MC000
M101
M801
M901
M902
NOTES, SYMBOLS & ABBREVIATIONS
FIRST FLOOR PLAN
SCHEDULES
DETAILS
DETAILS
GENERAL MECHANICAL NOTES1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HAS TOTALLY
FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HASAGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION OFEACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST PRACTICESOF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.
2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDINGTHAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THEBASIS OF INFORMATION SUCH AS CONTAINED IN THE CONTRACT DOCUMENTS. IT IS THE INTENT OF THECONTRACT DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOROPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES ANDREGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FORTHE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THEWORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE CONTRACT DRAWINGS.IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCHDEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FORAPPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE ENGINEER.
3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT/ENGINEERAND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK.
4. THE CONTRACT DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVELOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TO BE PROVIDED.CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACTREQUIREMENTS TO BEST AVAILABLE STANDARDS AT THE SCALE INDICATED.
5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED ANDCOMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONSDETERMINED USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONED DRAWINGSCOORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTING SUCHINTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGS AND DISTRIBUTESAME AS REQUIRED.
6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULE WORK INACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL OF THE WORK CAN BE INSTALLEDWITHOUT DELAYING THE PROJECT.
7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGS SHALL BEFORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALL SUBSEQUENTLY IN SUCCESSIONDELINEATE HIS RESPECTIVE WORK ON THESE COORDINATION DRAWINGS. WHEN ALL WORK HAS BEENPROPERLY SHOWN ON THE COORDINATION DRAWINGS, AND ALL CONTRACTORS AGREE THAT THEIRRESPECTIVE WORK CAN BE INSTALLED AND WILL PROPERLY FIT TOGETHER, THEY SHALL SOACKNOWLEDGE BY ENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TO COMPLETION OFABOVE COORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED AND REPLACED ATCONTRACTOR’S EXPENSE.
8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.
9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER’S WRITTENINSTRUCTIONS.
10. SCHEDULE ALL SHUTDOWNS THAT AFFECT UTILITIES AND PORTIONS OF THE BUILDING THAT MUSTREMAIN IN OPERATION WITH THE OWNER.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTION OFMATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT.
12. PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT AND TRANSFER TO POINT OFINSTALLATION OWNER FURNISHED ITEMS.
13. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATED FLOORS ORWALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS ULLISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLEFOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTSOF THE MANUFACTURER TO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL ORFLOOR.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAMPENETRATIONS AND CORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALL SUBMIT SIZE ANDLOCATION TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.
15. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THIS SCHEDULESHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FOR THIS PROJECT,INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THE REQUIREMENTS OFDIVISION 1 OF THE SPECIFICATIONS. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TORECEIPT OF ENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BEREPLACED AT CONTRACTOR EXPENSE.
16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATIONDRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BEPROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NOSUBMISSION WILL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE CONTRACTOR. THECONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.
17. PROVIDE AS-BUILT DOCUMENTS AND OPERATING/MAINTENANCE MANUALS AS SPECIFIED INDIVISION 1 OF THE SPECIFICATIONS.
18. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND ORVIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER. OBJECTIONABLESOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVED MANNER BY THECONTRACTOR AT HIS EXPENSE.
19. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, CONTROLS, ETC., AND COORDINATE THEIR DELIVERY WITH THE INSTALLINGTRADE.
20. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALLDEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN ONE (1) YEARFROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIPDEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACEDWITHOUT ADDITIONAL COST.
21. NOTIFY ARCHITECT / ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK ANDATE OF BOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE MINIMUM OF ONE WEEKPRIOR TO COMPLETION DATE TO ENABLE ARCHITECT / ENGINEER SCHEDULING OF PRELIMINARYPUNCHLIST INSPECTION PRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALLSIMILARLY NOTIFY ARCHITECT / ENGINEER OF COMPLETION OF ALL WORK, INDICATING THECONTRACTOR IS READY FOR THE ARCHITECT / ENGINEER TO PERFORM THE FINAL PUNCHLISTINSPECTION.
22. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ARCHITECT / ENGINEER’SFINAL PUNCHLIST, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OFCOMPLETION CERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS,MANUALS, ETC. HAVE BEEN SUBMITTED.
MECHANICAL NOTES
1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNINGCODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE APPLICABLECODES, AS AMENDED BY THE STATE OF NEW JERSEY. REFER TO ARCHITECTURAL PLANS FORAPPLICABLE CODES FOR THIS PROJECT.
2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.
4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.
NOTE: ALL DUCT SIZES SHOWN INCLUDE 1-1/2 OF INTERNAL OR EXTERNAL INSULATION.
5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.
6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.
7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.
DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING
8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.
9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.
10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.
11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.
12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.
13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.
14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.
15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.
16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.
17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.
18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.
19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:
A. WALL APPLICATION: MODEL RAP 14.8
20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.
21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:
A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.
B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.
22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.
23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.
24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.
25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.
26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND APPLICABLE CODE. EACH VERTICALRISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.
27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.
28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.
29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.
30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.
31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.
32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.
33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.
34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.
35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.
36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.
37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.
38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.
39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.
MECHANICAL SYSTEMS BASIS OF DESIGN
SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.
1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.
WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937
OUTDOOR NON- RESIDENTIAL RESIDENTIAL WINTER DRY BULB 11∘F 9.8 0F 13 0F SUMMER DRY BULB 92 ∘F 92.6 0F 90 0F SUMMER WET BULB 75 ∘F 74.4 0F 73.7 0F
INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX
2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):
STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF.
MECHANICAL SCOPE OF WORK
THE WORD “PROVIDE” SHALL MEAN “FURNISH AND INSTALL".
THE CONTRACTORS SHALL BE RESPONSIBLE TO PROVIDE ALL LABOR AND MATERIALS ASREQUIRED AND AS INDICATED ON THESECONTRACT DRAWINGS AND NOTES. THE WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THEFOLLOWING:
1. PERFORMANCE OF ALL WORK AS DESCRIBED ON THESE CONTRACT DRAWINGS AND ASREFERENCED IN THE SPECIFICATIONS AND NOTES AS APPLICABLE FOR EACH PARTICULARCONSTRUCTION DISCIPLINE.
2. CONTRACTOR SHALL PROVIDE MECHANICAL SYSTEMS TO FEED NEW FIXTURES AND EQUIPMENT.INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE STATED MECHANICAL CODE.
3. RESTORATION OF EXISTING SYSTEMS, DEVICES, FINISHES, ETC. DAMAGED OR ALTERED BY NEWWORK TO ACCEPTABLE CONDITION AS DETERMINED BY THE OWNER, ARCHITECT AND/ORENGINEER.
4. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL UTILITIES BEFORE WORK BEGINS.
5. CONTRACTOR SHALL PROVIDE CUTTING, CORING, AND PATCHING AS REQUIRED FORINSTALLATION.
6. CONTRACTOR SHALL COORDINATE PHASING WITH BUILDING OWNER’S REPRESENTATIVE.
MECHANICAL NOTES1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNING
CODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE FOLLOWINGAPPLICABLE CODES, AS AMENDED BY THE STATE OF NEW JERSEY.
A. 2009 INTERNATIONAL BUILDING CODE - NEW JERSEY EDITION B. 2009 INTERNATIONAL RESIDENTIAL CODE - NEW JERSEY EDITION C. 2009 ENERGY CONSERVATION CODE - NEW JERSEY EDITION D. 2009 INTERNATIONAL MECHANICAL CODE - NEW JERSEY EDITION E. 2009 INTERNATIONAL FUEL GAS CODE - NEW JERSEY EDITION F. 2009 NATIONAL STANDARD PLUMBING CODE
2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.
4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.
NOTE: DUCT SIZES SHOWN ARE CLEAR INTERNAL DIMENSIONS.
5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.
6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.
7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.
DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING
8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.
9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.
10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.
11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.
12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.
13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.
14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.
15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.
16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.
17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.
18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.
19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:
A. WALL APPLICATION: MODEL RAP 14.8
20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.
21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:
A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.
B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.
22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.
23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.
24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.
25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.
26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND SECTION 504.6 OF THE 2009 IMC. EACHVERTICAL RISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.
27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.
28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.
29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.
30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.
31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.
32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.
33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.
34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.
35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.
36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.
37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.
38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.
39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.
MECHANICAL SYSTEMS BASIS OF DESIGN
SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.
1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.
WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937
OUTDOOR WINTER DRY BULB 11∘F SUMMER DRY BULB 92 ∘F SUMMER WET BULB 75 ∘F
INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX
2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):
STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF.
HVAC LEGEND
ACCU AIR-COOLED CONDENSING UNITAFF ABOVE FINISHED FLOORATG ACOUSTICAL TRANSFER GRILLEAU INDOOR AIR UNITAWR ADJUSTABLE WALL REGISTER
BD MANUAL BALANCING DAMPERBDD BACKDRAFT DAMPERBOD BOTTOM OF DUCT
COND CONDENSATE DRAINCA COMBUSTION AIRCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCG CEILING GRILLECR CEILING RETURN AIR GRILLECRD CEILING RADIATION DAMPERCS CEILING SUPPLY REGISTERCW COLD WATER
DISP DISPOSABLEDV DRYER VENT
EA EXHAUST AIREF EXHAUST FANESP EXTERNAL STATIC PRESSURE
F, FURN GAS FIRED FURNACEFC FLEXIBLE CONNECTIONFD FIRE DAMPERFL(S),FLR(S) FLOORSFR FLOOR REGISTERFRG FILTER RETURN AIR GRILLEFS FLOOR SUPPLY
HHW HEATING HOT WATERHHWR HEATING HOT WATER RETURNHHWS HEATING HOT WATER SUPPLYHP HORSEPOWERHS HIGH SIDEHW HOT WATERHWE HIGH WALL EXHAUST AIR
GRILLEHWR HIGH WALL RETURN AIR GRILLE
IS INSECT SCREEN
L LINING FOR ACOUSTICSLD LOUVERED DOORLS LOW SIDELSC LOCKSHIELD COVERLWC LOUVERED WALL CAPLWE LOW WALL EXHAUST AIR GRILLELWR LOW WALL RETURN AIR GRILLELWS LOW WALL SUPPLY REGISTER
MA MAKE-UP AIRMFR MANUFACTURERMIN MINIMUM
N/A NOT APPLICABLENTS NOT TO SCALE
OA OUTSIDE AIROSTD OFFSET TRANSFER DUCTOTW OUT THRU WALLOV OVAL
PERM PERMANENT
RJ ROOF JACKRA RETURN AIRRQD REQUIREDRQMTS REQUIREMENTS
SA SUPPLY AIRSN SHEET NOTES
T THERMOSTATTR REVERSE ACTING THERMOSTATTG TRANSFER GRILLE
UTA UP TO ATTICUTR UP THRU ROOF
WC WALL CAPWCS WALL CAP w/INSECT SCREENWH DOMESTIC WATER HEATER
ZD ZONE DAMPER
HVAC LEGEND
ACCU AIR-COOLED CONDENSING UNITAFF ABOVE FINISHED FLOORATG ACOUSTICAL TRANSFER GRILLEAU INDOOR AIR UNITAWR ADJUSTABLE WALL REGISTER
BD MANUAL BALANCING DAMPERBDD BACKDRAFT DAMPERBOD BOTTOM OF DUCT
COND CONDENSATE DRAINCA COMBUSTION AIRCD CEILING DIFFUSERCFM CUBIC FEET PER MINUTECLG CEILINGCG CEILING GRILLECR CEILING RETURN AIR GRILLECRD CEILING RADIATION DAMPERCS CEILING SUPPLY REGISTERCW COLD WATER
DISP DISPOSABLEDV DRYER VENT
EA EXHAUST AIREF EXHAUST FANESP EXTERNAL STATIC PRESSURE
F, FURN GAS FIRED FURNACEFC FLEXIBLE CONNECTIONFD FIRE DAMPERFL(S),FLR(S) FLOORSFR FLOOR REGISTERFRG FILTER RETURN AIR GRILLEFS FLOOR SUPPLY
HHW HEATING HOT WATERHHWR HEATING HOT WATER RETURNHHWS HEATING HOT WATER SUPPLYHP HORSEPOWERHS HIGH SIDEHW HOT WATERHWE HIGH WALL EXHAUST AIR
GRILLEHWR HIGH WALL RETURN AIR GRILLE
IS INSECT SCREEN
L LINING FOR ACOUSTICSLD LOUVERED DOORLS LOW SIDELSC LOCKSHIELD COVERLWC LOUVERED WALL CAPLWE LOW WALL EXHAUST AIR GRILLELWR LOW WALL RETURN AIR GRILLELWS LOW WALL SUPPLY REGISTER
MA MAKE-UP AIRMFR MANUFACTURERMIN MINIMUM
N/A NOT APPLICABLENTS NOT TO SCALE
OA OUTSIDE AIROSTD OFFSET TRANSFER DUCTOTW OUT THRU WALLOV OVAL
PERM PERMANENT
RJ ROOF JACKRA RETURN AIRRQD REQUIREDRQMTS REQUIREMENTS
SA SUPPLY AIRSN SHEET NOTES
T THERMOSTATTR REVERSE ACTING THERMOSTATTG TRANSFER GRILLE
UTA UP TO ATTICUTR UP THRU ROOF
WC WALL CAPWCS WALL CAP w/INSECT SCREENWH DOMESTIC WATER HEATER
ZD ZONE DAMPER
NOTE: THIS IS A GENERAL MECHANICAL LEGEND. ALLSYMBOLS MAY NOT APPEAR ON THE PLANS.REFER TO PLANS FOR ACTUAL SYMBOLS USED.
MECHANICAL NOTES
1. THE INSTALLING CONTRACTORS SHALL BE RESPONSIBLE FOR COMPLIANCE WITH ALL GOVERNINGCODES AND REGULATIONS. THIS PROJECT HAS BEEN DESIGNED ACCORDING TO THE APPLICABLECODES, AS AMENDED BY THE STATE OF NEW JERSEY. REFER TO ARCHITECTURAL PLANS FORAPPLICABLE CODES FOR THIS PROJECT.
2. REMOTE AIR COOLED CONDENSING UNITS SHALL BE MOUNTED ON A PRE-FORMED FIBERGLASSEQUIPMENT PAD. FINAL LOCATION SHALL BE COMPATIBLE WITH MAXIMUM REFRIGERATION PIPINGROUTING AND LENGTH LIMITATIONS RECOMMENDED BY UNIT MANUFACTURER.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING OF REFRIGERANT PIPING IN ACCORDANCEWITH MANUFACTURER’S RECOMMENDATIONS. PROPER REFRIGERANT CHARGE SHALL BE VERIFIEDBASED ON THE INSTALLED LINESET USING SUPERHEAT, SUBCOOLING, OR WEIGH-IN.
4. LINED RECTANGULAR DUCTING (WHERE APPLICABLE) SHALL UTILIZE A DUCT LINER COMPLIANTWITH N.F.P.A.-90 FIRE RESISTANCE CODE AND A.S.T.M. TEST E-84-75 RATING OF 25 FOR FLAMESPREAD AND 50 FOR SMOKE DEVELOPED. LINER SHALL BE INSTALLED PER MANUFACTURER’SRECOMMENDATIONS.
NOTE: ALL DUCT SIZES SHOWN INCLUDE 1-1/2 OF INTERNAL OR EXTERNAL INSULATION.
5. USE ROUND GALVANIZED STEEL DUCTING TO INDIVIDUAL AIR OUTLETS EXCEPT AS NOTED.FLEXIBLE DUCT WORK, WHERE INDICATED, SHALL BE PROPERLY SUPPORTED AND KINK FREE.FLEXIBLE DUCT SHALL BE U.L. LABELED CLASS-1 AIR DUCT.
6. PROVIDE SUPPLY BRANCH VOLUME DAMPERS WHERE PRACTICAL ACCESS ALLOWS, SUCH AS INBASEMENT AND ATTICS.
7. ALL SUPPLY AND RETURN DUCTWORK IN ATTIC AREAS OR ADJACENT TO UNCONDITIONED AREASSHALL BE INSULATED PER THE FOLLOWING SCHEDULE AND CONTAIN AN EXTERIOR VAPOR BARRIER.
DUCT LOCATION SUPPLY RETURN CONDITIONED R-0 R-0 SPACE HEATED R-0 R-0 BSMT/CRAWL UNHEATED R-8 R-6 BSMT/CRAWL ATTIC ABOVE R-8 R-8 THE THERMAL ENVELOPE EXTERIOR WALL R-8 R-6 GARAGE WALL R-8 R-6 FLOOR OVER R-8 R-6 OPEN AREA FLOOR OVER R-8 R-6 GARAGE OUTSIDE THE R-8 R-8 BUILDING
8. ALL MECHANICAL/ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCEWITH THEIR CODE APPROVED LISTINGS.
9. THE RETURN AIR SYSTEM SHALL BE 100% DUCTED. FRAMING MEMBERS SHALL NOT BE USED.
10. ALL DUCTWORK SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF S.M.A.C.N.A. LOW PRESSURE SYSTEM AND APPLICABLE LOCAL OR STATECODES.
11. CAP ALL OPEN DUCT SYSTEM ENDS AND COVER ALL OPEN SUPPLY AND RETURN BOXESDURING CONSTRUCTION TO MINIMIZE DEBRIS ENTRY.
12. AIR SYSTEM SHALL BE BALANCED UPON INSTALLATION OF AIR OUTLET REGISTERS AND INLETGRILLES. CONTRACTOR SHALL VERIFY SYSTEM AIR FLOW BETWEEN 350 AND 450 CFM PER TONFOR COOLING AND WITHIN MANUFACTURER REQUIREMENTS FOR TEMPERATURE RISE FOR HEATINGWITH A WARM AIR FURNACE.
13. PROVIDE AIR FILTRATION WITH A MINIMUM PERFORMANCE OF MERV 8 WITH FILTER GRILLES,EXTERNAL RETURN PLENUM FILTER, OR INTERNAL RETURN PLENUM FILTER. FILTER PRESSUREDROP SHALL NOT EXCEED 0.2 INCHES WC.
14. VENTING OF FURNACE AND DOMESTIC WATER HEATER SHALL BE SIZED AND INSTALLED INACCORDANCE WITH MANUFACTURER’S REQUIREMENTS.
15. ALL AIR DISTRIBUTION SYSTEM JOINTS, SEAMS, TAKE-OFFS, OPENINGS OF THE AIR HANDLERCABINET, AND CONNECTIONS AND FINISHED BUILDING MATERIALS SHALL BE SEALED WITH DUCTMASTIC. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH FLEXIBLE CONNECTION AT ALLDUCTWORK CONNECTIONS. SYSTEM AIR LEAKAGE INTO UNCONDITIONED SPACES SHALL NOTEXCEED 5% OF TOTAL SYSTEM AIRFLOW AT 25 PA. (0.1 INCHES WC) AS TESTED WITH DUCT AIRTIGHTNESS TESTER.
16. EXTERNAL AIR FILTER ACCESS SLOTS SHALL BE SEALED WITH A GASKETED MECHANICALCLOSURE OR DUCT TAPE. THE CLOSURE SHALL BE EASILY MAINTAINED BY THE USER.
17. THERMOSTATS SHALL BE LOCATED FOUR (4) FEET ABOVE FINISHED FLOOR.
18. GRILLES, REGISTERS AND DIFFUSERS SHALL NOT EXCEED A NOISE CRITERIA (NC) LEVEL OF25-30 AND SHALL BE AS MANUFACTURED BY HART AND COOLEY OR EQUAL. MODEL NUMBERS ASSCHEDULED.
19. ACOUSTICAL TRANSFER GRILLE (ATG) SHALL BE AS MANUFACTURED BY TAMARACKTECHNOLOGIES, INC. OR EQUAL. MODEL NUMBER AS FOLLOWS:
A. WALL APPLICATION: MODEL RAP 14.8
20. FIRE DAMPERS NOT DIRECTLY MOUNTED BEHIND AIR DEVICES, SUCH AS GRILLES ORREGISTERS, SHALL BE PROVIDED WITH A SUITABLE DUCT-MOUNTED ACCESS DOOR.
21. PROVIDE ACCESS TO MECHANICAL EQUIPMENT AS REQUIRED BY SECTION 306 OF THE 2009IBC AS SPECIFIED BELOW:
A. ATTIC: EQUIPMENT SHALL BE ACCESSIBLE BY AN OPENING AND UNOBSTRUCTEDPASSAGEWAY NOT LESS THAN 22 INCHES WIDE AND 30 INCHES HIGH AND NOT MORE THAN20 FEET LONG. A LEVEL SERVICE SPACE NO LESS THAN 30 INCHES WIDE AND 30 INCHESDEEP SHALL BE PROVIDED ON THE SERVICE SIDE OF THE EQUIPMENT.
B. MECHANICAL CLOSET OR BASEMENT: EQUIPMENT SHALL BE ACCESSIBLE BY ANUNOBSTRUCTED PASSAGEWAY OR DOOR NOT LESS THAN 24 INCHES WIDE AND SHALL HAVEA LEVEL SERVICE SPACE 30 INCHES DEEP AND THE HEIGHT OF THE EQUIPMENT ON THESERVICE SIDE OF THE EQUIPMENT.
22. PROVIDE AUXILIARY CONDENSATE DRAIN SYSTEM FOR EACH COOLING COIL IN ACCORDANCEWITH SECTION 307.2.3 OF THE 2009 IMC.
23. DISCHARGE FURNACE CONDENSATE TO INDIRECT CONNECTION WITH THE STORM SYSTEM OROTHER APPROVED LOCATION. ALL CONDENSATE LINES LOCATED IN UNHEATED AREAS SHALL BEPREVENTED FROM FREEZING PER MANUFACTURER’S REQUIREMENTS.
24. MECHANICAL VENTILATION FOR OCCUPIED SPACE OTHER THAN DWELLING UNITS IS PROVIDEDACCORDING TO SECTION 403 OF THE 2009 IMC.
25. LOUVER WALL CAPS, WALL CAPS AND ROOF JACKS SHALL BE COLOR AS SELECTED BYARCHITECT.
26. CLOTHES DRYER EXHAUST VENT SHALL BE INSTALLED IN ACCORDANCE WITH THERECOMMENDATIONS OF THE DRYER MANUFACTURER AND APPLICABLE CODE. EACH VERTICALRISER SHALL BE PROVIDED WITH A CLEAN OUT UNLESS A DRYER BOX IS UTILIZED.
27. ALL PIPING AND DUCTWORK SHALL BE HUNG FROM BUILDING STRUCTURE ONLY. DO NOT HANGFROM THE FLOOR/SLAB. PROVIDE SUPPLEMENTARY SUPPORT MEMBERS AS NECESSARY TOSUPPORT PIPES AND DUCTS FROM BUILDING STRUCTURE. NO ANCHORAGE TO ANY STRUCTURALLYUNSUITABLE OR INADEQUATE ELEMENTS SHALL BE PERMITTED. THE ARCHITECT & STRUCTURALENGINEER SHALL BE THE SOLE DETERMINANTS AS TO PERMISSIBILITY OF HANGING NEW WORKFROM BUILDING STRUCTURAL MEMBERS. WHERE THIS IS NOT POSSIBLE, FURNISH AND INSTALLINTERMEDIATE STRUCTURAL MEMBER SUPPORTS OF SUFFICIENT SIZE AND LOAD BEARINGCAPACITY SPANNING FROM EXISTING BUILDING STRUCTURAL MEMBER TO EXISTING BUILDINGSTRUCTURAL MEMBER. NEW WORK SHALL BE SUPPORTED FROM THESE MEMBERS AS REQUIRED.
28. FLEXIBLE DUCTWORK AT CLOTHES DRYERS SHALL MEET UL 2158 REQUIREMENTS ASMANUFACTURED BY DRYER FLEX, DEFLECT-O OR JUNDAS-JAFINE.
29. FINAL LOCATION OF ALL CEILING DIFFUSERS, RETURN REGISTERS AND CEILING GRILLES SHALLBE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. PROVIDE DUCTWORK ASREQUIRED TO COMPLY WITH THIS. QUANTITIES OF THESE DEVICES SHALL BE PROVIDED AS SHOWNON THE CONTRACT DRAWINGS. ANY DISCREPANCIES BETWEEN THE MECHANICAL DRAWINGS ANDTHE ARCHITECTURAL REFLECTED CEILING PLANS SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID. THE ARCHITECT SHALL APPROVE COLOROF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES.
30. WHILE THE CONTRACT DRAWINGS SHALL BE ADHERED TO AS CLOSELY AS POSSIBLE, THEARCHITECT’S/ENGINEER’S RIGHT IS RESERVED TO VARY THE RUN AND SIZE OF DUCTS DURING THEPROGRESS OF THE WORK IF REQUIRED TO MEET CEILING HEIGHTS, STRUCTURAL AND FIELDCONDITIONS. CONTRACTOR SHALL PROVIDE RE-DRAWING OF SHOP DRAWINGS AS NECESSARYTO ACCOMMODATE THE ARCHITECT’S/ENGINEER’S REQUIREMENTS, AT NO ADDITIONAL COST TOTHE OWNER. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR REQUIRED CEILINGHEIGHTS.
31. INSTALL ALL DUCTWORK IN STRICT ADHERENCE TO THE CEILING HEIGHTS INDICATED ON THEARCHITECT’S DRAWINGS. CONSULT WITH OTHER CONTRACTORS AND IN CONJUNCTION WITH THEOTHER CONTRACTORS, ESTABLISH THE NECESSARY SPACE REQUIREMENTS FOR EACH TRADE.PREPARE THE COORDINATION DRAWINGS AS PER THE SPECIFICATIONS.
32. THE SHEET METAL DUCTWORK SHALL, WHETHER INDICATED OR NOT, RISE AND/OR DROP AND/OR CHANGE IN SHAPE TO CLEAR ANY AND ALL OTHER DUCTWORK, CONDUITS, LIGHTING FIXTURES,HEATING, PLUMBING AND SPRINKLER LINES TO MAINTAIN THE DESIRED CEILING HEIGHTS, AND TOPROVIDE ADEQUATE MAINTENANCE ROOM AND HEAD ROOM IN MECHANICAL EQUIPMENT ROOMS.THE CONTRACT DRAWINGS IN GENERAL DO NOT SHOW ALL RISES, DROPS AND DUCT TRANSITIONSREQUIRED. THE CONTRACT DRAWINGS SHOW GENERAL ROUTING REQUIREMENTS.
33. THE DUCTWORK SHALL BE CONTINUOUS, WITH AIRTIGHT JOINTS AND SEAMS PRESENTING ASMOOTH SURFACE ON THE INSIDE AND NEATLY FINISHED ON THE OUTSIDE. DUCTS SHALL BECONSTRUCTED WITH CURVES AND BENDS AS TO EFFECT AN EASY FLOW OF AIR. UNLESSOTHERWISE SHOWN ON THE CONTRACT DRAWINGS, THE INSIDE RADIUS OF ALL CURVES ANDBENDS SHALL BE NOT LESS THAN WIDTH OF DUCTS IN PLANE OF BEND.
34. ALL RECTANGULAR DUCTWORK, UNLESS OTHERWISE NOTED, SHALL BE BUILT FROMGALVANIZED SHEET STEEL AND THOROUGHLY BRACED AND STIFFENED. REFER TO CONTRACTDRAWINGS AND SPECIFICATIONS FOR DUCTS REQUIRED TO BE FABRICATED OF ALUMINUM ANDSTAINLESS STEEL.
35. REFER TO SPECIFICATION AND CONTRACT DRAWINGS FOR DUCTS REQUIRED TO BE LINED.DIMENSIONS GIVEN ON THE CONTRACT DRAWINGS FOR LINED DUCTS ARE CLEAR DIMENSIONS.INCREASE SIZE OF SHEET METAL DUCT TO PROVIDE THE SPECIFIED CLEAR DIMENSION WITHACOUSTICAL LINING ADDED.
36. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES, COILS, FIRE DAMPERS, CONTROLS, DAMPERS, ETC. AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE. THESE ACCESS DOORS SHALL BE LOCATED AS TOPERMIT MAINTENANCE. LOCATE SUCH EQUIPMENT ABOVE ACCESSIBLE CEILINGS TO THE EXTENTPOSSIBLE TO AVOID ACCESS DOORS IN THE CEILING.
37. DIFFUSERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED TO BE LIFTED UP INTO THECEILING. FLEXIBLE DUCT (MAXIMUM LENGTH OF 5 FT.) SHALL BE PROVIDED AT THE DIFFUSER TOALLOW FOR ACCESS ABOVE THE CEILING. FLEXIBLE DUCTS SHALL NOT BE USED AT ANY OTHERLOCATIONS.
38. REFER TO ENGINEERING DRAWINGS FOR LOCATIONS OF ALL MEP/FP(SP) COMPONENTS FORFULL INTEGRATION INTO ARCHITECTURAL DESIGN. BIDDERS SHALL IMMEDIATELY CALL THEARCHITECT’S/ENGINEER’S ATTENTION TO ANY DISCREPANCIES IN QUANTITIES, TYPES AND SCOPEFOR ALL DISCIPLINES/TRADES.
39. COORDINATE ALL ROOF PENETRATIONS + ROOF SUPPORT DUNNAGE WITH THE STRUCTURALDWGS, SPECS AND REQS.
MECHANICAL SYSTEMS BASIS OF DESIGN
SIZING, DESIGN AND PERFORMANCE OF THE HEATING AND COOLING SYSTEMS ARE BASED ONTHE FOLLOWING DESIGN CHARACTERISTICS. MODIFICATION OF ANY OF THESE CHARACTERISTICS MAYADVERSELY AFFECT THE HEATING AND COOLING PERFORMANCE AND LEVEL OF COMFORT TO THEBUILDING OCCUPANTS.
1. DESIGN CONDITIONS: OUTDOOR DESIGN CONDITIONS ARE BASED ON ASHRAE 97 1/2%WINTER DESIGN TEMPERATURES AND 2 1/2% SUMMER DESIGN TEMPERATURES AS PER IMC.2009. INDOOR DESIGN CONDITIONS ARE BASED ON ACCA MANUAL J RECOMMENDATIONS.MODIFICATIONS DUE TO LOCAL CONDITIONS ARE IDENTIFIED BELOW, IF APPLICABLE.
WEATHER STATION LOCATION – PHILADELPHIA, PA HEATING DEGREE DAYS = 4937
OUTDOOR NON- RESIDENTIAL RESIDENTIAL WINTER DRY BULB 11∘F 9.8 0F 13 0F SUMMER DRY BULB 92 ∘F 92.6 0F 90 0F SUMMER WET BULB 75 ∘F 74.4 0F 73.7 0F
INDOOR WINTER DRY BULB 70 ∘F SUMMER DRY BULB 75 ∘F SUMMER RELATIVE HUMIDITY 50% MAX
2. PERFORMANCE SPECIFICATIONS (ACCA MANUAL RS):
STANDARD HEATING COOLING TEMP. @ TSTAT (FROM SETTING) +/- 2∘F +/- 3∘F ROOM TO ROOM TEMP. DIFF. MAX 4∘F MAX 6∘F FLOOR TO FLOOR TEMP. DIFF. MAX 4∘F MAX 6∘F TEMP. DIFF. (4” TO 67” AFF.) 1∘F PER 15∘F 3∘F PER 10∘F IN/OUT DIFF. IN/OUT DIFF. VD
M
M
M
DUCT WORK W/ACOUSTIC LINING
SINGLE LINE DUCTWORK - NEW
MECHANICAL EQUIPMENT - NEW
DUCTWORK / EQUIPMENT -EXISTING
DUCTWORK / EQUIPMENT - DEMO
DUCT UNDER POSITIVE PRESSURE(SUPPLY AIR OR FANDISCHARGE)DUCT UNDER NEGATIVEPRESSURE(RETURN, EXHAUST OR OUTSIDEAIR)
VANED ELBOWOR
OR RADIUS ELBOW
RECTANGULAR TORECTANGULAR TRANSITION
OR
OR
RECTANGULAR TO ROUNDTRANSITION
OR
POSITIVE PRESSURE VERTICALDROP(IN DIRECTION OF AIR FLOW)
OR
NEGATIVE PRESSURE VERTICALDROP(IN DIRECTION OF AIR FLOW)
OR
POSITIVE PRESSURE VERTICALRISE(IN DIRECTION OF AIR FLOW)
OR
NEGATIVE PRESSURE VERTICALRISE(IN DIRECTION OF AIR FLOW)
OR DUCT FLEXIBLE CONNECTION
RIGID DUCTWORK TERMINATION
FLEXIBLE DUCT
BRANCH CONNECTIONSOR
VOLUME DAMPER
FIRE DAMPER & ACCESS DOOR
SMOKE DAMPER & ACCESSDOOR
BACK DRAFT DAMPER
AUTOMATIC DAMPER(PNEUMATIC)
AUTOMATIC DAMPER (ELECTRIC)
COMBINATION SMOKE & FIREDAMPER & ACCESS DOOR
RISE IN DUCTWORK (IN DIRECTION OFAIR FLOW)DROP IN DUCTWORK (IN DIRECTION OFAIR FLOW)
LOUVER IN DOOR
UNDERCUT DOOR
R
D
L
U
POINT OF CONNECTION
POINT OF DISCONNECTION
B
P
ACCESS PANEL
C-8"Ø235 CFM
RECTANGULAR CEILING DIFFUSERW/ 8"Ø NECK235 CFM SUPPLY AIR
C-8"Ø235 CFM
ROUND CEILING DIFFUSER W/ 8"ØNECK235 CFM SUPPLY AIR
12" x 12" CEILING REGISTER(GRILLE)260 CFM RETURN AIRG-12x12
260 CFM
DIFFUSER W/ BLANKING PLATE
EXHAUST FAN
TRANSFER GRILLE
"A" - 12x12XXX -
1W = 1 WAY2W = 2 WAY3W = 3WAY4W = 4 WAYMA = MULTI-ANGLE
TYPE DESIGNATORREFER TO REGISTER,GRILLE AND DIFFUSERSCHEDULE
4 WAY TYPICAL UNLESSINDICATED OTHERWISE
AIR QUANTITY (CFM)
T
XXXX
EQUIPMENT DESIGNATION
T THERMOSTAT (PNEUMATIC)
BOD BOTTOM OF DUCT ELEVATIONFROM FLOOR
GENERAL MECHANICAL NOTES
MECHANICAL SCOPE OF WORK
MECHANICAL ABBREVIATIONS
MECHANICAL DRAWING LIST
MECHANICAL BASIS OF DESIGN
MECHANICAL NOTES MECHANICAL SYMBOLS
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
NO
TES,
SYM
BOLS
& A
BBR
EVIA
TIO
NS,
Thur
sday
, Mar
ch 3
, 201
6,3:
26 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
MC000
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
NOTES, SYMBOLS &ABBREVIATIONS
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
F3
L3
T
L2
C3
C2
C1
T
L1
27
27
27
CU1
CU2
WW
WW
WW
DD
DD
DD
115 CFM10x10CD
115 CFM10x10CD
S1-130 CFM12x12CD
130 CFM12x12CD
14x12
6"⦰
6"⦰
14x12
10x10
18x12
10x10
12x12
115 CFM12x12WL
S2-100 CFM10x8WD
14x12
10x8DUCT UP
8"⦰
8"⦰
12x12
680 CFM20x20CR
S1-110 CFM9x9CD
75 CFM9x9CD
25 CFM6x6CD
25 CFM6x6CD
50 CFM
50 CFM
90 CFM9x9CD
75 CFM9x9CD
25 CFM6x6CD
MOUNT ABOVE WINDOW
225 CFM12x12
22x16
22x16
20
x16
12x1012x10
12x1012x10
12x10
DUCT UP
225 CFM12x12
225 CFM12x12
225 CFM12x12
288 CFM30x18WL
24x16 RETURN DUCT AIR
75 CFM
288 CFM18x12 WL
288 CFM14x14
8x8
6x6
10x8
10x8
6x6
6x6
8x8
6"⦰
100 CFM10x10
10x12
12x12
14x12
14x12
10x10
10x10
10x10
200 CFM24x12WL
BO
D 1
0'6
"
BO
D 1
0'6
"
DW
R
R
OFFICE
116
MGMT. OFFICE
115
VESTIBULE
101
EXERCISE
102
LAUNDRY
103
COMMUNITY ROOM
111
PATIO
01
CONSULT
118
KITCHENETTE
121
MEN
113
COMMON CORRIDOR
112
ELEC./IT
109
PORCH
01
PORCH
01
CONIFER CORRIDOR
110
STORAGE
107
JAN.
108
MAINTENANCE
104
SPRINKLER
105
MECH.
106
WOMEN
114
EF3
EF2
F1
EF4
EH6
EH6
EH6
HP2
HP1
EH5
F2
EF5
L2
EH1
R1
225 CFM12x12
16x1612x10
14x1212x10
225 CFM12x12
225 CFM12x12
225 CFM12x12
10"⦰
10"⦰
10"⦰
10"⦰
10"⦰
10"⦰
10"⦰
10"⦰
R2-1512 CFM20x20 WR
R1-12x12CR250 CFM
KEYED NOTES
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
INSTALL FURNACE PER MANUFACTURER'SRECOMMENDATIONS. PROVIDE FULL SIZE (MIN. 3/4 INCH)COOLING COIL CONDENSATE PIPING WITH TRAP ANDFURNACE CONDENSATE PIPING FROM EQUIPMENT TO THEFLOOR DRAIN INDIRECT WASTE CONNECTION POINT WITHINTHE MECHANICAL ROOM. FLOOR DRAIN BY PLUMBINGCONTRACTOR. MAINTAIN A MINIMUM CLEARANCE OF 3" ATBACK AND SIDES OF FURNACE. PROVIDE INTER-CONNECTINGCONTROL WIRING BETWEEN FURNACE AND AIR-COOLEDCONDENSING UNIT ON GRADE.
CONNECT 2" PVC VENT PIPING AND COMBUSTION AIRPIPING TO FURNACE. ROUTE PIPING TO SIDEWALLTERMINATION KIT.
SIDEWALL TERMINATION KIT. INCREASE 2" VENT ANDCOMBUSTION AIR PIPING TO 3" VENT AND COMBUSTION AIRPIPING ON TERMINATION KIT AS REQUIRED.
PROGRAMMABLE THERMOSTAT. PROVIDE INTER-CONNECTING CONTROL WIRING.
COORDINATE LOCATION OF EXHAUST FAN WITH WOODTRUSSES.
LOCATION OF FURNACE COMBUSTION AIR AND AND VENTSIDEWALL TERMINATION KIT (MIN. 12" FROM ANY AIROPENINGS INTO THE BUILDING SUCH AS WINDOWS)
ROUTE DUCTWORK THRU OPEN WEB OF WOOD TRUSSES.
SIZE AND INSTALL REFRIGERANT PIPING ANDACCESSORIES IN ACCORDANCE WITH MANUFACTURER'SINSTRUCTIONS. ROUTE REFRIGERANT PIPING FROMMECHANICAL ROOMS TO AIR-COOLED CONDENSING UNITAND FROM LAUNDRY ROOM TO HEAT PUMP. RUN LINESFROM EQUIPMENT LOCATION TO AIR-COOLED CONDENSINGUNIT AND HEAT PUMP UNIT LOCATED ON GRADE. OFFSETPIPING AS REQUIRED.
ROUTE SUPPLY AIR DUCTWORK UP THRU CEILING TOBETWEEN WOOD TRUSSES. OFFSET DUCTWORK ASREQUIRED.
RUN FULL SIZE (MIN. 3/4 INCH) CONDENSATE DRAIN PIPINGIN CEILING SPACE FROM EQUIPMENT TO THE FLOOR DRAININDIRECT WASTE CONNECTION POINT LOCATED IN THEMECHANICAL ROOM.
MAINTAIN 30" CLEAR SERVICE CLEARANCE IN FRONT OFFURNACE.
NOT IN USE.
ALL DUCTWORK TRAVERSING THE ATTIC SPACE IN ORDERTO PASS THRU THE ROOF AND OUTSIDE AIR DUCTWORKSHALL BE INSULATED.
THE DUCT SHALL DISCHARGE THRU A ROOF JACK ON THEROOF. COLOR AS SELECTED BY ARCHITECT.
SUPPLY CEILING REGISTERS SHALL BE CENTERED ON THEWINDOWS.
PROVIDE RETURN AIR GRILLE MOUNTED HIGH ON WALL.TOP OF RETURN AIR GRILLE SHALL BE MOUNTED 3" BELOWCEILING. RETURN AIR GRILLE BLADES SHALL FACE UP FORSIGHT PROOF. PAINT AREA BEHIND GRILLES FLAT BLACK.
PROVIDE EACH AIR-COOLED CONDENSING UNIT AND HEATPUMP UNIT WITH AN ENGRAVED PLATE IDENTIFYING WHICHAREAS THE ACCU OR HP SERVES (I.E. "COMMUNITY ROOM","BUILDING PUBLIC AREA", ETC.).
MECHANICALLY FASTEN AIR-COOLED CONDENSING UNITAND MOUNTING KIT TO EQUIPMENT CURBS.
REFER TO FURNACE INSTALLATION DETAIL ON THE DETAILSHEET.
REFER TO DRYER AND LAUNDRY ROOM DETAILS ON THEDETAIL SHEET.
F-1 CONTROL SEQUENCE SHALL BE CONTROLLED BY ANOCCUPIED/UNOCCUPIED SCHEDULE PROGRAMMABLETHERMOSTAT. THE OUTSIDE AIR MOTORIZED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" DURING THEOCCUPIED CYCLE AS REQUIRED BY THE ROOM MOUNTEDCO2 SENSOR. THE OPERATION OF THE FURNACE & AIR-COOLED CONDENSING UNIT SHALL BE CONTROLLED BY THEPROGRAMMABLE ROOM MOUNTED THERMOSTAT.
F-2 CONTROL SEQUENCE SHALL BE CONTROLLED BY ANOCCUPIED/UNOCCUPIED SCHEDULE PROGRAMMABLETHERMOSTAT. THE OUTSIDE AIR MOTORIZED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" DURING THEOCCUPIED CYCLE. THE OPERATION OF THE FURNACE & AIR-COOLED CONDENSING UNIT SHALL BE CONTROLLED BY THEPROGRAMMABLE ROOM MOUNTED THERMOSTAT.
AU-1 CONTROL SEQUENCE SHALL BE CONTROLLED BY THEWALL MOUNTED PROGRAMMABLE THERMOSTAT.
INTERLOCK THE MOTOR OPERATED DAMPER TO EACHCLOTHES DRYER. THE MOTOR OPERATED DAMPERNORMALLY "CLOSED" SHALL BE "OPENED" UPON OPERATIONOF ANY ONE DRYER. THE ELECTRICAL CONTRACTOR SHALLPROVIDE DRYER AMP CURRENT SENSOR ON POWER SUPPLYOF EACH DRYER (COORDINATE LOCATION WITH ELECTRICALCONTRACTOR). WHEN ANY ONE DRYER IS ENERGIZED, THEMOTOR OPERATED DAMPER SHALL MODULATE "OPEN".WHEN DRYERS ARE DE-ENERGIZED, THE REVERSE SHALLOCCUR. THE MECHANICAL CONTRACTOR SHALL PROVIDEALL INTERLOCK CONTROL WIRING BETWEEN EQUIPMENT ANDMOTOR OPERATED DAMPER AND CONTROLLERS ATCONTROL VOLTAGE (NO LINE VOLTAGE) TO PROVIDECONTROL AS STATED.
PROVIDE METAL HOODED WALL VENT WITH CONCEALEDBACKDRAFT DAMPER AS MANUFACTURED BY MID-ATLANTICSIDING COMPONENTS. PROVIDE CUSTOM COLOR SELECTEDBY ARCHITECT. PROVIDE BAND CLAMP CONNECTIONS TODUCTWORK. CAULK AND SEAL WEATHER TIGHT.
LOCATION OF TEMPERATURE CONTROLLER WITHIN A
LOCKSHIELD COVER ON THE ROOM SIDE OF THE SHAFT.
N
SCALE: 1/4" = 1'-0"1 FIRST FLOOR PLAN
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
FIR
ST F
LOO
R P
LAN
,Thu
rsda
y, M
arch
3, 2
016,
3:26
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
M101
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
FIRST FLOOR PLAN
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
NOM.CAPACITY
TONSTAG LOCATION/SERVICE
C-1
SEER
NOTES:1. PROVIDE PRE-INSULATED REFRIGERANT LINE SET, COMPRESSOR RUBBER ISOLATION KIT, HARD START KIT, WIND BAFFLE FOR LOW AMBIENT
CONTROL AND ALL ACCESSORIES REQUIRED FOR LONG LINE APPLICATIONS, AS DETERMINED BY THE MANUFACTURER.
AIR-COOLED CONDENSING UNIT SCHEDULE
AT GRADE/ COMMUNITY RM.
CONDENSER FANS
NO. RPM HP NO. RLA STAGES
COMPRESSOR
V/PH/HZ MCA
ELECTRICALBASIS OF DESIGN
MFR/MODEL REMARKSEERREFRIG.AMBIENTTEMP.(ºF)
410A 95 5.0 14.25 12.25 1/4 835 1/5 1 134 1 208/2301ϕ 60HZ 32.7 YCIF60S41S2(E)
Y0RK REFER TO NOTE 1
C-2 AT GRADE/ MANAGEMENT 410A 95 2.0 14.5 12.3 1/8 850 1/8 1 58 1 16.8 REFER TO NOTE 1
C-3 AT GARDE/ CONSULTANT 410A 95 2.5 14.5 12.3 1/8 - - - 73 - 18.4 YCJF30S41S1(E) -
YCJF24S41S1(E)208/2301ϕ 60HZ208/2301ϕ 60HZ
MOD
50
25
30
TAG LOCATION/SERVICE TYPE CFM ESP(IN. WG.)
FANRPM
MOTORSIZE
HP(W)/AMP V/PH/HZBASIS OF DESIGN
MFR/MODEL REMARKSWEIGHT(LBS.)
FAN SCHEDULE
EF-2
EF-3
WOMEN'S ROOM.
MEN'S ROOM
CEILING
CEILING
115/1/60
115/1/60
SP-A50GREENHECK
SP-A50GREENHECK
EF-1 OFFICE / LOUNGE ROOM CEILING 115/1/60 SP-A90GREENHECK
50
50
100
700
700
9000.125
0.125
0.125
17.6/0.15
18.3/0.31
18.3/0.31
-
-
-
ELECTRICAL
EF-4 STORAGE ROOM CEILING 115/1/60 SP-A70GREENHECK
75 8500.125 15.9/0.14 -
NOTES:1.
-
-
-
-
-EF-5 COMMUNITY ROOM CEILING 115/1/60 SP-A290GREENHECK
288 10000.125 67/0.56 -
TAG
EH-1
NOTES:1. PROVIDE RECESSED UNIT IN COLOR AS SELECTED BY ARCHITECT. TAMPER PROOF THERMOSTAT .2. PROVIDE WALL MOUNTING BRACKET, BUILT-IN ADJUSTABLE THERMOSTAT AND COLOR AS SELECTED BY ARCHITECT.3. PROVIDE AIRFLOW SWITCH, DUCT THERMOSTAT AND DISCONNECT.4. PROVIDE w/BUILT-IN ADJUSTABLE THERMOSTAT AND TRANSFORMER. COLOR AS SELECTED BY ARCHITECT.5. PROVIDE INDIVIDUAL TEMPERATURE SENSOR WITH EACH UNIT CONTROLLED BY A COMMON CONTROLLER FOR ALL EH-5'S AND EH-6'S.
ELECTRIC HEATING SCHEDULE
LOCATION/SYSTEM
WALL/HEATING
REQ.CAPACITY
MBH
-
AIRSIDE
TEMPT.RISE
30/27
REMARKS
REFER TO NOTE 1
MAX PDIN/WG
-
BASIS OF DESIGNMFR/MODEL
933U01500VINDEECO
CFM
160
ELECTRICAL DATA
WATTS
1500/1125
TOTALAMPS
6.5/5.8
VOLTS(1 PHASE)
240/208
WEIGHT(LBS.)
24
SERVICE
VESTIBULE
EH-2 WALL/HEATING - 30/27 REFER TO NOTE 2- 933U01500VINDEECO160 1500
/11256.5/5.8 240/208 24MECHANICAL RM.
EH-3
EH-4 30/27 - 24MECHANICAL RM.WALL/HEATING - 160
EH-5
EH-6 CEILING/HEATING MAINTENANCE RM.
- ---
21/16 -300-
-
- 8.7/7.6
- -
240/208
-
20 924UO2000VAULI INDEECO
WALL/HEATING SPRINKLER RM. 933U01500VINDEECO
933U01500VINDEECO
1500/11251500/1125
160 6.5/5.86.5/5.8
30/27 24
-
240/208
240/208
--
DUCTLESS MINI SPLIT SYSTEM SCHEDULE (SPLIT SYSTEM HEAT PUMP)
CU-1
LOCATION/SERVICE
TAG REMARKS
NOTES:1. PROVIDE PRE-INSULATED REFRIGERANT LINE SET, ALL ACCESSORIES FOR LONG LINE APPLICATION, LOW AMBIENT CONTROL, WALL MOUNTED WIRELESS THERMOSTAT MODEL MHK1, FILTERS, CONDENSATE PUMP PACKAGE AND AIR OUTLET GUIDE
INDOOR UNIT OUTDOOR UNIT
AT GRADE/EXERCISE RM.
UNIT TYPE RQD
COOLINGCAPACITY
(MBH)AIR FLOW (CFM) WEIGHT
(LBS)
ELECTRICALFAN
MOTOROUTPUT(WATTS)
FANMOTORRLA (A)
BASIS OF DESIGNMFR/MODEL REFRIGERANT RQD COOLING
CAPACITY(MBH)
TOTALCOOLING
(MBH)
SEER FANMOTOR(WATTS)
COMPRESSOR MAX.
WEIGHT(LBS)
ELECTRICAL
V/PH/HZ MCA MODBASIS OF DESIGN
MFR/MODEL
WALLMOUNTED 18 501-460-383-324 29 20 0.28 DHPM18NWM42Q1A 410A 18 1.5 18 60 DC INVERTER 91
208/2301ϕ/60 HZ 16 20 DHPM18CSM42Q1A
MITSUBISHI REFER TO NOTE 1
V/PH/HZ
208/23060HZ
CU-2 AT GRADE/LAUNDRY RM.
WALLMOUNTED 18 590-472-413-354 29 20 0.24 DHPM24NWM42Q1 410A 18 2.0 18 90 DC INVERTER 91 16 20 DHPM18CSM42Q1A
MITSUBISHI REFER TO NOTE 1208/23060HZ
AMBIENTTEMP ˚F
95
95
EER
10
10
RLA
9.35
10.45 208/2301ϕ/60 HZ
TAG LOCATION/SERVICE
F-1
NOMINALAIRLFOW
NOTES:1. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT WITH HEAT-OFF-COOL, FAN AUTO-OFF SWITCHES, w/BATTERY BACK-UP, 1" MERV 8 FILTER FOR
INSTALLATION WITHIN BLOWER CABINET, FILTER RACK RAILS WITH RETAINING PINS & SPRINGS, COOLING COIL w/NON-BLEED TXV KIT (FACTORY INSTALLED),CONDENSATE NEUTRALIZER KIT AND HORIZONTAL TERMINATION KIT BAYVENT 200B BY TRANE.
GAS-FIRED FURNACE SCHEDULE
MECH RM/COMMUNITY RM
MOTOR
V/PH/HZ HP AMPS STARTER TMBH MODEL/SERIES
MIN.OUTPUT(MBH)
RQD COOLINGBASIS OF DESIGN
MFR/MODELREMARKSTYPE MIN. O.A.
CFM INPUT(MBH)
E.S.P.IN W.C.
REQ. HEATING
REFRIG.TYPE
CONDENSINGUPFLOW 2000 288 0.60 120/1/60 3/4 804 - 51.6 R410A - - 95 TM9E100C20MP11 -
F-2 1000 200 0.50 120/1/60 1/2 6.8 - 21.1 R410A - - 38 TM9E040A10MP11 -
AFUER%
95
95
F-3 MECH RM CONDENSINGUPFLOW 1200 115 0.50 120/1/60 1/2 6.8 - 25.0 R410A - - 57 TM9E060B12MP11 -95
MECH RM CONDENSINGUPFLOW
DIFFUSER REGISTER AND GRILLE SCHEDULE
CEILING SUPPLYS1
SERVICETAG CFM RANGE NECK DIA.(IN)
SIZE FACE(IN)
MAX.PD
(IN. WG)MAX. NOISE
(NC) PATTERN BASIS OF DESIGNMFR/MODEL REMARKS
R1
- HART & COOLEY/ARS SERIES
AS SHOWN REFER TO NOTES 1 & 2AS SHOWN - - -
-AS SHOWN - - -
-AS SHOWN - - -
-AS SHOWN - - -
CEILING RETURN HART & COOLEY/RH45AS SHOWN REFER TO NOTE 2
WALL SUPPLYS2
R2 WALL RETURN HART & COOLEY/RH45AS SHOWN REFER TO NOTE 2
HART & COOLEY/VHD SERIES
AS SHOWN REFER TO NOTES 1 & 2
NOTES:1. PROVIDE WITH MULTI-SHUTTER VALVE.2. PROVIDE STEEL MATERIAL IN STAIN WHITE.
TAG LOCATION/SERVICE CFM
NOTES:1. PROVIDE WITH MULTI-SHUTTER VALVE.2. PROVIDE STEEL MATERIAL IN STAIN WHITE.
LOUVER SCHEDULE
L1 MECHANICAL ROOM
WIDTH
24
RQD. FREEAREA (SQ.
FEET)
200 0.40
APPROXIMATE GROSS (NOM.) SIZE (IN.)
12
HEIGHT
AS REQ'D
DEPTHMAX P.D.IN W.G.
0.05
BIRDSCREEN
ALUM
BASIS OFDESIGN
MFR/ MODELREMARKS
GREENHECKESD-635 REFER TO NOTE 1
L2 MECHANICAL ROOM 30288 0.57 18 AS REQ'D 0.05 ALUM GREENHECKESD-635 -
L3 MECHANICAL ROOM AS REQ'D 0.05 ALUM GREENHECKESD-635 REFER TO NOTE 1
- - -- - - - - - - -
12115 0.23 12
REMARKSTAG
WALL MOUNTED/INDICATED ON
CONTRACT DWGS
ELECTRICALDATA
LOCATION /SERVICE
24V AC CLASS2 POWERSUPPLY
REFER TONOTE 1
BASIS OF DESIGNMFR/MODEL
CO2 MONITOR-JOHNSON
CONTROLS CD-WSERIES
CO2
CO2 SENSOR SCHEDULE
NOTES:1. PROVIDE w/RELAY MODULE TO OUTSIDE AIR VENTILATION
DAMPER. MOUNTING HEIGHT AFF SAME AS THERMOSTAT.
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
SCH
EDU
LES,
Thur
sday
, Mar
ch 3
, 201
6,3:
26 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
M801
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
SCHEDULES
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
MAIN DUCT/ COLLAR ANDCOLLAR/FLEXIBLE DUCTCONNECTIONS SEALEDWITH MASTIC
MAX SAG 1/2" PER FOOT (41.7mmPER m) OF SUPPORT SPACING
CLOSER MAXIMUM INTERVALSMAY BE SPECIFIED AS ACONDITION OF U.L. LISTING,PARTICULARLY IN FIRE RATEDFLOOR-CEILING ASSEMBLIES.
DUCT SHOULD EXTENDSTRAIGHT FOR ONEDUCT DIAMETER FROM ACONNECTION BEFOREBENDING.
3'-0" MAXIMUMMAIN AIR DUCT
SUPPLY DUCT
VOLUME DAMPER
SPINCOLLAR
CEILING DIFFUSER
CEILING
FLEX DUCT MAX. 5'-0"
DRAW BAND WITHSILICONE SEALER
DRAW BANDWITH SILICONESEALER
SIDE OF DUCT CONNECTION
CEILING DIFFUSERBOTTOM OF DUCT CONNECTION
SUPPLY DUCT
SPIN COLLAR
FLEX DUCT WHERE REQUIRED(MAX. LENGTH 5'-0")
FLEX DUCT SIZESSHALL MATCHDIFFUSER NECK SIZES
ROUND TO SQUAREADAPTERAS REQUIRED
CEILING
VOLUME DAMPER
DRAW BAND WITHSILICONE SEALER
OPPOSED BLADEDAMPER
OPPOSEDBLADE DAMPER
FLEX DUCT SIZESSHALL MATCHDIFFUSER NECK SIZES
PLAN OR SIDE VIEW
SHOWN SHALL APPLY.NOTE: UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES
DUCT TRANSITION
PLAN OR SIDE VIEW
ACCESS PANEL
EQUIPM
ENT 30° MAX20° MAX
20° MAX 30° MAX
15° MAX.
15° MAX.
FLOOR
FLOOR/CEILINGTRUSS SPACE
SUPPLY DUCT SIZED SAME ASCOIL CASING DISCHARGE SIZE
DX COOLINGCASED COIL
FURNACE
FLEXIBLE CONNECTION
COMBUSTION AIR &VENT PIPING ROUTE UPTHROUGH SPACE,REFER TO PLAN
PRIMARY/AUXILIARYCONDENSATE DRAINS
LINED RETURN PLENUM
FILTER RACK
SEPARATE COIL &FURNACE CONDENSATETO 1" AIR GAP ATFLOOR DRAIN
1/2" NEOPRENE ISOLATIONPAD
ROUTE RETURN DUCT TORETURN GRILLE PERLOCATION SHOWN ONPLAN
FLEXCONNECTION
REQUIRED ASINDICATED ON PLANS
ANCHORSTRUT TOBASE
STRUT CLAMPWITH PADDING
REFRIGERANTPIPING
GRADE
RUBBER SUPPORTBASE w/GALV.CHANNEL
NOTES:
A. MIFAB C SERIES ROOF SUPPORTS, 600 LB/FT LOAD LIMIT
PIPE SIZE PIPE MATERIAL
REFRIGERANT PIPINGSTEEL1/4" TO 9/4"
4 FT. MAX.
SUPPORT SPACING SCHEDULE
4"MIN.
(TYPICAL)12"C.C. MAX.
2"2"
COATED SURFACE OFINSULATION EXPOSED TO AIRSTREAM.
ALL ENDS OF LINER TO BECOATED WITH ADHESIVE(MIRACLE PF96). ENDS OF LINERSHALL BE BUTTED FIRMLYTOGETHER.
TOP AND BOTTOM SECTIONS OFLINER SHALL OVERLAP THESIDES.
NOTES:
GALVANIZED SHEET METALDUCT
1" THICK ACOUSTIC DUCT LINER,LINER TO BE ADHERED TODUCT WITH 100% ADHESIVE(MIRACLE PF96)
NOT MORE THAN 2" FROMEDGE OF DUCT LINER
GRIP NAILS SHALL BE INSTALLED BY "GRIP-NAIL AIR HAMMER" OR BY AUTOMATICFASTENER EQUIPMENT.
METAL FASTENERS:OMARK INSUL-PINS. DURA DYNEFASTENERS OR GRIP NAILS.
1
2
3
4
5
6
1
2
6
3 4 5 2 1
HW
W H
CRD (EASY ACCESS TYPE)RECTANGLE, OPEN POSITION
CRD (EASY ACCESS TYPE)RECTANGLE, CLOSED POSITION
UL LISTED LINK
BLADES 22 GA.GALV. STEEL
CERAMICFIBER WITHFIBERGLASSCOVER
STEEL DUCTDROP (BYOTHERS)
FIRSTDIMENSION
FIRSTDIMENSION
EXHAUST INTAKE(BEHIND PLATE)
PVC PIPE SIZED AS REQUIRED
COUPLING AS REQUIRED
PVC PIPE SIZED AS REQUIRED
WITH PVC PIPE
2 3/8"
12" MINIMUM(RECOMMENDED)
DO NOT BLOCK AIRINTAKE
DO NOT BLOCK AIR INTAKE
DO NOT BLOCK EXHAUST
EXTERIOR WALLCOMPOSITION MAYVARY WITH SPECIFICBUILDING
FIRE DAMPER
"S" TYPE SLIPFITTING
WALL SLEEVE
DUCTWORK
SLEEVE RETAININGANGLE
FIRE PARTITION
DUCT
SHEET METAL SAFING ORANGLES. ANGLES REQUIREDWHEN SAFING USED FOR DUCTSUPPORT AT FLOORS
DUCT LINING WHERE SHOWNON PLANS OR SPECIFIED
PACK SPACE WITHFIBROUS MATERIAL ANDSEAL BOTH SIDES.
NOTE:WHERE FIRE, SMOKE, OR COMBINATIONFIRE/SMOKE DAMPERS ARE REQUIRED,INSTALLATION SHALL BE PER DAMPERMANUFACTURER'S REQUIREMENTS.
SILICONE SEALANT
BOLT SAFING / ANGLES TOSTRUCTURE
6"
MIN 6" HIGHCONCRETE SLAB
4" CRUSHEDSTONE BASE
DRYER(TYPICAL)
PROVIDE 3/4"PLYWOOD BOXFRAME TO MATCHDIMENSIONS OFDRYER COMBUSTIONAIR INLET. REFER TODETAIL 13 THISDRAWING.
4"∅
12"
12"
16"
6"
26"
1"CHASE WALL
CAULK AND SEALAIR TIGHT
3/4" PLYWOOD BOX
PROVIDE COMPRESSIBLEWEATHER STRIPPING
NOTE:COORDINATE WITHDRYER LOUVERDIMENSIONS. DIMENSIONSBASED ON MACGRAYDRYER
30
"
FLOOR
FLEX CONNECTOR
CEILING
CLOTHESDRYER
4"∅ DV
SEAL OPENINGS AIR TIGHT
OUTSIDE AIR PLENUM
NOT TO SCALE2 TYPICAL FLEX DUCT DETAIL
NOT TO SCALE1 TYPICAL DIFFUSER CONNECTION DETAIL
NOT TO SCALE3 TYPICAL DUCT TRANSITION DETAIL
NOT TO SCALE7 FURNACE DETAIL
NOT TO SCALE5 PIPING SUPPORT DETAIL
NOT TO SCALE8 ACOUSTICAL LINING INSTALLATION DETAIL
NOT TO SCALE4 TYPICAL CEILING RADIATION DAMPER DETAIL
NOT TO SCALE6 FLUSH MOUNT VENT TERMINATION DETAIL
NOT TO SCALE11 FIRE DAMPER DETAIL
NOT TO SCALE12 SLAB/WALL DUCT PENETRATION DETAIL
NOT TO SCALE14 CONCRETE PAD SUPPORT DETAIL
NOT TO SCALE13 DRYER INTAKE DETAIL
NOT TO SCALE9 LAUNDRY RM. SECTION DETAIL
NOT TO SCALE10 DRYER DETAIL
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
DET
AILS
,Thu
rsda
y, M
arch
3, 2
016,
3:26
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
M901
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
DETAILS
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
"A"
2" AIR GAP
CLEANOUT PLUG(TYP)
TO SUITCONDITIONS
DRIP PAN
PAN WATERLEVEL
IPS. TO COPPERADAPTER. "B"
FLOOR LINE180° BEND
NOTES:
'A' = PLENUM STATIC PRESSURE AT DESIGN OPERATING CONDITIONS PLUS 1 1/2".
'B'= PIPE SIZE SHALL MATCH DRAIN PAN CONNECTIONBCT SHALL NOT BE LESS THAN 1 1/2".
"B"
INCH MINIMUM0.25xW OR 4
W
BALANCINGWHERE REQUIRED FOR AIRMANUAL DAMPER, PROVIDE
FLOW
AIR
FLOW
AIR
NOT TO SCALE1 CONDENSATE DRAIN PIPING DETAIL
NOT TO SCALE2 TYPICAL MAIN DUCT TAKE-OFF DETAIL
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
DET
AILS
,Thu
rsda
y, M
arch
3, 2
016,
3:26
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
M902
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
DETAILS
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
P000
P101
P900
NOTES, SYMBOLS & ABBREVIATIONS
FIRST FLOOR PLAN
RISER DIAGRAMS & SCHEDULES
SANITARY PIPING
PLUMBING EQUIPMENT
COLD WATER PIPING
PIPING DROP / ELBOW DOWN
PIPING RISE / VERTICAL LINE /ELBOW UP
HOT WATER PIPING
VENT PIPING ABOVE CEILING
GAS PIPINGG
ARROW INDICATES DIRECTIONOF FLOW
PITCH PIPE DOWN IN DIRECTION OFARROW
WCO WALL CLEANOUT
FLOOR CLEANOUT
UNDERGROUND SANITARY PIPING
BOTTOM PIPE CONNECTION
FCO
DRAIN & P-TRAP
METERM
XX
CAP
UNION
VALVE IN VERTICAL
CHECK VALVE
VALVEOR
BALL / GATE VALVE
HOSE BIBBHB
SANITARY VERTICAL STACKDESIGNATION (REFER TOCOMPOSITE BUILDING PLANSAND RISER DIAGRAMS FORNUMBERING)
DOMESTIC WATER VERTICALSTACK DESIGNATION (REFER TOCOMPOSITE BUILDING PLANSAND RISER DIAGRAMS FORNUMBERING)
KEY NOTE DESIGNATION
VACUUM BREAKERV
#S
#W
GENERAL PLUMBING NOTESPLUMBING NOTESPLUMBING ABBREVIATIONS
PLUMBING DRAWING LIST
PLUMBING SYMBOLS
A AMPERESAC AIR CONDITIONINGAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITALUM ALUMINUMARCH ARCHITECT
BP BOOSTER PUMPBT BATH TUB
C CENTER LINEøC DEGREES CELSIUSCB CAST IRON BOOTCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE
CONNECTIONCFM CUBIC FEET PER MINUTECLG CEILINGCO CLEANOUTCOND CONDENSATECONN CONNECTCONT CONTINUATIONCP CIRCULATION PUMPCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CHECK VALVECW COLD WATER
D DROPDF DRINKING FOUNTAINDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDR DRAINDTL DETAILDWG DRAWINGDW DISH WASHER
EL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALESP ELEVATOR SUMP PUMPET EXPANSION TANKEWC ELECTRIC WATER COOLEREWT ENTERING WATER TEMPERATUREEXP EXPANSION
F FILTERºF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFF FINISHED FLOORFL FLOORFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOOR SINKFT FEET
G GASGAL GALLONGPH GALLONS PER HOURGPM GALLONS PER MINUTEGWH GAS WATER HEATER
HB HOSE BIBBHD HEADHP HORSE POWERHR HOURHT HEIGHTHW HOT WATERHWR HOT WATER RECIRCULATION
IN INCH OR INCHES
JC JANITOR'S CLOSETJS JANITOR'S SINK
KS KITCHEN SINKL LENGTHLAV LAVATORYLBS POUNDS
MER MECHANICAL EQUIPMENT ROOMMAX MAXIMUMMHP MOTOR HORSEPOWERMIN MINIMUMMR MOP RECEPTORMTD MOUNTED
NFWH NON-FREEZE WALL HYDRANTNIC NOT IN CONTRACTNO NORMALLY OPENNo NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE
OS&Y OUTSIDE SCREW & YOKE
P PUMPPD PUMP DISCHARGEPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE INCH ABSOLUTEPSIG POUNDS PER SQUARE INCH GAUGE
R RISERD ROOF DRAINRH RELATIVE HUMIDITYRLA RUNNING LOAD AMPSRM ROOMRPM REVOLUTIONS PER MINUTERPZ REDUCING PRESSURE ZONE BACKFLOW
PREVENTER
SA SHOCK ABSORBERSAN SANITARYSD SMOKE DETECTORSF SUPPLY FANSH SHOWERSP STATIC PRESSURESPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEAL
TD TRENCH DRAINTEMP TEMPERATURETYP TYPICAL
UNO UNLESS OTHERWISE NOTEDUR URINAL
V VENTVTR VENT THROUGH ROOF
W WASTEW/ WITHWC WATER CLOSETWCA WATER CLOSET ACCESSIBLEWCO WALL CLEAN OUTWFU WATER FIXTURE UNITW/O WITHOUTWH WATER HEATERWHA WATER HAMMER ARRESTERWMB WASHING MACHINE BOXWPD WATER PRESSURE DROP
1. ALL EQUIPMENT AND MATERIALS USED AND WORK PERFORMED SHALL BE IN ACCORDANCE WITHRULES AND REGULATIONS LISTED IN "CODE DATA" ON DRAWING CS-1 IN ADDITION TO THEAUTHORITY HAVING JURISDICTION.
2. PROVIDE ALL WORK AND MATERIALS AS REQUIRED IN THE SPECIFICATIONS AND ON THEDRAWINGS INCLUDING THE FOLLOWING:
A. DOMESTIC WATERB. SANITARY SEWERC. NATURAL GASD. CONDENSATE
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY LICENSES ANDCERTIFICATIONS.
4. AT THE COMPLETION OF WORK, REMOVE ALL DEBRIS AND CLEAN STAINS CAUSED BYTHIS WORK.
5. ALL ABOVE GRADE PIPING SHALL BE PROPERLY SUPPORTED FROM THE BUILDINGSTRUCTURE AND SHALL NOT REST ON THE FINISHED CEILING.
6. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONSAND IN ACCORDANCE WITH THE REQUIREMENTS OF THE ELECTRICAL DRAWINGS.
7. WATER HEATER TEMPERATURE/PRESSURE RELIEF VALVE SHALL BE PIPED TO FLOORDRAIN IN ACCORDANCE WITH CODE REQUIREMENTS.
8. WATER SERVICE PIPING BELOW GRADE SHALL BE DUCTILE IRON WITH MECHANICAL JOINTFITTINGS.
9. WATER SERVICE PIPE THROUGH THE WALL SHALL BE PROTECTED WITH SLEEVEACCORDING TO CODE.
10. DOMESTIC WATER DISTRIBUTION PIPING SHALL BE SCHEDULE 40 CPVC WITH SOCKETFITTINGS AND SOLVENT CEMENTED JOINTS.
11. ALL HOT AND COLD WATER BRANCHES SHALL BE A MINIMUM OF 3/4” UNLESS OTHERWISENOTED.
12. PROVIDE SHUTOFF VALVES AT EACH FIXTURE LOCATION ACCORDING TO CODEREQUIREMENTS.
13. WATER PIPING IN THE ATTIC OR EXTERIOR WALLS SHALL BE PIPED ON THE INTERIOR SIDEOF THE INSULATION.
14. ABOVE GROUND SANITARY AND VENT PIPING AND FITTINGS SHALL BE SOLID WALLSCHEDULE 40 PVC WITH PVC SOCKET FITTINGS AND SOLVENT CEMENTED JOINTS.
15. SANITARY LINES SHALL BE INSTALLED WITH A MINIMUM SLOPE OF 1/8” PER FOOT FOR 4"AND LARGER PIPES, 1/4" PER FOOT FOR 3" AND SMALLER PIPES.
16. ALL VENTS THROUGH ROOF SHALL BE PROVIDED WITH 3" PIPE VENT EXTENSIONSTHROUGH THE ROOF IF FROST CLOSURE IN LIKELY OR WHERE REQUIRED BY LOCAL CODE.
17. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE INTENT OF THE CODEREQUIREMENTS. PIPING SHALL BE ROUTED UP, DOWN AND OFFSET AS REQUIRED TO SUIT FIELDCONDITIONS. DIELECTRIC COUPLINGS SHALL BE USED WHERE DISSIMILAR METALS ARE JOINED.
18. PIPING HANGERS SHALL BE SPACED SO AS TO PREVENT SAG AND PERMIT PROPERDRAINAGE AND SHALL NOT BE SPACED MORE THAN EIGHT (8) FEET APART UNLESS A GREATERSPACE IS DEFINITELY INDICATED ON THE DRAWINGS. A HANGER SHALL BE PLACED WITHIN ONE(1) FOOT OF EACH HORIZONTAL ELBOW. HANGERS SHALL BE SIZED TO FIT OVER INSULATIONAND BE PROVIDED WITH AN INSULATION SHIELD.
19. CONDENSATE DRAIN PIPING AND FITTINGS SHALL BE PVC.
20. INDIRECT WASTE PIPING SHALL BE COPPER.
21. THE INSTALLATION OF ALL INSULATION SHALL BE PERFORMED BY AN EXPERIENCEDCRAFTSMAN IN A NEAT WORKMANLIKE MANNER AND SHALL BE IN ACCORDANCE WITHMANUFACTURER'S PUBLISHED RECOMMENDATIONS FOR SERVICE INTENDED.
22. ALL MATERIALS OF INSULATION SHALL BE OF THE TYPE AND QUALITY AS MANUFACTUREDBY ARMSTRONG, CERTAIN TEED , OWENS-CORNING OR SCHULLER. ALL MATERIAL ANDEQUIPMENT SPECIFIED TO BE INSULATED SHALL BE THOROUGHLY TESTED AND APPROVEDPRIOR TO APPLYING THE INSULATION.
23. DOMESTIC WATER PIPING AND FITTINGS SHALL BE INSULATED PER THE SPECIFICATIONS.
24. CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH 1” THICK ARMSTRONG “ARMAFLEX”OR EQUAL. EXTERIOR INSULATION SHALL BE COATED WITH ULTRAVIOLET RESISTANT MATERIALIN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
25. POTABLE WATER PIPING SHALL BE DISINFECTED PRIOR TO USE PER ANSI/AWWASTANDARD C651-92 OR LOCAL REQUIREMENTS. THE PIPING SHALL BE FILLED WITH A WATER-CHLORINE SOLUTION CONTAINING AT LEAST 50 PARTS PER MILLION OF CHLORINE AND SHALLBE VALVED OFF FOR 24 HOURS OR FILLED WITH A WATER -CHLORINE SOLUTION CONTAINING ATLEAST200 PARTS PER MILLION OF CHLORINE AND ALLOWED TO STAND FOR AT LEAST 3HOURS. FOLLOWING THE ALLOWED STANDING TIME , THE SYSTEM SHALL BE FLUSHED WITHPOTABLE WATER UNTIL NO CHLORINE REMAINS IN THE SYSTEM.
26. PROVIDE EACH FLOOR DRAIN WITH A TRAP PRIMER SYSTEM SIMILAR TO J.R. SMITH MFG.Co. FIGURE NUMBER 2689 PRIME TEAM OR IF ACCEPTABLE BY THE LOCAL AUTHORITIES,PROVIDE A TRAP SEAL GUARD EQUAL TO “TRAP GUARD” AS MANUFACTURED BY PROSETSYSTEMS.
27. PROVIDE SHOCK ABSORBERS FOR WASHING MACHINE.
28. PROVIDE TEMPERING VALVE ON TWO HANDLE FAUCET.
29. PROVIDE AMTROL #ST-5 EXPANSION TANK ON WATER HEATER.
30. DOMESTIC WATER SYSTEM TO BE INSULATED;
A. DOMESTIC COLD WATER SUPPLY: 1. Man-Made Mineral Fiber Insulation:
Pipe Size Range: ½” to 4 inchThickness: 1 inch
2. Cellular Glass Insulation:Pipe Size Range: ½” to 4 inch
Thickness: 1 inch3. Expanded Polystyrene Insulation:
Pipe Size Range: ½” to 4 inchThickness: 1 inch
B. DOMESTIC HOT WATER SUPPLY AND RECIRCULATION SYSTEM: 1. Man-Made Mineral Fiber Insulation:
Pipe Size Range: ½” to 4 inchThickness: 1 inch
2. Cellular Glass Insulation:Pipe Size Range: ½” to 4 inch
Thickness: 1 inch3. Expanded Polystyrene Insulation:
Pipe Size Range: ½” to 4 inchThickness: 1 inch
31. PROVIDE INSULATION ON THE ENTIRE SYSTEM INCLUDING FITTINGS, VALVES, UNIONS,FLANGES, STRAINERS, FLEXIBLE CONNECTIONS, PUMP BODIES ETC.A. PROVIDE FACTORY-APPLIED VAPOR RETARDER JACKETS. SECURE FACTORY-
APPLIED JACKETS WITH PRESSURE SENSITIVE ADHESIVE, SELF-SEALING LONGITUDINALLAPS AND BUTT STRIPS. SECURE FIELD-APPLIED JACKETS WITH OUTWARD CLINCHEXPANDING STAPLES AND SEAL STAPLE PENETRATIONS WITH VAPOR RETARDERADHESIVE OR PVC FITTING COVERS.
B. INSULATE FITTINGS, JOINTS, AND VALVES WITH MOLDED INSULATION OF LIKEMATERIAL AND THICKNESS AS ADJACENT PIPE. FINISH WITH GLASS CLOTH AND VAPORRETARDER ADHESIVE OR PVC FITTING COVERS.
32. ALL COMPONENTS OF THE POTABLE WATER SYSTEM SHALL COMPLY WITH THEENVIRONMENTAL PROTECTION AGENCY'S "REDUCTION OF LEAD IN DRINKING WATER ACT."
1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HASTOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITECONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FORTHE COMPLETE INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER INACCORDANCE WITH THE BEST PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALLAUTHORITIES HAVING JURISDICTION.
2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THEUNDERSTANDING THAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OFCONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS CONTAINED IN THECONTRACT DOCUMENTS. IT IS THE INTENT OF THE CONTRACT DRAWINGS ANDSPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION ANDIN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES AND REGULATIONS.MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTED NECESSARY FOR THEPROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS SHALL BE INCLUDED INTHE WORK AND IN THE PROPOSAL THE SAME AS SPECIFIED OR SHOWN ON THE CONTRACTDRAWINGS. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMEDNECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASON THEREFORE SHALL BESUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUTPRIOR APPROVAL OF THE ENGINEER.
3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT /ENGINEER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK.
4. THE CONTRACT DOCUMENTS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES ANDRELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TOBE PROVIDED. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHICREPRESENTATION OF CONTRACT REQUIREMENTS TO BEST AVAILABLE STANDARDS AT THESCALE INDICATED.
5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED
AND COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACTLOCATIONS USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONEDDRAWINGS COORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTINGSUCH INTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGSAND DISTRIBUTE SAME AS REQUIRED.
6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULEWORK IN ACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL THE WORK CANBE INSTALLED WITHOUT DELAYING THE PROJECT.
7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGSSHALL BE FORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALLSUBSEQUENTLY IN SUCCESSION DELINEATE HIS RESPECTIVE WORK ON THESE COORDINATIONDRAWINGS. WHEN ALL WORK HAS BEEN PROPERLY SHOWN ON THE COORDINATIONDRAWINGS, AND ALL CONTRACTORS AGREE THAT THEIR RESPECTIVE WORK CAN BEINSTALLED AND WILL PROPERLY FIT TOGETHER, THEY SHALL SO ACKNOWLEDGE BYENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TO COMPLETION OF ABOVECOORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED AND REPLACED ATCONTRACTOR'S EXPENSE.
8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.
9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'SWRITTEN INSTRUCTIONS.
10. SCHEDULE ALL SHUTDOWNS THAT EFFECT UTILITIES AND PORTIONS OF THE BUILDINGTHAT MUST REMAIN IN OPERATION WITH THE OWNER.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTIONOF MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH ORDEFECT.
12. PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT AND TRANSFER TO POINT OFINSTALLATION OWNER FURNISHED ITEMS.
13. WHERE CONDUIT, CABLES, DUCTWORK OR PIPING PASSES THROUGH FIRE RATEDFLOORS AND WALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOPMATERIAL THAT IS UL LISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIREDEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLEDIN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE ULLISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS,BEAM PENETRATIONS AND CORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALLSUBMIT SIZE AND LOCATION TO THE STRUCTURAL ENGINEER FOR REVIEW AND APPROVAL.
15. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THISSCHEDULE SHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FORTHIS PROJECT, INCLUDING ANY ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THEREQUIREMENTS OF DIVISION 1 OF THE SPECIFICATIONS. PROVIDE DRAWINGS OF ALLSPRINKLER PIPING, HEADS, VALVES, EQUIPMENT, MATERIALS, SIGNS FOR EACH FIREPROTECTION SYSTEM TO BE INSTALLED. ANY WORK INSTALLED OR EQUIPMENT PURCHASEDPRIOR TO RECEIPT OF ENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGESSHALL BE REPLACED AT CONTRACTOR EXPENSE.
16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELDINSTALLATION DRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTIONOF ALL ITEMS PROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOPDRAWINGS. NO SUBMISSION SHALL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THECONTRACTOR. THE CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.
17. PROVIDE AS-BUILT DOCUMENTS AND OPERATING / MAINTENANCE MANUALS AS SPECIFIEDIN DIVISION 1 OF THE SPECIFICATIONS.
18. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUNDOR VIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER.OBJECTIONABLE SOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVEDMANNER BY THE CONTRACTOR AT HIS EXPENSE.
19. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OFCONCEALED EQUIPMENT, VALVES AND CONTROLS, ETC., AND COORDINATE THEIRDELIVERY WITH THE INSTALLING TRADE.
20. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANYAND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESSTHAN ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANYDEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD SHALL BE REMEDIED ANDANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST.
21. NOTIFY ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK AND DATEOF BOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE A MINIMUM OF ONEWEEK PRIOR TO COMPLETION DATE TO ENABLE ENGINEER SCHEDULING OF PRELIMINARYPUNCHLIST INSPECTION PRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALLSIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK, INDICATING THE CONTRACTORIS READY FOR THE ENGINEER TO PERFORM THE FINAL PUNCHLIST INSPECTION.
22. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER'SPUNCHLIST, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OFCOMPLETION CERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC. HAVE BEEN SUBMITTED.
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
NO
TES,
SYM
BOLS
& A
BBR
EVIA
TIO
NS,
Thur
sday
, Mar
ch 3
, 201
6,3:
28 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
P000
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
NOTES, SYMBOLS &ABBREVIATIONS
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
ELEC./IT
109
CL.
120
MECH.
106
WW
WW
WW
DD
DD
DD
DW
R
RFCO
LT
WMB
WMB
WMB
WMB
WMB
WMB
MR
EWC
LAV LAV
LAV LAV
WC WCA
WCA
UR
SK
SK
FD2FD2
FD1
FD1
FD1
FD2
OFFICE
116
MGMT. OFFICE
115
VESTIBULE
101
PORCH
01
EXERCISE
102
COMMON CORRIDOR
112
CONIFER CORRIDOR
110
MAINTENANCE
104
LAUNDRY
103
STORAGE
107
COMMUNITY ROOM
111PATIO
01
CONSULT
118
MECH.
117
PORCH
01
KITCHENETTE
121
WOMEN
114
MEN
113
SPRINKLER
105
M
TD
FCO
NFWH
UTILITY NATURAL GAS METER.SIZE PER NATURAL GAS RISERDIAGRAM. COORDINATELOCATION OF METER WITHUTILITY COMPANY ANDELECTRIC METER.
NATURAL GAS SERVICE
NFWH
NFWH
FF = 00.00'
4" SANITARY
PROVIDE ADDITIONAL REDUCEDPRESSURE PRINCIPLE BACKFLOWPREVENTER FOR SITE IRRIGATION.SEE RISER DIAGRAM FORCONNECTION POINT.
WATER HEATER WH-1
CONCENTRIC VENT
DOMESTIC WATER UTILITY METER.
REDUCED PRESSURE PRINCIPLEBACKFLOW PREVENTER
DOMESTIC WATER SERVICE
LINT TRAP
N
SCALE: 1/4" = 1'-0"1 FIRST FLOOR PLAN
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
FIR
ST F
LOO
R P
LAN
,Thu
rsda
y, M
arch
3, 2
016,
3:28
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
P101
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
FIRST FLOOR PLAN
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
FCOTD
3"
1-1/2"
FD1
2"
1ST FLOOR
ROOF
FCO FD2
2"
FD2
4"
CO
WMB
LINTTRAP
WMB WMB WMB WMB WMB
1-1/2"
3"
MR
3"
EWC
1-1/2"
2"
LAVLAV
1-1/2"
2"
1-1/4"
2"
LAV LAV
1-1/2"
1-1/4"
2"
2"
SK
UR
WC FD1
2"
FD1
2"
WCAWCA
SK
FD2
2"
CO
3" 3"
WH-1
1"
ROOF
M
2" INCOMINGDOMESTICWATER SERVICE
1ST FLOOR 2"
1-1/2"
1-1/2" REDUCED PRESSUREZONE BACKFLOWPREVENTER, SIMILAR TOZURN WILKINS #375-S
WATERMETER
1-1/2" SUPPLY TOIRRIGATION SYSTEM. CAPFOR CONTINUATION BYIRRIGATION CONTRACTOR.
MREWC
3/4"
3/4"
3/4" LAV LAV WC WCA LAV LAV UR WCA 3/4" SK 3/4" SK
NFWH NFWH NFWH
WMB WMB WMB WMB WMB WMB
3/4" 3/4"
FLOOR
M
GRADE
ROOF
GAS METER
XXX"
XXX"XXX CFH
SHUTOFF VALVEEXPOSED INSPRINKLER ROOM
XXX CFH
XXX"XXX CFH
FURNACE
XXXCFH
XXX"XXX CFH
WATERHEATER XX" (TYP.)
24 CFH
XX"144 CFH
XX"24 CFH
3/4"120 CFH
XXX CFHFURNACE
XXX"XXX CFH
24 CFHDRYER
XXX"XXX CFH
XXX"XXX CFH
XXX"XXX CFH
XXX"XXX CFH
24 CFHDRYER
24 CFHDRYER
24 CFHDRYER
24 CFHDRYER
24 CFHDRYER
PLUMBING FIXTURE SCHEDULE & SPECIFICATIONS
WATER HEATER SCHEDULE
COMMUNITYROOM SINK
---1 1/4"1/2"1/2"
---
---1 1/2"1/2"1/2"
1/2" 1/2"
1/2" 1/2" 2" ---
3" ---
---3/4" -
FIXTURE NAMETAGVENT
MANUFACTURERDESCRIPTION MODELNUMBER
TRIM, FITTINGS, ACCESSORIESCONNECTION SIZES
CW SANHWREMARKS
-
- - ASNOTED
WMB WASHINGMACHINE BOX
FD1 FLOOR DRAIN
MR MOP RECEPTOR
LAV WALL HUNGLAVATORY
NFWH
SK
NON-FREEZEWALLHYDRANT
20-3/8" X 17-3/8" OVAL DROP-INLAVATORY, WHITE VITREOUSCHINA, FRONT OVERFLOW, ADACOMPLIANT, THREE FAUCETHOLES ON 4" CENTERS
0476.028AMERICANSTANDARD
PROVIDE W/ MOEN CHATEAU FAUCET MODEL#L4601 LAVATORY FAUCET W/ GRID DRAIN ANDSINGLE HANDLE OPERATION. PROVIDE PVC P-TRAP AND CHROME PLATED BRASS SUPPLIES/STOPS. PROVIDE W/ O.5 GPM AERATOR.
PROVIDE TRUBROINSULATION ON P-TRAP ANDEXPOSED SUPPLIES/STOPS.
STERLING 11403-325" x 22" x 6" SINGLE BOWLSINK, #20 GAUGE STAINLESSSTEEL, (3) FAUCET HOLES ON4" CENTERS, ADA COMPLIANT
PROVIDE W/ MOEN FAUCET MODEL # 7425KITCHENFAUCET W/ SINGLE LEVER, LESS SPRAY, 1.5 GPMAERATOR MODEL #116711. PROVIDE WITH BASKETSTRAINER, PVC P-TRAP AND SUPPLIES/STOPS.
MUSTEE 63M24" x 24" x 10" MOLDEDDURASTONE FIBERGLASSCOMPOSITE MOP RECEPTORW/ INTEGRAL MOLDED DRAINBODY.
PROVIDE W/ MOEN SERVICE FAUCET MODEL #8124
GALVANIZED STEEL WASHINGMACHINE OUTLET BOX,SINGLE LEVER HANDLE, 2"DRAIN
GUY GRAY WB200
WOODFORD 17CPFREEZELESS ANTI-SIPHON WALLFAUCET WITH WHEEL HANDLE
CAST IRON BODY FLOORDRAIN WITH ADJUSTABLECOLLAR AND POLISHEDNICKEL BRONZE, LIGHT-DUTYSTRAINER.
ZURN Z415B-P
ELKAY 1/2" - 1 1/4" ---
PROVIDE WATER HAMMER ARRESTORS ON HOTAND COLD WATER SUPPLIES TO CLOTHES WASHERS
1/2" --- 3" --- PROVIDE TRIP LEVER ONWIDE SIDE OF THE ROOM
PROVIDE WITH OPEN FRONT TOILET SEAT LESSCOVER, BEMIS MODEL #1955SSCT WITH STAINLESSSTEEL HINGES. PROVIDE WITH CHORME PLATEDBRASS ANGLE STOP VALVE.
WCA ADA WATERCLOSET
WHITE VITREOUS CHINA, HIGHEFFICIENCY, 1.28 GPF,ELONGATED BOWL, 16-1/2" RIMHEIGHT, TANK TYPE
COLONY221AA.104
PROVIDE EACH FLOOR DRAIN WITH ANAUTOMATIC TRAP PRIMER AND TRAP PRIMERCONNECTION
COORDINATE WITH ACTUALWALL THICKNESS.
-
TD TRENCH DRAIN ZURN ---- - 3"Z886-DGC6-1/4" WIDE REVEAL, HDPETRENCH DRAIN SYSTEM WITHCLASS C DUCTILE IRON GRATE.
SYSTEMTAG STORAGE CAPACITY(GAL.)
TYPE RECOVERY AT 100ºFTEMP RISE (GPM)
INPUT(AS NOTED)
ELECTRICAL
V PREMARKSMANUFACTURER AND
MODEL NUMBER
60 MBH
LOCATION
WH-1 DOMESTIC HOTWATER
MECHANICALCLOS.
NATURALGAS
48 58 120 1 BRADFORD WHITELG2PDV50H603N
VENT WATER HEATER THROUGH EXTERIORWALL WITH CONCENTRIC VENT TERMINAL KIT.
EWC ELECTRICWATERCOOLER
LRPB28KFULLY EXPOSED DUAL HEIGHTSTAINLESS STEEL FOUNTAINSWITH IN-THE-WALLREFRIGERATION SYSTEM ANDSTAINLESS STEEL GRILL.
REFRIGERATION SYSTEM SHALL BE CAPABLE OFPROVIDING 8.6 GPH OF 50 DEG F DRINKINGWATER AT 70 DEG F AMBIENT TEMPERATURE
SEE ARCHITECTURALELEVATION FOR MOUNTINGHEIGHT.
LT LINT TRAPCOATED INTERIOR, EXTERIORFABRICATED STEEL, NON-SKIDSECURED COVER W/ REMOVABLELIFT HANDLE, PERMANENTSTRAINING BAFFLE ANDSECONDARY LINT SCREEN.
ZURN Z1185 SIZE SHALL BE FOR A MAXIMUM OF 7 MACHINES. ---- - 3"
FD2 FLOOR DRAINCAST IRON BODY FLOORDRAIN WITH ADJUSTABLECOLLAR AND POLISHEDNICKEL BRONZE, LIGHT-DUTYSTRAINER, OVAL FUNNEL.
ZURN Z415B-P-OF PROVIDE EACH FLOOR DRAIN WITH ANAUTOMATIC TRAP PRIMER AND TRAP PRIMERCONNECTION AND OVAL FUNNEL
---- -2"
AMERICANSTANDARD
NOT TO SCALE1 SANITARY RISER DIAGRAM
NOT TO SCALE2 DOMESTIC WATER RISER DIAGRAM
NOT TO SCALE3 NATURAL GAS RISER DIAGRAM
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
RIS
ER D
IAG
RAM
S &
SCH
EDU
LES,
Thur
sday
, Mar
ch 3
, 201
6,5:
17 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
P900
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
RISER DIAGRAMS &SCHEDULES
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
E000
E101
E102
E801
ABBREVIATIONS & SYMBOLS
FIRST FLOOR POWER PLAN
FIRST FLOOR LIGHTING PLAN
SCHEDULES
A AMPERESACS AUTOMATIC CONTROL SYSTEMACT ACOUSTICAL CEILING TILEACU AIR CONDITIONING UNITAF AMPERE FRAMEAFCI ARC FAULT CURRENT INTERRUPTERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAIC AMPERES INTERRUPTING CAPACITYALUM ALUMINUMAMCS AUTOMATED MONITORING & CONTROL
SYSTEMAMP AMPERE, AMPACITYARCH ARCHITECTAT AMPERE TRIPATS AUTOMATIC TRANSFER SWITCHAWG AMERICAN WIRE GAUGE
C CONDUIT∘C DEGREES CELSIUSCAP CAPACITYCB CIRCUIT BREAKERCCP CENTRAL CONTROL PANELCCTV CLOSED CIRCUIT TELEVISIONCIRC. CIRCUITCKT CIRCUITCLG CEILINGCM CONTROL MODULECT CURRENT TRANSFORMERCUH CABINET UNIT HEATER
DC DIRECT CURRENTDDC DIRECT DIGITAL CONTROLDG DIESEL GENERATORDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDPDT DOUBLE POLE DOUBLE THROWDPSP DOUBLE POLE SINGLE THROWDS DISCONNECT SWITCHDWG DRAWING
E.C. ELECTRICAL CONTRACTORECB ENCLOSED CIRCUIT BREAKEREDH ELECTRIC DUCT HEATEREF EXHAUST FANEL ELEVATIONELEC ELECTRIC, ELECTRICALELEV ELEVATOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEP EXPLOSION PROOFEPO EMERGENCY POWER OFFEQ EQUALEUH ELECTRIC UNIT HEATEREWC ELECTRIC WATER COOLEREXH EXHAUST
ºF DEGREES FAHRENHEITFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFC FOOT CANDLE, FAULT CURRENTFCU FAN COIL UNITFD FIRE DAMPERFD/SD COMBINATION FIRE/SMOKE DAMPERFIXT FIXTUREFLA FULL LOAD AMPERESFLUOR FLUORESCENTFMC FLEXIBLE METAL CONDUITFT FEET
G GROUNDGAL GALLONGC GENERAL CONTRACTORGF GROUND FAULTGFI/GFCI GROUND FAULT CIRCUIT INTERRUPTERGND GROUNDGRS GALVANIZED RIGID STEELGWB GYPSUM WALL BOARD
HC HEATING COILHH HANDHOLEHLC HOUSE LIGHTING CONTRACTORHP HORSE POWERHPS HIGH PRESSURE SODIUMHR HOURHT HEIGHTHWY HIGHWAYHZ FREQUENCY (HERTZ)
I CURRENTIC INTERRUPTING CAPACITYIG ISOLATED GROUNDIMC INTERMEDIATE METAL CONDUITIN INCH OR INCHESINCA INCANDESCENTIT INFORMATION TECHNOLOGYJB JUNCTION BOX
K KILOKCM THOUSAND CIRCUIT MILLSKCMIL KILOCIRCULAR MILSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR
L LENGTHLBS POUNDSLCP LOCAL CONTROL PANELLFMC LIQUID-TIGHT FLEXIBLE METAL
CONDUITLIN .FT. LINEAR FEETLTG LIGHTINGLV LOW VOLTAGE
MC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCP MOTOR CIRCUIT PROTECTORMDP MAIN DISTRIBUTION PANELMER MECHANICAL EQUIPMENT ROOMMFS MAXIMUM FUSE SIZEMH MAN HOLEMHP MOTOR HORSEPOWERMIN MINIMUMMLO MAIN LUGS ONLYMTR MOTORMTD MOUNTEDMV MERCURY VAPORMX MECHANICAL ROOM EXHAUST
N NEUTRALNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATIONNF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNO NORMALLY OPENNo NUMBERNTS NOT TO SCALE
OPP OPPOSITE
P POLESPB PULL BOX, PUSH BUTTONPC PHOTOCELLPH PHASEPNL PANELPT POTENTIAL TRANSFORMERPWR POWER
RECEP RECEPTACLEREFL REFLECTORREFR REFRIGERANTRLA RUNNING LOAD AMPSRM ROOMRMC RIGID METAL CONDUITRMS ROOT MEAN SQUARERPM REVOLUTIONS PER MINUTE
SC SHORT CIRCUITSCCR SHORT CIRCUIT CURRENT RATINGSD SMOKE DETECTORSERV SERVICESF SUPPLY FANSMD SMOKE DAMPERSPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEELSW SWITCHSWBD SWITCH BOARDSWGR SWITCH GEARSYS SYSTEM
TBD TO BE DETERMINEDTC TIME CLOCKTCOM TELECOMMUNICATIONTEL TELEPHONETEMP TEMPERATURETVSS TRANSIENT VOLTAGE SURGE
SUPPRESSIONTYP TYPICAL
UC UNDER COUNTERUH UNIT HEATERUON UNLESS OTHERWISE NOTEDUV UNIT VENTILATOR
V VOLTSVA VOLT AMPEREVAC VACUUMVAV VARIABLE AIR VOLUME UNITVD VOLUME DAMPERVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVOL VOLUME
W WATTW/ WITHW/O WITHOUTWBT WET BULB TEMPERATUREWC WATER COLUMNWG WIRE GUARDWP WEATHER PROOF
XFMR TRANSFORMER
Z IMPEDENCE
JB JUNCTION BOX
K KILOKCM THOUSAND CIRCUIT MILLSKCMIL KILOCIRCULAR MILSKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR
L LENGTHLBS POUNDSLCP LOCAL CONTROL PANELLFMC LIQUID-TIGHT FLEXIBLE METAL
CONDUITLIN .FT. LINEAR FEETLTG LIGHTINGLV LOW VOLTAGE
MC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCP MOTOR CIRCUIT PROTECTORMDP MAIN DISTRIBUTION PANELMER MECHANICAL EQUIPMENT ROOMMFS MAXIMUM FUSE SIZEMH MAN HOLEMHP MOTOR HORSEPOWERMIN MINIMUMMLO MAIN LUGS ONLYMTR MOTORMTD MOUNTEDMV MERCURY VAPORMX MECHANICAL ROOM EXHAUST
N NEUTRALNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATIONNF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNO NORMALLY OPENNo NUMBERNTS NOT TO SCALE
OPP OPPOSITE
P POLESPB PULL BOX, PUSH BUTTONPC PHOTOCELLPH PHASEPNL PANELPT POTENTIAL TRANSFORMERPWR POWER
RECEP RECEPTACLEREFL REFLECTORREFR REFRIGERANTRLA RUNNING LOAD AMPSRM ROOMRMC RIGID METAL CONDUITRMS ROOT MEAN SQUARERPM REVOLUTIONS PER MINUTE
SC SHORT CIRCUITSCCR SHORT CIRCUIT CURRENT RATINGSD SMOKE DETECTORSERV SERVICESF SUPPLY FANSMD SMOKE DAMPERSPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEELSW SWITCHSWBD SWITCH BOARDSWGR SWITCH GEARSYS SYSTEM
TBD TO BE DETERMINEDTC TIME CLOCKTCOM TELECOMMUNICATIONTEL TELEPHONETEMP TEMPERATURETVSS TRANSIENT VOLTAGE SURGE
SUPPRESSIONTYP TYPICAL
UC UNDER COUNTERUH UNIT HEATERUON UNLESS OTHERWISE NOTEDUV UNIT VENTILATOR
V VOLTSVA VOLT AMPEREVAC VACUUMVAV VARIABLE AIR VOLUME UNITVD VOLUME DAMPERVF VENTILATION FANVFD VARIABLE FREQUENCY DRIVEVOL VOLUME
W WATTW/ WITHW/O WITHOUTWBT WET BULB TEMPERATUREWC WATER COLUMNWG WIRE GUARDWP WEATHER PROOF
XFMR TRANSFORMER
Z IMPEDENCE
3 4
LT
LT
PC
TC
J
XXXX
277/120 V SWITCH, SINGLE POLE, THREE-WAY AND FOUR-WAY, RESPECTIVELY.FLUSH MOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT; FOR ALLCOMMON AREA "HOUSE" WIRING SWITCHES, UTILIZE ONLY SPECIFICATION GRADESWITCHES RATED 20 A: FOR DWELLING UNITS, 15 A STANDARD GRADESWITCHES ARE PERMITTED ONLY WHERE CONTROLLING LIGHTING AND ONLYWHERE THE TOTAL LAMP WATTS CONTROLLED IS 1,000 W OR LESS (USE ONLY20 A STANDARD GRADE SWITCHES FOR CONTROLLING MOTORS AND OTHEREQUIPMENT)
F
120 V 300W COMBINATION LIGHT(INSTANT ON, INSTANT OFF) AND (INSTANT ON,INSTANT OFF) FAN CONTROL SWITCH, FLUSH MOUNTED, WHITE FINISH ANDCOVER PLATE, SEPARATELY WIRED TO FAN AND LIGHTING (INDEPENDENTLYCONTROLLED). MOUNT IN DEDICATED 1-GANG OUTLET BOX, STANDARDGRADE, CONNECT TO NON-AFCI BATHROOM LIGHTING CIRCUIT, LEVITON #1754-T" OR APPROVED EQUAL.
LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURE SCHEDULEINDICATES BRANCH CIRCUIT NUMBER
WALL MOUNTED LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULEINDICATES BRANCH CIRCUIT NUMBER
FLUORESCENT LUMINAIRE, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULEINDICATES BRANCH CIRCUIT NUMBER
INDICATES NIGHT-LIGHTING LUMINAIRE AND/OR ON EMERGENCY POWER CIRCUIT,UN-SWITCHED, ON 24 HOURS, TYPE AS INDICATED ON THE LIGHTING FIXTURESCHEDULE
EXIT SIGN, TYPE ("EXIT" UNLESS INDICATED OTHERWISE) AS INDICATED ON THELIGHTING FIXTURE SCHEDULE WITH DIRECTIONAL ARROW AS INDICATED
EMERGENCY LIGHTING BATTERY UNIT, ("EM" UNLESS INDICATED OTHERWISE) ASINDICATED ON THE LIGHTING FIXTURE SCHEDULE
REMOTE EMERGENCY LIGHTING HEADS, WALL MOUNTED, TYPE AS INDICATED ONTHE LIGHTING FIXTURE SCHEDULE
120 V DUPLEX RECEPTACLE, TAMPER RESISTANT, FLUSH MOUNTED, FINISH ANDCOVER PLATE AS PER ARCHITECT, (+) INDICATES ABOVE COUNTER MOUNTINGHEIGHT; FOR ALL COMMON AREA "HOUSE" RECEPTACLES, UTILIZE ONLYSPECIFICATION GRADE RECEPTACLES RATED 20 A; FOR DWELLING UNITS, 15 ASTANDARD GRADE RECEPTACLES ARE PERMITTED FOR CONVENIENCERECEPTACLES ONLY IN FAMILY ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,DENS, SUN ROOMS, BEDROOMS AND RECREATION ROOMS, WHERE APPLICABLE(USE ONLY 20 A STANDARD GRADE RECEPTACLES FOR KITCHENS, DININGROOMS, BATHROOMS AND RECEPTACLES SERVING EQUIPMENT, AS PER THETYPICAL DWELLING UNIT EQUIPMENT SCHEDULE)
20 A OR 15 A, 120 V DUPLEX RECEPTACLE, STANDARD GRADE, TAMPERRESISTANT, WITH ONE (1) RECEPTACLE POSITION CONTROLLED BY SWITCH ASINDICATED ON THE DRAWINGS AND WITH ONE (1) RECEPTACLE POSITION UN-SWITCHED, FLUSH MOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT, (+)INDICATES ABOVE COUNTER MOUNTING HEIGHT. CONNECT SO THAT TOP HALFOF RECEPTACLE IS SWITCHED.
20 A, 120 V DUPLEX GROUND FAULT CIRCUIT INTERRUPTER (G.F.C.I.) TYPE/PROTECTED RECEPTACLE, SPECIFICATION GRADE, TAMPER RESISTANT, FLUSHMOUNTED, FINISH AND COVER PLATE AS PER ARCHITECT, (+) INDICATES ABOVECOUNTER MOUNTING HEIGHT, (WP) INDICATES MOUNTING IN A WEATHERPROOFOUTLET BOX WITH SINGLE SPRING-LATCHED IN-USE WEATHER-PROOF COVER;PROTECTION OF STANDARD TYPE RECEPTACLES FROM OTHER G.F.C.I.RECEPTACLES IS NOT ACCEPTABLE (EXCEPT THAT FEED THROUGH PROTECTIONIS PERMITTED FOR KITCHEN RECEPTACLES ONLY WHERE ALL PROTECTEDRECEPTACLE(S) ARE WITHIN SIGHT OF THE PROTECTING G.F.C.I. TYPERECEPTACLE AND PROVIDED PROTECTED RECEPTACLES ARE IDENTIFIED ASPROTECTED AS PER THE N.E.C.)
QUADRAPLEX ("DOUBLE DUPLEX") RECEPTACLE, WITH RECEPTACLE TYPE ASINDICATED
EQUIPMENT CONNECTION, REFER TO THE EQUIPMENT SCHEDULE AND THEEQUIPMENT NOTES FOR INFORMATION
EQUIPMENT DESIGNATION, FOR REFERENCE TO THE EQUIPMENT SCHEDULE
FUSED DISCONNECT (SAFETY) SWITCH, WITH SIZE, POLES AND FUSES ASINDICATED; IN NEMA-1 ENCLOSURE, (WP) INDICATES NEMA-3R ENCLOSURE; FORALL COMMON AREA "HOUSE" WIRING SWITCHES (AND ALL SWITCHES FED FROMEMERGENCY POWER), USEONLY HEAVY DUTY TYPE; FOR DWELLING UNITS, GENERAL DUTY TYPE ISPERMITTED
NON-FUSED DISCONNECT (SAFETY) SWITCH, WITH SIZE AND POLES ASINDICATED, HEAVY DUTY OR GENERAL DUTY TYPE, IN NEMA-1 ENCLOSURE, (WP)INDICATES NEMA-3R ENCLOSURE; FOR ALL COMMON AREA "HOUSE" WIRINGSWITCHES (AND ALL SWITCHES FED FROM EMERGENCY POWER), UTILIZE ONLYHEAVY DUTY TYPE; FOR DWELLING UNITS, GENERAL DUTY TYPE IS PERMITTED
ENCLOSED CIRCUIT BREAKER (ECB), WITH TRIP RATING AND POLES ASINDICATED, IN NEMA-1 ENCLOSURE, (WP) INDICATES NEMA-3R ENCLOSURE
M
THERMAL OVERLOAD SWITCH (I.E. MANUAL MOTOR STARTER, "O/L SWITCH"),277-120 V AND HORSEPOWER RATED, COORDINATE THERMAL OVERLOAD UNITRATING WITH LOAD SERVED; IN FINISHED SPACES, PROVIDE FLUSH MOUNTEDWITH COVER PLATE AS PER ARCHITECT; IN UNFINISHED SPACES, PROVIDE FLUSHMOUNTED OR SURFACE MOUNTED IN A SUITABLE NEMA-1 ENCLOSURE, (WP)INDICATES MOUNTING IN A NEMA-3R ENCLOSURE
ELECTRICAL PANEL, REFER TO THE SINGLE LINE DIAGRAM AND RESPECTIVEPANEL SCHEDULE
ELECTRICAL JUNCTION BOX (J-BOX), AS INDICATED ON THE DRAWINGS, WHEREJUNCTION BOX SERVICES EQUIPMENT, PROVIDE COMPLETE EQUIPMENTCONNECTION AS REQUIRED
PHOTOCELL, REFER TO SPECIFICATIONS, WALL MOUNTED
INDICATES HOME RUN OF WIRING TO PANEL AND CIRCUIT INDICATED
COMMON AREA TELEPHONE/DATA OUTLET, FLUSH MOUNTED, PROVIDE OWNERAPPROVED JACK AND COVER PLATE ON SUITABLE 2-GANG OUTLET BOX INWALL AND OWNER APPROVED CABLE (8-CONDUCTOR, "CATEGORY-6" STYLE)RUN FROM OUTLET TO MAIN TELEPHONE/CATV BACKBOARD, (+) INDICATESABOVE COUNTER MOUNTING HEIGHT OR WALL MOUNTED TELEPHONE MOUNTINGHEIGHT (COORDINATE WITH ARCHITECT/OWNER DURING CONSTRUCTION)
DWELLING UNIT TELEPHONE/DATA OUTLET, FLUSH MOUNTED, PROVIDE OWNERAPPROVED JACK AND COVER PLATE ON SUITABLE 1-GANG OUTLET BOX INWALL AND OWNER APPROVED CABLE (8-CONDUCTOR, "CATEGORY-6" STYLE)RUN FROM OUTLET TO DWELLING UNIT SYSTEMS DISTRIBUTION BOX SERVINGDWELLING UNIT (INDIVIDUAL HOME RUN OF CABLE FROM EACH OUTLET IN EACHDWELLING, CONNECT AND TERMINATE ALL CABLES AT BOTH ENDS); (+)INDICATES ABOVE COUNTER MOUNTING HEIGHT OR WALL MOUNTED TELEPHONEMOUNTING HEIGHT (COORDINATE WITH ARCHITECT/OWNER DURINGCONSTRUCTION, FOR WALL MOUNTED TELEPHONE LOCATIONS PROVIDE COVERPLATE WITH STUDS TO FACILITATE WALL MOUNTED TELEPHONE)
XX
XX
XX
XX
XX
OCCUPANCY SENSOR LIGHTING CONTROL WITH INTEGRAL MANUAL OVERRIDETO "ON" PUSH BUTTON (S-OC), FLUSH MOUNTED ON WALL (ON FLUSH MOUNTEDOUTLET BOX), SELF-CONTAINED "STAND ALONE" TYPE (SINGLE SENSOR FORLOCAL LIGHTING CONTROL OF SINGLE CIRCUT ONLY), PASSIVE INFRARED (PIR)TYPE WITH INTEGRAL SWITCHING RELAY, RATED 1,800 VA FOR 120VOPERATION AND 4,000 VA FOR 277V OPERATION, SINGLE POLE SPECIFICATIONGRADE,WHITE FINISH.
OCCUPANCY SENSOR LIGHTING CONTROL (OC), FLUSH MOUNTED IN CELING FORCOMMON CONTROL OF LIGHTING(MULTIPLE SENSORS FOR LIGHTING CONTROLIN CONJUNCTION WITH REMOTE LIGHTING CONTROL RELAY MODULE(S), PASSIVEINFRARED (PIR) TYPE, SPECIFICATION GRADE, WHITE FINISH. PROVIDE POWERPACKS AND LOW VOLTAGE CONTROL WIRING AS REQUIRED.
OC
OC
DEDICATED EQUIPMENT RECEPTACLE, REFER TO EQUIPMENT SCHEDULE & NOTESFOR INFORMATION
TIME CLOCK, REFER TO SPECIFICATIONS, WALL MOUNTED
SDB
DWELLING UNIT SYSTEMS DISTRIBUTION BOX, FLUSH MOUNTED, FOR TELEPHONEAND CATV WIRING, TO SPLICE AND INTERCONNECT ALL TELEPHONE AND CATVDISTRIBUTION WIRING IN DWELLING UNIT TO INCOMING (FROM SERVICE)TELEPHONE AND CATV LINES SERVING DWELLING UNIT; PROVIDE TWO (2) OWNERAPPROVED TELEPHONE/DATA CABLES (8-CONDUCTOR, "CATEGORY 6" STYLE, 1ACTIVE AND 1 SPARE) AND ONE (1) TYPE "RG-6Q" CATV COMPANY APPROVEDCABLE RUN FROM EACH SDB TO MAIN TELEPHONE/CATV BACKBOARD; PROVIDELEVITON #SMC-140/47605-14W (OR APPROVED EQUAL) NOMINAL 14"x14"x4" (355mm X 355 mm X 100 mm) MANUFACTURED ENCLOSURE WITH COVER FACILITATINGSYSTEM EXPANSION BY ADDING MODULAR SYSTEM COMPONENTS (MODULARCOMPONENTS [SUCH AS DATA MODULES, TELEPHONE MODULES, MINI-HUBMODULES, VIDEO MODULES, AUDIO MODULES, CATV MODULES, POWER SUPPLYMODULES, ETC.] ARE NOT IN CONTRACT BUT MAY BE USED [AT THECONTRACTOR'S OPTION] IN LIEU OF SEPARATELY MOUNTED TELEPHONE/CATVCONNECTION COMPONENTS LIST BELOW): PROVIDE TELEPHONE CONNECTIONBRIDGE (LEVITON #47689-B OR APPROVED EQUAL) OR TELEPHONE CONNECTIONPUNCH-DOWN BLOCK ("110" STYLE) IN ENCLOSURE AS REQUIRED TOINTERCONNECT AND ACTIVATE ALL INCOMING AND OUTGOING BRANCHTELEPHONE CABLES (I.E. TO ACTIVATE ALL TELEPHONE OUTLETS); PROVIDE AFEMALE-FEMALE "F" CONNECTOR FITTING IN ENCLOSURE AS REQUIRED TOINTERCONNECT AND ACTIVATE ONE (1) OUTGOING BRANCH CATV CABLE FROMTHE INCOMING CATV SERVICE CABLE (I.E. TO ACTIVATE ONE (1) CATV OUTLET INTHE DWELLING UNIT , ALL REMAINING OUTLETS SHALL BE INACTIVE); LOCATE THEFOLLOWING AT THE DISTRIBUTION BOX:
FOR ALL UNITS EXCEPT THOSE IDENTIFIED AS H&VI: PROVIDE DOORBELLPOWER SUPPLY/ TRANSFORMER IN ENCLOSURE, EXACT TYPE AND RATINGS TOMATCH DOORBELL CHIME AND DOORBELL PUSH-BUTTON; INTERCONNECT WITHCHIME AND PUSH-BUTTON AS REQUIRED SO CHIME OPERATES WHEN PUSH-BUTTONIS PRESSED, PROVIDE INCOMING 120 VAC SUPPLY WIRING AND CONNECT TONEARBY RECEPTACLE CIRCUIT AS REQUIRED
FOR "H&VI" UNITS ONLY: PROVIDE STROBE/TELEPHONE INTERFACE ANDPOWER SUPPLY IN ENCLOSURE, EXACT TYPE AND RATINGS COORDINATED WITH TELEPHONE INDICATING STROBE LIGHT WIRING; INCLUDE COMPLETE WITHSUITABLE TELEPHONE INTERFACE TO ACTIVATE WHEN TELEPHONE RINGS:INTERCONNECT WITH STROBE AND TELEPHONE AS REQUIRED SO STROBEOPERATES WHEN THE TELEPHONE RINGS, PROVIDE INCOMING 120 VAC SUPPLYWIRING AND CONNECT TO NEARBY RECEPTACLE CIRCUIT AS REQUIRED
CABLE TELEVISION (CATV) OUTLET, FLUSH MOUNTED, PROVIDE CATV COMPANYAPPROVED STANDARD "F" CONNECTOR CATV JACK AND COVER PLATE ONSUITABLE OUTLET BOX IN WALL, AND TYPE "RG-6Q" CATV COMPANYAPPROVED CABLE RUN FROM OUTLET TO DWELLING UNIT SYSTEMSDISTRIBUTION BOX SERVING DWELLING UNIT (INDIVIDUAL HOME RUN OF CABLEFROM EACH OUTLET IN EACH DWELLING, CONNECT AND TERMINATE ALL CABLESAT BOTH ENDS); (+) INDICATES ABOVE COUNTER MOUNTING HEIGHT(COORDINATE WITH ARCHITECT/OWNER DURING CONSTRUCTION)
TV
S
SD
H
H
F
FS
C
TS
S
S
IC
IM
T
INT
F
F
F
FACP
ANN
FIRE ALARM CONTROL PANEL, ADDRESSABLE ANALOG TYPE, WITH INTEGRALBATTERY BACKUP, WITH MIMIUM POINT ADDRESSES AS REQUIRED FORCONNECTED DEVICES (OR 197 POINT ADDRESSES, WHICHEVER IS GREATER),WITH PROVISIONS TO EXPAND UP TO BUT NOT LESS THAN 750 POINTS BYADDING ADDRESSABLE ANALOG MODULES WITH INTEGRAL 80-CHARACTER(MINIMUM) KEYBOARD DISPLAY UNIT; PROVIDE TWO TELEPHONE/DATA OUTLETS(AS INDICATED ELSEWHERE ON THE ELECTRICAL SYMBOL LIST) MOUNTEDADJACENT TO CONTROL PANEL AND PROVIDE 27 mm (1") CONDUIT (WITH PULLWIRE) RUN FROM TELEPHONE/DATA OUTLET TO THE MAIN TELEPHONEBACKBOARD
FIRE ALARM REMOTE ANNUNCIATOR PANEL, 80-CHARACTER (MINIMUM)ALPHANUMERIC TYPE, EXACT MATCHING FIRE ALARM CONTROL PANEL, FLUSHMOUNTED, RED OR BEIGE FINISH AS PER ARCHITECT
FIRE ALARM AUDIO/VISUAL HORN/STROBE, ADA APPROVED TYPE PROVIDINGADA APPROVED COVERAGE, WITH SYNCHRONIZED TYPE STROBE, SEMI-FLUSHMOUNTED, 80" AFF TO BOTTOM OF LENS, 15/75 CANDELA UNLESS OTHERWISENOTED
FIRE ALARM AUDIO ONLY HORN, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, FLUSH MOUNTED
FIRE ALARM VISUAL ONLY STROBE, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, SYNCHRONIZED TYPE, FLUSH MOUNTED
FL
"H&VI ADAPTABLE" FIRE ALARM VISUAL ONLY STROBE LOCATION (OUTLET BOXWITH WIRING AND BLANK COVER, SEE TYPICAL DWELLING NOTES), FOR "H&VI"UNITS ONLY, PROVIDE A FIRE ALARM VISUAL ONLY STROBE AT EACH LOCATION.PROVIDE 100 CANDELA UNIT IN SLEEPING ROOMS.
FIRE ALARM MANUAL PULL STATION, METAL, NON-CODED, DOUBLE ACTION,FLUSH MOUNTED, ADDRESSABLE TYPE
FIRE ALARM SMOKE DETECTOR, ANALOG PHOTOELECTRIC TYPE,WITH SUITABLE BASE
SPRINKLER SYSTEM FLOW SWITCH CONNECTION, FURNISHED AND INSTALLED ONPIPING BY SPRINKLER CONTRACTOR AND WIRED TO FIRE ALARM SYSTEM (VIALOCAL IDENTIFICATION MODULE) BY E.C.
SPRINKLER SYSTEM TAMPER SWITCH CONNECTION, FURNISHED AND INSTALLEDON PIPING BY SPRINKLER CONTRACTOR AND WIRED TO FIRE ALARM SYSTEM(VIA LOCAL IDENTIFICATION MODULE) BY E.C.
SINGLE- OR MULTIPLE-STATION SMOKE ALARM, PHOTOELECTRIC TYPE, 120 VAC(WITH BATTERY BACKUP) OPERATION LOCAL TYPE (FEATURING ADA APPROVEDAUDIBILITY), NOT CONNECTED TO FIRE ALARM SYSTEM; INTERCONNECT ALLDETECTORS WITHIN EACH INDIVIDUAL UNIT; CONNECT TO NEARBY LIGHTINGCIRCUIT (IN LINE "TANDEM" SO ACTIVATION OF ANY ONE (1) SMOKE ALARMSOUNDS ALARM IN ALL SMOKE ALARMS), PROVIDE SMOKE ALARM OF A TYPEFULLY COMPATIBLE WITH STROBE UNITS BELOW; IN DWELLING UNITS NOTIDENTIFIED AS "H&VI" PROVIDE AUDIBLE SMOKE ALARMS ONLY (I.E. WITHOUTASSOCIATED STROBE UNIT), UTILIZE BRK ELECTRONICS #7010B OR APPROVEDEQUAL; IN DWELLING UNITS IDENTIFIED ON THE DRAWINGS AS "H&VI" PROVIDESMOKE ALARMS AS INDICATED ABOVE IN ADDITION TO A SEPARATE STROBEUNIT (FEATURING ADA APPROVED VISIBILITY) MOUNTED DIRECTLY ADJACENT TOEACH SMOKE ALARM, UTILIZE BRK ELECTRONICS #SL177 STROBE (IN ADDITIONTO DETECTOR) OR APPROVED EQUAL
L
"H&VI ADAPTABLE" TELEPHONE INDICATING STROBE LIGHT LOCATION (OUTLET BOXWITH WIRING AND BLANK COVER, SEE TYPICAL DWELLING NOTES); FOR "H&VI" UNITSONLY, PROVIDE TELEPHONE INDICATING STROBE LIGHT, ADA APPROVED TYPE,SEMI-FLUSH MOUNTED, WITH SPECIAL WORDING "BELL" ON THE STROBE, WITHSPECIAL FINISH AS PER THE ARCHITECT, TORK #TA 5500 SERIES OR APPROVEDEQUAL; INTERCONNECT WITH STROBE/TELEPHONE INTERFACE AND POWER SUPPLYAS REQUIRED SO STROBE OPERATES WHEN TELEPHONE RINGS.
INTERCOM ENTRANCE DOOR STATION, WITH INTEGRAL SPEAKER AND MICROPHONEMODULE, WITH QUANTITY OF DWELLING CALL PUSHBUTTONS TO MATCH DWELLINGSSERVED, SUITABLE FOR OUTDOOR INSTALLATION, FLUSH MOUNTED IN WALL(INCLUDE ALL CUTTING AND PATCHING EXTERIOR WALLS AS REQUIRED), AEGIS9000 SERIES WITH HEATER PAD AHP5 OR APPROVED EQUAL. PROVIDE SEPARATETELEPHONE LINE AND SURGE PROTECTOR USP1.
INTERCOM DWELLING STATION, WALL MOUNTED (AT WALL TELEPHONE MOUNTINGHEIGHT) WITH TELEPHONE TYPE HANDSET, WITH PROVISIONS FOR REMOTE DOOROPENING, FLUSH MOUNTED IN WALL, AEG15 SERIES OR APPROVED EQUAL
INTERCOM POWER SUPPLY UNIT (EXACT TYPE TO MATCH INTERCOM EQUIPMENT)
F
FIRE ALARM AUDIO ONLY MINI HORN, ADA APPROVED TYPE PROVIDING ADAAPPROVED COVERAGE, FLUSH MOUNTED
FIRE ALARM HEAT DETECTOR, ANALOG, WITH SUITABLE BASE190º FIXED TEMP190
COMBINATION CARBON MONOXIDE (CO) DETECTOR AND SINGLE-STATION SMOKEALARM, 120 VAC (WITH INTEGRAL BATTERY BACKUP) OPERATION LOCAL TYPE(FEATURING ADA APPROVED AUDIBILITY), NOT CONNECTED TO FIRE ALARMSYSTEM; INTERCONNECT ALL SMOKE ALARMS AND CO DETECTORS WITHIN EACHINDIVIDUAL DWELLING UNIT IN "TANDEM" SO ACTIVATION OF ANY ONE (1) ALARM ORDETECTOR SOUNDS ALARM IN ALL SMOKE ALARMS IN THE INDIVIDUAL UNIT;CONNECT TO NEARBY LIGHTING CIRCUIT (ON LINE SIDE OF ALL SWITCHES, DO NOTCONNECT TO A RECEPTACLE CIRCUIT OR CIRCUIT DEDICATED TO DETECTORS),PROVIDE CO DETECTOR OF A TYPE FULLY COMPATIBLE WITH SMOKE ALARM ANDSTROBE UNITS (SEE SMOKE ALARM SYMBOL ABOVE); IN DWELLING UNITS NOTIDENTIFIED AS "H&VI" PROVIDE AUDIBLE SMOKE ALARMS ONLY (I.E. WITHOUTASSOCIATED STROBE UNIT), UTILIZE BRK ELECTRONICS #SC7010B OR APPROVEDEQUAL; IN DWELLING UNITS IDENTIFIED ON THE DRAWINGS AS "H&VI". PROVIDESMOKE ALARMS AS INDICATED ABOVE IN ADDITION TO A SEPARATE STROBE UNIT(FEATURING ADA APPROVED VISIBILITY) MOUNTED DIRECTLY ADJACENT TO EACHSMOKE ALARM, UTILIZED BRK ELECTRONICS #SL177 STROBE (IN ADDITION TODETECTOR) OR APPROVED EQUAL.
CO
DUCT MOUNTED SMOKE DAMPER,
FIRE ALARM HEAT DETECTOR, ANALOG, WITH SUITABLE BASE 165º
CONTROL MODULE
ELECTRICAL SYMBOLSELECTRICAL ABBREVIATIONS ELECTRICAL DRAWING LISTELECTRICAL SYMBOLS
STANDARD MOUNTING HEIGHTSSCALE: NTS
EXIT SIGN (UON) EMERGENCY LIGHTINGFIXTURE (UON)
FIRE ALARM NOTIFICATION DEVICE (UON)
SINGLE SWITCH (UON)
DUAL SWITCH (UON)
GFI DUPLEX RECEPTACLE (UON)THERMOSTAT (UON)
TEMPERATURE SENSOR (UON)
FIRE ALARM PULL STATION (UON)
HORIZONTAL DATA OUTLET (UON)
DATA OUTLET (UON)DOUBLE DUPLEX RECEPTACLE/ QUAD RECEPTACLE (UON)
HORIZONTAL DUPLEX RECEPTACLE (UON)
+96" AFF
+84" AFF
+48" AFF
+18" AFF
FINISHED FLOOR
FINISHED CEILING
EXIT
NURSE CALL STATION (UON)
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
ABBR
EVIA
TIO
NS
& SY
MBO
LS,T
hurs
day,
Mar
ch 3
, 201
6,3:
29 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
E000
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
ABBREVIATIONS &SYMBOLS
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
EF5
C3
C2
C1
F3
F2
EH1
HP2
5
1
1
EH-
S
JH
EF4
S
S
S
S
EF2
CU2
CU1
HP1
EH5
F1
WW
WW
WW
DD
DD
DD
Trash
Trash
Trash
CB1-3
CB1-5
CB1-1
CB1-7
CB1-1
CB1-1
CB1-16
FOR MICROWAVEOVEN CB1-14
FOR DISHWASHERCB1-15
CONNECT TO ROOMLIGHTING CIRCUIT
WP
CB1-23
CB1-1
TV
CB1-5
CB1-1
MOUNT INATTICSPACE
190
CB1-(35,37)CB1-(31,33)CB2-(35,37)
CB1-1
WPWPWP
CB1-39
CB2-14
CB2-17CB2-17
CB2-23
WP
CB2-17
CB2-20
CB2-20
CB1-20
EWH
CB2-20
CB2-20
CB2-20
CB1-21
CB2-20
CB2-20 CB2-23
CB2-23
CB1-7+42 CB1-7
CB1-7
CB1-41
CB1-23WP
CB2-39
CB1-12CB1-10
CB1-10
CB1-10
CB1-10CB1-8
CB1-8
CB1-8
TV
CB1-12
CB2-12
CB1-12
190
CB2-2
CB2-4
CB2-6
CB2-8
CB2-10
CB2-21
CB2-3
CB2-5
CB2-7
CB2-9
CB2-11
CB2-27&29
4' x 5' x 3/4" FIRERETARDANTPLYWOOD BACKBOARD
CB1-13
CB1-12
CB2-13
CB2-23
WP+48CB2-16
MOUNT INATTIC SPACE
190
CB1-17
CB1-32,34 &36
CB2-25
CB2-25
CB2-25
CB2-25
CB2-25
WP
CB1-23
CB2-25
CB2-25
CB2-23
CB2-23
CB2-23
CB2-23
CB1-9 CB1-9 CB1-9
CB1-9CB1-9CB2-23
DW
R
R
OFFICE
116MGMT. OFFICE
115
VESTIBULE
101EXERCISE
102
LAUNDRY
103
MAINTENANCE
104
MECH.
106SPRINKLER
105
PATIO
01
CONSULT
118
KITCHENETTE
121
MECH.
117
MEN
113
COMMON CORRIDOR
112
STORAGE
107
ELEC./IT
109
PORCH
01
PORCH
01CONIFER CORRIDOR
110
COMMUNITY ROOM
111
WOMEN
114
JAN.
108
2
2
S
S
F
H
H
CR
FACP
WF TS F S
S
S
S
F
S
S
S
ANN
CR
DS
6
S
H
3
F
DS
CR
EH6
EH6
H
S
SCPDCPPRPS
DCPPRPS
J
4
CR
DS
F
F
FF
F
F
EF3
TT
EH6
CB1-3
CB1-3
CB1-22
CB1-2+42
CEILING FAN(TYPICAL FOR 2)
CB2-15
+44CB1-19
+44CB1-19
CB2-31
CB2-33
CB2-17
PANEL"CB1"
PANEL"CB2"
CB2-32CONNECT TOLIGHTING CKT
CB1-7
CB1-7
CONNECT TOTOILETLIGHTING CKT
KEYED NOTES
1
2
3
4
5
6
MOUNT ACCESS CONTROL PANELS ON WALL ABOVECEILING.
PROVIDE 52" ENERGY STAR RATED CEILING FAN.BASIS OF DESIGN: 15030-962 QUALITY MAX 52" CEILINGFAN BY SEA GULL LIGHTINFG OR APPROVED EQUAL.HOUSING FINISH TO BE BRUSHED NICKEL. BLADE FINISHTO BE OAK. PROVIDE 2' DOWNROD EXTENSION.COORDINATE WITH LIGHTING FIXTURES AND SLOPE OFCEILING.
PROVIDE TELEPHONE CONNECTION FOR DEBITMACHINE IN LAUNDRY ROOM 106. COORDINATELOCATION WITH ARCHITECT.
PROVIDE JUNCTION BOXES WITH BLANK COVERS INTHE RAFTER SPACE FOR FUTURE RADON FANCONNECTIONS. CONNECT RADON FAN JUNCTION BOXESTO 20A, 120V BRANCH CIRCUIT IN PANEL "CB2". FINALQUANTITIES AND LOCATIONS OF RADON FAN JUNCTIONBOXES TO BE DETERMINED, COORDINATE WITHARCHITECT, REFER TO ARCHITECTURAL DRAWINGS ANDSPECIFICATIONS FOR ADDITIONAL INFORMATION.
ACCESS PANEL TO ATTIC SPACE. COORDINATELOCATION WITH ARCHITECT. PROVIDE GFI RECEPTACLEAND PORCELAIN SOCKET WITH PULL CORD AND 45WCFL R20 GE SMART ENERGY LAMP ABOVE ACCESSPANEL. CONNECT TO RADON FAN CIRCUIT, PROVIDEADDITIONAL PORCELAIN SOCKET AND LAMP AT RADONFAN JUNCTION BOX AS SHOWN.
SPRINKLER SYSTEM ELECTRIC BELL, INSTALL BELL(FURNISHED BY FIRE PROTECTION SYSTEMCONTRACTOR) AND PROVIDE 2#12,#12G IN 3/4"C ANDCONNECT SO THAT BELL SOUNDS WHEN WATER FLOWSWITCH IS ACTIVATED.
N
SCALE: 1/4" = 1'-0"1 FIRST FLOOR POWER PLAN
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
FIR
ST F
LOO
R P
OW
ER P
LAN
,Thu
rsda
y, M
arch
3, 2
016,
3:29
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
E101
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
FIRST FLOORPOWER PLAN
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
CB1-26CH
1
33
1
CB2-20CH
CB2-20CH
331
3
CB1-24CH
CB1-24CH
4
OC
1
1
1
CL
CB1-26
CLCB1-26
1
4
1
4
CB
1-26
CL
CB
1-26
CL
1
CB1-24
CA
CB1-24
CA
OC
CB2-20
CA
CB2-20
CA
CB1-24
CA
1
31
1
3
1
CB
1-26
CI
CB
1-26
CI
F
3
3
CB2-19
CA
CB2-19
CA
CB2-19
CA
CB2-19
CA
CB2-19
CB
CB2-19
CA
CB2-19
CA
CB2-19
CB
CB2-19
CB
CB2-19
CB
CB2-19
CB
CB2-19CB
1CB2-19
CB
1
1
CF
CB2-19
CF CF
D
CB2-20
CF
CB1-24CF
CF
CB2-20
CB2-20
CA1
CB2-20
CA1
CB2-20
CA1
CB
1-26
CI
CB1-24
CA
CB1-24
CA
CB1-24
CA
WW
WW
WW
DD
DD
DD
Trash
Trash
Trash
+42
DW
R
R
OFFICE
116MGMT. OFFICE
115
VESTIBULE
101EXERCISE
102
LAUNDRY
103
MAINTENANCE
104
MECH.
106SPRINKLER
105
PATIO
01
CONSULT
118
KITCHENETTE
121
MECH.
117
MEN
113
COMMON CORRIDOR
112
STORAGE
107
ELEC./IT
109
PORCH
01
PORCH
01CONIFER CORRIDOR
110
COMMUNITY ROOM
111
WOMEN
114
JAN.
108
CB1-24CE
CB1-24CE
CB1-24CE
1
CB1-24CE
CB1-24CE CB1-24
CHCH
CH
CK
CK
CB1-24
CHCH
CH
CB1-24CH
CB1-24CH
CB1-25CG
CB1-25CG
1
CB1-24
CFCB1-25
CJ
CB1-25CH
CB1-25CH
CB1-24
CFCF
CB2-20
CA1
CB2-20
CA1
CB2-20
CA1
CB2-20
CA1
CB2-20
CA1
CB1-26CM
CB1-26CH
CB1-25CG
CB1-25CG
CB1-25CG
CB1-25CG
CB1-25
CH
CB1-25
CH
XEM-3
EM
gg
e
EM
e
XEM-3
RH
EM
EM
EM
e
XEM
XEM-3e
e
e
RH
EM
EM
EM
XEM-3
RH
RH
OC
EM
XEM-3
EM
d
d
EM
XEM
g
g f
f
F
d
d
d
d
KEYED NOTES
1
2
CONNECT EMERGENCY AND EXIT LIGHTING FIXTURESTO LIGHTING CIRCUIT IN AREA AHEAD OF ALLSWITCHING.
PROVIDE PHOTOCELL FOR CONTROL OFBUILDING MOUNTED LIGHTING.
N
SCALE: 1/4" = 1'-0"1 FIRST FLOOR LIGHTING PLAN
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
FIR
ST F
LOO
R L
IGH
TIN
G P
LAN
,Thu
rsda
y, M
arch
3, 2
016,
3:29
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
E102
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
FIRST FLOORLIGHTING PLAN
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
CH
CE
CG
CC
CK
CI
CF
LIGHTING FIXTURE SCHEDULE FOR CLUBHOUSEFIXTURE TYPE DESCRIPTION MANUFACTURER AND
CATALOG NO.VOLT/
BALLASTLAMPS
NO. TYPEREMARKS
CA 2FTx4FT, STEEL HOUSING WITH MOUNTING COLLAR,FLUSH ALUMINUM DOOR, ACRYLIC PRISMATIC LENS
LITHONIA LIGHTING2RT8SX-2-32-MVOLT-GEB1OIS-
LP835
120V/ELECTRONIC 2 LP835 SURFACE MOUNTED
CB4FT, SURFACE WRAP AROUND 4-LAMP HOUSING: 20 GA
DIE FORMED STEEL WITH STEEL END PLATES.SHIELDING: CLEAR ACRYLIC PRISMATIC, CONTINUOUS
WRAP SIDES. FINISH: WHITE POWDER COAT
PROGRESS LIGHTINGP7279-60EB
120V/ELECTRONIC 2 F32T8 SURFACE MOUNTED
CC 12.5" DIA x 6.5" H DECORATIVE FLUORESCENT,BRUSHED NICKEL FINISH, WHITE GLASS LENS
SEAGULL LIGHTING79364B-LE-962
120V/ELECTRONIC 2
GU24 13WCLF SURFACE MOUNTED
CD 4FT, SURFACE WRAP AROUND VANDAL RESISTANTHOUSING, PRISMATIC POLYCARBONATE DIFFUSER
PROGRESS LIGHTINGP7279-60EB
120V/ELECTRONIC 2 F32T8 SURFACE MOUNTED
CE20IN DIAMETER, ILLUMINATED BOWL, BOWL: WHITE
ACRYLIC DIFFUSER, 4.25" HT, BRUSHED NICKEL FINISHSEAGULL LIGHTING
79130BLE-98120V/
ELECTRONIC 4GU24 13W
CLF CEILING MOUNTED
CF COMPACT FLUORESCENT CEILING LAMP HOLDER LEVITRON9860-LHG
120V/ELECTRONIC 1 13W CFL CEILING MOUNTED
CG 21.25" DIA., PENDANT MTD, BRUSHED STAINLESS FINISH,WITH SATIN WHITE GLASS
SEAGULL LIGHTING69133BLE-98
120V/ELECTRONIC 3 13W CFL CEILING MOUNTED
CH RECESSED COMPACT FLUORESCENT AIR TIGHTDOWNLIGHT
SEAGULL LIGHTING11061AT-861
120V/ COLDWEATHER
ELECTRONIC1
26W97046
PROVIDE WITH STANDARDTEMPERATURE BALLAST FOR
INTERIOR LOCATIONS.
CIEXTERIOR WALL LANTERN, BODY: BLACK DIE CAST
ALUMINUM. PANELS: WHITE FLAT GLASS.SEAGULL LIGHTING
8988BLE-12120V/COLDWEATHER
ELECTRONIC1 13W FLUOR. EXTERIOR WALL MOUNTED
CJ2FT, UNDER CABINET LIGHT, HOUSING: 20 GA DIE
FORMED STEEL WITH STEEL END PLATES. SHIELDING:HIGH IMPACT, EXTRUDED WHITE OPAL ACRYLIC. FINISH:
WHITE POWDER COAT
PROGRESS LIGHTINGP7011-30EB
120V/ELECTRONIC 1 F13WT5
ABOVE SINK UNDER CABINETMOUNTED
EM EMERGENCY LIGHTING BATTERY FIXTURE FIXED LENSWITH MAINTENANCE FREE LEAD BATTERY
LIGHT ALARMSLCA-2SQ SERIES 120V 2 6V 6W
WALL MOUNTED. CONNECT TOROOM LIGHTING CIRCUIT AHEAD
OF ALL SWITCHING.
XEMTHERMOPLASTIC COMBINATION LED EXIT SIGN ANDEMERGENCY LIGHTING BATTERY FIXTURE. TWO UNITMOUNTED HEADS, WITH MAINTENANCE FREE LEAD
BATTERY AND INTERNAL DIAGNOSTICS
PROGRESS LIGHTINGP3052-09EBWB
120V 2 13W CFL WALL MOUNTED
XEM-3
LIGHT ALARMSV2LXN500R-2SQ 120V 4 WALL MOUNTED
NO REMOTE CAPABILITY
SIMILAR TO TYPE 'XEM' EXCEPT REMOTE CAPABLELIGHT ALARMSLTURW-31-03L 120V 4 3W
LED
WALL MOUNTED. EXTERIORSEALED BEAM TWIN REMOTEHEAD TO BE INSTALLED 12"
ABOVE THE DOOR. CONNECT TOROOM LIGHTING CIRCUIT AHEAD
OF ALL SWITCHING.REMOTE CAPABILITY
CK
RH WATERPROOF REMOTE DUAL HEAD FIXTURELIGHT ALARMS
ELF647D/KH4-M6 6V DC 26W
B1 PIN HALOGEN MOUNT 12" ABOVE DOOR HEIGHT
XEM-3
EM
RH
XEM
OVER MIRROR FLUORESCENT FIXTURE, ALABASTERGLASS BRUSHED NICKEL
3WLED
SURFACE MOUNTEDLP8352120V/
ELECTRONICLITHONIA LIGHTING
2RT8SX-2-17-MVOLT-GEB10IS-LP835
2FTx2FT, STEEL HOUSING WITH MOUNTING COLLAR,FLUSH ALUMINUM DOOR, ACRYLIC PRISMATIC LENSCA1
3/2/16/Volumes/Public/Projects/2014/14204_ConiferClayton/engineering/electrical/ELECTRICAL LOAD CALC'S/PANEL SCHEDULES/xls/CAMP SALUTE CLUB HOUSE PANEL CB1.xls
Page 1
WIRE AND CONDUIT
CKT DESCRIPTION VA ØA ØB VA DESCRIPTION CKT WIRE AND CONDUIT
2#12+G 1 540 20 1 1,540 - 20 1 1000 2 2#12+G2#12+G 3 540 20 1 - 1,640 20 1 1100 4 2#12+G2#12+G 5 540 20 1 2,040 - 20 1 1500 6 2#12+G2#12+G 7 360 20 1 - 900 20 1 540 8 2#12+G2#12+G 9 360 20 1 720 - 20 1 360 10 2#12+G2#12+G 11 720 20 1 - 1,080 20 1 360 12 2#12+G2#12+G 13 360 20 1 720 - 20 1 360 14 2#12+G2#12+G 15 1200 20 1 - 1,950 20 1 750 16 2#12+G2#8+G 17 1000 20 1 1,500 - 20 1 500 18 2#12+G
2#12+G 19 360 20 1 - 1,010 20 1 650 20 2#12+G2#12+G 21 360 20 1 660 - 20 1 300 22 2#12+G2#12+G 23 720 20 1 - 1,611 20 1 891 24 2#12+G2#14+G 25 550 20 1 655 - 20 1 105 26 2#12+G
1 2#12+G 27 500 20 1 - 1,000 20 1 500 28 2#12+G1 2#12+G 29 250 20 1 750 - 20 1 500 30 2#12+G 1
31 2808 40 - 3,984 20 1 1176 32 2#12+G 133 2808 2 2,908 - 20 1 100 34 2#12+G35 972 20 - 2,628 20 1 1656 36 2#12+G37 972 2 1,668 - 20 1 696 38 2#12+G
2#12+G 39 1176 20 1 - 22,476 150 21300 40 3#3/0(AL)2#12+G 41 750 20 1 16,236 - 2 15486 42 1#2(AL)G
LIGHTINGRECEPT
A/C
HEATING
MISC
TOTAL
REFERENCE DWG:
GAS-FIRED FURNACE GF-2
4
5
GAS-FIRED FURNACERECEPTACLE - MECHANICAL ROOMBOTTLED WATER DISPENSER
LIGHTING - COMMUNITY ROOMACCESS CONTROL PANELDOOR CONTROL PANEL FIRE ALARM CONTROL PANEL
240/120V, 1Ø, 3W
54858
RECEPTACLES - OFFICE
DRY SYSTEM AIR COMPRESSOR
LIGHTING - OFFICE, HALL, EXERCISE
RECEPTACLES - TOILET ROOMS
RECEPTACLES - EXTERIOR
RECEPTACLES - COMPUTER
RECEPTACLES - COMPUTERRECEPTACLES - COMPUTER
RECEPTACLES - EXERCISE ROOMRECEPTACLES - EXERCISE ROOMRECEPTACLES - EXERCISE ROOM
2#10+G
1MAINTENANCE V, Ø, W:
DISHWASHER
CEILING FANS
TELEPHONE EQUIPMENT
LIGHTING - BUILDING MOUNTEDDOOR CONTROL PANEL
ØA TOTAL VA
RECEPTACLES - COMMUNITY ROOMRECEPTACLES - COMMUNITY ROOMTV RECEPTACLE - COMMUNITY ROOM
PANEL CB2
RECEPTACLES - KITCHEN
REFRIGERATORMICROWAVE OVEN
228.58
28701
10846
NOTES:
1. PROVIDE LOCK-ON HANDLE ON CIRCUIT BREAKER
8872
3099
3340
MOUNTING:
RECEPTACLES - HALL
SURFACESTANDARDSTANDARD
22 kAICNEUTRALGROUNDING:
300A MCB
SITE LIGHTING
NOTE
S
NOTE
S
MIN. INT. RATING:MAIN CB/LUGS
CB
PANELSECTION
CB1
CB
3,340
100%
LOCATION
2
25,084 30,667
3
67,676
38,268
100%
80%
75%
75%
11,090
4,132
10,846
ØB TOTAL VA TOTAL DEMAND AMPS
ACCU-1
GAS-FIRED FURNACEELECTRIC HEAT EH-1
2#8+#10G
ACCU-2
DIVERSITY
GAS-FIRED FURNACE GF-1WATER HEATER WH-1
3/2/16/Volumes/Public/Projects/2014/14204_ConiferClayton/engineering/electrical/ELECTRICAL LOAD CALC'S/PANEL SCHEDULES/xls/CAMP SALUTE CLUB HOUSE PANEL_CB2.xls
Page 1
WIRE AND CONDUIT
CKT DESCRIPTION VA ØA ØB VA DESCRIPTION CKT WIRE AND CONDUIT
2#12+G 1 180 20 1 1,380 - 20 1 1200 2 2#12+G2#12+G 3 100 20 1 - 1,300 20 1 1200 4 2#12+G2#12+G 5 100 20 1 1,300 - 20 1 1200 6 2#12+G2#12+G 7 100 20 1 - 1,300 20 1 1200 8 2#12+G2#12+G 9 100 20 1 1,300 - 20 1 1200 10 2#12+G2#12+G 11 100 20 1 - 600 20 1 500 12 2#12+G2#12+G 13 180 20 1 360 - 20 1 180 14 2#12+G2#12+G 15 100 20 1 - 1,000 20 1 900 16 2#12+G2#12+G 17 540 20 1 1,540 - 15 1000 182#12+G 19 704 20 1 - 1,704 2 1000 202#12+G 21 100 20 1 1,100 - 15 1000 222#12+G 23 1260 20 1 - 2,260 2 1000 242#12+G 25 1250 20 1 2,450 - 20 1 1200 26 2#12+G
27 100 15 - 1,691 20 1591 2829 100 2 1,691 - 2 1591 3031 1000 15 - 1,270 20 1 270 32 2#12+G33 1000 2 1,250 - 20 1 250 34 2#12+G35 1000 15 - 1,000 20 1 0 3637 1000 2 7,000 - 70 6000 38 3#4
2#12+G 39 100 20 1 - 6,100 2 6000 40 1#8G41 0 20 1 1,260 - 20 1 1260 42
LIGHTINGRECEPT
A/C
HEATING
MISC
TOTAL
REFERENCE DWG:
RECEPTACLES - HALLWAY CORRIDOR
3#12+GHP-1
4
5
RECEPTACLES - MAINTENANCE ROOM
RECEPTACLES - CONSULT ROOM
AU-1
33786
DIVERSITY794
WASHING MACHINE
DRYER (GAS FIRED)
LIGHTING - MAINTENANCE, LAUNDRY
RECEPTACLES - HALLWAY
RECEPTACLES - MECHANICAL ROOM
DRYER (GAS FIRED)DRYER (GAS FIRED)
WASHING MACHINEELECTRIC HEAT EH-4
WASHING MACHINE
ELECTRIC HEAT EH-2
1MAINTENANCE V, Ø, W:
WATER HEATER (GAS-FIRED)
SPRINKLER BELL
RECEPTACLE - LAUNDRY ROOM
ELECTRIC HEAT EH-2
DRYER (GAS FIRED)DRYER (GAS FIRED)
RECEPTACLES - MAINTENANCE ROOM
3#12+G
3#12+G
FUTURE RADON FANSCURRENT SENSORSSPARE
PLENUM HEATING PANEL 'PEH'
ELECTRIC HEAT EH-23#12+G
140.78
20500
6950
NOTES:
1
2160
3382
18,225
MOUNTING:
DRYER (GAS FIRED)
SURFACESTANDARDSTANDARD
10 kAICNEUTRALGROUNDING:
150A MLO
DEBIT MACHINE RECEPTACLE
NOTE
S
NOTE
S
MIN. INT. RATING:MAIN CB/LUGS
CB
PANELSECTION
CB2
CB
794
100%
SPARE
LOCATION
2
20,631
3
33,786
20,500
100%
100%
100%
100%
2,160
3,382
6,950
ØA TOTAL VA
240/120V, 1Ø, 3W
WASHING MACHINE
WASHING MACHINEWASHING MACHINE
ØB TOTAL VA TOTAL DEMAND AMPS
ELECTRIC HEAT EH-2
3#12+G
3#12+G
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
SCH
EDU
LES,
Thur
sday
, Mar
ch 3
, 201
6,3:
29 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
E801
03-03-1614204
RW/AH/SWRW
Date
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:N
J PE
GE0
3005
8St
ephe
n F.
Fin
kelm
an
CO
A#: 2
4GA2
8203
000
SCHEDULES
©20
15 -
Kitc
hen
& As
soci
ates
.
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
ELECTRIC ALARM GONG
SIAMESE FIRE DEPARTMENT CONNECTION
BACK FLOW PREVENTER
PIPE ELBOW DOWN
SPRINKLER PIPING
MONITORED OS&Y VALVE
PRESSURE GAUGE
CHECK VALVE
DRY ALARM CHECK VALVE
FP000
FP101
NOTES, SYMBOLS & ABBREVIATIONS
FIRST FLOOR PLAN
16
4
1
GRADE
2-1/2"
11
14
5 6
ZONE RISER FOR SPRINKLER SYSTEM
FIRE DEPARTMENT CONNECTION ATBUILDING. VERIFY THREAD TYPE WITHFIRE MARSHAL. LABEL "SPRINKLERSYSTEM"
FIRE DEPARTMENT CONNECTION PIPING
CHECK VALVE. LOCATE IN WATERSERVICE ROOM.
PROTECTION SERVICE NOTES
BACKFLOW PREVENTER SIMILAR TOZURN WILKINS MODEL #350ASTDAWITH SUPERVISED OS&Y GATEVALVES
THRUST BLOCK
ELECTRIC GONG
NEW 4" UNDERGROUND FIRE WATERSERVICE
SUPERVISED GATE VALVE
8
9
3
5
6
7
4
1
2
FIRE DEPARTMENT CONNECTION PIPING.CONNECT TO WET-PIPE SECTION OFFIRE SUPPRESSION SYSTEM.
10
BALL DRIP. ROUTE TO BUILDINGEXTERIOR.
11
DRY-ALARM CHECK VALVE WITHTRIM SIMILAR TO VIKING G-2000RISER ASSEMBLY
12
13
PRESSURE GAUGE
14
15
3
3
SLEEVE WITH WATERPROOF SEAL
INCOMING FIRE
13
12
10
2
15
TO DRY-PIPE SPRINKLER MAIN
9
AIR COMPRESSOR FOR DRY-PIPESYSTEM. BASIS OF DESIGN SHALL BEGENERAL AIR PRODUCTS OLPLUSSERIES. FINAL SIZING OF AIRCOMPRESSOR SHALL BE BASED ONACTUAL SYSTEM VOLUME.
16
8
7
GENERAL FIRE PROTECTION NOTES FIRE PROTECTION NOTES FIRE PROTECTION ABBREVIATIONS FIRE PROTECTION SYMBOLS
FIRE PROTECTION DRAWING LIST
NOT TO SCALE1 INCOMING SERVICE DETAIL
A AMPERESAC AIR CONDITIONINGACS AUTOMATIC CONTROL SYSTEMAFF ABOVE FINISHED FLOORAHU AIR HANDLING UNITALUM ALUMINUMARCH ARCHITECT
BAD BOTTOM ANGULAR DISCHARGEBCP BOILER CIRCULATION PUMPBFP BOILER FEED PUMPBHD BOTTOM HORIZONTAL
DISCHARGEBP BOOSTER PUMPBT BATH TUB
C CONVERTORC CENTER LINEøC DEGREES CELSIUSCAC CONTROL AIR COMPRESSORCB CAST IRON BOOTCCP CENTRAL CONTROL PANELCCW COUNTER CLOCKWISECD CEILING DIFFUSERCFFC CAP FOR FUTURE CONNECTIONCFM CUBIC FEET PER MINUTECFP CHEMICAL FEED PUMPCH CHILLERCHWP CHILLER WASTE PUMPCLG CEILINGCO CLEANOUTCOND CONDENSATECONN CONNECTCONT CONTINUATIONCP CIRCULATION PUMPCU FT CUBIC FEETCU IN CUBIC INCHESCUH CABINET UNIT HEATERCV CHECK VALVECW COLD WATERCWP CONDENSATE WATER PUMP
D DROPDDC DIRECT DIGITAL CONTROLDFWP DEARATOR FEED WATER PUMPDF DRINKING FOUNTAINDG DIESEL GENERATORDHW DOMESTIC HOT WATERDIA DIAMETERDN DOWNDR DRAINDTL DETAILDWG DRAWINGDW DISH WASHER
EL ELEVATIONELEC ELECTRICELEV ELEVATOREQ EQUALESP ELEVATOR SUMP PUMPET EXPANSION TANKEM EMERGENCYEW EMERGENCY EYE WASHEWC ELECTRIC WATER COOLEREWT ENTERING WATER
TEMPERATURE EXP EXPANSION
F FILTERºF DEGREES FAHRENHEITFCO FLOOR CLEAN OUTFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFFE FINISHED FLOOR ELEVATIONFL FLOORFP FIRE PROTECTIONFPI FINS PER INCHFPM FEET PER MINUTEFPS FEET PER SECONDFS FLOOR SINKFT FEET
G GASG GAUGEGAL GALLONGCO GRADE CLEAN OUTGPH GALLONS PER HOURGPM GALLONS PER MINUTEGWH GAS WATER HEATER
H HUMIDIFIERHB HOSE BIBBHD HEADHP HORSE POWERHR HOURHT HEIGHTHTWP HIGH TEMPERATURE WATER
PUMPHW HOT WATERHWR HOT WATER RECIRCULATIONHWB HOT WATER BOILERHWP HOT WATER PUMP IN INCH OR INCHES
JC JANITOR'S CLOSETJS JANITOR'S SINK
KS KITCHEN SINK
L LENGTHLAV LAVATORYLBS POUNDSLCP LOCAL CONTROL PANELLIN .FT. LINEAR FEETL&S LIQUID & SUCTION LINESLWT LEAVING WATER TEMPERATURE
MB MIXING BOXMER MECHANICAL EQUIPMENT ROOMMAX MAXIMUMMHP MOTOR HORSEPOWERMIN MINIMUMMM MILLIMETERMR MOP RECEPTORMTD MOUNTED
NC NORMALLY CLOSEDNFWH NON-FREEZE WALL HYDRANTNIC NOT IN CONTRACTNO NORMALLY OPENNo NUMBERNPSH NET POSITIVE SUCTION HEADNTS NOT TO SCALE
OA OUTSIDE AIROAI OUTSIDE AIR INTAKEOAS OUTSIDE AIR SENSOROSA OUTSIDE AIROS&Y OUTSIDE SCREW & YOKE
P PUMPPD PUMP DISCHARGEPHC PREHEAT COILPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHPSIA POUNDS PER SQUARE INCH
ABSOLUTEPSIG POUNDS PER SQUARE INCH
GAUGE
R RISERD ROOF DRAINRAD RADIATIONREFR REFRIGERANTRF RETURN FANRH RELATIVE HUMIDITYRHC REHEAT COILRHWP REHEAT WATER PUMPRLA RUNNING LOAD AMPSRM ROOMRPM REVOLUTIONS PER MINUTERPZ REDUCING PRESSURE ZONE
BACKFLOW PREVENTER
S SOILSA SHOCK ABSORBERSAN SANITARYSCHWP SECONDARY CHILLED WATER
PUMPSD SMOKE DETECTORSF SUPPLY FANSHWP SECONDARY HOT WATER PUMPSH SHOWERSMK CTL SMOKE CONTROL OPERATIONSP STATIC PRESSURESPEC SPECIFICATIONSQ FT SQUARE FOOTSS STAINLESS STEEL
T THROATTEMP TEMPERATURETSP TOTAL STATIC PRESSURETV TURNING VANESTYP TYPICAL
UNO UNLESS OTHERWISE NOTEDUR URINAL
V VENTVTR VENT THROUGH ROOF
W WASTEW WIDTHW/ WITHWC WATER CLOSETWCA WATER CLOSET ACCESSIBLEWCO WALL CLEAN OUTWFU WATER FIXTURE UNITW/O WITHOUTWG WATER GAUGEWH WATER HEATERWHA WATER HAMMER ARRESTERWMB WASHING MACHINE BOXWPD WATER PRESSURE DROP
1. THE SUBMISSION OF A PROPOSAL BY THE CONTRACTOR IS NOTIFICATION THAT HE HAS TOTALLYFAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HASAGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATIONOF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BESTPRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.
2. THE CONTRACT DRAWINGS ARE PRESENTED TO THE CONTRACTOR WITH THE UNDERSTANDINGTHAT HE IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THEBASIS OF INFORMATION SUCH AS CONTAINED IN THE CONTRACT DOCUMENTS. IT IS THE INTENT OFTHE CONTRACT DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED ANDREADY FOR OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULESAND REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTEDNECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS SHALLBE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS SPECIFIED OR SHOWN ON THECONTRACT DRAWINGS. IF ANY DEPARTURES FROM THE CONTRACT DRAWINGS ARE DEEMEDNECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASON THEREFORE SHALL BE SUBMITTEDTO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVALOF THE ENGINEER.
3. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND ADVISE THE ARCHITECT OF ANYDISCREPANCIES BEFORE PERFORMING THE WORK.
4. THE CONTRACT DOCUMENTS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES ANDRELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES AND SERVICES TO BEPROVIDED. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATIONOF CONTRACT REQUIREMENTS TO BEST AVAILABLE STANDARDS AT THE SCALE INDICATED.
5. LAYOUT OF EQUIPMENT INDICATED ON THE CONTRACT DRAWINGS SHALL BE CHECKED AND
COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACTLOCATIONS USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICALINTERFERENCE OCCURS, CONSULT WITH ENGINEER AND PREPARE DATED, DIMENSIONED DRAWINGSCOORDINATED WITH ALL OTHER TRADES WORK IN THE AREA AND CORRECTING SUCHINTERFERENCES. OBTAIN WRITTEN APPROVAL OF ENGINEER FOR SUCH DRAWINGS AND DISTRIBUTESAME AS REQUIRED.
6. COORDINATE ALL WORK WITH THE OWNER AND ALL OTHER CONTRACTORS. SCHEDULE WORK INACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL THE WORK CAN BE INSTALLEDWITHOUT DELAYING THE PROJECT.
7. PREPARE FULLY DIMENSIONED FIELD INSTALLATION DRAWINGS. THESE DRAWINGS SHALL BEFORWARDED TO ALL CONTRACTORS. EACH CONTRACTOR SHALL SUBSEQUENTLY IN SUCCESSIONDELINEATE HIS RESPECTIVE WORK ON THESE COORDINATION DRAWINGS. WHEN ALL WORK HASBEEN PROPERLY SHOWN ON THE COORDINATION DRAWINGS, AND ALL CONTRACTORS AGREETHAT THEIR RESPECTIVE WORK CAN BE INSTALLED AND WILL PROPERLY FIT TOGETHER, THEYSHALL SO ACKNOWLEDGE BY ENDORSING THE DRAWING(S). ANY WORK DONE PRIOR TOCOMPLETION OF ABOVE COORDINATION PROCESS FOUND IN CONFLICT SHALL BE REMOVED ANDREPLACED AT CONTRACTOR'S EXPENSE.
8. SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.
9. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'SWRITTEN INSTRUCTIONS.
10. SCHEDULE ALL SHUTDOWNS THAT EFFECT UTILITIES AND PORTIONS OF THE BUILDING THATMUST REMAIN IN OPERATION WITH THE OWNER.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING AND PROTECTION OFMATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT.
12. WHERE PIPING PASSES THROUGH FIRE RATED FLOORS AND WALLS, THE PENETRATION SHALLBE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED AND ACCEPTED BY THEBUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THISMATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURERTO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, ANDCORING AS IT RELATES TO HIS WORK. CONTRACTOR SHALL SUBMIT SIZE AND LOCATION TO THESTRUCTURAL ENGINEER FOR REVIEW AND APPROVAL. STRUCTURAL ELEMENTS SHALL NOT BEPENETRATED WITHOUT PRIOR APPROVAL OF STRUCTURAL ENGINEER.
14. SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS. THISSCHEDULE SHALL IDENTIFY ALL PRODUCT DATA, DRAWINGS, ETC. TO BE SUBMITTED FOR THISPROJECT, INCLUDING ANY ANTICIPATED DATE OF EACH SUBMISSION. COMPLY WITH THEREQUIREMENTS OF DIVISION 1 OF THE SPECIFICATIONS. PROVIDE DRAWINGS OF ALL SPRINKLERPIPING, HEADS, VALVES, EQUIPMENT, MATERIALS, AND SIGNS FOR EACH FIRE PROTECTION SYSTEMTO BE INSTALLED. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO RECEIPT OFENGINEER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE REPLACED ATCONTRACTOR EXPENSE.
15. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATIONDRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMSPROVIDED. THE CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NOSUBMISSION SHALL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE CONTRACTOR. THECONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.
16. PROVIDE AS-BUILT DOCUMENTS AND OPERATING/MAINTENANCE MANUALS AS SPECIFIED INDIVISION 1 OF THE SPECIFICATIONS.
17. INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND ORVIBRATION THAT IS OBJECTIONABLE TO THE ENGINEER, ARCHITECT OR OWNER. OBJECTIONABLESOUND OR VIBRATION CONDITIONS SHALL BE CORRECTED IN APPROVED MANNER BY THECONTRACTOR AT HIS EXPENSE.
18. FURNISH ACCESS DOORS AS REQUIRED FOR OPERATION AND MAINTENANCE OF CONCEALEDEQUIPMENT, VALVES AND CONTROLS, ETC., AND COORDINATE THEIR DELIVERY WITH THEINSTALLING TRADE.
19. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALLDEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN ONE (1) YEARFROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIPDEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIALREPLACED WITHOUT ADDITIONAL COST.
20. NOTIFY ENGINEER OF ESTIMATED DATE OF COMPLETION OF ROUGH-IN WORK AND DATE OFBOTH WALL AND CEILING INSTALLATION. NOTIFICATION SHALL BE A MINIMUM OF ONE WEEK PRIORTO COMPLETION DATE TO ENABLE ENGINEER SCHEDULING OF PRELIMINARY PUNCHLIST INSPECTIONPRIOR TO WALL AND CEILING INSTALLATION. CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEEROF COMPLETION OF ALL WORK, INDICATING THE CONTRACTOR IS READY FOR THE ENGINEER TOPERFORM THE FINAL PUNCHLIST INSPECTION.
21. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER'S PUNCHLIST,THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETIONCERTIFYING THAT ALL PUNCHLIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS,ETC. HAVE BEEN SUBMITTED.
22. CONTRACTOR SHALL COORDINATE WORK WITH EEBA DETAILS SHOWN ON DRAWINGS A907THROUGH A908.
1. ALL EQUIPMENT AND MATERIALS USED AND WORK PERFORMED SHALL BE IN ACCORDANCE WITH RULESAND REGULATIONS LISTED IN "CODE SUMMARY" ON DRAWING CS001 IN ADDITION TO THE AUTHORITYHAVING JURISDICTION.
2. FIRE SUPPRESSION SYSTEMS, STANDPIPES, AND FIRE PUMPS SHALL BE INSTALLED INACCORDANCE WITH NEW JERSEY EDITION OF THE INTERNATIONAL BUILDING CODE, NFPA-13 ANDREQUIREMENTS.
3. THE ENTIRE SYSTEM SHALL BE DESIGNED UNDER THE SUPERVISION OF A PROFESSIONALENGINEER EXPERIENCED IN THE WORK AND LICENSED IN THE STATE OF NEW JERSEY. ALL LAYOUTSHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL BE SIGNED AND SEALED BY THEPROFESSIONAL ENGINEER.
4. FIRE PROTECTION CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH COMPLETE SET OFCONSTRUCTION DOCUMENTS, INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL,HVAC, PLUMBING, ELECTRICAL, AND SITE DRAWINGS.
5. PERFORM HYDRAULIC CALCULATIONS IN ACCORDANCE WITH NFPA-13 AND CRITERIA ASREQUIRED BY THE AUTHORITY HAVING JURISDICTION. ALL PIPE SIZES, NUMBER AND LOCATION OFHEADS, FLOW RATES, ETC. SHALL BE AS REQUIRED BY THE HYDRAULIC CALCULATION AND NFPA.WHERE FIELD CONDITIONS OR AUTHORITY HAVING JURISDICTION REQUIRES MORE HEADS OROTHER WORK BEYOND WHAT IS SHOWN ON THESE DRAWINGS, PROVIDE SAME AT NO COST TOOWNER.
6. CONDUCT A FLOW TEST IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE. CONTACT THELOCAL WATER COMPANY TO SCHEDULE THE TEST.
7. REQUIRED COPIES OF SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER'S INSURANCECARRIER FOR REVIEW AND APPROVAL. DISTRIBUTION AND ROUTING OF DRAWINGS SHALL BEDETERMINED AFTER AWARDING OF CONTRACT.
8. APPROVAL OF THE COMPLETE SYSTEM SHALL BE OBTAINED FROM THE AUTHORITIES HAVINGJURISDICTION, AND A COPY OF THE SAME SHALL BE DELIVERED TO THE OWNER'SREPRESENTATIVE AND ARCHITECT.
9. AFTER APPROVAL FROM THE OWNER'S INSURANCE COMPANY, SUBMIT TO THE ENGINEER FOR
APPROVAL ELECTRONIC COPIES OF HYDRAULIC CALCULATIONS AND SHOP DRAWINGS FOR THECOMPLETE FIRE PROTECTION SYSTEM. ALSO SUBMIT FOR APPROVAL THE MANUFACTURER'S NAME,FIGURE NUMBERS, OR OTHER MEANS OF IDENTIFICATION OF ALL PIPE FITTINGS, VALVES,SPRINKLERS AND OTHER MATERIAL REQUIRED FOR THE WORK.
10. ROUTE ALL SPRINKLER PIPING TO AVOID INTERFERENCE WITH LIGHTING FIXTURES, DUCTS,PIPING AND OTHER TRADES. ALL SPRINKLER PIPING IN FINISHED AREAS SHALL BE CONCEALED.
11. REFER TO THE FINAL ARCHITECT'S REFLECTED CEILING PLAN AND VERIFY ACTUAL FIELDCONDITIONS TO COORDINATE LOCATIONS OF SPRINKLER HEADS. COORDINATE SPRINKLER HEADLOCATIONS WITH LIGHTING, DIFFUSER LAYOUT, CEILING FANS, AND ANY OTHER OBSTRUCTIONS.
12. COORDINATE LOCATION, THREADS, AND TYPE OF FIRE DEPARTMENT CONNECTION WITH LOCALFIRE DEPARTMENT
13. COORDINATE ALL FIRE PROTECTION SHUTDOWNS WITH FIRE SUBCODE OFFICIAL. A MINIMUM OF48 HOURS NOTICE IS REQUIRED PRIOR TO COMMENCING WORK. PAY ALL CHARGES FROM THEFIRE DEPARTMENT AND STAND BY CREWS. SHUTDOWNS OF FIRE PROTECTION SYSTEM AFFECTINGOCCUPIED AREAS WILL NOT BE PERMITTED PRIOR TO 10:00 AM.
14. UNLESS INDICATED OTHERWISE ON THE CONTRACT DRAWINGS, FOR AREAS GOVERNED BYNFPA-13 STANDARD, ALL WET-PIPE SPRINKLER PIPING 3" AND SMALLER MAY BE BLAZEMASTERCPVC PLASTIC PIPE OR APPROVED EQUAL, LARGER THAN 3" UP SHALL BE SCHEDULE 10 STEELROLL GROOVED PIPES AND FITTINGS. ALL SPRINKLER PIPING SHALL BE INSTALLED INACCORDANCE WITH THEIR LISTING.
15. ALL DRY-PIPE SPRINKLER PIPING SHALL BE GALVANIZED STEEL.
16. THE FOLLOWING METHODS AND MATERIALS ARE NOT ACCEPTABLE:
A. SCHEDULE 5 PIPINGB. PRESS FITTINGSC. PLAIN END PIPING AND FITTINGS
17. REFER TO SPECIFICATIONS FOR ADDITIONAL PIPE MATERIAL INFORMATION.
18. UNLESS INDICATED OTHERWISE ON CONTRACT DRAWINGS, ALL SPRINKLERS LOCATED INPUBLIC AREAS AND DWELLING UNITS, REGARDLESS OF CEILING TYPE SHALL BE QUICK RESPONSE,SEMI-RECESSED TYPE. THE SPRINKLER ESCUTCHEON SHALL BE WHITE.
19. ALL SPRINKLERS LOCATED IN MECHANICAL ROOMS, ELECTRICAL ROOMS, WATER METERROOMS AND STORAGE ROOMS SHALL HAVE WIRE CAGES.
20. SPRINKLERS SHALL BE PROVIDED THROUGHOUT ALL CONCEALED SPACES OF COMBUSTIBLECONSTRUCTION IN ACCORDANCE WITH NFPA-13.
21. ALL FIRE PROTECTION WORK AS DESCRIBED IN CONTRACT DRAWINGS AND THESPECIFICATIONS SHALL BE DESIGNED AND BUILT BY A LICENSED FIRE PROTECTION CONTRACTOR.
22. SPRINKLER HEADS EXTENDING INTO UNHEATED SPACES SHALL BE PROTECTED FROMFREEZING. THE MINIMUM LENGTH OF THE EXPOSED DRY BARRELS OF DRY SPRINKLERSCONNECTED TO WET-PIPE SYSTEM SHALL BE 12".
23. CODE COMPLIANCE OF THE FIRE SUPPRESSION SYSTEM IS THE RESPONSIBILITY OF THE FIRESPRINKLER SUBCONTRACTOR. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DESIGNDOCUMENTS ARE SCHEMATIC ONLY. FIRE SPRINKLER SUBCONTRACTOR SHALL PROVIDE CODECOMPLIANT SHOP DRAWINGS TO THE AUTHORITY HAVING JURISDICTION FOR APPROVAL.
24. COORDINATE ALL ELECTRICAL WORK AND FIRE ALARM WORK WITH ELECTRICALCONSTRUCTION SECTION AND FIRE ALARM CONSTRUCTION SECTION.
25. PROVIDE ALL NFPA TEST REPORTS TO ENGINEER FOR REVIEW.
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
NO
TES,
SYM
BOLS
& A
BBR
EVIA
TIO
NS,
Thur
sday
, Mar
ch 3
, 201
6,3:
29 P
M©
201
6 - K
itche
n &
Asso
ciat
es.
All p
lann
ing
and
arch
itect
ural
con
cept
s sh
own
on th
is d
ocum
ent a
re th
e in
telle
ctua
l pro
perty
of K
itche
n &
Asso
ciat
es
FP000
03-03-1614204AD/SB
CPDate
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:2
1AI0
1218
000
Mar
y M
. Joh
anne
sen
CO
A#: 2
1AC
0008
2700
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
NOTES, SYMBOLS &ABBREVIATIONS
©20
15 -
Kitc
hen
& As
soci
ates
.
3
2 4
8
7
1
1
1
1
DW
R
R
6
5
9
9
9
KEYED NOTES
DRY-PIPE SPRINKLER SYTEM AREA. PROVIDE SEMI-RECESSED WHITECEILING SPRINKLERS WITH WHITE ESCUTCHEONS THROUGHOUT THE AREAINDICATED IN ACCORDANCE WITH NFPA 13 REQUIREMENTS. PROVIDEUPRIGHT SPRINKLERS THROUGHOUT CONCEALED SPACES CONSTRUCTEDOF COMBUSTIBLE MATERIALS IN ACCORDANCE WITH NFPA 13REQUIREMENTS.
4" INCOMING FIRE SUPPRESSION SERVICE.
4" DOUBLE CHECK DETECTOR BACKFLOW PREVENTER ASSEMBLY.
FIRE DEPARTMENT CONNECTION POINT OF CONNECTION TO FIRESUPPRESSION SYSTEM. PROVIDE CHECK VALVE WITH BALL DRIP IN WATERSERVICE ROOM. PIPE BALL DRIP TO FLOOR DRAIN.
FIRE DEPARTMENT CONNECTION PIPING BETWEEN FIRE DEPARTMENTCONNECTION AND POINT OF CONNECTION TO FIRE SUPPRESSION SYSTEM.
FIRE DEPARTMENT CONNECTION WITH ELECTRIC GONG LOCATED ABOVE.COORDINATE FINAL LOCATION AND INLET QUANTITY AND THREAD TYPEWITH FIRE MARSHAL PRIOR TO INSTALLATION.
SPRINKLER ZONE RISER WITH DRY ALARM CHECK VALVE AND BASEMOUNTED AIR COMPRESSOR.
DRY-PIPE SPRINKLER SUPPLY. PROVIDE MAIN AND BRANCH PIPING TOSPRINKLERS AS REQUIRED BASED ON FINAL DESIGN.
PROVIDE DRY SIDEWALL SPRINKLER COVERAGE BELOW EXTERIOR ROOF.
1
2
3
4
5
6
7
8
9
N
SCALE: 1/4" = 1'-0"1FIRST FLOOR PLAN
CA
MP
SALU
TE -
CLU
BH
OU
SE
PRO
GR
ESS
ISSU
E -
NO
T FO
R C
ON
STR
UC
TIO
N
BIM
Ser
ver:
bim
19.k
itche
nand
asso
ciat
es.c
om -
BIM
Ser
ver 1
9/14
204_
Cam
pSal
ute/
1420
4_C
ampS
alut
e_C
lub,
FIR
ST F
LOO
R P
LAN
,Thu
rsda
y, M
arch
3, 2
016,
3:29
PM
© 2
016
- Kitc
hen
& As
soci
ates
. Al
l pla
nnin
g an
d ar
chite
ctur
al c
once
pts
show
n on
this
doc
umen
t are
the
inte
llect
ual p
rope
rty o
f Kitc
hen
& As
soci
ates
FP101
03-03-1614204AD/SB
CPDate
Date:Job #:Drawn:Mngr:Revision
14204_CampSalute_Club
LIC
. #:2
1AI0
1218
000
Mar
y M
. Joh
anne
sen
CO
A#: 2
1AC
0008
2700
NO
RTH
DEL
SEA
DRI
VE
- BLO
CK
1601
, LO
T 13
BORO
UG
H O
F C
LAYT
ON
, NJ
0831
2
FIRST FLOOR PLAN
©20
15 -
Kitc
hen
& As
soci
ates
.