVelocitySignalLD 12 2
ttVelocitySignalLD
1.1unit2.1unit
rr
0cVelocitySignalPH
TDR TDD
-
March 5, 2015
Field diagnostics and diagnostic monitoring of HV insulation at generators, motors, transformers and cables (part II)
-
Page 2
Topics
Page 2
> Transformer
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities
> HV Cables
Lifetime expectations
Faults and Aging
Measurement & monitoring parameters /quantities
-
Seite 3 OMICRON
Field Diagnostics & diagnostic monitoring of transformers
-
Seite 4 OMICRON
Life Time expectation
When a Transformer is operated under ANSI / IEEE basic loading conditions (ANSI C57.96), its normal life expectancy is about 20 years. The ANSI / IEEE basic loading conditions for Transformer are:
i. The Transformer is continuously loaded at rated kVA (kilo Volt Ampere) and rated Voltages (Transformer must be operated at the rated Voltage and kVA)
ii. The average temperature of the ambient air during any 24-hour period is equal to 30C (86 F) and at no time exceeds 40C (104 F).
iii. The height where the transformer is installed, does not above 3300 feet or 1000 meters
-
Seite 5 OMICRON
Transformer Breakdowns
-
Seite 6 OMICRON
Faults in Transformers
Win
ding
Cor
e Bus
hing
Vess
el &
Oil
Acc
esso
ries
Tap
Cha
nger
Source: Cigre_WG 12-05 An international survey on failures in large power transformers in service, Electra No. 88, 1983
-
Condition and Time based maintenance
Time
Insu
latio
n st
reng
th New condition
Operating stress
Time based maintenance
Diagnostic levelCondition based maintenance
Condition based maintenance requires reliable diagnostic tools
-
Seite 8 OMICRON
Possible Impacts by lack of maintenance
Life of the Transformer
Baseline data not recorded Problems during warranty period not detected OLTC contacts wear Oil oxidation begins Fan and Pump bearing wear Visible effects of weathering and UV Oil decay products affect paper insulation Miss opportunity to intercept accelerated ageing Oxidation and hydrolysis enters accelerated ageing state OLTC and bushing failure rates increase Dielectric withstand diminishes Expensive failure (bushing, OLTC)
-
Seite 9 OMICRON
Overview: Transformer Measurements
-
Maintenance Intervals
Action Task Interval Remark
Light Regular IntensiveVisit 6 m 1 m 1 d In service
Detailed inspection (visual)
1 y 3 m 2 w In service
DGA 2 y 1 y 3 m Task interval may differ with monitoring
Oil Test 6 y 2 y 1 y
Cooling system cleaning
Conditional Conditional Any interval Outage may be required
Accessories verification
12 y or conditional
6-8 y 1-2 y Outage required
Electrical basic tests Conditional Conditional Any interval Outage required
Insulation tests (DF) Conditional 6-8 y 2-4 y Outage required
OLTC inspection 12 y 6-8 y 4 y
-
Seite 11 OMICRON
Overview: Transformer MeasurementsType of ProblemMagnetic Circuit Integrity
Magnetic Circuit Insulation
Winding Geometry
Winding/Bushing/OLTC Continuity
Winding/Bushing Insulation
Winding Turn to Turn Insulation
Diagnostic Technique
Bas
ic E
lect
rical
Winding Ratio x
Winding Resistance x
Magnetisation Current x x
Capacitance and DF/PF x x x x
Leakage Reactance x
Insulation Resistance x x
Core Ground Test x
Adv
ance
d El
ectr
ical
Frequency Response of Stray Losses x x
Frequency Response Analysis x x x x
Polarisation/Depolarisation x
Frequency Domain Spectroscopy x
Recovery Voltage Method x
Electrical Detection of PD x x
Acoustical detection of PD x x
UHF Detection of PD x x
Dissolved Gas Analysis x x x x x
-
Assessment and Interpretation
Indication RBP OIP RIP
increase of capacitance oil in cracksor partial breakdowns partial breakdowns partial breakdowns
high dissipation factor
partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;
partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;
partial breakdowns;insulator surface wet or dirty (clean the insulator);ageing of the inner insulation;water in the inner insulation;
dissipation factor is decreasing withincreasing voltage
bad potential connections;partial breakdowns
bad potential connections;partial breakdowns
bad potential connections;partial breakdowns
dissipation factor isstrongly increasing with increasing temperature
high moisture in the insulation;high degree of ageing
high moisture in the insulation;high degree of ageing
high moisture in the insulation;high degree of ageing
partial discharges normal, if constant
Discharges produce gasses;Errosion of the cellulose;production of x-wax
partial breakdowns;cracks or voids after electrical or mechanical stress;
-
Seite 13 OMICRON
Overview: Transformer Measurements
> Turns Ratio
> Exciting Current
> Winding Resistance (Dynamic and Static)
> Short Circuit Impedance (+FRSL)
> C & DF (Winding, Bushing and Oil sample)
> Moisture Determination in liquid and solid insulation
> Frequency Response Analysis Partial Discharge
-
0nF
5nF
10nF
15nF
20nF
25nF
30nF
0V
2000V
4000V
6000V
8000V
1000
0V
1200
0V
1400
0V
H(V) HL(V) L(V)
0.2%
0.25%
0.3%
0.35%
0.4%
0.45%
0.5%
0V
2000V
4000V
6000V
8000V
1000
0V
1200
0V
1400
0V
H(V) HL(V) L(V)
OMICRON
Tan delta(voltage sweep)
Capacitance (voltage sweep)
Cap
acita
nce
V
Pow
er fa
ctor
/ di
ssip
atio
n fa
ctor
(tan
del
ta)
V
Transformer power and dissipation factor (tan delta) + insulation capacitancePower transformer diagnosis
Automated testing with test templates and reporting with ExcelTM
-
0%
0.1%
0.2%
0.3%
0.4%
0.5%
0.6%
0.7%
0Hz
50H
z
100
Hz
150
Hz
200
Hz
250
Hz
300
Hz
350
Hz
400
Hz
450
Hz
H(f) HL(f) L(f)
OMICRON
0%
0.1%
0.2%
0.3%
0.4%
0.5%
0.6%
0Hz
50H
z
100
Hz
150
Hz
200
Hz
250
Hz
300
Hz
350
Hz
400
Hz
450
Hzff
New transformer Transformer with aged oil
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
Increased power factor / dissipation factor especially
at low frequencies
H(f) HL(f) L(f)
Transformer power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz
Advanced diagnostics
Additional diagnostics revealed through frequency sweep from 15 Hz to 400 Hz.
-
OMICRON
Transformer power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz
Advanced diagnostics
Advantages
> Faster and more reliable assessment of transformer and bushing conditions (aging)
> Shows additional details not obtainable from single power factor measurements:
> Determines whether moisture contamination is in the cellulose or if the oil is contaminated or otherwise compromised.
> Effective discrimination between a deteriorated power factor test result that warrants more frequent monitoring and one that requires immediate remediation.
> Faster fault localization
-
0.24%0.25%0.26%0.27%0.28%0.29%
0.3%0.31%0.32%
0 V
2000
V
4000
V
6000
V
8000
V
1000
0 V
1200
0 V
1400
0 V
A B C
0.5%
0.6%
0.7%
0.8%
0.9%
1%
1.1%
0V
2000V
4000V
6000V
8000V
1000
0V
1200
0V
1400
0V
A B C
New bushing Bad bushing
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
V
OMICRON
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
V
Inmost layer was not connected to the HV conductor properly.
Bushing power and dissipation factor (tan delta) + insulation capacitancePower transformer diagnosis
-
0.25%
0.35%
0.45%
0.55%
0.65%
0.75%
0.85%
0Hz 100Hz 200Hz 300Hz 400Hz 500Hz
f
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta) only fNOM values
Aged bushing
Medium-aged bushing
New bushing
OMICRON
Condenser type bushing (220 kV RIP)
Bushing power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz
Advanced diagnostics
Additional diagnostics revealed through frequency sweep from 15 Hz to 400 Hz.
-
OMICRON
0.4 %
0.45 %
0.5 %
0.55 %
0.6 %
0 H
z
50 H
z
100
Hz
150
Hz
200
Hz
250
Hz
300
Hz
350
Hz
400
Hz
450
Hz
1 2 3 4 5 6
f
Pow
er fa
ctor
/ di
ssip
atio
nfa
ctor
(tan
del
ta)
Oil-impregnated bushings (OIP)
Bushing power and dissipation factor (tan delta)with variable frequency from 15 Hz to 400 Hz
Advanced diagnostics
Looking at the whole frequency range shows that four bushings have aged considerably. At lower frequencies there is an
extreme increase in the dissipation factor (tan delta).
-
OMICRON
Insulating fluids (oil test cell) power and dissipation factor (tan delta)Power transformer diagnosis
Testing the insulation condition of oil
-
Exciting current per tap changer position
0.001 A
0.0015 A
0.002 A
0.0025 A
0.003 A
0.0035 A
0.004 A
0.0045 A
0 5 10 15 20 25 30
A B C
OMICRON
Tap changer position
Exci
ting
curr
ent
Exciting current and phase angle per tap
Exciting current per tapPower transformer diagnosis
-
OMICRON
OLTCPosition
DETCPosition
Phase AI out [mA]
WattLoss [W]
Reactance(+/-jX)[k]
Phase BI out[mA]
WattLoss[W]
Reactance(+/-jX)[k]
Phase CI out [mA]
WattLoss [W]
Reactance(+/-jX)[k]
PatternRating
1 0 61,56 573,22 67,62 42,81 396,23 88,42 59,00 540,12 67,43 NONE
2 0 62,62 569,87 66,09 44,31 410,38 86,00 61,12 559,15 66,15 NONE
3 0 64,79 588,69 64,45 45,79 422,97 83,65 63,23 577,36 64,53 NONE
4 0 67,05 608,41 62,72 47,44 438,60 81,21 65,46 596,85 62,81 NONE
5 0 70,51 625,79 60,10 49,08 452,48 78,84 67,80 617,27 61,04 NONE
6 0 71,89 651,07 59,04 50,92 469,99 76,44 70,24 638,84 59,23 NONE
7 0 74,44 673,86 57,11 52,74 486,24 73,79 72,79 661,55 57,33 NONE
8 0 77,18 698,20 55,26 54,69 503,53 71,31 75,56 685,89 55,56 NONE
9 0 80,07 724,07 53,37 56,78 522,56 68,86 78,47 711,65 53,72 NONE
10 0 82,97 750,83 51,35 58,97 542,90 66,22 81,55 739,10 51,88 NONE
11 0 86,33 780,10 49,64 61,28 564,43 63,40 84,81 768,08 50,05 NONE
0 mA
20 mA
40 mA
60 mA
80 mA
100 mA
1 2 3 4 5 6 7 8 9 10 11
A
B
C
Tap changer position
Exci
ting
curr
ent
0 W
200 W
400 W
600 W
800 W
1000 W
1 2 3 4 5 6 7 8 9 10 11
A
B
C
Tap changer position
Wat
t los
ses
Measurement and report table
Exciting current per tapPower transformer diagnosis
-
OMICRON
12
13
14
15
16
17
000 005 010 015 020
A
B
C
Rat
io
Tap
Settings: transformer ratio per tap
Transformer turns ratio (TTR) per tapPower transformer diagnosis
-
-0.08 %
-0.06 %
-0.04 %
-0.02 %
0.00 %
0.02 %
0.04 %
0 5 10 15 20
A
B
C
0.002 A
0.004 A
0.006 A
0.008 A
0.01 A
0 5 10 15 20
ABC
TRRatio: A
Date/Time: 02.05.2008 13:22
Overload: NO
Assessment: n/a
Range: AC 2kV
Nominal values:
Frequency: 50,0Hz
V test: 1000,0V
Tap V prim. Nom.Vsec.nom.
Ratio nom. V prim. Vsec. Ratio I prim.
001 449610,0/3V 15750,0V 16,4814:1 999,59V 0,0 60,636585V 0,0 16,4849:1 -0,02% 0,004566A -40,71
002 444890,0/3V 15750,0V 16,3084:1 999,74V 0,0 61,285938V 0,01 16,3127:1 -0,03% 0,004625A -41,18
003 440170,0/3V 15750,0V 16,1354:1 999,79V 0,0 61,947819V 0,0 16,1392:1 -0,02% 0,004721A -41,48
004 435440,0/3V 15750,0V 15,962:1 999,85V 0,0 62,622185V 0,0 15,9664:1 -0,03% 0,004791A -41,86
005 430720,0/3V 15750,0V 15,789:1 999,83V 0,0 63,309776V -0,01 15,7927:1 -0,02% 0,004902A -42,1
006 426000,0/3V 15750,0V 15,616:1 999,81V 0,0 64,010597V -0,01 15,6194:1 -0,02% 0,005008A -42,35
007 421280,0/3V 15750,0V 15,4429:1 999,78V 0,0 64,727524V -0,01 15,446:1 -0,02% 0,005097A -42,77
008 416560,0/3V 15750,0V 15,2699:1 999,89V 0,0 65,464005V -0,01 15,2739:1 -0,03% 0,005211A -42,96
009 411830,0/3V 15750,0V 15,0965:1 999,6V 0,0 66,197601V -0,01 15,1002:1 -0,02% 0,005334A -42,71
010 407110,0/3V 15750,0V 14,9235:1 999,78V 0,0 66,981621V 0,01 14,9262:1 -0,02% 0,005422A -43,33
011 402390,0/3V 15750,0V 14,7505:1 999,73V 0,0 67,760643V 0,0 14,7538:1 -0,02% 0,00568A -45,03
012 397670,0/3V 15750,0V 14,5775:1 999,83V 0,0 68,570297V 0,0 14,5811:1 -0,02% 0,005816A -45,37
013 392950,0/3V 15750,0V 14,4044:1 999,78V 0,0 69,396141V -0,02 14,4069:1 -0,02% 0,005939A -45,7
014 388230,0/3V 15750,0V 14,2314:1 999,74V 0,0 70,235367V 0,0 14,2341:1 -0,02% 0,006073A -45,83
015 383500,0/3V 15750,0V 14,058:1 999,79V 0,0 71,101517V 0,0 14,0614:1 -0,02% 0,006229A -46,1
016 378780,0/3V 15750,0V 13,885:1 999,72V 0,0 71,986328V 0,0 13,8876:1 -0,02% 0,006361A -46,33
017 374060,0/3V 15750,0V 13,712:1 999,78V 0,0 72,902046V -0,01 13,714:1 -0,01% 0,00651A -46,59
018 369340,0/3V 15750,0V 13,539:1 999,79V 0,0 73,832764V -0,01 13,5413:1 -0,02% 0,006659A -46,73
019 364620,0/3V 15750,0V 13,3659:1 999,75V 0,0 74,779701V -0,01 13,3693:1 -0,02% 0,006823A -46,88
Taps
OMICRON
Rat
io d
evia
tion
Exci
ting
curr
ent
Taps
Transformer turns ratio (TTR) per tapPower transformer diagnosis
Transformer in good condition
-
OMICRON
> Tremendous time-saver: removes the need to change test connections between tests
> Automatically operates the tap changer
> Quickly discharges the transformer
> Increases safety by reducing the risk of accidents
> Minimizes the likelihood of measurement errors
> Automated ratio and winding resistance tests
> Manual operation mode: allows measurements for special applications (e.g. auto transformer tests)
Transformer turns ratio (TTR) per tapPower transformer diagnosis
Automated measurement with switch box CP SB1
-
OMICRON
Leakage reactance / short circuit impedancePower transformer diagnosis
Determination of winding or core deformation due to high fault currents
-
OMICRON
Equivalent circuit diagram: effective resistance and reactance
Forces
10 kV winding 220 kV windingLeakage flux
Leakage reactance / short circuit impedancePower transformer diagnosis
Forces in a transformer, especially in case of a short circuit, can damage windings and the core.
-
Factory Test with W-Meter 3-Phase Measurement
SN [kVA] Pk [kW] f [Hz] Tap Position: UHV [kV] ULV [kV] uk [%] Uk [kV]
6500 34.5 50 1 51.7 27.2 6.250 1.9
Three Phase Equivalent Test CPC 100 Measurement
f [Hz] V1 AC [V] I AC [A] Z [] Phi [] R [] X [] L [mH]A-B 50 55.224 1.049 25.7019 85.01 2.2370 25.6044 81.50B-C 50 54.675 1.048 25.8922 85.24 2.1470 25.8030 82.13A-C 50 54.464 1.048 25.2547 84.96 2.2196 25.1570 80.08
Average Impedance
f [Hz] uk [%] Z [] Phi [] R [] X [] xk [%] L [mH]Factory Test Values: 50 6.250 25.7009 85.13 2.1826 25.6080 6.227 81.51Measured Values: 50 6.229 25.6162 85.07 2.2012 25.5215 6.206 81.24
Difference to Factory Test [%] -0.33 -0.33 -0.07 0.85 -0.34 -0.34 -0.34
Per-Phase Test CPC 100 Measurement
f [Hz] V1 AC [V] I AC [A] Z [] Phi [] R [] X [] L [mH]A-B 50 25.061 1.010 24.5892 84.37 2.4102 24.4708 77.89B-C 50 25.337 1.011 24.8397 84.54 2.3641 24.7270 78.71A-C 50 25.485 1.010 24.9888 84.44 2.4224 24.8711 79.17
Average Impedance24.8059 2.3989 24.6896 78.5896
Maximum delta of Average [%] 0.87 1.45 0.89 0.89
OMICRON
Factory test data
Measurement in accordance to IEEE Std C57.12.90
Factory test and measurement comparison
Per-phase test
Leakage reactance / short circuit impedancePower transformer diagnosis
-
OMICRON
Frequency
Mea
sure
d re
sist
ance
Frequency response of stray losses (FRSL)Advanced diagnostics
This test is automatically performed with the leakage reactance / short circuit impedance test.
R is frequency-dependent due to eddy losses (induced currents) in the windings which will increase with the frequency.
-
OMICRON
B
HV winding
LV winding
Losses through induced currents
Frequency response of stray losses (FRSL)Advanced diagnostics
Parallel strands without twisting
-
OMICRON
B
HV winding
LV winding
Induced currents are compensated
Parallel strands with twisting
Frequency response of stray losses (FRSL)Advanced diagnostics
Parallel strands with twisting compensate the induced currents.
-
OMICRON
B
HV winding
LV winding
Additional losses through induced currents
Frequency response of stray losses (FRSL)Advanced diagnostics
If the twisted strands are shorted additional losses will occur due to induced currents.
-
0
1
2
3
4
5
0Hz 100Hz 200Hz 300Hz 400Hz
ZkAB ZkBC ZkAC
18.8mH
19.2mH
19.6mH
20mH
20.4mH
0Hz 100Hz 200Hz 300Hz 400Hz
ZkAB ZkBC ZkAC
f
Three phase equivalent
f
R L
Three phase equivalent
OMICRON
Frequency response of stray losses (FRSL)Advanced diagnostics
The deviation of the resistance Rk,AC indicates short circuit parallel strands in the left diagram.
-
OMICRON
Tap changer
Connection clampsTap selector
DC winding resistancePower transformer diagnosis
Measurement of winding resistance and internal contacts
-
OMICRON
0.14
0.15
0.16
0.17
0.18
0.19
0 5 10 15 20 25 30
Rmeas
0.14
0.15
0.16
0.17
0.18
0.19
0 5 10 15 20 25 30
Rref Rmeas
Tap changer in good condition
Taps
Defective contacts in the tap selector
Win
ding
resi
stan
ce
Win
ding
resi
stan
ce
Taps
DC winding resistancePower transformer diagnosis
Measurement example
The contacts which were used in taps1, 3, 5, 23, 25, and 27 were defective.
-
OMICRON
Transformer demagnetizationPower transformer diagnosis
Influence of remanence
0.0A
0.002A
0.004A
0.006A
0.008A
0.01A
0.012A
0.014A
0.016A
0.018A
0.02A U with remanenceV with remanenceW with remanenceU without remanenceV without remanenceW without remanence
Initial FRA verificationAfter DC testAfter demagnetization
Exciting current Frequency response anaylsis
-
OMICRON
Dynamic LTC diagnostics with CP SB1 (OLTC test)Advanced diagnostics
-
4.7 A
4.8 A
4.9 A
5.0 A
5.1 A
-0.05 s 0 s 0.05 s 0.1 s 0.15 s 0.2 s 0.25 s 0.3 s 0.35 s
OMICRON
Ripple
Slope
Transient current during switching process
Time
Cur
rentDiverter switch switches to the
first commutating or transition resistor
Both commutating resistors are in parallel
Final contact of the diverter contact B is reached
Current control of the CPC 100 regulates the current to the nominal test current again
Dynamic LTC diagnostics with CP SB1 (OLTC test)Advanced diagnostics
The transient switch is recorded and graphically displayed to find faults in the OLTC,