MEDICAL DESIGN GUIDE
DEPARTMENT OF THE ARMY Volume 1
MEDICAL DESIGN GUIDE
Office of the Surgeon General Office of the Chief of EngineersHealth Facility Planning Agency Medical Facilities Design Office
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
2/648
Table of Contents
Title Page
Preface 1
Room Index ))Clinic Facilities 2
Room Index ))Ancillary Facilities 2
Room Index))
Inpatient Facilities 3
Room Index ))Abbreviations 4
Architectural Schedule ))Notes 5 - 6
Architectural Schedule )) Miscellaneous Abbreviations 7
Architectural Schedule ))Finish Abbreviations 8
Architectural Schedule ))Door Types and Materials 9
Architectural Schedule ))Hardware Sets 10 - 11
Architectural Schedule))
Fire Protection 12
Mechanical Schedule ))Symbols and Notes 13 - 15
Mechanical Schedule ))Piping Note 16
Mechanical Schedule ))Medical Gas Units 17
Mechanical Schedule ))Dental Utility Center 18 - 19
Electrical Schedule ))Notes 20 - 23
Electrical Schedule ))Luminaire Schedule 24 - 26
Electrical Schedule ))Symbols 27 - 28
Communication Schedule ))Notes 29 - 30
Communication Schedule ))Symbols 31 - 34
Doctor's Office/Exam Room Elevations 35 - 42
Patient Service Console Elevations 43 - 58
X-Ray Room Criteria and Elevations 59 - 67
JULY 1988
-
8/13/2019 Medical Design Guide
3/648
Preface
The material contained in this Design Guide was compiled and verified by theOffice of the Surgeon General, Health Facilities Planning Agency and theCorps of Engineers, Medical Facility Design Office. This document is intendedto be used as a guide and a supplement to current Technical Manuals and otherpublished criteria, in the planning and design of Army Health Facilities.Information contained in the Design Guide is subject to changes in medicaltechnology and revisions to Technical Manuals or other criteria. The use ofthe Schedules or Room Designs shall not preclude compliance to current
criteria of any applicable codes and standards. The Medical Design Guide wasprepared by the Joint Venture of Harwood K. Smith & Partners Inc./Wingler &Sharp Inc., and was updated September 1994 by JMGR Inc.
Each Room Design series is composed of five individual plates:
Plate "A" - The Matrix Data Provides specific information on technicalrequirements including architectural, electrical, communication andmechanical requirements. Plate A also includes a specific equipment programincluding Joint Schedule Number (JSN), nomenclature, quantity and thelogistical responsibility category as defined in Military Standard 1691. AJoint Schedule Number with a sub-script is a variation of the basic JSN asdescribed in Military standard 1691.
Plate "B" - The Functional Diagram Illustrates the specific spatialutilization including dimensional requirements, maximum, minimum and/orpreferred dimensions.
Plate "C" - The Floor Plan Locates the equipment scheduled in the equipmentprogram with respect to equipment clearances and functional requirements.Some portable equipment not critical to room layout or utility requirements.may not be indicated in this plan, but can be found in the Medical FaciltyRoom Contents List (MFRCL), which is supplied separately for each project.
Plate "D" - The Reflected Ceiling Plan Coordinates architectural materials,ceiling located equipment, and locates lighting, communications, mechanicaland electrical components with proper relationship to room equipment andfunction.
Plate "E" - The Composite Plan Combines multidisciplinary information fromPlates "C" and "D" to reflect a total room requirement for equipment andbuilding systems.
Refer to the following schedules for general notes and graphic "keys" whichapply to all Room Designs and for specific notes referenced in the MatrixData.
JULY 1988 1REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
4/648
-
8/13/2019 Medical Design Guide
5/648
Room Index (Cont'd)
VOLUME III INPATIENT FACILITIES
Room Type Room Number
CCU Bedroom 3.01.01ICU Bedroom 3.01.02ICU Isolation Bedroom 3.01.03
One Bedroom (Mob) 3.02.01Two Bedroom (Mob) 3.02.02Four Bedroom (Mob) 3.02.03Four Bedroom, ALT (Mob) 3.02.04Isolation Bedroom 3.02.05Ped-One Bedroom (Mob) 3.02.06Ped-Two Bedroom (Mob) 3.02.07Ped-Four Bedroom (Mob) 3.02.08Ped Isolation Room 3.02.09Seclusion Room 3.03.01One Bedroom 3.04.01Two Bedroom 3.04.02Four Bedroom 3.04.03Four Bedroom, ALT 3.04.04
Ped-One Bedroom 3.04.05Ped-Two Bedroom 3.04.06Ped-Four Bedroom 3.04.07Normal Newborn Nursery 3.05.01Adm/Obs/Cont Care Nrsy 3.05.02Intermed Care Nursery 3.05.03ICU Nursery 3.05.04Isolation Nursery 3.05.05Nurses Station 3.06.01Nurses Station CCU/ICU 3.06.02Mediprep 3.06.03Soiled Utility-NU 3.06.04Tub/Shower Room 3.06.05Nourishment Pantry 3.06.06
JULY 1988 3
-
8/13/2019 Medical Design Guide
6/648
Room, Index (Cont'd)
ABBREVIATIONS
ABBREV. DESCRIPTION ABBREV. DESCRIPTION
Adm Admission OB ObstetricsALT Alternate Obs ObservationAudio Audiology, Audiometric OR Operating Room
Cath Catherization Ped PediatricsCCU Coronary Care Unit Prep PreparationCL Clinic Photo PhotographicCont Continuing Phys Ther Physical TherapyCommo Communications Prev PreventiveDecon Decontamination Psych PsychiatricDr's Doctor's Rm RoomECG/EKG Electrocardiogram Sm SmallEEG Electroencephlogram w/ withENT Ear, Nose, and Throat (Otorhinolaryngology)ER Emergency RoomExam ExaminationGen General
Intermed IntermediateICU Intensive Care UnitIV IntravenousLab LaboratoryLG LargeMediprep Medicine PreparationMob MobilizationNrsy NurseryNU Nursing Unit
JULY 1988 4
-
8/13/2019 Medical Design Guide
7/648
Architectural Schedule
ARCHITECTURAL NOTES
GENERAL NOTES
1. Doctor's Office and Examination Room are to be identical in all respects with the exception of the equipment and room designation.
2. Ceiling height to be a minimum of 8'-6" with a minimum of 9'-0" to
structural support for ceiling mounted surgical light.
3. A minimum of 6 is required between room walls and prefabricated Audiometric Testing Room. The Audiometric Testing Room will require a recessed slab and special structural design due to the weight of the rooms
4. Add 6 NSF for Nurse Server and 5 NSF for Wardrobe to Bedroom Area.
5. Patient Service Console M5541 shall be provide in all Labor Rooms in Medical Centers and in 25% of the Labor Room in MEDDACS.
6. Area includes 80 SF for Plaster Preparation.
7. Add 12 NSF for Nurse Servers and 10 NSF for Wardrobes to Bedroom Area.
8. Add 24 NSF for Nurse Servers, 20 NSF for Wardrobes and 20NSF for a lavatory to Bedroom Area.
9. Walls for Seclusion Bedroom shall be reinforced with plywood or steel backed GWB. All items to be tamperproof and installed with tamperproof fasteners.
10. Add 8 NSF for undercounter Nurse Server and 5 NSF for Wardrobe to Bedroom Area.
11. Add 16 NSF for Nurse Servers, one undercounter and one full height, 10 NSF for Wardrobes and 20 NSF for a lavatory to Bedroom Area.
12. Add 32 NSF for Nurse Servers, two undercounter and two full height, 20 NSF for Wardrobes to Bedroom Area.
13. Add 8 NSF for one undercounter Nurse Server to Anteroom and 5 NSF for a Wardrobe and 20 NSF for a lavatory to Bedroom Area.
14. Add 6 NSF for Nurse Server to Anteroom and 5 NSF for Wardrobe to Bedroom.
15. Add 6 NSF for Nurse Server to Anteroom and 5 NSF for Wardrobe to Toilet.
16. Provide a minimum of 1 Oral Surgery Room with X-ray capability per Dental Suite.
17. Room requires lead lined walls.
18. Provide 2 Dressing Cubicles at 20 NSF each.
JULY 1988 5
-
8/13/2019 Medical Design Guide
8/648
Architectural Schedule(Cont'd)
ARCHITECTURAL NOTES
GENERAL NOTES (Cont'd)
19. Provide undercut (cu) to door.
20. Wall finish as noted with Ceramic Tile Wainscot.
21. Add 8 NSF for undercounter Nurse Server to Bedroom Area.
22. Provide one lavatory at 15 NSF per each six bassinets.
23. Provide one lavatory at 15 NSF per each four bassinets.
24. VWF is an optional wall finish.
25. Interior glazing shall contain integral Mini-Blinds.
26. The columns shown in patient bedrooms are for purposes of establishing the minimum clear width of these rooms. The selection of a structural system that requires columns along the corridor wall will establish a
minimum clear dimension of 13 in the patient bedrooms. A structural system without columns on the corridor wall will establish a minimum clear dimension of 12'-6". These dimensions are set, as indicated on the room design for the patient bedroom, by the items to be installed along the corridor wall and entrance to the room. A 13 clear dimension will require a 27' column spacing on the exterior wall and a 12'-6" will require a 26' column spacing. The one patient bedroom indicates the preferred column location when only one exterior column is required.
27. Add 30 NSF to room for x-ray generating equipment.
28. Area requires computer flooring.
29. Square footage must be added to this area as required to meet requirements of largest computer equipment.
30. If Halogen is used for Fire Protection, special exhaust may be required.
31. This room must be located on building exterior, occupied areas should not be located above or below this room.
32. Verify floor tolerances with equipment manufacturer.
33. Provide ICU type patient service consoles for 25% of recovery beds.
34. The quantity and type of equipment, infant incubators and/or infant care centers, will be determined by the user.
35. Wall finish as noted with Ceramic Tile Wainscot.
JULY 1988 6
-
8/13/2019 Medical Design Guide
9/648
Architectural Schedule (Cont'd) MISCELLANEOUS ABBREVIATIONS
ABBREV. DESCRIPTION ABBREV. DESCRIPTIONAFF Above Finished Floor MOD Modified
AR As Required MV Medical Vacuum
CFM Cubic Feet Per Minute N Nitrogen
CRS Corrosive Resistive Steel N20 Nitrous Oxide
CR50 Color Corrected Fluor Lamp 5000 K NA Not Applicable
CONFID Confidential NCRP National Council on Radiation ProtectionCW Cool White NP Normal PowerCWX Cool White Deluxe OC On CenterDA Dental Air
OE Dental Oral EvacuationEA Each
OX OxygenEC Electrical Receptacle,emergency circuit PA Process Air
EFF Efficient PR PairEP Emergency Power RFI Radio Frequency
InterferenceEP Emergency Power S Switch, for type seeEXH Exhaust symbols
F Fluorescent STD StandardG Natural Gas TV Television
HID High Intensity Discharge UON Unless Otherwise Noted
Hosp Hospital VS Vacuum Bottle Slide BracketLA Laboratory Air WAGE Waste Anesthesia GasLG Laboratory Gas Evacuation
LV Laboratory Vacuum W/O WithoutMA Medical Air WP Weatherproof
MG Medical Gases
MG-MA Medical Gas - Master Alarm Panel
MG-RA Medical Gas - Remote Alarm Panel
MG-ZA Medical Gas - Zone Alarm Panel
MG-ZV Medical Gas - Zone Valves
JULY 1988 7
-
8/13/2019 Medical Design Guide
10/648
Architectural Schedule(Cont'd)
FINISH ABBREVIATIONS
FLOOR FINISHES CEILING FINISHES
ABBREV. DESCRIPTION ABBREV. DESCRIPTION
CT Ceramic Tile ACT Lay-In Acoustical Tile
Conc-1 Concrete Sealer - Size to be SpecifiedConc-2 Fluid Applied Membrane ACT(P) Lay-In Acoustical Tile Waterproofing ACT-2* Lay-In Acoustical TileET Epoxy Terrazzo w/Vinyl Protective FinishQT Quarry Tile ACT-3 Concealed SplineSV Sheet Vinyl 1' x 1' or 2' x 2'VCT Vinyl Composition Tile ACT-3(P) Concealed SplineCarpet Carpet - Mineral Tile - 1' x 1' orRF Resinous Flooring 2' x 2' ACT-3(V) Concealed Spline - Mineral Tile - 1' x 1' or 2' x 2' w/Vinyl ProtectiveBASE Finish ACT-4 Concealed Spline
CT Ceramic Tile - Metal Tile - 1' x 1' orET Epoxy Terrazzo 1' x 2'QT Quarry Tile ACT-4(P) Concealed SplineIV Integral Vinyl - Metal Tile - 1' x 1' orR Resilient (Vinyl w/Cove 1' x 2' Base is Acceptable) VP -Veneer PlasterConc Concrete GW Gypsum Wallboard GW-LGC Gypsum Wallboard with Liquid Glazed Coating
PARTITION FINISHES * Use ACT-2 gasketed and clipped in place as alternate if 2' x 2' tileABBREV. DESCRIPTION is required as standard.
CT Ceramic Tile
CMU Concrete BlockGW Gypsum Wallboard w/Paint type not SpecifiedGW-VWF Gypsum Wallboard w/Vinyl Wall FabricGW-SG Gypsum Wallboard with Semi Gloss PaintCT-WS Ceramic Tile WainscotWG Wall Corner GuardWB Wall Bumper (Mounting Height to be Specified)
JULY 1988 8
-
8/13/2019 Medical Design Guide
11/648
Architectural Schedule (Cont'd)
JULY 1988 9REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
12/648
Architectural Schedule (Cont'd)
SET DESCRIPTION
H01 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stop L02101 2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN
Gaskets1 Automatic Pemko 434A
Door Bottom
H02 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stretcher Plates J105
2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN Gaskets 1 Automatic Pemko 434A Door Bottom
H03 1-1/2 PR Butts A5111
1 Lockset F05 w/ Levers 1 Stop L02101 2 Mop Plates J107 3 Silencers L03011
H04 1-1/2 PR Butts A5111 1 Stop L02101 1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011
H05 3 PR Butts A5111 1 Lockset F05 w/ Levers (36") 2 Automatic Type 25 (18") Flush Bolts
1 Stop L02101 (36") 1 Holder C01511 (18") 2 Stretcher Plates J105 4 Mop Plates J107 1 Push Plate J301 (18") 1 Pull Glynn-Johnson GJKH1 (18") 2 Silencers L03011 36" Leaf w/ 18" Leaf
H06 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Stop L02101 1 Armor Plate J105 2 Mop Plates J107
3 Silencers L03011
H07 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Lock Electronic Cipher type 1 Stop L02101 2 Mop Plates J107 3 Silencers L03011
H08 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers 1 Closer C02011 1 Stop L02101
-
8/13/2019 Medical Design Guide
13/648
1 Kick Plate J102 1 Stretcher Plate J105 1 Mop Plate J107 1 Head & Jamb Pemko S88 Gaskets 1 Automatic Pemko 412AN Door Bottom
H09 1-1/2 PR Butts A5111 1 Lockset F05 w/ Levers
1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011
H10 1-1/2 PR Butts A5111 1 Hosp Latch Set Glynn-Johnson HL-6 1 Stop L02101 1 Stretcher Plate J105 2 Mop Plate J107 3 Silencers L03011
H11 1-1/2 PR Butts A5111 1 Hosp Latch Set Glynn-Johnson HL-6 1 Closer C02051 or C02061
1 Kick Plate J102 1 Stretcher Plate J105 1 Mop Plate J107 1 Stop L02101 3 Silencers L03011
H12 1-1/2 PR Butts A5111 1 Lockset F02 w/ Levers 1 Holder C01511 1 Stretcher Plate J105 3 Silencers L03011
H13 1-1/2 PR Butts A5111 1 Lockset F02 w/ Levers 1 Stop L02101
2 Mop Plates J107 3 Silencers L03011
JULY 1988 10
-
8/13/2019 Medical Design Guide
14/648
Architectural Schedule (Cont'd)SET DESCRIPTION
H14X 1-1/2 PR Butts A5111-5 1 Lockset F02 w/ Levers 1 Stop L02101 1 Mop Plates J107 1 Silencers L03011 Provide lead shields for mortise lock cases.
Levers and roses to be lead lined
H15X Pivots (Top, Bottom, & C07111 & C07311 Intermediate) 1 Lockset F17 1 Hatch Latch Set Glynn Johnson HL-6 1 Holder C05531 1 Stretcher Plate J105 2 Mop Plates J107 3 Silencers L03011 Provide lead shields for mortise lock cases. Levers and roses to be lead linedH16 3 PR Butts A5111 w/ Hosp Tips
2 Latch Set E59091 at Head 2 Holder C01511 2 Push Plates J301 2 Pulls Glynn Johnson GJKH1 2 Armor Plates J101 2 Mop Plates J103 2 Silencers L03011 48" Leaf w/ 18" Leaf
H17 1-1/2 PR Butts A5111 w/Hosp Tips 1 Latch Set E59101 1 Closer C02051 or C02061 1 Push Plate J301 1 Pull Glynn-Johnson GJKH1 1 Kick Plate J102
1 Mop Plate J103
H18 1-1/2 PR Butts A5111 w/ Hosp Tips 1 Latch Set E59101 1 Closer C02051 or C02061 1 Push Plate J301
1 Pull Glynn-Johnson GJKH1 1 Armor Plate J101 1 Mop Plate J103
H19 1-1/2 PR Butts A511 1 Lockset F04 w/ Lever 1 Closer C02011 1 Stop L02101
1 Kick Plate J102 1 Mop Plate J103 1 Silencers L03011 1 Set Head & Jamb Pemko 319 AN Gaskets 1 Automatic Pemko 434A Door Bottom Fire Rated Hardware
H20 1-1/2 PR Butts A5111 1 Lockset F04 w/ Levers 1 Stop L02101 2 Mop Plates J107
-
8/13/2019 Medical Design Guide
15/648
3 Silencers L03011H21 1-1/2 PR Butts A5111 1 Lockset F18 1 Latch Set E59101 1 Stop L02101 2 Pulls J403 2 Mop Plates J107 1 Set Head & Jamb Pemko 319AN Gaskets 1 Automatic Pemko 434A
Door BottomH22 - Hardware by Door Manufacturer
NOTES:
1. Manufacturer's Name and Number are furnished to serve only as examples of the type of products desired and not a proprietary item.
2. All metal kick plates, stretcher plates, armor plates, pulls and push plates shall be stainless steel.
3. All door trim protection plates shall be 2" less than the width of a single door and 1" less for pairs of doors.
4. All closers shall be provided with the capability for regular or parallel arm mounting applications. Delay action type closers will be provided on doors where cart traffic and handicap accessible is a consideration.
JULY 1988 11
-
8/13/2019 Medical Design Guide
16/648
Architectural Schedule(Cont'd)
FIRE PROTECTION NOTES
GENERAL NOTES
A. Noncombustible construction with one-hour corridor walls are required for unsprinklered buildings.
B. ICU and CCU patient rooms may be open to a nurse's station as one large room without corridor, provided the space has it s own exits and is not a required exit for another space.
C. Nurse's station may be open to a corridor provided it is staffed 24 hours/day; does not reduce width of corridor; contains only communication and monitoring equipment, counter and seating, space for charts and one day s supply of forms.
D. No more than one day s supply of flammable liquid permitted in a room at one time.
E. One hour enclosure for oil-cooled transformers. Refer to NFPA No. 70 for enclosure ratings for other types and sizes of transformers.
F. Provide smoke detectors only when waiting areas are open to corridors. Open waiting cannot exceed 250 square feet in patient sleeping areas and 600 square feet in non-sleeping areas.
G. When several laboratories are contiguous an. d within applicable total area limitations, the labs may be considered as one room.
H. Engineered Smoke Control/Evacuation System will be considered on a case- by-case basis, depending on building design and other fire protection features utilized. Generally, there will be no equivalences given for such systems.
I. Local fire department support for the building design must be considered. Generally, totally sprinklered buildings will be the most
economical design.
J. References:
1. National Fire Protection Association Codes - current edition.
2. Uniform Building Code - current edition (for building type only).
3. MIL-HDBK-1191 - Department of Defense Medical and Dental Treatment Facilities Design and Construction Criteria.
4. MIL-HDBK-1691 - Construction and Medical Schedule for MilitaryMedical and Dental Facilities - current edition.
JULY 1988 12REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
17/648
Mechanical Schedule
JULY 1988 13REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
18/648
Mechanical Schedule(Cont'd)
MECHANICAL NOTES
GENERAL NOTES (Cont'd)
4. HEPA filters having DOP test efficiencies of 99.9% shall be used on air supply systems serving rooms used for clinical treatment of patients with a high susceptibility to infection from leukemia and burns. They
shall also be used on the exhaust discharge air from fume hoods or safety cabinets in which infections or highly radioactive materials are processed and shall be designed and equipped to permit safe removal, disposal and replacement of contaminated filters.
For radioactive exhaust, use nuclear grade HEPA filters with DOP efficiency at 97.97% at 0.3 micron.
5. See MIL-HDBK-1191 for additional requirements.
SPECIFIC NOTES
6. Air Supply will in general, be obtained from adjacent areas, mechanicalexhaust will be provided.
7. The Oral Surgery Operating Rooms will be treated as medical operating rooms. Normal treatment other than oral surgery will be performed in dental treatment rooms.
8. Hood exhausts and equipment exhausts will be considered in balance of supply and exhaust air quantities.
9. Four low air exhausts will be provided for improved distribution of clean air and removal of contaminants in operating room.
10. Audiobooth air supply and return will be through sound attenuating ducts and discharge silencers supplied by the manufacturer. The building supply and return ducts will be connected directly to the audiobooth silencers. These connections will be coordinated with the audiobooth manufacturer.
11. The Bedroom shall be negative to the anteroom, positive to the toilet and the anteroom shall be negative to corridor for a normal isolation room. For positive isolation room, reverse air flow and increase filtration to 95% efficiency except for toilet, which will remain negative.
12. Not Used
13. Temperature and humidity control required.
14. Separate packaged air conditioning unit may be required.
15. The soiled side of all undercounter Nurse Servers must e supplied with
on exhaust connection form beneath, when ceiling exhaust cannot be utilized.
JULY 1988 14REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
19/648
Mechanical Schedule(Cont'd)
MECHANICAL NOTES
SPECIFIC NOTES (Cont'd)
16. Equipment vent connection required.
17. Exhaust from this room must pass through a filter before being released to atmosphere.
18. Equipment heat loads must be taken into account for calculation purposes.
JULY 1988 15
-
8/13/2019 Medical Design Guide
20/648
Mechanical Schedule(Cont'd)
PIPING NOTES
GENERAL NOTES
1. Treatment Rooms - Provide Oxygen and Medical Vacuum in Clinic Treatment Room and Oxygen, Medical Air and Medical Vacuum in Nursing Unit Treatment Room.
2. Medical Gas Remote Zone Panel will be located in the area.
3. Medical Gas Remote Alarm Panel will be located in the room.
4. This area to contain plaster trap under the sink.
5. Refer to Patient Service Console/Service Column for distribution of Medical Gases.
6. One MG-3 required for each 6-8 Bassinets.
7. One MG-3 required for each Observation Bassinet and for each 6-8 Cont. Care Bassinets.
8. Refer to Mechanical Schedule page 17 and 18 for details of Dental Utility Center.
9. Room requires Acid Waste plumbing.
10. Waste Water from this room must be diverted into a Holding Tank and not into the sanitary waste system.
JULY 1988 16
-
8/13/2019 Medical Design Guide
21/648
Mechanical Schedule(Cont'd)
JULY 1988 17
-
8/13/2019 Medical Design Guide
22/648
Mechanical Schedule(Cont'd)
JULY 1988 18
-
8/13/2019 Medical Design Guide
23/648
Mechanical Schedule(Cont'd)
JULY 1988 19
-
8/13/2019 Medical Design Guide
24/648
Electrical Schedule
ELECTRICAL NOTES
GENERAL NOTES
1. Ambient illumination levels listed in matrix data are maintained averages for the space, measured in footcandles on a horizontal plane at work plane height and based on the following effective reflectances:
A. Operation Rooms, Delivery Rooms and similar locations:
Walls - 70% Ceilings - 80% Floors - 20%
B. General Rooms with gypsum wallboard ceilings and walls:
Walls - 50% Ceilings - 80% Floors - 20%
C. General Rooms with lay-in tile ceiling:
Walls - 50% Ceilings - 70% Floors - 20%
D. Darkrooms and other film processing rooms:
Walls - 0% Ceilings - 0% Floors - 0%
E. Eye test and eye exam rooms:
Walls - 30% Ceilings - 50% Floors - 20%
F. Rooms with wall mounted luminaires having non-symmetricaldistribution:
Walls - 50%Ceilings - Effective reflectance based on IES
calculation and IES fig. 9-11Floors - 20%
2. Luminaire type designation applies only to layouts shown on reflected ceiling plans, and are not functional requirements. When required, utilize 40 watt, rather than 35 watt, fluorescent lamps with appropriate ballast (i.e. color improved lamp or dimmed fixture).
JULY 1988 20
-
8/13/2019 Medical Design Guide
25/648
Electrical Schedule (Cont'd) ELECTRICAL NOTES
GENERAL NOTES-(Cont'd)
3. Switching:
Std. Single on-off switch adjacent to entrance controlling all general room lighting.
Std-by Areas Each area controlled by separate switch adjacent to entrance or as indicated. Ext External, to be controlled from central location. Dim Lighting controlled by a single dimmer switch in Std. location. Fluorescent lighting luminaires shall be equipped with dimmable ballasts and 40 watt lamps. Multi-Sw Multiple switching, by separate switches adjacent to entrance, of multilamp luminaires e.g., 4-lamp
luminaire having two switches each disconnecting one 2-lamp ballast from supply circuit.
4. Ambient and task illumination levels shown are from recommended levels specified in MIL-HDBK 1191, Appendix "A" and supplemented by the Illumination Engineering Society and Committee Report CP-29 (Lighting
for Health Care Facilities) and IES Lighting Handbook 1987 Application Volume.
SPECIFIC NOTES
5. In radiology rooms provide wall mounted direct/indirect 4 ft. cove lighting luminaires, units mounted in continuous rows.
6. Dark Room, 20 fc. average under normal white light only. Safe light receptacle and darkroom in-use light separately switched at standard location. Film loading bin, when provided, shall have drawer limit switch to be interlocked with normal light and safelight/in-use light to shut off normal light and turn on safe light/in-use light if bin drawer is opened or in open position. Provide switched duplex receptacle for safe light.
7. Scrub area lighting controlled by local switch(es).
8. 25% of lighting shall be provided with battery back-up and separately switched
9. Not Used
10. Illumination should be provided by special fluorescent lamps producing light at CRI of 90-100. Color temperature, 5000 degree Kelvin.
11. Minimum light ratios of 5:1 (clear or laminated mirror glass) or 2:1 (grey mirror glass) must be obtainable from the Group Therapy Room, and other observed rooms, to the Mirror Room. Increased ratios to 10:1 and
4:1, respectively, are preferred.
JULY 1988 21REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
26/648
Electrical Schedule (Cont'd)
ELECTRICAL NOTES
SPECIFIC NOTES (Cont'd)
12. Reading light, connected to emergency branch circuit, to be controlled by switch in nurse call handset. Reading light may be wall or ceiling mounted to permit reading in a bed at an angle of 35 to 65 degrees, as
well as straight down. Luminaire is to provide 30 fc minimum on reading material at any position.
13. Examination light to be controlled by switch at patient service console.
14. In patient bedrooms, wall mounted uplight/downlight luminaire mounted 6'-6" above finished floor over the beds. Controlled individually from switch on patient service console. All bedroom uplight may be controlled by common switch. Utilize offset type I.V. pole with electrically operated beds to prevent damaging luminaire.
15. Night lights, connected to emergency branch circuit, will be photocell controlled, and be all on or all off . No switch at standard location or nurse station for night light control.
16. Observation light to be controlled by switch at patient service console, except in psychiatric units where they will be switched at the door.
17. X-ray room (having uncontrolled room access) door limit switch to be interlocked with X-ray unit control circuit to shut off or prevent production of X-rays if door is opened or in open position.
18. X-ray in-use light to be interlocked with X-ray unit power on-off control circuit, not X-ray control circuit.
19. Luminaires shall be equipped with RFI and EMI suppression.
20. Locate room to minimize RFI. Coordinate location of room with architects.
21. Not Used
22. Wiring connection as required by manufacturer. (GFI circuit protection required).
23. Not Used
24. Lighting luminaires above work station shall be connected to life safety branch as required to meet NFPA 101 emergency egress requirements.
25. One X-ray film processing room per department to be connected to emergency power.
26. Power supply requirements, exact quantity and location of enclosed circuit breaker disconnect switches and emergency push buttons shall be per manufacturer's recommendations.
JULY 1988 22
-
8/13/2019 Medical Design Guide
27/648
Electrical Schedule (Cont'd)
ELECTRICAL NOTES
SPECIFIC NOTES (Cont'd)
27. All electrical requirements, including luminaire and switching, shall be per manufacturer's requirements.
28. Dedicated circuit required for equipment.
29. 15% to 25% of lighting shall be provided with 30 minute battery back up and separate switch.
30. Provide a minimum of one simplex receptacle for each infant care station.
31. Provide a minimum of four simplex receptacles for each infant care station.
32. Provide a minimum of sixteen simplex receptacles per ICU infant care station.
33. All utilities to casework must feed from below, utility columns from ceiling to casework are not acceptable.
34. Provide a minimum of one 2" conduit from each bed location to nurses station for physiological monitoring.
35. Provide a minimum of one Radiographic Room and associated support with emergency power.
36. All Remote Alarm Panel, Master Clock Panel, Master Telephone Console, and Security Monitors shall be located in this room.
37. Dimmer controls for group therapy and play therapy to be located in mirror room.
38. Refer to Patient Service Console/Service Column for electrical outlets and location.
39. Air conditioning equipment for this area shall be on emergency power.
40. Provide a minimum of eight simplex receptacles for each infant care station.
41. 5% of lighting shall be provided with 30 minute battery back-up and separately switched.
42. 25% of power shall be on emergency.
43. Provide empty conduit from antenna location to communication equipment.
44. Ceiling Lighting Fixtures must not be located directly over bassinet or infant care centers in Nurseries.
JULY 1988 23
-
8/13/2019 Medical Design Guide
28/648
Electrical Schedule (Cont'd)
LUMINAIRE SCHEDULE
COE DWG 40-06-04TYPE DESCRIPTION TYPE SH.
A1 2' x 4' recessed fluor. W/4-F40 CW lamps. 206C 19
A2 2' x 4 recessed fluor. W/4-F40 CWX lamps. 206C 19
B1 2' x 4 recessed fluor. W/2-F40 CW lamps. 206A 19
B2' 2' x 4' recessed fluor. W/2-F40 CWX lamps. 206A 19
C1 2' x 4' recessed fluor. W/3-F40 CW lamps. 206B 19
C2 2' x 4' recessed fluor. W/3-F40 CWX lamps. 206B 19
D1 2' x 4 recessed fluor. W/6-F40 CR50 (CRI 90) SIM TO 19 lamps. 206
D2 2' x 4' recessed fluor. W/6-F40 CWX lamps. SIM TO 19 206
D3 2' x 4' recessed fluor. W/6-F40 CW lamps. SIM TO 19 206
E1 4' surface wall mounted fluor. with up/ down light distribution, aluminum extrusion shell, acrylic prismatic lens on bottom, clear acrylic lens on top and F40 CW lamps (number as req'd) for continuous row mounting. Units may be in continuous extrusion housing. Mount at 18 below finish ceiling unless otherwise indicated.
E2 3' luminaire same as type "E1" except W/
F30 CW lamps (number as req'd)
E3 2' luminaire same as type "E1" except W/ F20 CW lamps (number as req'd)
F1 2 x 4 recessed fluor with 12 cell, 3" deep, semi-specular anodized aluminum parabolic louver and 2-F40 CW lamps.
F2 2 x 4 recessed fluor same type "F1" except W/ 3-F40 CW lamps.
G1 6" x 4' recessed fluor with 1-F40 CW lamp. SIM TO 19 204
G2 6" x 3' recessed fluor with 1-F30 CW lamp. SIM TO 19 204
JULY 1988 24
-
8/13/2019 Medical Design Guide
29/648
Electrical Schedule (Cont'd)
LUMINAIRE SCHEDULE COE DWG 40-06-04TYPE DESCRIPTION TYPE SH.
G3 6" x 2' recessed fluor with 1-F30 lamp. SIM TO 19 204
H1 4' luminaire similar to type "E1" except with uplight only and F40 CW lamp(s) (number as req'd).
H2 3 luminaire similar to type "E1" except with uplight only and F30 CW lamp(s) (number as req'd).
H3 2' luminaire similar to type "E1" except with uplight only and F20 CW lamp(s) (number as req'd).
J1 4 luminaire similar to type "E1" except with uplight only and F40 CWX lamp(s) (number as req'd).
J2 3' luminaire similar to type "E1" except with
uplight only and F30 CWX lamp(s) (number as req'd).
J3 2 luminaire similar to type "E1" except with uplight only and F20 CWX lamp(s) (number as req'd).
K Patient reading light (specification to be developed).
L1 4' single lamp enclosed undercounter mounted fluor w/acrylic prismatic lens, rocker switch and 1-F40 CW lamp.
L2 3' luminaire same as type "L1" except with 1-F30 CW lamps.
L3 2' luminaire same as type "L1" except with 1-F20 CW lamps.
M1 4' luminaire same as type "E1" except with F40 CWX lamps (number as req'd).
M2 3' luminaire same as type "E1" except with F40 CWX lamps (number as req'd).
N1 2' x 4' recessed, gasketed fluor with gasketed SIM TO acrylic prismatic lens (smooth side down) 206C 19 gasketed door and frame, F40 CW lamps (number as req'd) and approved for damp locations.
P1 4' surface, wall mounted, enclosed fluor 223 17 with acrylic prismatic lens and 2-F40 CW lamps.
JULY 1988 25
-
8/13/2019 Medical Design Guide
30/648
-
8/13/2019 Medical Design Guide
31/648
Electrical Schedule (Cont'd)
JULY 1988 27
-
8/13/2019 Medical Design Guide
32/648
Electrical Schedule (Cont'd)
JULY 1988 28
-
8/13/2019 Medical Design Guide
33/648
Communication Schedule
COMMUNICATION NOTES
GENERAL NOTES
1. Telephone System: Total System including instruments - contractor furnished and installed. (Unless directed otherwise by OCE)
2. Public Address/Program Distribution System: Total System - Contractor
furnished and installed.
3. Nurse Call System: Total System - Contractor furnished and installed.
4. Room Status System: Total System - Contractor furnished and installed.
5. Central Clock System: Total System - Contractor furnished and installed.
6. Fire Alarm System: Total System - Contractor furnished and installed.
7. Television System (excluding CCTV System):
a. Conduits, antennas, amplifiers, splitters, terminations, outlets, and cables - Contractor furnished and installed.
b. TV mounting brackets, all types - Government furnished and Contractor installed.
c. Television cameras and receivers - Government furnished andinstalled.
8. Central Dictation System:
a. Conduits, cables and outlets - Contractor furnished and installed.
b. Equipment - Government furnished and installed.
9. Trimis System:
a. Conduits, cables, headend equipment, distribution amplifiers,splitters, couplers, and outlets - Contractor furnished and installed.
b. Data terminals, computers, and bus interface units/modems -Government furnished and installed.
10. Intrusion Detection System:
a. Conduits and outlets - Contractor furnished and installed.
b. Cables, sensors and equipment - Government furnished and installed.(unless directed otherwise by OCE)
11. Closed Circuit Television System:
a. Conduits and outlets - Contractor furnished and installed.
b. Cables, camera and monitors - Government furnished and installed.
JULY 1988 29
-
8/13/2019 Medical Design Guide
34/648
Communication Schedule(Cont'd)
COMMUNICATION NOTES
GENERAL NOTES
12. All trimis and television outlet locations will include a duplex electrical receptacle.
13. TV distribution and trimis system will utilize the same cable system. (unless directed otherwise by OCE)
14. All elapse time clocks will include remote controls.
SPECIFIC NOTES
15. Provide Room Status and Nurse Call Emergency Systems in Clinic Treatment Rooms and Nurse Call System with Single Patient Station and duty station in Nursing Unit Treatment Rooms.
16. Coordinate telephone and trimis outlets with Audiometric Room manufacturers.
17. Refer to Patient Service Console for communication requirements.
JULY 1988 30
-
8/13/2019 Medical Design Guide
35/648
-
8/13/2019 Medical Design Guide
36/648
Communication Schedule(Cont'd)
JULY 1988 32
-
8/13/2019 Medical Design Guide
37/648
Communication Schedule(Cont'd)
JULY 1988 33
-
8/13/2019 Medical Design Guide
38/648
Communication Schedule(Cont'd)
JULY 1988 34
-
8/13/2019 Medical Design Guide
39/648
Doctor's Office/Exam Room
JULY 1988 35REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
40/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 36REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
41/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 37REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
42/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 38REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
43/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 39REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
44/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 40REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
45/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 41REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
46/648
Doctor's Office/Exam Room (Cont'd)
JULY 1988 42REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
47/648
Patient Service Console
JULY 1988 43REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
48/648
Typical Med Gas Locations
SEPTEMBER 1994 43A
-
8/13/2019 Medical Design Guide
49/648
Patient Service Console (Cont'd)
JULY 1988 44REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
50/648
Patient Service Console (Cont'd)
JULY 1988 45REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
51/648
Patient Service Console (Cont'd)
JULY 1988 46REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
52/648
Patient Service Console (Cont'd)
JULY 1988 47REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
53/648
Patient Service Console (Cont'd)
JULY 1988 48
REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
54/648
-
8/13/2019 Medical Design Guide
55/648
Patient Service Console (Cont'd)
JULY 1988 50REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
56/648
Patient Service Console (Cont'd)
JULY 1988 51REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
57/648
Patient Service Console (Cont'd)
JULY 1988 52REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
58/648
Patient Service Console (Cont'd)
JULY 1988 53REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
59/648
Patient Service Console (Cont'd)
JULY 1988 54REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
60/648
Patient Service Console (Cont'd)
JULY 1988 55REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
61/648
Patient Service Console (Cont'd)
JULY 1988 56REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
62/648
Patient Service Console (Cont'd)
JULY 1988 57REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
63/648
Patient Service Console (Cont'd)
JULY 1988 58REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
64/648
-
8/13/2019 Medical Design Guide
65/648
X-ray Rooms Criteria(Cont'd)
d. Manufacturers are to meet a plus or minus five percent supply voltage regulation specification. The requirement for power conditioning equipment should be determined for each project.
e. Provide one 120/208v, three-phase panel per room with minimum of five circuits, located with breaker behind control booth.
f. Provide shunt trip breaker control switch located on recessed riser duct, 5 feet below ceiling height (see Enclosure - Elevation B).
(1) Must meet NFPA 70 requirments.
(2) To assure front clearance, this breaker may optionally be installed on Wall D through vertical riser D-1.
g. Provide main breaker with 150 amp rating located on Wall D behind panel*, and
(1) Include for selective circuit restoration.
(2) Assure for 3-1/2" feet "clear" in front of box face (NFPA 70).
(3) Locate 4'-0" below ceiling height.
* This feature may be combined with the shunt breaker on Wall B.
h. Provide duplex receptacles at 8'-0" on center, 18" above finished floor, with the following exceptions:
(1) Double duplex (4 outlets) located behing the control booth.
(2) Duplex located behind the table in open space of Wall A, and
(3) Duplex located at foot of table.
i. Where single phase is anticipated,k design the raceway system and breaker back box for 80 KW, three-phase capacity. Where three-phase is used, also install single phase for additional flexibility in the future.
j. Normally emergency power for X-ray equipment, illumination and duplex receptacles shall be provided through a manual transfer switch to one or two X-ray rooms (including one fluoroscopic unit, if applicable). One X-ray film processor is also included on the emergency power.
JULY 1988 60
-
8/13/2019 Medical Design Guide
66/648
X-ray Rooms Criteria(Cont'd)
k. Dedicated power:
(1) Where required, size for the smaller of the loads - two largest load or by the Line-Amperage method (largest load plus 22.5 percent of the remaining unit loads).
(a) Substations require nomninal unit loading of 10 to 15
percent of substation capacity.
(b) This substation sizing does not apply where only two units are supported, in which case the designer should investigate the history of brown-outs and the location of the transformers to determine the need for the dedicated power.
(2) Where not required, substation being utilized must not support motor loads but amore constant loading (i.e., lighting), and line losses shall be minimized to avoid X- ray contrast problems.
(3) Required for providing additional cooling to handle
transformer heat load where substations are located in electrical rooms to avoid build-up of excessive temperatures.
l. Illumination
(1) Illumination levels and dimmer devices for all Radiographic rooms shall be in accordance with DOD 4270.1M.
(2) Location of luminaires and X-ray viewing boxes are at the discretion of individual service or agency.
(3) Dimmers shall be nearly RFI propogation free.
3. Case Work:
a. Case work shall as shown on Guide Plates.
(1) A pass box shall be specified normally only where the dark room is adjacent to the radiology room. It may be installed for film storage at user's discretion.
(2) Refer to latest edition of DOD MIL-STD-1691 for the lost of other category "A" equipment.
b. Universal design shall include rough-in for hand sink, hot/cold water with drain, location as shown.
c. Warning lights and interlocks should be provided to meet safety regulations.
JULY 1988 61
-
8/13/2019 Medical Design Guide
67/648
X-ray Rooms Criteria(Cont'd)
4. Structural Support System:
a. Mechanical supporting devices on both sides of each vertical riser or vertical studs, shown on the Enclosure, shall:
(1) Provide floor-to-ceiling coverage in all cases with closure strips.
(2) Be capable of supporting static loads of 220 lbs. vertical-to-horizontal pull.
b. Ceiling grid, unistrut or equal:
(1) Spacing is 26" OC with 1-5/8" member thickness resulting in 2'-0" clearance between members and flush with accoustical ceiling.
(2) Ceiling grid channels shall be provided with closure strips.
(3) Dead Load bearing capacity.
(a) Vertical point loading is 800 to 900 pounds.
(b) Uniformly distributed load is 50 lbs.square foot.
c. Support system for ceiling mounted X-ray equipment (i.e., C arms) shall be designed to actual support requirements to suit the particular situation. Specify anchor supports and grid elements to suit situation.
5. Radiology Shielding
a. As a minimum:
(1) Comply with the design requirements of NRCP Nos. 33, 34, and 49, and certify accordingly.
(2) Lead shielding shall be 1/16 " thick up to 7' high above finished floor.
(3) Where possible, lead shielding shall be applied to exterior side of wall partitions behind gypsum board for protection.
b. Use of modular shielding (Ray Bar or equivalent) for operator's booth is encouraged.
c. Specify the operator's view window at 18" by 24" or nextavailable standard larger size.
d. All duct work, grilles, registers and diffusers shall belocated at a height higher than seven feet clear above thefinished floor. Thermostats with associated transmission lines
shall be surface mounted.
JULY 1988 62
-
8/13/2019 Medical Design Guide
68/648
X-ray Rooms Criteria (Cont'd)
JULY 1988 63
-
8/13/2019 Medical Design Guide
69/648
X-ray Rooms Criteria (Cont'd)
JULY 1988 64
-
8/13/2019 Medical Design Guide
70/648
X-ray Rooms Criteria (Cont'd)
JULY 1988 65
-
8/13/2019 Medical Design Guide
71/648
X-ray Rooms Criteria (Cont'd)
JULY 1988 66
REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
72/648
X-ray Rooms Criteria (Cont'd)
JULY 1988 67
-
8/13/2019 Medical Design Guide
73/648
-
8/13/2019 Medical Design Guide
74/648
Dr's Office/Exam RmMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 100 J.S.N. Log Code Nomenclature Qty Cat
Finishes -Walls - GW A5080 Dispenser, Paper Towel 2 A -Base - R A5115 Mirror 18 X 30 2 A -Floor - VCT A5145 Coat Hook 4 A -Ceiling - ACT A5180 Track & Curtain, Cubicle 2 ACeiling Ht - 8'-0" M1620 Record Holder 2 A P3100 Lavatory, Wall Hung 2 A X3830 Illuminator, X-ray Film 1 ADoor Size & Type - 36A X3930 Illuminator X-ray Film 1 AHardware Set - H01 F0210 Chair, Side 2 CAmbient Noise Level - NC 30-35 F0280 Chair, Rotary w/ Arms 1 CSpeech Privacy Level - Confidential F0300 Chair, Rotary w/o Arms 1 C F0635 Work Station, Doctor 1 CArchitectural Notes - 1 FC695 Work Station, Computer 1 C ref. pp. 5-6 F2000 Waste Receptacle, Off 1 C
F2010 Waste Receptacle SS 1 C M3075 Cabinet, Exam Rm 1 CELECTRICAL M7425 Light, Exam, Mobile 1 C M4200 Otoscope/ Ophthalmoscope 1 CAmbient Illum (FC) - 50 M4100 Sphygmomanometer 1 CTask Illum (FC) - 100 M8830 Table Instrument 1 CLuminare Type - A2 M8945 Stool Revolving 1 C M9025 Table, Exam, Cab 1 CSwitching - Std
Electrical Notes -
MECHANICAL
Total Air Changes - 6
Outside Air Changes - 1.5Room Pressure (%) - 0Temperature (F) - Sum 78 Win 70
Relative Hum(%) - 30-60
Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0
Mechanical Notes
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 2 AWaste/Vent - Yes RSOSS Selector Switch 3 Button 2 AFloor Drain - No MDOOD Desk Outlet-18" AFF 2 ASteam - No MDOOW Wall Outlet-48" AFF 2 ACondensate - No
Piping Notes -
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
75/648
-
8/13/2019 Medical Design Guide
76/648
-
8/13/2019 Medical Design Guide
77/648
1.01.02 ATreatment RoomMatrix Data
ARCHITECTURAL/ACOUSTICS
Square Foot Area Net - (1) Clinic - 150 (2) Nursing Unit - 150
Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT(2) VCT - Ceiling - (1) ACT(2) ACTCeiling Ht - (1) 8'-6" - (2) 8'-6"
Door Size & Type - 48AHardware Set - H02Ambient Noise Level - NC 30-35Speech Privacy Level - Confidential
Architectural Notes - 2
ref. pp. 5-6
ELECTRICAL
Ambient Illum (FC) - (1) 50 (2) 50Task Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A2 - (2) A2
Switching - (1) Std by Area - (2) Std by Area
Electrical Notes -
MECHANICAL
Total Air Changes - (1) 4 (2) 6Outside Air Changes - (1) 1 (2) 1.5Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70
Relative Hum(%) - (1) 30-60 (2) 30-60
Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,80,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - Yes QtyHot Water - YesTreated Water - No (1) MG-2 - 1Chilled Water - No (2) MG-3 - 2Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No
-
8/13/2019 Medical Design Guide
78/648
Piping Notes - 1 ref. pp. 16EQUIPMENT PROGRAM
J.S.N. LogCode Nomenclature Qty Cat
C02Q0 Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 A
C04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS150 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 1 AM3800 Desk, Folding, Wall Mount 1 AM4740 Light, Exam, Ceiling 1 AM5960 Coat Hook 2 AM7960 Track Curtain, Cubicle 1 AX3990 Illuminator X-ray Film 1 AM4001 Otoscope/ Ophthalmoscope 1 BM4460 Sphygmomanometer 1 BF2010 Waste Receptacle SS 1 C
M3051 Defibrillator w/Cart 1 CM7100 Table Exam., Cab 1 CM7400 Table Instrument 1 CM7415 Stand Mayo 1 CM7705 Stool, Revolving 1 CM8160 Scale, Weighing 1 C
COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty Cat
NC001 Single Patient Station 1 ANCODL Dome Light - 3 Lamp 1 ANCOEL Dome Light w/Chime 1 ANCOET Pullcord Station, Emer 1 A
NCOOD Duty Station 1 APAOMO Ceiling Speaker-Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch 3 Button 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A
Communication-Notes - 15 ref. pp. 29-30JULY 1988
-
8/13/2019 Medical Design Guide
79/648
-
8/13/2019 Medical Design Guide
80/648
-
8/13/2019 Medical Design Guide
81/648
-
8/13/2019 Medical Design Guide
82/648
-
8/13/2019 Medical Design Guide
83/648
1.01.03 ASoiled Utility - CLMatrix Data
ARCHITECTURAL ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R
- Floor - VCT C01C0 Cabinet, U/C, Base 1 A - Ceiling - ACT C02Q0 Cabinet, U/C, Sink 1 ACeiling Ht - 8'-0" CC010 Cabinet, Wall Hung 1 ADoor Size & Type - 36D CS140 Sink, SS, Counter 1 AHardware Set - H19 CT030 Counter Top - P.L 1 AAmbient Noise Level - NC 35-40 M3620 Dispenser, Paper Towel 1 ASpeech Privacy Level - Noncritical P6350 Sink, SVC, Wall Hung 1 A M2020 Trashcan, Mobile 2 C M4500 Hamper, Linen 2 C
Architectural Notes
ELECTRICAL
Ambient Illum (FC) - 20Task Illum (FC) - 20Luminare Type - B1Switching - Std
Electrical Notes -
MECHANICAL
Total Air Changes - 6Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - Yes
Return Air - NoFiltration(%) - 25,0,0
Mechanical Notes
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatChilled Water - NoWaste/Vent - Yes TLOOW Wall Outlet-54" AFF 1 AFloor Drain - No TSOOW Wall Outlet-36" AFF 1 ASteam - NoCondensate - No
Piping Notes
JULY 1988
-
8/13/2019 Medical Design Guide
84/648
JULY 1988
-
8/13/2019 Medical Design Guide
85/648
JULY 1988
-
8/13/2019 Medical Design Guide
86/648
JULY 1988
-
8/13/2019 Medical Design Guide
87/648
JULY 1988 1.01.04 A
-
8/13/2019 Medical Design Guide
88/648
Satellite LabMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 80 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT CC020 Cabinet, Wall Hung 1 A - Ceiling - ACT C0045 Drawer Unit, Double - 36"L 1 A
Ceiling Ht - 8'-0" C06C0 Cabinet, UC, Base 1 ADoor Size & Type - 36G C06D0 Cabinet U/C, Base 1 AHardware Set - H03 C07C0 Cabinet U/C, Base 1 AAmbient Noise Level - NC 30-35 C07A0 Cabinet, U/C, Sink 1 ASpeech Privacy Level - Normal CS150 Sink, SS, Counter 1 A CT030 Counter Top - P.L. 1 A M3620 Dispenser, Paper Towel 1 A F2000 Waste Receptacle, Off 1 CArchitectural Notes - R6200 Refrigerator, U/C, Lab 1 C
ELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) - 100
Luminare Type - C1Switching - Std-by Area
Electrical Notes - 42 ref pp 20-23MECHANICAL
Total Air Changes - 6Outside Air Changes - 1.5Room Pressure (%) - - 10Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - YesReturn Air - NoFiltration (%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No TL00W Wall Outlet-54" AFF 1 AWaste/Vent - Yes TS00D Wall Outlet-18" AFF 1 AFloor Drain - NoSteam - NoCondensate - No
Piping Notes -
JULY 1988
-
8/13/2019 Medical Design Guide
89/648
JULY 1988
-
8/13/2019 Medical Design Guide
90/648
JULY 1988
-
8/13/2019 Medical Design Guide
91/648
JULY 1988
-
8/13/2019 Medical Design Guide
92/648
JULY 1988
-
8/13/2019 Medical Design Guide
93/648
1.01.05 AReception AreaMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 120 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT C0045* Drawer Unit, Single - 36"L 1 A - Ceiling - ACT C0046 Drawer Unit, Double - 48"L 2 A
Ceiling Ht - 8'-0" C06D0 Cabinet, U/C, Base 2 ADoor Size & Type - 36A C06M0 Cabinet U/C, Base 2 AHardware Set - H03 F0224 Reception Counter 1 AAmbient Noise Level - NC 30-35 F0300 Chair, Rotary w/o Arms 2 CSpeech Privacy Level - Normal F0460 Cabinet, Filing, 5 Drw 1 C
Architectural Notes - * Removable Drawer Sections
ELECTRICAL
Ambient Illum (FC) - 30Task Illum (FC) - 70Luminare Type - B1,L1,Q1Switching - Std-by Area
Electrical Notes -
MECHANICAL
Total Air Changes - 4Outside Air Changes - 1Room Pressure (%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - NoHot Water - No QtyTreated Water - NoChilled Water - No MG-ZA - 1Waste/Vent - NoFloor Drain - NoSteam - NoCondensate - No
Piping Notes - 2ref. pp. 16
COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty CatNCOAP Clinic Annunciator Panel 1 APAOOM Desk Microphone 1 APAOVR Volume Ctrl. W/By-Pass Relay 1 ARSOAP Annunciator Panel, Desk 1 AMDOOC Counter Outlet - 6" Above CT 2 AMDOOW Wall Outlet - 48" AFF 1 A
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
94/648
-
8/13/2019 Medical Design Guide
95/648
-
8/13/2019 Medical Design Guide
96/648
-
8/13/2019 Medical Design Guide
97/648
-
8/13/2019 Medical Design Guide
98/648
1.02.01 ATrauma RoomMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - CT Code Nomenclature Qty Cat - Base - ET
- Floor - ET CE040 Cabinet, Wall Hung 1 A - Ceiling - GWT CE050 Cabinet, Wall Hung 1 ACeiling Ht - 9'-6" C02Q0 Cabinet U/C, Sink 1 ADoor Size & Type - 48A/18A C04J0 Cabinet U/C, Base 1 AHardware Set - H16 C05E0 Cabinet U/C, Base 1 AAmbient Noise Level - NC 30-35 CS150 Sink, SS, Counter 1 ASpeech Privacy Level - Confidential CT030 Counter Top - P.L. 1 A M3620 Dispenser, Paper Towel 2 A M4802 Light, Surgical, Ceiling 1 A M5540 Patient SVC Column 1 A M7960 Track & Curtain, Cubicle 1 AArchitectural Notes - M8000 IV Track 1 A P6950 Scrub Sink w/Knee Control 1 A X3990 Illuminator, X-ray Film 1 A
M4001 Otoscope/Ophthalmoscope 1 BELECTRICAL M4460 Sphygmomanometer 1 B F1938 Table, Treatment, ER 1 CAmbient Illum (FC) - 100 F2010 Waste Receptacle SS 1 CTask Illum (FC) - 100 M3051 Defibrillator w/ Cart 1 CLuminare Type - D1 M7400 Table, Instrument 1 CSwitching - Multi-Sw M7415 Stand Mayo 1 C M7705 Stool, Revolving 2 C
Electrical Notes - 8,34,38 ref pp 20-23
MECHANICAL
Total Air Changes - 12
Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - Yes QtyHot Water - Yes
Treated Water - No M5540 - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No
Piping Notes - 5ref. pp. 16
COMMUNICATION PROGRAM
Commo Log
-
8/13/2019 Medical Design Guide
99/648
Code Nomenclature Qty Cat
NCO01 Single Patient Station 1 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOOW Wall Outlet - 54" AFF 1 ATLOKH CAPOC Outlet 1 ATSOOH Trimis Outlet 1 A
TSOOW Wall Outlet-36" AFF 1 A
Communication Notes - 17 ref pp 29-30JULY 1988
-
8/13/2019 Medical Design Guide
100/648
JULY 1988
-
8/13/2019 Medical Design Guide
101/648
JULY 1988
-
8/13/2019 Medical Design Guide
102/648
JULY 1988
-
8/13/2019 Medical Design Guide
103/648
JULY 1988
-
8/13/2019 Medical Design Guide
104/648
1.02.02 ATrauma Room - 2 TableMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 300 J.S.N. LogFinishes - Walls - CT Code Nomenclature Qty Cat - Base - ET - Floor - ET CE040 Cabinet, Wall Hung 2 A
- Ceiling - GWT C02Q0 Cabinet U/C, Sink 1 ACeiling Ht - 9'-6" C04J0 Cabinet U/C, Base 1 ADoor Size & Type - 48A/18A C04L0 Cabinet U/C, Base 1 AHardware Set - H16 CS150 Sink, SS, Counter 1 AAmbient Noise Level - NC 30-35 CT030 Counter Top - P.L. 1 ASpeech Privacy Level - Confidential M3620 Dispenser, Paper Towel 2 A M4740 Light, Exam, Ceiling 2 A M5540 Patient SVC Column 2 A M7960 Track & Curtain, Cubicle 2 A M8000 IV Track 2 AArchitectural Notes - P6950 Scrub Sink w/Knee Control 1 A X3990 Illuminator, X-ray Film 2 A M4001 Otoscope/Ophthalmoscope 2 BELECTRICAL M4460 Sphygmomanometer 2 B
F1938 Table, Treatment, ER 2 CAmbient Illum (FC) - 100 F2000 Waste Receptacle SS 2 CTask Illum (FC) - 100 M3051 Defibrillator w/ Cart 1 CLuminare Type - D1 M7400 Table, Instrument 2 CSwitching - Std By Area M7405 Pail 2 C M7410 Carriage 2 C M7415 Stand Mayo 2 C M7705 Stool Revolving 2 C
Electrical Notes - 8,34,38 ref pp 20-23
MECHANICAL
Total Air Changes - 12
Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - YesHot Water - Yes Qty
Treated Water - No M5540A - 1Chilled Water - NoWaste/Vent - YesFloor Drain - NoSteam - NoCondensate - No
Piping Notes - 5 ref. pp. 16
COMMUNICATION PROGRAM
Commo Log
-
8/13/2019 Medical Design Guide
105/648
Code Nomenclature Qty Cat
NC001 Single Patient Station 2 ANCOOS Staff Station 1 ANCODL Dome Light - 3 Lamp 1 APAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 1 ATLOKH CAPOC Outlet 2 ATLOOW Wall Outlet-54" AFF 1 ATSOOH Trimis Outlet 2 A
TSOOW Wall Outlet-36" AFF 1 A
Communication Notes - 17 ref pp 29-30
JULY 1988
-
8/13/2019 Medical Design Guide
106/648
-
8/13/2019 Medical Design Guide
107/648
-
8/13/2019 Medical Design Guide
108/648
-
8/13/2019 Medical Design Guide
109/648
-
8/13/2019 Medical Design Guide
110/648
1.02.03 AER Treatment CubicleMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 120 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R
- Floor - VCT M3620 Dispenser, Paper Towel 2 A - Ceiling - ACT M4802 Light, Exam, Ceiling 3 ACeiling Ht - 8'-6" M5542J Patient SVC Column - ER 3 ADoor Size & Type - M7960 Track & Curtain, Cubicle 3 AHardware Set - M8000 IV Track 3 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall Hung 2 ASpeech Privacy Level - Confidential P9145 Bath, Nursing Table 1 A M4001 Otoscope/Ophthalmoscope 3 BArchitectural Notes - M4460 Sphygmomanometer 3 B F1938 Table, Treatment, ER 3 C F2010 Waste Receptacle SS 3 CELECTRICAL
Ambient Illum (FC) - 100
Task Illum (FC) - 100Luminare Type - D1Switching - Multi-Sw
Electrical Notes - 8,34,38 ref pp 20-23
MECHANICAL
Total Air Changes - 12Outside Air Changes - 3Room Pressure (%) - + 10Temperature (F) - Sum 75 Win 75Relative Hum(%) - 30-60
Exhaust Air - NoReturn Air - YesFiltration (%) - 25,80,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - Yes QtyHot Water - YesTreated Water - No M5542J - 3Chilled Water - NoWaste/Vent - YesFloor Drain - No
Steam - NoCondensate - No
Piping Notes - 5 ref. pp. 16
COMMUNICATION PROGRAM
Commo Log Code Nomenclature Qty Cat
NCO01 Single Patient Station 3 ANCODL Dome Light - 3 Lamp 3 A
-
8/13/2019 Medical Design Guide
111/648
PAOOV Volume Control 1 APAOMO Ceiling Speaker-Music Only 2 ATLOOH Service Console Outlet - 54" AFF 3 ATSOOH Trimis Outlet 3 A
Communication Notes - 17 ref pp 29-30
JULY 1988
-
8/13/2019 Medical Design Guide
112/648
JULY 1988
-
8/13/2019 Medical Design Guide
113/648
JULY 1988
-
8/13/2019 Medical Design Guide
114/648
JULY 1988
-
8/13/2019 Medical Design Guide
115/648
JULY 1988 1.02.04 A
-
8/13/2019 Medical Design Guide
116/648
Central CommoMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 200 J.S.N.Log
Finishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A4020 Clock, Central System 1 A
- Ceiling - ACT C0043 Drawer Unit, Single - 24" L 1 ACeiling Ht - 8-O C0044 Drawer Unit, Single - 30" L 1 ADoor Size & Type - 36G C0045 Drawer Unit, Single - 36" L 2 AHardware Set - H07 C06D0 Cabinet, U/C, Base 1 AAmbient Noise Level - NC 30-35 C06M0 Cabinet, U/C, Base 3 ASpeech Privacy Level - Normal C08F0 Cabinet, U/C, Base 1 A C09J0 Cabinet, U/C, Base 1 A CT030 Counter Top - P.L 1 A F3050 Chalkboard, WCP, 36X48 1 A F3000 Bulletin Board 1 A
Architectural Notes - F0300 Chair, Rotary w/o Arms 4 C M4010 Radio Communications Equip. 1 C
ELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) - )-Luminare Type - B1Switching - Std by Area
Electrical Notes - 8,36,39,43 ref. pp. 20-23
MECHANICAL
Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0
Temperature(F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0
Mechanical Notes - 18 ref. pp. 13-15
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - No Commo LogHot Water - No Qty Code Nomenclature Qty CatTreated Water - No
Chilled Water - No MG-RA - 1 CCOOM Master Control Unit 1 AWaste/Vent - No CCOOW Wall Outlet 1 AFloor Drain - No FAOCP Main Control Panel 5 ASteam - No NCOOD Duty Station 1 ACondensate - No PAOOM Desk Microphone 1 A TLOMC Master Control Console 1 APiping Notes - 3 MDOOC Counter Outlet-6" Above CT 4 A ref. pp. 16 CTOOM Monitor Outlet 1 C
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
117/648
-
8/13/2019 Medical Design Guide
118/648
-
8/13/2019 Medical Design Guide
119/648
-
8/13/2019 Medical Design Guide
120/648
-
8/13/2019 Medical Design Guide
121/648
1.02.05 ADecon ShowerMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 225 J.S.N. Log Code Nomenclature Qty CatFinishes - Walls - CT
- Base - CT P9320 Floor Drain w/Primer 2 A - Floor - CT N/A Hand Held Shower - Ceiling - GW-SGCeiling Ht - 8'-0"Door Size & Type - 48AHardware Set - H08Ambient Noise Level - NC 35-40Speech Privacy Level - Not Critical
Architectural Notes -
ELECTRICAL
Ambient Illum (FC) - 30
Task Illum (FC) -))
Luminare Type - N1Switching - Std
Electrical Notes -
MECHANICAL
Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(% - -20Temperature (F) - Sum 78 Win 70Relative Hum(%) - N/AExhaust Air - YesReturn Air - No
Filtration(%) - 25,0,0
Mechanical Notes - 17 ref pp 13-15
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No TLOWP Wall Outlet, WP-54" AFF 1 AWaste/Vent - YesFloor Drain - YesSteam - No
Condensate - No
Piping Notes - 10 ref pp 16JULY 1988
-
8/13/2019 Medical Design Guide
122/648
-
8/13/2019 Medical Design Guide
123/648
-
8/13/2019 Medical Design Guide
124/648
-
8/13/2019 Medical Design Guide
125/648
-
8/13/2019 Medical Design Guide
126/648
1.02.06 AScreeningMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 60 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A
- Ceiling - ACT A5115 Mirror, 18 x 30 1 ACeiling Ht - 8'-0" M1620 Record Holer 1 ADoor Size & Type - 36A P3100 Lavatory, Wall Hung 1 AHardware Set - H01 F0300 Chair, Rotary w/o Arms 1 CAmbient Noise Level - NC 30-35 F0640 Desk, Single Ped 1 CSpeech Privacy Level - Confidential F2095 Chair, Stacking 1 C M4025 Scale, Weighing 1 C M4100 Sphygmomanometer 1 CArchitectural Notes -
ELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) - )-
Luminare Type - A1Switching - Std
Electrical Notes -
MECHANICAL
Total Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No MDOOD Desk Outlet-18" AFF 1 ASteam - NoCondensate - No
Piping Notes -
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
127/648
-
8/13/2019 Medical Design Guide
128/648
-
8/13/2019 Medical Design Guide
129/648
-
8/13/2019 Medical Design Guide
130/648
-
8/13/2019 Medical Design Guide
131/648
1.04.01 AImmunization Room
Matrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 200 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat
- Base - R - Floor - VCT M0381 Record Holder 1 A - Ceiling - ACT M3150 Clock, Elapsed Time 1 ACeiling Ht - 8'-0" M3162 Clock, Electric 1 ADoor Size & Type - 48A M3620 Dispenser, Paper Towel 1 AHardware Set - H01 M5252 Medicine SVC Center 1 AAmbient Noise Level - NC 30-35 M7960 Track & Curtain, Cubicle 1 ASpeech Privacy Level - Confidential P3100 Lavatory, Wall Hung 1 A F0300 Chair, Rotary w/o Arms 1 C F0640 Desk. Single Ped 1 C F2010 Waste Receptacle SS 1 CArchitectural Notes - F2095 Chair, Stacking 1 C M3051 Defibrillator w,/ Cart 1 C M5325 Apparatus, Injection 1 C
M7300 Table, Exam., SS 1 C M7400 Table, Instrument 1 C M7415 Stand Mayo 1 CELECTRICAL R6090 Refrigerator, Dual Temp 1 C
Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A1Switching - Multi-Sw & Std by Area
Electrical Notes -
MECHANICAL
Total Air Changes - 4
Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty Cat
Treated Water - NoChilled Water - No MG-2 - 1 CCOOW Wall Outlet 1 AWaste/Vent - Yes NCOEL Dome Light w/Chime 1 AFloor Drain - No NCOET Pullcord Station, Emer 1 ASteam - No PAOMO Ceiling Speaker-Music Only 1 ACondensate - No PAOOV Volume Control 1 A RSODL Indicator Light, 3 Lamp 1 APiping Notes - RSOSS Selector Switch, 3 Button 1 A TLOOD Desk Outlet-18" AFF 1 A TSOOW Wall Outlet-36" AFF 1 A
JULY 1988
-
8/13/2019 Medical Design Guide
132/648
JULY 1988
-
8/13/2019 Medical Design Guide
133/648
JULY 1988
-
8/13/2019 Medical Design Guide
134/648
JULY 1988
-
8/13/2019 Medical Design Guide
135/648
JULY 1988
-
8/13/2019 Medical Design Guide
136/648
1.05.01 AECG Testing/Work RmMatrix Data
ARCHITECTURAL/ACOUSTICS
Square Foot Area Net - (1) Testing - 125(2) Work - 110
Finishes - Walls - (1) GW (2) GW
- Base - (1) R (2) R- Floor - (1) VCT (2) VCT- Ceiling - (1) ACT (2) ACT
Ceiling Ht - (1) 8'-0" (2) 8'-0"Door Size Type - (1) 48A (2) 36AHardware Set - (1) H02 (2) H02Ambient Noise Level - NC 30-35Speech Privacy Level - Normal
Architectural Notes -
ELECTRICAL
Ambient Illum (FC) - (1) 50 (2) 50Tad( Illum (FC) - (1) 100 (2) 100Luminare Type - (1) A1 (2) A1
Switching - (1) Std by Area (2) Std
Electrical Notes -
MECHANICAL
Total Air Changes - (1) 4 (2) 4Outside Air Change - (1) 1 (2) 1
Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70
Relative Hum(%) - (1) 30-60 (2) 30-60
Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0
Mechanical Notes -
MECHANICAL PIPING
Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - NoPiping Notes -
EQUIPMENT PROGRAM
-
8/13/2019 Medical Design Guide
137/648
J.S.N LogCode Nomenclature Qty Cat
C0200 Cabinet, U/C, Sink 1 AC04E0 Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 1 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 A
M5300 Mirror 14 x 20 1 AM5960 Coat Hook 2 AM7960 Track & Curtain, Cubicle 1 AP3100 Lavatory, Wall Hung 1 AF0300 Chair, Rotary w/o Arms 2 CF0405 Cabinet, Filing, 5 Drw C 1 CF0780 Table, Work 1 CF2000 Waste Receptacle, Off 1 CF2010 Waste Receptacle SS 1 CM4400 Electrocardiograph 1 CM7100 Table, Exam., Cab 1 C
COMMUNICATION PROGRAM
Commo LogCode Qty Cat
PAOMO Ceiling Speaker - Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 ATLOOD Desk Outlet - 18" AFF 1 ATLOOK CAPOC Outlet 2 ATLOOW Wall Outlet - 54" AFF 1 ATSOOW Wall Outlet - 36" AFF 2 A
JULY 1988
-
8/13/2019 Medical Design Guide
138/648
JULY 1988
-
8/13/2019 Medical Design Guide
139/648
JULY 1988
1.05.01 D
-
8/13/2019 Medical Design Guide
140/648
ECG Testing/Work Rm
JULY 1988
-
8/13/2019 Medical Design Guide
141/648
1.05.01 E ECG Testing/Work Rm
JULY 1988
-
8/13/2019 Medical Design Guide
142/648
1.05.02 ATreadmill RoomMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 150 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A4015 Clock, Elapsed Time 1 A
- Ceiling - ACT A4020 Clock, Electric 1 ACeiling Ht - 9'- 0" A5080 Dispenser, Paper Towel 1 ADoor Size & Type - 48A A5115 Mirror 18 X 30 1 AHardware Set - H02 A5145 Coat Hook 2 AAmbient Noise Level - NC 35-40 M1620 Record Holder 1 ASpeech Privacy Level - Normal P3100 Lavatory, Wall hung 1 A F0300 Chair, Rotary w/o Arms 1 C F0640 Desk, Single Ped 1 C F2000 Waste Receptacle, Off 1 CArchitectural Notes - F2095 Chair, Stacking 1 C M7655 Defibrillator w/Cart 1 C M7705 Electrocardiograph 1 C M8830 Treadmill 1 C
ELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) - 50Luminare Type - C1Switching - Std
Electrical Notes -
MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60
Exhaust Air - NoReturn Air - YesFiltration(%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING COMMUNICATION PROGRAMCold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-3 - 1 CCOOW Wall Outlet 1 AWaste/Vent - Yes PAOMO Ceiling Speaker-Music Only 1 AFloor Drain - No PAOOV Volume Control 1 ASteam - No RSODL Indicator Light, 3 Lamp 1 A
Condensate - No RSOSS Selector Switch, 3 Button 1 A MDOOD Desk Outlet-18" AFF 1 APiping Notes - MDOOW Wall Outlet - 48" AFF 1 AJULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
143/648
-
8/13/2019 Medical Design Guide
144/648
-
8/13/2019 Medical Design Guide
145/648
-
8/13/2019 Medical Design Guide
146/648
-
8/13/2019 Medical Design Guide
147/648
1.06.01 APulmonary FunctionMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A
- Ceiling - ACT A5115 Mirror 18 x 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 1 ADoor Size Typo - 36A M1620 Record Holder 1 AHardware Set - H01 P3100 Lavatory, Wall Hung 1 AAmbient Noise Level - NC 35-40 F0210 Chair Side 1 CSpeech Privacy Level - Normal F0300 Chair Rotary w/o Arms 2 C F0640 Desk, Single Ped 1 C M0720 Analyzer, Pulmonary 1 C
Architectural Notes -
ELECTRICAL
Ambient Illum (FC) - 50
Task Illum (FC) - 100Luminare Type - C1Switching - Std
Electrical Notes
MECHANICAL
Total Air Changes - 6Outside Air Changes - 1.5Room Pressure(%) - -10Temperature (F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - Yes
Filtration() - 25,0,0
Mechanical Notes
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-3 - 1 PAOMO Ceiling speaker-Music Only 1 AWaste/Vent - Yes PAOOV Volume Control 1 AFloor Drain - No RSODL Indicator Light, 3 lamp 1 ASteam - No RSOSS Selector Switch 3 button 1 ACondensate - No MDOOD Desk Outlet-18" AFF 1 A
Piping Notes -
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
148/648
-
8/13/2019 Medical Design Guide
149/648
-
8/13/2019 Medical Design Guide
150/648
-
8/13/2019 Medical Design Guide
151/648
1.07.01 A
-
8/13/2019 Medical Design Guide
152/648
Proctoscopy SuiteMatrix Data
ARCHITECTURAL/ACOUSTICS
Square Foot Area Net - (1) Procto Area - 150 (2) Toilet - 30
Finishes - Walls - (1) GW (2) GW-SG
- Base - (1) R (2) CT - Floor - (1) VCT (2) CT - Ceiling - (1) ACT (2) GWCeiling Ht - (1) 8'-6" (2) 8'-0"
Door Size & Type - (1) 48A (2) 36AHardware Set - (1) H02 (2) H13Ambient Noise Level - (1) NC30-35 (2) NC35-40Speech Privacy Level - (1) Confid (2) Normal
Architectural Notes - (1) 2 (2) 19 ref. pp. 5-6
ELECTRICAL
Ambient Illum (FC) - (1) 50 (2) 20Task Illum (FC) - (1) 100 (2) )-Luminare Type - (1) A2 (2) R1
Switching - (1) Std by Area (2) Std
Electrical Notes
MECHANICAL
Total Air Changes - (1) 6 (2) 10
Outside Air Changes - (1) 1.5 (2))-
Room Pressure(%) - (1) (2) - 100Temperature (F) - (1) Sum 78 Win 70 (2) Sum )- Win )-
Relative Hum(%) - (1) 30-60 (2) ))Exhaust Air - (1) Yes (2) YesReturn Air - (1) No (2) NoFiltration(%) - (1) 25,0,0 (2) ))
Mechanical Notes - (2) 6 ref. pp. 20-23
MECHANICAL PIPING
Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No
Piping Notes -
-
8/13/2019 Medical Design Guide
153/648
EQUIPMENT PROGRAM
J.S.N. LogCode Nomenclature Qty CatC02QO Cabinet, U/C Sink 1 AC04EO Cabinet, U/C Base 1 AC04JO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 2 ACS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L. 1 A
M0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 AM3800 Desk, Folding, Wall Mount 1 AM4600C Grab Bar, Toilet-36"x48" 1 AM4740 Light, Exam, Ceiling 1 AM5300 Mirror 14 X 20 1 AM5960 Coat Hook 2 AM7960 Track & Curtain, Cubicle 1 AP3000 Lavatory, Wall Hung 1 AP9050 Water Closet 1 AX3990 Illuminator, X-ray Film 1 AM4460 Sphygmomanometer 1 BF2010 Waste Receptacle SS 1 CM3051 Defibrillator w/Cart 1 C
M7366 Table, Exam, Procto 1 CM7400 Table, Instrument 1 CM7415 Stand, Mayo 1 CM7705 Stool, Revolving 1 C
COMMUNICATION PROGRAMCommo LogCode Nomenclature Qty Cat
NCOEL Dome Light W/Chime 2 ANCOET Pullcord Station, Emer 2 APAOMO Ceiling Speaker-Music Only 1 APAOOV Volume Control 1 ARSODL Indicator Light, 3 Lamp 1 A
RSOSS Selector Switch, 3 Button 1 ATLOOW Wall Outlet-54" AFF 1 ATSOOW Wall Outlet-36" AFF 1 A
JULY 1988
-
8/13/2019 Medical Design Guide
154/648
JULY 1988
-
8/13/2019 Medical Design Guide
155/648
JULY 1988
-
8/13/2019 Medical Design Guide
156/648
JULY 1988
-
8/13/2019 Medical Design Guide
157/648
JULY 1988
-
8/13/2019 Medical Design Guide
158/648
1.08.01 AWeights & MeasuresMatrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A
- Ceiling - ACT A5115 Mirror 18 x 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 2 ADoor Size & Type - 36A A5180 Track & Curtain, Cubicle 1 AHardware Set - H01 M1620 Record Holder 1 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall hung 1 ASpeech Privacy Level - Confidential F0210 Chair, Side 1 C F0300 Chair, Rotary w/o Arms 1 C F0640 Desk, Single Ped 1 C F1907 Table, Equip. Hold 1 CArchitectural Notes - M4010 Scale, Infant 1 C M4040 Scale, Weighing 1 C M4100 Sphygmomanometer 1 CELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Std
Electrical Notes
MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature(F) - Sum 78 Win 70Relative Hum(%) - 30-60Exhaust Air - NoReturn Air - Yes
Filtration(%) -25,0,0
Mechanical Notes
MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch 3 Button 1 AFloor Drain - No MDOOD Desk Outlet-18" AFF 1 ASteam - No MDOOW Wall Outlet-48" AFF 1 ACondensate - No
Piping Notes -
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
159/648
-
8/13/2019 Medical Design Guide
160/648
-
8/13/2019 Medical Design Guide
161/648
1.10.01 AEEG Testing/Work RmMatrix Data
ARCHITECTURAL/ACOUSTICS
Square Foot Area Net - (1) Work - 130 (2) Testing - 90
Finishes - Walls - (1) GW (2) GW - Base - (1) R (2) R - Floor - (1) VCT(2)VCT - Ceiling - (1) ACT(2)ACTCeiling Ht - (1) 8'-0" (2) 8'-0"
Door Size & Type - (1) 30A,36A(2) 48AHardware Set - (1) H02(2) H02Ambient Noise Level - NC 25-30Speech Privacy Level - Confidential
Architectural Notes -
ELECTRICAL
Ambient Illum (FC) - (1) 70 (2) 0-20Task Illum (FC) - )) (2) 100Luminare Type - (1) A1 (2) A1
Switching - (1) Multi-Sw (2) Dim
Electrical Notes - (1) 20 (2) 9,20 ref. pp. 20-23
MECHANICAL
Total Air Changes - (1) 4 (2) 4Outside Air Changes - (1) 1 (2) 1Room Pressure(%) - (1) 0 (2) 0Temperature (F) - (1) Sum 78 Win 70 (2) Sum 78 Win 70
Relative Hum(%) - (1) 30-60 (2) 30-60
Exhaust Air - (1) No (2) NoReturn Air - (1) Yes (2) YesFiltration(%) - (1) 25,0,0 (2) 25,0,0
Mechanical Notes
MECHANICAL PIPING
Cold Water - YesHot Water - Yes QtyTreated Water - NoChilled Water - No (2) MG-2 - 1Waste/Vent - YesFloor Drain - NoSteam - NoCondensate - No
-
8/13/2019 Medical Design Guide
162/648
Piping Note -
EQUIPMENT PROGRAM
J.S.N. LogCode Nomenclature Qty Cat
C0200 Cabinet, U/C, Sink 1 AC04EO Cabinet, U/C, Base 1 ACE040 Cabinet, Wall Hung 1 A
CS140 Sink, SS, Counter 1 ACT030 Counter Top - P.L 1 AM0381 Record Holder 1 AM3620 Dispenser, Paper Towel 2 AM5300 Mirror 14 X 20 1 AM5960 Coat Hook 1 AP3100 Lavatory, Wall Hung 1 AF0105 Bed Hospital, Manual 1 CF0300 Chair, Rotary w/o Arms 1 CF0405 Cabinet, Filing, 5 Drw 1 CF0780 Table, Work 1 CF2000 Waste Receptacle, Off 2 CM3702 Electroencephalograph 1 C
COMMUNICATION PROGRAM
Commo LogCode Nomenclature Qty Cat
RSODL Indicator Light, 3 Lamp 1 ARSOSS Selector Switch, 3 Button 1 ATLOOW Wall Outlet-54" AFF 2 ATSOOW Wall Outlet-36" AFF 2 A
JULY 1988
-
8/13/2019 Medical Design Guide
163/648
JULY 1988
-
8/13/2019 Medical Design Guide
164/648
JULY 1988
-
8/13/2019 Medical Design Guide
165/648
JULY 1988
-
8/13/2019 Medical Design Guide
166/648
JULY 1988
1.11.01 A
-
8/13/2019 Medical Design Guide
167/648
Cast RoomMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 280 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - IV - Floor - SV C03EO Cabinet, U/C, Base 3 A - Ceiling - ACT C03JO Cabinet, U/C. Base 2 ACeiling Ht - 8'-6" C04PO Cabinet, U/C, Sink 1 A
Door Size & Type - 36G,18G CE030 Cabinet, Wall Hung 2 AHardware Set - H05 CE080 Cabinet, Wall Hung 1 AAmbient Noise Level - NC 30-35 CS190 Sink, SS, Counter 1 ASpeech Privacy Level - Non-Critical CT030 Counter Top - P.L 3 A M0381 Record Holder 1 A M3620 Dispenser, Paper Towel 1 A M7960 Track & Curtain, Cubicle 2 AArchitectural Notes - 6 P7600 Plaster Trap 1 A ref. pp. 5-6 X3830 Illuminator, X-ray Film 2 A M2020 Trashcan, Mobile 1 C M4700 Light, Exam, Mobile 1 C M6200 Cast Cutter/Vacuum 2 C M7300 Table Exam., SS 2 CELECTRICAL M7400 Table Instrument 2 C
M7415 Stand Mayo 2 CAmbient Illum (FC) - 50Task Illum (FC) - 50Luminare Type - C1Switching - Std by Area
Electrical Notes -
MECHANICALTotal Air Changes - 10 LogOutside Air Changes - 1.5 CatRoom Pressure(%) - - 10 ATemperature (F) - Sum 78 Win 70 ARelative Hum(%) - 30-60 AExhaust Air - Yes A
Return Air - No AFiltration(%) - 25,0,0 A
Mechanical Notes -MECHANICAL PIPING COMMUNICATION PROGRAM
Cold Water - Yes Commo LogHot Water - Yes Qty Code Nomenclature Qty CatTreated Water - NoChilled Water - No MG-2 - 1 PAOMO Ceiling Speaker-Music Only 2 AWaste/Vent - Yes PAOOV Volume Control 1 AFloor Drain - No RSODL Indicator Light, 3 Lamp 1 ASteam - No RSOSS Selector Switch, 3 Button 1 ACondensate - No TLOOW Wall Outlet-54" AFF 1 A
TSOOW Wall Outlet-36" AFF 1 APiping Note - 4 ref. pp. 16JULY 1988
-
8/13/2019 Medical Design Guide
168/648
JULY 1988
-
8/13/2019 Medical Design Guide
169/648
JULY 1988
-
8/13/2019 Medical Design Guide
170/648
JULY 1988
-
8/13/2019 Medical Design Guide
171/648
JULY 1988
-
8/13/2019 Medical Design Guide
172/648
1.12.01 AENT Exam RoomMatrix DataARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 100 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT A5080 Dispenser, Paper Towel 1 A
- Ceiling - ACT A5115 Mirror 18 X 30 1 ACeiling Ht - 8'-0" A5145 Coat Hook 2 ADoor Size & Type - 36A A5180 Track & Curtain, Cubicle 1 AHardware Set - H01 M1620 Record Holder 1 AAmbient Noise Level - NC 30-35 P3100 Lavatory, Wall Hung 1 ASpeech Privacy Level - Confidential X3830 Illuminator, X-ray Film 1 A F0300 Chair, Rotary w/o Arms 1 C F0695 Work Station, Computer 1 C F2010 Waste Receptacle SS 1 CArchitectural Notes - M4915 Chair, Exam 1 C M5510 Cabinet, ENT 1 C M7425 Light, Exam, Mobile 1 C M8540 Microscope ENT 1 C M8945 Stool, Revolving 1 C
ELECTRICALAmbient Illum (FC) - 50Task Illum (FC) - 100Luminare Type - A2Switching - Std
Electrical Notes -
MECHANICALTotal Air Changes - 4Outside Air Changes - 1Room Pressure(%) - 0Temperature (F) - Sum 78 Win 68Relative Hum(%) - 30-60Exhaust Air - No
Return Air - YesFiltration(%) - 25,0,0
Mechanical Notes -
MECHANICAL PIPING COMMUNICATION PROGRAMCold Water - Yes Commo LogHot Water - Yes Code Nomenclature Qty CatTreated Water - NoChilled Water - No RSODL Indicator Light, 3 Lamp 1 AWaste/Vent - Yes RSOSS Selector Switch, 3 Button 1 AFloor Drain - No MDOOD Wall Outlet-18" AFF 1 ASteam - No MDOOW Wall Outlet-48" AFF 1 ACondensate - No
Piping Notes -
JULY 1988REVISED SEPTEMBER 1994
-
8/13/2019 Medical Design Guide
173/648
-
8/13/2019 Medical Design Guide
174/648
-
8/13/2019 Medical Design Guide
175/648
1.12.02 AAudio Testing (Sm)Matrix Data
ARCHITECTURAL/ACOUSTICS EQUIPMENT PROGRAM
Square Foot Area Net - 110 J.S.N. LogFinishes - Walls - GW Code Nomenclature Qty Cat - Base - R - Floor - VCT M0300 Audiometric Booth 2 A
- Ceiling - ACT M0381 Record Holder 1 ACeiling Ht - 9'-0" M5960 Coat Hook 1 ADoor Size & Type - 48A F0300 Chair, Rotary w/o Arms 1 CHardware Set - H01 F0780 Table, Equipment 1 CAmbient Noise Level - NC 35-40 F2000 Waste Receptacle, Off 1 CSpeech Privacy Level - Non-Critical F2095 Chair, Stacking 1 C M0255 Audiometer 1 CArchitectural Notes - 3 ref. pp. 5-6
ELECTRICAL
Ambient Illum (FC) - 50Task Illum (FC) -
Luminare Type - C1Switching - Std