micom p121

Upload: eliecer-castillo

Post on 03-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 MICOM P121

    1/2

    More protection : Independent phase and earth

    overcurrent functions. 3 phase overcurrent thresholds.

    3 earth overcurrent thresholds. 11 families of curves (IEC,IEEE/ANSI, Electromechanical).

    Blocking logic. Instantaneous units.

    More information : True RMS measurement (up to

    10th harmonic). Alarm and trip messages in

    selectable language.

    Applications Industrial electrical networks. Utilities. HV & MV substations. MV & LV transformers.

    Protection and control 3 independent phase.

    overcurrent thresholds (50/51). 3 independent earth.

    overcurrent thresholds(50N/51N).

    11 families of curves (IDMT)

    (5 x CEI, 5 x IEEE/ANSI, 1 RI). Blocking logic. Start contacts. Output relay latching (86)

    Inputs and outputs 3 phase current inputs. 1 earth current input. Dual rated 1 & 5 Amp CT

    inputs. 2 programmable logic inputs. 5 programmable logic outputs.

    Measurements True RMS phase & earth

    currents. Permanent self-test. Fault memorisation and display.

    User interface 8 leds including

    4 programmables. 32 character alphanumeric

    display. RS 485 rear connection. MODBUSTM Courier or

    IEC 60870-5-103communication.

    Drawout case.

    MiCOM P 121Phase and earth overcurrent protection

    MiCOM P121 is the universal phase and earth overcurrent andoverload relay. Advanced functions allow maximum performance atan optimised cost.

    More convenient : Dedicated messages. Programmable leds.

    More compatible : MODBUSTM, Courier or IEC60870-5-103 communicationprotocols.

    Drawout case with CT shortcircuits.

    Dual rated 1 and 5 Amp CTinputs.

  • 7/28/2019 MICOM P121

    2/2

    Current inputs

    Phase current range : 1 and 5 Amp

    burden : < 0.3 VA (5 A) overload withstand :

    1 second @ 100 x rated current ;2 seconds @ 40 x rated currentcontinuous @ 3 x rated current

    Earth current range : 1 and 5 Amp burden : < 0.01 VA at 0.1IE (5A) overload withstand :

    1 second @ 100 x rated current ;2 seconds @ 40 x rated currentcontinuous @ 3 x rated current

    SettingsPhase time overcurrent thresholds : 3 (I>, I>>, I>>>) ranges : from 0.1 to 40 x rated

    current I> IDMT curves :

    IEC 255-3 : STI, SI, VI, EI, LTIIEEE/ANSI : MI, VI, EI, CO2,CO8Electromecanical : RI

    instantaneous time :(I>, I>>, I>>>) < 30 ms

    time delay :

    (tI>, tI>>, tI>>>) from 0 to 150 s dropout time : 50 ms

    Earth time overcurrent thresholds : 3 (IE>, IE>>, IE>>>) ranges : from 0.002 to 8 x rated

    current

    IE> IDMT curves :IEC 255-3 : STI, SI, VI, EI, LTIIEEE/ANSI : MI, VI, EI, CO2,

    CO8Electromechanical : RI instantaneous time :

    (IE>, IE>>, IE>>>) < 30 ms time delay :

    (tIE>, tIE>>, tIE>>>) from 0 to 150 s dropout time : 50 ms

    Auxiliary supply ranges : 24 to 250 Vdc

    110 to 250 Vac ;50/60 Hz

    burden :< 2 W + 0.25 W per logicoutput,

    < 5 VA with AC voltage supply variations : 0.8 to 1.2 Uaux DC supply interruption : 50 ms

    Logic inputs 2 isolated programmable inputs range : 24 to 250 Vdc burden : 0.25 W per input

    Logic outputs 2 change-over programmable

    outputs 2 N/O programmable outputs 1 watch-dog output current : make and carry for

    0.2 s ; 30 Acarry continuously 5 A

    break :at 135 Vdc (L/R = 30ms) ; 0.3 Aat 220 Vac (50/60 Hz) ;cos = 0.6 ; 5 A

    T&D Protection & Contrle - 95, rue de la Banquire - BP 75 - 34975 Lattes Cedex FRANCE

    Tl : 33 (0)4 67 20 54 54 - Tlex : 485 093 F - Fax : 33 (0)4 67 20 54 99 - E-mail: [email protected]

    5051

    50N51N

    52 TRIP

    WD

    Logicinputs

    Logicoutputs

    Phase CTs

    P121

    RS 485Communication

    3

    Earth CT

    Busbar

    86

    Remotecontrol

    L11501B-02/99

    Technical specifications

    Communication type : RS485 2 wires, half

    duplex, isolated

    data rate : from 300 to 38 400bauds protocol : MODBUSTM RTU

    Courier or IEC 60870-5-103

    Housing case : MiCOM 20 TE, rack or

    flush mounting, rear connections,full drawout with automatic CTshorting

    case size : 4U (152mm)H x 103 mm W x 230 mm D

    protection : IEC 529 ; IP 52,IK 07

    weight : 1.9 Kg connectors : MIDOS 2 x28 points (double faston + M4screw per connection)

    HMI display : 2 x 16 alphanumeric

    characters, back-lit leds : 8 including

    4 programmables keyboard : 7 button tactile key-

    pad languages : French, English,

    Dutch, German, Spanish,

    Portuguese, Italian, American,Russian, Polish

    Environment temperature : IEC 255-6

    operating : - 25C to +55Cstorage : - 25C to +70C

    humidity : IEC 68-2-3 dielectric withstand : IEC 255-5 impulse voltage : IEC 255-5 fast transient : IEC 1000-4-4;

    ANSI C37.90.1 high frequency disturbance :

    IEC 1000-4-1 class 3 RFI : IEC 1000-4-3 ;

    ANSI C37.90.2 electrostatic discharge: IEC 100-4-2 auxiliary supply : IEC 255-11,

    VDEW ; ripple : 12%,supply interruption : 50 ms

    vibration : IEC 255-21-1 class 2 shock & bump : IEC 255-21-1

    class 1 seismic : IEC 255-21-3 class 1

    StandardsCE conformity to IEC 947-1 (EMC

    and LV directives)ARCEAUX49Imp.-Tl.04992325

    00

    This

    brochure

    sh

    ould

    only

    be

    regarded

    as

    a

    guide.

    Itcontents

    do

    notconstitu

    te

    an

    offerforsale,nor

    advice

    on

    any

    application

    forany

    pr

    oductreferred

    to

    in

    it.

    1999ALSTOMT

    &DProtection

    &ContrleSA