model gfy - tornatech€¦ · gfy-di500 156 [6-¼"] /e electric fire pump controller reduced...
TRANSCRIPT
August 2018
Technical Data Submittal Document
Contents:Data Sheets
Dimensional DataWiring SchematicsField Connections
Project: Customer: Engineer: Pump Manufacturer:
The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.
Note:
Model GFYWye-delta Open
Electric Fire Pump Controller
2018-2019
2
Technical DataModel GFA Electric Fire Pump Controller
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeAugust 2018
From normal incoming power through Disconnecting Means (IS/CB)
2018-2019
Standard & Certification
Built to NFPA 20 (latest edition)
□ CE Mark: Various EN, IEC & CEE directives and standards
Enclosure
Protection RatingIP55
Accessories• Bottom entry gland plate
Disconnecting Means
• Isolating switch and circuit breaker:Isolating switch rated not less than 115% of motor full load currentCircuit breaker continuous rating not less than 115% of motor full load currentOvercurrent sensing non-thermal type, magnetic onlyInstantaneous trip setting of not more than 20 times the motor full load current
• Individual operating handles
Emergency Start Handle
• Flange mounted• Pull and latch activation• Integrated limit switch• Across the line start (direct on line)
Locked Rotor• Operate shunt trip to open circuit breaker• Factory set at 600% of motor full load current• Trip between 8 and 20 seconds
Electrical Readings
• Voltage phase to phase (normal power)• Amperage of each phase when motor is running
Pressure Readings
• Continuous system pressure display• Cut-in and Cut-out pressure settings
Paint Specifications• Red RAL3002• Powder coating• Glossy textured finish
T2
T1
T31M
T4
T6
T52M
1S
3L2
1M
CR4
2M
CR5
1S
CR5 2M
1S
3L1
3L2
3L3
3L1
M
3
Technical DataModel GFA Electric Fire Pump Controller
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
August 2018
Pressure and Event recorder
• Pressure readings with date stamp• Event recording with date stamp• Under regular maintained operation, events can be stored in memory for up to 5 years.• Data viewable on operator interface display screen
Pressure Sensing
• Pressure transducer for fresh water application• Pressure sensing line connection 1/2” Female NPT• Drain connection 3/8”• Rated for 0-500PSI working pressure (calibrated at 0-300psi)• Externally mounted with protective cover
Visual Indications & Alarms
• Power available• Phase reversal• Motor run• Pump room alarm• Motor trouble• Phase loss• Low water level
Remote Alarm Contacts
SPDT-8A-250V.AC• Power available• Phase reversal• Motor run• Common pump room alarm
• Overvoltage • Undervoltage • Phase unbalance• Common motor trouble
• Overcurrent • Undercurrent • Fail to start
ViZiTouch Light Operator Interface
• Embedded microcomputer with software PLC logic• 4.2” color touch screen (HMI technology)• Upgradable software• Expandable storage• Multi-language
Operation
Automatic Start • Start on pressure drop• Remote start signal from automatic device
Manual Start
• Start pushbutton• Run test pushbutton• Deluge valve start• Remote start from manual device
Stopping • Manual with Stop pushbutton• Automatic after expiration of minimum run timer **
Timers Field Adjustable & Visual Countdown
• Minimum run timer **(off delay)• Sequential start timer (on delay)• Manual test timer
ActuationVisual Indication
• Pressure• Non-pressure
Mode • Automatic• Non-automatic
• Deluge valve start• Remote automatic start• Remote manual start• Overcurrent • Undercurrent• Undervoltage• Overvoltage
• Phase unbalance• Locked rotor• Fail to start• Low discharge pressure• Pump on demand/Automatic start• Emergency start• Manual start
** Can only be used if approved by the AHJ
4
Technical DataModel GFA Electric Fire Pump Controller
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeAugust 2018
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
L01 Other language and English (bilingual)
L02 French
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
D14 Anti-condensation heater & thermostat
5
Technical DataModel GFA Electric Fire Pump Controller
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
August 2018
4
9
11
10
5 6 7
3
2
1
88
12
ViZiTouch Light Operator Interface
1 - Power on LED2 - Color touch screen3 - Alarm LED4 - HOME page button 5 - ALARM page button6 - CONFIGURATION page button7 - HISTORY page button
8 - USB port9 - START button10- Contextual navigation pad11 - STOP button12 - RUN TEST button
PANTONE 82-3-2 CBLACK
Drawing No.
DATEDESCRIPTION
DESIGNED BYVER
REV.
2 3 4 5
3 4 5 6 72
6
G
H
0 1 8
0 1
B
C
D
E
F
I
A A
7 8
0. FIRST ISSUE 12/09/12
GFX-S1-ViZi
815 [32-⅛"]
250 [9-⅞"]600 [23-⅝"]
952 [37-½"] 850 [33-½"]
250 [9-⅞"]
456 [18"]
142 [5-⅝"]
78 [3-⅛"]
677 [26-⅝"]
366 [14-⅝"]
77 [3"]
27 [1-⅛"]
1/2 " F.NPT
GFY-DI500
156 [6-¼"]
/E
ELECTRIC FIRE PUMP CONTROLLERREDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION)Dimension BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
Model: GFY
PROJECTION
Power Table
Voltage Min Max
220-2405 HP 75 HP
3.7 kW 55 kW
380 /400 / 4155 HP 125 HP
3.7 kW 90 kW
- All Dimensions are in Millimeters (Inches)- Paint: Textured Red RAL 3002.- Bottom Conduit Entrance Through Removable Gland Plate Recommended- Use Watertight Conduit and Connector Only.- Protect Equipment Against Drilling Chips.
Notes:- IP55 Assembly
Sensing LineConnection
25 [1"]
25 [1"]
1. GENERAL REVISION 13/11/162. Révision du logo 18/06/15
Drawing No.
DATEDESCRIPTION
DESIGNED BYVER
REV.
2 3 4 5
3 4 5 6 72
6
G
H
0 1 8
0 1
B
C
D
E
F
I
C
A A
7 8
G
P.1
0. FIRST ISSUE 12/09/12
GFX-S1-ViZi
3L1 (P.2/D5)
P2
DI0
CO
M
CO
M
J14
DI1
CO
M
DI2
CO
M
DI3
CO
M
DI4
CO
M
DI5
CO
M
DI6
CO
M
DI7
24V
GN
D
J13
(+)
(-)J16
J6
RS485P1
J3
J11
(P.2 / G5)P1
18
20
19
21
17
3
2(P.2 / F4)
3L1
3L33L2
1L1
1L21L3
6465
6667
6869
3L13L23L3
(P.2/F6)
(P.2/F8)
GFY-WS5001. REMOVED SURGE ARRESTER 13/04/23 /E
ELECTRIC FIRE PUMP CONTROLLERREDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION)Wiring schematic BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
Model: GFY
Main Board
To I/O Relay Board P1
** Contact closes when emergency starts is in "ON" position.
To J45
To J76
White
Black
White
Black
White
Black
To J57
Drawing for information only.Manufacturer reserves the right to modify this drawing whitout notice.Contact manufacturer for "As Built" drawing.
2. Révision du logo 18/06/15
Drawing No.
DATEDESCRIPTION
DESIGNED BYVER
REV.
2 3 4 5
3 4 5 6 72
6
G
H
0 1 8
0 1
B
C
D
E
F
I
C
A A
7 8
G
P.2
0. FIRST ISSUE 12/09/12
GFX-S1-ViZi
J40 J42 J37 J39
11 1214
J19
J18
J41
11 1412
J36
11 1412
J38 AI4-
IN (-)(+)
J14 J15 J16 J17
SV1
NG
J43
GN
D
ST2
J45+ REC
GN
DJ44
N L
J47
24VAC
31
H2
H1
J86 57
J573 24 1
6
57
J76
3
24
1
8
31
3230
J25
34
3533
36
2923 272521
2422 26 28
2 1
J53J1
P1
37
38
AI3-
IN (-)(+)
PT1-
IN
(-)(+)
PT2-
IN
(-)(+)
TB1 TB2 TB3 TB4 TB5
J2*J1*
(P.1 / H5)
LS1
X1
X23L23L13
1
3L1
3L2
3L1
3L2
(P.1 / F1)3L1
11 121411 1214 11 121411 121411 121411 1214
XTR1
(Fail Safe)
23
(P.1 / C1)
3L3
(P.1 / D1)
(P.1 / G3)
68 67 6669 65 64
1M
1M
GFY-WS5001. 13/04/23REMOVED SURGE ARRESTER /E
ELECTRIC FIRE PUMP CONTROLLERREDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION)Wiring schematic BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
Model: GFY
To ViZiTouchMain Board
Mot
or R
un
Powe
r Ava
ilable
Phas
e Re
v.
Pum
p Ro
om A
larm
Mot
or T
roub
le
Rem
ote
Man
ual S
tart
Lock
out
Rem
ote
Auto
Sta
rtDe
luge
Valve
Wat
er R
eser
voir
Low
* Remove this jumper to use this feature** Contact closes when emergency starts is in "ON" position.
White
Black
White
Black
I/O Relay Board
Red Whi
teBl
ack
Blac
kR
edWhi
te
BlackRed
White
Red
Gre
enR
edG
reen
To ST
To3L1-2-3
To CR4
ToCT1-2-3
Whi
teBl
ack
Whi
teBl
ack
2. Révision du logo 18/06/15
Drawing No.
DATEDESCRIPTION
DESIGNED BYVER
REV.
2 3 4 5
3 4 5 6 72
6
G
H
0 1 8
0 1
B
C
D
E
F
I
A
7 8
P.3
0. FIRST ISSUE 12/09/12
GFX-S1-ViZi
J40 - 12J40 - 11J40 - 14
J42 - 12J42 - 11J42 - 14
J39 - 12J39 - 11J39 - 14
J37 - 12J37 - 11J37 - 14
TB1
TB2
TB3
TB4
J19 - 12J19 - 11J19 - 14
31
32
30
34
35
33
36
29
23
27
25
24
26
28
J25
*J1
*J2
0.5 Nm
0.5 Nm
38
37
12 - 24 AWG
12 - 24 AWG
GND
GND
(Fail Safe)
M
T6 T4 T5
2M
L2L1IS
L3
T1 T2 T3
1M
GFY-WS5001. 13/04/23REMOVED SURGE ARRESTER /E
ELECTRIC FIRE PUMP CONTROLLERREDUCED VOLTAGE / WYE DELTA (OPEN TRANSITION)Terminals diagram BUILT TO THE LATEST EDITION OF THE NFPA 20 STANDARD
Model: GFY
Field Connections Alarm ContactsTerminals Wire Size:
Motor Run
Power Available
Phase Rev.
Pump Room Alarm
Motor Trouble
I/O Relay Board
I/O Relay Board
Remote Manual Start
Lockout
Remote Auto Start
Deluge Valve
Water Reservoir Low
Control ConnectionsTerminals Wire Size:
* Remove this jumper to use this feature
Field ConnectionsNormal Power Connections
Normally ClosedOpens to alarm
Normally OpenedCloses to alarm
Normally ClosedOpens to alarm
Normally ClosedOpens to alarm
Normally ClosedOpens to alarm
Normally ClosedOpens to alarm
Normally OpenedCloses to alarm
Normally OpenedCloses to alarm
Normally OpenedCloses to alarm
Normally OpenedCloses to alarm
Ground
Incoming Power
2. Révision du logo 18/06/15