mnm fatal 2008-13 electrical accident electrical accident august 15, 2008 (arizona) august 15, 2008...

5
MNM Fatal 2008-13 MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician Apprentice Electrician Apprentice 41 years old 41 years old 14 years experience 14 years experience

Upload: lee-harris

Post on 03-Jan-2016

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician

MNM Fatal 2008-13MNM Fatal 2008-13

Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician Apprentice Electrician Apprentice 41 years old41 years old 14 years experience14 years experience

Page 2: MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician

OverviewOverview

The victim was fatally injured when he The victim was fatally injured when he

contacted a 480-volt electrical contacted a 480-volt electrical conductor. He conductor. He

was replacing the ballast in a was replacing the ballast in a floodlight.floodlight.

Page 3: MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician

Energized conductor contacted by victim BallastIn-line fuse

(the other fuse is inside box and out of view)

Page 4: MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician

Root CauseRoot Cause

Management policies and controls were inadequate and failed to ensure that the electrical circuit was deenergized, locked-out, tagged, and tested before work was performed on the circuit.

Page 5: MNM Fatal 2008-13 Electrical Accident Electrical Accident August 15, 2008 (Arizona) August 15, 2008 (Arizona) Copper Operation Copper Operation Electrician

Best PracticesBest Practices

De-energize power from the circuit and De-energize power from the circuit and lock out/tag the switch. lock out/tag the switch.

Verify that the circuit is de-energized by Verify that the circuit is de-energized by testing the circuit for voltage using testing the circuit for voltage using properly rated test equipment. properly rated test equipment.

Closely supervise and monitor persons Closely supervise and monitor persons with limited electrical experience. with limited electrical experience.

Establish and follow safe work procedures Establish and follow safe work procedures when working with less experienced when working with less experienced miners. miners.