NTSMECHANICAL LEGENDS AND SCHEDULES M0.1
19.
CONNECTION INTO EXISTING
18.
17.
16.
15.
14.
13.
12.
11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.REFER TODRAWING/DETAIL NUMBER
SHEET NUMBER
RE: 2/M1.71
DRAWING NOTE REFERENCE (I.E., NOTES BY SYMBOL)1
MISCELLANEOUS
DRAWING/DETAIL REFERENCE
ABBREVIATIONS
GENERAL NOTES
MECHANICAL SYMBOLS AND ABBREVIATIONS NOTE: ALL SYMBOLS AND ABBREVIATIONS SHOWNARE NOT NECESSARILY USED ON THE DRAWINGS
DIFFUSER, GRILLE DESIGNATIONAMOUNT OF AIR
NECK SIZE OR WIDTH X HEIGHT (FOR LOUVERS)A 10X10
25020X20
20X20
20X20
20X20
18Ø
20X20
16X20
20X20 16Ø
SYMBOLSSYMBOL DESCRIPTION
18Ø
(4-WAY UNLESS OTHERWISE INDICATED)SQUARE CEILING DIFFUSER (SUPPLY)
(RETURN OR EXHAUST)
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
THERMOSTAT (OR) TEMP SENSOR
FIRE DAMPER
SQUARE CEILING GRILLE
DUCT SPLITTER WITH DAMPER
FD
M
T
or
VOLTSVUNIT HEATERUH
TRANSFER AIRT/ATHERMOSTAT, ROOM SENSORT, TSTATSPECIFICATIONSSPECSSQUARE FOOT, SUPPLY FANSF
SUPPLY AIRS/A
RETURN AIRR/A
PURGE EXHAUST FANPEFON CENTERO/C
MBH 1000 BRITISH THERMAL UNITS / HOUR
GALLONS PER MINUTEGPM
FLOORFLR
FT. FOOT, FEET
FD FIRE DAMPER
EF EXHAUST FANEDH ELECTRIC DUCT HEATER
EQUIPMENTEQUIP
DN DOWN
COOLING COILCC
CLG CEILING
BTU BRITISH THERMAL UNIT PER HOUR
W/OWB
UL
TSTAT
THRU
RMRLA
RE:
PSI
PROVIDEPH
O/AN/O,N/CN/A
MIN
MCA
LWTLRALB
L
kWJUNCTION BOX
INCH, INCHESHERTZ
HORSEPOWERHEIGHT
EXHAUST AIR
CONDENSING UNIT
AIR HANDLING UNIT
ABOVE FINISHED FLOORAFF
AHU
CU
E/A
HHP
HZIN.
J-BOX
F DEGREES FAHRENHEIT
KILOWATT
LENGTH
POUNDSLOCKED ROTOR AMPSLEAVING WATER TEMPERATURE
MINIMUM CIRCUIT AMPACITY
MINIMUM
NOT APPLICABLENORMALLY OPEN, NORMALLY CLOSEDOUTSIDE AIR/FRESH AIR
PHASEFURNISH AND INSTALL
POUNDS PER SQUARE INCH
REFERENCE, REFER
RUNNING LOAD AMPSROOM
THROUGH
THERMOSTAT OR ROOM SENSOR
UNDERWRITERS LABORATORIES, INC.
WET BULBWITHOUT
DEGREESDEG
FIRE SMOKE DAMPERFSD
APPROXIMATEAPPROX
ARCHITECT/ENGINEERA/E
EQUIPMENT DRAIND
EXISTING(E)
FAN COIL UNITFCU
ACCESS DOORADA/C AIR CONDITIONING UNIT
AIR FLOW SWITCHAFS
BRAKE HORSE POWERBHP
COMBUSTION AIRC/A
CUBIC FEET PER HOURCFHCUBIC FEET PER MINUTECFM
DB DRY BULB
ENTERING AIR TEMPERATUREEAT
ENTERING WATER TEMPERATUREEWT
FLA FULL LOAD AMPS
FPVAV FAN POWERED VAV
FEET WATER GAUGEFT. WGGA U.S. GAUGE
HEATING WATER RETURNHWRHWS HEATING WATER SUPPLY
INCHES WATER GAUGEIN.WG
LEAVING AIR TEMPERATURELATLPC LOW PRESSURE CONDENSATE
LOW PRESSURE STEAMLPS
HIGH PRESSURE CONDENSATEHPCHIGH PRESSURE STEAMHPS
MAXIMUMMAX
MFR MANUFACTURER
SMOKE DETECTORSD
VELOCITYVEL
WITHW/VARIABLE FREQUENCY DRIVEVFD
VAV VARIABLE AIR VOLUME
TOTAL STATIC PRESSURETSP
TYPICALTYP
OPPOSED BLADE DAMPEROBD
PRV PRESSURE REDUCING VALVE
REFRIGERANT LIQUIDRL
RS REFRIGERANT SUCTIONREVOLUTIONS PER MINUTERPM
D
R=3D/2
W
R=3W/2
20X20ACOUSTICAL DUCT LINING (FIGURESSHOWN ARE INSIDE DUCT DIMENSIONS
SUPPLY AIR DUCT UP (POSITIVE PRESSURE)
RETURN, EXHAUST OR OUTSIDE AIR INTAKEDUCT UP (NEGATIVE PRESSURE)
SUPPLY AIR DUCT DOWN (POSITIVE PRESSURE)
RETURN, EXHAUST OR OUTSIDE AIR INTAKEDUCT DOWN (NEGATIVE PRESSURE)
ROUND DUCT UP
TRANSITION CONCENTRIC UNLESS TOP LEVEL(TOP LVL)OR BOTTOM LEVEL(BOT LVL) IS NOTED
TRANSITION, RECTANGULAR TO ROUND CONCENTRICUNLESS TOP LEVEL (TOP LVL) OR BOTTOM LEVEL(BOT LVL) IS NOTED
ROUND DUCT RADIUS ELBOW
RECTANGULAR DUCT RADIUS ELBOW
RECTANGULAR DUCT SQUARE ELBOW WITHTURNING VANES
ROUND DUCT DOWN
20.
21.
22.
23.
ELEVATION NUMBERM301
1
SHEET NUMBER
FSD FIRE SMOKE DAMPER
PRIMARY MECHANICAL CODES:MECHANICAL: 2003 INTERNATIONAL MECHANICAL CODE (WITH CITY AMENDMENTS).ENERGY: 2003 INTERNATIONAL ENERGY CODE (WITH CITY AMENDMENTS).
PROJECT DESIGN VALUES:OUTDOOR DESIGN TEMPERATURE (SUMMER): 99 F (DRYBULB), 77 F (WETBULB)AMBIENT TEMPERATURE AT CONDENSING UNITS: 105 F (DRYBULB, SUMMER)OUTDOOR DESIGN TEMPERATURE (WINTER): 22 F (DRYBULB)INDOOR DESIGN TEMPERATURE (SUMMER): 75 F (DRYBULB), 50% (RELATIVE HUMIDITY)INDOOR DESIGN TEMPERATURE (WINTER): 72 F (DRYBULB)OUTSIDE AIR REQUIREMENTS: PER IMC TABLE 403.3
BUILDING AUTOMATION SYSTEMBAS
PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE CODES AND AUTHORITIESHAVING JURISDICTION. PROVIDE ALL PERMITS, INSPECTIONS, LICENSES AND FEES. FURNISHALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS NECESSARY TO PROVIDE COMPLETE ANDOPERATIONAL SYSTEMS.
THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL DESIGN AND ARRANGEMENTOF PIPES, FIXTURES, EQUIPMENT, SYSTEMS, ETC. INFORMATION SHOWN IS DIAGRAMMATIC INCHARACTER AND DOES NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC.DO NOT SCALE THE DRAWINGS FOR DIMENSIONS. TAKE ALL DIMENSIONS, MEASUREMENTS,EQUIPMENT LOCATIONS, LEVELS, ETC FROM THE ARCHITECTURAL DRAWINGS AND FROM THEEQUIPMENT TO BE FURNISHED. PIPING MAY BE RELOCATED OR OFFSET FOR PROPERCLEARANCES OR TO AVOID CONFLICTS WITH OTHER TRADES. THE DESIGN INTENT (I.E.PITCHES, VELOCITIES, PRESSURE DROPS, VOLTAGE DROPS, ETC) CANNOT BE GREATLYALTERED WITHOUT THE APPROVAL OF THE ARCHITECT. THE COST OF THESE DEVIATIONS TOAVOID INTERFERENCE'S SHALL BE PART OF THE ORIGINAL CONTRACT BID.
EACH SUBCONTRACTOR SHALL CONFER AND COOPERATE WITH ALL OTHER TRADES TOCOORDINATE THEIR WORK. COORDINATION SHALL INCLUDE, BUT SHALL NOT BE LIMITED TOMATERIALS AND EQUIPMENT ROUTED IN CEILING AND WALL CAVITIES, EQUIPMENTARRANGEMENT IN MECHANICAL SPACES, INCLUDING EQUIPMENT CLEARANCEREQUIREMENTS, ELEVATIONS AND DIMENSIONS OF STRUCTURAL MEMBERS AND OPENINGS,ETC. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY CONFLICTS.
BASE FINAL INSTALLATION OF MATERIALS AND EQUIPMENT ON ACTUAL DIMENSIONS ANDCONDITIONS AT THE PROJECT SITE. FIELD MEASURE FOR MATERIALS AND EQUIPMENTREQUIRING EXACT FIT. NO EXTRAS WILL BE GIVEN FOR THE CONTRACTORS FAILURE TOFIELD COORDINATE.
THE OWNER OR ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETYPRECAUTIONS OR FOR MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, ORPROCEDURES REQUIRED TO PERFORM THE WORK.
THE CONTRACTOR SHALL LOCATE ALL EQUIPMENT THAT MUST BE SERVICED, OPERATED, ORMAINTAINED IN FULLY ACCESSIBLE POSITIONS. EQUIPMENT SHALL INCLUDE (BUT NOTLIMITED TO) VALVES, MOTORS, CONTROLLERS, SWITCHGEAR, AND DRAIN POINTS IFREQUIRED FOR BETTER ACCESSIBILITY. FURNISH ACCESS DOORS FOR THIS PURPOSE.MINOR DEVIATIONS FROM THE DRAWINGS MAY BE ALLOWED TO PROVIDE FOR BETTERACCESSIBILITY. ANY CHANGES SHALL BE APPROVED BY THE ARCHITECT AND CONSTRUCTIONMANAGER/GENERAL CONTRACTOR PRIOR TO MAKING THE CHANGE.
THE CONTRACTOR SHALL PROVIDE ACCESS DOORS, WALL OPENINGS, ROOF OPENINGS ORANY OTHER CONSTRUCTION REQUIREMENT NEEDED TO ACCOMMODATE THE MECHANICALEQUIPMENT. LOCATIONS OF THESE OPENINGS SHALL BE SUBMITTED IN SUFFICIENT TIME TOBE INSTALLED IN THE NORMAL COURSE OF WORK.
THE CONTRACTOR SHALL COORDINATE ELECTRICAL REQUIREMENTS OF APPROVEDEQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO THE PURCHASE ANDINSTALLATION OF ANY ELECTRICAL GEAR OR CONDUIT.
GENERAL CONTROL WIRING, THERMOSTATS, MOTORIZED DAMPERS AND CONDUIT ASSOCIATEWITH HVAC EQUIPMENT IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTORSHALL COORDINATE THE LOCATION OF ALL THERMOSTATS, ROOM SENSORS, ETC WITH THEARCHITECT AND ALL OTHER TRADES PRIOR TO INSTALLATION. IF A CONFLICT WITHMILLWORK, LIGHT SWITCHES, WINDOWS, ETC EXISTS, THE CONTRACTOR SHALL NOTIFY THEARCHITECT OF THE POTENTIAL INTERFERENCE PRIOR TO INSTALLATION. INSTALLTHERMOSTATS WITH PROTECTIVE LOCKING COVER, CENTERED AT 4'-0" ABOVE FINISHEDFLOOR, UNLESS OTHERWISE INDICATED. COMPLY WITH THE PROVISIONS OF THE AMERICANSWITH DISABILITIES ACT (ADA) AND THE TEXAS ACCESSIBILITY'S STANDARD (TAS).
ALL DIMENSIONS SHOWN ON THE DRAWINGS FOR DUCTWORK ARE NET INSIDE CLEARDIMENSIONS. FOR RECTANGULAR DUCT, THE FIRST FIGURE OF THE DUCT SIZE INDICATESTHE DIMENSION OF THE FACE SHOWN. VERIFY THAT THE DUCTWORK SPECIFIED WILL FIT INTHE SPACE AVAILABLE USING THE ARCHITECTURAL, STRUCTURAL AND ELECTRICALDRAWINGS AS REFERENCE PRIOR TO FABRICATION AND INSTALLATION. ROUND DUCT OFEQUAL NET INSIDE CLEAR AREA MAY BE USED IN LIEU OF RECTANGULAR DUCT.
PROVIDE TURNING VANES ON ALL RECTANGULAR SUPPLY, EXHAUST AND RETURNDUCTWORK INCLUDING THE TOP AND BOTTOM OF VERTICAL DUCTS.
PROVIDE A LOCKING QUADRANT VOLUME DAMPER AT THE TAP OF EACH RUN-OUT TODIFFUSERS FOR BALANCING PURPOSES, UNLESS OTHERWISE INDICATED. THE RUN-OUTDUCT SIZE IS THE SAME SIZE AS THE DIFFUSER OR GRILLE NECK SIZE UNLESS OTHERWISEINDICATED.
CEILING SPACE IS NEEDED AS A RETURN AIR PLENUM IN CERTAIN AREAS. FOLLOW ALLAPPLICABLE CODES AS TO MATERIALS ALLOWED FOR USE IN AIR PLENUMS. COORDINATEWITH THE GENERAL CONTRACTOR TO PROVIDE FREE RETURN OF AIR FROM ALL LOCATIONS.
REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF ALL FIRE RATED WALLS ANDCEILINGS. PROVIDE FIRE DAMPERS AND/OR COMBINATION FIRE/SMOKE DAMPERS INDUCTWORK AT ALL LOCATIONS WHERE DUCTS PASS THROUGH FIRE RATED ASSEMBLY.MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROVIDING FIREAND SMOKE DAMPERS. COORDINATE CONSTRUCTION REQUIREMENTS WITH GENERALCONTRACTOR.
LOCATION OF ALL GRILLES, REGISTERS, DIFFUSERS AND CEILING DEVICES SHALL BEDETERMINED FROM THE ARCHITECTURAL REFLECTED CEILING PLANS AND WALL SECTIONS.COORDINATE ALL CEILING DIFFUSERS AND GRILLE LOCATIONS WITH LOCATION OF LIGHTS.
ALL DUCTWORK SHALL BE SHEET METAL FABRICATED IN ACCORDANCE WITH SMACNASTANDARDS. ALL DUCT WORK FROM AHU TO TERMINAL UNIT SHALL BE CONSTRUCTED TO 1"W.G. AND SEALED TO SMACNA CLASS A. DUCT WORK DOWN STREAM OF TERMINAL UNITSSHALL BE CONSTRUCTED TO 1/2" W.G. AND SEALED TO SMACNA CLASS C. SEAL ALL SEAMSWITH UL 181 MASTIC RATED FOR APPLICATION.
INSTALL DX PIPING AS SPECIFIED, INCLUDING FILTER/DRYER, SIGHT GLASS,ISOLATION/CHARGING VALVES AND ALL APPURTENANCES PER MANUFACTURER'SRECOMMENDATIONS. INSTALLATION SHALL BE ACCOMPLISHED IN A NEAT AND ORDERLYFASHION, AS APPROVED BY THE ENGINEER. COORDINATE FOR ROUTING OF DX PIPING, UPINSIDE OF WALLS, ETC. AS REQUIRED, TERMINATING AT AHU's. PROVIDE BRACING/ISOLATION,AS REQUIRED TO PREVENT VIBRATION OF DX PIPING INSIDE WALLS, ETC. SIZE, ROUTE ANDINSULATE DX PIPING PER MANUFACTURER'S RECOMMENDATIONS AND SPECIFICATIONREQUIREMENTS.
PROVIDE VIBRATION ISOLATORS FOR MOTOR DRIVEN EQUIPMENT UNLESS NOTEDOTHERWISE. PROVIDE ISOLATION AS INDICATED OR AS RECOMMENDED BY THE EQUIPMENTMANUFACTURER.
SOME PIPES AND DUCTS SHOWN ON EACH FLOOR PLAN MAY BE SHOWN WITH AN OFFSETFOR CLARITY.
SEAL ALL PIPE AND DUCT PENETRATIONS THROUGH FIRE RATED BUILDING ELEMENTS WITHAN APPROVED FIRE PROOFING MATERIAL.
ALL EQUIPMENT SHALL HAVE IDENTIFICATION TAGS. TAGS SHALL BE PLASTIC LAMINATE,WHITE FACE WITH 1/2" TALL BLACK LETTERS. THE TAG SHALL MATCH THE UNITDESIGNATIONS SHOWN ON THE SCHEDULES.
THE CONTRACTOR SHALL EXPAND OR REDUCE DUCTS AT EQUIPMENT CONNECTIONS BASEDON THE EQUIPMENT PURCHASED, WITH TRANSITIONS NOT TO EXCEED 30 DEGREES. SIZESSHOWN ON SCHEDULES, ETC. ARE FOR GUIDANCE ONLY. ASPECT RATIO SHALL BE NOGREATER THAN 4:1, PER SMACNA'S GUIDELINES.
ALL DUCTS WITH A DIMENSION GREATER THAN 12" PASSING THRU A NON-RATED WALL SHALLHAVE THE OPENING FRAMED IN WITH METAL STUDS. CONTRACTOR SHALL COORDINATEOPENING SIZE AND LOCATION WITH OTHER TRADES.
PRIOR TO INSTALLATION COORDINATE ALL MECHANICAL WORK WITH PNEUMATIC TUBESYSTEM BY OTHERS..
EQUIPMENT TO BE REMOVED(D)
EQUIPMENT TO BE RELOCATED(R)
(N) NEW EQUIPMENT
24.
FOR
T W
OR
TH, T
EX
AS
761
16
2570
RIV
ER
PA
RK
PLA
ZA S
UIT
E 1
00
EM
AIL
: m
ail@
schw
arz-
hans
on.c
om
FAX
: 81
7-37
7-36
12
PH
ON
E:
817-
377-
3600
A N
EW
LE
AS
E F
AC
ILIT
Y F
OR
CIT
Y O
F W
ES
TWO
RTH
VIL
LAG
E, T
EX
AS
C. C
ON
NE
LLY
SU
RV
EY
AB
STR
AC
T N
o. 3
19 T
AR
RA
NT
CO
., TX
2/6/2012
4458.2.6.2012.11107
18"x
14"
10"
AHU-1
EF-3
A640
B10260
A635
A640
A10210
A12430
A10365 A12
430
G22/22
G22/22
B10360
G22/22
B10250
E8250
M8M8
E8250
E8250
A12345
A695
VAV-2-3
VAV-2-2
VAV-2-1
EF-2
VAV-1-3
VAV-2-1
VAV-1-1
G22/22
E12255
B10270
EF-1
E12255
G22/22
G22/22
18"x
16"
AC-1
CU-1 HP-1
T
T
T
T
TT
14"
G22/22
A10240
6"
16"x12"
20"x12"
8"
2 23 3L6/6
6
L6/6
L6/6
1
5 5
1
8
8
55
5
5
8
5
G22/22
5
4
7
7
1
16"x12" 8
G22/22 5
16"x12"
T CCP
16"x12" 8
20"x12" 8
10"x8"8
16"x16"8
VAV-1B
HP-2
10
9
10
VAV-2B
6"
14"x
14"
18"x18"
AHU-2
6"
16"x
14"
2
3
40"x
18"
40"x18"
11
1
1
1
1
1
1
12
13
13
1415
15
15
100
101
102
103
104
104B
105
106
107
108
109
110
111
112
114
113
115
118
116
117
119
120
16
1/8" = 1'-0"MECHANICAL FLOOR PLAN
8'
1/8"=1'-0"
0 8' 16' M2.1
NOTES #
1 EQUIPMENT AND DUCTWORK ROUTED IN PLENUM SPACE BELOW ATTICINSULATION.
2 REFRIGERANT LINES SUPPORT ON AND CLAMP TO UNI-STRUT CHANNEL ANCHOREDTO PAD 48" O.C.. PAINT ELECTROMETRIC INSULATION WITH TWO COATS UV RATEDPAINT. INSULATED REFRIGERANT LINES - ROUTE UP THRU STUD WALL CAVITY TOABOVE CEILING. PROVIDE WALL SUPPORT. CAULK AROUND EXTERIOR WALLPENETRATIONS.
3 SPLIT SYSTEM OUTDOOR UNIT, PAD AND ANCHORS SHALL BE RATED FOR 150MPH WIND CRITERIA.
4 DUCTLESS SPLIT SYSTEM AIR HANDLER (AC-1) LOCATED IN CEILING GRID SUPPORT FROMSTRUCTURE PER MANUFACTURES RECOMMENDATIONS.
5
67
LINED 22X22 DUCT ELBOW FROM GRILLE (MARK G22/22). SEE 'RETURN GRILLEDETAIL' ON SHEET M6.1.
8
9
PROVIDE CONDENSATE OVERFLOW ALARM
10
1112
MOUNT CENTER LINE OF SLOT DIFFUSERS AT 10'-6" A.F.F.LINED TRANSFER DUCT. SEE 'ACOUSTICALLY LINED TRANSFER DUCT DETAIL' ONSHEET M6.1.PREBALANCE TO CFM INDICATED. TYPICAL FOR SLOT DIFFUSERS IN VESTIBULE.RETURN DUCT FULL SIZE OF CONNECTION. ROUTE UP THRU METAL DECK ANDTERMINATE.INSTALL SMOKE DETECTOR IN RETURN DUCT OF AHU-2.
ROOM SCHEDULENUMBER NAME
100 VESTIBULE101 GREETER102 LOBBY103 WAITING AREA104 TRAINING ROOM
104B COAT CLOSET105 MSR 1106 MSR 2107 ASSISTANT MANAGER108 MANAGER109 MSR110 WOMEN'S TOILET ROOM111 CORRIDOR112 MEN'S TOILET ROOM113 TELE/COMM/ELEC ROOM114 BREAK ROOM115 JANITOR'S STORAGE CLOSET116 VAULT ROOM117 WORK ROOM118 TELLER AREA119 IRT / ATM PROCESSING AREA120 EXPRESS AREA
INSTALL HVAC CENTRAL CONTROL UNITS THIS LOCATION.
SEQUENCE OF OPERATIONAHU-1 AND AHU-2:
THE CENTRAL CONTROL PANEL SHALL INDEX THE AHU FOR "OCCUPIED" PERIODS BASED ONUSER DEFINED, PROGRAMMABLE. DURING "OCCUPIED" MODE, THE CONTROL SYSTEM SHALLBE PLACED IN OPERATION, THE OUTSIDE AIR DAMPER SHALL OPEN AND THE SUPPLY FANSHALL RUN CONTINUOUSLY. THE CENTRAL CONTROL PANEL SHALL CONTROL, IN SEQUENCE,THE HEATING MODE AND COOLING MODE ACCORDING TO THE ZONE TEMPERATURE SENSORSSETPOINTS.
OCCUPIED OPERATION:
UNOCCUPIED OPERATION:THE CENTRAL CONTROL PANEL SHALL INDEX THE AHU FOR "UNOCCUPIED" PERIODSBASED ON USER DEFINED OCCUPANCY SCHEDULE. DURING "UNOCCUPIED" MODE THE UNITFAN, HEATING, AND COOLING SHALL CYCLE TO MAINTAIN THE HEATING AND COOLING SETPOINTS (64 F HEATING ADJ, 81 F COOLING ADJ) AND THE OUTSIDE AIR DAMPER SHALLREMAIN CLOSED.COOLING MODE:UPON A MAJORITY CALL FOR COOLING BY THE ZONE TEMPERATURE SENSORS, THECOMPRESSOR(S) SHALL BE ENERGIZED. WHEN ALL ZONE TEMPERATURE SENSORSHAVE BEEN SATISFIED, THE REVERSE SHALL OCCUR.
HEATING MODE:
BYPASS VAV SYSTEM OPERATION:ZONE CONTROL DAMPERS, BYPASS DAMPER, ZONE TEMPERATURE SENSORS, BYPASSCONTROLLER, CENTRAL CONTROL PANEL WITH PROGRAMMABLE TIME CLOCK AND ALLACCESSORIES NECESSARY FOR AN OPERABLE PRESSURE INDEPENDENT BYPASS VAVSYSTEM, SHALL BE PROVIDED BY A SINGLE VENDOR IN COORDINATION WITH THEPACKAGED HEATING AND AIR CONDITIONING UNITS MANUFACTURERS.
ZONE CONTROL DAMPERS SHALL BE UNDER CONTROL OF THEIR RESPECTIVE ZONETEMPERATURE SENSORS.DURING COOLING, THE ZONE DAMPERS SHALL MODULATE CLOSED ON A FALL IN ZONETEMPERATURE BELOW THE SET POINT (76 ADJ), ON A RISE IN ZONE TEMPERATUREABOVE THE SET POINT (76 ADJ), THE REVERSE SHALL OCCUR.DURING HEATING, THE ZONE DAMPER OPERATION SHALL REVERSE CONTROL ACTIONSUCH THAT ON A FALL IN ZONE TEMPERATURE BELOW THE SET POINT (68 ADJ), THEZONE DAMPER SHALL MODULATE OPEN, ON A RISE IN ZONE TEMPERATURE ABOVE THESET POINT (68 ADJ), THE REVERSE SHALL OCCUR.
COOLING AND HEATING OPERATION SHALL BE ESTABLISHED BY SYSTEM VENDORSSTANDARD METHODS. DUCT DISCHARGE STATIC PRESSURE SHALL BE CONTROLLEDSUCH THAT IN A RISE IN DUCT STATIC PRESSURE ABOVE SETPOINT, THE BYPASS DAMPERSHALL MODULATE OPEN. ON A FALL IN DUCT STATIC PRESSURE THE REVERSE SHALLOCCUR. SET POINT SHALL BE COORDINATED WITH EQUIPMENT VENDOR.
START-UP AND FIELD TEST FOR PROPER OPERATION OF ALL AHUs SHALL BEACCOMPLISHED BY, OR BE UNDER DIRECT SUPERVISION OF, A TECHNICIAN CERTIFIED BYTHE MANUFACTURER. (2) COPIES OF THE START-UP REPORT SHALL BE SENT TO THEENGINEER PRIOR TO FINAL ACCEPTANCE.
EF-2 AND EF-3EXHAUST FANS SHALL BE CONTROLLED BY THEIR RESPECTIVE LIGHT SWITCH.
EF-1:EXHAUST FAN SHALL BE INTERLOCKED WITH AHU-1 AND SHALL OPERATE AS FOLLOWS:EXHAUST FAN SHALL BE ENERGIZED WHEN AHU IS INDEXED FOR "OCCUPIED" MODE.WHEN AHU IS INDEXED FOR "UNOCCUPIED" MODE, THE EXHAUST FAN SHALL BE DE-ENERGIZED.
DUCTLESS SPLIT SYSTEM:
ON A RISE IN SPACE TEMPERATURE ABOVE THE THERMOSTAT SET POINT (76 F ADJ.),THE COMPRESSOR(S) SHALL BE ENERGIZED. ON A DROP IN TEMPERATURE THEREVERSE SHALL OCCUR.
CU-1 AND AC-1:COOLING MODE:
UPON DETECTION OF WATER IN THE CLOGGED PRIMARY LINE, THE ALARM WILLACTIVATE AN LED AND BUZZER, AND IT WILL DE-ENERGIZE THE CONDENSINGUNIT. WHEN THE ALARM CONDITION IS RESOLVED AND PROBES ARE DRIED, THESYSTEM WILL BE AUTOMATICALLY RESET TO NORMAL OPERATION.
CONDENSATE OVERFLOW DETECTION ALARM:
ON A DROP IN SPACE TEMPERATURE BELOW THE HEATING SET POINT (68 F ADJ) THEHEAT PUMP SHALL BE ENERGIZED. ON A CONTINUED DROP IN SPACE TEMPERATURE,THE ELECTRIC HEATING ELEMENT SHALL BE ENERGIZED. ON A RISE IN SPACETEMPERATURE ABOVE THE HEATING SET POINT (68 ADJ) THE REVERSE SHALL OCCUR.ON A DROP IN OUTDOOR TEMPERATURE BELOW 35 F (ADJ), THE HEAT PUMP SHALL BEDE-ENERGIZED AND THE ELECTRIC HEATING ELEMENT SHALL BE ENERGIZED TOMAINTAIN THE HEATING SETPOINT.
A DUCT MOUNTED SMOKE DETECTOR SHALL BE MOUNTED IN THE RETURN AIRDUCT OF AHU-1. UPON DETECTION OF PRODUCTS OF COMBUSTION AS SENSEDBY THE DETECTOR, THE DETECTOR SHALL SHUT DOWN THE FAN MOTOR ANDCONTROL SYSTEMS FOR THE RTU AND ACTIVATE A VISIBLE AND AUDIBLESUPERVISORY SIGNAL ON SYSTEM SENSOR SSK451 MULTI-SIGNALINGACCESSORY. RESET SHALL BE MANUAL.
SMOKE DETECTOR:
13 MOTORIZED DAMPER TO BE INTERLOCKED WITH AHU. DAMPER IS TOCLOSE WHEN AHU FAN IS OFF AND OPEN WHEN AHU FAN IS ON.
14 PROVIDE INSULATED SHEET METAL PLENUM FULL SIZE OF LOUVER AND18" DEEP. SEE ARCHITECTURAL DRAWINGS FOR LOUVER LOCATION ANDSIZE.
15 MOUNT GRILLE IN SOFFIT, TRANS AT GRILLE AS REQUIRED.
COORDINATE DUCT ROUTE WITH STRUCTURAL.
FOR
T W
OR
TH, T
EX
AS
761
16
2570
RIV
ER
PA
RK
PLA
ZA S
UIT
E 1
00
EM
AIL
: m
ail@
schw
arz-
hans
on.c
om
FAX
: 81
7-37
7-36
12
PH
ON
E:
817-
377-
3600
A N
EW
LE
AS
E F
AC
ILIT
Y F
OR
CIT
Y O
F W
ES
TWO
RTH
VIL
LAG
E, T
EX
AS
C. C
ON
NE
LLY
SU
RV
EY
AB
STR
AC
T N
o. 3
19 T
AR
RA
NT
CO
., TX16
2/6/2012
4458.2.6.2012.11107
NTSMECHANICAL DETAILS M6.1
1" ACOUSTICALDUCT LINER
DUCT SUPPORTEDFROM STRUCTUREABOVE
CEILING GRID
30" MINIMUM
RETURN GRILLE DETAILNO SCALE
RETURN GRILLE (G22/22)
FLEXIBLE DUCT CONNECTION DETAILNO SCALE
FACTORY INSULATED FLEXIBLE DUCTFULL NECK SIZE OF DIFFUSER6'-0" MAXIMUM LENGTH
VOLUME DAMPER
SEALANT AND CLAMPS
SEALANT AND CLAMPS
CEILINGINSULATION
RIGID DUCT MINIMUMLENGTH OF 2 TIMES THEDUCT DIAMETER
DIFFUSER
PARTITION
6' MIN.,TYP.
PLAN VIEW
PARTITION
1" ACOUSTICALDUCT LINER
CEILING GRID
HEIGHT
SECTION VIEW
MINIMUM LENGTHEQUAL TO THEHEIGHT
ACOUSTICALLY LINEDTRANSFER DUCT DETAILNO SCALE
NOTE: SEE PLAN FOR INSIDE CLEAR DIMENSION.
2. STAINLESS STEEL CLAMPS SHALL BE USED TO SECURE FLEX DUCT.
FLEX. CONNECTION
SUPPLY DUCT
CONTROL PANEL
NOTE 1
BOX INLETPRIMARY AIR
TRANSITION TO DUCT SIZE, AS REQ'D.
HIGH PRESSURE FLEXIBLE DUCTMAX. 2 FT LENGTH
DUCT SHALL BE 2" LARGER THANBOX VALVE SIZE.
NOTES:
DUCT CONNECTION TO BE SAME SIZE AS INLET. WITH A MINIMUM STRAIGHTSECTION OF 4Ø OR AS RECOMMENDED BY MANUFACTURER.
1.
W/ AVERGING AIR FLOW SENSOR
3. SUPPORT BOX FROM STRUCTURE WITH ALL THREAD RODS.PROVIDE VIBRATION ISOLATION AS REQUIRED.
AIR
FLO
W
SUPPLY AIR DEVICE, AND OTHERWISE AS INDICATED.REQ'D AT EACH RUN-OUT TAP TO EVERY TERMINAL
FLOWAIR
DAMPER W/ SHAFT EXTENSIONLOCKING QUADRANT
CONICAL SPIN TAP
AND 2" BUILD OUT
STRUCTURE ABOVE
OR WALL CAPTO LOUVER
EXHAUST GRILLE
EXHAUST FANWITH INTEGRALBACKDRAFT DAMPER
CEILING OR STRUCTURE
M
RETURN AIR DUCT
SEE DETAIL NOTE 3
SUPPLY AIR DUCT
FLEX CONNECTION (TYPICAL)
STRUCTURE
VIBRATION ISOLATORS
6.
1.
2.
3.
5
4.
NOTES FOR DETAIL:
MECHANICAL CONTRACTOR TO SUSPENDFROM STRUCTURE. USE 3"x3"x1/4" PAINTEDOR GALVANIZED ANGLE SUSPENDED USING3/8" ALL THREAD RODS.
EXTERIOR WALL
CLEARANCE ZONE FOR
DISCONNECT (TYPICAL)
CLEARANCE ZONE FOR
DISCONNECT (TYPICAL)
NOTE 3 EXTERIOR WALLOF BUILDING
NOTE 4NOTE 4
36"
15" 15"
30"
36"
15" 15"
30"
TYPICAL AHU DETAILNO SCALE
TYPICAL OUTDOOR UNIT DETAILNO SCALE
TYPICAL TERMINAL UNIT DETAILNO SCALE
TYPICAL EXHAUST FAN DETAILNO SCALE
TYPICAL TAP DETAILNO SCALE
FOR
T W
OR
TH, T
EX
AS
761
16
2570
RIV
ER
PA
RK
PLA
ZA S
UIT
E 1
00
EM
AIL
: m
ail@
schw
arz-
hans
on.c
om
FAX
: 81
7-37
7-36
12
PH
ON
E:
817-
377-
3600
A N
EW
LE
AS
E F
AC
ILIT
Y F
OR
CIT
Y O
F W
ES
TWO
RTH
VIL
LAG
E, T
EX
AS
C. C
ON
NE
LLY
SU
RV
EY
AB
STR
AC
T N
o. 3
19 T
AR
RA
NT
CO
., TX
2/6/2012
4458.2.6.2012.11107