minipurge type x / et size 2 manual ml 443 - expo technologies€¦ · expo technologies uk t: +44...
TRANSCRIPT
ML443 | v14 04-Dec-19
MiniPurge Type X / ET Size 2 Manual
ML 443
Contents 1. Specification Sheet – MiniPurge Type X Systems 2. Application Suitability 3. Description and Principle of Operation 4. Installation of the System 5. Commissioning 6. Maintenance of the System 7. Fault Finding 8. Approval Documents 9. Glossary
ML443 | v14 Page
1 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Approval / Certification
Europe EN60079-0, EN60079-2 Sira 01ATEX1295X 2813 II 2 (2) G D Ex [pxb] ia IIC T5 Gb Ex [pxb] ia IIIC T100ºC Db Tamb -20ºC +55ºC
IEC IEC60079-0, IEC60079-2 IECEx SIR 07.0027X Ex [pxb] ia IIC T5 Gb Ex [pxb] ia IIIC T100ºC Db Tamb -20ºC +55ºC
Brazil INMETRO - TUV TÜV 12.1462X Ex [pxb] ia IIC T5 Gb Ex [pxb] ia IIIC T100ºC Db -20°C ≤ Ta ≤ +55°C
USA / Canada NFPA 496 FM 1X8A4AE Class I Div 1 Groups A, B, C & D For limitations and conditions of use refer to the applicable certificate at the back of this manual.
MiniPurge Housing
ss = 316L Stainless Steel (NROB finish) Neoprene “Top” Mount Gasket pm = Panel Mount (Side/Front Mount) 316L
Stainless Steel (NROB finish)
Presurization Method
CF = Continuous Flow LC = Leakage Compensation
1. Specification Sheet – MiniPurge Type X Systems
Supply Pressure: Must be regulated at inlet Minimum 60 psi / 0.4 MPa / 4 bar Maximum 115 psi / 0.8 MPa / 8 bar Air Quality: Compressed air / Nitrogen to instrument quality Ambient Temperature: -20ºC to + 55ºC Leakage Compensation: Variable up to 9 scfm / 250 Nl/min to compensate for leakage of enclosure Purge Timer: Adjustable between 99 minutes(-0+3 seconds) Flow & Pressure Sensors: CF: One sensor for both “Low Pressure and Flow”: 1” WC / 250 Pa (2.5 mbar) LC: “Low Pressure Sensor” 0.2” WC / 50 Pa (0.5 mbar) “Flow Sensor” 1.13” WC/ 280 Pa / (2.8 mbar) Relief Valve: System: CF LC Model No: RLV36/ss RLV36/FS/ss Opening Pressure: 4” WC / 1 kPa (10 mbar) 4” WC / 1 kPa (10 mbar) Purge Flow Rate: N/A (see Spark Arrestor) 16 scfm / 450 Nl/min Material: 316L Stainless Steel, Spark Arrestor: Stainless Steel mesh, Gasket: Neoprene Spark Arrestor Unit Model No: SAU40 (CF systems only) Purge / Dilution Flow Rate: 8 - 16 scfm / 225 - 450 Nl/min 4 user selectable orifice plates Material: Stainless Steel Bulkhead Pipe Fittings: Air Supply: 1/2” NPT Output: 1/2” NPT Signal: 1/8” NPT Visual Indicators: CF: Alarm / Pressurized (Red / Green) Purge Complete (Black / Yellow) LC: Alarm / Pressurized (Red / Green) Purge Complete (Black / Yellow) Action on “Loss of Pressure”: CF: Action on “Loss of Pressure” = “Alarm & Trip”. Option /AO specifies an “Alarm Only” kit. LC: Action on “Loss of Pressure” = “Alarm & Trip” or “Alarm Only”. LC Model is user selectable.
Size 2 = MiniPurge Purge flow rate 450 Nl /min, 16 scfm
Purge System Type
07 = MiniPurge
Power & Alarm (Signals)
PO = Pneumatic Output “Power” : On Purge Complete = 30 psi / 0.2 MPa / 2 bar Signal “Alarm” : Loss of Pressure = No signal ”Pressurized” = 30 psi / 0.2 MPa / 2 bar Signal PA = Power and Alarm Terminal Box Ex e IIC T5 Gb Power and Alarm Terminal Box Ex e IIC T4 Gb “Power” ; 250 Vac 4 Amp AC15 2PNO – Ex d IIC T6 “Alarm” : 250 Vac 4 Amp AC15 SPCO – Ex d IIC T6 (European and IEC Systems Only)
IS = Intrinsically Safe, Ex i & Ex i circuit “Power” : used with others’ Ex i equipment “Alarm” : Relay / Barrier
ET = Electronic Timer
Model No. (Example): 07 2XLC / ss / ET / PO / WM (Note: Not all codes are applicable)
Options as Required
AO = Alarm Only MO = Manual Override MK = MIU Mounting Kit (PO systems only) WM = Wall Mounting Bars
Page 2
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
2. Application Suitability
MiniPurge Systems are certified for use in Hazardous Areas, where the Hazardous Area is non-mining (i.e. above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model, the systems may be used in IECEx, ATEX Zone 1(21) - Category 2 and NEC 500 Class I, Div 1.
MiniPurge systems may be used for hazards of any gas group. However, apparatus
associated with the MiniPurge system, such as Intrinsically Safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability. This system is designed for use primarily with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the Pressurized Enclosure.
The following materials are used in the construction of MiniPurge systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo for further guidance. Materials of construction:
• Stainless Steel • Aluminium • Acrylic • Polycarbonate
• Mild (carbon) Steel • Nylon • Silicone Rubber • ABS
• Brass • Polyurethane • Neoprene • Glass Filled Polyester
ML443 | v14 Page
3 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
3. Description and Principle of Operation
All Expo Technologies MiniPurge pressurization systems provide: a) a method of pressurizing a Pressurized Enclosure (PE) while at the same time compensating for any leakage, together with b) a method of purging the enclosure, before power is applied, to remove any flammable gas that may have entered the enclosure while it was not pressurized,
c) visual indication of the MiniPurge system status, and d) an output to provide remote indication or control.
The MiniPurge system comprises a number of component units. The units required depend on the type of system selected. These are summarised in Table 1. The general description and function of each is as follows: 3.1 Control Unit (CU) The Control Unit (CU) is the heart of the system. It contains a pneumatic logic circuit specially designed and built to control the functions required for purge and pressurization. For all systems this includes air filtration, pressure and purge flow measurement, electronic purge timing, and local visual indication of Pressurized/Alarm and flow sensed. It also provides the outputs for power and remote alarm control corresponding to the output type selected. 3.2 Relief Valve (RLV)
The Relief Valve unit is fitted to the PE to provide a means of limiting the maximum pressure experienced by the PE during operation. The RLV model number has a suffix giving the diameter of the valve aperture in millimetres e.g. RLV36 (= 36mm bore). The RLV also incorporates a Spark Arrestor to prevent sparks being ejected from the PE into the classified area. In Leakage Compensation systems, the RLV is combined with the flow measurement mechanism.
Figure 1 LC Relief Valve
3.3 Calibrated Outlet Orifice/Spark Arrestor (SAU) Continuous Flow systems incorporate the SAU40. This unit has a range of interchangeable calibrated orifice plates, which are used to measure the flow through the PE. 3.4 The Methods of Pressurizing a) CF - Continuous Flow A Continuous Flow (CF) of protective gas is passed through the PE. Initially this flow is verified and performs the purging phase of the operation. When the purging phase is completed – i.e. the purge time has elapsed- the same flow of protective gas maintains the pressurization of the enclosure. This flow may be required to dilute an internal source of hazardous gas release.
Page 4
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
D.P. HI /
"OR"
GATE
'PURGE
COMPLETE'
VALVE
B
A
PURGE OUTLET TO
ENCLOSURE PRESSURE
TEST POINT (PLUGGED)
IN-LINE RESTRICTOR
LOGIC
GAUGE
PRESSURE
REGULATOR
2 barg
30 psi
D.P. LO /
MINIMUM PRESSURE /
FLOW SENSOR
ALARM INDICATOR 1
RED = ALARM
GREEN = PRESSURIZED
FILTER
t
PURGE FLOW
SENSORTIMER
VALVE
PURGE SUPPLY
AIR OR INERT
GAS
PURGE
INDICATOR 2
YELLOW =
PURGING
Figure 2 Continuous Flow Circuit Diagram
b) LC - Leakage Compensation Initially a high flow of protective gas is passed through the enclosure. This flow is verified and performs the purging phase of the operation. When the purging phase is completed – i.e. the purge time has elapsed - the flow of protective gas is provided via an adjustable valve so that it just compensates for any leakage from the PE in addition to maintaining its pressurization. If leakage is less than 5 l/min then the LCV will be awkward to set. You will find that the RLV spring will cycle open and closed. If this happens contact our service department for advice.
'PURGE
COMPLETE'
VALVE
ENCLOSURE
PRESSURE
TEST POINT
(PLUGGED)
D.P. HI / ENCLOSURE PRESSURE
PURGE OUTLET TO PRESSURIZED ENCLOSURE
PURGE VALVE
PILOT RESTRICTOR
LOGIC GAUGE
PRESSURE
REGULATOR
2 barg
30 psi
"OR"
IN-LINE RESTRICTOR
GATE
PURGE
VALVE
LEAKAGE
COMPENSATION
VALVE
TIMER
VALVE
D.P. LO / RLV CONNECTION
ALARM
INDICATOR 1
RED = ALARM
GREEN =
PRESSURIZED
PURGE
INDICATOR 2
YELLOW =
PURGING
ALARM
& TRIP
SENSOR
MINIMUMPRESSURE
ALARM ONLY (OPTION)
AIR OR INERT
GAS
FILTER
t
PURGE FLOW
SENSOR
ELECTRONIC
TIMER
B
A
Figure 3 Leakage Compensation Circuit Diagram
ML443 | v14 Page
5 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
3.5 Type of Output The functions of the outputs are power control and alarm/pressurized indication. Power control provides a signal to switch the power to the PE. Alarm output provides a passive signal to indicate remotely when the enclosure is not pressurized and an active signal when pressurized. a) PO- Pneumatic Output The power control and pressurized outputs are pneumatic signals, which may be used to operate other devices to provide power switching or alarm indication. The lack of any output signal indicates incomplete purge and alarm. In many instances these outputs may be
connected to the Expo range of MiniPurge Interface Unit s (MIU).
Figure 4 Typical MiniPurge Interface Unit type (MIU/dA)
Figure 5 Pneumatic Output Option
b) IS - Intrinsically Safe Output The power control and alarm outputs are volt free contacts which form part of an Intrinsically Safe (IS) circuit which then provides power control or alarm outputs in a safe (unclassified) area. These contacts must only be connected to IS circuits as the switch contacts are in the hazardous area. In many instances these outputs may be connected to the Expo range of
MiniPurge Interface Units (MIU).
Figure 6 Intrinsically Safe (IS) Option
Page 6
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
c) PA - Power and Alarm
Figure 7 Ex de Power and Alarm (PA) Option
The Terminal Box is increased safety (Ex e) certified and incorporates the terminal connection points for the alarm and interlock switches. All contacts provided are volt free (dry). Cable entry methods (for example conduit or cable glands) must be certified to IECEx, ATEX or INMETRO standards. The main requirement is that IP66 (or better) ingress protection must be provided by use of seals or washers.
ML443 | v14 Page
7 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
4. Installation of the System
This MiniPurge is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.
The MiniPurge system shall be installed in accordance with relevant standards, such as IEC / EN 60079-14, NEC 500, NFPA 496 and any local codes of practice that are in force.
There are up to three components for the MiniPurge system, dependent upon the system type:
System type Control Unit (CU) Relief Valve (RLV)
Spark Arrestor Unit
Leakage Compensation YES YES Integral to RLV
Continuous Flow YES YES YES (SAU40)
Table 1 System Components
4.1 Control Unit (CU)
The MiniPurge system should be installed either directly on or close to the PE. See mounting details. Generally, the most convenient arrangement is to install the CU on the top of the PE.
Must be mounted vertically as shown in MiniPurge Configuration XBR-7TD0-003. The CU can be mounted on the side of the PE using the rear mounting fixings. The piped connections to the PE should be made using metallic tube through suitable bulkhead connections. The CU can be remote mounted using the wall mounting bars (/WM option) and should be installed as close as possible to the PE. It should be installed so that the system indicators and certification labels may be readily observed. 4.2 Relief Valve (RLV) and Spark Arrestor Unit (SAU) To achieve efficient purging the points where air enters and exits the PE should normally be at opposite ends of the PE. These items must be mounted vertically. The RLV or SAU are recommended to be situated at the bottom, or on the side of the enclosure at the bottom, when the CU is top mounted on the enclosure, thus achieving top to bottom purging. The purge air may be piped within the PE to ensure purging of potential dead air spots. It is important that the interior and exterior of the Spark Arrestor is kept clean and debris is not allowed to accumulate which might affect the calibration of the device. In particular the exterior of the Spark Arrestor should not be painted or blocked off in any way. 4.3 Connections to Protective Gas Supply The MiniPurge® system should be connected to a protective gas supply, which is suitable for purging and pressurization. The supply pipe connection to the MiniPurge® must be appropriate for the maximum input flow rate for the application. The air supply must be regulated at a pressure less than the maximum stated inlet pressure. The air supply must be clean, non-flammable and from a non-hazardous location. The air should be of Instrument Air Quality. Although the purge control system will operate with lower air quality, its operational life will be adversely affected. The equipment that is being protected by the MiniPurge® may also suffer because of poor air quality.
Page 8
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
With reference to BS ISO 8573-1: 2010, Instrument Air is typically specified as: Particle Class 1 In each cubic metre of compressed air, the particulate count should not exceed 20,000 particles in the 0.1 to 0.5 micron size range, 400 particles in the 0.5 to 1 micron size range and 10 particles in the 1 to 5 micron size range. Humidity or pressure dew point The dew point, at line pressure, shall be at least 10 °C below the minimum local recorded ambient temperature at the plant site. In no case, should the dew point at line pressure exceed +3 °C. Oil Class 2
In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is a total level for liquid oil, oil aerosol and oil vapour. When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section.
Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe.
Unless a supply shut-off valve has been fitted to the MiniPurge® system, an external shut-off valve with the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow.
The purge air from the MiniPurge® Control Unit should be piped within the pressurized enclosure to ensure purging of potential dead air spots. The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic. 4.4 Purge Air from CU to PE When the CU is mounted directly on the top of the PE, no connection will normally be necessary, as the purge air will discharge into the PE directly. When the CU is not mounted on the top of the PE, or where internal air distribution is necessary a connection should be made from the purge air outlet on the CU (normally ½” NPT Female), via pipe pressure rated at least to the supply pressure, to the PE. This should be kept as short as possible and should be adequately sized to ensure that the full purge flow can be delivered. 4.5 CU to Enclosure Pressure Monitor When the CU is mounted directly on the top of the PE, no connection will normally be necessary, as the enclosure pressure monitor point will sense directly inside the PE. If the CU is not mounted directly on the top of the PE or if there are fans, which may create localised low-pressure areas within the PE, it is necessary to pipe this connection. The connection is made to the enclosure pressure sensor fitting (normally 1/8” NPT Female) on the CU. There is virtually no flow in this circuit, so small bore tube may be used. Expo recommends 6mm O/D stainless steel tube. Make sure that all connections are free of leaks. 4.6 CU to Flow Sensor In Continuous Flow (CF) systems, a Differential Pressure Sensor is combined with the Minimum Pressure Sensor and measures the "DP HI (High) / Enclosure Pressure" within the PE and the
ML443 | v14 Page
9 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
pressure in the monitoring device at the back of the SAU "DP LO (Low) SAU Connection". This connection requires a pipe connection between the CU and the SAU40. In Leakage Compensation (LC) systems a dedicated Purge Flow Sensor measures the differential pressure between the "DP HI (High) / Enclosure Pressure" and the pressure in the monitoring device at the back of the RLV "DP LO (Low) RLV Connection". This connection requires a pipe to connect the CU to the RLV36. 4.7 Power Supplies and their Isolation All power entering the PE shall be provided with a means of isolation. This requirement also applies to any external power sources, which are connected to equipment such as "volt-free" or "dry" contacts within the PE. Printer signal, network cards, etc need isolation. Exception: Power to other apparatus that is already suitable for the hazardous area need not to
be isolated by the MiniPurge system.
In all cases the application and the isolation of the power must be controlled by the MiniPurge system. Refer to Specification Sheet for output options available. 4.8 Adjustments and Settings Purge Time If no specific purge test has been performed on the PE, the volume of the PE must be determined by the manufacturer or user and the necessary purging time calculated based on the purge flow rate specified by the “standard” being used. It is the user's responsibility to verify
or enter this data on the PE and/or MiniPurge system nameplate. Ask Expo if in doubt. The IEC / EN 60079-2 permit 5 volume changes and an example of the calculations is as follows:
If the PE external dimensions indicate an internal volume of 1000 Litres then, 1000 litres enclosure volume x 5 volume changes = 12 minutes purge time
450 litres/minute purge flow rate If the PE is a motor, experience of purge testing shows that it is prudent to multiply the motor internal "free” volume by ten to get the purging volume.
1000 litres enclosure volume x 10 volume changes = 23 minutes purge time 450 litres/minute purge flow rate
The following applies for NFPA 496 standards where 4 complete volume changes are permitted for enclosures except when the PE contains a motor when 10 volume changes are required.
If the PE external dimensions indicate a total volume of 40 cubic foot, then, 40 cubic foot enclosure volume x 4 volume changes = 10 minutes purge time
16 cubic foot/minute purge flow rate, (see above) If the same PE contains a motor, then,
40 cubic foot enclosure volume x 10 volume changes = 25 minutes purge time 16 cubic foot/minute purge flow rate, (see above)
The standard MiniPurge units have an electronic timer system as shown in Figure 8 MiniPurge Timer Selector Switches. The purge time is set by adjusting the Timer Selector Switches so that the time equals or exceeds the required purge time. If the time is set to ‘00’, the purge time will be indefinite.
Figure 8 MiniPurge Timer Selector Switches
Page 10
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
Purge Flow Rate (Orifice Size Selection) – Only for CF Systems The purge flow rate is selected by placing the appropriate orifice plate in the SAU. The purge flow rates given in Table 2 are based on standard setting of the flow sensor of 2.5mbar, 1” WC, 250Pa. For LC systems the purge flow rate is set by the selection of the RLV and is not user adjustable.
Orifice Plate Number
Continuous Flow Rate with 2.5 mbarg, 1” WC, 250 Pa flow sensor set point
N litre/minute SCFM
1 225 8 2 275 10 3 365 13 4 450 16
Table 2 Purge Flow Rates
Action on Loss of Pressurization The action on loss of pressurization is the responsibility of the user. The action on loss of pressurization can be set to ALARMS ONLY (AO), or ALARM AND AUTOMATIC DISCONNECT OF POWER (A&T). For both Leakage Compensation and Continuous Flow systems, the action on loss of pressurization is set by moving the jumper tube (see Figure 9 Action on Loss of Pressurization Jumper Tube). The standard setting is Alarm and Trip where the link is from C to A&T, with a plug in AO. Changing to Alarm Only (AO) is user adjustable by moving the link from C to AO, and plugging A&T.
Figure 9 Action on loss of pressurization jumper tube
The selection for action on loss of pressurization depends on the area of operation and the following guidelines should be followed. The user must make use of this alarm facility in accordance with the local code of practice for "action on pressure or flow failure". Most codes include the following recommendations: Zone 1 Installations: Alarm and automatic disconnect of power. Exception: If the equipment inside the PE is suitable for use in Zone 2, the power trip may be performed manually, (no automatic power trip), if the pressure or flow failure persists for an unacceptable time. Zone 2 Installations: Where automatic timing is preferred, Alarm Only on pressure or flow failure with power being
removed manually by turning off the air supply to the MiniPurge system if the failure persists for an unacceptable time. Class I Division 1 Installations: Alarm and Automatic Trip of Power. Note: NFPA 496 states power to the circuits shall be permitted to be continued for a short period if immediate loss of power would result in a more hazardous condition and if both audible and visual alarms are provided at a constantly attended location.
ML443 | v14 Page
11 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Class I Division 2 Installations: Where automatic timing is preferred, Alarm Only on pressure or flow failure with power being
removed manually by turning off the air supply to the MiniPurge system if the failure persists for an unacceptable time. 4.9 Internal Gas Release If the PE contains an internal source of release of flammable gas or vapour, the procedures for assessment of the release as given in NFPA 496 or IEC / EN 60079-2 should be used. Expo is pleased to provide assistance or consultancy and advice on such matters. The user must verify that the specifications of the Expo system e.g. pressure, continuous flow (dilution) rate and type of protective gas are correct for the specific application. 4.10 Multiple Enclosures More than one PE can be protected by a single system. Where PE’s are connected and purged in "series" e.g. "Daisy Chained", the RLV and when using a CF system, the SAU40 should be fitted on the last enclosure with the Purge Inlet connected to the first enclosure. The bore and length of the pipe or conduit used to interconnect the enclosures is critical and will determine the maximum pressure experienced by the first enclosure in the series. Advice on sizing can be obtained from the Expo sales office but in general terms when using RLV36 or SAU40, the pipe
bore size should not be less than 36mm (1½”).
A common fault of installing small bore pipe leads to over pressurizing of all but the last enclosure. PE’s should not be connected in parallel.
Page 12
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
5. Commissioning
Start by checking that the system has been installed in accordance with this manual.
Disconnect the supply pipe from the inlet to the MiniPurge system and blow it through for at least 10 seconds per meter (3ft) of length to remove any debris or condensation. Connect a temporary pressure gauge or water manometer to
the PE or MiniPurge system pressure test point (Remove the red plug on the low pressure sensor and connect 4mm OD nylon tube).
Figure 20 PE or MiniPurge system pressure test point
Unless a supply shut-off valve has been specially fitted inside the MiniPurge system, it may be advisable to install an external shutoff valve with the same, or larger, thread size as the
MiniPurge CU inlet fitting upstream of the connection. 5.1 Continuous Flow (CF) Systems Open the Flow Control Valve (FCV) until the alarm/pressurized indicator just turns from red to green. Clockwise will reduce the flow and anti-clockwise will increase the airflow. If the FCV is opened fully and the indicator has still not turned green, check the air supply pressure at the inlet to the Control Unit while flow is taking place. It must be above the minimum 4 bar/ 60 psig/ 400kPa specified.
Check that the internal logic gauge reads 2bar /30 psig/200kPa. The electronic timer will start as soon as the ‘alarm/pressurized’ indicator turns from red (alarm) to green (pressurized). Check that the time delay between the indicator flashing yellow and the application of power to the PE is not less than the minimum time required to purge the PE. When the purge time has been completed, the ‘purge complete’ indicator will stop flashing. After the power has been turned on by the CU, the air flow will continue at the same rate to provide dilution as required.
Figure 11 Flow Control Valve (FCV)
ML443 | v14 Page
13 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
5.2 Leakage Compensation Systems (LC)
• Open the Leakage Compensation Valve (LCV) fully, turn anti-clockwise.
• Clockwise will reduce the flow and anti-clockwise will increase the airflow.
• Open the supply regulator SLOWLY and allow the PE pressure to rise until the RLV opens. Check that the RLV opens at or below the figure specified in the documentation.
• RLV tolerance +0, -20% of default setting.
• Repeat the test several times.
• Open the supply regulator to between 4 and 8 barg / 60 and 115 psi / 400 and 800 kPa and the purging flow will start.
• Check that the internal logic gauge reads 2 bar /30 psi / 200 kPa
Figure 12 Leakage Compensation Valve (LCV)
At this time the "alarm/pressurized” indicator should be green and the "purging” indicator should be flashing yellow. If the “purging” indicator remains black the flow through the RLV is below the minimum for which the flow sensor has been calibrated. Check the air supply pressure at the inlet to the Control Unit while purging is taking place. It must be above the minimum specified. The electronic purge timer will start as soon as the "purging" indicator starts flashing yellow. Check that the time delay between the “purging” indicator flashing yellow and the application of power to the PE is not less than the minimum time required purging the PE. Times in excess of the minimum are permitted. If the time is too short, it must be increased accordingly. After the power has been applied via the CU, the purging valve will close and the air flow into the enclosure will be controlled by the LCV. The initial setting of fully open will normally be too high. It should now be adjusted to set the PE pressure and leakage. There are three possible situations:
Air continues to come out through the RLV Spark Arrestor after power has been applied in considerable quantity. The LCV is much too far open, and the air flow is holding the RLV open continuously. Close the LCV slowly. The PE pressure will start to fall as the flow decreases but eventually the RLV will close and the enclosure pressure rise again. At this point the RLV may start to open intermittently as the PE pressure rises to the point where it exceeds the RLV opening pressure. When the RLV opens the pressure will fall quickly to the point where the RLV re-closes and the enclosure pressure starts to rise again. This is entirely normal for this type of RLV.
If the RLV is opening intermittently the LCV is slightly too far open. When the RLV opens, the enclosure pressure falls quickly to the point where the RLV re-closes and the enclosure pressure starts to rise again. This is entirely normal for this type of RLV and shows that it is working correctly. Continue then to close the LCV until the cycling stops and the enclosure pressure starts to fall. Carefully adjust the LCV until the PE pressure is approximately 50% of the RLV opening pressure and stable. This pressure may be around 5 mbarg / 2” WC / 500 Pa and will be the "normal working pressure".
Page 14
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
We recommend that the setting of the minimum pressure sensor be checked at this time. Note the position of the LCV knob. (A pencil mark placed on the knob at "12 O'clock” can be used). Slowly lower the PE pressure by closing the LCV further, counting the number of turns from the "normal working pressure" position. Note the pressure at which the "alarm/pressurized" indicator turns from green to red and check that it is not lower than the figure given in the documentation. Check also the "alarm" electrical contacts. As soon as the "alarm/pressurized" indicator turns red, the system will start to re-purge. If Alarm and Trip function is selected the enclosure power will be switched off. While it is re-purging return the LCV to its "normal working pressure" position so that, at the end of purging, the enclosure pressure should immediately settle down at the correct "normal" pressure.
If, at the end of purging, the PE pressure falls below the minimum pressure sensor setting and the LCV is fully open, the system will start to purge again. This is indicative of excessive leakage from the enclosure. In this case, check the enclosure for leakage, and reduce or eliminate the leaks. This time, at the end of purging, the enclosure should stay pressurized and the RLV action is as in a) or b) above. Proceed as described above.
5.3 Normal operation Turn the air supply on or off to start or stop the system. After this the pressurizing and purging sequence is entirely automatic
ML443 | v14 Page
15 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
6. Maintenance of the System
The maintenance recommended for the system consists of the following items, supplemented by any additional local requirements imposed by the local Code of Practice. Expo recommends that the commissioning tests be repeated at least every six to 24 months dependant on site conditions. In addition, the following checks are also recommended at that time:
• Check the RLV and all Spark Arrestors. Remove all debris & corrosion or replace with a spare.
• Check the condition of the air supply filter element. Clean or replace it as necessary.
At least every two years check the following additional items:
• Apparatus is suitable for the Hazardous Location
• There are no unauthorised modifications
• The air supply must be to the correct quality, refer to section Air Quality
• The interlocks and alarms function correctly
• Approval labels are legible and undamaged
• Adequate spares are carried
• The action on pressure failure is correct
The Intrinsically Safe Battery Pack should be changed at least every three years, and the commissioning tests repeated. After the timing phase has elapsed, the battery may be ‘hot-swapped’ in a hazardous environment without effecting the operation of the MiniPurge Ex px system. Recommended spares ETM-IS31-001 Intrinsically Safe Battery Pack Pressure Sensor calibration If it is decided that the minimum pressure /purge flow sensor needs recalibrating it must be returned to Expo for this service. Filter cleaning If the filter element needs cleaning the filter bowl can be unscrewed and removed. The filter element also unscrews and can then be cleaned in soapy water or replaced. Do not use solvents on any part of the filter assembly.
Page 16
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
7. Fault Finding
If the system does not behave in the manner described above, there is a fault. Some of the more likely faults are dealt with below. If a cure cannot be affected by following the procedure shown below, please call Expo (24 hour answering) or your supplier for further assistance. The system has been designed for ease of fault finding and the many of the components fitted are plug-in or manifold mounted. Check components by substitution only after establishing that such action is necessary. If the system is less than 12 months old, parts under warranty should be returned to Expo for investigation, with a full report of the fault and the system serial number. As with any pneumatic system the greatest enemies are water, oil and dirt in the air supply. For this reason, the air system must always incorporate a dust and water filter. This can be part of the Expo system or can be provided by others. However, dirt can enter from other sources and it is vital therefore that the procedures described in Section 2 is carried out before using the system for the first time or following any disconnection of the pipe-work. Failure to perform this work may cause damage that will not be covered under warranty. Before making the following checks verify that both the main air supply pressure to the purge system & the regulated pressure to the logic are as specified on the system specification sheet. Different flow charts for faulting have been provided for both the CF and LC options.
ML443 | v14 Page
17 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Fault Finding (CF)
Is the PE strong enough?
Is the Pressure / Flow Sensor out of calibration or
faulty?
Pressurized indicator will not turn green or Purging
indicator will not flash yellow
Call Expo
Is the supply pipe to the air inlet as least 12mm I.D?
Is there excessive
leakage from the PE?
Is the air supply pressure incorrect?
No
Check the air supply pressure at the inlet to the MiniPurge is stable between 4 - 8 Barg / 60 - 115 psi
Yes
Replace pipe work
No
Yes
Any significant leakage must be corrected. Check for leaks down the cables or conduit. Ensure leakage does not exceed 250 Nl/min (9 scfm)
Yes
No
Yes
No
The standard requires that the PE is tested to 1.5 times the Relief Valve opening pressure e.g. 15 mbarg for many systems. Has this been done?
No
The basic operation of the Pressure Sensor can be checked by unscrewing the 60mm diameter diaphragm housing and, by using a rubber pad, e.g. an eraser, block the 12mm threaded hole in the top of the valve module. The valve should operate and the indicator turn green. If this is correct, the sensor diaphragm needs recalibrating or replacing.
Yes
Page 18
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
For PO option only Is there pressure at the
power switch output bulkhead and at the power switch? Is the power switch OK?
Is the Purge time correct?
System fails to switch power on after the purge time has
elapsed.
Call Expo
Has the purge time completed
its course?
Is Power available?
No
Yes
Check the small indicator button
on the timer valve. When the valve has timed
out, it should return out when
depressed.
No
Yes
Yes
Check if the external Power Switch contacts close at 1.4 Barg
No
Note the timer setting. Reset the timer to the minimum available purging period and check
the operation on that purge time. Ensure that the purge time is returned to its original setting and checked before putting the system back into service.
No
For PO option only Is the tube to the power switch air
tight?
Ensure fitting nuts are tightened and that the tube is not damaged. Check and repair as necessary.
No
Yes
Yes
Is Power isolator closed?
No
Yes
Yes
Are the fuses or circuit breaker?
OK?
No
ML443 | v14 Page
19 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Is the Pressurized Enclosure
pressure too high?
Is there debris on the RLV disk allowing air to leak from the
valve?
Relief Valve opens
continuously or intermittently.
Call Expo
Remove the RLV cover and clean the valve
disk. If it is necessary to remove the disk and spring from the RLV, draw a line around it with a pencil to allow accurate replacement
before removal, otherwise the opening
pressure may be affected.
The Flow Control Valve (FCV) is too far open.
Adjust the FCV clockwise to reduce the
PE pressure
No
Yes
No
Yes
Page 20
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
Fault Finding (LC)
Is the actual PE pressure below
the setting of the Minimum
Pressure Sensor?
Is the Leakage Compensation
Valve setting too low causing the
MiniPurge to auto-repurge?
System purges correctly but the alarm comes on at the end of purge time and the purging cycle is
repeated.
Call Expo
Increase the PE pressure by turning the Leakage Compensation
Valve anti-clockwise.
Check the PE pressure with a manometer or
gauge.
Yes
No
Yes
No
Yes
ML443 | v14 Page
21 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Is the tube between the RLV tapping and flow sensor air tight?
Is the PE strong enough?
Is the Purge Flow Sensor out of calibration or
faulty?
Purging indicator will not flash "Yellow" during
Purging.
Call Expo
Is the supply pipe to the air inlet as least 12mm I.D?
Is there excessive
leakage from the PE?
Is the air supply pressure incorrect?
No
Check the air supply pressure at the inlet to the MiniPurge is stable between 4 - 8 Barg / 60 - 115 psi
Yes
Replace pipe work
No
Yes
Any significant leakage must be corrected. Check for leaks down the cables or conduit. Ensure leakage does not exceed 250 Nl/min (9 cfm)
Yes
No
No
The standard requires that the PE is tested to 1.5 times the Relief Valve opening pressure e.g. 15 mbarg for many systems. Has this been done?
No
The operation of the Purge Flow Sensor can be checked by carefully removing the insulated female spade crimp terminals* on the underside of the hexagonal sensor. A wire link across them should operate the Electronic Timer and the ‘purging’ indicator flash yellow. If this is correct, the sensor diaphragm needs recalibrating or replacing, if not, replace the I.S. Battery Pack.
Yes
Ensure fitting nuts are tightened and that the tube is not damaged. Check and repair as necessary.
No
Yes
Yes
Page 22
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
For PO option only Is there pressure at the
power switch output bulkhead and at the power switch? Is the power switch OK?
Is the Purge time correct?
System fails to switch power on after the purge time has
elapsed.
Call Expo
Has the purge time completed
its course?
Is Power available?
No
Yes Check the small indicator button on the timer valve. When the valve has timed out, it should return out when depressed.
No
Yes
Yes
Check if the external Power Switch contacts close at 1.4 Barg
No
Note the timer setting. Reset the timer to the minimum available purging period and check the operation on that purge time. Ensure that the purge time is returned to its original setting and checked before putting the system back into service.
No
For PO option only Is the tube to the power switch air
tight?
Ensure fitting nuts are tightened and that the tube is not damaged. Check and repair as necessary.
No
Yes
Yes
Is Power isolator closed?
No
Yes
Yes
Are the fuses or circuit breaker?
OK?
No
ML443 | v14 Page
23 Expo Technologies UK T: +44 (0) 20 8398 8011 E: [email protected]
Expo Technologies US T: +1 (440) 247 5314 E:[email protected]
Expo Technologies China T: +86 532 8906 9858 E: [email protected]
Is the Pressurized Enclosure
pressure too high?
Is there debris on the RLV disk allowing air to leak from the
valve?
Relief Valve opens
continuously or intermittently.
Call Expo
Remove the RLV cover and clean the valve
disk. If it is necessary to remove the disk and spring from the RLV, draw a line around it with a pencil to allow accurate replacement
before removal, otherwise the opening
pressure may be affected.
The Leakage
Compensation Valve (LCV) is too far open.
Adjust the LCV clockwise to reduce the
PE pressure
No
Yes
No
Yes
Page 24
ML443 | v14
Expo Technologies UK T: +44 (0) 20 8398 8011
Expo Technologies US T: +1 (440) 247 5314
Expo Technologies China T: +86 532 8906 9858
8. Approval Documents
Certificates can be found in the accompanying booklet (ML499) or download the certificates at www.expoworldwide.com/downloads.
System Certificate Certificate Number
MiniPurge IECEx Certificate IECEx SIR 07.0027X
ATEX Certificate 01ATEX 1295X
INMETRO/TÜV TÜV 12.1462X
FM Certificate 1X8A4.AE
Electronic Timer IECEx Certificate FME 10.0001X
ATEX Certificate 10 ATEX0003X
For PA Option Only Certificate Certificate Number
Ex e junction box IECEx Certificate IECEx EXV 19.0057X
ATEX Certificate ExVeritas 19 ATEX0542X
Ex d switches IECEx Certificate IECEx EPS 14.0092X
ATEX Certificate EPS 14 ATEX 1 766 X
9. Glossary
Acronym Description
A&T Alarm and Trip
AO Alarm Only
CF Continuous Flow
CU Control Unit
FCV Flow Control Valve
FM Factory Mutual
IS Intrinsically Safe
LC Leakage Compensation
LCV Leakage Compensation Valve
MIU MiniPurge Interface Unit
PA Ex d Power and Alarm Switch Wired to Ex e terminal box
PE Pressurized Enclosure
PO Pneumatic Output
RLV Relief Valve
SAU Spark Arrestor Unit
UL Underwriter Laboratories
Min
iPur
ge
FLA
TNE
SS
TO
BE
LE
SS
TH
AN
0.4
mm
OV
ER
AN
Y 1
00m
m L
EN
GTH
UN
SP
EC
IFIE
DTO
LER
AN
CE
S
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AW
ING
STA
TUS
:A
PP
RO
VE
D:
MO
D. N
o:D
ATE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CTI
ON
DIM
EN
SIO
NS
IN m
m
DO
NO
T S
CA
LE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
ME
R:
SH
EE
T N
o.O
F
SU
RR
EY
TW
16 5
DB
UN
ITE
D K
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht ã
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DE
C P
LAC
E ±
0.5
1 D
EC
PLA
CE
±0.
22
DE
C P
LAC
E ±
0.1
150
[5.9
1"]
102
[4.0
2"]
240 [9.45"]
129
[5.0
8"]
270 [10.63"]MOUNTING BAR HOLES
12
NO
TES
MIN
IPU
RG
E M
UST
BE
MO
UN
TED
WIT
H P
URG
E O
UTL
ET
FITT
ING
IN
VER
TICAL
PLAN
E PO
INTI
NG
DO
WN
.
APP
RO
XIM
ATE
WEI
GH
T: 6
.1 k
g [1
3.3
lb].
EQU
IVALE
NT
IMPE
RIA
L D
IMEN
SIO
NS S
HO
WN
IN
BRACKET
S.
REF
ER T
O D
RG
XSD
-7TD
0-00
1 FO
R M
OU
NTI
NG
DET
AIL
S.
78 [
3.07
"]
90[3
.54"
] LEAKAG
ECO
MPE
NSATI
ON
(LC)
CO
NTI
NU
OU
SFL
OW
(CF)
CO
NTI
NU
OU
SFL
OW
AFT
ERH
IGH
PU
RG
E(C
FHP)
ALA
RM
IND
ICATO
R 1
ALARM
RED
RED
RED
PRESSURIZED
GREEN
GREEN
GREEN
PURG
EIN
DIC
ATO
R 2
PURGING
YELL
OW
YELL
OW
YELL
OW
PURGECOMPLETE
BLAC
K
BLAC
K
BLAC
K
IND
ICATO
RS
27.0
5 [1
.06"
] APP
RO
X.
1. 2. 3. 4.
20 [
0.79
"]
28 [1.10"]
95[3
.74"
]
IS O
PTIO
N:
HO
LE S
UIT
ABLE
FO
RG
LAN
D M
20 O
R 1
/2"
NPT
65 [2.56"]
95 [3.74"]
125 [4.92"]
162 [6.38"]
20 [
0.79
"]
42 [
1.65
"]
42 [
1.65
"]
SYS
TEM
BREA
THER
-D
O N
OT
OBSTR
UCT
POW
ER S
WIT
CH
- P
O O
PTIO
N O
NLY
1/8"
NPT
F
PASSIV
E ALA
RM
/PRES
SU
RIS
ED S
IGN
AL
-PO
OPT
ION
ON
LY1/
8"N
PTF
FILT
ER D
RAIN
1/8"
NPT
F
AIR
SU
PPLY
4-8
MAX b
arg
[60-
115
psi]
1/2"
NPT
F
74 [2.91"]
REM
OVABLE
CO
VER
180
[7.0
9"]
MO
UN
TIN
G B
AR
HO
LES
IND
ICATO
RS
180 [7.09"]
240
[9.4
5"]
290 [11.42"]
6 [0.24"]
PURG
E O
UTL
ET1/
2" N
PTF
ENCLO
SU
RE
PRES
SU
RE
1/8"
NPT
FFL
OW
SW
ITCH
-LC
. O
PTIO
N O
NLY
1/8"
NPT
F
MO
UN
TIN
G B
ARS W
ITH
HO
LES
FOR M
6 O
R 1
/4"
FIXIN
G(S
PECIA
L O
PTIO
N O
NLY
)
M6
EARTH
STU
D(W
ITH
PA O
PTIO
N)
PAO
PTIO
N
31 [1.22"]
8 [0.31"]
PA.
OPT
ION
:CU
STO
MER
TO
SIT
EAN
D D
RIL
L IN
PUT
GLA
ND
HO
LE
Min
iPur
ge
FLA
TNE
SS
TO
BE
LE
SS
TH
AN
0.4
mm
OV
ER
AN
Y 1
00m
m L
EN
GTH
UN
SP
EC
IFIE
DTO
LER
AN
CE
S
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AW
ING
STA
TUS
:A
PP
RO
VE
D:
MO
D. N
o:D
ATE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CTI
ON
DIM
EN
SIO
NS
IN m
m
DO
NO
T S
CA
LE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
ME
R:
SH
EE
T N
o.O
F
SU
RR
EY
TW
16 5
DB
UN
ITE
D K
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht ã
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DE
C P
LAC
E ±
0.5
1 D
EC
PLA
CE
±0.
22
DE
C P
LAC
E ±
0.1
NO
TES
MIN
IPU
RG
E M
UST
BE
MO
UN
TED
WIT
H P
URG
E O
UTL
ET
PIPE
IN
VER
TICAL
PLAN
E PO
INTI
NG
DO
WN
.
APP
RO
XIM
ATE
WEI
GH
T: 6
.1 k
g [1
3.3
lb].
EQU
IVALE
NT
IMPE
RIA
L D
IMEN
SIO
NS S
HO
WN
IN
BRACKET
S.
REF
ER T
O D
RG
XSD
-7TD
0-00
1 FO
R M
OU
NTI
NG
DET
AIL
S.
1. 2. 3.8
INTE
RN
AL
STU
DS
M6
x 15
LO
NG
CU
TOU
T D
ETAIL
65 [2.56"]
95 [3.74"]
162 [6.38"]
240 [9.45"]
90[3
.54"
]
145
[5.7
1"]
42.5 [1.67"]
79.5 [3.13"]
96[3
.78"
]
= 30
0 [1
1.81
"] =
300 [11.81"]
8 H
OLE
S ø
7.5
TO S
UIT
INTE
RN
AL
STU
DS I
NCU
TOU
T D
ETAIL
= =
84[3
.31"
]
45 [
1.77
"]
IND
ICATO
RS -
SEE
TABLE
ON
SH
EET
1
12
FILT
ER D
RAIN
1/8
" N
PTF
AIR
SU
PPLY
4 -
MAX 8
bar
g (6
0 -
115
psi)
1/2"
NPT
F
SYS
TEM
BREA
THER
DO
NO
T O
BSTR
UCT
FLO
W S
WIT
CH
- L
.C.
OPT
ION
ON
LY1/
8" N
PTF
ENCLO
SU
RE
PRES
SU
RE
1/8"
NPT
F
PURG
E O
UTL
ET1/
2" N
PTF
2 CABLE
GLA
ND
HO
LES S
UIT
ABLE
FO
R M
20 O
R 1
/2"
NPT
FO
R C
ON
NEC
TIO
N T
O R
EMO
TE P
A B
OX.
FOR I
.S.
OPT
ION
USE
LOW
ER H
OLE
ON
LY.
MIN
IPU
RG
E SU
PPLI
ED W
ITH
BO
TH H
OLE
S P
LUG
GED
.
= 276 [10.87"] =
= 254 [10.00"] =
= 172 [6.77"] =
= 2
54 [
10.0
0"]
=
= 1
72 [
6.77
"] =
= 2
76 [
10.8
7"]
=
PAN
EL M
OU
NTI
NG
OPT
ION
PASSIV
E ALA
RM
/PRES
SU
RIZ
ED S
IGN
AL
1/8"
NPT
F
POW
ER I
NTE
RLO
CK S
IGN
AL
1/8"
NPT
F
20 [
0.79
"]
FLA
TNE
SS
TO
BE
LE
SS
TH
AN
0.4
mm
OV
ER
AN
Y 1
00m
m L
EN
GTH
UN
SP
EC
IFIE
DTO
LER
AN
CE
S
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AW
ING
STA
TUS
:A
PP
RO
VE
D:
MO
D. N
o:D
ATE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CTI
ON
DIM
EN
SIO
NS
IN m
m
DO
NO
T S
CA
LE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
ME
R:
SH
EE
T N
o.O
F
SU
RR
EY
TW
16 5
DB
UN
ITE
D K
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht ã
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DE
C P
LAC
E ±
0.5
1 D
EC
PLA
CE
±0.
22
DE
C P
LAC
E ±
0.1
15
2614
19
22161
213
187
MIN
IMU
M P
RES
SU
RE
SEN
SO
R
"OR"
GATE
LEAKAG
E CO
MPE
NSATI
ON
VALV
E
PURG
E BO
OST
VALV
E
PLU
G 4
mm
(EN
CLO
SU
RE
PRES
SU
RE
TEST
POIN
T)
PURG
E CO
MPL
ETE
VALV
E
LOG
IC A
IR S
UPP
LY R
EGU
LATO
R
ELEC
TRO
NIC
TIM
ER
BLA
CK C
OLL
AR (
PLU
GG
ED)
IND
ICATO
R,
"ALA
RM
/PRES
SU
RIZ
ED"
IND
ICATO
R,
"PU
RG
ING
"
PURG
E FL
OW
SEN
SO
R
2 9 127 83
GAU
GE,
LO
GIC
AIR
SU
PPLY
1
MAIN
AIR
SU
PPLY
FIL
TER,
AU
TOM
ATI
C D
RAIN
15
TIM
ER V
ALV
E
19 22 2616 17 1814
ALA
RM
ON
LY P
USH
-IN
FIT
TIN
G
ALA
RM
AN
D T
RIP
PU
SH
-IN
FIT
TIN
G
PURG
E TI
ME
SEL
ECTO
R S
WIT
CH
ES
"ACTI
ON
ON
ALA
RM
" O
PTIO
N P
IPE
34 763533
123
3335
34
ENCLO
SU
RE
PRES
SU
RE
TEST
POIN
T
PUSH
-IN
PLU
G
ALA
RM
ON
LYALA
RM
AN
D T
RIP
VIE
W O
F D
OO
R F
RO
M I
NSID
E
AO
CA&
TA&
TAO
C
LC L
EAKAG
E C
OM
PEN
SATI
ON
PO
OPT
ION
SH
OW
N (
ITEM
S I
N D
OTT
EDREM
OVED
FO
R C
F AN
D I
TEM
13
REP
LACED
BY
TIM
ER S
WIT
CH
)
26
17
INTE
RN
AL
CO
MPO
NEN
TS
I.S.
BATT
ERY
PACK
13
76
8
FLA
TNE
SS
TO
BE
LE
SS
TH
AN
0.4
mm
OV
ER
AN
Y 1
00m
m L
EN
GTH
UN
SP
EC
IFIE
DTO
LER
AN
CE
S
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AW
ING
STA
TUS
:A
PP
RO
VE
D:
MO
D. N
o:D
ATE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CTI
ON
DIM
EN
SIO
NS
IN m
m
DO
NO
T S
CA
LE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
ME
R:
SH
EE
T N
o.O
F
SU
RR
EY
TW
16 5
DB
UN
ITE
D K
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht ã
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DE
C P
LAC
E ±
0.5
1 D
EC
PLA
CE
±0.
22
DE
C P
LAC
E ±
0.1 PA
OPT
ION
IS O
PTIO
NPO
OPT
ION
Ex d
SW
ITCH
WIR
ED T
O A
LARM
TERM
INALS
IN
PA B
OX
Ex d
SW
ITCH
WIR
ED T
O P
OW
ERTE
RM
INALS
IN
PA B
OX
PA B
OX
CLE
AR 4
mm
PIP
E TO
PASSIV
EALA
RM
/PRES
SU
RIZ
ED S
IGN
AL
1/8"
NPT
F CO
NN
ECTO
R
BLU
E 4m
m P
IPE
TO P
OW
ERIN
TERLO
CK 1
/8"N
PTF
CO
NN
ECTO
R
NO
TE:
LC L
EAKAG
E C
OM
PEN
SATI
ON
PO
OPT
ION
SH
OW
N (
ITEM
S I
ND
OTT
ED R
EMO
VED
FO
R C
F AN
D R
EPLA
CED
BY
TIM
ER S
WIT
CH
)
TERM
INALS
FO
R C
ON
NEC
TIN
GI.
S.
CIR
CU
ITS V
IA M
20 C
ABLE
ENTR
Y O
N L
HS O
R B
OTT
OM
OPT
ION
S
RE
TLIF5
1
E
VLA
V E
GR
UP
RO
TCI
RTS
ER
TOLI
P
M
RAL
A YL
NO
)N
OIT
PO(
M
RAL
API
RT
&
2 R
OT
ACI
DNI
EG
RUP
G
NIG
RU
P=
WOLL
EY
YLP
PU
S E
GR
UP
T
NE
MU
RTS
NI
SA
G T
RE
NI/RI
A
grab
8 X
AM -
4is
p 5
11
XA
M - 0
6
FO LI
AT
ED
LO
RT
NO
C E
VLA
V E
GR
UP
EG
RU
PINI
M 2
DN
A 1
EZI
S
)YL
NO
3 E
ZIS(
NIA
RD
RETLIF
2 D
NA
1 S
ET
ON
EE
S
15
8 LAIT
NE
REFFI
D
OL E
RU
SS
ER
P
1
RO
TA
CID
NI M
RAL
A
MR
ALA
=D
ER
DE
ZIR
US
SE
RP
=N
EE
RG
FO LI
AT
ED
LO
RT
NO
C E
VLA
V E
GR
UP
EG
RU
PINI
M 3
EZI
S3
ET
ON
EE
S
E
GR
UP
T
SO
OB
EVL
AV T
OLIP
34
NOIT
AS
NEPM
OC E
GA
KA
EL - CL
31
CI
GOL
E
RU
SS
ER
PE
GU
AG
21
81
61
"R
O"E
TA
G
R
EMI
TE
VLA
V
RO
TAL
UG
ER
isp
03
grab
2
44
W
OLF E
GR
UP
EVL
AV L
OR
TN
OC
)YLN
O 3
EZI
S(
71
EG
AK
AEL
N
OITA
SN
EPM
OC
EVL
AV
S
NOI
TP
O R
OFE
ES
3 FO
3 TE
EH
S
62
M
UM
NIM
E
RU
SS
ER
PR
OS
NE
S
E
RU
SOL
CN
E T
SE
T E
RU
SS
ERP
)D
EG
GUL
P( T
NIOP
LAIT
NE
REFFI
D I
H E
RU
SS
ER
P
E
NIL-NI
RO
TCI
RT
SE
R
E
GR
UP
T
SO
OB
EVL
AV
B
91
A
.2
.1
.3
E
VLA
V E
GR
UP
EE
S - LO
RTN
OC
LIA
TE
D
ET
ON
NIA
RD L
AU
NA
M H
TIW
RETLIF
SA
H E
GR
UPI
NIM
1 E
ZIS
CIT
AM
OT
UA
HTIW
RETLIF
EV
AH
EV
OB
A D
NA
2 E
ZIS
.T
NIO
P N
OIT
CE
NN
OC
NIA
RD L
AN
RE
TX
E D
NA
NIA
RD
EG
RU
PINI
M 3
EZI
S OT
DE
TTIF YLN
O E
RA
DE
TTO
D NI
NW
OH
S S
ME
TI
O
T T
ELT
UO
EG
RUP
ER
US
OLC
NE
DE
ZIR
US
SE
RP
22
41
"ET
ELPM
OC
EG
RUP"
EVL
AV
YLP
PU
S E
GR
UP
EG
UA
G E
RU
SS
ER
P)
YLN
O 3
EZI
S(
W
OLF E
GR
UP
RO
SN
ES
ER
US
OLC
NE
ER
US
SE
RP
9
CI
NO
RT
CEL
ER
EMI
T3
HTG
NEL
mm001 Y
NA
REV
O m
m4.0 N
AHT
SSEL E
B OT
SSE
NTALF
DEIFI
CEP
SN
US
EC
NA
REL
OT
LAI
RE
TA
M
NW'RD
D'PPA
D'KHC
:S
UTAT
S G
NIW
AR
D
:D
EV
OR
PP
A
:oN .
DO
M
:ET
AD
:E
US
SIELG
NA dr3
NOIT
CEJ
OR
P
mm
NI SN
OISN
EMI
D
ELA
CS T
ON
OD
deti
miL
sei
gol
on
hc
eT
op
xE
:oN
BOJ
HSI
NIF
EL
TIT
:R
EM
OTS
UC
.oN T
EE
HS
FO
HR0 7T
K YE
RR
USM
OD
GNI
K D
ETIN
U
.oN
GNI
WA
RD
ELA
CS
thgirypoC era tne
mucod / gniward siht fo stnetnoc ehT
elbanruter era dna laitnedifnoc sa detaert eb ot era yehT .deti
miL seigolonhceT opxE rehtien ,deti
miL seigolonhceT opxE morf tnesnoc nettir
w tuohtiw eloh
w ni ro trap ni detacinum
moc ro deipoc eb ot ton era yehT .tseuqer nopu.stseretni ruo tsniaga ya
w yna ni desu eb ot yeht era
5.0± E
CALP
CED
ON
2.0± ECAL
P CE
D 11.0±
ECALP
CED 2
WOLF
SU
OU
NITN
OC - F
C
SN
OIT
PO
ROF
3 FO
3 TE
EH
S E
ES
PIRT
& M
RAL
A S
WO
HS TI
UC
RIC
EV
OB
A
RE
TLIF
.1
SET
ON
NIA
RD L
AU
NA
M HTI
W R
ETLIF
SA
H E
GR
UPINI
M 1
EZI
SCIT
AM
OTU
A H
TIW
RE
TLIF E
VA
H E
VO
BA
DN
A 2
EZI
S.T
NIOP
NOI
TC
EN
NO
C NI
AR
D LA
NR
ET
XE
DN
A NI
AR
D
E
GR
UP"
"ET
ELP
MO
CE
VLA
V
B A
OL
ER
US
SE
RP L
AITN
ER
EFFID
LAI
TN
ER
EFFID
IH
ER
US
SE
RP
E
RU
SOL
CN
E
TS
ET E
RU
SS
ER
P)
DE
GG
ULP(
TNI
OP
E
NIL-NI
RO
TCI
RT
SE
R
O
T T
ELT
UO
EG
RUP
ER
US
OLC
NE
DE
ZIR
US
SE
RP
M
UMI
NIM
W
OLF/E
RU
SS
ER
P
RO
SN
ES
CI
NO
RT
CEL
ER
EMI
T
2 R
OT
ACI
DNI
EG
RUP
G
NIG
RU
P=
WOLL
EY
3
81
R
EMI
TE
VLA
V
9
31
t
R
EMI
TH
CTI
WS
S
AG
TR
ENI/
RIA
TN
EM
UR
TS
NI YL
PP
US
EG
RUP
gr
ab
8 X
AM -
4is
p 5
11
XA
M - 0
6
)1
ET
ON
EE
S( NI
AR
D R
ETLIF
22
418
62
CI
GOL
E
RU
SS
ER
PE
GU
AG
1
ROT
ALU
GE
R
grab
2is
p 0
32
W
OLF L
ORT
NO
CE
VLA
V
"R
O"E
TA
G6
1
1 R
OTA
CID
NI M
RAL
AM
RAL
A =
DE
RD
EZI
RU
SS
ER
P =
NE
ER
G
E
RU
SOL
CN
EE
RU
SS
ER
P
HTG
NEL
mm001 Y
NA
REV
O m
m4.0 N
AHT
SSEL E
B OT
SSE
NTALF
DEIFI
CEP
SN
US
EC
NA
REL
OT
LAI
RE
TA
M
NW'RD
D'PPA
D'KHC
:S
UTAT
S G
NIW
AR
D
:D
EV
OR
PP
A
:oN .
DO
M
:ET
AD
:E
US
SIELG
NA dr3
NOIT
CEJ
OR
P
mm
NI SN
OISN
EMI
D
ELA
CS T
ON
OD
deti
miL
sei
gol
on
hc
eT
op
xE
:oN
BOJ
HSI
NIF
EL
TIT
:R
EM
OTS
UC
.oN T
EE
HS
FO
HR0 7T
K YE
RR
USM
OD
GNI
K D
ETIN
U
.oN
GNI
WA
RD
ELA
CS
thgirypoC era tne
mucod / gniward siht fo stnetnoc ehT
elbanruter era dna laitnedifnoc sa detaert eb ot era yehT .deti
miL seigolonhceT opxE rehtien ,deti
miL seigolonhceT opxE morf tnesnoc nettir
w tuohtiw eloh
w ni ro trap ni detacinum
moc ro deipoc eb ot ton era yehT .tseuqer nopu.stseretni ruo tsniaga ya
w yna ni desu eb ot yeht era
5.0± E
CALP
CED
ON
2.0± ECAL
P CE
D 11.0±
ECALP
CED 2
AP
NOI
TP
OM
RAL
A D
NA
RE
WO
PO
P N
OITP
OT
UPT
UO
CITA
MU
EN
PSI
NOIT
PO
EFA
S YLL
ACI
SNI
RT
NI
.X
OB
NOIT
CN
UJ e xE
NI D
ETA
NIM
RET
SE
HCTI
WS
FO
OR
PE
MAL
F d xE
.D
ES
U E
B TS
UM
SD
NAL
G EL
BA
C EL
BATI
US
E
ER
F TLO
V E
RA
STU
PTU
O M
RAL
A E
VIS
SA
P D
NA
KC
OLR
ETNI
RE
WO
P
YLLA
CIS
NIRT
NI OT
DET
CE
NN
OC
EB
YLN
O TS
UM
DN
A ST
CAT
NO
C.11-2-08
PE
GNI
WA
RD
EE
S LU
DN
A M
F R
OF .
STIU
CRI
C E
FA
S
A
SA
HC
US
SE
CIV
ED
ELB
ATIU
S OT
STU
PTU
O TP
N "8/1 TC
EN
NO
C.TI
NU
EC
AF
RET
NI E
GR
UPI
NIM
XO
B N
OIT
CN
UJ 6T II e x
E
EDI
RR
EV
O LA
UN
AM
+O/
M + + 12
MR
ALA
EVI
SS
AP
NO
MM
OC
NO
MM
OC
KC
OLR
ETNI
RE
WO
P1
A
YE
K
BC
P H
CTI
WS .
S.I
2 +O/M
B
C/N
LA
NGI
S D
EZI
RU
SS
ER
P/M
RAL
A E
VIS
SA
P
isp 03
grab 2
H
CTI
WS
& R
OT
AU
TC
AA4 51
CA
V052
A6 1C
A V05
2
ST
CA
TN
OC
DE
ZIR
US
SE
RP/
MR
ALA
C76
A"
DE
ZIR
US
SE
RP"
A
isp 03
grab 2
LA
NGI
S K
COL
RE
TNI
RE
WO
P
H
CTI
WS
& R
OT
AU
TC
A
1YL
PP
US
RE
WO
P
LA
RT
UE
N
LA
RT
UE
N
A4 51C
A V05
2
O
T R
EW
OP
DE
ZIR
US
SE
RP
ER
US
OL
CN
E
A6 1C
A V05
2
O/N
3E
VIL
2 4 5ST
CA
TN
OC
KC
OLR
ET
NI R
EW
OP
HT
RA
E
EVIL
B"
ET
ELP
MO
C E
GR
UP"
B
HTG
NEL
mm001 Y
NA
REV
O m
m4.0 N
AHT
SSEL E
B OT
SSE
NTALF
DEIFI
CEP
SN
US
EC
NA
REL
OT
LAI
RE
TA
M
NW'RD
D'PPA
D'KHC
:S
UTAT
S G
NIW
AR
D
:D
EV
OR
PP
A
:oN .
DO
M
:ET
AD
:E
US
SIELG
NA dr3
NOIT
CEJ
OR
P
mm
NI SN
OISN
EMI
D
ELA
CS T
ON
OD
deti
miL
sei
gol
on
hc
eT
op
xE
:oN
BOJ
HSI
NIF
EL
TIT
:R
EM
OTS
UC
.oN T
EE
HS
FO
HR0 7T
K YE
RR
USM
OD
GNI
K D
ETIN
U
.oN
GNI
WA
RD
ELA
CS
thgirypoC era tne
mucod / gniward siht fo stnetnoc ehT
elbanruter era dna laitnedifnoc sa detaert eb ot era yehT .deti
miL seigolonhceT opxE rehtien ,deti
miL seigolonhceT opxE morf tnesnoc nettir
w tuohtiw eloh
w ni ro trap ni detacinum
moc ro deipoc eb ot ton era yehT .tseuqer nopu.stseretni ruo tsniaga ya
w yna ni desu eb ot yeht era
5.0± E
CALP
CED
ON
2.0± ECAL
P CE
D 11.0±
ECALP
CED 2
EN
CL
OS
UR
E F
RO
NT
B
DE
TA
IL 'B
'
C
UT
OU
T / H
OL
ES
FO
R S
IZE
2 E
NC
LO
SU
RE
S
= 2
40
[9
.45
"] =
= 1
93
[7
.60
"] =
= 1
60
[6
.30
"] =
42
[1.6
5"]
FLA
TN
ES
S T
O B
E L
ES
S T
HA
N 0
.4m
m O
VE
R A
NY
100m
m L
EN
GT
H
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.
No:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
IN
mm
DO
NO
T S
CA
LE
Exp
o T
ech
no
log
ies
Lim
ited
JO
B N
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No
.O
F
SU
RR
EY
K
T7 0
RH
UN
ITE
D K
ING
DO
M
DR
AW
ING
No
.
SC
ALE
The c
onte
nts
of
this
dra
win
g /
docum
ent
are
Copyright
E
xpo T
echnolo
gie
s L
imited.
They a
re t
o b
e t
reate
d a
s c
onfidential and a
re r
etu
rnable
upon r
equest.
They a
re n
ot
to b
e c
opie
d o
r com
munic
ate
d in p
art
or
in w
hole
without
written c
onsent
from
Expo T
echnolo
gie
s L
imited,
neither
are
they t
o b
e u
sed in a
ny w
ay a
gain
st
our
inte
rests
.
NO
DE
C P
LA
CE
±0.5
1 D
EC
PL
AC
E ±
0.2
2 D
EC
PL
AC
E ±
0.1
17
3 [6
.81
"]
35
[1.3
8"]
55
[2.1
7"]
19
[0
.75
"]
EN
CL
OS
UR
E F
RO
NT
= 1
60
[6
.30
"] =
= 1
93
[7
.60
"] =
= 2
40
[9
.45
"] =
68
[2.68"]
AC
D
A
68
[2.68"]
= 150 [5.91"] =
= =
62
[2.44"]
AB
B
= =
A
DE
TA
IL 'A
'
C
UT
OU
T / H
OL
ES
FO
R S
IZE
1 E
NC
LO
SU
RE
S
42
[1.6
5"]
17
3 [6
.81
"]
19
[0
.75
"]
68
[2.68"]
CA
10.5 [0.41"]
A
D
37
[1.4
6"]
33
[1.3
0"]
19
[0
.75
"]23
3 [9
.17
"]
10
[0
.39
"]
EN
CL
OS
UR
E F
RO
NT
10 [0.39"]
= 1
60
[6
.30
"] =
= 1
93
[7
.60
"] =
36
0 [
14
.17
"]
10.5 [0.41"]
68
[2.68"]
D
BAA
= 150 [5.91"] =
CA
62
[2.44"]
68
[2.68"]
CU
TO
UT
BA
DE
TA
IL 'C
'
C
UT
OU
T / H
OL
ES
FO
R S
IZE
3 E
NC
LO
SU
RE
S
= 150 [5.91"] =
68
[2.68"]
BA
= =
= =
62
[2.44"]
A
38
[1
.50
"]
5 [0.20"]
10 [0.41"]
= =
= =
= =
= =
= =
DE
SC
RIP
TIO
N
HO
LE
Ø
7.5
[9/3
2"]
HO
LE
Ø
26
[1
"] (
AL
TE
RN
AT
IVE
TO
CU
TO
UT
)
HO
LE
Ø
38
[1
1/2
"] (
AL
TE
RN
AT
IVE
TO
CU
TO
UT
)
3 C
EN
TR
E D
OT
S F
OR
PA
OP
TIO
N O
NL
Y
RE
F
A B C D
FLA
TN
ES
S T
O B
E L
ES
S T
HA
N 0
.4m
m O
VE
R A
NY
100m
m L
EN
GT
H
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.
No:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
IN
mm
DO
NO
T S
CA
LE
Exp
o T
ech
no
log
ies
Lim
ited
JO
B N
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No
.O
F
SU
RR
EY
K
T7 0
RH
UN
ITE
D K
ING
DO
M
DR
AW
ING
No
.
SC
ALE
The c
onte
nts
of
this
dra
win
g /
docum
ent
are
Copyright
E
xpo T
echnolo
gie
s L
imited.
They a
re t
o b
e t
reate
d a
s c
onfidential and a
re r
etu
rnable
upon r
equest.
They a
re n
ot
to b
e c
opie
d o
r com
munic
ate
d in p
art
or
in w
hole
without
written c
onsent
from
Expo T
echnolo
gie
s L
imited,
neither
are
they t
o b
e u
sed in a
ny w
ay a
gain
st
our
inte
rests
.
NO
DE
C P
LA
CE
±0.5
1 D
EC
PL
AC
E ±
0.2
2 D
EC
PL
AC
E ±
0.1
275 [10.83"]
= 210 [8.27"] =
NO
TE
EN
CL
OS
UR
E M
OU
NT
ING
EIT
HE
R T
HR
OU
GH
4 x
Ø7
.5 [9
/32
"] H
OL
ES
OR
ON
4 x
M6
ST
UD
S U
SIN
G W
AL
L B
AR
S
18
0 [7
.09
"]
12
5 [4
.92
"]
90
[3
.54
"]
= 150 [5.91"] =
DE
TA
IL 'D
'
WA
LL
MO
UN
TE
D S
IZE
1 E
NC
LO
SU
RE
365 [14.37"]
= 390 [15.35"] WALL BARS =
305 [12.01"]
= 270 [10.63"] WALL BARS =
15
0 [5
.91
"]
22
5 [8
.86
"]
18
8 [7
.40
"]
15
5 [6
.10
"]
30
0 [
11
.81
"]
13
2 [5
.20
"]
18
0 [7
.09
"]
90
[3
.54
"]
DE
TA
IL 'F
'
WA
LL
MO
UN
TE
D S
IZE
3 E
NC
LO
SU
RE
= 180 [7.09"] =
= 300 [11.81"] =
DE
TA
IL 'E
'
WA
LL
MO
UN
TE
D S
IZE
2 E
NC
LO
SU
RE
DA
TU
M P
OIN
T
4 H
OL
ES
Ø7.5
[9/3
2"]
WALL BARS
4 H
OL
ES
Ø7.5
[9/3
2"]
4 W
EL
DS
TU
DS
M6
x 1
6 L
ON
G F
OR
WA
LL
BA
RS
.
HO
LE
S IN
WA
LL
BA
RS
Ø7.5
[9/3
2"]
DA
TU
M P
OIN
T
4 H
OL
ES
Ø7.5
[9/3
2"] D
AT
UM
PO
INT
35
[1
.38
"]
HO
LE
Ø22.5
[7/8
"]
48
[1
.89
"]
NO
TE
EN
CL
OS
UR
E M
OU
NT
ING
EIT
HE
R T
HR
OU
GH
4 x
Ø7
.5 [9
/32
"] H
OL
ES
OR
ON
4 x
M6
ST
UD
S U
SIN
G W
AL
L B
AR
S
NO
TE
EN
CL
OS
UR
E M
OU
NT
ING
EIT
HE
R T
HR
OU
GH
4 x
Ø7
.5 [9
/32
"] H
OL
ES
OR
ON
4 x
M6
ST
UD
S U
SIN
G W
AL
L B
AR
S
4 W
EL
DS
TU
DS
M6
x 1
6 L
ON
G F
OR
WA
LL
BA
RS
.
HO
LE
S IN
WA
LL
BA
RS
Ø7.5
[9/3
2"]
4 W
EL
DS
TU
DS
M6
x 1
6 L
ON
G F
OR
WA
LL
BA
RS
.
HO
LE
S IN
WA
LL
BA
RS
Ø7.5
[9/3
2"]
2 H
OL
ES
Ø14 [
9/1
6"]
HO
LE
Ø2
2.5
[7
/8"]
2 H
OL
ES
Ø1
4 [9
/16
"]
2 H
OL
ES
Ø1
4 [9
/16
"]
HO
LE
Ø22.5
[7/8
"]
150 [5.91"]
FLA
TN
ES
S T
O B
E L
ES
S T
HA
N 0
.4m
m O
VE
R A
NY
100m
m L
EN
GT
H
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.
No:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
IN
mm
DO
NO
T S
CA
LE
Exp
o T
ech
no
log
ies
Lim
ited
JO
B N
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No
.O
F
SU
RR
EY
K
T7 0
RH
UN
ITE
D K
ING
DO
M
DR
AW
ING
No
.
SC
ALE
The c
onte
nts
of
this
dra
win
g /
docum
ent
are
Copyright
E
xpo T
echnolo
gie
s L
imited.
They a
re t
o b
e t
reate
d a
s c
onfidential and a
re r
etu
rnable
upon r
equest.
They a
re n
ot
to b
e c
opie
d o
r com
munic
ate
d in p
art
or
in w
hole
without
written c
onsent
from
Expo T
echnolo
gie
s L
imited,
neither
are
they t
o b
e u
sed in a
ny w
ay a
gain
st
our
inte
rests
.
NO
DE
C P
LA
CE
±0.5
1 D
EC
PL
AC
E ±
0.2
2 D
EC
PL
AC
E ±
0.1
= 2
90
[1
1 1
3/3
2"]
CU
TO
UT
=
= 3
20
[1
2 1
9/3
2"]
PA
NE
L O
UT
LIN
E =
= 120 [4 23/32"] =
= 225 [8 27/32"] =
= 1
70
[6
11
/16
"] =
= 3
05
[1
2"]
=
= 210 [8 9/32"] CUTOUT =
= 240 [9 7/16"] PANEL OUTLINE =
DE
TA
IL 'A
'
PA
NE
L M
OU
NT
SIZ
E 1
8 O
FF
HO
LE
S Ø
7.5
[9/3
2"]
= 290 [11 13/32"] PANEL OUTLINE =
= 254 [10"] CUTOUT =
= 276 [10 7/8"] =
= 172 [6 25/32"] =
= 2
76
[1
0 7
/8"]
=
= 1
72
[6
25
/32
"] =
= 2
90
[1
1 1
3/3
2"]
PA
NE
L O
UT
LIN
E =
= 2
54
[1
0"]
CU
TO
UT
=
8 O
FF
INT
ER
NA
L W
ELD
ST
UD
M6
x 1
5 L
ON
G
DE
TA
IL 'B
'
PA
NE
L M
OU
NT
SIZ
E 2
NO
TE
S:
US
E D
IRE
CT
MO
UN
TIN
G W
HE
RE
VE
R P
OS
SIB
LE
; W
AL
L M
OU
NT
ING
BR
AC
KE
TS
AN
D P
IPIN
G K
ITS
FO
R
SID
E M
OU
NT
ING
AR
E O
PT
ION
AL
.
MIN
IPU
RG
E M
US
T B
E M
OU
NT
ED
WIT
H T
HE
PU
RG
E O
UT
LE
T P
IPE
IN
VE
RT
ICA
L P
LA
NE
PO
INT
ING
DO
WN
.
PU
RG
E A
IR T
O V
EN
T IN
TO
TO
P O
F T
HE
EN
CL
OS
UR
E A
ND
EX
IT T
HR
OU
GH
TH
E
RE
LIE
F V
AL
VE
/SP
AR
K A
RR
ES
TO
R A
T T
HE
BO
TT
OM
OF
TH
E E
NC
LO
SU
RE
.
EX
TE
RN
AL
TU
BE
S S
HO
UL
D B
E M
ET
AL
LIC
(N
ON
-CR
US
HA
BL
E),
MIN
IMU
M B
OR
E 4
mm
1. 2.
3.
4.
RE
LIE
F V
AL
VE
PIP
ING
KIT
(OP
TIO
NA
L)
DIR
EC
T M
OU
NT
(P
RE
FE
RR
ED
OP
TIO
N)
SID
E
MO
UN
T
OP
TIO
NA
L
PA
NE
L M
OU
NT
FO
R S
IZE
S 1
AN
D 2
ON
LY
LC
OP
TIO
N O
NL
Y.
FL
OW
MO
NIT
OR
ING
PIP
E R
EQ
UIR
ED
MIN
IPU
RG
E C
ON
FIG
UR
AT
ION
25 [1"] MIN
SP
AR
K A
RR
ES
TO
R
(CF
OP
TIO
N O
NL
Y)
FL
OW
MO
NIT
OR
ING
CO
NN
EC
TIO
N F
OR
TH
E
RLV
52
FL
OW
MO
NIT
OR
ING
CO
NN
EC
TIO
N F
OR
AL
L
RE
LIE
F V
AL
VE
S E
XC
EP
T
TH
E R
LV
52
FLA
TN
ES
S T
O B
E L
ES
S T
HA
N 0
.4m
m O
VE
R A
NY
100m
m L
EN
GT
H
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.
No:
DA
TE
:
ISS
UE
:
3rd
AN
GL
E
PR
OJE
CT
ION
DIM
EN
SIO
NS
IN
mm
DO
NO
T S
CA
LE
Exp
o T
ech
no
log
ies
Lim
ited
JO
B N
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No
.O
F
SU
RR
EY
K
T7
0R
H
UN
ITE
D K
ING
DO
M
DR
AW
ING
No
.
SC
ALE
Th
e c
on
ten
ts o
f th
is d
raw
ing
/ d
ocu
me
nt a
re C
op
yri
gh
t
Exp
o T
ech
no
log
ies L
imite
d. T
he
y a
re to
be
tre
ate
d a
s c
on
fid
en
tia
l a
nd
are
re
turn
ab
le
up
on
re
qu
est.
T
he
y a
re n
ot to
be
co
pie
d o
r co
mm
un
ica
ted
in
pa
rt o
r in
wh
ole
with
ou
t w
ritt
en
co
nse
nt fr
om
Exp
o T
ech
no
log
ies L
imite
d, n
eith
er
are
they t
o b
e u
sed in a
ny w
ay a
gain
st
our
inte
rests
.
NO
DE
C P
LA
CE
±0.5
1 D
EC
PLA
CE
±0.2
2 D
EC
PLA
CE
±0.1
CERT
REL
ATED
JPd
B
DRAW
N1
12
ZX
Y
GASKET
4.5
[0.
18"]
BEF
ORE
CO
MPR
ESSIO
N
MIN 25 [0.98"]
WID
TH X
62 [
2.44
"]
88 [
3.46
"]
110
[4.3
3"]
HEI
GH
T Y
133
[5.2
4"]
170
[6.6
9"]
185
[7.2
8"]
DEP
TH Z
28 [
1.10
"]
33 [
1.30
"]
37 [
1.46
"]
RLV
25
RLV
36
RLV
52
MIN
IPU
RG
E
SIZ
E 1
SIZ
E 2
SIZ
E 3
17 [
0.67
"]G
ASKET
3 [
0.12
"]
BEF
ORE
CO
MPR
ESSIO
N
CO
NN
ECTI
ON
(M
5) F
OR P
RES
SU
RE
MEA
SU
REM
ENT
= =
44 [
1.73
"]
= =44 [1.73"]
= 64
[2.
52"]
=
= 64 [2.52"] =
= 76.2 [3"] =
= 76
.2 [
3"]
=
46 [1.81"]
133 [5.24"]
= =
62 [
2.44
"]
RLV OU
TLIN
E
= 88
[3.
46"]
=
=
10
9 [4
.29"
] =
56 [2.2"]
170 [6.69"]
65 [2.56"]
185 [7.28"]
RLV OU
TLIN
E
RLV OU
TLIN
ER
LV
25
CU
TO
UT
DET
AIL
'A'
DET
AIL
'B'
DET
AIL
'C'
RL
V3
6 C
UT
OU
TR
LV
52
CU
TO
UT
FLA
TN
ES
S T
O B
E L
ES
S T
HA
N 0
.4m
m O
VE
R A
NY
100m
m L
EN
GT
H
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.
No:
DA
TE
:
ISS
UE
:
3rd
AN
GL
E
PR
OJE
CT
ION
DIM
EN
SIO
NS
IN
mm
DO
NO
T S
CA
LE
Exp
o T
ech
no
log
ies
Lim
ited
JO
B N
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No
.O
F
SU
RR
EY
K
T7
0R
H
UN
ITE
D K
ING
DO
M
DR
AW
ING
No
.
SC
ALE
Th
e c
on
ten
ts o
f th
is d
raw
ing
/ d
ocu
me
nt a
re C
op
yri
gh
t
Exp
o T
ech
no
log
ies L
imite
d. T
he
y a
re to
be
tre
ate
d a
s c
on
fid
en
tia
l a
nd
are
re
turn
ab
le
up
on
re
qu
est.
T
he
y a
re n
ot to
be
co
pie
d o
r co
mm
un
ica
ted
in
pa
rt o
r in
wh
ole
with
ou
t w
ritt
en
co
nse
nt fr
om
Exp
o T
ech
no
log
ies L
imite
d, n
eith
er
are
they t
o b
e u
sed in a
ny w
ay a
gain
st
our
inte
rests
.
NO
DE
C P
LA
CE
±0.5
1 D
EC
PLA
CE
±0.2
2 D
EC
PLA
CE
±0.1
CERT
REL
ATED
JPd
B
DRAW
N1
22
4 H
OLE
SØ
5.5
4 H
OLE
SØ
5.5
4 H
OLE
SØ
5.5
HO
LEØ
25 -0 +
2
[1"
-0 +0.
1 ]
HO
LEØ
36 -0 +
2
[11 2"
-0 +0.
1 ]
HO
LEØ
52 -0 +
2
[2"
-0 +0.
1 ]
114224567
NEU
TRAL
LIVE
NEU
TRAL
LIVE
POW
ERACTU
ATO
R A
ND
SW
ITCH
ALA
RM
/PRES
SU
RIZ
EDACTU
ATO
R &
SW
ITCH
MIN
IPU
RG
E
POW
ER A
ND
ALA
RM
BO
X
MAN
UAL
OVER
RID
E SW
ITCH
KEY
OPE
RATE
D
Ex d
IIC
T6
EARTH
1 1
2 2
4 13 323
POW
ERSU
PPLY
IN
POW
ER T
OPR
ESSU
RIZ
EDEN
CLO
SU
RE
PRES
SU
RE
ALA
RM
CO
NTA
CTS
FIT
END
PLATE
SFLA
TNE
SS
TO
BE
LE
SS
TH
AN
0.4
mm
OV
ER
AN
Y 1
00m
m L
EN
GTH
UN
SP
EC
IFIE
DTO
LER
AN
CE
S
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AW
ING
STA
TUS
:A
PP
RO
VE
D:
MO
D. N
o:D
ATE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CTI
ON
DIM
EN
SIO
NS
IN m
m
DO
NO
T S
CA
LE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
ME
R:
SH
EE
T N
o.O
F
SU
RR
EY
KT7
0R
HU
NIT
ED
KIN
GD
OM
DR
AW
ING
No.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht ã
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DE
C P
LAC
E ±
0.5
1 D
EC
PLA
CE
±0.
22
DE
C P
LAC
E ±
0.1
[This Page Intentionally Left Blank]
[This Page Intentionally Left Blank]
[This Page Intentionally Left Blank]
Expo Technologies USAExpo Technologies Inc.
9140 Ravenna Road Unit #3Twinsburg,
OH 440878, USAT: +1 440 247 5314F: +1 330 487 0611
Expo Technologies UKExpo Technologies Ltd.
Unit 2 The Summit, Hanworth RoadSunbury-On-Thames,
TW16 5DB, UKT: +44 20 8398 8011F: +44 20 8398 8014
Expo Technologies ChinaQingdao Expo M&E Technologies Co. Ltd
329 Huashan Er LuJimo City, Qingdao,
266200 ChinaT: +86 532 8906 9858F: +86 532 8906 9858
www.expoworldwide.com