mn woodsolutions bcd220-1-fireresistance design-1hr ......designs in section 721designs in section...

37
Fire Resistance Design for Wood Fire-Resistance Design for Wood Construction - BCD 220-1 James B. Smith, P.E. Midwest Regional Manager American Wood Council Copyright This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of AWC is prohibited AWC is prohibited. © American Wood Council 2016 2

Upload: others

Post on 15-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire Resistance Design for WoodFire-Resistance Design for Wood Construction - BCD 220-1James B. Smith, P.E.Midwest Regional ManagerAmerican Wood Council

Copyright

This presentation is protected by US and International Copyright laws. Reproduction,

distribution, display and use of the presentation without written permission of

AWC is prohibitedAWC is prohibited.

© American Wood Council 2016

2

Page 2: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

DescriptionDetermining the proper code application for wood-framefi bli b h ll i d i ft f thfire assemblies can be challenging and is often furthercomplicated with increases in a project’s size and scale.In a building environment where the ability to maximizeheight and area is key to cost effectiveness, designersmust understand the gamut of fire protectiong pconsiderations applicable to mid- and low-rise woodstructures. This presentation will include coderequirements, compliance options and nuances relatedto assembly selection for required fire-resistance-ratedfloor/ceiling assemblies exterior walls fire barriers firefloor/ceiling assemblies, exterior walls, fire barriers, firepartitions, and fire walls. Topics will include distinctionsbetween fire-resistive elements for separation vs. classof construction. 3

Learning Objectives

1. Apply code requirements and intent for wood-f fi i d bliframe fire-resistance rated assemblies.

2. Discuss the differences in exterior walls, fire walls, fire barriers, and fire partitions considering performance expectations, code requirements and appropriate applicationrequirements, and appropriate application.

3. Understand the paths to achieving code-compliant, fire-resistance rated wood-frame assemblies as outlined by the 2015 IBC.

4. Recognize important nuances in the various methods for demonstrating fire-resistance including: tested assemblies, prescriptive designs, calculations, and engineering analysis. 4

Page 3: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Outline

• Code Overview• Code Overview• Background• Fire-resistance

building elementsbuilding elements• Achieving Fire-

Resistance

5

International Building Code

The IBC• Controls building size• Regulates types of

materialsmaterials• Stipulates fire-

resistance

6

Page 4: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

International Building Code

Allowable heights & areas determined by

• Tabular values• Factors allowing• Factors allowing

increases• Frontage• Sprinkler Systems

Special Provisions IBC• Special Provisions IBC 510

7

Allowable Heights & AreasAllowable area is based uponupon

• Use of building• Type of construction• Frontage• Existence of sprinkler

systemsTabular areas establishminimum allowable building areas that can be increased byareas that can be increased by added fire safety features -frontage and/or frontage.

8

Page 5: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Allowable Heights & Areas

Each occupancy groupEach occupancy group presents a different level of fire and life safety risk:

N b f t• Number of occupants• Capability of occupants• Fuel load

9

Allowable Heights & AreasAllowable heights and areas are based on a concept of equivalent risk, involving three p q , ginterdependent considerations

• level of fire hazard likely to be associated with the occupancy

• nature of contents associated with the use• nature of contents associated with the use• level of overall fire protection provided by the

• Type of construction• Setbacks of the building from other structures

(exposure)• Sprinklers and life safety systems• Other code trade-offs 10

Page 6: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Table 601 Fire-Resistance Rating Requirements For Building Elements (hours)

Building Elements

Building Elements (hours)

BUILDING ELEMENTTYPE I TYPE II TYPE III

TYPE

IVTYPE V

A B Ad B Ad B HT Ad B

Primary structural frameg

( )(see Section 202)

3a 2a 1 0 1 0 HT 1 0

Bearing walls, Exteriorf, g

Interior 3

3a2

2a1

1

0

0

2

1

2

0

2

1/HT

1

1

0

0

11

Nonbearing walls and

partitions, ExteriorSee Table 602

Nonbearing walls and

partitions, Interiore

0 0 0 0 0 0See

Section 0 0

Exterior Walls

12

Page 7: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

• Define separate buildings for allowable building size (706)

Fire Walls (706)

size (706)• Not fire barriers (707)• Not fire partitions (708)• Not smoke barriers, smoke partitions or horizontal

assembliesassemblies• Table 706.4 gives required ratings based on occupancy

13

• Type V construction

Fire Walls (706.3)

• Fire walls may be wood frame

• Types I, II, III and IV construction• Fire walls must be of noncombustible materials

in accordance with Section 706.3

14

Page 8: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

• A fire-resistance-rated wall assembly of materials

Fire Barrier (707)

designed to restrict the spread of fire in which continuity is maintained

• Of materials permitted by the building type of construction

• Fire-resistance rating 707.3 - specific ratings as indicated for shaft enclosures, interior exit stairways and ramp, enclosed exit access stairways, exit passageway, horizontal exit, atriums, incidental uses, control areas, separated occupancies fire areasseparated occupancies, fire areas

15

Fire-resistance rating for separation of fire

Fire Barrier (707)

areas per table 707.3.10

16

Page 9: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Separation of Occupancies

17

• A vertical assembly of materials designed to restrict the spread of fire in which openings are

Fire Partition (708)

restrict the spread of fire in which openings are protected.

• Wall assemblies for:• Separation walls for Group I-1, R-1, R-2 and R-3 per section

420 2420.2• Walls separating tenant spaces in covered and open mall

buildings per section 402.4.2.1• Corridor walls per section 1020.1

El t l bb ti ti 3006 2• Elevator lobby separation per section 3006.2• Egress balconies per section 1019.2

18

Page 10: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

• A vertical assembly of materials designed to restrict the spread of fire in which openings are

Fire Partition (708)

restrict the spread of fire in which openings are protected. cont.

• Of materials permitted by the building type of construction

• Fire-resistance rating 708.3 not less than 1 hour.

• See exceptions for corridor walls, dwelling unit separations, and sleeping unit separations

19

• A continuous membrane, either vertical or

Smoke Barriers (709)

horizontal, such as a wall, floor or ceiling assembly, that is designed and constructed to restrict the movement of smoke.

• Vertical and horizontal smoke barrierse t ca a d o o ta s o e ba e s• Of materials permitted by the building type of

construction• 1 hour fire-resistance rating Exception: Smoke barriers

constructed of minimum 0.10- inch-thick (2.5 mm) steel in b ld ( )Group I-3 buildings. (709.3)

20

Page 11: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

• A fire-resistance-rated floor or roof assembly of

Horizontal Assemblies (711)

materials designed to restrict the spread of fire in which continuity is maintained.

• Of materials permitted by the building type of construction

• Fire-resistance rating - specific ratings as indicated 711.2.4 but not less than that for building type of construction : separating mixed occupancies, fire areas, dwelling units and sleeping units,

k t t i id t l th tismoke compartments, incidental uses, other separations.

21

Outline

• Code Overview• Code Overview• Background• Fire-resistance

building elementsbuilding elements• Achieving Fire-

Resistance

22

Page 12: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

1 Tested fire assembly (ASTM E 119 or UL 263)

Methods for Determining Fire-Resistance (703)

1. Tested fire assembly (ASTM E 119 or UL 263)2. Fire-resistance designs documented in approved

sources 3. Prescriptive assemblies using of fire-resistance-rated

designs in Section 721designs in Section 7214. Calculation of fire-resistance per Section 7225. Engineering analysis based on a comparison of

building element, component or assembly designs that have been tested

6. Alternative protection methods per Section 104.117. Fire-resistance designs certified by an approved

agency23

Fire TestsTested fire assembly (ASTM E 119)

http://www.awc.org/Code-Officials/2012-IBC-Challenges/# 24

Page 13: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire TestAmerican Wood CouncilASTM E119 Fire Endurance Half-lapped –Test• 5-Ply CLT (approx. 7” thick)• 5/8” Type X GWB each side• Sought 2 hour rating• RESULTS: 3 hours 6 minutes

ppmiddle of panel

25

• Based on testing to the ASTM E 119 or UL 263 d d

Documented in Approved Source

standard• Choose listed assemblies from fire-resistance

publications or directories

26

Page 14: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Documented in Approved SourceFire-resistance designs - AWC Design for Code Acceptance Pubs -Acceptance Pubs

27

Documented in Approved Source

DCA 3DCA 3Fire-Resistive Wood Wall and Floor/Ceiling Assemblies• ASTM E 119 or UL 263• NFPA 251

28

Page 15: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Documented in Approved Source

29

Documented in Approved Source

30

Page 16: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Documented in Approved Source

31

Fire-resistance of certain wood assemblies is prescribed in Section 721 based on testing using ASTM E 119 or UL 263

Prescriptive Fire-Resistance Rated Assemblies

32

Page 17: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Prescriptive Fire-Resistance-Rated Assemblies

Fire-resistance of certain wood assemblies is ib d i S ti 721 b d t ti iprescribed in Section 721 based on testing using

ASTM E 119 or UL 263

• Fire-resistance of wood frame assemblies

Calculated Resistance (703.3)

also may be calculated based on the known fire-resistance of the components, using the provisions of Section 722.6

• 1.0 hour maximum0 ou a u

34

Page 18: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Calculated Fire Resistance (722.6)

DCA 4DCA 4 Component Additive Method (CAM) for Calculating and Demonstrating AssemblyDemonstrating Assembly Fire Endurance

35

CAM

Calculated Fire Resistance (722.6)

Membrane Table

Time AssignedTime Assigned to Protective Membranes

•IBC Table 722 6 2(1)722.6.2(1)

36

Page 19: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

CAM Wood Component Table

Calculated Fire Resistance (722.6)

CAM Wood Component TableAssigned Times for Wood ComponentsIBC Table 722.6.2(2)

37

CAM Wall Membranes

Calculated Fire Resistance (722.6)

Membranes on Exterior Face of WallsIBC Table 722.6.2(3)

38

Page 20: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

CAM Cavity Insulation Table

Calculated Fire Resistance (722.6)

yAssigned Times for Insulation of Cavity

•IBC Table 722.6.2(5)

39

Interior Wall

CAM Example 1

Interior Wall

40

Page 21: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Floor/Ceiling with Wood Joists

CAM Example 2

41

Floor/Ceiling with I-joists

CAM Example 3

/ g j

42

Page 22: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Columns within Wall Assembly

IBC 704.2 and 704.3 No addition

43

al fireproofing required for the co

lumnin the assembly

• 704.2 Column protection (IBC 2018 text)

Columns within Wall Assembly

• “Exception: Columns that meet the limitations of Section 704.4.1”

• 704.4.1 Light-frame construction (IBC 2018 text)• “Studs columns and boundary elements that• Studs, columns, and boundary elements that

are integral elements in walls of light-frame construction, and are located entirely between the top and bottom plates or tracks shall be permitted to have required fire-resistance ratings provided by the membrane protection provided for the wall.”

44

Page 23: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Structural Stability 705.6

2 hour wall

1 hour floor

2 hour wall

45

Calculated Fire-Resistance

Fire-resistance up to two hours

• Columns

• Beams

• Tension Members…

e s o e be s

• ASD only

Products

• Lumber

Gl l

46

• Glulam

• SCL

• Decking

• CLT

Page 24: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire Design of Exposed Wood Members

Beam Fire Test ASTM E 119

47

Calculated Fire-Resistance (722)

Chapter 16 of the National Design Specification® (NDS®)

48

Page 25: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Effective char rate

Fire Design of Exposed Wood Members

lid l l d l i d f d l i dsolid sawn, structural glued laminated softwood, laminated veneer lumber, parallel strand lumber, and laminated strand lumber

49

Effective char depth

Fire Design of Exposed Wood Members

C16.2.1.2 Using Equation 16.2-1 and assuming nominal char rate, n or 1.5 inches/hr:

50

Page 26: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire Design of Exposed Wood Members

51

CLT manufactured with laminations of equal thickness

Fire Design of Exposed Wood Members

CLT manufactured with laminations of equal thickness

52

Page 27: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Technical Report No. 10 (TR10)

Calculated Resistance (722)

(TR10)• contains background and

examples for the method

53

TR-10 Design Example

TR10 containsTR10 contains:• decking• beam

l• column• CLT• etc

54

Page 28: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire-Resistance of Exposed Wood

16 3 Wood Connections16.3 Wood Connections• Where fire endurance is required,

connectors and fasteners shall be protected from fire exposure

• Wood• Fire-rated gypsum board

55

Connections

Beam-to-column(Protection provide(Protection provided by membrane)

Source: AWC TR-10 56

Page 29: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Connections

Concealed

Source: AWC TR-10

Concealedbeam-to-column

57

Connections

Source: AWC TR-10

Beam supporting one hour rated ceiling58

Page 30: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Connections

Covered column connection

Source: AWC TR-10 59

Connections

Concealed beam-to-

girder connection

Source: AWC TR-10 60

Page 31: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Fire Design of Exposed Wood Members

722.6.3 deleted

Limited to 1-Hour – IBC 722.6.1.1Si lifi d h

722.6.3 deleted NOT INCLUDED IN 2015 IBC

61

Simplified approachOnly Beams/Columns

Fire Design of Exposed Wood Members

DCA 2Design of Fire-Resistive Exposed Wood Members• Glued-laminated

timber, sawn lumber, & timber decking

• 1 1 5 & 2 hours• 1, 1.5 & 2 hours

62

Page 32: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

May be used in almost all occupancies.

Wood Interior Finish (Chapter 8)

63

Wood Interior Finish Classification System

Nonsprinklered Buildings: Minimum Interior FinishNonsprinklered Buildings: Minimum Interior Finish Classification by Occupancy

Location Minimum Interior Finish Classification

Ab B CAb B C

Exit enclosures and exit

passagewaysc

A, B, E, I, M, R-1, R-4

F, S, R-2 R-3

64

Corridors Ad, I-2, I-3,

I-4

B, E, M, S,I-1, R-1, R-2, R-4

F, R-3

(Table 803.11)

Page 33: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Wood Interior Finish Classification System

Sprinklered Buildings: Minimum Interior FinishSprinklered Buildings: Minimum Interior Finish Classification by Occupancya, b

Location Minimum Interior Finish Classification

A B CA Bc C

Exit enclosures and exit

passagewaysd

I-3 A, B, E, M, R-1,R-4, I-1, I-2, I-4

F, R-2, R-3, S

65

Corridors I-3 A, I-2, I-4B, E, F, M,R, S, I-1

A

(Table 803.11)

Wood Interior Finish (803)• Most wood species

lif Cl Cqualify as Class C or Class B.

• Wood boards and panels may meet Class A criteria whenA criteria when pressure treated with a fire-retardant chemical.

• AWC’s DCA-1

66

• AWC s DCA-1 documents the performance.

Page 34: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Flame Spread

Class I or A 0 ‐ 25

Class II or B 26 ‐ 75

fire retardant treated wood

redwoodcedard l f

pine (other than lodge pole, ponderosa & red)

most other wood speciessoftwood plywood

Class III or C 76 ‐ 200

douglas‐firhem‐fir

spruce

softwood plywoodhardwood plywoodparticleboard

67

Flame Spread

E84 T l• E84 Tunnel Apparatus

68

Page 35: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Smoke Developed Index

A smoke-developed pindex was also measured for some of the wood products listed in DCA 1. None of the products testedof the products tested exceeded the limiting value of 450 commonly used in building code regulationsregulations.

69

Wood Interior Finish – Exceptions

• Traditional wood floor covering is exempt from interior floor finish requirements (804.1).

• Exposed portions of Type IV structural members also

70

members also exempt (803.3).

Page 36: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

Design for Code Acceptance Pubs.

71

Available for free download www.awc.org

• Special occupancies

2015 Code Conforming Wood Design

• Fire-resistance• Building features• Wood in noncombustible

construction types• Structural considerations• Precautions during

construction• Also available for 2009 and

2012 IBC2012 IBC• http://awc.org/codes-

standards/buildingcodes/ccwd 72

Page 37: MN WoodSolutions BCD220-1-FireResistance Design-1HR ......designs in Section 721designs in Section 721 4. Calculation of fire-res istance per Section 722 5. Engineering analysis based

• This concludes The American Institute of Architects Continuing Education Systems Course

Questions?

Education Systems Course

American Wood [email protected]

73

Questions

J B S i h P EJames B. Smith, P.E.Midwest Regional Manager

[email protected] 635 6635