MC000 M101 M801 M901 M902 NOTES, SYMBOLS & ABBREVIATIONS FIRST FLOOR PLAN SCHEDULES DETAILS DETAILS 1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HAS TOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION. 2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDING THAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS CONTAINED IN THE CONTRACT DOCUMENTS. IT IS THE INTENT OF THE CONTRACT DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES AND REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE CONTRACT DRAWINGS. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ENGINEER. 3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT/ENGINEER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK. 4. THE CONTRACT DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TO BE PROVIDED. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACT REQUIREMENTS TO BEST AVAILABLE STANDARDS AT THE SCALE INDICATED. 5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED AND COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONS DETERMINED USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICAL INTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONED DRAWINGS COORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTING SUCH INTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGS AND DISTRIBUTE SAME AS REQUIRED. 6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULE WORK IN ACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL OF THE WORK CAN BE INSTALLED WITHOUT DELAYING THE PROJECT. 7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGS SHALL BE FORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALL SUBSEQUENTLY IN SUCCESSION DELINEATE HIS RESPECTIVE WORK ON THESE COORDINATION DRAWINGS. WHEN ALL WORK HAS BEEN PROPERLY SHOWN ON THE COORDINATION DRAWINGS, AND ALL CONTRACTORS AGREE THAT THEIR RESPECTIVE WORK CAN BE INSTALLED AND WILL PROPERLY FIT TOGETHER, THEY SHALL SO ACKNOWLEDGE BY ENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TO COMPLETION OF ABOVE COORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED AND REPLACED AT CONTRACTOR’S EXPENSE. 8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT. 9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER’S WRITTEN INSTRUCTIONS. 10. SCHEDULE ALL SHUTDOWNS THAT AFFECT UTILITIES AND PORTIONS OF THE BUILDING THAT MUST REMAIN IN OPERATION WITH THE OWNER. 11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTION OF MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT. 12. PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT AND TRANSFER TO POINT OF INSTALLATION OWNER FURNISHED ITEMS. 13. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR. 14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAM PENETRATIONS AND CORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALL SUBMIT SIZE AND LOCATION TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL. 15. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THIS SCHEDULE SHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FOR THIS PROJECT, INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THE REQUIREMENTS OF DIVISION 1 OF THE SPECIFICATIONS. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO RECEIPT OF ENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE REPLACED AT CONTRACTOR EXPENSE. 16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATION DRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BE PROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NO SUBMISSION WILL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE CONTRACTOR. THE CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS. 17. PROVIDE AS-BUILT DOCUMENTS AND OPERATING/MAINTENANCE MANUALS AS SPECIFIED IN DIVISION 1 OF THE SPECIFICATIONS. 18. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND OR VIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER. OBJECTIONABLE SOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVED MANNER BY THE CONTRACTOR AT HIS EXPENSE. 19. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALED EQUIPMENT, VALVES, CONTROLS, ETC., AND COORDINATE THEIR DELIVERY WITH THE INSTALLING TRADE. 20. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST. 21. NOTIFY ARCHITECT / ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK AN DATE OF BOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE MINIMUM OF ONE WEEK PRIOR TO COMPLETION DATE TO ENABLE ARCHITECT / ENGINEER SCHEDULING OF PRELIMINARY PUNCHLIST INSPECTION PRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALL SIMILARLY NOTIFY ARCHITECT / ENGINEER OF COMPLETION OF ALL WORK, INDICATING THE CONTRACTOR IS READY FOR THE ARCHITECT / ENGINEER TO PERFORM THE FINAL PUNCHLIST INSPECTION. 22. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ARCHITECT / ENGINEER’S FINAL PUNCHLIST, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETION CERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC. HAVE BEEN SUBMITTED. 1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNING CODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE APPLICABLE CODES, AS AMENDED BY THE STATE OF NEW JERSEY. REFER TO ARCHITECTURAL PLANS FOR APPLICABLE CODES FOR THIS PROJECT. 2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASS EQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPING ROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIED BASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN. 4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANT WITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAME SPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’S RECOMMENDATIONS. NOTE: ALL DUCT SIZES SHOWN INCLUDE 1-1/2 OF INTERNAL OR EXTERNAL INSULATION. 5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED. FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE. FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT. 6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS IN BASEMENT AND ATTICS. 7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREAS SHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER. DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING 8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THEIR CODE APPROVED LISTINGS. 9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED. 10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATE CODES. 11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXES DURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY. 12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLET GRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TON FOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATING WITH A WARM AIR FURNACE. 13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES, EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSURE DROP SHALL NOT EXCEED 0.2 INCHES WC. 14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER’S REQUIREMENTS. 15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLER CABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCT MASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALL DUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOT EXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIR TIGHTNESS TESTER. 16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICAL CLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER. 17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR. 18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF 25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS AS SCHEDULED. 19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACK TECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS: A. WALL APPLICATION: MODEL RAP 14.8 20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES OR REGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR. 21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009 IBC AS SPECIFIED BELOW: A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTED PASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN 20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHES DEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT. B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY AN UNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVE A LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THE SERVICE SIDE OF THE EQUIPMENT. 22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCE WITH SECTION 307.2.3 OF THE 2009 IMC. 23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OR OTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BE PREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS. 24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDED ACCORDING TO SECTION 403 OF THE 2009 IMC. 25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BY ARCHITECT. 26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE DRYER MANUFACTURER AND APPLICABLE CODE. EACH VERTICAL RISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED. 27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANG FROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TO SUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLY UNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURAL ENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORK FROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALL INTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARING CAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDING STRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED. 28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS AS MANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE. 29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK AS REQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWN ON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS AND THE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOR OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES. 30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THE ARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THE PROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELD CONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARY TO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TO THE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILING HEIGHTS. 31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THE ARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THE OTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE. PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS. THE WORD “PROVIDE” SHALL MEAN “FURNISH AND INSTALL". THE CONTRACTORS SHALL BE RESPONSIBLE TO PROVIDE ALL LABOR AND MATERIALS AS REQUIRED AND AS INDICATED ON THESE CONTRACT DRAWINGS AND NOTES. THE WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THE FOLLOWING: 1. PERFORMANCE OF ALL WORK AS DESCRIBED ON THESE CONTRACT DRAWINGS AND AS REFERENCED IN THE SPECIFICATIONS AND NOTES AS APPLICABLE FOR EACH PARTICULAR CONSTRUCTION DISCIPLINE. 2. CONTRACTOR SHALL PROVIDE MECHANICAL SYSTEMS TO FEED NEW FIXTURES AND EQUIPMENT. INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE STATED MECHANICAL CODE. 3. RESTORATION OF EXISTING SYSTEMS, DEVICES, FINISHES, ETC. DAMAGED OR ALTERED BY NEW WORK TO ACCEPTABLE CONDITION AS DETERMINED BY THE OWNER, ARCHITECT AND/OR ENGINEER. 4. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL UTILITIES BEFORE WORK BEGINS. 5. CONTRACTOR SHALL PROVIDE CUTTING, CORING, AND PATCHING AS REQUIRED FOR INSTALLATION. 6. CONTRACTOR SHALL COORDINATE PHASING WITH BUILDING OWNER’S REPRESENTATIVE. 32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/ OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES, HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TO PROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS. THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONS REQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS. 33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING A SMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BE CONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESS OTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES AND BENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND. 34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROM GALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACT DRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM AND STAINLESS STEEL. 35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED. DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS. INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITH ACOUSTICAL LINING ADDED. 36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALED EQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIR DELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TO PERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENT POSSIBLE TO AVOID ACCESS DOORS IN THE CEILING. 37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THE CEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TO ALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHER LOCATIONS. 38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FOR FULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THE ARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPE FOR ALL DISCIPLINES/TRADES. 39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURAL DWGS, SPECS AND REQS. MECHANICAL SYSTEMS BASIS OF DESIGN ACCU AIR-COOLED CONDENSING UNIT AFF ABOVE FINISHED FLOOR ATG ACOUSTICAL TRANSFER GRILLE AU INDOOR AIR UNIT AWR ADJUSTABLE WALL REGISTER BD MANUAL BALANCING DAMPER BDD BACKDRAFT DAMPER BOD BOTTOM OF DUCT COND CONDENSATE DRAIN CA COMBUSTION AIR CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CLG CEILING CG CEILING GRILLE CR CEILING RETURN AIR GRILLE CRD CEILING RADIATION DAMPER CS CEILING SUPPLY REGISTER CW COLD WATER DISP DISPOSABLE DV DRYER VENT EA EXHAUST AIR EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE F, FURN GAS FIRED FURNACE FC FLEXIBLE CONNECTION FD FIRE DAMPER FL(S),FLR(S) FLOORS FR FLOOR REGISTER FRG FILTER RETURN AIR GRILLE FS FLOOR SUPPLY HHW HEATING HOT WATER HHWR HEATING HOT WATER RETURN HHWS HEATING HOT WATER SUPPLY HP HORSEPOWER HS HIGH SIDE HW HOT WATER HWE HIGH WALL EXHAUST AIR GRILLE HWR HIGH WALL RETURN AIR GRILLE IS INSECT SCREEN L LINING FOR ACOUSTICS LD LOUVERED DOOR LS LOW SIDE LSC LOCKSHIELD COVER LWC LOUVERED WALL CAP LWE LOW WALL EXHAUST AIR GRILLE LWR LOW WALL RETURN AIR GRILLE LWS LOW WALL SUPPLY REGISTER MA MAKE-UP AIR MFR MANUFACTURER MIN MINIMUM N/A NOT APPLICABLE NTS NOT TO SCALE OA OUTSIDE AIR OSTD OFFSET TRANSFER DUCT OTW OUT THRU WALL OV OVAL PERM PERMANENT PERM PERMANENT RJ ROOF JACK RA RETURN AIR RQD REQUIRED RQMTS REQUIREMENTS SA SUPPLY AIR SN SHEET NOTES T THERMOSTAT T R REVERSE ACTING THERMOSTAT TG TRANSFER GRILLE UTA UP TO ATTIC UTR UP THRU ROOF WC WALL CAP WCS WALL CAP w/INSECT SCREEN WH DOMESTIC WATER HEATER ZD ZONE DAMPER NOTE: THIS IS A GENERAL MECHANICAL LEGEND. ALL SYMBOLS MAY NOT APPEAR ON THE PLANS. REFER TO PLANS FOR ACTUAL SYMBOLS USED. SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ON THE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAY ADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THE BUILDING OCCUPANTS. 1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2% WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC. 2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS. MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE. WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937 OUTDOOR NON- RESIDENTIAL RESIDENTIAL WINTER DRY BULB 11 F 9.8 0 F 13 0 F SUMMER DRY BULB 92 F 92.6 0 F 90 0 F SUMMER WET BULB 75 F 74.4 0 F 73.7 0 F INDOOR WINTER DRY BULB 70 F SUMMER DRY BULB 75 F SUMMER RELATIVE HUMIDITY 50% MAX 2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS): STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2 F +/- 3 F ROOM TO ROOM TEMP. DIFF. MAX 4 F MAX 6 F FLOOR TO FLOOR TEMP. DIFF. MAX 4 F MAX 6 F TEMP. DIFF. (4” TO 67” AFF.) 1 F PER 15 F 3 F PER 10 F IN/OUT DIFF. IN/OUT DIFF. VD M M M DUCT WORK W/ ACOUSTIC LINING SINGLE LINE DUCTWORK - NEW MECHANICAL EQUIPMENT - NEW DUCTWORK / EQUIPMENT - EXISTING DUCTWORK / EQUIPMENT - DEMO DUCT UNDER POSITIVE PRESSURE (SUPPLY AIR OR FAN DISCHARGE) DUCT UNDER NEGATIVE PRESSURE (RETURN, EXHAUST OR OUTSIDE AIR) VANED ELBOW O R O R RADIUS ELBOW RECTANGULAR TO RECTANGULAR TRANSITION O R O R RECTANGULAR TO ROUND TRANSITION O R POSITIVE PRESSURE VERTICAL DROP (IN DIRECTION OF AIR FLOW) O R NEGATIVE PRESSURE VERTICAL DROP (IN DIRECTION OF AIR FLOW) O R POSITIVE PRESSURE VERTICAL RISE (IN DIRECTION OF AIR FLOW) O R NEGATIVE PRESSURE VERTICAL RISE (IN DIRECTION OF AIR FLOW) O R DUCT FLEXIBLE CONNECTION RIGID DUCTWORK TERMINATION FLEXIBLE DUCT BRANCH CONNECTIONS O R VOLUME DAMPER FIRE DAMPER & ACCESS DOOR SMOKE DAMPER & ACCESS DOOR BACK DRAFT DAMPER AUTOMATIC DAMPER (PNEUMATIC) AUTOMATIC DAMPER (ELECTRIC) COMBINATION SMOKE & FIRE DAMPER & ACCESS DOOR RISE IN DUCTWORK (IN DIRECTION OF AIR FLOW) DROP IN DUCTWORK (IN DIRECTION OF AIR FLOW) LOUVER IN DOOR UNDERCUT DOOR R D L U POINT OF CONNECTION POINT OF DISCONNECTION B P ACCESS PANEL C-8"Ø 235 CFM RECTANGULAR CEILING DIFFUSER W/ 8"Ø NECK 235 CFM SUPPLY AIR C-8"Ø 235 CFM ROUND CEILING DIFFUSER W/ 8"Ø NECK 235 CFM SUPPLY AIR 12" x 12" CEILING REGISTER (GRILLE) 260 CFM RETURN AIR G-12x12 260 CFM DIFFUSER W/ BLANKING PLATE EXHAUST FAN TRANSFER GRILLE "A" - 12x12 XXX - 1W = 1 WAY 2W = 2 WAY 3W = 3WAY 4W = 4 WAY MA = MULTI-ANGLE TYPE DESIGNATOR REFER TO REGISTER, GRILLE AND DIFFUSER SCHEDULE 4 WAY TYPICAL UNLESS INDICATED OTHERWISE AIR QUANTITY (CFM) T XX XX EQUIPMENT DESIGNATION T THERMOSTAT (PNEUMATIC) BOD BOTTOM OF DUCT ELEVATION FROM FLOOR GENERAL MECHANICAL NOTES MECHANICAL SCOPE OF WORK MECHANICAL ABBREVIATIONS MECHANICAL DRAWING LIST MECHANICAL BASIS OF DESIGN MECHANICAL NOTES MECHANICAL SYMBOLS CAMP SALUTE - CLUBHOUSE PROGRESS ISSUE - NOT FOR CONSTRUCTION BIM Server: bim19.kitchenandassociates.com - BIM Server 19/14204_CampSalute/14204_CampSalute_Club,NOTES, SYMBOLS & ABBREVIATIONS,Thursday, March 3, 2016,3:26 PM © 2016 - Kitchen & Associates.  All planning and architectural concepts shown on this document are the intellectual property of Kitchen & Associates MC000 03-03-16 14204 RW/AH/SW RW Date Date: Job #: Drawn: Mngr: Revision 14204_CampSalute_Club LIC. #:NJ PE GE030058 Stephen F. Finkelman COA#: 24GA28203000 NOTES, SYMBOLS & ABBREVIATIONS ©2015 - Kitchen & Associates. NORTH DELSEA DRIVE - BLOCK 1601, LOT 13 BOROUGH OF CLAYTON, NJ 08312

Upload: dinhnhi

Post on 28-Aug-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

MC000

M101

M801

M901

M902

NOTES, SYMBOLS & ABBREVIATIONS

FIRST FLOOR PLAN

SCHEDULES

DETAILS

DETAILS

GENERAL MECHANICAL NOTES1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HAS TOTALLY

FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HASAGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION OFEACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST PRACTICESOF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.

2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDINGTHAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THEBASIS OF INFORMATION SUCH AS CONTAINED IN THE CONTRACT DOCUMENTS. IT IS THE INTENT OF THECONTRACT DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOROPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES ANDREGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FORTHE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THEWORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE CONTRACT DRAWINGS.IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCHDEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FORAPPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ENGINEER.

3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT/ENGINEERAND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK.

4. THE CONTRACT DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVELOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TO BE PROVIDED.CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACTREQUIREMENTS TO BEST AVAILABLE STANDARDS AT THE SCALE INDICATED.

5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED ANDCOMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONSDETERMINED USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONED DRAWINGSCOORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTING SUCHINTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGS AND DISTRIBUTESAME AS REQUIRED.

6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULE WORK INACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL OF THE WORK CAN BE INSTALLEDWITHOUT DELAYING THE PROJECT.

7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGS SHALL BEFORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALL SUBSEQUENTLY IN SUCCESSIONDELINEATE HIS RESPECTIVE WORK ON THESE COORDINATION DRAWINGS. WHEN ALL WORK HAS BEENPROPERLY SHOWN ON THE COORDINATION DRAWINGS, AND ALL CONTRACTORS AGREE THAT THEIRRESPECTIVE WORK CAN BE INSTALLED AND WILL PROPERLY FIT TOGETHER, THEY SHALL SOACKNOWLEDGE BY ENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TO COMPLETION OFABOVE COORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED AND REPLACED ATCONTRACTOR’S EXPENSE.

8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.

9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER’S WRITTENINSTRUCTIONS.

10. SCHEDULE ALL SHUTDOWNS THAT AFFECT UTILITIES AND PORTIONS OF THE BUILDING THAT MUSTREMAIN IN OPERATION WITH THE OWNER.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTION OFMATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT.

12. PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT AND TRANSFER TO POINT OFINSTALLATION OWNER FURNISHED ITEMS.

13. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS ORWALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS ULLISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLEFOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTSOF THE MANUFACTURER TO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL ORFLOOR.

14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAMPENETRATIONS AND CORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALL SUBMIT SIZE ANDLOCATION TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.

15. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THIS SCHEDULESHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FOR THIS PROJECT,INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THE REQUIREMENTS OFDIVISION 1 OF THE SPECIFICATIONS. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TORECEIPT OF ENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BEREPLACED AT CONTRACTOR EXPENSE.

16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATIONDRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BEPROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NOSUBMISSION WILL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE CONTRACTOR. THECONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.

17. PROVIDE AS-BUILT DOCUMENTS AND OPERATING/MAINTENANCE MANUALS AS SPECIFIED INDIVISION 1 OF THE SPECIFICATIONS.

18. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND ORVIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER. OBJECTIONABLESOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVED MANNER BY THECONTRACTOR AT HIS EXPENSE.

19. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, CONTROLS, ETC., AND COORDINATE THEIR DELIVERY WITH THE INSTALLINGTRADE.

20. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALLDEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN ONE (1) YEARFROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIPDEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACEDWITHOUT ADDITIONAL COST.

21. NOTIFY ARCHITECT / ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK ANDATE OF BOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE MINIMUM OF ONE WEEKPRIOR TO COMPLETION DATE TO ENABLE ARCHITECT / ENGINEER SCHEDULING OF PRELIMINARYPUNCHLIST INSPECTION PRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALLSIMILARLY NOTIFY ARCHITECT / ENGINEER OF COMPLETION OF ALL WORK, INDICATING THECONTRACTOR IS READY FOR THE ARCHITECT / ENGINEER TO PERFORM THE FINAL PUNCHLISTINSPECTION.

22. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ARCHITECT / ENGINEER’SFINAL PUNCHLIST, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OFCOMPLETION CERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS,MANUALS, ETC. HAVE BEEN SUBMITTED.

MECHANICAL NOTES

1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNINGCODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE APPLICABLECODES, AS AMENDED BY THE STATE OF NEW JERSEY. REFER TO ARCHITECTURAL PLANS FORAPPLICABLE CODES FOR THIS PROJECT.

2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.

4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.

NOTE: ALL DUCT SIZES SHOWN INCLUDE 1-1/2 OF INTERNAL OR EXTERNAL INSULATION.

5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.

6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.

7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.

DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING

8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.

9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.

10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.

11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.

12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.

13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.

14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.

15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.

16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.

17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.

18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.

19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:

A. WALL APPLICATION: MODEL RAP 14.8

20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.

21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:

A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.

B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.

22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.

23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.

24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.

25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.

26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND APPLICABLE CODE. EACH VERTICALRISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.

27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.

28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.

29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.

30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.

31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.

32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.

33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.

34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.

35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.

36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.

37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.

38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.

39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.

MECHANICAL SYSTEMS BASIS OF DESIGN

SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.

1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.

WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937

OUTDOOR NON- RESIDENTIAL RESIDENTIAL WINTER DRY BULB 11∘F 9.8 0F 13 0F SUMMER DRY BULB 92 ∘F 92.6 0F 90 0F SUMMER WET BULB 75 ∘F 74.4 0F 73.7 0F

INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX

2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):

STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF.

MECHANICAL SCOPE OF WORK

THE WORD “PROVIDE” SHALL MEAN “FURNISH AND INSTALL".

THE CONTRACTORS SHALL BE RESPONSIBLE TO PROVIDE ALL LABOR AND MATERIALS ASREQUIRED AND AS INDICATED ON THESECONTRACT DRAWINGS AND NOTES. THE WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THEFOLLOWING:

1. PERFORMANCE OF ALL WORK AS DESCRIBED ON THESE CONTRACT DRAWINGS AND ASREFERENCED IN THE SPECIFICATIONS AND NOTES AS APPLICABLE FOR EACH PARTICULARCONSTRUCTION DISCIPLINE.

2. CONTRACTOR SHALL PROVIDE MECHANICAL SYSTEMS TO FEED NEW FIXTURES AND EQUIPMENT.INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE STATED MECHANICAL CODE.

3. RESTORATION OF EXISTING SYSTEMS, DEVICES, FINISHES, ETC. DAMAGED OR ALTERED BY NEWWORK TO ACCEPTABLE CONDITION AS DETERMINED BY THE OWNER, ARCHITECT AND/ORENGINEER.

4. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL UTILITIES BEFORE WORK BEGINS.

5. CONTRACTOR SHALL PROVIDE CUTTING, CORING, AND PATCHING AS REQUIRED FORINSTALLATION.

6. CONTRACTOR SHALL COORDINATE PHASING WITH BUILDING OWNER’S REPRESENTATIVE.

MECHANICAL NOTES1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNING

CODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE FOLLOWINGAPPLICABLE CODES, AS AMENDED BY THE STATE OF NEW JERSEY.

A. 2009 INTERNATIONAL BUILDING CODE - NEW JERSEY EDITION B. 2009 INTERNATIONAL RESIDENTIAL CODE - NEW JERSEY EDITION C. 2009 ENERGY CONSERVATION CODE - NEW JERSEY EDITION D. 2009 INTERNATIONAL MECHANICAL CODE - NEW JERSEY EDITION E. 2009 INTERNATIONAL FUEL GAS CODE - NEW JERSEY EDITION F. 2009 NATIONAL STANDARD PLUMBING CODE

2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.

4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.

NOTE: DUCT SIZES SHOWN ARE CLEAR INTERNAL DIMENSIONS.

5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.

6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.

7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.

DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING

8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.

9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.

10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.

11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.

12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.

13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.

14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.

15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.

16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.

17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.

18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.

19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:

A. WALL APPLICATION: MODEL RAP 14.8

20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.

21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:

A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.

B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.

22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.

23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.

24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.

25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.

26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND SECTION 504.6 OF THE 2009 IMC. EACHVERTICAL RISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.

27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.

28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.

29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.

30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.

31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.

32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.

33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.

34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.

35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.

36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.

37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.

38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.

39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.

MECHANICAL SYSTEMS BASIS OF DESIGN

SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.

1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.

WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937

OUTDOOR WINTER DRY BULB 11∘F SUMMER DRY BULB 92 ∘F SUMMER WET BULB 75 ∘F

INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX

2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):

STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF.

HVAC LEGEND

ACCU AIR-COOLED CONDENSING UNITAFF ABOVE FINISHED FLOORATG ACOUSTICAL TRANSFER GRILLEAU INDOOR AIR UNITAWR ADJUSTABLE WALL REGISTER

BD MANUAL BALANCING DAMPERBDD BACKDRAFT DAMPERBOD BOTTOM OF DUCT

COND CONDENSATE DRAINCA COMBUSTION AIRCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCG CEILING GRILLECR CEILING RETURN AIR GRILLECRD CEILING RADIATION DAMPERCS CEILING SUPPLY REGISTERCW COLD WATER

DISP DISPOSABLEDV DRYER VENT

EA EXHAUST AIREF EXHAUST FANESP EXTERNAL STATIC PRESSURE

F, FURN GAS FIRED FURNACEFC FLEXIBLE CONNECTIONFD FIRE DAMPERFL(S),FLR(S) FLOORSFR FLOOR REGISTERFRG FILTER RETURN AIR GRILLEFS FLOOR SUPPLY

HHW HEATING HOT WATERHHWR HEATING HOT WATER RETURNHHWS HEATING HOT WATER SUPPLYHP HORSEPOWERHS HIGH SIDEHW HOT WATERHWE HIGH WALL EXHAUST AIR

GRILLEHWR HIGH WALL RETURN AIR GRILLE

IS INSECT SCREEN

L LINING FOR ACOUSTICSLD LOUVERED DOORLS LOW SIDELSC LOCKSHIELD COVERLWC LOUVERED WALL CAPLWE LOW WALL EXHAUST AIR GRILLELWR LOW WALL RETURN AIR GRILLELWS LOW WALL SUPPLY REGISTER

MA MAKE-UP AIRMFR MANUFACTURERMIN MINIMUM

N/A NOT APPLICABLENTS NOT TO SCALE

OA OUTSIDE AIROSTD OFFSET TRANSFER DUCTOTW OUT THRU WALLOV OVAL

PERM PERMANENT

RJ ROOF JACKRA RETURN AIRRQD REQUIREDRQMTS REQUIREMENTS

SA SUPPLY AIRSN SHEET NOTES

T THERMOSTATTR REVERSE ACTING THERMOSTATTG TRANSFER GRILLE

UTA UP TO ATTICUTR UP THRU ROOF

WC WALL CAPWCS WALL CAP w/INSECT SCREENWH DOMESTIC WATER HEATER

ZD ZONE DAMPER

HVAC LEGEND

ACCU AIR-COOLED CONDENSING UNITAFF ABOVE FINISHED FLOORATG ACOUSTICAL TRANSFER GRILLEAU INDOOR AIR UNITAWR ADJUSTABLE WALL REGISTER

BD MANUAL BALANCING DAMPERBDD BACKDRAFT DAMPERBOD BOTTOM OF DUCT

COND CONDENSATE DRAINCA COMBUSTION AIRCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCG CEILING GRILLECR CEILING RETURN AIR GRILLECRD CEILING RADIATION DAMPERCS CEILING SUPPLY REGISTERCW COLD WATER

DISP DISPOSABLEDV DRYER VENT

EA EXHAUST AIREF EXHAUST FANESP EXTERNAL STATIC PRESSURE

F, FURN GAS FIRED FURNACEFC FLEXIBLE CONNECTIONFD FIRE DAMPERFL(S),FLR(S) FLOORSFR FLOOR REGISTERFRG FILTER RETURN AIR GRILLEFS FLOOR SUPPLY

HHW HEATING HOT WATERHHWR HEATING HOT WATER RETURNHHWS HEATING HOT WATER SUPPLYHP HORSEPOWERHS HIGH SIDEHW HOT WATERHWE HIGH WALL EXHAUST AIR

GRILLEHWR HIGH WALL RETURN AIR GRILLE

IS INSECT SCREEN

L LINING FOR ACOUSTICSLD LOUVERED DOORLS LOW SIDELSC LOCKSHIELD COVERLWC LOUVERED WALL CAPLWE LOW WALL EXHAUST AIR GRILLELWR LOW WALL RETURN AIR GRILLELWS LOW WALL SUPPLY REGISTER

MA MAKE-UP AIRMFR MANUFACTURERMIN MINIMUM

N/A NOT APPLICABLENTS NOT TO SCALE

OA OUTSIDE AIROSTD OFFSET TRANSFER DUCTOTW OUT THRU WALLOV OVAL

PERM PERMANENT

RJ ROOF JACKRA RETURN AIRRQD REQUIREDRQMTS REQUIREMENTS

SA SUPPLY AIRSN SHEET NOTES

T THERMOSTATTR REVERSE ACTING THERMOSTATTG TRANSFER GRILLE

UTA UP TO ATTICUTR UP THRU ROOF

WC WALL CAPWCS WALL CAP w/INSECT SCREENWH DOMESTIC WATER HEATER

ZD ZONE DAMPER

NOTE: THIS IS A GENERAL MECHANICAL LEGEND. ALLSYMBOLS MAY NOT APPEAR ON THE PLANS.REFER TO PLANS FOR ACTUAL SYMBOLS USED.

MECHANICAL NOTES

1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNINGCODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE APPLICABLECODES, AS AMENDED BY THE STATE OF NEW JERSEY. REFER TO ARCHITECTURAL PLANS FORAPPLICABLE CODES FOR THIS PROJECT.

2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.

4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.

NOTE: ALL DUCT SIZES SHOWN INCLUDE 1-1/2 OF INTERNAL OR EXTERNAL INSULATION.

5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.

6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.

7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.

DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING

8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.

9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.

10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.

11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.

12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.

13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.

14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.

15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.

16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.

17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.

18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.

19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:

A. WALL APPLICATION: MODEL RAP 14.8

20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.

21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:

A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.

B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.

22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.

23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.

24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.

25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.

26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND APPLICABLE CODE. EACH VERTICALRISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.

27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.

28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.

29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.

30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.

31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.

32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.

33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.

34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.

35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.

36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.

37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.

38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.

39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.

MECHANICAL SYSTEMS BASIS OF DESIGN

SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.

1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.

WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937

OUTDOOR NON- RESIDENTIAL RESIDENTIAL WINTER DRY BULB 11∘F 9.8 0F 13 0F SUMMER DRY BULB 92 ∘F 92.6 0F 90 0F SUMMER WET BULB 75 ∘F 74.4 0F 73.7 0F

INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX

2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):

STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF. VD

M

M

M

DUCT WORK W/ACOUSTIC LINING

SINGLE LINE DUCTWORK - NEW

MECHANICAL EQUIPMENT - NEW

DUCTWORK / EQUIPMENT -EXISTING

DUCTWORK / EQUIPMENT - DEMO

DUCT UNDER POSITIVE PRESSURE(SUPPLY AIR OR FANDISCHARGE)DUCT UNDER NEGATIVEPRESSURE(RETURN, EXHAUST OR OUTSIDEAIR)

VANED ELBOWOR

OR RADIUS ELBOW

RECTANGULAR TORECTANGULAR TRANSITION

OR

OR

RECTANGULAR TO ROUNDTRANSITION

OR

POSITIVE PRESSURE VERTICALDROP(IN DIRECTION OF AIR FLOW)

OR

NEGATIVE PRESSURE VERTICALDROP(IN DIRECTION OF AIR FLOW)

OR

POSITIVE PRESSURE VERTICALRISE(IN DIRECTION OF AIR FLOW)

OR

NEGATIVE PRESSURE VERTICALRISE(IN DIRECTION OF AIR FLOW)

OR DUCT FLEXIBLE CONNECTION

RIGID DUCTWORK TERMINATION

FLEXIBLE DUCT

BRANCH CONNECTIONSOR

VOLUME DAMPER

FIRE DAMPER & ACCESS DOOR

SMOKE DAMPER & ACCESSDOOR

BACK DRAFT DAMPER

AUTOMATIC DAMPER(PNEUMATIC)

AUTOMATIC DAMPER (ELECTRIC)

COMBINATION SMOKE & FIREDAMPER & ACCESS DOOR

RISE IN DUCTWORK (IN DIRECTION OFAIR FLOW)DROP IN DUCTWORK (IN DIRECTION OFAIR FLOW)

LOUVER IN DOOR

UNDERCUT DOOR

R

D

L

U

POINT OF CONNECTION

POINT OF DISCONNECTION

B

P

ACCESS PANEL

C-8"Ø235 CFM

RECTANGULAR CEILING DIFFUSERW/ 8"Ø NECK235 CFM SUPPLY AIR

C-8"Ø235 CFM

ROUND CEILING DIFFUSER W/ 8"ØNECK235 CFM SUPPLY AIR

12" x 12" CEILING REGISTER(GRILLE)260 CFM RETURN AIRG-12x12

260 CFM

DIFFUSER W/ BLANKING PLATE

EXHAUST FAN

TRANSFER GRILLE

"A" - 12x12XXX -

1W = 1 WAY2W = 2 WAY3W = 3WAY4W = 4 WAYMA = MULTI-ANGLE

TYPE DESIGNATORREFER TO REGISTER,GRILLE AND DIFFUSERSCHEDULE

4 WAY TYPICAL UNLESSINDICATED OTHERWISE

AIR QUANTITY (CFM)

T

XXXX

EQUIPMENT DESIGNATION

T THERMOSTAT (PNEUMATIC)

BOD BOTTOM OF DUCT ELEVATIONFROM FLOOR

GENERAL MECHANICAL NOTES

MECHANICAL SCOPE OF WORK

MECHANICAL ABBREVIATIONS

MECHANICAL DRAWING LIST

MECHANICAL BASIS OF DESIGN

MECHANICAL NOTES MECHANICAL SYMBOLS

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

NO

TES,

SYM

BOLS

& A

BBR

EVIA

TIO

NS,

Thur

sday

, Mar

ch 3

, 201

6,3:

26 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

MC000

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

NOTES, SYMBOLS &ABBREVIATIONS

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

F3

L3

T

L2

C3

C2

C1

T

L1

27

27

27

CU1

CU2

WW

WW

WW

DD

DD

DD

115 CFM10x10CD

115 CFM10x10CD

S1-130 CFM12x12CD

130 CFM12x12CD

14x12

6"⦰

6"⦰

14x12

10x10

18x12

10x10

12x12

115 CFM12x12WL

S2-100 CFM10x8WD

14x12

10x8DUCT UP

8"⦰

8"⦰

12x12

680 CFM20x20CR

S1-110 CFM9x9CD

75 CFM9x9CD

25 CFM6x6CD

25 CFM6x6CD

50 CFM

50 CFM

90 CFM9x9CD

75 CFM9x9CD

25 CFM6x6CD

MOUNT ABOVE WINDOW

225 CFM12x12

22x16

22x16

20

x16

12x1012x10

12x1012x10

12x10

DUCT UP

225 CFM12x12

225 CFM12x12

225 CFM12x12

288 CFM30x18WL

24x16 RETURN DUCT AIR

75 CFM

288 CFM18x12 WL

288 CFM14x14

8x8

6x6

10x8

10x8

6x6

6x6

8x8

6"⦰

100 CFM10x10

10x12

12x12

14x12

14x12

10x10

10x10

10x10

200 CFM24x12WL

BO

D 1

0'6

"

BO

D 1

0'6

"

DW

R

R

OFFICE

116

MGMT. OFFICE

115

VESTIBULE

101

EXERCISE

102

LAUNDRY

103

COMMUNITY ROOM

111

PATIO

01

CONSULT

118

KITCHENETTE

121

MEN

113

COMMON CORRIDOR

112

ELEC./IT

109

PORCH

01

PORCH

01

CONIFER CORRIDOR

110

STORAGE

107

JAN.

108

MAINTENANCE

104

SPRINKLER

105

MECH.

106

WOMEN

114

EF3

EF2

F1

EF4

EH6

EH6

EH6

HP2

HP1

EH5

F2

EF5

L2

EH1

R1

225 CFM12x12

16x1612x10

14x1212x10

225 CFM12x12

225 CFM12x12

225 CFM12x12

10"⦰

10"⦰

10"⦰

10"⦰

10"⦰

10"⦰

10"⦰

10"⦰

R2-1512 CFM20x20 WR

R1-12x12CR250 CFM

KEYED NOTES

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

INSTALL FURNACE PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE FULL SIZE (MIN. 3/4 INCH)COOLING COIL CONDENSATE PIPING WITH TRAP ANDFURNACE CONDENSATE PIPING FROM EQUIPMENT TO THEFLOOR DRAIN INDIRECT WASTE CONNECTION POINT WITHINTHE MECHANICAL ROOM. FLOOR DRAIN BY PLUMBINGCONTRACTOR. MAINTAIN A MINIMUM CLEARANCE OF 3" ATBACK AND SIDES OF FURNACE. PROVIDE INTER-CONNECTINGCONTROL WIRING BETWEEN FURNACE AND AIR-COOLEDCONDENSING UNIT ON GRADE.

CONNECT 2" PVC VENT PIPING AND COMBUSTION AIRPIPING TO FURNACE. ROUTE PIPING TO SIDEWALLTERMINATION KIT.

SIDEWALL TERMINATION KIT. INCREASE 2" VENT ANDCOMBUSTION AIR PIPING TO 3" VENT AND COMBUSTION AIRPIPING ON TERMINATION KIT AS REQUIRED.

PROGRAMMABLE THERMOSTAT. PROVIDE INTER-CONNECTING CONTROL WIRING.

COORDINATE LOCATION OF EXHAUST FAN WITH WOODTRUSSES.

LOCATION OF FURNACE COMBUSTION AIR AND AND VENTSIDEWALL TERMINATION KIT (MIN. 12" FROM ANY AIROPENINGS INTO THE BUILDING SUCH AS WINDOWS)

ROUTE DUCTWORK THRU OPEN WEB OF WOOD TRUSSES.

SIZE AND INSTALL REFRIGERANT PIPING ANDACCESSORIES IN ACCORDANCE WITH MANUFACTURER'SINSTRUCTIONS. ROUTE REFRIGERANT PIPING FROMMECHANICAL ROOMS TO AIR-COOLED CONDENSING UNITAND FROM LAUNDRY ROOM TO HEAT PUMP. RUN LINESFROM EQUIPMENT LOCATION TO AIR-COOLED CONDENSINGUNIT AND HEAT PUMP UNIT LOCATED ON GRADE. OFFSETPIPING AS REQUIRED.

ROUTE SUPPLY AIR DUCTWORK UP THRU CEILING TOBETWEEN WOOD TRUSSES. OFFSET DUCTWORK ASREQUIRED.

RUN FULL SIZE (MIN. 3/4 INCH) CONDENSATE DRAIN PIPINGIN CEILING SPACE FROM EQUIPMENT TO THE FLOOR DRAININDIRECT WASTE CONNECTION POINT LOCATED IN THEMECHANICAL ROOM.

MAINTAIN 30" CLEAR SERVICE CLEARANCE IN FRONT OFFURNACE.

NOT IN USE.

ALL DUCTWORK TRAVERSING THE ATTIC SPACE IN ORDERTO PASS THRU THE ROOF AND OUTSIDE AIR DUCTWORKSHALL BE INSULATED.

THE DUCT SHALL DISCHARGE THRU A ROOF JACK ON THEROOF. COLOR AS SELECTED BY ARCHITECT.

SUPPLY CEILING REGISTERS SHALL BE CENTERED ON THEWINDOWS.

PROVIDE RETURN AIR GRILLE MOUNTED HIGH ON WALL.TOP OF RETURN AIR GRILLE SHALL BE MOUNTED 3" BELOWCEILING. RETURN AIR GRILLE BLADES SHALL FACE UP FORSIGHT PROOF. PAINT AREA BEHIND GRILLES FLAT BLACK.

PROVIDE EACH AIR-COOLED CONDENSING UNIT AND HEATPUMP UNIT WITH AN ENGRAVED PLATE IDENTIFYING WHICHAREAS THE ACCU OR HP SERVES (I.E. "COMMUNITY ROOM","BUILDING PUBLIC AREA", ETC.).

MECHANICALLY FASTEN AIR-COOLED CONDENSING UNITAND MOUNTING KIT TO EQUIPMENT CURBS.

REFER TO FURNACE INSTALLATION DETAIL ON THE DETAILSHEET.

REFER TO DRYER AND LAUNDRY ROOM DETAILS ON THEDETAIL SHEET.

F-1 CONTROL SEQUENCE SHALL BE CONTROLLED BY ANOCCUPIED/UNOCCUPIED SCHEDULE PROGRAMMABLETHERMOSTAT. THE OUTSIDE AIR MOTORIZED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" DURING THEOCCUPIED CYCLE AS REQUIRED BY THE ROOM MOUNTEDCO2 SENSOR. THE OPERATION OF THE FURNACE & AIR-COOLED CONDENSING UNIT SHALL BE CONTROLLED BY THEPROGRAMMABLE ROOM MOUNTED THERMOSTAT.

F-2 CONTROL SEQUENCE SHALL BE CONTROLLED BY ANOCCUPIED/UNOCCUPIED SCHEDULE PROGRAMMABLETHERMOSTAT. THE OUTSIDE AIR MOTORIZED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" DURING THEOCCUPIED CYCLE. THE OPERATION OF THE FURNACE & AIR-COOLED CONDENSING UNIT SHALL BE CONTROLLED BY THEPROGRAMMABLE ROOM MOUNTED THERMOSTAT.

AU-1 CONTROL SEQUENCE SHALL BE CONTROLLED BY THEWALL MOUNTED PROGRAMMABLE THERMOSTAT.

INTERLOCK THE MOTOR OPERATED DAMPER TO EACHCLOTHES DRYER. THE MOTOR OPERATED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" UPON OPERATIONOF ANY ONE DRYER. THE ELECTRICAL CONTRACTOR SHALLPROVIDE DRYER AMP CURRENT SENSOR ON POWER SUPPLYOF EACH DRYER (COORDINATE LOCATION WITH ELECTRICALCONTRACTOR). WHEN ANY ONE DRYER IS ENERGIZED, THEMOTOR OPERATED DAMPER SHALL MODULATE "OPEN".WHEN DRYERS ARE DE-ENERGIZED, THE REVERSE SHALLOCCUR. THE MECHANICAL CONTRACTOR SHALL PROVIDEALL INTERLOCK CONTROL WIRING BETWEEN EQUIPMENT ANDMOTOR OPERATED DAMPER AND CONTROLLERS ATCONTROL VOLTAGE (NO LINE VOLTAGE) TO PROVIDECONTROL AS STATED.

PROVIDE METAL HOODED WALL VENT WITH CONCEALEDBACKDRAFT DAMPER AS MANUFACTURED BY MID-ATLANTICSIDING COMPONENTS. PROVIDE CUSTOM COLOR SELECTEDBY ARCHITECT. PROVIDE BAND CLAMP CONNECTIONS TODUCTWORK. CAULK AND SEAL WEATHER TIGHT.

LOCATION OF TEMPERATURE CONTROLLER WITHIN A

LOCKSHIELD COVER ON THE ROOM SIDE OF THE SHAFT.

N

SCALE: 1/4" = 1'-0"1 FIRST FLOOR PLAN

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

FIR

ST F

LOO

R P

LAN

,Thu

rsda

y, M

arch

3, 2

016,

3:26

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

M101

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

FIRST FLOOR PLAN

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

NOM.CAPACITY

TONSTAG LOCATION/SERVICE

C-1

SEER

NOTES:1. PROVIDE PRE-INSULATED REFRIGERANT LINE SET, COMPRESSOR RUBBER ISOLATION KIT, HARD START KIT, WIND BAFFLE FOR LOW AMBIENT

CONTROL AND ALL ACCESSORIES REQUIRED FOR LONG LINE APPLICATIONS, AS DETERMINED BY THE MANUFACTURER.

AIR-COOLED CONDENSING UNIT SCHEDULE

AT GRADE/ COMMUNITY RM.

CONDENSER FANS

NO. RPM HP NO. RLA STAGES

COMPRESSOR

V/PH/HZ MCA

ELECTRICALBASIS OF DESIGN

MFR/MODEL REMARKSEERREFRIG.AMBIENTTEMP.(ºF)

410A 95 5.0 14.25 12.25 1/4 835 1/5 1 134 1 208/2301ϕ 60HZ 32.7 YCIF60S41S2(E)

Y0RK REFER TO NOTE 1

C-2 AT GRADE/ MANAGEMENT 410A 95 2.0 14.5 12.3 1/8 850 1/8 1 58 1 16.8 REFER TO NOTE 1

C-3 AT GARDE/ CONSULTANT 410A 95 2.5 14.5 12.3 1/8 - - - 73 - 18.4 YCJF30S41S1(E) -

YCJF24S41S1(E)208/2301ϕ 60HZ208/2301ϕ 60HZ

MOD

50

25

30

TAG LOCATION/SERVICE TYPE CFM ESP(IN. WG.)

FANRPM

MOTORSIZE

HP(W)/AMP V/PH/HZBASIS OF DESIGN

MFR/MODEL REMARKSWEIGHT(LBS.)

FAN SCHEDULE

EF-2

EF-3

WOMEN'S ROOM.

MEN'S ROOM

CEILING

CEILING

115/1/60

115/1/60

SP-A50GREENHECK

SP-A50GREENHECK

EF-1 OFFICE / LOUNGE ROOM CEILING 115/1/60 SP-A90GREENHECK

50

50

100

700

700

9000.125

0.125

0.125

17.6/0.15

18.3/0.31

18.3/0.31

-

-

-

ELECTRICAL

EF-4 STORAGE ROOM CEILING 115/1/60 SP-A70GREENHECK

75 8500.125 15.9/0.14 -

NOTES:1.

-

-

-

-

-EF-5 COMMUNITY ROOM CEILING 115/1/60 SP-A290GREENHECK

288 10000.125 67/0.56 -

TAG

EH-1

NOTES:1. PROVIDE RECESSED UNIT IN COLOR AS SELECTED BY ARCHITECT. TAMPER PROOF THERMOSTAT .2. PROVIDE WALL MOUNTING BRACKET, BUILT-IN ADJUSTABLE THERMOSTAT AND COLOR AS SELECTED BY ARCHITECT.3. PROVIDE AIRFLOW SWITCH, DUCT THERMOSTAT AND DISCONNECT.4. PROVIDE w/BUILT-IN ADJUSTABLE THERMOSTAT AND TRANSFORMER. COLOR AS SELECTED BY ARCHITECT.5. PROVIDE INDIVIDUAL TEMPERATURE SENSOR WITH EACH UNIT CONTROLLED BY A COMMON CONTROLLER FOR ALL EH-5'S AND EH-6'S.

ELECTRIC HEATING SCHEDULE

LOCATION/SYSTEM

WALL/HEATING

REQ.CAPACITY

MBH

-

AIRSIDE

TEMPT.RISE

30/27

REMARKS

REFER TO NOTE 1

MAX PDIN/WG

-

BASIS OF DESIGNMFR/MODEL

933U01500VINDEECO

CFM

160

ELECTRICAL DATA

WATTS

1500/1125

TOTALAMPS

6.5/5.8

VOLTS(1 PHASE)

240/208

WEIGHT(LBS.)

24

SERVICE

VESTIBULE

EH-2 WALL/HEATING - 30/27 REFER TO NOTE 2- 933U01500VINDEECO160 1500

/11256.5/5.8 240/208 24MECHANICAL RM.

EH-3

EH-4 30/27 - 24MECHANICAL RM.WALL/HEATING - 160

EH-5

EH-6 CEILING/HEATING MAINTENANCE RM.

- ---

21/16 -300-

-

- 8.7/7.6

- -

240/208

-

20 924UO2000VAULI INDEECO

WALL/HEATING SPRINKLER RM. 933U01500VINDEECO

933U01500VINDEECO

1500/11251500/1125

160 6.5/5.86.5/5.8

30/27 24

-

240/208

240/208

--

DUCTLESS MINI SPLIT SYSTEM SCHEDULE (SPLIT SYSTEM HEAT PUMP)

CU-1

LOCATION/SERVICE

TAG REMARKS

NOTES:1. PROVIDE PRE-INSULATED REFRIGERANT LINE SET, ALL ACCESSORIES FOR LONG LINE APPLICATION, LOW AMBIENT CONTROL, WALL MOUNTED WIRELESS THERMOSTAT MODEL MHK1, FILTERS, CONDENSATE PUMP PACKAGE AND AIR OUTLET GUIDE

INDOOR UNIT OUTDOOR UNIT

AT GRADE/EXERCISE RM.

UNIT TYPE RQD

COOLINGCAPACITY

(MBH)AIR FLOW (CFM) WEIGHT

(LBS)

ELECTRICALFAN

MOTOROUTPUT(WATTS)

FANMOTORRLA (A)

BASIS OF DESIGNMFR/MODEL REFRIGERANT RQD COOLING

CAPACITY(MBH)

TOTALCOOLING

(MBH)

SEER FANMOTOR(WATTS)

COMPRESSOR MAX.

WEIGHT(LBS)

ELECTRICAL

V/PH/HZ MCA MODBASIS OF DESIGN

MFR/MODEL

WALLMOUNTED 18 501-460-383-324 29 20 0.28 DHPM18NWM42Q1A 410A 18 1.5 18 60 DC INVERTER 91

208/2301ϕ/60 HZ 16 20 DHPM18CSM42Q1A

MITSUBISHI REFER TO NOTE 1

V/PH/HZ

208/23060HZ

CU-2 AT GRADE/LAUNDRY RM.

WALLMOUNTED 18 590-472-413-354 29 20 0.24 DHPM24NWM42Q1 410A 18 2.0 18 90 DC INVERTER 91 16 20 DHPM18CSM42Q1A

MITSUBISHI REFER TO NOTE 1208/23060HZ

AMBIENTTEMP ˚F

95

95

EER

10

10

RLA

9.35

10.45 208/2301ϕ/60 HZ

TAG LOCATION/SERVICE

F-1

NOMINALAIRLFOW

NOTES:1. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT WITH HEAT-OFF-COOL, FAN AUTO-OFF SWITCHES, w/BATTERY BACK-UP, 1" MERV 8 FILTER FOR

INSTALLATION WITHIN BLOWER CABINET, FILTER RACK RAILS WITH RETAINING PINS & SPRINGS, COOLING COIL w/NON-BLEED TXV KIT (FACTORY INSTALLED),CONDENSATE NEUTRALIZER KIT AND HORIZONTAL TERMINATION KIT BAYVENT 200B BY TRANE.

GAS-FIRED FURNACE SCHEDULE

MECH RM/COMMUNITY RM

MOTOR

V/PH/HZ HP AMPS STARTER TMBH MODEL/SERIES

MIN.OUTPUT(MBH)

RQD COOLINGBASIS OF DESIGN

MFR/MODELREMARKSTYPE MIN. O.A.

CFM INPUT(MBH)

E.S.P.IN W.C.

REQ. HEATING

REFRIG.TYPE

CONDENSINGUPFLOW 2000 288 0.60 120/1/60 3/4 804 - 51.6 R410A - - 95 TM9E100C20MP11 -

F-2 1000 200 0.50 120/1/60 1/2 6.8 - 21.1 R410A - - 38 TM9E040A10MP11 -

AFUER%

95

95

F-3 MECH RM CONDENSINGUPFLOW 1200 115 0.50 120/1/60 1/2 6.8 - 25.0 R410A - - 57 TM9E060B12MP11 -95

MECH RM CONDENSINGUPFLOW

DIFFUSER REGISTER AND GRILLE SCHEDULE

CEILING SUPPLYS1

SERVICETAG CFM RANGE NECK DIA.(IN)

SIZE FACE(IN)

MAX.PD

(IN. WG)MAX. NOISE

(NC) PATTERN BASIS OF DESIGNMFR/MODEL REMARKS

R1

- HART & COOLEY/ARS SERIES

AS SHOWN REFER TO NOTES 1 & 2AS SHOWN - - -

-AS SHOWN - - -

-AS SHOWN - - -

-AS SHOWN - - -

CEILING RETURN HART & COOLEY/RH45AS SHOWN REFER TO NOTE 2

WALL SUPPLYS2

R2 WALL RETURN HART & COOLEY/RH45AS SHOWN REFER TO NOTE 2

HART & COOLEY/VHD SERIES

AS SHOWN REFER TO NOTES 1 & 2

NOTES:1. PROVIDE WITH MULTI-SHUTTER VALVE.2. PROVIDE STEEL MATERIAL IN STAIN WHITE.

TAG LOCATION/SERVICE CFM

NOTES:1. PROVIDE WITH MULTI-SHUTTER VALVE.2. PROVIDE STEEL MATERIAL IN STAIN WHITE.

LOUVER SCHEDULE

L1 MECHANICAL ROOM

WIDTH

24

RQD. FREEAREA (SQ.

FEET)

200 0.40

APPROXIMATE GROSS (NOM.) SIZE (IN.)

12

HEIGHT

AS REQ'D

DEPTHMAX P.D.IN W.G.

0.05

BIRDSCREEN

ALUM

BASIS OFDESIGN

MFR/ MODELREMARKS

GREENHECKESD-635 REFER TO NOTE 1

L2 MECHANICAL ROOM 30288 0.57 18 AS REQ'D 0.05 ALUM GREENHECKESD-635 -

L3 MECHANICAL ROOM AS REQ'D 0.05 ALUM GREENHECKESD-635 REFER TO NOTE 1

- - -- - - - - - - -

12115 0.23 12

REMARKSTAG

WALL MOUNTED/INDICATED ON

CONTRACT DWGS

ELECTRICALDATA

LOCATION /SERVICE

24V AC CLASS2 POWERSUPPLY

REFER TONOTE 1

BASIS OF DESIGNMFR/MODEL

CO2 MONITOR-JOHNSON

CONTROLS CD-WSERIES

CO2

CO2 SENSOR SCHEDULE

NOTES:1. PROVIDE w/RELAY MODULE TO OUTSIDE AIR VENTILATION

DAMPER. MOUNTING HEIGHT AFF SAME AS THERMOSTAT.

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

SCH

EDU

LES,

Thur

sday

, Mar

ch 3

, 201

6,3:

26 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

M801

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

SCHEDULES

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

MAIN DUCT/ COLLAR ANDCOLLAR/FLEXIBLE DUCTCONNECTIONS SEALEDWITH MASTIC

MAX SAG 1/2" PER FOOT (41.7mmPER m) OF SUPPORT SPACING

CLOSER MAXIMUM INTERVALSMAY BE SPECIFIED AS ACONDITION OF U.L. LISTING,PARTICULARLY IN FIRE RATEDFLOOR-CEILING ASSEMBLIES.

DUCT SHOULD EXTENDSTRAIGHT FOR ONEDUCT DIAMETER FROM ACONNECTION BEFOREBENDING.

3'-0" MAXIMUMMAIN AIR DUCT

SUPPLY DUCT

VOLUME DAMPER

SPINCOLLAR

CEILING DIFFUSER

CEILING

FLEX DUCT MAX. 5'-0"

DRAW BAND WITHSILICONE SEALER

DRAW BANDWITH SILICONESEALER

SIDE OF DUCT CONNECTION

CEILING DIFFUSERBOTTOM OF DUCT CONNECTION

SUPPLY DUCT

SPIN COLLAR

FLEX DUCT WHERE REQUIRED(MAX. LENGTH 5'-0")

FLEX DUCT SIZESSHALL MATCHDIFFUSER NECK SIZES

ROUND TO SQUAREADAPTERAS REQUIRED

CEILING

VOLUME DAMPER

DRAW BAND WITHSILICONE SEALER

OPPOSED BLADEDAMPER

OPPOSEDBLADE DAMPER

FLEX DUCT SIZESSHALL MATCHDIFFUSER NECK SIZES

PLAN OR SIDE VIEW

SHOWN SHALL APPLY.NOTE: UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES

DUCT TRANSITION

PLAN OR SIDE VIEW

ACCESS PANEL

EQUIPM

ENT 30° MAX20° MAX

20° MAX 30° MAX

15° MAX.

15° MAX.

FLOOR

FLOOR/CEILINGTRUSS SPACE

SUPPLY DUCT SIZED SAME ASCOIL CASING DISCHARGE SIZE

DX COOLINGCASED COIL

FURNACE

FLEXIBLE CONNECTION

COMBUSTION AIR &VENT PIPING ROUTE UPTHROUGH SPACE,REFER TO PLAN

PRIMARY/AUXILIARYCONDENSATE DRAINS

LINED RETURN PLENUM

FILTER RACK

SEPARATE COIL &FURNACE CONDENSATETO 1" AIR GAP ATFLOOR DRAIN

1/2" NEOPRENE ISOLATIONPAD

ROUTE RETURN DUCT TORETURN GRILLE PERLOCATION SHOWN ONPLAN

FLEXCONNECTION

REQUIRED ASINDICATED ON PLANS

ANCHORSTRUT TOBASE

STRUT CLAMPWITH PADDING

REFRIGERANTPIPING

GRADE

RUBBER SUPPORTBASE w/GALV.CHANNEL

NOTES:

A. MIFAB C SERIES ROOF SUPPORTS, 600 LB/FT LOAD LIMIT

PIPE SIZE PIPE MATERIAL

REFRIGERANT PIPINGSTEEL1/4" TO 9/4"

4 FT. MAX.

SUPPORT SPACING SCHEDULE

4"MIN.

(TYPICAL)12"C.C. MAX.

2"2"

COATED SURFACE OFINSULATION EXPOSED TO AIRSTREAM.

ALL ENDS OF LINER TO BECOATED WITH ADHESIVE(MIRACLE PF96). ENDS OF LINERSHALL BE BUTTED FIRMLYTOGETHER.

TOP AND BOTTOM SECTIONS OFLINER SHALL OVERLAP THESIDES.

NOTES:

GALVANIZED SHEET METALDUCT

1" THICK ACOUSTIC DUCT LINER,LINER TO BE ADHERED TODUCT WITH 100% ADHESIVE(MIRACLE PF96)

NOT MORE THAN 2" FROMEDGE OF DUCT LINER

GRIP NAILS SHALL BE INSTALLED BY "GRIP-NAIL AIR HAMMER" OR BY AUTOMATICFASTENER EQUIPMENT.

METAL FASTENERS:OMARK INSUL-PINS. DURA DYNEFASTENERS OR GRIP NAILS.

1

2

3

4

5

6

1

2

6

3 4 5 2 1

HW

W H

CRD (EASY ACCESS TYPE)RECTANGLE, OPEN POSITION

CRD (EASY ACCESS TYPE)RECTANGLE, CLOSED POSITION

UL LISTED LINK

BLADES 22 GA.GALV. STEEL

CERAMICFIBER WITHFIBERGLASSCOVER

STEEL DUCTDROP (BYOTHERS)

FIRSTDIMENSION

FIRSTDIMENSION

EXHAUST INTAKE(BEHIND PLATE)

PVC PIPE SIZED AS REQUIRED

COUPLING AS REQUIRED

PVC PIPE SIZED AS REQUIRED

WITH PVC PIPE

2 3/8"

12" MINIMUM(RECOMMENDED)

DO NOT BLOCK AIRINTAKE

DO NOT BLOCK AIR INTAKE

DO NOT BLOCK EXHAUST

EXTERIOR WALLCOMPOSITION MAYVARY WITH SPECIFICBUILDING

FIRE DAMPER

"S" TYPE SLIPFITTING

WALL SLEEVE

DUCTWORK

SLEEVE RETAININGANGLE

FIRE PARTITION

DUCT

SHEET METAL SAFING ORANGLES. ANGLES REQUIREDWHEN SAFING USED FOR DUCTSUPPORT AT FLOORS

DUCT LINING WHERE SHOWNON PLANS OR SPECIFIED

PACK SPACE WITHFIBROUS MATERIAL ANDSEAL BOTH SIDES.

NOTE:WHERE FIRE, SMOKE, OR COMBINATIONFIRE/SMOKE DAMPERS ARE REQUIRED,INSTALLATION SHALL BE PER DAMPERMANUFACTURER'S REQUIREMENTS.

SILICONE SEALANT

BOLT SAFING / ANGLES TOSTRUCTURE

6"

MIN 6" HIGHCONCRETE SLAB

4" CRUSHEDSTONE BASE

DRYER(TYPICAL)

PROVIDE 3/4"PLYWOOD BOXFRAME TO MATCHDIMENSIONS OFDRYER COMBUSTIONAIR INLET. REFER TODETAIL 13 THISDRAWING.

4"∅

12"

12"

16"

6"

26"

1"CHASE WALL

CAULK AND SEALAIR TIGHT

3/4" PLYWOOD BOX

PROVIDE COMPRESSIBLEWEATHER STRIPPING

NOTE:COORDINATE WITHDRYER LOUVERDIMENSIONS. DIMENSIONSBASED ON MACGRAYDRYER

30

"

FLOOR

FLEX CONNECTOR

CEILING

CLOTHESDRYER

4"∅ DV

SEAL OPENINGS AIR TIGHT

OUTSIDE AIR PLENUM

NOT TO SCALE2 TYPICAL FLEX DUCT DETAIL

NOT TO SCALE1 TYPICAL DIFFUSER CONNECTION DETAIL

NOT TO SCALE3 TYPICAL DUCT TRANSITION DETAIL

NOT TO SCALE7 FURNACE DETAIL

NOT TO SCALE5 PIPING SUPPORT DETAIL

NOT TO SCALE8 ACOUSTICAL LINING INSTALLATION DETAIL

NOT TO SCALE4 TYPICAL CEILING RADIATION DAMPER DETAIL

NOT TO SCALE6 FLUSH MOUNT VENT TERMINATION DETAIL

NOT TO SCALE11 FIRE DAMPER DETAIL

NOT TO SCALE12 SLAB/WALL DUCT PENETRATION DETAIL

NOT TO SCALE14 CONCRETE PAD SUPPORT DETAIL

NOT TO SCALE13 DRYER INTAKE DETAIL

NOT TO SCALE9 LAUNDRY RM. SECTION DETAIL

NOT TO SCALE10 DRYER DETAIL

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

DET

AILS

,Thu

rsda

y, M

arch

3, 2

016,

3:26

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

M901

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

DETAILS

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

"A"

2" AIR GAP

CLEANOUT PLUG(TYP)

TO SUITCONDITIONS

DRIP PAN

PAN WATERLEVEL

IPS. TO COPPERADAPTER. "B"

FLOOR LINE180° BEND

NOTES:

'A' = PLENUM STATIC PRESSURE AT DESIGN OPERATING CONDITIONS PLUS 1 1/2".

'B'= PIPE SIZE SHALL MATCH DRAIN PAN CONNECTIONBCT SHALL NOT BE LESS THAN 1 1/2".

"B"

INCH MINIMUM0.25xW OR 4

W

BALANCINGWHERE REQUIRED FOR AIRMANUAL DAMPER, PROVIDE

FLOW

AIR

FLOW

AIR

NOT TO SCALE1 CONDENSATE DRAIN PIPING DETAIL

NOT TO SCALE2 TYPICAL MAIN DUCT TAKE-OFF DETAIL

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

DET

AILS

,Thu

rsda

y, M

arch

3, 2

016,

3:26

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

M902

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

DETAILS

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

P000

P101

P900

NOTES, SYMBOLS & ABBREVIATIONS

FIRST FLOOR PLAN

RISER DIAGRAMS & SCHEDULES

SANITARY PIPING

PLUMBING EQUIPMENT

COLD WATER PIPING

PIPING DROP / ELBOW DOWN

PIPING RISE / VERTICAL LINE /ELBOW UP

HOT WATER PIPING

VENT PIPING ABOVE CEILING

GAS PIPINGG

ARROW INDICATES DIRECTIONOF FLOW

PITCH PIPE DOWN IN DIRECTION OFARROW

WCO WALL CLEANOUT

FLOOR CLEANOUT

UNDERGROUND SANITARY PIPING

BOTTOM PIPE CONNECTION

FCO

DRAIN & P-TRAP

METERM

XX

CAP

UNION

VALVE IN VERTICAL

CHECK VALVE

VALVEOR

BALL / GATE VALVE

HOSE BIBBHB

SANITARY VERTICAL STACKDESIGNATION (REFER TOCOMPOSITE BUILDING PLANSAND RISER DIAGRAMS FORNUMBERING)

DOMESTIC WATER VERTICALSTACK DESIGNATION (REFER TOCOMPOSITE BUILDING PLANSAND RISER DIAGRAMS FORNUMBERING)

KEY NOTE DESIGNATION

VACUUM BREAKERV

#S

#W

GENERAL PLUMBING NOTESPLUMBING NOTESPLUMBING ABBREVIATIONS

PLUMBING DRAWING LIST

PLUMBING SYMBOLS

A AMPERESAC AIR CONDITIONINGAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITALUM ALUMINUMARCH ARCHITECT

BP BOOSTER PUMPBT BATH TUB

C CENTER LINEøC DEGREES CELSIUSCB CAST IRON BOOTCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE

CONNECTIONCFM CUBIC FEET PER MINUTECLG CEILINGCO CLEANOUTCOND CONDENSATECONN CONNECTCONT CONTINUATIONCP CIRCULATION PUMPCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CHECK VALVECW COLD WATER

D DROPDF DRINKING FOUNTAINDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDR DRAINDTL DETAILDWG DRAWINGDW DISH WASHER

EL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALESP ELEVATOR SUMP PUMPET EXPANSION TANKEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXP EXPANSION

F FILTERºF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFF FINISHED FLOORFL FLOORFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOOR SINKFT FEET

G GASGAL GALLONGPH GALLONS PER HOURGPM GALLONS PER MINUTEGWH GAS WATER HEATER

HB HOSE BIBBHD HEADHP HORSE POWERHR HOURHT HEIGHTHW HOT WATERHWR HOT WATER RECIRCULATION

IN INCH OR INCHES

JC JANITOR'S CLOSETJS JANITOR'S SINK

KS KITCHEN SINKL LENGTHLAV LAVATORYLBS POUNDS

MER MECHANICAL EQUIPMENT ROOMMAX MAXIMUMMHP MOTOR HORSEPOWERMIN MINIMUMMR MOP RECEPTORMTD MOUNTED

NFWH NON-FREEZE WALL HYDRANTNIC NOT IN CONTRACTNO NORMALLY OPENNo NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE

OS&Y OUTSIDE SCREW & YOKE

P PUMPPD PUMP DISCHARGEPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE INCH ABSOLUTEPSIG POUNDS PER SQUARE INCH GAUGE

R RISERD ROOF DRAINRH RELATIVE HUMIDITYRLA RUNNING LOAD AMPSRM ROOMRPM REVOLUTIONS PER MINUTERPZ REDUCING PRESSURE ZONE BACKFLOW

PREVENTER

SA SHOCK ABSORBERSAN SANITARYSD SMOKE DETECTORSF SUPPLY FANSH SHOWERSP STATIC PRESSURESPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEAL

TD TRENCH DRAINTEMP TEMPERATURETYP TYPICAL

UNO UNLESS OTHERWISE NOTEDUR URINAL

V VENTVTR VENT THROUGH ROOF

W WASTEW/ WITHWC WATER CLOSETWCA WATER CLOSET ACCESSIBLEWCO WALL CLEAN OUTWFU WATER FIXTURE UNITW/O WITHOUTWH WATER HEATERWHA WATER HAMMER ARRESTERWMB WASHING MACHINE BOXWPD WATER PRESSURE DROP

1. ALL EQUIPMENT AND MATERIALS USED AND WORK PERFORMED SHALL BE IN ACCORDANCE WITHRULES AND REGULATIONS LISTED IN "CODE DATA" ON DRAWING CS-1 IN ADDITION TO THEAUTHORITY HAVING JURISDICTION.

2. PROVIDE ALL WORK AND MATERIALS AS REQUIRED IN THE SPECIFICATIONS AND ON THEDRAWINGS INCLUDING THE FOLLOWING:

A. DOMESTIC WATERB. SANITARY SEWERC. NATURAL GASD. CONDENSATE

3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY LICENSES ANDCERTIFICATIONS.

4. AT THE COMPLETION OF WORK, REMOVE ALL DEBRIS AND CLEAN STAINS CAUSED BYTHIS WORK.

5. ALL ABOVE GRADE PIPING SHALL BE PROPERLY SUPPORTED FROM THE BUILDINGSTRUCTURE AND SHALL NOT REST ON THE FINISHED CEILING.

6. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONSAND IN ACCORDANCE WITH THE REQUIREMENTS OF THE ELECTRICAL DRAWINGS.

7. WATER HEATER TEMPERATURE/PRESSURE RELIEF VALVE SHALL BE PIPED TO FLOORDRAIN IN ACCORDANCE WITH CODE REQUIREMENTS.

8. WATER SERVICE PIPING BELOW GRADE SHALL BE DUCTILE IRON WITH MECHANICAL JOINTFITTINGS.

9. WATER SERVICE PIPE THROUGH THE WALL SHALL BE PROTECTED WITH SLEEVEACCORDING TO CODE.

10. DOMESTIC WATER DISTRIBUTION PIPING SHALL BE SCHEDULE 40 CPVC WITH SOCKETFITTINGS AND SOLVENT CEMENTED JOINTS.

11. ALL HOT AND COLD WATER BRANCHES SHALL BE A MINIMUM OF 3/4” UNLESS OTHERWISENOTED.

12. PROVIDE SHUTOFF VALVES AT EACH FIXTURE LOCATION ACCORDING TO CODEREQUIREMENTS.

13. WATER PIPING IN THE ATTIC OR EXTERIOR WALLS SHALL BE PIPED ON THE INTERIOR SIDEOF THE INSULATION.

14. ABOVE GROUND SANITARY AND VENT PIPING AND FITTINGS SHALL BE SOLID WALLSCHEDULE 40 PVC WITH PVC SOCKET FITTINGS AND SOLVENT CEMENTED JOINTS.

15. SANITARY LINES SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8” PER FOOT FOR 4"AND LARGER PIPES, 1/4" PER FOOT FOR 3" AND SMALLER PIPES.

16. ALL VENTS THROUGH ROOF SHALL BE PROVIDED WITH 3" PIPE VENT EXTENSIONSTHROUGH THE ROOF IF FROST CLOSURE IN LIKELY OR WHERE REQUIRED BY LOCAL CODE.

17. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE INTENT OF THE CODEREQUIREMENTS. PIPING SHALL BE ROUTED UP, DOWN AND OFFSET AS REQUIRED TO SUIT FIELDCONDITIONS. DIELECTRIC COUPLINGS SHALL BE USED WHERE DISSIMILAR METALS ARE JOINED.

18. PIPING HANGERS SHALL BE SPACED SO AS TO PREVENT SAG AND PERMIT PROPERDRAINAGE AND SHALL NOT BE SPACED MORE THAN EIGHT (8) FEET APART UNLESS A GREATERSPACE IS DEFINITELY INDICATED ON THE DRAWINGS. A HANGER SHALL BE PLACED WITHIN ONE(1) FOOT OF EACH HORIZONTAL ELBOW. HANGERS SHALL BE SIZED TO FIT OVER INSULATIONAND BE PROVIDED WITH AN INSULATION SHIELD.

19. CONDENSATE DRAIN PIPING AND FITTINGS SHALL BE PVC.

20. INDIRECT WASTE PIPING SHALL BE COPPER.

21. THE INSTALLATION OF ALL INSULATION SHALL BE PERFORMED BY AN EXPERIENCEDCRAFTSMAN IN A NEAT WORKMANLIKE MANNER AND SHALL BE IN ACCORDANCE WITHMANUFACTURER'S PUBLISHED RECOMMENDATIONS FOR SERVICE INTENDED.

22. ALL MATERIALS OF INSULATION SHALL BE OF THE TYPE AND QUALITY AS MANUFACTUREDBY ARMSTRONG, CERTAIN TEED , OWENS-CORNING OR SCHULLER. ALL MATERIAL ANDEQUIPMENT SPECIFIED TO BE INSULATED SHALL BE THOROUGHLY TESTED AND APPROVEDPRIOR TO APPLYING THE INSULATION.

23. DOMESTIC WATER PIPING AND FITTINGS SHALL BE INSULATED PER THE SPECIFICATIONS.

24. CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH 1” THICK ARMSTRONG “ARMAFLEX”OR EQUAL. EXTERIOR INSULATION SHALL BE COATED WITH ULTRAVIOLET RESISTANT MATERIALIN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.

25. POTABLE WATER PIPING SHALL BE DISINFECTED PRIOR TO USE PER ANSI/AWWASTANDARD C651-92 OR LOCAL REQUIREMENTS. THE PIPING SHALL BE FILLED WITH A WATER-CHLORINE SOLUTION CONTAINING AT LEAST 50 PARTS PER MILLION OF CHLORINE AND SHALLBE VALVED OFF FOR 24 HOURS OR FILLED WITH A WATER -CHLORINE SOLUTION CONTAINING ATLEAST200 PARTS PER MILLION OF CHLORINE AND ALLOWED TO STAND FOR AT LEAST 3HOURS. FOLLOWING THE ALLOWED STANDING TIME , THE SYSTEM SHALL BE FLUSHED WITHPOTABLE WATER UNTIL NO CHLORINE REMAINS IN THE SYSTEM.

26. PROVIDE EACH FLOOR DRAIN WITH A TRAP PRIMER SYSTEM SIMILAR TO J.R. SMITH MFG.Co. FIGURE NUMBER 2689 PRIME TEAM OR IF ACCEPTABLE BY THE LOCAL AUTHORITIES,PROVIDE A TRAP SEAL GUARD EQUAL TO “TRAP GUARD” AS MANUFACTURED BY PROSETSYSTEMS.

27. PROVIDE SHOCK ABSORBERS FOR WASHING MACHINE.

28. PROVIDE TEMPERING VALVE ON TWO HANDLE FAUCET.

29. PROVIDE AMTROL #ST-5 EXPANSION TANK ON WATER HEATER.

30. DOMESTIC WATER SYSTEM TO BE INSULATED;

A. DOMESTIC COLD WATER SUPPLY: 1. Man-Made Mineral Fiber Insulation:

Pipe Size Range: ½” to 4 inchThickness: 1 inch

2. Cellular Glass Insulation:Pipe Size Range: ½” to 4 inch

Thickness: 1 inch3. Expanded Polystyrene Insulation:

Pipe Size Range: ½” to 4 inchThickness: 1 inch

B. DOMESTIC HOT WATER SUPPLY AND RECIRCULATION SYSTEM: 1. Man-Made Mineral Fiber Insulation:

Pipe Size Range: ½” to 4 inchThickness: 1 inch

2. Cellular Glass Insulation:Pipe Size Range: ½” to 4 inch

Thickness: 1 inch3. Expanded Polystyrene Insulation:

Pipe Size Range: ½” to 4 inchThickness: 1 inch

31. PROVIDE INSULATION ON THE ENTIRE SYSTEM INCLUDING FITTINGS, VALVES, UNIONS,FLANGES, STRAINERS, FLEXIBLE CONNECTIONS, PUMP BODIES ETC.A. PROVIDE FACTORY-APPLIED VAPOR RETARDER JACKETS. SECURE FACTORY-

APPLIED JACKETS WITH PRESSURE SENSITIVE ADHESIVE, SELF-SEALING LONGITUDINALLAPS AND BUTT STRIPS. SECURE FIELD-APPLIED JACKETS WITH OUTWARD CLINCHEXPANDING STAPLES AND SEAL STAPLE PENETRATIONS WITH VAPOR RETARDERADHESIVE OR PVC FITTING COVERS.

B. INSULATE FITTINGS, JOINTS, AND VALVES WITH MOLDED INSULATION OF LIKEMATERIAL AND THICKNESS AS ADJACENT PIPE. FINISH WITH GLASS CLOTH AND VAPORRETARDER ADHESIVE OR PVC FITTING COVERS.

32. ALL COMPONENTS OF THE POTABLE WATER SYSTEM SHALL COMPLY WITH THEENVIRONMENTAL PROTECTION AGENCY'S "REDUCTION OF LEAD IN DRINKING WATER ACT."

1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HASTOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITECONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FORTHE COMPLETE INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER INACCORDANCE WITH THE BEST PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALLAUTHORITIES HAVING JURISDICTION.

2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THEUNDERSTANDING THAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OFCONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS CONTAINED IN THECONTRACT DOCUMENTS. IT IS THE INTENT OF THE CONTRACT DRAWINGS ANDSPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION ANDIN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES AND REGULATIONS.MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTED NECESSARY FOR THEPROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS SHALL BE INCLUDED INTHE WORK AND IN THE PROPOSAL THE SAME AS SPECIFIED OR SHOWN ON THE CONTRACTDRAWINGS. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMEDNECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASON THEREFORE SHALL BESUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUTPRIOR APPROVAL OF THE ENGINEER.

3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT /ENGINEER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK.

4. THE CONTRACT DOCUMENTS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES ANDRELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TOBE PROVIDED. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHICREPRESENTATION OF CONTRACT REQUIREMENTS TO BEST AVAILABLE STANDARDS AT THESCALE INDICATED.

5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED

AND COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACTLOCATIONS USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONEDDRAWINGS COORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTINGSUCH INTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGSAND DISTRIBUTE SAME AS REQUIRED.

6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULEWORK IN ACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL THE WORK CANBE INSTALLED WITHOUT DELAYING THE PROJECT.

7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGSSHALL BE FORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALLSUBSEQUENTLY IN SUCCESSION DELINEATE HIS RESPECTIVE WORK ON THESE COORDINATIONDRAWINGS. WHEN ALL WORK HAS BEEN PROPERLY SHOWN ON THE COORDINATIONDRAWINGS, AND ALL CONTRACTORS AGREE THAT THEIR RESPECTIVE WORK CAN BEINSTALLED AND WILL PROPERLY FIT TOGETHER, THEY SHALL SO ACKNOWLEDGE BYENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TO COMPLETION OF ABOVECOORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED AND REPLACED ATCONTRACTOR'S EXPENSE.

8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.

9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'SWRITTEN INSTRUCTIONS.

10. SCHEDULE ALL SHUTDOWNS THAT EFFECT UTILITIES AND PORTIONS OF THE BUILDINGTHAT MUST REMAIN IN OPERATION WITH THE OWNER.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTIONOF MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH ORDEFECT.

12. PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT AND TRANSFER TO POINT OFINSTALLATION OWNER FURNISHED ITEMS.

13. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATEDFLOORS AND WALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOPMATERIAL THAT IS UL LISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIREDEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLEDIN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE ULLISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.

14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS,BEAM PENETRATIONS AND CORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALLSUBMIT SIZE AND LOCATION TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.

15. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THISSCHEDULE SHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FORTHIS PROJECT, INCLUDING ANY ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THEREQUIREMENTS OF DIVISION 1 OF THE SPECIFICATIONS. PROVIDE DRAWINGS OF ALLSPRINKLER PIPING, HEADS, VALVES, EQUIPMENT, MATERIALS, SIGNS FOR EACH FIREPROTECTION SYSTEM TO BE INSTALLED. ANY WORK INSTALLED OR EQUIPMENT PURCHASEDPRIOR TO RECEIPT OF ENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGESSHALL BE REPLACED AT CONTRACTOR EXPENSE.

16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELDINSTALLATION DRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTIONOF ALL ITEMS PROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOPDRAWINGS. NO SUBMISSION SHALL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THECONTRACTOR. THE CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.

17. PROVIDE AS-BUILT DOCUMENTS AND OPERATING / MAINTENANCE MANUALS AS SPECIFIEDIN DIVISION 1 OF THE SPECIFICATIONS.

18. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUNDOR VIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER.OBJECTIONABLE SOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVEDMANNER BY THE CONTRACTOR AT HIS EXPENSE.

19. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OFCONCEALED EQUIPMENT, VALVES AND CONTROLS, ETC., AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE.

20. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANYAND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESSTHAN ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANYDEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD SHALL BE REMEDIED ANDANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST.

21. NOTIFY ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK AND DATEOF BOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE A MINIMUM OF ONEWEEK PRIOR TO COMPLETION DATE TO ENABLE ENGINEER SCHEDULING OF PRELIMINARYPUNCHLIST INSPECTION PRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALLSIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK, INDICATING THE CONTRACTORIS READY FOR THE ENGINEER TO PERFORM THE FINAL PUNCHLIST INSPECTION.

22. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER'SPUNCHLIST, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OFCOMPLETION CERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC. HAVE BEEN SUBMITTED.

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

NO

TES,

SYM

BOLS

& A

BBR

EVIA

TIO

NS,

Thur

sday

, Mar

ch 3

, 201

6,3:

28 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

P000

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

NOTES, SYMBOLS &ABBREVIATIONS

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

ELEC./IT

109

CL.

120

MECH.

106

WW

WW

WW

DD

DD

DD

DW

R

RFCO

LT

WMB

WMB

WMB

WMB

WMB

WMB

MR

EWC

LAV LAV

LAV LAV

WC WCA

WCA

UR

SK

SK

FD2FD2

FD1

FD1

FD1

FD2

OFFICE

116

MGMT. OFFICE

115

VESTIBULE

101

PORCH

01

EXERCISE

102

COMMON CORRIDOR

112

CONIFER CORRIDOR

110

MAINTENANCE

104

LAUNDRY

103

STORAGE

107

COMMUNITY ROOM

111PATIO

01

CONSULT

118

MECH.

117

PORCH

01

KITCHENETTE

121

WOMEN

114

MEN

113

SPRINKLER

105

M

TD

FCO

NFWH

UTILITY NATURAL GAS METER.SIZE PER NATURAL GAS RISERDIAGRAM. COORDINATELOCATION OF METER WITHUTILITY COMPANY ANDELECTRIC METER.

NATURAL GAS SERVICE

NFWH

NFWH

FF = 00.00'

4" SANITARY

PROVIDE ADDITIONAL REDUCEDPRESSURE PRINCIPLE BACKFLOWPREVENTER FOR SITE IRRIGATION.SEE RISER DIAGRAM FORCONNECTION POINT.

WATER HEATER WH-1

CONCENTRIC VENT

DOMESTIC WATER UTILITY METER.

REDUCED PRESSURE PRINCIPLEBACKFLOW PREVENTER

DOMESTIC WATER SERVICE

LINT TRAP

N

SCALE: 1/4" = 1'-0"1 FIRST FLOOR PLAN

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

FIR

ST F

LOO

R P

LAN

,Thu

rsda

y, M

arch

3, 2

016,

3:28

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

P101

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

FIRST FLOOR PLAN

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

FCOTD

3"

1-1/2"

FD1

2"

1ST FLOOR

ROOF

FCO FD2

2"

FD2

4"

CO

WMB

LINTTRAP

WMB WMB WMB WMB WMB

1-1/2"

3"

MR

3"

EWC

1-1/2"

2"

LAVLAV

1-1/2"

2"

1-1/4"

2"

LAV LAV

1-1/2"

1-1/4"

2"

2"

SK

UR

WC FD1

2"

FD1

2"

WCAWCA

SK

FD2

2"

CO

3" 3"

WH-1

1"

ROOF

M

2" INCOMINGDOMESTICWATER SERVICE

1ST FLOOR 2"

1-1/2"

1-1/2" REDUCED PRESSUREZONE BACKFLOWPREVENTER, SIMILAR TOZURN WILKINS #375-S

WATERMETER

1-1/2" SUPPLY TOIRRIGATION SYSTEM. CAPFOR CONTINUATION BYIRRIGATION CONTRACTOR.

MREWC

3/4"

3/4"

3/4" LAV LAV WC WCA LAV LAV UR WCA 3/4" SK 3/4" SK

NFWH NFWH NFWH

WMB WMB WMB WMB WMB WMB

3/4" 3/4"

FLOOR

M

GRADE

ROOF

GAS METER

XXX"

XXX"XXX CFH

SHUTOFF VALVEEXPOSED INSPRINKLER ROOM

XXX CFH

XXX"XXX CFH

FURNACE

XXXCFH

XXX"XXX CFH

WATERHEATER XX" (TYP.)

24 CFH

XX"144 CFH

XX"24 CFH

3/4"120 CFH

XXX CFHFURNACE

XXX"XXX CFH

24 CFHDRYER

XXX"XXX CFH

XXX"XXX CFH

XXX"XXX CFH

XXX"XXX CFH

24 CFHDRYER

24 CFHDRYER

24 CFHDRYER

24 CFHDRYER

24 CFHDRYER

PLUMBING FIXTURE SCHEDULE & SPECIFICATIONS

WATER HEATER SCHEDULE

COMMUNITYROOM SINK

---1 1/4"1/2"1/2"

---

---1 1/2"1/2"1/2"

1/2" 1/2"

1/2" 1/2" 2" ---

3" ---

---3/4" -

FIXTURE NAMETAGVENT

MANUFACTURERDESCRIPTION MODELNUMBER

TRIM, FITTINGS, ACCESSORIESCONNECTION SIZES

CW SANHWREMARKS

-

- - ASNOTED

WMB WASHINGMACHINE BOX

FD1 FLOOR DRAIN

MR MOP RECEPTOR

LAV WALL HUNGLAVATORY

NFWH

SK

NON-FREEZEWALLHYDRANT

20-3/8" X 17-3/8" OVAL DROP-INLAVATORY, WHITE VITREOUSCHINA, FRONT OVERFLOW, ADACOMPLIANT, THREE FAUCETHOLES ON 4" CENTERS

0476.028AMERICANSTANDARD

PROVIDE W/ MOEN CHATEAU FAUCET MODEL#L4601 LAVATORY FAUCET W/ GRID DRAIN ANDSINGLE HANDLE OPERATION. PROVIDE PVC P-TRAP AND CHROME PLATED BRASS SUPPLIES/STOPS. PROVIDE W/ O.5 GPM AERATOR.

PROVIDE TRUBROINSULATION ON P-TRAP ANDEXPOSED SUPPLIES/STOPS.

STERLING 11403-325" x 22" x 6" SINGLE BOWLSINK, #20 GAUGE STAINLESSSTEEL, (3) FAUCET HOLES ON4" CENTERS, ADA COMPLIANT

PROVIDE W/ MOEN FAUCET MODEL # 7425KITCHENFAUCET W/ SINGLE LEVER, LESS SPRAY, 1.5 GPMAERATOR MODEL #116711. PROVIDE WITH BASKETSTRAINER, PVC P-TRAP AND SUPPLIES/STOPS.

MUSTEE 63M24" x 24" x 10" MOLDEDDURASTONE FIBERGLASSCOMPOSITE MOP RECEPTORW/ INTEGRAL MOLDED DRAINBODY.

PROVIDE W/ MOEN SERVICE FAUCET MODEL #8124

GALVANIZED STEEL WASHINGMACHINE OUTLET BOX,SINGLE LEVER HANDLE, 2"DRAIN

GUY GRAY WB200

WOODFORD 17CPFREEZELESS ANTI-SIPHON WALLFAUCET WITH WHEEL HANDLE

CAST IRON BODY FLOORDRAIN WITH ADJUSTABLECOLLAR AND POLISHEDNICKEL BRONZE, LIGHT-DUTYSTRAINER.

ZURN Z415B-P

ELKAY 1/2" - 1 1/4" ---

PROVIDE WATER HAMMER ARRESTORS ON HOTAND COLD WATER SUPPLIES TO CLOTHES WASHERS

1/2" --- 3" --- PROVIDE TRIP LEVER ONWIDE SIDE OF THE ROOM

PROVIDE WITH OPEN FRONT TOILET SEAT LESSCOVER, BEMIS MODEL #1955SSCT WITH STAINLESSSTEEL HINGES. PROVIDE WITH CHORME PLATEDBRASS ANGLE STOP VALVE.

WCA ADA WATERCLOSET

WHITE VITREOUS CHINA, HIGHEFFICIENCY, 1.28 GPF,ELONGATED BOWL, 16-1/2" RIMHEIGHT, TANK TYPE

COLONY221AA.104

PROVIDE EACH FLOOR DRAIN WITH ANAUTOMATIC TRAP PRIMER AND TRAP PRIMERCONNECTION

COORDINATE WITH ACTUALWALL THICKNESS.

-

TD TRENCH DRAIN ZURN ---- - 3"Z886-DGC6-1/4" WIDE REVEAL, HDPETRENCH DRAIN SYSTEM WITHCLASS C DUCTILE IRON GRATE.

SYSTEMTAG STORAGE CAPACITY(GAL.)

TYPE RECOVERY AT 100ºFTEMP RISE (GPM)

INPUT(AS NOTED)

ELECTRICAL

V PREMARKSMANUFACTURER AND

MODEL NUMBER

60 MBH

LOCATION

WH-1 DOMESTIC HOTWATER

MECHANICALCLOS.

NATURALGAS

48 58 120 1 BRADFORD WHITELG2PDV50H603N

VENT WATER HEATER THROUGH EXTERIORWALL WITH CONCENTRIC VENT TERMINAL KIT.

EWC ELECTRICWATERCOOLER

LRPB28KFULLY EXPOSED DUAL HEIGHTSTAINLESS STEEL FOUNTAINSWITH IN-THE-WALLREFRIGERATION SYSTEM ANDSTAINLESS STEEL GRILL.

REFRIGERATION SYSTEM SHALL BE CAPABLE OFPROVIDING 8.6 GPH OF 50 DEG F DRINKINGWATER AT 70 DEG F AMBIENT TEMPERATURE

SEE ARCHITECTURALELEVATION FOR MOUNTINGHEIGHT.

LT LINT TRAPCOATED INTERIOR, EXTERIORFABRICATED STEEL, NON-SKIDSECURED COVER W/ REMOVABLELIFT HANDLE, PERMANENTSTRAINING BAFFLE ANDSECONDARY LINT SCREEN.

ZURN Z1185 SIZE SHALL BE FOR A MAXIMUM OF 7 MACHINES. ---- - 3"

FD2 FLOOR DRAINCAST IRON BODY FLOORDRAIN WITH ADJUSTABLECOLLAR AND POLISHEDNICKEL BRONZE, LIGHT-DUTYSTRAINER, OVAL FUNNEL.

ZURN Z415B-P-OF PROVIDE EACH FLOOR DRAIN WITH ANAUTOMATIC TRAP PRIMER AND TRAP PRIMERCONNECTION AND OVAL FUNNEL

---- -2"

AMERICANSTANDARD

NOT TO SCALE1 SANITARY RISER DIAGRAM

NOT TO SCALE2 DOMESTIC WATER RISER DIAGRAM

NOT TO SCALE3 NATURAL GAS RISER DIAGRAM

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

RIS

ER D

IAG

RAM

S &

SCH

EDU

LES,

Thur

sday

, Mar

ch 3

, 201

6,5:

17 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

P900

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

RISER DIAGRAMS &SCHEDULES

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

E000

E101

E102

E801

ABBREVIATIONS & SYMBOLS

FIRST FLOOR POWER PLAN

FIRST FLOOR LIGHTING PLAN

SCHEDULES

A AMPERESACS AUTOMATIC CONTROL SYSTEMACT ACOUSTICAL CEILING TILEACU AIR CONDITIONING UNITAF AMPERE FRAMEAFCI ARC FAULT CURRENT INTERRUPTERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAIC AMPERES INTERRUPTING CAPACITYALUM ALUMINUMAMCS AUTOMATED MONITORING & CONTROL

SYSTEMAMP AMPERE, AMPACITYARCH ARCHITECTAT AMPERE TRIPATS AUTOMATIC TRANSFER SWITCHAWG AMERICAN WIRE GAUGE

C CONDUIT∘C DEGREES CELSIUSCAP CAPACITYCB CIRCUIT BREAKERCCP CENTRAL CONTROL PANELCCTV CLOSED CIRCUIT TELEVISIONCIRC. CIRCUITCKT CIRCUITCLG CEILINGCM CONTROL MODULECT CURRENT TRANSFORMERCUH CABINET UNIT HEATER

DC DIRECT CURRENTDDC DIRECT DIGITAL CONTROLDG DIESEL GENERATORDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDPDT DOUBLE POLE DOUBLE THROWDPSP DOUBLE POLE SINGLE THROWDS DISCONNECT SWITCHDWG DRAWING

E.C. ELECTRICAL CONTRACTORECB ENCLOSED CIRCUIT BREAKEREDH ELECTRIC DUCT HEATEREF EXHAUST FANEL ELEVATIONELEC ELECTRIC, ELECTRICALELEV ELEVATOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEP EXPLOSION PROOFEPO EMERGENCY POWER OFFEQ EQUALEUH ELECTRIC UNIT HEATEREWC ELECTRIC WATER COOLEREXH EXHAUST

ºF DEGREES FAHRENHEITFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFC FOOT CANDLE, FAULT CURRENTFCU FAN COIL UNITFD FIRE DAMPERFD/SD COMBINATION FIRE/SMOKE DAMPERFIXT FIXTUREFLA FULL LOAD AMPERESFLUOR FLUORESCENTFMC FLEXIBLE METAL CONDUITFT FEET

G GROUNDGAL GALLONGC GENERAL CONTRACTORGF GROUND FAULTGFI/GFCI GROUND FAULT CIRCUIT INTERRUPTERGND GROUNDGRS GALVANIZED RIGID STEELGWB GYPSUM WALL BOARD

HC HEATING COILHH HANDHOLEHLC HOUSE LIGHTING CONTRACTORHP HORSE POWERHPS HIGH PRESSURE SODIUMHR HOURHT HEIGHTHWY HIGHWAYHZ FREQUENCY (HERTZ)

I CURRENTIC INTERRUPTING CAPACITYIG ISOLATED GROUNDIMC INTERMEDIATE METAL CONDUITIN INCH OR INCHESINCA INCANDESCENTIT INFORMATION TECHNOLOGYJB JUNCTION BOX

K KILOKCM THOUSAND CIRCUIT MILLSKCMIL KILOCIRCULAR MILSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR

L LENGTHLBS POUNDSLCP LOCAL CONTROL PANELLFMC LIQUID-TIGHT FLEXIBLE METAL

CONDUITLIN .FT. LINEAR FEETLTG LIGHTINGLV LOW VOLTAGE

MC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCP MOTOR CIRCUIT PROTECTORMDP MAIN DISTRIBUTION PANELMER MECHANICAL EQUIPMENT ROOMMFS MAXIMUM FUSE SIZEMH MAN HOLEMHP MOTOR HORSEPOWERMIN MINIMUMMLO MAIN LUGS ONLYMTR MOTORMTD MOUNTEDMV MERCURY VAPORMX MECHANICAL ROOM EXHAUST

N NEUTRALNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATIONNF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNO NORMALLY OPENNo NUMBERNTS NOT TO SCALE

OPP OPPOSITE

P POLESPB PULL BOX, PUSH BUTTONPC PHOTOCELLPH PHASEPNL PANELPT POTENTIAL TRANSFORMERPWR POWER

RECEP RECEPTACLEREFL REFLECTORREFR REFRIGERANTRLA RUNNING LOAD AMPSRM ROOMRMC RIGID METAL CONDUITRMS ROOT MEAN SQUARERPM REVOLUTIONS PER MINUTE

SC SHORT CIRCUITSCCR SHORT CIRCUIT CURRENT RATINGSD SMOKE DETECTORSERV SERVICESF SUPPLY FANSMD SMOKE DAMPERSPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEELSW SWITCHSWBD SWITCH BOARDSWGR SWITCH GEARSYS SYSTEM

TBD TO BE DETERMINEDTC TIME CLOCKTCOM TELECOMMUNICATIONTEL TELEPHONETEMP TEMPERATURETVSS TRANSIENT VOLTAGE SURGE

SUPPRESSIONTYP TYPICAL

UC UNDER COUNTERUH UNIT HEATERUON UNLESS OTHERWISE NOTEDUV UNIT VENTILATOR

V VOLTSVA VOLT AMPEREVAC VACUUMVAV VARIABLE AIR VOLUME UNITVD VOLUME DAMPERVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVOL VOLUME

W WATTW/ WITHW/O WITHOUTWBT WET BULB TEMPERATUREWC WATER COLUMNWG WIRE GUARDWP WEATHER PROOF

XFMR TRANSFORMER

Z IMPEDENCE

JB JUNCTION BOX

K KILOKCM THOUSAND CIRCUIT MILLSKCMIL KILOCIRCULAR MILSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR

L LENGTHLBS POUNDSLCP LOCAL CONTROL PANELLFMC LIQUID-TIGHT FLEXIBLE METAL

CONDUITLIN .FT. LINEAR FEETLTG LIGHTINGLV LOW VOLTAGE

MC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCP MOTOR CIRCUIT PROTECTORMDP MAIN DISTRIBUTION PANELMER MECHANICAL EQUIPMENT ROOMMFS MAXIMUM FUSE SIZEMH MAN HOLEMHP MOTOR HORSEPOWERMIN MINIMUMMLO MAIN LUGS ONLYMTR MOTORMTD MOUNTEDMV MERCURY VAPORMX MECHANICAL ROOM EXHAUST

N NEUTRALNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATIONNF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNO NORMALLY OPENNo NUMBERNTS NOT TO SCALE

OPP OPPOSITE

P POLESPB PULL BOX, PUSH BUTTONPC PHOTOCELLPH PHASEPNL PANELPT POTENTIAL TRANSFORMERPWR POWER

RECEP RECEPTACLEREFL REFLECTORREFR REFRIGERANTRLA RUNNING LOAD AMPSRM ROOMRMC RIGID METAL CONDUITRMS ROOT MEAN SQUARERPM REVOLUTIONS PER MINUTE

SC SHORT CIRCUITSCCR SHORT CIRCUIT CURRENT RATINGSD SMOKE DETECTORSERV SERVICESF SUPPLY FANSMD SMOKE DAMPERSPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEELSW SWITCHSWBD SWITCH BOARDSWGR SWITCH GEARSYS SYSTEM

TBD TO BE DETERMINEDTC TIME CLOCKTCOM TELECOMMUNICATIONTEL TELEPHONETEMP TEMPERATURETVSS TRANSIENT VOLTAGE SURGE

SUPPRESSIONTYP TYPICAL

UC UNDER COUNTERUH UNIT HEATERUON UNLESS OTHERWISE NOTEDUV UNIT VENTILATOR

V VOLTSVA VOLT AMPEREVAC VACUUMVAV VARIABLE AIR VOLUME UNITVD VOLUME DAMPERVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVOL VOLUME

W WATTW/ WITHW/O WITHOUTWBT WET BULB TEMPERATUREWC WATER COLUMNWG WIRE GUARDWP WEATHER PROOF

XFMR TRANSFORMER

Z IMPEDENCE

3 4

LT

LT

PC

TC

J

XXXX

277/120 V SWITCH, SINGLE POLE, THREE-WAY AND FOUR-WAY, RESPECTIVELY.FLUSH MOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT; FOR ALLCOMMON AREA "HOUSE" WIRING SWITCHES, UTILIZE ONLY SPECIFICATION GRADESWITCHES RATED 20 A: FOR DWELLING UNITS, 15 A STANDARD GRADESWITCHES ARE PERMITTED ONLY WHERE CONTROLLING LIGHTING AND ONLYWHERE THE TOTAL LAMP WATTS CONTROLLED IS 1,000 W OR LESS (USE ONLY20 A STANDARD GRADE SWITCHES FOR CONTROLLING MOTORS AND OTHEREQUIPMENT)

F

120 V 300W COMBINATION LIGHT(INSTANT ON, INSTANT OFF) AND (INSTANT ON,INSTANT OFF) FAN CONTROL SWITCH, FLUSH MOUNTED, WHITE FINISH ANDCOVER PLATE, SEPARATELY WIRED TO FAN AND LIGHTING (INDEPENDENTLYCONTROLLED). MOUNT IN DEDICATED 1-GANG OUTLET BOX, STANDARDGRADE, CONNECT TO NON-AFCI BATHROOM LIGHTING CIRCUIT, LEVITON #1754-T" OR APPROVED EQUAL.

LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURE SCHEDULEINDICATES BRANCH CIRCUIT NUMBER

WALL MOUNTED LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULEINDICATES BRANCH CIRCUIT NUMBER

FLUORESCENT LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULEINDICATES BRANCH CIRCUIT NUMBER

INDICATES NIGHT-LIGHTING LUMINAIRE AND/OR ON EMERGENCY POWER CIRCUIT,UN-SWITCHED, ON 24 HOURS, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULE

EXIT SIGN, TYPE ("EXIT" UNLESS INDICATED OTHERWISE) AS INDICATED ON THELIGHTING FIXTURE SCHEDULE WITH DIRECTIONAL ARROW AS INDICATED

EMERGENCY LIGHTING BATTERY UNIT, ("EM" UNLESS INDICATED OTHERWISE) ASINDICATED ON THE LIGHTING FIXTURE SCHEDULE

REMOTE EMERGENCY LIGHTING HEADS, WALL MOUNTED, TYPE AS INDICATED ONTHE LIGHTING FIXTURE SCHEDULE

120 V DUPLEX RECEPTACLE, TAMPER RESISTANT, FLUSH MOUNTED, FINISH ANDCOVER PLATE AS PER ARCHITECT, (+) INDICATES ABOVE COUNTER MOUNTINGHEIGHT; FOR ALL COMMON AREA "HOUSE" RECEPTACLES, UTILIZE ONLYSPECIFICATION GRADE RECEPTACLES RATED 20 A; FOR DWELLING UNITS, 15 ASTANDARD GRADE RECEPTACLES ARE PERMITTED FOR CONVENIENCERECEPTACLES ONLY IN FAMILY ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,DENS, SUN ROOMS, BEDROOMS AND RECREATION ROOMS, WHERE APPLICABLE(USE ONLY 20 A STANDARD GRADE RECEPTACLES FOR KITCHENS, DININGROOMS, BATHROOMS AND RECEPTACLES SERVING EQUIPMENT, AS PER THETYPICAL DWELLING UNIT EQUIPMENT SCHEDULE)

20 A OR 15 A, 120 V DUPLEX RECEPTACLE, STANDARD GRADE, TAMPERRESISTANT, WITH ONE (1) RECEPTACLE POSITION CONTROLLED BY SWITCH ASINDICATED ON THE DRAWINGS AND WITH ONE (1) RECEPTACLE POSITION UN-SWITCHED, FLUSH MOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT, (+)INDICATES ABOVE COUNTER MOUNTING HEIGHT. CONNECT SO THAT TOP HALFOF RECEPTACLE IS SWITCHED.

20 A, 120 V DUPLEX GROUND FAULT CIRCUIT INTERRUPTER (G.F.C.I.) TYPE/PROTECTED RECEPTACLE, SPECIFICATION GRADE, TAMPER RESISTANT, FLUSHMOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT, (+) INDICATES ABOVECOUNTER MOUNTING HEIGHT, (WP) INDICATES MOUNTING IN A WEATHERPROOFOUTLET BOX WITH SINGLE SPRING-LATCHED IN-USE WEATHER-PROOF COVER;PROTECTION OF STANDARD TYPE RECEPTACLES FROM OTHER G.F.C.I.RECEPTACLES IS NOT ACCEPTABLE (EXCEPT THAT FEED THROUGH PROTECTIONIS PERMITTED FOR KITCHEN RECEPTACLES ONLY WHERE ALL PROTECTEDRECEPTACLE(S) ARE WITHIN SIGHT OF THE PROTECTING G.F.C.I. TYPERECEPTACLE AND PROVIDED PROTECTED RECEPTACLES ARE IDENTIFIED ASPROTECTED AS PER THE N.E.C.)

QUADRAPLEX ("DOUBLE DUPLEX") RECEPTACLE, WITH RECEPTACLE TYPE ASINDICATED

EQUIPMENT CONNECTION, REFER TO THE EQUIPMENT SCHEDULE AND THEEQUIPMENT NOTES FOR INFORMATION

EQUIPMENT DESIGNATION, FOR REFERENCE TO THE EQUIPMENT SCHEDULE

FUSED DISCONNECT (SAFETY) SWITCH, WITH SIZE, POLES AND FUSES ASINDICATED; IN NEMA-1 ENCLOSURE, (WP) INDICATES NEMA-3R ENCLOSURE; FORALL COMMON AREA "HOUSE" WIRING SWITCHES (AND ALL SWITCHES FED FROMEMERGENCY POWER), USEONLY HEAVY DUTY TYPE; FOR DWELLING UNITS, GENERAL DUTY TYPE ISPERMITTED

NON-FUSED DISCONNECT (SAFETY) SWITCH, WITH SIZE AND POLES ASINDICATED, HEAVY DUTY OR GENERAL DUTY TYPE, IN NEMA-1 ENCLOSURE, (WP)INDICATES NEMA-3R ENCLOSURE; FOR ALL COMMON AREA "HOUSE" WIRINGSWITCHES (AND ALL SWITCHES FED FROM EMERGENCY POWER), UTILIZE ONLYHEAVY DUTY TYPE; FOR DWELLING UNITS, GENERAL DUTY TYPE IS PERMITTED

ENCLOSED CIRCUIT BREAKER (ECB), WITH TRIP RATING AND POLES ASINDICATED, IN NEMA-1 ENCLOSURE, (WP) INDICATES NEMA-3R ENCLOSURE

M

THERMAL OVERLOAD SWITCH (I.E. MANUAL MOTOR STARTER, "O/L SWITCH"),277-120 V AND HORSEPOWER RATED, COORDINATE THERMAL OVERLOAD UNITRATING WITH LOAD SERVED; IN FINISHED SPACES, PROVIDE FLUSH MOUNTEDWITH COVER PLATE AS PER ARCHITECT; IN UNFINISHED SPACES, PROVIDE FLUSHMOUNTED OR SURFACE MOUNTED IN A SUITABLE NEMA-1 ENCLOSURE, (WP)INDICATES MOUNTING IN A NEMA-3R ENCLOSURE

ELECTRICAL PANEL, REFER TO THE SINGLE LINE DIAGRAM AND RESPECTIVEPANEL SCHEDULE

ELECTRICAL JUNCTION BOX (J-BOX), AS INDICATED ON THE DRAWINGS, WHEREJUNCTION BOX SERVICES EQUIPMENT, PROVIDE COMPLETE EQUIPMENTCONNECTION AS REQUIRED

PHOTOCELL, REFER TO SPECIFICATIONS, WALL MOUNTED

INDICATES HOME RUN OF WIRING TO PANEL AND CIRCUIT INDICATED

COMMON AREA TELEPHONE/DATA OUTLET, FLUSH MOUNTED, PROVIDE OWNERAPPROVED JACK AND COVER PLATE ON SUITABLE 2-GANG OUTLET BOX INWALL AND OWNER APPROVED CABLE (8-CONDUCTOR, "CATEGORY-6" STYLE)RUN FROM OUTLET TO MAIN TELEPHONE/CATV BACKBOARD, (+) INDICATESABOVE COUNTER MOUNTING HEIGHT OR WALL MOUNTED TELEPHONE MOUNTINGHEIGHT (COORDINATE WITH ARCHITECT/OWNER DURING CONSTRUCTION)

DWELLING UNIT TELEPHONE/DATA OUTLET, FLUSH MOUNTED, PROVIDE OWNERAPPROVED JACK AND COVER PLATE ON SUITABLE 1-GANG OUTLET BOX INWALL AND OWNER APPROVED CABLE (8-CONDUCTOR, "CATEGORY-6" STYLE)RUN FROM OUTLET TO DWELLING UNIT SYSTEMS DISTRIBUTION BOX SERVINGDWELLING UNIT (INDIVIDUAL HOME RUN OF CABLE FROM EACH OUTLET IN EACHDWELLING, CONNECT AND TERMINATE ALL CABLES AT BOTH ENDS); (+)INDICATES ABOVE COUNTER MOUNTING HEIGHT OR WALL MOUNTED TELEPHONEMOUNTING HEIGHT (COORDINATE WITH ARCHITECT/OWNER DURINGCONSTRUCTION, FOR WALL MOUNTED TELEPHONE LOCATIONS PROVIDE COVERPLATE WITH STUDS TO FACILITATE WALL MOUNTED TELEPHONE)

XX

XX

XX

XX

XX

OCCUPANCY SENSOR LIGHTING CONTROL WITH INTEGRAL MANUAL OVERRIDETO "ON" PUSH BUTTON (S-OC), FLUSH MOUNTED ON WALL (ON FLUSH MOUNTEDOUTLET BOX), SELF-CONTAINED "STAND ALONE" TYPE (SINGLE SENSOR FORLOCAL LIGHTING CONTROL OF SINGLE CIRCUT ONLY), PASSIVE INFRARED (PIR)TYPE WITH INTEGRAL SWITCHING RELAY, RATED 1,800 VA FOR 120VOPERATION AND 4,000 VA FOR 277V OPERATION, SINGLE POLE SPECIFICATIONGRADE,WHITE FINISH.

OCCUPANCY SENSOR LIGHTING CONTROL (OC), FLUSH MOUNTED IN CELING FORCOMMON CONTROL OF LIGHTING(MULTIPLE SENSORS FOR LIGHTING CONTROLIN CONJUNCTION WITH REMOTE LIGHTING CONTROL RELAY MODULE(S), PASSIVEINFRARED (PIR) TYPE, SPECIFICATION GRADE, WHITE FINISH. PROVIDE POWERPACKS AND LOW VOLTAGE CONTROL WIRING AS REQUIRED.

OC

OC

DEDICATED EQUIPMENT RECEPTACLE, REFER TO EQUIPMENT SCHEDULE & NOTESFOR INFORMATION

TIME CLOCK, REFER TO SPECIFICATIONS, WALL MOUNTED

SDB

DWELLING UNIT SYSTEMS DISTRIBUTION BOX, FLUSH MOUNTED, FOR TELEPHONEAND CATV WIRING, TO SPLICE AND INTERCONNECT ALL TELEPHONE AND CATVDISTRIBUTION WIRING IN DWELLING UNIT TO INCOMING (FROM SERVICE)TELEPHONE AND CATV LINES SERVING DWELLING UNIT; PROVIDE TWO (2) OWNERAPPROVED TELEPHONE/DATA CABLES (8-CONDUCTOR, "CATEGORY 6" STYLE, 1ACTIVE AND 1 SPARE) AND ONE (1) TYPE "RG-6Q" CATV COMPANY APPROVEDCABLE RUN FROM EACH SDB TO MAIN TELEPHONE/CATV BACKBOARD; PROVIDELEVITON #SMC-140/47605-14W (OR APPROVED EQUAL) NOMINAL 14"x14"x4" (355mm X 355 mm X 100 mm) MANUFACTURED ENCLOSURE WITH COVER FACILITATINGSYSTEM EXPANSION BY ADDING MODULAR SYSTEM COMPONENTS (MODULARCOMPONENTS [SUCH AS DATA MODULES, TELEPHONE MODULES, MINI-HUBMODULES, VIDEO MODULES, AUDIO MODULES, CATV MODULES, POWER SUPPLYMODULES, ETC.] ARE NOT IN CONTRACT BUT MAY BE USED [AT THECONTRACTOR'S OPTION] IN LIEU OF SEPARATELY MOUNTED TELEPHONE/CATVCONNECTION COMPONENTS LIST BELOW): PROVIDE TELEPHONE CONNECTIONBRIDGE (LEVITON #47689-B OR APPROVED EQUAL) OR TELEPHONE CONNECTIONPUNCH-DOWN BLOCK ("110" STYLE) IN ENCLOSURE AS REQUIRED TOINTERCONNECT AND ACTIVATE ALL INCOMING AND OUTGOING BRANCHTELEPHONE CABLES (I.E. TO ACTIVATE ALL TELEPHONE OUTLETS); PROVIDE AFEMALE-FEMALE "F" CONNECTOR FITTING IN ENCLOSURE AS REQUIRED TOINTERCONNECT AND ACTIVATE ONE (1) OUTGOING BRANCH CATV CABLE FROMTHE INCOMING CATV SERVICE CABLE (I.E. TO ACTIVATE ONE (1) CATV OUTLET INTHE DWELLING UNIT , ALL REMAINING OUTLETS SHALL BE INACTIVE); LOCATE THEFOLLOWING AT THE DISTRIBUTION BOX:

FOR ALL UNITS EXCEPT THOSE IDENTIFIED AS H&VI: PROVIDE DOORBELLPOWER SUPPLY/ TRANSFORMER IN ENCLOSURE, EXACT TYPE AND RATINGS TOMATCH DOORBELL CHIME AND DOORBELL PUSH-BUTTON; INTERCONNECT WITHCHIME AND PUSH-BUTTON AS REQUIRED SO CHIME OPERATES WHEN PUSH-BUTTONIS PRESSED, PROVIDE INCOMING 120 VAC SUPPLY WIRING AND CONNECT TONEARBY RECEPTACLE CIRCUIT AS REQUIRED

FOR "H&VI" UNITS ONLY: PROVIDE STROBE/TELEPHONE INTERFACE ANDPOWER SUPPLY IN ENCLOSURE, EXACT TYPE AND RATINGS COORDINATED WITH TELEPHONE INDICATING STROBE LIGHT WIRING; INCLUDE COMPLETE WITHSUITABLE TELEPHONE INTERFACE TO ACTIVATE WHEN TELEPHONE RINGS:INTERCONNECT WITH STROBE AND TELEPHONE AS REQUIRED SO STROBEOPERATES WHEN THE TELEPHONE RINGS, PROVIDE INCOMING 120 VAC SUPPLYWIRING AND CONNECT TO NEARBY RECEPTACLE CIRCUIT AS REQUIRED

CABLE TELEVISION (CATV) OUTLET, FLUSH MOUNTED, PROVIDE CATV COMPANYAPPROVED STANDARD "F" CONNECTOR CATV JACK AND COVER PLATE ONSUITABLE OUTLET BOX IN WALL, AND TYPE "RG-6Q" CATV COMPANYAPPROVED CABLE RUN FROM OUTLET TO DWELLING UNIT SYSTEMSDISTRIBUTION BOX SERVING DWELLING UNIT (INDIVIDUAL HOME RUN OF CABLEFROM EACH OUTLET IN EACH DWELLING, CONNECT AND TERMINATE ALL CABLESAT BOTH ENDS); (+) INDICATES ABOVE COUNTER MOUNTING HEIGHT(COORDINATE WITH ARCHITECT/OWNER DURING CONSTRUCTION)

TV

S

SD

H

H

F

FS

C

TS

S

S

IC

IM

T

INT

F

F

F

FACP

ANN

FIRE ALARM CONTROL PANEL, ADDRESSABLE ANALOG TYPE, WITH INTEGRALBATTERY BACKUP, WITH MIMIUM POINT ADDRESSES AS REQUIRED FORCONNECTED DEVICES (OR 197 POINT ADDRESSES, WHICHEVER IS GREATER),WITH PROVISIONS TO EXPAND UP TO BUT NOT LESS THAN 750 POINTS BYADDING ADDRESSABLE ANALOG MODULES WITH INTEGRAL 80-CHARACTER(MINIMUM) KEYBOARD DISPLAY UNIT; PROVIDE TWO TELEPHONE/DATA OUTLETS(AS INDICATED ELSEWHERE ON THE ELECTRICAL SYMBOL LIST) MOUNTEDADJACENT TO CONTROL PANEL AND PROVIDE 27 mm (1") CONDUIT (WITH PULLWIRE) RUN FROM TELEPHONE/DATA OUTLET TO THE MAIN TELEPHONEBACKBOARD

FIRE ALARM REMOTE ANNUNCIATOR PANEL, 80-CHARACTER (MINIMUM)ALPHANUMERIC TYPE, EXACT MATCHING FIRE ALARM CONTROL PANEL, FLUSHMOUNTED, RED OR BEIGE FINISH AS PER ARCHITECT

FIRE ALARM AUDIO/VISUAL HORN/STROBE, ADA APPROVED TYPE PROVIDINGADA APPROVED COVERAGE, WITH SYNCHRONIZED TYPE STROBE, SEMI-FLUSHMOUNTED, 80" AFF TO BOTTOM OF LENS, 15/75 CANDELA UNLESS OTHERWISENOTED

FIRE ALARM AUDIO ONLY HORN, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, FLUSH MOUNTED

FIRE ALARM VISUAL ONLY STROBE, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, SYNCHRONIZED TYPE, FLUSH MOUNTED

FL

"H&VI ADAPTABLE" FIRE ALARM VISUAL ONLY STROBE LOCATION (OUTLET BOXWITH WIRING AND BLANK COVER, SEE TYPICAL DWELLING NOTES), FOR "H&VI"UNITS ONLY, PROVIDE A FIRE ALARM VISUAL ONLY STROBE AT EACH LOCATION.PROVIDE 100 CANDELA UNIT IN SLEEPING ROOMS.

FIRE ALARM MANUAL PULL STATION, METAL, NON-CODED, DOUBLE ACTION,FLUSH MOUNTED, ADDRESSABLE TYPE

FIRE ALARM SMOKE DETECTOR, ANALOG PHOTOELECTRIC TYPE,WITH SUITABLE BASE

SPRINKLER SYSTEM FLOW SWITCH CONNECTION, FURNISHED AND INSTALLED ONPIPING BY SPRINKLER CONTRACTOR AND WIRED TO FIRE ALARM SYSTEM (VIALOCAL IDENTIFICATION MODULE) BY E.C.

SPRINKLER SYSTEM TAMPER SWITCH CONNECTION, FURNISHED AND INSTALLEDON PIPING BY SPRINKLER CONTRACTOR AND WIRED TO FIRE ALARM SYSTEM(VIA LOCAL IDENTIFICATION MODULE) BY E.C.

SINGLE- OR MULTIPLE-STATION SMOKE ALARM, PHOTOELECTRIC TYPE, 120 VAC(WITH BATTERY BACKUP) OPERATION LOCAL TYPE (FEATURING ADA APPROVEDAUDIBILITY), NOT CONNECTED TO FIRE ALARM SYSTEM; INTERCONNECT ALLDETECTORS WITHIN EACH INDIVIDUAL UNIT; CONNECT TO NEARBY LIGHTINGCIRCUIT (IN LINE "TANDEM" SO ACTIVATION OF ANY ONE (1) SMOKE ALARMSOUNDS ALARM IN ALL SMOKE ALARMS), PROVIDE SMOKE ALARM OF A TYPEFULLY COMPATIBLE WITH STROBE UNITS BELOW; IN DWELLING UNITS NOTIDENTIFIED AS "H&VI" PROVIDE AUDIBLE SMOKE ALARMS ONLY (I.E. WITHOUTASSOCIATED STROBE UNIT), UTILIZE BRK ELECTRONICS #7010B OR APPROVEDEQUAL; IN DWELLING UNITS IDENTIFIED ON THE DRAWINGS AS "H&VI" PROVIDESMOKE ALARMS AS INDICATED ABOVE IN ADDITION TO A SEPARATE STROBEUNIT (FEATURING ADA APPROVED VISIBILITY) MOUNTED DIRECTLY ADJACENT TOEACH SMOKE ALARM, UTILIZE BRK ELECTRONICS #SL177 STROBE (IN ADDITIONTO DETECTOR) OR APPROVED EQUAL

L

"H&VI ADAPTABLE" TELEPHONE INDICATING STROBE LIGHT LOCATION (OUTLET BOXWITH WIRING AND BLANK COVER, SEE TYPICAL DWELLING NOTES); FOR "H&VI" UNITSONLY, PROVIDE TELEPHONE INDICATING STROBE LIGHT, ADA APPROVED TYPE,SEMI-FLUSH MOUNTED, WITH SPECIAL WORDING "BELL" ON THE STROBE, WITHSPECIAL FINISH AS PER THE ARCHITECT, TORK #TA 5500 SERIES OR APPROVEDEQUAL; INTERCONNECT WITH STROBE/TELEPHONE INTERFACE AND POWER SUPPLYAS REQUIRED SO STROBE OPERATES WHEN TELEPHONE RINGS.

INTERCOM ENTRANCE DOOR STATION, WITH INTEGRAL SPEAKER AND MICROPHONEMODULE, WITH QUANTITY OF DWELLING CALL PUSHBUTTONS TO MATCH DWELLINGSSERVED, SUITABLE FOR OUTDOOR INSTALLATION, FLUSH MOUNTED IN WALL(INCLUDE ALL CUTTING AND PATCHING EXTERIOR WALLS AS REQUIRED), AEGIS9000 SERIES WITH HEATER PAD AHP5 OR APPROVED EQUAL. PROVIDE SEPARATETELEPHONE LINE AND SURGE PROTECTOR USP1.

INTERCOM DWELLING STATION, WALL MOUNTED (AT WALL TELEPHONE MOUNTINGHEIGHT) WITH TELEPHONE TYPE HANDSET, WITH PROVISIONS FOR REMOTE DOOROPENING, FLUSH MOUNTED IN WALL, AEG15 SERIES OR APPROVED EQUAL

INTERCOM POWER SUPPLY UNIT (EXACT TYPE TO MATCH INTERCOM EQUIPMENT)

F

FIRE ALARM AUDIO ONLY MINI HORN, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, FLUSH MOUNTED

FIRE ALARM HEAT DETECTOR, ANALOG, WITH SUITABLE BASE190º FIXED TEMP190

COMBINATION CARBON MONOXIDE (CO) DETECTOR AND SINGLE-STATION SMOKEALARM, 120 VAC (WITH INTEGRAL BATTERY BACKUP) OPERATION LOCAL TYPE(FEATURING ADA APPROVED AUDIBILITY), NOT CONNECTED TO FIRE ALARMSYSTEM; INTERCONNECT ALL SMOKE ALARMS AND CO DETECTORS WITHIN EACHINDIVIDUAL DWELLING UNIT IN "TANDEM" SO ACTIVATION OF ANY ONE (1) ALARM ORDETECTOR SOUNDS ALARM IN ALL SMOKE ALARMS IN THE INDIVIDUAL UNIT;CONNECT TO NEARBY LIGHTING CIRCUIT (ON LINE SIDE OF ALL SWITCHES, DO NOTCONNECT TO A RECEPTACLE CIRCUIT OR CIRCUIT DEDICATED TO DETECTORS),PROVIDE CO DETECTOR OF A TYPE FULLY COMPATIBLE WITH SMOKE ALARM ANDSTROBE UNITS (SEE SMOKE ALARM SYMBOL ABOVE); IN DWELLING UNITS NOTIDENTIFIED AS "H&VI" PROVIDE AUDIBLE SMOKE ALARMS ONLY (I.E. WITHOUTASSOCIATED STROBE UNIT), UTILIZE BRK ELECTRONICS #SC7010B OR APPROVEDEQUAL; IN DWELLING UNITS IDENTIFIED ON THE DRAWINGS AS "H&VI". PROVIDESMOKE ALARMS AS INDICATED ABOVE IN ADDITION TO A SEPARATE STROBE UNIT(FEATURING ADA APPROVED VISIBILITY) MOUNTED DIRECTLY ADJACENT TO EACHSMOKE ALARM, UTILIZED BRK ELECTRONICS #SL177 STROBE (IN ADDITION TODETECTOR) OR APPROVED EQUAL.

CO

DUCT MOUNTED SMOKE DAMPER,

FIRE ALARM HEAT DETECTOR, ANALOG, WITH SUITABLE BASE 165º

CONTROL MODULE

ELECTRICAL SYMBOLSELECTRICAL ABBREVIATIONS ELECTRICAL DRAWING LISTELECTRICAL SYMBOLS

STANDARD MOUNTING HEIGHTSSCALE: NTS

EXIT SIGN (UON) EMERGENCY LIGHTINGFIXTURE (UON)

FIRE ALARM NOTIFICATION DEVICE (UON)

SINGLE SWITCH (UON)

DUAL SWITCH (UON)

GFI DUPLEX RECEPTACLE (UON)THERMOSTAT (UON)

TEMPERATURE SENSOR (UON)

FIRE ALARM PULL STATION (UON)

HORIZONTAL DATA OUTLET (UON)

DATA OUTLET (UON)DOUBLE DUPLEX RECEPTACLE/ QUAD RECEPTACLE (UON)

HORIZONTAL DUPLEX RECEPTACLE (UON)

+96" AFF

+84" AFF

+48" AFF

+18" AFF

FINISHED FLOOR

FINISHED CEILING

EXIT

NURSE CALL STATION (UON)

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

ABBR

EVIA

TIO

NS

& SY

MBO

LS,T

hurs

day,

Mar

ch 3

, 201

6,3:

29 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

E000

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

ABBREVIATIONS &SYMBOLS

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

EF5

C3

C2

C1

F3

F2

EH1

HP2

5

1

1

EH-

S

JH

EF4

S

S

S

S

EF2

CU2

CU1

HP1

EH5

F1

WW

WW

WW

DD

DD

DD

Trash

Trash

Trash

CB1-3

CB1-5

CB1-1

CB1-7

CB1-1

CB1-1

CB1-16

FOR MICROWAVEOVEN CB1-14

FOR DISHWASHERCB1-15

CONNECT TO ROOMLIGHTING CIRCUIT

WP

CB1-23

CB1-1

TV

CB1-5

CB1-1

MOUNT INATTICSPACE

190

CB1-(35,37)CB1-(31,33)CB2-(35,37)

CB1-1

WPWPWP

CB1-39

CB2-14

CB2-17CB2-17

CB2-23

WP

CB2-17

CB2-20

CB2-20

CB1-20

EWH

CB2-20

CB2-20

CB2-20

CB1-21

CB2-20

CB2-20 CB2-23

CB2-23

CB1-7+42 CB1-7

CB1-7

CB1-41

CB1-23WP

CB2-39

CB1-12CB1-10

CB1-10

CB1-10

CB1-10CB1-8

CB1-8

CB1-8

TV

CB1-12

CB2-12

CB1-12

190

CB2-2

CB2-4

CB2-6

CB2-8

CB2-10

CB2-21

CB2-3

CB2-5

CB2-7

CB2-9

CB2-11

CB2-27&29

4' x 5' x 3/4" FIRERETARDANTPLYWOOD BACKBOARD

CB1-13

CB1-12

CB2-13

CB2-23

WP+48CB2-16

MOUNT INATTIC SPACE

190

CB1-17

CB1-32,34 &36

CB2-25

CB2-25

CB2-25

CB2-25

CB2-25

WP

CB1-23

CB2-25

CB2-25

CB2-23

CB2-23

CB2-23

CB2-23

CB1-9 CB1-9 CB1-9

CB1-9CB1-9CB2-23

DW

R

R

OFFICE

116MGMT. OFFICE

115

VESTIBULE

101EXERCISE

102

LAUNDRY

103

MAINTENANCE

104

MECH.

106SPRINKLER

105

PATIO

01

CONSULT

118

KITCHENETTE

121

MECH.

117

MEN

113

COMMON CORRIDOR

112

STORAGE

107

ELEC./IT

109

PORCH

01

PORCH

01CONIFER CORRIDOR

110

COMMUNITY ROOM

111

WOMEN

114

JAN.

108

2

2

S

S

F

H

H

CR

FACP

WF TS F S

S

S

S

F

S

S

S

ANN

CR

DS

6

S

H

3

F

DS

CR

EH6

EH6

H

S

SCPDCPPRPS

DCPPRPS

J

4

CR

DS

F

F

FF

F

F

EF3

TT

EH6

CB1-3

CB1-3

CB1-22

CB1-2+42

CEILING FAN(TYPICAL FOR 2)

CB2-15

+44CB1-19

+44CB1-19

CB2-31

CB2-33

CB2-17

PANEL"CB1"

PANEL"CB2"

CB2-32CONNECT TOLIGHTING CKT

CB1-7

CB1-7

CONNECT TOTOILETLIGHTING CKT

KEYED NOTES

1

2

3

4

5

6

MOUNT ACCESS CONTROL PANELS ON WALL ABOVECEILING.

PROVIDE 52" ENERGY STAR RATED CEILING FAN.BASIS OF DESIGN: 15030-962 QUALITY MAX 52" CEILINGFAN BY SEA GULL LIGHTINFG OR APPROVED EQUAL.HOUSING FINISH TO BE BRUSHED NICKEL. BLADE FINISHTO BE OAK. PROVIDE 2' DOWNROD EXTENSION.COORDINATE WITH LIGHTING FIXTURES AND SLOPE OFCEILING.

PROVIDE TELEPHONE CONNECTION FOR DEBITMACHINE IN LAUNDRY ROOM 106. COORDINATELOCATION WITH ARCHITECT.

PROVIDE JUNCTION BOXES WITH BLANK COVERS INTHE RAFTER SPACE FOR FUTURE RADON FANCONNECTIONS. CONNECT RADON FAN JUNCTION BOXESTO 20A, 120V BRANCH CIRCUIT IN PANEL "CB2". FINALQUANTITIES AND LOCATIONS OF RADON FAN JUNCTIONBOXES TO BE DETERMINED, COORDINATE WITHARCHITECT, REFER TO ARCHITECTURAL DRAWINGS ANDSPECIFICATIONS FOR ADDITIONAL INFORMATION.

ACCESS PANEL TO ATTIC SPACE. COORDINATELOCATION WITH ARCHITECT. PROVIDE GFI RECEPTACLEAND PORCELAIN SOCKET WITH PULL CORD AND 45WCFL R20 GE SMART ENERGY LAMP ABOVE ACCESSPANEL. CONNECT TO RADON FAN CIRCUIT, PROVIDEADDITIONAL PORCELAIN SOCKET AND LAMP AT RADONFAN JUNCTION BOX AS SHOWN.

SPRINKLER SYSTEM ELECTRIC BELL, INSTALL BELL(FURNISHED BY FIRE PROTECTION SYSTEMCONTRACTOR) AND PROVIDE 2#12,#12G IN 3/4"C ANDCONNECT SO THAT BELL SOUNDS WHEN WATER FLOWSWITCH IS ACTIVATED.

N

SCALE: 1/4" = 1'-0"1 FIRST FLOOR POWER PLAN

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

FIR

ST F

LOO

R P

OW

ER P

LAN

,Thu

rsda

y, M

arch

3, 2

016,

3:29

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

E101

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

FIRST FLOORPOWER PLAN

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

CB1-26CH

1

33

1

CB2-20CH

CB2-20CH

331

3

CB1-24CH

CB1-24CH

4

OC

1

1

1

CL

CB1-26

CLCB1-26

1

4

1

4

CB

1-26

CL

CB

1-26

CL

1

CB1-24

CA

CB1-24

CA

OC

CB2-20

CA

CB2-20

CA

CB1-24

CA

1

31

1

3

1

CB

1-26

CI

CB

1-26

CI

F

3

3

CB2-19

CA

CB2-19

CA

CB2-19

CA

CB2-19

CA

CB2-19

CB

CB2-19

CA

CB2-19

CA

CB2-19

CB

CB2-19

CB

CB2-19

CB

CB2-19

CB

CB2-19CB

1CB2-19

CB

1

1

CF

CB2-19

CF CF

D

CB2-20

CF

CB1-24CF

CF

CB2-20

CB2-20

CA1

CB2-20

CA1

CB2-20

CA1

CB

1-26

CI

CB1-24

CA

CB1-24

CA

CB1-24

CA

WW

WW

WW

DD

DD

DD

Trash

Trash

Trash

+42

DW

R

R

OFFICE

116MGMT. OFFICE

115

VESTIBULE

101EXERCISE

102

LAUNDRY

103

MAINTENANCE

104

MECH.

106SPRINKLER

105

PATIO

01

CONSULT

118

KITCHENETTE

121

MECH.

117

MEN

113

COMMON CORRIDOR

112

STORAGE

107

ELEC./IT

109

PORCH

01

PORCH

01CONIFER CORRIDOR

110

COMMUNITY ROOM

111

WOMEN

114

JAN.

108

CB1-24CE

CB1-24CE

CB1-24CE

1

CB1-24CE

CB1-24CE CB1-24

CHCH

CH

CK

CK

CB1-24

CHCH

CH

CB1-24CH

CB1-24CH

CB1-25CG

CB1-25CG

1

CB1-24

CFCB1-25

CJ

CB1-25CH

CB1-25CH

CB1-24

CFCF

CB2-20

CA1

CB2-20

CA1

CB2-20

CA1

CB2-20

CA1

CB2-20

CA1

CB1-26CM

CB1-26CH

CB1-25CG

CB1-25CG

CB1-25CG

CB1-25CG

CB1-25

CH

CB1-25

CH

XEM-3

EM

gg

e

EM

e

XEM-3

RH

EM

EM

EM

e

XEM

XEM-3e

e

e

RH

EM

EM

EM

XEM-3

RH

RH

OC

EM

XEM-3

EM

d

d

EM

XEM

g

g f

f

F

d

d

d

d

KEYED NOTES

1

2

CONNECT EMERGENCY AND EXIT LIGHTING FIXTURESTO LIGHTING CIRCUIT IN AREA AHEAD OF ALLSWITCHING.

PROVIDE PHOTOCELL FOR CONTROL OFBUILDING MOUNTED LIGHTING.

N

SCALE: 1/4" = 1'-0"1 FIRST FLOOR LIGHTING PLAN

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

FIR

ST F

LOO

R L

IGH

TIN

G P

LAN

,Thu

rsda

y, M

arch

3, 2

016,

3:29

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

E102

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

FIRST FLOORLIGHTING PLAN

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

CH

CE

CG

CC

CK

CI

CF

LIGHTING FIXTURE SCHEDULE FOR CLUBHOUSEFIXTURE TYPE DESCRIPTION MANUFACTURER AND

CATALOG NO.VOLT/

BALLASTLAMPS

NO. TYPEREMARKS

CA 2FTx4FT, STEEL HOUSING WITH MOUNTING COLLAR,FLUSH ALUMINUM DOOR, ACRYLIC PRISMATIC LENS

LITHONIA LIGHTING2RT8SX-2-32-MVOLT-GEB1OIS-

LP835

120V/ELECTRONIC 2 LP835 SURFACE MOUNTED

CB4FT, SURFACE WRAP AROUND 4-LAMP HOUSING: 20 GA

DIE FORMED STEEL WITH STEEL END PLATES.SHIELDING: CLEAR ACRYLIC PRISMATIC, CONTINUOUS

WRAP SIDES. FINISH: WHITE POWDER COAT

PROGRESS LIGHTINGP7279-60EB

120V/ELECTRONIC 2 F32T8 SURFACE MOUNTED

CC 12.5" DIA x 6.5" H DECORATIVE FLUORESCENT,BRUSHED NICKEL FINISH, WHITE GLASS LENS

SEAGULL LIGHTING79364B-LE-962

120V/ELECTRONIC 2

GU24 13WCLF SURFACE MOUNTED

CD 4FT, SURFACE WRAP AROUND VANDAL RESISTANTHOUSING, PRISMATIC POLYCARBONATE DIFFUSER

PROGRESS LIGHTINGP7279-60EB

120V/ELECTRONIC 2 F32T8 SURFACE MOUNTED

CE20IN DIAMETER, ILLUMINATED BOWL, BOWL: WHITE

ACRYLIC DIFFUSER, 4.25" HT, BRUSHED NICKEL FINISHSEAGULL LIGHTING

79130BLE-98120V/

ELECTRONIC 4GU24 13W

CLF CEILING MOUNTED

CF COMPACT FLUORESCENT CEILING LAMP HOLDER LEVITRON9860-LHG

120V/ELECTRONIC 1 13W CFL CEILING MOUNTED

CG 21.25" DIA., PENDANT MTD, BRUSHED STAINLESS FINISH,WITH SATIN WHITE GLASS

SEAGULL LIGHTING69133BLE-98

120V/ELECTRONIC 3 13W CFL CEILING MOUNTED

CH RECESSED COMPACT FLUORESCENT AIR TIGHTDOWNLIGHT

SEAGULL LIGHTING11061AT-861

120V/ COLDWEATHER

ELECTRONIC1

26W97046

PROVIDE WITH STANDARDTEMPERATURE BALLAST FOR

INTERIOR LOCATIONS.

CIEXTERIOR WALL LANTERN, BODY: BLACK DIE CAST

ALUMINUM. PANELS: WHITE FLAT GLASS.SEAGULL LIGHTING

8988BLE-12120V/COLDWEATHER

ELECTRONIC1 13W FLUOR. EXTERIOR WALL MOUNTED

CJ2FT, UNDER CABINET LIGHT, HOUSING: 20 GA DIE

FORMED STEEL WITH STEEL END PLATES. SHIELDING:HIGH IMPACT, EXTRUDED WHITE OPAL ACRYLIC. FINISH:

WHITE POWDER COAT

PROGRESS LIGHTINGP7011-30EB

120V/ELECTRONIC 1 F13WT5

ABOVE SINK UNDER CABINETMOUNTED

EM EMERGENCY LIGHTING BATTERY FIXTURE FIXED LENSWITH MAINTENANCE FREE LEAD BATTERY

LIGHT ALARMSLCA-2SQ SERIES 120V 2 6V 6W

WALL MOUNTED. CONNECT TOROOM LIGHTING CIRCUIT AHEAD

OF ALL SWITCHING.

XEMTHERMOPLASTIC COMBINATION LED EXIT SIGN ANDEMERGENCY LIGHTING BATTERY FIXTURE. TWO UNITMOUNTED HEADS, WITH MAINTENANCE FREE LEAD

BATTERY AND INTERNAL DIAGNOSTICS

PROGRESS LIGHTINGP3052-09EBWB

120V 2 13W CFL WALL MOUNTED

XEM-3

LIGHT ALARMSV2LXN500R-2SQ 120V 4 WALL MOUNTED

NO REMOTE CAPABILITY

SIMILAR TO TYPE 'XEM' EXCEPT REMOTE CAPABLELIGHT ALARMSLTURW-31-03L 120V 4 3W

LED

WALL MOUNTED. EXTERIORSEALED BEAM TWIN REMOTEHEAD TO BE INSTALLED 12"

ABOVE THE DOOR. CONNECT TOROOM LIGHTING CIRCUIT AHEAD

OF ALL SWITCHING.REMOTE CAPABILITY

CK

RH WATERPROOF REMOTE DUAL HEAD FIXTURELIGHT ALARMS

ELF647D/KH4-M6 6V DC 26W

B1 PIN HALOGEN MOUNT 12" ABOVE DOOR HEIGHT

XEM-3

EM

RH

XEM

OVER MIRROR FLUORESCENT FIXTURE, ALABASTERGLASS BRUSHED NICKEL

3WLED

SURFACE MOUNTEDLP8352120V/

ELECTRONICLITHONIA LIGHTING

2RT8SX-2-17-MVOLT-GEB10IS-LP835

2FTx2FT, STEEL HOUSING WITH MOUNTING COLLAR,FLUSH ALUMINUM DOOR, ACRYLIC PRISMATIC LENSCA1

3/2/16/Volumes/Public/Projects/2014/14204_ConiferClayton/engineering/electrical/ELECTRICAL LOAD CALC'S/PANEL SCHEDULES/xls/CAMP SALUTE CLUB HOUSE PANEL CB1.xls

Page 1

WIRE AND CONDUIT

CKT DESCRIPTION VA ØA ØB VA DESCRIPTION CKT WIRE AND CONDUIT

2#12+G 1 540 20 1 1,540 - 20 1 1000 2 2#12+G2#12+G 3 540 20 1 - 1,640 20 1 1100 4 2#12+G2#12+G 5 540 20 1 2,040 - 20 1 1500 6 2#12+G2#12+G 7 360 20 1 - 900 20 1 540 8 2#12+G2#12+G 9 360 20 1 720 - 20 1 360 10 2#12+G2#12+G 11 720 20 1 - 1,080 20 1 360 12 2#12+G2#12+G 13 360 20 1 720 - 20 1 360 14 2#12+G2#12+G 15 1200 20 1 - 1,950 20 1 750 16 2#12+G2#8+G 17 1000 20 1 1,500 - 20 1 500 18 2#12+G

2#12+G 19 360 20 1 - 1,010 20 1 650 20 2#12+G2#12+G 21 360 20 1 660 - 20 1 300 22 2#12+G2#12+G 23 720 20 1 - 1,611 20 1 891 24 2#12+G2#14+G 25 550 20 1 655 - 20 1 105 26 2#12+G

1 2#12+G 27 500 20 1 - 1,000 20 1 500 28 2#12+G1 2#12+G 29 250 20 1 750 - 20 1 500 30 2#12+G 1

31 2808 40 - 3,984 20 1 1176 32 2#12+G 133 2808 2 2,908 - 20 1 100 34 2#12+G35 972 20 - 2,628 20 1 1656 36 2#12+G37 972 2 1,668 - 20 1 696 38 2#12+G

2#12+G 39 1176 20 1 - 22,476 150 21300 40 3#3/0(AL)2#12+G 41 750 20 1 16,236 - 2 15486 42 1#2(AL)G

LIGHTINGRECEPT

A/C

HEATING

MISC

TOTAL

REFERENCE DWG:

GAS-FIRED FURNACE GF-2

4

5

GAS-FIRED FURNACERECEPTACLE - MECHANICAL ROOMBOTTLED WATER DISPENSER

LIGHTING - COMMUNITY ROOMACCESS CONTROL PANELDOOR CONTROL PANEL FIRE ALARM CONTROL PANEL

240/120V, 1Ø, 3W

54858

RECEPTACLES - OFFICE

DRY SYSTEM AIR COMPRESSOR

LIGHTING - OFFICE, HALL, EXERCISE

RECEPTACLES - TOILET ROOMS

RECEPTACLES - EXTERIOR

RECEPTACLES - COMPUTER

RECEPTACLES - COMPUTERRECEPTACLES - COMPUTER

RECEPTACLES - EXERCISE ROOMRECEPTACLES - EXERCISE ROOMRECEPTACLES - EXERCISE ROOM

2#10+G

1MAINTENANCE V, Ø, W:

DISHWASHER

CEILING FANS

TELEPHONE EQUIPMENT

LIGHTING - BUILDING MOUNTEDDOOR CONTROL PANEL

ØA TOTAL VA

RECEPTACLES - COMMUNITY ROOMRECEPTACLES - COMMUNITY ROOMTV RECEPTACLE - COMMUNITY ROOM

PANEL CB2

RECEPTACLES - KITCHEN

REFRIGERATORMICROWAVE OVEN

228.58

28701

10846

NOTES:

1. PROVIDE LOCK-ON HANDLE ON CIRCUIT BREAKER

8872

3099

3340

MOUNTING:

RECEPTACLES - HALL

SURFACESTANDARDSTANDARD

22 kAICNEUTRALGROUNDING:

300A MCB

SITE LIGHTING

NOTE

S

NOTE

S

MIN. INT. RATING:MAIN CB/LUGS

CB

PANELSECTION

CB1

CB

3,340

100%

LOCATION

2

25,084 30,667

3

67,676

38,268

100%

80%

75%

75%

11,090

4,132

10,846

ØB TOTAL VA TOTAL DEMAND AMPS

ACCU-1

GAS-FIRED FURNACEELECTRIC HEAT EH-1

2#8+#10G

ACCU-2

DIVERSITY

GAS-FIRED FURNACE GF-1WATER HEATER WH-1

3/2/16/Volumes/Public/Projects/2014/14204_ConiferClayton/engineering/electrical/ELECTRICAL LOAD CALC'S/PANEL SCHEDULES/xls/CAMP SALUTE CLUB HOUSE PANEL_CB2.xls

Page 1

WIRE AND CONDUIT

CKT DESCRIPTION VA ØA ØB VA DESCRIPTION CKT WIRE AND CONDUIT

2#12+G 1 180 20 1 1,380 - 20 1 1200 2 2#12+G2#12+G 3 100 20 1 - 1,300 20 1 1200 4 2#12+G2#12+G 5 100 20 1 1,300 - 20 1 1200 6 2#12+G2#12+G 7 100 20 1 - 1,300 20 1 1200 8 2#12+G2#12+G 9 100 20 1 1,300 - 20 1 1200 10 2#12+G2#12+G 11 100 20 1 - 600 20 1 500 12 2#12+G2#12+G 13 180 20 1 360 - 20 1 180 14 2#12+G2#12+G 15 100 20 1 - 1,000 20 1 900 16 2#12+G2#12+G 17 540 20 1 1,540 - 15 1000 182#12+G 19 704 20 1 - 1,704 2 1000 202#12+G 21 100 20 1 1,100 - 15 1000 222#12+G 23 1260 20 1 - 2,260 2 1000 242#12+G 25 1250 20 1 2,450 - 20 1 1200 26 2#12+G

27 100 15 - 1,691 20 1591 2829 100 2 1,691 - 2 1591 3031 1000 15 - 1,270 20 1 270 32 2#12+G33 1000 2 1,250 - 20 1 250 34 2#12+G35 1000 15 - 1,000 20 1 0 3637 1000 2 7,000 - 70 6000 38 3#4

2#12+G 39 100 20 1 - 6,100 2 6000 40 1#8G41 0 20 1 1,260 - 20 1 1260 42

LIGHTINGRECEPT

A/C

HEATING

MISC

TOTAL

REFERENCE DWG:

RECEPTACLES - HALLWAY CORRIDOR

3#12+GHP-1

4

5

RECEPTACLES - MAINTENANCE ROOM

RECEPTACLES - CONSULT ROOM

AU-1

33786

DIVERSITY794

WASHING MACHINE

DRYER (GAS FIRED)

LIGHTING - MAINTENANCE, LAUNDRY

RECEPTACLES - HALLWAY

RECEPTACLES - MECHANICAL ROOM

DRYER (GAS FIRED)DRYER (GAS FIRED)

WASHING MACHINEELECTRIC HEAT EH-4

WASHING MACHINE

ELECTRIC HEAT EH-2

1MAINTENANCE V, Ø, W:

WATER HEATER (GAS-FIRED)

SPRINKLER BELL

RECEPTACLE - LAUNDRY ROOM

ELECTRIC HEAT EH-2

DRYER (GAS FIRED)DRYER (GAS FIRED)

RECEPTACLES - MAINTENANCE ROOM

3#12+G

3#12+G

FUTURE RADON FANSCURRENT SENSORSSPARE

PLENUM HEATING PANEL 'PEH'

ELECTRIC HEAT EH-23#12+G

140.78

20500

6950

NOTES:

1

2160

3382

18,225

MOUNTING:

DRYER (GAS FIRED)

SURFACESTANDARDSTANDARD

10 kAICNEUTRALGROUNDING:

150A MLO

DEBIT MACHINE RECEPTACLE

NOTE

S

NOTE

S

MIN. INT. RATING:MAIN CB/LUGS

CB

PANELSECTION

CB2

CB

794

100%

SPARE

LOCATION

2

20,631

3

33,786

20,500

100%

100%

100%

100%

2,160

3,382

6,950

ØA TOTAL VA

240/120V, 1Ø, 3W

WASHING MACHINE

WASHING MACHINEWASHING MACHINE

ØB TOTAL VA TOTAL DEMAND AMPS

ELECTRIC HEAT EH-2

3#12+G

3#12+G

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

SCH

EDU

LES,

Thur

sday

, Mar

ch 3

, 201

6,3:

29 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

E801

03-03-1614204

RW/AH/SWRW

Date

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:N

J PE

GE0

3005

8St

ephe

n F.

Fin

kelm

an

CO

A#: 2

4GA2

8203

000

SCHEDULES

©20

15 -

Kitc

hen

& As

soci

ates

.  

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

ELECTRIC ALARM GONG

SIAMESE FIRE DEPARTMENT CONNECTION

BACK FLOW PREVENTER

PIPE ELBOW DOWN

SPRINKLER PIPING

MONITORED OS&Y VALVE

PRESSURE GAUGE

CHECK VALVE

DRY ALARM CHECK VALVE

FP000

FP101

NOTES, SYMBOLS & ABBREVIATIONS

FIRST FLOOR PLAN

16

4

1

GRADE

2-1/2"

11

14

5 6

ZONE RISER FOR SPRINKLER SYSTEM

FIRE DEPARTMENT CONNECTION ATBUILDING. VERIFY THREAD TYPE WITHFIRE MARSHAL. LABEL "SPRINKLERSYSTEM"

FIRE DEPARTMENT CONNECTION PIPING

CHECK VALVE. LOCATE IN WATERSERVICE ROOM.

PROTECTION SERVICE NOTES

BACKFLOW PREVENTER SIMILAR TOZURN WILKINS MODEL #350ASTDAWITH SUPERVISED OS&Y GATEVALVES

THRUST BLOCK

ELECTRIC GONG

NEW 4" UNDERGROUND FIRE WATERSERVICE

SUPERVISED GATE VALVE

8

9

3

5

6

7

4

1

2

FIRE DEPARTMENT CONNECTION PIPING.CONNECT TO WET-PIPE SECTION OFFIRE SUPPRESSION SYSTEM.

10

BALL DRIP. ROUTE TO BUILDINGEXTERIOR.

11

DRY-ALARM CHECK VALVE WITHTRIM SIMILAR TO VIKING G-2000RISER ASSEMBLY

12

13

PRESSURE GAUGE

14

15

3

3

SLEEVE WITH WATERPROOF SEAL

INCOMING FIRE

13

12

10

2

15

TO DRY-PIPE SPRINKLER MAIN

9

AIR COMPRESSOR FOR DRY-PIPESYSTEM. BASIS OF DESIGN SHALL BEGENERAL AIR PRODUCTS OLPLUSSERIES. FINAL SIZING OF AIRCOMPRESSOR SHALL BE BASED ONACTUAL SYSTEM VOLUME.

16

8

7

GENERAL FIRE PROTECTION NOTES FIRE PROTECTION NOTES FIRE PROTECTION ABBREVIATIONS FIRE PROTECTION SYMBOLS

FIRE PROTECTION DRAWING LIST

NOT TO SCALE1 INCOMING SERVICE DETAIL

A AMPERESAC AIR CONDITIONINGACS AUTOMATIC CONTROL SYSTEMAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITALUM ALUMINUMARCH ARCHITECT

BAD BOTTOM ANGULAR DISCHARGEBCP BOILER CIRCULATION PUMPBFP BOILER FEED PUMPBHD BOTTOM HORIZONTAL

DISCHARGEBP BOOSTER PUMPBT BATH TUB

C CONVERTORC CENTER LINEøC DEGREES CELSIUSCAC CONTROL AIR COMPRESSORCB CAST IRON BOOTCCP CENTRAL CONTROL PANELCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE CONNECTIONCFM CUBIC FEET PER MINUTECFP CHEMICAL FEED PUMPCH CHILLERCHWP CHILLER WASTE PUMPCLG CEILINGCO CLEANOUTCOND CONDENSATECONN CONNECTCONT CONTINUATIONCP CIRCULATION PUMPCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CHECK VALVECW COLD WATERCWP CONDENSATE WATER PUMP

D DROPDDC DIRECT DIGITAL CONTROLDFWP DEARATOR FEED WATER PUMPDF DRINKING FOUNTAINDG DIESEL GENERATORDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDR DRAINDTL DETAILDWG DRAWINGDW DISH WASHER

EL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALESP ELEVATOR SUMP PUMPET EXPANSION TANKEM EMERGENCYEW EMERGENCY EYE WASHEWC ELECTRIC WATER COOLEREWT ENTERING WATER

TEMPERATURE EXP EXPANSION

F FILTERºF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFFE FINISHED FLOOR ELEVATIONFL FLOORFP FIRE PROTECTIONFPI FINS PER INCHFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOOR SINKFT FEET

G GASG GAUGEGAL GALLONGCO GRADE CLEAN OUTGPH GALLONS PER HOURGPM GALLONS PER MINUTEGWH GAS WATER HEATER

H HUMIDIFIERHB HOSE BIBBHD HEADHP HORSE POWERHR HOURHT HEIGHTHTWP HIGH TEMPERATURE WATER

PUMPHW HOT WATERHWR HOT WATER RECIRCULATIONHWB HOT WATER BOILERHWP HOT WATER PUMP IN INCH OR INCHES

JC JANITOR'S CLOSETJS JANITOR'S SINK

KS KITCHEN SINK

L LENGTHLAV LAVATORYLBS POUNDSLCP LOCAL CONTROL PANELLIN .FT. LINEAR FEETL&S LIQUID & SUCTION LINESLWT LEAVING WATER TEMPERATURE

MB MIXING BOXMER MECHANICAL EQUIPMENT ROOMMAX MAXIMUMMHP MOTOR HORSEPOWERMIN MINIMUMMM MILLIMETERMR MOP RECEPTORMTD MOUNTED

NC NORMALLY CLOSEDNFWH NON-FREEZE WALL HYDRANTNIC NOT IN CONTRACTNO NORMALLY OPENNo NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE

OA OUTSIDE AIROAI OUTSIDE AIR INTAKEOAS OUTSIDE AIR SENSOROSA OUTSIDE AIROS&Y OUTSIDE SCREW & YOKE

P PUMPPD PUMP DISCHARGEPHC PREHEAT COILPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE INCH

ABSOLUTEPSIG POUNDS PER SQUARE INCH

GAUGE

R RISERD ROOF DRAINRAD RADIATIONREFR REFRIGERANTRF RETURN FANRH RELATIVE HUMIDITYRHC REHEAT COILRHWP REHEAT WATER PUMPRLA RUNNING LOAD AMPSRM ROOMRPM REVOLUTIONS PER MINUTERPZ REDUCING PRESSURE ZONE

BACKFLOW PREVENTER

S SOILSA SHOCK ABSORBERSAN SANITARYSCHWP SECONDARY CHILLED WATER

PUMPSD SMOKE DETECTORSF SUPPLY FANSHWP SECONDARY HOT WATER PUMPSH SHOWERSMK CTL SMOKE CONTROL OPERATIONSP STATIC PRESSURESPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEEL

T THROATTEMP TEMPERATURETSP TOTAL STATIC PRESSURETV TURNING VANESTYP TYPICAL

UNO UNLESS OTHERWISE NOTEDUR URINAL

V VENTVTR VENT THROUGH ROOF

W WASTEW WIDTHW/ WITHWC WATER CLOSETWCA WATER CLOSET ACCESSIBLEWCO WALL CLEAN OUTWFU WATER FIXTURE UNITW/O WITHOUTWG WATER GAUGEWH WATER HEATERWHA WATER HAMMER ARRESTERWMB WASHING MACHINE BOXWPD WATER PRESSURE DROP

1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HAS TOTALLYFAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HASAGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATIONOF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BESTPRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.

2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDINGTHAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THEBASIS OF INFORMATION SUCH AS CONTAINED IN THE CONTRACT DOCUMENTS. IT IS THE INTENT OFTHE CONTRACT DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED ANDREADY FOR OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULESAND REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTEDNECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS SHALLBE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS SPECIFIED OR SHOWN ON THECONTRACT DRAWINGS. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMEDNECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASON THEREFORE SHALL BE SUBMITTEDTO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVALOF THE ENGINEER.

3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT OF ANYDISCREPANCIES BEFORE PERFORMING THE WORK.

4. THE CONTRACT DOCUMENTS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES ANDRELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TO BEPROVIDED. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATIONOF CONTRACT REQUIREMENTS TO BEST AVAILABLE STANDARDS AT THE SCALE INDICATED.

5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED AND

COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACTLOCATIONS USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONED DRAWINGSCOORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTING SUCHINTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGS AND DISTRIBUTESAME AS REQUIRED.

6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULE WORK INACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL THE WORK CAN BE INSTALLEDWITHOUT DELAYING THE PROJECT.

7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGS SHALL BEFORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALL SUBSEQUENTLY IN SUCCESSIONDELINEATE HIS RESPECTIVE WORK ON THESE COORDINATION DRAWINGS. WHEN ALL WORK HASBEEN PROPERLY SHOWN ON THE COORDINATION DRAWINGS, AND ALL CONTRACTORS AGREETHAT THEIR RESPECTIVE WORK CAN BE INSTALLED AND WILL PROPERLY FIT TOGETHER, THEYSHALL SO ACKNOWLEDGE BY ENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TOCOMPLETION OF ABOVE COORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED ANDREPLACED AT CONTRACTOR'S EXPENSE.

8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.

9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'SWRITTEN INSTRUCTIONS.

10. SCHEDULE ALL SHUTDOWNS THAT EFFECT UTILITIES AND PORTIONS OF THE BUILDING THATMUST REMAIN IN OPERATION WITH THE OWNER.

11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTION OFMATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT.

12. WHERE PIPING PASSES THROUGH FIRE RATED FLOORS AND WALLS, THE PENETRATION SHALLBE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED AND ACCEPTED BY THEBUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THISMATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURERTO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.

13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, ANDCORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALL SUBMIT SIZE AND LOCATION TO THESTRUCTURAL ENGINEER FOR REVIEW AND APPROVAL. STRUCTURAL ELEMENTS SHALL NOT BEPENETRATED WITHOUT PRIOR APPROVAL OF STRUCTURAL ENGINEER.

14. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THISSCHEDULE SHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FOR THISPROJECT, INCLUDING ANY ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THEREQUIREMENTS OF DIVISION 1 OF THE SPECIFICATIONS. PROVIDE DRAWINGS OF ALL SPRINKLERPIPING, HEADS, VALVES, EQUIPMENT, MATERIALS, AND SIGNS FOR EACH FIRE PROTECTION SYSTEMTO BE INSTALLED. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO RECEIPT OFENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE REPLACED ATCONTRACTOR EXPENSE.

15. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATIONDRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMSPROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NOSUBMISSION SHALL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE CONTRACTOR. THECONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.

16. PROVIDE AS-BUILT DOCUMENTS AND OPERATING/MAINTENANCE MANUALS AS SPECIFIED INDIVISION 1 OF THE SPECIFICATIONS.

17. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND ORVIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER. OBJECTIONABLESOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVED MANNER BY THECONTRACTOR AT HIS EXPENSE.

18. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES AND CONTROLS, ETC., AND COORDINATE THEIR DELIVERY WITH THEINSTALLING TRADE.

19. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALLDEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN ONE (1) YEARFROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIPDEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIALREPLACED WITHOUT ADDITIONAL COST.

20. NOTIFY ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK AND DATE OFBOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE A MINIMUM OF ONE WEEK PRIORTO COMPLETION DATE TO ENABLE ENGINEER SCHEDULING OF PRELIMINARY PUNCHLIST INSPECTIONPRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEEROF COMPLETION OF ALL WORK, INDICATING THE CONTRACTOR IS READY FOR THE ENGINEER TOPERFORM THE FINAL PUNCHLIST INSPECTION.

21. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER'S PUNCHLIST,THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETIONCERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS,ETC. HAVE BEEN SUBMITTED.

22. CONTRACTOR SHALL COORDINATE WORK WITH EEBA DETAILS SHOWN ON DRAWINGS A907THROUGH A908.

1. ALL EQUIPMENT AND MATERIALS USED AND WORK PERFORMED SHALL BE IN ACCORDANCE WITH RULESAND REGULATIONS LISTED IN "CODE SUMMARY" ON DRAWING CS001 IN ADDITION TO THE AUTHORITYHAVING JURISDICTION.

2. FIRE SUPPRESSION SYSTEMS, STANDPIPES, AND FIRE PUMPS SHALL BE INSTALLED INACCORDANCE WITH NEW JERSEY EDITION OF THE INTERNATIONAL BUILDING CODE, NFPA-13 ANDREQUIREMENTS.

3. THE ENTIRE SYSTEM SHALL BE DESIGNED UNDER THE SUPERVISION OF A PROFESSIONALENGINEER EXPERIENCED IN THE WORK AND LICENSED IN THE STATE OF NEW JERSEY. ALL LAYOUTSHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL BE SIGNED AND SEALED BY THEPROFESSIONAL ENGINEER.

4. FIRE PROTECTION CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH COMPLETE SET OFCONSTRUCTION DOCUMENTS, INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL,HVAC, PLUMBING, ELECTRICAL, AND SITE DRAWINGS.

5. PERFORM HYDRAULIC CALCULATIONS IN ACCORDANCE WITH NFPA-13 AND CRITERIA ASREQUIRED BY THE AUTHORITY HAVING JURISDICTION. ALL PIPE SIZES, NUMBER AND LOCATION OFHEADS, FLOW RATES, ETC. SHALL BE AS REQUIRED BY THE HYDRAULIC CALCULATION AND NFPA.WHERE FIELD CONDITIONS OR AUTHORITY HAVING JURISDICTION REQUIRES MORE HEADS OROTHER WORK BEYOND WHAT IS SHOWN ON THESE DRAWINGS, PROVIDE SAME AT NO COST TOOWNER.

6. CONDUCT A FLOW TEST IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE. CONTACT THELOCAL WATER COMPANY TO SCHEDULE THE TEST.

7. REQUIRED COPIES OF SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER'S INSURANCECARRIER FOR REVIEW AND APPROVAL. DISTRIBUTION AND ROUTING OF DRAWINGS SHALL BEDETERMINED AFTER AWARDING OF CONTRACT.

8. APPROVAL OF THE COMPLETE SYSTEM SHALL BE OBTAINED FROM THE AUTHORITIES HAVINGJURISDICTION, AND A COPY OF THE SAME SHALL BE DELIVERED TO THE OWNER'SREPRESENTATIVE AND ARCHITECT.

9. AFTER APPROVAL FROM THE OWNER'S INSURANCE COMPANY, SUBMIT TO THE ENGINEER FOR

APPROVAL ELECTRONIC COPIES OF HYDRAULIC CALCULATIONS AND SHOP DRAWINGS FOR THECOMPLETE FIRE PROTECTION SYSTEM. ALSO SUBMIT FOR APPROVAL THE MANUFACTURER'S NAME,FIGURE NUMBERS, OR OTHER MEANS OF IDENTIFICATION OF ALL PIPE FITTINGS, VALVES,SPRINKLERS AND OTHER MATERIAL REQUIRED FOR THE WORK.

10. ROUTE ALL SPRINKLER PIPING TO AVOID INTERFERENCE WITH LIGHTING FIXTURES, DUCTS,PIPING AND OTHER TRADES. ALL SPRINKLER PIPING IN FINISHED AREAS SHALL BE CONCEALED.

11. REFER TO THE FINAL ARCHITECT'S REFLECTED CEILING PLAN AND VERIFY ACTUAL FIELDCONDITIONS TO COORDINATE LOCATIONS OF SPRINKLER HEADS. COORDINATE SPRINKLER HEADLOCATIONS WITH LIGHTING, DIFFUSER LAYOUT, CEILING FANS, AND ANY OTHER OBSTRUCTIONS.

12. COORDINATE LOCATION, THREADS, AND TYPE OF FIRE DEPARTMENT CONNECTION WITH LOCALFIRE DEPARTMENT

13. COORDINATE ALL FIRE PROTECTION SHUTDOWNS WITH FIRE SUBCODE OFFICIAL. A MINIMUM OF48 HOURS NOTICE IS REQUIRED PRIOR TO COMMENCING WORK. PAY ALL CHARGES FROM THEFIRE DEPARTMENT AND STAND BY CREWS. SHUTDOWNS OF FIRE PROTECTION SYSTEM AFFECTINGOCCUPIED AREAS WILL NOT BE PERMITTED PRIOR TO 10:00 AM.

14. UNLESS INDICATED OTHERWISE ON THE CONTRACT DRAWINGS, FOR AREAS GOVERNED BYNFPA-13 STANDARD, ALL WET-PIPE SPRINKLER PIPING 3" AND SMALLER MAY BE BLAZEMASTERCPVC PLASTIC PIPE OR APPROVED EQUAL, LARGER THAN 3" UP SHALL BE SCHEDULE 10 STEELROLL GROOVED PIPES AND FITTINGS. ALL SPRINKLER PIPING SHALL BE INSTALLED INACCORDANCE WITH THEIR LISTING.

15. ALL DRY-PIPE SPRINKLER PIPING SHALL BE GALVANIZED STEEL.

16. THE FOLLOWING METHODS AND MATERIALS ARE NOT ACCEPTABLE:

A. SCHEDULE 5 PIPINGB. PRESS FITTINGSC. PLAIN END PIPING AND FITTINGS

17. REFER TO SPECIFICATIONS FOR ADDITIONAL PIPE MATERIAL INFORMATION.

18. UNLESS INDICATED OTHERWISE ON CONTRACT DRAWINGS, ALL SPRINKLERS LOCATED INPUBLIC AREAS AND DWELLING UNITS, REGARDLESS OF CEILING TYPE SHALL BE QUICK RESPONSE,SEMI-RECESSED TYPE. THE SPRINKLER ESCUTCHEON SHALL BE WHITE.

19. ALL SPRINKLERS LOCATED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, WATER METERROOMS AND STORAGE ROOMS SHALL HAVE WIRE CAGES.

20. SPRINKLERS SHALL BE PROVIDED THROUGHOUT ALL CONCEALED SPACES OF COMBUSTIBLECONSTRUCTION IN ACCORDANCE WITH NFPA-13.

21. ALL FIRE PROTECTION WORK AS DESCRIBED IN CONTRACT DRAWINGS AND THESPECIFICATIONS SHALL BE DESIGNED AND BUILT BY A LICENSED FIRE PROTECTION CONTRACTOR.

22. SPRINKLER HEADS EXTENDING INTO UNHEATED SPACES SHALL BE PROTECTED FROMFREEZING. THE MINIMUM LENGTH OF THE EXPOSED DRY BARRELS OF DRY SPRINKLERSCONNECTED TO WET-PIPE SYSTEM SHALL BE 12".

23. CODE COMPLIANCE OF THE FIRE SUPPRESSION SYSTEM IS THE RESPONSIBILITY OF THE FIRESPRINKLER SUBCONTRACTOR. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DESIGNDOCUMENTS ARE SCHEMATIC ONLY. FIRE SPRINKLER SUBCONTRACTOR SHALL PROVIDE CODECOMPLIANT SHOP DRAWINGS TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL.

24. COORDINATE ALL ELECTRICAL WORK AND FIRE ALARM WORK WITH ELECTRICALCONSTRUCTION SECTION AND FIRE ALARM CONSTRUCTION SECTION.

25. PROVIDE ALL NFPA TEST REPORTS TO ENGINEER FOR REVIEW.

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

NO

TES,

SYM

BOLS

& A

BBR

EVIA

TIO

NS,

Thur

sday

, Mar

ch 3

, 201

6,3:

29 P

201

6 - K

itche

n &

Asso

ciat

es.  

All p

lann

ing

and

arch

itect

ural

con

cept

s sh

own

on th

is d

ocum

ent a

re th

e in

telle

ctua

l pro

perty

of K

itche

n &

Asso

ciat

es

FP000

03-03-1614204AD/SB

CPDate

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:2

1AI0

1218

000

Mar

y M

. Joh

anne

sen

CO

A#: 2

1AC

0008

2700

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

NOTES, SYMBOLS &ABBREVIATIONS

©20

15 -

Kitc

hen

& As

soci

ates

.  

3

2 4

8

7

1

1

1

1

DW

R

R

6

5

9

9

9

KEYED NOTES

DRY-PIPE SPRINKLER SYTEM AREA. PROVIDE SEMI-RECESSED WHITECEILING SPRINKLERS WITH WHITE ESCUTCHEONS THROUGHOUT THE AREAINDICATED IN ACCORDANCE WITH NFPA 13 REQUIREMENTS. PROVIDEUPRIGHT SPRINKLERS THROUGHOUT CONCEALED SPACES CONSTRUCTEDOF COMBUSTIBLE MATERIALS IN ACCORDANCE WITH NFPA 13REQUIREMENTS.

4" INCOMING FIRE SUPPRESSION SERVICE.

4" DOUBLE CHECK DETECTOR BACKFLOW PREVENTER ASSEMBLY.

FIRE DEPARTMENT CONNECTION POINT OF CONNECTION TO FIRESUPPRESSION SYSTEM. PROVIDE CHECK VALVE WITH BALL DRIP IN WATERSERVICE ROOM. PIPE BALL DRIP TO FLOOR DRAIN.

FIRE DEPARTMENT CONNECTION PIPING BETWEEN FIRE DEPARTMENTCONNECTION AND POINT OF CONNECTION TO FIRE SUPPRESSION SYSTEM.

FIRE DEPARTMENT CONNECTION WITH ELECTRIC GONG LOCATED ABOVE.COORDINATE FINAL LOCATION AND INLET QUANTITY AND THREAD TYPEWITH FIRE MARSHAL PRIOR TO INSTALLATION.

SPRINKLER ZONE RISER WITH DRY ALARM CHECK VALVE AND BASEMOUNTED AIR COMPRESSOR.

DRY-PIPE SPRINKLER SUPPLY. PROVIDE MAIN AND BRANCH PIPING TOSPRINKLERS AS REQUIRED BASED ON FINAL DESIGN.

PROVIDE DRY SIDEWALL SPRINKLER COVERAGE BELOW EXTERIOR ROOF.

1

2

3

4

5

6

7

8

9

N

SCALE: 1/4" = 1'-0"1FIRST FLOOR PLAN

CA

MP

SALU

TE -

CLU

BH

OU

SE

PRO

GR

ESS

ISSU

E -

NO

T FO

R C

ON

STR

UC

TIO

N

BIM

Ser

ver:

bim

19.k

itche

nand

asso

ciat

es.c

om -

BIM

Ser

ver 1

9/14

204_

Cam

pSal

ute/

1420

4_C

ampS

alut

e_C

lub,

FIR

ST F

LOO

R P

LAN

,Thu

rsda

y, M

arch

3, 2

016,

3:29

PM

© 2

016

- Kitc

hen

& As

soci

ates

.  Al

l pla

nnin

g an

d ar

chite

ctur

al c

once

pts

show

n on

this

doc

umen

t are

the

inte

llect

ual p

rope

rty o

f Kitc

hen

& As

soci

ates

FP101

03-03-1614204AD/SB

CPDate

Date:Job #:Drawn:Mngr:Revision

14204_CampSalute_Club

LIC

. #:2

1AI0

1218

000

Mar

y M

. Joh

anne

sen

CO

A#: 2

1AC

0008

2700

NO

RTH

DEL

SEA

DRI

VE

- BLO

CK

1601

, LO

T 13

BORO

UG

H O

F C

LAYT

ON

, NJ

0831

2

FIRST FLOOR PLAN

©20

15 -

Kitc

hen

& As

soci

ates

.