metro hangers and supports burnett transit center ... · or 27) complying with mss sp-69,...

120
METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS 260529-1 Section 260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 - G E N E R A L 1.01 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.02 PERFORMANCE REQUIREMENTS A. Delegated Design: Design supports for multiple raceways, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated. B. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents. C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components. D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force. 1.03 ACTION SUBMITTALS A. Product Data: For steel slotted support systems. B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following: 1. Trapeze hangers. Include Product Data for components. 2. Steel slotted channel systems. Include Product Data for components. 3. Equipment supports. 1.04 INFORMATIONAL SUBMITTALS A. Welding certificates.

Upload: others

Post on 17-Apr-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-1

Section 260529

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section includes:

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1.02 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design supports for multiple raceways, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.

B. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.

C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.

1.03 ACTION SUBMITTALS

A. Product Data: For steel slotted support systems.

B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:

1. Trapeze hangers. Include Product Data for components. 2. Steel slotted channel systems. Include Product Data for components. 3. Equipment supports.

1.04 INFORMATIONAL SUBMITTALS

A. Welding certificates.

Page 2: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-2

1.05 QUALITY ASSURANCE

A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

B. Comply with NFPA 70.

1.06 MEASUREMENT AND PAYMENT

A. Payment for Hangers and Supports for Electrical Systems is on a Lump Sum basis.

PART 2 - P R O D U C T S

2.01 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Allied Tube & Conduit. b. Cooper B-Line, Inc.; a division of Cooper Industries. c. ERICO International Corporation. d. GS Metals Corp. e. Thomas & Betts Corporation. f. Unistrut; Tyco International, Ltd. g. Wesanco, Inc.

2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA-4.

3. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.

4. Painted Coatings: Manufacturer's standard painted coating applied according to MFMA-4.

5. Channel Dimensions: Selected for applicable load criteria.

B. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

C. Conduit and Cable Support Devices: Steel or stainless steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

Page 3: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-3

D. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be malleable iron.

E. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

F. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.

a. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

b. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) Hilti Inc. 2) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc. 3) MKT Fastening, LLC. 4) Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems

Unit.

2. Mechanical-Expansion Anchors: Insert-wedge-type, stainless steel, for use in hardened portland cement concrete with tension, shear, and pullout capacities appropriate for supported loads and building materials in which used.

a. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

b. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) Cooper B-Line, Inc.; a division of Cooper Industries. 2) Empire Tool and Manufacturing Co., Inc. 3) Hilti Inc. 4) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc. 5) MKT Fastening, LLC.

Page 4: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-4

3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS Type 18; complying with MFMA-4 or MSS SP-58.

4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

5. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A 325.

6. Toggle Bolts: All-steel springhead type. 7. Hanger Rods: Threaded steel.

G. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.

B. Materials: Comply with requirements in Section 055000 "Metal Fabrications" for steel shapes and plates.

PART 3 - E X E C U T I O N

3.01 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for EMT, IMC, and RMC as required by scheduled in NECA 1, where its Table 1 lists maximum spacings less than stated in NFPA 70. Minimum rod size shall be 1/4 inch (6 mm) in diameter.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted or other support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with two-bolt conduit clamps, single-bolt conduit clamps, single-bolt conduit clamps using spring friction action for retention in support channel.

D. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1-1/2-inch (38-mm) and smaller raceways serving branch circuits and communication systems above suspended ceilings and for fastening raceways to trapeze supports.

Page 5: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-5

3.02 SUPPORT INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this Article.

B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and RMC may be supported by openings through structure members, as permitted in NFPA 70.

C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb (90 kg).

D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

1. To Wood: Fasten with lag screws or through bolts. 2. To New Concrete: Bolt to concrete inserts. 3. To Masonry: Approved toggle-type bolts on hollow masonry units and

expansion anchor fasteners on solid masonry units. 4. To Existing Concrete: Expansion anchor fasteners. 5. Instead of expansion anchors, powder-actuated driven threaded studs

provided with lock washers and nuts may be used in existing standard-weight concrete 4 inches (100 mm) thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches (100 mm) thick.

6. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts, Beam clamps (MSS Type 19, 21, 23, 25, or 27) complying with MSS SP-69, Spring-tension clamps.

7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces:

Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that meet seismic-restraint strength and anchorage requirements.

E. Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing bars.

3.03 INSTALLATION OF FABRICATED METAL SUPPORTS

A. Comply with installation requirements in Section 055000 "Metal Fabrications" for site-fabricated metal supports.

Page 6: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO HANGERS AND SUPPORTS Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260529-6

B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.

C. Field Welding: Comply with AWS D1.1/D1.1M.

3.04 CONCRETE BASES

A. Construct concrete bases of dimensions indicated but not less than 4 inches (100 mm) larger in both directions than supported unit, and so anchors will be a minimum of 10 bolt diameters from edge of the base.

B. Use 3000-psi (20.7-MPa), 28-day compressive-strength concrete. Concrete materials, reinforcement, and placement requirements are specified in Section 033000 "Cast-in-Place Concrete."

C. Anchor equipment to concrete base.

1. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

2. Install anchor bolts to elevations required for proper attachment to supported equipment.

3. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

3.05 PAINTING

A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils (0.05 mm).

B. Touchup: Comply with requirements in Section 099113 "Exterior Painting," Section 099123 "Interior Painting" and Section 099600 "High Performance Coatings" for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION

Page 7: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-1

Section 260533

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Metal conduits, tubing, and fittings. 2. Nonmetal conduits, tubing, and fittings. 3. Metal wireways and auxiliary gutters. 4. Nonmetal wireways and auxiliary gutters. 5. Surface raceways. 6. Boxes, enclosures, and cabinets. 7. Handholes and boxes for exterior underground cabling.

1.02 ACTION SUBMITTALS

A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, and attachment details.

1.03 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved:

1. Structural members in paths of conduit groups with common supports. 2. HVAC and plumbing items and architectural features in paths of conduit

groups with common supports.

1.04 MEASUREMENT AND PAYMENT

A. Payment for Raceways and Boxes for Electrical Systems is on a Lump Sum basis.

Page 8: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-2

PART 2 - P R O D U C T S

2.01 METAL CONDUITS, TUBING, AND FITTINGS

A. Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. GRC: Comply with ANSI C80.1 and UL 6.

C. ARC: Comply with ANSI C80.5 and UL 6A.

D. IMC: Comply with ANSI C80.6 and UL 1242.

E. PVC-Coated Steel Conduit: PVC-coated rigid steel conduit.

1. Comply with NEMA RN 1. 2. Coating Thickness: 0.040 inch (1 mm), minimum.

F. EMT: Comply with ANSI C80.3 and UL 797.

G. FMC: Comply with UL 1; zinc-coated steel.

H. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.

I. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.

1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886 and NFPA 70.

2. Fittings for EMT:

a. Material: Steel. b. Type: Compression.

3. Expansion Fittings: PVC or steel to match conduit type, complying with UL 651, rated for environmental conditions where installed, and including flexible external bonding jumper.

4. Coating for Fittings for PVC-Coated Conduit: Minimum thickness of 0.040 inch (1 mm), with overlapping sleeves protecting threaded joints.

J. Joint Compound for IMC, GRC, or ARC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity.

Page 9: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-3

K. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 NONMETALLIC CONDUITS, TUBING, AND FITTINGS

A. Listing and Labeling: Nonmetallic conduits, tubing, and fittings shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. ENT: Comply with NEMA TC 13 and UL 1653.

C. RNC: Type EPC-40-PVC, complying with NEMA TC 2 and UL 651 unless otherwise indicated.

D. LFNC: Comply with UL 1660.

E. Continuous HDPE: Comply with UL 651B.

F. Coilable HDPE: Preassembled with conductors or cables, and complying with ASTM D 3485.

G. Fittings for ENT and RNC: Comply with NEMA TC 3; match to conduit or tubing type and material.

H. Fittings for LFNC: Comply with UL 514B.

I. Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less, respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

J. Solvent cements and adhesive primers shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

K. Fiberglass Reinforce Conduit: Comply with UL 2515.

2.03 METAL WIREWAYS AND AUXILIARY GUTTERS

A. Description: Sheet metal, complying with UL 870 and NEMA 250, Type 1 unless otherwise indicated, and sized according to NFPA 70.

Page 10: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-4

1. Metal wireways installed outdoors shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

2.04 NONMETALLIC WIREWAYS AND AUXILIARY GUTTERS A. Listing and Labeling: Nonmetallic wireways and auxiliary gutters shall be listed

and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Description: Fiberglass polyester, extruded and fabricated to required size and shape, without holes or knockouts. Cover shall be gasketed with oil-resistant gasket material and fastened with captive screws treated for corrosion resistance. Connections shall be flanged and have stainless-steel screws and oil-resistant gaskets.

C. Description: PVC, extruded and fabricated to required size and shape, and having snap-on cover, mechanically coupled connections, and plastic fasteners.

D. Fittings and Accessories: Couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings shall match and mate with wireways as required for complete system.

E. Solvent cements and adhesive primers shall have a VOC content of 510 and 550 g/L or less, respectively, when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

F. Solvent cements and adhesive primers shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

2.05 SURFACE RACEWAYS

A. Listing and Labeling: Surface raceways and tele-power poles shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Surface Metal Raceways: Galvanized steel with snap-on covers complying with UL 5.

Page 11: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-5

C. Surface Nonmetallic Raceways: Two- or three-piece construction, complying with UL 5A, and manufactured of rigid PVC. Product shall comply with UL 94 V-0 requirements for self-extinguishing characteristics.

2.06 BOXES, ENCLOSURES, AND CABINETS

A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations.

B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloy, Type FD, with gasketed cover.

D. Nonmetallic Outlet and Device Boxes: Comply with NEMA OS 2 and UL 514C.

E. Metal Floor Boxes:

1. Material: Cast metal. 2. Type: Fully adjustable. 3. Shape: Rectangular. 4. Listing and Labeling: Metal floor boxes shall be listed and labeled as

defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

F. Nonmetallic Floor Boxes: Nonadjustable, rectangular.

1. Listing and Labeling: Nonmetallic floor boxes shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

G. Luminaire Outlet Boxes: Nonadjustable, designed for attachment of luminaire weighing 50 lb (23 kg). Outlet boxes designed for attachment of luminaires weighing more than 50 lb (23 kg) shall be listed and marked for the maximum allowable weight.

H. Paddle Fan Outlet Boxes: Nonadjustable, designed for attachment of paddle fan weighing 70 lb (32 kg).

1. Listing and labeling: Paddle fan outlet boxes shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

I. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

Page 12: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-6

J. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, galvanized, cast iron with gasketed cover.

K. Box extensions used to accommodate new building finishes shall be of same material as recessed box.

L. Device Box Dimensions: 4 inches by 2-1/8 inches by 2-1/8 inches deep (100 mm by 60 mm by 60 mm deep).

M. Gangable boxes are prohibited.

N. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1 with continuous-hinge cover with flush latch unless otherwise indicated.

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

2. Nonmetallic Enclosures: Fiberglass. 3. Interior Panels: Steel; all sides finished with manufacturer's standard

enamel.

O. Cabinets:

1. NEMA 250, Type 1 galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge. 3. Key latch to match panelboards. 4. Metal barriers to separate wiring of different systems and voltage. 5. Accessory feet where required for freestanding equipment. 6. Nonmetallic cabinets shall be listed and labeled as defined in NFPA 70, by

a qualified testing agency, and marked for intended location and application.

2.07 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING

A. General Requirements for Handholes and Boxes:

1. Boxes and handholes for use in underground systems shall be designed and identified as defined in NFPA 70, for intended location and application.

2. Boxes installed in wet areas shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

Page 13: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-7

B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and aggregate, bound together with polymer resin, and reinforced with steel, fiberglass, or a combination of the two.

1. Standard: Comply with SCTE 77. 2. Configuration: Designed for flush burial with integral closed bottom unless

otherwise indicated. 3. Cover: Weatherproof, secured by tamper-resistant locking devices and

having structural load rating consistent with enclosure and handhole location.

4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.

5. Cover Legend: Molded lettering, "ELECTRIC." 6. Conduit Entrance Provisions: Conduit-terminating fittings shall mate with

entering ducts for secure, fixed installation in enclosure wall.

C. Fiberglass Handholes and Boxes: Molded of fiberglass-reinforced polyester resin, with frame and covers of cast iron.

1. Standard: Comply with SCTE 77. 2. Configuration: Designed for flush burial with integral closed bottom unless

otherwise indicated. 3. Cover: Weatherproof, secured by tamper-resistant locking devices and

having structural load rating consistent with enclosure and handhole location.

4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.

5. Cover Legend: Molded lettering, "ELECTRIC." 6. Conduit Entrance Provisions: Conduit-terminating fittings shall mate with

entering ducts for secure, fixed installation in enclosure wall.

PART 3 - E X E C U T I O N

3.01 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed Conduit: PVC coated rigid steel conduit or FRC conduit. 2. Concealed Conduit, Aboveground: PVC coated rigid steel conduit. 3. Underground Conduit: RNC, Type EPC-80-PVC, concrete encased. 4. Connection to Vibrating Equipment (Including Transformers and Hydraulic,

Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC. 5. Boxes and Enclosures, Aboveground: NEMA Type 4X.

Page 14: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-8

B. Indoors: Apply raceway products as specified below unless otherwise indicated.

1. Exposed, Not Subject to Physical Damage: PVC coated rigid steel conduit or FRC conduit.

2. Exposed and Subject to Severe Physical Damage: PVC coated rigid steel conduit.

3. Concealed in Ceilings and Interior Walls and Partitions: GRC. 4. Connection to Vibrating Equipment (Including Transformers and Hydraulic,

Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations.

5. Damp or Wet Locations: PVC coated rigid steel conduit. 6. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250,

Type 4 stainless steel in institutional and commercial kitchens and damp or wet locations.

C. Minimum Raceway Size: 1/2-inch (16-mm) trade size.

D. Raceway Fittings: Compatible with raceways and suitable for use and location.

1. Rigid Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB 2.10.

2. PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with this type of conduit. Patch and seal all joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Use sealant recommended by fitting manufacturer and apply in thickness and number of coats recommended by manufacturer.

3. Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with NEMA FB 2.20.

E. Do not install aluminum conduits, boxes, or fittings in contact with concrete or earth.

F. Install surface raceways only where indicated on Drawings.

G. Do not install nonmetallic conduit where ambient temperature exceeds 120 deg F (49 deg C).

3.02 INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NECA 102 for aluminum conduits. Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors.

Page 15: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-9

B. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.

C. Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for hangers and supports.

D. Arrange stub-ups so curved portions of bends are not visible above finished slab.

E. Install no more than the equivalent of three 90-degree bends in any conduit run except for control wiring conduits, for which fewer bends are allowed. Support within 12 inches (300 mm) of changes in direction.

F. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines.

G. Support conduit within 12 inches (300 mm)of enclosures to which attached.

H. Raceways Embedded in Slabs:

1. Run conduit larger than 1-inch (27-mm) trade size, parallel or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support. Secure raceways to reinforcement at maximum 10-foot (3-m) intervals.

2. Arrange raceways to cross building expansion joints at right angles with expansion fittings.

3. Arrange raceways to keep a minimum of 2 inches (50 mm) of concrete cover in all directions.

4. Do not embed threadless fittings in concrete unless specifically approved by Architect for each specific location.

5. Change from ENT to Type EPC-40-PVC to GRC before rising above floor.

I. Stub-ups to Above Recessed Ceilings:

1. Use RMC for raceways. 2. Use a conduit bushing or insulated fitting to terminate stub-ups not

terminated in hubs or in an enclosure.

J. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to threads of raceway and fittings before making up joints. Follow compound manufacturer's written instructions.

K. Coat field-cut threads on PVC-coated raceway with a corrosion-preventing conductive compound prior to assembly.

Page 16: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-10

L. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors including conductors smaller than No. 4 AWG.

M. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to 1-1/4-inch (35-mm) trade size and insulated throat metal bushings on 1-1/2-inch (41-mm) trade size and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits.

N. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 200-lb (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end of pull wire. Cap underground raceways designated as spare above grade alongside raceways in use.

O. Surface Raceways:

1. Install surface raceway with a minimum 2-inch (50-mm)radius control at bend points.

2. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inches (1200 mm) and with no less than two supports per straight raceway section. Support surface raceway according to manufacturer's written instructions. Tape and glue are not acceptable support methods.

P. Install raceway sealing fittings at accessible locations according to NFPA 70 and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces.

Q. Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal the interior of all raceways at the following points:

1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces.

2. Where an underground service raceway enters a building or structure. 3. Where otherwise required by NFPA 70.

R. Expansion-Joint Fittings:

1. Install in each run of aboveground RNC that is located where environmental temperature change may exceed 30 deg F (17 deg C) and that has straight-run length that exceeds 25 feet (7.6 m).

2. Install type and quantity of fittings that accommodate temperature change listed for each of the following locations:

Page 17: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-11

a. Outdoor Locations Not Exposed to Direct Sunlight: 125 deg F (70 deg C) temperature change.

b. Outdoor Locations Exposed to Direct Sunlight: 155 deg F (86 deg C) temperature change.

c. Indoor Spaces Connected with Outdoors without Physical Separation: 125 deg F (70 deg C) temperature change.

d. Attics: 135 deg F (75 deg C) temperature change.

3. Install fitting(s) that provide expansion and contraction for at least 0.00041 inch per foot of length of straight run per degree F (0.06 mm per meter of length of straight run per degree C) of temperature change for PVC conduits.

4. Install expansion fittings at all locations where conduits cross building or structure expansion joints.

5. Install each expansion-joint fitting with position, mounting, and piston setting selected according to manufacturer's written instructions for conditions at specific location at time of installation. Install conduit supports to allow for expansion movement.

S. Flexible Conduit Connections: Comply with NEMA RV 3. Use a maximum of 72 inches (1830 mm) of flexible conduit for recessed and semirecessed luminaires, equipment subject to vibration, noise transmission, or movement; and for transformers and motors.

1. Use LFMC in damp or wet locations subject to severe physical damage. 2. Use LFMC or LFNC in damp or wet locations not subject to severe

physical damage.

T. Mount boxes at heights indicated on Drawings. If mounting heights of boxes are not individually indicated, give priority to ADA requirements. Install boxes with height measured to bottom of box unless otherwise indicated.

U. Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block, and install box flush with surface of wall. Prepare block surfaces to provide a flat surface for a raintight connection between the box and cover plate or the supported equipment and box.

V. Horizontally separate boxes mounted on opposite sides of walls so they are not in the same vertical channel.

W. Locate boxes so that cover or plate will not span different building finishes.

X. Support boxes of three gangs or more from more than one side by spanning two framing members or mounting on brackets specifically designed for the purpose.

Page 18: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-12

Y. Fasten junction and pull boxes to or support from building structure. Do not support boxes by conduits.

Z. Set metal floor boxes level and flush with finished floor surface.

AA. Set nonmetallic floor boxes level. Trim after installation to fit flush with finished floor surface.

3.03 INSTALLATION OF UNDERGROUND CONDUIT

A. Direct-Buried Conduit:

1. Excavate trench bottom to provide firm and uniform support for conduit. Prepare trench bottom as specified in Section 312000 "Earth Moving" for pipe less than 6 inches (150 mm) in nominal diameter.

2. Install backfill as specified in Section 312000 "Earth Moving." 3. After installing conduit, backfill and compact. Start at tie-in point, and work

toward end of conduit run, leaving conduit at end of run free to move with expansion and contraction as temperature changes during this process. Firmly hand tamp backfill around conduit to provide maximum supporting strength. After placing controlled backfill to within 12 inches (300 mm) of finished grade, make final conduit connection at end of run and complete backfilling with normal compaction as specified in Section 312000 "Earth Moving."

4. Install manufactured duct elbows for stub-up at poles and equipment and at building entrances through floor unless otherwise indicated. Encase elbows for stub-up ducts throughout length of elbow.

5. Install manufactured rigid steel conduit elbows for stub-ups at poles and equipment and at building entrances through floor.

a. Couple steel conduits to ducts with adapters designed for this purpose, and encase coupling with 3 inches (75 mm) of concrete for a minimum of 12 inches (300 mm) on each side of the coupling.

b. For stub-ups at equipment mounted on outdoor concrete bases and where conduits penetrate building foundations, extend steel conduit horizontally a minimum of 60 inches (1500 mm) from edge of foundation or equipment base. Install insulated grounding bushings on terminations at equipment.

6. Underground Warning Tape: Comply with requirements in Section 260553 "Identification for Electrical Systems."

Page 19: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO RACEWAYS AND BOXES Burnett Transit Center Escalator Design FOR ELECTRICAL SYSTEMS

260533-13

3.04 INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES

A. Install handholes and boxes level and plumb and with orientation and depth coordinated with connecting conduits to minimize bends and deflections required for proper entrances.

B. Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from 1/2-inch (12.5-mm) sieve to No. 4 (4.75-mm) sieve and compacted to same density as adjacent undisturbed earth.

C. Elevation: In paved areas, set so cover surface will be flush with finished grade. Set covers of other enclosures 1 inch (25 mm) above finished grade.

D. Install handholes with bottom below frost line, below grade.

E. Field-cut openings for conduits according to enclosure manufacturer's written instructions. Cut wall of enclosure with a tool designed for material to be cut. Size holes for terminating fittings to be used, and seal around penetrations after fittings are installed.

3.05 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and Cabling."

3.06 FIRESTOPPING

A. Install firestopping at penetrations of fire-rated floor and wall assemblies. Comply with requirements in Section 078413 "Penetration Firestopping."

3.07 PROTECTION

A. Protect coatings, finishes, and cabinets from damage and deterioration.

1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

2. Repair damage to PVC coatings or paint finishes with matching touchup coating recommended by manufacturer.

END OF SECTION

Page 20: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 21: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design ELECTRICAL RACEWAYS AND CABLING

260544-1

Section 260544

SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Sleeves for raceway and cable penetration of non-fire-rated construction walls and floors.

2. Sleeve-seal systems. 3. Sleeve-seal fittings. 4. Grout. 5. Silicone sealants.

B. Related Requirements:

1. Section 078413 "Penetration Firestopping" for penetration firestopping installed in fire-resistance-rated walls, horizontal assemblies, and smoke barriers, with and without penetrating items.

1.02 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. LEED Submittals:

1. Product Data for Credit EQ 4.1: For sealants, documentation including printed statement of VOC content.

2. Laboratory Test Reports for Credit EQ 4: For sealants, documentation indicating that products comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

1.03 MEASUREMENT AND PAYMENT

A. Payment for Sleeves and Sleeve Seals for Electrical Raceways and Cabling is on a Lump Sum basis.

Page 22: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design ELECTRICAL RACEWAYS AND CABLING

260544-2

PART 2 - P R O D U C T S

2.01 SLEEVES

A. Wall Sleeves:

1. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, plain ends.

2. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.

B. Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies: Galvanized-steel sheet; 0.0239-inch (0.6-mm) minimum thickness; round tube closed with welded longitudinal joint, with tabs for screw-fastening the sleeve to the board.

C. Sleeves for Rectangular Openings:

1. Material: Galvanized sheet steel. 2. Minimum Metal Thickness:

a. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and with no side larger than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm).

b. For sleeve cross-section rectangle perimeter 50 inches (1270 mm) or more and one or more sides larger than 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).

D. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 SLEEVE-SEAL SYSTEMS

A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:

a. Advance Products & Systems, Inc. b. CALPICO, Inc. c. Metraflex Company (The). d. Pipeline Seal and Insulator, Inc. e. Proco Products, Inc.

Page 23: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design ELECTRICAL RACEWAYS AND CABLING

260544-3

2. Sealing Elements: EPDM or Nitrile (Buna N) rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.

3. Pressure Plates: Carbon steel or Stainless steel. 4. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant

coating or Stainless steel of length required to secure pressure plates to sealing elements.

2.03 SLEEVE-SEAL FITTINGS

A. Description: Manufactured plastic, sleeve-type, waterstop assembly made for embedding in concrete slab or wall. Unit shall have plastic or rubber waterstop collar with center opening to match piping OD.

1. Basis-of-Design Product: Subject to compliance with requirements, provide comparable product by the following:

a. Presealed Systems.

2.04 GROUT

A. Description: Nonshrink; recommended for interior and exterior sealing openings in non-fire-rated walls or floors.

B. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.

C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

2.05 SILICONE SEALANTS

A. Silicone Sealants: Single-component, silicone-based, neutral-curing elastomeric sealants of grade indicated below.

1. Grade: Pourable (self-leveling) formulation for openings in floors and other horizontal surfaces that are not fire rated.

2. Sealant shall comply with the testing and product requirements of the California Department of Health Services' "Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers."

B. Silicone Foams: Multicomponent, silicone-based liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam.

Page 24: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design ELECTRICAL RACEWAYS AND CABLING

260544-4

PART 3 - E X E C U T I O N

3.01 SLEEVE INSTALLATION FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS

A. Comply with NECA 1.

B. Comply with NEMA VE 2 for cable tray and cable penetrations.

C. Sleeves for Conduits Penetrating Above-Grade Non-Fire-Rated Concrete and Masonry-Unit Floors and Walls:

1. Interior Penetrations of Non-Fire-Rated Walls and Floors:

a. Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Section 079200 "Joint Sealants."

b. Seal space outside of sleeves with mortar or grout. Pack sealing material solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect material while curing.

2. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

3. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and raceway or cable unless sleeve seal is to be installed or unless seismic criteria require different clearance.

4. Install sleeves for wall penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush with both surfaces of walls. Deburr after cutting.

5. Install sleeves for floor penetrations. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level. Install sleeves during erection of floors.

D. Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies:

1. Use circular metal sleeves unless penetration arrangement requires rectangular sleeved opening.

2. Seal space outside of sleeves with approved joint compound for gypsum board assemblies.

E. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.

F. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel or cast-iron pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical sleeve seals.

Page 25: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design ELECTRICAL RACEWAYS AND CABLING

260544-5

G. Underground, Exterior-Wall and Floor Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch (25-mm) annular clear space between raceway or cable and sleeve for installing sleeve-seal system.

3.02 SLEEVE-SEAL-SYSTEM INSTALLATION

A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at raceway entries into building.

B. Install type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

3.03 SLEEVE-SEAL-FITTING INSTALLATION

A. Install sleeve-seal fittings in new walls and slabs as they are constructed.

B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall.

C. Secure nailing flanges to concrete forms.

D. Using grout, seal the space around outside of sleeve-seal fittings.

END OF SECTION

Page 26: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 27: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-1

Section 260553

IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Identification for raceways. 2. Identification of power and control cables. 3. Identification for conductors. 4. Underground-line warning tape. 5. Warning labels and signs. 6. Instruction signs. 7. Equipment identification labels. 8. Miscellaneous identification products.

1.02 ACTION SUBMITTALS

A. Product Data: For each electrical identification product indicated.

1.03 QUALITY ASSURANCE

A. Comply with ANSI A13.1.

B. Comply with NFPA 70.

C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145.

D. Comply with ANSI Z535.4 for safety signs and labels.

E. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969.

1.04 MEASUREMENT AND PAYMENT

A. Payment for Identification for Electrical Systems is on a Lump Sum basis.

Page 28: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-2

PART 2 - P R O D U C T S

2.01 POWER RACEWAY IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway size.

B. Colors for Raceways Carrying Circuits at 600 V or Less:

1. Black letters on an orange field. 2. Legend: Indicate voltage and system or service type.

C. Self-Adhesive Vinyl Labels for Raceways Carrying Circuits at 600 V or Less: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

D. Snap-Around Labels for Raceways Carrying Circuits at 600 V or Less: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

E. Snap-Around, Color-Coding Bands for Raceways Carrying Circuits at 600 V or Less: Slit, pretensioned, flexible, solid-colored acrylic sleeve, 2 inches (50 mm) long, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

F. Write-On Tags: Polyester tag, 0.010 inch (0.25 mm) thick, with corrosion-resistant grommet and cable tie for attachment to conductor or cable.

1. Marker for Tags: Permanent, waterproof, black ink marker recommended by tag manufacturer.

2. Marker for Tags: Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer.

G. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 ARMORED AND METAL-CLAD CABLE IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway and cable size.

Page 29: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-3

B. Colors for Raceways Carrying Circuits at 600 V and Less:

1. Black letters on an orange field. 2. Legend: Indicate voltage and system or service type.

C. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

D. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; 2 inches (50 mm) wide; compounded for outdoor use.

2.03 POWER AND CONTROL CABLE IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway and cable size.

B. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

C. Write-On Tags: Polyester tag, 0.010 inch (0.25 mm) thick, with corrosion-resistant grommet and cable tie for attachment to conductor or cable.

1. Marker for Tags: Permanent, waterproof, black ink marker recommended by tag manufacturer.

2. Marker for Tags: Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer.

D. Snap-Around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

E. Snap-Around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeve, 2 inches (50 mm) long, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

2.04 CONDUCTOR IDENTIFICATION MATERIALS

A. Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils (0.08 mm) thick by 1 to 2 inches (25 to 50 mm) wide.

B. Self-Adhesive Vinyl Labels: Preprinted, flexible label laminated with a clear, weather- and chemical-resistant coating and matching wraparound adhesive tape for securing ends of legend label.

Page 30: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-4

C. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.

D. Write-On Tags: Polyester tag, 0.010 inch (0.25 mm) thick, with corrosion-resistant grommet and cable tie for attachment to conductor or cable.

1. Marker for Tags: Permanent, waterproof, black ink marker recommended by tag manufacturer.

2. Marker for Tags: Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer.

2.05 FLOOR MARKING TAPE

A. 2-inch- (50-mm-) wide, 5-mil (0.125-mm) pressure-sensitive vinyl tape, with black and white stripes and clear vinyl overlay.

2.06 UNDERGROUND-LINE WARNING TAPE

A. Tape:

1. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical and communications utility lines.

2. Printing on tape shall be permanent and shall not be damaged by burial operations.

3. Tape material and ink shall be chemically inert, and not subject to degrading when exposed to acids, alkalis, and other destructive substances commonly found in soils.

B. Color and Printing:

1. Comply with ANSI Z535.1 through ANSI Z535.5. 2. Inscriptions for Red-Colored Tapes: ELECTRIC LINE, HIGH VOLTAGE. 3. Inscriptions for Orange-Colored Tapes: TELEPHONE CABLE, CATV

CABLE, COMMUNICATIONS CABLE, OPTICAL FIBER CABLE.

C. Tag: Type I:

1. Pigmented polyolefin, bright-colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.

2. Thickness: 4 mils (0.1 mm). 3. Weight: 18.5 lb/1000 sq. ft. (9.0 kg/100 sq. m). 4. 3-Inch (75-mm) Tensile According to ASTM D 882: 30 lbf (133.4 N), and

2500 psi (17.2 MPa).

Page 31: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-5

D. Tag: Type ID:

1. Detectable three-layer laminate, consisting of a printed pigmented polyolefin film, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core, bright-colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.

2. Overall Thickness: 5 mils (0.125 mm). 3. Foil Core Thickness: 0.35 mil (0.00889 mm). 4. Weight: 28 lb/1000 sq. ft. (13.7 kg/100 sq. m). 5. 3-Inch (75-mm) Tensile According to ASTM D 882: 70 lbf (311.3 N), and

4600 psi (31.7 MPa).

2.07 WARNING LABELS AND SIGNS

A. Comply with NFPA 70 and 29 CFR 1910.145.

B. Self-Adhesive Warning Labels: Factory-printed, multicolor, pressure-sensitive adhesive labels, configured for display on front cover, door, or other access to equipment unless otherwise indicated.

C. Baked-Enamel Warning Signs:

1. Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size required for application.

2. 1/4-inch (6.4-mm) grommets in corners for mounting. 3. Nominal size, 7 by 10 inches (180 by 250 mm).

D. Metal-Backed, Butyrate Warning Signs:

1. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396-inch (1-mm) galvanized-steel backing; and with colors, legend, and size required for application.

2. 1/4-inch (6.4-mm) grommets in corners for mounting. 3. Nominal size, 10 by 14 inches (250 by 360 mm).

E. Warning label and sign shall include, but are not limited to, the following legends:

1. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES."

2. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 INCHES (915 MM)."

3. Other: Provide wording of warning signs or labels; e.g., arc-flash, multiple services and voltages, and others as indicated on drawings.

Page 32: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-6

2.08 INSTRUCTION SIGNS

A. Engraved, laminated acrylic or melamine plastic, minimum 1/16 inch (1.6 mm) thick for signs up to 20 sq. inches (129 sq. cm) and 1/8 inch (3.2 mm) thick for larger sizes.

1. Engraved legend with black letters on white face. 2. Punched or drilled for mechanical fasteners. 3. Framed with mitered acrylic molding and arranged for attachment at

applicable equipment.

B. Adhesive Film Label: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8 inch (10 mm).

C. Adhesive Film Label with Clear Protective Overlay: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8 inch (10 mm). Overlay shall provide a weatherproof and UV-resistant seal for label.

2.09 EQUIPMENT IDENTIFICATION LABELS

A. Adhesive Film Label with Clear Protective Overlay: Machine printed, in black, by thermal transfer or equivalent process. Minimum letter height shall be 3/8 inch (10 mm). Overlay shall provide a weatherproof and UV-resistant seal for label.

B. Self-Adhesive, Engraved, Laminated Acrylic or Melamine Label: Adhesive backed, with white letters on a dark-gray background. Minimum letter height shall be 3/8 inch (10 mm).

C. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1 inch (25 mm).

2.10 MISCELLANEOUS IDENTIFICATION PRODUCTS

A. Paint: Comply with requirements in painting Sections for paint materials and application requirements. Select paint system applicable for surface material and location (exterior or interior).

B. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.

Page 33: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-7

PART 3 - E X E C U T I O N

3.01 INSTALLATION

A. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment.

B. Apply identification devices to surfaces that require finish after completing finish work.

C. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.

D. Attach signs and plastic labels that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.

E. System Identification Color-Coding Bands for Raceways and Cables: Each color-coding band shall completely encircle cable or conduit. Place adjacent bands of two-color markings in contact, side by side. Locate bands at changes in direction, at penetrations of walls and floors, at 50-foot (15-m) maximum intervals in straight runs, and at 25-foot (7.6-m) maximum intervals in congested areas.

F. Underground-Line Warning Tape: During backfilling of trenches install continuous underground-line warning tape directly above line at 6 to 8 inches (150 to 200 mm) below finished grade. Use multiple tapes where width of multiple lines installed in a common trench or concrete envelope exceeds 16 inches (400 mm) overall.

G. Painted Identification: Comply with requirements in painting Sections for surface preparation and paint application.

3.02 IDENTIFICATION SCHEDULE

A. Accessible Raceways and Metal-Clad Cables, 600 V or Less, for Service, Feeder, and Branch Circuits More Than 30 A, and 120 V to ground: Install labels at 10-foot (3-m) maximum intervals.

B. Accessible Raceways and Cables within Buildings: Identify the covers of each junction and pull box of the following systems with self-adhesive vinyl labels with the wiring system legend and system voltage. System legends shall be as follows:

Page 34: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-8

1. Emergency Power. 2. Power. 3. UPS.

C. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use color-coding conductor tape to identify the phase.

1. Color-Coding for Phase and Voltage Level Identification, 600 V or Less: Use colors listed below for ungrounded service, feeder, and branch-circuit conductors.

a. Color shall be factory applied or field applied for sizes larger than No. 8 AWG, if authorities having jurisdiction permit.

b. Colors for 208/120-V Circuits:

1) Phase A: Black. 2) Phase B: Red. 3) Phase C: Blue.

c. Colors for 480/277-V Circuits:

1) Phase A: Brown. 2) Phase B: Orange. 3) Phase C: Yellow.

d. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 inches (150 mm) from terminal points and in boxes where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding. Locate bands to avoid obscuring factory cable markings.

D. Install instructional sign including the color-code for grounded and ungrounded conductors using adhesive-film-type labels.

E. Conductors to Be Extended in the Future: Attach write-on tags or marker tape to conductors and list source.

F. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections.

1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation.

2. Use system of marker tape designations that is uniform and consistent with system used by manufacturer for factory-installed connections.

3. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual.

Page 35: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-9

G. Locations of Underground Lines: Identify with underground-line warning tape for power, lighting, communication, and control wiring and optical fiber cable.

1. Limit use of underground-line warning tape to direct-buried cables. 2. Install underground-line warning tape for both direct-buried cables and

cables in raceway.

H. Workspace Indication: Install floor marking tape to show working clearances in the direction of access to live parts. Workspace shall be as required by NFPA 70 and 29 CFR 1926.403 unless otherwise indicated. Do not install at flush-mounted panelboards and similar equipment in finished spaces.

I. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Baked-enamel warning signs or metal-backed, butyrate warning signs.

1. Comply with 29 CFR 1910.145. 2. Identify system voltage with black letters on an orange background. 3. Apply to exterior of door, cover, or other access. 4. For equipment with multiple power or control sources, apply to door or

cover of equipment including, but not limited to, the following:

a. Power transfer switches. b. Controls with external control power connections.

J. Operating Instruction Signs: Install instruction signs to facilitate proper operation and maintenance of electrical systems and items to which they connect. Install instruction signs with approved legend where instructions are needed for system or equipment operation.

K. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8-inch- (10-mm-) high letters for emergency instructions at equipment as required.

L. Equipment Identification Labels: On each unit of equipment, install unique designation label that is consistent with wiring diagrams, schedules, and the Operation and Maintenance Manual. Apply labels to disconnect switches and protection equipment, central or master units, control panels, control stations, terminal cabinets, and racks of each system. Systems include power, lighting, control, communication, signal, monitoring, and alarm systems unless equipment is provided with its own identification.

1. Labeling Instructions:

a. Indoor Equipment: Engraved, laminated acrylic or melamine label. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on 1-1/2-inch- (38-mm-) high label;

Page 36: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO IDENTIFICATION FOR Burnett Transit Center Escalator Design ELECTRICAL SYSTEMS

260553-10

where two lines of text are required, use labels 2 inches (50 mm) high.

b. Outdoor Equipment: Engraved, laminated acrylic or melamine label, Stenciled legend 4 inches (100 mm) high.

c. Elevated Components: Increase sizes of labels and letters to those appropriate for viewing from the floor.

d. Unless provided with self-adhesive means of attachment, fasten labels with appropriate mechanical fasteners that do not change the NEMA or NRTL rating of the enclosure.

END OF SECTION

Page 37: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-1

Section 262726

WIRING DEVICES

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Receptacles, receptacles with integral GFCI, and associated device plates.

2. Weather-resistant receptacles. 3. Snap switches and wall-box dimmers. 4. Solid-state fan speed controls. 5. Wall-switch and exterior occupancy sensors. 6. Communications outlets.

1.02 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Receptacles for Owner-Furnished Equipment: Match plug configurations.

1.03 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

1.04 INFORMATIONAL SUBMITTALS

A. Field quality-control reports.

1.05 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.06 MEASUREMENT AND PAYMENT

A. Payment for Wiring Devices is on a Lump Sum basis.

Page 38: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-2

PART 2 - P R O D U C T S

2.01 MANUFACTURERS

A. Acceptable Manufacturers' include the following: 1. Cooper Wiring Devices; Division of Cooper Industries, Inc. (Cooper). 2. Hubbell Incorporated; Wiring Device-Kellems (Hubbell). 3. Leviton Mfg. Company Inc. (Leviton). 4. Pass & Seymour/Legrand (Pass & Seymour).

B. Source Limitations: Obtain each type of wiring device and associated wall plate from single source from single manufacturer.

C. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 GENERAL WIRING-DEVICE REQUIREMENTS

A. Wiring Devices, Components, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NFPA 70.

C. Devices that are manufactured for use with modular plug-in connectors may be substituted under the following conditions:

1. Connectors shall comply with UL 2459 and shall be made with stranding building wire.

2. Devices shall comply with the requirements in this Section.

2.03 STRAIGHT-BLADE RECEPTACLES

A. Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498, and FS W-C-596.

1. Products: Subject to compliance with requirements, provide one of the following:

a. Cooper; 5351 (single), CR5362 (duplex). b. Hubbell; HBL5351 (single), HBL5352 (duplex). c. Leviton; 5891 (single), 5352 (duplex). d. Pass & Seymour; 5361 (single), 5362 (duplex).

Page 39: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-3

2.04 GFCI RECEPTACLES

A. General Description:

1. Straight blade, feed-through type. 2. Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 943 Class A, and

FS W-C-596. 3. Include indicator light that shows when the GFCI has malfunctioned and

no longer provides proper GFCI protection.

B. Duplex GFCI Convenience Receptacles, 125 V, 20 A:

1. Products: Subject to compliance with requirements, provide one of the following:

a. Cooper; VGF20. b. Hubbell; GFR5352L. c. Pass & Seymour; 2095. d. Leviton; 7590.

2.05 TOGGLE SWITCHES

A. Comply with NEMA WD 1, UL 20, and FS W-S-896.

B. Switches, 120/277 V, 20 A:

1. Products: Subject to compliance with requirements, provide the following:

1) Single Pole: 2) Cooper; AH1221. 3) Hubbell; HBL1221. 4) Leviton; 1221-2. 5) Pass & Seymour; CSB20AC1. 6) Two Pole: 7) Cooper; AH1222. 8) Hubbell; HBL1222. 9) Leviton; 1222-2. 10) Pass & Seymour; CSB20AC2. 11) Three Way: 12) Cooper; AH1223. 13) Hubbell; HBL1223. 14) Leviton; 1223-2. 15) Pass & Seymour; CSB20AC3. 16) Four Way: 17) Cooper; AH1224. 18) Hubbell; HBL1224.

Page 40: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-4

19) Leviton; 1224-2. 20) Pass & Seymour; CSB20AC4.

C. Pilot-Light Switches, 20 A:

1. Products: Subject to compliance with requirements, provide the following:

a. Cooper; AH1221PL for 120 and 277 V. b. Hubbell; HBL1201PL for 120 and 277 V. c. Leviton; 1221-LH1. d. Pass & Seymour; PS20AC1RPL for 120 V, PS20AC1RPL7 for

277 V.

2. Description: Single pole, with neon-lighted handle, illuminated when switch is "off."

D. Key-Operated Switches, 120/277 V, 20 A:

1. Products: Subject to compliance with requirements, provide the following:

a. Cooper; AH1221L. b. Hubbell; HBL1221L. c. Leviton; 1221-2L. d. Pass & Seymour; PS20AC1-L.

2. Description: Single pole, with factory-supplied key in lieu of switch handle.

2.06 WALL PLATES

A. Single and combination types shall match corresponding wiring devices.

1. Plate-Securing Screws: Metal with head color to match plate finish. 2. Material for Finished Spaces: 0.035-inch- (1-mm-) thick, satin-finished,

Type 302 stainless steel. 3. Material for Unfinished Spaces: Galvanized steel. 4. Material for Damp Locations: Stainless steel with spring-loaded lift cover,

and listed and labeled for use in wet and damp locations.

B. Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R, weather-resistant, die-cast aluminum with lockable cover.

Page 41: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-5

2.07 FINISHES

A. Device Color:

1. Wiring Devices Connected to Normal Power System: As selected by Architect unless otherwise indicated or required by NFPA 70 or device listing.

2. Wiring Devices Connected to Emergency Power System: Red. 3. TVSS Devices: Blue.

B. Wall Plate Color: For plastic covers, match device color.

PART 3 - E X E C U T I O N

3.01 INSTALLATION

A. Comply with NECA 1, including mounting heights listed in that standard, unless otherwise indicated.

B. Coordination with Other Trades:

1. Protect installed devices and their boxes. Do not place wall finish materials over device boxes and do not cut holes for boxes with routers that are guided by riding against outside of boxes.

2. Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust, paint, and other material that may contaminate the raceway system, conductors, and cables.

3. Install device boxes in brick or block walls so that the cover plate does not cross a joint unless the joint is troweled flush with the face of the wall.

4. Install wiring devices after all wall preparation, including painting, is complete.

C. Conductors:

1. Do not strip insulation from conductors until right before they are spliced or terminated on devices.

2. Strip insulation evenly around the conductor using tools designed for the purpose. Avoid scoring or nicking of solid wire or cutting strands from stranded wire.

3. The length of free conductors at outlets for devices shall meet provisions of NFPA 70, Article 300, without pigtails.

4. Existing Conductors:

a. Cut back and pigtail, or replace all damaged conductors. b. Straighten conductors that remain and remove corrosion and foreign

matter.

Page 42: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-6

c. Pigtailing existing conductors is permitted, provided the outlet box is large enough.

D. Device Installation:

1. Replace devices that have been in temporary use during construction and that were installed before building finishing operations were complete.

2. Keep each wiring device in its package or otherwise protected until it is time to connect conductors.

3. Do not remove surface protection, such as plastic film and smudge covers, until the last possible moment.

4. Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm) in length.

5. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid conductor tightly clockwise, two-thirds to three-fourths of the way around terminal screw.

6. Use a torque screwdriver when a torque is recommended or required by manufacturer.

7. When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice No. 12 AWG pigtails for device connections.

8. Tighten unused terminal screws on the device. 9. When mounting into metal boxes, remove the fiber or plastic washers

used to hold device-mounting screws in yokes, allowing metal-to-metal contact.

E. Receptacle Orientation:

1. Install ground pin of vertically mounted receptacles up, and on horizontally mounted receptacles to the right.

F. Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.

G. Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension vertical and with grounding terminal of receptacles on top. Group adjacent switches under single, multigang wall plates.

H. Adjust locations of service poles to suit arrangement of partitions and furnishings.

3.02 GFCI RECEPTACLES

A. Install non-feed-through-type GFCI receptacles where protection of downstream receptacles is not required.

Page 43: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design WIRING DEVICES

262726-7

3.03 FIELD QUALITY CONTROL

A. Perform the following tests and inspections:

1. Test Instruments: Use instruments that comply with UL 1436. 2. Test Instrument for Convenience Receptacles: Digital wiring analyzer with

digital readout or illuminated digital-display indicators of measurement.

B. Tests for Convenience Receptacles:

1. Line Voltage: Acceptable range is 105 to 132 V. 2. Percent Voltage Drop under 15-A Load: A value of 6 percent or higher is

unacceptable. 3. Ground Impedance: Values of up to 2 ohms are acceptable. 4. GFCI Trip: Test for tripping values specified in UL 1436 and UL 943. 5. Using the test plug, verify that the device and its outlet box are securely

mounted. 6. Tests shall be diagnostic, indicating damaged conductors, high resistance

at the circuit breaker, poor connections, inadequate fault current path, defective devices, or similar problems. Correct circuit conditions, remove malfunctioning units and replace with new ones, and retest as specified above.

C. Wiring device will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

END OF SECTION

Page 44: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 45: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design FUSES

262813-1

SECTION 262813

FUSES

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes: Cartridge fuses rated 600-V ac and less for use in control circuits, enclosed switches, panelboards, and enclosed controllers.

1.02 ACTION SUBMITTALS

A. Product Data: For each type of product indicated.

1.03 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.04 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NEMA FU 1 for cartridge fuses.

C. Comply with NFPA 70.

1.05 MEASUREMENT AND PAYMENT

A. Payment for Fuses is on a Lump Sum basis.

PART 2 - P R O D U C T S

2.01 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Cooper Bussmann, Inc. 2. Edison Fuse, Inc. 3. Ferraz Shawmut, Inc. 4. Littelfuse, Inc.

Page 46: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design FUSES

262813-2

B. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 CARTRIDGE FUSES

A. Characteristics: NEMA FU 1, nonrenewable cartridge fuses with voltage ratings consistent with circuit voltages.

PART 3 - E X E C U T I O N

3.01 FUSE APPLICATIONS

A. Service Entrance: Class L, fast acting, Class L, time delay, Class RK1, fast acting, Class RK1, time delay, Class J, fast acting, Class J, time delay, Class T, fast acting. (As indicated on drawings).

B. Feeders: Class L, fast acting, Class L, time delay, Class RK1, fast acting, Class RK1, time delay, Class RK5, fast acting, Class RK5, time delay, Class J, fast acting, Class J, time delay. (As indicated on drawings).

C. Motor Branch Circuits: Class RK1, Class RK5, time delay.

D. Other Branch Circuits: Class RK1, time delay, Class RK5, time delay, Class J, fast acting, Class J, time delay.

E. Control Circuits: Class CC, fast acting, time delay.

3.02 INSTALLATION

A. Install fuses in fusible devices. Arrange fuses so rating information is readable without removing fuse.

3.03 IDENTIFICATION

A. Install labels complying with requirements for identification specified in Section 260553 "Identification for Electrical Systems" and indicating fuse replacement information on inside door of each fused switch and adjacent to each fuse block and holder.

END OF SECTION

Page 47: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-1

Section 262816

ENCLOSED SWITCHES AND CIRCUIT BREAKERS

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5. Molded-case circuit breakers (MCCBs). 6. Enclosures.

1.02 DEFINITIONS

A. NC: Normally closed.

B. NO: Normally open.

C. SPDT: Single pole, double throw.

1.03 PERFORMANCE REQUIREMENTS

A. Seismic Performance: Enclosed switches and circuit breakers shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."

1.04 ACTION SUBMITTALS

A. Product Data: For each type of enclosed switch, circuit breaker, accessory, and component indicated.

B. Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations, sections, details, and attachments to other work.

1. Wiring Diagrams: For power, signal, and control wiring.

Page 48: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-2

1.05 INFORMATIONAL SUBMITTALS

A. Seismic Qualification Certificates: For enclosed switches and circuit breakers, accessories, and components, from manufacturer.

B. Field quality-control reports.

1.06 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

1.07 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NFPA 70.

1.08 MEASUREMENT AND PAYMENT

A. Payment for Enclosed Switches and Circuit Breakers is on a Lump Sum basis.

PART 2 - P R O D U C T S

2.01 FUSIBLE SWITCHES

A. Basis-of-Design Product: Subject to compliance with requirements, provide comparable product by one of the following:

1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical

Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric.

B. Type GD, General Duty, Single Throw, 240-V ac, 800 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, with cartridge fuse interiors to accommodate specified fuses, lockable handle with capability to accept two padlocks, and interlocked with cover in closed position.

C. Type HD, Heavy Duty, Single Throw, 600-V ac, 1200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, with clips or bolt pads to accommodate

Page 49: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-3

specified fuses, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

D. Type HD, Heavy Duty, Six Pole, Single Throw, 600-V ac, 200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, with clips or bolt pads to accommodate specified fuses, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

E. Type HD, Heavy Duty, Double Throw, 600-V ac, 1200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, with clips or bolt pads to accommodate specified fuses, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

F. Accessories:

1. Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground conductors.

2. Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded; labeled for copper and aluminum neutral conductors.

3. Class R Fuse Kit: Provides rejection of other fuse types when Class R fuses are specified.

4. Lugs: Suitable for number, size, and conductor material. 5. Service-Rated Switches: Labeled for use as service equipment.

G. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 NONFUSIBLE SWITCHES

A. Basis-of-Design Product: Subject to compliance with requirements, provide comparable product by one of the following:

1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical

Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric.

B. Type GD, General Duty, Single Throw, 600 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, lockable handle with capability to accept two padlocks, and interlocked with cover in closed position.

C. Type HD, Heavy Duty, Single Throw, 600-V ac, 1200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

Page 50: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-4

D. Type HD, Heavy Duty, Six Pole, Single Throw, 600-V ac, 200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

E. Type HD, Heavy Duty, Double Throw, 600-V ac, 1200 A and Smaller: UL 98 and NEMA KS 1, horsepower rated, lockable handle with capability to accept three padlocks, and interlocked with cover in closed position.

F. Accessories:

1. Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground conductors.

2. Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded; labeled for copper and aluminum neutral conductors.

3. Lugs: Suitable for number, size, and conductor material.

2.03 RECEPTACLE SWITCHES

A. Basis-of-Design Product: Subject to compliance with requirements, provide comparable product by one of the following:

1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical

Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric.

B. Type HD, Heavy-Duty, Single-Throw Fusible Switch: 600-V ac, 100 A; UL 98 and NEMA KS 1; horsepower rated, with clips or bolt pads to accommodate specified fuses; lockable handle with capability to accept three padlocks; interlocked with cover in closed position.

C. Type HD, Heavy-Duty, Single-Throw Nonfusible Switch: 600-V ac, 100 A; UL 98 and NEMA KS 1; horsepower rated, lockable handle with capability to accept three padlocks; interlocked with cover in closed position.

D. Interlocking Linkage: Provided between the receptacle and switch mechanism to prevent inserting or removing plug while switch is in the on position, inserting any plug other than specified, and turning switch on if an incorrect plug is inserted or correct plug has not been fully inserted into the receptacle.

E. Receptacle: Polarized, three-phase, four-wire receptacle (fourth wire connected to enclosure ground lug).

Page 51: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-5

2.04 SHUNT TRIP SWITCHES

A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:

1. Cooper Bussmann, Inc. 2. Ferraz Shawmut, Inc. 3. Littelfuse, Inc.

B. General Requirements: Comply with ASME A17.1, UL 50, and UL 98, with 200-kA interrupting and short-circuit current rating when fitted with Class J fuses.

C. Switches: Three-pole, horsepower rated, with integral shunt trip mechanism and Class J fuse block; lockable handle with capability to accept three padlocks; interlocked with cover in closed position.

D. Control Circuit: 120-V ac; obtained from integral control power transformer, with primary and secondary fuses, with a control power transformer of enough capacity to operate shunt trip, connected pilot, and indicating and control devices.

E. Accessories:

1. Oiltight key switch for key-to-test function. 2. Oiltight ON pilot light. 3. Isolated neutral lug. 4. Mechanically interlocked auxiliary contacts that change state when switch

is opened and closed. 5. Form C alarm contacts that change state when switch is tripped. 6. Three-pole, double-throw, fire-safety and alarm relay; 120-V ac or 24-

V dc coil voltage per equipment manufacturers’ requirements. 7. Three-pole, double-throw, fire-alarm voltage monitoring relay complying

with NFPA 72.

2.05 MOLDED-CASE CIRCUIT BREAKERS

A. Basis-of-Design Product: Subject to compliance with requirements, provide comparable product by one of the following:

1. Eaton Electrical Inc.; Cutler-Hammer Business Unit. 2. General Electric Company; GE Consumer & Industrial - Electrical

Distribution. 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric.

Page 52: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-6

B. General Requirements: Comply with UL 489, NEMA AB 1, and NEMA AB 3, with interrupting capacity to comply with available fault currents.

C. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger.

D. Electronic Trip Circuit Breakers: Field-replaceable rating plug, rms sensing, with the following field-adjustable settings:

1. Instantaneous trip. 2. Long- and short-time pickup levels. 3. Long- and short-time time adjustments. 4. Ground-fault pickup level, time delay, and I2t response.

E. Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller, and let-through ratings less than NEMA FU 1, RK-5.

F. Features and Accessories:

1. Standard frame sizes, trip ratings, and number of poles. 2. Lugs: Suitable for number, size, trip ratings, and conductor material. 3. Application Listing: Appropriate for application; Type SWD for switching

fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity discharge lighting circuits.

4. Ground-Fault Protection: Comply with UL 1053; integrally mounted, self-powered type with mechanical ground-fault indicator; relay with adjustable pickup and time-delay settings, push-to-test feature, internal memory, and shunt trip unit; and three-phase, zero-sequence current transformer/sensor.

5. Shunt Trip: Trip coil energized from separate circuit, with coil-clearing contact.

6. Auxiliary Contacts: Two SPDT switches with "a" and "b" contacts; "a" contacts mimic circuit-breaker contacts, "b" contacts operate in reverse of circuit-breaker contacts.

7. Alarm Switch: One NO contact that operates only when circuit breaker has tripped.

2.06 ENCLOSURES

A. Enclosed Switches and Circuit Breakers: NEMA AB 1, NEMA KS 1, NEMA 250, and UL 50, to comply with environmental conditions at installed location.

1. Indoor, Dry and Clean Locations: NEMA 250, Type 1. 2. Outdoor Locations: NEMA 250, Type 3R.

Page 53: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-7

3. Other Wet or Damp, Indoor Locations: NEMA Type 4X stainless steel. 4. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive

Liquids: NEMA 250, Type 12.

PART 3 - E X E C U T I O N

3.01 INSTALLATION

A. Install individual wall-mounted switches and circuit breakers with tops at uniform height unless otherwise indicated.

B. Comply with mounting and anchoring requirements specified in Section 260548 "Vibration and Seismic Controls for Electrical Systems."

C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from enclosures and components.

D. Install fuses in fusible devices.

E. Comply with NECA 1.

3.02 IDENTIFICATION

A. Comply with requirements in Section 260553 "Identification for Electrical Systems."

1. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs.

2. Label each enclosure with engraved metal or laminated-plastic nameplate.

3.03 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Acceptance Testing Preparation:

1. Test insulation resistance for each enclosed switch and circuit breaker, component, connecting supply, feeder, and control circuit.

2. Test continuity of each circuit.

Page 54: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO ENCLOSED SWITCHES Burnett Transit Center Escalator Design AND CIRCUIT BREAKERS

262816-8

C. Tests and Inspections:

1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.

D. Enclosed switches and circuit breakers will be considered defective if they do not pass tests and inspections.

E. Prepare test and inspection reports, including a certified report that identifies enclosed switches and circuit breakers and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

END OF SECTION

Page 55: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design LIGHTING FIXTURES

265600-1

Section 265600

LIGHTING FIXTURES

PART 1 - G E N E R A L

1.01 DESCRIPTION

A. This section specifies the requirements for proving lighting fixtures and lamps.

1.02 QUALITY ASSURANCE

A. Reference Standards Applicable to this Section

1. ANSI: American National Standards Institute

a. C78.377: Specification for Chromacity of Solid State Lighting Products.

2. IES: Illumination Engineering Society of North America

a. LM-79-08: Electrical and Photometric Measurement of Solid State Lighting Products

b. LM-80-08: Measuring Lumen Maintenance of LED Light Sources.

c. TM-21-11: Projecting Long Term Lumen Maintenance of LED Light Sources.

d. LM-82-11: IES Approved Method for Chromacity LED Light Engines and LED Lamps for Electrical and Photometric Properties as a function of Temperature.

3. NFPA: National Fire Protection Association

a. 70: National Electrical Code (NEC)

4. UL: Underwriters Laboratories, Inc. a. 57: Electrical Lighting Fixtures b. 8750: UL Standard for Safety LED Equipment for use in Lighting

Products.

1.03 SUBMITTALS

A. Submittals shall be presented according to the terms of the contract and Specified in Section for Shop Drawings, Product Data, and Samples.

Page 56: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design LIGHTING FIXTURES

265600-2

B. Specific items to be submitted:

1. Manufactures data sheets, specifications, photometrics and details of

Lighting fixtures. 2. A computer printout of the light distribution, in ft-candles, for outdoor

Areas.

1.04 PRODUCT DELIVERY, STORAGE, AND HANDLING

A. Deliver equipment in sealed manufacturers, containers, appropriately packaged and crated for protection during domestic shipment and storage in humid, dusty conditions.

B. Indelibly label all containers, including containers contained within others, On outside with item description(s) per title, Mark Numbers, and this Section number.

C. Store indoors all light fixtures and other items subject to damage due to Exposure to weather conditions and moisture accumulation.

1.05 LABELING

A. Manufacturer shall securely attach in a prominent location on each

major item of equipment a 316 Stainless Steel nameplate showing manufacturer's name, address, model number, serial number, and pertinent utility or operating data.

1.06 MEASUREMENT AND PAYMENT

A. Payment for Lighting Fixtures is on lump sum basis.

PART 2 - P R O D U C T S

2.01 LIGHTING FIXTURES

A. Standards: UL 57, UL 8750, as applicable, and NFPA 70 (NEC). UL listed and labeled.

B. Lighting Fixture Types, Materials and Finishes: As indicated on Lighting

Fixture schedules shown on Drawings.

C. Drivers 1. Drivers shall be suitable and compatible to LED fixtures to meet ANSI,

IES, and UL standards as applicable. ANSI C78.377, UL 8750, UL listed and labeled.

Page 57: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design LIGHTING FIXTURES

265600-3

D. Lamps

1. General Requirements: Number type and wattage of lamps shall be as indicated on drawings.

E. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 GROUNDING

A. Lighting fixtures grounding shall be as specified in Section 16450 - Grounding.

PART 3 - E X C U T I O N

3.01 INSPECTION

A. Locations in which products are to be installed shall be examined for conditions dehimental to installation.

B. Do not proceed with installation until all unsatisfactory conditions have

been corrected.

3.02 LIGHTING FIXTURES

A. Lighting fixtures shall be installed, in accordance with fixture manufacturer's written instructions and procedures, applicable requirements of NFPA 70 (NEC) and as indicated.

B. Lighting fixture shall be aligned. Fixtures shall be plumb and level.

C. Where the indicated location for lighting fixtures interfere with other

equipment, change lighting fixture layout to avoid interference and submit for approval before installation.

D. Lighting fixture supports shall be anchored to channels of ceiling

construction, to structural slab or to structural members as required.

E. Surface mounted lighting fixtures shall be bracketed rigidly from the mounting surfaces. Where the fixture is flat mounted against concrete surfaces, a suitable clearance shall be provided between fixture and concrete.

Page 58: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design LIGHTING FIXTURES

265600-4

F. Where aluminum is placed against dissimilar metals, except galvanized steel, stainless steel or zinc. The contact surfaces shall be separated in a suitable manner approved by METRO.

3.03 LAMPS

A. Lamps of the indicated types, wattage's and number shall be installed in

Lighting Fixtures.

END OF SECTION

Page 59: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design ELECTRICAL TESTING

266000-1

Section 266000

ELECTRICAL TESTING

PART 1 – G E N E R A L 1.01 RELATED DOCUMENTS

A. The requirements of the General Conditions, Supplementary Conditions and the following specification sections apply to all Work herein:

1. Section 260010 - Electrical General Requirements.

1.02 SUMMARY

A. Provide all testing to demonstrate proper operation as required by these Specifications, the City of Houston, and the authorities having jurisdiction of the electric system, equipment and components as indicated on the Drawings and as specified herein. Tests shall include, but not be limited to the items specified in this section and in other Division 26 Specification sections.

1.03 QUALITY ASSURANCE

A. Submit evidence to show that the personnel who will actually test the systems are qualified to perform the required Work.

B. All test procedures shall be in accordance with the manufacturer’s

recommendations for the equipment being tested. 1.04 SUBMITTAL DATA

A. The following submittal data shall be furnished according to the General Conditions and Section 260010 and shall include, but not be limited to:

1. Test Procedures for all tests proposed. 2. Recording Forms. 3. Test Data and Results including the following:

a. Test performed. b. Test procedure. c. System and area tested. d. Date(s) and time(s) of test. e. Weather conditions. f. Test criteria. g. Test results. h. Additional pertinent data.

Page 60: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design ELECTRICAL TESTING

266000-2

4. Instruments including documentation that such instruments were

properly calibrated at the time of the testing.

5. Personnel and Qualifications

B. All items or equipment listed above with asterisks (*) shall be certified by the manufacturer using Manufacturer Certification “MCA” as set forth in Section 260010. See Section 260010 for certification requirements.

1.05 MEASUREMENT AND PAYMENT

A. Payment for Electrical Testing is on a Lump Sum basis.

PART 2 – P R O D U C T S

2.01 TESTING MATERIALS

A. Provide all materials and test equipment required for testing of specified electrical system components, including any retests required to obtain acceptable results.

B. Testing materials that fail to provide acceptable test results shall be

repaired or replaced with suitable materials as required to obtain acceptable test results.

C. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

PART 3 – E X E C U T I O N 3.01 FACTORY TESTING

A. Refer to the various Division 26 Specification sections for requirements for factory testing of equipment and devices.

3.02 FIELD TESTING OF ELECTRICAL SYSTEMS

A. During the progress of the Work and upon completion, tests shall be made as specified herein and as required by authorities having jurisdiction including inspectors, Owner or Owner’s Representative, Owner's insurance agency. Tests shall be witnessed by the Electrical

Page 61: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design ELECTRICAL TESTING

266000-3

Subcontractor as part of the Work of this Division and shall include the services of qualified personnel as well as all equipment, apparatus, and services required. Each wiring system with devices connected must test free from short circuits and from grounds and must have an insulation resistance between conductors and ground, based on maximum load, not less than the requirements of the latest edition of the National Electrical Code.

B. In accordance with the Subcontractor Scheduling Procedures in Section

260010 titled “Electrical General Provisions”, the Electrical Subcontractor shall submit in writing proposed test procedures, recording forms, list of personnel and qualifications and test equipment for the Owner's or Owner’s Representative’s review.

C. The tests shall include but not be limited to the following:

1. Electrical conductor tests as specified in Section 260519 titled

“Low-Voltage Electrical Power Cables” and Section 260523 titled “Control-Voltage Electrical Power Cables.

2. Grounding system tests as specified in Section 260526 titled

“Grounding and Bonding for Electrical Systems”.

3. Operation of entire electrical power system including:

a. Voltage and current readings for each feeder and motor circuit under maximum operating conditions. Readings shall be submitted to the Owner or Owner’s Representative for review. Readings questioned shall be repeated for confirmation.

b. Operation of lighting and receptacle circuits with associated

switching and controls, including dimmer systems.

c. Running of motors with demonstration of controls and interlocks.

d. Operation of transformers with voltage check while loaded to

assure proper transformer tap settings.

e. Operation of electrical equipment and appliances whether provided under this Division or not.

4. Demonstration and operating test of the entire Fire Detection,

Alarm and Communication System as required by the Owner and the local authorities.

Page 62: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design ELECTRICAL TESTING

266000-4

D. The foregoing shall in no way relieve the Contractor of any warranty requirements.

END OF SECTION

Page 63: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-1

Section 270528

PATHWAYS FOR COMMUNICATIONS SYSTEMS

PART 1 – G E N E R A L

1.01 SECTION INCLUDES

A. Metal conduits and fittings. B. Nonmetallic conduits and fittings. C. Surface pathways. D. Boxes, enclosures, and cabinets. E. Handholes and boxes for exterior underground cabling.

1.02 RELATED REQUIREMENTS:

A. Section 260533 "Raceways and Boxes for Electrical Systems" for conduits, wireways, surface raceways, boxes, enclosures, cabinets, handholes, and faceplate adapters serving electrical systems.

1.03 ACTION SUBMITTALS

A. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For custom enclosures and cabinets.

1.04 MEASUREMENT AND PAYMENT

A. Payment for Pathways for Communications Systems is on a Lump Sum basis.

PART 2 – P R O D U C T S

2.01 METAL CONDUITS AND FITTINGS

A. General Requirements for Metal Conduits and Fittings:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Comply with TIA-569-B.

B. GRC: Comply with ANSI C80.1 and UL 6.

Page 64: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-2

C. ARC: Comply with ANSI C80.5 and UL 6A.

D. EMT: Comply with ANSI C80.3 and UL 797.

E. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.

1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886 and NFPA 70.

2. Fittings for EMT:

a. Material: Steel or die cast. b. Type: Compression.

3. Expansion Fittings: PVC or steel to match conduit type, complying with UL-467, rated for environmental conditions where installed, and including flexible external bonding jumper.

F. Joint Compound for GRC or ARC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity.

G. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 NONMETALLIC CONDUITS AND FITTINGS

A. General Requirements for Nonmetallic Conduits and Fittings:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Comply with TIA-569-B.

B. RNC: Type EPC-40-PVC, complying with NEMA TC 2 and UL 651 unless otherwise indicated.

C. Continuous HDPE: Comply with UL 651B.

D. Fittings for RNC: Comply with NEMA TC 3; match to conduit or tubing type and material.

2.03 SURFACE PATHWAYS

A. General Requirements for Surface Pathways:

Page 65: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-3

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Comply with TIA-569-B.

B. Surface Metal Pathways: Galvanized steel with snap-on covers complying with UL 5. Manufacturer's standard enamel finish.

C. Surface Nonmetallic Pathways: Two- or three-piece construction, complying with UL 5A, and manufactured of rigid PVC with texture and color selected by Architect from manufacturer's standard colors. Product shall comply with UL-94 V-0 requirements for self-extinguishing characteristics.

D. Tele-Power Poles:

1. Material: Galvanized steel with baked-enamel finish. 2. Fittings and Accessories: Dividers, end caps, covers, cutouts, wiring harnesses,

devices, mounting materials, and other fittings shall match and mate with tele-power pole as required for complete system.

2.04 BOXES, ENCLOSURES, AND CABINETS

A. General Requirements for Boxes, Enclosures, and Cabinets:

1. Comply with TIA-569-B. 2. Boxes, enclosures and cabinets installed in wet locations shall be listed for use in

wet locations.

B. Sheet-Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloy, Type FD, with gasketed cover.

D. Box extensions used to accommodate new building finishes shall be of same material as recessed box.

E. Metal Floor Boxes:

1. Material: Cast metal or sheet metal (in mechanical or electrical rooms). 2. Type: Fully adjustable. 3. Listing and Labeling: Metal floor boxes shall be listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

F. Nonmetallic Floor Boxes: Nonadjustable, rectangular.

Page 66: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-4

G. Listing and Labeling: Nonmetallic floor boxes shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

H. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

I. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, galvanized, cast iron or stainless steel (as required) with gasketed cover.

J. Device Box Dimensions: 4 inches square by 2-1/8 inches deep (100 mm square by 60 mm deep).

K. Gangable boxes are prohibited.

L. Nonmetallic Outlet and Device Boxes: Comply with NEMA OS 2 and UL 514C.

M. Hinged-Cover Enclosures: Comply with UL 50 and NEMA Type 4X with continuous-hinge cover with flush latch unless otherwise indicated.

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

2. Nonmetallic Enclosures: Plastic or fiberglass finished inside with radio-frequency-resistant paint.

3. Interior Panels: Steel; all sides finished with manufacturer's standard enamel.

N. Cabinets:

1. NEMA Type 3R galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge. 3. Key latch to match panelboards. 4. Metal barriers to separate wiring of different systems and voltage. 5. Accessory feet where required for freestanding equipment. 6. Nonmetallic cabinets shall be listed and labeled as defined in NFPA 70, by a

qualified testing agency, and marked for intended location and application.

2.05 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND CABLING

A. General Requirements for Handholes and Boxes:

1. Boxes and handholes for use in underground systems shall be designed and identified as defined in NFPA 70, for intended location and application.

2. Boxes installed in wet areas shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Comply with TIA-569-B.

Page 67: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-5

B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and aggregate, bound together with polymer resin, and reinforced with steel, fiberglass, or a combination of the two.

1. Standard: Comply with SCTE 77. 2. Configuration: Designed for flush burial with integral closed bottom unless

otherwise indicated. 3. Cover: Weatherproof, secured by tamper-resistant locking devices and having

structural load rating consistent with enclosure and handhole location. 4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50. 5. Cover Legend: Molded lettering, "COMMUNICATIONS."

C. Fiberglass Handholes and Boxes: Molded of fiberglass-reinforced polyester resin, with frame and covers of reinforced concrete, cast iron, hot-dip galvanized-steel diamond plate.

1. Standard: Comply with SCTE 77. 2. Color of Frame and Cover: Gray. 3. Configuration: Designed for flush burial with integral closed bottom unless

otherwise indicated. 4. Cover: Weatherproof, secured by tamper-resistant locking devices and having

structural load rating consistent with enclosure and handhole location. 5. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50. 6. Cover Legend: Molded lettering, "COMMUNICATIONS."

PART 3 – E X E C U T I ON

3.01 PATHWAY APPLICATION

A. Outdoors: Apply pathway products as specified below unless otherwise indicated:

1. Exposed Conduit: GRC. 2. Concealed Conduit, Aboveground: EMT. 3. Underground Conduit: RNC, Type EPC-80-PVC, concrete encased. 4. Boxes and Enclosures, Aboveground: NEMA Type 4X.

B. Indoors: Apply pathway products as specified below unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: RMC. 2. Exposed, Not Subject to Severe Physical Damage: RMC identified for such use. 3. Exposed and Subject to Severe Physical Damage: GRC PVC coated. 4. Concealed in Ceilings and Interior Walls and Partitions: GRC OR RMC. 5. Damp or Wet Locations: GRC PVC coated. 6. Boxes and Enclosures: NEMA 250 Type 1, except use NEMA Type 4X stainless

steel in institutional and commercial kitchens and damp or wet locations.

Page 68: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-6

C. Minimum Pathway Size: 3/4-inch (21-mm) trade size. Minimum size for optical-fiber cables is 1 inch (27 mm).

D. Pathway Fittings: Compatible with pathways and suitable for use and location.

1. Rigid Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB 2.10.

E. Do not install aluminum conduits, boxes, or fittings in contact with concrete or earth.

F. Install surface pathways only where indicated on Drawings.

G. Do not install nonmetallic conduit where ambient temperature exceeds 120 deg F (49 deg C).

3.02 INSTALLATION

A. Comply with NECA 1, NECA 101, and TIA-569-B for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NECA 102 for aluminum pathways. Comply with NFPA 70 limitations for types of pathways allowed in specific occupancies and number of floors.

B. Keep pathways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal pathway runs above water and steam piping.

C. Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for hangers and supports.

D. Arrange stub-ups so curved portions of bends are not visible above finished slab.

E. Install no more than the equivalent of two 90-degree bends in any pathway run. Support within 12 inches (300 mm) of changes in direction. Utilize long radius ells for all optical-fiber cables.

F. Conceal conduit and EMT within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines.

G. Pathways Embedded in Slabs:

1. Run conduit larger than 1-inch (27-mm) trade size, parallel or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support. Secure pathways to reinforcement at maximum 10-foot (3-m) intervals.

2. Arrange pathways to cross building expansion joints at right angles with expansion fittings.

3. Arrange pathways to keep a minimum of 2 inches (50 mm) of concrete cover in all directions.

Page 69: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-7

4. Do not embed threadless fittings in concrete unless specifically approved by Architect for each specific location.

H. Stub-ups to Above Recessed Ceilings:

1. Use a conduit bushing or insulated fitting to terminate stub-ups not terminated in hubs or in an enclosure.

I. Coat field-cut threads on PVC-coated pathway with a corrosion-preventing conductive compound prior to assembly.

J. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install insulated bushings on conduits terminated with locknuts.

K. Install pathways square to the enclosure and terminate at enclosures with locknuts. Install locknuts hand tight plus 1/4 turn more.

L. Do not rely on locknuts to penetrate nonconductive coatings on enclosures. Remove coatings in the locknut area prior to assembling conduit to enclosure to assure a continuous ground path.

M. Spare Pathways: Install pull wires in empty pathways. Cap underground pathways designated as spare above grade alongside pathways in use.

N. Surface Pathways:

1. Install surface pathway for surface telecommunications outlet boxes only where indicated on Drawings.

O. Pathways for Optical-Fiber and Communications Cable: Install pathways as follows:

1. 3/4-Inch (21-mm) Trade Size and Smaller: Install pathways in maximum lengths of 50 feet (15 m).

2. 1-Inch (27-mm) Trade Size and Larger: Install pathways in maximum lengths of 75 feet (23 m).

3. Install with a maximum of two 90-degree bends or equivalent for each length of pathway unless Drawings show stricter requirements.

P. Install pathway sealing fittings at accessible locations according to NFPA 70 and fill them with listed sealing compound.

Q. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal the interior of all pathways at the following points:

1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces.

2. Where an underground service pathway enters a building or structure. 3. Where otherwise required by NFPA 70.

Page 70: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-8

R. Expansion-Joint Fittings:

1. Install in each run of aboveground RNC that is located where environmental temperature change may exceed 30 deg F (17 deg C), and that has straight-run length that exceeds 25 feet (7.6 m). Install in each run of aboveground RMC conduit that is located where environmental temperature change may exceed 100 deg F (55 deg C) and that has straight-run length that exceeds 100 feet (30 m).

2. Install type and quantity of fittings that accommodate temperature change listed for each of the following locations:

a. Outdoor Locations Not Exposed to Direct Sunlight: 125 deg F (70 deg C) temperature change.

b. Outdoor Locations Exposed to Direct Sunlight: 155 deg F (86 deg C) temperature change.

c. Indoor Spaces Connected with Outdoors without Physical Separation: 125 deg F (70 deg C) temperature change.

d. Attics: 135 deg F (75 deg C) temperature change.

3. Install fitting(s) that provide expansion and contraction for at least 0.00041 inch per foot of length of straight run per deg F (0.06 mm per meter of length of straight run per deg C) of temperature change for PVC conduits. Install fitting(s) that provide expansion and contraction for at least 0.000078 inch per foot of length of straight run per deg F (0.0115 mm per meter of length of straight run per deg C) of temperature change for metal conduits.

4. Install expansion fittings at all locations where conduits cross building or structure expansion joints.

5. Install each expansion-joint fitting with position, mounting, and piston setting selected according to manufacturer's written instructions for conditions at specific location at time of installation. Install conduit supports to allow for expansion movement.

S. Mount boxes at heights indicated on Drawings in accordance with ADA requirements. Install boxes with height measured to center of box unless otherwise indicated.

T. Horizontally separate boxes mounted on opposite sides of walls so they are not in the same vertical channel.

3.03 INSTALLATION OF UNDERGROUND CONDUIT

A. Direct-Buried Conduit:

1. Excavate trench bottom to provide firm and uniform support for conduit. Prepare trench bottom as specified in Section 312000 "Earth Moving" for pipe less than 6 inches (150 mm) in nominal diameter.

2. Install backfill as specified in Section 312000 "Earth Moving." 3. After installing conduit, backfill and compact. After placing controlled backfill to

within 12 inches (300 mm) of finished grade, make final conduit connection at end

Page 71: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO PATHWAYS FOR Burnett Transit Center Escalator Design COMMUNICATIONS SYSTEMS

270528-9

of run and complete backfilling with normal compaction as specified in Section 312000 "Earth Moving."

4. Install manufactured rigid steel conduit elbows for stub-ups at poles and equipment and at building entrances through floor.

a. Couple steel conduits to ducts with adapters designed for this purpose, and encase coupling with 3 inches (75 mm) of concrete for a minimum of 12 inches (300 mm) on each side of the coupling.

b. For stub-ups at equipment mounted on outdoor concrete bases and where conduits penetrate building foundations, extend steel conduit horizontally a minimum of 60 inches (1500 mm) from edge of foundation or equipment base. Install insulated grounding bushings on terminations at equipment.

5. Underground Warning Tape: Comply with requirements in Section 260553 "Identification for Electrical Systems."

3.04 INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES

A. Install handholes and boxes level and plumb and with orientation and depth coordinated with connecting conduits to minimize bends and deflections required for proper entrances.

B. Elevation: In paved areas, set so cover surface will be flush with finished grade. Set covers of other enclosures 1 inch (25 mm) above finished grade.

C. Install handholes with bottom below frost line, below grade.

D. Field cut openings for conduits according to enclosure manufacturer's written instructions.

3.05 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR COMMUNICATIONS PENETRATIONS

A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 270544 "Sleeves and Sleeve Seals for Communications Pathways and Cabling."

3.06 FIRESTOPPING

A. Install firestopping at penetrations of fire-rated floor and wall assemblies. Comply with requirements in Section 078413 "Penetration Firestopping."

3.07 PROTECTION

A. Protect coatings, finishes, and cabinets from damage or deterioration.

END OF SECTION

Page 72: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 73: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design COMMUNICATIONS PATHWAYS AND CABLING

270544-1

Section 270544

SLEEVES AND SLEEVE SEALS FOR COMMUNICATIONS PATHWAYS AND CABLING

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section Includes:

1. Sleeves for pathway and cable penetration of non-fire-rated construction walls and floors.

2. Sleeve-seal systems. 3. Sleeve-seal fittings. 4. Grout. 5. Silicone sealants.

B. Related Requirements:

1. Section 078413 "Penetration Firestopping" for penetration firestopping installed in fire-resistance-rated walls, horizontal assemblies, and smoke barriers, with and without penetrating items.

1.02 MEASUREMENT AND PAYMENT

A. Payment for Sleeves and Sleeve Seals for Communications Pathways and Cabling is on a Lump Sum basis.

PART 2 - P R O D U C T S

2.01 SLEEVES

A. Wall Sleeves:

1. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, plain ends.

2. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.

B. Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies: Galvanized-steel sheet; 0.0239-inch (0.6-mm) minimum thickness; round tube

Page 74: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design COMMUNICATIONS PATHWAYS AND CABLING

270544-2

closed with welded longitudinal joint, with tabs for screw-fastening the sleeve to the board.

C. Sleeves for Rectangular Openings:

1. Material: Galvanized-steel sheet. 2. Minimum Metal Thickness:

a. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and with no side larger than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm).

b. For sleeve cross-section rectangle perimeter 50 inches (1270 mm) or more and one or more sides larger than 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).

D. It is the Contractor’s responsibility to confirm that all products/vendors meet the “BUY AMERICA” requirement and the Contractor must provide documentation in accordance with Specification 01 33 00 – Submittal Procedures.

2.02 SLEEVE-SEAL SYSTEMS

A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and pathway or cable.

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following:

a. Advance Products & Systems, Inc. b. CALPICO, Inc. c. Metraflex Company (The). d. Pipeline Seal and Insulator, Inc. e. Proco Products, Inc.

2. Sealing Elements: EPDM or Nitrile (Buna N) rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.

3. Pressure Plates: Stainless steel. 4. Connecting Bolts and Nuts: Stainless steel of length required to secure

pressure plates to sealing elements.

2.03 SLEEVE-SEAL FITTINGS

A. Description: Manufactured plastic, sleeve-type, waterstop assembly made for embedding in concrete slab or wall. Unit shall have plastic or rubber waterstop collar with center opening to match piping OD.

Page 75: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design COMMUNICATIONS PATHWAYS AND CABLING

270544-3

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by the following:

a. Presealed Systems.

2.04 GROUT

A. Description: Nonshrink; recommended for interior and exterior sealing openings in non-fire-rated walls or floors.

B. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.

C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

2.05 SILICONE SEALANTS

A. Silicone Sealants: Single-component, silicone-based, neutral-curing elastomeric sealants of grade indicated below.

B. Silicone Foams: Multicomponent, silicone-based liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam.

PART 3 - E X E C U T I O N

3.01 SLEEVE INSTALLATION FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS

A. Comply with NECA 1.

B. Comply with NEMA VE 2 for cable tray and cable penetrations.

C. Sleeves for Conduits Penetrating Above-Grade Non-Fire-Rated Concrete and Masonry-Unit Floors and Walls:

1. Interior Penetrations of Non-Fire-Rated Walls and Floors:

a. Seal annular space between sleeve and pathway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Section 079200 "Joint Sealants."

b. Seal space outside of sleeves with mortar or grout. Pack sealing material solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect material while curing.

Page 76: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design COMMUNICATIONS PATHWAYS AND CABLING

270544-4

2. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

3. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pathway or cable unless sleeve seal is to be installed or unless seismic criteria require different clearance.

4. Install sleeves for wall penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush with both surfaces of walls. Deburr after cutting.

5. Install sleeves for floor penetrations. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level. Install sleeves during erection of floors.

D. Sleeves for Conduits Penetrating Non-Fire-Rated Gypsum Board Assemblies:

1. Use circular metal sleeves unless penetration arrangement requires rectangular sleeved opening.

2. Seal space outside of sleeves with approved joint compound for gypsum board assemblies.

E. Roof-Penetration Sleeves: Seal penetration of individual pathways and cables with flexible boot-type flashing units applied in coordination with roofing work.

F. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical sleeve seals.

G. Underground, Exterior-Wall and Floor Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch (25-mm) annular clear space between pathway or cable and sleeve for installing sleeve-seal system.

3.02 SLEEVE-SEAL-SYSTEM INSTALLATION

A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at pathway entries into building.

B. Install type and number of sealing elements recommended by manufacturer for pathway or cable material and size. Position pathway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pathway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

3.03 SLEEVE-SEAL-FITTING INSTALLATION

A. Install sleeve-seal fittings in new walls and slabs as they are constructed.

Page 77: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO SLEEVES AND SLEEVE SEALS FOR Burnett Transit Center Escalator Design COMMUNICATIONS PATHWAYS AND CABLING

270544-5

B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall.

C. Secure nailing flanges to concrete forms.

D. Using grout, seal the space around outside of sleeve-seal fittings.

END OF SECTION

Page 78: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 79: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-1

Section 31 20 00

EARTH MOVING

PART 1 - G E N E R A L

1.01 SUMMARY

A. Section includes:

1. Preparing subgrades for walks.

2. Excavating and backfilling for buildings and structures.

3. Excavating and backfilling trenches for utilities and pits for buried utility structures.

1.02 MEASUREMENT AND PAYMENT

A. No separate payment will be made for 31 20 00 EARTH MOVING. Include price for all EARTH MOVING in Bid Form line item 03 30 00 CAST-IN-PLACE CONCRETE. The price shall include all work and material required for EARTH MOVING as described in the plans and specifications.

1.03 DEFINITIONS

A. Backfill: Soil material or controlled low-strength material used to fill an excavation.

1. Initial Backfill: Backfill placed beside and over pipe in a trench, including haunches to support sides of pipe.

2. Final Backfill: Backfill placed over initial backfill to fill a trench.

B. Bedding Course: Aggregate layer placed over the excavated subgrade in a trench before laying pipe.

C. Excavation: Removal of material encountered above subgrade elevations and to lines and dimensions indicated.

1. Unauthorized Excavation: Excavation below subgrade elevations or beyond indicated lines and dimensions without direction by Architect. Unauthorized excavation, as well as remedial work directed by Architect, shall be without additional compensation.

Page 80: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-2

D. Structures: Buildings, footings, foundations, retaining walls, slabs, tanks, curbs, mechanical and electrical appurtenances, or other man-made stationary features constructed above or below the ground surface.

E. Subgrade: Uppermost surface of an excavation or the top surface of a fill or backfill immediately below subbase, drainage fill, drainage course, or topsoil materials.

F. Utilities: On-site underground pipes, conduits, ducts, and cables as well as underground services within buildings.

1.04 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct preexcavation conference at Project site.

1. Require representatives of each entity directly concerned with earthwork to attend, including the following:

a. Contractor's superintendent.

b. Representatives of the Owner, Architect, Structural Engineer, and Civil Engineer.

c. Owner’s geotechnical consultant.

2. Earthwork subcontractorReview methods and procedures related to earthmoving, including, but not limited to, the following:

a. Review geotechnical report and recommendations that has been prepared for this site.

b. Personnel and equipment needed to make progress and avoid delays.

c. Coordination of Work with utility locator service.

d. Coordination of Work and equipment movement with the locations of tree- and plant-protection zones.

e. Extent of trenching by hand or with air spade.

f. Field quality control.

1.05 ACTION SUBMITTALS

A. Product Data: For each type of the following manufactured products required:

1. Warning tapes.

Page 81: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-3

B. Samples for Verification: For the following products, in sizes indicated below:

1. Warning Tape: 12 inches long; of each color.

1.06 INFORMATIONAL SUBMITTALS

A. Material Test Reports: For each on-site soil material proposed for fill and backfill as follows:

1. Classification according to ASTM D 2487.

2. Laboratory compaction curve according to ASTM D 698.

1.07 FIELD CONDITIONS

A. Traffic: Minimize interference with adjoining roads, streets, walks, and other adjacent occupied or used facilities during earth-moving operations.

1. Do not close or obstruct streets, walks, or other adjacent occupied or used facilities without permission from Owner and authorities having jurisdiction.

2. Provide alternate routes around closed or obstructed traffic ways if required by Owner or authorities having jurisdiction.

3. Provide barriers to direct vehicle and pedestrian traffic around construction site. Cover open excavation at the end of each work day.

B. Utility Locator Service: Notify utility locator service for area where Project is located before beginning earth-moving operations.

1. Clearly mark, on the ground, the location of existing utilities with wire and flag markers that are color coded by type of utility.

C. Do not commence earth-moving operations until temporary site fencing and erosion- and sedimentation-control measures are in place.

PART 2 - P R O D U C T S

2.01 SOIL MATERIALS

A. General: Provide borrow soil materials when sufficient satisfactory soil materials are not available from excavations.

B. Satisfactory Soils: Soil Classification Groups GW, GP, GM, SW, SP, and SM according to ASTM D 2487, a combination of these groups, or other soils acceptable to the Owner’s geotechnical consultant; free of rock or gravel larger

Page 82: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-4

than 3 inches in any dimension, debris, waste, frozen materials, vegetation, and other deleterious matter.

C. Unsatisfactory Soils: Soils not acceptable to the Owner’s geotechnical consultant.

1. Unsatisfactory soils also include satisfactory soils not maintained within 2 percent of optimum moisture content at time of compaction.

D. Engineered Fill: Naturally or artificially graded mixture of natural or crushed gravel, crushed stone, and natural or crushed sand; ASTM D 2940/D 2940M; with at least 90 percent passing a 1-1/2-inch sieve and not more than 12 percent passing a No. 200 sieve.

E. Bedding Course: Naturally or artificially graded mixture of natural or crushed gravel, crushed stone, and natural or crushed sand; ASTM D 2940/D 2940M; except with 100 percent passing a 1-inch sieve and not more than 8 percent passing a No. 200 sieve.

F. Sand: ASTM C 33/C 33M; fine aggregate.

2.02 ACCESSORIES

A. Detectable Warning Tape: Acid- and alkali-resistant, polyethylene film warning tape manufactured for marking and identifying underground utilities, a minimum of 6 inches wide and 4 mils thick, continuously inscribed with a description of the utility, with metallic core encased in a protective jacket for corrosion protection, detectable by metal detector when tape is buried up to 30 inches deep; colored as follows:

1. Red: Electric.

2. Yellow: Gas, oil, steam, and dangerous materials.

3. Orange: Telephone and other communications.

4. Blue: Water systems.

5. Green: Sewer systems.

Page 83: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-5

PART 3 - E X E C U T I O N

3.01 PREPARATION

A. Protect structures, utilities, sidewalks, pavements, and other facilities from damage caused by settlement, lateral movement, undermining, washout, and other hazards created by earth-moving operations.

B. Protect and maintain erosion and sedimentation controls during earth-moving operations.

C. Protect subgrades and foundation soils from freezing temperatures and frost. Remove temporary protection before placing subsequent materials.

3.02 DEWATERING

A. Prevent surface water and ground water from entering excavations, from ponding on prepared subgrades, and from flooding Project site and surrounding area.

B. Protect subgrades from softening, undermining, washout, and damage by rain or water accumulation.

1. Reroute surface water runoff away from excavated areas. Do not allow water to accumulate in excavations. Do not use excavated trenches as temporary drainage ditches.

3.03 EXPLOSIVES

A. Explosives: Do not use explosives.

3.04 EXCAVATION, GENERAL

A. Obtain a copy of the geotechnical report that has been prepared for this site. Comply with the geotechnical report’s recommendations. If recommendations in the report conflict with the Specifications, notify the Contracting Officer for clarification.

B. Unclassified Excavation: Excavate to subgrade elevations regardless of the character of surface and subsurface conditions encountered. Unclassified excavated materials may include rock, soil materials, and obstructions. No changes in the Contract Sum or the Contract Time will be authorized for rock excavation or removal of obstructions.

1. If excavated materials intended for fill and backfill include unsatisfactory soil materials and rock, replace with satisfactory soil materials.

Page 84: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-6

3.05 EXCAVATION FOR STRUCTURES

A. Excavate to indicated elevations and dimensions within a tolerance of plus or minus 1 inch. If applicable, extend excavations a sufficient distance from structures for placing and removing concrete formwork, for installing services and other construction, and for inspections.

1. Excavations for Footings and Foundations: Do not disturb bottom of excavation. Excavate by hand to final grade just before placing concrete reinforcement. Trim bottoms to required lines and grades to leave solid base to receive other work.

3.06 EXCAVATION FOR WALKS AND PAVEMENTS

A. Excavate surfaces under walks and pavements to indicated lines, cross sections, elevations, and subgrades.

3.07 EXCAVATION FOR UTILITY TRENCHES

A. Excavate trenches to indicated gradients, lines, depths, and elevations.

1. Beyond building perimeter, excavate trenches to allow installation of top of pipe below frost line.

B. Excavate trenches to uniform widths to provide the following clearance on each side of pipe or conduit. Excavate trench walls vertically from trench bottom to 12 inches higher than top of pipe or conduit unless otherwise indicated.

1. Clearance: As indicated.

C. Trench Bottoms: Excavate trenches 4 inches deeper than bottom of pipe and conduit elevations to allow for bedding course. Hand-excavate deeper for bells of pipe.

1. Excavate trenches 6 inches deeper than elevation required in rock or other unyielding bearing material to allow for bedding course.

3.08 SUBGRADE INSPECTION

A. Notify Architect when excavations have reached required subgrade.

B. If Architect determines that unsatisfactory soil is present, continue excavation and replace with compacted backfill or fill material as directed.

Page 85: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-7

C. Reconstruct subgrades damaged by freezing temperatures, frost, rain, accumulated water, or construction activities, as directed by Architect, without additional compensation.

3.09 UNAUTHORIZED EXCAVATION

A. Fill unauthorized excavation under foundations or wall footings by extending bottom elevation of concrete foundation or footing to excavation bottom, without altering top elevation. Lean concrete fill, with 28-day compressive strength of 2500 psi, may be used when approved by Architect.

1. Fill unauthorized excavations under other construction, pipe, or conduit as directed by Architect.

3.10 STORAGE OF SOIL MATERIALS

A. Stockpile borrow soil materials and excavated satisfactory soil materials without intermixing. Place, grade, and shape stockpiles to drain surface water. Cover to prevent windblown dust.

1. Stockpile soil materials away from edge of excavations. Do not store within drip line of remaining trees.

3.11 BACKFILL

A. Place and compact backfill in excavations promptly, but not before completing the following:

1. Construction below finish grade including, where applicable, subdrainage, dampproofing, waterproofing, and perimeter insulation.

2. Surveying locations of underground utilities for Record Documents.

3. Testing and inspecting underground utilities.

4. Removing concrete formwork.

5. Removing trash and debris.

6. Removing temporary shoring, bracing, and sheeting.

7. Installing permanent or temporary horizontal bracing on horizontally supported walls.

B. Place backfill on subgrades free of mud, frost, snow, or ice.

Page 86: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-8

3.12 UTILITY TRENCH BACKFILL

A. Place backfill on subgrades free of mud, frost, snow, or ice.

B. Place and compact bedding course on trench bottoms and where indicated. Shape bedding course to provide continuous support for bells, joints, and barrels of pipes and for joints, fittings, and bodies of conduits.

C. Trenches under Footings: Backfill trenches excavated under footings and within 18 inches of bottom of footings with satisfactory soil; fill with concrete to elevation of bottom of footings. Concrete is specified in Division 03 “Cast-in-Place Concrete.”

D. Trenches under Roadways: Provide 4-inch- thick, concrete-base slab support for piping or conduit less than 30 inches below surface of roadways. After installing and testing, completely encase piping or conduit in a minimum of 4 inches of concrete before backfilling or placing roadway subbase course. Concrete is specified in Division 03 “Cast-in-Place Concrete.”

E. Backfill voids with satisfactory soil while removing shoring and bracing.

F. At the locations where utility trenches go under on grade building, disrupt aggregate bedding joint with two feet of compacted impervious “fat” clay.

G. Initial Backfill:

1. Soil Backfill: Place and compact initial backfill of satisfactory soil, free of particles larger than 1 inch in any dimension, to a height of 12 inches over the pipe or conduit.

a. Carefully compact initial backfill under pipe haunches and compact evenly up on both sides and along the full length of piping or conduit to avoid damage or displacement of piping or conduit. Coordinate backfilling with utilities testing.

2. Controlled Low-Strength Material: Place initial backfill of controlled low-strength material to a height of 12 inches over the pipe or conduit. Coordinate backfilling with utilities testing.

H. Final Backfill:

1. Soil Backfill: Place and compact final backfill of satisfactory soil to final subgrade elevation.

I. Warning Tape: Install warning tape directly above utilities, 12 inches below finished grade, except 6 inches below subgrade under pavements and slabs.

Page 87: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-9

3.13 SOIL FILL

A. Plow, scarify, bench, or break up sloped surfaces steeper than 1 vertical to 4 horizontal so fill material will bond with existing material.

B. Place and compact fill material in layers to required elevations as follows:

1. Under walks and pavements, use satisfactory soil material.

2. Under building slabs, use engineered fill.

3. Under footings and foundations, use engineered fill.

C. Place soil fill on subgrades free of mud, frost, snow, or ice.

3.14 SOIL MOISTURE CONTROL

A. Uniformly moisten or aerate subgrade and each subsequent fill or backfill soil layer before compaction to within 2 percent of optimum moisture content.

1. Do not place backfill or fill soil material on surfaces that are muddy, frozen, or contain frost or ice.

2. Remove and replace, or scarify and air dry, otherwise satisfactory soil material that exceeds optimum moisture content by 2 percent and is too wet to compact to specified dry unit weight.

3.15 COMPACTION OF SOIL BACKFILLS AND FILLS

A. Place backfill and fill soil materials in layers not more than 8 inches in loose depth for material compacted by heavy compaction equipment and not more than 4 inches in loose depth for material compacted by hand-operated tampers.

B. Place backfill and fill soil materials evenly on all sides of structures to required elevations and uniformly along the full length of each structure.

C. Compact soil materials to not less than the following percentages of maximum dry unit weight according to ASTM D 698:

1. Under structures, building slabs, steps, and pavements, scarify and recompact top 12 inches of existing subgrade and each layer of backfill or fill soil material at 95 percent.

2. Under walkways, scarify and recompact top 6 inches below subgrade and compact each layer of backfill or fill soil material at 92 percent.

Page 88: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-10

3. For utility trenches, compact each layer of initial and final backfill soil material at 85 percent.

3.16 GRADING

A. General: Uniformly grade areas to a smooth surface, free of irregular surface changes. Comply with compaction requirements and grade to cross sections, lines, and elevations indicated.

1. Provide a smooth transition between adjacent existing grades and new grades.

2. Cut out soft spots, fill low spots, and trim high spots to comply with required surface tolerances.

B. Site Rough Grading: Slope grades to direct water away from buildings and to prevent ponding. Finish subgrades to elevations required to achieve indicated finish elevations, within the following subgrade tolerances:

1. Walks: Plus or minus 1 inch.

2. Pavements: Plus or minus 1/2 inch.

C. Grading inside Building Lines: Finish subgrade to a tolerance of 1/2 inch when tested with a 10-foot straightedge.

3.17 FIELD QUALITY CONTROL

A. Testing Agency: Owner will engage a qualified geotechnical engineering testing agency to perform tests and inspections.

B. Allow testing agency to inspect and test subgrades and each fill or backfill layer. Proceed with subsequent earth moving only after test results for previously completed work comply with requirements.

C. Testing agency will test compaction of soils in place according to ASTM D 1556, ASTM D 2167, ASTM D 2937, and ASTM D 6938, as applicable. Tests will be performed at the following locations and frequencies:

1. Paved and Building Slab Areas: At subgrade and at each compacted fill and backfill layer, at least one test for every 2000 sq. ft. or less of paved area or building slab but in no case fewer than three tests.

2. Foundation Wall Backfill: At each compacted backfill layer, at least one test for every 100 feet or less of wall length but no fewer than two tests.

Page 89: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design EARTH MOVING

31 20 00-11

3. Trench Backfill: At each compacted initial and final backfill layer, at least one test for every 150 feet or less of trench length but no fewer than two tests.

D. When testing agency reports that subgrades, fills, or backfills have not achieved degree of compaction specified, scarify and moisten or aerate, or remove and replace soil materials to depth required; recompact and retest until specified compaction is obtained.

3.18 PROTECTION

A. Protecting Graded Areas: Protect newly graded areas from traffic, freezing, and erosion. Keep free of trash and debris.

B. Repair and reestablish grades to specified tolerances where completed or partially completed surfaces become eroded, rutted, settled, or where they lose compaction due to subsequent construction operations or weather conditions.

1. Scarify or remove and replace soil material to depth as directed by Architect; reshape and recompact.

C. Where settling occurs before Project correction period elapses, remove finished surfacing, backfill with additional soil material, compact, and reconstruct surfacing.

1. Restore appearance, quality, and condition of finished surfacing to match adjacent work, and eliminate evidence of restoration to greatest extent possible.

3.19 DISPOSAL OF SURPLUS AND WASTE MATERIALS

A. Remove surplus satisfactory soil and waste materials, including unsatisfactory soil, trash, and debris, and legally dispose of them off Owner's property.

END OF SECTION

Page 90: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow
Page 91: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 1

Section 31 23 18

EXCAVATION AND BACKFILL FOR UTILITIES

PART 1 G E N E R A L

1.01 SECTION INCLUDES

Excavation, trenching, foundation, embedment, and backfill for installation of utilities, including manholes and other pipeline structures.

A.02 MEASUREMENT AND PAYMENT

A. No additional payment will be made for Work under this section. Include price with applicable utility construction.

B. No additional payment will be made for over excavated trench bottom, in the following situations:

1. No payment will be paid if Owner’s Representative does not direct Contractor to over excavate trench bottom.

2. No over excavation will be measured or paid when unsuitable conditions result from dewatering system not in conformance with Section 01 57 25 – Control of Ground Water and Surface Water.

C. No additional payment will be made for performing Critical Location exploratory excavation. Include cost in unit price for installed underground piping, sewer, conduit, or duct work.

D. Unit Price Line Item – Extra Unit Price Table

1. If Owner’s Representative directs Contractor to over excavate trench bottom, Contractor will be paid by unit price bid per linear foot under bid item “6-Inch Over-excavation of Trench Bottom”.

1.03 DEFINITIONS

A. Pipe Foundation: Suitable and stable native soils that are exposed at trench subgrade after excavation to depth of bottom of bedding as shown on Drawings, or foundation backfill material placed and compacted in over–excavations.

B. Pipe Bedding: Portion of trench backfill that extends vertically from top of foundation up to level line at bottom of pipe, and horizontally from one trench sidewall to opposite sidewall.

Page 92: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 2

C. Haunching: Material placed on either side of pipe from top of bedding up to springline of pipe and horizontally from one trench sidewall to opposite sidewall.

D. Initial Backfill: Portion of trench backfill that extends vertically from springline of pipe (top of haunching) up to level line 12 inches above top of pipe, and horizontally from one trench sidewall to opposite sidewall.

E. Pipe Embedment: Portion of trench backfill that consists of bedding, haunching, and initial backfill.

F. Trench Zone: Portion of trench backfill that extends vertically from top of pipe embedment up to pavement subgrade or up to final grade when not beneath pavement.

G. Unsuitable Material: Unsuitable soil materials are the following:

1. Materials that are classified as ML, CL–ML, MH, PT, OH, and OL according to ASTM D 2487.

2. Materials that cannot be compacted to required density due to either gradation, plasticity, or moisture content.

3. Materials that contain large clods, aggregates, stones greater than 4 inches in any dimension, debris, vegetation, waste or any other deleterious materials.

4. Materials that are contaminated with hydrocarbons or other chemical contaminants.

H. Suitable Material: Suitable soil materials are those meeting specification requirements. Materials mixed with lime, fly ash, or cement that can be compacted to required density and meeting requirements for suitable materials may be considered suitable materials, unless otherwise indicated.

I. Backfill: Suitable material meeting specified quality requirements, placed, and compacted under controlled conditions.

J. Ground Water Control Systems: Installations external to trench, such as well points, eductors, or deep wells. Ground water control includes dewatering to lower ground water, intercepting seepage which would otherwise emerge from side or bottom of trench excavation, and depressurization to prevent failure or heaving of excavation bottom. Refer to Section 01 57 25 – Control of Ground Water and Surface Water.

K. Surface Water Control: Diversion and drainage of surface water runoff and rain water away from trench excavation. Rain water and surface water accidentally entering trench shall be controlled and removed as part of excavation drainage.

Page 93: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 3

L. Excavation Drainage: Removal of surface and seepage water in trench by sump pumping and using drainage layer, as defined in ASTM D 2321, placed on foundation beneath pipe bedding or thickened bedding layer of Class I material.

M. Trench Conditions are defined with regard to stability of trench bottom and trench walls of pipe embedment zone. Maintain trench conditions that provide for effective placement and compaction of embedment material directly on or against undisturbed soils or foundation backfill, except where structural trench support is necessary.

1. Dry Stable Trench: Stable and substantially dry trench conditions exist in pipe embedment zone as result of typically dry soils or achieved by ground water control (dewatering or depressurization) for trenches extending below ground water level.

2. Stable Trench with Seepage: Stable trench in which ground water seepage is controlled by excavation drainage.

a. Stable Trench with Seepage in Clayey Soils: Excavation drainage is provided in lieu of or to supplement ground water control systems to control seepage and provide stable trench subgrade in predominately clayey soils prior to bedding placement.

b. Stable Wet Trench in Sandy Soils: Excavation drainage is provided in embedment zone in combination with ground water control in predominately sandy or silty soils.

3. Unstable Trench: Unstable trench conditions exist in pipe embedment zone if ground water inflow or high water content causes soil disturbances, such as sloughing, sliding, boiling, heaving, or loss of density.

N. Sub–trench: Sub-trench is special case of benched excavation. Sub-trench excavation below trench shields or shoring installations may be used to allow placement and compaction of foundation or embedment materials directly against undisturbed soils. Depth of sub-trench depends upon trench stability and safety as determined by Contractor.

O. Trench Dam: Placement of low permeability material in pipe embedment zone or foundation to prohibit ground water flow along trench.

P. Over–Excavation and Backfill: Excavation of subgrade soils with unsatisfactory bearing capacity or composed of otherwise unsuitable materials below top of foundation as shown on Drawings, and backfilled with foundation backfill material.

Page 94: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 4

Q. Foundation Backfill Materials: Natural soil or manufactured aggregate of controlled gradation, and geotextile filter fabrics as required, to control drainage and material separation. Foundation backfill material is placed and compacted as backfill to provide stable support for bedding. Foundation backfill materials may include concrete seal slabs.

R. Trench Safety Systems include both protective systems and shoring systems as defined in Section 31 50 01 – Trench Safety Systems.

S. Trench Shield (Trench Box): Portable worker safety structure moved along trench as work proceeds, used as protective system and designed to withstand forces imposed on it by cave-in, thereby protecting persons within trench. Trench shields may be stacked if so designed or placed in series depending on depth and length of excavation to be protected.

T. Shoring System: Structure that supports sides of an excavation to maintain stable soil conditions and prevent cave-ins, or to prevent movement of ground affecting adjacent installations or improvements.

U. Special Shoring: Shoring system meeting special shoring as specified in Paragraph 1.08, Special Shoring Design Requirements, for locations identified on Drawings.

V. Vacuum Excavation: An excavation technique performed by an experienced subcontractor in which water or air jets are used to slough off and vacuum away soil.

1.04 REFERENCES

A. ASTM C 12 – Standard Practice for Installing Vitrified Clay Pipe Lines.

B. ASTM D 558 – Standard Test Methods for Moisture-Density Relations of Soil Cement Mixtures.

C. ASTM D 698 – Standard Test Method for Laboratory Compaction Characteristics of Soil Using Standard Effort (12,400 ft-lb/ft).

D. ASTM D 1556 – Standard Test Method for Density and Unit Weight of Soil in Place by Sand-Cone Method.

E. ASTM D 2321 – Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity Flow Applications.

F. ASTM D 2487 – Standard Classification of Soils for Engineering Purposes.

G. ASTM D 2922 – Standard Test Methods for Density of Soil and Soil-Aggregate in Place by Nuclear Methods (Shallow Depth).

Page 95: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 5

H. ASTM D 3017 – Standard Test Method for Water Content of Soil and Rock in Place by Nuclear Methods (Shallow Depth).

I. ASTM D 4318 – Standard Test Method for Liquid Limit, Plastic Limit, and Plasticity Index of Soils.

J. TxDOT Tex–101–E – Preparing Soil and Flexible Base Materials for Testing.

K. TxDOT Tex–110–E – Particle Size Analysis of Soils.

L. Federal Regulations, 29 CFR Part 1926, Standards-Excavation, Occupational Safety and Health Administration (OSHA).

1.05 SCHEDULING

Schedule work so that pipe embedment can be completed on same day that acceptable foundation has been achieved for each section of pipe installation, manhole, or other structures.

1.06 SUBMITTALS

A. Conform to requirements of Section 01 33 00 – Submittal Procedures.

B. Submit proposed vacuum excavation method and qualifications of proposed subcontractor for approval by Owner’s Representative.

C. Submit planned typical method of excavation, backfill placement, and compaction including:

1. Trench widths.

2. Procedures for foundation and pipe zone bedding placement, and trench backfill compaction.

3. Procedures for assuring compaction against undisturbed soil when premanufactured trench safety systems are proposed.

D. Submit backfill material sources and product quality information in accordance with requirements of Section 31 23 32 – Utility Backfill Materials.

E. Submit trench excavation safety program in accordance with requirements of Section 31 50 01 – Trench Safety System. Include designs for special shoring meeting requirements defined in Paragraph 1.08, Special Shoring Design Requirements contained herein.

F. Submit record of location of utilities as installed, referenced to survey control points. Include locations of utilities encountered or rerouted. Give stations, horizontal dimensions, elevations, inverts, and gradients.

Page 96: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 6

G. Submit 11 inch by 17 inch copy of Drawing with plotted utility or obstruction location titled “Potential Obstruction Report” to Owner’s Representative.

1.07 TESTS

A. Testing and analysis of backfill materials for soil classification and compaction during construction will be performed by an independent laboratory provided by the Owner in accordance with requirements of Section 01 45 29 – Testing Laboratory Services and as specified in this Section.

B. Perform backfill material source qualification testing in accordance with requirements of Section 31 23 32 – Utility Backfill Materials.

1.08 SPECIAL SHORING DESIGN REQUIREMENTS

Have special shoring designed or selected by Contractor’s Professional Engineer to provide support for sides of excavations, including soils and hydrostatic ground water pressures as applicable, and to prevent ground movements affecting adjacent installations or improvements such as structures, pavements, and utilities. Special shoring may be a premanufactured system selected by Contractor’s Professional Engineer to meet project site requirements based on manufacturer’s standard design.

PART 2 P R O D U C T S

2.01 EQUIPMENT

A. Perform excavation with hydraulic excavator or other equipment suitable for achieving requirements of this Section.

B. Use only hand-operated tamping equipment until minimum cover of 12 inches is obtained over pipes, conduits, and ducts. Do not use heavy compacting equipment until adequate cover is attained to prevent damage to pipes, conduits, or ducts.

C. Use trench shields or other protective systems or shoring systems which are designed and operated to achieve placement and compaction of backfill directly against undisturbed native soil.

D. Use special shoring systems where required which may consist of braced sheeting, braced soldier piles and lagging, slide rail systems, or other systems meeting requirements as specified in Paragraph 1.08, Special Shoring Design Requirements.

2.02 MATERIAL CLASSIFICATIONS

A. Embedment and Trench Zone Backfill Materials: Conform to classifications and product descriptions of Section 31 23 32 - Utility Backfill Materials and

Page 97: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 7

Section 02321 - Cement Stabilized Sand the City of Houston Standard Specifications.

B. Concrete Backfill: Conform to requirements for Class B concrete as specified in Section 03315 – Concrete for Utility Construction of the City of Houston Standard Specifications.

C. Geotextile (Filter Fabric): Conform to requirements of Section 02621 – Geotextile of the City of Houston Standard Specifications.

D. Concrete for Trench Dams: Concrete backfill or 3 sack premixed (bag) concrete.

PART 3 E X E C U T I O N

3.01 STANDARD PRACTICE

A. Install flexible pipe, including “semi-rigid” pipe, to conform to standard practice described in ASTM D 2321, and as described in this Section. Where an apparent conflict occurs between standard practice and requirements of this Section, this Section governs.

B. Install rigid pipe to conform to standard practice described in ASTM C 12, and as described in this Section. Where an apparent conflict occurs between standard practice and requirements of this Section, this Section governs.

C. Classification of material will be determined by the Owner’s Representative, based on documentation from the Contractor.

3.02 PREPARATION

A. Establish traffic control to conform with requirements of Section 01 14 16 – Safety and Security.

B. Maintain barricades and warning lights for streets and intersections affected by Work, and are considered hazardous to traffic movements.

C. Perform work to conform with applicable safety standards and regulations. Employ trench safety system as specified in Section 31 50 01 – Trench Safety Systems.

D. Immediately notify agency or company owning any existing utility line which is damaged, broken, or disturbed. Obtain approval from Owner’s Representative and agency for any repairs or relocations, either temporary or permanent.

E. Remove existing pavements and structures, including sidewalks and driveways, to conform with requirements of Section 02 41 14 – Removing Existing Pavements and Structures, as applicable.

Page 98: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 8

F. Install and operate necessary dewatering and surface water control measures to conform with Section 01 57 25 – Control of Ground Water and Surface Water. Provide stable trench to allow installation in accordance with Specifications.

G. Maintain permanent benchmarks, monumentation, and other reference points. Unless otherwise directed in writing, replace those which are damaged or destroyed in accordance with Section 01 57 25 – Field Surveying.

H. Limit concrete removal, pavement removal, and dewatering to less than five pipe laying days in advance of pipe laying.

3.03 CRITICAL LOCATION INVESTIGATION

A. Horizontal and vertical location of various underground lines shown on Drawings, including but not limited to water lines, gas lines, storm sewers, sanitary sewers, telecommunication lines, electric lines or power ducts, pipelines, concrete and debris, are based on best information available but are only approximate locations. Unless otherwise approved by Owner’s Representative, at Critical Locations shown on Drawings, perform vacuum excavation to field verify horizontal and vertical locations of such lines within zone of 2 feet vertically and 4 feet horizontally of proposed work.

1. Verify location of existing utilities prior to manufacturing pipe and prior to beginning installation of auger pit or tunnel shaft. Use extreme caution and care when uncovering utilities designated by Critical Locate.

2. Notify Owner’s Representative in writing immediately upon identification of obstruction. In event of failure to identify obstruction in minimum of 7 days, Contractor will not be entitled to extra cost for downtime including, but not limited to, payroll, equipment, overhead, demobilization and remobilization, until 7 days has passed from time Owner’s Representative is notified of obstruction.

C. Notify involved utility companies of date and time that investigation excavation will occur and request that their respective utility lines be marked in field. Comply with utility or pipeline company requirements that their representative be present during excavation. Provide Owner’s Representative with 48 hours notice prior to field excavation or related work.

D. Survey vertical and horizontal locations of obstructions relative to project baseline and datum and plot on 12 inch by 18 inch copy of Drawings. For large diameter water lines, submit to Owner’s Representative for approval, horizontal and vertical alignment dimensions for connections to existing lines, tied into project baseline, signed, and sealed by R.P.L.S.

3.04 PROTECTION

Page 99: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 9

A. Protect trees, shrubs, lawns, existing structures, and other permanent objects outside of grading limits and within grading limits as designated on Drawings.

B. Protect and support above-grade and below-grade utilities which are to remain.

C. Restore damaged permanent facilities to pre-construction conditions unless replacement or abandonment of facilities is indicated on Drawings.

D. Take measures to minimize erosion of trenches. Do not allow water to pond in trenches. Where slides, washouts, settlements, or areas with loss of density or pavement failures or potholes occur, repair, recompact, and pave those areas at no additional cost to Owner.

3.05 EXCAVATION

A. Except as otherwise specified or shown on Drawings, install underground utilities in open cut trenches with vertical sides.

B. Perform excavation work so that pipe, conduit, and ducts can be installed to depths and alignments shown on Drawings. Avoid disturbing surrounding ground and existing facilities and improvements.

C. Determine trench excavation widths using following schedule as related to pipe outside diameter (O.D.).

Nominal Pipe Size, Inches

Minimum Trench Width, Inches

Less than 18 O.D. + 18

18 to 30 O.D. + 24

Over 30 O.D. + 36

Excavate trench so that pipe is centered in trench. Do not obstruct sight distance for vehicles utilizing roadway or detours with stockpiled materials.

D. Use sufficient trench width or benches above embedment zone for installation of well point headers or manifolds and pumps where depth of trench makes it uneconomical or impractical to pump from surface elevation. Provide sufficient space between shoring cross braces to permit equipment operations and handling of forms, pipe, embedment, and backfill, and other materials.

E. Upon discovery of unknown utilities, badly deteriorated utilities not designated for removal, or concealed conditions, discontinue work at that location. Notify Owner’s Representative and obtain instructions before proceeding.

Page 100: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 10

F. Shoring of Trench Walls.

1. Install Special Shoring in advance of trench excavation or simultaneously with trench excavation, so that soils within full height of trench excavation walls will remain laterally supported at all times.

2. For all types of shoring, support trench walls in pipe embedment zone throughout installation. Provide trench wall supports sufficiently tight to prevent washing trench wall soil out from behind trench wall support.

3. Leave sheeting driven into or below pipe embedment zone in place to preclude loss of support of foundation and embedment materials, unless otherwise directed by Owner’s Representative. Leave rangers, walers, and braces in place as long as required to support sheeting, which has been cut off, and trench wall in vicinity of pipe zone.

4. Employ special methods for maintaining integrity of embedment or foundation material. Before moving supports, place and compact embedment to sufficient depths to provide protection of pipe and stability of trench walls. As supports are moved, finish placing and compacting embedment.

5. If sheeting or other shoring is used below top of pipe embedment zone, do not disturb pipe foundation and embedment materials by subsequent removal. Maximum thickness of removable sheeting extending into embedment zone shall be equivalent of 1-inch-thick steel plate. As sheeting is removed, fill in voids left with grouting material.

G. Use of Trench Shields. When trench shield (trench box) is used as worker safety device, the following requirements apply:

1. Make trench excavations of sufficient width to allow shield to be lifted or pulled freely, without damage to trench sidewalls.

2. Move trench shields so that pipe, and backfill materials, after placement and compaction, are not damaged nor disturbed, nor degree of compaction reduced. Recompact after shield is moved is soil is disturbed.

3. When required, place, spread, and compact pipe foundation and bedding materials beneath shield. For backfill above bedding, lift shield as each layer of backfill is placed and spread. Place and compact backfill materials against undisturbed trench walls and foundation.

4. Maintain trench shield in position to allow sampling and testing to be performed in safe manner.

5. Conform to applicable Government regulations.

Page 101: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 11

H. Voids under paving area outside shield caused by Contractor’s work will require removal of pavement, consolidation and replacement of pavement in accordance with Contract Documents. Repair damage resulting from failure to provide adequate supports.

I. Place sand or soil behind shoring or trench shield to prevent soil outside shoring from collapsing and causing voids under pavement. Immediately pack suitable material in outside voids following excavation to avoid caving of trench walls.

J. Coordinate excavation within 15 feet of pipeline with company’s representative. Support pipeline with methods agreed to by pipeline company’s representative. Use small, rubber–tired excavator, such as backhoe, to do exploratory excavation. Bucket that is used to dig in close proximity to pipelines shall not have teeth or shall have guard installed over teeth to approximate bucket without teeth. Excavate by hand within 1 foot of pipeline company’s line. Do not use larger excavation equipment than normally used to dig trench in vicinity of pipeline until pipelines have been uncovered and fully exposed. Do not place large excavation and hauling equipment directly over pipelines unless approved by pipeline company’s representative.

K. When, during excavation to uncover pipeline company’s pipelines, screwed collar or an oxyacetylene weld is exposed, immediately notify Owner’s Representative. Provide supports for collar or welds. Discuss with pipeline company’s representative and determine methods of supporting collar or weld during excavation and later backfilling operations. When collar is exposed, request pipeline company to provide welder in a timely manner to weld ends of collar prior to backfilling of excavation.

3.06 HANDLING EXCAVATED MATERIALS

A. Use only excavated materials which are suitable as defined in this Section and conforming with Section 31 23 32 – Utility Backfill Materials. Place material suitable for backfilling in stockpiles at distance from trench to prevent slides or cave-ins.

B. When required, provide additional backfill material conforming to requirements of Section 31 23 32 – Utility Backfill Materials.

C. Do not place stockpiles of excess excavated materials on streets and adjacent properties. Protect excess stockpiles for use on site. Maintain site conditions in accordance with Section 01 51 00 – Temporary Facilities. Excavate trench so that pipe is centered in trench. Do not obstruct sight distance for vehicles utilizing roadway or detours with stockpiled materials.

3.07 TRENCH FOUNDATION

Page 102: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 12

A. Excavate bottom of trench to uniform grade to achieve stable trench conditions and satisfactory compaction of foundation or bedding materials.

B. When wet soil is encountered on trench bottom and dewatering system is not required, overexcavate an additional 6 inches with approval by Owner’s Representative. Place nonwoven geotextile fabric and then compact 12 inches of crushed stone in one lift on top of fabric. Compact crushed stone with four passes of vibratory-type compaction equipment.

C. Perform over excavation, when directed by Owner’s Representative, in accordance with Paragraph 3.07B above.

1. Even though Contractor has not determined material to be unsuitable, or

2. If unstable trench bottom is encountered and an adequate ground water control system is installed and operating according to Section 01 57 25 – Control of Ground Water and Surface Water.

D. Place trench dams in Class I foundations in line segments longer than 100 feet between manholes and not less than one in every 500 feet of pipe placed. Install additional dams as needed to achieve workable construction conditions. Do not place trench dams closer than 5 feet from manholes.

3.08 PIPE EMBEDMENT, PLACEMENT, AND COMPACTION

A. Remove loose, sloughing, caving, or otherwise unsuitable soil from bottoms and sidewalls of trenches immediately prior to placement of embedment materials.

B. Place embedment including bedding, haunching, and initial backfill as shown on Drawings.

C. For pipe installation, manually spread embedment materials around pipe to provide uniform bearing and side support when compacted. Protect flexible pipe from damage during placing of pipe zone bedding material. Perform placement and compaction directly against undisturbed soils in trench sidewalls, or against sheeting which is to remain in place.

D. Do not place trench shields or shoring within height of embedment zone unless means to maintain density of compacted embedment material are used. If moveable supports are used in embedment zone, lift supports incrementally to allow placement and compaction of material against undisturbed soil.

E. Place geotextile to prevent particle migration from in-situ soil into open–graded (Class I) embedment materials or drainage layers.

Page 103: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 13

F. Do not damage coatings or wrappings of pipes during backfilling and compacting operations. When embedding coated or wrapped pipes, do not use crushed stone or other sharp, angular aggregates.

G. Place haunching material manually around pipe and compact it to provide uniform bearing and side support. If necessary, hold small-diameter or lightweight pipe in place during compaction of haunch areas and placement beside pipe with sand bags or other suitable means.

H. Place electrical conduit, if used, directly on foundation without bedding.

I. Shovel in-place and compact embedment material using pneumatic tampers in restricted areas, and vibratory-plate compactors or engine-powered jumping jacks in unrestricted areas. Compact each lift before proceeding with placement of next lift. Water tamping is not allowed.

J. For water lines construction embedment, use bank run sand, concrete sand, gem sand, pea gravel, or crushed limestone as specified in Section 31 23 32 – Utility Backfill Material. For water lines adhere to the following subparagraph numbers 1 and 2; for utility installation other than water, adhere to numbers 3 and 4 below:

1. Class I, II, and III Embedment Materials:

a. Maximum 6 inch compacted lift thickness.

b. Compact to achieve minimum of 95 percent of maximum dry density as determined according to ASTM D 698.

c. Moisture content to be within –3 percent to +5 percent of optimum as determined according to ASTM D 698, unless otherwise approved by Owner’s Representative.

2. Cement Stabilized Sand:

a. Maximum 6 inch compacted thickness.

b. Compact to achieve minimum of 95 percent of maximum dry density as determined according to ASTM D 698.

c. Moisture content to be on dry side of optimum as determined according to ASTM D 698 but sufficient for effective hydration.

3. Class I Embedment Materials.

a. Maximum 6 inch compacted lift thickness.

Page 104: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 14

b. Systematic compaction by at least two passes of vibrating equipment. Increase compaction effort as necessary to effectively embed pipe to meet deflection test criteria.

c. Moisture content as determined by Contractor for effective compaction without softening soil of trench bottom, foundation, or trench walls.

4. Class II Embedment and Cement Stabilized Sand.

a. Maximum 6 inch compacted thickness.

b. Compaction by methods determined by Contractor to achieve minimum of 95 percent of maximum dry density as determined according to ASTM D 698 for Class II materials and according to ASTM D 558 for cement stabilized materials.

c. Moisture content of Class II materials within 3 percent of optimum as determined according to ASTM D 698. Moisture content of cement stabilized sands on dry side of optimum as determined according to ASTM D 558 but sufficient for effective hydration.

K. Place trench dams in Class I embedment in line segments longer than 100 feet between manholes, and not less than one in every 500 feet of pipe placed. Install additional dams as needed to achieve workable construction conditions. Do not place trench dams closer than 5 feet from manholes.

3.09 TRENCH ZONE BACKFILL PLACEMENT AND COMPACTION

A. Place backfill for pipe or conduits and restore surface as soon as practicable. Leave only minimum length of trench open as necessary for construction.

B. For water lines, under pavement and to within one foot back of curb, use backfill materials described by trench limits.

1. For water lines 20 inches in diameter and smaller, use bank run sand or select backfill materials up to pavement base or subgrade.

2. For water lines 24 inches in diameter and larger, backfill with suitable on-site material (random backfill) up to 12 inches below pavement base or subgrade. Place minimum of 12 inches of select backfill below pavement base or subgrade.

C. For sewer pipes under pavement and to within one foot back of curb, use backfill materials described by trench limits.

l. For sewer pipes 36 inches in diameter and smaller use cement stabilized sand up to pavement base or subgrade.

Page 105: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 15

2. For sewer pipes 42 inches in diameter and larger, backfill with suitable on-site material (random backfill) up to 12 inches below pavement base or subgrade. Place minimum of 12 inches of select backfill below pavement base or subgrade.

D. Where damage to completed pipe installation work is likely to result from withdrawal of sheeting, leave sheeting in place. Cut off sheeting 1.5 feet or more above crown of pipe. Remove trench supports within 5 feet from ground surface.

E. Where shown on the Drawings, remove unsuitable material from the site and backfill with suitable material.

F. Unless otherwise shown on Drawings. Use one of the following trench zone backfills under pavement and to within one foot of edge of pavement. Place trench zone backfill in lifts and compact. Fully compact each lift before placement of next lift.

1. Class I, II, or III or combination thereof:

a. Place in maximum 12-inch thick loose layers.

b. Compact by vibratory equipment to minimum of 95 percent of maximum dry density determined according to ASTM D 698.

c. Moisture content within zero percent to +5 percent of optimum determined according to ASTM D 698, unless otherwise approved by Owner’s Representative.

2. Cement-Stabilized Sand:

a. Maximum lift thickness determined by Contractor to achieve uniform placement and required compaction, but do not exceed 12 inches.

b. Compact by vibratory equipment to minimum of 95 percent of maximum dry density determined according to ASTM D 538.

c. Moisture content on dry side of optimum determined according to ASTM D 558 but sufficient for cement hydration.

3. Class IVA and IVB (Clay Soils):

a. Place in maximum 8-inch thick loose lifts.

b. Compact by vibratory Sheepfoot Roller to minimum of 95 percent of maximum dry density determined according to ASTM D 698.

Page 106: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 16

c. Moisture content within zero percent to +5 percent above optimum determined according to ASTM D 698, unless approved by Owner’s Representative.

G. Unless otherwise shown on Drawings, for trench excavations not under pavement, random backfill of suitable material may be used in trench zone.

1. Class IVA and IVB (Clay Soils) may he used as trench zone backfill outside paved areas.

2. Place in maximum 12-inch thick loose lift.

3. Compaction by appropriate equipment to minimum of 90 percent of maximum dry density determined according to ASTM D 698.

4. Moisture content as necessary to achieve density.

H. For electric conduits, remove form work used for construction of conduits before placing trench zone backfill.

I. Buried warning and identification tape for non-metallic pipe.

Polyethylene plastic and metallic core or metallic-faced, acid- and alkali-resistant, polyethylene plastic warning tape manufactured specifically for warning and identification of buried utility lines. Provide tape on roles, 18 inch minimum width, blue color for water line with warning and identification imprinted in bold black letters continuously over the entire tape length. Warning and identification to read, “CAUTION, BURIED WATER LINE BELOW” or similar wording. Color and printing shall be permanent, unaffected by moisture or soil. Warning and identification tape shall be centered above water main and buried 36-inches below finished grade.

Detectable Warning Tape for Non-Metallic Piping shall be polyethylene plastic tape conforming to the width, color, and printing requirements specified above. Minimum thickness of the tape shall be 5.0 mil. Tape shall have a minimum tensile strength of 1,500 psi lengthwise and 1,250 psi crosswise. Tape shall be manufactured with integral wires, foil, or other means of enabling detection by a metal detector when tape is buried up to 36-inches. Encase metallic element of the tape in a protective jacket or provide other means of corrosion protection.

3.10 MANHOLES, JUNCTION BOXES, AND OTHER PIPELINE STRUCTURES

Encapsulate manhole, junction box and other pipeline structures with cement stabilized sand; minimum of 1 foot below base, minimum 1 foot around walls, up to within 12 inches of pavement subgrade. Compact in accordance with Paragraph 3.09.F.2 of this Section.

Page 107: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 17

3.11 FIELD QUALITY CONTROL

A. Test for material source qualifications as defined in Section 31 23 32 – Utility Backfill Materials.

B. Provide excavation and trench safety systems at locations and to depths required for testing and retesting during construction at no additional cost to Owner.

C. Tests will be performed on minimum of three different samples of each material type for plasticity characteristics, in accordance with ASTM D 4318, and for gradation characteristics, in accordance with Tex-101-E and Tex-110-E. Additional classification tests will be performed whenever there is noticeable change in material gradation or plasticity, or when requested by Owner’s Representative.

D. At least three tests for moisture-density relationships will be performed initially for backfill materials in accordance with ASTM D 698, and for cement-stabilized sand in accordance with ASTM D 558. Perform additional moisture-density relationship tests once a month or whenever there is noticeable change in material gradation or plasticity.

E. In-place density tests of compacted pipe foundation, embedment and trench zone backfill soil materials will be performed according to ASTM D 1556, or ASTM D 2922 and ASTM D 3017, and at following frequencies and conditions.

1. For open cut construction projects and auger pits: Unless otherwise approved by Owner’s Representative, successful compaction to be measured by one test per 40 linear feet measured along pipe for compacted embedment and two tests per 40 linear feet measured along pipe for compacted trench zone backfill material. Length of auger pits to be measured to arrive at 40 linear feet.

2. A minimum of three density tests for each full shift of Work.

3. Density tests will be distributed among placement areas. Placement areas are: foundation, bedding, haunching, initial backfill, and trench zone.

4. The number of tests will be increased if inspection determines that soil type or moisture content are not uniform or if compacting effort is variable and not considered sufficient to attain uniform density, as specified.

5. Density tests may be performed at various depths below fill surface by pit excavation. Material in previously placed lifts may therefore be subject to acceptance/rejection.

Page 108: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO EXCAVATION AND Burnett Transit Center Escalator Design BACKFILL FOR UTILITIES

31 23 18 - 18

6. Two verification tests will be performed adjacent to in-place tests showing density less than acceptance criteria. Placement will be rejected unless both verification tests show acceptable results.

7. Recompacted placement will be retested at same frequency as first test series, including verification tests.

8. Identify elevation of test with respect to natural ground or pavement.

F. Recondition, recompact, and retest at Contractor’s expense if tests indicate Work does not meet specified compaction requirements. For hardened soil cement with nonconforming density, core and test for compressive strength at Contractor’s expense.

G. Acceptability of crushed rock compaction will be determined by inspection.

3.12 DISPOSAL OF EXCESS MATERIAL

Dispose of excess materials in accordance with requirements of Section 01 74 00 – Waste Material Disposal.

END OF SECTION

Page 109: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 1

Section 31 23 32

UTILITY BACKFILL MATERIALS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Material Classifications.

B. Utility Backfill Materials:

1. Concrete sand

2. Gem sand

3. Pea gravel

4. Crushed stone

5. Crushed concrete

6. Bank run sand

7. Select backfill

8. Random backfill

C. Material Handling and Quality Control Requirements.

1.02 MEASUREMENT AND PAYMENT

A. No separate payment will be made for backfill material. Include payment in

price for applicable utility installation.

1.03 DEFINITIONS

A. Unsuitable Material:

1. Materials classified as ML, CL-ML, MH, PT, OH, and OL according to

ASTM D 2487.

2. Materials that cannot be compacted to required density due to either

gradation, plasticity, or moisture content.

Page 110: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 2

3. Materials containing large clods, aggregates, or stones greater than 4

inches in any dimension; debris, vegetation, or waste; or any other

deleterious materials.

4. Materials contaminated with hydrocarbons or other chemical

contaminants.

B. Suitable Material:

1. Materials meeting specification requirements.

2. Unsuitable materials meeting specification requirements for suitable soils

after treatment with lime or cement.

C. Foundation Backfill Materials: Natural soil or manufactured aggregate

meeting Class I requirements and geotextile filter fabrics as required, to

control drainage and material separation. Foundation backfill material is

placed and compacted as backfill where needed to provide stable support for

structure foundation base. Foundation backfill materials may include

concrete fill and seal slabs.

D. Foundation Base: Crushed stone aggregate with filter fabric as required,

cement stabilized sand, or concrete seal slab. Foundation base provides

smooth, level working surface for construction of concrete foundation.

E. Backfill Material: Classified soil material meeting specified quality

requirements for designated application as embedment or trench zone

backfill.

F. Embedment Material: Soil material placed under controlled conditions within

embedment zone extending vertically upward from top of foundation to an

elevation 12 inches above top of pipe, and including pipe bedding, haunching

and initial backfill.

G. Trench Zone Backfill: Classified soil material meeting specified quality

requirements and placed under controlled conditions in trench zone from top

of embedment zone to base course in paved areas or to surface grading

material in unpaved areas.

H. Foundation: Either suitable soil of trench bottom, or material placed as

backfill of over-excavation for removal and replacement of unsuitable or

otherwise unstable soils.

Page 111: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 3

I. Source: Source selected by Contractor for supply of embedment or trench

zone backfill material. Selected source may be project excavation, off-site

borrow pits, commercial borrow pits, or sand and aggregate production or

manufacturing plants.

J. Refer to Section 31 23 18 - Excavation and Backfill for Utilities for other

definitions regarding utility installation by trench construction.

1.04 REFERENCES

A. ASTM C 33 - Standard Specification for Concrete Aggregate.

B. ASTM C 40 - Standard Test Method for Organic Impurities in Fine Aggregates

for Concrete.

C. ASTM C 123 - Standard Test Method for Lightweight Particles in Aggregate.

D. ASTM C 131 - Standard Test Method for Resistance to Degradation of Small-

Size Coarse Aggregate by Abrasion and Impact in Los Angeles Machine.

E. ASTM C 136 - Standard Test Method for Sieve Analysis of Fine and Coarse

Aggregates.

F. ASTM C 142 - Standard Test Method for Clay Lumps and Friable Particles in

Aggregates.

G. ASTM D 1140 - Standard Test Method for Amount of Material in Soils Finer

Than No. 200 Sieve.

H. ASTM D 2487 - Standard Classification of Soils for Engineering Purposes

(Unified Soil Classification System).

I. ASTM D 4318 - Standard Test Method for Liquid Limit, Plastic Limit, and

Plasticity Index of Soils.

J. ASTM D 4643 - Standard Test Method for Determination of Water (Moisture)

Content of Soil by Microwave Oven Method.

K. ASTM D 4832-02 - Standard Test Method for Preparation and Testing of

Controlled Low Strength Material (CLSM) Test Cylinders.

L. TxDOT Tex-110-E - Determining Particle Size Analysis of Soils.

M. TxDOT Tex-460-A - Material Finer Than 75 µm (No.200) Sieve In Mineral

Aggregates (Decantation Test for Concrete Aggregates).

Page 112: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 4

1.05 SUBMITTALS

A. Conform to requirements of Section 01 33 00 - Submittal Procedures.

B. Submit description of source, material classification and product description,

production method, and application of backfill materials.

C. Submit test results for samples of off-site backfill materials. Comply with

Paragraph 2.03, Material Testing, of this specification.

D. Before stockpiling materials, submit copy of temporary easement or approval

from landowner for stockpiling backfill material on private property.

E. Provide delivery ticket which includes source location for each delivery of

material that is obtained from off-site sources or is being paid as specific bid

item.

1.06 TESTS

A. Perform tests of sources for backfill material in accordance with Paragraph

2.03B.

B. Verification tests of backfill materials may be performed by the Owner in

accordance with Section 01 45 29 - Testing Laboratory Services and in

accordance with Paragraph 3.03, Field Quality Control, of this specification.

PART 2 PRODUCTS

2.01 MATERIAL CLASSIFICATIONS

A. Classify materials for backfill for purpose of quality control in accordance with

Unified Soil Classification Symbols as defined in ASTM D 2487. Material use

and application is defined in utility installation specifications and Drawings

either by class, as described in Paragraph 2.01B, or by product descriptions,

as given in Paragraph 2.02.

B. Class Designations Based on Laboratory Testing:

1. Class I: Well-graded gravels and sands, gravel-sand mixtures, crushed

well-graded rock, little or no fines (GW, SW):

a. Plasticity index: non-plastic.

Page 113: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 5

b. Gradation: D60/D10 - greater than 4 percent; amount passing No. 200

sieve - less than or equal to 5 percent.

2. Class II: Poorly graded gravels and sands, silty gravels and sands, little to

moderate fines (GM, GP, SP, SM):

a. Plasticity index: non-plastic to 4.

b. Gradations:

1. Gradation (GP, SP): amount passing No. 200 sieve - less than 5

percent.

2. Gradation (GM, SM): amount passing No. 200 sieve - between 12

percent and 50 percent.

3. Borderline gradations with dual classifications (e.g., SP-SM):

amount passing No. 200 sieve - between 5 percent and 12 percent.

3. Class III: Clayey gravels and sands, poorly graded mixtures of gravel,

sand, silt, and clay (GC, SC, and dual classifications, e.g., SP-SC):

a. Plasticity index: greater than 7.

b. Gradation: amount passing No. 200 sieve - between 12 percent and

50 percent.

4. Class IVA: Lean clays (CL).

a. Plasticity Indexes:

1. Plasticity index: greater than 7, and above A line.

2. Borderline plasticity with dual classifications (CL-ML):

PI between 4 and 7.

b. Liquid limit: less than 50.

c. Gradation: amount passing No. 200 sieve - greater than 50 percent.

d. Inorganic.

5. Class IVB: Fat clays (CH)

a. Plasticity index: above A line.

Page 114: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 6

b. Liquid limit: 50 or greater.

c. Gradation: amount passing No. 200 sieve - greater than 50 percent.

d. Inorganic.

6. Use soils with dual class designation according to ASTM D 2487, and

which are not defined above, according to more restrictive class.

2.02 PRODUCT DESCRIPTIONS

A. Soils classified as silt (ML) silty clay (CL-ML with PI of 4 to 7), elastic silt

(MH), organic clay and organic silt (OL, OH), and organic matter (PT) are not

acceptable as backfill materials. These soils may be used for site grading

and restoration in unimproved areas as approved by Owner’s Representative.

Soils in Class IVB, fat clay (CH) may be used as backfill materials where

allowed by applicable backfill installation specification. Refer to Section

02316 - Excavation and Backfill for Structures, of the City of Houston

standard specifications and Section 31 23 18 - Excavation and Backfill for

Utilities.

B. Provide backfill material that is free of stones greater than 6 inches, free of

roots, waste, debris, trash, organic material, unstable material, non-soil

matter, hydrocarbon or other contamination, conforming to following limits for

deleterious materials:

1. Clay lumps: Less than 0.5 percent for Class I, and less than 2.0 percent

for Class II, when tested in accordance with ASTM C 142.

2. Lightweight pieces: Less than 5 percent when tested in accordance with

ASTM C 123.

3. Organic impurities: No color darker than standard color when tested in

accordance with ASTM C 40.

C. Manufactured materials, such as crushed concrete, may be substituted for

natural soil or rock products where indicated in product specification, and

approved by Owner’s Representative provided that physical property criteria

are determined to be satisfactory by testing.

D. Bank Run Sand: Durable bank run sand classified as SP, SW, or SM by

Unified Soil Classification System (ASTM D 2487) meeting following

requirements:

Page 115: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 7

1. Less than 15 percent passing number 200 sieve when tested in

accordance with ASTM D 1140. Amount of clay lumps or balls not

exceeding 2 percent.

2. Material passing number 40 sieve shall meet the following requirements

when tested in accordance with ASTM D 4318: Plasticity index: not

exceeding 7.

E. Concrete Sand: Natural sand, manufactured sand, or combination of natural

and manufactured sand conforming to requirements of ASTM C 33 and

graded within following limits when tested in accordance with ASTM C 136:

Sieve Percent Passing

3/8" 100

No. 4 95 to 100

No. 8 80 to 100

No. 16 50 to 85

No. 30 25 to 60

No. 50 10 to 30

No. 100 2 to 10

F. Gem Sand: Sand conforming to requirements of ASTM C 33 for course

aggregates specified for number 8 size and graded within the following limits

when tested in accordance with ASTM C 136:

Sieve Percent Passing

3/8" 95 to 100

No. 4 60 to 80

No. 8 15 to 40

G. Pea Gravel: Durable particles composed of small, smooth, rounded stones or

pebbles and graded within the following limits when tested in accordance with

ASTM C 136:

Sieve Percent Passing

½" 100

3/8" 85 to 100

No. 4 10 to 30

No. 8 0 to 10

No. 16 0 to 5

Page 116: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 8

H. Crushed Aggregates: Crushed aggregates consist of durable particles

obtained from an approved source and meeting the following requirements:

1. Materials of one product delivered for same construction activity from

single source, unless otherwise approved by Owner’s Representative.

2. Non-plastic fines.

3. Los Angeles abrasion test wear not exceeding 45 percent when tested in

accordance with ASTM C 131.

4. Crushed aggregate shall have minimum of 90 percent of particles retained

on No. 4 sieve with 2 or more crushed faces as determined by Tex-460-A,

Part I.

5. Crushed stone: Produced from oversize plant processed stone or gravel,

sized by crushing to predominantly angular particles from naturally

occurring single source. Uncrushed gravel is not acceptable material for

embedment where crushed stone is shown on applicable utility

embedment drawing details.

6. Crushed Concrete: Crushed concrete is an acceptable substitute for

crushed stone as utility backfill. Gradation and quality control test

requirements are same as crushed stone. Provide crushed concrete

produced from normal weight concrete of uniform quality; containing

particles of aggregate and cement material, free from other substances

such as asphalt, reinforcing steel fragments, soil, waste gypsum (calcium

sulfate), or debris.

7. Gradations, as determined in accordance with Tex-110-E.

Sieve

Percent Passing by Weight for Pipe Embedment

by Ranges of Nominal Pipes Sizes

>15" 15" - 8" <8"

1" 95 - 100 100 -

¾" 60 - 90 90 - 100 100

½" 25 - 60 - 90 - 100

3/8" - 20 - 55 40 - 70

No. 4 0 - 5 0 - 10 0 - 15

No. 8 - 0 - 5 0 - 5

Page 117: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 9

I. Select Backfill: Class III clayey gravel or sand or Class IV lean clay with

plasticity index between 7 and 20 or clayey soils treated with lime in

accordance with Section 02951 - Pavement Repair and Resurfacing of the

City of Houston standard specifications, to meet plasticity criteria.

J. Random Backfill: Any suitable soil or mixture of soils within Classes I, II, III

and IV; or fat clay (CH) where allowed by applicable backfill installation

specification. Refer to Section 02316 - Excavation and Backfill for Structures

of the City of Houston standard specifications and Section 31 23 18 -

Excavation and Backfill for Utilities.

K. Cement Stabilized Sand: Conform to requirements of Section 02321 -

Cement Stabilized Sand of the City of Houston standard specifications.

L. Concrete Backfill: Conform to Class B concrete as specified in Section 03315

- Concrete for Utility Construction of the City of Houston standard

specifications.

M. Flowable Fill Material: Where shown on Drawings, controlled low-strength

material consisting of fluid mixture of cement, fly ash, aggregate, water, and

with admixtures as necessary to provide workable properties. Long-term

unconfined compressive strength shall be 300 psi minimum.

2.03 MATERIAL TESTING

A. Source Qualification. Perform testing to obtain tests by suppliers for selection

of material sources and products not from the project site. Test samples of

processed materials from current production representing material to be

delivered. Use tests to verify that materials meet specification requirements.

Repeat qualification test procedures each time source characteristics change

or there is planned change in source location or supplier. Include the

following qualification tests, as applicable:

1. Gradation. Report complete sieve analyses regardless of specified control

sieves from largest particle through No. 200 sieve.

2. Plasticity of material passing No. 40 sieve

3. Los Angeles abrasion wear of material retained on No. 4 sieve

4. Clay lumps

5. Lightweight pieces

Page 118: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 10

6. Organic impurities

B. Production Testing. Provide reports to Owner’s Representative from an

independent testing laboratory that backfill materials to be placed in Work

meet applicable specification requirements.

C. Assist Owner’s Representative in obtaining material samples for verification

testing at source or at production plant.

D. Testing of Flowable Fill Material shall be performed in accordance with ASTM

D 4832-02 - Standard Test Method for Preparation and Testing of Controlled

Low Strength Material (CLSM) Test Cylinders.

PART 3 EXECUTION

3.01 SOURCES

A. Use of existing material in trench excavations is acceptable, provided

applicable specification requirements are satisfied.

B. Identify off-site sources for backfill materials at least 14 days ahead of

intended use so that Owner’s Representative may obtain samples for

verification testing.

C. Materials may be subjected to inspection or additional verification testing after

delivery. Materials which do not meet requirements of specifications will be

rejected. Do not use material which, after approval, has become unsuitable

for use due to segregation, mixing with other materials, or by contamination.

Once material is approved by Owner’s Representative, expense for sampling

and testing required to change to different material will be credited to the

Owner through change order.

D. Bank run sand, select backfill, and random backfill, if available in project

excavation, may be obtained by selective excavation and acceptance testing.

Obtain additional quantities of these materials and other materials required to

complete work from off-site sources.

E. The Owner does not represent or guarantee that any soil found in excavation

work will be suitable and acceptable as backfill material.

Page 119: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow

METRO Burnett Transit Center Escalator Design UTILITY BACKFILL MATERIALS

31 23 32 - 11

3.02 MATERIAL HANDLING

A. When backfill material is obtained from either commercial or non-commercial

borrow pit, open pit to expose vertical faces of various strata for identification

and selection of approved material to be used. Excavate selected material by

vertical cuts extending through exposed strata to achieve uniformity in

product.

B. Establish temporary stockpile locations for practical material handling, control,

and verification testing by Owner’s Representative in advance of final

placement. Obtain approval from landowner for storage of backfill material on

adjacent private property.

C. When stockpiling backfill material near project site, use appropriate covers to

eliminate blowing of materials into adjacent areas and prevent runoff

containing sediments from entering drainage system.

D. Place stockpiles in layers to avoid segregation of processed materials. Load

material by making successive vertical cuts through entire depth of stockpile.

3.03 FIELD QUALITY CONTROL

A. Quality Control

1. The Owner’s Representative may sample and test backfill at:

a. Sources including borrow pits, production plants and Contractor's

designated off-site stockpiles.

b. On-site stockpiles.

c. Materials placed in Work.

2. The Owner’s Representative may re-sample material at any stage of work

or location if changes in characteristics are apparent.

END OF SECTION

Page 120: METRO HANGERS AND SUPPORTS Burnett Transit Center ... · or 27) complying with MSS SP-69, Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow