metering station flow data - flocontrol ltd | picv, abv, … · 2016-01-06 · double regulating...
TRANSCRIPT
Metering StationFlow Data
Sizes DN65 to 600
© FloControl Limited 2014
In this flow data manual we have endeavoured to make the information as accurate as possible.We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as aresult of further developments or otherwise.
Stainless Steel Metering StationTechnical Data
FloControl Limited Tel: 01282 564425Ribble Court, No. 1 Meadway Fax: 01282 564426Shuttleworth Business Park, Padiham email: [email protected], Lancashire BB12 7NG website: www.flocontrol.ltd.uk© FloControl Limited 2014
Flow Measurement The flow rate can be calculated using the Kvs value and a measured signal.
Kv = Q Kvs = Q √∅P √∅Ps where Kv & Kvs = flow coefficient (m3/hr at 1 bar differential) Q = flow rate (m3/hr) ∅P = headloss attributable to valve (bar) ∅Ps = differential pressure across tappings (signal) (bar)Kvs Values
Pressure Loss The pressure loss across the metering station can be determined by multiplying the signal by the pressure loss factor. The pressure loss is always less than measured signal.
Pressure Loss Factors
Size DN65 DN80 DN100 DN125 DN150 DN200 DN250 DN300
Kvs 100.7 133.8 237.7 339 511 858 1235 1793
Size DN65 DN80 DN100 DN125 DN150 DN200 DN250 DN300
Factor 0.40 0.40 0.35 0.35 0.35 0.35 0.35 0.35
Size DN350 DN400 DN450 DN500 DN600
Kvs 2260 2961 3741 4789 6866
Size DN350 DN400 DN450 DN500 DN600
Factor 0.35 0.35 0.35 0.35 0.35
Stainless Steel Metering StationTechnical Data
FloControl Limited Tel: 01282 564425Ribble Court, No. 1 Meadway Fax: 01282 564426Shuttleworth Business Park, Padiham email: [email protected], Lancashire BB12 7NG website: www.flocontrol.ltd.uk© FloControl Limited 2014
Installation Metering stations can be installed in isolation or close coupled to an oblique globe double regulating valve complying to BS 7350, of the same nominal diameter. Regardless of installation there must always be a minimum of 5 pipe diameters of straight pipe, without intrusion, upstream of the metering station. When used in isolation a minimum of 2 pipe diameters of straight pipe are required downstream of the metering station. When close coupled to an oblique double regulating valve no straight pipe is required after the valve. When used in conjunction with a butterfly double regulating valve, a spool piece equivalent to a minimum of 2 pipe diameters is required between the metering station and butterfly valve. For more detailed instructions please refer to the Installation, Operation and Maintenance Instructions supplied with the metering station.
ß Ratio The ß ratio is the ratio between the pipe bore and the orifice diameter. This range of metering stations has been designed using ß ratios selected to minimise the effects of variations in pipe bores.
Sizing Once the required flow rate has been calculated, the size of the metering station can be determined based on the following: The minimum signal at the design flow rate of 1 kPa. For minimum pressure loss, a maximum signal of 4.5 kPa, which corresponds to the maximum differential pressure range of a flurocarbon manometer. The recommended maximum flow velocity is 3 m/s, although for sizes up to and including DN150 a 2 m/s maximum velocity is recommended to minimise water noise.
5D 2D5D 5D3D
© FloControl Ltd 2014
Stainless Steel Metering StationDN65
Graph of Signal against Flow Rate.Velocity based on the inside diameter of BS EN 10255 Medium series pipe
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
1.5 2.0 3.0 4.0 5.0 6.0 8.0 10 15 FLOWRATE - l/s
VELOCITY - m/s0.5 0.75 1.0 1.5 2.0 2.5 3.0
Issue 1 DN65 Metering Station
Flow Coefficient Kvs = 100.7
Pressure Loss Factor = 0.40
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on the inside diameter of BS EN 10255 Medium series pipe
Stainless Steel Metering StationDN80
Issue 1 DN80 Metering Station
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
2.0 3.0 4.0 5.0 6.0 8.0 10 20 FLOWRATE - l/s
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.40
Flow Coefficient Kvs = 133.8
© FloControl Ltd 2014
Stainless Steel Metering StationDN100
Graph of Signal against Flow Rate.Velocity based on the inside diameter of BS EN 10255 Medium series pipe
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
4.0 5.0 6.0 8.0 10 20 30 FLOWRATE - l/s
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Issue 1 DN100 Metering Station
Flow Coefficient Kvs = 237.7
Pressure Loss Factor = 0.35
© FloControl Ltd 2014
Stainless Steel Metering StationDN125
Graph of Signal against Flow Rate.Velocity based on the inside diameter of BS EN 10255 Medium series pipe
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
5.0 6.0 8.0 10 20 30 40
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
FLOWRATE - l/s
Flow Coefficient Kvs = 339
Pressure Loss Factor = 0.35
Issue 1 DN125 Metering Station
© FloControl Ltd 2014
Stainless Steel Metering StationDN150
Graph of Signal against Flow Rate.Velocity based on the inside diameter of BS EN 10255 Medium series pipe
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
7.0 8.0 10 20 30 40 50 60
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
FLOWRATE - l/s
Flow Coefficient Kvs = 511
Pressure Loss Factor = 0.35
Issue 1 DN150 Metering Station
© FloControl Ltd 2014
Stainless Steel Metering StationDN200
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 206.5 mm.
0.4
0.6
0.8
2.0
1.0
3.0
4.0
5.0
6.0
8.0
10
20
30
10 20 30 40 50 60 70 80 100Flow Rate l/s
Sign
al k
Pa
Issue 1 DN200 Metering Station
Velocity m/s 0.4 0.5 0.75 1.0 1.2 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 858
© FloControl Ltd 2014
Stainless Steel Metering StationDN250
Issue 1 DN250 Metering Station
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
20 30 40 50 60 80 100 200 FLOWRATE - l/s
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 1235
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 260.4 mm.
© FloControl Ltd 2014
Stainless Steel Metering StationDN300
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 309.7 mm.
Issue 1 DN300 Metering Station
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
30 40 50 60 80 100 200 300 FLOWRATE - l/s
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 1793
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 339.6 mm.
Stainless Steel Metering StationDN350
Issue 1 DN350 Metering Station
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
30 40 50 60 80 100 200 300 FLOWRATE - l/s
VELOCITY - m/s 0.4 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 2260
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 388.8 mm.
Stainless Steel Metering StationDN400
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
50 60 80 100 200 300 400
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
FLOWRATE - l/s
Flow Coefficient Kvs = 2961
Pressure Loss Factor = 0.35
Issue 1 DN400 Metering Station
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 490.4 mm.
Stainless Steel Metering StationDN450
Issue 1 DN450 Metering Station
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
60 80 100 200 300 400 500 FLOWRATE - l/s
VELOCITY - m/s 0.4 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 3741
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 490.4 mm.
Stainless Steel Metering StationDN500
20
10
8.0
6.0
4.0
2.0
1.0
0.8
0.6
0.4
SIG
NA
L kP
a
30
80 100 200 300 400 500 600
VELOCITY - m/s 0.5 0.75 1.0 1.5 2.0 2.5 3.0
FLOWRATE - l/s
Flow Coefficient Kvs = 4789
Pressure Loss Factor = 0.35
Issue 1 DN500 Metering Station
© FloControl Ltd 2014
Graph of Signal against Flow Rate.Velocity based on BS EN 10220 pipe, inside diameter 592.4 mm.
Stainless Steel Metering StationDN600
0.4
0.5
0.6
0.8
2.0
1.0
3.0
4.0
5.0
6.0
8.0
10
20
30
100 200 300 400 500 600 700 800 900Flow Rate l/s
Sign
al k
Pa
Issue 1 DN600 Metering Station
Velocity m/s 0.4 0.5 0.75 1.0 1.5 2.0 2.5 3.0
Pressure Loss Factor = 0.35
Flow Coefficient Kvs = 6866