MITSUBISHI F / F1 / F2Serial Communications
Procedure for connecting PLC to PC
Requires: F2-20F1 & PCX-KIT1
And MELSEC MEDOC®
Click to Begin Presentation….
![Page 2: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/2.jpg)
Components Needed:
• Programming Software for PC – – MELSEC MEDOC
![Page 3: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/3.jpg)
• Insure that MELSEC MEDOC has been installed on your laptop or desktop PC. When started, the initial screen should appear like this:
MEDOC Programming Software
![Page 4: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/4.jpg)
Components Needed:
• 1) Programming Software:– MELSEC MEDOC
• 2) Interface (I/F) to connect to programming port on F / F1 / F2
![Page 5: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/5.jpg)
F2-20GF1 I/F
![Page 6: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/6.jpg)
F2-20GF1 I/F
![Page 7: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/7.jpg)
F2-20GF1 I/FThis device is obsolete and quite rare.There were at least two other Interface units, either of which would work in place of the F2-20GF1.They are F-LINK and A-LINK. As these are so rare, we will concentrate on the F2-20GF1 for this procedure.
![Page 8: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/8.jpg)
Components Needed:
• 1) Programming Software:– MELSEC MEDOC
• 2) Interface (I/F) to connect to programming port on F / F1 / F2
•3) Serial Protocol Converter – i.e. PCX-KIT1.
![Page 9: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/9.jpg)
PCX-KIT1
![Page 10: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/10.jpg)
PCX-KIT1
![Page 11: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/11.jpg)
PCX-KIT1This kit from Mitsubishi Tech Support incorporates a connector (adapter) which:
connects to the DB25 connector on top of the F2-20GF1,
Converts the Serial Protocol from RS422 to RS232C,
Provides Power (12VDC) to the Converter,
And, Provides connection (DB9) to your computer.
![Page 12: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/12.jpg)
PCX-KIT1
• 1) Remove the access cover on your Mitsubishi PLC.
![Page 13: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/13.jpg)
Mount F2-20GF1
• The F2-20GF1 mounts on the port (also used for hand-held programmer). The two blue connectors fit together, and the two “sliders” on each side of the F2-20GF1 hold the I/F securely to the PLC.
• Note the end of the F2-20GF1 is flush with the end of the PLC (mentioned just as an aid to positioning).
![Page 14: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/14.jpg)
F2-20GF1 Mounting
![Page 15: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/15.jpg)
F2-20GF1 Mounting
![Page 16: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/16.jpg)
F2-20GF1NOTE That the DIP switches are set to 19.2K BAUD. The setting of this DIP switch should agree with the BAUD rate you choose in MEDOC (Transfer) Setup!!!
![Page 17: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/17.jpg)
Connection…
• 1 Install F2-20GF1 on PLC• 2 Slide “tabs” to secure I/F on PLC• 3 Connect cable to I/F
![Page 18: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/18.jpg)
What We Have So Far…
![Page 19: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/19.jpg)
12VDC Power
WAIT TO PLUG IT IN, BUT DON’T FORGET TO…..
![Page 20: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/20.jpg)
Connection…• 1 Install F2-20GF1 on PLC• 2 Slide “tabs” to secure I/F on PLC• 3 Connect cable to I/F• 4 Plug 12VDC Transformer into
120VAC source.• 5 Insure that connections are secure
on “electronics box” (the actual I/F).• 6 Connect I/F to your PC COM Port.
![Page 21: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/21.jpg)
Complete the Connection !
• Your installation should like something like this…
![Page 22: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/22.jpg)
Connect the Power !
• Now is the right time to connect the 12VDC to the I/F…
![Page 23: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/23.jpg)
F2-20GF1 in Action.
Briefly, all the RED LEDs come on, then after the F2-20GF1 determines which unit to which it is connected, that LED comes on solid. In this case, the F1/F2 LED is lit.
![Page 24: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/24.jpg)
Putting It All Together…
• You’ve got MEDOC Running on your PC…
• You’ve got the F2-20GF1 and the PCX-KIT1 connected from the PC to the PLC…
• And you’ve remembered to plug in the 12VDC …
![Page 25: MITSUBISHI F / F1 / F2 Serial Communications Procedure for connecting PLC to PC Requires: F2-20F1 & PCX-KIT1 And MELSEC MEDOC ® Click to Begin Presentation…](https://reader037.vdocument.in/reader037/viewer/2022102504/55176bbf5503463e368b4aa0/html5/thumbnails/25.jpg)
Now the hard part begins!
• We at Lighthouse PLCs, Inc. hope you will benefit from this tutorial/primer.
• Communications with the older Mitsubishi (as well as other brand) PLCs is rapidly becoming a lost art.
• And, relevant manuals and documentation are becoming as rare as the PLCs themselves.