method for extracting positive and negative sequence current
TRANSCRIPT
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
1/7
1115
A Method for Extracting the Fundamental
Frequency Positive-Sequence Voltage Vector Basedon Simple Mathematical Transformations
F. Bradaschia, J. P. Arruda, H. E. P. Souza, G. M. S. Azevedo, F. A. S. Neves, M. C. Cavalcanti
Universidade Federal de Pernambuco/Departamento de Engenharia Eletrica e Sistemas de Potencia, Recife - PE, Brazil
AbstractIn this paper a novel scheme for obtaining thefundamental-frequency positive-sequence grid voltage is pro-posed. The method is based on four simple mathematicaltransformations, two of them in the stationary reference frame,which are able to eliminate odd harmonics from the originalsignals. The other two transformations are implemented in a
synchronously rotating reference frame in order to eliminate evenharmonics. The output of the last transformation block is input toa synchronous reference frame phase locked loop for detectingfrequency and position of the positive-sequence voltage vector.The proposed algorithm was verified through simulations andexperiments by applying distorted and unbalanced signals, con-taining positive and negative-sequence components. The resultsare in agreement with those theoretically predicted and indicatethat the proposed scheme has a great potential for using in gridconnected converters synchronization algorithms.
I. INTRODUCTION
Voltage oriented control (VOC) is one of the most used
techniques for the operation and control of any equipment
connected to the grid through a DC-AC controlled converter,such as a distributed power generation system, uninterrupt-
ible power supply or active filter. The correct value of
the fundamental-frequency positive-sequence voltage vector
of the electric grid is essential for achieving good control
performance when using VOC. This information is usually
obtained by using a phase locked loop (PLL). The PLL must
be capable of following the fundamental-frequency positive-
sequence voltage vector as fast as possible for eliminating the
impacts of the grid signal imperfections, even during voltage
sags or if the grid voltages are distorted and unbalanced [1][2].
The synchronous reference frame PLL (SRF-PLL) is fre-
quently used in three-phase systems and for balanced undis-
torted grid conditions, good results can be reached [3]. TheSRF-PLL can also operate correctly if only high order harmon-
ics are present in the grid voltages, by reducing its bandwidth
to attenuate these harmonics [4]. However, under unbalanced
conditions, the second harmonic content of the dq voltage
vector, caused by the negative-sequence components, makes
the reduction of the bandwidth an inefficient solution, since
the dynamics of the PLL would become very slow for such
a narrow bandwidth. A better performance under unbalanced
conditions can be achieved by separating the positive and
negative-sequence components of the voltage vector. This is
made by the double synchronous reference frame PLL (DSRF-
PLL) that uses a decoupling cell to isolate the positive and
negative-sequence components [5]. A cell for obtaining any
other harmonic component may be implemented and then
that component may be subtracted from the original voltages.
However, the computational cost greatly increases if many
harmonic components should be attenuated.
An alternative technique uses an enhanced PLL (EPLL)[6] for each phase. The phase voltages and their respective
values delayed by 900 detected by the EPLL are used forobtaining the positive-sequence voltages of the three-phase
system using the instantaneous symmetrical components (ISC)
method. Finally, a fourth EPLL is applied to the output of
the ISC method to estimate the positive-sequence voltage
phase angle. The fundamental-frequency negative-sequence
components of the grid voltages are eliminated by the EPLL
calculator. However, some harmonics will pass through the
EPLL and may be present in its output.
In the so called delayed signal cancellation method [7],
[8], the positive- and negative-sequence components of the
grid voltage are determined based on the voltage vector in astationary () reference frame and also on that voltage vectordelayed by a quarter of cycle. The method is suitable for un-
balanced undistorted grid voltages, but the calculated positive-
and negative-sequence voltages are sensitive to harmonics in
the grid voltages.
The PLL using a dual second order generalized integrator
(DSOGI) [9] is based on the ISC method in the stationary
() domain. The grid voltages are transformed to the reference frame and the and components delayed by900 are obtained by the DSOGI-QSG, where QSG meansquadrature signals generation. These signals are used as the
inputs of a positive-sequence calculator (PSC). After that, a
SRF-PLL is used to obtain the angle, frequency and position ofthe fundamental-frequency positive-sequence voltage vector.
This frequency is used to feedback the DSOGI-QSG.
A fast instantaneous method for sequence extraction from
a three-phase signal was proposed in [10]. It was shown that
the phase voltages can be manipulated through mathemati-
cal transformations to eliminate specific harmonics from the
original signals without using filters. The signal is passed
through some cascaded mathematical transformations in order
to eliminate odd harmonics. The even harmonic components
are not eliminated, although some of them may be attenuated.
This paper presents an original scheme that employs
only simple calculations to extract the fundamental-frequency
978-1-4244-1668-4/08/$25.00 2008 IEEE
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
2/7
1116
positive-sequence grid voltages, eliminating odd and even
harmonics. The method is based on different ways of obtaining
the positive- and negative-sequence components of the grid
voltage, by applying the symmetric components theory to
the dq voltage vector transformed into different referenceframes ( and synchronous with the fundamental positive-sequence voltage). It is shown how these transformations
affect each harmonic component of the grid voltage. The
extracted positive-sequence voltage is the input to a SRF-PLL
for detecting the frequency and the position of the desired
voltage vector.
I I . TRANSFORMATIONS TOE XTRACTO DD H ARMONICS
Using the method of symmetrical coordinates (1), it is
possible to obtain the symmetrical components (S+,S andS0) of a three-phase signal (current, voltage or flux:
Sa,
Sb
andSc) [11]. S+SS0= 1
3
1 1120 11201 1120 11201 1 1
[M]
SaSbSc (1)
The negative- and positive-sequence components can be
extracted in abc from: SaSbSc
=13
1 160 160160 1 160
160 160 1
[M] SaSbSc
(2)
and S+aS+bS+c=1
3
1 160 160160 1 160
160 160 1
[M+]
SaSbSc .(3)
As demonstrated in [10], operations (2) and (3) can be
written in different ways for obtaining the same responses
if the phase signals contain only fundamental- frequency
components. However, if the harmonics present in the orig-
inal signals are differently modified by each operation forobtaining the positive- or negative-sequence component. Four
of these transformations are used in the time domain (using
the instantaneous symmetrical components theory [12]), two
for obtaining the positive-sequence and two for the negative-
sequence components:
[s] =13{A1[s] + A2[s60] + A3[s60]} (4)
[s] = 1
3{B1[s] + B2[s90]} (5)
[s+] =13{C1[s] + C2[s60] + C3[s60]} (6)
[s+] = 1
3{D1[s] + D2[s90]} , (7)
where
A1 = C1 =
1 0 00 1 00 0 1
,A2 = C2 =
0 1 00 0 11 0 0
,
A3 = C3 =
0 0 11 0 00 1 0
, B1 = D1 =
1 12
12
12 1 1
212
12 1
,
B2 = D2 =
0 32 3232
032
32
32 0
, [s] = sasbsc
,
[s] = sa
sbsc
, [s+] = s+a
s+b
s+c , [s60] = sa60sb60
sc60 ,
[s60] =
sa60sb60sc60
, [s90] =
sa90sb90sc90
, [s90] =
sa90sb90sc90
.
The subscripts60 (60) and 90 (90) are used to indicatethe instantaneous signals delayed from the original ones by the
correspondent value in degrees. They can be implemented by
storing the original signals during a time interval correspond-
ing to the desired angles at the fundamental-frequency. For
discrete-time implementation, a determined number of samples
(N) of a fundamental period must be stored. For a delay of
90o the lastN/4samples are stored. To obtain a 90o advancedsignal, the 90o delayed signal with opposite signal is used.The delay of 60o can be generated by saving the last N/6samples. The advance of60o is produced by storing the lastN/3 samples, for obtaining a delay of120o, and multiplyingby -1.
The operations defined by (4)-(7) are called ofA, B, CandD, respectively. After applyingA,B ,CorD, the signalssa, sb and sc are modified. The operations A and B keepthe fundamental-frequency negative-sequence component, but
some harmonics are modified. On the other hand, the op-
erations C and D keep the fundamental-frequency positive-sequence component, changing the characteristics of other
components. Table I, an extended version of that presentedin [10], shows the gains (absolute values and phase shiftings)
of each operation A, B , C and D . The results of the cascadeapplication of operations AB and CD are also shown. Evenharmonics are not canceled, being only attenuated by these
operations.
III. PROPOSEDM ETHOD
Transforming the original signals to an arbitrary dq ref-
erence frame (stationary or rotating), operations capable of
producing the same results ofA, B, C and D are presentedand a way of using these transformations for eliminating odd
and even harmonics is proposed.
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
3/7
1117
Table IGAINS OF THE MATHEMATICAL OPERATIONS FOR THE ODD HARMONICS
Operation A B C D AB CD
1seq+ - - 10 10 - 10
1seq- 10 10 - - 10 -3seq+ - 10 - - - -3seq- - - - 10 - -5seq+ 10 - - 10 - -5seq- - 10 10 - - -7seq+ - 10 10 - - -7seq- 10 - - 10 - -9seq+ - - - 10 - -9seq- - 10 - - - -
11seq+ 10 10 - - 10 -11seq- - - 10 10 - 1013seq+ - - 10 10 - 1013seq- 10 10 - - 10 -15seq+ - 10 - - - -15seq- - - - 10 - -
A. Transformations in an arbitrary dq reference frame
From the Park transformation:
[sdq] = 2
3
cos cos(120) cos(+ 120) sin sin(120) sin(+ 120)
12
12
12
T
[s]
(8)
whereis thedaxis angular position and using (4) and (8), thenegative-sequence instantaneous components in an arbitrarydq
reference frame can be calculated as follows:
T[s] =13{TA1[s] + TA2[s60] + TA3[s60]} .
Thus,
[sdq] =1
3
TA1T
1[sdq] + TA2T1[sdq60] + TA3T
1[sdq60]
(9)
where
[sdq] =
sdsqs0
, [sdq] =
sdsqs0
,
[sdq60] = sd60sq60s060 , [sdq60] = sd60
sq60s060 .As T is not singular, the process of changing the referenceframe (An TAnT
1, n = 1, 2, 3) is a transformationof similarity. Some properties are common in the similar
matricesAn and TAnT1: the same characteristic polynomial
and eingevalues, algebraic and geometrical multiplicity [13].
Disregarding the zero sequence components, operation A inthe dq reference frame can be obtained from (9): sdsq
=
1
3A1dq
sdsq
+
1
6A2dq
sd60sq60
+
1
6A3dq
sd60sq60
.
(10)
Transformations of similarity analogous to (9) can be applied
to operations B , C and D to obtain them in any dq referenceframe, respectively:
sdsq = 12B1dq sdsq +12B2dq sd90sq90 , (11) s+ds+q
=
1
3C1dq
sdsq
+
1
6C2dq
sd60sq60
+
1
6C3dq
sd60sq60
,
(12) s+ds+q
=
1
2D1dq
sdsq
+
1
2D2dq
sd90sq90
. (13)
The transformed matrices in (10), (11), (12) and (13) are:
A1dq = B1dq =C1dq =D1dq =
1 00 1
,
A2dq = C2dq = 1 33 1
,A3dq = C3dq =
1
3
3 1
,B2dq =D2dq =
0 11 0
.
It is important to note that operations (10) - (13), named
Adq , Bdq , Cdq and Ddq , respectively, are identical to oper-ations A through D regarding to the effects over the har-monic components (Table I). This is proved now. Consider
a three-phase balanced positive-sequence signal of order h
(h= 1, 2, 3, . . .):
sah= Shcos(ht + h)sbh = Shcos(ht + h120o)sch= Shcos(ht + h+ 120
o). (14)
Transforming to the reference frame: sh = Shcos(ht + h)sh = Shsin(ht + h)
, (15)
and applying the formula of Euler in (15):
sh+ jsh = Shej(ht+h). (16)
Using the signal in (15) as the input to operationAdq in (10) and taking into account that an advance of 60
o
corresponds to a delay of120o with the opposite signal,
s =
Sh
3
cos(h) 12cos(h h120o) +
32 sin(h h120o)+
+12
cos(hh60o) +32
sin(hh60o)
s =
Sh
3
sin(h)
32
cos(h h120o) 12sin(hh120o)32 cos(hh60o) + 12sin(hh60o)
,
(17)
whereh = ht+h. Changing (17) for the complex domainand using the formula of Euler:
s +js
=She
j(ht+h) 1
3 1 + ej(1+h)120
o+ ej(1+h)60
o
.
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
4/7
1118
Then,
s +js
= (sh+ jsh)
1
3
1 + ej(1+h)120
o+ ej(1+h)60
o
GA+,
(18)where GA+ is the gain of the operation Adq for positive-sequence signals.
Considering a three-phase balanced negative-sequence sig-
nal of order h (h= 1,2,3, . . .), it can be shown that:
sjs = (shjsh)
1
3
1 + ej(1+h)120
o+ ej(1+h)60
o
GA
, (19)
where GA is the gain of the operation Adq for negative-sequence signals.
Using the signal in (15) as the input to operation Bdqin (11),
ss
=
Sh
2
cos(h) + sin(hh90o)sin(h)cos(hh90o)
, (20)
whereh= ht+h. Changing (20) for the complex domainand using the formula of Euler:
s +js
=She
j(ht+h) 1
2
1 + ej(1+h)90
o.
Then,
s +js
= (sh+ jsh)
1
2
1 + ej(1+h)90
o
GB+
, (21)
where GB+ is the gain of the operation Bdq for positive-sequence signals.
For negative-sequence signals (h= 1,2,3, . . .):
s js = (shjsh)
1
2
1 + ej(1+h)90
o
GB
, (22)
where GB is the gain of the operation Bdq .Results similar to (18) and (19) can be obtained for the
operation Cdq in (12):
s+js
= (sh+jsh)
1
3 1 + ej(1h)60
o
+ ej(1h)120o
GC+, (23)
s js = (shjsh)
1
3
1 + ej(1h)60
o+ ej(1h)120
o
GC,
(24)whereGC+ and GC are the gains of the operation Cdq forpositive- and negative-sequence signals, respectively.
Results similar to (21) and (22) can be obtained for the
operation Ddq in (13):
s +js
= (sh+ jsh)
1
2
1 + ej(1h)90
o
GD+
, (25)
s js = (shjsh)
1
2
1 + e
j(1h)90o
GD
, (26)
whereGD+ and GD are the gains of the operation Ddq for
positive and negative-sequence signals, respectively.
B. Implementation of the proposed method
After measuring the signals in abc and transforming them
into the reference frame, operations Cdq and Ddq areapplied in cascade. In this way, many odd harmonics are
canceled, but the even harmonics remain present in the signals.
The next step is to transform the output signals into asynchronous dq reference frame. Therefore, the fundamental
component becomes constant, the second harmonic becomes
of fundamental frequency and any harmonic of positive-
sequence with frequencyhin has its frequency decreasedby one in dq. The negative-sequence components have their
frequency increased by one, when they are transformed to thesynchronous dq reference frame. Then, the even harmonics
become odd and vice-versa. If the signals in the synchronous
dq reference frame go through the operations Adq and Bdq incascade, then odd harmonics of these signals (even harmonics
of the original signals) are eliminated and their constant
components contain the information about the fundamental-
frequency positive-sequence vector. The scheme is described
in the block diagram of Fig. 1.
Since the constant components do not pass integrally by the
operationsAdq andBdq, an adjustment must be made in orderto obtain the correct magnitudes of the fundamental frequency
positive-sequence signal insd and sq . Therefore, making a DC
signal go through Adq:
PI 1
s+-
v*q
= 0
vabc abc dq
vdDdq
vq
Cdq Adq Bdq MDCVv + vd q
2 2
1
Bdq++ff
LPF
LPF
dq
abc
vabc+
v +d
v +q
Figure 1. Block diagram of the proposed solution.
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
5/7
1119
sdsq
=
1
3A1dq
sDCdsDCq
1
6A2dq
sDCdsDCq
+
1
6A3dq
sDCdsDCq
.
Then, sdsq
=
1
3A3dq
sDCdsDCq
. (27)
The result goes through Bdq . Thus, sdsq
=
1
2B1dq
1
3A3dq
sDCdsDCq
+
1
2B2dq
1
3A3dq
sDCdsDCq
sdsq
=
1
6
(1 3) (1 + 3)(1 3) (1 3)
sDCdsDCq
. (28)
Then, the matrix [MDC]that must multiply the signal comingfrom the operation
Bdq is:
[MDC] =
1
6
(1 3) (1 + 3)(1 3) (1 3)
1[MDC] =
3
4
(1 3) (1 3)(1 +
3) (1 3)
. (29)
In the proposed solution, as it can be observed in Table I, the
11th negative-sequence and the 13th positive-sequence har-monic components and the fundamental-frequency positive-
sequence component are not eliminated by the cascaded Cdqand Ddq transformations. Since these components becomeeven after the to dq transformation, they cannot be
eliminated by the cascaded Adq and Bdq transformations andthey are present in the output signals. Analogously, the 12thpositive-sequence and the12thnegative-sequence componentsare not canceled by the cascaded Cdq andDdq transformationsand become the 11th positive-sequence and 13th negative-sequence components after the todq transformation. Thus,as it can be seen in Table I, these components are not
eliminated. All of the other harmonic components among the
above mentioned are canceled. In general, using the equations
shown in this paper, it is concluded that the positive-sequence
harmonics of order 12h and 12h + 1 as well as the negative-sequence harmonics of order 12h1and 12hare not canceledby the mathematical operations. However, the bandwidth of the
SRF-PLL may be reduced in such a way that the estimationof the frequency and the position are barely affected bythose harmonics.
To recover correctly the three-phase signal, it is advisable
to pass the estimated signalsv+d andv+q through filters that do
not affect the system dynamics, since they are not in the loop,
and have a high bandwidth. In this paper, filters with finite
impulse response (FIR) are used. The filters are based on the
windowHammingsmethod of order20 and cut-off frequencyof300 Hz.
To avoid the problems of offsets in the measurement and
acquisition signals, the following procedure is used: each
fundamental period, the last N samples of the input signal
are added and the result is divided by N. The result of thedivision is the offset. The offset is subtracted from the original
signal and this solution has a very small computational effort.
IV. SIMULATION ANDE XPERIMENTALR ESULTS
In order to verify the proposed algorithm effectiveness, sim-
ulations were carried out for obtaining the positive-sequence
fundamental-frequency voltages from unbalanced and dis-
torted input signals. The fundamental-frequency of the grid is
50 Hz. In all situations, v+1pf = 10p.u. is the pre-fault grid
voltage. In the first case, the unbalanced and distorted grid
voltage during the fault consisted ofv+1 = 0.747 14p.u.,v1 = 0.163 171.37p.u., v5 = 0.07 60p.u.,v+7 =0.0530p.u.. In the second case, v+1 = 2.5v1 = 10p.u.,v+h = vh = 0.6v
+1
h , h = 2, 3, . . . , 25. Figures 2 and 3
show the simulation results. In both figures, the first graphic
shows the input voltages, the second graphic shows the output
voltages, the third graphic shows the voltages (vd, vq) and thefourth graphic shows the error.
0 40 80 120 160 200 240-150
0
150
v a
bc
(%)
t(ms)
0 40 80 120 160 200 240
-100
0
100
v+ a
bc
(%)
t(ms)
0 40 80 120 160 200 240-50
0
50
100
150
v+ d
,v
+ q
(%)
t(ms)
0 40 80 120 160 200 240-1
-0.5
0
0.5
1
=+
-
+(ra
d)
t(ms)
Figure 2. Simulation results for unbalanced signals with low distortion.
Experiments are performed using a OMICRON-CMC256
programmable source to generate the same simulated input
voltages. The signals are acquired and processed using a
Texas Instruments TMS320F2812 DSP and measured after
passing through a digital-analog converter. Figures 4 and 5
show the experimental results for the same situations tested in
simulation. In both figures, the first graphic shows the input
voltages, the second graphic shows the output voltages and the
third graphic shows the voltages (vd, vq) and . It can be seen
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
6/7
1120
0 40 80 120 160 200 240
-150
0
150
300
450
v a
bc
(%)
t(ms)
0 40 80 120 160 200 240
-100
0
100
v+ a
bc
(%)
t(ms)
0 40 80 120 160 200 240-50
0
50
100
150
v+ d
,v
+ q
(%)
t(ms)
0 40 80 120 160 200 240-1
-0.5
0
0.5
1
=+
-
+(r
ad)
t(ms)
Figure 3. Simulation results for unbalanced signals with high distortion.
a very good agreement between simulation and experiment,
showing that the theoretical assumptions used in simulationsare valid. The results illustrate the behavior of the proposed
method in two different conditions and verify its harmonic
rejection capability. In the first case, a realistic situation with
unbalanced signals and low distortion is considered. In the
second case, it is proved that the proposed method can handle
signals with high distortion.
Table II provides a quantitative comparison of the proposed
method with three existing synchronization methods, based on
the output total harmonic distortion (THD), response time and
offset. The methods used for comparison are the SRF, DSRF
and DSOGI. In Table II, (1) means the first case: unbalanced
signals with low distortion (Fig. 2), (2) means the second case:
unbalanced signals with high distortion (Fig. 3) and (3) meansthe third case: unbalanced signals without distortion (Fig. 2
without distortion). It is considered the highest THD among
the three phases. In the first and the second cases, the THD
of the input voltages is 14.34% and 66.71%, respectively. In
practice, the higher harmonic component of the THD that can
be calculated is equal to half of the sample frequency of the
input signals. In all simulations and experiments the sample
frequency is 18 kHz. Then, all THD results have harmoniccomponents up to 9 kHz.
The response time is the time necessary for that the absolute
error of stays between a tolerance range of1.5o (0.0262rad).In the cases in which the method does not guarantee the error
between the tolerance range, the response times in the table
are represented by - .Table II
COMPARISON OF THE SYNCHRONIZATION METHODS
SRF DSRF DSOGI Proposed
THD(1) 2.98% 1.16% 1.10% 0.01%
THD(2) 17.67% 23.04% 19.25% 0.24%
response time(1) - 49.44ms 42.78ms 32.06msresponse time(2) - - - 7.78msresponse time(3) - 36.67ms 42.72ms 31.89mscompense offset No No No Yes
V. CONCLUSION
In this paper simple mathematical transformations are
proposed for handling distorted and unbalanced three-phase
signals in order to eliminate part of the information (har-
monic and unbalanced content) and keep the positive-sequence
fundamental-frequency components. Using finite impulse re-
sponse filters, the components that are not eliminated by the
mathematical operations can be attenuated. These filters do
not affect the dynamic of the system since they are not in
the loop and they have a high bandwidth. Four situations
are tested to confirm the theoretical assumptions: unbalanced
signals with high distortion, unbalanced voltage sag with low
distortion, unbalanced voltage sag and balanced voltage with
offset. The results were obtained through simulations and also
using an experimental platform, showing that the proposed
scheme has a great potential for grid synchronization of power
converters, even during unbalanced faults and highly distorted
grid voltages.
REFERENCES
[1] J. G. Nielsen, M. Newman, H. Nielsen, and F. Blaabjerg, Controland Testing of a Dynamic Voltage Restorer (DVR) at Medium VoltageLevel, IEEE Transactions on Power Electronics, vol. 19, no. 3, pp.806813, May 2004.
[2] V. Kaura and V. Blasko, Operation of Phase Locked Loop SystemUnder Distorted Utility Conditions, IEEE Transactions on IndustryApplications, vol. 33, no. 1, pp. 5863, January/February 1997.
[3] L. N. Arruda, S. M. Silva, and B. J. C. Filho, PLL Structuresfor Utility Connected Systems, Proceedings of Industry ApplicationsSociety Annual Meeting01, vol. 4, pp. 26552660, September/October2001.
[4] S.-K. Chung, A Phase Tracking System for Three Phase UtilityInterfece Inverters, IEEE Transactions on Power Electronics, vol. 15,
no. 3, pp. 431438, May 2000.[5] P. Rodrguez, J. Pou, J. Bergas, I. Candela, R. Burgos, and D. Boroye-
vich, Double Synchronous Reference Frame PLL for Power Convert-ers, Proceedings of IEEE Power Electronics Specialists Conference -PESC05, pp. 14151421, 2005.
[6] M. Karimi-Ghartemani and M. R. Iravani, A Method for Synchroniza-tion of Power Electronic Converters in Polluted and Variable-FrequencyEnvironment, IEEE Transactions Power Systems, vol. 19, no. 3, pp.12631270, August 2004.
[7] J. Svensson, M. Bongiorno, and A. Sannino, Practical Implementationof Delayed Signal Cancellation Method for Phase-Sequence Separation,IEEE Transactions on Power Delivery, vol. 22, no. 1, pp. 1826, January2007.
[8] G. Saccomando and J. Svensson, Transient Operation of Grid Con-nected Voltage Source Converter Under Unbalanced Voltage Condi-tions, Proceedings of IEEE Industry Applications Society - IAS01, pp.24192424, 2001.
-
8/10/2019 Method for Extracting Positive and Negative Sequence current
7/7
1121
Figure 4. Experimental results for unbalanced signals with low distortion.
[9] P. Rodrguez, R. Teodorescu, I. Candela, A. Timbus, M. Liserre, andF. Blaabjerg, New Positive-Sequence Voltage Detector for Grid Syn-chronization of Power Converters Under Faulty Grid Conditions, Pro-ceedings of IEEE Power Electronics Specialists Conference - PESC06,pp. 17, June 2006.
[10] R. Cutri and L. M. Jr., A Fast Instantaneous Method for SequenceExtraction, Proceedings of Brazilian Power Electronics Conference -
Figure 5. Experimental results for unbalanced signals with high distortion.
COBEP07, pp. 16, October 2007.[11] C. L. Fortescue, Method of Symmetrical Co-ordinates Applied to
the Solution of Polyphase Networks, 34th Annual Convention of theAmerica Istitute of Eletrical Engineers. Atlantic City, N.J., June 1918.
[12] W. V. Lyon, Application of the Method of Symmetrical Components.New York: McGraw-Hill, 1937.
[13] L. N. Trefethen and D. Bau, Numerical Linear Algebra. SIAM, 1997.