Installation and Operation Handbook Contents
HA026639 Issue 1 Jul-99. Applies to 2216e Controller software versions 3.03 i
MODEL 2216eTEMPERATURE CONTROLLER
INSTALLATION AND OPERATION HANDBOOK
Contents Page
Chapter 1 OPERATION ............................................................. 1-1
Chapter 2 INSTALLATION ........................................................... 2-1
Chapter 3 ACCESS LEVELS ...................................................... 3-1
Chapter 4 TUNING ..................................................................... 4-1
Chapter 5 CONFIGURATION ...................................................... 5-1
Chapter 6 USER CALIBRATION ................................................. 6-1
Chapter 7 ALARM CONFIGURATION ......................................... 7-1
Appendix A UNDERSTANDING THE ORDERING CODE ............. A-1
Appendix B SAFETY & EMC INFORMATION ............................ B-1
TECHNICAL SPECIFICATION ............................ B-6
Appendix C ADDRESS ............................ C-1
Appendix D VALVE POSITIONER ............................ D-1
Appendix E LOAD CURRENT MONITORING ………………… E-1
Appendix F RETRANSMISSION ………………… F-1
“This product is covered by one or more of the following US Patents:5,484,206 and 5,793,754; Additional patents pending.
PDSIO is a registered trademark of Eurotherm.
INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor™are trademarks of Eurotherm.”
Installation and Operation Handbook Operation
2216e Controller 1-1
Chapter 1 OPERATION
PAGE
Front Panel Layout .................................................................. 1-2
GETTING STARTED .................................................................. 1-4
Navigation Diagram .................................................................. 1-10
Parameter Tables .................................................................. 1-12
Setting Alarm Levels .................................................................. 1-18
Diagnostic Alarms .................................................................. 1-19
Installation and Operation Handbook Operation
1-2 2216e Controller
FRONT PANEL LAYOUT
Upper readout
Lower readout
Setpoint ratelimit active
DownButton
Manual mode
PageButton
ScrollButton
UpButton
Remote SetpointPDSIO®
Output 2
Setpoint 2 active
2216e
OP1
OP2
SP2
REM
Output 1
RUN
MAN
Fig 1-1 Model 2216e front panel layout
Installation and Operation Handbook Operation
2216e Controller 1-3
Button orindicator
Name Explanation
OP1 Output 1When lit, it indicates that heating output is on.
OP2 Output 2When lit, it indicates that cooling output is on.
SP2 Setpoint 2When lit, this indicates that Setpoint 2 has beenselected.
REM Remote SetpointWhen lit, this indicates that the PDSIO® remoteSetpoint input has been selected. ‘REM’ is alsoused to indicate that user comms is active.
MAN Manual lightWhen lit, it indicates that manual mode hasbeen selected
RUN Run lightWhen lit, it indicates that Setpoint rate limit isactive.
Page button Press to select a new list of parameters.
Scroll button Press to select a new parameter in a list.
Down button Press to decrease a value in the lower readout.
Up button Press to increase a value in lower readout.
Figure 1.3 Controller buttons and indicators
For Valve Positioning, please refer to Appendix D ‘Motorised Valve Control’NOTE
Installation and Operation Handbook Operation
1-4 2216e Controller
GETTING STARTED
Thank you for selecting the EUROTHERM 2216e controller.This section shows the principle of operation.
VIEWING THE PROCESS VALUE and SETPOINT
Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3second self-test sequence, this is the display you will see,
Figure 1.4 The “Home Display”
The display may flash an alarm message. Refer to the Parameter Tableslater in this chapter for a complete list and meaning of the messages.
TO ADJUST THE SETPOINT
Figure 1.5 The lower readout shows the setpoint
After 2 seconds the lower readout will ‘blink’ indicating that the new value has been accepted.For everyday use you may not need to do anymore than this.
NOTE
Output 1Actual Temperature(Process Value)
Output 2
Required Temperature (Setpoint)
OP1
OP2
SP2
Rem
Press and hold toincrease temperature
Press and hold todecrease temperature
OP1
OP2
SP2
Rem
Installation and Operation Handbook Operation
2216e Controller 1-5
VIEWING THE DISPLAY UNITS
Figure 1.6 Pressing or will flash the display units for 0.5 secs
If you get lost, pressing and together will return you to theHome display
USE OF THE “SCROLL” BUTTON
Pressing the scroll button will display the output power level. Continued pressing willdisplay further parameters in the operator scroll list.
Figure 1-7 Upper readout is parameter name. Lower is value
Momentarilypress eitherbutton
NOTE
Keep pressing to return to Home display or select furtherparameters (if available)
2nd press
3rd press
Output
Actual output level %
Manual/Auto
Actual state
Display Units Degrees Centigrade Degrees Farenheit Degrees KelvinNo units - Linear inputs
.05 sec.
Installation and Operation Handbook Operation
1-6 2216e Controller
USE OF THE PAGE BUTTON
The “PAGE” button accesses parameter LISTS.Parameters are settings in the instrument which, generally, can be changed by the user to suitthe process. Examples are: Alarms, Self Tune, etc. They are found under headings calledLISTS and a full set is given later in this chapter.
Figure 1.8 Press to choose a parameter list
The actual list headings may be longer or shorter than indicated above and you cancustomise this for the operator’s convenience in EDIT level, Chapter 3.
NOTE
1st press
0.2 sec.
Keep pressing toselect more list headingscontinue around a continuous loop
3rd press2nd press
Installation and Operation Handbook Operation
2216e Controller 1-7
PARAMETER LISTS
Press to choose a LIST - “ALARMS” is a good one. This list allows you to set thealarm trip levels. The parameters which appear in the list will vary according to theconfiguration of your controller.
Figure 1.9 Choose a list. Press to select a parameter
If, at any time, no key is pressed within 45 seconds, the display will alwaysreturn to the “HOME” display.
NOTE
or tochange trip level
or tochange trip level
1st press
2nd press
0.2 sec.
There are 4 alarms in thecontroller. The firstcharacter is the alarmnumber. The followingthree letters indicatealarm type as follows: Full Scale Low Full Scale High Deviation High Deviation Low Deviation Band Low current High currentDisabled alarms will notbe displayed.Chapter 7 gives a fulldescription of alarms.
Alarm List
Alarm 1
Now pressthe SCROLLbutton
2nd press
Keep pressing1. to scroll through further parameters2. to return to list header
Alarm 2
Installation and Operation Handbook Operation
1-8 2216e Controller
OPERATING MODES
The controller can be used in two modes:Automatic mode - in which the output power is automatically adjusted to hold thetemperature at the required value. The controller normally operates in this mode.Manual mode - in which the output is manually adjusted by the Operator. In this mode the‘MAN’ light will be on. Unit must be in full access to see ‘MAN’.
One other mode is available:Remote setpoint - The setpoint is generated as an input signal from a master 2000 seriescontroller. In this mode the REM light is on.
AUTO or MANUAL SELECT
Figure 1.10 Auto/Manual select
or to select
2 sec.
1st press
Output
Actual output level %
Manual/Auto
automatic mode manual mode
2nd press
3rd press
Keep pressingto return to “HOME”display
Installation and Operation Handbook Operation
2216e Controller 1-9
MANUAL ADJUSTMENT OF OUTPUT POWER
Figure 1.11 The “Home Display” in manual mode
Manual mode is generally used for test and commissioning purposes, take carenot to leave the controller in this mode since damage or personal injury couldoccur.
SUMMARY
To step through list headers press the Page button until the required header is obtained
To step through parameters within a particular list press the Scroll button until therequired parameter is obtained
To change the value (or state) of a parameterpress the Raise button or the Lower button
The remainder of this chapter provides a complete list of all parameters available.
Actual Temperature (Process Value)
OP1 OP2
Output Power Demand
Manual Indicator onMAN
Press and hold toincrease power
Press and hold todecrease power
NOTE
OP1
OP2
OP1
REM
Installation and Operation Handbook Operation
1-10 2216e Controller
NAVIGATION DIAGRAM (Part A)
The navigation diagram shows a full list ofpossible parameters. However, some may notappear because they are dependent upon theparticular controller variant.
Figure 1.12a Navigation diagram
HomeList
PID(1)
List
AlarmList
AutotuneList
SetpointList
5
2
2
2
2
8
8
8
3
3
8
8
3
3
!4
"9
#$
%&'
$()
*
Installation and Operation Handbook Operation
2216e Controller 1-11
NAVIGATION DIAGRAM (Part B)
The shaded boxes are normally hidden in Operator level. To see all the availableparameters you must select Full level. See Chapter 3, Access Levels
Figure 1.12b Navigation diagram
InputList
OutputList
CommsList
AccessList
On OffList(1)
7
7
&
Notes:1. Either the PID list or the On/Off list will be present
depending upon the type of control in use.2. The last three characters depend upon the type of alarm
configured3. Absolute setpoint limits are set in configuration, see Chapter
5.4. VPOS only for VP. Refer to VP Appendix D.5. Amps is Mode 2 or Mode 5 PDSIO.6. mtr used for VP version. Refer to VP Appendix D.7. Beware! Used for calibration. See chapter 6.8. Is only available if using PDSIO® comms in the HA slot.9. WSP is available if using ramp to setpoint.
&
%&
%&
$
*
Return toHome Display
6
+7
+
!
Installation and Operation Handbook Operation
1-12 2216e Controller
PARAMETER TABLES
Name Parameter Description Default Value Minimum Maximum Units Customer Setting
UK USA Value Value
Home List
Home Measured Value and Setpoint(SP) SP=25°C SP=75°F as display
Valve positioner output power % of mtr
% Output Level %
Working setpoint as display
Setpoint as display
Heater current (PDSIO modes 2) Amps
Auto/manual select
Configure lower readout of home display None, StD,AmPS, OP, stat,vPoS
Customer ID
Additional parameters may appear in the Home display if the ‘promote’ feature has been used (see Edit Level, Chapter 3).
Installation and Operation Handbook Operation
2216e Controller 1-13
Name Parameter Description Default Value Minimum Maximum Units Customer Setting
UK USA Value Value
Alarm List
Alarm 1 set point value as display
Alarm 2 set point value as display
Alarm 3 set point value as display
Alarm 4 set point value as display
In place of dashes, the last three characters indicate the alarm type, as follows:
Full Scale High alarm as display
Full Scale Low alarm as display
Deviation band alarm as display
Deviation High alarm as display
Deviation Low alarm as display
Low current alarm Amps
High current alarm Amps
Hysterisis as display
Loop break time secs
Installation and Operation Handbook Operation
1-14 2216e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer Settings
UK USA Value Value
!! Autotune List
! Self tune enable !
Automatic droop compensation (Manual Reset)enable (only present if is set to OFF)
"! "! "!
PID List
Proportional band as display
Integral time # seconds
Derivative time # seconds
Manual reset (appears when ti set to OFF) %
Cutback low as display
Cutback high as display
Relative cool gain (set 1)
Installation and Operation Handbook Operation
2216e Controller 1-15
Name Parameter Description Default Value Minimum Maximum Units Customer Settings
UK USA Value Value
Set Point List
Select SP1 or SP2 SP1 SP2
Local or remote setpoint select Loc rmt
Setpoint 1 value $ % As display range
Setpoint 2 value $ % As display range
Remote setpoint As display range
Local trim As display range
Setpoint 1 low limit As display range
Setpoint 1 high limit As display range
Setpoint 2 low limit As display range
Setpoint 2 high limit As display range
Local setpoint trim low limit # As display range
Local setpoint trim high limit As display range
Setpoint rate limit As display range
& Dwell time 0.1 to 999.9 minutes
! End type ' '
( Program control !'
) Status of program
Installation and Operation Handbook Operation
1-16 2216e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer Settings
UK USA Value Value
Input list
Input filter time constant # # Off* secs
PV Offset as display
The next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.
FACt will re-instate factory settings and disable User Calibration. Default setting FACtUSEr will re-instate any previously set User Calibration offsets and make available User Calibration parameters as follows:
User calibration select none none Hi, Lo, none
* Adjust calibrated reference source
The following two parameters are always present in Full Access level but not in Operator level
+ Cold Junction compensation temperature
, Millivolt input* Do not make adjustments to the * parameter unless you wish to offset the controller calibration.
Installation and Operation Handbook Operation
2216e Controller 1-17
Output list Note; If On/Off control is configured only , ! and ! will appear in the following list
Low (power) output limit (cool) %
High (power) output limit %
Output setting when in sensor break %1 - Heat cycle time (logic) (relay) secs
! Heat output min. on time (50mS) secs1 - Cool cycle time (logic) (relay) secs
1 ! Cool output min. on time (50mS) secs
VP motor travel time
* A minimum filter time of 1.0 seconds is recommended to provide sufficient noise immunity.1 Are not used for value position control.
Installation and Operation Handbook Operation
1-18 2216e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer Settings
UK USA Value Value
!.!. On/off list
This set of parameters only appear if On/Off control has been configured
/- Heat hysteresis as display
/- Cool hysteresis as display
Heat/Cool dead band as display
C omms list
Communications address $
Access list
Full and Edit level password
( Goto level '''
!
!
! Configuration level password
Installation and Operation Handbook Operation
2216e Controller 1-19
SETTING ALARM LEVELS
Up to 4 Alarms may be configured. Each alarm is given a name to describe its function - seetable below:If an alarm is not used it does not appear in the list below.
In place of dashes,letters indicate alarmtype as follows:
Full Scale Low
Full Scale High
Deviation Band
Deviation High
Deviation Low
Low current
High current
Alarm List
Alarm 1
2nd press
or to change
3rd press
4th press
5th press
Alarm 2
Alarm 3
Alarm 4
Loop break time
or to change
or to change
or to change
or to change
Press to returnto list header
Operation Installation and Operation Handbook
1-20 2216e Controller
Diagnostic alarms
These indicate that a fault exists in either the controller or the connected devices.
Displayshows
What it means What to do about it
Electrically ErasableMemory Error:The value of an operator orconfiguration parameterhas been corrupted.
This fault will automatically take you intoconfiguration level. Check all of theconfiguration parameters before returning tooperator level. Once in operator level, check allof the operator parameters before resumingnormal operation. If the fault persists or occursfrequently, contact Eurotherm Controls.
Sensor Break:Input sensor is unreliableor the input signal is out ofrange.
Check that the sensor is correctly connected.
Loop Break:The feedback loop is opencircuit.
Check that the heating and cooling circuits areworking properly.
Load failureIndication that there is afault in the heating circuitor the solid state relay.
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR)operating in PDSIO® SSRx Load Doctor-seeElectrical installation Chapter 2. It indicateseither an open or short circuit SSR, blown fuse,missing supply or open circuit heater.
Solid state relay failureIndication that there is afault in the solid state relay
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR)operating in PDSIO® SSRx Enhanced LoadDoctor-see Electrical installation Chapter 2. Itindicates either an open or short circuitcondition in the SSR.
Heater failureIndication that there is afault in heating circuit
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR)operating in PDSIO® SSRx Enhanced LoadDoctor -see Electrical installation Chapter 2. Itindicates either a blown fuse, missing supply oropen circuit heater.
Hardware errorIndication that a module isof the wrong type, missingor faulty
Check that the correct modules are fitted.
Figure 1.13a Diagnostic alarms - continued on the next page
Installation and Operation Handbook Operation
2216e Controller 1-21
Diagnostic alarms continued
These indicate that a fault exists in either the controller or the connected devices.
Displayshows
What it means What to do about it
No I/O moduleModules are configured butnot fitted
Fit module
Remote input failure. ThePDSIO® input is opencircuit (PDSIO modes alsoknown as SST SmartSetpoint Transmission)
Check for open or short circuit wiring on thePDSIO® input
Out of Display range, lowreading
Check the value of the display range
Out of Display range, highreading
Check the value of the display range
Error 1: ROM self-test fail Return the controller for repair
Error 2: RAM self-test fail Return the controller for repair
Error 3: Watchdog fail Return the controller for repair
Error 4: Keyboard failureStuck button, or a buttonwas pressed during powerup.
Switch the power off and then on withouttouching any of the controller buttons.
Error 5: Input circuit failure Return the controller for repair*
Power failure. The linevoltage is too low
Check that the supply to the controller is withinthe rated limits
Figure 1.13b Diagnostic alarms
* If the user has disassembled and reassembled the instrument, this error can occur if anyconnectors are not seated properly.
Installation and Operation Handbook Installation
2216e Controller 2-1
Chapter 2 INSTALLATION
PAGE
Instrument Layouts ....................................................... 2-2
Introduction ....................................................... 2-4
Mechanical Installation ....................................................... 2-4
Wiring ....................................................... 2-5
Outputs 1 and 2 Connection ....................................................... 2-7
Communication Connections ....................................................... 2-8
Typical Wiring Diagram ....................................................... 2-9
Installation Installation and Operation Handbook
2-2 2216e Controller
INSTRUMENT LAYOUT
KEY
1. Display screen
2. Latching ears
3. Panel sealing gasket
4. Panel retaining clips
5. Label
6. Sleeve
7. Terminal covers
8. Ratchets
Figure 2-1 2216e 1/16 DIN controller
1
2
2 3
4
4
5
6
8
8
7
Installation and Operation Handbook Installation
2216e Controller 2-3
2204
OP1 OP2
SP2 REM
Outline dimensions Model 2216e
Figure 2-2 Outline dimensions Model 2216e controller
The controller plugs into a plastic sleeve, which in turn fits into the panel cutout shown above.
Panel cutout
45 x 45 -0 +0.8mm
1.77 x 1.77 -0 +0.03in
103mm (4.01in)48mm (1.89in)
48mm1.89in
Recommendedminimumspacing ofcontrollers
38mm(1.5in)
10mm(0.4in)
(Not toscale)
IP65, panel sealing gasket
OP1
OP2
SP2
Re
Installation Installation and Operation Handbook
2-4 2216e Controller
INTRODUCTION
The Model 2216e is a precision temperature controller with self tuning. It has a modularhardware construction which provides two control outputs, one alarm relay and onecommunications port.
Controller labels
The labels on the sides of the controller identify the ordering code, the serial number, and thewiring connections.
Appendix A, Understanding the Ordering Code explains the hardware and softwareconfiguration of your particular controller.
MECHANICAL INSTALLATION
To install the controller
1. Cut the panel to the relevant hole size shown in Figure 2-3 and 2.4.
2. Insert the controller through the front of this cutout.
3. Spring the upper and lower panel retaining clips into place. Secure the controller inposition by holding it level and pushing both retaining clips forward.
If the panel retaining clips subsequently need removing, they can be unhooked fromthe side with either your fingers or a screwdriver
Unplugging and plugging-in the controller
The controller can be unplugged from its sleeve by easing the latching ears outwards andpulling it forward out of the sleeve. When plugging the controller back into its sleeve, ensurethat the latching ears click into place to maintain the IP 65 sealing.
NOTE
Installation and Operation Handbook Installation
2216e Controller 2-5
WIRING
Please read Appendix B, Safety and EMC information before proceeding.
WARNINGPlease ensure that the controller is correctly configured for your application.Incorrect configuration could result in damage to the process being controlled,and/or personal injury. The controller may either have been configured whenordered, or may need configuring now. See Chapter 5, Configuration.
Figure 2-3 Model 2216e wiring connections
* The ground connection is not required for electrical safety but must be connected to satisfyEMC requirements.
Wire Sizes
All electrical connections are made to the screw terminals at the rear of the controller. Theyaccept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG), and are protected by a hinged cover toprevent hands or metal making accidental contact with live wires. Rear terminals should betightened to a torque of 0.4Nm (3.5 lb in).
Wiring connections
The wiring connections are shown in Figure 2-3.Outputs 1 and 2 are factory fitted modules which can be any one of the types shown in figure2-8. Check the ordering code on the controller side label to determine which have been fitted.
Neutral
Ground*
+PV-
85-264VacOutput 1
Output 2
Line
+
-Pt100
N
VI
V+
V-
L
HB
HC
HD
HE
HF
HA
1B
2A
2B
3A
3B
1A
CommsOutput 3
Installation Installation and Operation Handbook
2-6 2216e Controller
Sensor input connections
The connections for the various types of input are as follows:
Sensor inputs should not be paralleled.
Fig 2-7 Sensor input connections
OUTPUTS 1 AND 2 CONNECTIONS
Outputs 1 and 2 can be any one of the types shown in the table below, configured to performany one of the functions shown.
To check which outputs are installed, and their configuration, refer to the ordering code andthe wiring information on the controller side labels.
Connections
Output 1 Output 2 Possible functions
Module type 1A 1B 2A 2B
Relay: 2-pin(2A, 264 Vac max.)
HeatingCoolingAlarms
Logic: non-isolated*(18Vdc at 24mA)
+ - + - +PDSIO® modes 1or 2 (SSRxLoad Doctor Functions)
HeatingCoolingAlarms
Triac(1A, 30 to 264Vac)
Heating or cooling
DC control: isolated(18Vdc, 20mA max) + -
DC not availablein output 2
PID Heating or cooling
*Logic can also be configured as logic input on module 2A.+PDSIO® Mode 1 & 2 are only supported in Output 1.
Figure 2-8 Outputs 1 and 2 connections
VI
V+
V-
VI
V+
V-
VI
V+
V-
VI
V+
V-
ThermocoupleResistance
thermometer mA inputVolts or mV
inputs
+
-PV
2.49Ωcurrentsenseresistor
Line Load Line Load
NOTE
Installation and Operation Handbook Installation
2216e Controller 2-7
PDSIO® modes
PDSIO® is a proprietary technique developed by Eurotherm for bi-directional communicationover a single pair of wires. There are several operating modes. In SSRx Load Doctor a logic output delivers a power demand signal to a TE10 solid staterelay (SSR) and the SSR responds with a single load circuit failure message.In SSRx Enhanced Load Doctor a logic output delivers a power demand signal to an SSRand the SSR responds with the ON state RMS load current, and two fault messages - SSRfailure or heater circuit failure.
Snubbers
The controller is supplied with ‘snubbers’ (15nF +100Ω) which should be wired across therelay or triac outputs when switching inductive loads such as mechanical contactors andsolenoid valves. The snubbers are used to prolong contact life and to suppress interferencewhen switching such loads.Snubbers pass 0.6mA at 110Vac and 1.2mA at 240Vac, which may be sufficient to hold inhigh impedance relay coils. They should not, therefore, be used in such installations.
WARNINGWhen a relay contact is used in an alarm circuit ensure that the current passing throughthe snubber when the relay contact is open does not hold in low power electrical loadsand thereby interfere with the failsafe operation of the alarm circuit.
COMMUNICATION CONNECTIONS
The communication option can be either of four types shown in the table below
Connection
Communications type HB HC HD HE HF
4-wire EIA-422 serialcommunications*
A’(RX +)
B’(RX -)
Common A(TX +)
B(TX -)
EIA-232 serialcommunications
Not used Not used Common A B
PDSIO™ Setpoint input (SST) Not used Not used Not used Signal Common
2-wire EIA-485 SerialCommunications
Not used Not used Common A(TX +)(RX +)
B(TX -)(RX -)
Figure 2-9 Communication connections
*The 4-wire EIA-422 communication board can be modified to support 2-wire 485communication. Please consult factory.
Installation Installation and Operation Handbook
2-8 2216e Controller
Wiring of EIA-485 serial communication links
Local
LocalEarth
HF +S eries 2000™Controller
Com
Note:All termination res is tors are 220 ohm 1/4W carbon composition.Local grounds are at equipotential. Where equipotential is not available wire intoseparate zones us ing a galvanic isolator.
AB
PC
Universal Convertor
RXT XCom
Com T XRX
Up to 32controllers orInterface Units maybe included on thenetwork
232
Com B A
Com
AB
GalvanicIsolationBarrier
Com
AB
Com
AB
Local Earth
Com
AB
Earth
UniversalConverter
MMI
S eries 2000™Controller
S eries 2000™Controller
For safety reasons ,do not connect tolocal earth here.
HD
HF+
HE
HD
HF+
HE
HE
HD
Figure 2-10 2-wire EIA-485 wiring
Standard EIA-485 is a 2-wire connection which allows up to 32controllers to be multi-dropped from a single communicationslink over a distance of up to 1.2Km. To ensure reliable operationof the communications link, (without data corruption due to noiseor line reflections) the connections between the controller shouldbe made using a twisted pair of wires inside a shielded cablewith the connections terminated with resistors in the mannershown in this diagram. This diagram also shows the use of aconverter to connect the 2-wire EIA-485 link into a standard EIA-232 computer port.
Installation and Operation Handbook Installation
2216e Controller 2-9
TYPICAL WIRING DIAGRAM
Fig 2-8 Typical wiring diagram, Model 2216e Controller
NeutralCooling PowerFuse 1A(T)
Heating power fuse(load dependent)
CoolingSolenoid Valve
Heater
Thermocouple
ControllerFuse2A(T)
Solid StateRelay
such asTE10S+
-
Line
N
V1
V+
V-
L
HB
HC
HD
HE
HF
HA
1B
2A
2B
3A
3B
1A
Comms
Snubber
Installation and Operation Handbook Access Levels
2216e Controller 3-1
Chapter 3 ACCESS LEVELS
PAGE
The Different Access Levels .......................................................... 3-2
Selecting an Access Level .......................................................... 3-3
Edit Level .......................................................... 3-5
Access Levels Installation and Operation Handbook
3-2 2216e Controller
This chapter describes the different levels of access to the operating parameters within the2208e and 2204e controller.
There are three topics:
• THE DIFFERENT ACCESS LEVELS
• SELECTING AN ACCESS LEVEL
• EDIT LEVEL
THE DIFFERENT ACCESS LEVELS
Access level Displayshows
What you can do PasswordProtection
Operator In this level operators can view and adjust thevalue of parameters defined in Edit level (seebelow).
No
Full In this level all the parameters relevant to aparticular configuration are visible. Allalterable parameters may be adjusted.
Yes
Edit In this level you can set which parameters anoperator in Operator level is able to view andadjust. You can hide or reveal complete listsand individual parameters within each list, andyou can make parameters read-only oralterable. You can also promote parametersto the home list. (See Edit level at the end ofthe chapter).
Yes
Configuration This special level allows access to set up thefundamental characteristics of the controller.
Yes
Figure 3-1 Access levels
Installation and Operation Handbook Access Levels
2216e Controller 3-3
SELECTING AN ACCESS LEVEL
Access to Full, Edit or Configuration levels is protected by a password to preventunauthorised access.If you need to change the password, see Chapter 5, Configuration
Access list header
Press until you reach the access list header ‘’.
Press the Scroll button
Password entry
The password is entered from the ‘ display.
Enter the password using the or buttons. Once
the correct password has been entered, there is a two second delayafter which the lower readout will change to show ‘indicating that access is now unlocked.The pass number is set to ‘1’ when the controller is shipped fromthe factory.
Note; A special case exists if the password has been set to ‘’. Inthis case access will be permanently unlocked and the lowerreadout will always show ‘’
Press the Scroll button to proceed to the display.
(If an incorrect password has been entered and the controller is still‘locked’ then pressing Scroll at this point will simply return you tothe list header.)
Note: From this display, you can access “read only”configuration level by pressing and together.
To escape, press and together.
Access Levels Installation and Operation Handbook
3-4 2216e Controller
.
.
Level selection
The display allows you to select the requiredaccess level.
Use and to select from the following displaycodes: Operator level
: Full level Edit level: Configuration level
Press the Scroll button
If you selected either ‘, or level youwill be returned to the ‘ list header in the level thatyou chose. If you selected ‘’, you will get analternative display showing ‘’ in the upper readout(see below).
Configuration password
When the ‘’ display appears, you must enter theConfiguration password in order to gain access toConfiguration level. Do this by repeating the passwordentry procedure described in the previous sectionThe configuration password is set to ‘’ when thecontroller is shipped from the factory. If you need tochange the configuration password, see Chapter 5,Configuration
Press the Scroll button
Configuration level
The first display of configuration is shown. See chapter5, Configuration for details of the configurationparameters.For instructions on leaving configuration level seeChapter 5, Configuration.
Installation and Operation Handbook Access Levels
2216e Controller 3-5
Returning to Operator Level
To return to operator level from either ‘’ or ‘’ level, repeat entry of the passwordand select ‘’ on the ’’ display.In ‘Edit’ level the controller will automatically return to operator level if no button is pressedfor 45 seconds.
EDIT LEVEL
Edit level is used to set which parameters you can see and adjust in Operator level. It alsogives access to the ‘Promote’ feature which allows you to select and add (‘Promote’) up totwelve parameters into the Home display list, thereby giving simple access to commonly usedparameters.
Setting operator access to a parameter
First you must select level, as shown on the previous page.Once in level you select a list or a parameter within a list in the same way as you wouldin Operator or Full level. Τhat is, you move from list header to list header by pressing thePage button, and from parameter to parameter within each list using the Scroll button.However, in Edit level what is displayed is not the value of a selected parameter but a coderepresenting the parameter’s availability in Operator level.
When you have selected the required parameter, use the and buttons to set itsavailability in operator level.There are four codes: Makes a parameter alterable in Operator level Promotes a parameter into the Home display list Makes a parameter or list header read-only (it can be viewed but not altered) Hides a parameter or list header.For example:
The parameter selected is the set point for Alarm2 - Full Scale Low
It will be alterable in Operator level
Access Levels Installation and Operation Handbook
3-6 2216e Controller
Hiding or revealing a complete list
To hide a complete list of parameters, all you have to do is hide the list header. If a list headeris selected only two selections are available: and .(It is not possible to hide the ‘’ list which will always display the code: ‘’.)
Promoting a parameter
Scroll through the lists to the required parameter and choose the ‘’ code. The parameter isthen automatically added (promoted) into the Home display list (the parameter will also beaccessible as normal from the standard lists. a maximum of 16 parameters can be promoted.Promoted parameters are automatically ‘alterable’.
Installation and Operation Handbook Tuning
2216e Controller 4-1
Chapter 4 TUNING
PAGE
What is Tuning? .................................................................. 4-2
Automatic Tuning .................................................................. 4-3
Manual Tuning .................................................................. 4-6
Tuning Installation and Operation Handbook
4-2 2216e Controller
Before tuning please read Chapter 1, Operation, to learn how to select and change aparameter.
This chapter has three main topics:
• WHAT IS TUNING?
• AUTOMATIC TUNING
• MANUAL TUNING
WHAT IS TUNING?
In tuning you match the characteristics of the controller to that of the process being controlledin order to obtain good control. Good control means:
Stable ‘straight-line’ control of the temperature at setpoint without fluctuation
Acceptable overshoot or undershoot of the temperature setpoint
Quick response to deviations from the setpoint caused by external disturbances, therebyrestoring the temperature rapidly to the setpoint value.
Tuning involves calculating and setting the value of the parameters listed in Table 4-1. Theseparameters appear in the list.
Parameter Code Meaning or Function
Proportionalband
The bandwidth in display units over which the output power isproportioned between minimum and maximum.
Integral time Determines the time taken by the controller to remove steady-state error signals.
Derivativetime
Determines how strongly the controller will react to the rate-of-change of the measured value.
Low cutback The number of display units below setpoint at which thecontroller will cutback the output power in order to preventovershoot on heat up.
High Cutback The number of display units above setpoint at which thecontroller will increase the output power in order to preventundershoot on cool down.
Relative coolgain
Only present if cooling has been configured. Sets the coolingproportional band by dividing the Pb value by the rEL.C value.
Table 4-1 Tuning parameters
Installation and Operation Handbook Tuning
2216e Controller 4-3
AUTOMATIC TUNING
This method automatically determines the value of the parameters listed in table 4-1 on theprevious page.
The 2216e uses a ‘one-shot’ tuner which works by switching the output on and off to inducean oscillation in the measured value. From the amplitude and period of the oscillation, itcalculates the tuning parameter values.
If the process cannot tolerate full heating or cooling being applied during tuning, then thelevel of heating or cooling can be restricted by setting the heating and cooling power limits inthe Output list. However, the measured value must oscillate to some degree for the tuner to beable to calculate values
A One-shot Tune can be performed at any time but normally it is performed only once duringthe initial commissioning of the process. However, if the process under control subsequentlybecomes unstable (because its characteristics have changed), you can re-tune again for the newconditions.
It is best to start tuning with the process at ambient temperature. This allows the tuner tocalculate more accurately the low cutback and high cutback values that restrict the amount ofovershoot or undershoot.
Heating and Cooling Output Cycle Times
Before commencing a tuning cycle, set the values of (heat cycle time) and (coolcycle time) in the op (output list). These values apply if you are using a logic, relay or triacoutput. They have no effect on a DC output.
A logic output switching a solid state relay can be set to values such as 1 sec.
A relay or triac output should be set to 20 sec.
Tuning Installation and Operation Handbook
4-4 2216e Controller
How to tune
1. Set the setpoint to the value at which you will normally operate the process.
2. In the ‘’ list, select ‘’ and set it to ‘ ’
3. Press the Page and Scroll buttons together to return to the Home display. The displaywill flash ‘’ to indicate that tuning is in progress.
4. The controller will induce an oscillation in the temperature by turning the heating on andthen off. The first cycle will not complete until the measured value has reached therequired setpoint.
5. After two cycles of oscillation the tuning will be completed and the tuner will switchitself off.
6. The controller will then calculate the tuning parameters listed in Table 4-1 and willresume normal control action.
If you want ‘Proportional only’ or ‘PD’ or ‘PI’ control, you should set the ‘’ or ‘’parameters to before commencing the tuning cycle. The tuner will leave them off andwill not calculate a value for them.
For valve position tuning and set-up, please refer to Appendix D.
Installation and Operation Handbook Tuning
2216e Controller 4-5
Typical automatic tuning cycle
Calculation of the cutback values
Low cutback and High cutback are values that restrict the amount of overshoot or undershootthat occur during large step changes in temperature (for example, under startup conditions).
If either low cutback or high cutback is set to ‘ ’ the values will be fixed at three timesthe proportional band, and will not be changed during automatic tuning.
Time
Setpoint
Temperature
Tuning Installation and Operation Handbook
4-6 2216e Controller
MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results, you can tune the controllermanually. There are a number of standard methods for manual tuning. The one describedhere is the Ziegler-Nichols method.
With the process at its normal running temperature:
1. Set the Integral Time ‘ and the Derivative Time ‘’ to .
2. Set High Cutback and Low Cutback, ‘’ and ‘’, to ‘ ’
3. Ignore the fact that the temperature may not settle precisely at the setpoint
4. If the temperature is stable, reduce the proportional band ‘’ so that the temperature juststarts to oscillate. If the temperature is already oscillating, increase the proportional banduntil it just stops oscillating. Allow enough time between each adjustment for the loop tostabilise. Make a note of the proportional band value ‘B’ and the period of oscillation ‘T’.
5. Set the Pb, ti, td parameter values according to the calculations given in Table 4-2.
Type of control Proportionalband ‘Pb’
Integral time ‘ti’ Derivative time‘td’
Proportional only 2xB OFF OFF
P + I control 2.2xB 0.8xT OFF
P + I + D control 1.7xB 0.5xT 0.12xT
Table 4-2 Tuning values
Installation and Operation Handbook Tuning
2216e Controller 4-7
Setting the cutback values
The above procedure sets up the parameters for optimum steady state control. If unacceptablelevels of overshoot or undershoot occur during start-up or for large step changes intemperature, then manually set the cutback parameters and .
Proceed as follows:
1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb= Hcb = 3 x Pb).
2. Note the level of overshoot or undershoot that occurs for large temperature changes (seethe diagrams below).
In example (a) increase by the overshoot value. In example (b) reduce by theundershoot value.
Example (a)
Temperature
Example (b)
Temperature
Where the temperature approaches setpoint from above, you can set ina similar manner.
Time
Undershoot
SetpointOvershoot
Tuning Installation and Operation Handbook
4-8 2216e Controller
Integrating action and manual resetIn a full three-term controller (that is, a PID controller), the integral term ‘ti’ automaticallyremoves steady state errors from the setpoint. If the controller is set up to work in two-termmode (that is, PD mode), the integral term will be set to . Under these conditions themeasured value may not settle precisely at setpoint. When the integral term is set to OFF theparameter manual reset (code ) appears in the in ‘’ Access level.This parameter represents the value of the power output that will be delivered when the erroris zero. You may set this value manually in order to remove the steady state error.
Automatic droop compensation (Adc)
The steady state error from the setpoint, which occurs when the integral term is set to OFF, issometimes referred to as ‘droop’. automatically calculates the manual reset value inorder to remove this droop. To use this facility, you must first allow the temperature tostabilise. Then, in the autotune parameter list, you must set to ‘’. The controllerwill then calculate a new value for manual reset, and switch to ‘’.
can be repeated as often as you require but between each adjustment you must allow timefor the temperature to stabilise.
Installation and Operation Handbook Configuration
2216e Controller 5-1
Chapter 5 CONFIGURATION
PAGE
Selecting Configuration Level ...................................................... 5-2
Leaving Configuration ................................................................... 5-3
Steps Involved in Configuring a Controller .................................... 5-3
Navigation Diagram ...................................................................... 5-4
Configuration Parameter Tables .................................................. 5-6
WARNINGConfiguration is protected and should only be carried out by an authorised person.Incorrect configuration could result in damage to the process being controlled and/orpersonal injury. It is the responsibility of the person commissioning the instrument toensure that the configuration is correct.
Configuration Installation and Operation Handbook
5-2 2216e Controller
SELECTING CONFIGURATION LEVEL
Figure 5.1
At this point thecontroller is inconfiguration level
“HOME”display
Press Pagebuttonrepeatedlyuntil AccessList appears
or to enter password (factory default = 1)
If incorrectpasswordentered
or to enterpassword (factory default = 2)
Note: Selectingor will allow direct entry tothese levels at this point
1st press
2nd press
3rd press
If the password hasbeen set to ‘’ - accessis permanentlyunlocked & the lowerreadout always shows
Repeated pressing of “Page” buttonselects configuration list headings in a
continuous loop
2 secs
or to select
4th press
Installation and Operation Handbook Configuration
2216e Controller 5-3
LEAVING CONFIGURATION LEVEL
STEPS INVOLVED IN CONFIGURING A CONTROLLER
The navigation diagram which follows shows the general location of parameters which definethe way in which the controller works. They are grouped under headings. The actualparameters shown in your controller may differ slightly since some appear only as a result ofselecting others. A full list of possibilities is included in the PARAMETER TABLES whichfollow the navigation diagram.
or to select
Keep pressing untilExit display appears
After a 2 second delay the screenwill blank, the instrument will reset,and revert to the Home display
Figure 5.2
Configuration Installation and Operation Handbook
5-4 2216e Controller
NAVIGATION DIAGRAM (PART A)
Instrument Input User cal. AlarmsConfig Config Config Config
°
!
!
"
#
$
$
%
&
&
'!
&
#!
&
The Principle of Operation is thesame as that already described inCh1.That is:
Step through List Headers using the ‘Page’ button
Choose a parameter from a list using the ‘Scroll’ button
Change value using the ‘Raise/Lower’ buttons
The first 4 headings set up thecontroller functions, as follows:Instrument Config. - Groups thoseparameters associated with thedisplay and control action.Input Config. - selects the inputsensor typeUser cal. Config. - to calibrate toexternal reference sourcesAlarms Config. - sets up the alarmtypes
()%
**!
Installation and Operation Handbook Configuration
2216e Controller 5-5
NAVIGATION DIAGRAM (PART B)
Comms Output 1 Output 2 Output 3 10A output PasswordConfig Config Config Config Config Config
(
See Table Bparametertable, page 5-13
See Table Bparametertable, page 5-13
'
#
!
+
+
+
%(
%
% ,
%!!
&-%./
%
!%
0 %1
!%
$-
$-
Configuration Installation and Operation Handbook
5-6 2216e Controller
Heading Input/Output Functions Wiring Terminals
The first four headings set up the controller functions as follows:
Sets up display and control parameters Not applicable
Selects the input sensor type Not applicable
To calibrate to external reference sources Not applicable
Sets up the alarm types Not applicableThe remaining headings configure the controller input/output functions.The upper readout corresponds to rear terminal numbers associated with a particular i/o.
Sets up the action of the two digital inputs LA & LB
Sets up the action of the fixed relay on output AA AA to AC
Sets up digital comms type HB to HF
Sets up the output modules 1A and 2A 1A & 1B / 2A & 2B
Sets up the action of the fixed relay on output 3A 3A to 3C
Sets the action of the 10A output relay in 2204 4A to 6D
To choose new passwords
/ To leave configuration level and return to operator level
Installation and Operation Handbook Configuration
2216e Controller 5-7
NOTE
CONFIGURATION PARAMETER TABLES
Name Parameter description Values Meaning
Instrument configuration
% Instrument 2 Centigrade (default UK)units 2 Fahrenheit (default USA)
23 Kelvin
Units are not displayed
Decimal places in the Nonedisplayed value One
Two
Control type ! On/off control
)
PID controlVP Control
Control action Reverse acting (required fortemperature control) - outputdecreases on approach tosetpoint.
Direct acting
Type of cooling Linear
Oil (50mS min on time)
! Water(non-linear)
Fan (0.5S min on time)
" Power feedback Power feedback is on(compensates for changes insupply voltage)
! Power feedback is off
Bumpless manual/auto Non-bumpless transfertransfer when using PD control Bumpless transfer (auto to manual
and manual to auto)
Forced manual output Bumpless manual/auto transfer
4 Returns to the manual value thatwas set when last in manualmode.
* Sensor break output *! Go to pre-set value (maintainsoutput at a known, safe level)
Freeze output (maintains output atvalue immediately before break)
Load Current Scaling Factor See Appendix E-10
Factory default parameter values and states are included where applicable and areindicated by the shaded areas in the following tables.
Configuration Installation and Operation Handbook
5-8 2216e Controller
Name Parameter description Value Meaning
Input configuration
Input type J thermocouple (default USA)
K thermocouple (default UK)
L thermocouple
R thermocouple (Pt/Pt13%Rh)
* B thermocouple (Pt30%Rh/Pt6%Rh)
N thermocouple
T thermocouple
S thermocouple (Pt/Pt10%Rh)
PL 2 thermocoupleNOTE: 100Ω platinum resistance thermometer.After selecting an inputtype, do not forget toadjust the setpoint limitsin Full Access level
Custom downloaded input type. Thedefault is C thermocouple, or the name ofthe downloaded custom input will bedisplayed.
($ Linear millivolt (Also mA input via anexternal 2.49Ω current sense resistor)
Linear voltage
Input range low Display low range for input
Input range high Display high range for input
CJC ref. temperature % Automatic cold junction compensation(CJC does not appear for 2 0°C external referencelinear inputs) #52 45°C external reference
52 50°C external reference
Linear Input Scaling - The next 4 parameters only appear if a linear input is chosen
Input value low
Input value high
$ Displayed reading low
$ Displayed reading high
( Sensor break inputimpedance trip level
! Sensor break detection is disabledAppears for mV or V inputs only
% Trip level set by the sensor input table
Trip level set at 7.5KΩ Trip level set at 15KΩ (must be selected
when input is enabled)
Displayed Value
ElectricalInput
Installation and Operation Handbook Configuration
2216e Controller 5-9
Name Parameter description Value Meaning
User calibration config. See Chapter 6 - User calibration
User cal enable User calibration is disabled
User calibration is enabled
User calibrationpoint low
This is the value (in display units) at which a Userlast performed a low point calibration
User calibrationpoint high
This is the value (in display units) at which a Userlast performed a high point calibration
! Low pointcalibration offset
Offset, in display units, at the user low calibrationpoint ‘Pnt.L’. This value is automatically calculatedwhen performing low point calibration.
! High pointcalibration offset
Offset, in display units, at the user high calibrationpoint ‘Pnt.H’. This value is automatically calculatedwhen performing a high point calibration.
* If User calibration is enabled, then the User calibration parameters will appear in the Input list ofOperator Full access level. See Chapter 6, User calibration.
Configuration Installation and Operation Handbook
5-10 2216e Controller
NOTE
Name Parameter description Values
Alarm configuration Values Defaults if not specified
Alarm 1 Type As table A !
* Alarm 1 Blocking(1)/
Alarm 1 Latching /%/(-
Alarm 2 Type As table A !
* Alarm 2 Blocking(1)/
Alarm 2 Latching /%/(-
' Alarm 3 Type As table A !
* Alarm 3 Blocking(1)/
Alarm 3 Latching /-%/(-
# Alarm 4 Type As table A !
* Alarm 4 Blocking(1)/
Alarm 4 Latching /-%/(-
Table A: Alarm types
! No alarm
Full scale low
Full scale high
Deviation band
Deviation high
Deviation low
Low current
High current
(1) Blocking allows the alarm to become active only after it has first entered a safe state.
These are ‘soft’ alarms, i.e. Indication only. They would normally be attached to anoutput. See Chapter 7 for a step by step guide.
Installation and Operation Handbook Configuration
2216e Controller 5-11
Name Parameter description Functions Meaning
Comms module config Functions Meaning
Identity of the option installed PDSIO® setpoint input
( 2- or 4-wire EIA-485 (422) orEIA-232 comms module
% Function
Some of the following parameters may appear if one of the comms options is installed
( DIGITAL Communicationprotocol ordered
None
The following parameters will appear if the PDSIO setpoint input option is installed.
No PDSIO® function
PDSIO® setpoint input
$ PDSIO® low input value Range = -999 to 9999
$ PDSIO® high input value Range = -999 to 9999
The following parameters will appear if the function chosen is Mod protocol.
&% Baud Rate 1200, 2400, 4800, 9600, 19.20, 1920 (19200)
*+ Comms Parity No parity
Even parity
! Odd parity
* Comms Resolution % Full resolution
Integer resolution
*Not used with some communication protocols. Please consult factory.
Configuration Installation and Operation Handbook
5-12 2216e Controller
Name Parameter description Function Meaning
Output 1 configuration Function Meaning
Identity of module installed No module fitted
0 + Relay output
! DC output (isolated)
Logic or PDSIO® output
Triac output
% Function 6 Module does not operate
Function set by
Heating output
!! Cooling outputOnly appear for id = dC.OP ! Retransmission of output
demandOnly appear for id = dC.OP $ Retransmission of Process
ValueOnly appear for id = dC.OP Retransmission of errorOnly appear for id = dC.OP " Retransmission of setpointOnly appear for id = LoG PDSIO® mode heatingOnly appear for id = LoG PDSIO® mode 2 heating
For 7%tion = go to table B below
Sense of output
Normal (e.g.heating and cooling)Inverted (alarms - de-energise inalarm)
DC output scaling For id = dC.OP the following parameters appear
!% DC output minimum 0mA to 20mA
!% DC output maximum 0mA to 20mA
Installation and Operation Handbook Configuration
2216e Controller 5-13
Table B The following parameters appear if ‘’ is chosen as the function.
Digital output functions No changeAny number of the functionslisted can be combined on tothe output. Use the and buttons toselect a desired digitalfunction. After two secondsthe display will blink andreturn to the ‘’ display.Use the arrows again toscroll through the functionlist. The previously selectedfunction display will showtwo decimal points indicatingthat it has been added to theoutput.
8 8 8
* 8 8 8 *' 8 8 8 *# 8 8 8 *9** 7 66"-0(!
Clear all existing functionsAlarm 1 *Alarm 2 *Alarm 3 *Alarm 4 *Manual/AutoSensor BreakLoop BreakHeater FailLoad FailEND ProgramPV Out of RangePDSIO® SSR FailureNew AlarmRemote Sp FailCTx open circuitCtx short circuit
* From previous page. In place of the dashes, the last three characters indicate the alarm type as per tableA in the AL list: eg = Full Scale Low If an alarm is not configured the displayed name will differ:e.g. ‘ 2 will be shown, for the first alarm.
Name Parameter description Function Meaning
Output 2 configuration Function Meaning
Identity of module installed No module fitted
+ Relay output
Logic
Triac output
% Function none
Outputs Function set by
Heating output
!! Cooling output
Logic Inputs ( Manual mode select
( Remote setpoint select
Setpoint 2 select
Integral hold
Acknowledge alarms
* Standby - ALL outputs = OFF
For % = (Refer to table B on page 5-13).
Sense of output
Normal (heat and cool outputs)Inverted (alarms - de-energise in alarm)
Configuration Installation and Operation Handbook
5-14 2216e Controller
Password list
FuLL or Edit level password
Configuration level Password
Exit Configuration /
Installation and Operation Handbook User Calibration
2216e Controller 6-1
Chapter 6 USER CALIBRATION
PAGE
What is the Purpose of User Calibration? ................................... 6-2
User Calibration Enable ............................................................... 6-3
Single Point Calibration ............................................................... 6-4
Two Point Calibration .................................................................. 6-5
Calibration Points and Calibration Offsets .................................. 6-6
User Calibration Installation and Operation Handbook
6-2 2216e Controller
This chapter has five topics:
• WHAT IS THE PURPOSE OF USER CALIBRATION?
• USER CALIBRATION ENABLE
• SINGLE POINT CALIBRATION
• TWO POINT CALIBRATION
• CALIBRATION POINTS AND CALIBRATION OFFSETS
To understand how to select and change parameters in this chapter you will need to have readChapter 2 - Operation, Chapter 3- Access Levels and Chapter 5 - Configuration.
WHAT IS THE PURPOSE OF USER CALIBRATION?
The basic calibration of the controller is highly stable and set for life. User calibration allowsyou to offset the ‘permanent’ factory calibration to either:
1. Calibrate the controller to your reference standards
2. Match the calibration of the controller to that of a particular transducer or sensor input
3. Calibrate the controller to suit the characteristics of a particular installation.
User calibration works by introducing zero and span offsets onto the factory set calibration.The factory set calibration can always be retrieved.
Installation and Operation Handbook User Calibration
2216e Controller 6-3
USER CALIBRATION ENABLEThe User calibration facility must first be enabled in configuration level by setting theparameter ‘' in the list to ' ' This will make the User calibrationparameters appear in Operator ‘’ level.Select configuration level as shown in Chapter 5, Configuration
The User calibration configuration List
Press until you reach the ‘ list
ress the Scroll button until you reach
User calibration enable
Use or to select:
: Calibration enable: Calibration disabled
Press and together to go to the Exit display
Exit configuration
Use or to select ‘ ’and return to Operator level.
User Calibration Installation and Operation Handbook
6-4 2216e Controller
SINGLE POINT CALIBRATION
Your controller is calibrated for life against known reference sources during manufacture. Acalibration offset is often used to allow the controller to compensate for sensor and othersystem errors. The normal procedure is to set up the system under test against a knownindependent reference, as follows:Set up the process to be calibrated such that the known reference displays the required value(temperature).Observe the reading on the controller. If it is different, proceed as follows:Select ‘ Access level as described in Chapter 3
Input list header
Press until you reach the input list header.
Press Scroll until you reach the ‘’ display
Calibration type
Use or to select either ‘’ or ‘ ’.Selecting ‘’ will reinstate the factory calibration andhide the following User calibration parameters.Selecting ‘ ’ will reinstate any previously set Usercalibration and make available the User parameters, asfollows:
Press the Scroll button
Calibrate low point?
Use or to select ‘ ’Selecting ‘no’ will hide the next parameter
Press the Scroll buttoncontinued on the next page
Installation and Operation Handbook User Calibration
2216e Controller 6-5
To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the ‘’facility describe in Chapter 3.
TWO POINT CALIBRATION
The previous section described how to perform a single point calibration which applies a fixedoffset over the full display range of the controller. A two-point calibration is used to calibratethe controller at two points and apply a straight line between them. Any readings above orbelow the two calibration points will be an extension of this straight line. For this reason it isbest to calibrate with the two points as far apart as possible.
Proceed as follows:
1. Decide upon the low and high points at which you wish to calibrate.
2. Perform a single point calibration at the low calibration point in the mannerdescribed above
3. Set the process under calibration such that the known reference exhibits the requiredhigher Process Value (temperature) and allow to stabilize.
4. Press the Scroll button to obtain the high calibration point as shown in thefollowing diagrams.
Adjust the low point calibration
The controller will display the current measured input value in thelower readout.
Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value. You can calibrate at any pointover the entire display rangeThis is a single point calibration which applies a fixed offset over thefull display range of the controller.The calibration is now complete. You can return to the factorycalibration at any time by select ‘’ in the CAL display shownearlier.
Press and together to return to theHome display
User Calibration Installation and Operation Handbook
6-6 2216e Controller
To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the ‘’facility described in Chapter 3.
CALIBRATION POINTS AND CALIBRATION OFFSETS
If you wish to see the points at which the User calibration was performed and the value of theoffsets introduced these are shown in Configuration, under . The parameters are:
Name Parameter description Meaning
User low calibration point This is the value (in display units) at which a Userlast performed an ‘’ (adjust low calibration).
User high calibration point This is the value (in display units) at which a Userlast performed an ‘’ (adjust high calibration).
Low point calibration offset Offset, in display units, at the user low calibrationpoint ‘
High point calibration offset Offset, in display units, at the user high calibrationpoint ‘ .
Calibrate high point?
Use or to select ‘’
Press the Scroll button
Adjust the high point calibration
The controller will display the current measured input value in thelower readout.
Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value.
The calibration is now complete. You can return to the factorycalibration at any time by select ‘’ in the display shownearlier.
Installation and Operation Handbook Alarm Operation
2216e Controller 7-1
Chapter 7 ALARM CONFIGURATION
PAGE
Definition of Alarms and Events ...................................................... 7-2
Types of Alarms ................................................................................ 7-2
Step 1 - Configuring the Four ‘Soft’ Alarms .................................... 7-5
Step 2 - Attaching an Alarm to a Physical Output .......................... 7-6
Step 3 - Grouping Alarms on a Single Output ................................. 7-7
Step 4 - Removing Alarms from an Output ...................................... 7-7
The 2200e series controllers are capable of very sophisticated alarm strategies and, althoughsetting up of alarms has already been covered in previous chapters, this section has beenincluded to enable operators and commissioning engineers to design their own strategies foroptimum plant operation.
Alarm Operation Installation and Operation Handbook
7-2 2216e Controller
DEFINITION OF ALARMS AND EVENTS
Alarms are used to alert an operator when a pre-set level or condition has been exceeded.They are normally used to switch an output - usually a relay - to provide interlocking of themachine or plant or external audio or visual indication of the condition.
Soft Alarms are indication only within the controller and are not attached to an output (relay).
Events - can also be alarms - but are generally defined as conditions which occur as part of thenormal operation of the process. They do not generally require operator intervention.
Events are referred to as Digital Output Functions in the manual (see Table B, page 5-13).
For the purposes of the operation of this instrument alarms and events can be consideredthe same.
TYPES OF ALARMS
The use of alarms in the 2216econtroller is extremely versatile.Up to 4 alarms can be configured. Any combination of these 4 alarms can be attached to anyone or more available outputs, or any number of the available “soft” alarms can be combinedto operate a single output.
Note: In a three term controller at least one of these outputs is used to maintainthe required temperature of the process.
Outputs 1A and 2A Are plug in modules.Normally used for control outputs, eg. Heat and Cool, but canbe used for alarm outputs.
Output 3A Is a fixed relay.Normally used for alarms or events, but can be used as controloutputs.
NOTE
Installation and Operation Handbook Alarm Operation
2216e Controller 7-3
There are seven process alarm types listed below. Alarm Types are found in configurationmode under the Alarm Config. List.
ALARMS
Full Scale High The PV exceeds a set high level
Full Scale Low The PV exceeds a set low level
Deviation Band The difference between PV & SP is outside a set band
Deviation High The difference between PV & SP is higher than a set level
Deviation Low The difference between PV & SP is lower than a set level
High Current The measured current returned from a PDSIO® slave is higher than aset level
Low Current The measured current returned from a PDSIO® slave is lower than aset level
Each alarm can be set to:
Latching Alarm is indicated until acknowledged(Off, Auto, MAN)
Auto Acknowledge: ( )If the alarm is acknowledged while the alarm condition is stillpresent, it will cause the alarm to reset as soon as the alarmcondition is removed.
Manual Acknowledge: ( )If the alarm is acknowledged while the alarm condition isstill present, it will be ignored. A further acknowledgementis required when the alarm condition has been removed tocause the alarm to reset.
Blocking Alarm occurs after it has been through a start up phase not in alarmcondition.
Sense Of Output Relay energised or de-energised in alarm condition.
Alarm Operation Installation and Operation Handbook
7-4 2216e Controller
In addition there are nine “digital output functions” used as events or alarms depending uponthe requirements of the process under control:
DIGITAL OUTPUT FUNCTIONS
Sensor Break` The input is open circuit
Loop Break The controller does not measure a response to anoutput change
Load Failure Used with PDSIO® Mode 1 load failure
Manual Controller in manual mode
PV Out Of Range Process Variable too high or too low
Remote SP Fail No signal measured at the remote set point input terminals
Heater Fail Used with PDSIO® Mode 2 heater open circuit
SSR Fail Used with PDSIO® Mode 2 solid state relay open or shortcircuit
Program END Signals the end of a program
New Alarm Signals a new alarm
The Sense of the Output can be set to relay energised or de-energised in the alarm conditionfor any of the above functions.
Installation and Operation Handbook Alarm Operation
2216e Controller 7-5
STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS
Go To Configuration LevelRefer to Chapter 5
Press “PAGE” keyas many times as necessaryto find Alarm Configuration
Press “SCROLL” keyto the alarm which needs tobe configured
Alarm Type choicesare
OFF
Full Scale Low
Full Scale High
deviation Band
deviation High
deviation low
Low current
High current
Press “SCROLL” keyto choose alarm 1 latchingor non-latching
Choices No/Auto/Man Press
Press “SCROLL” keyto choose alarm 1 blocking
Choices Yes/No press
Press “SCROLL” keyto repeat for alarms 2 - 4to return to list header
Figure 7.1
Alarm Operation Installation and Operation Handbook
7-6 2216e Controller
STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUTThis may be necessary if:1. The instrument has been supplied un-configured or it is required to re-configure2. Alarm relays are added
Press “PAGE” keyas many times as necessaryto find 3A Configuration
Press “SCROLL” keyto identification of outputtype (this is read only)
Press “SCROLL” keyto output Function
Use or to select Other choices are:
1.
2.
3.
Use or buttons toselect a desired digital function,e.g., . Other choices areshown in the table on the nextpage. After two seconds, thedisplay will blink and return tothe ‘’ (no change) display.Use the arrows again to scrollthrough the function list. Thepreviously selected function willshow 2 decimal pointsindicating that it has beenadded to the output, i.e., .
Use orto select:1. inverted (relay de-energised
in alarm)2. direct (relay energised in
alarm)
Press “SCROLL” keyto digital output function
Keep pressing “SCROLL”button to return to list header
Figure 7.2
Installation and Operation Handbook Alarm Operation
2216e Controller 7-7
STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT
In the previous example one alarm condition is allocated to one output relay.
The 2216e controller allow alarms and events to be grouped on to a single output. Theseevents are shown in the table below.
No change
Clear all existingfunctionsAlarm 1*Alarm 2*Alarm 3*Alarm 4*
* See Table B page 5-13
Figure 7.3
STEP 4 - REMOVING ALARMS FROM AN OUTPUT
Figure 7.4
!!
Press until you reach the1stsoft alarm you wish to attach toan output, e.g., . The displayreturns to no change after 2 sec.accepting the condition.
Press until you reach the2nd soft alarm you wish to attach tothe output, e.g., !. The displayreturns to no change after 2 sec.accepting the condition.
Repeat for all alarms to beattached to the chosen output
Press once to show clearAfter 2 sec. the lower readoutreverts to no change clearing allevents from the chosen output.
Each time you scroll through thetable of alarms, note that 2decimal points appear confirmingacceptance that the particularalarm has been attached to theoutput, i.e., , !, etc.
Installation and Operation Handbook Understanding the Ordering Code
2216e Controller A-1
Appendix A
UNDERSTANDING THE ORDERING CODE
The 2216e controller have a modular hardware construction with the option of three outputsand one communications port.
The ordering code is in two parts: the hardware code followed by the software code. Thehardware code specifies the hardware build of the controller, and the software code thesoftware configuration. The software code is optional.
UK Default USA DefaultType KTIC 0 to 1000°C Type JTIC 32 to 2192°F
Hardware code Software code
Model Output 1 Comms DisplayNumber Language units
Supply Output 2 ManualVoltage Sensor
Output 3 input
Rangemin
Range Max Options
Function
Understanding the Ordering Code Installation and Operation Handbook
A-2 2216e Controller
Hardware code
Modelnumber
Function Supplyvoltage
Output1
Output2
Output3
Comms Manual
2216e CC VH LH RC FL 2YM ENG
Supply voltageVH 85-264Vac
Output 1XX NoneRelay: 2-pinR1 UnconfiguredRU VP raise O/PRH PID heatingFH High alarm 1FL Low alarm 1DB Deviation band 1DL Low dev. alarm 1DH High dev alarm 1Logic: non-isolatedL1 UnconfiguredLH PID heatingM1 PDSIO mode 1(1)
M2 PDSIO mode 2(1)
TriacT1 UnconfiguredTH PID heatingTU VP raise O/PDC control -isolatedD3 UnconfiguredH6 0-20mA PID heatingH7 4-20mA PID heatingC6 0-20mA PID coolingC7 4-20mA PID cooling
Output 2XX NoneRelay: 2-pinR1 UnconfiguredRW VP lower O/PRC PID coolingFH High alarm 2FL Low alarm 2DB Deviation band 2DL Low dev. alarm 2DH High dev alarm 2Logic: non-isolatedL1 UnconfiguredLC PID coolingTriacT1 UnconfiguredTC PID coolingTW VP lower O/P
Output 3(3)
XX NoneRF UnconfiguredRH PID heatingFH High alarm 3FL Low alarm 3DB Deviation band 3DL Low dev. alarm 3DH High dev alarm 3LF PDSIO load failHF PDSIO heater failSF PDSIO SSR failRC PID cooling
FunctionCC ControllerVC Valve
PositionerNF On/Off
ManualXXX No manualENG EnglishFRA FrenchGER GermanITA Italian
Comms2XX None2-wire EIA-4852YM Modbus2YE EI Bisynch4-wire EIA-4222FM Modbus2FE EI BisynchEIA-2322AM Modbus2AE EI BisynchPDSIO® input2M4 Fitted unconfig.2RS Setpoint input2NS Nonstandard
Installation and Operation Handbook Understanding the Ordering Code
2216e Controller A-3
Software code
Sensor input Range min Range max Units Logic input1
Logic input2
Options
K 0(note 2)
1000(note 2)
C XX XX CF
Sensor input Range Min Range MinStandard sensors Min °C max Min °F maxJ J thermocouple -210 1200 -340 2192K K thermocouple -200 1372 -325 2500T T thermocouple -200 400 -325 750L L thermocouple -200 900 -325 1650N N thermocouple -200 1300 -325 2370
R R thermocouple -50 1768 -58 3200S S thermocouple -50 1768 -58 3200B B thermocouple 0 1820 32 3310P Platinel II therm’ple 0 1369 32 2496C *C thermocouple
W5%Re/W26%Re(Hoskins)
0 2319 32 4200
Z RTD/PT100 -200 850 -325 1562Custom sensors (*replaces C thermocouple)D W3%Re/W25%Re 0 2399 32 4350E E thermocouple -200 1000 -325 18301 Ni/Ni18%Mo 0 1399 32 25502 Pt20%Rh/Pt40%R
h 0 1870 32 3398
3 W/W26%Re(Englehard)
0 2000 32 3632
4 W/W26%Re(Hoskins)
0 2010 32 3650
5 W5%Re/W26%Re(Englehard)
10 2300 50 4172
6 W5%Re/W26%Re(Bucose)
0 2000 32 3632
7 Pt10%Rh/Pt40%Rh
-200 1800 392 3272
Linear inputs Min MaxF -100 to +100mV -999 9999Y 0 to 20mA -999 9999A 4 to 20ma -999 9999W 0 to 5Vdc -999 9999G 1 to 5Vdc -999 9999V 0 to 10Vdc -999 9999
OptionsAdd as many options asrequiredControl optionsDP Direct acting PIDHeating optionPD Power feedback
disabledCooling optionsXX Linear coolingCF Fan coolingCW Water coolingCL Oil cooling
Logic inputs 1 & 2XX DisabledAM Manual mode selectSR Remote setpoint selectS2 Second setpointEH Integral holdAC Alarm acknowledgeSB Standby mode
UnitsC CentigradeF FahrenheitK KelvinX Blank
Understanding the Ordering Code Installation and Operation Handbook
A-4 2216e Controller
Notes:
1. PDSIO® is a proprietary technique developed by Eurotherm for bi-directionalcommunication over a single pair of wires. There are several operating modes.
In SSRx Load Doctor a logic output delivers a power demand signal toa TE10 solid state (SSR) relay and the SSR responds with a single loadcircuit failure message. Also called SSRx Load Doctor.
In SSRx Enhanced Load Doctor a logic output delivers a powerdemand signal to an SSR and the SSR responds with the ON state rmsload current, and two fault messages - SSR failure or heater circuitfailure. Also called SSRx Enhanced Load Doctor.
2. Range min and Range max: Enter a numeric value, with a decimal point if required.Thermocouple and RTD sensor inputs will always display over the full operating rangeshown in the sensor input table. The values entered here will act as limits for the setpointhigh and low limit parameters and for alarm setpoints.
3. Alarms are normally supplied configured as non-latching and de-energised-in-alarm, butthey can be configured as latching, energised-in-alarm, or blocking-type alarms (whichonly become active after the alarm has first entered a safe state). Up to four alarms can becombined onto a single output.
Installation and Operation Handbook Safety and EMC Information
2216e Controller B-1
Appendix B
SAFETY and EMC INFORMATION
This controller is intended for industrial temperature and process control applications when itwill meet the requirements of the European Directives on Safety and EMC. Use in otherapplications, or failure to observe the installation instructions of this handbook may impairsafety or EMC. The installer must ensure the safety and EMC of any particular installation.
Safety
This controller complies with the European Low Voltage Directive 73/23/EEC, amended by93/68/EEC, by the application of the safety standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection requirements of the EMC Directive89/336/EEC, amended by 93/68/EEC, by the application of a Technical Construction File. Thisinstrument satisfies the general requirements of the industrial environment defined in EN50081-2 and EN 50082-2. For more information on product compliance refer to the TechnicalConstruction File.
GENERAL
The information contained in this manual is subject to change without notice. While everyeffort has been made to ensure the accuracy of the information, Eurotherm Controls shall notbe held liable for errors contained herein.
Unpacking and storage
The packaging should contain an instrument mounted in its sleeve, two mounting brackets forpanel installation and this operating book. Certain ranges are supplied with an input adapter.If on receipt, the packaging or the instrument are damaged, do not install the product butcontact your nearest Eurotherm Controls agent. If the instrument is to be stored before use,protect from humidity and dust in an ambient temperature range of -30oC to +75oC.
SERVICE AND REPAIR
This controller has no user serviceable parts. Contact your nearest Eurotherm Controls agentfor repair.
Caution: Charged capacitors
Before removing an instrument from its sleeve, disconnect the supply and wait at least twominutes to allow capacitors to discharge. It may be convenient to partially withdraw theinstrument from the sleeve, then pause before completing the removal. In any case, avoidtouching the exposed electronics of an instrument when withdrawing it from the sleeve.Failure to observe these precautions may cause damage to components of the instrument orsome discomfort to the user.
Safety and EMC Information Installation and Operation Handbook
B-2 2216e Controller
Electrostatic discharge precautions
When the controller is removed from its sleeve, some of the exposed electronic componentsare vulnerable to damage by electrostatic discharge from someone handling the controller. Toavoid this, before handling the unplugged controller discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels or they will become illegible.Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to cleanother exterior surfaces of the product.
INSTALLATION SAFETY REQUIREMENTS
Safety Symbols
Various symbols are used on the instrument, they have the following meaning:
Caution, (refer to the accompanying documents)
Functional earth (ground) terminal!
The functional earth connection is not required for safety purposes but is used to ground RFIfilters.
Personnel
Installation must only be carried out by qualified personnel.
Enclosure of live parts
To prevent hands or metal tools touching parts that may be electrically live, the controller mustbe installed in an enclosure.
Caution: Live sensors
The logic and PDSIO® outputs are electrically connected to the main PV input, (thermocoupleetc.). If the temperature sensor is connected directly to an electrical heating element then thesenon-isolated inputs and outputs will also be live. The controller is designed to operate underthese conditions. However you must ensure that this will not damage other equipmentconnected to these inputs and outputs and that service personnel do not touch connections tothese I/O while they are live. With a live sensor, all cables, connectors and switches forconnecting the sensor and non-isolated inputs and outputs must be mains rated.
Wiring
Installation and Operation Handbook Safety and EMC Information
2216e Controller B-3
It is important to connect the controller in accordance with the wiring data given in thishandbook. Take particular care not to connect AC supplies to the low voltage sensor input orother low level inputs and outputs. Only use copper conductors for connections, (exceptthermocouple). Ensure that the wiring of installations comply with all local wiring regulations.For example in the in the UK, use the latest version of the IEE wiring regulations, (BS7671).In the USA, use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker that disconnects allcurrent carrying conductors. The device should be mounted in close proximity to thecontroller, within easy reach of the operator and marked as the disconnecting device for theinstrument.
Earth leakage current
Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect thedesign of an installation of multiple controllers protected by Residual Current Device, (RCD)or Ground Fault Detector, (GFD) type circuit breakers.
Overcurrent protection
To protect the internal PCB tracking within the controller against excess currents, the ACpower supply to the controller and power outputs must be wired through the fuse or circuitbreaker specified in the technical specification.
Voltage rating
The maximum continuous voltage applied between any connection to ground must not exceed264Vac.
The controller should not be wired to a three phase supply with an unearthed star connection.Under fault conditions such a supply could rise above 264Vac with respect to ground and theproduct would not be safe.
Voltage transients across the power supply connections, and between the power supply andground, must not exceed 2.5kV. Where occasional voltage transients over 2.5kV are expectedor measured, the power installation to both the instrument supply and load circuits shouldinclude a transient limiting device.
These units will typically include gas discharge tubes and metal oxide varistors that limit andcontrol voltage transients on the supply line due to lightning strikes or inductive loadswitching. Devices are available in a range of energy ratings and should be selected to suitconditions at the installation.
Safety and EMC Information Installation and Operation Handbook
B-4 2216e Controller
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the controller ismounted. For example, carbon dust is a form of electrically conductive pollution. To secure asuitable atmosphere, install an air filter to the air intake of the cabinet. Where condensation is likely,for example at low temperatures, include a thermostatically controlled heater in the cabinet.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the temperature sensor while thecontroller is still powered up. Under these conditions, as additional protection against electricshock, we recommend that the shield of the temperature sensor is grounded. Do not rely ongrounding through the framework of the machine.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part ofthe system should fail. In temperature control applications the primary danger is that theheating will remain constantly on. Apart from spoiling the product, this could damage anyprocess machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on
• an external valve or contactor sticking in the heating condition
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a separate over-temperatureprotection unit, with an independent temperature sensor, which will isolate the heating circuit.
Please note that the alarm relays within the controller will not give protection under all failureconditions.
INSTALLATION REQUIREMENTS FOR EMC
To ensure compliance with the European EMC directive certain installation precautions arenecessary as follows:
• For general guidance refer to Eurotherm Controls EMC Installation Guide, HA025464.
• When using relay or triac outputs it may be necessary to fit a filter suitable for suppressingthe conducted emissions. The filter requirements will depend on the type of load. Fortypical applications we recommend Schaffner FN321 or FN612.
• If the unit is used in table top equipment which is plugged into a standard power socket,then it is likely that compliance to the commercial and light industrial emissions standardis required. In this case to meet the conducted emissions requirement, a suitable mainsfilter should be installed. We recommend Schaffner types FN321 and FN612.
Installation and Operation Handbook Safety and EMC Information
2216e Controller B-5
Routing of wires
To minimise the pick-up of electrical noise, the low voltage DC connections and the sensorinput wiring should be routed away from high-current power cables. Where it is impractical todo this, use shielded cables with the shield grounded at both ends. In general keep cablelengths to a minimum.
Safety and EMC Information Installation and Operation Handbook
B-6 2216e Controller
TECHNICAL SPECIFICATION
InputGeneral Range ± 100mV and 0 to 10Vdc (auto ranging)
Sample rate 9Hz (110mS)Calibration accuracy 0.25% of reading, ±1 LSD, ±1°C/FResolution <1µV for ± 100mV range, <0.2mV for
10Vdc rangeLinearisation accuracy <0.1% of readingInput filter 1.0 to 999.9 secsZero offset User adjustable over the fully display range
Thermocouple Types Refer to Sensor inputs and display rangestable
Cold junction compensation Automatic compensation typically >30 to 1rejection of ambient temperature change(incorporates INSTANT ACCURACY™ coldjunction sensing technology).External references 32, 113 and 122°F (0, 45and 50°C)
RTD/PT100 Type 3-wire, Pt100 DIN43760Bulb current 0.2mALead compensation No error for 22 ohms in all 3 leads
Process Linear ±100mV, 0 to 20mA or 0 to 10Vdc (Allconfigurable between limits)
OutputsRelay Rating: 2-pin relay Min: 12V, 100mA dc Max: 2A, 264Vac
resistiveRating: change-over, alarm relay Min: 6V, 1mA dc Max: 2A, 264Vac resistiveApplication Heating, cooling or alarms
Logic Rating 18Vdc at 24mA (non-isolated)Application Heating, cooling or alarms
PDSIO® mode 1: SSRx Load Doctor™ logicheating with load failure alarmPDSIO® mode 2: SSRx Enhanced LoadDoctor™ logic heating with load/SSC failurealarms and load current display
Triac Rating 1A, 30 to 264Vac resistiveApplication Heating or cooling
Analog Range Isolated, 0 to 20mA 0 to 10Vdc (configurablebetween limits)
Application Heating or cooling
CommunicationsDigital Transmission standard EIA-485 2wire, EIA-422 4 wire or EIA-232 at
1200, 2400, 4800, 9600, 19,200 baudProtocols Modbus®
PDSIO® Setpoint input Setpoint input from master PDSIO®controller
Installation and Operation Handbook Safety and EMC Information
2216e Controller B-7
Control functionsControl Modes PID or PI with overshoot inhibition, PD, PI,
P only or On/OffApplication Heating and coolingAuto/manual Bumpless transferSetpoint rate limit 0.01 to 99.99 degrees or display units per
minuteCooling algorithms Linear; Water (non-linear); Fan (minimum
on time), Oil, proportional onlyTuning One-shot tune Automatic calculation of PID and overshoot
inhibition parametersAutomatic droop compensation Automatic calculation of manual reset value
when using PD controlAlarms Types Full scale high or low. Deviation high, low,
or bandModes Latching or non-latching. Normal or
blocking actionUp to four process alarms can be combinedonto a single output
GeneralDisplay Dual, 4 digit x 7 segment high intensity LEDDimensions and weight 1.89W x 1.89H x 4.06D in (48W x 48H x
103Dmm) 8.82oz (250g)Supply 85 to 264Vac -15%, +10%. 48 to 62Hz.
10watts maxTemperature and RH Operating: 32 to 131°F (0 to 55°C), RH: 5 to
90% non-condensing. Storage: 14 to 158°F(-10 to 70°C)
Panel sealing IP 65Electromagnetic compatibility Meets generic emissions standard EN50081-
2 for industrial environmentsMeets general requirements of EN50082-2(95) standards for industrial environments
Safety standards EN61010, installation category 2 (voltagetransients must not exceed 2.5kV)
Atmospheres Electrically conductive pollution must beexcluded from the cabinet in which thiscontroller is mounted. This product is notsuitable for use above 6,562ft (2000m) or incorrosive or explosive atmospheres withoutfurther protection.
Installation and Operation Handbook Address
2216e Controller C-1
Appendix C
North America:
EUROTHERM CONTROLS INC
Eurotherm Controls Inc11485 Sunset Hills RoadReston, VA 20190-5286
Tel: (703) 471-4870Fax: (703) 787-3436Fax-on Demand: (703) 787-3441BBS: (703) 787-3444Website: http://www.eurotherm.comTechnical Library: www.eurotherm.com/ library.htmEmail: sales @controls.eurotherm.com
Europe:
EUROTHERM CONTROLS LTD
Eurotherm Controls LTDFaraday CloseDurringtonWorthingWest SussexBN13 3PL
Tel: +44-1903-268500Fax: +44-1903-265982Website: http://www.eurotherm.co.uk
Installation and Operation Handbook Valve Position
2216e Controller D-1
Appendix D
MOTORISED VALVE CONTROL
The 2216e can be configured for motorised valve control as an alternative to the standard PIDcontrol algorithm. This algorithm is designed specifically for positioning motorised valves.
The motorised valve algorithm operates in the Velocity mode, which does not require aposition feedback potentiometer for control purposes.
The following parameter list will appear in the navigation diagram shown in Chapter 2; if yourcontroller is configured for motorised valve control.
Name Description Values
Output list Min Max Default
Valve travel time in seconds.This is the time taken for the valve to travel fromits fully closed position to its fully open position.
is the low output power limit.
is the High output power limit
Output pulse minimum on time, in seconds.
Table D-1 Motorised valve parameter list
COMMISSIONING THE MOTORISED VALVE CONTROLLER
Proceed as follows:
1. Measure the time taken for the valve to be raised from its fully closed to its fully openposition and enter this as the value in seconds into the ‘’ parameter.
2. Set all the other parameters to the default values shown in Table D-1.
The controller can then be tuned using the automatic or manual tuning techniques.
ADJUSTING THE MINIMUM ON-TIME ‘
The default value of 0.2 seconds is satisfactory for most processes. The minimum on timedetermines how accurately the valve can be positioned. The shorter the time, the more precisethe control. However, if the time is set too short, process noise will cause anexcessively busy valve.
Valve Position Installation and Operation Handbook
D-2 2216e Controller
MOTORISED VALVE APPLICATIONS
AUTO TUNING
Before the auto tune is activated, the parameter must be set to a numeric value. The parameter cannot be set to when an auto tune is activated. When the auto tune iscomplete, the auto tune will set the parameter back to the position.
2200e Valve Positioner Set-up Table
Name Description Value
Configuration Mode
In the configuration list set the to.
Module 1A needs to be a or a .
The for 1A should be configured for!". (Open Valve)
Module 2A needs to be a or a .
The for 2A should be configured for. ( Close Valve)
Operating Mode (OP List)
Valve travel time in seconds.This is the time taken for the valve to travelfrom its fully closed position to its fully openposition.
Low output power limit.
High output power limit
Output pulse minimum on-time, in seconds.
Home List
# Calculated position of valve % of motor traveltime
Table D-2 Valve Positioner Set-up Table
The following operating parameters do not effect the 2200e when the valvepositioner option has been configured:
$ Heat Cycle Time
$ Cool Cycle Time
Minimum on time for cooling
NOTE
Installation and Operation Handbook Load Current Monitoring and Diagnostics
2216e Controller E-1
Appendix E LOAD CURRENT MONITORING ANDDIAGNOSTICS
Current flowing in a system of electrical heating elements (the ‘Load’) can be displayed onthe controller by using a Eurotherm TE10 SSR fitted with intelligent current transformer,PDCTX, or an SSR or contactor with an external PDCTX.Load current monitoring and diagnostics may be used with any time proportioned output,fitted in module position 1A, and uses the logic output wires which drive the SSR to returnsignals back to the controller These signals represent the RMS value of the load currentduring the ON period, or load related alarm conditions. It is not designed for analogueoutputs i.e. phase angle control.It is also designed for single phase operation only.There are two modes of operation:-
1. Mode 1Detects if there is a break in the heater circuit. This includes heater or SSR open circuit.A single Load Failure alarm message is displayed on the lower readout of the controller.
2. Mode 2Provides the following:-
Display of true RMS load current Onthe lower readout of the controller
Displays the true RMS current in the ONstate to the load.
Low current alarm Analogous to PartialLoad Failure (PLF) supplied in someEurotherm SSRs
Provides advanced warning of failure ofone or more heaters in parallel
High current alarm Activated when theheater exceeds a set limit
Typically used where element bunchingmay occur
SSR short circuit This will apply full power to the heaterswhich could result in an over temperaturecondition. This alarm provides earlywarning.
Heater failure Indicates open circuit load conditions
Load Current Monitoring and Diagnostics Installation and Operation Handbook
E-2 2216e Controller
1.
EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)
Hardware Required
1. Eurotherm SSR type TE10/PDS2 OR2. Eurotherm intelligent current transformer type PD/CTX + contactor or zero voltage
switching SSR2216e controller configured for PDSIO mode 2 option using logic output. This modulemust be fitted in module position 1. (order code M2).
Figure E.1 Connections for Mode 1 & 2
WARNING!
Take care that the controller is correctly wired for the mode of operation which isconfigured. Failure to do so may be hazardous in some situations.
Heater
Heaterpower fuse
(loaddependent)
L NControllerFuse 2A(T)
N
L
V+
V-
1B
1A
COMMS1
+-
+PV -
Alternative current regulatorarrangements:-
The Eurotherm TE10/PDS2 contains integralpower regulator and intelligent PDCTX
The PDCTX can be supplied separately foruse with any SSR or logic thyristor unit as
shown in the diagram below.The output drive capability of the PDCTX is
5V at 7mA maximum
PDCTXIntelligentCurrentTransformer
Logic inputSSR
+
+-
-
ToHeater
To LTo logic output1A & 1B
TE10SolidStateRelay
T/C
+-
L N
Thisrepresents asingle turnthrough theCT
Installation and Operation Handbook Load Current Monitoring and Diagnostics
2216e Controller E-3
OPERATION
To Read Load Current (mode 2 only)
Do This This Is The Display You Should See Additional Notes
From the ‘HOME’display, Figure 1.4,
Press until,0 is shown in theupper display
It will revert to theHOME display after45 seconds or 10seconds if an alarmis present
To Display Load Current Continuously in the Lower Readout (mode 2 only)
Do This This Is The Display You Should See Additional NotesFrom the ‘HOME’display, Figure 1.4,
Press untilO0 is shown in theupper display
Press or until ,0 isdisplayed in the lowerdisplay
Current will bedisplayed in the lowerreadout continuouslywhen the controllerreverts to the HOMEdisplay, see also‘Display Modes’below.
Display Modes
SSR RMS On State CurrentThis is the default state when high or low current alarms are configured. The load currentdisplayed is the steady state true rms current measured during the ON period.The minimum on time is:-Mode 2 0.1second
,0,0
,0,0
BBBBBBBB
O0O0,0,0
Current will be displayed inthe lower readout. See also‘Display Modes’ below.
This display will be shown if:I. The controller is unable to resolve the readingII. The controller is obtaining a readingIII. The measurement has timed out i.e. current has
not flowed for 15 seconds.
Load Current Monitoring and Diagnostics Installation and Operation Handbook
E-4 2216e Controller
How Heater Alarms Are Displayed
Do This This Is The Display You Should See Additional Notes
If an alarm is presentit will flash a fourcharacter mnemonicin the lower display
If more than onealarm is active, thedisplay will alternatebetween the alarmmessages and thedefault parameter inthe lower display
The Alarm Messages are:-
Mnemonic Meaning Description
The following two messages are alarms which are produced as a result of failure within theprocess. In place of dashes the alarm number will appear i.e , , , or
B)5 Alarm number- Low Current
Used for partial load failure detection. To avoid nuisancetripping due to supply voltage variations set to a value at least15% below the minimum normal operating current
B#5 Alarm number- High Current
Used for load overcurrent protection. To avoid nuisancetripping due to supply voltage variations set to a value at least15% above the maximum normal operating current.
Note: This alarm is not intended to provideinstantaneous safety protection from short circuit faultconditions
The following message is a diagnostic alarm which appears for mode 1 operation only.
) Load Fail This includes failure of the heater circuit or the SSR
The following two messages are diagnostic alarms produced as a result of failure within theequipment or wiring connections. They appear for mode 2 operation only.
#65D Heater Fail No current is being drawn while the controller output demandsignal is on
5D SSR Fail The load is continuously on while the controller outputdemand signal is off
ActualTemperature(PV)
HOME Display
D)5
OP1 OP2
Installation and Operation Handbook Load Current Monitoring and Diagnostics
2216e Controller E-5
TO SET THE ALARM TRIP LEVELS
Do This This Is The Display You Should See Additional Notes
From the HOMEdisplay
press until the)) )O6)O6 isdisplayed
Press button
until the desiredalarm number isdisplayed
Press or
to adjust the alarmtrip level
To select the AlarmList header
To select thediagnostic alarmparameter foundunder the Alarm Listheader
The alarm trip level isset to 123
RELAY OUTPUTS
Any plug in module can be used for alarms provided they are not already being used foranother purpose , such as control. Any one or more alarms can be attached to an output,which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operatingexternal beacons or audible devices.
)))O6)O6
BBBBBB
or indicates the alarmnumber;BBB indicates thealarm type:-e.g. )5 or #5
Load Current Monitoring and Diagnostics Installation and Operation Handbook
E-6 2216e Controller
TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS
Configuration of PDS load current diagnostics is in four parts:-
1. Configure the Logic Module for PDSIO Mode 1 or 2 operation..2. Configure the Low and High Current trip alarms.3. Attach the alarms to operate an output relay.4. Set up the Scaling Factor.
First enter Configuration Level. See Chapter 5
TO CONFIGURE THE LOGIC MODULE FOR PDSIO MODES 1 OR 2
Do This This Is The Display You Should See Additional Notes
Press until the /. isdisplayed
Press to showO
Press to show9.
Press or to show 5 or5 as required.
Press to show.
Press or toshow ./5
This opens theconfiguration listassociated withmodule position 1A
This shows theidentity of the module
The module identityis logic output
This shows thefunction of module
The module functionis set to PDSIOmode 1
This sets the outputsignal to normal forheating control
/. /.
OO)/")/"
9.9.55
.../5./5
Installation and Operation Handbook Load Current Monitoring and Diagnostics
2216e Controller E-7
TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS
Alarm 1 will be configured as Load Current Low ()5)Alarm 2 will be configured as Load Current High (#5)
Do This This Is The Display You Should See Additional Notes
Press button
until the ) /. is
displayed
This opens theconfiguration listwhich contains theAlarms
Press to show) (alarm 1)
Press or toshow )5
Press until) (alarm 2)appears
Press or to show #5
To select alarm 1
To make alarm 1 =Low Current
To select alarm 2.
To make alarm 2 =High Current
Note:- The above alarms are known as SOFT ALARMS because they are indicationonly.
))/. /.
)))5)5
After 0.5 sec the displaywill blink to show thealarm type has beenaccepted
))#5#5
After 0.5 sec the displaywill blink to show thealarm type has beenaccepted
Load Current Monitoring and Diagnostics Installation and Operation Handbook
E-8 2216e Controller
TO ATTACH SOFT ALARMS TO A RELAY OUTPUT
Any one alarm indicated above may be attached to an output (normally a relay).Alternatively any combination of alarms may be attached to operate a relay using theprocedure below:-
Do This This Is The Display You Should See Additional Notes Press “PAGE” key
as many timesas necessary to /.
Press untilO"D appears
Press or until the first alarmyou wish to attach tothe 3A output isdisplayed e.g. #65
Repeat the abovestep for every alarmto be attached to theoutput
Any output modulecan be configured foran alarm outputprovided it is notused for any otherpurpose, eg as acontrol output.In place of youshould select themodule required, i.e. or
O! = digitalfunctions./$ = no change
After 0.5 second thedisplay will revert to./$ to attach thealarm
Each time you scrollthrough the table ofalarms note that twodecimal pointsappear. Thisconfirms that theparticular alarm hasbeen attached to theoutput, i.e. #6D5DD5D etc
To remove alarms from an output press or until )5 appears in the lowerdisplay. This will clear all alarms attached to this output.
O"D O"D ./D$./D$
/. /.
O"D O"D #65 #65
O"D O"D ./D#./D#
0.5 sec
Alarms Connected to a RelayOutput
N!.
./5
O.: OutputModule
SoftAlarms OR
3A
3B
Installation and Operation Handbook Load Current Monitoring and Diagnostics
2216e Controller E-9
THE SCALING FACTOR
The value of the current displayed on the controller is scaled using the scaling factor. Thisis found in the O.6 /. list. It is set, by default, to 100 and assumes a single turnthrough the current transformer. If two turns are made through the current transformer itwill be necessary to adjust the scaling factor to 50 to obtain the same reading.Under normal conditions you should not need to change the scaling factor.If, however, you wish to change the sensitivity of the current reading, for example, to readvery low currents you may need to change the number of turns through the PDCTX and/oradjust the scaling factor to compensate. See also note 1 below.
TO ADJUST THE SCALING FACTOR
Do This This Is The Display You Should See Additional Notes
Press button
until O.6 /. is
displayed
Press until)D#O is displayed
Press or to change the scalingfactor
Note 1:-Minimum Resolvable CurrentTE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10.PDCTX 4A RMS for a single turn through the PDCTXShould you wish to read currents lower than 4A using a PDCTX it is necessary to increasethe number of turns through the PDCTX and adjust the scaling factor to compensate.For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factorto 25 as shown in the table below.
Scalar = 100/N Where N = Turns through PDCTXN Scalar1 1002 504 255 2010 10
O.6O.6/. /.
)D#O)D#O
Load Current Monitoring and Diagnostics Installation and Operation Handbook
E-10 2216e Controller
Maximum Resolvable CurrentTE10 Determined by the maximum range of the SSRPDCTX 100A (or 100 ampere turns)
Finally Exit configuration level. See Chapter 5.
Installation and Operation Handbook Retransmission
2216e Controller F-1
Appendix F RETRANSMISSION
WHAT IS RETRANSMISSION
The controller can be configured to generate an analogue output signal which represents aselected parameter.The parameters which can be configured for retransmission are:-
1. Process Variable2. Setpoint3. Error4. Control Output
The retransmission signal is available as 0-20mA, 4-20mA, 0-5V, 1-5V or 0-10V and isconnected to terminals 1A and 1B when module 1A is fitted as a DC module.
Retransmission Installation and Operation Handbook
F-2 2216e Controller
TO CONFIGURE THE CONTROLLER FOR RETRANSMISSION
A DC module must be fitted in module position 1A.
First enter configuration level. See Chapter 5.Then:-
Do This This Is The Display You Should See Additional Notes
Press button
until the /. is
displayed
This opens theconfiguration list formodule 1A.
Press to showO
Press to show9.
Press or to select theparameter forretransmission
Press to show.
This is the identity ofthe module fitted inthis position
The module must bea DC output D0
If 9. is aretransmissionparameter the valueof . has noeffect.
/. /.
OOD0D0
9.9.0;0;
.../5./5
The choices are:-
./. Output turned off
Control Outputs
#7 Heat control output
) Cool control output
Retransmission
0 Output demand
0; Process Variable
55 Error
=0 Setpoint (working)
Installation and Operation Handbook Retransmission
2216e Controller F-3
Press to show96D)
Press to show
96D#
The retransmittedoutput signal can belimited by adjustingthese parameters.
To reverse theoutput, set 96D) toD and 96D# toD.
SCALING RETRANSMITTED OUTPUT SIGNALS
The analogue output signal may be set between 0 and 20mA. A 4-20mA output is achievedby applying an offset as described below.A 0 to 10Vdc output may be achieved by fitting a 500 ohm resistor across the outputterminals 1A and 1B. A 0 to 5Vdc output may be achieved by fitting a 250 ohm resistoracross the output terminals 1A and 1B. Suitable resistors are supplied with the controller.
To Range Retransmitted Output 00
96D)96D)DD
96D#96D#DD
87D#87D)
% Output
For output of 0-100% = 0-20mA
set 96D# to 20.0 and 96D) to 0.0
For output of 0-100% = 4-20mA
set 96D# to 20.0 and 96D) to 4.0
Retransmission Installation and Operation Handbook
F-4 2216e Controller
To Range Retransmitted Setpoint 00 or Process Variable 0;0;
To Range Retransmitted Error 5555
For output of 0 - 1000 oC = 0-20mA
set 96D) to 0.0 and 96D# to 20.0
and 5.!D) to 0.0 and 5.!D# to 1000
5.!D) is the low limit of the input range
5.!D# is the high limit of the input range
These are found in the O0 /. list asdescribed in Chapter 5. If the range limits are notset the retransmitted output is the maximum inputrange as stated in the order code, Appendix A.
The retransmitted output value is dependent uponthe range limits 5.!D# and 5.!D) set in the O0/. list of the controller.
The following examples are given to illustrate theretransmitted error values:
Example 1:Type K thermocouple,5.!D) = -2005.!D# = +200Retransmitted Value0mA for an error of -20010mA for an error of 020mA for an error of +200Example 2:
As above but 5.!D) = -10 and 5.!D# = 400Retransmitted Value0mA for an error of -100.0487mA for an error of 020mA for an error of +400Note:
To read a negative error it is necessary to set5.!D) to a negative limit
87D#87D)
5."D)
5."D#
87D#87D)
5."D)
5."D#
0