micom p121
TRANSCRIPT
-
7/28/2019 MICOM P121
1/2
More protection : Independent phase and earth
overcurrent functions. 3 phase overcurrent thresholds.
3 earth overcurrent thresholds. 11 families of curves (IEC,IEEE/ANSI, Electromechanical).
Blocking logic. Instantaneous units.
More information : True RMS measurement (up to
10th harmonic). Alarm and trip messages in
selectable language.
Applications Industrial electrical networks. Utilities. HV & MV substations. MV & LV transformers.
Protection and control 3 independent phase.
overcurrent thresholds (50/51). 3 independent earth.
overcurrent thresholds(50N/51N).
11 families of curves (IDMT)
(5 x CEI, 5 x IEEE/ANSI, 1 RI). Blocking logic. Start contacts. Output relay latching (86)
Inputs and outputs 3 phase current inputs. 1 earth current input. Dual rated 1 & 5 Amp CT
inputs. 2 programmable logic inputs. 5 programmable logic outputs.
Measurements True RMS phase & earth
currents. Permanent self-test. Fault memorisation and display.
User interface 8 leds including
4 programmables. 32 character alphanumeric
display. RS 485 rear connection. MODBUSTM Courier or
IEC 60870-5-103communication.
Drawout case.
MiCOM P 121Phase and earth overcurrent protection
MiCOM P121 is the universal phase and earth overcurrent andoverload relay. Advanced functions allow maximum performance atan optimised cost.
More convenient : Dedicated messages. Programmable leds.
More compatible : MODBUSTM, Courier or IEC60870-5-103 communicationprotocols.
Drawout case with CT shortcircuits.
Dual rated 1 and 5 Amp CTinputs.
-
7/28/2019 MICOM P121
2/2
Current inputs
Phase current range : 1 and 5 Amp
burden : < 0.3 VA (5 A) overload withstand :
1 second @ 100 x rated current ;2 seconds @ 40 x rated currentcontinuous @ 3 x rated current
Earth current range : 1 and 5 Amp burden : < 0.01 VA at 0.1IE (5A) overload withstand :
1 second @ 100 x rated current ;2 seconds @ 40 x rated currentcontinuous @ 3 x rated current
SettingsPhase time overcurrent thresholds : 3 (I>, I>>, I>>>) ranges : from 0.1 to 40 x rated
current I> IDMT curves :
IEC 255-3 : STI, SI, VI, EI, LTIIEEE/ANSI : MI, VI, EI, CO2,CO8Electromecanical : RI
instantaneous time :(I>, I>>, I>>>) < 30 ms
time delay :
(tI>, tI>>, tI>>>) from 0 to 150 s dropout time : 50 ms
Earth time overcurrent thresholds : 3 (IE>, IE>>, IE>>>) ranges : from 0.002 to 8 x rated
current
IE> IDMT curves :IEC 255-3 : STI, SI, VI, EI, LTIIEEE/ANSI : MI, VI, EI, CO2,
CO8Electromechanical : RI instantaneous time :
(IE>, IE>>, IE>>>) < 30 ms time delay :
(tIE>, tIE>>, tIE>>>) from 0 to 150 s dropout time : 50 ms
Auxiliary supply ranges : 24 to 250 Vdc
110 to 250 Vac ;50/60 Hz
burden :< 2 W + 0.25 W per logicoutput,
< 5 VA with AC voltage supply variations : 0.8 to 1.2 Uaux DC supply interruption : 50 ms
Logic inputs 2 isolated programmable inputs range : 24 to 250 Vdc burden : 0.25 W per input
Logic outputs 2 change-over programmable
outputs 2 N/O programmable outputs 1 watch-dog output current : make and carry for
0.2 s ; 30 Acarry continuously 5 A
break :at 135 Vdc (L/R = 30ms) ; 0.3 Aat 220 Vac (50/60 Hz) ;cos = 0.6 ; 5 A
T&D Protection & Contrle - 95, rue de la Banquire - BP 75 - 34975 Lattes Cedex FRANCE
Tl : 33 (0)4 67 20 54 54 - Tlex : 485 093 F - Fax : 33 (0)4 67 20 54 99 - E-mail: [email protected]
5051
50N51N
52 TRIP
WD
Logicinputs
Logicoutputs
Phase CTs
P121
RS 485Communication
3
Earth CT
Busbar
86
Remotecontrol
L11501B-02/99
Technical specifications
Communication type : RS485 2 wires, half
duplex, isolated
data rate : from 300 to 38 400bauds protocol : MODBUSTM RTU
Courier or IEC 60870-5-103
Housing case : MiCOM 20 TE, rack or
flush mounting, rear connections,full drawout with automatic CTshorting
case size : 4U (152mm)H x 103 mm W x 230 mm D
protection : IEC 529 ; IP 52,IK 07
weight : 1.9 Kg connectors : MIDOS 2 x28 points (double faston + M4screw per connection)
HMI display : 2 x 16 alphanumeric
characters, back-lit leds : 8 including
4 programmables keyboard : 7 button tactile key-
pad languages : French, English,
Dutch, German, Spanish,
Portuguese, Italian, American,Russian, Polish
Environment temperature : IEC 255-6
operating : - 25C to +55Cstorage : - 25C to +70C
humidity : IEC 68-2-3 dielectric withstand : IEC 255-5 impulse voltage : IEC 255-5 fast transient : IEC 1000-4-4;
ANSI C37.90.1 high frequency disturbance :
IEC 1000-4-1 class 3 RFI : IEC 1000-4-3 ;
ANSI C37.90.2 electrostatic discharge: IEC 100-4-2 auxiliary supply : IEC 255-11,
VDEW ; ripple : 12%,supply interruption : 50 ms
vibration : IEC 255-21-1 class 2 shock & bump : IEC 255-21-1
class 1 seismic : IEC 255-21-3 class 1
StandardsCE conformity to IEC 947-1 (EMC
and LV directives)ARCEAUX49Imp.-Tl.04992325
00
This
brochure
sh
ould
only
be
regarded
as
a
guide.
Itcontents
do
notconstitu
te
an
offerforsale,nor
advice
on
any
application
forany
pr
oductreferred
to
in
it.
1999ALSTOMT
&DProtection
&ContrleSA