medical college(g+7), boq.hllhites.com/uploads/tenders/_1649947670.pdfproviding m-35 grade concrete...
TRANSCRIPT
Medical College(G+7), Boq.
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha) BOQ CIVIL WORKS
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
A 2.0 EARTH WORKS
1
2.1
Modified
Earthwork in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10
sqm on plan including disposal of excavated earth irrespective of lead and lift upto 1.5 m, disposed soil
to be levelled and neatly dressed
i 2.1.1 All kinds of soil Sqm 6402.18 0.00 Note: Top layer of soil to be stacked as per GRIHA requirement.
2
2.3
Modified
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling
each layer with ½ tonne roller, or wooden of steel rammers, and rolling every 3rd and top-most
layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood
banks, marginal banks, and guide banks etc., irrespective of lead and lift upto 1.5 m, disposed soil to be
levelled and neatly dressed
i 2.3.1 All kinds of soil Cum. 50.00 0.00
3
2.6
Modified
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas
(exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated
earth, irrespective of lead and lift upto 1.5m, disposed earth to be levelled and neatly dressed.
i 2.6.1 All kinds of soil Cum. 10078.57 0.00
4
2.26
Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked
materials.
i 2.26.1 All Kinds Of Soil Cum 1185.71 0.00
5
2.10
Excavating trenches of required width for pipes, cables, etc. including excavation for sockets, and
dressing of sides, ramming of bottoms, depth upto 1.5m including getting out the excavated soil, and
then returning the soil as required, in layers not exc
a 2.10.1 All kinds of soil.
i 2.10.1.2 Pipes, cables, etc. exceeding 80mm dia but not exceeding 300mm dia. rmt 298.38 0.00
6
2.25
Modified
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in
layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering,
irrespective of lead and lift upto 1.5 m.
Cum.
7510.86
0.00
7 1.1.2 Carriage of Earth by mechanical transport including loading, unloading and Stacking including royalty & carriage up to 5 KM complete.
Cum. 2567.71
0.00
8 2.27 Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete.
Cu.Mt. 615.13
0.00
9
2.33 Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of trunks
and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.
i 2.33.1 Beyond 30 cm girth upto and including 60 cm girth each 15.00 0.00
ii 2.33.2 Beyond 60 cm girth upto and including 120 cm girth each 15.00 0.00 iii 2.33.3 Beyond 120 cm girth upto and including 240 cm girth each 7.00 0.00
iv 2.33.4 Above 240 cm girth each 7.00 0.00
10 2.34 Supplying chemical emulsion in sealed containers including delivery as specified
i 2.34.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 472.00 0.00 Anti termite treatment
11 2.35 Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :
a)
2.35.2 Along the external wall below concrete or masonry apron using chemical emulsion @
2.25 litres per linear metre including drilling and plugging holes etc.:
i 2.35.2.1 With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration. metre 393.28 0.00
b)
2.35.3
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart
including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse
sand) to match the existing floor :
i 2.35.3.1 With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. Sqm 4728.34 0.00
TOTAL Earth works (Carried Over to Summary of Civil Works) 0.00
B 4.0 CONCRETE WORKS
1 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
i 4.1.4 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal size).
Cu.Mt. 163.33
0.00
ii 4.1.5 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40mm nominal size).
Cu.Mt. 13.79
0.00
iii 4.1.8 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Cu.Mt. 996.81
0.00
iv 4.1.10 1:5:10 (1 Cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size).
Cu.Mt. 5.00
0.00
2
4.2
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness)
including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing
courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to
floor five level, excluding the cost of centering, shuttering and finishing:
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
i 4.2.3 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
Cu.Mt. 2.00
0.00
3
4.6
Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved
pattern and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), including the cost of
required centering, shuttering complete.
i 4.6.1 1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size).
Cu.Mt. 1.50
0.00
4
4.11
Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size).
Sqm
76.13
0.00
5
4.12
Extra for providing and mixing water proofing material in cement concrete work in doses by weight
of cement as per manufacturer’s specification.
per 50
kg cement
19.49
0.00
6
4.13
Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per
square metre on damp proof course after cleaning the surface with brushes and finally with a piece of
cloth lightly soaked in kerosene oil.
Sqm
76.13
0.00
7
4.17
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse sand : 6graded
stone aggregate 20mm nominal size) over 75mm bed by dry brick ballast 40mm nominal size well
rammed and consolidated and grouted with fine sand including finishing the top smooth
Sqm
250.61
0.00
TOTAL Concrete works (Carried Over to Summary of Civil Works) 0.00
C 5.0 REINFORCED CEMENT CONCRETE WORK
1 5.9 Centering and shuttering including strutting, propping etc. and removal of form for :
a 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete. Sqm 404.42 0.00
b 5.9.2 Walls (any thickness) including attached pilasters, butteresses,plinth and string courses etc.
Sqm 443.47
0.00
c 5.9.3 Suspended floors, roofs, landings, balconies and access platform. Sqm 21332.21 0.00 d 5.9.4 Shelves (Cast in situ) Sqm 229.27 0.00
e 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers Sqm 20716.15 0.00
f 5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts. Sqm 14814.27 0.00
g 5.9.7 Stairs, (excluding landings) except spiral-staircases. Sqm 930.13 0.00
h 5.9.15 Small lintels not exceeding 1.5m clear span, moulding as in cornices, window sills, string courses, bands, copings, bed plates, anchor blocks and the like.
Sqm 96.44
0.00
i 5.9.16 Edges of slabs and breaks in floors and walls
5.9.16.1 Under 20 cm wide metre 3339.68 0.00 j 5.9.19 Weather shade, Chajjas, corbels etc., including edges. Sqm 59.57 0.00
k
5.11
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping
etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional
height of 1 metre or part thereof (Plan area to be measured).
5.11.1
Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) Sq.Mt. 28566.18
0.00
2
5.13
Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not
exceeding 1.5m clear span up to floor five level, including the cost of required centering, shuttering but ,
excluding the cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) : 3 graded stone
aggregate 20 mm nominal size).
Cum
40.50
0.00
3
5.18
Providing precast cement concrete Jali 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 6 mm
nominal size), reinforced with 1.6 mm dia mild steel wire, including centering and shuttering,
roughening cleaning, fixing and finishing in cement mortar 1:3 (1 cement: 3 fine sand) etc. complete,
excluding plastering of the jambs, sills and soffits.
i 5.18.1 50 mm thick Sq.Mt. 802.98 0.00
4 5.22B
Modified
Reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make from
factory/workshop to construction site including placing in position and binding all complete upto plinth level.
i 5.22.B.1 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 1221173.87 0.00
4 5.22C
Modified
Reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make
from factory/workshop to construction site including placing in position and binding all complete
Above plinth level.
i 5.22.C.1 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 1371023.50 0.00
5
5.33
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work, using cement content as per approved design mix,
including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing
and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate,
retard setting of concrete, improve workability without impairing strength and durability as per
direction of Engineer-in-charge.
(Note :- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/recoverable separately).
i 5.33.1 All works upto plinth level. Cum 6190.53 0.00
ii 5.33.2 All works above plinth level upto floor V level. Cum 1812.14 0.00
6 5.34 Extra for providing richer mixes at all floor levels.
Note:- Excess/less cement over the specified cement content used is payable /recoverable separately.
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
a 5.34.1 Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/Cum).
Cu.Mt. 10.00
0.00
b 5.34.2 Providing M-35 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-35 is @ 350 kg/Cum).
Cu.Mt. 1671.40
0.00
7 5.35 Add for using extra cement in the items of design mix over and above the specified cement content therein.
quintal 334.28
0.00
8
5.37
Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete
work, using cement content as per approved design mix, manufactured in fully automatic batching plant
and transported to site of work in transit mixer for all leads, having continuous agitated mixer,
manufactured as per mix design of specified grade for reinforced cement concrete work, including
pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering
finishing and reinforcement, including cost of admixtures in recommended proportions as per IS :
9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and
durability as per direction of the Engineer -
in - charge.
(Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).
i 5.37.1 All works upto plinth level. Cum 5.00 0.00 ii 5.37.2 All works above plinth level upto floor V level. Cum 6082.28 0.00
9 5.38 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof.
i i 5th. Floor Lvl. To Top Lvl. Cu.Mt. 2762.06 0.00
10
5.43
Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm thick as per design for
expansion joints.
i 5.43.1 200 mm wide. Metre 140.20 0.00
ii 5.43.2 300 mm wide. Metre 77.83 0.00
11
5.44
Providing and fixing of expansion joint system related with floor location as per drawings and
direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self
aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be
such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in
load application areas that accommodates multi directional seismic movement without stress to
it's components. System shall consist of metal profiles with a universal aluminum base member
designed to accommodate various project conditions and finish floor treatments. The cover
plate shall be designed of width and
thickness required to satisfy projects movement and loading requirements and secured to base members
by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates /
moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends
that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement
and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in
the Joint System to have watertight joint is mandatory requirement all as per the manufactures design
and as approved by Engineer -in- Charge . (Material shall confirm to ASTM 6063.)
i 5.44.1 Floor Joint of 100 mm gap Rmt 622.64 0.00
12
5.45
Providing and fixing of expansion joint system related with wall joint (internal/external)
location as per drawings and direction of Engineer-In- Charge.
The joints shall be of extruded aluminum base members, self aligning / centering arrangement and
support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints
System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in
office Buildings & complexes with no slipping down tendency amongst the components of the Joint
System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed
aluminum surfaces mechanically snap locking the multicellular to facilitate movement.
(Material shall confirm to ASTM 6063.)
i 5.45.1 wall Joint of 100 mm gap Rmt 692.20 0.00
13
5.46
Providing and fixing of expansion joint system of approved make and manufactures for various roof
locations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extruded
aluminum base members with, self aligning and self centering arragement support plates asper ASTM
B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover
expansion control system that is capable of accommodating multidirectional seismic movement without
stress to its components. System shall consist of metal profile that incorporates a universal
aluminum base member designed to accommodate various project conditions and roof treatments.
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
The cover plate shall be designed of width and thickness required to satisfy movement and loading
requirements and secured to base members by utilizing manufacturer’s pre engineered self-centering
arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit
circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow
freedom of movement and flexure in all directions including vertical displacement. The Joint
System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne
contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier
Membrane in the Joint System to have water tight joint is mandatory requirement. Material shall
confirm to ASTM 6063.
i 5.46.1 roof Joint of 100 mm gap Rmt 77.83 0.00
TOTAL RCC (Carried Over to Summary of Civil Works) 0.00
D 6.0 BRICK WORK
1 6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:
i 6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 52.13 0.00
2
6.34
Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average
compressive strength in super structure above plinth level up to floor V level in :
i 6.34.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 6599.98 0.00
3
6.5 Extra for brick work / AAC block masonry / Tile brick masonry in superstructure above floor V level, for
each four floors or part thereof by mechanical means.
i i 5th. Floor Lvl. To Top Lvl. Cu.Mt. 2581.28 0.00
4
6.45 Half brick masonry with non modular fly ash bricks of class designation 10, conforming to IS : 12894, in
super structure above plinth and upto floor V level.
i 6.45.2 cement mortar 1:4 (1 cement : 4 coarse sand) Sqm. 3041.67 0.00
5 6.14 Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means.
i i 5th. Floor Lvl. To Top Lvl. Sq.Mt. 993.41 0.00
6 6.15 Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars at every third course of half brick masonry (with F.P.S. bricks).
Sqm 3041.67
0.00
6.44 Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non modular)
bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement : 4 fine sand).
metre
150.00
0.00
7
6.38
Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in
super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ).
The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of
masonry work.
Cu.Mt.
5.00
0.00
8
6.47
Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm
thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level
and lintel level with approved block laying polymer modified adhesive mortar all complete as per
direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for
seperately).
Cu.Mt.
5.00
0.00
TOTAL Brick work (Carried Over to Summary of Civil Works) 0.00
E 8.0 MARBLE & GRANITE WORK
1
8.2
Providing and fixing 18mm thick gang saw cut ( premoulded and prepolished) machine cut for kitchen
platforms, vanity counters, window sills , facias and similar locations of required size of approved shade,
colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints
treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing,
curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels.
a) 8.2.2 Granite of any colour and shade
i 8.2.2.1 Area of slab upto 0.50 sqm. Sqm. 2.00 0.00
ii 8.2.2.2 Area of slab over 0.50 sqm.( For Counter) Sqm. 229.27 0.00
2
8.3.2
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including
machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-
Charge. Granite work
metre
3825.71
0.00
3
8.4 Extra for fixing marble / granite stone over and above corresponding basic item, in facia and drops of width
upto 150mm with epoxy resin baesd adhesive including cleaning etc. complete.
metre
500.13
0.00
4
8.5
Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform,
vanity counters and similar location in marble/Granite/Stone work including necessary holes for pillar taps
etc. including rubbing and polishing of cut edge etc. complete.
each
111
0.00
5
8.8 Providing and fixing expansion hold fasteners on C.C. /R.C.C./Brick masonry surface backing including
drilling necessary holes and the cost of bolt etc complete.
a) 8.8.1 Wedge expansion type
i 8.8.1.1 Fastener with threaded dia 6 mm each 150 0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
ii 8.8.1.2 Fastener with threaded dia 10 mm each 150 0.00 iii 8.8.1.3 Fastener with threaded dia 12 mm each 150 0.00
6
8.10
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and
1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and
embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.
i 8.10.2 Granite Stone of approved shade Sq.Mt. 16.20 0.00
7
DSR-2016
(Refer
,8.11)
Providing and fixing machine cut, mirror / eggshell polished , Granite stone work for wall lining (veneer
work) including dado, skirting, risers of steps etc., in required design and pattern wherever required, stones
of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 oarse sand)
laid and jointed with white cement slurry @ 3.3 kg/Sq.Mt. including pointing with white cement slurry
admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per
Architectural drawings, and as directed by the Engineer-in-Charge. a. 18 mm thick Granite stone slab
any colour etc.
Sqm
4506.17
0.00
8
8.12
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear
as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm
thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and
jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching
shade including rubbing, curing and polishing etc. all complete as specified and as directed by the
Engineerin- Charge :
i 8.12.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Sqm. 138.73
0.00
9
8.13
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as
curvilinear portions of the building all complete as
per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement
mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement
slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as
specified and as directed by
the Engineer-in-Charge.
i 8.13.1 Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
Sqm. 5137.97
0.00
TOTAL Marble & Granite work (Carried Over to Summary of Civil Works) 0.00
F 9.0 WOOD & PVC WORK
1
9.1
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought
framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length ( hold fast
lugs or dash fastener shall be paid for separately).
i 9.1.3 Kiln seasoned and chemically treated hollock wood Cum 30.21 0.00
2
9.9
Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float
glass panes, including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws.
a) 9.9.1 Second class teak wood
i 9.9.1.2 30 mm thick Sqm 6.60 0.00
3
9.11
Extra for providing heavy sheet float glass panes instead of ordinary float glass in glazed doors,
windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured)
i 9.11.1 5.5 mm thick instead of 4 mm thick. Sqm 6.60 0.00
4
9.14
Extra for providing ISI marked Stainless Steel butt hinges instead of M.S. pressed butt hinges bright
finished of required size with necessary screws. (Shutter area to be measured).
Sqm
6.60
0.00
5
9.21
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non decorative type,
core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply
veneering with vertical grains or cross bands and face veneers on both faces of shutters:
i 9.21.1 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
sqm 1657.44
0.00
6
9.23 Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush
door shutters (over all area of door shutter to be measured).
Sqm
1657.44
0.00
7 9.24 Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured):
i 9.24.1 Rectangular or square. Sqm 82.87 0.00
8 9.26 Extra for cutting rebate in flush door shutters (Total area of the shutter to be measured).
Sqm 50.00
0.00
9
9.53
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts,
nuts and wooden plugs and embedding in cement concrete block 30x10x15cm 1:3:6 mix (1 cement :
3 coarse sand : 6 graded stone aggregate 20mm nominal size).
Each
2644.00
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
10
9.127
Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt / suede
finish with high density protective surface layer and reverse side of adhesive bonding quality conforming
to IS : 2046 Type S, including cost of adhesive of approved quality.
i 9.127.2 1.0 mm thick Sqm 3314.88 0.00
11
9.46
Providing and fixing curtain rods of 1.25 mm thick chromium plated brass plate, with two chromium
plated brass brackets fixed with C.P. brass screws and wooden plugs, etc., wherever necessary complete :
i 9.46.2 20 mm dia meter 2168.25 0.00
12
9.96
Providing and fixing aluminium sliding door bolts, ISI marked anodised anodic coating not less than
grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :
i 9.96.1 300x16 mm each 267.00 0.00
13
9.97 Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC
10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete :
i 9.97.1 300x10 mm each 1634.00 0.00
ii 9.97.4 150x10 mm each 1820.00 0.00
14
9.100
Providing and fixing aluminium handles of approved make anodized (anodic coating not
less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessry
screws etc. complete.
i 9.100.1 125 mm each 1634.00 0.00 ii 9.100.2 100 mm each 1820.00 0.00
15
9.101
Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating
not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with
necessary screws etc. complete.
i 9.101.1 Single rubber stopper each 817.00 0.00
16
9.103
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and
a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of
approved quality with necessary screws etc. complete.
each
626.00
0.00
17
9.84
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer
(having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door
width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and
screws etc. complete.
each
817
0.00
Fire Door
18
9.136
Modified
Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out
of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based
concrete mix, suitable for mounting 120 minutes fire rated door shutters. The frame is fitted with
intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of
approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as
per direction of Engineer-in-charge (Dash / expandable fastener to be paid for separately).
Metre
117.60
0.00
19
9.137
Modified
Providing and fixing 50 mm thick glazed fire resistant door shutters of 120 minutes fire rating conforming
to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with
suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom
rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR
insulation material and fixing with necessary stainless steel ball bearing hinges of approved make,
including applying a coat of approved fire resistant primer etc. all complete as per direction of
Engineer-in-charge. (Paneling to be paid for separately).
Sqm
60.48
0.00
20
9.138
Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading
made out of 1.6mm thick G.I sheet (zinc coating not less than 120 gm/m2), of size 20x33mm screwed
with M4 X38mm S.S Screws at distance 75mm from the edges and 150mm c/c, including applying a
coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I beading, &
special ceramic tape of 5x20mm size etc. complete in all respect as per NBC 2016, IS 16231 (Part-3)
:2016 and as per direction of Engineer-in-charge with glass of required thickness having 60
minutes of fire resistance both integrity & radiation control (EW60) and minimum 20 min of
insulation (E120). The manufacturer have to give should have the stamp showing the value of E, EW &
El. The glass shall be tested in approved NABL accredited lab or by any other accreditation body whitch
operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and
calibration scopes shall be eligible. The maximum glazing size shall not be more than
1100x2200mm (wxh) or2.42 sqm.
Sqm
60.48
0.00
21
9.139
Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on
back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
each
20.00
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
22
9.105
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including
providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with
zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide
having equal flanges of 32 mm and
0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener
of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the
studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed
vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre
by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with
suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and
fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling
channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with
joints staggered to avoid through cracks,
M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the
horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including
jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle
beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for
board as per manufacture’s specification and direction of engineer in charge all complete.
i 9.105.1 75 mm overall thickness partition with 12.5 mm thick double skin fire rated board conforming to IS: 2095: part I
Sqm 1422.81
0.00
23
NSI
Supply and Installation of Compact Interior grade 12mm thick panels of standard size with both side decor
as per specification. The panels are durmor high pressure laminates (HPL) in accordance with EN438 /4
type CGS for demanding application as Cubicles, Wall Partition, wall cladding etc. Toilet Partition
Cubicle System with approved color laminate and system, the system shall be designed for the sizes
mentioned in the drawing, all fixtures like SS thumb turn, SS occupancy indicators Door nob, SS hinges and
door opening shall be as per detail drawing, ( Note: Patch fittings, Pedestals , laminate colour shall be as
approved by Clients /Architect) Size:- 2000mm in height, door opening 600mm, side partition will be
1800mm
Each
240.00
0.00
24
Refer item
no.(9.147D
.2)
Providing and fixing factory made Powder coated Aluminium sliding glazed window upto 1.50 m in
height dimension comprising of of standard sections of approved brand for frame with in-built roller track
and sash extruded profiles duly reinforced with 1.60
± 0.2 mm thick galvanized mild steel section made from roll forming process of required length
(shape & size according to Aluminium profile), appropriate dimension of Aluminium extruded glazing
beads and Aluminium extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder
coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40
kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws
etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of
holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and
adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size
and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single
/ double glass panes, wire mesh and silicon sealent shall be paid separately)
screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of
holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and
adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required
size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge.
(Single / double glass panes, wire mesh and silicon sealent shall be paid separately) Note: For
Aluminium frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of
profile shall be acceptable.
i
Three track three panels sliding window with fly proof SS wire mesh (Two nos. glazed & one no. wire
mesh panels) made of (small series) frame 92 x 44 mm & sash 32 x 60 mm both having wall thickness of
1.9 ± 0.2 mm and single glazing bead of appropriate dimension (Area of window upto 1.75 sqm).
Sqm
107.10
0.00
TOTAL Wood & PVC work (Carried Over to Summary of Civil Works) 0.00
G 10.0 STEEL WORK
1
10.25
Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer using structural steel etc. as required
i 10.25.1 In stringers, treads, landings etc. of stair cases including use of chequered plate wherever required, all complete.
Kg 450.00
0.00
ii 10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
Kg 8561.57
0.00
2
10.2 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including
cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Kg
2870.38
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
3
10.5
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S.
gusset plates at the junctions and corners, all necessary fittings complete, including applying a
priming coat of approved steel primer.
I 10.5.1 Using M.S. angels 40x40x6 mm for diagonal braces Sqm 10.08 0.00
4
10.6
Supplying and fixing-rolling shuters of approved make.made of required size of M.S.Iaths inter
locked together through their intire length and jointed together at the end by end locks mounted on
specially designed pipe shaft with brackets, side guides and arragements for inside and outside locking
with push and pull operation complete including the cost of prioviding and fixing necessary 27.5 cm long
wire springs grade no. 2 and M.S. top cover of required thickness for rolling shutters.
i 10.6.1 80 x 1.25 MS laths with 1.25mm thick top cover Sqm 17.40 0.00
ii 10.7 Providing and fixing ball bearing for rolling shutters. each 6.00 0.00
iii 10.8 Extra for providing mechanical device chain and crank operation for operating rolling shutter.
iv 10.8.1 Exceeding 10.00 Sqm and upto 16.8 Sqm in the area. Sqm 17.40 0.00
v
10.9
Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar
instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured).
Sqm
1.74
0.00
5
10.27
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm
dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia
polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge.
i 10.27.1 10 x 60 mm each 1752.00 0.00
6
10.28
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc.,
including welding, grinding, buffing, polishing and making curvature (wherever required) and
fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with
necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top
of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge,
(for payment purpose only weight of stainless steel members shall be considered excluding fixing
accessories such as nuts, bolts, fasteners etc.).
KG
39438.60
0.00
7
NSI
Supply & Fixing of Stainless steel doors, frames & shutters made of stainless steel grade 304 of hairline
finish, frame with 1.2mm thick formed to single rebate profile of size 100 mm X 58 mm and filled with
in-fill Polyurethane foam, the Door Shutters are with
0.80 mm thick Stainless steel Sheet formed to provide a 46 mm thick fully flush, double skin door shell
with Lock Seam joints at stile edges, fitted with in-fill of Honeycomb Kraft Paper, the Shutter provided
with 6 MM clear float vision glass in Circular, Square or Rectangular shapes, Stainless Steel Ball Bearing Butt
Hinges 3 mm thick fixed flush to the frame and shutter (Profile 102x76x3mm thick).Mortise Sash Lock
with Lever Handles, Mortise Dead Bolt, etc for ICU, CT Scan,MRI etc. applications
Sqm
100.56
0.00
TOTAL Steel work (Carried Over to Summary of Civil Works) 0.00
H 11.0 FLOORING WORK
1
11.3
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate)
finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of
steps etc. complete.
i 11.3.1 40 mm thick with 20 mm nominal size stone aggregate Sqm 3514.92 0.00
2
11.20
Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement
slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc.
complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).
i 11.20.1 Light shade pigment using white cement Sqm 1888.51 0.00
3 11.24 Extra for pre finished nosing to treads of steps of marble/Stone stone. Metre 1530.63 0.00
4 11.25 Extra for marble/Granite stone flooring in treads of steps and risers using single length up to 2.00 metre.
Sqm 1261.57
0.00
5
11.26
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement
slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete
with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
i 11.26.1 25 mm thick. Sqm 2734.14 0.00
6
11.27
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick
cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment
to match the shade of the slabs, including rubbing and polishing complete.
Sqm
285.37
0.00
7
11.36
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be
specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle
green, black of any size as approved by Engineerin- Charge, in skirting, risers of steps and dados, over 12
mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @
3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Sqm
9833.60
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
8
11.38
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the
manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except
White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4
Coarse
sand), jointing with grey cement slurry @ 3.3 kg/ sq.m including pointing the joints with white cement and matching pigments etc., complete.
Sqm
98.06
0.00
9
11.41
Providing & Laying vitrified floor tiles in different sizes ( thickness to be specified by the
manufacturer) with water absorption's less than 0.08% and confirming to IS : 15622 of approved
make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand)
including grouting the joints with white cement and matching pigments etc, complete.
i 11.41.2 Size of Tile 600x600 mm Sqm 3193.57 0.00
10
11.46
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer),
with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours &
shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand),
including grouting the joint with white cement & matching pigments etc. complete..
i 11.46.2 Size of Tile 600x600 mm Sqm 375.57 0.00
11
11.52
Providing and laying machine cut, mirror polished Marble stone flooring, in required design (Simple
geometrical, abstract etc.) and in patterns in combination with Italian marble stones of different colours,
shades and finished surface texture etc., in linear portions of the building, all complete as per the
architectural drawings, with 18 mm thick stone slab laid over 20 mm (average) thick base of cement
mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with white cement slurry @ 4.4 kg/sqm
including pointing with white cement slurry admixed with pigment to match the marble shade
including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-
Charge. a. 18 mm thick Italian Marble stone slab,Perlato, Rosso verona, Fire Red or Dark Emperadore
etc.
Sqm
983.20
0.00
12
16.89
Providing and laying matt finished vitrified tile of size 300x300x9.8mm having with water absorption
less than 0.5% and conforming to IS: 15622 of approved make in all colours and shades in for outdoor
floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement
mortar 1:4 (1cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white
cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
Sqm
6530.59
0.00
13
NSI
Providing and laying Unbacked flexible P.V.C /marblex flooring/ skirting with P.V.C sheets/
Marblex tiles as specified below of approved make and shade including preparing the surface,
cleaning as required and applying adhesive - as recommended by the P.V.C / Marblex tile manufacturers,
laying, aligning, cutting in required size and pattern, trimming of tiles, removing the adhesive stains
on the surface including cleaning the surface with soap solution (2 table spoons of soap powder for 5
ltrs of water) using a cloth or mop or and wiping the dried surface with soft dry cloth etc; complete all
as per specifications.
i
i
In PVC flooring/ skirting/ dadoing: With 2mm thick Unbacked flexible fully homogeneous
PVC sheets in rolls of approved make and quality - viz Poly floor of M/s. Poly floor vinyl flooring or
TUSKER of M/s. Krishna vinyls Limited or Birla vinoleum of M/s Birla corporation Limited or equivalent
make conforming to IS: 3462-1986.
Sqm
3690.66
0.00
14
NSI
Providing and Laying 4mm thick Spacers for Tile Flooring as per design and drawings complete as per
Manufacturer specifications and direction of Engineer-in-charge.
Sqm
9724.16
0.00
TOTAL Flooring work (Carried Over to Summary of Civil Works) 0.00
I 12.0 ROOFING
1
12.21
Providing and laying gola 75x75mm in cement concrete M15 grade including finishing
with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design in 75x75 mm deep chase.
rmt.
663.90
0.00
2
12.22
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate of 20 mm nominal size) over
P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a
coat of neat cement, rounding the edges and making and finishing the outlet complete.
each
71.00
0.00
3
12.41
Providing and fixing on wall face unplasticised Rigid PVC RAIN WATER PIPES conforming to
IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for
thermal expansion.(i) Single socketed pipes.
i 12.41.2 110 mm diaMeter Metre 2142.90 0.00
4
12.42
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised
Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring
conforming to IS : 5382 leaving 10 mm gap for thermal expansion.
i 12.42.1 Coupler
12.42.1.2 110 mm Each 142.00 0.00 ii 12.42.5 Bend 87.5°
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
12.42.5.2 110 mm bend Each 71.00 0.00 iii 12.42.6 Shoe (Plain)
12.42.6.2 110 mm Shoe Each 142.00 0.00
5
12.45
Providing and fixing false ceiling at all height including providing and fixing of frame work made of
special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both
side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with
flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener
12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50
mm of required length with nuts & bolts of required size and other end of angle hanger fixed with
intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the
ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5
mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel
with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including
fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the
perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm
long dry wall screws @ 230 mm interval,
including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws
of size 3.5 x 25 mm edges of the board with recommended jointing compound , jointing tapes , finishing
with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer
suitable for board, all as per manufacturer's specification and also including the cost of making
openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed,
all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost
of painting with : at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square
i 12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board. Sqm 7160.61 0.00
6
12.52
Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal
level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120
grams/ sqm, both side inclusive) consisting of main “T” runner with suitably spaced joints to get
required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm
center to center and cross “T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm
long spaced between main “T” at 600 mm center to center to form a grid of 1200x600 mm and secondary
cross “T” of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be
interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size
24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required
cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main
“T” runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to
ceiling with 12.5 mm dia and 50 mm long dash fasteners,
4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm
center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted
with polyester paint, all complete for all heights as per specifications, drawings and as directed by
Engineer-in-charge.
i
12.52.2
GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm
thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and
20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5,
electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted
after bending and perforation, and backed with a black Glass fiber acoustical fleece.
Sqm
8203.91
0.00
7
12.55
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar
refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface
of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and
grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and
polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height
along the parapet walls in the same manner.
Sq.Mt.
3555.78
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
8
NSI
Providing and Fixing of 16mm Thick sky lights consisting of Multi cell/tight cell Polycarbonate
Panel System of approved colour, 16 mm thick (minimum) having uniform in color with an integral
Tight-Cell core constructed not to exceed 4mmx4mm in a cross section, Vertical Standing Seam
manufactured at both sides of the panel. Snap on connector to interlock the panels shall have a grip-
lock double tooth locking mechanism to ensure maximum uplift capability and shall be of same color
as that of panel. Panel shall be factory sealed/end welded panels with additional End-
cap/Aluminium U-Profile (mill finish) for ends. Panel shall be co-extruded with special anti glare
compound and UV protected. The full system shall be fitted on MS purlins perpendicular to direction of
sheeting with purlin spacing as specified by Manufacturer. The rate includes cost of all the operations,
labour and all materials and tests (as applicable) involved such as bolts nuts and screws etc. and labour
for cutting bending to required profile, necessary scaffolding, hoisting in position etc. for
proper completion of the work etc. complete as per specification drawings and direction of Engineer
in charge. Finished surface area of roofing fixed over steel tublar structure shall be measured for
payment. MS tabular frame work shall be measured separately for payment.
Sqm
88.89
0.00
TOTAL Roofing work (Carried Over to Summary of Civil Works) 0.00
J 13.0 FINISHING WORK
1 13.4 12 mm cement plaster of mix :
i 13.4.1 1:4 (1 cement: 4 coarse sand) Sqm. 28852.18 0.00
2 13.5 15 mm cement plaster on rough side of single or half brick wall of mix :
i 13.5.2 1:6 (1 cement: 6 coarse sand) Sqm. 28852.18 0.00
3 13.6 20 mm cement plaster of mix :
i 13.6.1 1:4 (1 cement: 4 coarse sand) Sqm. 19220.12 0.00
4 13.16 6 mm cement plaster of mix :
i 13.16.1 1:3 (1 cement: 3 fine sand) Sqm. 23890.75 0.00
5
13.21
Extra for providing and mixing water proofing material in cement plaster work in proportion
recommended by the manufacturers. per bag of
50KG
Cement
Used in
Mix
15087.34
0.00
6 13.22 Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
i i 10m to 13m Sqm 1573.10 0.00
ii ii 13m to 16m Sqm 1553.07 0.00
iii iii 16m to 19m Sqm 1402.46 0.00 iv iv 19m to 22m Sqm 1430.97 0.00
v v 22m to 25m Sqm 1357.16 0.00
vi vi 25m to 28m Sqm 1531.96 0.00
vii vii 28m to 31m Sqm 1274.96 0.00 viii viii 31m to 34m Sqm 1495.51 0.00
ix ix 34m to Top Sqm 1649.95 0.00
7 13.26 Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Sqm 8526.23
0.00
8 13.37.1 White washing with lime to give an even shade : New work (three or more coats)
Sqm 15364.52
0.00
9 13.41 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :
i 13.41.1 New work (two or more coats) over and including water tinnable priming coat with cement primer
Sqm 5002.49
0.00
10
13.81
Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound )
content less than 50 grams/ litre, of approved brand and manufacture, including applying additional
coats wherever required, to achieve even shade and colour.
i 13.81.2 Two coats Sqm 1605.96 0.00
11
13.82
Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less
than 50 grams/ litre, of approved brand and manufacture, including applying additional coats
wherever required, to achieve even shade and colour.
i 13.82.2 Two coats Sqm 39719.11 0.00
12 13.45 Finishing walls with textured exterior paint of required shade :
i 13.45.1 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm
Sqm 5433.53
0.00
13
13.52 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as
per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc.
complete.
i 13.52.2 On concrete work Sqm 150.00 0.00
14
13.84
Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150
grams/ litre, of approved brand and manufacture, including applying additional coats wherever
required to achieve even shade and colour.
i 13.84.2 Two coats. Sqm 1243.15 0.00
15 13.85 Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
i 13.85.1 With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/ litre
Sqm 947.99
0.00
ii 13.85.2 With ready mixed red oxide zinc chromatic on steel / iron works having VOC content less than 250 grams/ litre
Sqm 50.00
0.00
iii 13.85.3 With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
Sqm 41325.06
0.00
16
13.80
Providing and applying white cement based putty of average thickness 1 mm, of approved brand
and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete
Sqm
31622.65
0.00
17 5.30 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
meter 3339.68
0.00
18
NSI
Providing and fixing GI hexagonal chicken wire mesh of size 12mm x22g at the junction of disimilar
surfaces of brick masonry wall and R C C column by beams and the like including necessary nails for
fixing etc, complete all as per specification and direction of Engineer -in -charge for all floor at all heights.
Sqm
3844.02
0.00
19
NSI
Providing & laying Anti bacterial/Anti fungal paint having Low VOC on interior wall on new surface
with two or more coats of desired shade & approved make as per manufacturers, specifications .
The item rate to be inclusive of filling cracks & holes etc with approved make. Acrylic wall putty/Crack
seal compound etc complete in all respect as per direction of Engineer in charge.
Sqm
16514.54
0.00
TOTAL Finishing work (Carried Over to Summary of Civil Works) 0.00
K 20.0 PILE WORK
1
20.2
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of
specified diameter and length below the pile cap, to carry a safe working load not less than specified,
excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and
temporary casing of appropriate length for setting out and removal of same and the length of the pile to
be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and
chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated
earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap) Note:
Truck Mounted rotary/TMR/Tubewell boring mchine shall not be used .
i Refer
(20.2.4) 800 mm dia. Piles
Rmt 22177.60
0.00
2
20.6
Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading
platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and
dismantling of test cap after test etc. complete as per specification & the direction of Engineer
incharge.
a 20.6.1 Single pile upto 50 tonne Safe capacity
i 20.6.1.1 Initial test (Test Load 2.5 times the Safe capacity) per test 150.00 0.00
ii 20.6.1.2 Routine test (Test Load 1.5 times the Safe capacity) per test 150.00 0.00
TOTAL Pile work (Carried Over to Summary of Civil Works) 0.00
L 21.0 ALUMINIUM & GLAZING WORK
1
21.1
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded
built up standard tubular sections/appropriate Z sections and other sections of approved make
conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with
expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with
required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred
and jointed echanically wherever required including cleat angle, Aluminium snap beading for
glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the
directions of Engineer-in-charge. Glazing and paneling to be paid for separately) :
a) 21.1.1 For fixed portion.
i 21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) KG 10902.70 0.00
b)
21.1.2
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making
provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket
required (Fittings shall be paid for separately)
i 21.1.2.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) KG 9384.88 0.00
2
21.2
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood
particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors,
windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per
architectural drawings and directions of engineer-in-charge.
i 21.2.2 Pre-laminated particle board with decorative lamination on both sides Sqm 20.52 0.00
3
21.3
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc.
with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the
directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
i 21.3.2 With float glass panes of 5.50 mm thickness Sqm 20.52 0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
4
21.4
Providing and fixing double action hydraulic floor spring of approved brand and manufacture
conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism
and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required
and making good the same matching to the existing floor finishing and cover plates with brass pivot and
single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-
charge.
i 21.4.1 With stainless steel cover plate minimum 1.25 mm thickness
each 26.00
0.00
5
21.8
Filling the gap in between aluminium frame and adjacent RCC/Brickwork/ Stone Work by providing
weather silicon sealant over backer rod of approved quality as per architectural drawings and
direction of Engineer-in-charge
i 21.8.1 Upto 5mm depth and 5mm width metre 5451.35 0.00
6
21.10
Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and
partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM
gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per
specifications, drawings and direction of Engineer-in-charge complete.
Sqm
598.60
0.00
7 21.13 Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
each 26.00
0.00
8
21.14
Providing and fixing anodised aluminium (anodised transparent or dyed to required shade according
to IS: 1868. Minimum anodic coating of grade AC 15)
sub frame work for windows and ventilators with extruded built up standard tubular sections of approved
make conforming to IS: 733 and IS: 1285, fixed with dash fastener of required dia and size (Dash fastener
to be paid for separately).
KG
250.00
0.00
External Structure Glazing
9
25.1
Providing and supplying aluminium extruded tubular and other aluminium sections as per the
architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as
per BS 1474,including super durable powder coating of 60- 80 microns conforming to AAMA 2604 of
required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such
as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra
shall be paid on this account).
Kg
26503.24
0.00
10
25.2
Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of
structural glazing (with open joints) for linear as well as curvilinear portions of the building for all
heights and all levels including:
i
(a) Structural analysis, design and preparation of shop drawings for the specified design loads
conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure
without any failure), including functional design of the aluminum sections for fixing glazing panels of
various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts,
clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke
seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and
protection against fire hazard including:
ii
(b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets
of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving
perfect verticality and proper fixing of structural glazing system with the RCC/ masonry/structural
steel framework of building structure, using stainless steel anchor fasteners/ bolts, nylon seperator
to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the
required capacity and in required numbers.
iii
(c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone
sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory
/ work shop environment , including double sided spacer tape, setting blocks and backer rod, all of
approved grade, brand and manufacturer, as per the approved sealant design, within and all around the
perimeter for holding glass.
iv
(d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes
and profiles, as required as per the site conditions, to seal the gap between the building structure and
all its interfaces with curtain glazing to make it watertight.
v
(e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it
watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at
bottom (if required), making necessary holes of required sizes and of required numbers etc. complete.
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid,
installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc.,
enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The
item includes the cost of getting all the structural and functional design checked and all the shop
drawings vetted by the Principals of the structural glazing system.
The item also includes the cost of all mock ups at site, cost of all samples of the individual
components for testing in an approved laboratory, field tests on the assembled working
structural glazing as specified, cleaning and protection till the handing over of the building for
occupation. In the end, the Contractor shall provide a water tight structural glazing having all the
performance characteristics etc. all complete as required, as per the Architectural drawings, as per
item description, as specified, as per the approved shop drawings and as directed by the Engineer-
in- Charge.
Sqm
2650.32
0.00
11
25.3
Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-
sealed 6-12-6 mm insulated glass (double glazed) vision panel units of size and shape as required and
specified, comprising of an outer high performance heat strengthened float glass 6mm thick, of
approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an
inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including
primary seal and secondary seal (structural silicone sealant) etc. all complete for the required
performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as
directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass
processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.1)
For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the
grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.
i
(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap +
6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance
(VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading
coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc.
Sqm.
3974.67
0.00
12
25.4
Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all
accessories and hardwares for the openable panels as specified and of the approved make such as heavy
duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates,
handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all
complete as per the Architectural drawings, as per the approved shop drawings, as specified and as
directed by the Engineer- in-Charge.
Sqm.
265.03
0.00
13
NSI
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminum
Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the
building , for all heights and all levels etc. including: (a) Structural analysis & design and
preparation of shop drawings for pressure equalization or rain screen principle as required, proper
drainage of water to make it watertight including checking of all the structural and functional design. (b)
Providing, fabricating and supplying and fixing panels of aluminum composite panel cladding in pan
shape in metallic color of approved shades made out of 4mm thick aluminum composite panel
material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminum sheets
(each 0.5mm thick). The aluminum composite panel cladding sheet shall be coil coated, with Kynar
500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face
# 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts,
washers, cleats, weather silicone sealant,
backer rods etc.
i
(c) The fastening brackets of Aluminum alloy 6005 T5 / MS with Hot Dip Galvanized with serrations
and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of
approved make in SS 316, Nylon separators to prevent bi- metallic contacts all complete required to
perform as per specification and drawing The item includes cost of all material & labour component, the
cost of all mock ups at site, cost of all samples of the individual components for testing in an approved
laboratory, field tests on the assembled working curtain wall with aluminum composite panel
cladding, cleaning and protection of the curtain wall with aluminum composite panel cladding till the
handing over of the building for occupation. Base frame work for ACP cladding is payable under the
relevant aluminum items. The Contractor shall provide curtain wall with aluminum composite panel
cladding, having all the performance characteristics all complete , as per the Architectural drawings, as
per item description, as specified, as per the approved shop drawings and as directed by the Engineer-
in- Charge. However, for the purpose of payment, only the actual area on the external face of the curtain
wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in
sqm. up to two decimal places.
Sqm.
13786.59
0.00
14 NSI Automatic Sliding Doors
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
NSI
Automatic sliding door operator - supply of automatic sliding door Set 1 operator of DORMA (ES 200
easy ) as per approved dwg. Compliant with european standards and produced according to the
guidelines for power-operated windows, doors and gates, BGR 232, the UVV and the VDE regulations.
TÜV design tested, tested according to the low voltage guidelines, fulfils DIN 18650 standards Standards
for Pedestrian Safety, TUV Design Tested for Durability of 1 Million Cycles. The track profile
should be separate from the main profile for enabling reduction in vibration insulation. Operator length
= 6250 mm, clear passage opening width = 3000 mm, clear passage height = 2500 mm, includes micro
processor controlled drive unit, with self learning mechanism, program selector with knob, motion
detector (eagle 6 radars, 02 nos), mechanical components, toothed belt, cover profile, floor guide for
frameless glass (02 nos), glass clamping rail (02 nos), safety device-light barrier (01 pair).
Body finish : standard silver anodised operator profile, electromechanical lock with 12 mm plain
toughened frameless glass for complete elevation - 2 moving panels. UPS of 750 VA shall be provided by
others, which will give power backup of 20 min. Only & if the duration of power cut to the operator
is more than 30 min.,then separate arrangement needs to be done for the same as automatic
operator requires uninterrupted stabilized power supply. The above work complete in all respect as per
approved drawings and to the satisfaction of engineer-in-charge / architect consultant.
Each
7
0.00
TOTAL Aluminium work (Carried Over to Summary of Civil Works) 0.00
M 22.0 WATER PROOFING
1 22.3 Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of :
Sqm
1633.31
0.00
(i) Ist course of applying cement slurry @ 4.4 Kg/sqm mixed with water proofing compound
conforming to IS 2645 in recommended proportions including rounding off junction of vertical and
horizontal surface. (ii) IInd course of 20mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with
water proofing compound in recommended proportion including rounding off junction of vertical and
horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 Kg. per sqm of
area. (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm
wide and pasted to each other with bitumen @ 1.7 Kg/sqm.)
2
16.3.4
Supplying and Stacking Filling sunken floor with over burnt jhama brick aggregate
120mm to 40mm including compacting of materials complete as specified and directed for all levels.
Cum
530.83
0.00
3
22.7
Providing and laying integral cement based water proofing treatment including preparation of
surface as required for treatment of roofs, balconies, terraces etc consisting of following
operations:
(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing
compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including
adjoining walls upto 300 mm height including cleaning the surface before treatment.
(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of
cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to
IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1
cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by
Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm
height including rounding of junctions of walls and slabs.
(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement
admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin- charge.
(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse
sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-
charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing
the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm
deep.
(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for
curing and for final test. All above operations to be done in order and as directed and specified by the
Engineer-in-Charge :
i 22.7.1 With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
Sqm 3555.78
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
4
22.23
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing
treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums,
reservior, sewage & water treatment plant, tunnels
/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry :
2 parts water) for vertical surfaces and 3 : 1 (3 parts
integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative
(internal) side with the help of synthetic fiber brush. The material shall meet the requirements as
specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared
with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The
crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be
carried out all complete as per specification and the direction of the engineerin- charge. The
product performance shall carry guarantee for 10 years against any leakage.
i 22.23.1 For vertical surface two coats @0.70 kg per sqm Sqm 645.19 0.00
ii 22.23.2 For horizontal surface one coat @1.10 kg per sqm. Sqm 5857.60 0.00
TOTAL Water Proofing (Carried Over to Summary of Civil Works) 0.00
N MISCELLANEOUS WORK
1 18.76.1 Cutting holes up to 30x30 cm in walls including making good the same: With common burnt clay F.P.S. (non modular) bricks.
Each 50.00
0.00
2
18.77
Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole
after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof.
Each
150.00
0.00
3
19.17
Replacement of M.S. foot rests in manholes including dismantling concrete blocks and fixing with
20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size):
i 19.17.1 With 20x20 mm square bar Each 20.00 0.00 Core Cutting
4
NSI
Drilling with core cutting machine in Post RCC beams, slabs, floors etc. if not mentioned in the drawing but
required by Project Manager for laying pipes and rendering the same in RCC 1:2:4, finishing the same to
the satisfaction of the Project Manager.
Including nominal reinforcement wherever required, complete. The quoted rate shall also include for
providing EPOXY based water proofing compound for sealing the joints around the pipes. (Maximum
thickness of RCC members shall be 150mm for slab & 230mm for walls , 600 mm for beam).
A) A) RCC Slabs
i i 100mm dia. Nos. 20.00 0.00
ii ii 150mm dia Nos. 12.00 0.00 iii iii 200mm dia Nos. 8.00 0.00 B) B) RCC Beams
i i 65mm dia. Nos. 20.00 0.00
ii ii 160mm dia Nos. 12.00 0.00 iii iii 180mm dia Nos. 8.00 0.00 C) C) RCC Walls
i i 65mm dia. Nos. 10.00 0.00
ii ii 160mm dia Nos. 10.00 0.00 iii iii 180mm dia Nos. 5.00 0.00
TOTAL Miscellaneous (Carried Over to Summary of Civil Works) 0.00
External Development works
A 2 EARTH WORKS
1
.6Modified
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas
(exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth,
irrespective of lead and lift upto 1.5m, disposed earth to be levelled and neatly dressed.
i 2.6.1 All kinds of soil Cum. 245.19 0.00
2
2.1
Excavating trenches of required width for pipes, cables, etc. including excavation for sockets, and dressing of
sides, ramming of bottoms, depth upto 1.5m including getting out the excavated soil, and then returning
the soil as required, in layers not exc
a 2.10.1 All kinds of soil.
i 2.10.1.2 Pipes, cables, etc. exceeding 80mm dia but not exceeding 300mm dia. rmt 150.00 0.00
3
2.25
Modified
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in
layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering,
irrespective of lead and lift upto 1.5 m.
Cum.
168.73
0.00
4 1.1.2 Carriage of Earth by mechanical transport including loading, unloading and Stacking including royalty & carriage up to 5 KM complete. Cum. 76.46
0.00
6 2.27 Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. Cu.Mt. 10.00
0.00
B 4 CONCRETE WORKS
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
1 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
i 4.1.4 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal size). Cu.Mt. 3.24
0.00
ii 4.1.8 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) Cu.Mt. 25.38
0.00
iii 4.1.10 1:5:10 (1 Cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size). Cu.Mt. 64.92
0.00
2
4.2
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including
attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses,
parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five
level, excluding the cost of centering, shuttering and finishing:
3
4.6
Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved
pattern and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), including the cost of
required centering, shuttering complete.
4
4.11
Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand
: 4 graded stone aggregate 20 mm nominal size).
Sqm
47.69
0.00
5 4.12 Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer’s specification. 50 kg cem 12.21
0.00
6
4.13
Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square
metre on damp proof course after cleaning the surface with
brushes and finally with a piece of cloth lightly soaked in kerosene oil.
Sqm
47.69
0.00
7
4.17
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement :3 coarse sand : 6graded stone
aggregate 20mm nominal size) over 75mm bed by dry brick ballast 40mm nominal size well rammed and
consolidated and grouted with fine sand including finishing the top smooth
Sqm
112.50
0.00
8
4.9
Precasting and placing in position 125 mm dia Bollards 600 mm high of required shape, including
providing M.S. Pipe Sleeve 50 mm dia 300 mm long in the Bollard and M.S. Pipes 40 mm dia and 450 mm
long with 150x150x6mm M.S. plate welded at bottom and embedded 150 mm in cement concrete 1:3:6 (1
Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size), including necessary excavation of
size 250 x 250 x 450 mm deep for the same in bitumen/concrete pavement at specified spacing.
Each
50.00
0.00
C 5 REINFORCED CEMENT CONCRETE WORK
1 5.9 Centering and shuttering including strutting, propping etc. and removal of form for :
a 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete. Sqm 224.55 0.00 e 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers Sqm 255.74 0.00 f 5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts. Sqm 166.44 0.00
4
5.22B
Modified
Reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make from
factory/workshop to construction site including placing in position and binding
all complete upto plinth level.
i 5.22.B.1 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 14515.00 0.00
4 .
22C Modifie Reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make from
factory/workshop to construction site including placing in position and binding all complete Above plinth level.
i 5.22.C.1 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 2692.16 0.00
5
5.33
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work, using cement content as per approved design mix, including
pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and
reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard
setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.
(Note :- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/recoverable separately).
i 5.33.1 All works upto plinth level. Cum 132.55 0.00 ii 5.33.2 All works above plinth level upto floor V level. Cum 17.13 0.00 6 5.34 Extra for providing richer mixes at all floor levels.
D 6 BRICK WORK
1 6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:
i 6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 11.10 0.00
2
6.34 Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average
compressive strength in super structure above plinth level up to floor V
level in :
i 6.34.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 80.59 0.00
3
6.44 Brick edging 7cm wide 11.4 cm deep to plinth protection with common burnt clay F.P.S. (non modular)
bricks of class designation 7.5 including grouting with cement mortar 1:4 (1 cement : 4 fine sand).
metre
150.00
0.00
E 10 STEEL WORK
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
1
10.25 Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer using structural steel etc. as required
i 10.25.1 In stringers, treads, landings etc. of stair cases including use of chequered plate wherever required, all complete. Kg 150.00
0.00
ii 10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. Kg 689.00
0.00
F 13 FINISHING WORK
1 13.5 15 mm cement plaster on rough side of single or half brick wall of mix :
i 13.5.2 1:6 (1 cement: 6 coarse sand) Sqm. 501.26 0.00 2 13.6 20 mm cement plaster of mix :
i 13.6.1 1:4 (1 cement: 4 coarse sand) Sqm. 501.26 0.00
3 13.21 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. KG Cemen 133.34
0.00
4 13.45 Finishing walls with textured exterior paint of required shade :
i 13.45.1 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm Sqm 1002.52
0.00
5
13.84
Painting with synthetic enamel paint, having VOC (Volatile Organic Compound) content less than 150
grams/ litre, of approved brand and manufacture, including applying additional coats wherever
required to achieve even shade and colour.
i 13.84.2 Two coats. Sqm 10.80 0.00
6
13.8
Providing and applying white cement based putty of average thickness 1 mm, of
approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth
complete
Sqm
1002.52
0.00
G 16 ROAD WORK
1
16.1
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after
excavating earth to an average of 22.5 cm. depth, dressing to camber and consolidating with road roller
including making good the undulations etc. and re roller including making good the undulations etc. and re-
rolling the sub grade and disposal of surplus earth lead upto 50 metres.
Sq.Mt.
2975.50
0.00
2
16.78
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing
in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts,
spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting
with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineerin- Charge.
i 16.78.1 With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value- 30 Cum 297.55
0.00
3 16.3 Supplying and stacking at site.
i 16.3.2 63 mm to 45 mm size stone aggregate Cu.Mt. 110.39 0.00 ii 16.3.7 Stone screening 11.2 mm nominal size (Type B) Cu.Mt. 21.03 0.00
4
16.4
Laying, spreading and compacting stone aggregate of specified sizes to WBM specifications in
uniform thickness, hand picking, rolling with 3 wheeled road / vibratory roller 8-10 tonne capacity in
stages to proper grade and camber, applying and brooming requisite type of screening / binding material to
fill up interstices of coarse aggregate, watering and compacting to the required density .
Cu.Mt.
131.42
0.00
5
16.43
Providing and laying design mix cement concrete of M-30 grade, in roads/taxi tracks/ runways, using
cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in
appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie
bars wherever required, laying at site, spreading and compacting mechanically by using needle and
surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form
work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion,
construction & longitudinal joints ( 10 mm wide x50 mm deep) by groove cutting machine, providing and
filling joints with approved joint filler and sealants, complete all as per direction of Engineerin-
charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately). Note:-Cement
content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.
i 16.43.2 Cement concrete manufactured in automatic batching plant (RMC plant) i/c transportation to site in transit mixer Cu.Mt. 350.45
0.00
6 16.44 Extra for providing and mixing hardening compound of approved quality as per manufacturer’s specification in cement concrete. Litre 146.00
0.00
7
16.45
Providing and fixing in position pre-moulded joint filler in expansion joints.
per cm
depth
per cm
width
per m length
370.00
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
8
16.46.1
Providing and laying in position bitumen hot sealing compound for expansion joints etc. Using grade ‘A’
sealing compound.
depth per cm
width per m length
370.00
0.00
9
16.47
Painting runway/taxi track/apron marking with adequate nos of coats to give uniform finish with road marking paint of superior make as approved by the Engineer-in-charge, i/c cleaning the
surface of all dirt, scales, oil, grease and other foreign material etc. and lining out complete.
i 16.47.1 New work (Two or more coats) Sq.Mt. 617.64 0.00
10
16.63
Providing, laying and making kerb channel 30 cm wide and 50 mm thick with cement concrete 1:3:6 (1
cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40
mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top
smooth etc. complete and as per direction of Engineer-in-charge.
Sq.Mt.
50.00
0.00
11
16.69
Providing and laying at or near ground level factory made kerb stone of M- 25 grade cement concrete in
position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse
sand), including making joints with or without grooves (thickness of joints except at sharp curve shall
not to more than 5mm), including making drainage opening wherever required complete etc. as per
direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment).
(Precast C.C. kerb stone shall be approved by Engineer-in-charge).
Cu.Mt.
142.06
0.00
12
8.12
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear
as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm
thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and
jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching
shade including rubbing, curing and polishing etc. all complete as specified and as directed by the
Engineerin- Charge :
i 8.12.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. Sq.Mt. 10.00
0.00
13
11.2
Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement
slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on
20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).
i 11.20.1 Light shade pigment using white cement Sqm 108.48 0.00
14
8.12
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear
as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm
thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and
jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching
shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineerin- Charge :
i 8.12.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. Sqm. 10.00
0.00
15
16.91.1
Providing and laying factory made coloured chamfered edge Cement Concrete paver blocks of required
strength, thickness & size/shape, made by table vibratory method using PU mould, laid in required colour &
pattern over 50mm thick compacted bed of fine sand, compacting and proper embedding/laying of inter
locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,
filling the joints with jamuna sand and cutting of paver blocks as per required size and pattern, finishing
and sweeping extra sand in footpath, parks, lawns, drive ways or light traffic parking etc. complete as per
manufacturer’s specifications & direction of Engineerin- Charge.80mm thick C.C. paver block of M-35
grade with approved colour, design & pattern.
Sq.Mt.
1223.24
0.00
16
16.92
Providing and fixing 10x10x7.50 cm Granite stone block hand cut and chisel dressed on top, for paving in
floors, drains etc. laid over 20mm thick base mortar 1:4 (1cement:4 coarse sand) with joints 10mm wide
filled with same mortar including ruled pointing etc. complete as per direction of engineer-in charge.
Sq.Mt.
75.00
0.00
17
16.93
Providing and placing in position 100mm thick factory made machine batched & machine mixed
Precast RCC Rectangular Covers on drains of footpath of various sizes,of M-25 grade cement concrete for
RCC work, including cost of centering, shuttering, reinforcement of 8mm dia TMT bars of Fe 500 grade @
maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all
edges with 1.6 mm thick , 100mm wide MS sheet duly painted over priming coat , reinforcement to be
welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage ,all
leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge.
Sq.Mt.
49.14
0.00
18
19.32 Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks
and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design.
I 19.32.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Each 2.00 0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
19
19.36
Providing and laying Non Pressure NP-4 class (Heavy duty) R.C.C. pipes including collars/spigot
jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including
testing of joints etc. complete
i 19.36.1 450 mm dia RCC pipes. Rmt. 50.00 0.00
20
19.3
Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in
cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal
dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of
frame 15 kg), R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size), foundation concrete 1:5:10 (1 cement : 5 coarse sand(Zone-III) : 10 graded stone aggregate
40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand),
finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design:
i
19.30.2.1
Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets : With common
burnt clay F.P.S. (non modular) bricks of class designation 7.5
Each
25.00
0.00
21 19.31 Extra for depth beyond 45 cm of brick masonry chamber :
i 19.31.2.1 For 500x700 mm size, With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Rmt. 30.00
0.00
22
16.49
Making bell mouth opening/ entrance of size 100x50x50 cm for drainage pipe under footpath, including
providing cement concrete 1:3:6 (1 cement :
3 coarse sand : 6 graded stone aggregate 20 mm nominal size) for shape of bell mouth, including plastering
providing and fixing precast R.C.C./S.F.R.C. slab including plastering with cement mortar 1:3 (1
cement : 3 fine sand) of 6 mm thickness on exposed surface of the slab & bell mouth including centring,
shuttering & neat cement punning inside the bell mouth etc. all complete.
Each
20.00
0.00
H HORTICULTURE AND LAND SCAPING
1
2.2
Supplying and stacking of good earth at site including royalty and carriage upto 5 km complete (earth
measured in stacks will be reduced by 20% for payment).
Cu.Mt.
197.21
0.00
2
2.4
Supplying and stacking at site dump manure from approved source, including carriage upto 5 km complete
(manure measured in stacks will be reduced by 8% for payment) :
i 2.4.2 Screened through sieve of I.S. designation 16 mm Cu.Mt. 45.61 0.00 ii 2.4.3 Screened through sieve of I.S. designation 4.75 mm Cu.Mt. 45.61 0.00 3 2.7 Fine dressing of the ground. Sq.Mt. 912.25 0.00
4
2.8 Spreading of sludge, dump manure and/or good earth in required thickness as per direction of officer-in-
charge (cost of sludge, dump manure and/ or good earth to be paid separately).
Cu.Mt.
197.21
0.00
5 2.9 Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge Cu.Mt. 197.21
0.00
6
2.1
Grassing with selection No. 1 grass including watering and maintenance of the lawn for 60 days or more till
the grass forms a thick lawn, free from weeds and fit for mowing including supplying good earth, if
needed (the grass and earth shall be paid for separately).
i 2.10.2 With grass Turf Sq.Mt. 912.25 0.00
7
2.13
Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base
to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or
manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% : one part of stacked
volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary,
watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared
unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to
1.5 m complete (cost of sludge, manure or extra earth to be paid for separately)
Cu.Mt.
150.00
0.00
8
2.14
Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or
sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of
stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of
rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if
needed to be paid for separately) :
i 2.14.1 Holes 1.2 m dia and 1.2 m deep Each 66.00 0.00 ii 2.14.2 Holes 90 cm dia, and 90 cm deep Each 34.00 0.00 iii 2.14.3 Holes 60 cm dia, and 60 cm deep Each 10.00 0.00 iv 2.14.4 Holes 45 cm dia, and 45 cm deep. Each 6.00 0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
9
2.16
Providing and fixing M.S. flat iron tree guard 60 cm dia and 2 m high, above ground consisting 4 nos 25 x 6
mm, 2.25 m long and 8 nos 25 x 3 mm 2 m long verticals M.S. flats, riveted to 3 nos 25 x 6 mm M.S. flat iron
rings in two halves, fixing together at site with required six numbers of 8 mm dia and 30 mm long bolts,
including painting two coats with synthetic enamel paint of approved brand and manufacture over a coat
of primer. One name plate of 1 mm thick M.S. sheet of size 250x100 mm shall be welded to the tree guard
near the middle height and lettered CPWD / PWD/ any other approved name. The tree guard shall be
suitably fixed to the ground by embedding four legs of tree guard in pits of suitable dia and to a depth of 25
cm, refilling the pits with soil and ramming, complete in all respect as per satisfaction and direction of Officer-in-charge.
Each
16.00
0.00
10
2.26
Providing and fixing M. S. tree guard 45 cm square in plan, height 1.20 metre above ground level and 0.40
metre below ground level. The vertical members shall consist of four nos. angle iron of size 25x25x3 mm,
1.6 m long, one at each corner and 8 nos flat iron of size 25x3 mm, 1.2 m long. The vertical members shall
be welded to 4 nos. 25x6 mm M. S. flats placed horizontally around the vertical member of the cage. One
name plate of 1 mm thick M.S. sheet of size 250x100 mm shall be welded to the tree guard near the middle
height and lettered CPWD/ PWD/ any other approved name. The tree guard shall be fixed to the ground
by making suitable holes and by embedding four corners leg in the ground, including refilling the earth,
compaction etc. complete. The tree guard shall be painted with two or more coats of synthetic enamel
paint of approved brand and manufacture over a coat of primer, complete in all respect.
Each
50.00
0.00
11
2.29
Providing Circular Cement Concrete pots of specified size, cast with cement concrete of nominal mix 1:2:4
(1 cement: 2 coarse sand: 4 graded stone aggregate 6 mm nominal
size), reinforced with 7 Nos ( 3 nos horizontal & 4 nos vertical “ U “ shape) M.S. wires of
3.5 mm dia as per design, including required form work, finishing with cement punning on exposed
surface, curing for specified period and stacking in required rows & height, all complete as per direction
of Officer-in-charge.
i 2.29.1 Top inside dia 35 cm, outer bottom dia 25 cm, total height 35 cm with wall thickness of 25.4 mm Each 65.00
0.00
12
2.3
Providing Square Cement Concrete pots of specified size, cast with cement concrete of nominal mix 1:2:4 (1
cement: 2 coarse sand: 4 graded stone aggregate 6 mm nominal
size), reinforced with 7 Nos ( 3 nos horizontal & 4 nos vertical “ U “ shape) M.S. wires of
3.5 mm dia as per design, including required frame work, finishing with cement punning on exposed
surface, curing for specified period and stacking in required rows & height, all complete as per
direction of Officer-in-charge.
i 2.30.1 Top inner width 35 cm, outer bottom width 25 cm, total height 35 cm and wall thickness 25.4 mm Each 50.00
0.00
13
2.33
Providing and laying Neelgiri/Mexican grass turf with earth 50mm to 60mm thickness of existing ground
prepared with proper level and ramming with tools wooden (Dhurmos) and than rolling the surface
with light roller make the surface smoothen and light waterning with sprinkler and maintenance for 30
days or more till the grass establish properly, as per direction of officer-in-charge.
Sq.Mt.
912.25
0.00
14
2.4
Complete maintenance of the entire garden features having as per yard stick in the garden area i.e. lawn
trees, shrubs, hedge, flower beds, foliages, creepers etc. including hoeing,weeding pruning replacement of
plants, gap filling, watering, mowing of lawn, grass cutting by lawn mover and brush cutter , removal of
garden waste, applying insecticide, pesticide & fertilizers(whenever required) top dressing of lawn with
good earth and menure and maintenance of other garden related works as directed by office- in-charge
(Cost of Good Earth, Manure, Fertilizer, Insecticide , Pesticide will be provided by the Department & lawn
mover and brush cutter with fuel , other T & P material/articles shall be provided by the contractor.)
i 2.40.5 Play grounds / Public parks (as per yard stick 1Mali =2.00Acre). q.Mt. Per 912.25 0.00
15
2.43
Complete maintenance of shrubs (Out side garden features), jobs like making of basin at regular interval i/c
watering, weeding, pruning & application of fertilizer etc, (excluding the cost of material which shall be
supplied by the department) and as per direction of officer in charge.
hrub Per
250.00
0.00
16
2.5
Providing & fixing of White River (Stone) Pables size of 2" to 2.50" dia in natural colour
at site of work including loading, unloading, carriage and all taxes paid etc.and as per direction of officer in
charge.
Qtl.
5.00
0.00
17
2.55
Providing and applying anti termite treatment of infected trees i/c all branches/leaves by spraying
chemical emulsion 0.5% (Chlorpyriphos 20% EC) concentration through power spray machine (@ 100 ml
Chlorpyriphos per tree i/c cost of chemical) and as per direction of officer-in-charge.and as per
direction of officer-in-charge.
Each Tre
100.00
0.00
18
2.56
Anti termite treatment of lawn area through premise 30.50% I P. one liter premise diluted in 499 liters
water and applying solution @ 1.00 litre solution per sqm lawn or bed area.(two application) i/c cost of
chemical)and as per direction of officer-in- charge.and as per direction of officer-in-charge.
Sq.Mt.
228.06
0.00
19 4 Rose Plants
i
4.87 Providing and Displaying plants Budded Rose (H.T. variety) 3 to 4 healthy branch 30 cm and above ht. well
developed with one and above flower plant in 20 cm Earthen Pot, as per direction of the officer-in-charge.
Each
10.00
0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
ii
4.88 Providing and Displaying plants Creeper Rose variety 3 to 4 healthy branch 60 cm and above ht. well
developed with one and above flowers in 25 cm Earthen Pot, as per direction of the officer-in-charge.
Each
15.00
0.00
iii
4.89 Providing and Displaying plants Standard Rose (H.T. variety) 3 to 4 healthy branch 90 cm and above ht. well
developed with one and above flowers in 25 cm Earthen Pot, as
per direction of the officer-in-charge.
Each
25.00
0.00
20 5 Ornamental Plants
i
5.1
Providing and Displaying Acalypha plant Different colour well developed, fresh & healthy with good
foliage, multi branch 30 to 45 cm ht. in 20 cm size of Earthen Pot/ Plastic Pot bushy plant as per
direction of the officer-in-charge.
Each
6.00
0.00
ii
5.3
Providing and Displaying Acalypha red plant well developed with fresh & healthy 30 to 45 cm ht. in 20 cm
size Earthen Pot/ Plastic Pot as per direction of the officer-in-charge.
Each
14.00
0.00
iii
5.26
Providing and Displaying Ficus reginold piller type Topiary plant well developed with
fresh & healthy 210 to 240 cm ht in 40 cm Cement Pot as per direction of the officer-in- charge.
Each
6.00
0.00
iv
5.12
Providing and Displaying Bougainvillea named variety, Sobhra, Thima, Marry palmar, Cherry Blossom
etc. well developed with fresh & healthy bushy plant in full bloom 75 to 90 cm ht. in 40 cm Cement Pot as
per direction of the officer-in-charge.
Each
5.00
0.00
v
5.21 Providing and Displaying Ficus Long Island topiary plant well developed with fresh & healthy 5 to 6 ball
specific size and shape 120 to 150 cm ht in 40 cm Cement Pot as per direction of the officer-in-charge.
Each
5.00
0.00
21 6 Ground Covers Plants
i
6.7 Providing and Displaying of Clerodendron inerme plant of ht. 30 cm to 40 cm multi branched in 25 cm
size of Earthen Pot / Plastic Pot & as per direction of the officer-in-
charge.
Each
4.00
0.00
ii
6.17 Providing and Displaying of Iresine herbstii plant, of height 20-30 cm., full of branches well developed in 20
cm size of Earthen Pot / Plastic Pot & as per direction of the officer
in-charge..
Each
10.00
0.00
iii 6.3 Providing and Displaying of Wadelia trilobata plant,full of leaves in 15 cm size of Poly bags & as per direction of the officer-in-charge. Each 25.00
0.00
22 7 Tree Plants
i 7.4 Supply and stacking of Alstonia scholaris plant of height 150-165 cm. in bag of size 25 cm as per direction of the officer-in-charge. Each 5.00
0.00
ii 7.7 Supply and stacking of Bauhinia blakeana (Kachnar) plant of height 120- 150 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge. Each 10.00
0.00
iii
7.27 Supply and stacking of Ficus benjamina (green) plant of height 150-165 cm., bushy with healthy branches
and lush green foliage in big size HDPE bags as per direction of the officer-in-charge.
Each
7.00
0.00
iv 7.36 Supply and stacking of Ficus religiosa (Peepal) plant of height 150-165 cm. in big poly bags of size 30 cm as per direction of the officer-in-charge. Each 10.00
0.00
v 7.6 Supply and stacking of Nauclea cadamba (Kadam) plant of height 150-165 cm. in big poly bag of size 25 cm as per direction of the officer-in-charge.v Each 15.00
0.00
vi 7.68 Supply and stacking of Plumeria acutifolia plant of height 150-165 cm. with 3-4 branches in big size HDPE bag as per direction of the officer-in-charge. Each 10.00
0.00
vii
7.9 Supply and stacking of Washingtonia filifea palm plant stem ht. 120-135 cm with 8-10 healthy leaves lush
green leaves well developed in big size HDPE Bags as per direction of the officer-in-charge.
Each
5.00
0.00
23 8 SHRUBS
i 8.4 Supply and stacking of plant Caesalpinia pulcherrima species of height 45-60 cm. in earthen pot of size 20 cm as per direction of the officer-in-charge. Each 8.00
0.00
ii
8.7
Supply and stacking of plant Calliandra hybrida of height 105-120 cm., well branched, bushy in big size
HDPE bag as per direction of the officer-in-charge.
Each
10.00
0.00
iii 8.29 Supply and stacking of plant Hamelia patens of height 30-45 cm. with 3-4 branches in poly bags of size 20 cm as per direction of the officer-in-charge. Each 10.00
0.00
iv
8.33
Supply and stacking of plant Hibiscus rosasinensis of height 45-60 cm. with 3-4 branches in earthen pots of
size 20 cm as per direction of the officer-in-charge.
Each
6.00
0.00
v
8.58
Supply and stacking of plant Tabernaemontana coronaria (Chandni single) of height 90- 105 cm,bushy in
big size HDPE bag as per direction of the officer-in-charge.
Each
18.00
0.00
vi 8.67 Supply and stacking of plant Tecoma gaudichaudi of height 90-105 cm.,bushy in big size HDPE bag as per direction of the officer-in-charge. Each 14.00
0.00
TOTAL
External Development including Horticulture & Road work (carried over to
Summary of civil works)
0.00
SIGNAGES
I
Providing and fixing of signages, modular curved frame technology, of various widths and lengths, to form
suggested usages, made of aluminium extruded sections, duly anodised, all signages shall be provided with
0.6-0.8mm polycarbonate protecting film over the prints, of appropriate size, print shall on 0.6mm
coated, YUPO, make: biogradable sheet printed on HP 4500 UV flat bed printer., Model: Illusion, by SIGNSUTRA or equivalent.
1 WFS Way finding Signs
a Way finding ceiling hung sign(both side) Size-(1000x150)mm each 25 0
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
b Way finding ceiling hung sign(both side)Size-1500x150 each 17 0 2 TOI Toilets
a G,L,H Gents ,Ladies & Handicap - Wall Projected(both side) Size-250x210 each 34 0
b Door mounted Size- 120x120 each 48 0
c
CR
Change room with Toilet (Gents,Ladies & Nurses) - Wall Projected (both side) Size- 250x210
each
7
0
d Door mounted Size-120x120 each 14 0
e attch Attached Toilet Door mounted Size- 120x120 each 41 0
f CU Cubicles WC, Bath,Change, Janitor Size-120x120 each 110 0
3 NP Door /Name plate
a Number plate (4 digits) Size- 150x80 each 299 0
b Room Usage Size-300x80 each 218 0
c Doctor's/ Occupant's name Size-300x80 each 32 0
d Wall mounted over Door Size-600x150 each 195 0 e Number directional plate ,single line text Size-600x150 each 40 0
f Number plate Toilet Size- 120x60 each 34 0
g Staircase number plate Size- 400x150 each 29 0
h Ward no./Bed nos Size-600x150 each 58 0 4 NS Nurse Station
a Wall projected(both side) Size-250x210 each 9 0
b Behind Counter Size-800x150 each 24 0
c Ceiling hung over counter(both sides) Size-800x150 each 24 0 5 REG Registration/Reception etc.
a Behind Counter Size-800x150 each 1 0
b Ceiling hung over counter(both sides) Size-800x150 each 2 0 6 XR Radiography/MRI/CT Scan etc.
a Wall projected(both side) Size-250x210 each 3 0
b Door mounted Size-120x120 each 6 0 7 DN Department Name
a Wall mounted Size-600x150 each 29 0
b wall mounted Size-1000x150 each 8 0
8 WL Waiting Lounge
a Wall mounted Size-1000x150 each 14 0
b Ceiling hung (both sides) Size- 1000x150 each 18 0
9 OT Others
a Lifts (Elevators nos.) Size- 400x150 each 64 0 b Stairs Wall Projected(both side) Size- 250x210 each 19 0
c Drinking Water Size-400x150 each 16 0
d Electric / AHU rooms Size-400x150 each 37 0
e Bed number in more than 2 bedded rooms Size- 120x80 each 443 0 10 DLL Directory at Lift Lobby
a Floor(levels) Size-300x300 each 42 0 b Department Size-300x300 each 2 0
11 DD Department Direction
a W Wall mounted Size-600x300 each 14 0
12 DN Department Name
a C Ceiling hung (both sides) Size-1000x150 each 16 0
II
Providing and fixing of Snap fit frames,made of aluminium extruded profiles duly anodized , and shall be
also provided with .8mm thick polycarbonate film to protect
/hold the insertions. And 8mm thick MDF/PVC FOAM BOARD, as main inserion panel., Model: Tiara, by SIGNSUTRA or Equivalent.
1 SFF SNAP FIT FRAMES Size-600X450 each 91 0 2 SFF SNAP FIT FRAMES Size-600X900 each 40 0
III
Providing & fixing of 1mm,photoluminiscent sheel duly fitted in ABS moulded frame of size 300x300 mm,
Model: Auro, by SIGNSUTRA or Equivalent.
1 EDP ELEVATOR DISCLAIMER PLATE Size- 300x300 each 40 0
IV
FSS
Providing and fixing of edge lit ,emergency exit sign with 2 hrs power back up, concealed in false ceiling. Model: PROLITE AUTOGLO make or equivalent
1 H EXIT SIGN EDGE LIT (recess mounting)with 2hr backup Standard each 92 0 2 E EXIT LIGHT WITH 2 HR BACKU(Exit at Stairs entry/ Deptt. Exit) Standard each 32 0
V
PL
Providing and fixing of Photoluminescent, 1mm rigid pvc based sheet containg lumingen 3, as base
chemical,with high intensity luminous glow capacity. each sign shall be fixed in ABS moulded frames. The
rigid PVC sheets shall be fixed by using 3M double side adhsive tapes, all frames to be fixed on wall surface
by using approved fixing arrangements. Model: Ebony, by SIGNSUTRA or Equivalent.
1 FH PHOTOLUMINESCENT , FIRE HOSE Size- 200x200 each 17 0
2 ES PHOTOLUMINESCENT ,ESCAPE SIGN Size-300x150 each 87 0
3 FLV PHOTOLUMINESCENT ,FLOOR LEVEL Size-300x300 each 42 0 4 FA PHOTOLUMINESCENT ,FIRE ALARM CALL POINT Size- 200x200 each 18 0
5 EVA PHOTOLUMINESCENT , ROOM EVACUATION PLAN Size-300x200 each 81 0
6 P&P PHOTOLUMINESCENT ,PULL AND PUSH 100mm dia each 41 0 7 MISC. PHOTOLUMINESCENT SIGNS , ASSORTED Size- 300x150 each 16 0 8 FE PHOTOLUMINESCENT SIGNS , FIRE Extinguishers Size-200x200 each 17 0
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
9
PBO
PHOTOLUMINESCENT SIGNS , FIRE Exit door sign (push bar to open)w/o ABS frame Size-800x150
each
29
0
VI
XRAY
Providing and fixing of internally illuminated signage made with aluminium profile with insertion of 3mm
Cast acrylic duly cladded with electrocut casted 3M vinyl of required color, illumination by GE or Osram
or Samsung LED, as per Design., Model: Espire, by SIGNSUTRA or Equivalent.
1 Radiography/MRI/CTScan etc.
a In use (illuminated) Size- 400x400 each 6 0
VII
BNW
Providing and fixing of exterior signage, to be fixed with the help of MS framework, Signage to be made of
MS pipe frame work, cladded with 3mm Aluminium composite panel, duly cut by CNC router, and the
letters to be made from aluminum extruded profiles of 80mm width, duly bend by CNC benders and front
with 5mm cast acrylic and back made from 12 mm WPC ,front to be exterior grade vinyl of 3M, The signage
shall illuminated with back samsung LED, complete in all respects, recomended size, 8000x900,
with letter height of not less then 400mm
Building Name on Building's Top Wall faces Size-as per location sqmt 14.4 0
VIII
Providing and fixing of TOTEM , stating name of building on both sides,made of 0.8mm thick aluminium
sheet duly painted with Polyurethene paint of approved make and shade, aluminium sheet bented to
form a curve , and supported by moulded plastic components to hold the curve , the moulded plastic
components to be fixed on aluminium rails with clip on arrangment, a sper the product design. The Totem
shall be mounted over a rectangular base 300 mm high as per design. Model: POLKA, by Signsutra or equivalent.
a Floor Directory Totem Size-860x2400 sqmtr 6.2 0 d Area Allocation Totem Size-600x1800 sqmtr 2 0
IX
Providing and fixing Main Directory assembeled with standard alluminium alluminium extruded plates,
duly anodized.The plates shall be of size 1no. of 120mm wide as top subject plate and following plates of
any size and width to be of 40/60/80/100 mm width for contents plates. Each of the plates shall be
provided with 0.8 mm thick polycarbonate protecting film over the printed text and shall have a
arrangment to slide in the names as required. Model: Illusion, by SIGNSUTRA or equivalent.
a Main Directory Size-as per location sqmtr 6 0
X
Providing and fixing Main Directory assembeled with standard alluminium alluminium extruded plates,
duly anodized.The plates shall be of size 1no. of 120mm wide as top subject plate and following plates of
any size and width to be of 40/60/80/100 mm width for contents plates. Each of the plates shall be
provided with 0.8 mm thick polycarbonate protecting film over the printed text and shall have a
arrangment to slide in the names as required. Model: Illusion, by SIGNSUTRA or equivalent.
a Doctors' Directory Size-as per location sqmtr 6 0
XI
Providing and fixing Customised signage made of Stainess steel 304 grade Channel letters made from CNC
bender, and laser welded with 5mm laser cut acrylic of 600mm height, 100 mm in depth with acrylic front
with LED(tetra or minimax of GE) internally illumination. The letters shall be mounted on MS framing as
per approved design
.recomended size 5000x600, Model: Halo, by SIGNSUTRA or equivalent
Main & Emergency Entrances with Logo Size-as per location each 1 0
XII
Providing and fixing of exterior signage, to be fixed with the help of MS framework, Signage to be made of
MS pipe frame work, cladded with 3mm Aluminium composite panel, duly cut by CNC router, and the
letters to be made from aluminum extruded profiles of 80mm width, duly bend by CNC benders and front
with 5mm cast acrylic and back made from 12 mm WPC ,front to be exterior grade vinyl of 3M, The signage
shall illuminated with back samsung LED, complete in all respects , recomended size, 5000x900,
with letter height of not less then 400mm
Subsidary Entrance Sign Size-as per location sqmtr 9 0
XIII
Providing and fixing "Caution Signs" measuring 600 x 800 mm, made on 3mm aluminium sheet size
500x500, mounted on MS 60x60mm poles using aluminium fixture, 2400mm high, signage to be made with
reflective vinyl base and text
/pictogram on reflective vinyl. MS pipe to be grouted and painted as per the specs provided in the drg.
Model: Assure, by SIGNSUTRA or equivalent.
Drive way Sign Size- 600x800 each 11 0
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
XIV
Providing and fixing External direction Signage measuring 4 nos, 1200 mm long, 150 mm high
aluminium extruded profiles panels fitted into 60mm aluminium extruded poles , panels to have
pictograms and taxt in reflective vinyl ,as for Parking Direction Sign postings, Framed signs are secured
to 2 GI round powder coated pipe poles 200 mm high with customised fixtures. Model: Agora, by SIGNSUTRA or equivalent.
External Signage Size-1200x 1600 each 12 0
XV
Providing and fixing Evacuation floor plans measuring 500mmx 600mm made of 5 mm foam board and
1mm thick rigid plastic photoluminiscent printed plans framed into 25mmx20mm extruded aluminium
tubular frame with necessary holding slots. Model: Fringe, by SIGNSUTRA or equivalent.
1 Evacuation Plans Floor wise Size-500x600 each 52 0
XVI
Providing and fixing of exterior signage, to be fixed with the help of MS framework, Signage to be made of
MS pipe frame work, cladded with 3mm Aluminium composite panel, duly cut by CNC router, and the
letters to be made from aluminum extruded profiles of 80mm width, duly bend by CNC benders and front
with 5mm cast acrylic and back made from 12 mm WPC ,front to be exterior grade vinyl of 3M, The signage
shall illuminated with back samsung LED, complete in all respects, recomended size, 5000x900,
with letter height of not less then 400mm
Entrance Gate (External Signs) Size-as per location sqmt 9 0
XVII
Providing and fixing of traffic regulatory signages, made on 3mm aluminium sheet size 500x500, mounted
on MS 60x60mm poles using aluminium fixture, 2400mm high, signage to be made with reflective vinyl
base and text /pictogram on reflective vinyl. MS pipe to be grouted and painted as per the specs provided
in the drg. Model: Assure, by SIGNSUTRA or equivalent.
Traffic regulatory Signage Size-500x500 each 16 0
XVIII
Providing and fixing of prohibition signages, made on 3mm aluminium composite panel sheet size 300x300,
mounted with SS studs / 3M VHB tape as per locations, ACP to be screen printed with approved color and
design as per the specs provided in the drg. Model: Veto, by SIGNSUTRA or equivalent.
a Silent Zone Size-300x300 each 32 0
b No Smoking Size-300x300 each 32 0
c Restricted area-authorised personnel only Size-300x300 each 24 0 d No Eatables Size-300x300 each 24 0
e No crowding Size-300x300 each 24 0 f Use of Mobile phones prohibited Size-300x300 each 23 0
g No littering Size- 300x300 each 23 0 h No photography Size-300x300 each 16 0
i Safety Notice- be kept clear to Emergency carts Size- 300x300 each 24 0
j Misc. (As required) Size-300x300 each 16 0
Grand Total of Signages 0
UG TANK
A 2.0 EARTH WORKS
1
2.6
Modified
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas
(exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated
earth, irrespective of lead and lift upto 1.5m, disposed earth to be levelled and neatly dressed.
i 2.6.1 All kinds of soil Cum 2157.34 0.00
2
2.7
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas
(exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and
disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.
i 2.7.1 Ordinary rock Cum 132.69 0.00
3 2.26 Extra for every additional lift of 1.5 m or part thereof in.
2.26.1 All kinds of soils
i i 1.5m to 3m Cum 648.95 0.00
ii ii 3m to 4.5m Cum 648.95 0.00
iii iii 4.5m to 6m Cum 340.27 0.00
4
2.25
Modified
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in
layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering,
irrespective of lead and lift upto 1.5 m.
Cum
348.55
0.00
5 2.27 Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete.
Cu.Mt. 30.83
0.00
6 1.1.2 Carriage of Earth by mechanical transport including loading, unloading and Stacking including royalty & carriage up to 5 KM complete.
Cum 1941.48
0.00
B 4.0 CONCRETE WORKS
1 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
i 4.1.8 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Cu.Mt. 53.44
0.00
C 5.0 REINFORCED CEMENT CONCRETE WORK
1 5.9 Centering and shuttering including strutting, propping etc. and removal of form for :
a 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete. Sqm 57.61 0.00
b 5.9.2 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Sqm 1628.11
0.00
c 5.9.3 Suspended floors, roofs, landings, balconies and access platform. Sqm 290.09 0.00 d 5.9.7 Stairs, (excluding landings) except spiral-staircases. Sqm 23.12 0.00 e 5.9.16 Edges of slabs and breaks in floors and walls
5.9.16.1 Under 20 cm wide Rmt 79.82 0.00
f
5.11
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping
etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional
height of 1 metre or part thereof (Plan area to be measured).
i 5.11.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
Sq.Mt. 512.49
0.00
2 5.22B
Modified
Reinforcement for R.C.C. work ready to use "cut and bend" rebars of approved make from
factory/workshop to construction site including placing in position and binding all complete upto plinth level.
i 5.22.B.1 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 48306.28 0.00
4
5.33
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work, using cement content as per approved design mix,
including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing
and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate,
retard setting of concrete, improve workability without impairing strength and durability as per
direction of Engineer-in-charge.
(Note :- Cement content considered in this item is @ 330 kg/Cum. Excess/less cement used as per design mix is payable/recoverable separately).
i 5.33.1 All works upto plinth level. Cum 468.49 0.00 5 5.34 Extra for providing richer mixes at all floor levels.
Note:- Excess/less cement over the specified cement content used is payable /recoverable separately.
i 5.34.1 Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/Cum).
Cum 468.49
0.00
D 6.0 BRICK WORK
1 6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:
i 6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 5.18 0.00
E 10.0 STEEL WORK
1
10.25 Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and
applying a priming coat of approved steel primer using structural steel etc. as required.
i 10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
KG 715.50
0.00
2
10.5
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S.
gusset plates at the junctions and corners, all necessary fittings complete, including applying a
priming coat of approved steel primer.
I 10.5.1 Using M.S. angels 40x40x6 mm for diagonal braces Sqm 2.52 0.00
3
19.15 Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks
1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design :
i 19.15.1 With 20x20 mm square bar Each 90.00 0.00
4 19.19 Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape and approved quality 19.19.1 L D- 2.5 H D - 20
i 19.19.3.1 Circular shape 560 mm internal diameter Each 6.00 0.00
F FLOORING & CLADDING WORK
1
11.26
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement
slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete
with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
i 11.26.1 25 mm thick. Sqm 198.25 0.00
2
11.27
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick
cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment
to match the shade of the slabs, including rubbing and polishing complete.
Sqm
14.22
0.00
3 11.31 Extra for pre finished nosing to treads of steps of kota stone/sand stone. Metre 46.00 0.00
Medical College(G+7), Boq.
Sl. No. DSR Code DESCRIPTION UNIT QTY. RATE Amount (in Rs.)
4 11.32 Extra for kota/sand stone flooring in treads of steps and risers using single length up to 1.05 metre.
Sqm 29.70
0.00
5
11.36
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be
specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle
green, black of any size as approved by Engineerin- Charge, in skirting, risers of steps and dados, over 12
mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @
3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Sqm
567.00
0.00
6
11.38
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the
manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except
White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4
Coarse
sand), jointing with grey cement slurry @ 3.3 kg/ sq.m including pointing the joints with white cement and matching pigments etc., complete.
Sqm
128.21
0.00
G 22.0 WATER PROOFING
1
22.20.1
Providing and laying APP (Atactic Polypropylene Polymer) modified prefabricated five layer 3 mm
thick water proofing membrane, black finished reinforced with non-woven polyester matt consisting of
a coat of bitumen primer for bitumen membrane @ 0.40 litre/sqm by the same membrane manufacture
of density at 25°C, 0.87-0.89 kg/ litre and viscocity 70-160 cps. Over the primer coat the layer of
membrane shall be laid using Butane Torch and sealing all joints etc, and preparing the surface complete.
The vital physical and chemical parameters of the membrane shall be as under : Joint strength in
longitudinal and transverse direction at 23°C as 650/ 450N/5cm. Tear strength in longitudinal and
transverse direction as 300/250N. Softening point of membrane not less than 150°C. Cold
flexibility shall be upto -2°C when tested in accordance with ASTM, D - 5147. The laying of membrane
shall be got done through the authorised applicator of the manufacturer of membrane : 3 mm thick
Sqm
309.18
0.00
2
22.21
Extra for covering top of membrane with Geotextile, 120 gsm non woven, 100% polyester of
thickness 1 to 1.25 mm bonded to the membrane with intermittent touch by heating the membrane by
Butane Torch as per manufactures recommendation.
Sqm
309.18
0.00
3
22.23
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing
treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums,
reservior, sewage & water treatment plant, tunnels
/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry :
2 parts water) for vertical surfaces and 3 : 1 (3 parts
integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative
(internal) side with the help of synthetic fiber brush. The material shall meet the requirements as
specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared
with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The
crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be
carried out all complete as per specification and the direction of the engineerin- charge. The
product performance shall carry guarantee for 10 years against any leakage.
i 22.23.1 For vertical surface two coats @0.70 kg per sqm Sqm 483.93 0.00
ii 22.23.2 For horizontal surface one coat @1.10 kg per sqm. Sqm 363.13 0.00
4
22.4
Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/
expansion joints between two RCC members and fixed to the reinforcement with binding wire
before pouring concrete etc. complete :
i 22.4.1 Serrated with central bulb (225 mm wide, 8-11 mm thick) Rmt 147.42 0.00 Total UG Tank carried over to Summary Civil works 0.00
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1
1
SUB HEAD-17.0-SANITARY INSTALLATIONS
(SCHEDULE ITEM)
1.1
8.1
Providing and fixing stone slab with table rubbed, edges
rounded and polished, of size 75x50 cm deep and 1.8 cm thick,
fixed in urinal partitions by cutting a chase of appropriate width
with chase cutter and embedding the stone in the chase with
epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 6 mm nominal size) as per
direction of Engineer-in-charge and finished smooth.
1.1.1 8.10.2 Granite Stone of approved shade Sqm 19.2 0
1.2
17.1
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen
sink as per IS: 13983 with C.I. brackets and stainless steel plug
40 mm, including painting of fittings and brackets, cutting
and making good the
walls wherever required :
1.2.1 17.10.1.3 510x1040 mm bowl depth 200 mm Each 11 0
1.3
17.11
Providing and fixing white vitreous china laboratory sink with
C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass
waste and 40mm C.P. brass trap with necessary C.P. brass
unions complete, including painting of fittings and brackets,
cutting
and making good the wall wherever required :
1.3.1 17.11.1 Size 450x300x150 mm (Lab sink) Each 23 0
1.4
17.22A
Providing and fixing CP Brass 32mm size bottle trap of
approved quality & make and as per the direction
of engineer in charge.
Each
211
0
1.5
17.28
Providing and fixing P.V.C. waste pipe for sink or wash basin
including P.V.C. waste fittings complete.
1.5.1 17.28.2 Flexible pipe
1.5.2 17.28.2.2 40 mm dia Each 10 0
1.6
17.3
Providing and fixing in posotion of 25 diameter mosquito
proof coupling as per approved municipal
design
Each
11
0
1.7 17.34 Providing and fixing toilet paper holder :
1.7.1 17.34.1 C.P. brass Each 241 0
1.8 17.35 Providing and fixing soil, waste and vent pipes:
17.35.1 100mm dia pipe
1.8.1
17.35.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Metre
4065
0
17.35.2 75mm dia pipe
1.8.2
17.35.2.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Metre
185
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.9
17.37
Providing and fixing M.S. holder-bat clamps of approved
design to Sand Cast iron/cast iron (spun) pipe embedded in and
including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size), including cost of cutting holes and making good
the walls etc. :
1.9.1 17.37.1 For 100 mm dia pipe Each 400 0
1.9.2 17.37.2 For 75 mm dia pipe Each 200 0
1.1
17.38
Providing and fixing bend of required degree withh access
door, insertion rubber washer 3 mm thick,
bolts and nuts complete.
17.38.1 100mm dia pipe
1.10.1
17.38.1.3
HublessCentrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
150
0
17.38.2 75mm dia pipe
1.10.2
17.38.2.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
50
0
1.11
17.39
Providing and fixing plain bend of required degree.
17.39.1 100mm dia pipe
1.11.1
17.39.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
250
0
17.39.2 75mm dia pipe
1.11.2
17.39.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
50
0
1.12
17.42
Providing and fixing double equal plain junction of
required degree
17.42.1 100x100x100x100
1.12.1
17.42.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
100
0
17.42.2 75x75x75x75
1.12.2
17.42.2.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
10
0
1.13
17.44
Providing and fixing single equal plain junction of
required degree
17.44.1 100x100x75x75
1.13.1
17.44.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
50
0
17.44.2 75x75x75x75
1.13.2
17.44.2.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
20
0
1.14
17.46
Providing and fixing double unequal plain junction of
required degree
17.46.1 100x100x75X75
1.14.1
17.46.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
10
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
17.48
Providing and fixings single unequal plain junction of
required degree
17.48.1 100x100x75
1.14.2
17.48.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
10
0
1.15
17.53A
Providing and fixings Hubless Centrifugally cast iron offset
epoxy coated inside and out side IS : 15905
17.53A.1 65 mm offsets
1.15.1 17.53A.1.1 With 100mm dia pipe Each 20 0
1.15.2 17.53A.1.2 With 75mm dia pipe Each 10 0
1.16
17.54A
Providing and fixings Hubless Centrifugally cast iron offset
epoxy coated inside and out side IS : 15905
17.54A.1 130 mm offsets
1.16.1 17.54A.1.1 With 100mm dia pipe Each 20 0
1.16.2 17.54A.1.2 With 75mm dia pipe Each 10 0
1.17 17.56 Providing and fixing terminal guard
17.56.1. 100 mm dia pipe
1.17.1
17.56.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
45
0
1.18
17.57A
Providing and Fixing shielded coupling for hubless
centrifugl cast iron pipe
1757A.1 100 mm dia pipe
1.18.1
17.57A.1.1
SS 304 grade coupling with EPDM rubber gasket
Each
1355
0
1757A.2 75mm dia pipe
1.18.2
17.57A.2.1
SS 304 grade coupling with EPDM rubber gasket
Each
60
0
1.19
17.6
Providing and Fixing floor trap of self cleansing design with
screwed down or hinged grating with or without vent arm
complete, including cost of cutting and making good the walls
and floors.
17.60.1 100 mm inlet and 100 mm outlet
1.19.1
17.60.1.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
347
0
17.60.2 100 mm inlet and 75 mm outlet
1.19.2
17.60.2.3
Hubless Centrifugally cast (spun) iron pipes epoxy
coated inside and out side IS : 15905
Each
20
0
1.2
17.8
Providing and fixing white vitreous china battery based
infrared sensor operated urinal of approx. size 610 x 390 x 370 mm
having pre & post flushing with water (250 ml & 500 ml
consumption), having water inlet from back side, including
fixing to wall with suitable brackets all as per manufacturers
specification and direction of Engineer-in-charge.
Each
64
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.21
18.1
Providing and Fixing G.I. Class "B" pipe complete with
G.I. Fittings and angle suports, clamps, including cutting
and making good the walls etc.
1.21.1 18.10.4 a) 32 mm dia Metre 370 0
1.21.2 18.10.5 b) 40 mm dia Metre 90 0
1.21.3 18.10.6 c) 50 mm dia Metre 220 0
1.22
18.21
Providing and fixing uplasticised PVC connection
pipe with brass unions :
122.1 18.21.2.1 15 mm nominal bore Each 452 0
1.23
18.4
Painting of G.I. Pipes and fittings with two coats of anti-
corrosive bitumastic paint of approved quality.
1.23.1 18.40.4 a) 32 mm dia Metre 370 0
1.23.2 18.40.5 b) 40 mm dia Metre 90 0
1.23.3 18.40.6 c) 50 mm dia Metre 220 0
1.24
18.53
Providing and fixing C.P. brass angle valve for basin mixer and
geyser points of approved quality
conforming to IS:8931
1.24.1 18.53.1 a) 15 mm nominal bore Each 452 0
1.25
NSR
Providing and fixing white vitreous china extended wall
mounting water closet, white vitreous china cistern with dual
flush fitting, of flushing capacity 2 litre/4 litre, including seat
cover, and cistern fittings, nuts, bolts and gasket etc
complete.(Make Jaquar Model no-CNS-WHT-353N, CNS-
WHT-203 or
equivalent as per list of make)
Each
53
0
1.26
NSR
Providing and fixing white vitreous china floor mounting
water closet, vitreous china cistern with dual flush fitting, of
flushing capacity 2 litre/4 litre, including seat cover, and cistern
fittings, nuts, bolts and gasket etc complete. (Make Jaquar Model
no-CNS- WHT-755SN, CNS-WHT-207 or equivalent as per list
of make)
Each
172
0
1.27
NSR
Providing and fixing wash basins with C.I. Brackets, 32mm C.P.
brass waste of standard pattern, including painting of fittings and
brackets, cutting and making good the walls and floors wherever
required. (Make Jaquar Model no-CNS-WHT-801 or equivalent
as per
list of make)
1.27.1
White Vitreous China Flat back wash basin size 550x
400x195 mm
Each
10
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.28
NSR
Providing and fixing white vitreous china oval wash basin for
top/under counter mounting with fabricated MS brackets
painted white synthetic enamel paint over a coat of primer
of approved brand, all of approved brand and manufacturer
to wall with and rubber adopter for waste connection
complete, including cutting and making good the walls &
Floors wherever required. (Make Jaquar Model no-CNS-
WHT-705 or equivalent as per list of make)
1.28.1
Oval wash basin size (595x420x200 ) mm under
counter basin
Each
211
0
1.29
NSR
Providing and fixing of low flow C.P. pillar tap approved make
as per direction of engineer in the charge. (Make Jaquar Model
no-AQT-CHR-3011 or
equivalent as per list of make)
Each
158
0
1.3
NSR
Providing & fixing low flow C.P. brass single hole basin Mixer
Tap with aerator of approved make complete in all respect as
directed by Engineer- incharge. (Make Jaquar Model no-CQT-
CHR-23167BG or equivalent as per list of make)
Each
53
0
1.31
NSR
Providing, fixing,testing and commisioning CP brass single
lever low flow wall mounted Sink / Lab Sink mixer of approved
make with 15 mm CP brass single lever swivel spout with
waste complete including cutting and making good the walls
where required
and as directed by Engineer-in-charge
1.31.1
Lab Elbow Sink mixer (Make Jaquar Model no-FLR- CHR-
5166G or equivalent as per list of make)
Each
23
0
1.31.2
Sink Mixer (Make Jaquar Model no-LYR-38173B or
equivalent as per list of make)
Each
11
0
1.32
NSR
Providing and fixing Stainless Steel Bed Pan sink with
C.I. brackets and stainless steel plug 40 mm, including
painting of fittings and brackets, cutting and making good
the walls where required and as
directed by Engineer-in-charge
Each
6
0
1.33
NSR
Providing , Fixing , testing and commissioning of CP Brass
Shower Mixer of approved make with provision of
overhead shower with 120 mm long bend pipe, in built spout,
spout/shower selector with wall flange complete with all
accessories as required and making good the walls wherever
required complete in all respect as directed by Engineer-in-
charge. (Make Jaquar Model no-CQT-CHR-
23273UPR or equivalent as per list of make)
Each
40
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.34
NSR
Providing , Fixing, testing and commissioning of CP Brass 120
mm long Shower Arm of approved make with wall flange and
pressure adjustable Shower Rose complete with all accessories
as required and making good the walls wherever required as
directed by Engineer-in-charge. (Make Jaquar Model no-SHA-
CHR- 477P or equivalent as per list of make)
Each
40
0
1.35
NS-11
Providing and fixing Nickel Chromium Plated towel rail 600
mm Long complete with brackets fixed to wooden cleats with
CP brass screws with concealed fittings arrangement of
approved quality and colour, of approved brand & manufacture
complete as per direction of Engineer in Charge. (Make Jaquar
Model no-ACN-CHR- 1111SM or equivalent as per list of
make)
Each
40
0
1.36
NSR
Providing,Fixing satin finish stainless steel AISI 316 grade wall
mounted twin coat hook on door complete in all respect as
directed by Engineer-in- charge. (Make Jaquar Model no-ACN-
CHR- 1161N or equivalent as per list of make)
Each
241
0
1.37
NSR
Providing & fixing of CP brass soap dish of approved design
with fittings etc complete as directed by Engineer-in-charge.
(Make Jaquar Model no-ACN- CHR- 1131N or equivalent as
per list of make)
Each
40
0
1.38
NSR
Providing and fixing of fully automatic "NO TOUCH" durable
& shock proof hand drier of approved make & manufacture
suitable to operate on 220 volts, single phase 50 hz, A.C. power
supply, 1500 Watt and directly plugged to power point
complete in ABS plastic body having drying time 20-30
seconds complete as per direction of Engineer in Charge.
(Make Jaquar Model no-HDR- WHT- M04A or
equivalent as per list of make)
Each
44
0
1.39
NSR
Providing,fixing,testing and commissioning Hand Shower
(Health Faucet) with 8mm Dia,1 Metre Long Flexible Tube &
Wall Hook of approved make and manufacture complete as per
direction of Engineer in Charge. (Make Jaquar Model no-ALD-
CHR- 585 or equivalent as per list of make)
Each
241
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.4
NSR
Providing and fixing Nickel Chromium Plated towel ring square
with round flange outer 210x210 mm dia of 8 mm round solid
bar with concealed fittings arrangement (Nickel chromium
plating should pass Salt Spray Test for 200 hours) of approved
quality and colour, of approved brand & manufacture
complete as per direction of Engineer in Charge. (Make
Jaquar Model no-ACN-CHR- 1121N or equivalent as per
list of make)
Each
53
0
1.41
NSR
Providing and fixing straight type Macfit single body push fit
type WC pan connector with factory supplied spring loaded
seal guard of McAlpine, UK with integral single mould
sealing fins made of flexible EVA body, including
bush/adaptor for use with C.I. Pipe as supplied with the pan
connector complete with all respect as per direction of
Engineer in
Charge.
Each
241
0
1.42
NSR
Providingand fixixing of handicapped toilet, Matrix set 1
(WB 65 X 35 with one pair mounting brackets,EWC &
Cistern complete with fittings and seat cover,one no hinged
rail 76 cm and five nos of grab rails 60 cm. (Make Jaquar Model
no-AHS-CHR- 1503 or equivalent as per list of make)
Each
16
0
1.43
NSR
Providing and fixing mirror of superior glass (of approved
quality) and of required shape and size with plastic moulded
frame of approved make and shade with 6 mm thick hard board
backing complete
as required.
Sqm
75
0
1.44
NSR
Providing and fixing Stainless Steel Floor Trap / Floor Drain
Grating 143x143x5 mm thick Screwable with SS Fixed Frame
150 x150 mm size as per approved make & model complete
in all respect as directed by Engineer-in- charge
Each
528
0
1.45
NSR
Providing & fixing 100mm x 50mm G.I. waste with reducing
elbow & nipple cutting chases, the floor / slab, repairs complete
as required and connection to GI / CI waste pipe complete in all
respect as directed
by Engineer-in-charge.
Each
161
0
1.46
NSR
Providing and fixing CP Brass floor cleanout plug / Clean out
plug as per drawing complete with G.I. Socket jointed to
drainage pipe outlet including drip seal joint complete in all
respect as directed by
Engineer-in-charge.
Each
186
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
1.47
NS-26
Providing and fixing multi-floor trap fitting with maximum 3
inlets 32,40 or 50 mm size fabricated from 100 dia GI pipes and
sockets,fixed to C.I. trap with Drip Seal joint and set in cement
concrete as per standard drawing complete in all respect as
directed
by Engineer-incharge.
Each
347
0
1.48
NSR
Providing and fixing low flow type bib tap as per approved
make complete in all respect as per
engineer in the charge
Each
35
0
1.49
NSR
Providing and fixing low flow type two way bib tap as per
approved make complete in all respect as per
engineer in the charge
Each
241
0
1.5
NSR
Providing and fixing liquid soap Dispenser capacity of 0.8ltr with
push button fixed in stainless steel and
C.P. brass screws including cutting and making good the wall wherever required.
Each
128
0
TOTAL OF SUB HEAD-17.0-SANITARY
INSTALLATIONS
0
2 SUB HEAD-18.0-WATER SUPPLY
2.1
2.1
Excavating trenches of required width for pipes cables etc
including excavation for sockets, and dressing of sides,
ramming of bottoms, depth upto 1.5 m ncluding getting out the
excavated soil , and then returning the soil as required , in
layers not exceeding 20 cm in depth including consolidating
each deposited layer by ramming, watering, etc. and disposing of
surplus excavated soil as directed ,
within a lead of 50 m.
2.10.1 All kind of soil
2.1.1
2.10.1.2
Pipes, cables etc. exceeding 80 mm dia . But not
exceeding 300mm dia.
Metre
590
0
2.2
18.8
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC)
pipes, having thermal stability for hot & cold water supply,
including all CPVC plain & brass threaded fittings, i/c fixing the
pipe with clamps at
1.00 m spacing. This includes jointing of pipes & fittings with one
step CPVC solvent cement and the cost of cutting chases and
making good the same including testing of joints complete as per
direction
of Engineer in Charge.
Concealed work, including cutting chases and making
good the walls etc.
2.2.1 18.8.1 15 mm nominal outer dia Pipes Metre 1760 0
2.2.2 18.8.2 20 mm nominal outer dia Pipes Metre 1095 0
2.2.3 18.8.3 25 mm nominal outer dia Pipes Metre 715 0
2.2.4 18.8.4 32 mm nominal outer dia Pipes Metre 185 0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
2.3
18.10
Providing and fixing GI pipes complete with GI fittings and
clamps, i/c cutting and making good the walls etc. Internal
work - Exposed on Wall
2.3.1 18.10.1 15 mm nominal bore Metre 340 0
2.3.2 18.10.2 20 mm nominal bore Metre 310 0
2.3.3 18.10.3 25 mm nominal bore Metre 305 0
2.3.4 18.10.4 32 mm nominal bore Metre 300 0
2.3.5 18.10.5 40 mm nominal bore Metre 290 0
2.3.6 18.10.6 50 mm nominal bore Metre 255 0
2.4
18.12
Providing and fixing G.I. pipes complete with G.I.
fittings including trenching and refilling etc.
External Work
2.4.3 18.12.3 25mm nominal nominal bore Metre 15 0
2.4.6 18.12.6 50mm nominal nominal bore Metre 375 0
2.4.7 18.12.7 65 mm nominal nominal bore Metre 140 0
2.4.8 18.12.8 80 mm nominal nominal bore Metre 60 0
2.5
18.13
Making connection of G.I. distribution branch with
G.I. main of following sizes by providing and fixing tee,
including cutting and threading the pipe etc. complete :
2.5.1 18.13.1 25 to 40 mm nominal bore Each 10 0
2.5.2 18.13.2 50 to 80 mm nominal bore Each 10 0
2.6
18.16
Providing and fixing brass stop cock of approved
quality :
2.6.1 18.16.1 15 mm nominal bore Each 58 0
2.6.2 18.16.2 20 mm nominal bore Each 60 0
2.7
18.17
Providing and fixing gun metal gate valve with C.I.
wheel of approved quality (screwed end) :
2.7.1 18.17.1 25mm nominal bore Each 47 0
2.7.2 18.17.2 32mm nominal bore Each 48 0
2.7.3 18.17.3 40mm nominal bore Each 13 0
2.7.4 18.17.4 50mm nominal bore Each 6 0
2.7.5 18.17.5 65mm nominal bore Each 8 0
2.8
18.32
Constructing masonry Chamber 30x30x50 cm inside, in brick
work in cement mortar 1:4 (1 cement :4 coarse sand) for stop
cock, with C. I. surface box 100x100 x75 mm (inside) with
hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c
necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5
fine sand : 10 graded stone aggregate 40mm nominal size ) and
inside plastering with cement mortar 1:3 (1 cement : 3 coarse
sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :
2.8.1
18.32.1
With common burnt clay F.P.S (non modular) bricks
of class designation 7.5
Each
13
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
2.9
18.33
Constructing masonry Chamber 60x60x75 cm inside, in brick
work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice
valve, with C.I. surface box 100mm top diameter, 160 mm
bottom diameter and 180 mm deep ( inside) with chained lid and
RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20mm nominal size ) , i/c necessary excavation,
foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded
stone aggregate 40 mm nominal size) and inside plastering with
cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick,
finished with a floating coat of neat cement complete as per
standard design :
2.9.1
18.33.1
With common burnt clay F.P.S (non modular) bricks
of class designation 7.5
Each
2
0
2.3
18.34
Constructing masonry Chamber 90x90x100 cm inside, in
brick work in cement mortar 1:4 (1 cement
: 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top
diameter, 160 mm bottom diameter and 180 mm deep (inside)
with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size ), i/c
necessary excavation, foundation concrete 1:5:10 (1 cement : 5
fine sand : 10 graded stone aggregate 40 mm nominal size ) and
inside plastering with cement mortar 1:3 (1 cement : 3 coarse
sand) 12 mm thick, finished with a floating coat of neat cement
complete as per standard design :
2.30.1
18.34.1
With common burnt clay F.P.S (non modular) bricks
of class designation 7.5
Each
2
0
2.31
18.38
Painting G.I. pipes and fittings with synthetic enamel white
paint with two coats over a ready mixed priming coat, both
of approved quality for new work :
2.31.1 18.38.1 15mm diameter pipe Metre 340 0
2.31.2 18.38.2 20mm diameter pipe Metre 310 0
2.31.3 18.38.3 25mm diameter pipe Metre 305 0
2.31.4 18.38.4 32mm diameter pipe Metre 300 0
2.31.5 18.38.5 40mm diameter pipe Metre 290 0
2.31.6 18.38.6 50mm diameter pipe Metre 255 0
2.32
18.40
Painting G.I. pipes and fittings with two coats of anti- corrosive
bitumastic paint of approved quality.
2.32.6 18.40.6 50mm diameter pipe Metre 60 0
2.32.7 18.40.7 65mm diameter pipe Metre 140 0
2.32.8 18.40.8 80mm diameter pipe Metre 60 0
2.33
18.41
Providing and filling sand of grading zone V or
coarser grade, allround the G.I. pipes in external work :
2.33.6 18.41.6 50 mm diameter pipe Metre 60 0
2.33.7 18.41.7 65 mm diameter pipe Metre 140 0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
2.33.8 18.41.8 80 mm diameter pipe Metre 60 0
2.34
18.60
Providing & fixing enclosed type water meter ( bulk type )
conforming to IS : 2373 and tested by municipal board
complete with nuts , bolts , rubber insertion etc . ( The tail piece
if required will be paid
saperately )
2.34.1 18.60.1 80 mm dia nominal bore Each 3 0
2.35
NSR
Providing and fixing G.I. pipes c/B class class complete
with G.I. fittings and clamps, including cutting and making
good the walls etc. complete in all respect as directed by Engineer-
in-charge. Internal
work - Exposed on Wall
2.35.1 NSR 65 mm nominal outer dia C class Pipes Metre 275 0
2.35.2 NSR 80 mm nominal outer dia C class Pipes Metre 20 0
2.35.2 NSR 100 mm nominal outer dia B class Pipes Metre 70 0
2.36
NSR
Providing and fixing cast iron Wafer Type Butterfly valve of
the following size complete with bolts, nuts, washers and
neoprene gaskets complete in all respect as directed by
Engineer-in-charge.
2.36.1 NSR 80mm nominal bore Each 1 0
2.36.2 NSR 100mm nominal bore Each 1 0
2.37
NSR
Providing, Fixing, Testing & Commissioning of nitrile rubber
insulation on hot water supply pipes. of approved make
complete in all respect as directed by
Engineer-in-charge.
2.37.1 NSR 15mm dia (13 mm thickness) Metre 385 0
2.37.2 NSR 20mm dia (13 mm thickness) Metre 185 0
2.37.3 NSR 25mm dia (13 mm thickness) Metre 220 0
2.37.4 NSR 32mm dia (13 mm thickness) Metre 50 0
2.37.5 NSR 40mm dia (19 mm thickness) Metre 80 0
2.37.6 NSR 50mm dia (19 mm thickness) Metre 45 0
2.38
NSR
Providing and fixing C Class MS pipe puddle flanges of required
size with 6mm thick MS plate of required size of suitable size
properly fixed in RCC walls of water tanks, including necessary
welding complete in all respect as per details shown on
darwings and directions of Engineeer-in-charge for water
tanks.
2.38.1
NSR
25mm dia pipe, 600mm long with 6 mm MS plate of
size 250X250mm
Each
10
0
2.38.2
NSR
32mm dia pipe, 600mm long with 6 mm MS plate of
size 250X250mm
Each
4
0
2.38.3
NSR
40mm dia pipe, 600mm long with 6 mm MS plate of
size 250X250mm
Each
4
0
2.38.4
NSR
50mm dia pipe, 600mm long with 6 mm MS plate of
size 300X300mm
Each
10
0
2.38.5
NSR
65mm dia pipe, 600mm long with 6 mm MS plate of
size 300X300mm
Each
10
0
2.38.6
NSR
80mm dia pipe, 600mm long with 6 mm MS plate of
size 300X300mm
Each
8
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
2.38.7
NSR
100mm dia pipe 600mm long with 6 mm MS plate of
size 400X400mm
Each
8
0
2.38.8
NSR
150mm dia pipe, 600mm long with 6 mm MS plate of
size 400X400mm
Each
12
0
2.38.9
NSR
200mm dia (6mm thick) pipe, 600mm long with 6
mm MS plate of size 600X600mm
Each
4
0
2.38.10
NSR
250mm dia (6mm thick) pipe, 600mm long with 6
mm MS plate of size 600X600mm
Each
2
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
2.39
NSR
Providing and laying of HDPE pipes confirming to IS: 4984 type
PE-80 (6 kg/cm2) including all fittings wherever required e.g.,
tees, bends of any degree, couplings, adapters, plugs, unions etc.
and jointing as manufacturer recommondation etc.
including necessary excavation and refilling complete in all
respects. (For irrigation water Supply )
2.39.1 NSR 25 mm OD 8kg/cm2 Metre 15 0
2.39.2 NSR 50 mm OD 6kg/cm2 Metre 315 0
2.4
8.3 (Modif
Providing and fixing of Garden Hydrant outlet
consisting 1 no. 25mm dia Ball valve(Brass) of approved
quality for connecting rubber hose, pipes
and fittings complete as required
Each
13
0
TOTAL OF SUB HEAD-18.0-WATER SUPPLY 0
3 3 SUB HEAD : 12 - ROOFING
3.1
12.22
Making khurras 45x45 cm with average minimum thickness
of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate of 20 mm nominal size) over P.V.C. sheet 1
m x1 m x 400 micron, finished with 12 mm cement plaster 1:3
(1 cement : 3 coarse sand) and a coat of neat cement, rounding
the edges and making and finishing the outlet complete.
Each
11
0
3.2
12.41
Providing and fixing on wall face unplasticised Rigid PVC rain
water pipes conforming to IS : 13592 Type A, including jointing
with seal ring conforming to IS : 5382, leaving 10 mm gap for
thermal expansion, (i)
Single socketed pipes.
3.2.1 12.41.1 75 mm dia Metre 10 0
3.2.2 12.41.2 110 mm dia Metre 55 0
3.3
12.42
Providing and fixing on wall face unplasticised - PVC moulded
fittings/ accessories for unplasticised Rigid PVC rain water pipes
conforming to IS : 13592 Type A, including jointing with seal
ring conforming to
IS : 5382, leaving 10 mm gap for thermal expansion.
12.42.2 Single Push Fit Coupler
3.3.1 12.42.2.1 75 mm dia Each 2 0
3.3.2 12.42.2.2 110 mm dia Each 15 0
12.42.5 Plain bend 87.5 deg
3.3.3 12.42.5.1 75 mm dia Each 2 0
3.3.4 12.42.5.2 110 mm dia Each 5 0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
3.4
12.43
Providing and fixing unplasticised -PVC pipe clips of approved
design to unplasticised - PVC rain water pipes by means of
50x50x50 mm hard wood plugs, screwed with M.S. screws of
required length, including cutting brick work and fixing in
cement mortar 1:4 (1 cement : 4 coarse sand) and making
good the wall etc. complete.
3.4.1 12.43.1 75 mm dia Each 2 0
3.4.2 12.43.2 110 mm dia Each 15 0
3.5
12.44
Providing and fixing to the inlet mouth of rain water pipe cast
iron grating 15 cm diameter and weighing
not less than 440 grams.
Each
11
0
3.6
NSR
Providing and laying uPVC pipes of approved make
confirming to IS 4985: 2000) working pressure 6 kg/cm2
including all fittings e.g. plain or door bends,
junctions, cowls, offsets, Coupler, access pieces etc.
jointing with rubber rings and solvent cement including
cutting and making good the walls, floors, RCC work, etc.,
cutting chases and filling the same with cement concrete 1:3:6 (1
cement : 3 coarse sand
: 6 graded stone aggregate 20mm nominal size) or cement
mortar 1:4 (1 cement : 4 coarse sand)/ Fixing with clamps
complete in all respects as per Direction
of Engineer-in- charge
3.6.1 NSR 160 mm dia Metre 465 0
TOTAL OF SUB HEAD : 12 - ROOFING 0
4 4 SUB HEAD : 19 - DRAINAGE
4.1
2.1
Excavating trenches of required width for pipes cables etc
including excavation for sockets, and dressing of sides,
ramming of bottoms, depth upto 1.5 m ncluding getting out the
excavated soil , and then returning the soil as required , in
layers not exceeding 20 cm in depth including consolidating
each deposited layer by ramming, watering, etc. and disposing of
surplus excavated soil as directed ,
within a lead of 50 m.
2.10.1 All kind of soil
4.1.1
2.10.1.2
Pipes, cables etc. exceeding 80 mm dia . But not
exceeding 300mm dia.
Metre
1070
0
4.1.2
2.10.1.3
Pipes, cables etc. exceeding 300 mm dia . But not
exceeding 600mm dia.
Metre
20
0
4.2
2.11
"Extra for excavating trenches for pipes, cables etc.in all kinds of
soil for depth exceeding 1.5 m , but not exceeding 3 m.(Rate is
over corresponding basic item for depth upto 1.5 meter.)
4.2.1
2.11.1.2
Pipes, cables etc. exceeding 80 mm dia . But not
exceeding 300mm dia.
Metre
300
0
4.2.2
2.11.1.3
Pipes, cables etc. exceeding 300 mm dia . But not
exceeding 600mm dia.
Metre
20
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
4.3
19.1
Providing, laying and jointing glazed stoneware pipes class SP-1
with stiff mixture of cement mortar in the proportion of 1:1 (1
cement : 1 fine sand) including testing of joints etc. complete:
4.3.1 19.1.1 100 mm diameter Metre 30 0
4.3.2 19.1.2 150 mm diameter Metre 470 0
4.3.3 19.1.3 200 mm diameter Metre 130 0
4.3.4 19.1.4 250 mm diameter Metre 70 0
4.5
19.2
Providing and laying cement concrete 1:5:10 (1 cement : 5
coarse sand : 10 graded stone aggregate 40 mm nominal size) all-
round S.W. pipes including bed concrete as per standard
design:
4.5.1 19.2.1 100mm dia SW pipe Metre 30 0
4.5.2 19.2.2 150mm dia SW pipe Metre 690 0
4.5.3 19.2.3 200mm dia SW pipe Metre 130 0
4.5.4 19.2.4 250mm dia SW pipe Metre 165 0
4.6
19.4
Providing and fixing square-mouth S.W. gully trap class SP-1
complete with C.I. grating brick masonry chamber with water
tight C.I. cover with frame of 300 x300 mm size (inside) the
weight of cover to be not less than 4.50 kg and frame to be not
less than 2.70 kg as per standard design :
19.4.2 150 x 100mm size P-type
4.6.1
19.4.2.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
16
0
4.7
19.6
Providing and laying non-pressure NP2 class (light duty)
R.C.C. pipes with collars jointed with stiff mixture of cement
mortar in the proportion of 1:2 (1 cement : 2 fine sand)
including testing of joints etc.
complete :
4.7.1 19.6.2 150mm dia RCC pipe Metre 220 0
4.7.2 19.6.3 250mm dia RCC pipe Metre 95 0
4.7.3 19.6.4 300mm dia RCC pipe Metre 55 0
4.7.4 19.6.5 450mm dia RCC pipe Metre 50 0
4.8
19.7
(Modified)
Constructing brick masonry manhole in cement mortar 1:4
(1cement : 4 coarse sand) with RCC top slab with 1:2:4 mix (1
cement : 2 coarse sand 4 graded stone aggregate 20mm
nominal size) foundation concrete 1:4:8 mix (1 cement : 4
coarse sand : 8 graded stone aggregate 40 mm nominal size) inside
plastering 12 mm thick with cement mortar 1:3 (1 cement : 3
coarse sand) finished with floating coat of neat cement and
making channels in cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size) finished
with a floating coat of neat cement complete as per standard design.
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
19.7.1
Inside size 90 x 80 cm and 45 cm deep including pre- cast R.C.C.
manhole cover and frame of required shape and approved
quality H D - 20 Circular shape 560 mm internal diameter.
4.8.1
19.7.1.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
16
0
4.8
19.7.2
Inside size 120x90 cm and 90 cm deep including C.I. cover with
frame (medium duty) 500 mm internal diameter, total weight
of cover and frame to be not less than 116 kg (weight of cover 58
kg and weight of frame 58 kg) :
4.8.1
19.7.2.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
4
0
4.3 19.8 Extra for depth for manholes:
19.8.1 Size 90 x 80 cm
4.3.1
19.8.1.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Metre
5
0
4.4 19.8.2 Size 120x90 cm
4.4.1
19.8.2.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Metre
1
0
4.5
19.9
Constructing brick masonry circular type manhole
0.91 m internal dia at bottom and 0.56m dia at top in cement
mortar 1:4 (1 cement :4 coarse sand), inside cement plaster 12
mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)
finished with a floating coat of neat cement, foundation
concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone
aggregate 40 mm nominal size), and making necessary channel in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) finished with a floating coat of
neat cement, all complete as per standard design :
19.9.1
0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-
20 grade designation) 560 mm internal diameter conforming
to I.S. 12592, total weight of cover and frame to be not less than
182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size)
including centering, shuttering all complete.
(Excavation, foot rests and 12mm thick cement plaster at
the external surface shall be paid for
separately):
4.5.1
19.9.1.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
21
0
4.5
19.10
Extra depth for circular type manhole 0.91m internal dia (at
bottom) beyond 0.91 m to 1.67 m
4.5.1
19.10.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Metre
5
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
4.6
19.11
Constructing brick masonry circular manhole 1.22m internal dia
at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4
coarse sand) inside cement plaster 12mm thick with cement
mortar 1:3 (1 cement :3 coarse sand) finished with a floating
coat of neat cement foundation concrete 1:3:6 (1 cement : 3
coarse sand : 6 graded stone aggregate 40mm nominal size)
and making necessary channel in cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal
size) finished with a floating coat of neat cement, all complete as per standard design :
19.11.1
1.68 m deep with SFRC Cover and frame (heavy duty HD-20
grade designation) 560mm internal diameter conforming to I.S.
12592, total weight of cover and frame to be not less than
182kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand
: 4 graded stone aggregate 20mm nominal size) including
centering, shuttering all complete. (Excavation, foot rests and
12 mm thick cement plaster at the external
surface shall be paid for separately) :
4.6.1
19.11.1.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
8
0
4.7
19.12
Extra depth for circular type manhole 1.22m internal dia (at
bottom) beyond 1.68 m to 2.29 m :
4.7.1
19.12.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Metre
5
0
4.8
19.16
Providing orange colour safety foot rest of minimum 6 mm thick
plastic encapsulated as per IS : 10910 on 12mm dia steel bar
conforming to IS : 1786 having minimum cross section as 23
mmx25mm and over all minimum length 263 mm and width as
165mm with minimum 112 mm space between protruded legs
having 2 mm tread on top surface by ribbing or
chequering besides necessary and adequate anchoring
projections on tail length on 138 mm as per standard drawing
and suitable to with stand the bend test and chemical
resistance test as per specifications and having manufacture's
permanent identification mark to be visible even after fixing,
including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Each
350
0
4.9
19.19
Providing and fixing in position pre-cast R.C.C. manhole
cover and frame of required shape and
approved quality
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
19.19.1 LD - 2.5
4.9.1
19.19.1.1
Rectangular shape 600x450 mm internal dimensions
Each
10
0
19.19.2 M D - 10
4.9.2 19.19.2.2 Circular shape 500 mm internal diameter Each 31 0
4.1
19.27
Constructing brick masonry road gully chamber
50x45x60cm with bricks in cement mortar 1:4 (1 cement : 4
coarse sand) including 500x450mm precast RCC horizontal
grating with frame complete as per standard design.
4.10.1
19.27.1
With common burnt clay F.P.S. (non modular) bricks
of class designation 7.5
Each
40
0
4.11
NSR
Supplying and fixing C.I. cover with frame of approved
make for overhead tanks 450x600 mm rectangular C.I. cover
with (light duty) the weight of the cover to be not less than 23 kg
and frame to be not less than 15 kg complete in all respect as
directed
by Engineer-in-charge.
Each
4
0
4.12
NSR
Constructing brick masonry water tight grease trap (with three
chambers , each of 0.4 M X 0.6 M in plan) with 7.5 class
designation bricks in cement mortar 1 : 4 ( 1 cement : 4 fine sand )
earth work, excavation in all kinds of soil, foundation concrete
1 : 4 : 8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40
mm nominal size) inside and outside plastering 12 mm thick
with cement mortar 1 : 3 (1 cement : 3 coarse sand) finished
with a floating coat of neat cement including constructing
baffle wall, stainless steel angles on corners, stainless steel
perforated plates with stainless steel lifting handles in each
chamber, inlet and outlet fittings in UPVC, double seal C.I.
covers complete in all respect as directed by Engineer-in-charge.
4.12.1
Inside size 2.0m x 1.5m and 1.0m deep including two nos. 60x60
cm. C.I. Cover and frame (double seal
weight of cover and frame not less than 75 kg)
Each
1
0
TOTAL OF SUB HEAD : 19 - DRAINAGE 0
5 5 SUB HEAD : 23 - TUBEWELL
5.1
23.1
Boring/drilling bore well of required dia for casing/ strainer
pipe, by suitable method prescribed in IS: 2800 (part I),
including collecting samples from different strata, preparing
and submitting strata chart/ bore log, including hire & running
charges of all equipments, tools, plants & machineries required
for the job, all complete as per direction of Engineer -
in-charge, upto 90 metre depth below ground level.
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
23.1.1 All Type of Soil
5.1 23.1.1.1 300mm dia Metre 180 0
5.2
23.2
Boring/drilling bore well of required dia for casing/ strainer
pipe, by suitable method prescribed in IS: 2800 (part I),
including collecting samples from different strata, preparing
and submitting strata chart/ bore log, including hire & running
charges of all equipments, tools, plants & machineries required
for the job, all complete as per direction of Engineer - in-charge,
beyond 90 metre & upto 150 metre depth
below ground level.
23.2.1 All Type of Soil
5.2.1 23.2.1.1 300mm dia Metre 60 0
5.3
23.3
Supplying, assembling, lowering and fixing in vertical position in
bore well,unplasticized PVC medium well casing (CM) pipe of
required dia,conforming to IS: 12818, including required hire
and labour charges, fittings & accessories etc. all complete, for all
depths, as per direction of Engineer -in-charge.
5.3.1 23.3.1 100 mm nominal size dia Metre 120 0
5.4
23.4
Supplying, assembling, lowering and fixing in vertical position in
bore well unplasticized PVC medium well screen (RMS) pipes
with ribs, conforming to IS: 12818, including hire & labour
charges, fittings & accessories etc. all complete, for all depths, as
per
direction of Engineer-in-charge.
5.4.1 23.4.1 100 mm nominal size dia Metre 120 0
5.5
23.8
Gravel packing in tubewell construction in accordance
with IS: 4097, including providing gravel fine/ medium/ coarse,
in required grading & sizes as per actual requirement, all
complete as per direction of Engineerin- charge.
Cum
15
0
5.6
23.12
Development of tube well in accordance with IS : 2800 (part I)
and IS: 11189, to establish maximum rate of usable water
yield without sand content (beyond permissible limit), with
required capacity air compressor, running the compressor for
required time till well is fully developed,measuring yield of
well by “V” notch method or any other approved
method,measuring static level & draw down etc. by step draw
down method,collecting water samples & getting tested in
approved laboratory, i/c disinfection of tubewell, all complete,
including hire & labour charges of air compressor, tools &
accessories etc., all as per requirement and direction of
Engineer-in- charge.
Hour
80
0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
5.6
23.13
Providing and fixing suitable size threaded mild steel cap or
spot welded plate to the top of bore well housing/ casing
pipe, removable as per requirement,
all complete for borewell of:
5.6.1 23.13.1 100 mm nominal size dia Each 2 0
5.7
23.14
Providing and fixing M.S. clamp of required dia to the top of
casing/housing pipe of tubewell as per IS: 2800 (part I),
including necessary bolts & nuts f
required size complete.
5.7.1 23.14.1 100 mm clamp Each 2 0
5.8
23.15
Providing and fixing Bail plug/ Bottom plug of required
dia to the bottom of pipe assembly of
tubewell as per IS:2800 (part I).
5.8.1 23.15.1 100 mm nominal size dia Each 2 0
TOTAL OF SUB HEAD : 23 - TUBEWELL 0
6 6 RAIN WATER HARVESTING
6
23.1
Boring/drilling bore well of required dia for casing/ strainer
pipe, by suitable method prescribed in IS: 2800 (part I),
including collecting samples from different strata, preparing
and submitting strata chart/ bore log, including hire & running
charges of all equipments, tools, plants & machineries required
for the job, all complete as per direction of Engineer - in-charge,
upto 90 metre depth below ground level.
6.1 23.1.1 All types of soil
6.1.1 23.1.1.3 400 mm dia Metre 100 0
6.2 23.1.2 Rocky strata including Boulders
6.2.1 23.1.2.3 400 mm dia Metre 40 0
6.3
23.3
Supplying, assembling, lowering and fixing in vertical position in
bore well, unplasticized PVC (Slotted / Plain pipe) medium
well casing (CM) pipe of required dia, conforming to IS: 12818,
including required hire and labour charges, fittings &
accessories etc. all complete, for all depths, as per direction of
Engineer -
in-charge
6.3.1 23.3.3 200 mm nominal size dia Metre 40 0
6.4
Supplying, assembling, lowering and fixing in vertical position in
bore well unplasticized PVC medium well screen (RMS) pipes
with ribs, conforming to IS: 12818, including hire & labour
charges, fittings & accessories etc. all complete, for all depths, as
per direction of Engineer-in-charge.
6.4.1 23.4.3 200 mm nominal size dia Metre 100 0
S.N. DSR - Code
Description of item Unit QTY Rate (in Rs.) Amount (in Rs.)
6.5
23.5
Supplying, filling, spreading & leveling stone boulders of
size range 5 cm to 20 cm, in recharge pit, in the required
thickness, for all leads & lifts, all complete as per direction of
Engineer-in-charge.
Cum
12
0
6.6
23.6
Supplying, filling, spreading & leveling gravels of size range 5 mm
to 10 mm, in the recharge pit, over the existing layer of boulders,
in required thickness, for all leads & lifts, all complete as per
direction of
Engineer-incharge.
Cum
12
0
6.7
23.7
Supplying, filling, spreading & leveling coarse sand of size range
1.5 mm to 2 mm in recharge pit, in
required thickness over gravel layer, for all leads & lifts, all
complete as per direction of Engineer -in-
charge.
Cum
12
0
6.8
23.8
Gravel packing in Rainy well construction in accordance
with IS: 4097, including providing gravel fine/ medium/ coarse,
in required grading & sizes as per actual requirement, all
complete as per direction of Engineerin- charge.
Cum
20
0
6.9
23.15
Providing and fixing Bail plug/ Bottom plug of required
dia to the bottom of pipe assembly of
tubewell as per IS:2800 (part I).
6.9.1 23.15.3 200 mm dia Each 2 0
6.1
19.19
Providing and fixing in position pre-cast R.C.C. manhole
cover and frame of required shape and
approved quality
6.10.1 19.19.4.1 Circular shape 560 mm internal dia Each 2 0 TOTAL OF RAIN WATER HARVESTING 0
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BILL OF QUNATITIES FOR ELECTRICAL WORKS
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
NOTE:-
Obtaining of all the Statutory Approvals & liasoning for New 11/33 kV
HT Connection or Load enhancement from present sanctioned load to
the required load shall be in the scope of the contractor. Only
statutory fee paid to the authority shall be reimbursed against the
submission of the original receipt and nothing extra shall be paid on
this account.
SUB HEAD - I : HT EQUIPMENT & TRANSFORMER
1 MR TWO POLE STRUCTURE (BEFORE METER ROOM)
Supply, Installation, Testing and Commissioning of 11 KV DP structure as per SEB(state
Electricity Board) norms & comprising of the following, but not limited to it for
completion of works
RSJ (Rolled Steel Joist) pole of 9.15 mt length of size 175 x 90 mm complete with suitable
M.S. base plate welded at bottom base plate - 2 Nos.
MS Channel of Size 100 x 50 mm, length 4 mts (approx)
11 KV AB switch - 1 Set
11 KV Horn Gap Fuse Unit - 1 Set
11 KV Lightning Arrestor
11 KV Disc Insulator
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
11 KV Pin Insulator
6 SWG Copper wire for jumpering
Supply and erection of Stay set complete with necessary foundation, excavation and
refilling of earth etc. as required.
Concrete foundation for RSJ poles burrioed upto a depth of 1830 mm in ground in a pit
of size 450X450 mm in CC 1:3:6 along with 200 mm copping above ground
inclusive of earth work.
Necessary Nut, Bolts, clamps, operating handle for AB switch, clamping welding etc.
complete as required.
Painting the RSJ poles complete with two coat of Red Oxide and two coats of GI enamel
paints complete as required.
Transportation of all materials and accessories at site
Complete Erection, Testing and Commissioning. Set 1
0
2 MR 11 KV HT Metering Panel (SEB's)
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Supply, Installation, Testing & Commissioning of Indoor Type Floor Mounted, dust,
damp and vermin proof, cubicle HT. Metering Panel made out of 14 gauge CRCA sheet
steel complete with 5 Amp electronic trivector meter, C.T.'s of 200/100/5 Amp, 0.5 Class,
15 VA Burden, and P.T's of 11 KV / √3, 110V / √3, 100 VA conforming to relevant IS
Standards and complete as required. H.T. Metering cubicle along with C.T.'s, P.T.'s and
trivector meter shall be got tested and approved from local electricity supply
authority. The GA drawing shall be got approved from the local statutory authorities
before fabrication.
Set
1
0
3 MR 11 KV HT PANEL :
Supply, installation , Testing and commissioning of a FIVE Panel ( One Incomer +
Four Outgoing ) indoor duty totally enclosed sheet steel clad floor mounting, vermin
proof, fully interlocked vertical isolation, extensible, horizontal draw out, air
insulated, metal clad switchboard having double isolation features complete with
circuits as detailed below. The switchboard would be complete with necessary PVC
insulated copper busbars, small wiring, labels, cable eyes, cable termination to receive XLPE
cables, foundation bolts and suitable for operation on 11 kV, 3 phase, 50 cycle, earthed
system with a rupturing capacity of 350 MVA. This HT panel must be extendable for future
requirement in such a manner not to disrupt ongoing services at the point of use during
extension.
All Incoming and outgoing feeders shall have fault trip auxiliiary contacts
for wiring to annunciation fault trip indication panel
One Incoming Panel equipped with :
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1- Air insulated metal clad housing
1- set of 3 phase PVC insulated copper busbars 800 Amps rating
6- single pole cluster type isolating contacts i.e. plug and switches
1- Triple pole draw out truck mounted 11kV, 350 MVA, 800 Amps Vacuum
Circuit Breaker fitted with arc control devices.
6 NO/NC contacts for remote ON/OFF/TRIP status at BMS
1- Trip free 230 V AC, motor charged spring release closing mechanism
complete with necessary auxiliary switches, emergency hand trip device and
mechanical 'OFF' & 'ON' indicator.
1 - 24 Volt DC shunt trip coil
1 set-Dual Core Cast Resin Current transformers of ratio 250/125/5A Class 5P10 and Class
0.5, 15 VA burden for protection & metering.
1- 3 Phase cast resin horizontal draw out line potential transformer ratio 11
KV/√3:110/√3 Volt, class 0.5, 200 VA connected with H.V. and L.V. connections,
H.V.fuses and LV MPCB of adequate rating to withstand fault level in PT circuit, isolating
plugs for H.V. and L.V. connection.
1- Strip heater to prevent absorption of moisture
The instrument and relay panel fitted with :
1- Square voltmeter of 96 x 96 mm scaled 0-15000 volt with 3 way and
OFF selector switch.
1- Square Ammeter of 96 x 96 mm scaled 0-250 amps with 3 way and OFF
selector switch.
1 no. Energy Analyser to measure voltage, current, power factor,
frequency,kW/kVA, kWh, kVArh, kVAh,Real time,date with communication
module.
1 - no. Circuit Breaker control switch for electrical (T/N/C)
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1- Triple pole numerical I.D.M.T. overcurrent & earth fault relay with two outer
elements connected for overcurrent protection and the middle element for earth
fault protection overcurrent setting 50% - 200% Earth
fault setting 20% - 80% (51 and 51N)
1 - Electro mechanical Master trip relay (86)
1 - Electro mechanical Anti pumping relay (94)
1 - Trip Circuit supervision relay.
1- set of Red/Green indicating lamps for close and open position
1- Amber indicating lamp for auto trip
1- clear indicating lamp for trip circuit healthy
1- set of white indicating lamps one per phase
1 - blue indicating lamp for spring charged
1 - push button on front door for emergency trip
1- Four window annunciation display to indicate fault trip of incoming and
outgoing feeders including audio alarm hooter with accept push button, internal
wiring,protection fuses etc. complete.
1- cable box suitable for cable termination to receive 11 KV XLPE Cable 3
Core 300 sqmm.
1 Set of Power Pack 220 Volt A.C. / 24 Volt D.C. complete & suitable as
required for th complete item.
FOUR NOS OUTGOING FEEDERS - Three Nos. for TRANSFORMER
FEEDERS and 1 No. Standby, EACH EQUIPPED WITH:
1- Air insulated metal clad housing
1- Set of 3 phase PVC insulated copper busbars 800 amps
6- Single pole cluster type isolating contacts; i.e. plug and switches
1- Triple pole drawout truck mounted 11 kV 350 MVA, 630 amps Vacuum
circuit breaker fitted with arc control devices.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1- Trip free 230 V AC, motor charged spring release closing mechanism
complete with necessary auxiliary switches emergency hand trip device and
mechanical 'OFF' and 'ON' indicator.
6 NO/NC contacts for remote ON/OFF/TRIP status at BMS
1 - 24 volts DC shunt trip coil
3 - Dual Core Cast resin Current transformers of ratio 100/5 Class 5P10
and Class 0.5, 15 VA burden for protection & metering.
1- Strip heater to prevent absorption of moisture
1- Square Ammeter 96 mm x 96 mm scaled 0-100 amps with 3 way and
OFF selector switch
1- Triple pole numerical I.D.M.T. over current and earth fault relay, with two outer
elements connected for over current and the middle element for earth fault protection
over current setting 50% - 200% Earth fault setting 20% -80% and with instantaneous
element on all 3 pole settings 500- 2000% on over current and 200-800% on earth fault
(51, 50, 51N & 50N)
1 - Electro mechanical Master trip relay (86)
1 - Electro mechanical Anti pumping relay (94)
1 - Trip Circuit supervision relay.
1 - set of electro mechanical auxiliary relay for OLTC
1- set Electro mechanical auxiliary relay for transformer fault ALARM for
winding temperature conditions
1- set Electro mechanical auxiliary relay for transformer fault TRIP for
winding temperature conditions
1 - no. circuit breaker control switch for electrical (T/N/C)
1- set of Red/Green indicating lamps for close and open position
1- Amber indicating lamp for auto trip
1- clear indicating lamp for trip circuit healthy
1- set of white indicating lamps one per phase
1 - blue indicating lamp for spring charged
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1- cable termination suitable for cable joint to receive 11 KV XLPE cable 3
core 300 sqmm.
1- Eight window annunciation display to indicate fault trip of incoming and outgoing
feeders including audio alarm hooter with accept push button,
internal wiring,protection fuses etc. complete.
The switchboard shall be complete with all interconnections, label wiring,
etc as required and as per direction
Supplying, Installation, Testing & Commissioning of 11 kV HT Panel as
described above Set 1
0
4
MR
Supply, erection, testing and commissioning of 230V, single phase 2 wire AC to 24V DC
Batteries charger with semiconductor/IGBT fullwave rectifier with auto /manual float
cum boost facility complete with 24V DC, 120 AH sealed maintenance free batteries
including one no. distribution board having 63 Amps DP MCCB as incomer and 12 Nos.
20/16A DP MCB's (D.C. duty) as outgoing complete as required and as directed by
Engineer
Incharge.
Supplying, Installation, Testing & Commissioning Rate for 24V DC
Batteries charger as described above
Set 1
0
5 MR 11/.433 KV Transformer
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Supply, installation assembling, transporting, Loading, testing and commissioning of
Outdoor oil type 1600 kVA, 11/0.433 KV, 3 Phase, 50 Hz, Dyn11, Vector Group,
copper wound, class F insulation level, associated with Oil and winding temperature
indicator/ controller actuated by means of resistance temperature detector embedded in
LV windings Associated buccholz protection arrangement, Oil conservator as per IS
2026 and losses as per IS-1180 Level-3, Outdoor Type transformer with
approximately 6.25% impedance maximum allowable losses as per ECBC updation, with
ON Load tap changer (OLTC) on HV side in steps of -15 to 5
% in steps of 1.25 %.The transformer shall be provided with winding temperature
alarm & trip protection, having cable end boxes on HV side suitable for 3C x 300 Sqmm
XLPE cable of 11KV grade and arrangement on LV side suitable for required nos. of 3.5C X
300 Sqmm XLPE LT cable and including all control wiring as per specification attached
complete in all respects as required at site).
The transformer shall be provided with RTCC Panel for automatic sensing of incoming
voltage & AVR for automatic tap change.
Each
3
0
6 MR HT Yard Works
Providing of H.T Yard of suitable size raised from the existing ground level for minimum
height 300 mm provided with necessary retaining wall , inside the yard filled with
sand and top provided with 150 mm layer of 40 mm & below stone aggregated in the
yard complete
Lot
1
0
Supply and fixing MS rectangular pole made of 6 equal angles of 65X65X6 mm welded
together/back to back and with 4 Nos 16 mm dia MS rods equal of length including
all materials, cutting , bending , welding, Al.painting etc complete and fixed in
ground using CC 1:2:4 with all
accessories for chain Link Fencing
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Providing G.I. chain link fencing 50 mm size of 8 guage properly stertched between
rectangular poles and fixed wit suitable bolts and nuts, the free end shall be welded to
the pole and black pipe at top and bottom as required including the cost of all
materials and labour complete.
Supply and erection of welded mesh fencing M.S gate for a height of 2400 mm and 1200
mm wide hinged with necessary AL. frame work with painting the gate complete
with accessories.
7 P/ F MV Danger Notice Plate
7.1
2.21
Providing and fixing MV Danger Notice Plate of 200 mm x 150 mm, made of mild steel, at
least 2 mm thick, and vitreous enamelled white on both sides and with inscription in
single red colour on front side as required.
Each
50
0
8 P/ F HT Danger Notice Plate
8.1
2.22
Providing and fixing HT Danger Notice Plate of 250 mm x 200 mm, made of mild steel, at
least 2 mm thick, and vitreous enamelled white on both sides and with inscription in
single red colour on front side as required.
Each
10
0
9
7.10
Supplying and fixing cable route marker with 10 cm X 10 cmX 5 mm thick
G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron,
60 cm long and fixing the same in ground as required.
Each
40
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
10
8.3
Laying of one number PVC insulated and PVC sheathed / XLPE power cable
of 11 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
10.1 8.3.2 Above 120 sq. mm and upto 400 sq. mm Metre 100 0
11 HT CABLE END TERMINATION
11.1
Supplying and making indoor cable end termination with heat shrinkable jointing kit
complete with all accessories including lugs suitable for following size of 3 core, XLPE
aluminium conductor cable of 11 KV grade as
required :
10.4.4 300 sq. mm Each 10 0
11.2
Supplying and making outdoor cable end termination with heat shrinkable jointing kit
complete with all accessories including lugs suitable for following size of 3 core, XLPE
aluminium conductor cable of 11 KV grade as
required :
10.5.4 300 sq. mm Each 2 0
12 MR Supply of HT Cable
Supplying of following sizes of XLPE aluminium conductor, cross linked polythylene,
individual core screwed, flat steel strip armoured, PVC sheathed cable of 11KV grade
(earthed) comforming to IS: 7098 (Part 2), with uptodate ammendment complete as
required.
12.1 3 C X 300 Sq.mm XLPE HT cable (Earthed) Metre 100 0
P/ F RCC Hume Pipe
13
14.14
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground
complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand)
including trenching (75 cm deep) and refilling etc as
required.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
13.1 14.14.2 150 mm dia ID RM 50 0
13.2 14.14.4 300 mm dia ID RM 100 0
14
MR
Supply of fire buckets, 9 L (minimum capacity), 5 No. in each set duly filled with fine sand
and fixed on an angle iron frame, red painted as per requirement of local
authorities. Fire buckets shall be painted red from outside and white from inside with
additional handle at the bottom and
suitable for outdoor installation.
Sets.
3
0
15
MR
Supply and fixing on position the approved Single Line Diagram framed in 1000 x 800 mm
size glass frame and installed in main switch room as
directed by Engineer Incharge
No.
2
0
16 MR Supply of First Aid box as directed by Engineer Incharge No. 2 0
17 MR Supply of tool kit with 1 pair 11 KV rubber hand gloves as directed by
Engineer Incharge.
Set 2
0
19
MR
Supplying & fixing standard shock treatment charts in English & Hindi duly framed and
covered with glass as directed by Engineer Incharge.
No.
2
0
20
MR
Providing Safety Mat made of elastomeric polymers Material (Class B) 1.2
M wide with thickness 2.5 mm to withstand 12KV dielectric strength AS PER relevant
IS Code
RM
20
0
21
MR
Providing a mat made of elastomeric polymers Material (Class A )1.2 M wide with 2 mm
thickness to withstand 1.1 KV dielectric strength as per
relevant IS Code
RM
100
0
TOTAL CARRIED TO SUMMARY SHEET FOR SUBHEAD I 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
SUB HEAD -II :SUPPLY, INSTALLATION, TESTING AND COMMISIONING
OF DG SET INCLUDING ALL ACCESSORIES
1
MR
Supplying, loading, testing of Diesel Generating set having Prime Power Rating of 1010
KVA, radiator cooled without cooling tower, with Acoustic Enclosure with Hospital Type
silencer, 415 Volts at 1500 RPM, 0.8 lagging power factor suitable for 50 Hz, 3 phase system
and as per latest CPCB-II. The DG Sets shall be suitable for being overloaded upto 10% of
the rated capacity for 1 hour in every 12 hours and consisting of the followings: The DG set
shall be suitable for above 0.85 loading factor with net output shall be 1010kVA as per site
conditions.
A. DIESEL ENGINE:
Diesel Engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for
above output of alternator at 50 Degree C, 50% RH & at 1000 MSL and conforming to BS
5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of
continuous operation. The engine will be fitted complete with all the required
accessories.
Type: Water Cooled
Fuel injection :As per manufacturer
Engine Starting : Battery starting.
Starting position : Universal. Auto/Manual
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
The Engines shall include:
• Flywheel with guard.
• Flexible connection.
• Bellow / expansion joints
• Air Cleaner
• Blower fan
• Electronic governor with electronic fuel injection system
• Fuel and lube oil filters and pumps
• Day Fuel tank with visual level indicators etc.
• Silencer as per latest amendments of MOEF/CPCB
• Safety controls
• Instrument panel
• Exhaust piping to let out the exhaust at mandatory height above the canopy
including support arrangement and insulation with cladding inside the canopy etc.
B. ALTERNATOR;
Synchronous alternator rated at 1010 KVA, 415 volts at 1500 RPM, 3 phase 50 HZ, AC
supply with 0.8 lagging power factor at 50 Degree C, 50% RH & at 1000 Meter MSL. The
alternator shall be having SPDP enclosure, brushless, continuous duty, self excited &
self-regulated through AVR conforming to IS:4722/BS 2613 suitable for tropical
condition and with
Class-H insulation.
Type : Brushless.
Actual Power 1010 KVA at 50 deg C.
Frequency : 50 Cycles/sec.
Supply System: 3 phases & neutral
Connection : Star.
Rated rpm. : 1500 RPM
Casing protection : As per IP-23
Insulation : Class `H/F'.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Power Factor : 0.8.
Controller : The DG sets should be suitable for Auto Synchronization & Auto Load
Sharing with micro process based Synchronization controllers like Woodward/PCC
(Power Command Control) or equivalent including providing of Engine control
panel
C. ACCESSORIES:
The Diesel Engine shall be equipped with minimum following/ as indicated in the
specifications, devices/ accessories built-in type including all
standard fittings.
Fuel supply pump with manual venting pump.
Turbo charger with air filter (dry/oil bath type) and damper.
Charge air cooler.
Suction fuel filter
Lube oil filter.
Hour meter and RPM indicator.
Battery Starting Mechanism.
Instrument/Indication panel complete with the followings;
a) Starting Switch with key.
b) Lub. Oil Temp. gauge.
c) Lub. Oil Pressure Gauge.
d) Water Temp. gauge.
Control devices for safety and monitoring along with indicators.
Common base/foundation frame.
Daily service fuel tank of 990 liters capacity(as per manufacturers) fabricated out of
CRCA 2 mm thick MS sheet complete with all standard accessories and fuel piping
between fuel tank and diesel engine with MS Class C pipe of suitable dia. complete with
valves, level indication, flow switch & twin fuel filters with fuel injectors and accessories
as required as
per specifications.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Anti vibration pads
24V DC Starting system comprising of starter motors: Voltage regulator and
arrangement for initial excitation complete with suitable nos. of Maintenance free
batteries as per manufacturer standards for minimum 6 no. consecutive starts as required
as per specifications.
The cost of initial charge of lubricants, coolant etc.
The DG sets shall include the cost of all accessories, fittings, protections,
instruments, safety controls, alarms, indications etc. complete as per specifications,
as required
Diesel Generating Set (1010 KVA) as described above. Set 3 0
2
MR
Daily service fuel tank of 990 liters capacity(as per manufacturers) fabricated out of
CRCA 2 mm thick MS sheet complete with all standard accessories and fuel piping
between fuel tank and diesel engine with MS Class C pipe of suitable dia. complete with
valves, level indication, flow switch & twin fuel filters with fuel injectors and accessories
as required as
per specifications.
Set
1
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3
MR
Supply, installation, testing and commissioning of exhaust pipe fabricated out of 6 mm
thick MS pipe Class C Heavy Duty including suitable bends, flanges & reducers etc.
conforming to IS:3589 with all fixing accessories and hardwares.The work include
necessary cladding of exhaust pipe work using 50 mm thick Loosely bound resin (LBR)
mattress/ mineral wool/ Rockwool, density not less than 120 kg/m3 and aluminium
cladding (0.6 mm thick) for the complete portion. The exhaust pipe work includes
necessary supports, foundation etc. to avoid any load & stress on turbo charger / exhaust
piping.The exhaust pipe shall be run along the existing wall of the building duly
clamped/supported on independent structure for which, the design and Drawing for
such structure shall be got approved from the Engineer-in-charge.
500 mm dia "6mm thick" Metre 100 0 400 mm dia "6mm thick" Metre 100 0 250 mm dia "6mm thick" Metre 50 0
4
MR
Supply, installation, testing and commissioning of exhaust pipe Y-Joint
.The exhaust pipe/Y-Joint shall be run along the existing wall of the building duly
clamped/supported on independent structure for which, the design and Drawing for
such structure shall be got approved from the
Engineer-in-charge.
250 mm dia "6mm thick" Set 3 0
5
MR
Providing and fixing in position following size of heavy duty stainless steel flanged
expansion bellows with G.I. nut bolt washers for DG fume piping complete with GI nut
bolt washers etc. complete as required.
0
500 mm dia Nos. 6 0 400 mm dia Nos. 6 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
6
MR
Providing & fixing for MS support structure for exhaust fume pipes from DG Sets
(Exhaust Pipe to be measured and paid for separately) along horizontal and vertical
runs upto the height (as per CPCB norms) including cutting, welding etc. and applying two
coats of red oxide and two coats of synthetic enamelled paint of colour and shade as
directed by Engineer-In- Charge. The design of the support structure shall be done by the
contractor and shall be as per CPCB norms approved , also to get the approval from the
client/ consultant before execution etc. as required.
KG
4500
0
Total of Sub-Head - II carried to Summary Sheet 0
SUB-HEAD- III- LT PANELS & DISTRIBUTION BOARDS
A ALL LT PANELS SPECIFIC INCLUSIONS:
All LT Panels must fully conform to IS-61439 Part 1 & 2
The outgoing feeders as indicated below shall have suitable range of
followings (except capacitor feeders).
All ACB's shall be suitable for minimum 50 kA as specified in the items
(Icu=Ics=Icw for 1 sec.)
All MCCB's shall be suitable for unless otherwise specified in the item
(Icu=Ics= 1 sec=100%.)
All Outgoing Feeders of Main LT panel shall have Digital Multifunction
Meter with Control SP MCB
Necessary control and firing card with proper control wiring and lugs of
the required rating to be provided.
Each Incomer shall have Surge Protection Device.
Wiring with space heater, thermostat and control MCB's shall be provided
for all vertical sections of main LT panel.
All Outgoing Feeders shall have LED type Indication Lamps for ON/OFF
indication with suitable wiring, SP MCB etc.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
All breakers shall be interlocked as per schematic diagram through PLC
with Auto load management control.
All incoming as well as outgoing feeders shall have pad locking facility.
Suitable danger board shall be provided.
All MCCB’s shall be provided with front rotary handle and operating mechanism for
door interlock with Pad locking of MCCB’s handles in “OFF”
Position.
The Panel fabricator shall provide Al./ Copper Bus-bars link from Breakers wherever more
than two nos. of cables are terminated in the breakers.
All incoming and outgoing air circuit breakers shall be placed on middle
portion of the vertical in single tier formation.
All distribution sub panels shall be provided with class 0.5 accuracy meters
as well as CTs.
All hinged door shall be earthed through 2.5 sq mm tinned braided copper
wire.
Panels shall be Powder Coated with Siemens grey paint shade no. RAL-
7032 of IS-5.
All of the following panels enclosure having I/C more then 500 A shall be
type tested assembly as per IEC:61439
All motor feeders MCCBs shall be of motor duty.
Supporting/Base rigid steel framework.
TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate
size of neutral link.
Final rating & various parameter, in addition to the specified above shall be selected on the
bases of ambient conditions at site, approved equipments rating, client specific
requirements, standards specified in the tender, requirement for the NOC from various
statutory authorities & as per detail designed stage calculations.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
All Back access panel shall be housed with encapsulated Spark gap based class-1/type-1
SPD with in built fuse for each incomer at each Bus Section of 100kA 10/350mS as per
IS/IEC 62305-3 LPL-I. All front operated panel/Sub panels shall be housed with Mov
based class-2/type-2 SPD with in built fuse for each incomer at each Bus Section of In
10kA & Irms 20kA 5/20mS as per IS/IEC 62305-3 LPL-I.
B BACK ACCESS PANELS WITH ACB's
Design, fabrication, assembly, wiring and supply, erection , testing and commissioning
of front operated dead front cubicle type compartmentalised as per Form 3B, rear
access free standing, dust and vermin proof (IP 43 ingress protection) main switchboards
conforming to IEC-61439 suitable for use at 433 volts, 3 phase 4 wire 50 Hertz system
suitable for a symmetrical fault level of 36kA (specified with the panel) at 433 volts,
fabricated from 2 mm outer thick CRCA MS sheets with hinged, gasketted (metal based
neoprene) and lockable doors having structural reinforcement with suitable
angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom
and including lifting hooks and including earth strip of required size with 2 nos.
earthing terminals and including powder coated paint finish of approved shade over metal
surface cleaned and treated with nine tank process complete with interconnections etc. as
per specifications, as required and as below. The incoming and outgoing feeders shall
be accommodated in a modular arrangement, detachable gland plates, adequate size
cable alley, Sign writing, Painting, Earthing, Numbering, Danger plate, including PVC
insulated copper FRLS wires of minimum 1.5sq.mm & 2.5sq.mm for CT's etc. complete as
required as per specifications and drawing attached. A fairly uniform coating of 80 or
better microns shall be provided.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
(Note: The contractor may select the next higher fault rating of ACB/MCCB
if it is not readily available ,without any extra cost.)
TOTAL TYPE TESTED PANEL TTA (As per IS 61439 part 1 & 2)
1 MR MAIN LT Panel
A INCOMER FROM TRANSFORMER 1, 2 & 3 (3 Nos. 1600 KVA)
3 Nos. of 2500 A 4P electrically operated Drawout type ACB with Ics=Icu=Icw
50KA having Mircroprocessor based releases for O/L, S/C &
E/F.
3 Sets - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage, current, Hz, KW, KWHr, PF.)
with RS 485 port with matching cast resin CT's
3 Sets - 0-500V, 96 sqmm Voltmeter with selector switch, 3 No. phase
indicating LED lamp to show the incoming power with control SP MCB.
3 nos. indicating LED lamps for ACB On/Off/ Trip with protective SP
MCB's.
3 Sets of CTs of the ratio 2500/5A for APFC Relay, Burden 15 VA
3 Sets of CTs of the ratio 2500/5A with class 0.5 Accuracy for Metering,
burden 15 VA
3 No. 2500/5A , 15 VA, 5P10 CT's for Protection
3 No. Under Voltage relay (59)
Negative Phase protection Relay, reverse power relay
B INCOMER FROM DG Sets - 1,2 & 3 (3 Nos. 1010 KVA)
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3 Nos. of 1600 A 3P with Neutral isolation contactor, electrically operated Drawout type
ACB with Ics=Icu=Icw 50KA having Mircroprocessor based releases for O/L, S/C & E/F
with Neutral Isolating Contactor of suitable
rating.
3 Sets - Digital Multifunction Meter (showing harmonics along with all other electrical
parameters such as Voltage, current, Hz, KW, KVA, KVAR, KWh, PF.) with RS 485 port
with matching cast resin CT's
3 Sets - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
3 Nos. of Red, Yellow & blue LED type 22.5mm dia. Indicating lamps with
protective SP MCB's.
3 No. 3 phase and neutral, neutral to earth (minimum 10 mode) surge
suppressor for 50KA along with necessary fuses.
3 Set- of ON/OFF/Trip indicating lamps.
3 No. Under Voltage relay (59)
3 No. Over & under frequency relay
Negative Phase protection Relay, reverse power relay
3 No. 1600/5A , 15 VA, 5P10 CT's for Protection
C BUS COUPLER:
2 Nos. of 2500 A, 4P electrically operated Drawout type ACB with Ics=Ics=50KA
having Mircroprocessor based releases for O/L, S/C & E/F
protection.
3 Set of Breaker ON-OFF-TRIP, Spring charged indication Lamps as
required.
D Breaker Accessories
24 V DC Shunt trip Coil-1 Set
240 V AC under Voltage release-1 set
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Auto - manual/ test selector switch-1 set
Breaker control switch-1 set
Auxilliary contacts required for necessary interlocking of breakers
E BUS BARS
3 Sets of 3200 A 4P Aluminum bus bars with colour coded heat shrinkable
PVC sleeves
F D.G. Synchronisation
Synchronizing Relay like Woodward/Dief/Deepsea/PCCM or equivalent shall be
mounted on Main LT Panel individually for each DG set. Selection of Master DG Sets,
operation(Opening/closing) of breakers like BUSCOUPLER, Transformer & DG
incomers ACB's interlocking between
ACBs etc as required and complete with interfacing with DG Set Controller
8 Channel temperature scanner for monitoring bearing and winding
temperature for each DG set
Battery Charger 24 V, 20 A for each DG Set
16 window facia annunciator for each DG Set
Auto - manual selector switch for individual breaker & PLC
Incomer terminal/ Adapter box for bus duct & cable connection.
G OUTGOINGS-Bus Section-1
i)
1 No. 1250 A 4P ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
ii)
2 No. 1000 A 4P ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
iii)
2 Nos. 630 A 4P MCCB, 36 kA breaking capacity with microprocessor release and
rotatry handle with ON/OFF/TRIP indication Lamps, MFM with Communication
Facility along with Control SP MCB.
iv)
1 Nos. 400 A 4P MCCB, 36 kA breaking capacity with microprocessor release and
rotatry handle with ON/OFF/TRIP indication Lamps, MFM with Communication
Facility along with Control SP MCB.
v)
2 No. 250 A 4P MCCB, 36 kA breaking capacity with microprocessor release and rotatry
handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility
along with Control SP MCB.
vi)
1 No. 100 A 4P MCCB, 25 kA breaking capacity with microprocessor release and rotatry
handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility
along with Control SP MCB.
H OUTGOINGS-Bus Section-2
i)
1 No. 1250 A FP ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
ii)
2 No. 1000 A FP ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP Indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
iii)
1 Nos. 630 A 4P MCCB, 36 kA breaking capacity with microprocessor release and
rotatry handle with ON/OFF/TRIP indication Lamps, MFM with Communication
Facility along with Control SP MCB.
iv)
1 No. 250 A 4P MCCB, 36 kA breaking capacity with microprocessor release and rotatry
handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility
along with Control SP MCB.
v)
1 No. 160 A 4P MCCB, 25 kA breaking capacity with microprocessor release and rotatry
handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility
along with Control SP MCB.
vi)
1 No. 63 A 4P MCCB, 25 kA breaking capacity with microprocessor release
and rotatry handle with ON/OFF/TRIP indication Lamps, MFM with
Communication Facility along with Control SP MCB.
I OUTGOINGS - Bus Section-3
i)
1 No. 1250 A 4P ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
ii)
2 No. 1000 A FP ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
iii)
1 No. 800 A FP ACB, 50 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
iv)
1 No. 630 A FP MCCB, 36 kA breaking capacity, Electrically Draw Out (EDO) type with
microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM
with BMS Communication Facility along with
Control SP MCB.
v)
2 Nos. 400 A 4P MCCB, 36 kA breaking capacity with microprocessor release and
rotatry handle with ON/OFF/TRIP indication Lamps, MFM with Communication
Facility along with Control SP MCB.
vi)
1 Nos. 250 A 4P MCCB, 36 kA breaking capacity with microprocessor release and
rotatry handle with ON/OFF/TRIP indication Lamps, MFM with Communication
Facility along with Control SP MCB.
vii)
1 No. 100 A 4P MCCB, 25 kA breaking capacity with microprocessor release and rotatry
handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility
along with Control SP MCB.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Note: Incomers for Transformer, D.G. Sets & Bus Couplers shall be
electrically & mechanically interlocked, as required.
In case of PLC failure, Provision of manual operation for all Incomer
of Main LT Panel with on off slector switch.
Supplying, Installation, Testing & Commissioning of Main LT Panel as
described above Set
1 0
2 MR Capacitor Panel (600 kVAR)
A INCOMER
i) 1000 Amp. 4 Pole ACB - 1 Set
Incoming with microprocessor based release ACB for O/C, S/C & earth fault protection
front operating handle of following capacity and rating, 50 KA (Ics=Icu upto 433 V ) with Set
of Digital flush type calibrated Intelligent multifunction meters (with communication
port) suitable rating class -0.5 accuracy , showing V, A, KW with 3 Nos. cast resin current
transformers of dual core CT's of suitable Amp. ratio, 5 VA class 0.5 metering. , Spreader
links and phase barrier, solid neutral link complete with wiring , connections
etc.
METERING & INDICATION
1 set of phase indicating lamps
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 No. 16 Stage Microprocessor APFC controller/Relay shall continuously monitor all
three phases and LCD displays for various Electrical Parameters like voltage, input
current, capacitive current, KVA demand,KW, Power Factor, self diagnostic error
code indication with printout facility of the above with RS 485 C port. Controller
should mounted on the front side of the panel. Panel shall be suitable for
Auto/Manual operation and shall be provided as per technical
specifications.
C BUS-BAR
Electrolytic high conductivity Aluminium extensible three phase and neutral
busbars rated at 1200 amps , & auxiliary Bus Bars of suitable capacity insulated with
heat shrinkable coloured PVC sleeves & clip on shrouds for joints having a
maximum current density as per Indian standards suitable to with stand
symmetrical fault level of 36 kA at 433 volts i/c DMC/SMC bus bars supports at required
intervals complete for cross section, size supports & their spacing etc. The neutral busbar is
to be
of full capacity.
D OUTGOINGS
i) 2 Nos.of 160A TP MCCB (25 KA) each with
2 Nos. 100 KVAR capacitor Bank each with 7% harmonic & discharge resistor
suitable capacity to carry expected current continuosly. with suitable size capacitor
duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual
switch complete with wiring in all
respects.
ii) 6 Nos.of 125A TP MCCB (25 KA) each with
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
6 Nos. 50 KVAR capacitor Bank each with 7% harmonic & discharge resistor
suitable capacity to carry expected current continuosly. with suitable size capacitor
duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual
switch complete with wiring in all
respects.
iii) 4 No. of 80A TP MCCB (25 KA) each with
4 Nos. 25 KVAR capacitor Bank each with 7% harmonic & discharge resistor
suitable capacity to carry expected current continuosly. with suitable size capacitor
duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual
switch complete with wiring in all
respects.
Note: The capacitos shall also stipulate the following
(i) All the capacitors shall be suitable for 525 V
(ii) Necessary control and fixing card with proper wiring and lugs of the
required rating to be provided.
(iii) Suitable exhaust fans, ventilation louvers to be provided for cooling.
(iv) LED indication lamps for number of capacitor banks ' ON & Power
Factor lagging or leading.
(v) The APFC shall be protected from following
* Over- voltage& Voltage unbalance
* Over temperature-system should be in standby mode and automatically
restart after above condition restored.
(vi) Capacitor Panel shall be design to maintain Total Harmonic Distortion ( Voltage
Component) of entire system to be less than 3 %.
Supplying, Installation, Testing & Commissioning of 600 Kvar
Capacitor Panel as described above Set 3
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3 MR Ground Floor Panel- Equipment Panel (Panel Must conform to IS
61439 Part 1 & 2)
A INCOMER
1 No. of 800 A 4P electrically operated Drawout type ACB with Ics=Icu=Icw
50 kA having Mircroprocessor based releases for O/L, S/C & E/F.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V ,96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for ACB On/Off/ Trip with protective SP
MCB's.
1 Set of CTs of the ratio 800/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
1000A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D OUTGOINGS
1 Nos. 400A FP MCCB ,36 kA breaking capacity
5 Nos. 250A FP MCCB ,36 kA breaking capacity
2 Nos. 200A FP MCCB ,25 kA breaking capacity
2 No. 160A FP MCCB ,25 kA breaking capacity
3 Nos. 100A FP MCCB ,25 kA breaking capacity
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Supplying, Installation, Testing and Commissioning of Ground Floor
Panel as described above Set 1
0
4 MR Ground Floor Panel- Light and Power
A INCOMER
2 No. 160Amp FP motorised moulded case circuit breaker of (25KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection as per
specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160Amp FP motorised moulded case circuit breaker of 25KA (Ics
Value) with interlocking arrangement between incomers & bus coupler breaker.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
E OUTGOINGS
2 No. 100A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
7 Nos. 40A 4P MCB .
2 Nos. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Ground Floor
Panel as described above Set 1
0
5 MR First Floor Panel
A INCOMER
2 No. 250Amp FP motorised moulded case circuit breaker of (36KA Ics
Value) with Microprocessor release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 250/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
300A TPN Aluminium Bus Bar with colour coded PVC Sleeves
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
D BUS COUPLER
1 No. 250Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 160A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
10 Nos. 40A 4P MCB .
1 No. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Ground Floor
Panel as described above Set 1
0
6 MR Second Floor Panel
A INCOMER
2 No. 160Amp FP motorised moulded case circuit breaker of (25KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection as per
specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160Amp FP motorised moulded case circuit breaker of 25KA (Ics
Value) with interlocking arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 100A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
10 Nos. 40A 4P MCB .
1 No. 25A DP MCB .
Supplying, Installation,Testing & Commissioning of Second Floor
Panel as described above Set 1
0
7 MR Third Floor Panel
A INCOMER
2 No. 160 Amp FP motorised moulded case circuit breaker of (25 KA Ics
Value) with Microprocessor release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500 V, 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160 Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 100A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
10 Nos. 40A 4P MCB .
1 No. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Third Floor Panel
as described above Set 1
0
8 MR Fourth Floor Panel
A INCOMER
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2 No. 160 Amp FP motorised moulded case circuit breaker of (25KA Ics
Value) with Microprocessor release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase
indicating LED lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
21 No. 80A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
10 Nos. 40A 4P MCB .
1 No. 25A DP MCB .
Supplying, Installtion, Testing & Commissioning of Fourth Floor Panel
as described above Set 1
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9 MR Fifth Floor Panel
A INCOMER
2 No. 160 Amp FP motorised moulded case circuit breaker of (25KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection as per
specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500 V, 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 80A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
8 Nos. 40A 4P MCB .
2 Nos. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Fifth Floor Panel
as described above Set 1
0
10 MR Sixth Floor Panel
A INCOMER
2 No. 250Amp FP motorised moulded case circuit breaker of (36KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection as per
specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 250/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
300A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 No. 250Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 160A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
9 Nos. 40A 4P MCB .
1 No. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Sixth Floor Panel
as described above Set 1
0
11 MR Seventh Floor Panel
A INCOMER
2 No. 160Amp FP motorised moulded case circuit breaker of (25KA Ics
Value) with Microprocessor release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
2 Set - digital multifunction meter (showing harmonics along with all other
electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with
matching cast resin CT's
2 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
2 Set of indicating LED lamps for On/Off with protective SP MCB's.
2 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering,
burden 15 VA
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
C BUSBAR
200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 160Amp FP moulded case circuit breaker of 25KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 No. 80A FP MCCB ,25 kA breaking capacity
1 No. 63A 4P MCB .
10 Nos. 40A 4P MCB .
2 Nos. 25A DP MCB .
Supplying, Installation, Testing & Commissioning of Seventh Floor
Panel as described above Set 1
0
12 MR UPS INPUT PANEL- 1 (FOR OT)
A INCOMER
1 No. 630 Amp FP MCCB of (36 KA Ics Value) with Microprocessor release for O/L, S/C,
E/F protection as per specification.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF) with RS
485 port with matching cast resin CT's
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
1 Set of CTs of the ratio 630/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
800A 4P Aluminium Bus Bar with colour coded PVC Sleeves
D OUTGOINGS
2 Nos. 400A 4P MCCB ,36 kA breaking capacity
Supplying, Installation, Testing & Commissioning of UPS Input Panel-
1 (FOR OT) as described above Set 1
0
13 MR UPS Output Panel-1 (Ground to 3rd floor)
A INCOMER
1 No. 400Amp FP moulded case circuit breaker of (36KA Ics Value) with
Microprocessor release for O/L, S/C, E/F protection.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 400/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
500A 4P Copper Bus Bar with colour coded PVC Sleeves
D OUTGOINGS
5 Nos. 100A 4P MCCB ,25 kA breaking capacity
Supplying, Installation, Testing & Commissioning of UPS Output Panel-
1 as described above Set 1
0
14 MR UPS Output Panel-2 (4th to 7th floor)
A INCOMER
1 No. 250Amp FP moulded case circuit breaker of (36KA Ics Value) with Microprocessor
release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 Set of CTs of the ratio 250/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
250 A 4P Copper Bus Bar with colour coded PVC Sleeves
D OUTGOINGS
5 Nos. 100A 4P MCCB ,25 kA breaking capacity
Supplying, Installation, Testing & Commissioning of UPS Output Panel-
2 as described above Set 1
0
15 MR UPS OUTPUT PANEL - 3 (for OT Rooms)
A INCOMER
2 No. 400 Amp FP moulded case circuit breaker of (36KA Ics Value) with Microprocessor
release for O/L, S/C, E/F protection as per specification.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
1 Set of CTs of the ratio 400/5A with class 0.5 Accuracy for Metering,
burden 15 VA
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
C BUSBAR
500A 4P Aluminium Bus Bar with colour coded PVC Sleeves
D BUS COUPLER
1 No. 400 Amp FP moulded case circuit breaker of 36KA (Ics Value) with interlocking
arrangement between incomers & bus coupler breaker.
E OUTGOINGS
2 Nos. 400A 4P MCCB ,36 kA breaking capacity
Supplying, Installation, Testing & Commissioning of UPS Output Panel-
3 (For OT Rooms) as described above Set 1
0
16 MR Main Lift Panel (Indoor Type-IP42)
A INCOMER
1 No. 200 amp ,4P ATS with Single Solenoid confirming to UL-1008 with complete
overlapping neutral, In-phase monitoring ,microprocessor based controller & having
WCR as per specification.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 Set of CTs of the ratio 200/5A with class 0.5 Accuracy for Metering,
burden 15 VA
C BUSBAR
300A TPN Aluminium Bar with colour coded PVC Sleeves
D OUTGOINGS
1 No. 100A 4P MCCB ,25 kA breaking capacity
3 Nos. 80A 4P MCCB ,25 kA breaking capacity
3 Nos. 63A 4P MCCB ,25 kA breaking capacity
2 Nos. 40A 4P MCCB ,25 kA breaking capacity
2 Nos. 40A 4P MCB
Supplying, Installation, Testing & Commissioning of Main Lift Panel as
described above Set 1
0
17 MR Sub Lift Panel-1 (For Dumb Waiter)
A INCOMER
1 No. 80 A FP MCCB, 25 kA breaking capacity with thermal release and
adjustable setting and with rotary handle.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1 Set of CTs of the ratio 80/5A with class 0.5 Accuracy for Metering, burden
15 VA
C BUSBAR
100A TPN Aluminium Bar with colour coded PVC Sleeves
D OUTGOINGS
2 Nos. 40A 4P MCB
1 No. 32A 4P MCB
Supplying, Installation, Testing & Commissioning of Sub Lift Panel-1
(For Dumb Waiter) as described above Set 1
0
18 MR Sub Lift Panel-2 (For Passenger Lifts)
A INCOMER
1 No. 100 A FP MCCB, 25 kA breaking capacity with thermal release and
adjustable setting and with rotary handle.
B METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical
parameters such as voltage current, Hz, KW, KWHr, PF.) with RS
485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED
lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
1 Set of CTs of the ratio 100/5A with class 0.5 Accuracy for Metering,
burden 15 VA
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
C BUSBAR
160A TPN Aluminium Bar with colour coded PVC Sleeves
D OUTGOINGS
5 Nos. 40A 4P MCB
2 Nos. 32A 4P MCB
Supplying, Installation, Testing & Commissioning of Sub Lift Panel-2
(For Passenger Lifts) as described above Set 1
0
19
MR
EXTERNAL LIGHTING PANEL(Outdoor Type weather proof, double
door with canopy and suitable MS Structure stand duly painted)
A INCOMER
1No. 80 A FP MCCB (25 KA)
1No. 80 A TPN Contactor, Auto/Manual Switch & Digital Timers for 24 Hrs.
setting
B Metering & Indication
1 set of RYB phase indicating lamps
MFM with Digital Communication Facility along with control SP MCB
C BUS-BAR
1 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves
D OUTGOINGS
4 Nos. 63A TPN MCB
4 Nos. 40A TPN MCB
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
4 Nos. 25A DP MCB
2 Nos. 20A DP MCB
Supplying,Receiving, fixing, testing & commissioning of above
described Panel Set 1
0
20 MR Isolation Panel for OT’s - 10 KVA
Design, fabrication, assembling, wiring, supply, installation, testing and commissioning
of isolation panels fabricated out of Stainless Steel (304) incubicle compartmentalized
wall mounted, dust and vermin proof with reinformcement of suitable size angle iron,
channels T sections and / or flats wherever necessary including stainless steel door fitted
with stainless screws (Degree of protection IP42). Knockouts shall be provided at the top of
the panel. Panels shall be treated with all anticrossive process before painting.
Approval shall be taken in form of shop drawings before fabrication. Cadmimum
plated hardware and conform to NFPA / UL / IS / IEC code of
pratice shall be used with followings :
1 No. 63 Amps 4P ELCB 30 mA leakage current (primary side of
transformer).
1 No. 63 amps 4P MCB (Primary Side of transformer).
Isolation Transformer
Rating : 10 KVA
Ratio : 1:1
Primary voltage : 415 V AC + 10%
Secondary Voltage : 415 V AC + 1%
Cooling : Air Cooled
Winding & Type : Copper winding double wound with shield grounded to
isolated ground bus secondary ungrounded
Spike suppression level : Not more than 3 dB
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Insulation Class : H
Overloading Capacity : 50% for one hour
Sound level
complete Unit
with cabinet : Not more than 30 dB.
Line Isolation Monitor : Hazard Index 5 mA
Conist of leakage current detector control transformer mother board with
relay etc. LIM monitor card.(Pieco Make)
Indication & Metering
Meter with selection indicator including selector switch : 0-10 mA.
Following indication for Hazard Index.
Leakage Lamp Zone
Current mA Colour
0-4 Green Safe Zone
5-10 Red Hazard Zone Alarm
1 No. orange colour lamp shall be provided for mains ON.
Suitable rating MCB’s shall be provided for all indicating lamps.
Audio / Visual alarm, test / reset PB’s including all accessories as required.
Outgoing MCB : 8 Nos. 20 amps 4P MCBs.
Note:
All MCB’s shall be minimum of 10 KA breaking capacity & ‘D’ curve only.
Ventilation fans for cooling of isolation transformers shall be provided.
Isolation for OT’s described as above. Set 10 0
21 MR Supply of following rating MCCB in Sheet Steel Enclosure with extended
cable end box for Incoming Cable.
400 A 4P 36 KA MCCB for UPS Set 2 0 250 A 4P 36 KA MCCB For MGPS , CSSD and UPS Set 5 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
200 A 4P 25 KA MCCB For CT Set 2 0 160 A 4P 25 KA MCCB For X-RAY/MRI Set 2 0 100 A 4P 25 KA MCCB Set 2 0
SANDWICH TYPE RISING MAIN, TAP OFF BOX, END FEED UNIT
22
3.13
Supplying, installing by suspension on ceiling, testing and commissioning of following
capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C.
supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and
all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient
sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq
cm at nominal current rating, necessary joints, elbow joints & expansion joints and
bends, fire barrier at each floor, provision of tapping at every metre, adopter box and
copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size
(one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel
fasteners, connecting to earthing system etc. as required.
22.1 3.13.3 630 A, Isc = 50 kA for 1 second meter 40 0
22.2 3.13.6 1250 A, Isc = 50 kA for 1 second meter 40 0
23
MR
Supplying, installing, testing and commissioning of following capacity 4P tap off box
made of 1.6mm thick sheet steel enclosure duly painted with powder coating on
existing rising mains complete with 4P MCCB, 36kA breaking capacity, connections,
earthing etc. as required.
23.1 i 400A Each 2 0
23.2 ii 200A Each 2 0
23.3 iii 250A Each 5 0
23.4 iv 160A Each 14 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
24
MR
Supplying, installation, testing & commisioning of 1250A End Feed Unit for the existing
sandwich type rising mains for use on 3 phase 4 wire 415V, 50Hz A.C. supply made with
1.6mm thick steel sheet enclosure (IP54) duly powder coated with 1250 Amp, 4P ACB,50
kA breaking capacity complete with necessary joints including clamping brackets, angle
iron bracket, steel fasteners,connecting to earthing system etc. as required.
1250A, 4P ACB Each 2 0
Total of Sub-Head - III carried to summary sheet 0
SUB HEAD- IV : EARTHING
1
5.2
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and
providing masonry enclosure with cover plate having locking arrangement and
watering pipe etc. with charcoal/ coke and salt as
required.
Set
4
0
2
5.4
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories,
and providing masonry enclosure with cover plate having locking arrangement and
watering pipe of 2.7 meter long etc. with
charcoal/ coke and salt as required.
Set
26
0
3
5.6
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including
accessories, and providing masonry enclosure with cover plate having locking
arrangement and watering pipe of 2.7 meter long etc. with
charcoal/ coke and salt as required.
Set
38
0
4
5.7
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor
earth electrode, including connection/ termination with GI
thimble etc. as required.
Metre
1500
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
5
5.10
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth
electrode including connection with brass nut, bolt, spring,
washer excavation and re-filling etc. as required.
Metre
260
0
6
5.11
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode
including connection with G.I. nut, bolt, spring, washer
excavation and re-filling etc. as required.
Metre
380
0
7
5.12
Providing and laying earth connection from earth electrode with 6 SWG dia
G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I.
thimble excavation and re-filling as required.
Metre
2000
0
8 5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for
connections etc. as required. Metre 500
0
9 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required. Metre 2000
0
10 5.16 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop
earthing as required. Metre 50
0
Total of Sub-Head - IV carried to summary sheet 0
SUB HEAD- V : LIGHTNING CONDUCTOR
1
5.6
Earthing with Cu. earth Plate 600mm x 600mm x 3mm thick including accesssories,
and providing masonary enclosure with cover plate(CI heavy duty) having locking
arrangement and watering pipe pipe of 2.7 mtr long etc. with charcoal or coke and salt )
as required.
Sets
12
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2
6.2
Providing and fixing of lightning conductor finial, made of 25 mm dia 1200 mm long,
copper tube, having single prong at top , with 85 mm dia 3 mm thick copper base plate
including holes with insulation etc. complete as
required.
Each
12
0
3
MR
Providing and fixing Copper Lightning Tape in Horizontal Run: Providing
and fixing copper tape 20mm X 3 mm thick on parapet or surface of wall for lightning
conductor complete as required.
Mts.
600
0
4
MR
Providing and fixing Copper Lightning Tape in Vertical Run: Providing and fixing copper
tape 20mm X 3 mm thick on parapet or surface of wall for
lightning conductor complete as required.
Mts.
550
0
5
MR
Providing and fixing Testing Joint for Copper Lightning Conductor: Providing and
fixing testing joint made of 32 mm X 6 mm thick copper strip, 125 mm long with 4 nos.
of tinned brass bolts, nuts, check nuts and spring washers etc. complete as required.
each
26
0
6 6.15 Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly
in ground as required. Mts. 300
0
Total of Sub-Head - V carried to summary sheet 0
SUB HEAD-VI : LT CABLES & CABLE TRAY
1
7.1
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade
of following size direct in ground including excavation, sand cushioning, protective
covering and refilling the trench etc. as
required.
1.1 7.1.1 Upto 35 sq. mm Metre 200 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1.2 7.1.2 Above 35 sq. mm and upto 95 sq. mm Metre 50 0
1.3 7.1.3 Above 95 sq. mm and upto 185 sq. mm Metre 100 0
1.4 7.1.4 Above 185 sq. mm and upto 400 sq. mm Metre 2000 0
2
7.5
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade
of following size in the existing RCC/ HUME/ METAL pipe as required.
2.1 7.5.1 Upto 35 sq. mm Metre 80 0
2.2 7.5.2 Above 35 sq. mm and upto 95 sq. mm Metre 50 0
2.3 7.5.3 Above 95 sq. mm and upto 185 sq. mm Metre 50 0
2.4 7.5.4 Above 185 sq. mm and upto 400 sq. mm Metre 500 0
3
7.6
Laying of one number PVC insulated and PVC sheathed / XLPE power cable
of 1.1 kV grade of following size in the existing masonry open duct as required.
3.1 7.6.2 Above 35 sq. mm and upto 95 sq. mm Metre 50 0
3.2 7.6.3 Above 95 sq. mm and upto 185 sq. mm Metre 100 0
3.3 7.6.4 Above 185 sq. mm and upto 400 sq. mm Metre 1225 0
4
7.8
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of
1.1 kV grade of following size on cable tray as required.
4.1 7.8.1 Upto 35 sq. mm (clamped with 1mm thick saddle) Metre 3500 0
4.2 7.8.2 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat
clamp) Metre 435
0
4.3 7.8.3 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat
clamp) Metre 300
0
4.4 7.8.4 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat
clamp) Metre 2000
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
S/ F powder coated of approved shade GI Cable Trays
5
4.6
Supplying and installing following size of perforated Hot Dipped Galvanised
Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation
not more than 17.5%, in convenient sections, joined with connectors, suspended from
the ceiling with G.I. suspenders
including G.I. bolts & nuts etc. as required.
5.1 4.6.1 100 mm width X 50 mm depth X 1.6 mm thickness Metre 480 0
5.2 4.6.2 150 mm width X 50 mm depth X 1.6 mm thickness Metre 250 0
5.3 4.6.4 300 mm width X 50 mm depth X 1.6 mm thickness Metre 250 0
5.4 4.6.7 600 mm width X 50 mm depth X 2.0 mm thickness Metre 30 0
5.5 4.6.13 900 mm width X 62.5 mm depth X 2.0 mm thickness Metre 150 0
S/ F powder coated of approved shade GI Cable Tray Bends
6
4.7
Supplying and installing following size of perforated Hot Dipped Galvanised Iron
cable tray "Bends"(Galvanisation thickness not less than 50 microns) with perforation not
more than 17.5%, in convenient sections, joined with connectors, suspended from the
ceiling with G.I. suspenders including G.I. bolts & nuts etc. as required.
6.1 4.7.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 18 0
6.2 4.7.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 16 0
6.3 4.7.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 10 0
6.4 4.7.7 600 mm width X 50 mm depth X 2.0 mm thickness Each 8 0
6.5 4.7.13 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 12 0
S/ F powder coated of approved shade GI Cable Tray Tee's
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
7
4.8
Supplying and installing following size of perforated Hot Dipped Galvanised Iron
cable tray "Tee"(Galvanisation thickness not less than 50 microns) with perforation not
more than 17.5%, in convenient sections, joined with connectors, suspended from the
ceiling with G.I. suspenders including G.I. bolts & nuts etc. as required.
7.1 4.8.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 2 0
7.2 4.8.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 2 0
7.3 4.8.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 3 0
7.4 4.8.7 600 mm width X 50 mm depth X 2.0 mm thickness Each 1 0
7.5 4.8.13 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 3 0
S/ F powder coated of approved shade MS Cable Tray Cross Members
8
4.9
Supplying and installing following size of perforated Hot Dipped Galvanised Iron
cable tray "Cross Members"(Galvanisation thickness not less than 50 microns) with
perforation not more than 17.5%, in convenient sections, joined with connectors,
suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts etc. as
required.
8.1 4.9.1 100 mm width X 50 mm depth X 1.6 mm thickness Each 1 0
8.2 4.9.2 150 mm width X 50 mm depth X 1.6 mm thickness Each 2 0
8.3 4.9.4 300 mm width X 50 mm depth X 1.6 mm thickness Each 2 0
8.4 4.9.7 600 mm width X 50 mm depth X 2.0 mm thickness Each 1 0
8.5 4.9.13 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 2 0
9
9.1
Supplying and making end termination with brass compression gland and aluminium
lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1kV grade as required.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9.1 9.1.1 2 X 6 sq. mm (19 mm) Each 20 0
9.2 9.1.7 3 X 10 sq. mm (22 mm) Each 2 0
9.3 9.1.8 3 X 16 sq. mm (25 mm) Each 2 0
9.4 9.1.9 3 X 25 sq. mm (25 mm) Each 2 0
9.5 9.1.21 3½ X 35 sq. mm (32mm) Each 32 0
9.6 9.1.22 3½ X 50 sq. mm (35mm) Each 2 0
9.7 9.1.23 3½ X 70 sq. mm (38mm) Each 40 0
9.8 9.1.24 3½ X 95 sq. mm (45mm) Each 2 0
9.9 9.1.25 3½ X 120 sq. mm (45mm) Each 14 0
9.10 9.1.26 3½ X 150 sq. mm (50mm) Each 2 0
9.11 9.1.27 3½ X 185 sq. mm (57mm) Each 6 0
9.12 9.1.29 3½ X 240 sq. mm (62mm) Each 2 0
9.13 9.1.30 3½ X 300 sq. mm (70mm) Each 112 0
9.14 9.1.32 4 X 10 sq. mm (25mm) Each 16 0
9.15 9.1.33 4 X 16 sq. mm (28mm) Each 22 0
9.16 9.1.34 4 X 25 sq. mm (28mm) Each 2 0
Supply of LT Cables
10
MR
Supply, following sizes of PVC sheathed XLPE Insulated Aluminium
conductor/copper conductor power/ multicore control armoured cable of
1.1 KV grade,Conforming to IS 7098 (latest ammended).
10.1 MR 3 ½ C X 300 sq mm Aluminium Armoured Metre 4400 0
10.2 MR 3 ½ C X 240 sq mm Aluminium Armoured Metre 100 0
10.3 MR 3 ½ C X 185 sq mm Aluminium Armoured Metre 190 0
10.4 MR 3 ½ C X 150 sq mm Aluminium Armoured Metre 100 0
10.5 MR 3 ½ C X 120 sq mm Aluminium Armoured Metre 145 0
10.6 MR 3 ½ C X 95 sq mm Aluminium Armoured Metre 100 0
10.7 MR 3 ½ C X 70 sq mm Aluminium Armoured Metre 285 0
10.8 MR 3 ½ C X 50 sq mm Aluminium Armoured Metre 100 0
10.9 MR 3 ½ C X 35 sq mm Aluminium Armoured Metre 580 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
10.10 MR 4C X 25 sq mm Aluminium Armoured Metre 100 0
10.11 MR 3C X 25 sq mm Aluminium Armoured Metre 50 0
10.12 MR 4C X 16 sq mm Aluminium Armoured Metre 620 0
10.13 MR 3C X 16 sq mm Aluminium Armoured Metre 50 0
10.14 MR 4C X 10 sq mm Aluminium Armoured Metre 130 0
10.15 MR 4C X 6 sq mm Aluminium Armoured Metre 50 0
10.16 MR 3C X 10 sq mm Aluminium Armoured Metre 50 0
10.17 MR 3C X 6 sq mm Aluminium Armoured Metre 50 0
10.18 MR 2C X 6 sq mm Aluminium Armoured Metre 500 0
10.19 MR 1C X 35 Sqmm Copper Flexible Cable Metre 50 0
10.20 MR 1C X 50 Sqmm Copper Flexible Cable Metre 150 0
10.21 MR 1C X 70 Sqmm Copper Flexible Cable Metre 250 0
10.22 MR 4C X 2.5 Sqmm Copper Flexible Cable Metre 200 0
10.23 MR 12C X 2.5 Sqmm Copper Flexible Cable Metre 200 0
10.24 MR 3CX2.5 sqmm Armoured Shielded Cu Cable Metre 300 0
10.25 MR 4C X 16 sq mm Copper Armoured Metre 100 0
10.26 MR 4C X 10 sq mm Copper Armoured Metre 100 0
10.27 MR 4C X 6 sq mm Copper Armoured Metre 100 0
10.28 MR 3C X 10 sq mm Copper Armoured Metre 50 0
10.29 MR 3C X 6 sq mm Copper Armoured Metre 50 0
10.30 MR 2C X 6 sq mm Copper Armoured Metre 50 0 Total of Sub-Head - VI carried to summary sheet 0
SUB HEAD- VII : EXTERNAL LIGHTING WORK
The rates for fixing of lighting fixtures shall include all fixing accessories that may be
required to make the installation complete in all respects .
Internal wiring between accessories connecting wires wherever required.
Earthing of fixtures .
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1
MR
Supply, installation, testing & comissioning of 72 W LED Flood light luminaire for
building highlighter. Fixture is made out of Pressure die cast aluminium housing, powder
coated with weather proof gasket ensuring IP66., Heat resistant toughened glass, Optics -
Wide Beam with anodised Aluminium reflectors., Surge protection - Inbuilt 5KV,
optional 10KV with external Surge Protection device, System Luminous efficiency >
100 Lum/W, Constant Current LED Driver with >> 85% efficacy, THD < 10% and
Power factor > 0.95, Colour Temprature (6000K). The light fixture shall be complete
with all accessories required for fixing, termination etc complete in all respect to
complete the job CAT NO. LuxMax-FL-MB-72 6000 K., Philips- BRP410 LED CW 072
MR FG S1 PSU GR or equivalent .
Each
8
0
2
MR
Supply , Installation, Testing and Commissioning of LED Bollard Light. Make: Philips
(Model No. BCP150 LED150/WW PSU 220-240V 7043) or Equivalent.
Each
15
0
3
MR
Supply, Installation, Testing and Commissioning of LED Post Top luminaire with powder
coated PDC aluminium body with opal diffuser.
Make: Philips (Model No. BGP161 LED 2500/NW PSU 220-240V 7043 IN)
or Equivalent
Each
4
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
4
MR
36 W LED Hybrid Solar Street Light with 6 M Pole (Above ground)
Supply Installation,Testing and Commissioning of 36 W (3800 LUMENS ) standalone
dimmable solar street lights with 130WP panel , 120AH battery , 12 V system, 6 mts GI
Octagonal pole ,metal battery box, with all acessories MPPT BASED CHARGE
CONTROLLER standards :EN50530 for MPPT performance ,Solar Panel:IEC
61215,Electronics, EN50530 : MPPT Performance evaluation , IEC62124 : Solar standalone
system performance
,IEC61347-2-13 : LED driver safety ,IEC 62384 : LED driver performance, CISPR 15 :
Radio disturbance characteristics, IEC61547 : EMC Immunity requirements ,IEC60598 :
General requirements and tests , with overcharge protection for battery, with deep
discharge protection for battery, with reverse polarity protection for panel and
battery, with Temperature compensated charging for battery ,with dimming at 50%
after 6 hrs , Integrated Hybrid MPPT Charger + Driver+ Bluetooth on same PCB, luminare
manufacturer should have end to end from LED to Electronics in completing the
luminaire. health monitoring system enabled with bluetooth technology. Make: Philips
or equivalent
Each
5
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
5
MR
Supply, installation, testing & commissioning of LED Street Light Single Piece Pressure
Die Cast Aluminium Housing (LM6 Alloy), Minimum 3600 lumens with maximum
system wattage 36W, With PMMA Lenses, External built proper heat sinks and Toughen
Glass/PC ensuring IP66 & IK >05 protection, LED Used shall be SMD type and fixture
should have minimum efficacy at System level (Not Chip Level) 100 Lumens/watt, Life of
System should be 50000 hrs @L70 along with inbuilt Potted Driver, CCT >5000, CRI 70,
PF >0.9, The fixture should comply with the parameters as per IS10322 and IEC60598 .
The LED driver should comply to IEC55015 -3 - 2 for Harmonics, IEC61347 -2 -13, 2006
in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1,
2011 for performance and IEC61547 ed.2.0, 2009, CISPR- 15 for EMI,Company LOGO
shall be Engraved. Model: Philips BRP409 LED CW 036 NR PC S1 PSU GR, LM 79 and
LM80 or equivalent
Each
15
0
6
MR
Supply, installation, testing & commissioning of 6.0 meter high G.I octagonal pole
(Above Ground Level) with single arm of suitable length with inbuilt junction box
with 10A SP MCB, connectors for incoming/outgoing cable connection and 300mm
x 300mm x 20 mm thick base plate complete in all respect including CC foundation
minimum size 350mm x350mmx500mm with provision of PVC pipe for UG cable entry &
termination of cable with gland/ thimble including 4 Nos. heavy duty foundation
nut bolts with suitable length complete as required including erection of G.I. pole in 1:2:4
cement concrete (1 cement : 2 coarse sand : 4 graded stone aggregate 40mm nominal
size) including excavation & refilling etc as required below ground complete as per
requirement with all accessories. Philips or equivalent.
Each
15
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
7
MR
Providing, Installation of 200 x 150 x 125 mm polycarbonate weather proof (IP-55)
junction box and SP MCB’s and terminal block. Supplying and laying cable through GI pipe
upto junction box including excavation and back filling, wiring with 2 x 2.5 sq.mm
PVC insulated 1100 volts grade copper conductor wires from junction box to lighting
fixture complete.
Each
15
0
8 MR 16 METER HIGH MAST: SUPPLY & INSTALATION
Supply, instalation, testing & commissioning of 16 Mtr High Mast System hot
dipgalvanised (singledip) and suitable for wind velocity as per IS875 part3, with lowering
and raising motorized unit, with carriage assembly for 6 - 8 Luminaries and its control gear
box, lighting stand and avaition light and lightning arrestor. The mast shall be in three
finished sections.It shall also include accessories for 16 Mtr high mast including head
frame,steel wire rope 6mm dia,trailing cable,double drum winch,galvanized lantern
carriage arrangement suitable for 12 luminaires symmetrically & its control gear
boxes and lighting finial with internal power tool 1 Nos. Philips or equivalent.
0
Supply, instalation, testing & commissioning of foundation bolts
manufactured from special steel alongwith nuts,washers, anchor plates &
templates. 2 Nos.
Supply, instalation, testing & commissioning of control panel with suitable control curcuit
for automatic switching ON and OFFof the mast. It shall also have suitable controls for
operation of Power Tool. 1 No.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Supply OF SMD LED Flood Light with minimum 25500 Lumens (at system level ) with C
clamp mounting and LM6 Pressure die cast housing with High efficiency Glass
cover,Lens PMMA , Impact resistance IK 05, system Power : 255 watt , Driver Efficacy :>
90% , Life L70 , 50K Hrs , color temp : Cool white , Luminaire efficacy >100 lumen/Watt
at system level, LED Drive Current : Not more than 750 mA and should be of single
current rating (option for variation of drive current through hardware/switches is not
required), Junction temperature (Tj): at the soldering point should not exceed 55 degree C
+ 10% over an ambient temperature of 25degree C, Heat dissipation / heat sink : Well
designed Thermal management system with PDC Aluminum heat sink, Gravity die
cast shall not be accepted, Electrical safety & Conformation standards of luminaire :
The luminaire conform to IEC 60598. CJJ 45-2006, CIE--BS EN 13201-2:2003, RP-8)&
Photobiological Safety report is required, graduation disk for aiming, Serial number :
12 Nos. LED flood light fitting should be supplied with BAR CODE which should be
attached permanently to the fitting, LM 79 and LM80 reports need to be submitted
from a NABL/UL accredited lab to verify above parameters Similar to Philips make cat
ref BVP410 LED 255 CW HE SY20 FG S3 XTFC or Equivalent
Set
1
9 FAÇADE LIGHTING WORK
9.1
MR
Supply, installation, testing & commissioning of Surface mounted Grazer pro le (anodised
aluminium) semi translucent/ clear sealed encapsulation IP67 Standard: 36 W/m, 24
LED/ 1000 mm, 24V
DC,3000K,12º Aluminium body Weight: 1kg for 1000mm Life: 40000- 50000 hrs
Tempered glass Power factor >= 0.9 Power supply: Remote.
No.s
4
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9.2 MR Supply, installation, testing & commissioning of LPV-60-24V non dimmable
No.s 4
0
9.3
MR
Supply, installation, testing & commissioning of Surface mounted Grazer pro le (anodised
aluminium) semi translucent/ clear sealed encapsulation IP67 Standard: 36 W/m, 24 LED/
1000 mm, 24V DC,3000K,12º Aluminium body Weight: 1kg for 1000mm
Life: 40000-50000 hrs Tempered glass Power factor>= 0.9 Power supply:
Remote.
No.s
20
0
9.4 MR Supply, installation, testing & commissioning of LPV-60-24V non dimmable
No.s 4
0
9.5
MR
Supply, Installation, Testing & Commissioning of BEGA Wall luminaire 33817A.
Shielded with asymmetrical light distribution. LED 19 W, 2210 lm, colour 3000 K. Colour
rendering index (Ra) > 80. With replaceable BEGA LED module with overheating
protection and an expected service life of at least 50,000 operating hours. 20 years
warranty of availability of LED module and wear parts. With LED power supply unit,
DALI controllable, 220-240 V, 0/50-60 Hz. Protection class IP 64. Luminaire made of
cast aluminium, aluminium and stainless steel, colour silver. Safety glass with optical
texture. Reflector made of pure anodised aluminium. Two cable entries for through-
wiring power connecting cable up to 10.5 mm in diameter, max. 5 G 1.5 qmm.
Dimensions: 130 x 230 x 135 mm.
No.s
6
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9.6
MR
Supply, installation, testing & commissioning of BEGA Wall luminaire 66512A. Light
emission on two sides. LED, 5.4 W Luminaire connected wattage, Luminaire
luminous flux 297 lm, half beam angle 20°, colour temperature 3000 K. Colour
rendering index (Ra) >80. With replaceable BEGA LED module with overheating
protection and an expected service life of at least 50,000 operating hours. 20 years warranty
of availability of LED module and wear parts. With LED power supply unit 220-240 V,
0/50- 60 Hz. Protection class IP 65. Luminaire made of cast aluminium, aluminium and
stainless steel, colour silver. Safety glass panels. Reflectors made of pure anodised
aluminium. Two cable entries for through-wiring power connecting cable up to 10.5
mm in diameter, max. 3 x 1.5 qmm. Luminaire diameter 60 mm, height 275 mm.
No.s
12
0
9.7
MR
Supply, installation, testing & commissioning of BEGA Wall luminaire 22292A. Fixed
light distribution. LED 10.5 W, 1230 lm, colour temperature 3000 K. Colour rendering
index (Ra) > 80. With replaceable BEGA LED module with overheating protection and
an expected service life of at least 50,000 operating hours. 20 years warranty of availability
of LED module and wear parts. With LED power supply unit 220-240 V, 0/50-60 Hz.
Protection class IP 65.
Luminaire made of cast aluminium, aluminium and stainless steel, colour silver. Safety
glass, frosted. Reflector made of pure anodised aluminium. Two cable entries for
through-wiring power connecting cable up to 10.5 mm in diameter, max. 3 x 1.5 m².
Dimensions: 160 x 160 x 95 mm.
No.s
6
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9.8
MR
Supply, installation, testing & commissioning of Connect Floor Washer Housing
material : Aluminum Die cast Dimension Trim Ø 50mm,Height 33mm Beam angle
MediumLed SMD, CRI>80,Luminaire Finish white IP65
Led 3watt,255 lm, 85 lm/w.
No.s
8
0
9.9
MR
Supply, Installation, Testing & Commissioning of BEGA In-ground luminaire
84114K3, drive-over for pressure loads to 2,000 kg (20 kN). Adjustable light
distribution. Optical system 0-30° swivel-mounted in 3° steps and ± 180° infinitely
rotatable. LED, 21.8 W Luminaire connected wattage, Luminaire luminous flux 1185
lm, half beam angle 9°, colour temperature 3000 K. Colour rendering index (Ra) > 80.
With replaceable BEGA LED module with overheating protection and an expected service
life of at least 50,000 operating hours. 20 years warranty of availability of LED module and
wear parts. With LED power supply unit, DALI controllable, 220-240 V, 0/50-60 Hz.
Protection class IP 68 10 m. Luminaire made stainless steel, Steel grade no. 1.4301. Safety
glass, clear. Reflector made of pure anodised aluminium. 1,8 m waterproof connecting cable
07RN8-F 5 G
1 qmm with integral water stop and 1.2 m PVC conduit. Luminaire diameter 280
mm, installation depth 185 mm. Recessed opening Ø 257 mm. At the centre of the glass
surface, an operating temperature of 35 °C measured per EN 60598 at an ambient
No.s
32
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
9.10
MR
Supply, Installation, Testing & Commissioning of LED strip compatible with wtec
smartengine system with 9.6w/mtr 4000k LEDs mounted on aluminium profile
along elevations/ceiling as per drawing, 120 deg angle & all installation accessories. this
LED strip with aluminium profile to be installed as per final interior elevation drawings
as these lights are located at ceiling level, below counter levels, above handwash mirrors
etc. similar to alurays make 120 LEDs SMD 3528 led strip with profile.
MTR
50
0
9.11 MR Supply, installation, Testing & Commissioning of Aluminium channel and
diffuser MTR 1
0
9.12
MR
Supply, Installation, Testing & Commissioning of Landscape luminaire tree uplighter
integrated with 8x1 watt LED lamp having IP-65 protection, extruded dia cast
aluminium extruded body. Light
fitting provided withmounting bracket for proper angle/ aiming and 'spike' arrangement
for easy installation at site. Prewired with driver and suitable for operation in 240v, 50 Hz,
single phase AC supply besides terminal for earthing.
Nos
20
0
Total of Sub-Head - VII carried to summary sheet 0
SUB-HEAD - VIII- 45 KW ON GRID SOLAR PV SYSTEM
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
1
MR
Supply, Installation, testing & Commissioning of solar PV modules for 45 kWp,
necessary solar cables to connect solar cells together and to the DB's as well as inverters to
have a complete operational circuit, Conduits, cable trays, trucking, earthing system and
complete Main Junction Box according to the drawings and engineer's instruction and
approval. Price will include all materials needed to connect from modules to inverter
and have complete job ready for installing high quality PV modules connected. Price shall
include costs of repairing any damaged works.
Supply, Installation, testing & Commissioning of one lot of Module mounting
Structure according to the detailed drawing and approval by the Engineer. Contractor
should submit shop drawing for proper mounting structure. Rate shall include
aluminium anodized/ HD galvanized structure, supports, plates & screws, bracing and
angles for dividers etc to complete the structure. Rate shall include excavation, concreting
and fixing
of structure.
Supply, Installation, testing & Commissioning of One no. 45 kWp grid tie inverter with
minimum 2 MPPT inputs. The inverter depending on the system design and
installation proposed. The inverter unit shall be suitable for indoor and outdoor
installations. Cable terminations to inverter shall be of type DC plug and socket
connectors. Technical literature has to be provided as generated by the inverters
manufacturer software. Inverter shall allow an adjustable power factor outdoor, minimum
AC output power 8 kw, with all necessary electrical cables, Conduits and trays and all
other materials and workmanship needed to connect with the main distribution panel
according according to the drawings and engineer's instruction and approval and have a
complete job ready.
Set
1
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Supply, install, connect and operate one set of 20KA DC SPD DC surge protector for grid
connected system . The Surge protector unit shall be suitable for indoor and outdoor
installations. The surcharge protector system shall include all necessary electrical cables,
Conduits and trays and all other materials and workmanship needed to the system
according to the drawings and engineer's instruction and approval and have a complete job
ready.
Total of Sub-Head - VIII carried to summary sheet 0
SUB HEAD - IX : CIRCUIT CUM POINT WIRING
1
1.3
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS
PVC insulated copper conductor single core cable in surface/ recessed steel conduit with
modular switch modular plate suitable GI box and earthing the point with 1.5 sq.mm
FRLS PVC insulated copper conductor single core cable etc.as required.
1.1 1.3.3 Group C Point 3000 0
2 MR Same as item above but Secondary point. i.e. Points to be looped with
Primary point and Point wiring. Point 1500
0
3
MR
Wiring for the following light point with 2.5 sq.mm PVC insulated copper conductor
1100 volts grade stranded flexible FRLS wires of approved make in concealed or surface
mounted 25mm dia 16 gauge MS conduit including provinding and controlled by SPMCB
provided in the DB. (Cost of MCB not to be including here ) complete in all respect and
as per direction of
Engineer in charge.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3.1 26.1 Primary point controlled by one MCB. Point 17 0
3.2 26.2 Same as item above but Secondary point. i.e. Points to be looped with
Primary point with 2.5 sqmm wire and Point wiring Point 63
0
4
1.4
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable in surface / recessed steel conduit, 2 way modular
switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR
PVC insulated copper conductor single core cable
etc as required.
Point
132
0
5
1.5
Wiring for power plug points with 2 x 4 sq.mm. FRLS PVC insulated, Cu. Conductor,
single core cable in surface/ recessed steel conduit along with 1 No. 4 sq.mm. FRLS PVC
insulated copper conductor single core cable for
loop earthing as required.
Metre
33300
0
6
1.6
Wiring for light plug points / power plug points with 4 x 4 sq.mm. FRLS PVC insulated,
Cu. Conductor, single core cable in surface/ recessed steel conduit along with 2 Nos. 4
sq.mm. FRLS PVC insulated copper conductor single core cable for loop earthing as
required.
Metre
200
0
7
1.7
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS
PVC insulated copper conductor, single core cable in surface/
recessed Steel conduit as required
7.1 1.7.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Metre 100 0
7.2 1.7.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Metre 54735 0
7.3 1.7.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Metre 800 0
7.4 1.7.10 4x 10 sqmm+ 2x 6 sqmm earth wire Metre 4460 0
7.5 1.7.11 4x 16 sqmm+ 2x 6 sqmm earth wire Metre 20 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
8
1.20
Supplying and fixing of following sizes of steel conduit along with accessories in
surface/recess including painting in case of surface conduit, or cutting the wall and making
good the same in case of recessed conduit
as required
8.1 1.20.2 25mm Metre 100 0
9
1.21
Supply & fixing of following sizes of medium class PVC conduit along with accessories in
surface / recessed including cutting the wall & making good the same in case of recessed
conduit as required.
9.1 1.21.3 32 mm dia. Metre 100 0
10
1.25
Supplying and fixing of Stepped type 2 module electronic fan regulator on the existing
modular plate & switch box including connections but
excluding modular plate etc. as required.
Each
10
0
11 1.26 Supplying and fixing modular blanking plate on the existing modular plate
& switch box excluding modular plate as required. Each 100
0
12
1.31
Supplying and fixing suitable size GI box with modular plate and cover in front on surface
or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6
A modular switch, connection etc. as
required.
Each
2149
0
13
1.32
Supplying and fixing suitable size GI box with modular plate and cover in front on
surface or in recess including providing and fixing 6 pin 5/6 & 15/16 Amp modular
socket outlet and 15/16 A modular switch,
connection etc. as required.
Each
1110
0
14 1.33 Supplying & fixing of 3 pin, 5 amp ceiling rose on the existing junction box/
wooden block including connection etc as required. Each 10
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
15 1.34 Supplying and fixing brass batten/angle holder including connection etc. as
required. Each 50
0
16
1.45
Installation, testing and commissioning of ceiling fan, including wiring the down rods of
standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor,
single core cable,including providing and fixing phenolic laminated sheet cover on the
fan box etc. as required.
Each
20
0
17
1.48
Supplying and fixing extra conduit down rod of 20 cm lengthG.I. pipe 15 mm dia, heavy
gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to
the nearest 10 cm and 5 cm or less shall be
ignored)
Each
20
0
18
1.50
Installation of exhaust fan in the existing opening, including making good the damage,
connection, testing, commissioning etc. as required.
18.1 1.50.1 Upto 450 mm sweep Each 129 0
19
10.18
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan
clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top
surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet
box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall
be made of 12 mm dia M.S. bar bent to shape as per standard drawing
Each
20
0
Total of Sub-Head - IX carried to summary sheet 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2 SUB HEAD -X : DISTRIBUTION BOARD
1
2.2
Providing and fixing following rating and breaking capacity and pole MCCB with
thermomagnetic release and terminal spreaders in existing cubicle panel board including
drilling holes in cubicle panel, making connections,
etc. as required.
1.1 2.2.13 100 Amp, 30 KA,FP MCCB Each 12 0
2
2.3
Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar,
neutral bus bar, earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without
MCB/RCCB/Isolator)
2.1 2.3.3 12 way, Double door Each 12 0
3
2.4
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel,
MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus
bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But
without MCB/RCCB/ Isolator).
3.1 2.4.3 8 way (4 + 24), Double door Each 21 0
3.2 MR 12 way (4 + 36), Double door Each 70 0
4
2.5
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V,
TPN MCB distribution board of sheet steel, dust protected, duly powder painted,
inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for
mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type
MCB TPDB is normally used where 3 phase outlets are required.)
4.1 2.5.2 8 way (4 + 36), Double door Each 10 0
4.2 2.5.3 12 way (4 + 36), Double door Each 2 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
5
2.10
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB DB
complete with connections, testing and
commissioning etc. as required.
5.1 2.10.1 Single pole Each 3072 0
5.2 2.10.3 Double pole Each 5 0
5.3 2.10.4 Triple pole Each 5 0
6 2.11 Supplying and fixing single pole blanking plate in the existing MCB DB
complete etc. as required.
Each 250 0
7
MR
Supplying and fixing following rating, double pole, 240 V, MCB in the existing MCB
DB complete with connections, testing and commissioning
etc. as required.
7.1 25 amps Each 17 0
8
MR
Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB
complete with connections, testing and commissioning etc. as
required.
8.1 29.1 40 amps Each 21 0
8.2 29.2 63 amps Each 70 0
9
MR
Supplying and fixing following rating,Three pole(TP), 415 V, MCB in the
existing MCB DB complete with connections, testing and commissioning etc. as
required.
9.1 29.3 40 amps Each 30 0
9.2 29.4 63 amps Each 2 0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
10
2.14
Supplying and fixing following rating, double pole, (single phase and neutral), 240
V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in
the existing MCB DB complete with connections, testing and commissioning etc. as
required.
10.1 2.14.1 25 amps Each 12 0
10.2 2.14.2 40 amps Each 75 0
10.3 2.14.3 63 amps Each 210 0
11
2.17
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415
V “C” curve TP MCB complete with connections, testing
and commissioning etc. as required.
Each 10 0
12
2.18
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth,
metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket out let and complete
with connections, testing and
commissioning etc. as required.
Each 10
0
13
2.19
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth,
metal enclosed plug top alongwith 20 A, “C” curve, TPMCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket out let and complete
with connections, testing and
commissioning etc. as required.
Each 10
0
14
2.20
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth,
metal enclosed plug top alongwith 30 A, “C” curve, TPMCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket out let and complete
with connections, testing and
Each 10
0
commissioning etc. as required.
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
15
2.21
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel,
at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in
single red colour on front side as required.
Each 8 0
Total of Sub-Head - X carried to summary sheet 0
SUB HEAD - XI: LIGHTING FIXTURE & FAN
1
1.41
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact
fluorescent fitting of all types, complete with all accessories and tube etc. directly on
ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper
conductor, single core cable and earthing etc.
as required.
Each
440
0
2
1.35
Installation, testing and commissioning of wall bracket / ceiling fittings of all sizes and
shapes containing upto two GLS/CFL/LED lamps per fitting complete with all
accessories including connections etc. as required
Each
2992
0
3 MR Supply of Light fixture as given below
3.1
MR
Supply of recess mounting 30 W LED back-lit 2’x2’ with high efficient LED’s, CCT
5700 - 6500 K,CRI≥80, System lumen 120lm/W, Lumens ≥ 3600, white powder coated
CRCA with PMMA opal diffuser for glare free & uniform lighting, minimum burning hour
life >50000 hours. Driver shall be of constant current type, operating temperature from -
10 to +45 degree celcius, power factor>0.95, rated voltage 220-240V AC working range:- 140
270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all
respect with the entire satisfaction of Engineer-in-Charge. (Make Philips, Model No.
RC380B LED30S-6500 L60W60 PSU OD or equivalent.
Each
1735
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3.2
MR
Supply of 32W LED recessed clean room luminaire CRCA housing with single piece
CRCA frame Lumen Pack : 3200Lm, System Power : 33W, Life : L70 , 50K Hrs, IP 65 with
Toughened Glass, IP 54 with Clear Acrylic Suitable for front Opening Application. AC
working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt
2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-Charge (Make
Philips, Model No. CR652B LED33S CR CW GT or equivalent.
Each
235
0
3.3
MR
Supply of recess mounting 18 W LED down light with high efficient LED’s, CCT 5700 -
6500 K,CRI≥80, Lumens ≥ 1800, single piece pressure die cast aluminum powder coated
housing with opal diffuser for glare free & uniform lighting, minimum burning hour
life >50000 hours. Driver shall be of constant current type, operating temperature from -
10 to +45 degree celcius, power factor>0.95, rated voltage 220-240V AC working range:- 140
270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in
all respect with the entire satisfaction of Engineer-in- Charge.(Make Philips, Model
No. DN 395B LED20S-6500 PSU WH or equivalent.
Each
100
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3.4
MR
Supply of surface mounting 18 W LED down light with high efficient LED’s, CCT-6500
K,CRI >80, Lumens ≥ 1800, single piece pressure die cast powder coated housing with matt
finished opel diffuser for glare free & uniform lighting, Driver shall be of constant
current type, operating temperature from -10 to +50 degree celcius, power factor>0.90,
rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply.
Surge protection - Inbuilt 2.5KV. Complete in all respect with the entire satisfaction
of Engineer-in-Charge. (Make Philips, Model No. SM261C LED20S-6500 PSU WH or
equivalent.)
Each
140
0
3.5
MR
Supply and erection of recess mounting 12 W LED down light with high efficient LED’s,
CCT-6500 K,CRI >80, Lumens ≥ 1200, single piece pressure die cast powder coated housing
with matt finished opel diffuser for glare free & uniform lighting, Driver shall be of
constant current type, operating temperature from 0 to +45 degree celcius, power
factor>0.9, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%,
AC supply. Surge protection- Inbuilt 2.5KV, Complete in all respect with the entire
satisfaction of Engineer-in-Charge. (Make Philips, Model No. DN092B LED10S-6500
PSU WH or equivalent ).
Each
450
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3.6
MR
Supply & erection of 22 watt LED Tube Light rod, 4' long suitable for rated voltage 220-
240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply with aluminium
alloy base, frosted polycarbonate diffusers with power factor >0.90, Total Harmonic
Distortion (THD) < 20%, system current - 0.085A, system efficiency > 85% , with
operating temp. -20° C to 50° C, Lumen output for LED tube should be > 1800 lumen
and overall lumen/watt of luminaire should be greater than 80%, C.R.I. of LED>80%
with correlated colour temperature (CCT) of 6500 minimum burning hour life >40000
hours,LED viewing angle 120 Degree complete in all respect with the entire satisfaction
of the Engineer-in-incharge. (Make of tube fitting: Philips or equivalent). Supply of
Industrial General Purpose 4' long tube fitting suitable to house 1x20w LED tube rod 4'
long, Polycarbonate housing , rated voltage 240 V and Ingress protection IP-20 complete
in all respect with the entire satisfaction
of the Engineer-in-incharge. (Make Philips, Model No. BN 021 LED25S 6500 PSU GR
S1 or equivalent).
Each
400
0
3.7
MR
Supply and erection of 10 W bulk head light with high efficient LED’s, CCT- 5700 K,CRI
>80, Lumens ≥ 700, with polycarbonate sheet and Ingress protection IP-65, Driver
shall be of constant current type, operating temperature from 0 to +45 degree celcius,
power factor>0.90, rated voltage 220-240V AC working range:- 140-270 V A'c , 50 Hz +_
5%, AC supply. Surge protection - Inbuil 2.5KV. Complete in all respect with the
entire satisfaction of
Engineer-in-Charge.(Make Philips, Model No. DN092B LED10S-6500 PSU
WH or equivalent ).
Each
180
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3.8
MR
Supply and erection of 9 W mirror light with high efficient LED’s, CCT-6500 K,CRI >80,
Lumens ≥ 900, with Ingress protection IP- 20, Driver shall be of constant current type,
operating temperature from 0 to +45 degree celcius, power factor>0.90, rated voltage 220-
240V AC working range:- 140-270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection -
Inbuilt 2.5KV. Complete in all respect with the entire satisfaction of Engineer-in-
Charge. (Make Philips, Model No. WT202W LED6S CW PSU S2 PC or equivalent ).
Each
120
0
3.9 MR Supply of LED exit signage of Box size in mm 325x425x365(Make- Philips
or Equivalent . Each 30
0
3.10 MR Supply of LED aviation light luminaire (Make Philips or equivalent).
Each 2
0
3.11
MR
Supply of recess mounting 36 W LED back-lit 1’x4’ with high efficient LED’s, CCT
5700 - 6500 K,CRI≥80, System lumen 100lm/W, Lumens ≥ 3600, white powder coated
CRCA with PMMA opal diffuser for glare free & uniform lighting, minimum burning hour
life >50000 hours. Driver shall be of constant current type, operating temperature from -
10 to +45 degree celcius, power factor>0.95, rated voltage 220-240V AC working range:- 140
270 V A'c , 50 Hz +_ 5%, AC supply. Surge protection - Inbuilt 2.5KV. Complete in all
respect with the entire satisfaction of Engineer-in-Charge. (Make Philips, Model No. BN
021 LED25S 6500 PSU GR S1 or equivalent ).
Each
40
0
4
MR
Supplying of Mettalic Body Exhaust Fan Light duty 230V A.C 50 cycles,
300 mm sweep, energy efficient, complete erected in position with all
accessories.
Each
129
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
5
MR
Supplying, installation, testing & commissioning of wall bracket fan 230V
A.C 50 cycles, 400 mm sweep, energy efficient, complete erected in
position with all accessories.
Each
25
0
6
MR
Supply of 1200 mm ceiling fans complete with double ball bearing, motor, blades,
canopies, capacitor etc. suitable for operation on 230 volts, 50 Hz., 1 phase, AC supply with
BEE 5-star rating complete as required. ceiling fan, including wiring the down rods of
standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor,
single core cable, including providing and fixing phenolic laminated sheet cover on the
fan box etc. as required.
Each
20
0
7
15.1
Supplying, Installation, Testing and Commissioning of Passive Infrared(PIR)
technology based occupancy sensor having high preformance, non regulating
programmable type, suitable for connected load upto 10 Amp, for mounting height up
to 2.8 meter and for 5 meter diameter coverage area along with necessary fixing
arrangements i/c programming at site etc. complete as required.
Each
160
0
8
15.2
Supplying,Installation,Testing and commissioning of Passive Infrared(PIR) technology
based occupancy sensor with day light dimming(lighting level shall be regulated as per
availability of natural day light in an area along with occupancy detection.) having
high preformance, regulating programmable type, suitable for connected load upto 10
A, for mounting height up to 2.8 meter and for 5 meter diameter coverage area along with
necessary fixing arrangements i/c programming at site etc.
complete as required.
Each
140
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
Total of Sub-Head - XI carried to summary sheet 0
SUB HEAD - XII : UPS
Supply, installation, Testing and commissioning of the following rating UPS
as per specifications and complete in all respects.
1
MR
100 KVA UPS 3 phase (415 V + 15%) Volts input & 3 phase output (415 V
+ 1%), 50 Hz, IGBT based technology, Input harmonic Current THD <=3% typical at 100%
load, ,<=6% maximum at 100% load with inbuilt Isolation Transformer and Lead Acid
SMF batteries Suitable for 30 Min backup on Full load for each UPS along with battery
cabinet, parallel communication port, RS232, USB, EPO and SNMP interface, BMS
interface, Dust Filter at Air Inlet point including supporting steel structure for UPS and
Battery as required complete in all respect. Each UPS shall be compatible for working in
parallel redundant mode with other. UPS should be provided with environment
monitoring probe to measure temperature and humidity of UPS room. Quoted price
shall be inclusive of required rating single core copper conductor cable including
terminations,connections of UPS to batteries etc complete in all respect and as per
direction of Engineer in Charge.
Set
1
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
2
MR
200 KVA UPS 3 phase (415 V + 15%) Volts input & 3 phase output (415 V
+ 1%), 50 Hz, IGBT based technology, Input harmonic Current THD <=3% typical at 100%
load, ,<=6% maximum at 100% load with inbuilt Isolation Transformer and Lead Acid
SMF batteries Suitable for 30 Min backup on Full load for each UPS along with battery
cabinet, parallel communication port, RS232, USB, EPO and SNMP interface, BMS
interface, Dust Filter at Air Inlet point including supporting steel structure for UPS and
Battery as required complete in all respect. Each UPS shall be compatible for working in
parallel redundant mode with other. UPS should be provided with environment
monitoring probe to measure temperature and humidity of UPS room. Quoted price
shall be inclusive of required rating single core copper conductor cable including
terminations,connections of UPS to batteries etc complete in all respect and as per
direction of Engineer in Charge.
Set
3
0
Total of Sub-Head - XII carried to summary sheet 0
SUB-HEAD -XIII : LINEAR PNUEMATIC HEAT DETECTION TUBE
SYSTEM
1
MR
Supply, Installation, Testing and Commissioning of 2.5 LB capacity Novec 1230 , DLP
Assembly with automatic valve, push in connector for tube, 2.5 LB Novec 1230 gas ,
mounting bracket, End of Line adopter and low pressure switch for monitoring
system activation.
Each
3
0
2
MR
Supply, Installation, Testing and Commissioning of 5 LB capacity Novec 1230 , DLP
Assembly with automatic valve, push in connector for tube, 5 LB Novec 1230 gas ,
mounting bracket, End of Line adopter and low pressure switch for monitoring
system activation.
Each
5
0
Sr. No.
CPWD-E&M
DSR-2018
Item No
Description
Unit
QTY
Rate
Amount (in Rs.)
3
MR
Supply, Installation, Testing and Commissioning of 10 LB capacity Novec 1230, DLP
Assembly with automatic valve, push in connector for tube, 10 LB Novec 1230 gas ,
mounting bracket, End of Line adopter and low pressure switch for monitoring
system activation.
Each
3
0
4
MR
Supply, Installation, Testing and Commissioning of Linear pneumatic heat Detection
Tube with all necessary fittings & supports.
mtrs.
500
0
5
MR
Supply, Installation, Testing and Commissioning of Master Control Unit with Audio
Visual Alarm with wiring to make complete system operational. The control Panel should
have provision for integration with fire Alarm
/SCADA/BMS System.
Each
3
0
Total of Sub-Head - XIII carried to summary sheet 0
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BILL OF QUNATITIES FOR ELECTRICAL WORKS
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
SUB HEAD - I: LAN NETWORKING
1
MR
Supplying & Fixing of Non- PCB based Information Outlet (I/O) RJ45, Tolless
Termination TIA-568C Category-6, Termination of Catergory-6 UTP Cable, UL listed
,Shall conform to Category-6 as per the EIA/TIA- 568C.2,Shall support network
line speeds up to 1 Gbps, Shall have RJ-45 type connector with bend limiting and strain
relief boot for securing IDC contacts from external forces and for maintaining the bend
radius of the cable, Shall have minimum duraility of 950 or Above mating cycles and 200
termination cycles. Certified by independent labs like ETL/GHMT/3P for compliance
to EIA/TIA-568C.2 complete in all respect.
Nos
790
0
2
MR
Supplying & Fixing of Single Faceplate Shall be Duplex Port (RJ45) square plate,
dimension as per commercially available modular office furniture.Shall have spring
shuttered front access for preventing ingress of dust,Shall be supplied with Gang Box of the
same size by System Integrator complete in all respect.
Nos
395
0
3
MR
Supplying & Fixing of UTP Jack Panel, loaded with 24 nos UTP ports for Non PCB based IO
Jacks (RJ45, TIA-568C Category-6, Shall have integrated bonding bar or other
mechanism for grounding, Shall be loaded with individually replaceable 24 nos.
Category-6 certification by Jacks complying with TIA-568.C.2 , Shall be having a 6 port
module construction for better cable dressing at the rear, the jacks shall have RJ-45
type connector with bend limiting and strain relief boot for securing IDC contacts
from external forces and for maintaining the bend radius of the cable complete in all
respect.
Nos
27
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
4
MR
Supplying of 4-pair Unshielded twisted pair with a cross filler (+), meeting Category 6
standards as per TIA-568C.2, The cable should be tested till 250 MHz , Shall be Fire-
Retardant, Low-Smoke & Zero-Halogen as per IEC 60332-1, IEC 61034-2 & IEC
60754-1 respectively.
Mtrs
64500
0
5
MR
Supplying & Fixing of Category 6, UTP patch cords shall be constructed of 24-27 AWG
unshielded twisted pair stranded copper cable with an enhanced performance
modular plug at each end. Patch cord cable shall be offered in multiple colored UTP cable
for design flexibility with a clear strain relief boot on each modular plug. All patch cords
shall be compatible with both T568A and T568B wiring schemes. UTP Cable will be 1.0
mtr. complete in all respect. Jacket - LSZH.
Nos
990
0
6
MR
Supplying & Fixing of Category 6 UTP patch cords shall be constructed of 24-27 AWG
unshielded twisted pair stranded copper cable with an enhanced performance
modular plug at each end. Patch cord cable shall be offered in multiple colored UTP cable
for design flexibility with a clear strain relief boot on each modular plug. All patch cords
shall be compatible with both T568A and T568B wiring schemes. Blue UTP Cable, 2
Meter complete in all respect. Jacket -LSZH.
Nos
354
0
7
MR
Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack
Mount ,Shall have all accessories including coupler plates pre loaded with 12 Nos of LC
couplers (OM3) with all accessories complete in all respect. Pigtails Should Complie to ITU-
G657.B-Bend insestive fiber.
Nos
7
0
8
MR
Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack
Mount ,Shall have all accessories including coupler plates pre loaded with 24 Nos of LC
couplers (OM3) with all accessories complete in all respect. Pigtails Should Comply to ITU-
G657.B-Bend insestive fiber.
Nos
4
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
9
MR
Supplying & Fixing of Fiber Optic Patch Cable (LC-LC), 3 Mtrs. Long, ISO/IEC-
11801-OM3 50μ Duplex, LSZH,All patch cords shall conform to EIA/TIA-568C.3 and
ISO/IEC-11801,Shall be Duplex Multi Mode Fiber Optic Patch Cords OM3 50μ,Shall
support network line speeds up to 10 Gbps.Shall have LC-LC Connector connectors at
the ends complete in all respect.
Nos
14
0
10
MR
Supply & Fixing of OM3 50/125μ Type Pigtails of ISO/IEC-11801-OM3 Pigtails with
LC Type Connectors,pigtails for terminating fibers on the FOPP complete in all
respect.
Nos
84
0
11
MR
Supplying, Installation, Testing & Commissioning of 50μ, 6-core Multi mode OM3
metallic armored Fiber cable as per ISO/IEC-11801, Shall be able to meet Gigabit & 10
Gigabit Ethernet performance up to 300 meters requirement specified by IEEE 802.3z
(1000 Base-X) & IEEE 802.3ae (10G Base-X) Tensile load should be 4000 Newton or
higher and crush resistance should be 4000 Newton or higher ,The attenuation @ 850
nm should be ≤ 2.7 (Max) db/Km and @ 1300 nm should be ≤ 0.7 (Max) dB/Km, the
fiber construction can be unitube or multitube, but tensile and crush resistance parameters
should be matched, the jacket shall be FRLSZH complete in all respect.
RM
560
0
12
MR
Supplying, of 100 Pair anealed tinned copper conductor PVC insulated and sheathed
armoured copper telephone cables with suitable clamps, saddles and including making
terminal joints complete as required.
RM
1185
0
13
MR
Supplying, of 50 Pair anealed tinned copper conductor PVC insulated and sheathed
armoured copper telephone cables with suitable clamps, saddles and including making
terminal joints complete as required.
RM
640
0
14 MR Supplying, Installation, Testing & Commissioning of of 50 Port telephone Jack Panel
Approved. Nos 19
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
15
MR
Supplying Installation testing and Commissioning of 24 port 10/100/1000BASE-
T ports and four GbE/10GbE SFP/SFP+ uplink ports, layer 3 from day1 having static &
RIP ,stackable upto 10 switches, should support external redundant power supply,
certified , each switch should be provided with stacking port/cable complete in all
respect.
Nos
27
0
16
MR
Supplying Installation testing and Commissioning of SFP+ 10 Gigabit Ethernet Direct
Attach Copper (twinax copper cable) 1m in length complete in all respect.
Nos
14
0
17
MR
Supplying Installation testing and Commissioning of Small Form Factor Pluggable 1
Gigabit Ethernet (SFP+) SR Optics.
Nos
14
0
18
MR
Supplying Installation testing and Commissioning of 32 Port Fiber Switch
10/100/1000BASE-T ports, with up to 4X 10GbE uplinks and 2X 40GbE uplinks, Switch
should support stacking bandwidth of minimum 160gbps, Modular operating system, 32 1
Gig SFP port with additional 4 no. of 10g SFP+PORT, redundant power supply, layer3
switch, each switch should be provided with stacking port/cable complete in all respect.
Nos
1
0
19 MR Supplying Installation testing and Commissioning of 350W AC Power Supply, Front-to-Back Airflow.
Nos 1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
20
MR
Supplying & Fixing of Floor Standing Network/Server Rack - 42U / 800w / 800d, with
Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top
& Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles
with ‘U’ marking. Depth support channels - 3 pairs. With a Overall Weight Carrying
Capicity of 500Kgs. Side Panels - 42U/800d Front MS Door Perforated honeycomb
42U/800w Rear MS Door Split Perforated honeycomb 42U/800wFan 90CFM 230V AC,
4” dia Castors with Brake (set of 4) Vertical Cable manager 80mmW 42U Shelf,
Stationery 700mm N/W PDU 12Sockets 5/15Amps with MCB Mounting Hardware
(Pkt. Of 20) earthing Kit 150mmH Cable manager 1U MS with Loops complete in all
respect.
Nos
1
0
21
MR
Supplying & Fixing of Floor Standing Network Rack - 22U / 600w / 800d, with Heavy
Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top &
Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’
marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of
500Kgs. Side Panels - 22U/800d Front MS Door perforated honeycomb 22U/600w Rear
MS Door (Fully Perforated - Mesh) 22U/600w Fan 90CFM 230V AC, 4” dia Castors with
Brake (set of 4) Cable manager 1U MS with Loops Shelf, Stationery 475mm N/W PDU
7Sockets 5Amps with MCB Mounting Hardware (Pkt. Of
20) Vertical Cable Channel 50mmW 22U complete in all respect.
Nos
7
0
Total of Sub-Head - I carried to summary sheet 0
SUB HEAD - II: CCTV
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
1
MR
Supplying, installation, testing and commissioning of 2 megapixels
resolution Network Dome Camera for true HD quality images,2.8 – 12 mm varifocal
lens,True Day/Night (TDN) functionality for true color image
,Motion Detection 4 Zones, Multi- Level Sensitivity Privacy Zones 4 Zones,Snapshoot
Support JPEG format Password Protection Support Character Display Support(Channel
/Date) ONVIF Yes,IR Illumination20- 30M IR illuminators for clear images in low light
conditions Wide Dynamic Range 3D noise reduction for sharper images and lower
bandwidth use in low light ONVIF compliant complete in all respect.
Each
86
0
2
MR
Supply, installation, testing and commissioning of 2 megapixels resolution Network Bullet
camera camera,Imager 1/2.8”SONY 2.43 mega low illumination CMOS,Video
Compression. .H.264/MJPEG,Day/Night
.Mechanical ICR,Minimum Illumination-0Lux/F1.4(IR ON) IR Illumination- 40-
50M,,Electronic Shutter-Auto/Manual(1/25~1/10000) Lens 2.8 – 12 mm varifocal
lens,Resolution Main- stream:D1/Q1080P(960*540)/HD720P/ HD1080P 1-
25/30fps,Digital Noise Reduction-3D,Wide Dynamic Range-Digital WDR Motion
Detection -4 Zones, Multi- Level Sensitivity,Privacy Zones-4 Zones,Snapshoot-Support
JPEG format,Password Protection-Support,Character Display- Support(Channel
/Date).Regulatory Emissions-FCC Part 15 CE: EN55022,Immunity -CE: EN50130-4,IP
Rating- IP66 rated enclosure to protect against dust and water damage ONVIF
compliant.
Each
2
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
3
MR
Supply, Installation, Testing & Commissioning of 2MP PTZ Camera , UL,CE,FCC
Certified , ONVIF profile s , triple stream or more,4.3 to 129mm focal length , 30 X Optical
Zoom , 10 X digital Zoom ,Frame rate : 25 fps @ 3MP ,Shutter Speed : 1/3 - 1/10,000 s inbuilt
IR LED for night vision ,triple stream or more, IR distance upto 100 mtr or more , 2D
/ 3D noise reduction ,120 dB WDR , 360 deg endess pan , tilt -15 to 90 deg , auto flip support
,80 presets ,Auto pan ,SD Card support , Auto white balance, Auto iris , Alarm : 2 IN , 1 Out , IP
66 weather proof , Power : 24V AC/ POE+ / POE. The cameras shall be in an integrated
IP66 Weatherproof Housing and shall be with all accessories like tamper proof screws,
clamps, wiring etc. complete as required.
Each
3
0
4
MR
Supplying of 4U Rack mount single chassis Network Video Recorder with dual Gb NIC,
1 DVI-I + HDMI + 1 Display Port, max 2 simultaneous monitors, RS-232/485 serial
port, DVD, Server Operating System-Windows 10,Ubuntu Linux 16.04, Gen 4 Intel Core
i7, Local Client Display Rate (FPS)Windows – 700 FPS (HD)Linux – 900 FPS
(HD),High Performance, High Reliability IP Recorder. — Continuously records
400Mbps (Windows) & 800 Mbps (Linux)of video while hosting a local client,
multiple remote clients and the web server on a single server,RAM-8 GB, 16 GB
(Optional)solid-state operating system drive,USB-6 x USB 2.0, 2 x USB
3.0 high air flow cooling and hardware monitoring features ensure maximum
uptime. keyboard and mouse, Professional Grade client and server software pre-
installed and software updates. Access live and recorded video on multiple client
PCs with free Windows, Mac or Linux client application. web server application is pre-
installed on the server to access video through a web browser or free Mobile iPhone /
iPad and Android apps. Maximum Storage Capacity 240TB RAID6 & Maximum Hard
Drive 20 Slot(Up to 12TB) Support Up to 128 IP Camera.
Each
1
0
5 MR Supply, installation, testing and commissioning of Enterprise Class 6 TB HDD
Each 15
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
6
MR
Supply, installation, testing and commissioning of Video Management System (VMS)
software shall be used to view live and recorded video from capture cards and IP devices
connected to local and wide area networks. The VMS software shall have a client/server-
based architecture that can be configured as a standalone VMS system with the client
software running on the server hardware and/or the client running on any network-
connected TCP/IP workstation. Multiple client workstations shall be capable of
simultaneously viewing live and/or recorded video from one or more servers.
Multiple servers shall also be able to simultaneously provide live and/or recorded video
to one or more workstations. The VMS server software shall also have the ability
to be installed on an IP edge device—such as an IP camera or encoder that
allows for 3rd party applications—allowing the device to serve as both a server and IP
video recording device.The VMS shall not charge for the number of concurrent clients
(min. 50 thick clients and 16 mobile clients to be provided along with VMS).
Each
100
0
7
MR
Supplying Installation testing and Commissioning of 24 port 10/100/1000BASE-
T POE ports and four GbE/10GbE SFP/SFP+ uplink ports, layer 3 from day1 having
static & RIP ,stackable upto 10 switches, should support external redundant power
supply, certified , each switch should be provided with stacking port/cable complete in
all respect.
Each
8
0
8
MR
Supply, installation, testing & commissioning of Client Workstation having Intel Core i5
orginal motherboard, 16 GB RAM, Video graphics card 2 GB Licensed Windows 8
Professional (64 bit) and 1 TB Hard Disk with Web camera,Printer and finger print
scanner.
Each
2
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
9
Supplying, Installation,Testing & Commissioning of 55 " LED Full HD TV Resolution
1920 x 1080 ,Contrast Ratio (Typical) 5000:1,Built-in Speaker (10W + 10W), Magic Clone
(to USB), Auto Source Switching & Recovery, Lamp Error Detection, Super Clear Coating,
Temperature Sensor, Plug and Play (DDC2B), Pivot Display, Clock Battery, PIP/PBP,
Video Wall (10x10), Image Rotation, Button Lock, HDCP Support, Smart Scheduling,
Smart F/W update, Built-In MagicInfo Premium-Swith Mounting Brackets as per
Technical Specification complete in all respect.
Each
2
0
10 1.24.7 TV antenna socket outlet Each 25 0
11
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with
PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
RM
1250
0
12
1.27
Supplying and fixing following size/ modules, GI box alongwith modular
base & cover plate for modular switches in recess
etc. as required.
1.27.1 1 or 2 Module (75mm X 75mm) Each 25 0
Total of Sub-Head - II carried to summary sheet 0
SUB HEAD - III: FIRE ALARM & DETECTION SYSTEM
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
1
MR
supply, Installation, connecting testing and commissioing of EN-54 Compliant,
VdS/UL/ULC/ EN/ FM approved Networkable 16 Loops Micro processor based 2 wire
fault tolerant loop with optional redunadant network module ,6 Active loop card
expendable upto 16,each loop shall have the capability of connecting 159 devices and
integrated operating unit for up to 1512 addresses device,The fire alarm control panel shall
have built in degarde mode function.The panel should have inbuilt TCP/IP
communication for Panel Program and Remote Monitoring option through LAN or WAN
communication.The panel shall be able to give location of all fire and More Fire /fault and
Isolation conditions of addressable units via the address codes.The panel shall have the
capacity of storing upto 2000 events.Further, the panel must be able to automatically
switch ON /OFF respective control module when ever any alarm is triggered. The
panel should have inbuilt common Alarm, Fault and monitored sounder output. The
panel shall have a 8x40 characters LCD display with resolution of 256 X 112 pixels, and
analog output, external/inbuilt printer to log all fire or fault events complete in all
respects.
Nos.
1
0
The Panel Should have protection caregory of IP30. Also the panel should have the option
to operate in manned and unmanned mode.The panel shall have a built in power supply
and battery charger along with maintenance free 24 AH,2X 12 volt SMF Lead acid
batteries capable of running for a minimum of 24 hours with battery charger complete
as required.
2
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, Vds & FM
approved, Active Repeater Panel / Remote Terminal with mounting bracket and
required installation accessories. The remote terminal shall facilitate monitoring &
control of fire events from pre- decided strategic location away from the main
FACP. The remote terminal shall facilitate monitoring and control of fire events for
each and every device connected to the FACP. It shall have 6 lines x 40 characters
display.
Nos.
7
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
3
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, VdS/UL/ULC/
EN/ FM approved, Intelligent Analog Addressable Multi- Sensor type Smoke Detector
with inbuilt turbo Isolator and integral response indicator with 360 degree viewing
angle. Detector shall communicate 3 danger levels for differentiated alarm activation and
high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have
unque address for communication and assigned through panel with Mounting Base as
required with the protection category of IP40.
Nos.
1594
0
4
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, VdS/UL/ULC/
EN/ FM approved, Intelligent Addressable Heat Detector (Static+Rate of Rise) with
inbuilt Turbo Isolator & integral Response Indicator with 360⁰ viewing angle. The
detector shall be quoted with Base, required junction box and other mounting accessories.
The detector shall have high immunity to deceptive phenomena and shall have
selectable sensitivity levels for standard & sensitive areas.
Nos.
65
0
5
MR
Supply installation, Testing & Commissoing of responce Indicator Alarm status is
indicated By Red colour LED, Operates on 12 VDC, Dual LED’s for 360 visibility, Flush /
Ceiling wall mount,Operating Voltage : 12 VD.C, Operating Current : 10mA,
Approved.
Nos.
797
0
6
MR
Supply, Installation, Testing and Commissioning of Intelligent Addressable Manual Call
Point with inbuilt turbo Isolator suitable for flush or surface mounting, call point shall
include test key feature without removing the glass. Also should have protection
category of IP44 and extra acceesories as required, duly approved by EN54,LPCB,VDS
& FM.
Nos.
37
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
7
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, VdS/UL/ULC/
EN/ FM approved, Addressable, Loop Powered, Sounder cum Strobe with inbuilt Turbo
Isolator. The Sounder cum Strobe shall have 11 selectable tones, 3 Volume Settings
selectable from the Control Panel. The Sounder & Strobe shall be independently
programmable. The Sounder cum Strobe shall be quoted with required junction
box and mounting accessories.
Nos.
37
0
8
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, VdS/UL/ULC/
EN/ FM approved, addressable Control Module with inbuilt Turbo Isolator. The module
shall have LED indication for Normal, Fault, Test & Alarm activation. The Module shall be
quoted with required junction box and mounting accessories. The module shall have IP40
protection.
Nos.
37
0
9
MR
Supply, Installation, Testing & Commissioning of EN-54 Compliant, Vds & FM
approved, addressable Monitor Module with inbuilt Turbo Isolator. The monitor module
shall have LED indication for Normal, Fault, Test & Alarm activation. The Monitor
Module shall be quoted with required junction box and mounting accessories. The
module shall have IP40 protection.
Nos.
32
0
10
MR
Supply, installation, testing and commissioning of Automatic Analog addressable
Duct Detector with Duct Housing and Duct probe tubes complete with Photoelectric
Smoke Detector with mounting Base, alarm LED shall be viewable from 360 degrees.
The Detector shall have automatic Electronic/ dip switch addressing feature & each of
these shall be equipped with fault Isolator/ External Fault Isolator complete with the GI
Mounting Box and the hardware etc. as required. (UL/ EN Approved).
Nos.
16
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
11
MR
Supply, Installation, Testing & Commissioning of Addressable control Relay Module
with Address Switch and all mounting accessories complete as required. Shall be
complete with Pilot Relay for Tripping of Third Party Equipment, suitable for
switching 5A/15A current through the Relay contacts , MS Powder coated
Junction Box for mouting on Surface, Cable lugs at Ends, cable tags and Ferruling
etc. complete as required.
Nos.
15
0
12
17.5.1
Supplying & laying of 2 X 1.5 sqmm Fire Survival Armoured Cable, 600/1000V
rated with annealed copper conductor having glass mica fire barrier tape covered by an
extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and
LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
Mtr
14696
0
Total of Sub-Head -III carried to summary sheet 0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
SUB HEAD - IV: PUBLIC ADDRESS SYSTEM
1
MR
SITC of 6W Recessed Ceiling speakers with following features:-Speaker Drive 6",
Complete Aluminium grille and Metal baffle, line matching transformer 100/70V
line. Variable wattage tappings of 6 / 3 / 1.5, Effective frequency range 110-15kHz
(BS6840), SPL@1m/1W=91dB, Peak SPL 97dB complete with necessary mounting
hardware & accesories.
Nos
704
0
2
MR
Supply, Installation,Testing & Commissioning of Digital Voice Evacuation system for 8
Zones expandable to 120 Zones. The System shall meet the standards of BS EN54 - 32 &
EN 60849. The System Shall have Built in 500W Class-D Amplifier and it should be
capable for the EVAC, Paging, PA and BGM functions. The Controller shall have SD card
option to store the EVAC and Alert Voice Message. The Controller shall have Speaker
line supervision and amplifier auto changeover. The Controller shall have following
features: Seperate Zone volume control at the front side of panel, Status indications on the
Panel for EVAC,Fault ,AC,DC ,Fault,ALERT & Fireman mic, Zone capacity up to 96
Zones, 8 programmable Control Input and output, Fireman Microphone with High
Priority, THD<1%, Frequency response 80Hz - 20kHz, Up to 1000 Record files, 100V
Class-AB Speaker Output.
Nos
1
0
3
MR
SITC of Remote Paging microphone with minimum 12 buttons and Busy/Hole
Indication. The Microphone Should be suitable for Desktop
mounting.
Nos.
7
0
4
MR
Supply Installation testing and comisioning of 500W RMS Dual Channel Class-D
Digital Power Amplifier with Switch power technology for power electricity saving,
Separate PFC Design for highest reliability, Separate Power Supply System. Amplifier
shall have Following Features: 500RMS per Channel, Amplifier Output 100V, Supply
input AC 220 +/- 10% - 50/60Hz, Short Circuit, Power, Tempreature, Overload
Protection, Auto Cooling Fans. THD <0.1%, Frequency Response 40Hz - 20kHz, AC &
DC Fuse, SNR >89dB.
Nos
8
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
5 MR Supply Installation testing and comisioning of Professional CD/DVD player with USB flash
port & 19" Rack mount arrangement. Nos 1
0
6
MR
Supply Installation testing and comisioning of 19-inch Equipment Rack with
standardized frame or enclosure for mounting multiple PA controllers, CD player,
Amplifiers etc modules. Size 24U.
Nos
1
0
7
17.5.3
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable
in the existing surface / recessed steel conduit of following pairs, cores and size including
connections and interconnections etc. as required.
17.5.3.2 Speaker cable Two pair, 2-core, 1.5 sqmm Mtr 7040 0
8
1.20
Supplying and fixing of following sizes of steel conduit along with accessories in
surface/recess including painting in case of surface conduit, or cutting the wall and making
good the same in case of recessed conduit as
required.
1.20.1 20 mm Mtr 100 0 1.20.2 25 mm Mtr 3520 0 1.20.3 32 mm Mtr 50 0
Total of Sub-Head - IV carried to summary sheet 0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
SUB HEAD - V: ACCESS CONTROL SYSTEM
1
MR
Supply, Installation, testing and commissioning of Surface mounted Networkable
multiprocessor controlled 4 reader controller capable of controlling multiple readers
(IN/OUT) alongwith TCP/IP connectivity complete as per specifications. Control panel
housed in MS Powder Coated Cabinet with Tamper Switch, Complete with power
supply unit for Controllers & Magnetic Locks as per specification.
Nos.
3
0
2
MR
Supply, installation, testing and commissioning of Access Control Application
Software for 128 Reader Capacity, and 4000 Card Holder Capacity, Basic GUI , TA
Module with Alarm Module, T+ Module, 2-Nos Client Work Stations,Module for using
SQL DB , -MULTI Site Module.
Nos.
1
0
3
MR
Supply, installation, testing and commissioning of UL Listed Smart Card Reader with
compatible support of weigand output, 13.56 MHz technology platform and complies with
the ISO 15693 / 14443A standard for contact less smart card technology. Card reader
must be configurable to read encrypted ISO14443A sectors using standard or custom read
keys for Sign OUT Terminal. should be compatible with HID format cards. Encryption,All
RF data transmission between the card and reader should be encrypted using a secure
algorithm. Industry-standard encryption techniques and advanced key management
systems should be used to avoid the risk of compromised data or duplicated cards.
The reader should have audio transducer to provide various tone sequences to
signify access granted, access denied, power up and diagnostics. Visually impaired
cardholders can easily distinguish between access granted and access denied. High-
intensity light bar should provide a clear visual status indication in red, green or
amber, even in bright sunlight.
Each
10
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
4 MR Supply, testing and commissioning of Exit Push Button Each 10 0
8 MR Supply, testing and commissioning of I Class Smart card . Each 100 0
9 MR Supply, installation, testing and commissioning of Single Leaf Electro Magnetic Lock
of Suitable Capacity(Min 600 lbs). Each 7
0
10
MR Supply, installation, testing and commissioning of Double Leaf Electro Magnetic Lock
of Suitable Capacity(Min 1200 lbs).
Each
3
0
11 MR Supply and Fixing of ''U'' Bracket with Accessories. Each 10 0
12
MR
Supply, Fixing and Laying of 8 Core multi strand, copper, unarmoured Cable (between
the every readers & the access controllers).
Mtr
100
0
13
MR
Supply, Fixing and Laying of 2 Core x 1.5 Sq mm, multi strand, copper, unarmoured
cable (between the controller and EM Lock/Request to exit button).
Mtr
100
0
Total of Sub-Head -V carried to summary sheet 0
SUB HEAD - VI: NURSE CALL SYSTEM
1
MR
Supply,Installation Testing and Commissioning of Microprocessor controller
Nurses station with terminal monitor with in built power supply , with charger
enclosed in a powder coated cabinet . Having with Reset, alarm/ buzzer, Call
acknowledge with battery back up, battery charger complete system as per
technical specifications and as per required of following suitable configuration.
complte as required.
1.1 16 Way Nos 11 0
1.2 24 Way Nos 2 0
1.3 40 Way Nos 6 0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
2
MR
Supply Installation Testing & Commissioning of Bed Call Push Button with LED
indication and Flexible Cord with button , Call Reset , Call Indication, station for
each Bed complete as required.
Nos.
453
0
3
MR
Supply Installation Testing & Commissioning of Toilet Call Push Button with LED
indication and flexible cord with button , Call Reset , Call Indication, station for each
Bed complete as required.
Nos.
72
0
4 MR Supply Installation Testing & Commissioning of LED Indicators Module at Outside of
each ward complete as required. Nos 72
0
Total of Sub-Head - VI carried to summary sheet 0
SUB HEAD - VII: EPBAX
1
MR
Supply Installation, Testing and Commissioning of Server Based EPABX Fully
Computerized IP System, SIP Compliant. Multi slot 19: U Rack Mountable 2U Rack
Expandable upto 900 Ports Presently Configuration as Below
CO Line 16Nos.
PRI(30 Channel) 2Nos.
SIP Extension 64Nos
Digital Extension Circuits 128Nos
Analog Extension Circuits 320 Nos.
Lot
1
0
2
MR
Supply Installation, Testing and Commissioning of Integrated Viocemail System 4
Level IVR software with 6 different languages and 4 time
schedule(As per OEM).
Lot
1
0
3
MR
Supply Installation Testing and Commissioning of Digital Phone (24Key+ 60-line
DSS Console) Backlit keypad Hands-free, full duplex ,Headset support Easy to use
soft keys/LCD prompts,Directory dialling,Navigation wheel,Call history,Backlit LCD
screen,Bluetooth support (BCAZ),Security lock key XML open interface .
Each
1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
4
MR
Supply Installation Testing and Commissioning of 24Key Digital Phone Backlit keypad
Hands-free, full duplex ,Headset support Easy to use soft keys/LCD prompts,Directory
dialling,Navigation wheel,Call history,Backlit LCD screen,Bluetooth support
(BCAZ),Security lock key XML open interface
.
Each
1
0
5
MR
Supply Installation Testing and Commissioning of Digital Phone 12 key display Backlit
keypad Hands-free working Easy to use soft keys / LCD prompts on display model
Directory dial key 1000 system, 1000 group, 10 personal, 600 phone book Conference key
Wall mountable Message waiting indicator.
Each
20
0
6
MR
Supply Installation Testing and Commissioning of Digital Phone 6 key display
Backlit keypad Hands-free working Easy to use soft keys / LCD prompts on display
model Directory dial key 1000 system, 1000 group, 10 personal, 600 phone book
Conference key Wall mountable Message waiting indicator.
Each
90
0
7 MR Supply Installation, Testing and Commissioning of Analog CLI Phone with handsfree.
Each 304
0
Total of Sub-Head -VII carried to summary sheet 0
SUB HEAD - VIII: VIDEO CONFERENCING SYSTEM
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
1
MR
SITC of Projector Single 0.7" DLP® Technology having Resolution WUXGA (1920 x
1200),Brightness - 6000 ANSI Lumens and Contrast Ratio -2000:1
,Lamp Life and Type -1,500/3,500 hours (Normal/Eco Mode)
370W/280W,Projection Lens -F = 2.46 - 2.56 f = 22.82 - 28.49mm (std lens)
,Zoom Ratio -1.25x (std lens) Aspect Ratio -4:3 Native, 16:10 and 16:9 Compatible
,DisplayPort VGA-In (2x), HDMI v.1.4b, DisplayPort, DVI-D, Component (5-BNC),
Component (3xRCA), S-Video, Composite, Audio-In (RCA)(2X), Audio-In (Mini-
Jack)(2X), Audio-Out (Mini-Jack), RJ-45, RS- 232, 12V-trigger, 3D-Sync-Out, USB Type-
A (power only), Remote-Jack (for wired R/C), VGA-out(1x) ,Built-in 12V trigger for
external wireless module connection ,Audio ready with 2x3W stereo speakers
complete in all respects.
Each
1
0
2
MR
Supply, Installation,Testing & Commissioning of motorisedd front Projection
Screen, wide(8ft) X hight (6ft) with Remote Control.
Each
1
0
3 MR Supply, Installation,Testing & Commissioning of motorisedd Lift for Projector. Each 1
0
4
MR
Supply, Installation,Testing & Commissioning of Ceilingspeaker 2-way built-in
loudspeaker,Power rated-40W/20W/15W/8ohm, “the reference loudspeaker”. It can be
used with a standard Hifi amplifier and provides you with a Pro HiFi sound. The
loudspeaker has an enforced 6 ½” woofer and 1” tweeter.suitable for the distribution of
Back Ground Music.The housing is made of high quality ABS.SPL 1 watt/1 m-92db,SPL
Max peak- 106db,Frequency Range-60Hz to 20Hz Dispersion @ 1 kH-180Deg,@4KHz-
80Deg,@8KHz-45Deg,IP-54 Rated.
Each
6
0
5
MR
Supply Installation testing and comisioning of 240W RMS Dual Channel Class-D
Digital Power Amplifier with Switch power technology for power electricity
saving, Separate PFC Design for highest reliability, Separate Power Supply System.
Amplifier shall have Following Features: 240W RMS per Channel, Amplifier Output
100V, Supply input AC 220 +/- 10% - 50/60Hz, Short Circuit, Power, Tempreature,
Overload Protection, Auto Cooling Fans. THD <0.1%, Frequency Response 40Hz - 20kHz,
AC & DC Fuse, SNR >89dB.
Each
1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
6
MR
Supply, Installation,Testing & Commissioning of Handheld Wireless Mic system set
dynamic, hypercardioid 55-18,000 Hz Max. SPL 146 dB 1 - channel true diversity
receiver (UHF),Rugged 9.5" metal housing,16 pre- programmed UHF frequencies,
AutoScan/ACT-function,PLL-synthesised technology,Pilot tone recognition.
Each
1
0
7
MR
Supply Installation Testing & Commissioning of Table Top boundry layer Digital
conference delegate microphone.Frequency response : 40- 16000Hz,Sensitivity : -
42dB±2dB,Speaking reference distance 20-120cm, Built-in 1W 8Ω loudspeaker,The
indicative lamp will on when open the microphone, Microphone was supplied power
by main unit, Has TALK button and indicative lamp, it can control speaking status
freely. Has automatic closed function : Microphone will off after speech in 45 seconds.
Each
21
0
8
MR
Supply Installation Testing & Commissioning of Table Top boundry layer Digital
conference Chairman microphone.Chairman Unit has priority button which can cut the
signal of the delegate units, so that it can control the order for conference.Frequency
response : 40-16000Hz,Sensitivity : - 42dB±2dB,Speaking reference distance 20-
120cm, Built-in 1W 8Ω loudspeaker,The indicative lamp will on when open the
microphone, Microphone was supplied power by main unit, Has TALK button and
indicative lamp, it can control speaking status freely. Has automatic closed function :
Microphone will off after speech in 45 seconds.
Each
1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
9
MR
Supply Installation Testing & Commissioning of Digital conference Controller.it
can support 60 units delegate and chairman microphone, it could be extended to
support 200 units microphone by adding more Extension power supply unit.With
four group 8-DIN socket for multi-line connection With one group wired microphone
input port, independent volume adjusted,High fidelity sound quality,With audio input
signal and REC output Built-in 1W monitor loudspeaker volume adjusted,System
volume independent adjusted RCA input. For telephone coincidence,XLR output Mix
output two group—TRS/RCA,Special “T” type single cable with DIN socket,220V/50Hz
,Power consumption of main unit 450W.
Each
1
0
10
MR
Supply, Installation,Testing & Commissioning of Video Conferencing Unit should be
Codec and hardware based unit. Video Standards-H.263, H.264,
H.264 in an Encrypted call should be possible, H.264 should be possible when sending
or receiving two live video sources e.g. Presenter and Presentation. Video Frame
Rate-Should support 30 fps & 60fps (frames per second) with 1080p resolution from day
one, Should support H.239 and BFCP protocols with 1080p resolution. Video Output-
Should have at least 2 HDMI / DVI (High Definition Multimedia Interface) output to
connect Full High Definition display devices such as LCD / LED and projectors for both
Video and Content. (Dual Monitor Support), Video Input-Should have at least one HD
video Input to connect HD camera with full functionalities as mentioned in the camera
specifications, Should have DVI (Digital Video Interface) input to connect PC / Laptop
directly to the Video conferencing system and display resolutions WXGA / HD720p
along with PC Audio. Audio standards supported-G.711, G.722, G.722.1, 64 kbps MPEG-4
AAC-LD standard must be supported.
Each
1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
Other Desirable features-Noise Reduction, Automatic Gain control, Acoustic Echo
Canceller, Active Lip synchronization. Audio Inputs-Should support 2 Microphone inputs
from day one. Camera-1/3" CMOS, It must support an optical zoom of at least 12X and
must have the ability to be mounted upside down to get the best eye-to-eye
contact, 1920 x 1080 pixels progressive @ 30fps, The Camera and codec should be
from the same manufacturer, Should have at least 70 degrees field of view (horizontal). All
the VC components like VC Endpoint, MCU and other central infrastructure should be from
the same OEM complete in all respects.
11 MR Supply, Installation,Testing & Commissioning of Multipoint License-6-way HD
continuous presence. Each 1
0
12
MR
SITC of 12 Channels of AEC Processing with Auto Gain Control and Noise Cancellation
digital signal processor,8 Analog Outputs, Configurable Signal Processing.Clear Front
Panel LED Indication,Bi-Directional Locate Functionality,12 Control Inputs and 6
Logic Outputs for GPIO Integration, Soundweb London Interface Kit for Third Party
ControlSystem Integration (Documentation),HiQnet Device Configuration, Control
and Monitoring from HiQnet complete in all respects.
Each
1
0
13 MR SITC of Motorize Floor box enclosure with 2Nos power sockets,1Nos HDMI,1Nos Network Port.
Each 5
0
14
MR
SITC of 8X8 HDMI Cross Point Matrix Switcher,it should be capable to Routes high
definition Audio/Video signals from any Eight Input Sources to any Eight Display units.
Each
1
0
Sr. No. DSR- Item
No Description Unit QTY Rate Amount (Rs)
15
MR
Supplying & Fixing of Floor Standing Rack network Rack - 22U / 600 w / 800d, with
Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top
& Bottom cover with cable entry gland plates. Two pairs of 19” mounting angles with ‘U’
marking. Depth support channels - 3 pairs. With a Overall Weight Carrying Capicity of
500Kgs. Side Panels - 22U/800d Front MS Door perforated honeycomb 22U/600w Rear
MS Door (Fully Perforated - Mesh) 22U/600w Fan 90CFM 230V AC, 4” dia Castors with
Brake (set of 4) Cable manager 1U MS with Loops Shelf, Stationery 475mm N/W PDU
7Sockets 5Amps with MCB Mounting Hardware (Pkt. Of
20) Vertical Cable Channel 50mmW 22U complete in all respect .
Each
1
0
16 MR Supply & Fixing of cables and Connector for HDMI Cable, Speaker Cable for above system.
Lot 1
0
Total of Sub-Head - VIII carried to summary sheet 0
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BILL OF QUNATITIES : LIFT WORKS
Sr. No.
DSR 2018
Item No./NDSR
Description
Unit
QTY
Rate
Amount ( In Rs.)
1 SUB HEAD -: LIFT WORK
Note:- Laisoning & Obtaining Lift NOC from Lift Inspector shall be in the scope
of Contractor. All expenses in this regard shall be included in the Quoted
Rates of Lifts. Only Statutory Fee will be reimbursed on poduction of Original
Receipts. Lifts shall be BMS Compatible.
20 BED CUM PASSENGER (1360 KG) LIFT
Supply, installation, testing & commissioning of 20 bed cum passanger (1360 Kg) lifts having
contract speed of 1 MPS, centre opening GEARLESS WITH MACHINE ROOM serving different
floors in the lift shaft. Lift will be complete with combined luminous hall button with seven segment
digital hall position indicator at all floor, car operating panel with touchpanel luminous buttons,
seven segment digital car position indicator combined with direction arrows, overload warning
indicator, battery operated alarm bell and emergency light, fireman's switch at main lobby
enclosed and as under. LIFT SHALL BE DUPLEX/TRIPLEX COLLECTIVE
CONTROLLED. lift should comply with Technical Specifications & as per directions of E-I.C.
Each
5
-
DESIGN OF LIFTS - Bed cum Passenger Type
CAPACITY - 20 PASSENGER /1360 KG
SPEED -1 m/s
DRIVE - V3F
Overhead -As per NBC 2016 requirements or as per OEM standards
TRAVEL - 29 Mtr. (Approximately, to be correlated with Architectural Layouts)
FLOORS - Ground + 7 Floors
NO. OF STOPS - 8 Stops
REQUIRED WELL SIZE - As per NBC 2016 requirements or as per OEM standards
POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
Sr. No.
DSR 2018
Item No./NDSR
Description
Unit
QTY
Rate
Amount ( In Rs.)
AUXILIARY - Single Phase 220 V AC
CAR SIZE - As per NBC 2016 requirements or as per OEM standards
PIT DEPTH - As per NBC 2016 requirements or as per OEM standards
CAR ENCLOSURE
a) CAR CEILING - SS-304 Moonrock/Honeycomb scratchproof FINISH
b) CAR PANELS - SS-304 Moonrock/Honeycomb scratchproof FINISH
c) ILLUMINATION - LED LIGHT (Lux level/lumens as per requirements or OEM standards),
Supply Fan -2 Nos. min. or meeting ACPH norms. Pattern of lighting shall be staggered or any
other pattern as approved by E-I.C.
d) CAR FLOORING - 20 MM RECESS with Granite flooring
NO. OF ENTRANCE - ONE, LOCATION FRONT
CAR ENTRANCE - AUTOMATIC COPD DOORS IN SSMoonrock/Honeycomb
scratchproof FINISH
DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS FINISH
CONTROL - microprocessor based single automatic push buttons SELECTIVE
COLLECTIVE duplex/triplex with /without attendant.
HAND RAILING - STAINLESS STEEL (not less than 900 mm long, 900 mm above
floor level to be fixed adjacent to control panel in lift car)
CAR DOORS -SS-304 Moonrock/Honeycomb scratchproof FINISH
Car Operating Panel shall be enabled with Digital Touch panel facility and lit with
LED Lights
ARD - TO BE PROVIDED with dry maintenance free batteries with 30 min.backup, Voice
Announcement system in the Car to announce position of the elevator in the hoistway as the car
passes or stops at a floor served by eelvator & intercom facility to be provided. Also, braille buttons
for differently abled persons to be provided. Door Sensor (full door height) to be provided. All
necessary signboards should also be provided.
2 16 PASSENGER (1088 KG) LIFT
Sr. No.
DSR 2018
Item No./NDSR
Description
Unit
QTY
Rate
Amount ( In Rs.)
Supply, installation, testing & commissioning of 16 passanger (1088Kg) lifts having contract speed of
1.5 MPS, centre opening GEARLESS WITH MACHINE ROOM serving different floors in the
lift shaft. Lift will be complete with combined luminous hall button with seven segment digital
hall position indicator at all floor, car operating panel with touchpanel luminous buttons, seven
segment digital car position indicator combined with direction arrows, overload warning
indicator, battery operated alarm bell and emergency light, fireman's switch at main lobby
enclosed and as under. LIFT SHALL BE DUPLEX/TRIPLEX COLLECTIVE
CONTROLLED. lift should comply with Technical Specifications & as per directions of E-I.C.
Each
1
-
DESIGN OF LIFTS - Bed cum Passenger Type
CAPACITY - 16 PASSENGER /1088 KG
SPEED -1.5 m/s
DRIVE - V3F
Overhead -As per NBC 2016 requirements or as per OEM standards
TRAVEL - 29 Mtr. (Approximately, to be correlated with Architectural Layouts)
FLOORS - Ground + 7 Floors
NO. OF STOPS - 8 Stops
REQUIRED WELL SIZE - As per NBC 2016 requirements or as per OEM standards
POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
AUXILIARY - Single Phase 220 V AC
CAR SIZE - As per NBC 2016 requirements or as per OEM standards
PIT DEPTH - As per NBC 2016 requirements or as per OEM standards
CAR ENCLOSURE
a) CAR CEILING - SS-304 Moonrock/Honeycomb scratchproof FINISH
b) CAR PANELS - SS-304 Moonrock/Honeycomb scratchproof FINISH
c) ILLUMINATION - LED LIGHT (Lux level/lumens as per requirements or OEM
standards), Supply Fan -2 Nos. min. or meeting ACPH norms. Pattern of lighting shall be
staggered or any other pattern as approved by E-I.C.
d) CAR FLOORING - 20 MM RECESS with Granite flooring
NO. OF ENTRANCE - ONE, LOCATION FRONT
CAR ENTRANCE - AUTOMATIC COPD DOORS IN SSMoonrock/Honeycomb
scratchproof FINISH
DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS FINISH
CONTROL - microprocessor based single automatic push buttons SELECTIVE COLLECTIVE duplex/triplex with /without attendant.
Sr. No.
DSR 2018
Item No./NDSR
Description
Unit
QTY
Rate
Amount ( In Rs.)
HAND RAILING - STAINLESS STEEL (not less than 900 mm long, 900 mm above
floor level to be fixed adjacent to control panel in lift car)
CAR DOORS -SS-304 Moonrock/Honeycomb scratchproof FINISH
Car Operating Panel shall be enabled with Digital Touch panel facility and lit with
LED Lights
ARD - TO BE PROVIDED with dry maintenance free batteries with 30 min.backup, Voice
Announcement system in the Car to announce position of the elevator in the hoistway as the car
passes or stops at a floor served by eelvator & intercom facility to be provided. Also, braille buttons
for differently abled persons to be provided. Door Sensor (full door height) to be provided. All
necessary signboards should also be provided.
3 GOODS LIFT :-
Supply, installation, testing & commissioning of goods lift having contract speed of
0.5 MPS serving different floors in the lift shaft. LIFT SHALL BE WITH centre opening,
GEARLESS TYPE WITH MACHINE ROOM serving different floors in the lift shaft. Lift will be
complete with combined luminous hall button with seven segment digital hall position
indicator at all floor, car operating panel with luminous buttons, seven segment digital car
position indicator combined with direction arrows, overload warning indicator, battery
operated alarm bell and emergency light, fireman's switch at main lobby enclosed and as
under. LIFT SHALL BE DUPLEX/TRIPLEX COLLECTIVE CONTROLLED. lift should comply with
Technical Specifications & as per directions of E-I.C.
Each
2
-
DESIGN OF LIFTS - Goods lift
CAPACITY - 1 Tonne
SPEED -0.5 m/s
DRIVE - V3F
TRAVEL - 29 Mtr. (Approximately, to be correlated with Architectural Layouts)
FLOORS - Ground to 7th Floor
NO. OF STOPS - 8 Stops
REQUIRED WELL SIZE - As per NBC 2016 requirements or as per OEM standards
POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
AUXILIARY - Single Phase 220 V AC
CAR SIZE - As per NBC 2016 requirements or as per OEM standards
PIT DEPTH - As per NBC 2016 requirements or as per OEM standards
Sr. No.
DSR 2018
Item No./NDSR
Description
Unit
QTY
Rate
Amount ( In Rs.)
CAR ENCLOSURE
a) CAR CEILING - SS-304 Moonrock/Honeycomb scratchproof FINISH
b) CAR PANELS - SS-304 Moonrock/Honeycomb scratchproof FINISH
c) ILLUMINATION - LED LIGHT (Lux level/lumens as per requirements or OEM standards),
Supply Fan -2 Nos. min. or meeting ACPH norms. Pattern of lighting
shall be staggered or any other pattern as approved by E-I.C.
d) CAR FLOORING - SS chequered plate flooring
NO. OF ENTRANCE - ONE, LOCATION FRONT
CAR ENTRANCE - AUTOMATIC COPD DOORS IN SS Moonrock/Honeycomb
scratchproof FINISH
DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS FINISH
CONTROL - microprocessor based single automatic push buttons SELECTIVE
COLLECTIVE duplex/triplex with /without attendant.
HAND RAILING - STAINLESS STEEL (not less than 900 mm long, 900 mm above
floor level to be fixed adjacent to control panel in lift car)
CAR DOORS -SS 304 Moonrock/Honeycomb scratchproof FINISH
ARD - TO BE PROVIDED with dry maintenance free batteries with 30 min.backup, Voice
Announcement system in the Car to announce position of the elevator in the hoistway as the car
passes or stops at a floor served by eelvator & intercom facility to be provided. Also, braille buttons
for differently abled persons to be provided. Door Sensor (full door height) to be provided. All
necessary signboards should also be provided.
Total of Sub-Head - carried to summary sheet
-
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BOQ:- HVAC WORKS
Sl.No.
DSR
2018/NSR
Description
Unit
Qty
Rate(In Rs.)
Amount (in Rs.)
Note: The HVAC contractor shall provide fire shunt relay contact in main HVAC panel and all AHU panels/DBs along with auto / manual mode selector
switch in the outgoing feeder for AHU Fan, Ventilation & Pressurization fan etc. to take fire input signal (Potential Free Contact) to trip /switch off them.
Cost shall be included in the panel price quoted by him.
For establishing CFC free product, for Refrigerant, Insulation (duct/pipe) etc. third party certification from authorized
agency/catalog/GRIHA rated product shall be furnished by the Contractor.
Sub Head 'A' - Machinery
1 NSR-1 Air Cooled Screw Chiller (with VFD)
Supply ,Installation, Testing and Commissioning of AHRI/Eurovent certified Rotary Screw Air cooled Chilling M/C of 300 TR actual capacity at tender
operating conditions (as mentioned below) with R - 134a refrigerant (ozone friendly, HFC) ar any other refrigerant as per NBC 2016 norms meeting
all functional requirements and approved by E-I-C, semihermatic / hermetically sealed single /multiple compressors with mono/twin screw
complete with single/multi refrigerant circuit, driven by suitable KW Squirrel Cage induction motor complete with insulated shell and tube flooded
chiller, with S.S braided pipe flexible connector, insulation to be mechanically protected similar to chilled water piping insulation, flanged end for chiller
& condenser, electronic auto setting water flow switches at condenser & chiller outlet, factory done refrigerant piping, refrigerant and oil first charged,
microprocessor based control panel with non-volatile memory & touch screen display, motor driven by floor mounted air-cooled VSD/VFD with IP 54 or
better as per OEM standards enclosure with active harmonic filters with THID less than equal to 30-40% or as per OEM standards with machine &
accessories, IP 44 enclosure for control and terminal box, factory installed electrical disconnect / isolator switch integrating main fuses etc. all mounted
on M.S. frame. Motor shall be suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply, class F insulation & IE -3 rated. Chillers shall be provided
with Victaulic coupling & spring isolators. The Condenser Fan control shall be provided with VFD.It should include flow switch/DP switch at
chiller and condenser, vibration isolators, including oil separators, pressure relief devices, filter drier moisture indicators, refrigerant economizer,
integral refrigerant piping and wiring, accessories as required and called for, automatic and safety controls mounted in central console panel.
dB Level shall not be more than 82 @ 1.5 m or as per relevant norms.
Cost for Suitable PCC/RCC foundation ( PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including
making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster is
deemed to be included in this item cost.
The cost of chilling machine shall be inclusive of BMS interface card for integration with BMS System & any deration in capacity to be accounted in arriving at the actual capacity of chiller.
Chiller
Chilled water in : 54o F
Chilled water out : 44o F
Chilled water flow rate: 720 USGPM (min.)
Fouling Factor : 0.0005 (FPS)
Max pressure drop on water side : 6.0m (Max)
(1 No. standby Chiller included in above quantity)
Chilling machine COP (at AHRI conditions) shall be min 3.2 and IPLV of min. 3.7 & and all performance requirements are at ARI 550/590 -1998 Test conditions.(ECBC + Building Requirements 2017).
NSR-1.1
The price quoted for supply, installation, testing & commissioning of Chilling Unit shall be inclusive of all duties & taxes,
insurance, transportation / shipment cost from works to site, loading / unloading, port clearance charges etc. as required in Indian Rupees.
No.
4
-
Ambient Temperature : 115 Degree F (Peak Summer Conditions)
2 NSR-2 Primary Chilled Water Pumps Set
Supply, installation, testing and commissioning of vertical Inline Pump/ Vertical split casing , back pull out flexible coupled End Suction Pump mounted on
a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by
OSHA complaint coupling guard, with CI casing, SS (CF8) /bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The
pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation,
1500 RPM (Max.) Pump, base, coupling and motor shall be factory assembled.
The capacity of motor shall be at least 10% in excess of BHP requirement of pump.
The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum
efficiency of pump shall be as mentioned below.
Cost for pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts,
packing etc.) with plaster, Anti vibration arrangement of cushy foot mountings is deemed to be included in this item cost.
Suction guide to be provided by pump manufacturar for unit responsability. Pump curves & loss calculations shall be furnished during approval from
competant authority.
Pumps shall be BMS compatible.
Pump rating shall be PN 16 preferably.
Contractor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of Engineer-in-charge.
Water flow rate : 720 USGPM (2725 LPM Approx.)
Head : 40 ft.
Motor HP :10 HP (suggested) or as per OEM standard & meeting the functional requirements
Efficiency(Min) : 75 % or nearest as per OEM
NSR- 2.1 (1 No. standby pump included in above quantity) No. 4 -
3 NSR-3 Secondary Chilled Water Pumps Set With VFD
Supply, installation, testing and commissioning of Vertical Inline Pump/Vertical split casing , back pull out flexible coupled End Suction Pump mounted on a
common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by OSHA
complaint coupling guard, with CI casing, SS (CF8)/bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The pump motor
shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation, 1500 RPM
(Max.).
Pump, base, coupling and motor shall be factory assembled. adjustable
The capacity of motor shall be at least 10% in excess of BHP requirement of pump.
The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum efficiency of
pump shall be as mentioned below.
Cost for pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts,
packing etc.) with plaster.
Pumps Shall be BMS & VFD compatible.
Suction guide to be provided by pump manufacturar for unit responsability. Contractor to submit
proposed pump model with duty curve.
Pump rating shall be PN 16
The entire work shall be complete as per specifications & as per directions of Engineer-in-charge.
The chilled water pumps shall also include the cost of thermal insulation. Secondary chilled water pumps shall be suitable for operation on variable
frequency drives & conforming to the specifications of variable speed pumping system. The capacity of
motor shall be at least 10% in excess of BHP requirement of pump.
4 Secondary Chilled water pumps
Water flow rate : 720 USGPM (2725 LPM Approx.)
Head : 80 ft.
Motor HP : 25.0 HP(suggested) or as per OEM standard or meeting functional requirements
Efficiency : 75 % or nearest as per OEM
NSR-3.1 (1 No. standby pump included in above quantity) No. 4 -
NSR-4 Variable Speed Pumping System for Chilled Water Pumps (Secondary Pump)
Supply, installation, testing and commissioning of VSPS (variable Speed Pumping System) consisting of 03 No. 25 HP variable frequency drive (VFD)
having IP 54/IP-55 enclosure with heat sink suitably interfaced with other system components, hand / auto macro designed for pumping application, 01
No. dedicated microprocessor based pump logic controller, parallel pumping software duly downloaded, 03 No. Differential Pressure Sensor /
Transmitters (or as required to meet the functional requirements), interfacing amongst all components and compatibility of I/O signals etc.
complete with other accessories as required. It should be BMS compatible complete with other accessories as required.
It should be complete as per manufacturer's Specifications & as directed by Engineer-in-charge.
For 4 No. of 25 H.P Secondary Chilled Water Pumps (3W+1 S)
Set
1
-
5 NSR-5 Closed Type Pressurized Expansion Tank(Chilled Water Line)
Supplying, installing, testing and commissioning of PRESSURISED COLD WATER EXPANSION TANK WITH AIR SEPARATER with
S.S braided pipe flexible connector suitable for total volume of water in cold water circuits along with necessary accessories such as centrifugal air
separator, pumps etc. in order to keep cold water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the
system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection
and 20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank shall be fitted with
lifting rings and a floor mounting skirt for vertical installation. The tank and air separator must be constructed in accordance with section VIII of the
ASME Boiler and pressure vessel (Unfired)code and stamped 125 PSI working pressure. The complete system shall be sourced from single manufacturer
and supplied and installed with all accessories and safety fixtures and safety fixtures required for
proper functioning of the complete hydronic system.
The expansion tank shall be supplied along with pressurization unit. The pressurization unit shall consist of two No.(1 working+1 stand-by) high
pressure pumps of suitable pressure rating mounted on M.S. frame, complete with interconnecting piping, isolation valves, NRV, Y-strainer, Pressure
gauge, pressure transmitter, auto-logic panel(IP 55) with dry-run protection,
electrical MCB and interconnecting wiring.
The unit shall be housed in powder-painted canopy suitable for external installation, if required.
NSR-5.1 The capacity of tank shall be 2000 Liters approx. (for chilled water system). Set 1 -
6 NSR-6 VACUUM DEGASSER (installed as a bypass to the main CHW line)
Supply & Installation testing & commissioning of Vacuum Degasser to be connected as a bypass to the main water pipeline in the CHW system. The Vacuum
degasser shall be of automatic operation and fitted with a high efficiency multistage pump. The degasser shall be of 150 - 300 Cubic meter degassing
capacity (depending upon flow of the system) with a capacity to degas up to 1000 Liters per hour depending upon the model selected as per the system
working pressure and suitable up to 6 bar. The Vacuum Degasser shall be BMS Compatible. The Degasser shall be of Carbon Steel with a Brass Automatic Air
vent. The Degasser shall be of Plug & play type & shall be of automatic operation It should be complete as per manufacturer's specifications & as directed
by Engineer-in-charge. It may be wall mounted/floor mounted & necessary support for the same is to be included in
item's cost.
Total Chilled Water Flow Rate:- 2160 USGPM (8180 LPM) Approx. No. 1 -
7 NSR-7 Hot Water Generator For Winter Heating / Monsoon Reheat
Supply, installation, testing and commissioning of electrically operated Hot Water Generator of efficiency more than 90% of given capacity in multiple
bank complete with PLC based microprocessor controls, electrical panels, stainless steel braided pipe flexible connector etc. confirming to tender
specifications section. The pressure Vessel shall be constructed as per ASME standards and insulated on all sides with 2 layers of 50 mm thick fiberglass
of density 32 kg/cum & K value as per ECBC standards with 28 gauge Aluminum cladding as per specifications. The hot water generator shall be equipped
with all automatic and safety controls such as manual reset, high temperature water outlet, microprocessor based step controller with thermistor sensor to
control HWG in stages and recycling relay, on/off switch type thermostat, pilot light, low water cut off and other controls as per manufacturers
recommendations. All basic controls and terminals shall be located in an integral control cabinet factory wired and tested. The hot water generator shall
be suitable for 415±10%volts/50 cycles,3phase power supply. The entire hot water generator shall be factory assembled and tested. It should be BMS
compatible with RS-485 communication port. Cost for Suitable PCC/RCC foundation ( PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone
aggregate 30 cm above floor level including making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster, Anti
vibration arrangement of cushy foot mountings is deemed to be included in this item cost.
NSR-7.1 Capacity : 35 KW (For OTs )
Water temp in at 1120 F & temp. out at 1220 F with required flow rate No. 1 -
NSR-7.2 Capacity : 50 KW (For ICUs Area)
Water temp in at 1120 F & temp. out at 1220 F with required flow rate No. 1 -
NSR-7.3 Capacity : 150 KW (For Winter Heating)
Water temp in at 1120 F & temp. out at 1220 F with required flow rate No. 2
-
8 NSR-8 Hot Water Pumps Set
Supply, installation, testing and commissioning of vertical Inline Pump/ Vertical split casing , back pull out flexible coupled End Suction Pump mounted on
a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by
OSHA complaint coupling guard, with CI casing, SS (CF8) /bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The
pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply of (IE3) efficiency class. Motor shall be squirrel cage, Class F insulation,
1500 RPM (Max.) Pump, base, coupling and motor shall be factory assembled.
The capacity of motor shall be at least 10% in excess of BHP requirement of pump.
The internal components of pumps including mechanical seal shall be suitable to sustain a temperature of 122 degree Fahrenheit. Minimum
efficiency of pump shall be as mentioned below.
Cost for pump foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts,
packing etc.) with plaster, Anti vibration arrangement of cushy foot mountings is deemed to be included in this item cost.
Suction guide to be provided by pump manufacturar for unit responsability. Pump curves & loss calculations shall be furnished during approval from
competant authority.
Pumps shall be BMS compatible.
Pump rating shall be PN 16 preferably.
Contractor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of Engineer-in-charge.
Hot water pumps for OTs
Water flow rate :250 USGPM OR USGPM suitable for 35 KW HWG
Head : 80ft
Motor HP : 3.0 HP(suggested) or as per requirements meeting functional requirements
Efficiency : Nearest as per OEM
NSR- 8.1 (1 No. standby pump included in above quantity), Pump shall be highly efficient type. No. 2 -
Hot water pumps for ICUs Area
Water flow rate : 250 USGPM OR USGPM suitable for 50 KW HWG
Head : 80ft
Motor HP : 3.0 HP(suggested) or as per requirements meeting functional requirements
Efficiency : Nearest as per OEM
NSR- 8.2 (1 No. standby pump included in above quantity), Pump shall be highly efficient type. No. 2 -
Expansion Tank
9
NSR- 9
Supply, installation, testing and commissioning of expansion tank of following size made out of 6 mm MS sheet duly epoxy coated & insulated with
Closed Cell Elastomeric Nitrile Rubber of density 50+/-10 Kg/CMT of specified thickness of 32 mm and suitable for outdoor application with two coats of UV
resistance paint and mechanically protected with two layers (07 mil thick No. layer) of adhesive and Glass Cloth / CSM and finally aluminum cladded with 22
G aluminum sheet complete with float valve, over flow & make up connections etc..
Necessary civil work required for the above equipment shall be included in this item quoted price.
NSR- 9.1
For Hot Water Circuit - 1000mm x 1000mm x 1000mm No. 1
-
10 NSR -10 Chilled Water Fan Coil Unit
Supply, installation, testing and commissioning of GI powder coated horizantal ceiling suspended single skin chilled & hot water fan coil units
complete with fan, 3 speed motor, 3 row deep cooling coil , aluminium filters (MERV-8) with filter box, double sandwitched insulated tray, copper
connection, rotary switch, supporting arrangement, electrical wiring etc.The thickness of GSS sheet should be 1.25 mm . The fan shall be selected for
5 -8mm external static pressure. The unit shall have double sandwitched insulated extended tray to accomodate all FCU valves within extended tray.
Tray shall be duly insulated with nitrile rubber as specified for pipe insulation. The complete fan coil unit shall be in line with the standard
specification. The capacity of fan coil units shall be as follows. Proper supporting system for FCU to be provided & will be in
contractor's scope.
NSR-10.1 1200 CFM (3.0 TR) No. 12 - NSR-10.2 1000 CFM (2.5 TR) No. 7 - NSR-10.3 800 CFM (2.0 TR) No. 26 - NSR-10.4 600 CFM (1.5 TR) No. 78 - NSR-10.5 400 CFM (1.0 TR) No. 43 -
11 NSR -11 AIR HANDLING UNIT (FOR OT'S) -With VFD
Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for
Operation Theatres as per specifications given below:-
AHU Construction:- It shall be made out of 0.8 mm pre -coated Galvanised steel sheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF
insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drain pan (made out of 1.2
mm stainless steel (SS Grade 304) sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of
panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum.
Necessary foundation required & anti vibration pads shall be provided & cost for the same shall be included in this item.
Supply Air Stream:-
1) Filter section consisting of pre filter, fine filter & HEPA filters in aluminum casing .Pre-filter section shall be with non woven synthetic media of 10
micron particle size with an efficiency of 90%, fine/microvee filter section will be with filters of non woven synthetic media of 3 micron particle size
of efficiency 99%. HEPA filter section with non woven synthetic media of 0.3 micron particle size with an efficiency of 99.997% at terminals. For OTs,
cost of HEPA filter not to be included in this item only space shall be considered in AHU. The quoted price shall also include VCD, pressure differential
indicator across Fine filters and HEPA filters with audible and visual alarms.
2) Plug Fans with aerofoil profile blade, CENTRIFUGAL type (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and
duct flexible connection. The supply fan shall be provided with variable frequency drive and input / output signal compatible to BMS system with TEFC
drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably
designed for variable frequency drive applications shall be as per actual selection meeting other technical requirements.
3) 8 Row Deep Cooling Coil with Alu. fins
4) 2 Row Deep Heating Coil for winter Reheat.
5) Ultrasonic Humidifier of suitable capacity , complete with stainless steel SS-304 tank with level switch, piezo transducers duly interlocked with level
sensors, Solenoid operated RO water makeup, water over flow protection, overflow and drain connections.
6) Discharge Plenum Section.
Space For UVGI system along with power / control wiring. Access doors should be fitted with interlocks which will turn off the UV in the event the door is
opened. Precaution labels should be posted near access doors to any equipment with UV systems.
COIL- Copper tubes and Aluminum fins 12-13 fin./inch, Coil size shall be selected for air velocity of 350 ft./minute & velocity across filters at 350
ft./minute.
In Built VFD:- VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure for use on
standard centrifugal plug fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology.
VFD’s shall have built-in harmonic filters. No. VFD panel to be provided with digital display showing electrical parameters like voltage, current and
power consumption. No. VFD shall be installed in a dedicated external IP-65 enclosure and the inter connecting wires between driver and MCC shall be
included. Item tabulated separately.
Sound level 65 db. at the distance of 2 mtr.(maximum)
Sixth Floor
NSR-11.1 F/M Post OT Room,2000 CFM,12.0 TR,125 mm SP,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.2 F/M OT 1 , 3000 CFM, 9.26TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.3 F/M OT 9 , 3250 CFM, 6.88TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.4 F/M Sterile corridor, 4000 CFM,22.0 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Terrace Floor
NSR-11.5 F/M OT 2 , 2853CFM,8.5 TR,125 mm SP,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.6 F/M OT 3 , 3100 CFM,8.76 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.7 F/M OT 4 , 3100 CFM,8.76TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.8 F/M OT 5 , 3900 CFM,11.62TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.9 F/M OT 6 , 3900 CFM,11.64 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.10 F/M OT 7 , 3500 CFM,9.6 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.11 F/M OT 8 , 3450 CFM,9.6 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-11.12 F/M OT 10, 3100 CFM,6.88 TR,125 mm SP,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
12 NSR-12 AIR HANDLING UNITS TYPE 2 (2 STAGE FILTERATION) FOR ICUS & CRITICAL AREAS (WITH VFDs)
Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for
Other critical Areas like ICU, CT/MRI etc. areas as per specifications given below:-
AHU Construction:- It shall be made out of 0.8 mm pre -coated Galvanised steel sheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF
insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drain pan (made out of 1.2
mm stainless steel (SS Grade 304) sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile.AHUs Inner skin of
panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum.
Necessary foundation required & anti vibration pads shall be provided & cost for the same shall be included in this item.
1) Filter section consisting of pre filter & fine filter in aluminum casing .Pre-filter section shall be with non woven synthetic media of 10 micron
particle size with an efficiency of 90%, fine/microvee filter section will be with filters of non woven synthetic media of 3 micron particle size of
efficiency 99%.The quoted price shall also include VCD, pressure differential indicator across Fine filters with audible and visual alarms.
2) Plug Fans with aerofoil profile blade (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and duct flexible connection.
The supply fan shall be provided with variable frequency drive and input / output signal compatible to BMS system. Squirrel cage induction motors suitable
for 415 ± 10% volts, 50 Hz, AC supply & high efficiency (IE-2 Efficiency),
H.P of motor shall be as per actual selection meeting other technical requirements.
3) 6 Row Deep Cooling Coil, with aluminum fins.
4) 2 Row Deep Heating Coil for winter Reheat.
5) Ultrasonic Humidifier of suitable capacity , complete with stainless steel SS-304 tank with level switch, piezo transducers duly interlocked with level
sensors, Solenoid operated RO water makeup, water over flow protection, overflow and drain connections.
6) Discharge Plenum Section.
7) Space For UVGI Emitter system along with power / control wiring. Access doors should be fitted with interlocks which will turn off the UV in the event
the door is opened. Precaution labels should be posted near access doors to any equipment with UV systems.
8) COIL- Copper tubes and Aluminium fins 12-13 fin./inch, Coil size shall be selected for air velocity of 400 ft/minute & velocity across filters at 400
ft/minute. Motors shall be suitable for 415 ± 10% volts, 50 Hz, 3 phase AC supply & high efficiency(IE-3). Vibration isolation shall be as per
specifications and as shown on the drawings.
9) VFD:- VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure (for outdoor applications) &
IP-55 enclosure (for indoor applications) for use on standard centrifugal plug fans. The display should be in alpha-numeric characters and programming
facility should be in user-friendly HVAC terminology. VFD’s shall have built-in harmonic filters. No. VFD panel to be provided with digital display
showing electrical parameters like voltage, current and power consumption. No. VFD shall be installed in a dedicated external enclosure and the inter
connecting wires between driver and MCC shall be included. VFD Item is separatly tabulated.
Sound level 65 db at the distance of 2 mtr.(maximum)
Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply & high efficiency (IE-3 Efficiency), H.P of motor shall be as per actual
selection meeting other technical requirements.
Necessary potential free contacts shall be provided for BMS operation.
Ground Floor
NSR-12.1
C/S MRI, 1500 CFM,5.0 TR,65 mm SP,Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.2
C/S CT Scan ,1800 CFM,5.5 TR,65 mm SP,Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
First Floor
NSR-12.3
F/M ENDO 1 ,7000 CFM,30.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.4
F/M ENDO 2 ,7200 CFM,32.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Second Floor
NSR-12.5
F/M ENDO 1 ,7000 CFM,30.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.6
F/M ENDO 2 ,7200 CFM,32.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Third Floor
NSR-12.7
F/M ENDO 1 ,7000 CFM,30.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-12.8
F/M ENDO 2 ,7500 CFM,32.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Fourth Floor
NSR-12.9
F/M Plastic Surgery Ward-1 & 2 ,7000 CFM,35.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 2
-
Fifth Floor
NSR-12.10
C/S Neurology ICU, 2000 CFM, 8.2 TR, 65 mm SP ,Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL
REQUIREMENT No. 1
-
NSR-12.11
C/S Endocrnology, 1650 CFM, 5.5 TR , 65 mm SP ,Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.12
C/S Clinical Hematology, 1300 CFM, 4.0 TR , 65 mm SP ,Fan motor of 1.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.13
C/S Pediatric Surgery, 1100 CFM, 3.5 TR , 65 mm SP ,Fan motor of 1.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.14
C/S Corridor,3500 CFM, 17.0 TR , 65 mm SP , Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-12.15
C/S Surgerical Gastology ward/ICU 3300 CFM,12.0 TR , 65 mm SP , Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.16
C/S Hematology ICU/Clinical ICU,3000 CFM, 12 TR , 65 mm SP , Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-12.17
F/M Nephro/Plastic Surgery, 5500 CFM ,17 TR , 65 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-12.18
C/S Neurosurgery ICU, 4000 CFM, 15.0 TR, 65 mm SP ,Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 2
-
Sixth Floor
NSR-12.19 C/S Pre OT, 5000 CFM, 26.0 TR, 65 mm SP , 65 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 2
-
Seventh Floor
NSR-12.20 F/M Wards, 8000 CFM ,40 TR , 65 mm SP , Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.21 F/M Wards, 8500 CFM ,43 TR , 65 mm SP , Fan motor of 5.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-12.22 F/M CSSD ,7000 CFM,24.1 TR, 65 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
13 NS -13 AIR HANDLING UNITES TYPE 1 (1 STAGE FILTERATION) FOR COMMON AREAS -With VFDs
Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for
Waiting & Public areas as per specifications given below:-
AHU Construction:-It shall be made out of 0.8 mm pre -coated Galvanized steel sheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF
insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drain pan (made out of 1.2
mm stainless steel (SS Grade 304) sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of
panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum.
Necessary foundation required & anti vibration pads shall be provided & cost for the same shall be included in this item.
1) Filter section consisting of pre filter .Pre-filter section shall be with non woven synthetic media of 10 micron particle size with an efficiency of
90%.
2) Plug Fans with aerofoil profile blade (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and duct flexible connection.
The supply fan shall be provided with variable frequency drive and input / output signal compatible to BMS system. Squirrel cage induction motors suitable
for 415 ± 10% volts, 50 Hz, AC supply & high efficiency (IE-3 Efficiency),
H.P of motor shall be as per actual selection meeting other technical requirements.
3) 6 Row Deep Cooling Coil, with aluminum fins.
4) Discharge Plenum Section.
COIL- Copper tubes and Aluminum fins 12-13 fin./inch, Coil size shall be selected for air velocity of 350 ft./minute & velocity across filters at 350
ft./minute.
Sound level 65 db. at the distance of 2 mtr.(maximum)
Necessary potential free contacts shall be provided for BMS operation.
Ground Floor
NSR-13.1
F/M Waiting Area,15000 CFM,68.0 TR,50 mm SP,Fan motor of 7.5 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-13.2
C/S Staff Dining area,1200 CFM,5.0 TR,50 mm SP,Fan motor of 0.5 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-13.3
C/S Corridor area,3500 CFM,15.0 TR,50 mm SP,Fan motor of 1.5 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-13.4
C/S Conference area,1600 CFM,6.0 TR,50 mm SP,Fan motor of 1.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
First Floor
NSR-13.5
C/S Waiting Lobby,7000 CFM,30.0 TR, 50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Second Floor
NSR-13.6
C/S Waiting Lobby,7000 CFM,30.0 TR, 50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Third Floor
NSR-13.7
C/S Waiting Lobby,5500 CFM,30.0 TR, 50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Fourth Floor
NSR-13.8
C/S Waiting Area,4000 CFM,17.0 TR, 50 mm SP ,Fan motor of 2.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Fifth Floor
NSR-13.9
C/S Waiting Area, 5000 CFM, 30.0 TR, 50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Sixth Floor
NSR-13.10 C/S UPS & CCTV Room, 1100 CFM, 5.0 TR, 50 mm SP ,Fan motor of 1.5 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT No. 1
-
NSR-13.11 C/S VISITORS WT, 3000 CFM, 8.0 TR, 50 mm SP ,Fan motor of 1.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-13.12 C/S Common Area, 6500 CFM, 32TR, 50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
Seventh Floor
NSR-13.13 C/S Room, 1650 CFM, 6.5 TR, 50 mm SP ,Fan motor of 1.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
NSR-13.14 C/S Waiting Area, 6500 CFM ,32 TR ,50 mm SP ,Fan motor of 3.0 HP SUGGESTED OR AS REQUIRED MEETING FUNCTIONAL REQUIREMENT
No. 1
-
14 NSR- 14 VFDs -Variable Frequency Drives
Supply, installation, testing & commissioning of VFDs.VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) ,
IP-65 enclosure (for outdoor applications) & IP-20 enclosure (for indoor applications) for use on AHU fans. The display should be in alpha-numeric
characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have built-in harmonic filters with THDI less than 5%. No.
VFD panel to be provided with digital display showing electrical parameters like voltage, current and power consumption. No. VFD shall be installed in a
dedicated external/internal enclosure and the inter connecting wires between driver and MCC shall be included. Necessary transformer, power adapters,
sensors, relay etc. as required for satisfactory operation shall be in the scope of VFD supplier. It should be BMS Compatible.
NSR-14.1 10.0 HP/ 7.5 KW No. 1 - NSR-14.2 7.5 HP/ 5.6 KW No. 2 - NSR-14.3 5.0 HP/ 3.73 KW No. 1 - NSR-14.4 3.0 HP/ 2.2 KW and below rating No. 1 -
15 NSR-15 Thermostat for Fan Coil Units- Snap acting Type
NSR-15.1
Supply, installation, testing and commissioning of automatic control for Fan Coil Units for two pipe system consisting of snap acting digital thermostat,
which will have provision of setting of room temperature, setting of fan speed (High, Medium, Low). The quoted price of thermostat shall include the cost
of 20mm MS conduits, control cabling, MS Box etc. as required. It shall
include all accessories ,mountings, wiring between thermostat & unit, terminations etc.(BMS Compatibility to be provided).
No.
166
-
16 NSR-16 Humidistat for AHU (Proportional type )
Supply, installation, testing and commissioning of latest generation digital display type BMS compatible thermostat / humidis tat with controller for
cool / heat application suitable for two/four pipe system & humidistat suitable for working with humidifier and hot water coil control valves for various
air handling Units. The thermostat shall have provision of setting of space temperature and display of the same. The humidistat shall have provision of
setting space RH and display of the same. The quoted price of thermostat / humidistat shall include the cost of 20mm MS conduits, control cabling, MS Box
etc. as required. The cost quoted shall be excluding the control valves and humidifier. It shall include all accessories ,mountings, wiring between
thermostat & unit, terminations etc.(BMS Compatibility to be provided).
NSR-16.1 Humidistat for AHU No. 40 -
17 NSR-17 PRESSURE INDEPENDENT CONTROL/HIGH RANGEABILITY CONTROL VALVE & BALANCING VALVE) FOR AHUs
Supply, Installation, testing and commissioning of Two way , high range ability / Pressure independent dynamic Balancing cum Control valves fitted with
motorised,modulating actuators with linear stroke of minimum 15 mm, in chilled water lines at No. air handling unit. The actuator shall have shut off
capability of minimum 4 bar rating. The actuator shall be controlled by BMS &
should accept a signal of 4-20mA/2-10 VDC.The valves shall be suitable for following flow rate and confirming to specifications.
NSR-17.1 32 mm Dia No. 10 - NSR-17.2 40 mm Dia No. 10 - NSR-17.3 50 mm Dia No. 13 - NSR-17.4 65 mm Dia No. 15 - NSR-17.5 80 mm Dia No. 5 - NSR-17.6 100 mm Dia No. 1 -
18
NSR-18
Supply installation testing & commissioning of digital electronic controller for AHU with Thermostat & with LCD display capable of accepting 0-10v dc
signal from BMS and water water temperature signal from coil inlet and outlet sensors confirming to detailed specification. All other accessories i.e.
Temperature sensors-3nos,230V/24VAC power supply-1No.thermowell-1no
should be included in this item.
NSR-18.1 32 mm Dia No. 10 - NSR-18.2 40 mm Dia No. 10 - NSR-18..3 50 mm Dia No. 13 - NSR-18.4 65 mm Dia No. 15 - NSR-18.5 80 mm Dia No. 6 - NSR-18.6 100 mm Dia No. 1 -
19
NSR-19
Supply, installation, testing and commissioning of duct mounted air purification system/ cell based on Photohydroionization cell with the capability to
produce friendly oxidizers like Ionized Hydro Peroxides, Super Oxide Ions, Hydroxides Ions with quad metalic coating (Rohdium, silver, copper and
titanimum) and duly enclosed by a poly casing tube that should prevent glass or mercury leakage into the conditioned/ served space. The honeycomb matrix
shall not be accepted. The units should be designed after undertaking a load factor calculation for No. specific area where the equipment is to be installed.
The load shall clearly state the number of units required vis-à-vis the wattage of the units for submital. The system shall be capable of reducing
microbial bacteria, virus and spores , VoC’, odors and particulates matter. The equipment shall conform to UL 1598 CAN/CSA
C222 EN60335-1, EN60335-2-65, EU standards, certifications shall be submitted along with the technical submital.
NSR-19.1 Post OT 2000 CFM No. 1 - NSR-19.2 OT 1 4000 CFM No. 1 - NSR-19.3 OT 9 3700 CFM No. 1 - NSR-19.4 Sterlie Corridor 4000 CFM No. 1 - NSR-19.5 OT 2 2800 CFM No. 1 - NSR-19.6 OT 3 3000 CFM No. 1 - NSR-19.7 OT 4 3400 CFM No. 1 - NSR-19.8 OT 5 4200 CFM No. 1 - NSR-19.9 OT 6 4200 CFM No. 1 - NSR-19.10 OT 7 4000 CFM No. 1 - NSR-19.11 OT 8 4000 CFM No. 1 - NSR-19.12 OT 10 3600 CFM No. 1 - NSR-19.13 ENDO 1 7000 CFM No. 2 - NSR-19.14 ENDO 2 7200 CFM No. 2 - NSR-19.15 ENDO 1 5500 CFM No. 1 - NSR-19.16 ENDO 2 7500 CFM No. 1 - NSR-19.17 Plastic Surgery 7000 CFM No. 2 - NSR-19.18 Neuro ICU 2000 CFM No. 1 - NSR-19.19 Gastro ICU 3500 CFM No. 1 - NSR-19.20 Surgical ICU 3300 CFM No. 1 - NSR-19.21 Neuro ICU 4000 CFM No. 1 - NSR-19.22 Pre OT 2300 CFM No. 2 -
20 NSR-20 Cabinet Type Inline Fans (Accoustically Insulated)
Supplying, installing, testing and commissioning of inline fans suitable for installing in any position in vertical or horizontal ducts. The casing shall be
double skin, internally acoustically lined and constructed of galvanised steel. with efficient motor, fire retardent double layer canvass connection etc
complete in all respect & of following capacities. The casing shall be selected for lower noise level. Fan motor shall have inbuilt speed controller. Motor
shall be with class F insulation. Quoted price shall be inclusive of electronic speed regulator and wiring between fan & speed regulator for single phase fans.
Supporting/mounting arrangement complete with all accessories is in contractor's scope.
Fan dia. shall be selected such that it meets the functional requirements.
NSR-20.1 Air Quantity : 750 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Front Male Toilet No. 16 -
NSR-20.2 Air Quantity : 550 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Front Female Toilet No. 16 -
NSR-20.3 Air Quantity : 600 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Laundary Collection + Store No. 1 -
NSR-20.4 Air Quantity : 1300 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Back Male Toilet No. 6 -
NSR-20.5 Air Quantity : 1300 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Back Female Toilet No. 6 -
NSR-20.6 Air Quantity : 300 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : Back Toilet No. 2 -
NSR-20.7 Air Quantity : 200 CFM
Static Pressure : 15 mm wg
Motor rating : As Required
Duty : OT Scrub No. 5 -
21 GI Propeller Fans
NSR-21
Supplying, installing, testing and commissioning of direct driven PROPELLER FANS .No. fan shall be complete with permanent split capacitor or shaded
pole motor, mounting plate with light weight type GI impellers with aerofoil contours for high efficiency & low noise & gravity louvers for
weather protection as required. Fan selection arrangement and Electrical
characteristics shall be as follows :
NSR-21.1
Air Quantity : 500 CFM , 3 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.
Power : As Required
Duty : AC plant room at Terrace No. 2 -
22 NSR-22 AXIAL FLOW FANS
Supply, installation, testing and commissioning of ceiling /Floor mounted Tube Axial flow fans with adjustable pitch blade, MS / GI long casing (2mm
thick up to 800 mm dia fan, 3 mm thick from 900 to 1250 mm dia & 4 mm thick above 1300 mm dia) , cast aluminium alloy impeller complete with
TEFC Sq. Cage Induction motor suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C supply with support, mountings, vibration isolators, fire
retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) etc. & of following capacity. The
complete fan along with motor shall be high efficient(IE -3 or EQUIVALENT) with fire rated (class H) suitable for with standing 250 °C temperature rated for
2 hours.Exhaust fan shall be connected using circuit integrity cable. Fan outlet velocity shall be limited to maximum of 16 m/sec. Fan & Fan motor KW
given below are for guideline & actual Dia / KW shall be as per manufacturer selection based on
maximum 16 m/sec outlet velocity.
Axial Fan shall be AMCA certified for Air and Sound performance in accordance to AMCA 210 and AMCA 300. Complete Fan shall be tested and approved by
UL in accordance with "Power Ventilators for Smoke Control Systems" for min 250 °C for 2 hours. Manufacturer shall furnish AMCA Test Certificate for
air & sound performance along with UL fire test certificate (Latest) for No. fan sourced from that particular factory. The noise level of axial fan shall be less
than 80 dB at a distance of 3.0 mt from the fan.
The fan shall be low RPM (less than or equal to 1450 RPM) and capacities shall be as follows :
NSR-22.1 Air Quantity : 13500 CFM
Static Pressure : 30 mm wg
Motor Rating : 4.0 kW (Suggested) or meeting functional requirements
Duty : Lift Well (6/8) Pressurization at Terrace No. 2 -
NSR-22.2 Air Quantity : 16000 CFM
Static Pressure : 30 mm wg
Motor Rating : 5.5 kW (Suggested) or meeting functional requirements
Duty : Lift Well (1/2/3/4/5/7)Pressurization at Terrace No. 6 -
NSR-22.3 Air Quantity : 18000 CFM
Static Pressure : 30 mm wg
Motor Rating : 7.5 kW (Suggested) or meeting functional requirements
Duty : Lift Lobby Pressurization at Terrace No. 4 -
NSR-22.4 Air Quantity : 20000 CFM
Static Pressure : 25 mm wg
Motor Rating : 7.5 kW HP (Suggested) or meeting functional requirements
Duty : Atrium Exhaust at Terrace No. 2 -
NSR-22.5 Air Quantity : 7500 CFM
Static Pressure : 30 mm wg
Motor Rating : 2.2 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 4 -
NSR-22.6 Air Quantity : 7000 CFM
Static Pressure : 30 mm wg
Motor Rating : 2.2 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 4 -
NSR-22.7 Air Quantity : 4000 CFM
Static Pressure : 30 mm wg
Motor Rating : 1.5 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 10 -
NSR-22.8 Air Quantity : 5500 CFM
Static Pressure : 30 mm wg
Motor Rating : 1.5 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 2 -
NSR-22.9 Air Quantity : 3500 CFM
Static Pressure : 30 mm wg
Motor Rating : 1.5 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 3 -
NSR-22.10 Air Quantity : 3000 CFM
Static Pressure : 30 mm wg
Motor Rating : 1.5 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 3 -
NSR-22.11 Air Quantity : 6000 CFM
Static Pressure : 30 mm wg
Motor Rating : 2.2 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 2 -
NSR-22.12 Air Quantity : 8000 CFM
Static Pressure : 30 mm wg
Motor Rating : 2.2 kW(Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 1 -
NSR-22.13 Air Quantity : 8500 CFM
Static Pressure : 30 mm wg
Motor Rating : 3.0 kW (Suggested) or meeting functional requirements
Duty : Corridor Smoke Exhaust No. 1 -
23 NSR-23 Factory Fabricated Double Skin Air Washer
Supply, installation, testing and commissioning of factory fabricated Double Skinned Air-washer unit floor mounted type fabricated out of
extruded aluminum section with 0.6mm pre-plasticized / pre-coated Galvanized steel sheet outside &
0.6 mm plain Galvanized steel sheet inside with blower, blower section and blower motor TEFC (IE-3) type suitable for operation on 415 volts ±
10%, 50 Hz ± 5% AC supply, belt drive package, wet section & tank shall be made of 18 G stainless steel. The Air-washer shall be complete with fill of
depth 200 mm & face velocity across the fill shall be limited to 152 MPM. The Air-washer shall have an efficiency of 90% & shall be complete
with water circulation pump -2 No.(1W+1S), GI B Class interconnecting piping, Aluminum viscous filters. makeup, quickfill and drain connections,
Butterfly/Gate valves for Pumps, make up, drain & quickfill connections of Sump, 2 No. pumps of suitable capacity (1W +1 S), Y strainers and necessary
fittings etc.
Suitable PCC/RCC foundation with plaster, Antivibration arrangement of cushy foot mountings etc.in all respect shall be in contractor's scope.
The Air-washer shall have an efficiency of 90% & shall be complete with water circulation pump GI B Class interconnecting piping & valves
Aluminum viscous filters, fire retardant double canvass connection etc. The airwasher panels shall be insulated with 23mm thick & 36 Kg/m³ density
PU foam. The Airwasher shall conform to specification given in the
tender & shall be of following capacity. Motor Kw is indicative only, actual as per requirement to be included during installation.
NSR-23.1 Duty: Kitchen + Outdoor sitting
Air Qty :10000 CFM
Static Pressure : 50 mm wg
Fan Motor HP :10 HP(Suggested) or as per requirement
Pump Motor HP : 1.5 (Suggested) or as per requirement Set 1 -
NSR-23.2 Duty: Outdoor sitting
Air Qty :6000 CFM
Static Pressure : 50 mm wg
Fan Motor HP :7.5 HP(Suggested) or as per requirement
Pump Motor HP : 1.0 (Suggested) or as per requirement Set 1 -
24 NSR-24 DRY SCRUBBER
Supply, Installation, Testing and Commissioning of Scrubber No. comprising of extract air intake section, electrostatic preci pitation technology,
dry type air cleaner to remove oil, smoke and fumes from exhaust air, as per the Specifications. Electrostatic section shall be made of 16 gauge
galvanised sheet, high bake epoxy powder coated, washable type aluminium mesh filters, stainless steel spiked ionizers to create high voltage DC
field, aluminum collector plates which should be alternatively charged positive and negative with large collecting area with 14" deep cell, to work as
magnet for charged smoke and oil particles. Average efficiency of 90-95% in single pass as per ASHRAE test method. Electrostatic Precipitator should be
able to charge particles from 0.01 micron to 10 microns through solid state power supply. Collector cell should be of permanent type and incorporate slide out
facility for easy removal for cleaning. Power supplies shall be 100% solid state UL Listed, Module of capacity above 3000 CFM shall be equipped with Pulse
width modulating (PWM).The system should be fitted with interlock
switch for safety . The system should allow connection to a fan section to achieve 500 FPM velocity across the air cleaner.
Operating Voltage : 220V, 50 Hz Ionizing
Voltage : 12.5 to 13 KV DC Collector Cell
Voltage : 6 to 6.5 KV DC
Power Consumption : Not more than 50W per cell.
Supplying, installing, testing and commissioning of SISW (Single inlet single width) centrifugal fan as per specification, with statically and dynamically
balanced backward curved blades, galvanized steel housing, maintenance free bearings, belt driven complete with totally enclosed fan cooled squirrel cage
induction motor, centrifugal fan belt drive and vibration isolators. Motor shall be suitable for 415±10% volts, 50 cycles, 3 phase AC supply & meeting
criterion as per ASHRAE standard 90.1-2016 and
high efficiency (IS 12615) . Minimum 20 mm (WC) external static pressure after fan outlet.
NSR-24.1 Duty: Kitchen Exhaust
Capacity: 6500 CFM
Static Pressure : 50 mm wg
Fan Motor HP : 7.5 HP or as per requirement
Pump Motor HP: 3.0 HP or as per requirement Set 1 -
25 NSR-25 UVGI SYSTEM
Supply, installation, testing and commissioning of the UVGI unit to be fitted downstream (supply air side) portion of Chilled Water coil (for Cooling
Coil Treatment & to Improve Indoor Air Quality ) with Reflector, lamp status display, audio-visual lamp failure alarm , lamp lifetime counter, lamp
replacement reminder & SS stand.UVGI System shall be designed with scientifically developed UV sizing software in reference with CFD analysis &
generate a report to prove the UV delivery of designed intensity.UVGI system for disinfection shall utilize high output UV lamp. The parabolic reflector
shall be of semi circle Shape to utilize 100% of UV & it MOC will be Anodized Aluminum. The electrical control system should utilize high frequency
electronic ballasts and provide efficiency of more then 90%. System shall have a Dry Contacts or A 4-20 mA output shall also be provided for BMS
compatibility. Control Power panel with necessary wiring & cabling to UVGI system upto 15 Mtr.length shall be inclusive in the cost.The UVGI System shall
have ETL certification. UVGI system shall be provided for following AHUS for Air capacities as
mentioned below respectively.
NSR-25.1 Ground Floor
NSR-25.1.1 MRI, 1500 CFM,5.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.1.2 CT Scan ,1800 CFM,5.5 TR,125 mm SP,Fan motor of required HP No. 1 -
NSR-25.2 First Floor
NSR-25.2.1 ENDO 1 ,7000 CFM,30.0 TR, 65 mm SP ,Fan motor of required HP No. 1 - NSR-25.2.2 ENDO 2 ,7200 CFM,32.0 TR, 65 mm SP ,Fan motor of required HP No. 1 -
NSR-25.3 Second Floor
NSR-25.3.1 ENDO 1 ,7000 CFM,30.0 TR, 65 mm SP ,Fan motor of required HP No. 1 - NSR-25.3.2 ENDO 2 ,7200 CFM,32.0 TR, 65 mm SP ,Fan motor of required HP No. 1 -
NSR-25.4 Third Floor
NSR-25.4.1 ENDO 1 ,5500 CFM,30.5 TR, 65 mm SP ,Fan motor of required HP No. 1 - NSR-25.4.2 ENDO 2 ,7500 CFM,32.0 TR, 65 mm SP ,Fan motor of required HP No. 1 -
NSR-25.5 Fourth Floor
NSR-25.5.1 Plastic Surgery 1 & 2 ,7000 CFM,35.0 TR, 65 mm SP ,Fan motor of required HP No. 2 -
NSR-25.6 Fifth Floor
NSR-25.6.1 Neurology ICU, 2000 CFM, 8.2 TR, 65 mm SP ,Fan motor of required HP No. 1 - NSR-25.6.2 Endocrnology, 1650 CFM, 5.5 TR ,Fan motor of required HP No. 1 - NSR-25.6.3 Clinical Hematology, 1300 CFM, 4.0 TR ,Fan motor of required HP No. 1 - NSR-25.6.4 Pediatric Surgery, 1100 CFM, 3.5 TR ,Fan motor of required HP No. 1 - NSR-25.6.5 Gastro ICU/Surgerical,3500 CFM, 17.0 TR, Fan motor of required HP No. 1 - NSR-25.6.6 Surgerical Gastology ward/ICU 3300 CFM,12.0 TR ,Fan motor of required HP No. 1 - NSR-25.6.7 Hematology ICU,3000 CFM, 12 TR, Fan motor of required HP No. 1 - NSR-25.6.8 Nephro/Plastic Surgery, 5500 CFM ,17 TR ,Fan motor of required HP No. 1 - NSR-25.6.9 Neurology ICU, 4000 CFM, 15.0 TR, 65 mm SP ,Fan motor of required HP No. 2 -
NSR-25.7 Sixth Floor
NSR-25.7.1 Post OT Room,2000 CFM,10.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.7.2 OT 1 , 3000 CFM,9.5 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.7.3 OT 9 , 3700 CFM,10.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.7.4 Sterile corridor.3500 CFM,17.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.7.5 Post OT, 2300 CFM, 11.0 TR, 65 mm SP ,Fan motor of required HP No. 1 -
NSR-25.8 Seventh Floor
NSR-25.8.1 Wards, 8000 CFM ,40 TR ,Fan motor of required HP No. 1 - NSR-25.8.2 Wards, 8500 CFM ,43 TR ,Fan motor of required HP No. 1 -
NSR-25.9 Terrace Floor
NSR-25.9.1 OT 2 , 2800 CFM,8.5 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.2 OT 3 , 3000 CFM,9.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.3 OT 4 , 3400 CFM,9.5 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.4 OT 5 , 4200 CFM,12.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.5 OT 6 , 4200 CFM,12.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.6 OT 7 , 4000 CFM,12.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.7 OT 8 , 4000 CFM,12.0 TR,125 mm SP,Fan motor of required HP No. 1 - NSR-25.9.8 OT 10 , 3550 CFM,9.5 TR,125 mm SP,Fan motor of required HP No. 1 -
26 Magnehelic Gauges
NSR-26
Supply, installation, testing & commisioning of magnehelic gauges across OT rooms & Critical areas AHU Filters for differential pressure. This includes SS
box to mount these units & neessary tubing & other accessories to get these units functioning (-6 to
+6 mm of WG). It should be complete in all respect.
No.
40
-
27 NSR-27 HI WALL SPLIT UNITS - INVERTER DRIVEN COMPRESSOR
Supply, Installation, testing and commissioning of Air-cooled Hi-wall split air conditioners No. comprising an outdoor unit(s) consisting of inverter
driven compressor, air cooled condenser, condenser fan along with Cooling thermostats etc. with outer casing and indoor fan coil unit consisting of
centrifugal fans, fan motor, DX cooling coil, outer casing, filter, control and power panel with remote etc. entire cabling and wiring from indoor to
outdoor, insulation and with full charge of refrigerant gas and oil, supports, canvas connection etc. complete as per drawings. The indoor and outdoor
units shall be with structural steel supports, angles, rods etc. The quoted price shall also include 24 G soft copper refrigerant piping with 13 mm "O" class
factory backed nitrile rubber with aluminum foil from outdoor unit to indoor unit complete with insulation, refrigerant charging, PVC drain piping with
6mm thick nitrile rubber insulation, supports, clamps, fittings, connections, sleeves, supports, MCB, stabilizer etc. from main panel to the unit. The
refrigerant used shall CFC Free R-410 A. Also, EER should be in compliant with ECBC + Building requirements. Machine shall run on automatic wall
mounted relay that makes 2 No. units works under fault or 12hrs of
timer running operation.
NSR-27.1 1.5 TR Unit No. 32 -
VAV Boxes
28
NSR-28
Supply, installation, testing and commissioning of VARIABLE AIR VOLUME (VAV) BOXES complete with leakage proof damper, differential pressure
sensor, motorized damper, actuator, motorized aluminium construction damper with actuator (UL approved), Glass type Touchscreen thermostat
having humidity sensor, temperature sensor with large display thermostat with all the parameter control, differential pressure sensor,24 Volt power supply
unit for No. VAV box, controller capable of accepting analogue/digital signal from thermostat and output to damper actuator.
NSR-28.1 150 CFM-290 CFM No. 20 -
NSR-28.2 300 CFM-390 CFM No. 13 -
NSR-28.3 400 CFM-490 CFM No. 17 -
NSR-28.4 500 CFM-790 CFM No. 17 -
NSR-28.5 800 CFM-990 CFM No. 24 -
NSR-28.6 1000 CFM-1100 CFM No. 7 -
NSR-28.7 1200 CFM-1500 CFM No. 6 -
NSR-28.8 1600 CFM-2000 CFM No. 4 -
29
NSR-29
Supply, installation, testing and commissioning of INTEGRATOR for VAV boxes, capable of giving industry standard (Modbus / Lon Works / Bacnet)
output (BMS system compatable). Mapping shall be required for monitoring individual room temperature, air flow and damper position for areas
conditioned through VAV boxes.Quoted price shall be inclusive of wiring in GI conduit between integrator and individual VAV Boxes.Glass type
Touchscreen thermostat having humidity sensor, temperature sensor
with large display and wired control port.complete in all respect.
NSR-29.1 FIRST FLOOR, SECOND FLOOR & THIRD FLOOR Set 1 - NSR-29.2 FOURTH FLOOR, FIFTH FLOOR & SIXTH FLOOR Set 1 - NSR-29.3 SEVENTH FLOOR & TERRACE Set 1 -
Total of Sub Head 'A'- Machinery -
Sub Head-'B'- Chilled Water Piping,Fittings & Valves
INSULATED CHILLED /HOTWATER PIPING
30
DSR-
16.2(Modified)
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building & at terrace (with necessary
clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of
minimum 40-55 Kg / cu m density, insulation material shall be resistant to growth of Fungus as per ASTM C 1338 and resistant to growth of Bacteria as
per ASTM E 2180,thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation,with reinforced 7 mil woven glass
fiber covering in and applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required
complete in all respect.
Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as
per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia
and above.
16.2.2 350 mm dia. (32 mm thick insulation) RM 10 - 16.2.3 300 mm dia. (32 mm thick insulation) RM 72 - 16.2.4 250 mm dia. (32 mm thick insulation) RM 147 - 16.2.5 200 mm dia. (32mm thick insulation) RM 193 - 16.2.6 150 mm dia.(32 mm thick insulation) RM 33 - 16.2.7 125 mm dia. (32 mm thick insulation) RM 61 - 16.2.8 100 mm dia.(32 mm thick insulation) RM 585 - 16.2.9 80 mm dia. (32 mm thick insulation) RM 788 - 16.2.10 65 mm dia. (32 mm thick insulation) RM 487 - 16.2.11 50 mm dia. (32 mm thick insulation) RM 794 - 16.2.12 40 mm dia.(32 mm thick insulation) RM 663 - 16.2.13 32 mm dia. (32 mm thick insulation) RM 1540 - 16.2.14 25 mm dia. (19 mm thick insulation) RM 778 - NSR-30 20 mm dia (19 mm thick insulation) RM 636 -
31 INUSLATED VALVE
16.7
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
16.7.1
Butterfly Valve(Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified.
NSR-31.1 300 mm dia Gear Type No. 3 - NSR-31.2 250 mm dia Gear Type No. 5 - 16.7.1.1 200 mm dia Gear Type No. 24 -
16.7.1.2 150 mm dia Lever Type No. 4 - 16.7.1.3 125 mm dia Lever Type No. 12 - 16.7.1.4 100 mm dia Lever Type No. 24 - 16.7.1.5 80 mm dia Lever Type No. 22 - 16.7.1.6 65 mm dia Lever Type No. 30 - 16.7.1.7 50 mm dia Lever Type No. 26 - 16.7.1.8 40 mm dia Lever Type No. 20 -
32 16.7.2 Balancing Valve with built in measuring facility with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
NSR-32 250 mm dia No. 2 -
41.1 NSR-34.1 250 mm dia No. - 16.7.2.1 200 mm dia No. 4 - 16.7.2.3 125 mm dia No. 2 - 16.7.2.4 100 mm dia No. 10 - 16.7.2.5 80 mm dia No. 6 -
33
16.7.3
(Modified)
Non Return Valve with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including
insulation as specified. It shall be of wafer type preferably with flanged ends. It should be tested for required hydrostatic pressure for shell & seat as per OEM &
shall be suitable for maximum working temperature of 80 degree C
(approx.).
16.7.3.1 200 mm dia No. 8 - 16.7.3.3 125 mm dia No. 4 -
34 16.7.4 Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
16.7.4.1 200 mm dia No. 8 - 16.7.4.3 125 mm dia No. 6 - 16.7.4.4 100 mm dia No. 1 - 16.7.4.5 80 mm dia No. 4 - 16.7.4.6 65 mm dia No. 15 - 16.7.4.7 50 mm dia No. 13 - 16.7.4.8 40 mm dia No. 10 - NSR-33 32 mm dia No. 8 -
35 16.8 Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
No. 143
-
36 16.9 Providing & Fixing in position the mercury in glass with industrial type thermometers. No. 118 -
37
NSR-34
Providing and fixing in position the following Ball Valves with Strainer duly insulated as per specifications and drawings.
Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze
/forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating.
NSR-34.1 25 mm dia for FCUs No. 23 - NSR-34.2 20 mm dia for FCUs No. 147 -
38
NSR-35
Providing and fixing in position the following Ball Valves without strainer duly insulated as per specifications and drawings.
Ball valve shall be screwed type brass/bronze lever operated, quarter turn ball valve (screwed type) of full flow with bronze
/forged brass hard chrome plated ball with setting & gland of superior quality of preferably PN 16 rating.
NSR-35.1 25 mm dia for FCUs No. 23 - NSR-35.2 20 mm dia for FCUs No. 147 -
39
NSR-36
Supply, installation, testing and commissioning of TWO WAY MOTORISED CUM AUTOMATIC BALANCING VALVE provided with spring return
function & fitted with modulating actuators in chilled water lines at No. fan coil unit. The actuator shall have required shut off capability of minimum 4
bar rating and should be able to accept 24V power supply. The valves & actuators for FCU’s shall be compatible with Building Automation System.The
actuator shall be controlled by Building Automation System &
should accept a signal of 4–20mA/ 2–10 VDC. The valve shall be suitable for following pipe sizes:
NSR -36.1 25 mm dia pipes for FCUs No. 23 - NSR -36.2 20 mm dia pipes for FCUs No. 147 -
40
16.11.3
Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve (UL Approved actuators) with CI Body, SS Disc, O - ring and
minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC ,and upto 20 mA electric
signal and providing similar transduced feedback output to control system ,BMS
compatable as required
16.11.3.4 200 mm dia No. 4 -
41
NSR-37
Providing, fixing, testing & commissioning of resilient rubber lined double arch vibration eliminators suitable for raw water up to 45 deg. C temperature
to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.(PN 16 rating)
NSR-37.1 200 mm dia No. 24 - NSR-37.2 125 mm dia No. 8 -
42 NSR-38 Providing and fixing Auto air vents (Brass MOC) of following size
NSR-38.1 20 mm dia No. 10 -
43 NSR-39 Providing and fixing in position the following water flow switch as per specifications:
NSR-39.1 300 mm dia No. 2 -
44 Drain Pipings
NSR-40
Providing and fixing in position the following GI medium class cut to required length and installed with screw joints including the necessary fittings
(bends, tees, unions, sockets etc) duly insulated with 6 mm thickaluminium cladded nitrile rubber tublar insulation as per specifications.
NSR-40.1 20 mm dia RM 250 - NSR-40.2 25 mm dia RM 300 - NSR-40.3 32 mm dia RM 100 - NSR-40.4 40 mm dia RM 80 -
Total of Sub Head-'B'- Chilled Water Piping,Fittings & Valves -
Sub Head 'C' - Air Distribution
45
16.12.1
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete
with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following
sheet thickness complete as required.
16.12.1.1 0.63 MM (24 gauge) Galvanized Sheet Steel Ducting Sqmt 8592 - 16.12.1.2 0.80 MM (22 gauge) Galvanized Sheet Steel Ducting Sqmt 157 - 16.12.1.3 1.0 MM (20 gauge) Galvanized Sheet Steel Ducting Sqmt 30 - 16.12.1.4 1.25 MM (18 gauge) Galvanized Sheet Steel Ducting Sqmt 192 -
46
NSR-41
Supply, fabrication, installation and testing of Aluminium ducts for OT's in accordance with the approved shop floor drawing complete with all
accessories, bends, fittings, specials, chutes, vanes, necessary supports etc. as per specification.
NSR-41.1 20 gauge Aluminium Ducting Sqmt 903 -
NSR-42 Supply, fabrication, installation and testing of Kitchen duct with wire wraping complete in all respects, on kitchen exhaust ducts to provide minimum 1 Hr fire rating.
47 NSR-42.1 16 gauge MS duct work welded construction. Duct shall have fire rated coating compound. Fire rated coating compound used for construction of fire rated
ductwork shall be protected with minimum 0.7mm to 1mm nominal thickness tested to properties as per the requirements of BS 476: 6 & amp; 7,
including non-combustibility Class O and fire propagation - Class 1 surface
spread of flame & materials in accordance with building regulations.
Sqmt
145
-
48
16.13 (Modified)
Supply, installation, testing and commissioning of opposed blade aluminium volume control dampers with black mat finish in supply air duct
collars,Damper shall be with 16G GSS body and blades shall be with aluminium airfoil construction. complete
with neoprene rubber gaskets,nuts, bolts, screws linkages, flanges etc. as per approved shop drawings and specifications.
Sqmt
23.1
-
49
NSR-43
Supply, fabrication, installation and testing the non-porous flexible connections constructed of fire resistance flexible, double
canvas connection with resistoflex material as per the approved shop drawings.
Sqmt
352.2
-
50 16.15 Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Sqmt 18.1
-
51 16.16 Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers as per specifications.
Sqmt 18.1
-
52
16.17 (Modified)
Supplying, fixing testing commissioning of supply air diffusers (Flat face type) of powder coated & made from extruded
aluminium section with aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with removable
central core and concealed key operation for volume control damper.Complete as required.
Sqmt
231
-
53
16.18 (Modified)
Supplying, fixing testing commissioning of return air diffusers (Flat face type) of powder coated & made from extruded
aluminium section without aluminium volume control dampers with anti smudge ring.All extruded aluminium diffusers shall be provided with
removable central core..Complete as required.
Sqmt
231
-
54
NSR-44
Supply, installation, testing & commissioning of thermal insulated flexible duct.Duct should be UL 181 CLASS I AIR DUCT LISTED AND
LABELLED WITH NFPA 90A & 90B with double lamination of tough polyester which encapsulates steel helix wire forms the air tight inner core ,
double layer core wrapped in a multiple thickness of fiberglass wool with R Value 4.2 , Green guard certification of fiberglass wool must. , Reinforced
and sheathed in a rugged and durable tridirectionally reinforced matlized polyester jacket.Strapping the flexible duct connections with flexible duct
strap ties following sizes duly supported at
regular interval as per site requirement etc. complete as required as per specifications.
NSR-44.1 200mm dia Rmt 50 -
55 16.20 (Modified) FIRE DAMPERS
Supplying, Fixing,testing and commissioning of fire dampers of at least 1½ hour fire rating as per UL555/1995 tested by CBRI,in supply air duct/main branch
and return air path as and where required of required sizes, i/c control wiring,the damper shall be motorized and spring return so as to close the damper in
the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not
externally mounted. The damper shall also be closed in the event of fire signal.Damper blades shall be airfoil shaped (equivalent to 2.3mm thickness
strength) roll formed using 0.8mm thick single piece of galvanized sheet.Fire damper shall be equipped with a electric limit switch to indicate open and
close position of the damper blades.The dampers shall meet the requirements of NFPA90A, 92A and 92B and shall be classified as Leakage Class 2
smoke damper in accordance with latest version of UL555S. No. fire/smoke damper shall be AMCA licensed and bear the AMCA seal for air Performance.
Pressure drop shall not exceed 7.5Pa when tested at 300m/min face
velocity on 600x600mm size damper. Actuator shall be UL listed complete as required and as per specifications.
`
16.20.1 Fire damper(150 mm deep) Sqmt 30.0 - 16.20.2 Control Panel with actuator(10Nm Torque) & Wiring No. 48 -
56 NSR-45 DOOR TRANSFER GRILLE
Supply, installation ,testing and balancing of extruded aluminium powder coated door transfer grilles.
NSR-45.1 600 X 150 MM Sqmt 9.0 -
57 NSR-46 Supply, installation and balancing of extruded aluminium powder coated air louvers complete with aluminium wire mesh birdscreen as per specifications.
NSR-46.1 Fresh air louvers (with collar dampers) Sqmt 11 - NSR-46.2 Exhaust air louvers (without volume control dampers) Sqmt 4 -
58
NSR-47 Supply, installation, testing and balancing of Powder Coated Extruded Aluminium Linear supply Air Multi Slot Diffuser complete
with air pattern controllers & Hit & Miss volume control damper with acoustically line 22 G G.I plenum for Supply air ,duly insulated with 9 mm
Thick Cross Linked Polyethlene Foam as per specifications and approved drawings.
Sqmt
1
-
59 NSR-48 Supply, installation, testing and commissioning of Powder Coated Extruded Aluminium Multi Slot return Air Diffuser with air
pattern controller as per specification and approved drawings. Sqmt 1
-
60
NSR-49 Supply, installation, testing and commissioning of Eccentric square-to-round transitions duct piece to connect rectangular duct to round duct,The square
connector has a flange frame in the standard version,The round connector is male in the standard version.
Lot
1
-
61 NSR-50 Supply, installation, testing and commissioning of pressure relief damper to be installed in Lift Lobbies,Staircase & OT rooms
with pre set pressure rating Sqmt 9
-
DUCT THERMAL & ACOUSTIC INSULATION
62
NSR-51 Supplying and fixing of External Thermal duct insulation with 2 layer protective coating over closed cell Nitrile rubber (Class “O”) insulation on ducting
after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape
insulation.All air ducts be it supply air in the return air path, both the supply and return air above the false ceiling of the conditioned space, in the
conditioned space or in the non conditioned area inside the building and outside the building, shall be coated with STARBOND 30-36 / FOSTER 30-36 in
conjunction with facotry laminated 7 mil woven fiber glass cloth on insulation finally finished with 2 layers of STARBOND 30-36 to provide complete seal
against
air and moisture complete as per specifications and as required.
Insulation material for Duct shall be anti-microbial closed cell Elastomeric Nitrile Rubber. Thermal conductivity of the insulation material shall not exceed
0.038 W/moK or 0.212 BTU / (Hr-ft2-oF/inch) at an average temperature of 30oC. Density of the nitrile rubber shall be 40-60 Kg/m3. The product
shall have temperature range of –40 oC to 105oC. The insulation material shall be fire rated for Class 0 as per BS 476 Part 6 : 1989 for fire propagation test
and for Class 1 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be not less than 0.024 perm inch (2.48 x 10-14
Kg/m.s.Pa i.e. µ=7000: Water vapour diffusion resistance).
Thermal conductivity of the material shall not be affected by ageing, as per DIN 52616 The smoke density of the material as per AS-1530.3 shall not exceed 1.The material shall be antimicrobial as per ISO 22196, C1338 and ASTM G21-96.
There shall be no growth of fungus and mold.
NSR-51.1 19 mm thick (In Condition Space) with protective coating Sqmt 8592 - NSR-51.2 25 mm thick (In Non - Condition Space) with protective coating Sqmt 300 -
NSR-52 Supply, installation testing and commissioning of duct acoustic insulation Inside the Duct with Engineered Nitrile Rubber open cell foam with Density 140
- 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test or 10,000 fpm air velocity as per ASTM C 1071-05 to be applied using
manufacturer's recommended Rubber based Adhesive in a blend of solvents.
NSR-52.1 10 mm thick duct acoustic lining Sqmt 352.2 -
63
16.22 Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed
in 610mm x 610 mm frame work made of
25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm
perforated aluminium sheet etc. complete as
required and as per specifications.
Sqmt
1530
-
Total of Sub Head-'C'- Air Distribution -
Sub Head 'D' - ELECTRICAL WORKS FOR HVAC
64 NSR-53 HVAC Plant Room Panel (Panel Must conform to IEC 61439 part 1 & 2)
Design, fabrication, assembling, wiring, supply, installation, testing & commissioning of motor control centre, which
shall be fabricated out of 2 mm thick CRCA sheet steel in form in 3b formation with reinforcement of suitable size angle
iron, channel, T section iron & / flat wherever necessary. Cable gland plates shall be provided on top as well as at
bottom of teh panels. Panels shall be treated with anti corrosive process before painting as per specifications with 2
caots of red oxide primer & final approved shade of powder coated paint. 2 No. earthing terminals shall be provided for
3 phase, 415 V, 4 wire, 50 Hz supply systems. Liftinmg hooks shall also be provided in case of large panels.Approval
shall be taken for No. panel before fabrication. Cadmium plated hardware shall be used in fabrication of Panels.
As the panel is to kept at Terrace, it should have outdoor protection.
INCOMER FROM MAIN LT PANEL
3 No. of 1000 A 4P EDO Type ACB (50 KA) with microprocessor based release.
METERING & INDICATION
3 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's- It should be BMS compatible.
3 Sets - 0-500 V, 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
3 Sets Indicating LED lamps for ACB ON/OFF/ TRIP with protective SP MCB's,
3 Sets Indicating LED lamps R, Y, B Phase with protective SP MCB's,
3 Sets of CTs of the ratio 1000/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
3 Sets of 1250 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
BUSCOUPLER
2 No. of 1000 A, 4P ACB EDO , 50 kA Breaking Capacity
2 Set of Breaker ON-OFF-TRIP, Spring charged indication Lamps as required.
OUTGOINGS-BUS SECTION-1
2 No. 630A 4P MCCB , 36 kA breaking capacity
3 No. 80A 4P MCCB ,25 kA breaking capacity & 3 No. 25 H.P star delta starter
1 No. 63A 4P MCCB ,25 kA breaking capacity & 1 No. 10 H.P star delta starter
1 No. 40 A 4P MCB, ,10 kA breaking capacity, C curve with 1 No. 5 H.P DOL starter
2 No. 250 A 4P MCCB + 1 No. 100 A TPN MCCB with 36 kA breaking capacity
OUTGOINGS-BUS SECTION-2
2 No. 630A 4P MCCB 36 kA breaking capacity
7 No. 80A 4P MCCB ,25 kA breaking capacity & 7 No. 25 H.P star delta starter
2 No. 63A 4P MCCB ,25 kA breaking capacity & 2 No. 10 H. P star delta starter
2 No. 40 A 4P MCB, ,10 kA breaking capacity, C curve with 2 No. 5 H.P DOL starter
OUTGOINGS-BUS SECTION-3
1 No. 630A 4P MCCB , 36 kA breaking capacity
3 No. 80A 4P MCCB ,25 kA breaking capacity & 3 No. 25 H.P star delta starter
2 No. 63A 4P MCCB ,25 kA breaking capacity & 2 No. 10 H.P star delta starter
2 No. 40 A 4P MCB, ,10 kA breaking capacity, C curve with 2 No. 5 H.P DOL starter
1 No. 250 A 4P MCCB + 1 No. 80 A TPN MCCB with 36 kA breaking capacity
All Outgoing Feeders shall be provided with ON, OFF, TRIP Indication Lamps (LED Type), suitable range Ammeters with
Selector Switch.
All DOL & Star Delta Starters shall be provided with required size contactors, timer, wiring etc.
Supplying,Receiving, fixing, testing & commissioning of HVAC Plant Room Panel as described above
Set
1
-
65 NSR-54 CONTROL PANEL IN AHU ROOM (WITH DOL /SD STARTER)
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall
mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in No. panel shall be provided by the electrical
contractor.
All internal wiring and copper earthing of air handling unit motors from the panel shall be included.
All outgoing shall be provided with Stop / Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System.
The panel shall include the following components and accessories.
MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.
DOL / SD starter as per HP ratings
Terminal block for power distribution.
Contractor, over load relay with built in single phasing protection.
Phase indicating lights and indicating light for ON status.
96 X 96 sqmm Digital Voltmeter and digital ammeter with selector switches.
Time delay relay for delayed automatic restart of air handling unit motor.
Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application)
For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. AHU panel to facilitate override of the automatic operation.
All starters shall be provided with suitable potential free contact for connections to the Building Automation System.
3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare.
220 / 24 V Transformer (as required by application)
The number of AHU control panels shall be as follows:
NSR-54.1 16 Amp MCCB 1.0HP DOL Starter No. 7 - NSR-54.2 25 Amp MCCB 1.5HP DOL Starter No. 4 - NSR-54.3 25 Amp MCCB 2.0HP DOL Starter No. 9 - NSR-54.4 25 Amp MCCB 3.0HP DOL Starter No. 14 - NSR-54.5 25 Amp MCCB 5.0HP DOL Starter No. 21 - NSR-54.6 40 Amp MCCB 7.5HP Star Delta Starter No. 2 - NSR-54.7 40 Amp MCCB 10.0HP Star Delta Starter No. 2 -
66 NSR-55 CONTROL PANELS FOR AXIAL FANS, AIRWASHER & SCRUBBER
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels,
including anchoring into the wall, wiring terminating into MCCB and copper earthing, in No. panel shall be provided by the electrical contractor.
All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System.
All wiring and copper earthing of motors from the panel shall be included.
The panel shall include the following components & accessories.
MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.
DOL / SD starter as per HP gratings given.
Terminal block for power distribution as required.
Contractor, over load relay with built in single phasing protection.
Phase indicating lights and indicating light for `ON’ status.
96 X 96 sqmm voltmeter and digital ammeter.
Time delay relay for delayed automatic restart of motor.
Wiring for micro switch for stopping the fan when fire damper closes (in required by application).
For on/off/remote and local operation, 3 pole single throw switch shall be provided in No. panel to facilitate override of the automatic operation.
All starters shall be provided with suitable potential free contract for connections to the Building Automation System.
All starters for Air washer & Scrubber pumps (as required) with cabling,wiring & earthing shall be included in their control panel for fans.
220 / 24 V Transformer (as required by application)
The number of control panels shall be as follows.
NSR-55.1 25 amps MCCB, 2HP with DOL Starter No. 18 - NSR-55.2 25 amps MCCB, 3HP with DOL Starter No. 11 - NSR-55.3 25 amps MCCB,5HP with DOL Starter No. 3 - NSR-55.4 40 amps MCCB, 7.5HP with Star DeltaStarter No. 8 - NSR-55.5 32 amps MCCB, 10HP with Star-Delta Starter No. 6 -
67 NSR-56 AHU Panel-1 (Ground Floor)
INCOMER
1 No. 100 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's.
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 100/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
160A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
2 No. 40A 4P MCB ( 1 Spare)
4 No. 25A 4P MCB
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-1 (Ground Floor) as described above Set 1 -
68 NSR-57 AHU Panel-2 (First Floor)
INCOMER
1 No. 100 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 100/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
160A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
5 No. 40A 4P MCB ( 1 Spare)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-2 (First Floor) as described above Set 1 -
69 NSR-58 AHU Panel-3 (Second Floor)
INCOMER
1 No. 100 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 100/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
160A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
4 No. 40A 4P MCB ( 1 Spare)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-3 (Second Floor) as described above Set 1 -
70 NSR-59 AHU Panel-4 (Third Floor)
INCOMER
1 No. 100 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 100/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
160A 4P Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
4 No. 40A 4P MCB ( 1 Spare)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-4 (Third Floor) as described above Set 1 -
71 NSR-60 AHU Panel-5 (Fourth Floor)
INCOMER
1 No. 80 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 80/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
100A 4P Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
4 No. 40A 4P MCB ( 1 Spare)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-5 (Fourth Floor) as described above Set 1 -
72 NSR-61 AHU Panel-6 (Fifth Floor)
INCOMER
1 No. 160 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 80/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
100A 4P Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
3 No. 40A 4P MCB ( 1 Spare)
8 No. 25A 4P MCB
Supplying, Receiving, fixing, testing & commissioning of AHU Panel-6 (Sixth Floor) as described abobe Set 1 -
73 NSR-62 AHU Panel-7 (Sixth Floor)
INCOMER
1 No. 160 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
200A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
3 No. 40A 4P MCB ( 1 Spare)
3 No. 32A 4P MCB
4 No. 25A 4P MCB
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-7 (Sixth Floor) as described above Set 1 -
74 NSR-63 AHU Panel-8 (Seventh Floor)
INCOMER
1 No. 80 A FP MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for MCCB On/Off with protective SP MCB's.
1 Set of CTs of the ratio 80/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
160A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
4 No. 40A 4P MCB ( 1 Spare)
1 No. 32A 4P MCB
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-8 (Seventh Floor) as described above Set 1 -
75 NSR-64 AHU Panel-9 (Terrace Floor) Outdoor Type-IP 65
INCOMER
1 No. of 160 A 4P Aoto Transfer Switch (ATS)
METERING & INDICATION
1 Set - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT's
1 Set - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
1Set of indicating LED lamps for On/Off with protective SP MCB's.
1 Set of CTs of the ratio 160/5A with class 0.5 Accuracy for Metering, burden 15 VA
BUSBAR
200A TPN Aluminium Bar with colour coded PVC Sleeves
OUTGOINGS
10 No. 32A 4P MCB ( 2 Spare)
Supplying,Receiving, fixing, testing & commissioning of AHU Panel-9 (Terrace Floor) Outdoor Type-IP 65 as described
above Set 1
-
Total of Sub-Head - V carried to summary sheet
76 NSR-65
SUB HEAD-VII : LT CABLES & CABLE TRAY
Laying and fixing of one number XLPE insulated and PVC
sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.
NSR-65.1 Upto 35 sq. mm (clamped with 1mm thick saddle) Metre 300 - NSR-65.2 Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) Metre 100 - NSR-65.3 Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) Metre 350 -
S/ F powder coated of approved shade GI Cable Trays
77 NSR-66 Supplying and installing following size of perforated painted with powder coating GI cable trays with perforation not more than 17.5%, in convenient
sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
NSR-66.1 100 mm width X 50 mm depth X 1.6 mm thickness Metre 100 - NSR-66.2 150 mm width X 50 mm depth X 1.6 mm thickness Metre 200 - NSR-66.3 300 mm width X 50 mm depth X 1.6 mm thickness Metre 50 - NSR-66.4 600 mm width X 50 mm depth X 2.0 mm thickness Metre 25 -
78 NSR-67 S/ F powder coated of approved shade GI Cable Tray Bends
Supplying and installing following size of perforated painted with powder coating GI cable trays bends with perforation not more than 17.5%,, joined
with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
NSR-67.1 100 mm width X 50 mm depth X 1.6 mm thickness No. 18 - NSR-67.2 150 mm width X 50 mm depth X 1.6 mm thickness No. 16 - NSR-67.3 300 mm width X 50 mm depth X 1.6 mm thickness No. 10 - NSR-67.4 600 mm width X 50 mm depth X 2.0 mm thickness No. 8 -
S/ F powder coated of approved shade GI Cable Tray Tee's
79 NSR-68 Supplying and installing following size of perforated painted with powder coating GI cable trays Tee with perforation not more than 17.5%, joined with
connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
NSR-68.1 100 mm width X 50 mm depth X 1.6 mm thickness No. 2 - NSR-68.2 150 mm width X 50 mm depth X 1.6 mm thickness No. 1 - NSR-68.3 300 mm width X 50 mm depth X 1.6 mm thickness No. 1 - NSR-68.4 600 mm width X 50 mm depth X 2.0 mm thickness No. 1 -
80 NSR-69 Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed / XLPE
aluminium conductor cable of 1.1kV grade as required.
NSR-69.1 3 X 16 sq. mm (25 mm) No. 45 - NSR-69.2 3 X 25 sq. mm (25 mm) No. 60 - NSR-69.3 3½ X 150 sq. mm (50mm) No. 54 - NSR-69.4 3½ X 300 sq. mm (70mm) No. 76 - NSR-69.5 4 X 10 sq. mm (25mm) No. 120 - NSR-69.6 4 X 6sq. mm (20mm) No. 220 -
81 NSR-70 Supply of LT cable
Supply, following sizes of PVC sheathed XLPE insulated Aluminium conductor/copper conductor power/ multicore control armoured cable of 1.1
KV grade.
NSR-70.1 3 ½ C - 300 sq mm Aluminium Metre 105 - NSR-70.2 3 ½ C - 150 sq mm Aluminium Metre 85 - NSR-70.3 3C- 25 sq mm Aluminium Metre 95 - NSR-70.4 3C- 16 sq mm Aluminium Metre 200 - NSR-70.5 4C- 10 sq mm Aluminium Metre 236 - NSR-70.6 4C- 6 sq mm Aluminium Metre 270 -
Total of Sub-Head - "HVAC Electrical to summary sheet
-
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BOQ: BUILDING MANAGEMENT SYSTEM
Sl.No.
DSR
2018/N
SR
Description
Unit
Qty
Rate (In Rs.)
Amount (In Rs.)
SUBHEAD I (A)- BUILDING MANAGEMENT SYSTEM
1.00 NSR Software and Operator Workstation
1.01
NSR
Supply, installation, testing and commissioning of core i7-4790k or Xeon E5-1650 v3 processor, Memory of 32 GB, Hard disk size (1TB)
Professional/Enterprise SSD with SATA or SAS), Giga speed Network card with 2 GB Graphic card of Resolution 2.560 x 1600 with
Onboard Intel 4600 HD Windows 10, 64 Bit Edition or Windows Server 2008 R2 and original anti virus software.It should be
complete with keyboard, mouse & pre loaded windows 10 operating system.
No.
1
-
1.02 NSR Supply, installation, testing and commissioning of 32 Inch HD Color LED Monitor. No. 1
-
1.03 NSR Supply, installation, testing and commissioning of Laser jet Printer (A4 size, Colour) No. 1
-
1.04
NSR
Supply, installation, testing and commissioning of Layer 2/3 managed switch with 16 or 24 ports (RJ-45) port. The switch shall have 2 RSTP
enabled ports to communicate with other switches to built a ring topology network on CAT6 A cable. The switch shall have 1 GB port to
communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules, rack mountable, SMPS power
supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment ,Patch panel, Patch Cord, Etc) complete as per
specifications and as required for BMS DDC Panel Networking. The switch to switch distance shall not exceed beyond 80 meters. Vendor to
decide the quantity of network switches based on their network design.
Lot
1
-
2.00 NSR BUILDING MANAGEMENT SYSTEM WEB-BASED SERVER SOFTWARE
2.01
NSR
Supply, Installation, Testing & Commissioning of software for Building Management Software with features like 3D vector dynamic
graphics with Autocad import of plan with Zoom In & Zoom Out facility, Graphic Builder, Plant Viewer, Trend Viewer, Object Viewer,
Report Viewer, Alarm router, Log Viewer. The Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft
Internet Explorer, Netscape Navigator, etc. The software shall be capable of integartion third-party systems and should supports latest IP
technology (IP V4/V6). The Management Stations shall match the BACnet Profile B-AWS (Advanced workstation) as per the BTL Listing.
The Web based software shall include 1 Client License for remote viewing. The same includes the necessary dongles as required for each of
the workstation. Sms/Email feature for accessing critical alarms on mobile phone & Mobile App and Web Service sessions. The Vendor
shall include cost of GSM Module in the quoted price.
Number of IO points shall be considered as per the IO summary considering 15% spares.
Lot
1
-
2.02
NSR
Supply, Installation, Testing & Commissioning of High-quality CAPACTIVE touch 7.0'' panels for technical on-site operation of plants as
well as room operation. The Touch Panel shall have integrated web server and a BACnet/ IP web interface to connect a HTML5 browser
to a device on the network. Generic operation and monitoring of plant functions (alarms, schedulers, calendars, set point changes,
display of actual values, etc.)
No.
1
-
3 NSR PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED/BTL certified.
Supply, Installation, Testing & Commissioning of True IP Based Standalone 32 Bit Intelligent, BTL Listed & UL certified interoperable DDC
as per the specification. Each DDC Controller shall have inbuilt IP port & shall directly connect to the Network switches. No Supervisory
Controller/Router shall be acceptable for IP conversion. The DDC shall be Programmable and Application specific with Real Time
clock.The Controller shall have minimum 18 onboard points and can be expandable upto max of 52 points. The DDC must support trending
& scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend
documentation during communication failure.
The above shall be housed in IP 55 vandal proof, lockable & secure MS Cabinets to be supplied along with all
necessary switchgear protections as required. Number of controllers shall have spare capacity of 15% for future expansion.
A HVAC & Ventilation system
3.01 NSR DDC for Chilled Plant Manager includes Chiller, Primary, Secondary,Hot Water Pumps. Lot 1 -
3.02 NSR DDC for Air Handling Units/CSU (Max 1 AHU per DDC) Nos 52 -
3.03 NSR DDC for FCU (Max 2 FCU per DDC) Nos 85 -
3.04 NSR DDC for Toilet Exhaust Fans (52)/ Axial & Smoke (45)(Max 4 Fan per DDC) Nos 27 -
3.05 NSR DDC for Air Washer & Scrubber Units (3) Lot 2 -
B
Electrical System
3.06 NSR DDC for DG Set/ Transformer and LT Panel Lot 1
-
3.07 NSR DDC for Lifts Lot 1
-
C
Plumbing System
3.08 NSR DDC for Fire Fighting System Lot 1
-
3.09 NSR DDC for Sump and Water Pumps Lot 1
-
3.10 NSR DDC for Water Tank Lot 1
-
4 NSR SYSTEM INTEGRATION UNITS for 3rd party integartions - UL listed Controllers & BTL label
Supply, Installation, Testing & Commissioning of True IP Based System Integration unit consisting of microprocessor based
controller units BTL & UL Listed for third party integration. The same should support operations/ monitoring via portable operator
terminal. .The controller shall be Native BACnet type with communication via BACnet/LonTalk, Integration platforms and system
controllers for third-party devices and systems via KNX, Modbus, M-Bus and other protocols into the automation level via BACnet. The
same shall Support operation via local or network-compatible operator units. It should store trend logs and event buffer for a typical
duration of up to 30 Days. All the Integrators shall be seperate.
Chillers Integration on Modbus Protocol- 30 Points per Chiller
VFDs Integration of Secondary Pumps, Hot Water Pumps on Modbus Protocol-10 points per VFD. AHUs VFD Integration
on Modbus RTU with RS 485 Communication Port -10 points per VFD. Energy Meters to be on Modbus RTU with RS 485
Communication Port -10 points per meter.
Lift Integration on Modbus Protocol- 15 points /Lift.
Lot
1
-
5 NSR Field instruments
Supplying, installing, testing and commissioning of the following sensors / transducers / transmitters.
5.01 NSR Supply, Installation, Testing & Commissioning of Immersion temperature sensor 100 mm Pt1000 with Brass Thermowell.
No. 102
-
5.02
NSR
Supply, Installation, Testing & Commissioning of Outside air temperature + humidity sensors for measuring outside air temperature. It
should be provided with sun sheild and rain protection.
No.
1
-
5.03 NSR Supply, Installation, Testing & Commissioning of Differential Pressure Switch Water for pumps No. 24 -
5.04 NSR Supply, Installation, Testing & Commissioning of Water Flow Switch No. 1 -
5.05 NSR Supply, Installation, Testing & Commissioning of Duct Temperature & Humidity Sensor for AHU No. 102 -
5.06 NSR Supply, Installation, Testing & Commissioning of Differential pressure switch for Blower Status (Pa Range 50…300 Pa)
No. 217
-
5.07 NSR Supply, Installation, Testing & Commissioning of Ultrasonic Water Flow Meter- Dia. Size. 350 mm No. 1
-
5.08 NSR Supply, Installation, Testing & Commissioning of PH Analyser No. 1
-
5.09 NSR Supply, Installation, Testing & Commissioning of TDS Analyser No. 1
-
5.10 NSR Supply, Installation, Testing & Commissioning of Water Differential Pressure Sensor for Liquids (0-----10 V) No. 1
-
5.11 NSR Supply, Installation, Testing & Commissioning of Level Switch for sump No. 36
-
5.12 NSR Supply, Installation, Testing & Commissioning of Flameproof Level Transmitter No. 4
-
5.13 NSR Supply, Installation, Testing & Commissioning of Bi Level Switch water tanks No. 21
-
5.14 NSR Supply, Installation, Testing & Commissioning of Pressure sensor for lift lobby/lift well/staircase & OT areas No. 23
-
5.15 NSR Supply, Installation, Testing & Commissioning of CO2 sensor No. 51
-
6 NSR Cabling and Conduiting
6.01 NSR Supplying, laying, termination, testing and commissioning of signal cables. (2 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable.
Rmt 11500
-
6.02 NSR Supplying, laying, termination, testing and commissioning of signal cables. (4 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable.
Rmt 2500
-
6.03 NSR Supplying, laying, termination, testing and commissioning of 3 Core 1.5 Sqmm, unarmoured ATC conductor multistranded, FRLS cable for Powering DDC , Actuators.
Rmt 2000
-
6.04 NSR Supplying, laying, termination, testing & commissioning of CAT 6A unarmoured Cables with required accessories like RJ45 connector etc.
Rmt 2000
-
6.05 NSR Supply, Installation, Testing & Commissioning of MS Conduit 25 mm for Signal & Communication Cable Rmt 9300 -
6.06 NSR Supply, Installation, Testing & Commissioning of GI Flexible Rmt 1500 -
6.07 NSR Supplying, installing, testing and commissioning of 2 mm thick GI perforated cable trays of the following sizes complete with angle iron supports/hanging arrangement etc
a NSR 100 x 50 Rmt 500 -
b NSR 200 x 50 Rmt 500 -
TOTAL OF SUBHEAD I (A)- BMS
-
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
Sl.No.
DSR
2018/NSR
ITEM DESCRIPTION
Unit
Quantity
Rate (in RS.)
Amount (in RS.)
SUBHEAD-I(A):SOLAR HOT WATER GENRATION & HEAT PUMPS
SOLAR HYBRID HOT WATER SYSTEM
Supply, Installation, Testing & Commissioning of Solar Hybrid system (Combination of Solar and Heat Pump) with reference to the following specifications. The
quoted rates shall be inclusive of solar collectors, Collector frame and support as required, heat pumps, with anti-vibration foundations pad, circulation pumps,
Storage Tanks, Solar and heat pump controller with necessary plumbing, including valves,fittings, bends, sockets, safety devises, insulation,etc. with necessary
control cabling, cable trays, conduiting, earthing, termination glands etc. The solar tank having 9 x 3 = 27 kw Heater fitted for imergency heating of water. complete in
all respect as shown and mentioned in the specifications & schematic drawings.
1 SOLAR CIRCUIT
1.1
NSR
Solar Flat plate Collector:- Supply, Installation, Testing & Commissioning of Solar flat plate collector 0f size 2025mm x 1025mm x 95 mm, or as per OEM
Standards. Material :- Aluminium section, thickness 1.4 mm , bottom sheet 24 swg, insulation material Rockwool 50 mm bottom 25 mm side , thermal conductivity 0.681
mw/cm2degc. Absorber details :- material copper, area 1.9 sqmtr. coated with suitable material , solar absortivty 96%, emissivity 16% (approx) . Riser or header tube :
Material - copper, dia header 25 mm, dia riser -
12.5 mm , nos of Risers- 9 nos. Specing of riser- 110mm , flanged material brass , flanged dia 42mm, working pressure:-3 kg/sqcm , Glazing , , solar trastivity >83%, Nos of
fins -9. finishing powder caoted.Powder coated steel back sheet, confirming to EN12975-2 standards, with Solar Key Mark and ,with all necessary accessories, fittings,
valves , bends, supporting arrangements etc.complete in all respect as per specifications & drawings. weight 38kg/pc( dry).
Nos.
150
-
1.2
NSR
Solar Pump Station :-
Supply, Installation, Testing & Commissioning of standard solar circulation pump with digital differntial temperature and programable auto solar controller, complete
with all necessary accessories, fittings, valves , bends, control cabling etc.complete in all respect, as per specifications & drawings.
vertical inline type centrifugal pump as mentioned above with SS-304 casing, SS-304 /Brass impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900
rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge with
isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be provided
with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual
operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel
common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including
making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of
cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of E-I-C. Flow : 1.5 m3/h
Head : 30 mtrs
(Pump Qty:- 1 working +1 stand by Per set)
Set
3
-
1.3
NSR
Closed Expansion Vessel :-
Supply, Installation, Testing & Commissioning of Closed loop, diapharagm type, Metalic construction hot water expansion vessel for Solar Circuit, complete with all
necessary accessories, fittings etc.complete in all respect as per specifications & drawings. (Capacity - 24 ltrs)
Nos.
3
-
2
NSR
HEAT PUMP CIRCULATION PUMP : Supply, Installation, Testing & Commissioning of Supplying, installing, testing and commissioning of
vertical inline type centrifugal pump as mentioned above with SS-304 casing, SS-304 /Brass impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50
Hz, 2900 rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge
with isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be
provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual
operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel
common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including
making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of
cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of E-I-C. Heat Pump Circulation Pumps , for circulation of Hot water between Heat Pump &
Storage Tanks complete with timer/temparature sensing controller,all necessary accessories, fittings, valves, gauges, control cabling, Power Cabling, earthing,Vibration
Isolation Pads etc. complete in all respect as per specifications & drawings.
Pump Capacity:-13.0 M3/Hr Head :-2
bar
Nos.
3
-
2.1
NSR
RETURN CIRCULATION PUMP : Supply, Installation, Testing & Commissioning of Return circulation pump capacity ; 35m3/h, head - 25 mtr (1 working + 1
stand by)
vertical inline type centrifugal pump as mentioned above with SS-304 casing, SS-304 /Brass impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900
rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge with
isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be provided
with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual
operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel
common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including
making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of
cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of E-I-C.
Set
1
-
3
NSR
PLUMBING WORK (Pipe line , valves and fittings)Supply, Installation, Testing & Commissioning of all hot water pipes of required diameter of ERW heavy class
GI pipes of requied thickness and density confirming to IS 1239 complete with all necessary fittings including all types of valves, Pressure gauge, Thermometer,
pressure switch, Air vent, Sensor, safety valves, strainers, Tees, elbows, reducers, unions, rubber gaskets etc. along with rockwool insulation with 100 kg/cum density, Al
cladding of 24 G thickness, GI fanges etc. complete in all respect & as per directions of E-I.C.
Lot
1
-
4
NSR
ELECTRICAL JOB :- Supply, Installation, Testing & Commissioning of All electrical job like cable and tray laying from our panel to pumps and sensores, termination
and connection to the pumps and our panel. ( Note :- You have to provide the main power supply with 3 phase, nutral earthing etc with your MCCB to the our Main
electrical control panel.
4.1
NSR
ELECTRICAL CONTROL PANEL :-
Supply, Installation, Testing & Commissioning of MS fabricated powder coated electrical control panel
Complete with main switch suitable as per load , AV meter, MCCB for HEAT PUMP UNITs(1no) controlled with time and tank bottom sensor, and SOLAR
circulation pump controled with soler top temp. sensors and return solar water temp. with diffrencial contorler.Switch for cold water feed pump in mixing
tank, interlocking with solonoide valve valve in in let cold water line and ON/OFF Switch with DOL starter for each pumps , indicating Lamps, temp.
controller.complete with suitable contactors and temp. interloking system with each safety. Provision for Emergency heating for heater OF ADEQUATE CAAPCITY.
the heater will be interlocked with tank temp.
Incomer:-
400 amps TPN MCCB, 36 kA Breaking Capacity with the following accessories:
0-500 volts 96 x 96 mm square voltmeter with selector switch shall be protected by 2 amps TP MCB. 1 Set 0-400 amps 96 x 96 mm
square ammeter with selector switch and 125/5 amps 10 VA CL:1 CTs. 1 Set Busbar:-
500 amps TPN (36 KA) aluminium bus bar with heat shrinkable insulation sleeves Phase indicating
lamps shall be protected by 2 amp SP MCB 3 Sets
Outgoings:-
3 No 160 amps 4P MCCB with Star/ Delta starter and outgoing feeder to Heat pump (3 Working). Each compartment shall contain auto/manual selector switch and an
indicating lamp with MCB’s for ON / OFF / TRIP status of motor.
12 No. 32 amps 4P MCCB with DOL starter and outgoing feeder to ALL Pumps. Each compartment shall contain auto/manual selector switch and an indicating lamp
with MCB’s for ON / OFF / TRIP status of motor.
Job
1
-
5 HEAT PUMP CIRCUIT :-
5.1
NSR
HEAT PUMP- Supply, installation, testing & commisioning of Packaged type Air to Water Heat Pump of 80 KW. Each shall be completely factory assembled including
2 Nos. Scroll Hermetically Sealed Scroll / Reciprocating Compressor(s), evaporator, Condenser and Microprocessor Control Panel etc withR-407-c/R-134a/R-410a
Referigerant and COP between 3-4 & shell and tube heat exchanger. The Heat Pump shall have inbuilt hot water heat exchanger (preferably plate type) with
maximum pressure drop of 0.5 kg/sqcm with minimum working pressure of 10 kg/sqcm, solenoid valve to eb provided at inlet on steam line, vibration isolators, pumps,
valves (NRV/Ball valves/Balancing Valves), fittings, electronic expansion valve, Copper / Aluminium fins, flow switch, pressure gauge, thermogauges, air release
valves, and other accessories. The Heat Pump should be capable of producing hot water at minimum 55°C temperature at outlet (condenser circuit) temperatures at
approx. 40°C ∆T. The Machine should have an operating ambient temperature range of 0°C to 35°C.
PVC Make up Tank for Heat pump of capacity 1634 Lit. (Approx.) with all make up/drain/soft water inlet/flaot.air vent valve, indicators needs to be provided.
Heat Pump shall have built in electric panel as per safety norms as manufacturer standard. It shall be Suitable for electric supply of 415 + 10% volts & 50 Hz. The Heat pump
shall have an in-built facility to start / stop depending on variation in demand at different periods. All interconnecting wiring / cabling between heat pump and electrical
panel shall be part of the equipment. The Heat pump shall have an in- built facility to start / stop depending on variation in demand at different periods.
The Heat Pump Shall be designed at Ambient Temperature at 7 degree celcius. Flow rate on hot
water tank side & heat pump side - 8000 LPH Heat Exchanger- 40,000 Kcal./Hour.
Nos.
3
-
SITC of all hot water pipes of required diameter of ERW heavy class GI pipes confirming to IS 1239 complete with all necessary fittings including Tees, elbows,
reducers, unions, rubber gaskets etc. along with rockwool insulation with 100 kg/cum density, Al cladding of 24 G thickness, GI fanges etc. complete in all respect
& as per directions of E-I.C.
Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of motor control centre shall be fabricated out of 14 gauge CRCA sheet steel in
form in 3b formation with reinforcement of suitable size angle iron, channel ‘T’ sections irons and/or flats wherever necessary. Cable gland plates shall be provided on top
as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final
approved shade of powder coated paint. 2 Nos. earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in case of
large panels. Approval shall be taken for each panel before fabrication. Cadmium Plated hardware shall be used in fabrication of panels.
SUBHEAD-I(A):SOLAR HOT WATER GENRATION & HEAT PUMPS
-
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BOQ:- WATER TREATMENT PLANT
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.) Amount
(In Rs.)
A SUBHEAD-I(A):WTP PUMP WORKS (NON SCHEDULED ITEMS)
1
Supplying, installing, testing and commissioning of vertical inline type centrifugal pump with SS-
304 casing, SS-304 /Brass impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900
rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate
with coupling guard. Pump shall have pressure gauge with isolation cock, Isolation valve, NRV on
delivery line, strainer (with by-pass) at suction which will be paid separately under respective items.
Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved
design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The
installation shall be complete with all necessary ancillaries & accessories including base plate
complete as required. It shall be mounted on MS channel common base plate & fixed with suitable
bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm
above floor level including making connection of inlet & outlet with fittings including nut, bolts, packing
etc.Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of cushy foot
mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with
duty curve. The entire work shall be complete as per specifications & as per directions of E-I-C.
1.1 NSR Filter Feed Pump
Flow rate : 300 LPM each
Head : 30 Mts
No. of pumps : 2 (1 set=1 Working + 1 Standby)
Required for : Filter Feed Pump
Location : WTP Plant Room
HP rating of motor: Meeting requirements of flow & head Set 1 -
1.2 NSR STP Make up & Irrigation Pump
Flow rate : 150 LPM each
Head : 30 Mts
Required for : STP Make up Pump
No. of pumps : 2 (1 set=1 Working + 1 Standby)
Location : WTP Plant Room
HP rating of motor: Meeting requirements of flow & head Set 1 -
2
NSR
Supply, Installation, Testing and Commissioning of compact packaged type skid mounted, self
contained variable frequency drive hydropneumatic system complete as per directions of the engineer-
in-charge & as per following specification:-
(i) In- line vertical multistage centrifugal clear water pump set with SS-304 casing, SS- 304 impeller with
SS-316 shaft ,CI base with CED coating complete directly coupled with TEFC induction motor of class
"F" insulation & efficiency class IE-3, 2900rpm, suitable for opertion on 415 Volts ±10%, 3 phase, 50
Hz A.C. supply complete.
(ii) The entire system shall be mounted on a common base frame i/c common suction and common
delivery of G.I heavy class pipe headers with flanges, interconnecting piping with all required
Conrol Valves, Non-return valves, pressure guage with
isolation cock etc. and all requried accessories.
(iii) Pressure vessel of non corrosive FRP composite construction lined with NSF and/or FDA listed
material, like high density polyethylene with fully replaceable polyurethane. Air cell burst
pressure of minimum of 3 times the vessel operating pressure and prototype cycle tested for 80,000
cycles with charging connections to dischage pipe line with necessary flanges, gaskets, isolating valve, nuts/
bolts etc. with suitable foundation boits & other accessories, complete.
(iv) Panel mounted microprocessor multi pump contoller with large graphical display and Flying
variable frequency drive (VFD) mounted inside a panel complete with pressure sensor transmitter.
The graphical display capable to show number of pumps running & also communicate with other
controllers following with open protocol through RS485 port. System should be capable to
compensate for frictional losses at lower flows. All alarms should be displayed in the controller. The
panel should also have provision for manual / automatic alternate (cyclic) operation of pumps, ON/OFF
switch, complete.
2.1 NSR (v) Necessary foundationing bolts, vibration elimination pads and other accessories complete as required.
Domestic Water Transfer Pump
No. of Pumps : 2 Nos. (1 W + 1 S)
Capacity : 300 LPM of Each Pump
Head : 70 Meters
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.)
Amount (In Rs.)
Air Vessel : 1 No.of Min. 100 Liters Cap. Set 1 -
The entire system alongwith pumps & control panel must be sourced from single manufacturer only for unit responsibility.
2.2 NSR Flushing Water Transfer Pump
No. of Pumps : 2 nos. (1 W + 1 S)
Capacity : 150 LPM of Each Pump
Head : 70 Meters
Air Vessel : 1 Nos of Min. 100 Liters Cap. Set 1 -
The entire system alongwith pumps & control panel must be sourced from single manufacturer only for unit responsibility.
HP rating of motor: Meeting requirements of flow & head
3 NSR Submersible Pump
Submersible Centrifugal Non-clog Drainage Pump
Supply, installation, testing and commissioning of continuous duty submersible centrifugal single
stage single suction non-clogging drainage mono block pumps with stator frame of SS casing, SS impellar
complete with 3 phase tottaly water & dust proof motor suitable for operation 400/440 volts, 3 phase,
50 Hz, 2900 rpm, class -F isulation, IP 68 protection as per IS 2147 of electric motor with efficiency
class of min. IE-3 (tested for leak proof operation) with all necessary protection and double
mechanical seal, gland packed etc. complete with all ancillaries including float type level controllers,
float switch, electrical control panels fabricated from 14 gauge CRCA sheet volt meter ammeter with
selector switch, TPMCB, 5 VA CL : CTs, phase indicating lamps protected by 2 amp SP MCB, DOL starter
of suitable capacity (H.P), necessary wiring, cable alleys, nclusive of all terminations, earthing,
interlocking, starter with Automatic float type level controller, providion of high level alarm,
sequence timer, potential free contact to starter for connection to BAS, both pumps may run
simultaneously at pre determind level. (1Working + 1Standby). The submersible pump shall be protected
for dry run operation & with suitable foundation. The pump shall be suitable for auto/ manual
operation.
Vendor to submit proposed pump model with duty curve.
The entire work shall be complete as per specifications & as per directions of E-I-C.
3.1 NSR Flow rate : 200 LPM each
Head : 11-12 Mts
Solid Handling : upto 35 MM
Location : WTP Plant Room
No. of pumps : 2 (1 set=1 Working + 1 Standby)
HP rating of motor: Meeting requirements of flow & head Set 1 -
4
NSR
Providing, fixing, testing & commissioning of vertical MSFRP filter with adequate dirt holding
capacity. Fabricated from MS sheet as per IS-2825 and manufacturer's specifications complete
with intitial charge filter media including painting inside with two coats of non toxic epoxy and with one
coat of zinc chromate two coats of synthetic enamel paint outside. Including concrete foudation with
cement plaster complete as required. The filter shall also be provided with set of internals for raw water
inlet and bottom collecting system. Complete with frontal piping/face piping (heavy duty G.I.) and
butterfly valves of suitable diameter as per system parameters designed on 1.50 m
/ sec velocity & suitable provision of back wash(air blower with air flow approx. 5.1 lpm/sqm air
capacity, at 0.5 kg/sqcm pressure) & regeneraion needs to be considered. OBR:-8 hours HOS:-2500
MM, dia. of tank to be selected meeting our technical parameters. Depth of Filter Media:- 750-900
mm deep or as per manufacturer's design. Output water quality to confirmmin. IS 10500 standards.It
should be complete as per specifications and directions given by Engineer-in-charge.
4.1 NSR Dual Media Filter
Working pressure 3 Kg/Sq.cm
Capacity : 18000 LPH
Location:- WTP Plant Room Set 1 -
4.2 NSR Activated Carbon Filter
Working pressure 3 Kg/Sq.cm
Capacity : 18000 LPH
Location:- WTP Plant Room Set 1 -
4.3
NSR
Medium pressure synchronous motor type chemical dosing pump with noryl Plastic body and PVC
parts, dispensing valves, foot valves, relief valves, mounting plate,
chemical tank of 250 litre capacity complete.
4.3.1 NSR Capacity 0-6 LPH at pressure head of 40 MWC.. Set 1 -
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.)
Amount (In Rs.)
4.4
NSR
The Softner shall be constructed of FRP material with inner shell of integrated polyethylene,
polypropylene and other material as per manufacturer's standard.
The inter distribution system and the underbed draw off system shall be of Hub & Lateral type of
polypropylene material. with all piping/valve connection and adequate tripod with skid self supporting
structure for making the installation completed. The softener shall also be provided with vacuums
breaking connection / accessories to avoid any collapse of internal lining. All filters shall be provided
with lifting lugs and making the installation completed as required.With SS Agitatorr.(softner for
domestic water)
Flow Rate : 18 cum/hr
out put water hardnes- zero
Reg.time-10 hr.
(Incoming Hardness 500mg/lit (Approx)) Set 1 -
4.5
NSR
Providing and fixing Salt Saturator assembly (for supply of salt solution) consisting of HDPE/PVC tanks
with automatic agitators and all required accessories for holding and supplying salt for softener complete
in all respects, including providing and fixing vertical, inline multistage centrifugal pumping set with
stainless steel SS-316 L stage casing and SS-316 L impellers with stainless steel shaft and suction &
discharge casing . The effective capacity of the system to be of minimum 10% greater than actual salt
required for approx. 3 Days with complete structural arrangement including RCC foundation etc. as per
instructions of engineer-in-charge and approved fabrication shop drawings.
Set
1
-
5
NSR
Supplying, installing, testing and commissioning of annunciation and indication panel with
interlocking arrangement complete in accordance to specification with level controller (In Fire
Water, Raw Water, Treated Water , Soft Water Flushing Water Tank : High / Low Level Controller) etc
with control cabling from field to MCC as required at Plumbing Plantroom level. It should be
complete as per specifications and directions given by Engineer-in-charge.
(i) Recommended no. of tanks = 1 Nos.
(ii) Total Capacity of each Tank = 5 000 Liters
The system shall be complete to ensure automatic operaton of pump in accordance to water level in respective tanks.
Lot 1
-
6
NSR
Supplying, installing, testing and commissioning of level controllers (low/high) for water pumps
to start/stop the pump at set level. Including wiring, cabling from pump to panel & all other accessories
as required to operate the system automatically.
(1 Set consists of 1 low level & 1 high level indicator level contoller)
Set
10
-
SUBHEAD I (A) TOTAL -
B SUBHEAD-II(A):PIPING VALVE AND ACCESSORIES (NON SCHEDULED ITEMS)
7
Supplying, installing, testing and commissioning of Ductile CI `Y' Strainer (with flanged
ends) with stainless steel fine wire mesh perforated sheet basket with necessary flange/ unions
nuts, bolts and washers complete as required (on pump suction). It should be complete as per
specifications and directions given by Engineer-
in-charge.
7.1 NSR 80 mm dia Nos. 2 -
7.2 NSR 65 mm dia Nos. 2 -
8
Supplying, installing, testing and commissioning of Class -C (Heavy duty) GI pipe (header &
branch pipes) for pump suction & discharge complete with GI fiitings(elbows, tees, bends, sockets,
union etc.), including painting of pipes and fittings with red paint over a coat of ready mixed primer, both
of approved quality and clamps and other supports (at an interval specified in specification), including
cutting and making good the wall. All fittings & unions, supports & accessories cost is deemed to be
ioncluded in this item.
It should be complete as per specifications and directions given by Engineer-in-charge.
8.1 NSR 32 mm dia RMT 10 -
8.2 NSR 40 mm dia RMT 10 -
8.3 NSR 50 mm dia RMT 40 -
8.4 NSR 65 mm dia RMT 40 -
8.5 NSR 80 mm dia RMT 15 -
8.6 NSR 100 mm dia RMT 15 -
9
NSR
Providing, fixing, testing & commissioning of C.I body butterfly valve, SS disc, Nitrile Rubber
Seal & O-ring (upto 150mm dia with hand lever operation & above with gear box operation)
conforming to IS:13095. Tested to a pressure not less than 16 Kg/Sq.cm (PN-16 rated). Including rubber
gasket, flanges, nuts, bolts, washers & painting complete as required. It should be complete as per
specifications and directions given by Engineer-in-charge.
9.1 NSR 40 mm dia Nos. 2 -
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.)
Amount (In Rs.)
9.2 NSR 50 mm dia Nos. 4 -
9.3 NSR 65 mm dia Nos. 11 -
9.4 NSR 80 mm dia Nos. 9 -
9.5 NSR 100 mm dia Nos. 2 -
10
NSR
Providing, fixing, testing & commissioning of dual plate C.I. wafer type check valve with CI
body & SS plates, vulcanized rubber seal tested to a pressure not less than 16 Kg/sqcm (PN-
16 rated), including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required.
It should be complete as per specifications and directions given by Engineer-in-charge.
10.1 NSR 40 mm dia Nos. 2 -
10.2 NSR 50 mm dia Nos. 4 -
10.3 NSR 65 mm dia Nos. 2 -
11
Providing, fixing, testing & commissioning of resilient rubber lined single arch
vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8
Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges. It should be
complete as per manufacturer's specifications & as directed
by Engineer- in-charge.
11.1 NSR 40 mm dia Nos. 2 -
11.2 NSR 50 mm dia Nos. 4 -
11.3 NSR 65 mm dia Nos. 4 -
11.4 NSR 80 mm dia Nos. 5 -
12
NSR
Providing and fixing M.S. grating and preferably in 600mm long pieces, fabricated with 16x16mm
square bars, @ 20mm clear spacing and welded to angle iron 25x25x5mm and placed firmly on
angle iron frame of 30x30x5mm with 25x3mm hold fasts approximately 75mm long welded at intervals
of 500mm including two or more coats of synthetic enamel paint of approved quality and shade
over one coats of primer and set in cement mortar 1:3 (1 cement : 3 coarse sand) complete as per
attached details for drain.
Kg
500
-
13
NSR
Providing and fixing in position G.I. vent with brass mosquito proof coupling and air filter including
return bend, complete as required. The entire fitting shall be hot dip galvanised. It should be
complete as per specifications and directions given by
Engineer-in-charge.
13.1 NSR 80 mm dia (For OHTs) Nos. 4 -
13.2 NSR 100 mm dia (For UGTs) Nos. 6 -
14
NSR
Providing, testing & commissioning of industrial type pressure gauge (dial dia. 150mm)
with pressure scale of 0 to 15 kg / cm2. Provision of isolation cock suitable for maximum pressure of 15
kg/cm2 shall be included in cost.It should be complete as per specifications and directions given by
Engineer-in-charge.
Nos.
20
-
15
NSR
Supply, installation, testing and commissioning of sight tube (of 3.5 to 4 mm length) with isolation
valve at top / bottom, demarcation on tube for making the installation of level indication on the RCC water
tank for underground tanks. It should be complete as per specifications and directions given by
Engineer-in-charge.
Nos.
6
-
16
NSR
Supply, installation, testing and commissioning of testing kit with all chemicals complete suitable
for conducting test on water quality. The test kit shall be suitable to measure TDS, pH, Hardness, Iron
content and other parameters. It should be complete as per specifications and directions given by
Engineer-in-charge.
Set
1
-
SUBHEAD II (A) TOTAL -
C SUBHEAD-III(A): ELECTRICAL WORKS (NON SCHEDULED ITEMS)
ELECTRICAL PANEL
17
NSR
Supply, Installation, Testing and Commissioning of Water Treatment Panel cubicle type, made
out of 14 swg CRCA sheet steel, totally enclosed, IP-42, protection free standing, floor mounting, dust
and vermin proof ,indoor, compartmentalised, powder coated painting suitable for operation on 3 Phase
and neutral, 415v, 50 Hz AC supply system with busbars extensible on both sides, interconnections
with suitable size of copper leads/ solid aluminium strips, all MCCB's shall be provided with O/C &
S/C releases all as shown on drawing including supply & installation,earthing complete as required and
as per specifications:
Incoming
400 Amps FP MCCB (36 KA Breaking capacity)with microprocessor release for O/L, S/C, E/F Protection as per specifiactions including all accessories:
0-500 volts 96 x 96 mm square voltmeter with selector switch protected by 2 amps TP MCB. 1 Set
0-400 amps 96 x 96 mm square ammeter with selector switch and 400/5 amps 10 VA CL:1 CTs. 1 Set
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.)
Amount (In Rs.)
Phase indicating lamps protected by 2 amp SP MCB 3 Sets
1 set digital multifunction meter ( showing harmonics along with all other electrical parameters such
as voltage, current, HZ, KW, KWHR, P.F) with RS 485 port with
matching cast resin CTs.
Bus Bar
400 mps TPN (25 KA) aluminium bus bar with heat shrinkable insulation sleeves.
Outgoings
For STP water Make up /Irrigation pumps (1 Working & 1 Standby)- 2 No. 25 amps 4P MCCB with 2 nos. 2
H.P DOL Starter, overload relay, ammeter with single CT, start/stop push button, auto / manual selector
swtich, single phase preventor RELAY and indicating lamps with MCB for ON / OFF / TRIP status
of motor.
For Filter feed pumps (1 Working & 1 Standby)- 2 No. 40 amps 4P MCCB with 2 nos.4
H.P DOL Starter, overload relay, ammeter with single CT, start/stop push button, auto / manual selector
swtich, single phase preventor RELAY and indicating lamps with MCB for ON / OFF / TRIP status of
motor.
For OHT Transfer pumps -Domestic Purpose (1 Working & 1 Standby)- 2 No. 40 amps 4P MCCB with 2
nos. 6 HP DOL Starter, overload relay, ammeter with single CT, start/stop push button, auto /
manual selector swtich, single phase preventor RELAY and indicating lamps with MCB for ON / OFF /
TRIP status of motor.
For OHT Transfer pumps -Flushing Purpose (1 Working & 1 Standby)- 2 No. 40 amps 4P MCCB with 2
nos. 6 HP DOL Starter, overload relay, ammeter with single CT, start/stop push button, auto /
manual selector swtich, single phase preventor RELAY and indicating lamps with MCB for ON / OFF /
TRIP status of motor.
For plant room drainage pumps (1 Working & 1 Standby)- 2 No. 25 amps 4P MCCB,with 2 nos. 1
HP DOL Starter, overload relay, ammeter with single CT, start/stop push button, auto / manual selector
swtich, single phase preventor and indicating
lamps for ON / OFF / TRIP status of motor.
For Lighting & Power inside WTP plant room:-1 no. 63 Amp 4P (10 KA, C curve) MCB, OVERLOAD RELAY, SHORT CIRCUIT RELAY
For Borewell pumps (2 Working )- 2 No. 40 amps 4P MCCB, with 2 nos. 7.5 HP DOL Starter, overload
relay, ammeter with single CT, start/stop push button, auto / manual selector swtich, single phase
preventor RELAYand indicating lamps with MCB for ON /
OFF / TRIP status of motor.
All Incoming/ Outgoing Feeders shall be with suitable size switchgear & rating of starter alongwith
Busbar sizing to meet the functional requirement of Pump & other Equipment. Nothing extra will be paid in this regard.
Spare MCB’s of following capacities to be provided in this panel as mentioned below:-
63 Amp 4P MCB - 1 No.
6.3-10 Amp TP MPCB’s 2 No.
19-25 Amp TP MPCB’s 1 No.
17.1 Complete Item as mentioned above Set 1 -
18
NSR
Supply,installation,testing and commissioning of XLPE insulated sheathed 1.1 KV grade armoured
Copper control cables for various equipment through walls / ceilings with appropriate clamps / fixing
arrangements and complete with termination as per manufacturer's specifications & as directed by
Engineer-in-charge.
18.1 NSR 3C x 1.5 Sq. mm RMT 100 -
18.2 NSR 4C x 1.5 Sq. mm RMT 80 -
18.3 NSR 5C x 1.5 Sq. mm RMT 80 -
19
NSR
Supplying and making end termination with brass double compression gland and
aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium/copper
conductor cable of 1.1 KV grade as required.
19.1 NSR 3 core x 10 Sq.mm. (copper cable) Set 12 -
19.2 NSR 3 core x 6 Sq.mm. (copper cable) Set 8 -
19.3 NSR 3 core x 16 Sq.mm. (aluminium cable) Set 8 -
19.4 NSR 4 core x 10 Sq.mm (copper cable) Set 8 -
19.5 NSR 3.5 Core x 95 Sq.mm (Aluminium cable) Set 4 -
20
NSR
Supply, installation, testing & commissioning of XLPE insulated and PVC sheathed
Aluminium/Copper conductor armoured cable of 1.1 KV grade confirming to IS : 7098:1988 with
upto date amendments of following sizes
20.1 NSR 3 core x 10 Sq.mm. (copper cable) RMT 80 -
20.2 NSR 3 core x 6 Sq.mm. (copper cable) RMT 100 -
20.3 NSR 3 core x 16 Sq.mm. (aluminium cable) RMT 250 -
20.4 NSR 4 core x 10 Sq.mm (copper cable) RMT 80 -
20.5 NSR 3.5 Core x 95 Sq.mm (Aluminium cable) RMT 80 -
Sl. No. DSR 2018/ NSR Description Unit Quantity Rate (In Rs.)
Amount (In Rs.)
21
NSR
Supplying and installing following size of perforated pre-painted GI cable trays with perforation not
more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with
M.S. suspenders including bolts & nuts, painting suspenders etc as required. The cost shall include
Tees, bends etc.
21.1 NSR 150 mm width x 50mm depth x 1.6 mm thickness. RMT 60 -
22
NSR
Supply and fixing in position 1 m wide Insulation mat made of elastomeric polymers Material (Class -
A) of 415V grade as per IS 15642-2006 . Thickness of insulation mat shall be not less than 2 mm to
withstand 1.1 KV dielectric strength AS PER IS 15652 : 2006. It should be complete as per specifications &
directions of Engineer-in-charge. It should be complete as per specifications & directions of Engineer-
in-charge.
RMT
20
-
NOTE:
Contractor shall include provision of separate MDBs for light and power requirement of the plant room.
Power supply shall be taken from above panel
23
NSR
Supplying, installation, testing & commissioning of water meter (digital type) of varying dia. For
STP inlet, Irrigation, Cooling Tower Supply(IF APPLICABLE), Borewell/Municipal supply,
WTP/ETP etc. as reqd. in GRIHA.
Lot
1
-
24 NSR Operation & Maintenance Work
To operate the entire Water treatment plant under available load conditions for further period of 30 days on round the clock basis.
To provide services of contractors expert operating personal comprising of :
One Supervisor 4 hrs Three times a week.
One Plant operator one per shift in three shifts.
One helper for general maintenance and assistance. One per shift in three shifts.
Company’s back up services of senior engineers and experts for any major problems, general check up
and maintenance and advise. Once a week for 2 hours minimum
more or more if required.
All tools, equipment and testing devices to be provided by the contractor.
Consumable including lubricants and chemicals will be provided by Owners. Job 1
-
SUBHEAD III (A) TOTAL -
TOTAL OF WTP WORKS (In Rs.)
-
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BOQ OF REVERSE OSMOSIS (R.O) WORK (CENTRALIZED & PORTABLE)
Sl. No.
DSR / E&M
2018/ NSR
Description
Unit
Qty
Rate ( In Rs )
Amount (In Rs)
SUBHEAD-I(A):RO PLANT (NON SCHEDULED ITEMS) -Centralized &
Portable Type
Expected Treated Water Characteristics after RO Plant
Parameters Characteristics
PH 6. 0 – 7.0
Total Dissolved Solids <50 ppm
Suspended solids Nil
Turbidity Nil
Iron as Fe Nil
Total Hardness Less than 5 ppm
CENTRALIZED R.O SYSTEM
1
NSR
Supply, Installation, Testing & Commisioning of RO station of 500 LPH
capacity of suitable head, Cost supply shall be inclusive of RO
membrane/modules, and pre and post dosing of biocide dosing , hypodosing ,
antiscalant dosing system, post chlorine dosing and pH dosing, CIP system
(cleaning in place), pH orrection dosing system, centralized control panel complete
as required, shall be having capacity to treat the raw water having TDS 1200 ppm. The
treated water should have TDS less than 100 ppm and hardness less than 50 ppm or as
per WHO standards. The operating voltage to 415 volt/50 HZ +/- 10% alongwith
required capacity high pressure pump and solenoid valves,microprocessor
based Auto flushing ,MIMIC protection for complete RO,online sensor for
permeate flow,provition for Auto Dosing,skid mounted, dry run protection of
pump, automatic tank level control, SMS Alert System,inbuilt auto flush timer for
periodic flushing of membranes, over voltage and over current protection with
switch mode power supply syste painted & epoxy coated. Cost for suitable
PCC/RCC foundation with plaster, antivibration arrangement of cushy foot
mountings is deemed to be included in this item cost. in PCC foundation in PCC
(1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including
making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost
for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of
cushy foot mountings is deemed to be included in this it
1.1
NSR
Description of Equipments shall be as under : 01.= Raw
water Feed Pump
02= Multigrade Sand Filter 03 =
Activated Carbon Filter
04.= Antiscalant Dosing System
05.= Reverse Osmosis membrane - Hydramem 06 = High
pressure Feed pump
07 = Micron Filter
08 = All instrumentation including pH meter, panel mounted conductivity
meter, pressure switch, water flow meter, level switch, SDI kit, panel mounted online
hardness meter, flow meter, pressure gauge etc. as required
09 = pH correction dosing system
10 = Interconnecting pipe work & valves & other accessories= SS 316 11 = Ultraviolet
system
12 SS RO water storage tank
all above shall be provided with standby for complete uninterrupted supply of water for
drinking water demand and cooking water demand , complete as per schematic and
specifications.
First fill of all chemicals & lubricants to commission the Plant including &
provisioniong the same for 1 year.Cost for the same needs to be included in this
item cost.
All structural steel bases & supports shall be painted & epoxy coated. Cost for suitable
PCC/RCC foundation with plaster, antivibration arrangement of cushy foot mountings
is deemed to be included in this
Set
1
-
Sl. No.
DSR / E&M
2018/ NSR
Description
Unit
Qty
Rate ( In Rs )
Amount (In Rs)
2
NSR
Supply, installation , testing & commissioning of FRP filter (suitable for
3.5 Kg/Sqcm working pressure) complete with initial charge with pebbles,
anthracite, media , Auto multiport valve, for controlling all operations),
glycerine filled pressure gauge at inlet, outlet and Automatic back wash ),
complete as required including UPVC Frontal piping and all other accessories
required to make the system complete and air vent as required to complete the
system.
2.1 NSR Multi Grade Filter
Filteration Rate 3 Cum/Hr
Working pressure 3.5 Kg/Sq.cm
Diameter- 350 mm Set 1 -
2.2 NSR Activated Carbon Filter
Filteration Rate 3 Cum/Hr
Working pressure 3.5 Kg/Sq.cm
Diameter- 400 mm Set 1 -
3
NSR
Providing, Fixing, Testing & Commissioning of Water Purifier cum Water Cooler made
of stainless steel having storage capacity of MIN.40 liter or nearest available with
OEM & cooling capacity 40 liter / hour with Reverse osmosis system & ultra voilet
membrane TDS reduction 90% having automatic back wash system with
filteration unit & all other required accessories complete in all respect as per
direction of the engineer in charge .
Each
16
-
TOTAL AMOUNT ( IN RS) -
Vol V BOQ
Construction for Upgradation of Srirama Chandra Bhanja Medical College and Hospital, Cuttack (Odisha)
BOQ:- FIRE FIGHTING WORKS
Sl. No.
DSR
2018/NDSR
Description
Unit
Quantity
Rate (In Rs.)
Amount (In Rs.)
SUBHEAD-I(A): FIRE PUMP WORKS (NON SCHEDULED ITEMS) FOR HYDRANTS & SPRINKLER SYSTEM
Note:
1.NOC from fire authority shall be in the scope of Contractor . Only fee paid to the fire authority shall be reimbursed against
the submission of the receipt and nothing shall be paid extra.
2. All the Fire Fighting works shall be done in compliance of Fire Fighting authority requirement & relevant codes/standards.
1.1
NSR
FIRE PUMPS - ELECTRICAL
Supply ,installation, testing and commissioning of electrically driven fire-pump, suitable for automatic operation consisting
of the following : Horizontally mounted end suction single/multi stage, single/multi outlet centrifugal pump, suitable for
operation on 415 volts ± 10%, 3 phase, 50 HZ A.C supply, IE-2 Class efficiency, complete with flexible coupling and coupling
guard as required. Fire pump having C.I. body, bronze impeller and S.S. 410 Shaft with mechanical seal, capable for delivering
2850 Lpm water at 100 mts.head to ensure a minimum pressure of 3.5 kg/cm2 at the Terrace/farthest hydrant. (The pump
should meet the condition of Local fire Authority). 'Squirrel cage induction motor, TEFC type of suitable rating for operation on
415 volts, 3 phase 50 HZ A.C supply, for the above pump with synchronous speed of 2900 RPM. Common base plate for above
pump and motor from M.S. Channel as required size. Cost for Suitable PCC/RCC foundation with plaster, Antivibration
arrangement of cushy foot mountings is deemed to be included in this tem cost. It should be complete as per specifications &
directions of E-I-C. (For Hydrant & Sprinkler System).
Set
2
-
Vol V BOQ
FIRE PUMPS - DIESEL ENGINE DRIVEN
1.2
NSR
Supply, installation, testing and commissioning of Diesel Engine driven fire pump suitable for automatic operation comprising of the following :
Horizontally mounted end suction single/multi stage, single/multi outlet centrifugal pump, suitable for operation on 415 volts ±
10%, 3 phase, 50 HZ A.C supply, complete with flexible coupling and coupling guard as required. Fire pump having C.I. body,
bronze impeller and S.S. 410 Shaft with mechanical seal, capable for delivering 2850 LPM of water at 100 meters head to
ensure a minimum pressure of 3.5.kg/cm2 at the terrace/farthest hydrant. The pump should meet the condition of Local fire
Authority/NBC).
Water/Air Cooled Diesel engine (Min.4 CYLINDER ENGINE) of speed 1800 RPM for the above pump with automatic starting
mechanism (AMF autostart panel complete with necessary relays like no volt relay, over voltage and low voltage relays, contactors,
timer, pressure switch etc. as required for the auto start of the diesel engine in case of power failure complete with all accessories,
wiring & cabling) and other accessories including fuel tank (fabricated from 3 mm MS sheet painting with two coats of synthetic
enamel paint over a coat of primer) capacity 200 Litres(fitted with Magnetic oil level indicator,Diesel Engine oil and Coolant
required for Testing & Commissioining & First Fill of Fuel to be in Contractor's Scope MH with cover drain valve, Air vent
hydraulic pumps including structural supports (painted with approved shade),Hard Rubber Tubing of necessary
length to connect Diesel Tank with Diesel Pump, necessary Pressure Reducing Valve, 2 Nos. x 12 volt battery, heat
exchanger with necessary piping connections & fittings flexible coupling, coupling guard & exhaust pipe ( 150 mm diameter M.S.
Class 'C' diesel pump exhaust pipe includings all fittings, like bends, tees etc. clamps / structural steel supports. The pipe shall be
provided with 75mm thick fiberglass insulation/rockwool insulation & covering the insulation with 500 g polythene sheet giving
proper overlaps & sealing the joints with suitable adhesive compound. The pipe shall be provided with 24 gauge aluminium sheet
cladding.) as per drawing complete as required. Common base plate for above pump and Diesel Engine from M.S. channel of
required size. Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of cushy foot mountings is deemed
to be included in this tem cost. 24 volts, 180 AH Lead battery ( 12 volts-2 Nos) with boost / trickle charger for starting the engine
automatically as required. .It should be complete as per specifications & directions of E-I-C.
Set
1
-
Vol V BOQ
JOCKEY PUMP
1.3
NSR
Supply, installation, testing and commissioning of jockey pump comprising of the following :
Horizontally mounted end suction single/multi stage, single/multi outlet centrifugal pump, suitable for operation on 415
volts ± 10%, 3 phase, 50 HZ A.C supply, IE-2 Class efficiency, complete with flexible coupling and coupling guard as required.
Fire pump having C.I. body, bronze impeller and S.S. 410 Shaft with mechanical seal, capable for delivering 180 LPM of
water at 100 mts.head to ensure a minimum pressure of 3.5 kg/cm2 at the terrace/farthest hydrant. The pump should
meet the condition of Local fire Authority).
Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 HZ AC supply for the above pump with a speed of
2900 R.P.M. with flexible coupling and coupling guard etc. as required.
Common base plate for above pump and motor from M.S. channel as required size.
Cost for Suitable PCC/RCC foundation with plaster, Antivibration arrangement of cushy foot mountings is deemed to be included
in this tem cost.It should be complete as per specifications & directions of E-I-C. (For Hydrant & Sprinkler System)
Set
2
-
1.4 NSR Pressure Switch
1.4.1
Supplying, installing, testing and commissioning 0 to 12 Kg/ cm2 ON/OFF pressure switch in delivery line of pump along with
control wiring for auto starting and auto stopping of hydrant / spinkler and jockey pumps. It should be UL listed & should be in
IP 55 enclosure. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
Nos.
7
-
1.5
NSR
Pressure Vessel
Providing, fixing, testing and commissioning of pressure vessel for pressurization of fire system complete with valves at outlet /
drain to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top,
outside with one coat of primer & two coats of synthetic enamel paint of approved shade complete as required to operate
commonly main fire pump, sprinkler pump & jockey pump at drop of pressure, automatically at required pressure setting. It
should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
Working Pressure:- 7 kg/sqcm Test
Pressure: 10 kg/sqcm
Vol V BOQ
1.5.1
(450 mm dia. & 2000 mm height) Nos. 2
-
1.6
NSR
Providing, fixing, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45
deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges. It
should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
1.6.1 NSR 80 mm dia Nos. 2 -
1.6.2 NSR 100 mm dia Nos. 4 -
1.6.3 NSR 150 mm dia Nos. 6 -
1.7 Supply, installation, testing, trial run and commissioning of hydrants. It should be complete as per
manufacturer's specifications & as directed by Engineer- in-charge.
1.7.1
NSR
Internal hydrants/landing valves generally as specified and all complete with:
Sets
50
-
i) Supply, Installation, Testing & Commissioning of Type -A- single headed, Gunmetal ISI marked oblique pattern hydrant
landing valve with 80 mm dia flange inlet and 63 mm dia instantaneous type female out let, blank caps, chain, bend complete with
gunmetal cap and G.I chain twist release type plug and all accessories as per IS:5290-1983
ii) Providing & fixing swinging type First Aid hose reel in red colour drum with 36 mts long and 20 mm dia heavy duty rubber
water hose, 20 mm dia globe valve stop cock, terminating with G.M. coupling & nozzle of 5mm outlet with shut off valve
confirming to IS 8090 - 1976 complete with drum and brackets for fixing on wall, bolts & nuts conforming to IS:884-1985
complete as required.
iii) Providing & fixing Non per colating flexible rubberized fabric lined hose (RRL type – A) ISI marked (IS:636-1988 Type A)
63 mm dia x 15 m long complete with ISI marked gunmetalMale and female coupling (IS:903) bound and riveted to hose pipe with
copper rivets and 1.5 Sq.mm.copper wire.brusting pressure not less than 22 Kg/Sqcm. (two nos. for each hydrant-valve)
iv) Providing & Fixing of standard short size 63mm dia. Gunmetal branch pipe with gun metal nozzle of 20 mm nomnal bore
outlet with instaneous type 63 mm dia coupling complete & confirming to IS:903
v) Providing and fixing standard firemans axe with heavy duty insulated rubber handle.
Vol V BOQ
vi) Providing & Fixing of MS door made up of 16 gauge MS Sheet capable of accommodating fire hose reel, landing valve, hose
pipes, fittings. The door shall have a front glass with lock and key arrangement & shall be painted with one coat of primer & two
coat of finished stove enamelled post office red colour paint & "FIRE HOSE" written on front. (Approx. size of door: 2100 mm HEIGHT, WIDTH OF DOOR AS PER SHAFT SIZE )
1.7.2
NSR
External hydrant valve, IS marked of gunmetal with generally as specified and as required all complete.
Set
10
-
i) Supply, Installation, Testing & Commissioning of Type -A- single headed, Gunmetal ISI marked oblique pattern hydrant
landing valve with 80 mm dia flange inlet and 63 mm dia instantaneous type female out let, blank caps, chain, bend complete with
gunmetal cap and G.I chain twist release type plug and all accessories as per IS:5290-1983
ii) Providing & fixing Non per colating flexible rubberized fabric lined hose (RRL type – A) ISI marked (IS:636-1988 Type A)
63 mm dia x 15 m long complete with ISI marked gunmetalMale and female coupling (IS:903) bound and riveted to hose pipe with
copper rivets and 1.5 Sq.mm.copper wire.brusting pressure not less than 22 Kg/Sqcm. (two nos. for each hydrant-valve)
iii) Providing & Fixing of standard short size 63mm dia. Gunmetal branch pipe with gun metal nozzle of 20 mm nomnal bore
outlet with instaneous type 63 mm dia coupling complete & confirming to IS:903
iv) Providing & Fixing of M.S. fire hose weather proof cabinet (750x600x250mm) made out of 16 gauge M.S. sheet capable of
accommodating landing valve, hose pipes, fittings & accessories. The box shall have a front glass door with lock and key
arrangement & shall be painted with one coat of primer & two coat of finished stove enamelled post office red colour paint &
"FIRE HOSE" written on front.
1.8
NSR
Providing, installing, testing & commisioning of fire brigade inlet connection (fire department connection) consisting of 4 Nos. 63
mm dia instantaneous inlet, 1 No. 150 mm diameter sluice valve, 1 No. 150mm dia. Non-return valve and wall mounted box of
M.S. construction made out of 16 gauge MS Sheet with glass door to house the above mentioned components. It should be
painted with 2 coats of red paint shade conforming to 536 IS -5 over one coat of primer. Paint shall confirm to IS 2932. It should be
complete as per manufacturer's specifications & as directed by Engineer- in-charge. (FOR UG TANK & EXTERNAL RING
MAIN)
Set
3
-
Vol V BOQ
1.9
Providing, installing, testing & commisioning of fire brigade draw out connection (fire department connection) with suction
pipe MS class 'C' 100 mm dia. & 100 mm dia. foot valve & steel chain including wall mounted box M.S. construction made out of 16
gauge MS Sheet with glass door to house the above mentioned componenets. It should be complete as per manufacturer's
specifications & as directed by Engineer- in-charge. (to be connected to static water tank). It should be tested to hydraulic
test @ 21 kgf/sqcm.
Set
2
-
TOTAL OF SUBHEAD-I(A) -
SUBHEAD-II(A):PIPING FOR FIRE FIGHTING FOR HYDRANT & SPRINKLER SYSTEM SYSTEM (NON SCHEDULED ITEMS)
NON DSR ITEM
2.1
Supply, fabrication , laying, testing & commissioning of heavy grade (CLASS -C) IS marked & as approved make list black mild
steel piping confirming to IS 1239/3589 complete with all fittings(bends/elbows/reducers/Tees etc.), pipe supports,
clamps, hangers including cutting, threading, welding etc. as approved with weleded jointing for external hydrant system in
ground including excavation, refilling the trench & providing cement concrete blocks as supports, at an interval not exceeding 2.5
meters centre to centre.These pipes shall be painted with bitumen and provided with 2mm thick weather proof anti corrosive
treatment (pypkote or equivalent tape) as per IS 10221. It should be complete as per manufacturer's specifications & as
directed by Engineer- in-charge.
2.1.1 NSR 150 mm nominal bore Rmt 500 -
2.1.2 NSR 80 mm nominal bore Rmt 50 -
2.2
Supply, installation testing & commissioning double flanged MS Y-strainers with M.S. body and SS 40-grade mesh strainer & PN-16
Rating. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
2.2.1 NSR Size 200 mm dia. Nos. 2 -
Vol V BOQ
2.3
Supply, fabrication & laying heavy grade,class C, IS marked & as per approved make list black mild steel piping confirming to
IS 1239/3589 including cutting, threading, welding complete with all fittings(bends/elbows/Tees/reducers etc.),
pipe supports, clamps, hangers & painting with one coat of primer & two coat of finished stove enamelled post office red colour
paint etc. as approved with threaded
/welded jointing for Wet Riser/Sprinkler System. G.I. pipe sleeve to be provided wherever the pipes are crossing the
walls/floors and sealing the sleeves as per consultants requirements including cutting holes and chases in brick and making good
the same to original conditions, including cost of structural work for supports fabricated from standard sections of required sizes &
thickness eg. galvanised M.S rods, angles, channels, slotted angle etc. cutting to sizes, drilling, welding, fixing to insert plates
complete in all respects., It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
(Plant Room piping/Vertical Riser/Downcomer/Floor)
Note:
Threaded joint upto 50mm diameter pipe.
Welded joint above 50mm diameter pipe.
2.3.1 NSR 250 mm nominal bore Rmt 40 -
2.3.2 NSR 200 mm nominal bore Rmt 70 -
2.3.3 NSR 150 mm nominal bore Rmt 1170 -
2.3.4 NSR 100 mm nominal bore Rmt 385 -
2.3.5 NSR 80 mm nominal bore Rmt 1155 -
2.3.6 NSR 65 mm nominal bore Rmt 595 -
2.3.7 NSR 50 mm nominal bore Rmt 640 -
2.3.8 NSR 40 mm nominal bore Rmt 1100 -
2.3.9 NSR 32 mm nominal bore Rmt 565 -
2.3.10 NSR 25 mm nominal bore Rmt 7905 -
2.4
NSR
Providing and fixing dial type SS 304 case, Bourden operated pressure gauge with isolation cock and copper pipe on main
header Dial diameter 100 mm calibration 0-14 kg/ sq. cm. Accuracy shall be +- 0.5 %, sensing element shall be bourdon tube (SS
316L), SS 304 gear mechanism, Weatherproof protection, dial shall be of aluminium, window shall be plane & toughened
glass.
It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
No.
53
-
Vol V BOQ
TOTAL OF SUBHEAD-II(A) -
SUBHEAD-II(B):PIPING FOR FIRE FIGHTING FOR HYDRANT & SPRINKLER SYSTEM SYSTEM (SCHEDULED ITEMS)
DSR ITEM
2.5 16.11 Supply, fixing, testing and commissioning of following valves, gauges and strainers as per specifications:-
16.11.1
Butterfly valve (manual) with C.I body SS disc nitrile sheet & O ring & PN 16 Pressure rating as specified 100 mm nominal bore. It
should be compleet in all respect & as per directions of Engineer-in-charge.
2.5.1 16.11.1.1 200 mm dia. Nos. 5 -
2.5.2 16.11.1.2 150 mm dia. Nos. 18 -
2.5.3 16.11.1.4 100 mm dia. Nos. 3 -
2.5.4 16.11.1.5 80 mm dia. Nos. 3 -
2.6
16.11.2
Modified
Non - return valve with dual plate of CI Body SS plates vulcanized NBR seal & PN 16 rating as specified. It should be compleet in
all respect & as per directions of Engineer-in-charge. It shall be of wafer type preferably with flanged ends. It should be
tested for required hydrostatic pressure for shell & seat as per OEM & shall be suitable for maximum working temperature of
80 degree C (approx.).
2.6.1 16.11.2.1 200 mm dia. No. 2
-
2.6.2 16.11.2.2 150 mm dia. Nos. 10
-
2.6.3 16.11.2.4 100 mm dia. Nos. 2
-
2.6.4 16.11.2.5 80 mm dia. Nos. 2
-
TOTAL OF SUBHEAD-II(B) -
Vol V BOQ
SUBHEAD-III(A): SPRINKLER SYSTEM (NON SCHEDULED ITEMS)
3.1
NSR
Supply, installation, testing and commissioning of 150 mm dia Installation Control Valve inclusive of 1 no. 150 mm dia Butterfly
Valve, Alarm Valve with turbine type automatic alarm Gong, Pressure Gauges, Test Lines with Ball Valves with necessary MS
Class "C" piping with threaded fittings of required sizes. All accessories cost shall be included in this item & nothing extra
will be paid in this regard. It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge.
Set
2
-
3.2
NSR
Supply, installation, testing and commissioning of 150 mm dia Zonal Control Valve (Inspection test assembly) inclusive of
1 nos 150 mm dia butterfly valve, 150mm dia non return valve, Vane type Flow Switch (UL listed & FM approved preferably,
complying NFPA 13 requirements) of 150 mm dia., water pressure gauges & 25 mm dia. Auxillary Drain valve with sight glass with
necessary MS Class "C" piping with threaded fittings of required sizes. All accessories cost shall be included in this item & nothing
extra will be paid in this regard. It should be complete as per manufacturer's specifications & as directed by Engineer- in-
charge.
Set
16
-
3.3
Providing, fixing, testing and commissioning of quick response 15 mm dia. quartz bulb type having Bornze/Brass Frame
and Deflector and chrome finished type sprinkler head to operate at 68 degree centigrade including two piece of adjustable
C.P. Rosset complete as required. (minimum UL approved & FM preferably). It should be complete as per manufacturer's
specifications & as directed by Engineer- in-charge.
3.3.1 NSR Side wall type Nos. 90 -
3.3.2 NSR Upright/Pendent type Nos. 4,554 -
3.4
Providing & fixing in the false ceilings, high pressure braided type metallic hose with fittings (25 NB at one end for connection
to pipe and 15 NB at the other end for the Sprinkler) for connecting the Sprinklers to Sprinkler piping system, Hose & Fittings to
be UL listed and FM approved and installed in accordance with para 9.2.1.3.3 of NFPA-13 (2007 edition) Test Pressure 10.0
Kg/Sq.m.
3.4.1 NSR Length upto 700 mm Each 2000 -
3.4.2 NSR Length upto 1200 mm Each 1000 -
Vol V BOQ
3.5
NSR
Supply and laying RCC (NP-2 Class) hume pipe conforming to IS:458 under road crossing, paved area etc. With connecting collars
with cement motor etc. inculding excavation, refilling of earth, ramming and making good as approved complete.
3.5.1 NSR 250 mm dia. Metre 100
-
TOTAL OF SUBHEAD-III(A) -
SUBHEAD-IV(A): FIRE EXTINGUSHER (NON SCHEDULED ITEMS)
4.1
Providing, storing, handling, shifting, installation, testing and commissioning of halon free portable fire Extinguishers as
described below with best effective discharge & maximum jet length as per OEM:
4.1.1 NSR Dry Chemical Powder Type -Mono Ammonium Phosphate (ABC Type)-Cartridge Type -6 kgs. capacity Fire Extinguisher, IS : 15683,ISI MARKED
Nos. 90
-
4.1.2 NSR 9 ltr Water Squeez Grip Cartridge type Fire Extinguisher shall be as per BIS: 15683:2006 bearing ISI mark
Nos. 10
-
4.1.3 NSR 4.5 kg CO2 type, Cartridge type Fire Extinguisher, ISI marked, with high pressure discharge tube, control valve, CCE approved cylinder.
Nos. 48
-
4.1.4
NSR
Providing, fixing, testing and commissioning of 50 Litres (trolley mounted) Mechanical Foam type Fire Extinguisher. In
HP Mild Steel Cylinders ISI marked TAC approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve
fully charged complete in all respects including wall suspension bracket / trolley mounted and confoming to IS:910 .
Nos.
2
-
4.1.5
NSR
Providing, fixing, testing and commissioning of CO2 type Fire Extinguisher of capacity 22.5 kg filled with Co2 Gas as per IS
15222 with controll discharge mechanism fitted with Hose, Horn & TROLLEY confirms to IS 2878 bearing ISI mark. Co2 Cylinder as per IS 7285
Nos.
8
-
Vol V BOQ
4.1.6
NSR
Suply, Installation of 6 kg Clean Agent Fire Extinguisher filled with HFC 236fa or equivalent, Electrically nonconductive
non corrosive, colorless and non-residual gas, Applicable classes A, B, C, and electrical fires, UGTS Pressure Gauge, Gross Weight
8.9 Kg, empty Weight 2.9 Kg, Can Height 530mm, Diameter 150 ± 10mm, Discharge Time 8 Sec(approx), Controllable
discharge mechanism, Jet Range 2 Meter (approx.), Average Discharge is 95%, Deep Drawn with MIG Welding technology,
EPDM Rubber Hose with Special Aluminum Discharge Nozzle, External Coting Pure Polyester Powder (UV resistant), Internal
Coating Epoxy Polyester Powder, Brass forged valves with safety Pin is of SS, Fire rating 2A : 34B. Confirms to IS 15683 & ISI
marked.
Nos.
15
-
TOTAL OF SUBHEAD-IV(A) -
SUBHEAD-V (A): GAS FLOODING WORKS (NON SCHEDULED ITEMS)
5.1 NSR Supply, Installation, Testing & Commissioning of 46.7 Ltrs. Cylinder with Valve & Warning Sign Boards (42 Bar VDS/UL Approved System)
Nos. 7
-
5.2 NSR Sinorix 1230 (Novec or Equivalent) Kgs. 210 -
5.3
NSR
Master Cylinder Accessories: (Single Cylinder)
No.
7
-
* Pr. Guage + Low Pr. Supervisory Switch * Electromagnetic Actuator * Pneumatic Actuator * Flexible Discharge Hose * Flexible Actuation Hose * Manual Pneumatic Actuator * Union 7/16 JIC 1/8
5.4 NSR Supply, Installation, Testing & Commissioning of Nozzles Nos. 21 -
5.5 NSR Supply, Installation, Testing & Commissioning of 2 Zone Fire Alarm Cum Gas Release Module with 7AH x 2 Batteries
No.s 7
-
5.6 NSR Supply, Installation, Testing & Commissioning of Abort Switch No.s 7
-
5.7 NSR Supply, Installation, Testing & Commissioning of Release Switch No.s 20
-
TOTAL OF SUBHEAD-V(A) -
Vol V BOQ
SUBHEAD-VI (A): ELECTRICAL WORKS (NON SCHEDULED ITEMS)
6.1
NSR
Providing, fixing, tetsing & commissioning of annunciator panel for flow control switches, providing audio
/visual indication of actuation of automatic sprinkler system for each zone complete as per specifications. The panel should have
interface for connection to complete controlled building management system. The panel should have:-
a) Fault indication for each zone
b) Indication of zone fire
c) Fire/Fault hooter
d) Alarm Panel for fire/fault
e) Battery for emergency
f) Battery Charger
g) mains supply and shall cater for minimum 16 zones working and 6 zones spare
Each
1
-
6.2 NSR FIRE FIGHTING PANEL
Supply, installation, testing and commissioning of fire fighting panel suitable for 415V, 3 phase, 4 wires, 50 HZ power distribution
system. The panel shall be floor mounted dust and vermin proof conforming to IP- 52, Compartmentalized design, fabricated out
of 14 SWG sheet steel, painting, earthing numbering, danger plate as per specifications and drawings, flush front with
Aluminium busbars, separate earthing to be provided throughout the length of the panel. The incoming and outgoing feeder
breakers, fuses, indicating lamps etc shall be accommodated in modular multitier arrangement. The painting shall be done as
per relevant IS codes/as specified in the specifications. Adequate size cable alley shall be provided all round the panel and in the back
for each cable bending and termination. The outgoing feeders inside the panel shall be connected through solid bus bars. It should be
complete as per manufacturer's specifications & as directed by Engineer- in-charge.
Bus bars shall be provided with heat shrinkable sleeves and shall be colour coded . The panels shall be suitable for cable entry
from bottom/ top. The minimum fault rupturing of all incoming and outgoing switches/breakers shall be 35KA. The panel
shall be fabricated after the approval of fabrication drawings compring of :
Incoming
1 No. 630 amps 4 pole mechanically interlocked incoming MCCB complete with the following:
Vol V BOQ
0-500 volts 96 x 96mm square voltmeter with selector switch shall be protected by 2 amps TP MCB 1 Set
0-630 amps ammeter with 630/5 amps 15 VA CL:1 CT's and selector switch 1 Set
Phase indicating lamps shall be protected by 2 amps SP MCB (for all 3 phases) - 1 Set
Aluminium bus bar sleeves type, rated at 630 amps for three phase & neutral phase bus bar shall have maximum current
density of 0.8 amps per sq.cm. and the neutral bus bar of not less than 50% capacity.
Outgoing:
2 No. 250 amps TP+N MCCB outgoing feeders with required capacity (105 H.P Approx.) S/D starters out going feeders to Hydrant
/ Sprinkler pump motor. The compartment shall contain CT operated ammeter of 0-250 amps range with selector switch auto /
manual selector switch and indicating lamp with MCBs for
`ON'/OFF`TRIP' status of motor.
2 Nos. 63 amps TP+N MCCB, with required capacity (12.5 H.P Approx.) Direct online starter with single phase preventer and
outgoing feeder to jockey pump and Terrace Pump. The compartment shall contain CT operated ammeter of 0-63 amps and
indicating lamps with MCBs for ̀ ON'/OFF`TRIP' status of pump motors.
2 +1 Nos. 32 amps TP+N MCCB, with required capacity (5 H.P Approx.) Direct online starter with single phase preventer and
outgoing feeder to Dewatering Pump. The compartment shall contain CT operated ammeter of 0-32 amps and indicating lamps
with MCBs for ̀ ON/OFF`TRIP' status of pump motors.(This item includes 1 No. Spare)
1 No. space for S/D starter with self illuminated Push button for ON & OFF. 1 No. space for
DOL starter with self illuminated Push button for ON & OFF.
AMF Control & Starter for 105 HP or as reqd. Diesel Engine complete with Contactors, Fuses, MCBs & relays of suitable rating, as
required.
Connector Block/Strip of suitable no.of pairs complete with wiring upto all Starters, for parallel operation from control desk.
Facility for mode selection ie auto or manual test & local/remote.
Contractor shall include in his rates for providing level controllers, switches, wiring, cabling from level controller to panel etc.
complete as required to operate the system automatic/manual and pump shall be protected against running dry.
Electrical hooter with ON/OFF switch for the above pumps running indication Wiring from pressure
switch to starter -1 Lot for above pumps
Suitable rating TPN MCCB for Diesel Engine Control panel
Vol V BOQ
Set of control system to make the system automatic /BMS compatible as per functionl as requirements.
Control Panel for Diesel Engine comprising Auto/Manual selector switch & 3 attempt starting device, timers and relays as
required, push buttons, start/stop in manual mode.
Indication lamp for High/Low Lub.oil pressure, High Water Temp. and Engine ON Indication.
Battery charger suitable for 24V DC with boost and trickle selector switch, with digital panel meter for AC, DC voltage and
Ammeter for battery charging current
Necessary potential free contact for indication of diesel engine driven fire pump running/fault in the addressable fire
alarm panel/BMS Panel.
All standard relays and accessories for automatic operation of diesel engine.The diesel engine driven fire pump shall start
automatically in the event of pressure drop beyond preset limit or mains failure or failure of electrical driven pumps to start
Following provisions to be made in the fire panel:
6.2.1
NSR
Protection failure & control cabling.
Panel shall be interlocked in such a way when fire pump starts on pressure drop in the header, supply to working air
conditioning panels is disconnected.Neccessory Control wiring upto A/c panels , relevant relays & contactors etc. as required
complete in all respect shall be in the scope the Fire contractor (Control wire shall be paid separately under relevant item). Remote
indication of ON/OFF/TRIP shall be provided through potential free contact. Provision of remote starting/stopping (manuals) of
the engine shall be made. All pumps operation shall be controled by pressure switches.
Set
1
-
6.3
NSR
Supply, installation , testing & commissioning of of XLPE insulated and PVC sheathed Aluminium conductor armoured cable of 1.1
KV grade confirming to IS : 7098:1988 (with upto date amendments) of following sizes.
6.3.1 NSR 3 Core x 10 sqmm. Aluminium Armoured Mtr 50 - 6.3.2 NSR 3 Core x 50 sqmm. Aluminium Armoured Mtr 200 -
Vol V BOQ
6.4
NSR
Supply and fixing in position 1 m wide Insulation mat made of elastomeric polymers Material (Class -A) of 415V grade as per IS
15642-2006 . Thickness of insulation mat shall be not less than 2 mm to withstand
1.1 KV dielectric strength AS PER IS 15652 : 2006. It should be complete as per specifications & directions of Engineer-in-charge. It
should be complete as per specifications & directions of Engineer-in-charge.
Mtr
15
-
TOTAL OF SUBHEAD-VI(A) -
SUBHEAD-VI(B): ELECTRICAL WORKS (SCHEDULED ITEMS)
6.5
9.1 Supplying and making end termination with brass double compression gland and aluminium lugs for following size of XLPE
insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required. It should be complete as per specifications
& directions of Engineer-in-charge.
6.5.1 9.1.32 -
Modified
3 Core X 10 sqmm. Aluminium Armoured
Each
8
-
6.5.2 DSR - 9.1.11 3 Core X 50 sqmm. Aluminium Armoured Each 12 -
6.6
DSR-4.1 Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
6.6.1 DSR-4.1.2 150 mm width x 50mm depth x 1.6 mm thickness. Mtr 100
-
TOTAL OF SUBHEAD-VI(B) -
FIRE FIGHTING TOTAL
-