Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion processes The Rosemount OCX8800 Oxygen and Combustibles Transmitter provides continuous, accurate measurement of combustion flue in a single, easy-to-install transmitter design. The patented Rosemount zirconia oxygen sensor coupled with a combustibles sensor using catalytic bead technology provide the basis for measurement in flue gases with temperatures up to 2600 °F (1427 °C).

Upload: doque

Post on 29-Aug-2019

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Product Data Sheet00813-0100-4880, Rev AB

May 2019

Rosemount™ OCX8800Oxygen and Combustibles Transmitter

Continuous, accurate measurement for combustion processes

The Rosemount OCX8800 Oxygen and Combustibles Transmitter provides continuous, accuratemeasurement of combustion flue in a single, easy-to-install transmitter design. The patented Rosemountzirconia oxygen sensor coupled with a combustibles sensor using catalytic bead technology provide thebasis for measurement in flue gases with temperatures up to 2600 °F (1427 °C).

Page 2: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Overview

Proven performance and reliability■ Robust zirconia oxygen-sensing cell with catalytic platinized

beads increases cell lifetime in presence of sulfur and otherpoisoning agents.

■ Robust COe sensor features a large active surface area anddilution air for accurate readings even in reducingconditions.

■ Compact explosion-proof housings that are easy to mountdirectly to the process.

Adaptable to a range of processes

■ FOUNDATION™ Fieldbus and HART® communication protocoloptions allow technicians to view diagnostic and operationalinformation from the control room.

■ The local operator interface (LOI) enables localcommisioning and maintenance and permits visibility todiagnostics without additional tools.

■ Integral or remote-mounted electronics and auto-calibration options simplify routine maintenance tasks.

May 2019

2 Rosemount OCX8800

Page 3: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Ordering information

Rosemount™ OCX88A Oxygen /Combustibles Transmitter - General Purpose

Model Product description

OCX88A Oxygen /Combustibles Transmitter

Probe length and material

00 No probe or exhaust tube

11 18 in. (457 mm) 316 stainless steel, rated up to 1300 °F (704 °C)

12 3 ft (0.91m) 316 stainless steel, rated up to 1300 °F (704 °C)

13 6 ft (1.83 m) 316 stainless steel, rated up to 1300 °F (704 °C)

14 9 ft (2.74 m) 316 stainless steel, rated up to 1300 °F (704 °C)

21 18 in. (457 mm) Inconel 600, rated up to 1832 °F (1000 °C)

22 3 ft (0.91 m) Inconel 600, rated up to 1832 °F (1000 °C)

23 6 ft (1.83 m) Inconel 600, rated up to 1832 °F (1000 °C)

24 9 ft (2.74 m) Inconel 600, rated up to 1832 °F (1000 °C)

31 18 in. (457 mm) ceramic, rated up to 2600 °F (1426 °C)

32 3 ft (0.91 m) ceramic, rated up to 2600 °F (1426 °C)

Probe mounting assembly

10 Standard O2 Cell - ANSI (4 ¾" Dia. Bolt Circle, 6" Dia. Flange,with 4 x ¾" Dia. Holes)

11 High Sulfur O2 Cell - ANSI (4 ¾" Dia. Bolt Circle, 6" Dia. Flange,with 4 x ¾" Dia. Holes)

20 Standard O2 Cell - DIN (145mm Dia. Bolt Circle, 185mm Dia.Dlange, with 4 x 18mm Dia. Holes)

21 High Sulfur O2 Cell - DIN (145mm Dia. Bolt Circle, 185mm Dia.Dlange, with 4 x 18mm Dia. Holes)

Mounting hardware - stack side

0 No adapter plate (0 must also be chosen under MountingAdapter - Probe Side below)

1 New installation - square weld plate with studs

2 Mounting to Model 218/240 mounting plate (with Model218/240 shield removed)

3 Mounting to existing Model 218/240 support shield

4 Adapter Plate Required - Must Reference Adapter Plate PartNumber

5 Mounting to Model 132 adapter plate

Mounting hardware - probe side

0 No Additional Mounting Hardware

1 No Additional Mounting Hardware

May 2019

Product Data Sheet 3

Page 4: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

4 DIN Mounting Assembly

Electronic housing - NEMA 4X, IP66 HART® communications - std.

F1 Fieldbus communication, basic unit

F2 Fieldbus communication, local operator interface

F3 Fieldbus Communication - Blind Unit with AutocalibrationSolenoids

F4 Fieldbus Communication - Local Operator Interface andAutocalibration Solenoids

H1 HART communications, basic unit

H2 HART communications, local operator interface

H3 HART Communications, Blind Unit with AutocalibrationSolenoids

H4 HART Communications, Local Operator Interface andAutocalibration Solenoids

Electronic mounting(1)

01 Integral to sensor housing electronics

02 Split electronics with no cable

03 Split electronics with 20 ft (6 m) cable - rated up to 200 °C.Electronics mounting hardware included.

04 Split electronics with 40 ft (12 m) cable - rated up to 200 °C.Electronics mounting hardware included.

05 Split electronics with 60 ft (18 m) cable - rated up to 200 °C.Electronics mounting hardware included.

06 Split electronics with 80 ft (24 m) cable - rated up to 200 °C.Electronics mounting hardware included.

07 Split electronics with 100 ft (30 m) cable - rated up to 200 °C.Electronics mounting hardware included.

08 Split electronics with 150 ft (45 m) cable - rated up to 200 °C.Electronics mounting hardware included.

In-situ filter

0 None

1 Stainless Steel - Rated to 1000 °F (538 °C)

2 High Surface Area Stainless Steel - Rated to 1000 °F (538 °C)

3 Hastelloy - Rated to 1832 °F (1000 °C)

Accessories

0 None

1 Sample Probe Blowback, only

2 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet

3 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet, with Sample Probe Blowback

May 2019

4 Rosemount OCX8800

Page 5: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

4 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet, with Sample Probe Blowback, panel mounted

(1) For cold weather operation, preheat the instrument air by wrapping the stainless steel supply tubing around the heater neck several times andinsulate with the insulating scarf, PN - 6P00162H01. The entire sensor and electronics domes may also need to be separately insulated,depending on the temperatures and wind conditions. The dome insulation may be removed during the summer months.

May 2019

Product Data Sheet 5

Page 6: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Rosemount OCX88C Oxygen /Combustibles Transmitter - Explosion-Proof for Hazardous Area

Model Product description

OCX88C Oxygen /Combustibles Transmitter - Explosion-Proof (OCX 88C)

Probe length and material

00 No probe or exhaust tube

11 18 in. (457 mm) 316 stainless steel, rated up to 1300 °F (704 °C)

12 3 ft (0.91m) 316 stainless steel, rated up to 1300 °F (704 °C)

13 6 ft (1.83 m) 316 stainless steel, rated up to 1300 °F (704 °C)

14 9 ft (2.74 m) 316 stainless steel, rated up to 1300 °F (704 °C)

21 18 in. (457 mm) Inconel 600, rated up to 1832 °F (1000 °C)

22 3 ft (0.91 m) Inconel 600, rated up to 1832 °F (1000 °C)

23 6 ft (1.83 m) Inconel 600, rated up to 1832 °F (1000 °C)

24 9 ft (2.74 m) Inconel 600, rated up to 1832 °F (1000 °C)

31 18 in. (457 mm) ceramic, rated up to 2600 °F (1426 °C)

32 3 ft (0.91 m) ceramic, rated up to 2600 °F (1426 °C)

Probe mounting assembly

10 Standard O2 Cell - ANSI (4 ¾" Dia. Bolt Circle, 6" Dia. Flange,with 4 x ¾" Dia. Holes)

11 High Sulfur O2 Cell - ANSI (4 ¾" Dia. Bolt Circle, 6" Dia. Flange,with 4 x ¾" Dia. Holes)

20 Standard O2 Cell - DIN (145mm Dia. Bolt Circle, 185mm Dia.Dlange, with 4 x 18mm Dia. Holes)

21 High Sulfur O2 Cell - DIN (145mm Dia. Bolt Circle, 185mm Dia.Dlange, with 4 x 18mm Dia. Holes)

Mounting hardware - stack side

0 No adapter plate (0 must also be chosen under MountingAdapter - Probe Side below)

1 New installation - square weld plate with studs

2 Mounting to Model 218/240 mounting plate (with Model218/240 shield removed)

3 Mounting to existing Model 218/240 support shield

4 Adapter Plate Required - Must Reference Adapter Plate PartNumber

5 Mounting to Model 132 adapter plate

Mounting hardware - probe side

0 No Additional Mounting Hardware

1 No Additional Mounting Hardware

4 DIN Mounting Assembly

Electronic housing - NEMA 4X, IP66 HART communications - std.

F1 Fieldbus communication, basic unit

May 2019

6 Rosemount OCX8800

Page 7: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

F2 Fieldbus communication, local operator interface

F3 Fieldbus Communication - Blind Unit with AutocalibrationSolenoids

F4 Fieldbus Communication - Local Operator Interface andAutocalibration Solenoids

H1 HART communications, basic unit

H2 HART communications, local operator interface

H3 HART Communications, Blind Unit with AutocalibrationSolenoids

H4 HART Communications, Local Operator Interface andAutocalibration Solenoids

Electronic mounting(1)

01 Integral to sensor housing electronics

02 Split electronics with no cable

In-situ filter

0 None

1 Stainless Steel - Rated to 1000 °F (538 °C)

2 High Surface Area Stainless Steel - Rated to 1000 °F (538 °C)

3 Hastelloy - Rated to 1832 °F (1000 °C)

Accessories

0 None

1 Sample Probe Blowback, only

2 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet

3 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet, with Sample Probe Blowback

4 Calibration Flowmeter; Reference Gas Flowmeter & RegulatorSet, with Sample Probe Blowback, panel mounted

(1) For cold weather operation, preheat the instrument air by wrapping the stainless steel supply tubing around the heater neck several times andinsulate with the insulating scarf, PN - 6P00162H01. The entire sensor and electronics domes may also need to be separately insulated,depending on the temperatures and wind conditions. The dome insulation may be removed during the summer months.

May 2019

Product Data Sheet 7

Page 8: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

SpecificationsAll static performance characteristics are with operating variables constant. Specifications subject to change without notice.

OCX8800 Oxygen/comb transmitter

Performance Specifications

Net O2 range0-1% to 0-40%

Fully field-selectable via HART or LOI

Combustibles0-1000 ppm to 0-5%

Fully field-selectable via HART or LOI

AccuracyOxygen: ± .75% of reading or .05% O2, whichever is greater

Combustibles: ± 1% F.S. when calibrated at 0-5000 ppm range

System response to test gasOxygen: 10 sec T90

Combustibles: 25 sec T90

Calibration modes Semi-automatic or automatic

Calibration gases

Low O2: 0.4% O2, balance N2

High O2: 8% O2, balance N2

Combustibles: 1000 ppm CO, balance air

Regulate to 7 scfh (0.5 l/m)

Reference air 2 scfh (1 l/m), clean, dry, instrument-quality air (20.95% O2),regulated to 35 psi (238 kPa)

Eductor air 5 scfh (2.5 l/m), clean, dry, instrument-quality air (20.95% O2),regulated to 35 psi (238 kPa)

Dilution air 0.1 scfh (2.8 l/hr.), clean, dry, instrument-quality air (20.95%O2), regulated to 35 psi (238 kPa)

Blowback air (optional) Clean, dry, instrument quality air (20.95% O2) regulated to ≥ 60psi (413 kPa) or greater and ambient temperature of ≥ 0 °F (-18°C)

Functional Specifications

Table 1: Process Temperature Limits

Probe material Temperature range

316L stainless steel 0 to 704 °C (32-1300 °F)

Inconel 600 0 to 1000 °C (32-1832 °F)

Ceramic 0 to 1427 °C (32 to 2600 °F)

May 2019

8 Rosemount OCX8800

Page 9: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Table 2: Ambient Temperature Limits

Temperature range

Sensor housing -40° to 100 °C (-40° to 212 °F)

Electronics housing -40° to 65 °C (-40° to 149 °F)

Process pressure

Maximum process pressure 8” water column

Electrical

Electrictical noise EN 61326-1, Class A

Line voltage 100-240 VAC ± 10% 48-62 Hz

No switches or jumpers required

Isolated output O2, 4-20mAdc, 950 ohm maximum with HART capabilityCOMB, 4-20mAdc, 950 ohm maximum

Alarm output relay Logic Signals: dry contact, 30mA and 30 VDC capacity

SPA HART ALARM module (optional)

Low O2 alarm

High Comb alarm

Calibration status

Unit failure

Power consumption limits Heaters: 750 W nominal maximum

Electronics: 50 W nominal maximum

Physical Specifications

Materials of construction Enclosures: Low-copper aluminum

Mounting and mounting position Sensor housing: Flange

Electrical conduit size Sensor housing: Two 3/4 in - 14 NPT conduit ports

Electronic housing: Two 3/4 in - 14 NPT conduit ports

Table 3: Mounting Hardware and Adapter Plates

Outer diameter Bolt circle Studs

Square weld plate, ANSI studs 7.5 x 7.5 in. (190 x 190 mm) 4.75 in. (121 mm) 5/8 in. - 11

Square weld plate, DIN studs 6 x 6 in. (153 x 153 mm) 5.12 in. (130 mm) M12 X 1.75

Table 4: Shipping Weights

Probe length Approximate shipping weight

18 in. (457 mm) 54 lb (24.5 kg)

3 ft (0.91 m) 55 lb (24.5 kg)

May 2019

Product Data Sheet 9

Page 10: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Table 4: Shipping Weights (continued)

Probe length Approximate shipping weight

6 ft (1.83 m) 57 lb (26 kg)

9 ft (2.74 m) 59 lb (26.8 kg)

May 2019

10 Rosemount OCX8800

Page 11: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Dimensional drawingsFigure 1: Outline Dimensions for OCX 8800 Oxygen/Combustible Transmitter with Integral Electronics

A. Internal Local Operator Interface (LOI) has standard orientation as shown and can be rotated for desired orientation (90 °increments) for viewing through the window. Refer to manual for details.

May 2019

Product Data Sheet 11

Page 12: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

A. Dimension “A”B. Dimension “B” removal envelopeC. Mounting gasketD. Extractive ¼ NPT tube (0.D. = .54) Length:E. Exhaust tube (¼ NPT)F. Instrument air input

G. Calibration gas outputH. Allow 9.0 in. (228 mm) for cover removal

Table 5: Installation/Removal

Probe length Dim "A" insertion depth Dim "B" removal envelope

18 in. (457 mm) 18 in. (457 mm) 34 in. (864 mm)

3 ft (914 mm) 36 in. (914 mm) 52 in. (1321 mm)

6 ft. (1829 mm) 72 in. (1829 mm) 88 in. (2235 mm)

9 ft (2743 mm) 108 in. (2743 mm) 124 in. (3150 mm)

May 2019

12 Rosemount OCX8800

Page 13: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

A. ¾ NPT portsB. MTG. FlangeC. ⅛ npt air vent holeD. In-situ filter option

Figure 2: Electronics Housing

May 2019

Product Data Sheet 13

Page 14: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Figure 3: Sensor Housing

Table 6: Removal/Installation

Probe lenght Dim "A" insertion depth Dim "B" removal envelope

18 in. (457mm) 18.00 in. (457 mm) 34.00 in. (864 mm)

3 ft. (0.91m) 36.00 in. (914 mm) 52.00 in. (1321 mm)

6 ft. (1.83 m) Probes 72.00 in. (1829 mm) 88.00 in. (2235 mm)

9 ft. (2.74 m) Probes 108.00 in. (2743 mm) 124.00 in. (3150 mm)

May 2019

14 Rosemount OCX8800

Page 15: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

A. ⅝-11 STUDS (4) PLS EQ SP ON A 4.75 BCB. 2.50 minimum diagram in wallC. Weld or bolt adaptor plate to metal wall of stack or duct joint must be air tightD. Stack or duct metal wallE. Bolt adaptor plate to outside wall surfaceF. Field weld pipe to adaptor plateG. 3.50 O.D. REFH. Joint must be airtight

I. Outside wall surfaceJ. 3.00 schedule 40 pipe sleeve

K. Masonary stack wall

Table 7: Mounting Plate

ANSI DIN

Flange (x) 6.00 in. (153) 7.5 in. (190)

Stud size 5/8 in. - 11 M12 X 1.75

4 Studs Eq. Sp. on B.C. 4.75 BC 5.12 BC

May 2019

Product Data Sheet 15

Page 16: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Figure 4: Auto-Calibration Panel

Figure 5: Standard Stainless Steel and Hastelloy Filters

Figure 6: Stainless Steel High Surface Area Filter

May 2019

16 Rosemount OCX8800

Page 17: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Product certifications

European Directive informationA copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the ECDeclaration of Conformity can be found at Emerson.com/Rosemount.

Ordinary location certificationAs standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical,and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safetyand Health Administration (OSHA).

Installing equipment in North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment inZones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperatureclass. This information is clearly defined in the respective codes.

Rosemount™ OCX8800 Oxygen/Combustibles Transmitter (OCX88A) forgeneral purpose locations

USA

CSA

Certificate: 1602514

Standards: C22.2 No. 0-10 (September 2010), C22.2 No 94-M91 (R2006)

C22.3 No. 61010-1-12, CAN/CSA-C22.2 No. 60079-0:15

CAN/CSA-C22.2 No. 60079-1:16, ANSI/ISA-60079-0 (12.00.01)-2013

ANSI/ISA-60079-1 (12.22.01)-2009 (R2013)

ANSI/ISA-61010-1 (82.02.01) (Third Edition)

UL 50 (Tenth Edition)

Markings: Type 4X, IP66*

Special Conditions for Safe Use

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represent no more than that normally present in air.

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during thenormal operation of the equipment.

3. Flameproof joints are not intended to repaired.

May 2019

Product Data Sheet 17

Page 18: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

Canada

CSA

Certificate: 1602514

Standards: C22.2 No. 0-10 (September 2010), C22.2 No 94-M91 (R2006)

C22.3 No. 61010-1-12, CAN/CSA-C22.2 No. 60079-0:15

CAN/CSA-C22.2 No. 60079-1:16, ANSI/ISA-60079-0 (12.00.01)-2013

ANSI/ISA-60079-1 (12.22.01)-2009 (R2013)

ANSI/ISA-61010-1 (82.02.01) (Third Edition)

UL 50 (Tenth Edition)

Markings: Type 4X, IP66*

Special Conditions for Safe Use (X):

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represent no more than that normally present in air.

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during thenormal operation of the equipment.

3. Flameproof joints are not intended to repaired.

Rosemount™ OCX8800 Oxygen/Combustibles Transmitter (OCX88C) forHazardous Locations

USA

CSA

Certificate: 1602514

Standards: C22.2 No. 0-10 (September 2010), C22.2 No 94-M91 (R2006)

C22.3 No. 61010-1-12, CAN/CSA-C22.2 No. 60079-0:15

CAN/CSA-C22.2 No. 60079-1:16, ANSI/ISA-60079-0 (12.00.01)-2013

ANSI/ISA-60079-1 (12.22.01)-2009 (R2013)

ANSI/ISA-61010-1 (82.02.01) (Third Edition)

UL 50 (Tenth Edition)

Markings:

Class 1, Zone 1, Ex d IIB+H2 T3*

Class 1, Zone 1, AEx d IIB+H2 T3*

Type 4X, IP66**

*Sensor assembly enclosure: T3 (-40 °C <= Tamb <= +100 °C)

*Electronics assembly enclosure: T6 (-40 °C <= Tamb <= +65 °C)

*Integral configuration: T3 (-40 °C <= Tamb <= +65 °C)

Special Conditions for Safe Use

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represent no more than that normally present in air.

May 2019

18 Rosemount OCX8800

Page 19: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during thenormal operation of the equipment.

3. Flameproof joints are not intended to repaired.

Canada

CSA

Certificate: 1602514

Standards: C22.2 No. 0-10 (September 2010), C22.2 No 94-M91 (R2006)

C22.3 No. 61010-1-12, CAN/CSA-C22.2 No. 60079-0:15

CAN/CSA-C22.2 No. 60079-1:16, ANSI/ISA-60079-0 (12.00.01)-2013

ANSI/ISA-60079-1 (12.22.01)-2009 (R2013)

ANSI/ISA-61010-1 (82.02.01) (Third Edition)

UL 50 (Tenth Edition)

Markings:

Class 1, Zone 1, Ex d IIB+H2 T3*

Class 1, Zone 1, AEx d IIB+H2 T3*

Type 4X, IP66**

*Sensor assembly enclosure: T3 (-40 °C <= Tamb <= +100 °C)

*Electronics assembly enclosure: T6 (-40 °C <= Tamb <= +65 °C)

*Integral configuration: T3 (-40 °C <= Tamb <= +65 °C)

Special Conditions for Safe Use

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represent no more than that normally present in air.

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during thenormal operation of the equipment.

3. Flameproof joints are not intended to repaired.

Europe

ATEX

Certificate: KEMA 04ATEX2308 X

Standards: EN 60079-0:2012 + A11:2013

EN 60079-1: 2014

IEC 60079-0:2018

Markings: II 2G Ex db IIB + H2 T6 GB (split architecture – electronics assembly)

T3 Gb (split architecture – sensor assembly)

T3 Gb (integral version)

Special Conditions for Safe Use (X):

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represents no more than normally present in air.

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times atmospheric pressure during normaloperation.

May 2019

Product Data Sheet 19

Page 20: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

3. Flameproof joints are not intended to be repaired.

4. Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts.

International

IECEx

Certificate: IECEx CSA 10.0002X

Standards: IEC 60079-0: 2011

IEC 60079-1: 2014-06

Markings: Transmitter: Ex db IIB+H2 T6 Gb; Tamb: -40 °C to 65 °C

Sensor: Ex db IIB+H2 T3 Gb; Tamb: -40 °C to 100 °C

Integral Version: Ex db IIB+H2 T3 Gb; Tamb: -40 °C to 65 °C

Special Conditions for Safe Use

1. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gasmixture of which oxygen represents no more than normally present in air.

2. The pressure within the enclosure and gas lines shall not be higher than 1.1 times atmospheric pressure during normaloperation.

3. Flameproof joints are not intended to be repaired.

May 2019

20 Rosemount OCX8800

Page 21: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

May 2019

Product Data Sheet 21

Page 22: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

May 2019

22 Rosemount OCX8800

Page 23: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

May 2019

Product Data Sheet 23

Page 24: May 2019 Rosemount OCX8800 · Product Data Sheet 00813-0100-4880, Rev AB May 2019 Rosemount™ OCX8800 Oxygen and Combustibles Transmitter Continuous, accurate measurement for combustion

00813-0100-4880Rev. AB

May 2019

GLOBAL HEADQUARTERSEmerson Automation Solutions6021 Innovation BlvdShakopee, MN 55379, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

NORTH AMERICARosemount8200 Market BoulevardChanhassen, MN 55317

+1 800 999 9307

+1 952 949 7001

[email protected]

EUROPEEmerson Automation SolutionsNeuhofstrasse 19a P.O. Box 1046CH-6340 BaarSwitzerland

+ 41 (0) 41 768 6111

+ 41 (0) 41 768 6300

[email protected]

MIDDLE EAST AND AFRICAEmerson Automation SolutionsEmerson FZEJebel Ali Free ZoneDubai, United Arab Emirates, P.O. Box 17033

+971 4 811 8100

+971 4 886 5465

[email protected]

ASIA-PACIFICEmerson Automation Solutions1 Pandan CrescentSingapore 128461Singapore

+65 777 8211

+65 777 0947

[email protected]

Linkedin.com/company/Emerson-Automation-Solutions

twitter.com/rosemount_news

Facebook.com/Rosemount

youtube.com/RosemountMeasurement

©2019 Emerson. All rights reserved.

The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is amark of one of the Emerson family of companies. All other marks are the property of theirrespective owners.