Zuba-Dan Inverter
New Mr.SLIM Inverter for colder climate regions
Mitsubishi Electric CorporationShizuoka Works
2007 JSRAE Technology Award
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 2/43
1. Development background
2. Features of Zuba-Dan models
3Flash Injection Cycle & its characteristics4. Improvement on Start-up & Defrost
5. Field Test Result6. Summary
Mr. SLIM Zuba-Dan Inverter models
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 3/43
1. Development Background
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 4/43
<Min. Temp. in January>(average of 1991 to 2000)
1. Development Background
-15 to -20oC in Northernpart of Hokkaido.
Around -10oC in Southern
part of Hokkaido and inTohoku region
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 5/43
<in case of Standard Heat Pump air conditioner>
Electric heater assistedindoor unit
0.4
0.6
0.8
1
1.2
-15 -10 -5 0 5 10
Capacity is reduced at lowambient temperature.
Capacity is reduced by defrostoperation which leads to poor comfortability.
Burner assisted indoor unit
Liquid injection Heat Pump
Heating Peformance Curve
1. Development Background
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 6/43
Electric Heater assisted A/C
> Low in operation efficiency.
Burner assisted A/C> Periodical servicing is required for burner.> Requires big installation space.> Big amount of the initial investment.
Liquid INJ COMP mounted A/C
> Limited in injection amount(discharge temperature goes down too much)
> Operation efficiency should be improvedduring injection.
Challenges for Heat Pump*Poor performance at low ambient temperature.*Room temperature goes down during defrost.
Slow in starting up.*Not adequate for use in northern part of Hokkaido.
Required functions for A/Cfor cold climate regions
(1)No periodical servicing is required.
(2)Keeps good performance even atlow ambient temperature.
(3)Highly efficient operation at lowambient temperature.
(4)No drop in room temperaturewhile defrosting.
solution: Zuba-Dan
(5)Can be used in all areas
in Hokkaido.
1. Development Background
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 7/43
2. Features of Zuba-Dan models
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 8/43
(1)High heating capacity at low ambient temperature
Our ‘Flash Injection cycle’ (patent to be filed) enables to keepthe maximum heating capacity even at -15
oC.
(2)Comfortability
*Improved defrost control:Defrost duration is reduced to one third of the conventional model.
*Quick start-up:Required time to reach the air blowing temperature of 40oC is halved.
(3)Wider operation range <Industry First!>
Heating operation even at -25oC is possible. (conventionally only to -20oC)
> Possible to be used in all areas in Hokkaido.
2. Features of Zuba-Dan models
(4)Easy and quick installation <Industry First!>The ‘Activated carbon filter ’ and the ‘Wide strainer ’ enable the reuse of
existing piping even when the compressor is broken and the refrigerantoil is contaminated.
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 9/43
3. Flash Injection Cycle & its characteristics
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 10/43
*Flash Injection of refrigerant. Refrigerant heat is recovered by HIC circuit.*Power Receiver circuit without inlet accumulator (good in start up / inlet dry control)*3 LEVs optimally control evaporator, condenser and discharge temperature.
: Refrigerant flow in heating mode<Characteristics>
Injection
Compressor
HIC
LEV A LEV BLEV C
Outdoor HEXIndoor HEX
4-way valveOutdoor unit Indoor unit
Power Receiver (Heat recovery typeliquid pool)
A
B
C
D
E
FGH
J
K
3. Zuba-Dan refrigerant circuit<Flash Injection + Power Receiver Circuit>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 11/43
0.1
1
10
100 150 200 250 300 350 400 450 500Enthalpy[kJ/kg]
P r e s s u r e [ M
P a ]
A
B
K J
IH
GF
E
D C
Heat Exchangeby heat recovery type receiver
Heat Exchangeby HIC
Injected Gas gets drier >>>
Injection amount is increased. (Toprevent discharge SH to decrease.)
Increased
refrigeration
effect
(1)Increased refrigeration effect (improved refrigerant cycle theory)
(2)Quick recovery from defrosting with no accumulator.
(3)Inlet gas super heat >>> to secure compressor high efficiency
(to avoid liquid compression efficiency to be lowered)
3. Zuba-Dan refrigerant circuit<Zuba-Dan refrigeration cycle (Pressure-Enthalpy diagram)>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 12/43
: refrigerant flow in heating mode
Injection
Compressor
HIC
LEV A LEV BLEV C
4-way valve
Outdoor unit Indoor unit
Power Receiver (heat recoverytype liquid pool)
AB
C
D
EFGH
J
K
0.1
1
10
100 150 200 250 300 350 400 450 500Enthalpy[kJ/kg]
P r e s s u r e [ M P a ]
A
B
K J
IH
GF
E
D C
Heat Exchange
by heat recovery type receiver
Heat exchange by HIC
Increased
refrigeration
effectI n d o or HE X
O u t d o
or HE X
3. Zuba-Dan refrigerant circuit<Flash Injection Cycle>
(1)Increased refrigeration effect(improved refrigerant cycle theory)
(2)Quick recovery from defrosting with no accumulator.
(3)Inlet gas super heat
>>> to secure compressor high efficiency
(to avoid liquid compression efficiency to be lowered)
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 13/43
Flash INJGas INJLiquid INJ
Injection Compressor
Evaporator Condenser Gas/Liquid separator HIC
X=0.2X=0.21.0X=1.0
Discharge temperature increases>>> capacity cannot be increased a lot= not suitable for a/c for cold regions.
3. Zuba-Dan refrigerant circuit<Comparison with conventional injection>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 14/43
0.1
1
10
100 150 200 250 300 350 400 450 500Enthalpy[kJ/kg]
P r e s s u r e [ M P a ]
Pd
Ps
Pinj
Ge
Gi
Qc
Qe
Inside HEX without HIC
Conditions: Ambient-15oC / COMP 120rps / Heating capacity 14kW
COMP input = 7.13kW
Big amount of liquid injection>>> discharge temperature
decreases.Liquid INJ(w/o HIC)
Flash INJInlet gas gets drier
>>> discharge SH
can be secured.
0.1
1
10
100 150 200 250 300 350 400 450 500
Enthalpy[kJ/kg]
P r e s
s u r e [ M P a ]
“ ŕ• ”” M Ś đ Š ·Š íHIC— L‚ čŹ đ Ś ŹFŠ O‹ C-15 Ž A łŹk‹ @‰ ń“ ] ”120rps A ’ g– [” \ — Í14kW
łŹk‹ @“ ü—Í=6.14kW
Qc
Qe
3. Zuba-Dan refrigerant circuit<Comparison of Flash INJ with Liquid INJ (same capacity basis)>
Inside HEX with HIC
Conditions: Ambient-15oC / COMP 120rps / Heating capacity 14kW
COMP input = 6.14kW
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 15/43
0.1
1
10
100 150 200 250 300 350 400 450 500
Enthalpy[kJ/kg]
P r e s s u r e [ M P a ]
Pd
Ps
Pinj
Ge
Gi
Qc
Qe
“ ŕ• ”” M Ś đ Š ·Š íHIC – ł‚ µŹ đ Ś ŹFŠ O‹ C-15 Ž A łŹk‹ @‰ ń“ ] ”120rps A ’ g– [” \ — Í14kW
łŹk‹ @“ ü—Í=7.13kW
Liquid INJ(w/o HIC)
Flash INJ
0.1
1
10
100 150 200 250 300 350 400 450 500
Enthalpy[kJ/kg]
P r e s s u
r e [ M P a ]
“ ŕ• ”” M Ś đ Š ·Š íHIC— L‚ čŹ đ Ś ŹFŠ O‹ C-15 Ž A łŹk‹ @‰ ń“ ] ”120rps A ’ g– [” \ — Í14kW
łŹk‹ @“ ü—Í=6.14kW
Qc
Qe
HIC— L‚č HIC– ł‚µ
Ge kg/h 168.4 174.2
Gi kg/h 84.4 137.4“ fŹ o°Ęß°Ë°Ä deg 20 0
łŹk‹ @‰ ń“ ] ” rps 120 120
Qc ‚‹W 14.00 14.00
Qe kW 8.03 7.01
“ ü — Í kW 6.14 7.13
cop | 2.28(116%)1.96(100%)
3. Zuba-Dan refrigerant circuit<Flash Injection circuit>
COMP input = 7.13kW
Inside HEX with HIC
Conditions: Ambient-15oC / COMP 120rps / Heating capacity 14kW
Inside HEX without HICConditions: Ambient-15oC / COMP 120rps / Heating capacity 14kW
with HIC w/o HIC
discharge SH
input
COMP rotation
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 16/43
3.063MPa(50)
0.269MPa(-30)
0.908MPa
Sub cool 10deg
Super heat 10deg
Evaporator refrigerant amount Ge
Injection amount Gi
*Pomer množstiev α=Gi/Ge*HIC temperature efficiency ε ε=(T5-T7)/(T5-Tm)
Tm: Injection refrigerant temp.
T5:HIC inlet liquid temperature
T7:HIC outlet liquid temperature
Equal entropycompression
Condenser refrigerant amount Ge+Gi
3. Zuba-Dan refrigerant circuit<Theoretical characteristics: calculation conditions>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 17/43
1.00
1.05
1.10
1.15
1.20
1.25
1.30
1.35
0 0.2 0.4 0.6 0.8 1
HIC Temperature Efficiency ε
R a t i o o f H e a t i n g
C O P &
C a p a c i t y
( b a s e c o n d i t i o n
α = ε = 0 )
ratio of COP
ratio of Capacity
As HIC temperature efficiency increases,heating capacity and COP also increase.
3. Zuba-Dan refrigerant circuit<Theoretical characteristics: temperature efficiency influence>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 18/43
2.6
2.7
2.8
2.9
3
3.1
0 0.2 0.4 0.6 0.8
Injection Ratio α
D i s c h a r g e P r e s s u r e [ M P a ]
0m
1.5m
3m
HIC Length
40
50
60
70
80
90
100
110
120
0 0.2 0.4 0.6 0.8
Injection Ratio α
D i s c h a r g e T e m p e r a t u r e [
]
0m
1.5m
3m
HIC Length
*Discharge pressure increases as Injection ratio increases.It has got no relations with HIC length.
*Discharge temperature decreases as Injection ratio increases.
3. Zuba-Dan refrigerant circuit<Test Result (1)>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 19/43
100
105
110
115
120
125
130
135
0 0.2 0.4 0.6 0.8
Injection Ratio α
H e a
t i n g C a p a c i t y R a t i o [
]
0m
1.5m
3m
HIC Length
80
85
90
95
100
105
110
0 0.2 0.4 0.6 0.8
Injection Flow Ratio α
H
e a t i n g C O P R a t i o [
] 0m
1.5m
3m
HIC Length
*Heating capacity gets bigger as the HIC length gets longer.
It depends on the Injection ratio as well but not largely.*COP worsens as the Injection ratio gets bigger.125% Heating capacity / 100% COP is realized when injection ratio is 0.4.
3. Zuba-Dan refrigerant circuit<Test Result (2)>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 20/43
*Heating capacity is improved by 30% even at same COMP rotation speed (at -15oC)
*Heating capacity is almost doubled with increased COMP rotation speed. (at -15oC)
>>>This was impossible before due to the excessive temp.rise of discharge refrigerant.
0
2000
40006000
8000
10000
12000
14000
1600018000
-25 -20 -15 -10 -5 0 5
Outdoor Temp.mŽn
H e a t i n g C a p a c i t y [ W ]
ConventionalRotational Speed 70%
FLASH InjectionRotational Speed 70%
FLASH InjectionRotational Speed 100%
3. Zuba-Dan refrigerant circuit<Heating capacity at low ambient temp. (comparison with conventional model)>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 21/43
<LEV> <controls on> A: Suction refrigerant Super HeatB: Condenser Sub CoolC: Discharge refrigerant Super Heat
Suction SH
Discharge SHSC
“d Žq –c ’Ł •Ů A
“d Žq –c ’Ł •Ů C
“d Žq –c ’Ł •Ů B
3 conditions (suctionrefrigerant, condenser and evaporator) isoptimally controlled.
3. Zuba-Dan refrigerant circuit<Flash Injection Cycle Control>
LEV B
LEV C
LEV A
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 22/43
0
5
10
15
20
25
30
35
100 200 300 400
INJ LEV Š J“ x[pulse]
S
H , S C [ d e
“ fŹ oSH
SC
‹ z“ üSH
0
5
10
15
20
25
30
35
170 190 210 230
Ź ă’ iLEV Š J“ x[pulse]
S
H , S C [ d e
“ fŹ oSH
SC
‹ z“ üSH
0
5
10
15
20
25
30
35
100 110 120 130 140
‰ ş’ iLEV Š J“ x[pulse]
S
H , S C [ d e
“ fŹ oSH
SC
‹ z“ üSH
SH
Refrigerant distribution is analyzed when each LEV is controlled individually.
SH
SH SH SC
3. Zuba-Dan refrigerant circuit<LEV characteristics>
discharge SHSCsuction SH
discharge SHSCsuction SH
discharge SHSCsuction SH
Lower LEV opening (pulse) Upper LEV opening (pulse) INJ LEV opening (pulse)
Suction Super Heat control
Sub Cool control Discharge Super Heat control
Only suction SH responds toline shape.
Influence on refrigerantdistribution.
Discharge SH respondsacutely.
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 23/43
<Purpose>
*3 LEVs operates individually towards different control targets.
*Does individual LEV control interfere each other resulting in unstable refrigerant cycle?
*Most stable control constant is chosen.
<Background>
We apply ‘Quality Engineering’ in order to checkwhether the currently chosen ‘control constant combinations’(current control) is appropriate or not.
3. Zuba-Dan refrigerant circuit<Application of Quality Engineering>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 24/43
10deg
11deg
9deg
SHs
SHs
time
*What is the stability of the refrigerant cycle?<Definition of Basic Function>
Starting from the stable condition, compressor rotation should be increasedfrom 60 to 70rps. If the integrated value of SHs in the next 10 minutes issmall, it means the stability is high.
)119(0
)11(11
)9(9
,600
)( 260 0
12
SHsSHs
SHsSHsSHs
SHsSHsSHsSHs
t
L
L
L
=∆
>−=∆
<−=∆∆
=
∑=
σ
3. Zuba-Dan refrigerant circuit<System Basic Functions>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 25/43
Pd
Ps
Pm
Pinj
1
2
3
4
56
7
8
9
Ge
Gi
h1
h2
Vst1[cc/r] = Compressor’s suction volumeVst2[cc/r] = Compression room volumeat the end of injection
*Point 1
Inlet refrigerant (density D1) is trapped in Vst1.
*Point 1 >>> 2
Injection refrigerant (condition 9) is poured
into compression roomExisting refrigerant amount increases to D1 (1+α).
*Point 2 >>> 3
Injection port is closed at the compression roomvolume of Vst2. Normal pressure rise process afterward.
By adjusting the discharge SH at point 3 by α, and
by adjusting Pinj to make the density at point 2 gets D2,
Injection pressure can be calculated.
α = G i / G e
3. Zuba-Dan refrigerant circuit<Injection Pressure calculation method>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 26/43
Pinj is about 2.5 times of Ps.INJ amount (discharge SH) has
just small influence.
0
0.5
1
1.5
2
2.5
3
3.5
0 0.2 0.4 0.6 0.8 1
Ps[MPa(abs)]
[ M P a ( a b s ) ]
Pd
Pinj(SHd20deg)
Pinj(SHd50deg)
0
0.2
0.4
0.6
0.8
1
0 0.2 0.4 0.6 0.8 1
Ps[MPa(abs)]
I N J
α
INJ (SHd20)
INJ (SHd50)
The lower the Ps is, the bigger the INJ ratio α gets.
The smaller the discharge SH is,the bigger the α gets.
Pd: stable, Ps: variation character
3. Zuba-Dan refrigerant circuit<Injection Pressure>
INJ ratio (SHd20)
INJ ratio (SHd50)
Pressure(MPa(abs)) INJ
ratio
α
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 27/43
4. Improvement on Start up & Defrost
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 28/43
<Standard Accumulator circuit>Refrigerant is pooled in the accumulator during
start up and defrosting. As a result, it takeslong time to start up due to insufficient refrigerantcirculation.
Normal start up: Refrigerant within outdoor HEXmoves into the accumulator.
Defrost: surplus refrigerant is pooledin the accumulator.
<Flash Injection cycle>(1)Start up with a bit ‘return in liquid’ condition as there is
no liquid pool on low pressure side.(to secure circulation amount)
(2)Refrigerant pooled in the receiver during defrostis quickly let return to compressor from injection circuit.It contributes to improve start up characteristics.
(3)Refrigerant circulation amount at start up is securedby Injection.
Injection compressor
HIC
4-way valveOutdoor unit
Power receiver
Compressor
4-way valveOutdoor unit
Accumulator
Slowly returnto suction
through oilrecovery hole.
4. Improvement on Start up & Defrost
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 29/43
0
5
10
15
20
25
30
35
40
45
50
0 5 10 15 20 25 30
(min)
(
)
0
1
2
3
4
5
6
7
8
9
10
(
In accumulator cycle, the temperature does not rise rapidly due toinsufficient refrigerant circulation when starting up.
On the other hand in Zuba-Dan, the discharge air temperature can reachhigh level in short time.
4. Improvement on Start up & Defrost<Start up characteristics (at -10oC ambient)>
Zuba-Dan air discharge air temp.
Accumulator cycle air discharge temp
Zuba-Dan low pressure
Accumulator cycle low pressure
Air dischargetemp (oC)
Time (minute)
Low pressure(MPa)
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 30/43
(1)Quicker start up
*Optimal supply of refrigerant by receiver circuit at start up.
*Refrigerant circulation amount is increasedby Flash Injection.
(2)Shorter defrost
*Defrost is shortened by Flash Injection.
(3)Less frequent defrost
*Less frost on HEX with hydrophilic fins.*Estimation control on Frost formation contributes toreduce defrost frequency largely, especially in lowambient temperature (low absolute humidity).
Better comfort is achievedby ‘Flash Injection cycle’ and ‘new Defrost control’.
4. Improvement on Start up & Defrost<Better comfort with better defrost control>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 31/43
5. Field Test Result
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 32/43
<Tested units and conditions>
*Test Period: From December 2004 to February 2005
*Test Location: At an office building in Asahikawa, Hokkaido
Žş ŠO ‹@ 11.2KwN ‰ XŽş “ŕ ‹@ 5.6KwN ‰ X ~ c C “”z ŠÇ ’· –ń 15‚Ť§ Śä Žd — l ‡@ Š¦ — â ’n § Śä ( ÝĽŢŞ Ľ®Ý— L )
‡A ’Ę Źí § Śä ( ÝĽŢŞ Ľ®Ý–ł )*‡@ ,‡A ‚đ Śđ ŚÝ ‚É ŽŔ Ž{
‘Ş ’č Ť€ –Ú Žş “ŕ ‹z Ťž / Źo ‰· “xŽş “ŕ ‰· “x •Ş •z AŠO ‹C ‰· “x A
— â ”} ‰· “x AŹÁ ”ď “d — Í — Ę
*Test Points
5. FT Result (1): Office building in Asahikawa City
Outdoor unit: 11.2kW class unit
Indoor unit: 2 units of 5.6kW class
Piping length: about 15m
Control specifications: (1)with Injection (control for cold regions)
(2)w/o Injection (normal control)
*(1) & (2) are both realized alternatively.
Test points: *Indoor inlet & outlet temperature
*Indoor temperature distribution, Ambient temperature,
Refrigerant temperature, Energy consumption
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 33/43
Outdoor unit 2 Indoor units
5. FT Result (1): Office building in Asahikawa City
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 34/43
without INJ >>> with INJCapacity increases by about 30%
Heating Capacity & COP
based on the different ambient temperature
Heating CapacityBasic cycle
Heating Capacity
Injection cycle
Heating capacity:(indoor outlet – inlet) x air volume x density x specific heat
0
2
4
6
8
10
1214
16
18
-25 - -15 -10 -5 0
O‹ C‰·“ ( )
î – {» ˛ ¸
’ g – [ ” \ — Í
(
0
2
4
6
8
10
1214
16
18
-25 -20 -15 -10 -5 0
O‹ C‰·“ . ( )
Ę ’ g ’ g – [ ” \ — Í (
cataloguespecifications
Basic cycle Zuba-Dan
Heatingcapacity(kW)
Heatingcapacity(kW)
Ambient temperature (oC) Ambient temperature (oC)
5. FT Result (1): Office building in Asahikawa City
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 35/43
<with Injection>*Indoor outlet temperature
in stable condition>>> more than 50oC
*To reach indoor outlet temperatureof 45oC>>> takes only about 10 minutes
(when unit starts runningat the ambient temp of -15oC andat the indoor room temp of 23oC)
<Shorter start up>about ½ of conventional model
0
10
20
30
40
50
60
0 5 10 15 20 25Timemmin.n
I n d o o r U n i t D i s c h a r g e @ T e m p . m
Ž n Injection Cycle
Normal Cycle
45Ž
5. FT Result (1): Office building in Asahikawa City<Quicker Start up in Heating operation>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 36/43
-30
-20
-10
0
10
20
30
40
50
60
12:00 14:00 16:00 18:00 20:00 22:00 0:00 2:00 4:00 6:00 8:00 10:00
Timemhourn
T e m p .
m
Ž n
Ž “ŕ Źo ‰· “x Ž “ŕ ‰· “x ŠO ‹C ‰· “x
<data taken between 25 Jan 2004 (noon) and 26 Jan 2005 (noon)>
<ambient temp.: -20oC>(1)continuous operation of more than 150 min.
(2)Defrosting only for about 3 minutes.
(1) (2)
indoor outlet temp.
indoor roomtemp.
ambienttemp.
5. FT Result (1): Office building in Asahikawa City<Defrosting characteristics>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 37/43
As the ambient temp. decreases (below 0oC), the average heating operation ratio increases.>>> The operation ratio improves more by extending the continuous operation duration
with no frost on the coil.
<Heating operation ratio>
(Heating operation duration – Defrost duration) /(Heating operation duration)
90%
92%
94%
96%
98%
100%
-25 -20 -15 -10 -5 0
î – { TC N ׯĽ- ˛ ĽŢ޸Ľ® » ˛ ¸
Š O‹ C‰·“ x.( )
‰ ^ “ ] —
operationratio
minimum temperature in a day
Basic cycle Flash Injection cycle
5. FT Result (1): Office building in Asahikawa City<Defrosting characteristics (operation ratio)>
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 38/43
Feb 2006 (wooden building, door is opened frequently)
4HP wall mounted type indoor unitfor about 30m2 room.
5. FT Result (2): Station waiting room (in Niigata pref.)
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 39/43
-10
-5
0
5
10
15
20
25
30
35
40
45
50
0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 0:00
Indoor Temp.
Ambient Temp.
Outlet Temp.
Defrost (5 times in 12 hours)
Room Temp.
lowered by 2oC
during defrost
Exceeds 45oC in 18 min. from start up.(Room temp. at start up was about 8oC)
(
)
From 06.20 am to 18.30 on 12 Feb 2006.Humidity: 60 – 80 %
Much better comfort can be achieved by ‘quicker start up of heatingoperation’ and ‘improved defrost control’.
5. FT Result (2): Station waiting room (in Niigata pref.)
<Measured Data>
Temp.
(o
C)
Hours (o’clock)
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 40/43
6. Summary
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 41/43
(1)Improved Heating Performance*High heating performance & high COP achieved by Flash Injection.*Operation range extended down to -25oC.
(2)Better Comfort*Start up and Recovery from defrost are improved very much
by Injection together with Receiver circuit.*Defrosting frequency at below 0oC ambient is reduced to about 1/3.
(3)Exsisting piping can be reusedeven though the compressor was broken down.
*Since its launch in July 2005, Zuba-Dan has beenhighly appreciated in cold regions such as in Hokkaido.
*Zuba-Dan technology has also been adopted toour City Multi (VRF) since December 2006.
6. Summary: Following functions are realized as the A/C for cold regions
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 42/43
For which application do you need ZubaDAN?
Can you use Zuba Dan Air to Air without cooling function?
How do you calculate the cooling and heating capacity
What do you expect from ZubaDan?
ZubaDan
Which price is accaptable in comparison to Power Inverter?5% 10% 20% 30% 40% 50 %
7/27/2019 Mitsubishi Electric Zuba-Dan
http://slidepdf.com/reader/full/mitsubishi-electric-zuba-dan 43/43
Thank you very much!