Microfluidic Cooling for Detector and Electronic OUTLINE: Motivations for micro-channel cooling in HEP Micro-technologies involved First possible HEP cases: the NA62 GTK the ALICE ITS upgrade the LHCb VELO upgrade Other ongoing R&D programmes on micro-channel cooling Conclusions and perspectives A. Mapelli & P. Petagna CERN PH-DT Reporting on behalf of D. Bouit, J. Daguin, L. Kottelat, A. Mapelli, J. Noel, P. Petagna – CERN PH-DT K. Howell – Georges Mason University / CERN PH-UFT G. Nuessle – Universite Cathtolique de Louvain / CERN PH-UFT A. Pezous - CSEM P. Renaud – EPFL-LMIS4

Upload: paulina-dante

Post on 01-Jan-2016

69 views

Category:

Documents


2 download

DESCRIPTION

A. Mapelli & P. Petagna CERN PH-DT Reporting on behalf of D. Bouit , J. Daguin, L. Kottelat, A. Mapelli, J. Noel, P. Petagna – CERN PH-DT K. Howell – Georges Mason University / CERN PH-UFT G. Nuessle – Universite Cathtolique de Louvain / CERN PH-UFT A. Pezous - CSEM - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Microfluidic  Cooling for Detector and Electronic

Microfluidic Cooling for Detector and Electronic

OUTLINE:Motivations for micro-channel cooling in HEPMicro-technologies involvedFirst possible HEP cases: the NA62 GTK

the ALICE ITS upgradethe LHCb VELO upgrade

Other ongoing R&D programmes on micro-channel coolingConclusions and perspectives

A. Mapelli & P. PetagnaCERN PH-DT

Reporting on behalf ofD. Bouit, J. Daguin, L. Kottelat, A. Mapelli, J. Noel, P. Petagna – CERN PH-DT

K. Howell – Georges Mason University / CERN PH-UFTG. Nuessle – Universite Cathtolique de Louvain / CERN PH-UFT

A. Pezous - CSEMP. Renaud – EPFL-LMIS4

Page 2: Microfluidic  Cooling for Detector and Electronic

Motivations I : starting point

Channel parameters used for Thome’s preliminary simulations

based on the NA62 GTK test case

Silicon m-channel cooling device used for testing at EPFL

Twepp 2009 (Paris): J.R. Thome, J.A. Olivier, J.E. Park Two-Phase Cooling of Targets and Electronics for Particle Physics Experiments

• Main focus: high power densities, up to as high as 350 W/cm2;• However, interesting preliminary features also for HEP applications;• State-of-the-art heat transfer and pressure drop models presented;

Typical laboratory fluid distribution! Liquid vs. evaporative

Geometry sensitivity for liquid cooling

Page 3: Microfluidic  Cooling for Detector and Electronic

Motivations – II : advantages for HEP

MINIMIZATION OF MATERIAL BUDGET•ultra thin Si cooling plates and tiny (PEEK?) pipes•no mechanical components required for thermal bridges

COOLING POWER ENHANCEMENT•very high heat transfer coefficients (very small Dh)•very high heat flux (large S)

REDUCTION OF DT BETWEEN HEAT SOURCE & HEAT SINK•large surface available for the heat exchange (cold plate vs. cold pipe)•natural minimization of the thermal resistance between the source and the sink

Laminar flow3.66 ÷ 4.36

Fluid thermal conductivity

0.05 ÷ 0.11

O (10-4)O (103 W/m2K)

Page 4: Microfluidic  Cooling for Detector and Electronic

Motivations – III : thermal performance

NO CTE DIFFERENCE!

Examples of cooling solutions in LHC trackers

Pix

SubstrateHeat sink

Cooling pipe

ATLAS IBL staves

Strip

Carbon foam + CFRP skin

Thermal contact & Heat spreader

With a standard cooling approach, the DT between the module and the fluid ranges between 12 and 20 C (small contact surface + long chain of thermal resistances)

Lower temperatures are envisaged for the future Si-trackers at SHLC. This has non-negligible technical impacts on the cooling plants

Si sensor

Si chips

Si cold plate

DT ~ 15 C

DT ~ 10 C

DT ~ 5 C

Adhesive

Page 5: Microfluidic  Cooling for Detector and Electronic

Motivations – IV : impact on material budget

X/X0 vs. h for the CMS Si-strip Tracker

X/X0 vs. h for the CMS PIX detector

Present LHC large Si trackers (ATLAS and CMS) ~ 2% X0 per layer

SLHC “phase II” upgrade: “significant” reduction needed

Future trackers at ILC ~ 0.1 ÷ 0.2% X0 per layer

%X0

%X0

PANDA

Page 6: Microfluidic  Cooling for Detector and Electronic

Micro Fabrication Technologies

Weigl & Hedine, Am. Biotech. Lab., 2002, 20, 28-20

Microfabrication technologies are derived from microelectronics to fabricate microsystems and microfluidic devices.

Bulk micromachining: mechanical structures are etched in the wafer.

Surface micromachining: layers of material are deposited on the wafer and structured.

Commonly used substrates and materials include Silicon, SOI, Glass, Pyrex, Quartz, Polymers (SU-8, Polyimide, Parylene), Metals,...

Fully laminar flow ensures high degree of predictability and controlNo sources of instabilities and/or vibrations

Page 7: Microfluidic  Cooling for Detector and Electronic

Micro Fabrication: Etching

Etching of microchannels

Dry EtchingPlasma, RIE, DRIE

Wet EtchingChemical: KOH, TAMH, PGMEA

SU-8 photoresistVertical walls

Silicon KOHWalls depend on crystal orientation

Silicon DRIEAnisotropic, vertical walls

Page 8: Microfluidic  Cooling for Detector and Electronic

Micro Fabrication: Bonding

Anodic Bonding• Pyrex-Si, Si-Pyrex-Si• Temp. ~400°C• Voltage 50 ÷ 1200 V• Tool pressure

Direct Bonding• Silicon Fusion Bonding

• Si-Si, Si-SiO2

• Annealing ~1000°C• Optional tool pressure

• Plasma-activated• Low temp.

Required: - wafer flatness- Surface roughness < 1 nm

Intermediate layer bonding• Polymers (SU-8, Parylene,…)• Thermocompression

• Eutectic (AuIn, AuSn, AuSi, AlGe..)• Glass Frit

Page 9: Microfluidic  Cooling for Detector and Electronic

Micro Fabrication: Thinning

Wafer thinningGrindingChemical Mechanical PolishingEtching

Local thinningEtching (dry or wet)

Page 10: Microfluidic  Cooling for Detector and Electronic

NA62 GTK – Requirements and Basic Concept

Wedged manifold, 1.6 mm Max width, 150 mm thick

Wedged manifold, 1.6 mm Max width, 280 mm thick

Wedged manifold, 1.6 mm Max width, 400 mm thick

Design optimization

m-channel cooling plateFinal target: 0.10 – 0.15 % X0

(Silicon thickness < 150 mm)

• Priority: minimize X0

• Acceptable DT over sensing area ~ 5 °C• Dimension of sensing area: ~ 60 x 40 mm• Max heat dissipation: ~ 2 W/cm2 • Target T on Si sensor ~ -10 °C

3 INDEPENDENT STATIONS: “SIMPLE”

SYSTEM

“Keep it simple at first” approach:

liquid C6F

14 cooling

Page 11: Microfluidic  Cooling for Detector and Electronic

Channels: 100 ÷ 300 µm wide100 ÷ 70 µm deep

Manifolds 280 µm deepMax width = 1.6 mm

Through holes

Wall thickness between channels: 200mm (for Si

fusion bonding) or 50mm (for Si-Si anodic bonding)

NA62 GTK – Details of m-channel Design

chan

nels

man

ifold

s

NA62 baseline design holds ~ 20 bars.Critical point at the level of the manifold’s maximum width (1.6 mm).Safety factor: 3 to 5

Channels: 100 x 100 µm

Page 12: Microfluidic  Cooling for Detector and Electronic

Inlet

Outlet

Heater 1

Heater 2

Heater 3

1 2 3 4 5

6 7 8 9 10

11 12 13 14 15

NA62 GTK –m-channel Thermal Performance

611

712

813

914

1015

611

712

813

914

1015

Max DT on sensor ~ 6 C

Fluid-sensor DT ~ 6 C

Connectors

Wafer equipped with GTK simulator

Page 13: Microfluidic  Cooling for Detector and Electronic

150

200

70

100 ÷ 240

100 ÷ 240

480

÷ 76

0

280

Thinning by grindingThinning by selective etching

Limit of acceptance

Drawing not to scaleAll dimensions in µm

NA62 GTK – Second Order Optimization

IN IN

OUT OUT

chan

nels

man

ifold

s

Influence of channel geometry on total pressure drop

Dual inlet / dual outlet design allows for more uniform flow distribution and for sensible pressure drop reduction

A second round of CFD and structural parametric analysis brings to a fully compliant solution: now

submitted to the collaboration for approval

Page 14: Microfluidic  Cooling for Detector and Electronic

ALICE ITS – First Approach

Sketch of building blocks constituting a generic stave

~ 200 mmStave from SPD to ITS

Support Structure

Material budget X/X0

(%)

Carbon foam structure

0.22 – 0.34

Polyimide micro-channel structure

0.085 – 0.13

Silicon micro-channel structure

0.07 – 0.11Conventional configuration Micro-channel cooling approach

Two working possibilities: • evaporative C4F10• monophase water in underpressure

Page 15: Microfluidic  Cooling for Detector and Electronic

Sketch of building blocks constituting a generic stave

Sideline micro-channels

hole

Common Inlet pipe

Module n

Module n+1

Common return pipe

ALICE ITS – Sideline Micro Channels?

~ 0.5 W/cm2

No power dissipation

Remove silicon cooling plate where not needed

Page 16: Microfluidic  Cooling for Detector and Electronic

ALICE ITS – Open Issues

Sketch of building blocks constituting a generic stave

~ 200 mm

Long stave (~ 200 mm):• multi-module m-channel solution? (multi

connector or module-to module junction)• Single m-channel from 12” wafer? (higher

cost and more difficult handling of thinned devices)

“Packed” barrel configuration” • Need for a reliable in-plane m-connector.

Discussions ongoing with CSEM for a common R&D programme

?

Page 17: Microfluidic  Cooling for Detector and Electronic

LHCb VELO – First ApproachPower dissipated: 2 W/cm2∼Cooling: evaporative CO2

Cooling substrate in acceptance: 250 ÷ 500 μmout of acceptance: 1 mm∼

Baseline configuration

Micro-channel configuration

Out of acceptance up to 1 mm Si!

CO2 saturation pressure at room temperature: high pressure is not an issue!

Page 18: Microfluidic  Cooling for Detector and Electronic

LHCb VELO – Open Issues

Small issue:Out-of plane connector is acceptable, but a special reduced size production must be requested (Nanoport connectors rated up to 103 bar!)

Big issue:LHCb VELO is inside the secondary LHC vacuum: absolute reliability is required!!!Main problem: QA/QC of the hermetic bond between the two wafers

Page 19: Microfluidic  Cooling for Detector and Electronic

EPFL: Thome, Atienza, LeblebiciETHZ: PoulikakosIBM: Michel, Brunschwiller

“The CMOSAIC project is a genuine opportunity to contribute to the realization of arguably the most complicated system that mankind has ever assembled: a 3D stack of computer chips with a functionality per unit volume that nearly parallels the functional density of a human brain. CMOSAIC's aggressive goal is to provide the necessarily 3D integrated cooling system that is the key to compressing almost 1012 nanometer sized functional units (1 Tera) into one cubic centimeter with a 10 to 100 fold higher connectivity than otherwise possible”

Other R&D Programmes – CMOSAIC

Page 20: Microfluidic  Cooling for Detector and Electronic

Other R&D Programmes – Polyimide m-channels

Courtesy of I. Sgura and C. Pastore (INFN Bari)

Page 21: Microfluidic  Cooling for Detector and Electronic

Other R&D Programmes – Polyimide m-channels

Courtesy of I. Sgura and C. Pastore (INFN Bari)

Page 22: Microfluidic  Cooling for Detector and Electronic

Other R&D Programmes – Polyimide m-channels

Courtesy of I. Sgura and C. Pastore (INFN Bari)

Page 23: Microfluidic  Cooling for Detector and Electronic

Micro-channel cooling features highly interesting potentialities for HEP applications

Available m-technologies allow for a palette of solutions adapted to different requirements and specific environments

A working solution for the NA62 GTK is ready for submission to the experiment

Activities for the ALICE ITS and for the LHCb VELO upgrades have started

Parallel activities are ongoing outside CERN for hi-power computing (IBM, EPFL, ETHZ) and for HEP (Bari/CERN Polyimide m-channels for ALICE ITS)

m-channel cooling is perfectly suited for future 3D architectures (if any...)

Main issues to be addressed: 1) Reliable QA/QC process for hermetically sealed channels (bonding) 2) Reliable miniaturized in-plane connections

Conclusions

Page 24: Microfluidic  Cooling for Detector and Electronic

PHASE I: m-channel cooling plates conceived to adapt to an existing electronics design and placed in good thermal contact (NA62 GTK)

PHASE II: m-channel cooling plates conceived in connection with the electronics design and integrated at the same time in the module’s architecture (maybe already possible with ALICE and LHCb phase I upgrades)

PHASE III: m-channel cooling integrated in the module conception:a) In the sensor? Compatible with physics performance?b) In the chips? When? By whom?c) In the Si-Interposer? (should 3D become real...)

Perspectives for m-channels in HEP