minimizing tewi by charge reduction in a compact chiller - ideals

61
Minimizing TEWI by Charge Reduction in a Compact Chiller ACRC TR-176 For additional information: Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Urbana,IL 61801 (217) 333-3115 P. R. Barnes and C. W. Bullard August 2000 Prepared as part of ACRC Project 69 Stationary Air Conditioning System Analysis C. W. Bullard, Principal Investigator

Upload: others

Post on 11-Feb-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Minimizing TEWI by Charge Reduction in a Compact Chiller

ACRC TR-176

For additional information:

Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Urbana,IL 61801

(217) 333-3115

P. R. Barnes and C. W. Bullard

August 2000

Prepared as part of ACRC Project 69 Stationary Air Conditioning System Analysis

C. W. Bullard, Principal Investigator

The Air Conditioning and Refrigeration Center was founded in 1988 with a grant from the estate of Richard W. Kritzer, the founder of Peerless of America Inc. A State of Illinois Technology Challenge Grant helped build the laboratory facilities. The ACRC receives continuing support from the Richard W. Kritzer Endowment and the National Science Foundation. Thefollowing organizations have also become sponsors of the Center.

Amana Refrigeration, Inc. Ar~elik A. S. Brazeway, Inc. Carrier Corporation Copeland Corporation DaimlerChrysler Corporation Delphi Harrison Thermal Systems Frigidaire Company General Electric Company General Motors Corporation Hill PHOENIX Honeywell, Inc. Hussmann Corporation Hydro Aluminum Adrian, Inc. Indiana Tube Corporation Invensys Climate Controls Lennox International, Inc. Modine Manufacturing Co. Parker Hannifin Corporation Peerless of America, Inc. The Trane Company Thermo King Corporation Valeo, Inc. Visteon Automotive Systems Whirlpool Corporation Wolverine Tube, Inc. York International, Inc.

For additional information:

Air Conditioning & Refrigeration Center Mechanical & Industrial Engineering Dept. University of Illinois 1206 West Green Street Urbana,IL 61801

217 3333115

Abstract

MINIMIZING TEWI BY CHARGE REDUCTION IN A COMPACT CHILLER

A simulation model was developed to investigate strategies for reducing total equivalent

warming impact (TEWI) in compact water chillers. The focus was on minimizing R-410A

refrigerant charge while increasing efficiency. Compact flat plate heat exchangers with

refrigerant channels similar in scale to microchannels (Dh= 0.7 mm and 0.8 mm for the

condenser and evaporator, respectively) appear capable of reducing total system charge about

80% compared to conventional air-air split systems. Results are also compared to those obtained

for highly efficient air-to-air unitary systems, in which minimum-TEWI design strategies require

larger heat exchangers having greater charge. Overall the two approaches achieve comparable

reductions in global warming impacts; the chiller depends more on reducing direct emissions,

compared to unitary systems' dependence on reducing indirect emissions through use of flat

mUlti-port tubes with folded fins. These results are tentative, because the simulations did not

include detailed analysis of possible opportunities for improving the chiller technology by

optimizing the air and water pumping requirements in the secondary loop. The primary benefit

of the chiller technology, relative to air-air unitary, appears to lie in its compatibility with the use

of toxic or flammable refrigerants.

.,.-

Table of Contents

List of Tables ............................................................................................................. iii List of Figures ........................................................................................................... iv Nomenclature ............................................................................................................ v 1. Introduction ........................................................................................................... 1 2. Baseli ne systems ................................................................................................ 2

2. 1 Air-to-air split systems .................................................................................... 2

2.2 Compact hermetic chiller ............................................................................... 4 3. Minimum-TEWI chiller ........................................................................................ 8 4. Tradeoffs near the optimum .......................................................................... 15

4. 1 Standard operating conditions .................................................................... 15 4.2 Increased Tevap ............................................................................ .................... 16 4.3 Effect of water loop pressure drop ............................................................. 17

5. Conclusions ........................................................................................................ 20 6. References ............................................................................................................ 22 Appendix A. Baseline systems .......................................................................... 25

A. 1 Baseline residential split system ................................................................ 25 A.2. Baseline chillers ............................................................................................ 26

A.2.1 Geometry of commercially-available plate heat exchangers .................. 26 A.2.2 Correlation selection for plate heat exchangers ..................................... 27

A. 2. 2. 1 Single-phase correlations ....................................................................... 29 A.2.2.2 Evaporation ............................................................................................ 32 A.2.2.3 Condensation ......................................................................................... 35

A.2.3 Typical CBE simulation results ................................................................. 37 Appendix B. Details of ideal chiller optimization ........................................ 41

B. 1 Model development. ...................................................................................... 41 B.1.1 Design operating conditions ..................................................................... 41 B.1.2 Assumed model inputs .............................................................................. 41 B.1.3 Search variables ......................................................................................... 44 B.1.4 Model correlations ...................................................................................... 44

B.2 Chiller optimization .................. ...................................................................... 45

11

.,'

List of Tables

Table 2.1 Split system power comparison ...................................................................................... 3 Table 2.2 Hermetic chiller model inputs ......................................................................................... 5 Table 2.3 CBE results ...................................................................................................................... 6 Table 3.1 Correlations ..................................................................................................................... 8 Table 3.2 System comparison with standard inputs ...................................................................... 12 Table 4.1 Optimal chiller with higher Tevap ................................................................................ 18 Table 4.2 Tradeoffs when ~Pwloop=O .......................................................................................... 19 Table A.l Alc split system operating conditions at design point.. ................................................ 26 Table A.2 SWEP plate geometry .................................................................................................. 28 Table A.3 Correlation range .......................................................................................................... 31 Table A.4 Split systemlCBE model comparison ........................................................................... 39 Table B.l Design operating conditions ......................................................................................... 41 Table B.2 Model inputs ................................................................................................................. 42 Table B.3 Search variable constraints ........................................................................................... 44 Table B.4 Model comparison ........................................................................................................ 49

iii

List of Figures

Figure 2.1 Split system TEWI comparison ..................................................................................... 3 Figure 2.2 Split system/CBE TEWI comparison ............................................................................ 6 Figure 3.1 Condenser temperature profile of optimized chiller .................................................... 10 Figure 3.2 Evaporator temperature profile of optimized chiller ................................................... 11 Figure 3.3 Power requirements ..................................................................................................... 11 Figure 3.4 Charge comparison ...................................................................................................... 13 Figure 3.5 TEWI comparison ........................................................................................................ 13 Figure 3.6 Minimum-TEWI condenser ......................................................................................... 14 Figure 4.1 Minimum-charge at different COPs ............................................................................ 15 Figure 4.2 TEWI tradeoffs at standard inputs ............................................................................... 16 Figure 5.1 TEWI comparison for all options ................................................................................ 21 Figure A.l Alc split system charge distribution [glkW cooling capacity] .................................... 25 Figure A2 Typical brazed plate heat exchanger. .......................................................................... 26 Figure A.3 Plate spacing ............................................................................................................... 28 Figure A.4 Refrigerant-side velocity comparison ......................................................................... 28 Figure A5 Water-side velocity comparison ................................................................................. 29 Figure A.6 Single phase heat transfer correlations ....................................................................... 30 Figure A7 Single phase pressure drop correlations ...................................................................... 32 Figure A8 Evaporation heat transfer correlation .......................................................................... 33 Figure A9 Evaporation pressure drop correlation ........................................................................ 34 Figure A10 Condensation heat transfer correlation ..................................................................... 35 Figure A.ll Condensation pressure drop correlation .................................................................... 36 Figure A12 Split system and CBE power .................................................................................... 38 Figure A13 Split system and CBE charge distribution ................................................................ 38 Figure A14 Split system and TEWI comparison ........................................................................ .40 Figure B.l Chiller loop layout (10.6 kW unit) ............................................................................. .43 Figure B.2 Heat exchanger layout for current investigation ......................................................... 45 Figure B.3 Split system and optimum chiller power. .................................................................... 46 Figure B.4 Energy-charge comparison ........................................................................................ 47 Figure B.5 Split sytem and optimized chiller charge distribution ................................................. 48 Figure B.6 Split system and optimized chiller TEWI comparison .............................................. .48

iv

Nomenclature

A area m2

b plate spacing mm Cp specific heat kJ/kg-K D diameter mm Dh hydraulic diameter mm f Darcy friction factor fQ heat flux assumption for charge inventory g gravitational constant mls2

G mass flux per channel kglm2-s h heat transfer coefficient W/m2-K

lfg enthalpy of vaporization kJ/kg k thermal conductivity W/m-K KH Hughmark flow parameter L length m LMTD log-mean temperature difference °C m mass g ill mass flow rate kgls Np number of plates Perit critical pressure kPa q heat flow rate kW " heat flux kW/m2 q

T temperature °C V overall heat transfer coefficient W/m2-K

VA conductance W/K V ve1cocity mls

V volumetric flow rate m 3/s w plate width mm

VI power W Wg refrigerant gas density weighting factor x vapor quality

Dimensionless Groups "

Bo boiling number Bo=-q-G· i fg

Fr Froude number 2· !1P/pV~x

Nu Nusselt number hD/k

Pr Prandtl number IlCp/k

v

Re

Greek Symbols a ~ ~p

~T

11 pump

11s

~

P

Subscripts 2ph amb avg blower bulk calc cond c, cold comp dis eq evap fan h, hot In

I liq 10 loop out r sub suct sup tot w x

Reynolds number

Lockhart Martinelli parameter

void fraction corrugation angle, from vertical pressure drop temperature change water pump efficiency isentropic compressor efficiency viscosity density

two-phase ambien average evaporator blower, or sum of all fans in cold water loop pertaining to the entire bulk flow calculated value condenser cold water loop compressor discharge line equivalent evaporator condenser fan hot water loop inlet liquid property liquid line liquid only property water loops outlet refrigerant subcooled suction line superheated total water, water-side as a function of quality

vi

pVD/Jl

° kPa °C

kglm-s kglm3

1. Introduction

The Montreal Protocol mandated the phase-out of hydrochlorofluorocarbons (HCFCs),

requiring selection of new refrigerants and new technologies (Sands et al. 1997). To characterize

the global warming effects of new systems, the total equivalent warming impact (TEWI)

accounts for the release of refrigerant into the atmosphere (direct effects) and the release of

carbon dioxide from electricity generation (indirect effects).

The TEWI for a 10.6 kW residential air conditioner using R410A is about 10% direct and

90% indirect (Kirkwood and Bullard, 1999). Since the direct portion is a function of the amount

of charge and the loss rate, a 45% reduction in charge could improve TEWI as much as a 5%

increase in COP. Many alternatives to HCFCs are not greenhouse gases, but may be either toxic

or hazardous (e.g. butane, propane, ammonia) and therefore it is necessary to minimize charge

when those refrigerants are used. This study uses a simulation model to investigate various

means of reducing TEWI, with the primary focus on strategies for minimizing charge without

decreasing COP.

Section 2 describes two residential-scale "baseline" systems from which improvements

can be measured. One is a conventional U.S.-style split system; the other is a hermetic chiller

utilizing compact brazed plate heat exchangers. The residential scale was chosen only to provide

a familiar starting point for the analyses which are normalized in per unit cooling capacity, in the

interest of generalizing the resulting insights across a broader range of unitary alc system and

chiller sizes.

Section 3 briefly describes the optimization process and explains the results of the TEWI

minimization. Section 4 describes the sensitivity analysis performed near the optimum with

respect to several model assumptions. Conclusions are summarized in Section 5.

Appendix A describes the baseline systems: conventional split system and compact

brazed plate system. Appendix B provides a detailed discussion of the flat plate model

development.

1

.. ~-

2. Baseli ne systems

2.1 Air-to-air split systems A conventional air-to-air residential split system uses copper tubes and aluminum fins to

transfer heat between the refrigerant and air. Typically the condenser and compressor located

outside the house require long liquid and suction lines (>7.5 m each) to the evaporator inside the

house. The heat exchangers and long liquid line account for nearly 90% of total charge

(Andrade and Bullard, 1999).

Kirkwood and Bullard (1999) explored the extent to which TEWI could be reduced in

systems with refrigerant-air heat exchangers by using microchannel heat exchangers. They

examined microchannels because of their compactness for a given heat transfer capacity and

pressure drop, compared to traditional round-tube/plate-fin heat exchangers. Their simulations

suggested that TEWI could be reduced by approximately 13% compared to a conventional

R410A system, at the ARI 210/240-B standard rating condition (26.7 °C DB indoor, 19.4 °C WB

indoor, 27.8 °C DB outdoor). This improvement was achieved by increasing COP (4.5 vs. 3.8)

and reducing charge (235 glkW vs. 258 glkW), thus decreasing both the indirect and direct

components ofTEWI (Figure 2.1).

Kirkwood's design decreased TEWI considerably, but was limited by several factors.

First, the search was limited to "off the shelf' microchannel tubes and other components.

Secondly, air has a high thermal resistance which requires large area, which in tum limits heat

exchanger charge-reduction strategies. Larger heat exchangers increase COP, but also require

additional charge, even with microchannel tubes. This explains the minimal charge reduction

shown in Figure 2.l. There is still some potential improvement in the microchannel design by

either developing new microchannel technologies, or decreasing liquid line length (10.8 m in

Kirkwood's simulations) to reduce total charge. Table 2.1 compares the systems, with all figures

normalized per kW of cooling capacity.

The details of the TEWI calculations are shown below:

TEWI = Indirect Effect + Direct Effect Indirect Effect = Power. Run Time. Mass CO 2

Where: Power = total electric power consumed by the unit [kWeJ

2

(2.1) (2.2)

Run Time = hours the unit runs per year [900 hr/yr, Illinois] Mass CO2 = mass of CO2 produced in electric generation [0.65 kgC02lkWhe]

Direct Effect = Charge. Loss Rate. GWP (2.3) Where:

Charge = total refrigerant charge of the system [kg] Loss Rate = rate of refrigerant leakage per year [assumed 4%/yr] GWP = global warming potential of refrigerant [1730 kgC02IkgR41OA]

The C02 emission rate for electricity generation and global warming potential was

obtained from Sand et ai. (1997). The refrigerant leakage rate and run time were obtained from

Kirkwood and Bullard (1999).

180~-----------------.

II Indi rect [J Oi rect 160 +------{!

~140+---

m ~ 120 +---

8. ~ 100

~ o 80+---

~ ...... 60+---

~ .- 40 +---

20+---

0+---

Conventional split system Microchannel split system

Figure 2.1 Split system TEWI comparison

T bl 21 S r a e iPllt s stem power com~anson Conventional Microchannel split system split system

W tot [WIkW cooling capacity] 256 221

W comp [WIkW] 198 187

WpUmPing [WIkW] 58 34

Wblower [WIkW] 40 17

Wcondfan [WIkW] 18 17

3

....

2.2 Compact hermetic chiller An alternative way to minimize the direct TEWI effect would be to minimize charge by

building a small chiller to take advantage of the compactness obtainable with refrigerant-to-water

heat exchange instead of refrigerant-to-air. Commercially available compact brazed plate heat

exchangers (CBEs) are used in a wide variety of applications (food processing, chemical reaction

processes and pharmaceutical industries). Due to their very compact nature, high surface­

volume ratios, relatively low pressure drops, and their ability to utilize chevrons and bumps

imprinted on the plates, they rely more on heat transfer coefficient and less on area to transfer

heat.

Many studies have examined liquid-liquid heat transfer and pressure drop in CBEs:

Buonopane and Troupe (1969), Okada et al. (1972), Cooper (1974), Focke et al. (1985), Rortgen

(1988), Shah and Focke (1988), Roetzel et al. (1994), Yang and Rundle (1994), Bogaert and

Boles (1995), Talik et al. 1995, and Muley and Manglik (1999). However, only a few sources

have examined evaporation and condensation in CBEs: Panchal et al. (1983), Marvillet (1991),

Haseler and Butterworth (1995), Yan and Lin (1999), and Yan et al. (1999), with only the two

Yan studies providing correlations. The Yan correlations for two-phase heat transfer and

pressure drop were used in a simulation model with correlations from Shah and Focke for single­

phase heat transfer and Focke et al. for single-phase pressure drop. These were chosen by

applying criteria described in Appendix A.

The compact chiller using CBEs was modeled according to the ARI 550/590 standard

rating condition for chillers (0.054 Us per kW at 29.4 DC inlet condenser water, 0.043 Us per

kW at 6.7 DC outlet evaporator water). It was assumed that the connecting line lengths could be

quite short, as shown in Table 2.2. To provide chilled water to every room, a total length of

150 m was assumed for the cold water pipes, while the hot water loop was assumed to be 50 m.

It was assumed that the fan power requirements would be identical to the split system outdoors

(19 W/kW) and halved indoors due to the absence of ductwork (20 W/kW). Superheat was set to

7 DC as recommended by SWEP (1992) for that company's compact brazed plate heat

exchangers. Subcooling was set equal to 2 DC in order to minimize the amount of liquid in the

condenser, while still ensuring full condensation. The compressor was assumed to have an

4

isentropic efficiency of 0.7 and UA of 15.8 W/K, identical to the scroll compressor simulated by

Andrade and Bullard (1999). Water pumping power was calculated by Equation 2.4, and pump

efficiency was assumed to be 0.6 (Hall, 2000).

. V(M> HX + ilP1oop ) W = water pump (2.4)

11 pump

The compressor power for the chiller is greater due mainly to the difference in standard

rating conditions for the split system versus the chiller. As shown in Table 2.3, the split system

condenses at 39 °e and evaporates at 9 °e. The eBE system with 60 plates in both the

condenser and evaporator (denoted 60x60) has average condensing and evaporating temperatures

of 37 °e and 5 °e, respectively. This increases compressor power to 208 W/kW compared to

198 W/kW for the conventional split system. The two water loops introduce 9 W/kW that did

not exist in the conventional split system. However, because indoor blower power was reduced

by half, the total power consumed by the chiller (255 W/kW) about equal to the conventional

split system (256 W/kW).

T bl 22 H h'll d I ' a e ermetIc c 1 er mo e mputs

variable value variable value

qevap 10.6 kW l1s,comp 0.7

Wblower 20W/kW UAcomp 15.8 W/K

Weondfan 18 W/kW Lsuction 0.5m

TWe,out 6.7°e ~ischarge 0.5m

TWc,in 29.4 °e Lliquid 0.2m

Vw•e 1.73 m3/hr Dsuction 10.7 mm

"w,e 2.17 m3/hr Ddischarge 12.7 mm

ilTsup 7°e D1iquid 3.0mm

ilTsub 2°e L1oop,cold 150m

Tamb 27.8°e L1oop,hot 50m

11 pump 0.6 D1oop,h&c 25.4 mm

5

Table 2.3 CBE results Conventional CBE split system (60 plates in both HX's)

W IOI [WIkW] 256 255

W comp [WIkW] 198 208

WpUmPing [W/kW] 58 47

Wblower [W/kW] 40 20

WCOrul fan [WIkW] 18 18

WCOldlOOP [WIkW] -- 5

WhOllOOP [WIkW] -- 4

m [glkW] 258 100

Tcond,avg [0C] 39 37

Tevap,avg [0C] 9 5

The compact design of the CBEs, and the shorter liquid line, assumed for the remotely

located hermetic packaged chiller, provide substantial charge reduction (100 glkW vs. 258

glkW). As a result, TEWI is 7% less for the CBE system than the conventional split system, but

still 7% higher than the microchannel split system (Figure 2.2).

180,---------------------------------.

160

~ 140

l 8. 120

~ 100

~ 80 (,)

~ ..... 60

~ 40

20

o Conventional split system

Microchannel split system

60XSO Plate CBE

Figure 2.2 Split systemlCBE TEWI comparison

6

....

As mentioned earlier, one of the advantages of eBEs is that they can be used in a wide

variety of applications, but they are used primarily in liquid-liquid heat exchange applications.

As such, the design is not necessarily optimized for refrigerant evaporation and condensation

heat transfer. Initial analyses indicated that the best way to minimize charge was by decreasing

plate spacing, increasing heat transfer at the same time, paying a slightly higher price in pressure

drop. The resulting ideal plate heat exchanger had plate geometries well outside those used to

develop the correlations (Appendix A). Therefore, the model was altered by using different

correlations before conducting the optimization for minimum TEWI (briefly described in

Section 3, described in detail in Appendix B).

7

" ,,"

3. Minimum-TEWI chiller

Initial analyses suggested that the optimal heat exchanger geometries were well outside

the range of channel aspect ratios used to develop the correlations for the chevron plate CBBs.

The CBB model was then modified by replacing the heat transfer and pressure drop correlations

as described in Table 3.1. These correlations were developed for flow in smooth tubes and

applied to rectangular channels, using the hydraulic diameter calculated according to Equation

2.5. The optimizations had heat flux and mass flux values within the range of the correlations

and are extrapolated only on diameter.

2·w·b Dh =--­

w+b

Table 3.1 Correlations Conventional

Flat plate chiller CBE chiller

Heat transfer

Condensation Yan, Lio & Lin Dobson-Chato

Evaporation Yan&Lin Wattelet-Chato

Single-phase Shah & Focke Dittus-Boelter

Pressure drop

Condensation Yan, Lio & Lin de Souza-Pimenta

Evaporation Yan & Lin de Souza-Pimenta

Single-phase Focke ASHRAE

Charge Rice, with Hughmark void fraction

(2.5)

The optimization analysis favored smaller diameters, but previous experiments with

R410A in microchannels suggest that extrapolation errors are small (Stott et ai., 1999). The first

step was to maximize COP, within roundoff to two decimal places, by decreasing refrigerant

plate spacing and increasing the number of plates to decrease pressure drop. Then heat

exchanger geometry was adjusted to minimize charge for that specified value of COP, using

direct search and variable metric optimization algorithms. By maximizing COP first, the

compressor discharge pressure decreased and the suction pressure increased. This forced the

refrigerant outlet temperatures within 3.6 DC and 0.6 DC of the water inlet temperature for the

counterflow condenser and evaporator, respectively. To decrease charge at the high COP,

geometry was changed in a way that increased condenser pressure drop so that the refrigerant

8

....

outlet temperature was within 0.1 °C of the water inlet. As seen with the CBE chiller, the

biggest difference in compressor power is due to the different operating conditions, which were

specified by the standards.

The minimum-charge condenser has many long narrow plates (Np=200, L=3.8 m, w=1.9

mm) spaced closely together (br=O.4 mm) as shown in Table 3.2. The small refrigerant ports

create a mass flux in each channel 25% higher than the conventional split system. Due to the

narrow plate width, water-side plate spacing increases to 4.6 mm (vs. 1.6 mm for the CBE) in

order to decrease pressure drop. However, the result is a water mass flux per channel 3.9 times

higher than the conventional CBE. Since both water and refrigerant have high mass flux, overall

heat transfer coefficient is 138% higher than the conventional split system (3480 W/m2-K vs.

1600 W/m2-K). The high heat transfer coefficient allows for lower LMTD, 2.2°C (versus 5.6 °C

for the conventional split system) to decrease condensing temperature, as shown in Table 3.2.

The lower LMTD is obtained by decreasing the average condensing temperature to 34°C (at the

cost of increasing pressure drop) to have an approach temperature within 0.1 °C (Figure 3.1)

CBEs have many chevron bumps that restart the laminar boundary layer to create high

water heat transfer coefficients (-9500 W/m2-K) at low Reynolds numbers (-660). The

optimization analysis pointed towards geometries that lay outside the range of published

correlations for unsteady developing flow over chevron plates. Therefore, the current

investigation used correlations for smooth flat plates very closely spaced, relying on turbulent

flow (Re:::::2100) to achieve higher heat transfer coefficients (-4750 W/m2-K) than could be

obtained with lamilar flow between smooth plates. Even though the minimum-TEWI chiller has

a condenser 3.8 m long (compared to 0.4 m for the CBE) and higher Reynolds number, water­

side pressure drop is 8.6 kPa, while the CBE water pressure drop is 12 kPa due to the chevron

bumps.

The minimum-charge evaporator is much more sensitive to refrigerant pressure drop than

the condenser. While the evaporator has many plates, slightly longer than standard CBEs

(Np=200, L=0.7 m), they are much shorter than the condenser plates. The evaporator also tended

toward the minimum plate spacing on the refrigerant side, 0.4 mm, but the plates are much wider

than the condenser, 19 mm, (narrower than standard CBE width of 71 mm). The small

9

"~'

refrigerant channels have lower mass flux per channel than conventional split systems (76

kglm2-s vs. 157 kglm2-s), but have a much greater surface area and smaller hydraulic diameter

(0.8 mm versus 9.2 mm) providing higher refrigerant heat transfer coefficients. By using water

instead of air and the higher refrigerant heat transfer coefficient, the optimal chiller evaporator

has a higher overall heat transfer coefficient than conventional split systems (1872 W/m2-K vs.

700 W/m2-K). The refrigerant-side heat transfer area is much higher than the conventional split

system (2.6 m2 vs. 1.1 m2) and therefore, due to high U, has a much lower LMTD (3.6 °C versus

11°C). The evaporating temperature could not increase above 5 °C due to the low water

temperature required for the secondary loop, and the specified 7 °C superheat. The evaporator

temperature profile of the minimum-TEWI chiller is shown in Figure 3.2.

Despite the lower evaporating temperature (5°C vs. 9°C), compressor power was only

1 WIkW higher than the conventional split system, due to its lower average condensing

temperature (34°C vs. 39°C). As shown in Figure 3.3, total pumping power for the optimal

chiller was 21 % lower than the conventional split system. Due to the massive reduction in

charge (82%, Figure 3.4) the minimum-TEWI chiller reduces total TEWI 13% compared to the

conventional split system (Figure 3.5).

60

55

50 0' o

;:' 45

40

35 k-refrigeram

~----30 water~

Length [m]

Figure 3.1 Condenser temperature profile of optimized chiller

10

"~'

.. ~'

10

~ 8

6 refrigerant

4~~~~~~~~~~~~~~~

o 0.1 0.2 0.3 0.4 0.5 0.6 0.7

Length [m]

Figure 3.2 Evaporator temperature profile of optimized chiller

300~--------------------------------~

• Compressor [J Blower • Cond. Fan [J Cold Loop • Hot Loop

250 +----

'>: ... '1 200 +---

B ~ 150 +---­

~ ......

1100 +--­

a.

50+---

0+---

Conventional split system Mn-TEW I chiller

Figure 3.3 Power requirements

11

a e iystem companson WIt T bI 32 S

TEWI [kgC02lkW-year] Indirect TEWI Direct TEWI COP mtot [glkW]

Wcomp [W/kW]

WpUmPing [WlkW]

Wblower [WlkW]

Wcondfan [WlkW]

WCOldlOOP [WlkW]

WhotlOOP [WlkW]

Tavlt [0C]

AHT [m2]

LMTD [0C]

mass [glkW] D [mm]

~ w [mm] <Il

br [mm] s::: .g bw [mm] 0 u L [m]

No --# ref circuits APref [kPa]

APwcond [kPa] APw100D [kPa]

Tavg [0C]

AHT [m2] LMTD [0C]

mass [glkW] D [mm]

.... w [mm]

~ br [mm]

~ bw [mm] > ~ L [m]

N~ --# ref circuits

APref [kPa]

APwevao [kPa] APw100D [kPa]

- value tS at mmtmum search bound + value is at maximum search bound

Conventional split system

168 150 18

3.77 258

198

58

40

18

--

--39 1.6 5.6 144 9.1 ------

37.1 --

1.5 lO4 ----9

1.1 11.0 54 9.2 ------

6.3 --6

5.5 ----

12

....

stan ar mputs d d'

Min-TEWI chiller

147 144 3

3.96 47

199

46

20

18

5

3

34 1.7 2.2 9

0.7 1.9

0.4-4.8 3.8

200+ 99 355 8.6 29

5 2.6 3.6 8

0.8 19.0 0.4-0.6

0.69 200+

99 2.9 9.2 64

300.-----------------------------------, I!iI Condenser CI EloElporator • Uquid Une CI Suction Une • Discharge Une II Other

250+---

200 +---

I 150 +----1 ...... E

100 +---

50+---

0-/---

Conventional split system Win-TEWI chiller

Figure 3.4 Charge comparison

180.-----------------------------------, II Indirect CI Direct

160 +----------l

'i:' 140 +----m ~ 120 +----8-~ 100 +---

8 80+----

~ ...... 60+---i ~ 40+---

20+---

0+---

Conventional split system Min-TEWI chiller

Figure 3.5 TEWI comparison

The optimally sized condenser is actually very compact. Figure 3.6 shows a plate 3.8 m

long, but only about 2 mm thick and around 120 mm wide (allowing 0.2 mm channel dividers).

13

· .' "~'

Such a plate might be made of copper, steel or aluminum, and bent to fit into a more compact

package. Ends could be cut to accommodate brazed or welded fittings that would separate the

refrigerant and water channels at the inlets and outlets.

Figure 3.6 Minimum-TEWI condenser

14

,.'

4. Tradeoffs near the optimum

4. 1 Standard operating conditions

The results presented in Section 3 led to a chiller geometry in which TEWI was

minimized at the maximum COP achievable at the given operating conditions. The simulations

indicated that another 28% reduction in charge could be obtained, at a cost of 7% reduction in

COP, as shown in Figure 4.1a. Figure 4.1a shows minimum charge tradeoffs at various COP

values, while Figure 4.1 b shows the associated plate width and length tradeoffs for the

evaporator and condenser.

As COP decreased from the maximum of 3.96, charge was minimized by decreasing

condenser length, with little change to condenser plate width, and by simultaneously decreasing

evaporator width, with little change to evaporator plate length, as shown in Figure 4.1b. For both

heat exchangers, the number of plates remained at the arbitrarily selected upper bound (200)

while the refrigerant-side plate spacing remained 0.4 mm. Water-side plate spacing decreased

from 4.8 mm to 2.1 mm for the condenser and from 0.6 mm to 0.4 mm for the evaporator. These

effects increase all components of power (compressor and both water pumps) by increasing

condensing temperature, decreasing evaporating temperature and increasing water-side pressure

drop for both heat exchangers.

a. 0 (.)

4.0,----------------_

...

3.9 r max COP

3.8

3.7

3.6

3.5 30 35 40 45 50

charge [glkW capacity]

a) COP-charge tradeoffs

4

3.5

3

2.5

:g:2 ....I

1.5

0.5

~ ¢ maxCOP , I

~ ! ~ I

~ ~ ~

8

t. Evaporator _. ~- . Condenser

max COP

~ • o+---~---~---,____--~

o 5 10 w[mm]

15

b) HX geometry tradeoffs

20

Figure 4.1 Minimum-charge at different COPs

15

· ...

Manufacturing and cost considerations may also limit realization of the COP-maximizing

design. For example, the 19 mm wide by 0.4 mm tall rectangular evaporator channel would

require thick wall to withstand the pressures of R41OA. As seen in Figure 4.1 b, the charge­

minimizing design strategy allows for substantially narrower channels, but entails a COP

penalty. Similarly, the 3.7 m length of the optimal condenser could be a problem, but Figure

4.1 b shows how the length can be reduced as the maximum-COP constraint is relaxed.

Figure 4.2 shows TEWI for each of points in Figure 4.1 compared to the 60x60 plate

CBE and the conventional split system. Despite the lower COP, nearly every point has a lower

total TEWI than the CBE due to the drastic reduction in charge.

Of course, if the objective was not to minimize charge, plate lengths and widths could

probably be reduced with very little sacrifice of COP.

170~------------------------------------------~

'i:' co

160

~ 150 ... CI) Q.

3: 140

~130 ~ ...... 3: 120 W I-

110

100

II Indirect 0 Direct

- w

" 'a co en () Cij E Q) c 1ii 02

----_../ Y

;:; tn a:: c >. ~ en min-charge tradeoffs 0

co c x 8 0

co

Figure 4.2 TEWI tradeoffs at standard inputs

4.2 Increased Tevap

Due to the low water temperature in the evaporator (Twe.Dut= 6.7 DC) evaporating

temperature was 5.1 °C in the first stage of optimizations. In the previous optimizations, chilled

16

water returned at 12.2 °C as dictated by the ARI standard. The return temperature is well below

15.7 °C, the dewpoint of the bulk air specified in the ARI 21O/240-B air-conditioning rating

condition. In order to continue to allow for dehumidification in all the rooms of the house, the

return temperature was held constant at the specified 12.2 0c. The water outlet temperature was

then increased to 9 °C and water flow rate increased to still achieve the same amount of heat

transfer. In the earlier optimizations, the temperature of the refrigerant exiting the evaporator

could be increased no higher than 12.1 °C due to the specified 7°C superheat (SWEP, 1992). To

allow evaporating temperature to increase, superheat was arbitrarily decreased to 1°C,

simulating the impact of using some kind of liquid overfeed system or a low-side receiver.

The maximum COP with the higher water temperature was 4.38, achieved by evaporating

at 8.7 °C and condensing at 33.2 °C, as shown in Table 4.1. Compressor power decreased 20%

from the original optimization. However, the higher water flow rate increased water pumping

power from 5 to 21 W/kW cooling capacity. Water pressure drop through the evaporator was

decreased slightly by increasing plate width (to 22.2 mm) and water-side plate spacing (to 0.8

mm). The increased plate width required higher refrigerant flow rate to maintain a high heat

transfer coefficient, which in tum increased condenser plate width to decrease condenser

pressure drop. A more detailed analysis of the system is provided in Appendix A.

4.3 Effect of water loop pressure drop In the foregoing analyses, most of the water pumping power was needed to overcome ~P

in indoor and outdoor piping systems, as shown in Table 4.1. Values were selected arbitrarily

and held constant throughout the analysis, only the (relatively small) heat exchanger ~P'S

changed as different geometries were evaluated. The question arises: how sensitive are these

optimal heat exchanger designs to our assumptions about indoor and outdoor pipe lengths and

diameters? To answer this question, we examined an extreme case where there is no pressure

drop in the water lines, and pumping power is only needed to pump water to overcome pressure

drop in the condenser and evaporator. To determine how the minimum-TEWI system would be

designed under this assumption, pressure drop in both liquid lines was set to zero. The first

column of Table 4.2 lists the optimized chiller from Section 3. Next, the water loop pressure

17

a e 'pttma c 1 er WIt Igl er T bl 4 1 O' I h'll . hh' h T

COP

mlot [glkW]

Woomp [W/kW]

Wpumping [W/kW]

Wbtower [W/kW]

W rood fan [W/kW]

WroidlOOP [W/kW]

WhotlOOP [W/kW]

Tav2 [0C]

w [mm]

br [mm] ~ bw [mm] rIl t:: .g L [m] 0 No --U

LlPref [kPa]

LlPw cond [kPa]

LlPwlooo [kPa]

Tav2 [0C]

w [mm]

.... br [mm]

~ bw [mm] !5 L [m] ra- Np > --~

LlPref [kPa]

LlPwevao [kPa] LlPw loop [kPa] ..

- value IS at mmlmum search bound + value is at maximum search bound

Initial optimization (Section 3)

3.96 47

199

46

20

18

5

3

34 1.9

0.4-4.8 3.8

200+ 355 8.6 29

5 19.0 0.4-0.6

0.69 200+ 2.9 9.2 64

evap Min-TEWI (T evao=9°C)

4.38 77

160

63

20

18

21

3

33 2.7 0.4-4.0 5.0

200+ 245 6.6 29

8.7 22.2 0.4-0.8 1.2

200+ 3.3 8.7 166

drops were set to 0 kPa. Finally, COP was re-maximized (within 2 decimal places) and charge

was then minimized. The last column of Table 4.2 shows the results of these new optimizations.

The new minimum-TEWI system decreases total TEWI by only 0.1 kgC02lkW per year

compared to the system just before re-optimization. The reoptimization resulted in heat

exchanger dimensions nearly identical to those in the initial optimization. Therefore, the chiller

that was optimized with the standard inputs has virtually the same TEWI as the chiller that was

optimized without water loop pressure drop. This is an important observation as the water pipe

lengths and diameters were specified arbitrarily for the initial optimization. Therefore, if these

18

..•.

"' "" -,'

values are incorrect, it would only affect the power consumption, but not the optimal strategy for

designing of the heat exchangers.

Table 4 2 Tradeoffs when ~Pw -0 loop-

TEWI [kgC02lkW-year] Indirect TEWI DirectTEWI COP

mtot [glkW]

Wcomp [WlkW]

Ww.COld [WlkW]

Ww •hot [WlkW]

Tav2 [0C]

m [glkW] W [mm]

~ br [mm] '" s:: .g bw [mm] s::

L [m] 0 U

Np --Mlref [kPa]

Mlwcond [kPa]

Tav~ [0C]

m [glkW] W [mm] ...

~ br [mm] 0 bw [mm] g.

L [m] > ~

No --Mlref [kPa]

Mlwevao [kPa] - value is at minimum search bound + value is at maximum search bound

Initial Re-optimized optimization results (Section 3) (MlWlooo= 0)

147 142 144 138 3 4

3.96 4.10 47 56

199 198

5 <0.1

3 <0.1

33.9 33.8 9.4 10.6 1.9 1.9 0.4- 0.4-4.8 5.1 3.8 4.0

200+ 200+ 355 358 8.6 8.0

5.09 5.10 8.3 15.3 19.0 41 0.4- 0.4-0.6 0.4-0.69 0.58 200+ 200+ 2.9 0.5 9.2 7.5

19

5. Conclusions Previous attempts to reduce TEWI have focused on increasing COP while slightly

decreasing refrigerant charge. Since many potential HCFC replacement refrigerants, like

hydrocarbons and ammonia, are either toxic or hazardous, this investigation approached TEWI

reduction through charge minimization by examining a compact chiller loop with secondary

water loops. The following are several key conclusions of this study.

.,' .....

1. Under standard chiller rating operating conditions, a system using commercially available compact brazed heat exchangers (CBEs) requires 61 % less charge than a conventional residential split system. However, due to the lower evaporating temperature necessary to supply water at the ARI standard chiller rating condition, compressor power is 5% higher. It was assumed that the sum of all indoor fan powers could be reduced to half of the blower power required for the conventional split system, due to the absence of ductwork. As a result, total energy consumption is slightly less than the conventional air/air split system, resulting in a decrease of 7% of total TEWI.

2. The minimum-TEWI chiller with flat plate heat exchangers had refrigerant-side plate spacing reduced to 0.4 mm in the evaporator to increase heat transfer coefficient and 200 plates (99 refrigerant circuits) decrease pressure drop. The plates were 59% longer than a conventional CBE (0.7 m vs. 0.4 m) but were 73% narrower (19 mm vs. 71 mm). The minimum-TEWI condenser also had 200 plates and refrigerant-side spacing of 0.4 mm. However, the condenser is not as sensitive to pressure drop, and therefore the plates were 3.7 m long and only 1.9 mm wide.

3. The minimum-TEWI chiller was able to reduce charge 82% compared to conventional split systems. Despite a lower saturation temperature of the compressor discharge pressure (40 DC to 38 DC for the split system and optimal chiller, respectively), compressor power was 0.5% higher. This is because of the difference in rating conditions; chillers require a lower evaporating temperature. However, since the indoor blower power was smaller, due to the absence of ducts, total power was 4% lower than the split system, resulting in 12% less total TEWI.

4. Charge could be reduced by another 28% at the standard operating conditions, at a 7% reduction in COP, compared the minimum-TEWI chiller design. Since TEWI of the optimal chiller is more than 99% due to energy use, total TEWI would increase nearly 7%, but still be less than the conventional split system. This option might be advantageous when using toxic or flammable refrigerants, or for manufacturing reasons because thick walls would be required for an evaporator channel that was 19 mm wide by 0.4 mm high. The additional charge reduction would also decrease the "optimal" condenser length from 3.8 m to 1.4 m.

5. Total TEWI could be decreased an additional 8% compared the "optimal" chiller by increasing evaporating temperature. This could be achieved by simultaneously decreasing superheat (requiring a low-side receiver) and increasing the cold water

20

delivery temperature from 6.7 °C to 9°C (requiring higher mass flow rate and therefore increased pumping power).

6. The optimization strategy is not very sensitive to the water loop assumptions. Using the heat exchanger geometry from the "minimum-TEWI" chiller, eliminating the water pressure drop decreased TEWI 3% by reducing the total pumping power (air and water) 20%. Re-optimizing the heat exchangers had virtually no effect on TEWI.

7. At standard operating conditions the minimum-TEWI chiller reduced TEWI 12% compared to conventional split systems, no improvement over a minimum-TEWI microchannel split system, as shown in Figure 5.1. However, if evaporating temperature were increased, or water pipe lengths decreased (or some combination), then the compact chiller loop appears to offer the most potential for reducing TEWI.

180.-------------------------------------------------.

160 'i:' ! 140

~ 120 Do

~ 100

CJ 80

~ 60

i w 40 I-

20

o

.Indirect Cl Direct

Qi E CD Iii en ~ c: "Iii c: i c: CD a::w :.E ~ Iii :.E ~~ olD

0 '6 ~

0 ~

§~ <oC) § c: § § l-x 0 .£: 0 W 0 w

&l w .- Co <0 t-;- t-;- t-;- Cl ::E UI c: ~ c: ~ c: ;S

~ ~ s ~

Figure 5.1 TEWI comparison for all options

21

· "~'

6. References

Andrade, M.A and C.W. Bullard, "Controlling Indoor Humidity Using Variable-Speed Compressors and Blowers." University of Illinois at Urbana-Champaign, ACRC TR-151, 1999.

American Society of Heating, Refrigeration and Air-conditioning Engineers, "Handbook of Fundamentals." ASH RAE, 1997.

ARI, 1989, Standard for Unitary Air-Conditioning and Air-Source Heat Pump Equipment, ARI-2101240. .

ARI, 1998, Water Chilling Packages Using the Vapor Compression Cycle, ARI-550/590.

Bogaert, R and A Bolcs, "Global Performance of a Prototype Brazed Plate Heat Exchanger in a Large Reynolds Number Range." Experimental Heat Transfer, vol. 8, pp 293-311, 1995.

Buonopane, RA and RA Troupe, "A Study of the Effects of Internal Rib and Channel Geometry in Rectangular Channels." AICHE Journal, vol. 15, no. 4, pp 585-596, 1969.

Cooper A, "Recover More Heat with Plate Heat Exchangers." The Chemical Engineer, pp 280-285, May 1974.

Dittus, F.W., and L.M.K. Boelter, University of California, Berkeley, Publications on Engineering, vol. 2, p. 443, 1930.

Dobson, M.K. and J.C. Chato, "Condensation in Smooth Horizontal Tubes." Journal of Heat Transfer, 120:2, pp. 193-213, 1998.

Focke W.W., J. Zachariades and I. Olivier, "The Effect of the Corrugation Inclination Angle on the Thermohydraulic Performance of Plate Heat Exchangers." International Journal of Heat and Mass Transfer, vol. 28, no. 8, pp. 1469-1479, 1985.

Hall, Scott. Grundfos Pumps Corporation, Fresno, CA Personal communication. July 6,2000.

Haseler, L.E. and D. Butterworth, "Boiling in Compact Heat Exchangers/ Industrial Practice and Problems." Proceedings of Convective Flow Boiling, Banff, Alberta, Canada, pp. 57-70, 1995

Kirkwood, AC. and C.W. Bullard, "Modeling, Design, and Testing of a Microchannel Split­System Air Conditioner." University of Illinois at Urbana-Champaign, ACRC TR-149, 1999.

Marvillet, Ch. "Welded Plate Heat Exchangers as Refrigerants Dry-Ex Evaporators." EUROTHERM Seminar No. 18 (Design and Operation of Heat Exchangers), Germany, pp 255-268, 1992.

Muley, A and RM. Manglik, "Experimental Study of Turbulent Flow Heat Transfer and Pressure Drop in a Plate Heat Exchanger with Chevron Plates." Journal of Heat Transfer, vol. 121, pp. 110-117, February 1999.

22

.. ~-

· .. ~.

Okada, K, M. Ono, T. Tomimura, T. Okuma, H. Kono and S. Ohtani, "Design and Heat Transfer Characteristics of New Plate Heat Exchanger." Heat Transfer-Japanese Research, vol. 1, no. 1, pp. 90-95, January-March 1972.

Panchal, C.B, D.L. Hillis, and A. Thomas, "Convective Boiling of Ammonia and Freon 22 in Plate Heat Exchangers." ASMElJSME Thermal Engineering Joint Conference, Hawaii, ASME Book IOOI58-B, vol. 2, pp. 261-268, 1983.

Rice, C.K "The Effect of Void Fraction Correlation and Heat Flux Assumption on Refrigerant Charge Inventory Predictions." ASH RAE Transactions, vol. 93, part 1, pp. 341-367, 1987.

Roetzel, W., KD. Sarit, and X. Luo, "Measurement of the Heat Transfer Coefficient in Plate Heat Exchangers Using a Temperature Oscillation Technique." International Journal of Heat and Mass Transfer, vol. 37, suppl. 1, pp. 325-331, 1994.

Rortgen, H.G., "Mathematical Modeling of Heat Transfer in Plate Heat Exchangers Using the Finite Element Method." Wiirme-und Stof:fiibertragung, vol 23, pp. 353-364, 1988.

Sand, J.R, S.K Fischer, V.D. Baxter, "Energy and Global Warming Impacts of HFC Refrigerants and Emerging Technologies." A report sponsored by the Alternative Fluorocarbons Environmental Acceptability Study (AFEAS) and the U.S. Department of Energy. Oak Ridge National Laboratory, Oak Ridge, Tennessee. 1997.

Shah, RK and W. W. Focke, "Plate Heat Exchangers and Their Design Theory." Heat Transfer Equipment Design, Hemisphere. Washington, D.C. pp. 227-254,1988.

de Souza, A.L. and M.M. Pimenta, "Prediction of Pressure Drop During Horizontal Two-Phase Flow of Pure and Mixed Refrigerants." ASME Conf. Cavitation and Multiphase Flow, S. Carolina, FED Vol. 210, pp. 161-71, 1995.

Stott, S.L, C.W. Bullard, and W.E. Dunn, "Experimental Analysis of a Minimum-TEWI Air Conditioner Prototype." University of Illinois at Urbana-Champaign, ACRC CR-21, 1999.

SWEP Refrigeration Inc., Compact Brazed Heat Exchangers for Refrigerant Applications: A Technical Handbookfrom SWEP. Bohemia, NY, 1992.

Talik, A.c., L.W. Swanson, L.S. Fletcher, and N.K Anand, "Heat Transfer and Pressure Drop Characteristics of a Plate Heat Exchanger." ASMElJSME Thermal Engineering Conference, vol. 4, pp 321-329, 1995.

Wattelet, J.P., J.C. Chato, A.L. Souza, and B.R Christoffersen, "Evaporative Characteristics of R-12, R-134a, and MP-39 at Low Mass Fluxes," ASH RAE Transactions, vol. 100, no. 1, pp. 603-615, 1994.

Yan, Y.Y. and T.P. Lin, "Evaporation Heat Transfer and Pressure Drop of Refrigerant R-134a in a Plate Heat Exchanger." Journal of Heat Transfer, vol. 121, pp. 118-127, 1999.

23

Yan, Y.Y., H.C. Lio and T.F. Lin, "Condensation Heat Transfer and Pressure Drop of Refrigerant R -134a in a Plate Heat Exchanger." International Journal of Heat and Mass Transfer, vol. 42, pp. 993-1006, 1999.

Yang, W.J. and D. Rundle, "Optimized Thermal Design of Plate and Spiral Type Heat Exchangers." ASME Heat Transfer Equipment, HTD-Vol. 282,1994.

24

, ... '

Appendix A. Baseline systems

A. 1 Baseline residential split system The simulation model was examined first to determine how charge is distributed

throughout a residential alc system (Andrade and Bullard 1999). The system used R410A and

had conventional copper tube/aluminum fin heat exchangers. As indicated in Figure A.l, the

condenser, evaporator and liquid line contain the greatest amounts of charge at the ARI 210/240-

B rating condition. Therefore, charge-reduction strategies focused on maximizing refrigerant­

side surface-to-volume ratios in the heat exchangers, while minimizing lengths of connecting

lines. The 'other' category includes 29 glkW (of cooling capacity) charge in the accumulator,

compressor and refrigerant dissolved in oil, which are assumed to be unchanged for the case of a

chiller.

Figure A.l Alc split system charge distribution [glkW cooling capacity]

The conventional alc split system operated with evaporating and condensing temperatures

of 9° and 39°C, respectively. Total system energy use was calculated as follows, to facilitate

comparison with other alternatives. Condenser fan power was measured, and blower power was

set to the default value (365 W /1000 cfm) associated with the standard test procedure. The

compressor isentropic efficiency was 0.7 at this rating condition, so the same value was assumed

to apply to other systems (chillers) operating at their rating conditions.

25

c SPJIt sys em operatmg con 1 10 Table A.1 N l' t d't" ns at design point

variable value

qevap 10.6 kW

W comp 2051 W

Wblower 438 W

Wfan 196 W

Tevao 9°C

Tcond 39°C

~Tsup 5.6°C

~Tsub 8.7°C

A.2. Baseline chillers A.2.1 Geometry of commercially-available plate heat exchangers

Typical compact brazed plate heat exchangers (eBE) have chevron corrugations stamped

into the plates as shown in Figure A.2. For ease of manufacturing, many plates of the same

imprint design are stacked on top of one another creating many channels of the same width and

corrugation depth. While exact dimensions vary by manufacturer and model, most have w:b

ratios greater than 40, so hydraulic diameter approaches twice the corrugation depth (Dh,plate=

2·b).

Sec A-A /3=0°

Sec A-A /3=90°

~ ~

Figure A.2 Typical brazed plate heat exchanger

26

A.2.2 Correlation selection for plate heat exchangers

One of the major tasks of creating a system simulation model was to determine how to

model the plate heat exchangers. There is much published literature available for liquid-liquid

heat transfer in brazed plate heat exchangers (CBEs), but the openly available correlations for

condensation and evaporation is very limited. A computer program created by SWEP (1996),

simulating their actual CBEs, was run multiple times to provide a baseline to help select which

correlation to use.

The SWEP program includes many variables such as refrigerant and water Reynolds

numbers, film coefficients, pressure drops and property data. However, not all the parameters in

the heat transfer and pressure drop correlations are provided so they had to be estimated using a

"data set" created by running the program over a wide range of heat exchanger operating

conditions. The SWEP calculation procedure determines Re as

Re = mchannel ·2 I-lbulk • w

(Al)

The SWEP program reports Reynolds number, mass flowrate and viscosity. The

refrigerant-side Reynolds number is based on J.1v. Therefore, from each of the program runs it

was possible to use Eq. Al to determine the internal plate width (w). These numbers were then

averaged for each CBE simulated, including both water and refrigerant sides, with results

provided in Table A.2. The average values are all within 2mm the value listed for the external

plate width as provided on the SWEP dimension sheet.

The plate pressing depth (b) is required for all correlations, as the hydraulic diameter is

defined as twice the pressing depth (Dh=2·b). The value of b for each CBE is not explicitly

provided by SWEP so it must be calculated from other variables. The plate corrugations are

sinusoidal in shape, thus the pressing depth is the amplitude of the sine wave. Since the average

value of a sine wave is its amplitude, a sinusoidal channel of amplitude b would have the same

volume as two flat plates (of the same width and length) separated by a distance b, as indicated

in Figure A.3. This allows for the calculation of b to be determined by Eq. A2 since all other

variables are now known (Vol. and L from SWEP dimension sheet, w from Eq AI). The

average value of b for each geometry is provided in Table A2.

27

Vol channel = w· b· L (A. 2)

To check the results of the calculation of plate spacing, Eq. B.3 was used to calculate

channel velocity. The SWEP program output includes both refrigerant and water channel

velocities, rounded to one decimal place. Figures A.4 and A.5 show how the calculated values

compare to the SWEP values for the refrigerant and water-side velocities. On each graph, the

two lines indicate the bounds of where the calculated values should lie to fall within the rounding

to one decimal place.

mchannel = p . VChannel • W • b

~ ==> ---=-b.=X __ _ ~

Figure A.3 Plate spacing

a e PJ a e geomerry T bl A 2 SWEP Itt

w [m] b [mm] L [m] Vol. [cm3]

calculated Eq. A.l Eq.A.2

dimension dimension by

B15

B25

B45

.!.!

0.071

0.115

0.242

2

1.8

1.6

1.4

o 615

C 625

A 645

3 1.2 >

1

0.8

0.6

0.4

0.2

1.65

1.75

1.69

~ i

sheet

0.432

0.479

0.559

li C

oAC

o~

o~~~~~~~~~~~~

o 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2

Vswep

sheet

51.0

96.3

186.9

Figure A.4 Refrigerant-side velocity comparison

28

(A.3)

.. ~.

0.6

o 615

0.5 D 625

l>. 645

0.4

u

>B 0.3

0.2 .M---'rounding bounds

0.1

0.1 0.2 0.3 0.4 0.5 0.6

VSwep

Figure A.5 Water-side velocity comparison

At lower velocities, the calculated values match reasonably well to the SWEP data within

the one decimal place roundoff. At higher velocities Eq. A.3 tends to overpredict the SWEP

velocity. This most likely indicates that the average plate spacing is slightly greater than the

value obtained from Eq. A.2. Therefore, either there is a problem with the assumption of using

an average value of plate spacing for Eq. A.3, or the actual length of the channel is less than the

port-to-port value reported on the SWEP dimension sheet. However since the differences in

velocity are slight, the correlation should still closely match the SWEP data. Since most of the

heat transfer and pressure drop correlations are in the forms of equations A.4 and A.5, if there are

several good candidates, the one chosen should slightly overpredict h and ~P to account for the

actual pressing depth being larger than the calculated value.

A. 2. 2. 1 Single-phase correlations

A.2.2.1.1 Heat transfer Twelve different correlations were tested for each of the geometries and compared to

(A.4)

(A.5)

values from the SWEP program. Table A.3 shows the geometry and testing range of the twelve

29

correlations. Figure A.6 compares the 12 candidate correlations, using them to predict

performance of the B15 CBE parameter values from Table A.2. The procedure was repeated for

the other CBEs, with only slight differences in h, indicating that any slight difference between

actual and calculated plate spacing should not affect correlation selection. The dashed lines

indicate that the correlation has been extrapolated outside the Reynolds number range reported in

the correlation.

12000

10000

¥ (\Ie 8000

~ 6000

~

4000

2000

-{]- hS&T

--1:r hsogaert

-* heooper

~hFocke

~hMarriot

--¢-hMuley

-e-hOkada

_ .• - hRoetzel

-.-hRortgen

o Swep (all PHEs) -H-~alik

--- extrapolated ~hYan

outside Re.range -il-hY&R

o~~~~--~~~~--~~~~--~~~

o 200 400 600 800 1000 1200 1400

Rew

Figure A.6 Single phase heat transfer correlations

The correlation most closely matching the SWEP data is the Buonopane and Troupe

(B&T), however the correlation was developed for Re>3000. Therefore, of the correlations

within the proper Re range, the Marriott correlation (reported in Shah and Focke, 1988) is the

one that best corresponds to the SWEP data set and is provided in Eq A.6.

{0.729 Rel!3 Pr l/3

Nu . = Marnott 0.380 Re2l3 Pr l!3

Re ::; 7

Re>7

30

(A.6)

a e orre atlon range T bl A 3 C I'

Correlation

SWEPdata

Buonopane and Troupe (B&T)

Bogaert

Cooper

Focke

Marriott (from Shah and Focke)

Muley

Okada

Roetzel

Rortgen

Talik

Yan and Lin

Yang and Rundle (Y&R)

NIP: not provIded N/C: no correlation

geometry

Corrugated chevron plate

Triangular herringbone plate

Corrugated chevron plate (13=68°)

half corrugated plate

Corrugated chevron plate (8:-60°) Corrugated chevron plate (13=60°)

Corrugated chevron plate (13=60°) Corrugated chevron plate (8=60°) Corrugated chevron plate (13=70°)

plate (details not provided)

Corrugated chevron plate (13=60°)

Corrugated chevron plate (13=60°)

Corrugated plate

A2.2.1.2 Pressure drop

w [m] b

[mm]

varies varies

NIP NIP

0.113 2.0

NIP 2.5

NIP 5.0

0.354 2.9

0.163 2.5

0.100 8.5

0.071 2.0

0.260 3.6

0.346 2.3

0.120 2.9

0.163 3.2

L [m] Re range

for hand M>

varies Re < 1350

NIP 3000 < Re < 30,000

0.236 h:all M>: Re< 10

NIP NIP

NIP h: 20 < Re < 16,000 M>: 90 < Re < 16.000

0.904 all

0.392 600 < Re < 10,000

0.358 h: 500 < Re < 10,000

M>: N/C

0.177 h: 400 < Re < 2,000

M>: N/C

NIP h: NIP

M>: NIC

0.946 1500 < Re < 6000

0.450 h: 250 < Re < 2250

M>: N/C

0.406 Re>400

Some of the sources that provided heat transfer correlations did not include pressure drop

correlations too. Therefore, there are only 8 options to choose from, instead of 12. The above

procedure was repeated to compare correlation pressure drops and again there was no

appreciable difference in the values when simulating the various geometries. Therefore, Figure

A7 shows a comparison of all values calculated by the SWEP program to obtained using the

correlations when simulating the B15 geometry. Dashed lines indicate when the correlation has

been extrapolated outside the Reynolds number range used in its development. The Focke

correlation most closely matches the SWEP data and therefore is selected to be used in the

charge optimization program (Equations A7 and A8).

31

35

30

25

Ii D.. ~ 20 ~

D.. <l

15

10

5

o Swep (all PHEs)

._-- extrapolated

outside Re range

/ /

/

I

Ii /

Jioa / 0

//

A

I I

I I

I

p. /

I I

" }. -M- ~P cooper

"""*'" ~P Marriot

-e- ~PTalik

",/ e---e ~£1~~~i=f;~~:~:;-:;e1:-=::;,:=~.e!.~--=---~e~-~-....I--=e:"'--..J..-_---1.._,--J -.-~P Y &R (off chart)

0 0 200 400 600 800 1 000 1200 1400

Rew

Figure A.7 Single phase pressure drop correlations

A.2.2.2 Evaporation

A.2.2.2.1 Heat transfer

f = {5.03 + 755/Re 26.8 Re·O.209

Re<400

Re~400

There is not much discussion of evaporation in plate heat exchangers in the open

(A7)

(A8)

literature. Making things more difficult is the fact that most of the literature available on

evaporation in eBEs does not actually provide a correlation (Panchal 1983, MarviIIet 1991 and

Haseler 1995). Figure A8 shows a comparison of the SWEP values to the one correlation

available extrapolated into the SWEP data range (Yan and Lin, February, 1999) plotted against

the vapor Reynolds number. While the correlation was developed for R134a, it was applied to

R410A to match the SWEP data set runs. For the calculations, values such as liquid Prandtl

number, boiling number, and densities could be determined from the SWEP output program.

32

These values were used to calculate an integrated average two-phase heat transfer coefficient

from Yan's correlation, developed for vapor Reynolds numbers above 25,000. The evaporation

heat transfer correlation is given in Equations A.9 through A. 13.

9000 open-Swep

closed-Yan 8000 ••

~~ I!.

o t.. ~oD S2' 7000 <fI m.~ /J. t..

N I 00 t.. fIt. ~ .E

t.. Lbt..i~ tlJCbo 0

== 6000 h -...... o Ijj cP ~oA .c:

t.. Co ••• I.c:N IQ o ., -. --5000 .. 4.. 0 .1 o 815

4000 .- o 825

• t.. 845 I-

3000 2000 6000 10000 14000 18000

Revapor

Figure A.8 Evaporation heat transfer correlation

While the correlation does not match very well, especially at lower vapor Reynolds

numbers, the lack of choices forces the selection of this correlation. In the current model, the

vapor Reynolds number is between 4500 and 7000, depending on the number of plates.

(A. 10)

N = 1 926 Pr 113 Bo 0.3 Re 0.5 [(1 - x) + X(ELJO.5] uevap • I eq I Pg

(A.ll)

(A. 12)

33

" ,."

(A. 13)

A.2.2.2.2 Pressure Drop The above procedure was repeated for the pressure drop correlation provided by Yan

(Figure A.9). Again, at low Reynolds numbers there is a very large discrepancy between the

correlation and the SWEP data, especially considering that the SWEP program provides the total

pressure drop, and the Yan correlation is used for the two-phase zone only. However the lack of

options forces the selection of this correlation. However, since heat transfer is underpredicted

and pressure drop is overpredicted by the Yan correlations, the COP of an actual system will

higher than the calculated value, discussed in A.2.3 Typical CBE simulation results. Yan 's

evaporation pressure drop correlation is provided in Equations B.14 through B.16, and is

integrated over the quality range.

.... I'll Q. JIC ..... Q. <I

40r---~--.---~---r--~---,,---r---.

35

30

25

20

15

10

5

open-Swep (~P evap)

closed-Van (~Pfric, 2ph)

...... rI' ~~. -. U

.~ •• II

• • dlto

~~%o oCto%-~

cto

.,. ... "If

-ill -4. [] 0

[]~o " ~

[]

8

o 815

[] 825

to 845

-

o~--~--~--~--~--~----~--~~ 2000 6000 10000 14000 18000

Revapor

Figure A.9 Evaporation pressure drop correlation

L 0 2

LlP =f ---evap,x x Db 2 Px

34

(A. 14)

· ...

fx = !6.947X105 Re~609 [(1- x) + x~I/Pg t.5]

31.21 Re~~.45443[(I - x)+ X~I/pJO.5]

A.2.2.3 Condensation

A.2.2.3.1 Heat transfer

Reeq < 6000

Reeq ~ 6000

(A15)

(A16)

There is even less literature available for condensation than for evaporation. Fortunately,

Yan, Lio and Lin studied condensation of R134a in CBEs (1999). The analysis from above was

repeated for condensation heat transfer of R410A with the results shown in Figure A 10. The

scale is smaller than for the evaporation comparison, so while it may appear that the correlation

does not match as well as, it is actually better for condensation. This correlation is provided in

Equations A17 and A18.

4000r-r-~~'-~~~u~~~~~~~r-r-~~ open-Swep 0 0 0

3500

3000

1500

closed-Van B DO 0 0

o 0 0

DO BOo

o

~oBo 0

o o

•• ~o .: •• .. .". y ...

• • • ••

o 815 o 825 l1 845

1000 2000 3000 4000 5000 6000 7000 8000

Rev

Figure A10 Condensation heat transfer correlation

35

h = f NUeondkl d eond D x

h

(A. 17)

(A. 18)

A.2.2.3.2 Pressure drop Figure A.II shows the correlation comparison for condensation pressure drop. This

correlation matches the SWEP data much better than did the evaporation correlation, and is

provided in Equations A.19 and A.21, and is integrated over the full quality range.

0.3 ~

open-Swep closed-Yan

0.25

0.2 0 o 0 • I • ! ~ 0.15 • d • n • 8

0.1 OOO~"OO , ~

fi • •• o 815 c;; .,. 0.05 , o 825 • /'. t. 845

0 0 1000 2000 3000 4000 5000 6000 7000 8000

Rev

Figure A.II Condensation pressure drop correlation

L G2

~Peond,x = feond ---,x D 2

h Px

( JO.8

f = 94 75 Re-O.5 BoO.5 Peond Re-O.0467 eond,x . 1 P . eq

ent

" Bo=-q-G· i fg

36

(A. 19)

(A. 20)

(A.21)

"~'

A.2.3 Typical CBE simulation results

To provide a basis for comparison with existing chillers, the model was adapted to

simulate a system characterized by the design variables and operating assumptions listed in

Tables B.l and B.2. Then the heat exchanger geometry was modified to match a typical eBE

(SWEP B15) for both the condenser and evaporator. To model the heat exchangers, correlations

were chosen as described in Section A.2.2.

Typical eBEs offer great flexibility by allowing the designer to select the number of

plates for the specific application. Most typical designs have between 10 and 80 plates, with the

maximum around 200. Analysis of eBEs examined multiple combinations of plates. Systems

with 40 plates in both the evaporator and condenser, as well as 60 in each are presented here.

The system with 40 plates in each had 79 glkW and a eop of 3.69 (although it is probably

higher due to the underprediction of hand overprediction of M>cond as discussed in Section

A.2.2). The compressor consumed 2266 W by condensing at 38°e and evaporating at 5°e.

Each heat exchanger area was 1.2 m2, compared to 1.6 m2 and 1.1 m2 for the conventional split

system condenser and evaporator respectively.

In order to increase eop, the number of plates for each heat exchanger was increased to

60. This system increased charge to 100 glkW and eop to 3.82 by reducing compressor power

to 2196 Wand decreasing water pumping power for the hot and cold loops by at least 10 W

each. Table A.4 compares the two eBE simulations to the conventional split system design.

The biggest difference between the split system and eBE system operation is the

evaporating temperature. The refrigerant-air heat copper tube/aluminum fin evaporator in the

split system evaporates at 9 °e, while the refrigerant-water compact corrugated brazed plate

evaporator evaporates around 5 °e in order to cool every room in the house. Despite the higher

energy consumption for the 60 plate eBE system, total TEWI is slightly lower due to the 61 %

reduction in charge. Figures B.ll through B.13 compare the split system to the two eBE

systems.

37

....

. "~.

300 • Compressor [JBlower • Cond. Fan [JCold Loop • Hot Loop

250

'>: -"1200

B ~15O

III ;= ..... ... ; 100 0 a.

50

0

Com.entional split 60x60 Plate CBE 4Ox40 Plate CBE system

Figure A.12 Split system and CBE power

300 mCondenser [J E ISporator • Liquid Line [J Suction Line • Discharge Line • Other

250

200

{150 ..... E

100

50

0

Conventional split 60x60 Plate CBE 40x40 Plate CBE system

Figure A. 13 Split system and CBE charge distribution

38

a e ipllt syste T bI A 4 S r m1CBE d I mo e companson

ale split system CBE CBE

(40x40 plates) (60x60 plates) TEWI [kgC02/year ]

Indirect TEWI Direct TEWI COP mtot [glkW]

Wcomp [W/kW]

Wblower [W/kW]

Wfan [W/kW]

WW,COld [W/kW]

Ww.h01 [W/kW]

Tavg [0C]

AHT [m2]

mass [glkW]

D [mm]

w [mm] ... br [mm] <!) <Il

bw [mm] s:: <!)

"0 L [m] s:: 0 u No --

# ref circuits

~ref [kPa]

~wcond [kPa]

~wlooo [kPa] LMTD [0C]

Tavg [0C]

AHT [m2]

mass [glkW]

D [mm] w [mm]

... br [mm] 0 .... "" bw [mm] ... 0 0.. L [m] "" ;> ~ No --

# ref circuits

~ [kPa]

~wevao [kPa]

~wloop [kPa] LMTD [0C]

.. - value IS at minImum search bound + value is at maximum search bound

168 159 156 150 154 149 18 5 7

3.77 3.69 3.82 258 79 100

198 215 208

40 20 20

18 18 18

-- 6 5

-- 5 4

39 38 37 1.6 1.2 1.8 144 30 43 9.1 3.3 3.3 -- 71.4 71.4 -- 1.6 1.6 -- 1.6 1.6

37.1 0.43 0.43

-- 40 60 1.5 19 29

104 3.6 2 -- 25 12 -- 29 29

5.6 6.0 5.5

9 5 5.2

1.6 1.2 1.8 57 19 27

9.2 3.3 3.3

-- 71.4 71.4 -- 1.6 1.6

-- 1.6 1.6 6.3 0.43 0.43 -- 40 60 6 19 29

5.5 14.1 9.8 -- 25 11 -- 64 64

11.0 3.6 3.4

39

180,--------------------------------------,

160

'i:' 140

m ~ 120 CI) Q.

~ 100

(.) 80

~ ...... 60 3: UJ I- 40

20

o Conl.entional split 60x60 Plate CBE 40x40 Plate CBE

system

Figure A.14 Split system and TEWI comparison

40

Appendix B. Details of ideal chiller optimization

B. 1 Model development B.1.1 Design operating conditions

The model simulated a system with 10.6 W of cooling capacity while operating at the

ARI 550/590 standard test condition for water temperatures and flowrates (Table B.l). Compact

brazed heat exchanger (CBE) manufacturers recommend 6-8 °C of superheat to minimize

adverse effect of maldistribution on TXV operation (SWEP 1992). Therefore, in the

optimizations, superheat was specified as 7°C. To minimize the amount of liquid in the

condenser while ensuring full condensation, the amount of subcooling after the liquid line was

set equal to 2 °C at this standard rating condition.

Tabl BID . e estgn operatmg con d' 'ons ttl

variable value

qevap 10.6 kW

TWe•out 6.7°C

TWc.in 29.4 °C

"w.e 1.73 m3/hr

"we 2.17 m3/hr

dT,up 7°C

dT,ub 2°C

Tamb 27°C

B.1.2 Assumed model inputs

Since a compact water chiller used for home air conditioning would require secondary

loops, the fan power required for the each loop was considered in the COP calculation. It was

assumed that the required air flow rates would be the same as those of the traditional 10.6 W

split system (Table B.2). Due to the absence of ductwork, however, the air side pressure drops

would be lower, so the fan power requirements were assumed to identical outdoors, but indoors

were halved. Sensitivity analysis also examined the optimal system when blower power was

equal to the split system's (40 W/kW). This did not affect the geometry of the optimal heat

exchangers, only the total energy consumption, which affected COP and TEWI. Therefore, all

results presented are for the condition where blower power was 20 W/kW.

41

"~'

The additional water pumping power was calculated by Equation B.l, and assuming

TJpump= 0.60 (Hall 2000). The water-side pressure drop included the pressure drop across the heat

exchangers and the remainder of the water loop. It was assumed the cold water loop would be at

least 100 meters to distribute the chilled water to every room in the house. To account for the

pressure drop across the individual heat exchangers the entire loop was modeled as 25.4 mm ID

pipe 150 meters long. The hot water loop can be much shorter than the cold water loop, however

there would be water-side pressure drop across the air-water heat exchanger outside. Therefore,

to account for the tubing and heat exchanger, the hot water loop was simulated as 50 m long 25.4

mm ID pipe.

V(dP w + dPlOOP ) Wpump = ------'--

TJpump

(B.l)

To calculate compressor power, an isentropic compressor efficiency of 0.7 was assumed

for all cases, the same value calculated by Andrade for the ale split system at its standard test

condition. To calculate the heat rejected from the compressor, VA was set to 15.8 W/K. This

value was taken from Andrade, for the same 10.6 W compressor with R410A used in the

conventional split system.

T bl B 2 M d I . t a e o e mpu s variable value

Wrru].c 18 W/kW

"'blower,e 20 W/kW

11 pump 0.6

l1s,comp 0.7

UA"omp 15.8 W/K

Lsuction 0.5 m

Ldischarge 0.5 m

Lliquid 0.2 m

Dsuction 10.7 mm

Ddischarge 12.7 mm

Dliquid 3.0 mm

Lloop.cold 150 m

Lloop,hot 50 m

Dloop.h&c 0.025 m

42

It should be noted that the alc split system compressor utilized 198 W/kW, plus 58 W/kW

for fan and blower, for a total power of 256 W/kW. In contrast, the chiller will use 20 W/kW

less for the blower, but it will need about 8-9 W/kW for water pumping. Since the standard

design conditions for a chiller will cause its compressor to operate at different suction and

discharge pressures than the conventional split system. The objective of the current investigation

is to determine chiller heat exchanger geometry to decrease total power and charge to decrease

TEWI.

Figure B.l shows one possible layout of the refrigerant loop. To reduce system charge,

connecting line lengths should be minimized and were estimated accordingly. The values shown

in Figure B.l seemed reasonable. The compressor suction and discharge lines contain only

vapor and are assumed to be quite short (0.5m each) but longer tubes would have very little

impact on charge. When standard diameter tubes are assumed, the pressure drop in each line is

around lkPa, which is negligible compared to 355 kPa for the condenser and 3 kPa for the

evaporator. Since pressure drops are negligible, the diameters of both vapor lines were

arbitrarily set to the same values as found in the alc split system (10.7 and 12.7 mm respectively

for the suction and discharge lines). There is more charge in the liquid line then either vapor

line, however, liquid line diameter minimally affects the optimal heat exchanger geometry.

Therefore, liquid line diameter was decreased to 3.0 mm to reduce the internal volume.

~,COld Ww,hot

Evaporator Condenser coil

Figure B.l Chiller loop layout (10.6 kW unit)

43

B.1.3 Search variables

Table B.3 lists the condenser and evaporator parameters that were allowed to vary during

the search for minimum-charge configurations. Commercially available brazed plate heat

exchangers have plate spacings (b) between 1.5 and 3 mm. However, microchannel heat

exchangers have channel sizes of 0.4 mm or less, implying that it could conceivably be possible

to achieve plate spacings of similar magnitude. Therefore, refrigerant and water-side plate

spacings varied independently, with lower limits set at 0.4 mm. The lower limit for plate width

(w) was set to 0.4 mm as well, which would then create square microchannel ports.

There is a wide range of plate lengths (L) available commercially, with the shortest being

110 mm. To allow for even shorter plates, the lower limit was set to 50 mm. At least 4 plates

are necessary for plate heat exchangers (allowing for one refrigerant channel and two water

channels) but many current designs use 10 to 80 plates. Again, to increase the search range, the

maximum number of plates (Np) was limited to 200, corresponding to 99 refrigerant channels

and 100 water channels.

Table B.3 Search variable constraints lower bound upper bound

search standard variable standard

search CBEs CBEs

0.4 1.4 br [mm] 2.9 --0.4 1.4 bw [mm] 2.9 --0.4 71.4 w [mm] 350 --

50.0 110 L [mm] 900 --4 10 Np 80 200

B.1.4 Model correlations

The heat exchangers were modeled as having many parallel channels of alternating

refrigerant and water as shown in Figure B.2. As geometry was allowed to vary considerably, it

became obvious that the optimally designed heat exchangers had geometries lying well outside

the applicable range of typical heat transfer and pressure drop correlations for chevron plate (See

Appendix B). Therefore, the heat exchangers were modeled simply as smooth flat plates using

the Dittus-Boelter (1940) correlation for single-phase heat transfer, and a Darcy friction factor

for pressure drop in the single-phase regions (ASHRAE, 1997). Correlations from Wattelet et al.

44

'.~.

(1994) and Dobson et at. (1994) were used for evaporation and condensation heat transfer,

respectively, and the de Souza et al (1995) correlation calculated two-phase pressure drop. All

of these correlations were developed for flow in smooth tubes, and applied to rectangular

channels using the hydraulic diameter, calculated according to Equation A.2. The optimizations

had heat flux and mass flux values within the range of the correlations and are only extrapolated

on diameter.

2·w·b Dh =--­

w+b

1E---w--~

Figure B.2 Heat exchanger layout for current investigation

B.2 Chiller optimization

(A.2)

The alc split system has refrigerant-air heat exchangers allowing for evaporating and

condensing temperatures around 9 and 39 °e, respectively. Air exiting the evaporator then is

routed throughout the ductwork of the house, requiring high blower power (40 W IkW). The

current investigation has compact refrigerant-water heat exchangers with cold water pumped

throughout the house and passing through several water-air heat exchangers (one in each room).

The total length of the chilled water loop was assumed to be 150 m and was considered in the

water pumping power calculation. It was also assumed that the sum of all the individual fan

powers was half the split system evaporator blower power (20 WIkW). The optimum chiller

45

....

evaporated at 5 DC and condensed at 34 DC. The reduced temperatures resulted in a compressor

power of 199 W/kW, versus 198 W/kW for the split system. However, the additional water

pumping power adds an extra 8 W/kW to the total power, while saving 20 W/kW with the

blower power (Figure B.3). As a result, COP increased from 3.77 to 3.96. Table BA provides a

detailed comparison of the different models.

COP could not be increased above 3.96 because with the specified 7 DC superheat and the

evaporating temperature of 5 DC, the evaporator outlet was 12.1 DC, within 0.1 DC of the cold

water inlet temperature. The average condensing temperature could not be lowered below 34 DC

because the pressure drop and subcooling resulted in a condenser outlet temperature of 29.5 DC,

0.1 DC above the hot water inlet temperature.

300 II!! Compressor [J Blower • Cond. Fan • Cold Loop [J Hot Loop

250

>: ... . ~ 200 Q.

B ~ 150 -CJ

3= ...... ... ~ 100 0 a.

50

0 ConlA3ntional split Min-TEWI chiller Min-TEWI chiller

system (high Tevap)

Figure B.3 Split system and optimum chiller power

One means of reducing total power is to increase the evaporating temperature by

increasing the chilled water outlet temperature. To determine these effects, the model was run

again by holding the return temperature constant at 12.2 DC, and pumping more water to achieve

the same amount of heat transfer while having an outlet temperature of 9 DC instead of 6.7 DC.

The maximum COP with the decreased water temperature glide was 4.38, instead of 3.96

for the initial optimizations. This was accomplished by increasing evaporating temperature from

46

· .,'

5.0 °C to 8.7 °C. However, refrigerant mass f10wrate increased slightly and condenser plate

width increased from 1.9 mm to 2.7 mm to decrease pressure drop. The wider plates decreased

heat transfer coefficient and forced the average condensing temperature to decrease to 33.2 °C

while increasing total area to 3.0 mZ to rely less on LMTD and U, and more on A (Table B.4).

The higher evaporating temperature decreases compressor power from 199 to 160 W/kW

(Figure B.3), however the increased water f10wrate in the evaporator increased the water

pumping power from 5 to 21 W/kW. The result is a system using the least energy per year,

while having more than twice as much charge as the optimum systems at the standard operating

conditions. However, as shown in Figure B.4, there are other options for the higher-temperature

water systems that do not decrease power as much as the optimum, but still offer reduced power

compared to the standard-input system.

245

240 Do Optimized chiller

Do ° Tw=9°C

235 Do Do closed-optimized Do open-tradeoffs 230 Do

'l:' Do ~225 ~ 3:: Do ~ 8 " ';:220 0 CI ... 0 ~ 215 0 w 0

210 ~ 0,

205 ° 0

° 200 • 195

0 20 40 60 80 100 charge [gJkW capacity]

Figure B.4 Energy-charge comparison

The optimized chiller contains 47 grams of refrigerant per kW cooling capacity,

compared to 258 glkW for the split system and 77 glkW for the water chiller with increased

water temperature. Figure B.5 compares the charge distribution for the split system to the

optimized chiller.

The direct portion of TEWI (refrigerant leakage) is only 3 kgCOz/kW per year for the

optimized chiller, compared to 18 kgCOz/kW per year for the split system and 5 kgCOz/kW per

year for the higher temperature chiller. Since the optimized chiller consumes a total of 246

47

W IkW versus 256 W for the alc split system, the indirect portion of TEWI (C02 emissions from

electricity generation) was 144 kgCOz/kW per year versus 150 kgC02lkW per year for the alc

system. Since the optimized high temperature water chiller consumes only 222 WlkW, its

indirect portion of TEWI is the lowest, at 130 kgC02lkW per year. Figure B.6 shows the TEWI

comparison for each design.

300

.. Condenser c Evaporator • Liquid Line c Suction Une • Discharge Une • Other

250

200

~ 150 Q ...... E

100

50

0 Com.entional split Min-TEWI chiller Min-TEWI chiller

system (high T ov ap)

Figure B.5 Split sytem and optimized chiller charge distribution

180,-------------------------------,

160

..::" 140 ca cu >-120 b Q.

~ 100

~ 80

~ i 60 w I- 40

20

o

• Indirect c Direct

Conventional split Min-TEWI chiller Min-TEWI chiller system (high T .. ap)

Figure B.6 Split system and optimized chiller TEWI comparison

48

a e o e T bI B 4 M d 1

TEWI [kgC02IkW-year] Indirect TEWI Direct TEWI COP mtot [glkW]

Wcomp [WIkW]

Vvblower [WIkW]

Vvran [WIkW]

VvW,COld [WIkW]

Wwhot [W/kW]

Tavg [DC]

AHT [m2]

mass [glkW] D [mm]

w [mm]

t> br [mm] '" bw [mm] s:: CI)

"0 L [m] s:: 0

U Np --# ref circuits

LlPref [kPa]

LlPwcond [kPa]

LlPw 1000 [kPa] LMTD [DC]

Tav2 [DC]

AHT [m2]

mass [glkW] D [mm]

w [mm] .... br [mm] ~ bw [mm] .... 0 ~ L [m] > ~ No --

# ref circuits

LlP ref [kPa]

LlPwevan [kPa] LlP w 1000 [kPa] LMTD [DC]

- value is at minimum search bound + value is at maximum search bound

Conventional split system

168 150 18

3.77 258

198

40

18

----39 1.6 152 9.1 ------

37.1 --1.5 104 ----

5.6

9 1.1 57 9.2 ------

6.3 --6

5.5 ----

11.0

49

, ..... .

companson min-TEWI Optimized

chiller (T evan=9°C) 147 135 144 130 3 5

3.96 4.38 47 77

199 160

20 20

18 18

5 21

3 3

34 33 1.7 3.0 9 18

0.7 0.7 1.9 2.7

0.4- 0.4-4.8 4.0 3.8 5.0

200+ 200+ 99 99

355 245 8.6 6.6 29 29 2.2 1.5

5 8.7 2.6 5.4 8 29

0.8 0.8 19.0 22.2 0.4- 0.4-0.6 0.8

0.69 1.2 200+ 200+

99 99 2.9 3.3 9.2 8.7 64 166 3.6 1.2