mechanism of lightning and the latest lightning protection
TRANSCRIPT
Mechanism of lightning
and the latest lightning protection
1
LIGITNING PROTEC TAKETANI Co., Ltd.
and the latest lightning protection
Mechanism of lightning
Inside of water droplets in the air, polarization continues to occur at all the time due to
the electrical field 0.0001[V/m] which exists on the surface of the ground. When this
droplets is mechanically divided, the charge should also be divided into + and .
If many droplets with same polarity gather and move at the same time due to the
turbulence in the air, a part of cloud comes to have opposite polarity. The charge in the
bottom part of cloud induces opposite charge on the surface of the ground.
2LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 1. Charge which affects thundercloud and the ground
― ― ― ―― ― ――
+ + + + +
E : electric field
ground
As the water droplets with same polarity gather at once, a part of the electrical
field comes to exceed the dielectric strength of the air.
Afterward a discharge path is formed and the so-called stepped leader moves
toward the ground step by step.
Mechanism of lightning
the edge of the stepped leader
3LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 2. Gradual growth of stepped leader and occurrence of trapped discharge
+ + + + + + ground
trapped
discharge
the edge of the stepped leader
Mechanism of lightning
An enough charge for ionizing air is supplied from the cloud to the lightning discharge
path. It is said that the radius of space column influenced by the lightning is 500m.
It is known that the standard wave form is 10µs in crest length and 350µs in wave tail.
If this value is analyzed in Fourier series, you will find that this value is the sum of the
direct current and high frequency current with several kHz to hundreds of kHz.
rCharge with high frequency returns up to the
4LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 3. Return of the charge flowing to the cloud through the capacitance
― ― ――
Charge with high frequency returns up to the
cloud through the capacitance
⇒Subsequent stroke occurs due to the
returning charge
―ground
① LPL Ⅰ nuclear power plant / chemical plant /
installation with risk of explosion / large-scale computer center
② LPL Ⅱ industry plant / hospital / big banks / corporate headquarters
③ LPL Ⅲ and Ⅳ general office / administrative department
Lightning protection level
Protection efficiency of Lightning protection
Selected range of lightning current peak value
5LIGITNING PROTEC TAKETANI Co., Ltd.
Protection efficiency of
LPS
Lightning protection
levelmax. current min. current
0.98 Ⅰ 200 kA 2.9 kA
0.95 Ⅱ 150 kA 5.4 kA
0.90 Ⅲ 100 kA 10.1 kA
0.80 Ⅳ 100 kA 15.7 kA
source: IEC61024-1-1
Lightning current components
Figure 4. Definition of impulse current
which has crest length T and wave tail T
crest
length wave tail
6LIGITNING PROTEC TAKETANI Co., Ltd.
which has crest length T1 and wave tail T2
Lightning protection level
Ⅰ Ⅱ Ⅲ Ⅳ
Possibility of lightning
current peak value is below
the specified value99% 98% 97% 97%
Possibility of lightning
current peak value exceeding
the specified value1% 2% 3% 3%
See specified value in table on page 7. source: IEC62305-1
Occurrence probability of the lightning current
occurrence
probability
7LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 5. Distribution for occurrence probability of
lightning current peak value indicated by CIGRE
(CIGRE: Conference Internationale des Grands Reseaux Electriques a haute tension)
1 : first negative downward flash
2 : second negative downward flash
3 : positive lightning stroke
Distribution of lightning current
100kV
electrical device
power supply
structureair termination rod
lightning current path
electrical device
conductor
high
voltage
6.6kVpower supply
8LIGITNING PROTEC TAKETANI Co., Ltd.
electrical device
earthing for
enclosure of device
Figure 6. Condition of distribution of lightning current which strikes the air termination rod
ground resistance of structure 2Ω
earthing for
low voltage coil of
transformer
Induced voltage caused by lightning currentIn the case that
the electrical installation circuit is separated from the down conductor
lightning current
9LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 7. Mutual Inductance M2 in the case that the square circuit of electrical
installation inside of the structure is separated from the down conductor and separated
distance is S
Difference of lightning current waveform
waveform
[µs]
peak current
[kA]
total charge amount
[kAs]
ratio
(direct/induced)
Direct lightning
current10/350 100 0.04863852 24.92171277
Induced impulse
current8/20 100 0.001951652 ―
10
Figure 8. Comparison of waveform between direct lightning current and
induced impulse current
LIGITNING PROTEC TAKETANI Co., Ltd.
--- 10/350 (peak value : 100kA)
― 8/20 (peak value : 100kA)
Characteristic values of lightning current in each LPL
LPL
sign unit ⅠⅠⅠⅠ ⅡⅡⅡⅡ ⅢⅢⅢⅢ/ⅣⅣⅣⅣ
first stroke
peak value
of first stroke currentI max kA 200 150 100
charge of
first stroke currentQ short C 100 75 50
specific charge energy
of first stroke currentW/R MJ/Ω 10 5.6 2.5
wave form T1/T2 µs/µs 10/350 10/350 10/350
11LIGITNING PROTEC TAKETANI Co., Ltd.
wave form T1/T2 µs/µs 10/350 10/350 10/350
subsequent
stroke
peak value
of subsequent strokeI max kA 50 37.5 25
average steepness of
current rise of
subsequent stroke current
di/dt kA/µs 200 150 100
wave form T1/T2 µs/µs 0.25/100 0.25/100 0.25/100
long stroke
long stroke chargeQ long C 200 150 100
duration of
long stroke currentT long S 0.5 0.5 0.5
Operating characteristic
IEC 61643-1 : 1998
Surge protective devices connected to low-voltage power distribution systems
- Part 1 : Performance requirements and testing methods.
Typical SPD
voltage switching type SPD ( air gap ) … Class Ⅰ(Figure 9)
voltage limiting type SPD ( ZnO varistor ) … Class Ⅰ(Figure10)
(10/350µs) (10/350µs)
12LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 9. Terminal voltage change during
operation of voltage switching type SPD
Figure 10. Terminal voltage change during
operation of voltage limiting type SPD
SPD energy coordination
SPD is basically installed at the transition point of interface in the LPZ as this figure
shows.
Impulse withstand categories for each circuits or devices are determined in
accordance with each LPZ.
LPZ1
impulse withstand category ⅣⅣⅣⅣ : 6 kV
LPZ0
13LIGITNING PROTEC TAKETANI Co., Ltd.
Figure11. Energy coordination between lightning current arrester(classⅠⅠⅠⅠ)
and surge arrester(classⅡⅡⅡⅡ)
service entrance for
electrical power line
(the transition point of
interface in the LPZ ) lightning current arrester (classⅠⅠⅠⅠ)
wave from (10/350µs)
surge arrester (class ⅡⅡⅡⅡ)
wave form (8/20µs
decoupling inductance
Type 1 varistor-based SPD Type 1 spark-gap-based SPD
Comparison of the coordination behavior
of a spark gap and a varistor
total currenttotal current
Current flowing
through the type 1
SPD (spark gap)
current flowing
through the varistor
of the terminal
device
14LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 12. Current characteristic for a decoupling inductance in length of 10m
total current: 1.25kA 10/350µs)
Current flowing through
the varistor of the terminal device
The wave form indicated in green flows into the classⅡⅡⅡⅡSPD.
current flowing through the type 1 SPD(varistor)
SPD locations
conductor
power supplyclassⅡⅡⅡⅡSPD
low voltage
200V
high
voltage
6.6kV
LIGITNING PROTEC TAKETANI Co.,
Ltd. 15
earthing for
low voltage coil of
transformer
earthing
for enclosure
of device
classⅠⅠⅠⅠSPD
200V
Figure 13. The locations of classⅠⅠⅠⅠSPD and classⅡⅡⅡⅡSPD
TN system : One part is earthed directly at the power supply, and the exposed conductive
part of the installation is connected to that point by protective conductor.
Earthing system of power distribution line
installation
power
supply
supply cable
(if any)
power
exposed conductive part
terminal
device
16
(a)(a) JIS C 60364JIS C 60364--11 figure 31. A1 figure 31. A1 (b) example of single phase / 2 wire(b) example of single phase / 2 wire
LIGITNING PROTEC TAKETANI Co., Ltd.
Figure 14. TNS system which has neutral line and protective conductor separately
throughout the whole system
earthing at
power supply
earthing inside of the
supply cable
earthing of the system
which is connected via
more than one earth electrode
exposed conductive part
power
supplydevice
earthing for
low voltage coil of
transformer
earthed at the power supply
TT system The exposed conductive part of installation is connected to the earthing
electrode which is electrically separated from the earthing of power supply.
power
supply
supply cable
(if any) installation
power
supply
terminal
device
exposed
conductive
part
17
Figure 15. TT system which has neutral line and protective conductor
separately throughout the whole installation
(a)(a) JIS C 60364JIS C 60364--11 figure 31. F1 figure 31. F1 (b) example of single phase / 2 wire(b) example of single phase / 2 wire
LIGITNING PROTEC TAKETANI Co., Ltd.
earthed at
power supply
protective earthing
inside of the installation
exposed conductive part Each earthare separated.
earthing for
low voltage coil of
transformer
earthing for
enclosure of
device
SPD connection in the TT system
MCCB
Protective measure for short-circuit failure of SPD :
backup circuit breaker = MCCB
Electric
shock R
18
SPD
earthing for low voltage coil
of transformer
earthing for
enclosure of device
Figure 16. Lightning current path in the case of the short-circuit failure of SPD
(back up: MCCB)
Power supply voltage is
added to the enclosure
of the device via
protective conductor.
earth fault current
MCCB cannot detect
earth fault current because
this current is too small.
short
LIGITNING PROTEC TAKETANI Co., Ltd.
PE
SPD connection in the TT systemProtective measure for short-circuit failure of SPD
R
short
MCCB
short circuit
current
SPD is installed between L and N
Due to the N-PE gap,
hazardous voltage is
19
Figure 17 . Lightning current path in the case of the short-circuit failure of SPD
(back up: MCCB)
N-PE gap
Because of the short circuit current,
interruption by MCCB is possible.
hazardous voltage is
not added to the
enclosure of the
device.
LIGITNING PROTEC TAKETANI Co., Ltd.
earthing for low voltage coil
of transformer
earthing for
enclosure of device
PE
SPD connection in the TT system
ELB
It’s possible to interrupt
the earth fault current.
protective measure for short-circuit failure of SPD:
backup circuit breaker = ELB
RIn this case, earth
fault current is small
because impedance of
earth fault circuit is
large. (earthing for low
voltage coil of
transformer and
earthing for enclosure
of device) However
ELB can detect this
small fault current and
20
SPD
Figure 18. Lightning current path in the case of the short-circuit failure of SPD
(back up: ELB)
earth fault current
short
small fault current and
interrupt it.
Therefore there is no
danger of electric
shock.
DISADVANTAGE
ELB often trips
because ELB is
sensitive.
This occurs problem
on supply
discontinuity.
LIGITNING PROTEC TAKETANI Co., Ltd.
earthing for low voltage coil
of transformer
earthing for
enclosure of device
PE
Combination of MCCB and SPD
MCCB or fuse
MCCB or fuse
R
S
TELB
21
Figure 19. SPD installed at the side of power supply of ELB in TT system
(according to IEC 60364-5-53 Annex B, figure B.1)
LIGITNING PROTEC TAKETANI Co., Ltd.
N-PE gap
( rated follow current
extinguish capacity≧≧≧≧100A)
Combination of ELB and SPD
MCCB or fuse
MCCB or fuse
R
S
T
IΔ
ELB
22
Figure 20. SPD installed at the side of terminal device of ELB in TT system
(according to IEC 60364-5-53 Annex B, figure B.2)
No necessity
of N-PE gap
LIGITNING PROTEC TAKETANI Co., Ltd.
Interruption capacity of follow current
for N-PE gap requires over 100AR
MCCBSPD
I1
23
Figure 21. Follow current extinguish capacity of N-PE gap
N-PE gap
I1,I2 divert in inverse ratio to the
resistance at point A. I1 I2
⇒⇒⇒⇒Interruption capacity of follow current
of N-PE gap requires over 100A
(IEC 60364 )
I2
A
earth fault current
LIGITNING PROTEC TAKETANI Co., Ltd.
earthing for
enclosure of device
earthing for
low voltage coil
of transformerPE