message management pguard7 configurator · 2019. 10. 24. · pguard7 configurator 7 fig. 3-3...

36
English Rev. 3.0.0 / 2016-08-29 Configuration Message Management PGuard7 Configurator

Upload: others

Post on 02-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • English

    Rev. 3.0.0 / 2016-08-29

    Configuration

    Message Management PGuard7

    Configurator

  • PGuard7 Configurator

    www.dallmeier.com 2

    Information about Copyright, Trademarks, Design Patents

    © 2016 Dallmeier electronic

    The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.

    We reserve the right to make technical modifications.

    The manufacturer accepts no liability for damage to property or pecuniary damages arising due to minor defects of the product or documentation, e.g. print or spelling errors, and for those not caused by intention or gross negligence of the manufacturer.

    Dallmeier electronic GmbH & Co.KGCranachweg 193051 Regensburg, Germany

    [email protected]

    All trademarks identified by ® are registered trademarks of Dallmeier electronic.

    All trademarks identified by *) are trademarks or registered trademarks of the following owners:

    Third-party trademarks are named for information purposes only.Dallmeier electronic respects the intellectual property of third parties and always attempts to ensure the complete identification of third-party trademarks and indication of the respective holder of rights. In case that protected rights are not indicated separately, this circumstance is no reason to assume that the respective trademark is unprotected.

  • PGuard7 Configurator

    www.dallmeier.com 3

    Table of Contents

    1 Introduction ...................................................................................................41.1 Validity .............................................................................................................41.2 Documents ......................................................................................................41.3 Typographical Conventions.............................................................................4

    2 General Notes................................................................................................52.1 Appropriate Use ..............................................................................................52.2 Performance Features ....................................................................................52.3 Warranty .........................................................................................................5

    3 User Interface ................................................................................................63.1 Representation................................................................................................63.2 Customize Overviews .....................................................................................83.2.1 Expand ............................................................................................................83.2.2 Sort .................................................................................................................93.3 Language ........................................................................................................9

    4 Import ...........................................................................................................104.1 Automatically.................................................................................................104.2 Manually........................................................................................................124.2.1 Senders.........................................................................................................124.2.2 Receivers ......................................................................................................13

    5 Configuration ..............................................................................................155.1 Message Settings .........................................................................................155.1.1 Create A Processing Type .............................................................................155.1.2 Edit Messages ..............................................................................................175.2 Receiver Types .............................................................................................205.2.1 Activate Sender.............................................................................................215.2.2 Assign Processing Types ..............................................................................215.2.3 Apply Filters ..................................................................................................225.2.4 Activate Messages ........................................................................................245.2.5 Receivers Assignment ..................................................................................245.2.6 Receiver Search Mode .................................................................................265.3 Message States ............................................................................................265.3.1 Define A New State .......................................................................................265.3.2 Edit Message State .......................................................................................285.4 Configuration Subalarm ................................................................................285.5 Database Maintenance .................................................................................335.6 Program Status .............................................................................................345.7 Manage Connections ....................................................................................365.7.1 PGuard7 Database .......................................................................................365.7.2 SeMSy® III .....................................................................................................36

  • PGuard7 Configurator

    www.dallmeier.com 4

    1 Introduction

    1.1 ValidityThis document applies to the software ConfiguratorforPGuard7. It was created based on the software version 7.3.2.7.

    Illustrations in this document may differ from the actual product.

    1.2 DocumentsInstallationInstructions to install the software (for trained system integrators)

    Configuration(thisdocument)Instructions for configuring the software (for trained system integrators)

    1.3 Typographical ConventionsFor reasons of clarity and readability, various text formatting elements and types of em-phasis are used in this documentation:

    NOTICE

    NOTICE indicates practices for preventing property damage, incorrect configurations or faulty operations.

    Instructions are indicated by arrows (). Always carry out instructions one after the other in the sequence described.

    Expressions in bold/italics generally indicate a control element on the device (switches or labels) or on its user interface (buttons, menu entries).

    Paragraphs in italics provide information on basic principles, special features and efficient procedures as well as general recommendations.

  • PGuard7 Configurator

    www.dallmeier.com 5

    2 General Notes

    2.1 Appropriate UseThe Software Configurator for PGuard7 is a powerful configuration tool for the database of aPGuard7 server for the centralized message management in a SeMSy® III video management system. This allows the creation of individual message profiles and their allocation to different recipients in a SeMSy® III system. In addition, the Configurator offers comprehensive functions for the maintenance of a PGuard7 database.

    2.2 Performance FeaturesThe Configurator for PGuard 7 is characterized by the following functions and properties:• Comfortable import function for all relevant devices and data of SeMSy® III systems• Central configuration of all clients• Create individual profiles message (receiver types) for different recipients• Creating individual message states• Comprehensive database maintenance functions

    2.3 WarrantyThe terms and conditions valid at the signing of the contract shall apply.

  • PGuard7 Configurator

    www.dallmeier.com 6

    3 User Interface

    3.1 RepresentationThe PGuard7 Configurator user interface is displayed in its default state after launching the software:

    Menu bar Configuration tabs Search configuration tabs

    Configuration selection Fig. 3-1

    Fig. 3-2 PGuard7 server connection management

    Use the Option Menu item in order to manage connections to PGuard7 servers and SeMSy® III databases (see in the following).

  • PGuard7 Configurator

    www.dallmeier.com 7

    Fig. 3-3 Message states configuration tab

    Search with the arrow buttons through the configuration tabs (see in the following).

    Fig. 3-4 Receiver overview and settings

    Use the Configuration selection in order to display the imported or manually created receivers and their settings (see in the following).

    The “User” and “Sites” management is not yet supported by the current version of the software.

  • PGuard7 Configurator

    www.dallmeier.com 8

    3.2 Customize OverviewsThe overview lists on the appropriate configuration tabs can be displayed completely for easier editing on a monitor. Additionally, lists can be sorted by each column.

    3.2.1 ExpandThe column lists on the Configuration tabs can be displayed in a complete overview and thus, are edited conveniently.

    The area of the “Configuration selection” can always be hidden in this way and so can be arranged a focused view of all configuration areas.

    Select the corresponding configuration tab.

    Fig. 3-5 Example configuration tab Message settings

    The Configuration selection area can be hidden in order to make a better overview for the configuration of the messages:

    Fig. 3-6 Example configuration tab Message settings

    Move the handle of the Configuration selection with drag and drop to the left side until the area is hidden.

  • PGuard7 Configurator

    www.dallmeier.com 9

    Expand the entire program window additionally with drag and drop until all columns are displayed if required.

    The messages can be configured now clearly.

    Restore the Configuration selection area by moving the handle to the right again.

    3.2.2 SortLists can be sorted to columns alphabetically or numerically ascending or descending.

    Select the corresponding configuration tab.

    Fig. 3-7 Detail configuration tab Processing types

    Click the name of a column to sort the overview by this.

    The arrow on the column border shows the direction of the sort.

    Click the name of the column again in orrder to change the direction of the sort.

    3.3 LanguageThe graphical user interface can be displayed in different languages.

    Open the Set system language dialog via Option > Set system language....

    Fig. 3-8

    Select the required language from the drop down box. Confirm with OK.

    The language of the user interface is changed immediately and without restarting the application.

  • PGuard7 Configurator

    www.dallmeier.com 10

    4 Import

    4.1 AutomaticallyThe PGuard7 Configurator software allows to import senders (encoders / decoders of a SeMSy® III system), receivers (workstations of SeMSy® III system) and layouts (configured split views for the evaluation of messages) automatically from a SeMSy® III database.

    Select the SeMSy import configuration tab.

    Fig. 4-1

    Sender Import

    Fig. 4-2

    Select the required import options (multiple selection possible):• Import encoders• Import decoders• Encoders/Decoders Names Sync. (if this option is activated, manually added / con-

    figured sender names will not be changed at a recent import) Click Start sender import. Note the displayed Progress bar and Status information.

  • PGuard7 Configurator

    www.dallmeier.com 11

    Wait until the import is finished.

    The list of the imported senders can be checked on the Sender tab:

    Fig. 4-3

    Receiver Import

    Fig. 4-4

    Click Start receiver import. Note the displayed Progress bar and Status information. Wait until the import is finished.

    NOTICE

    New receivers are assigned automatically to the “Default receiver type” profile. In this way, they have access to all messages in the database as long as they have not been configured with an individual message profile (“Receiver type”).

    The list of the imported receivers can be checked and edited in the Receiver view on the Configuration selection (see below).

  • PGuard7 Configurator

    www.dallmeier.com 12

    SeMSy® III Layout Import

    Fig. 4-5

    Click Start SeMSy layout import. Note the displayed Progress bar and Status information. Wait until the import is finished. Assign in the further course a SeMSy® III layout to messages in the Message settings and Processing types if required (see in the following).

    4.2 ManuallySenders and receivers can be even imported manually.

    4.2.1 SendersProceed as follows in order to add a sender (encoder / decoder) manually:

    Select the Sender tab. Click Add in order to open the Add new sender dialog.

    Fig. 4-6

    Enter Name, Path and IP Address of the new sender.

    The “Path” is an optional specification of the encoder’s path in the “Navigator” module. In this way, the structure of the devices can be copied from the “Navigator” to the sender overview in PGuard7 if required.

  • PGuard7 Configurator

    www.dallmeier.com 13

    Select the Login tab.

    Fig. 4-7

    Enter User name and Password for the device login. Enter the communication Port if required. Finally, click OK in order to save the settings.

    The new manually added sender will be displayed in the overview on the tab Sender:

    Fig. 4-8

    Manually added sender can be edited and deleted by the corresponding buttons on the configuration tab.

    4.2.2 ReceiversReceivers can be imported manually via the Configuration selection.

    Select the Receiver tab on the site view. Click Add in order to display the dialog Add new receiver.

    Fig. 4-9

    Enter the new Receiver name.

  • PGuard7 Configurator

    www.dallmeier.com 14

    Confirm with OK.

    The new manually added receiver is displayed in the Receiver overview.

    Fig. 4-10

    Manually added receiver can be deleted via the corresponding button.

  • PGuard7 Configurator

    www.dallmeier.com 15

    5 Configuration

    The imported senders (recording systems, encoders, decoders) are listed on the configu-ration tab Sender. On the following configuration tabs messages can be individually con-figured, organized into message profiles and assigned to receivers. In addition, general settings for the server database can be made.

    5.1 Message SettingsThe Message settings tab includes the standard message profile. It is assigned as the Default processing to the receivers which are not configured with an own receiver type.The settings of the individual messages can be changed directly in the standard over-view. However, it is advisable to create own Processing types (message profiles) which are assigned via Receiver types to the different receivers (workstations) in a SeMSy® III system. Messages can be edited directly in the default list in the tab Messages settings if no different message profiles (Processing types) are needed. If different message profiles for different receivers are required first a new processing type must be created on the tab Processing types. The messages can then be configured there according to the requirements.

    5.1.1 Create A Processing TypeThe behavior of messages can be configured individually on a processing type (message profile).In order to create a new processing type proceed as follows:

    Select the tab Processing types. Click Add in order to open the dialog Add new processing type.

    Fig. 5-1

    Enter a Name for the processing type. Confirm with OK.

    The newly created processing type is selected automatically:

    In order to switch between different processing types, these can be selected from the drop down menu.

  • PGuard7 Configurator

    www.dallmeier.com 16

    Drop down menu

    Fig. 5-2

    The messages can now be configured as described below.

    Delete A Processing TypeProcessing types can be removed.

    Select the required processing type from the drop down menu. Click Delete. Confirm the subsequent info dialog.

    When a processing type is deleted, which is used in a receiver type configuration, it will be replaced automatically by the default profile (“Default processing”) of the tab “Message settings”.

    Labeling Of Differences in Message SettingsDifferences in the settings between Processing types and the default messages of the Message settings tab are displayed in color in the respective processing type.

    Fig. 5-3 Detail tab Processing types

  • PGuard7 Configurator

    www.dallmeier.com 17

    5.1.2 Edit MessagesThe behavior of the individual messages can be determined accurately. The descriptions in this section are valid for the standard messages on the tab Message settings as well as message lists from Processing types.

    Select the required message profile (configuration tab Message settings or Process-ing types).

    Make the required settings as described below.

    Settings and changes are saved automatically. The time period for the communication between the Configurator and the corresponding PGuard7 server can be adjusted on the configuration tab “Program status” in the “Refresh interval” column (see section “Program Status” on page 34).

    Message IDThe Msg ID column shows the respective ID of the message. An ID is unique and can not be changed. The number after the hyphen denotes subalarms that have been added to the respective main message.

    Fig. 5-4

    Change Message DescriptionThe description of a message can be changed or adapted.

    Double-click in the Message column of the required message.

    Fig. 5-5

    Enter a new name or adjust the text to the requirements.

    Change PriorityThe Priority allows receivers to classify incoming messages according to their impor-tance. For this is a scale of 1 (very important) to 6 (less important) available.

    Double-click in the Priority column of the required message.

    Fig. 5-6

  • PGuard7 Configurator

    www.dallmeier.com 18

    Use the arrow buttons in order to set the message priority.

    Alarm SoundMessages can be combined with an alarm sound. The sound can be played once, end-lessly or n-times. Sound for messages is disabled by default.

    Double-click in the Sound column of the required message in order to display the drop down menu.

    Fig. 5-7

    Select the required option. Enter in the column Sound loop the number of required sound repetitions when the option Sound N times is enabled.

    Camera Live DisplayThe display of the live image of the corresponding camera can be activated upon the ar-rival of the message. This requires in the module PGuard on a workstation the definition of a corresponding split view for the live switch by messages (see documentation “Opera-tion” for “SeMSy® III Workstation Software”).

    The live activation of an encoder works only for camera-related messages (for example, camera contact, image comparison event etc.), in which the corresponding encoder num-bers are included.

    Enable the check box Show live of the required message for the display of the live image with the arrival of the message.

    SeMSy® III LayoutsIn the module PGuard of the SeMSy® III Workstation Software can be defined a layout (a preconfigured split view in the module Mainviewer) which is automatically activated when evaluating a message on the corresponding workstation (see documentation “Operation” for “SeMSy® III Workstation Software”). This layouts that are defined in the module can be selected here for the message.

    Double-click the SeMSy Layout column of the required message in order to display the drop down menu.

    Fig. 5-8

  • PGuard7 Configurator

    www.dallmeier.com 19

    Select the required SeMSy® III layout which should be used for the message.

    ConfirmMessagesManuallyMessages can be confirmed with an input. For this purpose, a simple keyboard input may be required or a specific text phrase.

    Double-click the column Confirm properties in order to display the drop down menu.

    Fig. 5-9

    Select the required option:• Text needed: Any arbitrary text must be entered for the message confirmation.• Text phrase necessary: In order to confirm the message must be entered exactly

    the text phrase from the following column. Enter the text phrase for the confirmation of the message in the column Confirm phrase when this option is selected.

    IntervalForAutomaticConfirmationMessages can even be automatically confirmed after a certain time.

    Double-click the column Auto confirm time of the required message.

    Fig. 5-10

    Set the required confirmation interval (in minutes) with the arrow buttons.

    MessageStatesAfterAutomaticConfirmationMessages can be assigned to a certain state after an automatic confirmation. By default, messages remain after an automatic confirmation in the state New. There are predefined also the other states Confirmed and Auto Confirmed.The predefined states can be edited and new states can be configured on the tab Mes-sage states (see below).

    Double-click the column Auto confirm state of the required message in order to dis-play the drop down menu.

    Fig. 5-11

  • PGuard7 Configurator

    www.dallmeier.com 20

    Select the required state after an automatic confirmation.

    5.2 Receiver TypesFor receivers (workstations) different Receiver types can be created. In this recipient profiles are configured senders, message profiles and message states. In this way, the reception of messages can be precisely controlled on different workstations.

    Note that• the default setting for receivers – the Default receiver type – always contains all send-

    ers and all messages unfiltered and can not be edited in his settings. • Processing types have got to be configured where the selection and the behavior of

    messages has been individualized in order to configure various Receiver types.

    AddFirst, define a new receiver type.

    Select the tab Receiver types. Click Add in order to create a new receiver type.

    Fig. 5-12

    Enter a Name for the receiver type. Confirm the new receiver type with OK.

    The new receiver type will be selected automatically.

    Select the respective required type from the drop down box in order to edit saved “Re-ceiver types” (see below).

    DeleteSelected Receiver types can be removed with Delete if required.

  • PGuard7 Configurator

    www.dallmeier.com 21

    5.2.1 Activate SenderThe senders (encoders, recording systems) must be enabeld from which the receiver type should receive messages.

    Select the tab Sender.

    All imported senders are listed on the tab Sender. At first, all senders inactive.

    Fig. 5-13

    Expand the sender directories in order to display the individual encoders / cameras of a recording system if required.

    Select the senders of which this receiver type should receiver messages (multiple selection with pressed CTRL key).

    Activate the senders selection.

    Active senders of a receiver type can be switched off quickly with “Deactivate” if required.

    5.2.2 Assign Processing TypesA processing type can be assigned with the various senders on the Processing tab. This defines a different dealing with messages for the senders.

    Select the tab Processing.

  • PGuard7 Configurator

    www.dallmeier.com 22

    Drop down menu for selection of the Processing typeFig. 5-14

    Select the required Sender. Double-click the field in the column Processing type. Select one of the previously configured Processing types from the displayed drop down menu.

    5.2.3 Apply FiltersThe Filter tab allows to filter messages of the selected receiver type in number and time. Thus, a maximum upper limit (default: 50) of message entries can be set and the time range (default: Today) can be accurate defined for incoming messages.In addition, the various message states can enabled (default: all inactive) and the refresh interval (default: 10 seconds) can be adapted to the requirements.

    Select the tab Filter.

    Fig. 5-15

  • PGuard7 Configurator

    www.dallmeier.com 23

    Number Of Message Entries Change the Max. number of entries with the arrow buttons which should be displayed in the module PGuard on a workstation (=receiver) at the same time as the top list if required.

    In this way, a clear message list (top list) can be achieved with this limitation of message entries in the module “PGuard” on a workstation. If the maximum number of entries is reached to displayed messages in the top list, the new messages automatically replace the last (oldest) message entries. However, in the PGuard7 database all messages are stored permanently and can be re-displayed for evaluation by the operator with a database query at any time.

    Set Time Range Select in the Time range area the required option and make the appropriate settings:

    The messages of the current day will be displayed in the receiver type with the default setting “Today”. The “Time period” option allows to define a very precise period of time and, for example, only to activate a receiver-type for a specific time length and also automatically switch it off again. The messages of the last n-days (including the current day) will be displayed with the option “Last days” for the receiver type.

    Message States Activate the required message states for the receiver type in the section Message state filter which should be displayed on the corresponding receivers (workstations).

    Messages in inactive message states are not displayed on this receiver type. In this way, messages can be filtered using this option by their state for the display on receivers. In addition to the three predefined message states (“New”, “Confirmed”, “Auto Confirmed”), own states can be created (see section “Message States” on page 26).

    Refresh Interval Modify the Refresh interval (in seconds) for the receive of message list updates on the relevant receivers with the arrow buttons if required.

    Depending on the network and the number of receivers can be a very short update inter-val (for example, one second) lead to a high system load.

  • PGuard7 Configurator

    www.dallmeier.com 24

    5.2.4 Activate MessagesMessages that should be received in general with the receiver type can be enabled or disabled on the tab Message filter.

    Select the tab Message filter.

    Selection menu message activityFig. 5-16

    All messages of the selected receiver type are by default once active.

    Select the required message. Double-click in the corresponding field of the Active column in order to display the Selection menu.

    Select the required activity state for the relevant message. In this way, enable / disable all messages required for the receiver type.

    5.2.5 Receivers AssignmentThe configured Receiver types must be assigned to the respective receivers.

  • PGuard7 Configurator

    www.dallmeier.com 25

    Configuration selection Receiver

    Imported receivers

    Drop down selection Receiver typeFig. 5-17

    Select the tab Receiver in the Configuration selection. Select the required receiver in the Imported receivers list.

    Fig. 5-18

    Select from the drop down list the required Receiver type which should be assigned to the receiver.

    The Receiver type is automatically assigned to the receiver and the receiver will receive immediately the messages as they have been configured in the selected Receiver type.

    Proceed as described above in order to assign other Receiver types to different re-ceivers if required.

  • PGuard7 Configurator

    www.dallmeier.com 26

    5.2.6 Receiver Search ModeThis feature allows an operator on a receiver (workstation) to search and evaluate the database with all messages. Possible restrictions for receiving messages from the asso-ciated receiver type for the live view do not apply to a database query. After a specified period of time (Return from search mode) the view database query is automatically closed and the live view will be enabled on the workstation again.

    The function “Search Database” can be operated and controlled by an operator in the module “PGuard” on the workstation if the option is enabled for a receiver (see documen-tation “Operation” for “SeMSy® III Workstation Software”).

    Activate the check box Enable search mode in order to activate the function for data-base search for the receiver if required.

    Entern the period of time (in minutes) for the option Return from search mode if re-quired.

    5.3 Message StatesMessage states indicate the status of a message in the module PGuard in color. In addition, messages can be filtered about their conditions within a SeMSy® III system and in this way can be controlled the distribution / display on receivers (see section “Message States” on page 23). There are predefined three messages states: New, Confirmed, Auto Confirmed. These can be edited in description and color. In addition, new message states can be defined for own requirements.

    5.3.1 DefineANewStateProceed as described here in order to define a new message state.

    Select the configuration tab Message state.

    Fig. 5-19

    Click Add State in order to display the configuration dialog.

  • PGuard7 Configurator

    www.dallmeier.com 27

    Fig. 5-20

    Enter in the field Label a name / description for the message state. Select a not yet allocated Confirmation status for the new message state.

    The “Confirmation status” are required for the database management of the message state. Note that states larger than 240 are final states for messages. The “Confirmation Status” of predefined states can not be changed.

    Select in the section State color a color for the new message state – either with direct input of a decimal R G B color code or with Select color... and the following configura-tion dialog.

    Finally, click Apply and Exit in order to save the new message state.

    The new message state is displayed in the Message state definitions window.

    New, user-defined message state

    Fig. 5-21

    Activate in the window Message state transitions a succession or transition status for the new message state if required.

    Afterwards, enable the new message state for the required Receiver types (see sec-tion “Apply Filters” on page 22).

  • PGuard7 Configurator

    www.dallmeier.com 28

    5.3.2 Edit Message StateThe settings of message states can be edited.

    Message states can be edited and customized in name and color. The confirmation states can not be changed.

    Fig. 5-22

    Select the required message state. Click Edit State in order to display the edit dialog.

    Fig. 5-23

    Make the required changes in the fields Label and State color. Confirm the inputs with Apply and Exit.

    5.4 ConfigurationSubalarmMessages can be triggered from individual cameras. Such camera-related events can be configured as subalarms for certain messages. This message information can also be specified with the exact camera name and number. In addition, the priority of subalarms can be configured independently of the actual main message.

    Proceed as described below in order to configure subalarms:

  • PGuard7 Configurator

    www.dallmeier.com 29

    Add Recording Systems Select the configuration tab Subalarm configuration.

    The overview of camera-related main messages will be displayed in the Message list.

    Fig. 5-24

    Select a main message in the list for which a subalarm should be added. Click Add sender in order to display the configuration dialog for sender selection.

    Fig. 5-25

    Select the required recording system from the drop down menu Sender. Enable the check box Default entry if required.

    If the check box “Default entry” is activated, the configuration of this sub-alarm is auto-matically applied to all recording systems to the respective main message.

    Click Apply and Exit in order to confirm the selection and close the configuration dialog.

  • PGuard7 Configurator

    www.dallmeier.com 30

    Added recording systems (senders) are displayed in a subdirectory of the main message.

    Directory added senders

    Fig. 5-26

    Click the displayed triangle next to a main message in order to display the added re-cording systems if required.

    Create Subalarms In the next step, select the main message in the Message list again. Click Add subalarm under the window Subalarm list in order to open the respective configuration dialog.

    Fig. 5-27

    Select a free, unused Subalarm ID from the drop down box. Enter a new Message name for the subalarm or adjust the description to the require-ments if required.

    Select the required Priority for the subalarm with the arrow buttons. Click Apply and Exit in order to confirm the inputs and close the dialog. Repeat the steps in order to create all required subalarms.

  • PGuard7 Configurator

    www.dallmeier.com 31

    The created subalarms are displayed in the Subalarm list.

    Fig. 5-28

    Add Cameras Now, select the recording system associated with the main message in order to add a camera to a subalarm.

    The created subalarms are displayed with the camera option in the Subalarm list.

    Fig. 5-29

    Select a subalarm and double-click the corresponding field of the required camera. Process analog for all other camera assignments.

    Multiple cameras can be linked to one subalarm.When a subalarm is deleted, the corresponding cameras will automatically be reassigned to the main message.

  • PGuard7 Configurator

    www.dallmeier.com 32

    Subalarm SettingsThe message settings can be configured differently from the settings of the main mes-sage personalized for the various Processing types for a subalarm.

    These settings are optional. The settings of the main message are automatically mapped to a subalarm.

    Select the configuration tab Processing types. Select the required processing type from the drop down menu.

    Fig. 5-30

    Select the required subalarm from the message list.

    Subalarms will be listed under the appropriate main message.

    Make the required settings for a subalarm as described in section “Edit Messages” on page 17.

    Messages modified from the default setting are displayed colored.

    Activate SubalarmsSubalarms must be activated in the various Receiver types (message profiles).

    Select the configuration tab Receiver types. Select the required receiver type from the drop down menu. Select the tab Message filter.

  • PGuard7 Configurator

    www.dallmeier.com 33

    Fig. 5-31

    Select the required subalarms in the message list.

    Subalarms will be listed under the appropriate main message.

    Double-click in the Active column of the required subalarm in order to display the drop-down menu.

    Open the drop-down menu with a single-click and select active in order to turn on the sub-alarm.

    Repeat the process for all required receiver types in order to activate the correspond-ing subalarms for them.

    5.5 Database MaintenanceMessages can be deleted from the PGuard7 database according to age or number – de-pending on the individual requirements of the database server.

    Select the configuration tab Deleter settings. Set the Deletion rules as described in the following.

    In each case, the states “Confirmed” and “Unconfirmed” are distinguished for messages. Corresponding values must be entered for both states. It is not possible, for example, to delete only confirmed messages from the database.

  • PGuard7 Configurator

    www.dallmeier.com 34

    Fig. 5-32

    Deletion On Time: Select the option Delete messages older than. Enter the period (in days) after which messages should be deleted from the database.

    Deletion On Quantity: Select the option Delete messages on quantity. Enter the required number of messages after which messages should be deleted from the database.

    Finally, set the Deletion interval (in minutes) after which the database will be regular-ly maintained.

    5.6 Program StatusThe status of the currently connected PGuard7 server can be queried via the dialog Pro-gram status.First, there must be established the connection to the required server database via the Manage Connection dialog if multiple PGuard7 servers are managed with the Configu-rator. In addition, the refresh interval of the connection between configurator and the PGuard7 database can be set (default: 10 seconds).

    Select the configuration tab Program status. Click Refresh info in order to display the query overview.

  • PGuard7 Configurator

    www.dallmeier.com 35

    Fig. 5-33

    The Status (On) of the current connected server will be updated and displayed.

    The refresh rate for the auto-update between Configurator and database will be dis-played in the column Refresh interval (seconds). This value can be changed – for example, for a better network performance:

    Double-click in the column Refresh interval (seconds) in order to enable the input. Enter the required value. Click Refresh info in order to activate the new interval.

    Delete EntriesDatabase entries that are no longer required can be deleted from the list.

    Fig. 5-34

    Click on the number of the required database entry in order to select this. Click Delete. Confirm the subsequent info dialog.

  • PGuard7 Configurator

    www.dallmeier.com 36

    5.7 Manage ConnectionsThe connection configuration dialogs allow to establish and maintain the connections to PGuard7 database servers or SeMSy® III database servers.

    5.7.1 PGuard7DatabaseIn the dialog Manage Connection the connection is configured for the current PGuard7 database.

    Open the dialog via Options > Manage Connections... in the menu bar.

    Fig. 5-35

    Enter in the appropriate fields the required connection data. Click Test in order to check the connection. Click Apply and Exit after a successful connection test in order to save the settings and close the dialog.

    5.7.2 SeMSy® IIIThe connection to the database of a SeMSy® III configuration server is required for the import of the sender and receiver. In a connection dialog the settings can be managed.

    Open the dialog via Options > SeMSyII/III Connection... in the menu bar.

    Fig. 5-36

    Enter in the appropriate fields the required connection data. Click Test in order to check the connection. Click Apply and Exit after a successful connection test in order to save the settings and close the dialog.

    1Introduction1.1Validity1.2Documents1.3Typographical Conventions

    2General Notes2.1Appropriate Use2.2Performance Features2.3Warranty

    3User Interface3.1Representation3.2Customize Overviews3.2.1Expand3.2.2Sort

    3.3Language

    4Import4.1Automatically4.2Manually4.2.1Senders4.2.2Receivers

    5Configuration5.1Message Settings5.1.1Create A Processing Type5.1.2Edit Messages

    5.2Receiver Types5.2.1Activate Sender5.2.2Assign Processing Types5.2.3Apply Filters5.2.4Activate Messages5.2.5Receivers Assignment5.2.6Receiver Search Mode

    5.3Message States5.3.1Define A New State5.3.2Edit Message State

    5.4Configuration Subalarm5.5Database Maintenance5.6Program Status5.7Manage Connections5.7.1PGuard7 Database5.7.2SeMSy® III