modeling of generators for transient studies transients in power system may 2009
TRANSCRIPT
MODELING OF GENERATORS for Transient Studies
Transients in Power System MAY 2009
MODELING OF GENERATORS Model of a device is very dependent on its
physical attributes A generator model would be quite different
from a transformer model A generator has more coils than a
transformer, however they are connected in parallel
Generator coils on the other hand have relatively few turns
MODELING OF GENERATORS A turn has these parts: straight sections in
slots, with significant capacitance to grounded slot walls & to other conductors in the slot , but negligible capacitance to conductors elsewhere
There are end connections with less capacitance to frame & more mutual capacitance with other conductors in end or overhang region
The inductances, magnetic flux linkages per unit current are likewise different
MODELING OF GENERATORS
How different depends on speed of transient event
Eddy currents prevent immediate penetration of flux into stator iron and into adjacent turns for very fast transients
Hydro generators are different from turbo generators in that slots are shorter & the end sections longer
Hydro generators have more turns per coil than turbo generators
MODELING OF GENERATORS
Picture just presented advises that a good model for generator may comprise :
- a number of short transmission lines of alternatively low & high surge
impedances (corresponding to slot & end regions) connected in series or multiple π sections to represent winding fractions
Experience shows such an elaborate portrayal is rarely justified
MODELING OF GENERATORS
The form of a model depends on how it is to be used
A popular way of connecting generators is the unit scheme
G: generator GB: generator bus GSUT: generator step-up transformer AT: auxiliary transformer
MODELING OF GENERATORS In some stations, specially nuclear stations, a
generator circuit breaker is connected in main bus between generator and auxiliary tap so that auxiliaries can be supplied from system when generator is out of service
need to be concerned with transients caused: by lightning and switching surges on power system which reach generator through GSUT, & by faults , cct. B. operations on generator bus
Models used should be appropriate to source & nature of stimulus
MODELING OF GENERATORS Response of a 270 MVA, 18 kV, turbo
generator to a step of voltage shown below
test made at low voltage by applying 12 V from a stiff source , between phase & ground, & measuring transient on terminal of a second phase
MODELING OF GENERATORS
Remarkable feature of last oscillogram: is its near single frequency appearance
there is clearly at least one other frequency initially, however it dies out quickly
This evidence suggests generator can be represented by a relatively simple model at least as far as this particular event concern
An equivalent cct. Shown in next slide, in which each phase represented by a π cct.
MODELING OF GENERATORS
Figure: simple terminal model for a generator
MODELING OF GENERATORS In this figure R and L represents resistance
and leakage inductance of each phase and C is phase capacitance
Result of applying this model for 270 MVA generator is illustrated in next slide
Where for this machine L=540 μH & C=0.38 μF, the resistance selected is discussed later
Correspondence to measured result reasonable, however initial minor loop is missing
MODELING OF GENERATORS
Application of Model to a 270 MVA Gen.
MODELING OF GENERATORS This is attributed to omission of mutual
coupling between phase which must surely exist
A simple way of including such coupling proposed by Lauber as illustrated in figure below
MODELING OF GENERATORS
In this figure each phase of winding concentrated & produces uniform flux density in air gap
Outcome is a mutual phase inductance which is 1/3 of phase self-inductance
Note: normal convention of currents negative flux linkage
in general this coupling factor designated by K will not be 1/3 due to distributed nature of winding
MODELING OF GENERATORS
To include mutuals in equivalent transient model of this generator, L must be increased by 1+K & a mutual of K must be introduced between each pair of phases
Alternatively, L can be left intact & an additional inductance –KL inserted in neutral
these modified models shown in next slide
MODELING OF GENERATORS
Terminal transient models for a generator including mutual phase coupling
MODELING OF GENERATORS Using this corrected model, the voltage shown in
next slide will be observed at terminals B & C when generator is energized on phase A
question of damping to include in generator model is of some concern
figure of last slide is matched with the measured result by arbitrarily choosing value of resistance , chosen value is 5 Ω
if assume x/R=7 R=0.029 Ω This indicate damping arises mostly due to eddy
current losses
MODELING OF GENERATORS
Application of modified model to 270 MVA Gen.
MODELING OF GENERATORS This result suggest that ωL/R should be
considered constant At principal frequency of the response (6.9
kHz) resistance would be 115 times the 60 Hz value
model just described is suitable where an oscillatory disturbance created
Examples: disconnecting of generator by its breaker or disconnection of entire generator / transformer unit by opening H.V. breaker
MODELING OF GENERATORS
fast rising transients, such as those created by a reignition in a disconnect switch in generator bus, or a fast rising surge coupled capacitively through GSUT, need different model
in these circumstances generator might be represented by a distributed parameter model which appears on entry as a surge impedance, while choice of value depend on circumstances
MODELING OF GENERATORS As mentioned, conductor in slot behaves
like a short transmission line Initially, magnetic flux is confined within the
slot, screened from stator iron by eddy currents
These effects maintain L & consequently surge impedance Z0 , low
however both increase with time as flux penetrates iron
surge impedance of end connections is higher since inductance is higher & capacitance lower
MODELING OF GENERATORS Computation of inductance, based on geometry of
the winding Dick Formula for average surge impedance is: Z0=(Ks L’’d/CdNp)^0.5 L’’d=sub-transient inductance/phase Cd= capacitance/phase , Np=number of poles Ks is a geometrical factor typically about 0.6 Validity of formula for two machines in Ontario Hydro
system, verified by comparison: Machine Rating Z0 measured Z0
P: NGS 635 MVA/ 24 kV 28 Ω 27Ω A:TGS 270 MVA/18 kV 20 Ω 21Ω
MODELING OF GENERATORS Surge impedances are relatively low, lower
than surge impedance of isolated phase bus Which is around 50 Ω And it means surge arriving on the bus to
generator face a reduction due to a refraction coefficient of less than one
However it is expected that these values will increase as flux penetrates core steel
Abetti et. al. indicate a change from 50 Ω at 1 μs to 80 Ω at 10 μs for a 13.8 kV, 100 MVA generator
MODELING OF GENERATORS
A distributed parameter model is also appropriate for studying transient in a generator
Figure below shows such a model
MODELING OF GENERATORS Surge source shown by a thevenin equivalent, (Vb,
Zb) Where Vb twice incident wave (as discussed in chapter
nine) inductance Lc typically a few micro-Henries,
associated with unbonded enclosures in isolated phase bus, CTs, winding end ring & end winding preceding first winding slot
Z1 & Z2 represent surge impedances of slotted & end connection regions
Remaining coils of gen. winding modeled by a fixed Z0
This model applied to the 635 MVA/24 kV gen. & results shown in next slide
MODELING OF GENERATORS
Consequences of applying a step to 635 MVA/24 kV gen, through a 50 Ω bus