measured values and parameters sunny boy …ansi/nfpa 70 or the canadian electrical code® csa...

56
HF_STP_Par-eng-TUS114810 | Version 1.0 CA US Measured Values and Parameters SUNNY BOY 2000HF-US/2500HF-US/3000HF-US Technical Description

Upload: others

Post on 11-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

HF_STP_Par-eng-TUS114810 | Version 1.0 CA US

Measured Values and ParametersSUNNY BOY 2000HF-US/2500HF-US/3000HF-USTechnical Description

Page 2: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,
Page 3: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC Legal Restrictions

Technical Description HF_STP_Par-eng-TUS114810 3

Copyright © 2011 SMA America, LLC. All rights reserved.No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior written permission of SMA America, LLC.Neither SMA America, LLC nor SMA Solar Technology Canada Inc. makes representations, express or implied, with respect to this documentation or any of the equipment and/or software it may describe, including (with no limitation) any implied warranties of utility, merchantability, or fitness for any particular purpose. All such warranties are expressly disclaimed. Neither SMA America, LLC nor its distributors or dealers nor SMA Solar Technology Canada Inc. nor its distributors or dealers shall be liable for any indirect, incidental, or consequential damages under any circumstances.(The exclusion of implied warranties may not apply in all cases under some statutes, and thus the above exclusion may not apply.)Specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate and up-to-date. Readers are cautioned, however, that SMA America, LLC and SMA Solar Technology Canada Inc. reserve the right to make changes without notice and shall not be responsible for any damages, including indirect, incidental or consequential damages, caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material.All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand is not a registered trademark.The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by SMA America, LLC and SMA Solar Technology Canada Inc. is under license.

SMA America, LLC3801 N. Havana Street

Denver, CO 80239 U.S.A.

SMA Solar Technology Canada Inc.2425 Matheson Blvd. E

8th FloorMississauga, ON L4W 5K5

Canada

Page 4: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

Important Safety Instructions SMA America, LLC

4 HF_STP_Par-eng-TUS114810 Technical Description

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions for the following products:

• Sunny Boy 2000HF-US, 2500HF-US and 3000HF-USThis manual must be followed during installation and maintenance.

The product is designed and tested according to international safety requirements, but as with all electrical and electronic equipment, certain precautions must be observed when installing and/or operating the product. To reduce the risk of personal injury and to ensure the safe installation and operation of the product, you must carefully read and follow all instructions, cautions and warnings in this manual.

Warnings in this documentA warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the SMA equipment and/or other equipment connected to the SMA equipment or personal injury.

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to personal injury.

Page 5: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC Important Safety Instructions

Technical Description HF_STP_Par-eng-TUS114810 5

Other Symbols in this documentIn addition to the safety and hazard symbols described on the previous pages, the following symbol is also used in this manual:

Markings on this productThe following symbols are used as product markings with the following meanings.

InformationThis symbol accompanies notes that call attention to supplementary information that you must know and use to ensure optimal operation of the system.

Warning regarding dangerous voltageThe product works with high voltages. All work on the product must only be performed as described in the documentation of the product.

Beware of hot surfaceThe product can become hot during operation. Do not touch the product during operation.

Observe the operating instructionsRead the documentation of the product before working on it. Follow all safety precautions and instructions as described in the documentation.

UL1741 is the standard applied by Underwriters Laboratories to the product to certify that it meets the requirements of the National Electrical Code®, the Canadian Electrical Code® CSA C22.1 and IEEE‑929‑2000. IEEE 929-2000 provides recommendations regarding the proper equipment and functionality necessary to ensure compatible operation when power generation is connected to the utility grid.

Page 6: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

General Warnings SMA America, LLC

6 HF_STP_Par-eng-TUS114810 Technical Description

General Warnings

General WarningsAll electrical installations must be done in accordance with the local and National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial, federal or national laws, regulation or codes applicable to the installation and use of the product, including without limitation applicable electrical safety codes. All installations must conform with the laws, regulations, codes and standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the compliance or noncompliance with such laws or codes in connection with the installation of the product.The product contains no user-serviceable parts except for the fans on the bottom of the enclosure and the filters behind the fans as well as the handle covers on the sides of the unit. For all repair and maintenance, always return the unit to an authorized SMA Service Center.Before installing or using the product, read all of the instructions, cautions, and warnings in this manual.Before connecting the product to the electrical utility grid, contact the local utility company. This connection must be made only by qualified personnel.Wiring of the product must be made by qualified personnel only.

Page 7: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC Table of Contents

Technical Description HF_STP_Par-eng-TUS114810 7

Table of Contents1 Notes on this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.2 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.3 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.4 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.5 Communication Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.6 Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.7 Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.8 Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 DATA I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112.1 Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112.2 Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.3 Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153 DATA II+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173.1 Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173.1.1 Status - Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173.1.2 Status - Current event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173.1.3 Status - Device status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.1.4 DC Side - DC measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.1.5 DC Side - Insulation monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.1.6 AC Side - Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.1.7 AC Side - Measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.1.8 AC Side - Grid measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193.1.9 AC Side - Grid measurements - Power per phase . . . . . . . . . . . . . . . . . . . . . 193.1.10 AC Side - Grid measurements - Phase voltages . . . . . . . . . . . . . . . . . . . . . . 193.1.11 AC Side - Grid measurements - Phase currents . . . . . . . . . . . . . . . . . . . . . . . 193.2 Operating Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.2.1 Type Label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Page 8: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

Table of Contents SMA America, LLC

8 HF_STP_Par-eng-TUS114810 Technical Description

3.2.2 Device - Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213.2.3 Device - Cooling system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.2.4 Device - System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.2.5 Device - Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233.2.6 Device - Multifunction relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243.2.7 Device - Multifunction relay - Self-consumption . . . . . . . . . . . . . . . . . . . . . . . 243.2.8 Device - Multifunction relay - Control via communication . . . . . . . . . . . . . . . 243.2.9 Device - Multifunction Relay - Battery bank. . . . . . . . . . . . . . . . . . . . . . . . . . 253.2.10 User Rights - Access Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253.2.11 DC Side - DC settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263.2.12 AC Side - Measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263.2.13 AC Side - Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273.2.14 AC Side - Island mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283.2.15 Grid monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283.2.16 Grid monitoring - Country standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293.2.17 Grid monitoring - Country standard - PV module . . . . . . . . . . . . . . . . . . . . . 313.2.18 Grid monitoring - Frequency monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333.2.19 Grid monitoring - Country standard - Islanding detection . . . . . . . . . . . . . . . 363.2.20 Grid monitoring - Voltage monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363.2.21 Plant communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403.2.22 Device Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413.3 Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Page 9: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 1 Notes on this Manual

Technical Description HF_STP_Par-eng-TUS114810 9

1 Notes on this Manual1.1 ValidityThis manual describes measured values, operating parameters, and event messages for the following SMA inverters:

• Sunny Boy 2000HF-US (SB 2000HFUS-30)• Sunny Boy 2500HF-US (SB 2500HFUS-30)• Sunny Boy 3000HF-US (SB 3000HFUS-30)

The information is valid for the current firmware version of the inverter.

1.2 Target GroupThis manual is for operators and qualified personnel. Some parameters in this manual may only be changed by qualified personnel.Qualified personnel have received training and have demonstrated skills and knowledge in the construction and operation of this device. Qualified personnel are trained to deal with the dangers and hazards involved in installing electric devices.

1.3 Additional InformationAdditional information on specific topics can be found in the download area at www.SMA‑America.com.

1.4 NomenclatureIn this document, SMA America Production, LLC and SMA Solar Technology Canada Inc. will be referred to as SMA.

1.5 Communication ProtocolsCommunication protocol DATA I and DATA II+Depending on the mode of communication (RS485 or Bluetooth® Wireless Technology), the inverter uses a different communication protocol. Measured values, operating parameters, and event messages will be displayed in different ways.

• Communication via RS485: DATA I• Communication via Bluetooth and Sunny Explorer: DATA II+

Page 10: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

1 Notes on this Manual SMA America, LLC

10 HF_STP_Par-eng-TUS114810 Technical Description

1.6 Measured ValuesThe inverter measures signals during operation. The signals are depicted and stored in a communication device or communication software in the form of measured values.The measured values in this manual are categorized according to communication protocol. For an explanation of the values for Data I, refer to the descriptions under Data II+. The type of inverter will determine which measured values your inverter will display. Some measured values can be viewed only by the installer.

1.7 Operating ParametersThe various operating parameters control the functionality of the inverter. They can only be viewed and changed using a communication device or communication software.The operating parameters in this manual are categorized according to communication protocol. For an explanation of the parameters for Data I, refer to the descriptions under Data II+. The type of inverter will determine which operating parameters your inverter will display. Some operating parameters can only be viewed and changed by the installer. There are also display parameters that cannot be changed.

1.8 Event MessagesSection 2.3 "Event Messages", page 15 for Data I and section 3.3 "Event Messages", page 43 for Data II+ contain an overview of the event messages sent by the inverter when an update is carried out or an error arises. Some event messages can only be viewed by the installer.

Page 11: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 2 DATA I

Technical Description HF_STP_Par-eng-TUS114810 11

2 DATA I2.1 Measured ValuesName DescriptionA.Ms.Amp See "DC current input", page 18A.Ms.Vol See "DC voltage input", page 18A.Ms.Watt See "DC power input", page 18ComRev See "Communication version", page 20Error Event message

For more details see chapter 1.8 "Event Messages", page 10.E-Total See "Total yield", page 18GridMs.A.phsA See "Phase currents, phase L1", page 19GridMs.A.phsB See "Phase currents, phase L2", page 19GridMs.A.phsC See "Phase currents, phase L3", page 19GridMs.Hz See "Grid frequency", page 19GridMs.PhV.phsA See "Phase voltages, phase L1", page 19GridMs.PhV.phsB See "Phase voltages, phase L2", page 19GridMs.PhV.phsC See "Phase voltages, phase L3", page 19GridMs.W.phsA See "Phase power, phase L1", page 19GridMs.W.phsB See "Phase power, phase L2", page 19GridMs.W.phsC See "Phase power, phase L3", page 19Inv.TmpLimStt See "Derating", page 17Mode Operating modeMt.TotOpTmh See "Feed-in time", page 18Mt.TotTmh See "Operating time", page 18Op.EvtCntIstl See "Number of events for installer", page 17Op.EvtCntUsr See "Number of events for user", page 17Op.EvtNo Event number

For more details see chapter 3.3 "Event Messages", page 43.Op.GriSwCnt See "Number of grid connections", page 18Op.GriSwStt See "Grid relay status", page 17Pac See "Power", page 19Riso See "Insulation resistance", page 18Serial Number See "Serial number", page 21

Page 12: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

2 DATA I SMA America, LLC

12 HF_STP_Par-eng-TUS114810 Technical Description

2.2 Operating ParametersName DescriptionA.Const.VSet See "Voltage setpoint", page 26A.StrTms See "Start delay", page 26A.VStr See "Critical voltage to start feed-in", page 26AID.AngFact See "Escalation factor", page 36AMaxOfs See "Tripping threshold DC current monitoring", page 29 AMaxOfsTms See "Tripping time DC current monitoring", page 29BT.RevVer See "Revision status of the Bluetooth component", page 41BT.swRev See "Firmware version of the Bluetooth component", page 41BtPwr See "Maximum Bluetooth transmission power", page 40Cntry See "Country standard", page 28CntrySet See "Set country standard", page 28CoolSys.FanTst See "Fan test", page 22CPLD.RevVer See "Revision status of the logic component", page 41CPLD.swRev See "Firmware version of the logic component", page 41FrqCtl.ChgMax See "Maximum allowable frequency drift", page 35FrqCtl.ChgMaxTm See "Tripping time when exceeding max. frequency drift", page 36FrqCtl.hLim See "Frequency monitoring upper maximum threshold", page 33FrqCtl.hLimTms See "Frq. monitoring lower max. threshold trip. time", page 34FrqCtl.lLim See "Frequency monitoring upper minimum threshold", page 34FrqCtl.lLimTms See "Frq. monitoring upper min. threshold trip. time", page 35FrqCtl.Max See "Frequency monitoring upper maximum threshold", page 33FrqCtl.MaxTms See "Frq. monitoring upper max. threshold trip. time", page 34FrqCtl.Min See "Frequency monitoring lower minimum threshold", page 34FrqCtl.MinTms See "Frq. monitoring lower min. threshold trip. time", page 35GriFltMonTms See "Reconnection time upon grid interruption", page 30GriFltReConTms See "Reconnection time upon short interruption", page 30GriFltTms See "Maximum duration of a short interruption", page 29GriStrTms See "Reconnection time upon restart", page 31HP.hwRev See "Hardware version of the central assembly", page 42HP.RevVer See "Revision status of the central assembly", page 42HP.swRev See "Firmware version of the central assembly", page 42Inv.OutPhsSet See "Phase assignment", page 27Inv.OutWModSet See "Temporal control of the power limitation", page 23Inv.StopTms See "Deactivation delay", page 23Iso.LeakRisMin See "Minimum insulation resistance", page 30

Page 13: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 2 DATA I

Technical Description HF_STP_Par-eng-TUS114810 13

KP.hwRev See "Hardware version of the communication assembly", page 41KP.swRev See "Firmware version of the communication assembly", page 41LCD.swRev See "Firmware version of the display", page 41MainModel See "Device class", page 20Md.GndAmpMax See "Maximum module ground current", page 31Md.GndAmpMaxTmms See "Tripping time maximum module ground current", page 31Md.GndFltRea See "Measures in the case of a grounding error", page 32Md.GndMdt See "Module grounding prescribed?", page 31Md.GndModReq See "Prescribed module grounding type", page 32Mdl.hwRev See "Hardware version of the RS485 module", page 41Mdl.swRev See "Firmware version of the RS485 Module", page 41Mlt.BatCha.Pwr See "Minimum On power for MFR battery bank", page 25Mlt.BatCha.Tmm See "Minimum time before reconnection of MFR battery

bank", page 25Mlt.ComCtl.Sw See "Status of MFR with control via communication", page 24Mlt.MinOnPwr See "Minimum On power for MFR self-consumption", page 24Mlt.MinOnPwrTmm See "Minimum power On time, MFR self-consumption", page 24Mlt.MinOnTmm See "Minimum On time for MFR self-consumption", page 24Mlt.OpMode See "Operating mode of multifunction relay", page 24Model See "Device type", page 20Mt.TotkWhSet See "Set total yield", page 27Mt.TotOpTmhSet See "Set feed-in time", page 27Mt.TotTmhSet See "Set operating time", page 26OffGri.HzdLim See "Endpoint of the power control via frequency", page 28OffGri.HzdStr See "Start point of the power control via frequency", page 28Op.FncSetIstl See "Reset operating data", page 21Op.OpModSet See "Operating condition", page 21Op.StoFncSet See "Load parameter", page 22Op.TmsRmg See "Waiting time until feed-in", page 17Pkg.swRev See "Software package", page 20SerNumSet See "Serial number", page 21VolCtl.hhLim See "Voltage monitoring median maximum threshold", page 37VolCtl.hhLimTms See "Voltage monitoring median max. threshold trip.time", page 38VolCtl.hLim See "Voltage monitoring lower maximum threshold", page 37VolCtl.hLimTms See "Voltage monitoring lower max. threshold trip. time", page 39VolCtl.lLim See "Voltage monitoring upper minimum threshold", page 38VolCtl.lLimTms See "Voltage monitoring upper min. threshold trip. time", page 39

Name Description

Page 14: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

2 DATA I SMA America, LLC

14 HF_STP_Par-eng-TUS114810 Technical Description

VolCtl.llLim See "Voltage monitoring of median minimum threshold", page 38VolCtl.llLimTms See "Voltage monitoring median min. threshold trip.time", page 39VolCtl.Max See "Voltage monitoring upper maximum threshold", page 37VolCtl.MaxTmms See "Voltage monitoring upper max. threshold trip. time", page 38VolCtl.ReconMax See "Max. voltage for reconnection", page 40VolCtl.ReconMin See "Min. voltage for reconnection", page 40VolCtl.Rpro See "Voltage increase protection", page 39

Name Description

Page 15: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 2 DATA I

Technical Description HF_STP_Par-eng-TUS114810 15

2.3 Event MessagesName DescriptionComFlt See "Communication disturbed", page 49DcAmpMax See "DC overcurrent", page 47DcMinFlt See "Start conditions not met", page 48DcVMax See "DC overvoltage", page 47DevFlt See "Interference of device", page 48DscGndModRv See "Grounding error", page 48FanFlt See "Fan fault", page 50GndFuFlt See "Grounding error", page 48GrdGuardLock See "Grid parameter locked", page 51GriFlt See "Grid fault", page 44HzFlt See "Frequency not permitted", page 46InstabOp See "Unstable operation", page 47InstCdNok See "Installer code invalid", page 51InstCdOk Installer code validItnlDataStoFail See "Data storage not possible", page 50LeakRis Insulation resistanceNoGri Grid failureOvLod See "Overload", page 49OvTmp See "Overtemperature", page 49SDFail See "SD card defective", page 49SDFileRead SD card is readSDNoParaFile See "SD card defective", page 49SDSetPara Set parameterSDSetParaNok Parameter setting failedSDSetParaOk Parameters set successfullySDUpdAkt No new update on the SD cardSDUpdFileNok See "Update file defective", page 49SDUpdFileOk Update file OKSDUpdNoFile See "No update file found", page 49SlfDiag See "Self diagnosis", page 50SlfTst Self-testSlfTstErr Abort self-testStringAFlt See "Input A defective", page 49TmpSns See "Sensor fault fan permanently on", page 49UpdBT Bluetooth update active

Page 16: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

2 DATA I SMA America, LLC

16 HF_STP_Par-eng-TUS114810 Technical Description

UpdBTErr See "Update Bluetooth failed", page 50UpdEnd Update completeUpdHP Main CPU update activeUpdHPErr See "Update main CPU failed", page 50UpdKom Communication update activeUpdLang Language table update activeUpdLangErr See "Update language table failed", page 50UpdLCD Display update activeUpdLCDErr See "Update display failed", page 50Updi485 RSi485 module update activeUpdi485Err See "Update RS485I module failed", page 50WtDcMin See "Waiting for DC start conditions", page 48WtGri See "Waiting for grid voltage", page 46

Name Description

Page 17: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 17

3 DATA II+ 3.1 Measured Values

3.1.1 Status - Operation

3.1.2 Status - Current event

Name Description Value ExplanationNumber of events for user

Counter for events relevant for the plant operator

Number of events for installer

Counter for events relevant for the installer

Derating Status display for the derating due to excess temperatures

not active Temperature derating not effective

Active Temperature derating effective

Grid relay status State of grid relay Open Relay openClosed Relay closed

Waiting time until feed-in

Standby time after an error event to the next connection attempt

Condition Current diagnostic status of the inverter

ErrorWarningOK

Name Description Value ExplanationCurrent event number Number of current eventRecommended action Displays the recommended

service staffCall installerCall SMAInactivenone

Fault correction measure

Instructions for correction of error

Message Inverter event message

Page 18: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

18 HF_STP_Par-eng-TUS114810 Technical Description

3.1.3 Status - Device status

3.1.4 DC Side - DC measurements

3.1.5 DC Side - Insulation monitoring

3.1.6 AC Side - Operation

3.1.7 AC Side - Measured values

Name DescriptionNominal power in Fault Mode Nominal power in error mode in WNominal power in Ok Mode Nominal power in OK mode in WNominal power in Warning Mode Nominal power in warning mode in W

Name DescriptionDC power input DC power input in WDC voltage input DC voltage input in VDC current input DC current input in A

Name DescriptionInsulation resistance Insulation resistance of the PV plant prior to the

grid connection in kΩFor inverter with SMA Plug-in Grounding the value should be 0.

Name DescriptionNumber of grid connections Number of grid connections

Name DescriptionOperating time Total number of operating hours of inverterFeed-in time Total number of grid-feeding operational hoursTotal yield Total amount of feeding-in energy in kWh

Page 19: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 19

3.1.8 AC Side - Grid measurements

3.1.9 AC Side - Grid measurements - Power per phase

3.1.10 AC Side - Grid measurements - Phase voltages

3.1.11 AC Side - Grid measurements - Phase currents

Name DescriptionReactive power Total reactive power in %Power Delivered active power in W (total)Grid frequency Grid frequency in Hz

Name DescriptionPhase power, phase L1 Active power phase L1 in WPhase power, phase L2 Active power phase L2 in WPhase power, phase L3 Active power phase L3 in W

Name DescriptionPhase voltages, phase L1 Grid voltage phase L1 in VPhase voltages, phase L2 Grid voltage phase L2 in VPhase voltages, phase L3 Grid voltage phase L3 in V

Name DescriptionPhase currents, phase L1 Grid current phase L1 in APhase currents, phase L2 Grid current phase L2 in APhase currents, phase L3 Grid current phase L3 in A

Page 20: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

20 HF_STP_Par-eng-TUS114810 Technical Description

3.2 Operating Parameters

3.2.1 Type LabelDevice classDisplay of inverter device class

Device nameEntry of a selected name in the inverter description

Device typeDisplay of inverter device type

Communication versionCommunication protocol version number

Software packageSoftware version of components in inverter

Inverter Unit Value range Default setting― • Solar Inverters Solar inverters

Inverter Unit Value range Default setting― 1 … 30 characters ―

Inverter Unit Value range Default settingSB 2000HFUS-30 ― fixed SB 2000HFUS-30SB 2500HFUS-30 SB 2500HFUS-30SB 3000HFUS-30 SB 3000HFUS-30

Inverter Unit Value range Default setting― fixed ―

Inverter Unit Value range Default setting― fixed ―

Page 21: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 21

Serial numberInverter serial number display

3.2.2 Device - OperationReset operating dataReset operating counter to default setting.

Operating conditionSelect the desired operating mode.

Inverter Unit Value range Default setting― fixed ―

Inverter Value range Default setting• DoAll / Execute all• GriSwCnt / N° grid conn. at grid conn.pt.

(resetting the number of grid connection at grid connection point)

• RsEvtCnt / Reset events (resetting the event counter)

• RsPermStoOp / Reset operation inhibition(release the operation inhibition)

• RsTotWhLog / Reset energy logger• TotTmh / Operating time (resetting the hours of

operation)• TotFeedTms / Feed-in time

(resetting the feed-in hours)• TotOpTms / Operating time• TotWhOut / Total yield

(resetting the "total yield" meter)

Inverter Value range Default setting• MPP (Maximum Power Point)• VolDCConst / Constant voltage mode (setpoint is

defined by "constant voltage setpoint")• Stp / Stop (disconnection from grid, no operation)

MPP

Page 22: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

22 HF_STP_Par-eng-TUS114810 Technical Description

Load parameterReturn all operating parameters to default setting, except for SMA Grid Guard parameters, which are protected by the Grid Guard Code.

3.2.3 Device - Cooling systemFan testSetting the parameter to "on" checks the fan function. More information can be found in the inverter installation guide.

3.2.4 Device - SystemFind deviceTo identify the controlled inverters, set the parameter to "blink LED". The Bluetooth LED on the device will blink.

Inverter Value range Default setting• DfltParaLod / Load preset ―

Inverter Unit Value range Default setting― • Off (fan test off)

• On (fan test on)Off

Inverter Unit Value range Default setting― • Off

• LED blinkingOff

Page 23: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 23

3.2.5 Device - InverterDeactivation delayThis parameter defines the amount of time the inverter will wait before disconnecting from the grid when the feed-in conditions are no longer met.

Temporal control of the power limitationThis parameter defines the time intervals of the power measurements for determining the output power limitation.It is preset in accordance with the selected country standard and the performance category.

Inverter Unit Value range Default settings 1 … 3 600 2

Inverter Unit Value range Default setting― • LIM10M / 10 minute average

• LIMFST / Instantaneous valuesLIMFST / Instantaneous values

Page 24: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

24 HF_STP_Par-eng-TUS114810 Technical Description

3.2.6 Device - Multifunction relayOperating mode of multifunction relayYou configure the desired operating mode and further settings via parameters.

3.2.7 Device - Multifunction relay - Self-consumptionMinimum On power for MFR self-consumptionTrigger threshold for self-consumption function

Minimum power On time, MFR self-consumptionMinimum time for which the minimum start-up power must be fed for the relay to switch

Minimum On time for MFR self-consumptionMinimum duration for which the relay remains switched on.

3.2.8 Device - Multifunction relay - Control via communicationStatus of MFR with control via communicationState of the multifunction relay with the operating mode 'Control via communication'

Inverter Unit Value range Default setting― • FltInd / Fault indication

• FanCtl / Fan control• SelfCsmp / Self-consumption• ComCtl / Control via communication• BatCha / Battery bank

FltInd / Fault indication

Inverter Unit Value range Default setting W 100 … 17 000 1 500

Inverter Unit Value range Default settingmin 0 … 1 440 30

Inverter Unit Value range Default settingmin 1 … 1 440 120

Inverter Unit Value range Default setting― • On

• OffOff

Page 25: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 25

3.2.9 Device - Multifunction Relay - Battery bankMinimum On power for MFR battery bankThreshold for switching the relay in operating mode 'Charging the battery'

Minimum time before reconnection of MFR battery bankMinimum time between switching the relay off and back on

3.2.10 User Rights - Access ControlSet installer passwordSet new installer password.

Set user passwordSet new user password.

Inverter Unit Value range Default settingW 100 … 17 000 1 500

Inverter Unit Value range Default settingmin 1 … 1 440 30

Inverter Unit Value range Default setting― ― 1111

Inverter Unit Value range Default setting― ― 0000

Page 26: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

26 HF_STP_Par-eng-TUS114810 Technical Description

3.2.11 DC Side - DC settingsCritical voltage to start feed-inInitial voltage required before the inverter begins feeding in power into the grid. If the value is set too low, this may lead to an increased number of connections to the grid, and thus to increased wear.

Start delayDelay time for grid connection once start voltage is reached

Voltage setpointThis parameter is active in the "constant voltage" operating mode, and defines the constant voltage setpoint.

3.2.12 AC Side - Measured valuesSet operating timeSet the operating time ("operating time" measured value) of the inverterChanging this may be necessary if you replace the inverter and want to use the operating time from the old device.

Inverter Unit Value range Default setting V 220 … 700*

* The device has an open circuit voltage maximum of 600 V.

220

Inverter Unit Value range Default settings 1 … 4 1

Inverter Unit Value range Default settingV 175 … 700*

* The device has an open circuit voltage maximum of 600 V.

700

Inverter Unit Value range Default settingh 0 … 440 000 0

Page 27: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 27

Set feed-in timeSetting the feed-in time ("feed in time" measured value) of the inverterChanging this may be necessary if you replace the inverter and want to use feed time from the old device.

Set total yieldSet the total yield ("total yield" measured value) of the inverterChanging this may be necessary if you replace the inverter and want to use the yields from the old device.

3.2.13 AC Side - InverterPhase assignmentIdentifying the connected feed-in phaseThe set phase is also shown on the display, and the phase-dependent measured values are allocated to the AC current and AC voltage accordingly.

Inverter Unit Value range Default settingh 0 … 440 000 0

Inverter Unit Value range Default settingkWh 0 … 4 000 000 0

Inverter Unit Value range Default setting ― • Phase L1

• Phase L2• Phase L3

Phase L1

Page 28: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

28 HF_STP_Par-eng-TUS114810 Technical Description

3.2.14 AC Side - Island modeEndpoint of the power control via frequencySetting the frequency-dependent power reductionThis parameter can be used to set the endpoint of the frequency performance curve.

Start point of the power control via frequencySetting the frequency-dependent power reductionThis parameter can be used to set the starting point of the frequency output characteristic curve.

3.2.15 Grid monitoringSet country standardThe desired standards of all country-specific parameters can be restored via this parameter.

Country standardDisplays the current setting for the country-specific standard.

Inverter Unit Value range Default settingHz 0 … 5 2

Inverter Unit Value range Default settingHz 0 … 5 1

Inverter Value range Default setting • OFF-Grid60 (Island mode 60Hz)

• UL1741/2005 (USA, automatic voltage detection)

• UL1741/2005/208 (USA 208V)*• UL1741/2005/240 (USA 240V)*

* For grids without neutral contuctor

UL1741/2005

Inverter Unit Value range Default setting― • See "Set country standard", page 28

• Adj / Special setting• ------- / Information not available

Page 29: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 29

3.2.16 Grid monitoring - Country standardTripping threshold DC current monitoringThis parameter sets the tripping threshold for the DC current monitoring. These parameters may only be changed after prior agreement with the SMA Serviceline.

Tripping time DC current monitoringThis parameter sets the standard deactivation time for DC current monitoring These parameters may only be changed after prior agreement with the SMA Serviceline.

Maximum duration of a short interruptionThis parameter sets the maximum duration of grid monitoring during grid disruptions.

Inverter Unit Value range Default setting A 0.02 … 5 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

SB 2000HFUS-30 5 0.042 0.042 0.042SB 2500HFUS-30 5 0.052 0.052 0.052SB 3000HFUS-30 5 0.063 0.063 0.063

Inverter Unit Value range Default setting ms 0 … 10 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

SB 2000HFUS-30 10 000 2 000 2 000 2 000SB 2500HFUS-30 10 000 2 000 2 000 2 000SB 3000HFUS-30 10 000 2 000 2 000 2 000

Inverter Unit Value range Default settings 0 … 400 3

Page 30: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

30 HF_STP_Par-eng-TUS114810 Technical Description

Minimum insulation resistanceThis parameter sets the lower tripping threshold for insulation resistance. This parameter has no effect with the SMA Plug-in Grounding.

Grid nominal voltageNominal voltage value of the set country standard

Reconnection time upon short interruptionThis parameter sets the duration of the grid observation period following a brief grid disruption. The "Reconnection time upon grid interruption" parameter defines the duration of the brief grid disruption.

Reconnection time upon grid interruptionThis parameter defines the duration of a brief grid interruption.

Inverter Unit Value range Default setting k Ω 500 … 3 000 1 000

Inverter Unit Value range Default settingV 100 … 280 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

230 120 208 240

Inverter Unit Value range Default setting s 0 … 400 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

0 300 300 300

Inverter Unit Value range Default setting s 0 … 400 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

0 300 300 300

Page 31: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 31

Reconnection time upon restartThe parameter defines the time to reconnection to the grid after a restart.

3.2.17 Grid monitoring - Country standard - PV moduleMaximum module ground currentThe inverter disconnects from the grid when this threshold is exceeded.

Tripping time maximum module ground currentThe inverter disconnects from the grid after the tripping time when the maximum module ground current is exceeded.

Module grounding prescribed?Indicates whether a module grounding is required under the country standard.

Inverter Unit Value range Default setting s 0 … 400 0

Inverter Unit Value range Default setting A 0.3 … 1.5 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

1 1 1 1

Inverter Unit Value range Default setting ms 0 … 2 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

1 000 160 160 160

Inverter Unit Value range Default setting ― • Yes

• No (not available)Yes

Page 32: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

32 HF_STP_Par-eng-TUS114810 Technical Description

Prescribed module grounding typePV module grounding type

Measures in the case of a grounding errorThis parameter has no effect with the SMA Plug-in Grounding.

Inverter Unit Value range Default setting ― • GndModPs / Positive

• GndModNg / Negative• GndModNoneReq / None prescribed• GndModLrn / Learning (learning the

grounding type, store after 10 h)

see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

GndModLrn / Learning

GndModNg / Negative

GndModNg / Negative

GndModNg / Negative

Inverter Unit Value range Default setting ― • GndFltDscon / Disconnect from grid

• GndFltWrn / WarnGndFltWrn / Warn

Page 33: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 33

3.2.18 Grid monitoring - Frequency monitoringThe following parameters define the triggering times and corresponding triggering thresholds of the inverter frequency monitoring. The "set country standard" parameter can be used to restore the desired standard.

Frequency monitoring upper maximum thresholdThe inverter switches off when this threshold is exceeded.

Frequency monitoring lower maximum thresholdThe inverter switches off when this threshold is exceeded.

Inverter Unit Value range Default settingHz 50 … 65 65

Inverter Unit Value range Default settingHz 50 … 65 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

64.5 60.5 60.5 60.5

FrqCtl.Max upper maximum threshold

Grid frequencyFrqCtl.lLim upper minimum

threshold

FrqCtl.Min lower minimum threshold

FrqCtl.hLim lower maximum threshold

Page 34: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

34 HF_STP_Par-eng-TUS114810 Technical Description

Frequency monitoring upper minimum thresholdThe inverter switches off below this threshold.

Frequency monitoring lower minimum thresholdThe inverter switches off below this threshold.

Frq. monitoring upper max. threshold trip. timeThe inverter switches off after the tripping time after this threshold is exceeded.

Frq. monitoring lower max. threshold trip. timeThe inverter switches off after the tripping time after this threshold is exceeded.

Inverter Unit Value range Default settingHz 44 … 60 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

55 59.3 59.3 59.3

Inverter Unit Value range Default settingHz 44 … 60 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

44 57 57 57

Inverter Unit Value range Default settingms 0 … 10 000 10 000

Inverter Unit Value range Default setting ms 0 … 10 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

200 160 160 160

Page 35: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 35

Frq. monitoring upper min. threshold trip. timeThe inverter switches off after the tripping time below this threshold.

Frq. monitoring lower min. threshold trip. timeThe inverter switches off after the tripping time below this threshold.

Maximum allowable frequency driftMaximum frequency change in a specified time.

Upper frequency for reconnectionFor connection, the grid frequency must be below the threshold.

Lower frequency for reconnectionThe grid frequency must be above the threshold.

Inverter Unit Value range Default setting ms 0 … 300 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

2 000 160 160 160

Inverter Unit Value range Default settingms 0 … 300 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

300 000 160 160 160

Inverter Unit Value range Default settingHz/s 0 … 10 10

Inverter Unit Value range Default settingHz 50 … 65 65

Inverter Unit Value range Default settingHz 44 … 65 44

Page 36: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

36 HF_STP_Par-eng-TUS114810 Technical Description

Tripping time when exceeding max. frequency driftThe inverter switches off after the tripping time after this threshold is exceeded.

3.2.19 Grid monitoring - Country standard - Islanding detectionEscalation factorParameter for activation of the island grid identification.These parameters may only be changed after prior agreement with the SMA Serviceline. This parameter can be used to set the starting point of the frequency output characteristic curve.

3.2.20 Grid monitoring - Voltage monitoringThe following parameters define the triggering times and corresponding triggering thresholds of inverter voltage monitoring. The "set country standard" parameter can be used to restore the desired standard.

Inverter Unit Value range Default settingms 0 … 10 000 10 000

Inverter Unit Value range Default setting― 0 … 40 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

0 12 12 12

VolCtl.MaxUpper maximum threshold

VolCtl.hLimLower maximum threshold

Grid voltage phase

VolCtl.lLimUpper minimum threshold

VolCtl.hhLimMedian maximum threshold

VolCtl.llLimMedian minimum threshold

Page 37: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 37

Voltage monitoring upper maximum thresholdThe inverter switches off when this threshold is exceeded.

Voltage monitoring median maximum thresholdThe inverter switches off when this threshold is exceeded.

Voltage monitoring lower maximum thresholdThe inverter switches off when this threshold is exceeded.

Inverter Unit Value range Default settingV 300 … 420 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

400 420 400 420

Inverter Unit Value range Default setting V 130 … 290 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

280 144 249.6 288

Inverter Unit Value range Default setting V 120 … 290 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

264.5 132 228.8 264

Page 38: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

38 HF_STP_Par-eng-TUS114810 Technical Description

Voltage monitoring upper minimum thresholdThe inverter switches off below this threshold.

Voltage monitoring of median minimum thresholdThe inverter switches off below this threshold.

Voltage monitoring upper max. threshold trip. timeThe inverter switches off after the tripping time after this threshold is exceeded.

Voltage monitoring median max. threshold trip.timeThe inverter switches off after the tripping time after this threshold is exceeded.

Inverter Unit Value range Default setting V 60 … 240 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

180 105.6 183.1 211.2

Inverter Unit Value range Default setting V 60 … 240 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

100 60 104 120

Inverter Unit Value range Default settingms 0.1 … 5 0.312

Inverter Unit Value range Default setting ms 0 … 10 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

10 000 160 160 160

Page 39: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 39

Voltage monitoring lower max. threshold trip. timeThe inverter switches off after the tripping time after this threshold is exceeded.

Voltage monitoring upper min. threshold trip. timeThe inverter switches off after the tripping time below this threshold.

Voltage monitoring median min. threshold trip.timeThe inverter switches off after the tripping time below this threshold.

Voltage increase protectionParameter for setting the 10-minute average for the rise-in voltage protection (applies only to Germany)In Germany, inverters are permitted to feed into the public grid with up to 260 V AC. However, the DIN VDE 0126-1-1 standard stipulates that the 10-minute AC voltage average may not exceed 253 V. If the average over 10 minutes exceeds the threshold value of 253 V, the inverter disconnects itself from the grid. As soon as the 10-minute average decreases back to less than 253 V, the inverter will continue to feed power into the grid.

Inverter Unit Value range Default setting ms 0 … 10 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

200 1 000 1 000 1 000

Inverter Unit Value range Default setting ms 0 … 10 000 2 000

Inverter Unit Value range Default setting ms 0 … 10 000 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

10 000 160 160 160

Inverter Unit Value range Default settingV 230 … 280 280

Page 40: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

40 HF_STP_Par-eng-TUS114810 Technical Description

Max. voltage for reconnectionThe inverter switches over when this threshold is exceeded (low and medium voltage)

Min. voltage for reconnectionThe inverter switches off below this threshold (low and medium voltage).

3.2.21 Plant communicationMaximum Bluetooth transmission powerParameter for setting the Bluetooth transmission performanceThese parameters may only be changed after prior agreement with the SMA Serviceline.

Inverter Unit Value range Default setting V 120 … 280 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

280 127 220 254

Inverter Unit Value range Default setting V 45 … 240 see below

Inverter SettingOFF-Grid60 UL1741/2005 UL1741/2005/

208UL1741/2005/240

45 106 184 212

Inverter Unit Value range Default settingdBm 1 … 20 16

Page 41: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 41

3.2.22 Device ComponentsName DescriptionFirmware version of the Bluetooth component

Software version of the component present in the inverter

Serial number of the Bluetooth component

Serial number of the component present in the inverter

SUSyID of the Bluetooth component

Identification number of the device family in the inverter

Revision status of the Bluetooth component

Conversion and repair status of the component present in the inverter

Firmware version of the display Software version of the component present in the inverterSUSyID of the display Identification number of the device family in the inverterRevision status of the display Conversion and repair status of the component present in

the inverterFirmware version of the communication assembly

Software version of the component present in the inverter

Hardware version of the communication assembly

Version number of the component present in the inverter

Serial number of the communication assembly

Serial number of the component present in the inverter

SUSyID of the communication assembly

Identification number of the device family in the inverter

Revision status of the communication assembly

Conversion and repair status of the component present in the inverter

Firmware version of the logic component

Software version of the component present in the inverter

Revision status of the logic component

Conversion and repair status of the component present in the inverter

Firmware version of the RS485 Module

Software version of the component present in the inverter

Hardware version of the RS485 module

Version number of the component present in the inverter

Serial number of the RS485 module

Serial number of the component present in the inverter

SUSyID of the RS485 module Identification number of the device family in the inverterRevision status of the RS485 module

Revision and repair status of the component in the inverter

Page 42: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

42 HF_STP_Par-eng-TUS114810 Technical Description

Firmware version of the central assembly

Software version of the component present in the inverter

Hardware version of the central assembly

Version number of the component present in the inverter

Serial number of the central assembly

Serial number of the component present in the inverter

SUSyID of the central assembly Identification number of the device family in the inverterRevision status of the central assembly

Conversion and repair status of the component present in the inverter

Name Description

Page 43: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 43

3.3 Event MessagesEvent messages smaller than 100 correspond to the error number displayed in the inverter display.No. Display text Description1 Grid fault The grid voltage has exceeded the permissible range. For

safety reasons, the inverter disconnects itself from the grid. Cause:

• The grid voltage at the point of connection of the inverter is too high.

• Grid impedance at the connection point of the inverter is too high.

Corrective measures:• Check the grid voltage and connection on the

inverter.If the grid voltage lies outside the acceptable range because of local grid conditions, ask the utility provider if the voltage can be adjusted at the feed-in point or if it would agree to changes in the values of the monitored operational limits.If the grid voltage lies within the tolerance range, yet this error is still being displayed, contact the SMA Serviceline.

101 Grid overvoltage (spot value)

Spot value for the grid voltage measurement with reasonable elimination of outliers exceeds a preset maximum value.

102 Grid overvoltage fast The effective value of the grid voltage has exceeded the upper maximum grid voltage level for the set triggering time.

103 Grid overvoltage slow The effective value of the grid voltage has exceeded the lower maximum grid voltage level for the set triggering time.

Page 44: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

44 HF_STP_Par-eng-TUS114810 Technical Description

2 Grid fault The grid voltage has fallen below the permissible range. For safety reasons, the inverter disconnects itself from the grid.Cause:

• Grid disconnected.• AC cable damaged.• The grid voltage at the point of connection of the

inverter is too low.Corrective measures:

• Check for tripping of the line circuit breaker.• Check the grid voltage and connection on the

inverter.If the grid voltage lies outside the acceptable range because of local grid conditions, ask the utility provider if the voltage can be adjusted at the feed-in point or if it would agree to changes in the values of the monitored operational limits.If the grid voltage lies within the tolerance range, yet this error is still being displayed, contact the SMA Serviceline.

202 Grid undervoltage fast The effective value of the grid voltage has fallen below the lower minimum grid voltage level for the set triggering time.

203 Grid undervoltage slow The effective value of the grid voltage has fallen below the upper minimum grid voltage level for the set triggering time.

205 PLL outside limits PLL is under 140 V for 30 ms.

No. Display text Description

Page 45: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 45

3 Grid fault The average grid voltage over 10 minutes is no longer within the permissible range. The inverter disconnects to assure compliance with the voltage quality of the grid. Cause:

• The grid voltage at the point of connection of the inverter is too high.

• Grid impedance at the connection point of the inverter is too high.

Corrective measures:• Check the grid voltage at the point of connection of

the inverter:If, due to local grid conditions, the grid voltage exceeds the configured limiting value, ask the utility provider whether the voltage can be adjusted at the feed-in point, or whether it would agree to a modification of the limiting value for voltage quality monitoring.If the grid voltage is continually within the acceptable range, and this error is still displayed, contact the SMA Serviceline.

301 Voltage increase protection The effective value of the grid voltage is above the permitted threshold for a specified period of time (country parameters, e.g., 10 minutes).

4 Grid fault The internal inverter monitoring has detected an impermissibly high proportion of direct current in the grid current.Corrective measures:

• Check the grid connection for direct current.If this is a recurrent phenomenon, check with the utility provider whether it is possible to raise the limiting value of monitoring.

401 Island grid The average grid frequency is outside the specified limit for a defined period of time.

404 Frequency change not permitted

Detection of excessive frequency change per second for grid operation (island grid detected).

No. Display text Description

Page 46: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

46 HF_STP_Par-eng-TUS114810 Technical Description

5 Grid fault The grid frequency is not within the permissible range. For safety reasons, the inverter disconnects itself from the grid.Corrective measures:

• If possible, check the grid frequency and observe how often major deviations occur.

If repeated frequency variations occur and as a result this error occurs, ask the utility provider if it would agree to modify the operating parameters.Discuss the proposed parameters with the SMA Serviceline.

501 Grid frequency disturbance The average grid frequency is outside the specified limit for a defined period of time.

6 Grid fault The internal inverter monitoring has detected an impermissibly high proportion of direct current in the grid current.Corrective measures:

• Check the grid connection for direct current.If the event arises frequently, ask the grid operator if the operating parameters can be changed.Discuss the proposed parameters with the SMA Serviceline.

601 DC grid feed-in The DC content in the grid current exceeds a defined limit. The grid current average is compared to the limit value.

7 Frequency not permitted The grid frequency has left the allowable range. For safety reasons, the inverter disconnects itself from the grid. Corrective measures:

• Check the grid frequency and observe how often major deviations occur.

If repeated frequency variations occur and as a result this error occurs, ask the utility provider if it would agree to modify the operating parameters.Discuss the proposed parameters with the SMA Serviceline.

701 Grid frequency not permitted The grid frequency measurement indicates too much deviation from the nominal value. PLL output outside the country parameter limits.

8 Waiting for grid voltageCheck fuse

The inverter is waiting for grid voltage.Corrective measures:

• Check fuse.• Check AC installation.• Check whether there is a general black-out.

No. Display text Description

Page 47: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 47

801 Grid failure PLL briefly interrupted (> 30 s)33 Unstable operation The supply at the DC input of the inverter is not sufficient for

stable operation.Corrective measures:

• Wait for higher irradiation.• If this event recurs at medium irradiation, check the

PV plant design and correct the connection of the PV generator.

34 DC overvoltage The DC input voltage connected to the inverter is too high.Corrective measures:

• Immediately disconnect the PV generator from the inverter. Otherwise, the inverter may be destroyed.

• Check DC voltage of the strings to ensure they are maintaining the inverter's maximum input voltage

3401 Overvoltage input A (SW) The input voltage at string A exceeds the set maximum.35 Insulation resistance The inverter has detected a ground fault in the PV generator.

Corrective measures:• Check strings for ground faults • The installer of the PV generator must remedy the

ground faults before you re-connect the affected string.

3501 Insulation failure The measured value of the active RISO measurement is below a specified limit. For safety reasons, the inverter disconnects itself from the grid.

3502 Ground fault detected Ground fault detected3503 Overcurrent Ground fuse Too much current at the SMA Plug-in Grounding38 DC overcurrent An overcurrent condition occurs on the DC side of the

inverter and it switches off.Corrective measures:

• If this event recurs frequently, check the PV generator design and connection.

3801 Overcurrent input A (SW) The measured input current exceeds the specified maximum. Spot value with reasonable elimination of outliers is above the threshold of 20 A.

No. Display text Description

Page 48: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

48 HF_STP_Par-eng-TUS114810 Technical Description

39 Waiting for DC start conditions

Generator voltage is not sufficient to create or maintain intermediate circuit.Corrective measures:

• Wait for higher irradiation.39 Start conditions not met The input power or the voltage of the PV modules is not

sufficient for feeding into the grid.Corrective measures:

• Wait for higher irradiation.• If this event recurs at medium irradiation, check the

PV plant design and correct the connection of the PV generator.

42 Grounding error The polarity of the SMA Plug-in Grounding does not correspond to the polarity set at the inverter.Corrective measures:

• Check polarity of SMA Plug-in Grounding.• Remove SMA Plug-in Grounding.• Turn SMA Plug-in Grounding 180° and reconnect

with correct polarity.4201 Wrong earthing type SMA Plug-in Grounding is incorrectly connected.60 Interference of device Memory error

Corrective measures:• Contact the SMA Serviceline

(see section 4 "Contact", page 53).61 Interference of device FW error

Corrective measures:• Contact the SMA Serviceline

(see section 4 "Contact", page 53).63 Interference of device Measurement sequence

Corrective measures:• Contact the SMA Serviceline

(see section 4 "Contact", page 53).64 Interference of device Hardware fault

Corrective measures:• Contact the SMA Serviceline

(see section 4 "Contact", page 53).

No. Display text Description

Page 49: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 49

65 Overtemperature The inverter switches off due to too high temperature Corrective measures:

• Ensure sufficient ventilation.• Check heat removal.

66 Overload Overcurrent in grid or overvoltage in intermediate circuitCorrective measures:

• Check DC voltage of the strings to ensure they are maintaining inverter's maximum input voltage.

67 Communication disturbed A fault has occurred in the internal communication of the inverter. However, the inverter continues feeding into the grid.Corrective measures:

• Check communications module• If this event occurs often, contact the SMA Serviceline

(see section 4 "Contact", page 53).68 Input A defective String A defective

Corrective measures:• Check PV generator.

70 Sensor fault fan permanently on

Temperature sensorsCorrective measures:

• Contact the SMA Serviceline (see section 4 "Contact", page 53).

71 No update file found Corrective measures:• Perform update again• If this fault occurs often, contact the SMA Serviceline

(see section 4 "Contact", page 53).

Parameter setting failedParameter file not found or defectiveSD card defectiveUpdate file defective

7101 SD card defective SD card cannot read and write data.7102 Parameter file not found or

defectiveParameter file not found or defective

7105 Parameter setting failed Parameter setting failed7106 Update file defective Update file defective7110 No update file found No update file found

No. Display text Description

Page 50: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

50 HF_STP_Par-eng-TUS114810 Technical Description

72 Data storage not possible Internal device fault: however, the inverter continues to feed in.Corrective measures:

• If this fault occurs often, contact the SMA Serviceline (see section 4 "Contact", page 53).

73 Update main CPU failed Internal device faultCorrective measures:

• Contact the SMA Serviceline (see section 4 "Contact", page 53).

Update Bluetooth failed Internal device fault: however, the inverter continues to feed in.Corrective measures:

• Perform update again• If this fault occurs often, contact the SMA Serviceline

(see section 4 "Contact", page 53).

Update display failedUpdate RS485I module failedUpdate language table failed

7303 Update main CPU failed Update main CPU failed7305 Update RS485I module

failedUpdate RS485I module failed

7307 Update Bluetooth failed Update Bluetooth failed7309 Update display failed Update display failed7311 Update language table

failedUpdate language table failed

75 Fan fault Fan faultCorrective measures:

• Contact the SMA Serviceline (see section 4 "Contact", page 53).

77 Self diagnosis The inverter carries out a self test.Interference of device Corrective measures:

• Contact the SMA Serviceline (see section 4 "Contact", page 53).

80 Derating occurred The delivered power of the inverter was reduced below nominal power due to a too-high temperature for more than 10 minutes.Corrective measures:

• If the event arises frequently, ensure adequate ventilation.

• Check heat removal.

No. Display text Description

Page 51: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 3 DATA II+

Technical Description HF_STP_Par-eng-TUS114810 51

8001 Derating occurred See above81 Communication disturbed A fault has occurred in the internal communication of the

inverter. However, the inverter continues feeding into the grid.Corrective measures:

• If this event occurs often, contact the SMA Serviceline (see section 4 "Contact", page 53).

90 Changing of grid parameters not possible

Cause:• The DC voltage for the writing procedure is not

sufficient.• The selected rotary switch setting for the country

configuration is not programmed.• The parameters to be changed are protected.

Corrective measures:• Check setting of the rotary switch.• Enter Grid Guard Code.• Ensure sufficient DC voltage is available.

Installer code invalid Corrective measures:• Enter valid installer code.Grid parameter locked

Calibration failed Corrective measures:• If this event occurs often, contact the SMA Serviceline

(see section 4 "Contact", page 53).9002 Installer code invalid See above9003 Grid parameter locked See above9005 Waiting for main CPU Cause:

• DC voltage at the DC input is not sufficient to run the main CPU.

• The selected rotary switch setting for the country configuration is not programmed.

• The parameters to be changed are protected.Corrective measures:

• Make sure that there is sufficient DC voltage available (green LED is glowing or flashing).

• Check setting of the rotary switch.• Enter installer code.

No. Display text Description

Page 52: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

3 DATA II+ SMA America, LLC

52 HF_STP_Par-eng-TUS114810 Technical Description

100 General fault General error messageCorrective measures:

• Contact the SMA Serviceline (see section 4 "Contact", page 53).

10101 Setting of parameter … failed Setting of scalar parameter failed10102 Parameter … set successfully Status parameter set successfully10103 Setting of parameter … failed Setting of status parameter failed10104 Parameter … set successfully Parameter "…" set successfully10105 Setting of parameter … failed Setting of parameter "…" failed10108 Time adjusted / old time Time adjusted / old time10109 Time adjusted / new time Time adjusted / new time27103 Set parameter Parameter is set27104 Parameters set successfully Parameters were set successfully27107 Update file OK Update file checked and no errors found.27108 SD card is read SD card is read27109 No new update on the SD

cardNo new update on SD card

27301 Update communication Update communication27302 Update main CPU Update main CPU27304 Update RS485I module RS485I module update successful27306 Update Bluetooth Update Bluetooth27308 Update display Update display27310 Update language table Update language table27312 Update completed Update completed29001 Installer code valid Installer code valid29004 Grid parameter unchanged Grid parameter unchanged

No. Display text Description

Page 53: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,

SMA America, LLC 4 Contact

Technical Description HF_STP_Par-eng-TUS114810 53

4 ContactIf you have technical problems concerning our products, contact the SMA Serviceline. We require the following information in order to provide you with the necessary assistance:

• Type of inverter• Type and number of modules connected• Communication method• Sunny Boy failure or warning number• Display message of the Sunny Boy

SMA Solar Technology America, LLC6020 West Oaks Blvd, Ste 300Rocklin, CA 95765Tel. +1 916 625 0870Tel. +1 877-MY SMA TECHTel. +1 877 697 6283 (Toll free, available for USA, Canada and Puerto Rico)Fax +1 916 625 [email protected]

SMA Solar Technology Canada Inc.2425 Matheson Blvd E , 8th FloorMississauga, ON L4W 5K5 , CanadaTel. +1 877 506 1756 (Toll free, available for Canada)[email protected]

Page 54: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,
Page 55: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,
Page 56: Measured Values and Parameters SUNNY BOY …ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. This document does not and is not intended to replace any local, state, provincial,