1 T-300 Rev B
INTRODUCTION
1.1 INTRODUCTION
The Carrier Transicold model 69NT40 series units areof lightweight aluminum frame construction, designedto fit in the front of a container and serve as thecontainer’s front wall.
1.2 CONFIGURATION IDENTIFICATION
Unit identification information is provided on a platelocated near the compressor. The plate provides the unitmodel number, the unit serial number and the unit partsidentification number (PID). The model numberidentifies the overall unit configuration while the PIDprovides information on specific optional equipment,factory provision to allow for field installation ofoptional equipment and differences in detailed parts.This manual provides tabular listing of unit model andPID numbers, identification of the required Operationand Service Manual, required Parts List andidentification of the original equipment options andparts.The Operation and Service manual identificationnumbers take the form T--###. The Parts List manualsuse the sameT--### form with the addition of “PL”. Forexample, T--305 is the manual number for a unit withEverFresh option and T--305PL is the parts list for thisunit.If the Model Number or PID you are researching is notlisted herein, aweekly updated copymaybe found at theCarrier Web site, www.container.carrier.com.
1.3 OPTION DESCRIPTION
Various options may be factory or field equipped to thebase unit. These options are listed in the tables anddescribed in the following subparagraphs.
1.3.1 Battery
The refrigeration controller may be fitted with standardreplaceable batteries or rechargeable battery pack.When the unit is fitted with the EverFresh controlledatmosphere option, the CA controller is fitted with thesame battery option.
1.3.2 Dehumidification
The unit may be fitted with a humidity sensor. Thissensor allows setting of a humidity set point in therefrigeration controller. In the dehumidification modethe controller will operate to reduce internal containermoisture level.
1.3.3 Control Box
The control box may be of aluminum or compositematerial and each type boxmaybe fittedwith a lockabledoor.
1.3.4 Temperature Readout
The unit may be fitted with suction and dischargetemperature sensors. The sensor readings may beviewed on the controller display.
1.3.5 Pressure Readout
The unit may be fitted with suction and dischargepressure gauges or suction and discharge transducers orno pressure readout. The transducer readings may beviewed on the controller display.1.3.6 USDA
The unit may be supplied with fittings for additionaltemperature probes which allow recording of USDACold Treatment data by the integral DataCORDERfunction of the Micro--Link refrigeration controller.When the probes are factory suppled, an additional codeis provided to identify the required replacement part.1.3.7 Interrogator
Units that use theDataCORDER functionare fittedwithinterrogator receptacles for connection of equipment todownload the recorded data. Two receptacles may befitted, one accessible from the front of the container andthe other mounted inside the container (with the USDAreceptacles).1.3.8 Remote Monitoring
The unit may be fitted with a remote monitoringreceptacle. This item allows connection of remoteindicators for COOL, DEFROST and IN RANGE.Unless otherwise indicated, the receptacle is mounted atthe control box location.1.3.9 Communications
The unit may be fitted with a communications interfacemodule. The communications interface module is aslave module which allows communication with amaster central monitoring station. The module willrespond to communication and return information overthe main power line. Refer to the ship master systemtechnical manual for further information.1.3.10 Compressor
The unit may be fitted with one of three compressoroptions. The options include a single speedreciprocating compressor, a dual speed reciprocatingcompressor or a scroll compressor.1.3.11 Condenser Coil
The unit may be fitted with a 2 row, 4 row or 5 row coilusing nominal 3/8 inch tubing, or the unit may be fittedwith a 3 row or 4 row coil using 7mm tubing. Therequired refrigerant charge is different for each coil.1.3.12 Autotransformer
An autotransformermay be provided to allow operationon 190/230, 3phase, 50/60 hertz power. Theautotransformer raises the supply voltage to thenominal 380/460 volt power required by the base unit.The autotransformer may also be fitted with anindividual circuit breaker for the 230 volt power.
If the unit is equipped with an autotransformer andcommunications module, the autotransformer will befitted with a transformer bridge unit (TBU) to assist incommunications.
2T-300 Rev B
1.3.13 Temperature Recorder
One of three recording devices may be fitted to the unit.The devices include a mechanical recordermanufactured by Partlow Corporation, a mechanicalrecorder manufactured by Saginomiya Corporation,and an electronic recorder manufactured by PartlowCorporation.1.3.14 Gutters
Rain gutters may be fitted over the control box andrecorder (or CA controller) section to divert rain awayform the controls. The different gutters include standardlength bolted gutters, extended length gutters andriveted gutters.1.3.15 Handles
The unit may be equipped with handles to facilitateaccess to stacked containers. These handlesmay includefixed handles (located at the sides of the unit) and/or ahinged handle at the center (attached to the condensercoil cover).1.3.16 Thermometer Port
Theunitmay be fittedwith ports in the front of the framefor insertion of a thermometer tomeasure supply and/orreturn air temperature. If fitted, the port(s) will require acap and chain.1.3.17 Water Cooling
The refrigeration system may be fitted with a watercooled condenser. The condenser is constructed usingcopper--nickel tube for sea water applications. Thewater cooled condenser is in series with the air cooledcondenser and replaces the standard unit receiver.Whenoperating on the water cooled condenser, the condenserfan is deactivated by either a water pressure switch orcondenser fan switch.1.3.18 Back Panels
Back panel designs include panels of aluminum andstainless steel. Panels may have access doors and/orhinge mounting.1.3.19 460 Volt Cable
Various power cable and plug designs are available forthe main 460 volt supply. The plug options tailor thecables to each customers requirements.1.3.20 230 Volt Cable
Units equipped with an autotransformer require anadditional power cable for connection to the 230 voltsource. Various power cable and plug designs areavailable. The plug options tailor the cables to eachcustomers requirements.1.3.21 Cable Restraint
Various designs are available for storage of the powercables. These options are variations of the compressorsection front cover.1.3.22 Upper Air (Fresh Air Make Up)
The unit may be fitted with an upper fresh air makeupassembly. These assemblies are supplied in twodesigns, the standard design and the micro design. Theopenings may also be fitted with screens.
1.3.23 Lower Air (Fresh Air Make Up)
The unit may be fitted with a lower fresh air makeupassembly. These assemblies are supplied in twodesigns, the standard design and the macro design. Theopenings may also be fitted with screens.
1.3.24 Controlled Atmosphere
Controlled atmosphere units may be fitted with theTransFresh or the complete Carrier TransicoldEverFresh option.
For information on the TransFresh system, contactTransFresh Corporation, P.O. Box 1788, Salinas CA93902
The EverFresh option is the addition of the CarrierTransicold EverFresh controlled atmosphere system.This system continuously monitors and controlsoxygen and carbon dioxide levels in the container.
1.3.25 Arctic Mode
To improve operation in cold ambients, the unit may befitted with a crankcase heater and/or a condensate drainline heater. The crankcase heater is operated, beforestart--up, to warm the compressor oil and boil off anyliquid refrigerant that may be present in the crankcase.The drain line heater is operated to prevent freezing ofthe evaporator condensate drain system.
1.3.26 Humidification
The unit may be equipped with the Carrier TransicoldNatureFresh humiditymanagement system. Thesystemincludes a water tank, water pump, water heater andatomizer along with various control and monitoringdevices. It is designed to add additional moisture intothe supply air for control of cargo moisture level. Aseparately bound manual covering operation and partsfor the NatureFresh System is available, see thefollowing chart.
ManualNumber
EquipmentCovered
Type ofManual
T-297 Humidity ManagementSystem Option
TechnicalSupplement
1.3.27 Power Correction
The unit may be fitted with a set of power factorcorrection capacitors to assist in correction ofimbalance in current draw by the compressor.
1.3.28 Evaporator
Evaporator section options include a semi--hermeticthermal expansion valve, a hermetic thermal expansionvalve and two sizes of heat exchangers.
1.3.29 Evaporator Fan Operation
Two evaporator fan motor operation systems areavailable. On units with Normal Evaporator FanOperation, opening of an evaporator fan internalprotector will shut down the unit. On units equippedwith Single Evaporator Fan Capability, additionalrelays are installed to allow the unit to continue tooperate on a single fan.
3 T-300 Rev B
1.3.30 Labels
Operating Instruction and Function Code listing labelswill differ depending on the options installed. Forexample, additional operating instructions are requiredto describe start--up of a unit equipped with anautotransformer. Where the labels are available withadditional languages, they are listed in the parts list.1.3.31 Plate Set
Each unit is equipped with a tethered set of wiringschematic and wiring diagram plates. The plate sets areordered using a seven digit base part number and a twodigit dash number.If the table entry takes the form ##1, order plate79--01698--## where the “##” is the dash numberprovided in the table column.If the table entry takes the form ##2, order plate79--01793--## where the “##” is the dash numberprovided in the table column.If the table entry takes the form ##3, order plate79--01778--## where the “##” is the dash numberprovided in the table column.If the table entry takes the form ##4, order plate79--01801--## where the “##” is the dash numberprovided in the table column.If the table entry takes the form ##5, order plate79--01832--## where the “##” is the dash numberprovided in the table column.If the table entry takes the form ##6, order plate79--01843--## where the “##” is the dash numberprovided in the table column.Units with EverFresh controlled atmosphere have asecond set of plates for the controlled atmospheresystem. These plate sets are numbered and ordered inthe same manner.
1.3.32 ControllerReplacement controllers may be ordered as a universalun--configured controller (without configurationsoftware) or configured.The un--configured controller is ordered under partnumber 12--55458--00/5121.To order a configured controller the part number ischanged to 12--55061--00/5121 and the softwarenumber is added In the “--00” position. The softwarenumbers for each model is supplied in the tables.For example:to order a configured controller for a 69NT40--511--337,PID NT0652 the 12--55061--00/5121 number would bechanged to 12--55061--81/5121.1.3.33 Stepper DriveAll the units covered by this manual have suctionmodulating valves which act to control system capacity.Units indicated as being fitted with “stepper drive” havedigital control motors fitted to the suction modulatingvalve to open and close the valve in steps as required.1.3.34 Condenser GrilleTwo styles of condenser grilles are available, directbolted grilles and hinged grilles.1.3.35 Emergency BypassThe unit may be equipped with switches to allowemergency bypass of the controller. TheEMERGENCY BYPASS switch functions to bypassthe controller in the event of controller failure. TheEMERGENCY DEFROST switch functions to bypassall controls and place the unit in the defrost mode.1.4 OPTION TABLE CODESGenerally, the tabular option listing in the tablesprovides indication if the option is installed orprovisioned for. Where an option requires more than ainstalled/not installed indication, codes are establishedto identify the various options. The codes for each ofthese options is provided in the following OptionLegend.
4T-300 Rev B
OPTION LEGENDGENERAL-- = Feature Not ApplicableX = Features that apply to modelP = Factory Installation of Equipment to Allow
Field Installation
BATTERY CODESS = Standard (throw away) CellsR = Rechargeable Cells
CONTROL BOX CODESA = Aluminum Box Without Door LockAL = Aluminum Box With Door LockC = Composite Box Without Door LockCL = Composite Box With Door Lock
PRESSURE READOUT CODESG = Factory Installed Pressure GaugesT = Factory Installed Pressure TransducersSG = Factory Installed Suction Pressure Gauge
USDA CODESD = Option DV = Option V1 = Option 12 = Option 2
INTERROGATOR CODES1 = Left Straight Mount2 = Right Mount3 = Box Mount4 = Left Mount5 = Left Angled Mount6 = Right Mount
COMMUNICATIONS CODES1 = Standard2 = High Data Rate3 = Chipset Modem4 = Low Data Rate
COMPRESSOR CODES1R = Single Speed Reciprocating2R = Two Speed ReciprocatingS = Scroll
CONDENSER COIL CODES2 = Two Row Coil3 = Three Row (7mm) Coil4 = Four Row Coil5 = Five Row Coil
AUTOTRANSFORMER CODES1 = Transformer Fitted2 = Transformer with CB2 Fitted3 = Transformer with CB2 and Receptacle4 = Transformer with CB2 and Transformer
Bridging Unit
TEMPERATURE RECORDER CODES
OPTION TYPE PROBE
1 Partlow No
2 Partlow Yes
3 Partlow, Battery Operated No
4 Partlow Battery Operated Yes
5 Saginomiya No
6 Saginomiya Yes
7 Partlow Electronic, Standard ----
8 Partlow Electronic, Special ----
9 No Temperature Recorder ----
GUTTER CODES1 -- Standard Length Bolted Gutters2 = Standard Length Bolted (CA Units)3 = Extended Length Gutters4 = Riveted GuttersHANDLE CODES1 = Two Side and One Center2 = Two Side3 = One Center4 = One Right Side and Two CenterTHERMOMETER PORT CODES1 = Supply Air Port2 = Return Air PortB = Both PortsWATER COOLING CODESW = Water Pressure SwitchF = Condenser Fan SwitchBACK PANEL CODES1 = Bolted Panels2 = Bolted Panels with USDA Door3 = Bolted Panels with Probe Access Door4 = Hinged Panels5 = Hinged Stainless Steel Panels6 = Hinged Panels with Atomizer Door7 = Standard Panels with Additional Fasteners460 VOLT CABLE CODES1 = Option 12 = Option 23 = Option 34 = Option 45 = Option 56 = Option 67 = Option 78 = Option 89 = Option 9
5 T-300 Rev B
OPTION LEGEND -- (Continued)230 VOLT CABLE CODES1 = Option 12 = Option 23 = Option 34 = Option 45 = Option 56 = Option 67 = Option 78 = Option 89 = Option 910 = Option 10
CABLE RESTRAINT CODES1 = Cable Door2 = Left Bungy Cord Only3 = J--Hook4 = Left & Right Bungy Cord5 = Left Bungy Cord With Left Extended Guard6 = Left & Right Bungy Cord With
Extended Guards
UPPER AIR CODES1 = No Upper Fresh Air2 = Upper Fresh Air Installed3 = Upper Fresh Air Installed With Screen
LOWER AIR CODES1 = No Lower Fresh Air2 = Lower Fresh Air Installed3 = Lower Fresh Air Installed With Screen
CONTROLLED ATMOSPHERET = TransFreshE = Carrier Transicold EverFresh System
ARCTIC MODE CODESC = Crankcase HeaterL = Drain Line HeaterB = Both Crankcase Heater & Drain Line HeaterCONDENSER GRILLE CODESB = Bolted GrilleH = Hinged GrilleEVAPORATOR CODES1 = Original Coil with Semi--hermetic TXV and
Standard Heat Exchanger2 = Coil with Hermetic TXV and
Standard Heat Exchanger (4 Heaters)3 = Coil with Hermetic TXV and
Large Heat Exchanger (4 Heaters)4 = Helicox Hatched5 = NewCoil with Hermetic TXV and
Standard Heat Exchanger (6 Heaters)EVAPORATOR FAN CODES1 = Normal Evaporator Fan Operation2 = Single Evaporator Fan CapabilityLABEL CODES1 = English2 = English/Spanish3 = English/French4 = English/Korean5 = English/Traditional Chinese6 = English/Simplified Chinese7 = English/Japanese/Chinese8 = English/GermanEMERGENCY BYPASS CODESB = Emergency Bypass & Emergency DefrostEB = Emergency Bypass Only
6T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
531-06 0826 292 R X C X T D 1 -- P S 5 P 9 -- -- 1 P 1531-05 0615 292 R P C -- T P 1 -- P S 5 P 7 1 2 B F 1531-04 0600 292 R X C X T D 1 -- P S 5 P P -- -- -- F 1531-03 0597 292 R X CL -- T V/1 4 -- 2 S 5 P P -- 1 -- F 1531-02 0526 292 R P C -- T D 1 -- P S 5 P 7 -- -- -- -- 1531-01 0862 292 R P C -- T P 1 -- P S 5 2 P -- -- -- P 1
521-10 0108 268 R X A -- -- D 1 -- 1 1R 2 X 5 -- -- -- P 1
511-354 0863 285 -- P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1511-353 0857 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 1511-351 0861 285 R X C -- -- D 1 -- P 1R 3 P 9 -- -- 1 P 5
511-344 0819 296 -- -- C -- -- P 1 -- P 1R 3 1 9 -- -- -- P 1
0724 285 -- P C -- -- D 1 -- 2 1R 3 P 7 -- -- -- W 1
511-343 0809 285 R P C -- -- D 1 -- 1 1R 3 P P -- -- -- W 1511 3430821 285 R P C -- -- D 1 -- P 1R 3 P P -- -- -- P 1
511-342 0722 285 -- X C -- T P 1 -- 2 1R 3 P 7 -- -- -- W 1
511 3410718 285 -- X C -- T D 1 X P 1R 3 P 7 -- -- -- P 1
511-3410828 285 R X C -- T D 1 -- P 1R 3 P 5 -- -- -- P 1
511-340 0716 285 R X C -- G D 3 -- P 1R 3 P 5 -- 2 -- P 4511-339 0715 285 R X C -- G D 3 -- P 1R 3 P 5 -- 2 -- P 4511-338 0687 285 R X C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1511-337 0652 285 -- X C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1
0582 285 R P C -- -- P 1 P P 1R 3 P 7 1 -- B W 1
511 3340593 285 R X C -- T D 3 # P 1R 3 P 7 1 -- B W 4
511-334Note: NT0593 Unit is Fitted With Lower (External) Mounted Remote Monitoring
0721 285 R X C -- T D 3 X 2 1R 3 P 7 1 -- B W 4511-333 0673 285 R P C -- T P 1 X P 1 3 P 7 1 -- B W 1
0581 285 R P C -- T D 3 # P 1R 3 P 7 1 -- B W 4
511 3320633 285 R P C -- T D 3 # 2 1R 3 P 7 1 -- B W 4
511-3320820 285 R P C -- T D 3 # 2 1R 3 P 7 1 -- B W 4Note: NT0581, 0633 & 0820 Units are Fitted With Lower (External) Mounted Remote Monitoring
511-331 0563 285 R P C X T P 1 -- P 1R 3 2 8 1 -- B P 10577 285 R X C -- SG D 3 -- P 1R 3 3 P 4 -- -- P 10578 285 R X C -- -- D 3 -- P 1R 3 3 P 4 -- -- P 1
511 3300579 285 R X A -- SG D 3 -- P 1R 3 3 P 4 -- -- P 1
511-3300631 285 R X C -- SG D 3 -- P 1R 3 3 P 4 -- -- P 10642 285 R X C -- SG D 3 -- P 1R 3 3 P 4 -- -- P 10707 285 R X C -- SG D 3 -- P 1R 3 P P 4 -- -- P 1
7 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
531-06 0826 292 1 -- P -- 2 P -- H -- -- 4 1 1 033 -- 80 X --531-05 0615 292 1 -- P 1 2 -- -- H -- -- 4 1 5 003 -- 83 X --531-04 0600 292 1 -- P 1 2 -- -- H -- -- 4 1 1 003 -- 80 X --531-03 0597 292 2 -- 3 1 3 -- -- H -- -- 4 1 2 013 -- 80 X --531-02 0526 292 1 -- P 2 1 -- -- H -- -- 4 1 1 003 -- 65 X --531-01 0862 292 1 -- 2 2 1 -- -- B -- -- 4 1 1 016 -- 85 X --
521 100108 268 1 -- 1 2 1 -- -- B -- -- 1 1 4 # -- 16 X --
521-10Note: Plate Set for unit NT0108 = 69NT41-783-29
511-354 0863 285 1 -- P 2 1 -- -- H -- -- 5 1 8 005 -- 97 X --511-353 0857 285 1 -- P 2 1 -- -- H -- -- 5 1 1 005 -- 96 X --511-351 0861 285 1 -- P 2 1 -- -- H -- -- 5 1 1 005 -- 95 X --
511-344 0819 296 1 3 2 2 1 -- B B -- -- 2 1 1 202 -- 95 X --
0724 285 1 -- 2 2 1 -- -- H -- -- 2 1 7 032 -- 90 X --
511-343 0809 285 1 -- 1 2 1 -- -- H -- -- 2 1 2 032 -- 90 X --511 3430821 285 1 -- P 1 1 -- -- H -- -- 2 1 2 002 -- 90 X --
511-342 0722 285 1 -- P 2 1 -- -- B -- -- 2 1 7 032 -- 89 X --
511 3410718 285 1 -- P 2 1 P -- B -- -- 2 1 5 002 -- 88 X --
511-3410828 285 1 -- P 2 1 -- -- B -- -- 2 1 6 002 -- 88 X --
511-340 0716 285 6 -- P 2 1 -- -- H X -- 2 1 4 152 -- 87 X EB511-339 0715 285 6 -- P 2 1 -- -- H -- -- 2 1 4 142 -- 86 X EB511-338 0687 285 1 -- P 2 1 -- -- H X -- 2 1 2 132 -- 85 X --511-337 0652 285 1 -- P 2 1 -- B H -- -- 2 1 1 072 -- 81 X --
0582 285 1 -- P 3 1 -- -- B -- -- 2 1 7 511 -- 67 X --
511-334 0593 285 2 -- P 1 3 -- -- B -- -- 2 1 7 521 -- 67 X --
0721 285 2 -- P 1 3 -- -- B -- -- 2 1 7 032 -- 67 X --511-333 0673 285 1 -- P 1 1 -- -- B -- -- 2 1 7 002 -- 59 X --
0581 285 2 -- P 1 3 -- -- B -- -- 2 1 7 521 -- 48 X --0633 285 2 P 1 3 B 2 1 7 032 48 X511-332 0633 285 2 -- P 1 3 -- -- B -- -- 2 1 7 032 -- 48 X --511-3320820 285 2 -- P -- 3 -- -- B -- -- 2 1 7 032 -- 48 X --
511-331 0563 285 1 -- P 3 1 -- -- B -- -- 2 1 7 521 -- 79 X --0577 285 3 3 P 3 1 T -- H -- -- 2 2 2 611 -- 77 X EB0578 285 3 3 P 3 1 -- -- H -- -- 2 2 2 611 -- 77 X EB
511 3300579 285 3 3 P 3 1 P -- H -- -- 2 2 2 611 -- 77 X EB
511-3300631 285 3 3 P 3 1 T -- H -- -- 2 2 2 012 -- 77 X EB0642 285 3 3 P 3 1 -- -- H -- -- 2 2 2 012 -- 77 X EB0707 285 3 -- P 3 1 T -- H -- -- 2 1 2 012 -- 77 X EB
8T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
511 3290580 285 R X A -- -- P 3 -- P 1R 4 1 7 -- -- -- P 1
511-3290812 285 R X C -- G P 3 -- -- 1R 3 2 7 -- -- -- P 1
511-328 0576 285 R X C -- -- D 1 -- P 1R 3 P P -- -- -- P 10528 285 R X A -- G P 1 -- P 1R 4 P 7 -- -- -- P 1
511 3250539 285 R X A -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1
511-3250542 285 R X A -- -- P 1 -- P 1R 4 P 5 -- -- -- P 10543 285 R X A -- -- P 1 -- 1 1R 4 P 9 -- -- -- P 1
511-324 0551 285 R X A -- -- P -- -- -- 1R 4 P 7 -- -- -- P 10531 285 R P A -- -- P 1 -- P 1R 3 P P -- -- -- P 10532 285 R P A -- -- P 1 -- P 1R 4 P P -- -- -- P 10533 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10549 285 R P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 10552 285 R X A -- -- P 1 -- P 1R 4 P 7 -- -- -- P 10561 285 R P C -- -- P 1 -- P 1R 3 P 9 -- -- -- -- 10564 285 R -- C -- -- P 1 -- P 1R 3 P 9 -- -- -- P 10599 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10604 285 R P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 10630 285 R P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 10660 285 R P C -- -- P 1 -- P 1R 3 P 5 -- -- -- P 10661 285 R P C -- -- P 1 -- P 1R 3 2 7 -- -- -- P 10663 285 -- P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1
511 3230665 285 -- P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 1
511-3230668 285 -- P C -- -- P 1 -- 4 1R 3 P P -- -- -- P 10675 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10682 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10730 285 R P C -- -- P 1 -- P 1R 3 2 1 -- -- -- P 10731 285 -- P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10804 285 R P C -- -- P 1 -- P 1R 3 P 2 -- -- -- P 10805 285 R P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 10817 285 R P C -- -- P 1 -- P 1R 3 P 5 -- -- -- P 10822 285 -- P C -- -- P 1 -- P 1R 3 P 9 -- -- -- P 10823 285 R P C -- -- P 1 -- P 1R 3 P 9 -- -- -- P 10830 285 -- P C -- -- P 1 -- P 1R 3 2 7 -- -- -- P 10831 285 -- P C -- -- P 1 -- P 1R 3 P 7 -- -- -- P 10832 285 -- P C -- -- P 1 -- P 1R 3 2 2 -- -- -- P 10833 285 -- P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10477 285 R X A -- T D 3 -- P 1R 4 1 7 -- -- B W 4
511-322 0658 285 R X C -- T D 3 -- P 1R 3 -- 7 1 -- B W 4511 3220723 285 R X C -- T D 3 -- 2 1R 3 -- 7 1 -- B W 4
511-321 0476 285 R X A -- T D 3 X P 1R 4 2 7 1 -- B W 4
9 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
511 3290580 285 1 -- 2 2 1 -- -- H -- -- 2 2 2 291 -- 76 X --
511-3290812 285 4 3 2 2 1 T -- H -- -- 2 1 2 182 -- 76 X --
511-328 0576 285 1 -- P 3 1 -- -- H -- -- 2 1 1 511 -- 74 X --0528 285 1 -- 2 2 1 P -- H -- -- 2 1 1 341 -- 64 X --
511 3250539 285 1 -- 2 2 1 P -- H -- -- 2 1 1 341 -- 64 X --
511-3250542 285 1 -- 2 2 1 -- -- H -- -- 2 1 1 431 -- 64 X --0543 285 1 -- 2 2 1 -- -- H -- -- 2 1 1 431 -- 64 X --
511-324 0551 285 1 -- P 2 1 -- -- H X -- 2 1 1 431 -- 71 X --0531 285 1 -- P 2 1 -- -- H -- -- 2 1 1 431 -- 63 X --0532 285 1 -- P 2 1 -- -- H -- -- 2 1 1 341 -- 63 X --0533 285 1 -- P 2 1 -- -- H -- -- 2 1 1 511 -- 63 X --0549 285 1 -- P 2 1 -- -- H -- -- 2 1 1 511 -- 63 X --0552 285 1 -- P 2 1 -- -- H -- -- 2 1 1 341 -- 63 X --0561 285 1 -- P 2 1 -- -- H -- -- 2 1 1 511 -- 63 X --0564 285 1 -- P 2 1 T -- H -- -- 2 1 1 511 -- 63 X --0599 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0604 285 1 -- 2 2 1 -- -- H -- -- 2 1 1 511 -- 63 X --0630 285 1 -- P 1 1 -- -- H -- -- 2 1 1 002 -- 63 X --0660 285 1 -- 2 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0661 285 1 -- 2 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0663 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --
511 3230665 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --
511-3230668 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0675 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0682 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0730 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0731 285 1 -- P 2 1 -- -- B -- -- 2 1 1 002 -- 63 X --0804 285 1 -- P 2 1 P -- H -- -- 2 1 1 002 -- 63 X --0805 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0817 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0822 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 63 X --0823 285 1 -- P 1 1 -- -- H -- -- 2 1 1 002 -- 63 X --0830 285 1 9 2 2 1 -- -- B -- -- 3 1 4 002 -- 63 X --0831 285 1 -- P 2 1 -- -- H -- -- 2 1 8 002 -- 63 X --0832 285 3 3 2 2 1 -- -- B -- -- 3 1 1 002 -- 63 X --0833 285 1 -- P 2 1 -- -- B -- -- 3 1 1 002 -- 63 X --0477 285 5 -- P 3 1 -- -- B X -- 2 1 7 431 -- 60 X --
511-322 0658 285 2 -- P 1 3 -- -- B X -- 2 1 7 082 -- 60 X --511 3220723 285 2 -- P 1 2 -- -- B X -- 2 1 7 082 -- 60 X --
511-321 0476 285 5 2 5 3 1 -- -- B -- -- 2 1 7 401 -- 67 X --
10T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0455 285 -- X A -- G D 1 -- P 1R 4 P 5 -- 2 -- -- 4
511-320 0493 285 R X C -- G D 1 -- P 1R 4 P 5 -- 2 -- P 4511 3200530 285 R X A -- -- D 1 -- 1 1R 4 P 1 -- 3 -- P 10529 285 R X A -- -- D 1 -- 1 1R 4 P P -- 2 -- P 10536 285 R X A -- -- D 1 X P 1R 4 P 7 1 -- -- P 10537 285 R X A -- -- D 1 X P 1R 3 P 7 1 -- -- P 10541 285 R X A -- -- D 1 X P 1R 3 P 7 1 -- -- P 10550 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10603 285 R X CL X -- D 1 -- P 1R 3 P 7 -- -- -- P 10606 285 R X CL X -- D 1 -- P 1R 3 2 7 -- -- -- P 10618 285 R X C -- -- D 1 X P 1R 3 P 7 1 -- -- P 10629 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10636 285 R X C -- -- D 1 -- 1 1R 3 P P -- 2 -- P 10638 285 R X C -- -- D 1 X P 1R 3 P 7 1 -- -- P 1
511-319 0656 285 R X C -- -- D 1 -- P 1R 3 P P -- -- -- P 1511 3190676 285 R X C -- -- D 1 X P 1R 3 P 5 1 -- -- P 10681 285 R X C -- -- D 1 -- P 1R 3 P P -- -- -- P 10686 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10700 285 R X C -- -- D 1 -- P 1R 3 P P -- -- -- P 10703 285 R X C -- -- D 1 X P 1R 3 P 7 1 -- -- P 10725 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10803 285 R X C -- -- D 1 X P 1R 3 P 7 1 -- -- P 10811 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10813 285 R X C -- -- D 1 -- 2 1R 3 P P -- 2 -- P 10816 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10818 285 R X C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 10454 285 -- X A -- T P 1 X -- 1R 2 P 5 1 -- -- P 10470 285 -- X A -- T P 1 X -- 1R 2 P 1 1 -- -- P 10612 285 -- X C -- T P 1 -- 2 1R 3 P 5 -- -- -- P 10613 285 -- X C -- T P 1 -- -- 1R 3 P 1 1 2 -- P 10619 285 -- X C -- T P 1 -- P 1R 3 P 1 -- -- -- P 1
511-318 0639 285 -- X C -- T P 1 -- P 1R 3 P 1 -- -- -- P 1511 3180641 285 -- X C -- T P 1 -- P 1R 3 P 1 1 2 -- P 10651 285 R X C -- T P 1 X P 1R 3 P 7 -- -- -- P 10698 285 -- X C -- T P 1 -- P 1R 3 P 7 -- -- -- P 10717 285 -- X C -- T P 1 -- P 1R 3 P 7 1 2 -- P 10814 285 -- X C -- T P 1 -- P 1R 3 P 7 1 1 -- P 10400 285 R P A -- -- P 1 -- P 1R 4 2 1 -- -- -- P 1
511 3170475 285 -- P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P 1
511-3170478 285 R P A -- -- P 1 -- P 1R 2 1 2 -- -- -- P 10483 285 R P A -- -- P 1 -- P 1R 2 2 1 -- -- -- P 1
11 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
0455 285 6 -- P 2 1 T -- H -- -- 2 1 4 151 -- 61 X --
511-320 0493 285 6 -- P 2 1 T -- H -- -- 2 1 4 151 -- 61 X --511 3200530 285 6 -- P 2 1 -- -- H -- -- 2 1 4 341 -- 61 X --0529 285 1 -- P 2 1 -- -- H -- -- 2 1 1 341 -- 62 X --0536 285 1 -- P 2 1 -- -- H -- -- 2 1 1 341 -- 62 X --0537 285 1 -- P 2 1 -- -- H -- -- 2 1 1 341 -- 62 X --0541 285 1 -- P 2 1 T -- H -- -- 2 1 1 34 -- 62 X --0550 285 1 -- 2 2 1 P -- H -- -- 2 1 1 511 -- 62 X --0603 285 1 -- 2 1 3 T -- H -- -- 2 1 1 511 -- 62 X --0606 285 1 5 2 1 3 T -- H -- -- 3 1 1 511 -- 62 X --0618 285 1 -- 2 2 1 -- -- H -- -- 2 1 2 511 -- 62 X --0629 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 62 X --0636 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 62 X --0638 285 1 -- 2 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --
511-319 0656 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 62 X --511 3190676 285 1 -- P 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --0681 285 1 -- P 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --0686 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 62 X --0700 285 1 -- P 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --0703 285 1 -- 2 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --0725 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 62 X --0803 285 1 -- 2 2 1 -- -- H -- -- 2 1 2 002 -- 62 X --0811 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 62 X --0813 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 62 X --0816 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 62 X --0818 285 1 -- P 2 1 P -- H -- -- 2 1 2 002 -- 62 X --0454 285 1 -- P 2 1 -- -- B -- -- 2 1 5 151 -- 55 X --0470 285 1 -- P 2 1 -- -- B -- -- 2 1 5 151 -- 55 X --0612 285 1 -- P 2 1 P -- B -- -- 2 1 1 511 -- 55 X --0613 285 1 -- 2 2 1 -- -- H -- -- 2 1 6 511 -- 55 X --0619 285 1 -- P 2 1 -- -- B -- -- 2 1 1 511 -- 55 X --
511-318 0639 285 1 -- P 2 1 -- -- B -- -- 2 1 1 002 -- 55 X --511 3180641 285 1 -- P 2 1 -- -- B -- -- 2 1 6 002 -- 55 X --0651 285 1 -- P 2 1 -- -- B -- -- 2 1 1 002 -- 55 X --0698 285 1 -- P 2 1 -- -- B -- -- 2 1 1 002 -- 55 X --0717 285 1 -- P 2 1 -- -- B -- -- 2 1 7 002 -- 55 X --0814 285 1 -- P 2 1 -- -- B -- -- 2 1 7 002 -- 55 X --0400 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 68 X --
511 3170475 285 1 -- P 2 1 -- -- B -- -- 2 1 4 151 -- 68 X --
511-3170478 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 68 X --0483 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 68 X --
12T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0499 285 -- P A -- -- P 1 -- P 1R 2 2 1 -- -- -- P 1
511-317 0511 285 -- P A -- -- P 1 -- P 1R 2 2 9 -- -- -- P 1511 3170583 285 R P C -- G D 1 X P 1R 3 2 1 1 -- -- P 1
511-316 0451 285 R P A -- T P 1 X P 1R 4 1 7 1 -- B W 1511-315 0439 285 R P A X T P 1 X P 1R 4 1 7 1 -- B P 3511-314 0438 285 R P A X T P 1 X P 1R 4 1 7 1 -- B P 3
0434 285 -- P A -- T P 1 -- P 1R 4 2 5 -- -- -- W 4
511-313 0453 285 R P A -- T D 3 X P 1R 4 2 7 1 -- B W 4511 3130491 285 R P A -- T D 3 X P 1R 4 2 5 1 -- B W 4
511-312 0422 285 R X A -- -- D 1 -- 4 1R 4 -- 9 -- 1 -- P 10456 285 R X A -- -- D 1 X P 1R 4 P 9 -- -- -- P 1
511-311 0655 285 R P C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 1511 3110827 285 R P C -- -- D 1 -- P 1R 3 P 7 -- -- -- P 1
0435 296 R -- A -- G P 1 -- P 1R 3 1 7 -- 2 -- P 1
511 3100566 296 R -- C -- G P 1 -- P 1R 3 1 7 -- 2 -- P 1
511-3100669 296 R -- C -- -- P 1 -- P 1R 3 1 2 -- -- -- P 10712 296 R -- C -- G P 1 -- P 1R 3 2 7 4 4 B P 4
0398 285 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 10408 285 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 10449 285 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 10486 285 R P A -- -- D 1 -- P 1R 4 P 1 -- -- -- P 10502 285 R P A -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10503 285 R P A -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10534 285 R P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10589 285 R P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 1
511-309 0605 285 -- P C -- -- P 1 -- P 1R 3 2 1 -- -- -- P 1511 3090610 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10616 285 -- P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10627 285 R P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10628 285 R P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10635 285 R P C -- -- P 1 -- P 1R 3 P P -- -- -- P 10666 285 R P C -- -- P 1 -- P 1R 3 2 1 -- -- -- P 10667 285 -- P C -- -- P 1 -- P 1R 3 2 1 -- -- -- P 10680 285 -- P C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10425 285 -- X A -- -- P 1 X P 1R 2 P 9 -- -- -- P 1
511 3080474 285 R X A -- -- P 1 X 1 1R 2 2 5 -- -- -- P 1
511-3080544 285 R X AL -- -- P 1 X 1 1R 4 -- 9 -- -- -- P 10674 285 R X CL -- -- P 1 X 4 1R 3 -- 9 -- -- -- P 1
13 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
0499 285 1 -- 2 2 1 -- -- B -- -- 2 1 4 151 -- 68 X --
511-317 0511 285 1 5 2 2 1 -- -- B -- -- 2 1 1 151 -- 68 X --511 3170583 285 8 8 6 2 1 -- -- H -- -- 2 1 5 631 -- 68 X B
511-316 0451 285 1 5 1 3 1 -- -- B -- -- 2 1 7 341 -- 59 X --511-315 0439 285 1 5 P 3 1 -- -- B -- -- 2 1 7 341 -- 49 X --511-314 0438 285 1 5 P 3 1 T -- B -- -- 2 1 7 341 -- 49 X --
0434 285 1 -- 1 2 1 -- -- B -- -- 2 1 1 151 -- 48 X --
511-313 0453 285 5 2 2 3 1 -- -- B -- -- 2 1 7 401 -- 48 X --511 3130491 285 5 2 5 3 1 -- -- B -- -- 2 1 7 401 -- 48 X --
511-312 0422 285 2 -- 3 1 1 -- -- B X -- 2 1 2 181 -- 47 X --0456 285 1 -- P 2 1 -- -- B -- -- 2 1 1 151 -- 52 X --
511-311 0655 285 1 -- P 2 1 -- -- H -- -- 2 1 6 002 -- 52 X --511 3110827 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 52 X --
0435 296 1 -- 1 2 1 -- B H -- -- 2 1 1 371 -- 51 X --
511 3100566 296 2 10 1 2 1 -- B H -- -- 2 1 1 581 -- 51 X --
511-3100669 296 2 -- P 2 1 -- B H -- -- 2 1 1 581 -- 51 X --0712 296 2 10 2 2 1 -- B H -- -- 2 1 1 122 -- 51 X --
0398 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0408 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0449 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0486 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0502 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0503 285 1 -- P 2 1 P -- H -- -- 2 1 1 151 -- 44 X --0534 285 1 -- P 2 1 -- -- B -- -- 2 1 1 511 -- 44 X --0589 285 1 -- P 2 1 P -- H -- -- 2 1 1 511 -- 44 X --
511-309 0605 285 7 9 1 2 1 -- -- B -- -- 2 1 4 511 -- 44 X --511 3090610 285 1 -- P 2 1 P -- B -- -- 2 1 1 511 -- 44 X --0616 285 7 -- P 2 1 -- -- B -- -- 2 1 4 511 -- 44 X --0627 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 44 X --0628 285 1 -- P 2 1 P -- H -- -- 2 1 1 002 -- 44 X --0635 285 1 -- P 2 1 P -- H -- -- 2 1 1 002 -- 44 X --0666 285 1 -- 2 2 1 P -- H -- -- 2 1 1 002 -- 44 X --0667 285 1 9 2 2 1 -- -- B -- -- 2 1 1 002 -- 44 X --0680 285 1 -- P 2 1 -- -- B -- -- 2 1 1 002 -- 44 X --0425 285 1 -- P 2 1 -- -- B -- -- 2 1 1 151 -- 46 X --
511 3080474 285 1 -- P 2 1 -- -- B -- -- 2 1 1 151 -- 46 X --
511-3080544 285 2 -- 3 2 1 -- -- B -- -- 2 1 1 151 -- 46 X --0674 285 2 -- 3 2 1 -- -- B -- -- 2 1 1 002 -- 46 X --
14T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0391 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 10399 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 10437 285 -- P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 10440 285 -- P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 1
511 3070446 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 1
511-3070452 285 R P A -- -- P 1 X P 1R 2 P 1 -- -- -- P 10469 285 R P A -- -- P 1 -- P 1R 2 P P -- -- -- P 10473 285 R P A -- -- P 1 -- 1 1R 2 P P -- -- -- P 10482 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 10487 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 1
511 3060420 285 R P A -- -- -- 3 -- P 1R 4 -- 9 1 -- -- P 7
511-306Note: NT0420 Unit is Fitted With Control Box Mounted Hourmeter
0396 285 R X A -- SG P 3 -- P 1R 4 3 1 4 -- -- P 1
511-305 0406 285 R X A -- SG P 3 -- P 1R 4 3 1 4 -- -- P 1511 3050485 285 R X A -- SG P 3 -- P 1R 4 -- 7 1 -- -- F 40397 285 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 40407 285 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 40447 285 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 1
511 3040480 285 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 1
511-3040482 285 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P 10488 285 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 40720 285 -- X C -- -- P 1 -- P 1R 3 P 1 -- -- -- P 10815 285 R X C -- -- P 1 X P 1R 3 P 9 -- -- -- P 1
511 3030390 285 R P A -- -- -- 1 X P 1R 4 -- 9 -- -- -- W 1
511-3030404 285 R P A -- -- -- 1 X P 1R 4 -- 9 -- -- -- W 10363 285 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- F 10402 285 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- F 10481 285 R X AL X G V/2 4 -- 2 1R 4 -- 9 -- 1 -- F 10484 285 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- F 1
511-302 0501 285 R X AL X G V/2 4 -- 1 1R 3 -- 9 -- 1 -- F 1511 3020535 285 R X CL X G V/2 4 -- 1 1R 3 1 9 -- 4 -- F 10626 285 R X CL X G V/2 4 -- 1 1R 3 1 9 -- 4 -- F 10659 285 R X CL X G V/2 4 -- 1 1R 3 1 9 -- 4 -- F 10801 285 R X CL X G V/2 4 -- 1 1R 3 1 9 -- 4 -- F 1
511 301
0304 285 R P A -- G P 1 -- -- 1R 4 1 1 -- -- -- P 1
511-301 0436 285 R P A -- G P 1 -- -- 1R 4 1 1 -- -- -- P 10445 285 R P A -- G P 1 -- -- 1R 4 1 1 -- -- -- P 1
0273 285 R X AL X G V 4 -- 1 1R 4 -- 9 -- 1 -- -- 1511-300
0273 285 R X AL X G V 4 1 1R 4 9 1 1511 300
0313 285 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- -- 1
15 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
0391 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0399 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0437 285 1 -- P 2 1 -- -- H -- -- 2 1 5 151 -- 44 X --0440 285 1 -- P 2 1 -- -- H -- -- 2 1 5 151 -- 44 X --
511 3070446 285 1 -- P 2 1 P -- H -- -- 2 1 1 151 -- 44 X --
511-3070452 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0469 285 1 -- P 2 1 -- -- B -- -- 2 1 1 151 -- 44 X --0473 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0482 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 44 X --0487 285 1 -- P 2 1 P -- H -- -- 2 1 1 151 -- 44 X --
511-306 0420 285 1 -- P 2 1 -- -- H -- -- 2 1 2 331 -- 44 X --
0396 285 3 3 P 1 3 T -- H -- -- 2 2 2 291 -- 45 X --
511-305 0406 285 3 3 P 1 3 T -- H -- -- 2 2 2 291 -- 45 X --511 3050485 285 3 -- P 1 3 T -- B -- -- 2 2 2 291 -- 45 X --0397 285 1 -- 1 2 1 T -- H -- -- 2 1 1 151 -- 46 X --0407 285 1 -- 1 2 1 T -- H -- -- 2 1 1 151 -- 46 X --0447 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 46 X --
511 3040480 285 1 -- 1 2 1 P -- H -- -- 2 1 1 151 -- 46 X --
511-3040482 285 1 -- P 2 1 -- -- H -- -- 2 1 1 151 -- 46 X --0488 285 1 -- 1 2 1 -- -- H -- -- 2 1 1 151 -- 46 X --0720 285 1 -- P 2 1 -- -- H -- -- 2 1 1 002 -- 46 X --0815 285 1 -- P 2 1 T -- B -- -- 2 1 1 002 -- 46 X --
511 3030390 285 9 -- P 1 2 -- -- B -- -- 2 1 2 151 -- 69 X --
511-3030404 285 9 -- P 1 2 -- -- H -- -- 2 1 2 151 -- 69 X --0363 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 281 -- 43 X --0402 285 2 -- 3 1 3 -- -- B -- -- 2 1 2 281 -- 43 X --0481 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 281 -- 43 X --0484 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 281 -- 43 X --
511-302 0501 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 281 -- 43 X --511 3020535 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 471 -- 43 X --0626 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 022 -- 43 X --0659 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 004 -- 43 X --0801 285 2 -- 3 1 3 -- -- H -- -- 2 1 2 022 -- 43 X --0304 285 2 3 1 2 1 -- -- B -- -- 1 1 2 # -- 42 X --
511 301Note: Plate Set for unit NT0304 = 79-01675-23
511-3010436 285 2 -- 1 2 1 -- -- H -- -- 1 1 2 151 -- 42 X --0445 285 2 -- 1 2 1 -- -- H -- -- 2 1 2 151 -- 42 X --0273 285 2 -- 3 1 3 -- -- B -- -- 1 1 2 # -- 40 X --
511-300 Note: Plate Set for unit NT0273 = 69NT43-250-10511 3000313 285 2 -- 3 1 3 -- -- H -- -- 1 1 2 251 -- 40 X --
16T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0448 294 R P A -- -- P 1 -- 3 1R 4 2 9 -- -- -- W 50569 294 R P C -- -- P 1 -- 4 1R 3 2 9 -- -- -- W 5
511-201 0602 294 R P C -- -- P 1 -- 4 1R 3 2 9 -- -- -- W 5511 2010726 294 R P C -- -- P 1 -- 4 1R 3 2 9 -- -- -- W 50727 294 R P C -- -- P 1 -- 4 1R 3 2 9 -- -- -- W 5
Note: The Current Limit on -201 units is reset at the factory from the default of 21 to 13.5 amps.Also, the Units Are Fitted With A Control Box Mounted Hourmeter
17 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
0448 294 2 3 1 2 1 -- -- B -- -- 3 1 1 381 -- 50 X --0569 294 4 7 1 2 1 -- -- B -- -- 3 1 1 601 -- 50 X --
511-201 0602 294 4 7 1 2 1 T -- B -- -- 3 1 1 601 -- 50 X --511 2010726 294 4 7 1 2 1 -- -- B -- X 3 1 1 162 -- 50 X --0727 294 4 7 1 2 1 T -- B -- X 3 1 1 162 -- 50 X --
18T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
511-120 0410 268 -- X A -- -- -- 1 X -- 1R 2 P 9 -- -- -- P511-119 0389 268 R P A -- -- P 1 -- P 1R 4 1 2 -- -- -- P
511 1180387 268 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P
511-1180388 268 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P
511-117 0348 268 R X A -- -- D 1 X P 1R 4 P 1 -- -- -- P511-116 0302 268 R P A -- -- D 1 -- P 1R 2 2 9 -- -- -- P
511 1150299 268 R X A -- G P 1 -- P 1R 4 1 1 -- -- -- P
511-1150300 268 R X A -- -- P 1 -- P 1R 4 1 2 -- -- -- P0290 268 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P0326 268 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P
511-114 0335 268 R X A -- -- P 1 -- P 1R 4 -- 2 -- 1 -- --511 1140336 268 R X A -- -- P 1 -- 1 1R 4 -- 2 -- 1 -- -- n
0358 268 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P ation
511-113 0294 268 R X A -- -- P 1 X P 1R 4 1 1 -- -- -- W
tifica
511 1120289 268 -- P A -- -- P 1 -- -- 1R 2 P 1 -- -- -- P
dentif
511-1120325 268 -- P A -- -- P 1 -- -- 1R 2 P 1 -- -- -- P
elIde
0286 268 R X A -- -- D 1 -- P 1R 4 1 1 -- -- -- W
Pane
511-111 0295 268 R X A -- -- D 1 -- P 1R 4 1 5 -- -- -- W
ckPa
511 1110429 268 R X A -- -- D 1 -- P 1R 4 P 1 -- -- -- W B
ac
0288 268 R X A -- -- D 1 -- P 1R 4 1 1 -- -- -- P forB
511 1100296 268 R X A -- -- D 1 -- P 1R 4 1 5 -- -- -- P
8PLf
511-1100347 268 R X A -- -- D 1 -- P 1R 4 P 1 -- -- -- P 26
8P
0349 268 R X A -- -- D 1 -- P 1R 4 2 1 -- -- -- P lT--2
511-109 0284 268 R X A -- -- D 1 -- P 1R 4 P 1 -- -- -- P
nual
511-108 0264 268 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P Man
0275 268 R X A -- SG P 3 -- P 1R 4 2 1 2 -- -- Prto
M0277 268 R X A -- SG P 1 -- P 1R 4 2 2 2 -- 1 P ef
er
511 1070315 268 R X A -- SG P 3 -- P 1R 4 2 1 2 -- -- P R
e
511-1070354 268 R X A -- SG P 3 -- P 1R 4 2 1 2 -- -- P0381 268 R X A -- SG P 3 -- P 1R 4 2 1 2 -- -- P0385 268 R X A -- SG P 3 -- P 1R 4 2 1 2 -- -- P0263 268 R X A -- -- D 1 X P 1R 2 P 1 1 -- -- P
511-106 0414 268 R X A -- -- D 1 X P 1R 4 P 1 1 -- -- P511 1060415 268 R X A -- -- D 1 X P 1R 4 P 1 1 -- -- P
511-105 0274 268 R P A -- G D 1 X -- 1R 4 2 1 1 -- -- P511-104 0260 268 R X A -- -- P 1 -- -- 1R 2 1 1 -- -- 1 P511-103 0259 268 R X A -- -- P 1 -- P 1R 4 P P -- -- -- P
511 1020251 268 R P A -- -- P 1 -- P 1R 2 P P -- -- -- P
511-1020254 268 R P A -- -- P 1 -- P 1R 2 P P -- -- -- P
19 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
511-120 0410 268 P -- -- B -- -- 1 -- 07 -- --511-119 0389 268 1 -- -- B -- -- 1 -- 02 -- --
511 1180387 268 P -- -- B -- -- 1 -- 02 -- --
511-1180388 268 P -- -- B -- -- 1 -- 02 -- --
511-117 0348 268 P -- -- B -- -- 1 -- 12 -- --511-116 0302 268 P -- -- B -- -- 1 -- 34 -- --
511 1150299 268 1 -- -- B -- -- 1 -- 07 -- --
511-1150300 268 1 -- -- B -- -- 1 -- 07 -- --0290 268 1 T -- B -- -- 1 -- 07 -- --0326 268 1 T -- B -- -- 1 -- 07 -- --
511-114 0335 268 P -- -- B -- -- 1 -- 07 -- --511 1140336 268 P n -- -- B -- -- n 1
n
-- 07 -- --0358 268
on
1
ation
T -- B -- -- ation
1 n tion
-- 07 -- --511-113 0294 268
cation
1
tificat
T -- B -- --
tifica
1 ation
ficati
-- 07 -- --
511 1120289 268
ntifica
P
dentif
-- -- B -- --
dentif
1
tifica
entifi
-- 02 -- --511-112
0325 268 Ident
P
AirIde
-- -- B -- --
orIde
1
dentif
tIden
-- 02 -- --0286 268
bleId
1
upAi
T -- B -- -- rator
1
elIde
Set -- 12 -- --
511-111 0295 268 Cab 3
akeup
T -- B -- --apor
1
Labe
ateS
-- 12 -- --511 1110429 268 fo
rC
1
rMak
-- -- H -- -- Eva 1 orLa
orPla
-- 12 -- --0288 268
8PLf
1
Lfor
T -- B -- -- forE
1
PLfo
Lfor
-- 12 -- --
511 1100296 268 --2
68 2
68PL
T -- B -- --
8PLf
1268P
68PL
-- 12 -- --511-110
0347 268
alT--2
1
T--268
T -- B -- --
-268P
1 T--26
T--268
-- 12 -- --0349 268
anual
1 alT--
T -- B -- --
alT--2
1 ualT
alT-
-- 12 -- --511-109 0284 268
oMan
1 anua T -- B -- -- nual
1
Manu
anua
-- 07 -- --511-108 0264 268
erto 1
oMa
T -- B -- -- Man 1 toM
oMa
-- 07 -- --0275 268
Refer
P erto
T -- B -- -- rto
M
2 ferto
erto -- 36 -- --
0277 268
R
P Refe
T -- H -- -- efer 2 Refe
Refe
-- 36 -- --
511 1070315 268 P
R
T -- B -- -- Re
2
R
-- 36 -- --511--107
0354 268 P T -- B -- -- 2 -- 36 -- --0381 268 P T -- B -- -- 2 -- 36 -- --0385 268 P T -- B -- -- 2 -- 36 -- --0263 268 1 -- -- B -- -- 1 -- 35 -- --
511--106 0414 268 1 -- -- H -- -- 1 -- 35 -- --511 1060415 268 1 T -- H -- -- 1 -- 35 -- --
511--105 0274 268 2 -- -- B -- -- 1 -- 34 -- B511--104 0260 268 2 -- -- B -- -- 1 -- 07 -- --511--103 0259 268 1 T -- B -- -- 1 -- 07 -- --
511 1020251 268 P -- -- B -- -- 1 -- 02 -- --
511--1020254 268 P -- -- B -- -- 1 -- 02 -- --
20T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0250 268 -- P A -- T -- 1 X -- 1R 2 2 5 1 2 -- P
511-101 0298 268 -- P A X T -- 1 -- -- 1R 2 2 5 1 1 -- P511 1010333 268 -- P A X T -- 1 X -- 1R 2 2 5 1 1 -- P
511-100 0247 268 R D A -- -- P 1 -- P 1R 4 1 1 -- -- -- P511-99 0245 268 R D A -- -- X 1 X 1 1R 2 P 5 -- -- -- P511-98 0297 268 R D A -- -- P 1 -- P 1R 2 2 4 -- -- -- P
0228 268 R P A -- -- P 2 X P 1R 4 P 1 -- -- -- P
511-97 0285 268 R P A -- -- P 2 X P 1R 4 P 1 -- -- -- P511 970322 268 R P A -- -- P 1 X P 1R 4 P 1 -- -- -- P
511-96 0224 268 R P A X T P 1 X -- 1R 4 1 6 1 -- B P0220 268 -- P A -- -- P 1 -- P 1R 4 P P -- -- -- P
511-95 0344 268 R P A -- -- P 2 -- P 1R 4 P 1 -- -- -- P ion511 95
0365 268 R P A -- -- P 1 -- 1 1R 4 P P -- -- -- P catio
0204 268 R D A -- -- X 1 -- 4 1R 4 -- 9 -- -- -- P ntific
511-94 0262 268 R D A -- -- X 1 -- 4 1R 4 -- 9 -- -- -- P Iden511 94
0265 268 R D A -- -- X 1 -- 4 1R 4 -- 9 -- -- -- P nelId
511-93 0197 268 R D A -- -- X 1 -- 4 1R 4 -- 9 -- -- -- P
kPan
511-92 0218 268 -- D A -- G P 2 -- P 1R 4 1 5 3 2 -- -- ack
0202 268 R P A -- -- -- 1 -- P 1R 4 -- 9 1 -- -- P
orBa
0238 268 R P A -- -- -- 5 -- P 1R 4 -- 9 1 -- -- F Lfor
511-91 0278 268 R P A -- -- -- 5 -- P 1R 4 -- 9 1 -- -- F
68PL
511 91Note: NT0202, NT0238 & NT0278 Units Are Fitted With Control Box Mounted Hourmeter
T--26
0318 268 R P A -- -- -- 5 -- P 1R 4 -- 9 1 -- -- F
ualT
511-90 0222 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P anua
511 890212 268 R D A -- -- X 1 X P 1R 2 P P -- -- 1 P o
Ma
511-890243 268 R D A -- -- X 1 X P 1R 2 P 9 -- -- 1 P er
to511-87 0214 268 R P A -- T P 1 X P 1R 2 P 5 -- -- B P R
efe
0183 268 R D AL -- G X 4 -- 1 1R 4 -- 9 -- 1 -- W
R
511 850226 268 R D AL -- G X 4 -- 1 1R 4 -- 9 -- 1 -- F
511-850280 268 R D AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- F0317 268 R D AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- F0191 268 R P A -- -- -- 1 X P 1R 4 -- 9 -- -- -- W
511-84 0201 268 R P A -- -- -- 1 X P 1R 4 -- 9 -- -- -- W511 840334 268 R P A -- -- -- 1 X P 1R 4 -- 9 -- -- -- W
511-83 0210 268 R X A -- -- P 1 -- P 1R 4 P 1 -- -- -- P0187 268 R P A -- SG P 3 -- P 1R 2 2 1 4 -- -- P
511-82 0198 268 R P A -- SG P 3 -- P 1R 2 2 1 4 -- -- P511 820199 268 R P A -- SG P 3 -- P 1R 2 1 1 4 -- -- P
21 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
0250 268 P -- -- B -- -- 1 -- 13 -- --
511-101 0298 268 P -- -- B -- -- 1 -- 13 -- --511 1010333 268 P -- -- B -- -- 1 -- 13 -- --
511-100 0247 268 1 -- -- B -- -- 1 -- 07 -- --511-99 0245 268 P -- -- B -- -- 1 -- 12 -- --511-98 0297 268 3 -- -- B -- -- 1 -- 12 -- --
0228 268 P -- -- B -- -- 1 -- 02 -- --
511-97 0285 268 P -- -- B -- -- 1 -- 02 -- --511 970322 268 P -- -- B -- -- 1 -- 02 -- --
511-96 0224 268 P -- -- B -- -- 1 -- 32 -- --0220 268 P -- -- B -- --
n
1 -- 02 -- --
511-95 0344 268 P
on
-- -- B -- -- tion
1
n on -- 02 -- --511 95
0365 268 tion P
cation
-- -- B -- -- ficati
1
ation
catio -- 02 -- --
0204 268 ficati
P
ntifica
T -- B X --
entifi
1 ificat
ntifica
-- 27 -- --
511-94 0262 268
entifi
P dent
-- -- B X --
rIden
1 entif
dent
-- 27 -- --511 940265 268
eIde
P AirId
-- -- B X -- ator
1
elIde
setId
-- 27 -- --511-93 0197 268 ab
le
P
perA
T -- B P -- pora
1 abel
atese
-- 26 -- --511-92 0218 268
orCa
2 Uppe
T -- B -- --Evap
1
orLa
Plat
-- 07 -- --0202 268
PLfor
P forU
-- -- B -- --forE
1
PLfo
forP
-- 02 -- --0238 268 68
PL
P
8PLf
-- -- B -- --PLfo
1 68PL
8PLf
-- 02 -- --511-91 0278 268
alT--26
P
T--268P
-- -- B -- --
T--268P
1alT--26
T--268P
-- 02 -- --
0318 268 anua P ualT
-- -- B -- --
ualT-
1anua
ualT
-- 02 -- --511-90 0222 268
oMa
1
Manu
-- -- B -- -- anua
1
oMan
Manu
-- 02 -- --
511 890212 268 er
to P toM
-- -- B -- --
oMa
1
erto
toM
-- 33 -- --511-89
0243 268 Refe
P
efert
-- -- B -- -- erto 1
Refer
ferto
-- 33 -- --511-87 0214 268
R
1 Ref
T -- B -- -- Refe
1
Re
Ref -- 15 -- --
0183 268 3 -- -- B -- --
R
1 -- 04 -- --
511 850226 268 3 -- -- B -- -- 1 -- 04 -- --
511-850280 268 3 -- -- H -- -- 1 -- 04 -- --0317 268 3 -- -- H -- -- 1 -- 04 -- --0191 268 P -- -- B -- -- 1 -- 02 -- --
511-84 0201 268 P -- -- B -- -- 1 -- 02 -- --511 840334 268 P -- -- B -- -- 1 -- 02 -- --
511-83 0210 268 P -- C B -- -- 1 -- 29 -- --0187 268 P T -- B -- -- 1 -- 28 -- --
511-82 0198 268 P T -- B -- -- 2 -- 28 -- --511 820199 268 1 T -- B -- -- 2 -- 28 -- --
22T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0151 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0168 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
511-81 0180 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P511 810236 268 -- P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0258 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
511-80 0165 268 R P A -- -- P 1 -- P 1R 2 P P -- -- -- P511-79 0190 268 -- P A -- T -- 1 X -- 1R 2 2 5 1 2 -- P511-78 0182 268 -- X A -- -- P 1 X P 1R 2 1 1 -- -- -- P511-77 0176 268 R P A X T P 1 X P 1R 2 1 2 1 -- -- P511-76 0169 268 R P A X T P 1 X P 2R 2 1 4 1 -- B P n
511-75 0163 268 R X A -- G D 1 -- P 1R 4 P 1 -- -- -- P ation
511 740159 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P
tifica
511-740223 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P
dentif
511-73 0158 268 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P
elIde
511 720157 268 R P A -- -- P 1 -- P 1R 2 1 1 1 -- -- P
Pane
511-720200 268 -- P A -- -- P 1 -- P 1R 2 1 1 2 -- -- --
ckPa
511 710166 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P B
ac
511-710235 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P fo
rB
0241 268 R X A -- -- P 1 -- P 1R 4 1 1 -- -- -- P
8PLf
511 700271 268 R X A -- -- P 1 -- P 1R 4 1 1 -- -- -- P 26
8P
511-700311 268 R X A -- -- P 1 -- P 1R 4 1 1 -- -- -- P lT
--2
0353 268 R X A -- -- P 1 -- P 1R 4 1 1 -- -- -- P
nual
511-69 0177 268 R P A -- -- P 1 X P 1R 2 P P 1 -- -- P Man
511-67 0143 268 -- P A -- -- P 1 -- -- 1R 2 P P -- -- -- P
rto
M
511 660129 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- W ef
er
511-660147 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- W R
e511-65 0119 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- W511-64 0131 268 -- X A -- G P 1 -- P 1R 4 1 2 3 1 -- --
511 630140 268 R X A -- -- D 1 -- 2 1R 4 -- 9 -- -- -- P
511-630192 268 R X A -- -- D 1 -- 2 1R 4 -- 9 -- -- -- P
511-62 0127 268 R P A -- -- P 1 -- 1 1R 2 1 1 -- -- -- P
511 610126 268 R P A -- G D 1 X -- 1R 2 1 1 1 -- -- P
511-610154 268 R P A -- G D 1 X -- 1R 2 1 1 1 -- -- P
511 600125 268 R P A -- G D 1 X -- 1R 4 1 1 1 -- -- P
511-600153 268 R P A -- G D 1 X -- 1R 4 1 1 1 -- -- P
23 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA--
Controller
Stepper
Drive
Emergency
Bypass
0151 268 1 -- -- B -- -- 1 -- 02 -- --0168 268 1 -- -- B -- -- 1 -- 02 -- --
511-81 0180 268 1 -- -- B -- -- 1 -- 02 -- --511 810236 268 1 -- -- B -- -- 1 -- 02 -- --0258 268 1 -- -- B -- -- 1 -- 02 -- --
511-80 0165 268 1 -- -- B -- -- 1 -- 02 -- --511-79 0190 268 P -- -- B -- -- 1 -- 15 -- --511-78 0182 268 1 -- -- B -- -- 1 -- 31 -- --511-77 0176 268 1 -- -- B -- -- 1 -- 13 -- --511-76 0169 268 1
tion -- -- B -- -- n 1 -- 25 -- --
511-75 0163 268 n 1
ficati
-- -- B -- -- ation
1
on tion -- 12 -- --
511 740159 268 at
ion
1
entifi
-- -- B -- -- ifica 1
catio
ficati
-- 02 -- --511-74
0223 268 tifica
1 rIden
-- -- B -- --
dentif
1 tifica
entifi
-- 02 -- --511-73 0158 268
denti
1 rAir
-- -- B -- --
orIde
1 dent
tIden
-- 02 -- --
511 720157 268
bleId
1
ower T -- B -- -- rator
2
belId
Set -- 19 -- --
511-720200 268 C
able
1 &low
T -- B -- --
apora
2 Labe
ateS
-- 19 -- --
511 710166 268 fo
rC
1 per&
T -- B -- -- Eva 1 forL
rPla
-- 02 -- --511-71
0235 268 PLfo
1 Upp T -- B -- -- forE
1 PLfo
Lfor
-- 02 -- --0241 268 26
8P 1 forU
T -- B -- --8P
Lf
1 268P
68PL
-- 07 -- --
511 700271 268 lT
--2
1
8PLf
T -- B -- ---268P
1 T--2
T--268
-- 07 -- --511-70
0311 268 nual 1 --268 T -- B -- -- lT--2
1
nualT
alT--
-- 07 -- --0353 268 M
an 1
alT--2
T -- B -- -- nual 1 Manu
anua
-- 07 -- --511-69 0177 268 r
toM
1
anual
-- -- B -- -- Man 1 toM
oMa
-- 02 -- --511-67 0143 268
Refer P
oMan
-- -- B -- --
rto
M
1
efer
t
erto -- 02 -- --
511 660129 268 R
e
2
erto -- -- B -- -- efer 1 Ref
Refe
-- 02 -- --511-66
0147 268 2
Refer
-- -- B -- -- Re
1
R
-- 02 -- --511-65 0119 268 1
R
-- -- B -- -- 1 -- 18 -- --511-64 0131 268 1 T -- B -- -- 1 -- 07 -- --
511 630140 268 P T -- B -- -- 1 -- 26 -- --
511-630192 268 P T -- B -- -- 1 -- 26 -- --
511-62 0127 268 2 -- C B -- -- 1 -- 20 -- --
511 610126 268 1 -- -- B -- -- 1 -- 34 -- --
511-610154 268 1 -- -- B -- -- 1 -- 34 -- --
511 600125 268 1 -- -- B -- -- 1 -- 34 -- --
511-600153 268 1 -- -- B -- -- 1 -- 34 -- --
24T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0167 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0174 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P
511-59 0211 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P511 590272 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0312 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0105 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0122 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0138 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0141 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0160 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0161 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P n
511 580189 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P at
ion
511-580240 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
tifica
0269 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
dentif
0309 268 R P A -- -- P 1 -- P 1R 2 2 1 -- -- -- P
elIde
0340 268 R P A -- -- P 1 -- P 1R 2 2 P -- -- -- P
Pane
0386 268 R P A -- -- P 1 -- P 1R 2 2 1 -- -- -- P
ckPa
0418 268 R P A -- -- P 1 -- P 1R 2 2 1 -- -- -- P Bac
0428 268 R P A -- -- P 1 -- P 1R 2 2 5 -- -- -- P forB
511-57 0156 268 R P A -- -- P 1 X P 1R 2 1 1 -- -- -- P
8PLf
511-56 0242 268 R P A -- -- P 1 -- P 1R 4 P 1 -- -- -- P 268P
511 550120 268 R P A -- -- P 1 -- -- 1R 4 -- 2 -- -- -- -- lT
--2
511-550188 268 R P A -- -- P 1 -- -- 1R 4 -- 2 -- 2 -- --
nual
0118 268 R P A -- -- P 1 X P 1R 2 P 1 -- -- -- P Man
511-54 0136 268 R P A -- -- P 2 X P 1R 2 P 1 -- -- -- P
rto
M
511 540215 268 R P A -- -- P 2 X P 1R 2 P 1 -- -- -- P ef
er511-53 0113 268 R P A -- -- P 1 -- P 1R 2 P 9 -- -- -- P R
e
0109 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0111 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
511-52 0133 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P511 520162 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0225 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P0107 268 R P A -- G D 1 X -- 1R 4 1 2 -- -- -- P
511-51 0207 268 R P A -- G D 1 X -- 1R 4 1 2 -- -- -- P511 510417 268 R P A -- -- D 1 -- P 1R 4 P 9 -- -- -- P
511 500106 268 R X A -- -- D 1 X 1 1R 2 1 4 -- -- -- P
511-500178 268 R X A -- -- D 1 X 1 1R 2 1 3 -- -- -- P
25 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
0167 268 1 -- -- B -- -- 1 -- 02 -- --0174 268 1 -- -- B -- -- 1 -- 02 -- --
511-59 0211 268 1 -- -- B -- -- 1 -- 02 -- --511 590272 268 1 -- -- B -- -- 1 -- 02 -- --0312 268 1 -- -- B -- -- 1 -- 02 -- --0105 268 1 -- -- B -- -- 1 -- 02 -- --0122 268 1 -- -- B -- -- 1 -- 02 -- --0138 268 1 -- -- B -- -- 1 -- 02 -- --0141 268 1 -- -- B -- -- 1 -- 02 -- --0160 268 1 -- -- B -- -- 1 -- 02 -- --0161 268 1 tio
n -- -- B -- -- n 1 -- 02 -- --
511 580189 268 n 1 fic
ati
-- -- B -- --
ation
1
on tion -- 02 -- --
511-580240 268 at
ion
1
entifi
-- -- B -- -- ificat
1
catio
n
ficati
-- 02 -- --0269 268 tif
ica
1 rIde
-- -- B -- -- entif
1 tifica
entifi
-- 02 -- --0309 268
denti
1 rAir
-- -- B -- --
orIde
1
dent
tIden
-- 02 -- --0340 268
bleId
1
ower T -- B -- -- rator
1 elId
Set -- 02 -- --
0386 268 Cable
1 &low
T -- B -- --
apora
1 Labe
ateS
-- 02 -- --0418 268 fo
rC
2 per&
-- -- B -- -- Evap
1 forL
rPla
-- 02 -- --0428 268 P
Lfo
1 -- Upp -- -- B -- -- forE
1 PLfo
Lfor
-- 02 -- --511-57 0156 268 26
8P 1
-LforU
-- -- B -- --8P
Lf
1 268P
68PL
-- 02 -- --511-56 0242 268 lT
--2
1 8PLf
T -- B -- -- 268P
1 T--2
T--268
-- 02 -- --
511 550120 268 nu
al 2 --268 -- -- B -- -- lT--2
1nualT
alT--
-- 02 -- --511-55
0188 268 Man 2
alT--
-- -- B -- --
nual 1
Manu
anua
-- 02 -- --0118 268 r
toM
P
anua -- -- B -- -- Man 1 toM
oMa
-- 02 -- --
511-54 0136 268
Refer P
oMan
-- -- B -- --
rto
M
1
efer
t
erto -- 02 -- --511 54
0215 268 Re
P
erto -- -- B -- -- efer 1 Ref
Refe
-- 02 -- --511-53 0113 268 1 R
efer
T -- B -- -- Re
1
R
-- 02 -- --0109 268 2
R
-- -- B -- -- 1 -- 02 -- --0111 268 2 -- -- B -- -- 1 -- 02 -- --
511-52 0133 268 2 -- -- B -- -- 1 -- 02 -- --511 520162 268 2 -- -- B -- -- 1 -- 02 -- --0225 268 2 -- -- B -- -- 1 -- 02 -- --0107 268 2 -- -- B -- -- 1 -- 34 -- B
511-51 0207 268 2 -- -- B -- -- 1 -- 34 -- EB511 510417 268 P -- -- B -- -- 1 -- 02 -- B
511 500106 268 1 -- -- B -- -- 1 -- 12 -- --
511-500178 268 1 -- -- B -- -- 1 -- 12 -- --
26T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0103 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0134 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0184 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0216 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0268 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P
511-49 0282 268 -- P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P511 490283 268 R P A -- -- P 1 -- P 1R 2 P 5 -- -- -- P0303 268 R P A -- -- P 1 X -- 1R 2 P 5 -- -- -- P0308 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P0341 268 R P A -- -- P 1 X P 1R 2 P 5 -- -- -- P
on
0345 268 R P A -- -- P 1 X P 1R 4 P 1 -- -- -- P ation
511-48 0101 268 R P A -- -- P 2 X P 1R 4 P 2 -- -- -- P
tifica
0098 268 R P A -- B P 1 X P 1R 2 1 5 -- -- B W
denti
511 470124 268 R P A X B P 1 X P 1R 2 1 5 -- -- B W el
Ide
511-470146 268 R P A X B P 1 X P 1R 2 1 5 -- -- B W
Pane
0186 268 R P A X B P 1 -- P 1R 2 1 5 -- -- 1 W ckPa
511-46 0110 268 R P A -- -- P 1 -- P 1R 4 1 1 -- -- -- P Bac
511-45 0092 268 R P A -- -- P 1 -- -- 1R 2 P P -- -- -- P forB
0091 268 -- X A -- G P 2 -- P 1R 4 1 2 3 2 -- --
8PLf
0102 268 -- X A -- G P 2 -- P 1R 4 1 2 3 2 -- --
-268P
0137 268 -- X A -- G P 2 -- P 1R 4 1 2 3 2 -- -- lT--2
511-44 0185 268 -- X A -- G P 1 -- P 1R 4 1 2 3 2 -- P nual
511 440213 268 -- X A -- G P 2 -- P 1R 4 1 5 3 2 -- -- M
an
0244 268 -- X A -- G P 2 -- P 1R 4 1 5 3 2 -- -- rto
M
0266 268 -- X A -- G P 2 -- P 1R 4 1 5 3 2 -- -- efer
511-43 0081 268 -- P A -- -- P -- -- -- 1R 2 P 9 -- -- -- P Re
511-42 0088 268 -- P A -- -- P 1 -- -- 1R 2 P P -- -- -- P
511 410080 268 R P A -- -- P 1 -- P 1R 2 P 9 -- -- -- P
511-410090 268 R P A -- -- P 1 -- P 1R 2 P 9 -- -- 1 P0079 268 R X A -- -- D 1 -- 1 1R 2 P 1 -- -- 1 P
511-40 0085 268 R X A -- -- D 1 -- 1 1R 2 P 1 -- -- 1 P511 400096 268 R X A -- -- D 1 X 2 1R 2 P 1 -- -- 1 P0078 268 R X A -- -- D 1 -- 2 1R 2 P 1 -- -- 1 W
511-39 0084 268 R X A -- -- D 1 X 2 1R 2 P 1 -- -- 1 W511 390095 268 R X A -- -- D 1 X 2 1R 2 P 1 -- -- 1 W
27 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
0103 268 2 -- -- B -- -- 1 -- 02 -- --0134 268 2 -- -- B -- -- 1 -- 02 -- --0184 268 2 -- -- B -- -- 1 -- 02 -- --0216 268 2 -- -- B -- -- 1 -- 02 -- --0268 268 2 -- -- B -- -- 1 -- 02 -- --
511-49 0282 268 2 -- -- B -- -- 1 -- 02 -- --511 490283 268 2 -- -- B -- -- 1 -- 02 -- --0303 268 P -- -- B -- -- 1 -- 02 -- --0308 268 P -- -- B -- -- 1 -- 02 -- --0341 268 P tio
n -- -- B -- -- n 1 -- 02 -- --0345 268
n
P ficati
-- -- B -- --
ation
1
n on -- 02 -- --
511-48 0101 268
ation
p entifi
-- -- B -- -- ificat
1
ation
catio -- 02 -- --
0098 268
tificat
2 rIde
-- -- B -- -- entif
1 ificat
tifica
-- 15 -- --
511 470124 268
dentif
1
erAir
-- -- B -- --
orIde
1
dentif
dent
-- 15 -- --511-47
0146 268 leIde
1
ower
-- -- B -- -- rator
1 elIde
SetId
-- 15 -- --0186 268
Cable
1 &lo
-- -- B -- --
apora
1
Labe
teSe
-- 15 -- --511-46 0110 268
forC
p per&
-- -- B -- -- Evap
1
forLa
Plate
-- 18 -- --511-45 0092 268 P
Lfo
1
rUpp T -- B -- -- forE
1 PLfo
forP
-- 02 -- --0091 268 26
8P 1
Lfor
-- -- B -- --8P
Lf
1 268P
268fo
-- 07 -- --0102 268 lT
--2 1 8PL
-- -- B -- -- 268P
1 lT--2
T--26
-- 07 -- --0137 268
nual 1 --268 -- -- B -- -- lT--2
1
nual
ualT
-- 07 -- --
511-44 0185 268 Man 1 alT--
-- -- B -- --
nual 1 Man
Manu
-- 07 -- --511 440213 268
rtoM
2
anua -- -- B -- -- Man 1
rtoM
toM
-- 07 -- --0244 268 ef
er 2
oMa
-- -- B -- --
rto
M
1 efer
ferto
-- 07 -- --0266 268 R
e
2 erto -- -- B -- -- efer
t
1 Re
Ref -- 07 -- --
511-43 0081 268 -- Refe
T -- B -- -- Re
1 -- 02 -- --511-42 0088 268 1
R
-- -- B -- -- 1 -- 02 -- --
511 410080 268 1 -- -- B -- -- 1 -- 02 -- --
511-410090 268 1 -- -- B -- -- 1 -- 02 -- --0079 268 p -- -- B -- -- 1 -- 23 -- --
511-40 0085 268 p -- -- B -- -- 1 -- 23 -- --511 400096 268 p -- -- B -- -- 1 -- 23 -- --0078 268 p -- -- B -- -- 1 -- 23 -- --
511-39 0084 268 p -- -- B -- -- 1 -- 23 -- --511 390095 268 p -- -- B -- -- 1 -- 23 -- --
28T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0074 268 R X AL X G V 4 -- 1 1R 4 -- 9 -- 1 -- --0135 268 R X A X G V 4 -- 1 1R 4 -- 9 -- 2 1 --0208 268 R X AL -- G V 4 -- 1 1R 4 -- 9 -- 1 -- --
511-38 0246 268 R X AL -- G V/1 4 -- 1 1R 4 -- 9 -- 1 -- --511 380253 268 R X AL -- G V 4 -- 1 1R 4 -- 9 -- 1 -- --0267 268 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- --0307 268 R X AL X G V/2 4 -- 1 1R 4 -- 9 -- 1 -- P
511-37 0073 268 R X A -- T D 1 -- -- 1R 2 -- 2 -- 2 -- P511-36 0072 268 R X A -- G D -- -- 1 1R 4 -- 9 -- -- 1 --511-35 0071 268 R X A -- -- D 1 -- 2 1R 2 1 1 -- 1 1 P511-34 0065 268 -- P A -- T P -- -- -- 1R 2 P 2 -- -- 1 P n
511 330068 268 R P A -- -- P 1 -- P 1R 2 1 9 -- -- 1 P
ation
511-330239 268 R P A -- -- P 1 X P 1R 2 1 P -- -- -- P ifi
cat
511 320067 268 -- P A -- -- P 1 X P 1R 2 1 P -- -- 1 P en
tif
511-320097 268 R P A -- -- P 1 X P 1R 2 1 P -- -- -- P
elIde
511-31 0061 268 -- X A -- -- P 1 -- -- 1R 2 1 1 -- -- 1 P
Panel
511-30 0060 268 R X A -- G D 4 -- 1 2R 4 -- 9 -- 2 1 --
ckPa
0059 268 -- X A -- -- P 1 -- -- 1R 2 P 2 -- -- -- W Back
511-29 0219 268 R X A -- -- P 1 -- -- 1R 2 P 2 -- -- -- W forB
511 290343 268 R X A -- -- P 1 -- P 1R 2 P 2 -- -- -- W
8PLf
511 280057 268 S P A -- -- P 1 -- -- 1R 2 P 1 -- -- 1 P 26
8P
511-280132 268 R P A -- -- P 1 -- P 1R 2 P 1 -- -- -- P lT
--2
511-27 0056 268 R P A -- -- D 1 -- P 1R 4 1 2 -- -- -- P
nual
511 260047 268 R P A -- -- D 1 -- P 2R 2 P P -- -- 1 P M
an
511-260175 268 R P A -- -- D 1 X P 2R 2 P P -- -- -- P
rto
M511-25 0053 268 S P A -- -- P 1 -- -- 1R 2 P 2 -- -- 1 P ef
ert
511-24 0051 268 -- P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P Re
511 230050 268 S P A -- -- P 1 -- P 1R 2 1 1 -- -- 1 P
511-230069 268 S P A -- -- P 1 -- P 1R 2 1 1 -- -- 1 P0046 268 R P A -- G P 1 -- -- 1R 4 1 1 -- 2 1 P
511 220121 268 R P A X G P 1 -- -- 1R 4 1 1 -- -- -- P
511-220139 268 R P A X G P 1 -- -- 1R 4 1 1 -- 1 -- P0252 268 R P A -- G P 1 -- -- 1R 4 1 1 -- 1 -- P
511-21 0055 268 -- P A -- -- P 1 -- -- 1R 2 1 1 -- -- 1 P511-19 0037 268 -- P A -- -- P 1 -- -- 1R 2 1 1 -- -- 1 P511-18 0035 268 R P A -- G P -- -- 2 1R 2 1 1 -- 1 1 P511-17 0043 268 -- -- A -- -- X 1 X -- 2R 4 P 1 -- -- -- P
29 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
0074 268 3 -- -- B -- -- 1 -- 04 -- --0135 268 3 -- -- B -- -- 1 -- 04 -- --0208 268 3 -- -- B -- -- 1 -- 04 -- --
511-38 0246 268 3 -- -- B -- -- 1 -- 04 -- --511 380253 268 3 -- -- B -- -- 1 -- 04 -- --0267 268 3 -- -- B -- -- 1 -- 04 -- --0307 268 3 -- -- H -- -- 1 -- 04 -- --
511-37 0073 268 P T -- B -- -- 1 -- 14 -- --511-36 0072 268 3 -- -- B -- -- 1 -- 04 -- --511-35 0071 268 1 -- -- B -- -- 1 -- 34 -- --511-34 0065 268 P
tion -- -- B -- -- n 1 -- 13 -- --
511 330068 268
n
1
ficatio
T -- B -- --
ation
1
n tion -- 39 -- --
511-330239 268
ation
1
entific
T -- B -- -- ificat
1
ation
icati
-- 39 -- --
511 320067 268 ifi
cat
1 rIden
-- -- B -- -- entif
1
tificat
ntific
-- 39 -- --511-32
0097 268
dentif
1 rAir
-- -- B -- --
orIde
1
dentif
Iden -- 39 -- --
511-31 0061 268 leIde
1
ower -- -- B -- -- rator
1 elIde
SetI
-- 07 -- --511-30 0060 268
Cable
3 &low
-- -- B -- --
apora
1
Labe
ateS
-- 11 -- --0059 268
forC
P per&
-- -- B -- -- Evap
1 forL
rPla
-- 07 -- --
511-29 0219 268 PLfo
P Upp -- -- B -- -- forE
1 PLfo
Lfor
-- 07 -- --511 290343 268 26
8P P forU
-- -- B -- --8P
Lf
1 268P
68PL
-- 07 -- --
511 280057 268 T
--2 1
8PLf
T -- B -- -- 268P
1 lT--2
--268
-- 02 -- --511-28
0132 268
nualT
1 --268 T -- B -- -- lT--2
1nual
alT--
-- 02 -- --511-27 0056 268 M
anu
1
alT--2
-- -- B -- --
nual 1 Man
anua
-- 34 -- --
511 260047 268
rtoM
P
anual
P -- B -- -- Man 1 rtoM
oMan
-- 38 -- --511-26
0175 268 efer P
oMan
-- -- B -- --
rto
M
1
Refer
erto -- 38 -- --
511-25 0053 268 Re
P
erto -- -- B -- -- efer
t
1 Re
Refer
-- 02 -- --511-24 0051 268 P
Refer
-- -- B -- -- Re
1
R
-- 02 -- --
511 230050 268 --
R
-- -- B -- -- 1 -- 02 -- --511-23
0069 268 1 -- -- B -- -- 1 -- 02 -- --0046 268 -- -- -- B -- -- 1 -- 09 -- --
511 220121 268 1 -- -- B -- -- 1 -- 09 -- --
511-220139 268 1 -- -- B -- -- 1 -- 09 -- --0252 268 1 -- -- B -- -- 1 -- 09 -- --
511-21 0055 268 -- T -- B -- -- 1 -- 02 -- --511-19 0037 268 1 -- -- B -- -- 1 -- 02 -- --511-18 0035 268 1 -- -- B -- -- 1 -- 02 -- --511-17 0043 268 P -- -- B -- -- 1 -- 38 -- --
30T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
0028 268 S P A -- -- P -- X -- 1R 2 P 2 -- -- -- P
511 160054 268 S P A -- -- P 1 -- P 1R 2 P 2 -- -- 1 P
511-160070 268 S P A -- -- P 1 -- P 1R 2 P 1 -- -- 1 P0083 268 R P A -- -- P 2 X P 1R 2 P 2 -- -- -- P
511 150029 268 -- P A -- -- P -- -- -- 1R 2 1 1 -- -- -- W
511-150044 268 -- P A -- -- P -- -- -- 1R 2 1 1 -- -- -- W
511-14 0018 268 R X A -- G V 4 -- 2 1R 4 P 9 -- 1 -- --
511 130015 268 R X A -- G V 4 -- 1 1R 4 P 9 -- 1 -- --
511-130022 268 R X A -- G V 4 -- 1 1R 4 -- 9 -- 1 -- --
511 120076 268 -- P A -- -- P 1 -- -- 1R 2 P P -- -- -- P
511-120082 268 -- P A -- -- P 1 -- -- 1R 2 P P -- -- 1 P
n
511-11 0008 268 -- X A -- G P -- -- P 1R 4 P 1 1 -- -- --
ation
0024 268 S P A -- -- P -- -- -- 1R 2 1 1 -- -- -- P ficat
0027 268 S P A -- -- P -- -- -- 1R 2 1 1 -- -- -- P
entifi
0040 268 S P A -- -- P 1 -- -- 1R 2 1 1 -- -- -- P lIde
511 100041 268 S P A -- -- P -- -- -- 1R 2 1 1 -- -- -- P an
el
511-100104 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P k
Pa
0112 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
Back
0173 268 R P A -- -- P 1 -- 1 1R 2 1 1 -- -- -- P
forB
0209 268 R P A -- -- P 1 -- P 1R 2 1 1 -- -- -- P
PLfo
0064 268 -- P A -- -- P -- -- -- 1R 2 P 1 -- -- 1 P
268P
511-9 0089 268 -- P A X -- P 1 -- -- 1R 2 P 1 -- -- -- P T--26
511 90152 268 -- P A -- -- P 1 -- -- 1R 2 P 1 -- -- -- P u
alT
0005 268 -- P A -- -- P -- -- -- 1R 2 1 1 -- -- -- P
Manu
511-8 0037 268 -- P A -- -- P 1 -- -- 1R 2 1 1 -- -- -- P toM
511 80094 268 -- P A -- -- P 1 -- -- 1R 2 1 1 -- -- -- P
efer
t511-7 0014 268 -- X A -- -- V -- X -- 1R 2 P 9 -- -- -- -- R
ef511-6 0013 268 -- X A -- -- P -- X -- 1R 2 P 9 -- -- -- --
0011 268 -- P A -- -- P -- -- -- 1R 2 -- 9 -- -- -- --
511-5 0038 268 -- P A -- -- P -- -- -- 1R 2 1 2 -- -- -- P511 50099 268 -- P A -- -- P 1 -- -- 1R 2 1 2 -- -- -- P
511-4 0037 268 -- P A -- -- P -- -- -- 1R 2 1 1 -- -- -- P511-3 0007 268 S X A -- -- P 1 X -- 1R 2 P 1 -- -- -- --
511 20002 268 R X A -- -- V 1 -- 1 2R 2 P 1 -- -- 1 W
511-20017 268 -- X A -- -- V 1 X 2 2R 2 P 1 -- -- 1 W
511 10001 268 R X A -- -- V 1 -- 2 2R 2 P 1 -- -- 1 P
511-10062 268 R X A -- -- V 1 -- 2 2R 2 P 1 -- -- 1 P
31 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet
PlateSet
--CA
Controller
Stepper
Drive
Emergency
Bypass
0028 268 P -- -- B -- -- 1 -- 02 -- --
511 160054 268 P -- -- B -- -- 1 -- 02 -- --
511--160070 268 P -- -- B -- -- 1 -- 02 -- --0083 268 P -- -- B -- -- 1 -- 02 -- --
511 150029 268 1 -- -- B -- -- 1 -- 37 -- --
511--150044 268 1 -- -- B -- -- 1 -- 37 -- --
511-14 0018 268 3 -- -- B -- -- 1 -- 04 -- --
511 130015 268 3 -- -- B -- -- 1 -- 04 -- --
511-130022 268 3 -- -- B -- -- 1 -- 04 -- --
511 120076 268 P T -- B -- -- 1 -- 07 -- --
511-120082 268 -- on T -- B -- -- 1 -- 07 -- --
511-11 0008 268 -- catio -- -- B -- -- on 1
n
-- 07 -- --0024 268 io
n 1 ntific
T -- B -- --
catio 1
on tion
-- 02 -- --0027 268 ic
atio
1 Iden T -- B -- --
ntific
1
catio
ficati
-- 02 -- --0040 268 nt
ific
1 AirI
T -- B -- -- dent
1
ntifica
entifi
-- 02 -- --
511 100041 268 Id
en 1 werA
T -- B -- --
torId
1 Ident
etIde
-- 02 -- --511-10
0104 268
ableI
1
&low
T -- B -- -- orato
1 belId
eSet
-- 02 -- --0112 268 r
Cab
1
per&
T -- B -- --
vapo
1
rLab
Plate -- 02 -- --
0173 268
Lfor
1 Uppe
T -- B -- -- rEva
1
Lfor
orPl
-- 02 -- --0209 268
68PL
1 forU
T -- B -- --Lfor
1 8PL
PLfo
-- 02 -- --0064 268
T--268
P PLfo
-- -- B -- --
68PL
1 --268
268P -- 02 -- --
511-9 0089 268
ualT-
1 268P -- -- B -- --
T--268
1 alT--
T--26
-- 02 -- --511 90152 268 an
ua
1 lT--2
-- -- B -- -- alT--
1 anua
nualT
-- 02 -- --0005 268 o
Ma
-- nual -- -- B -- --
anua
1
oMa
Manu
-- 02 -- --
511-8 0037 268
ferto
P Man -- -- B -- --
oMa
1 erto
rtoM
-- 02 -- --511 80094 268 R
efe
1 rtoM
-- -- B -- --
erto 1 Refe
efert
-- 02 -- --511-7 0014 268
R
--
Refer -- -- B -- --
Refe
1
R
Re
-- 03 -- --511-6 0013 268 -- R
e
-- -- B -- --
R
1 -- 05 -- --0011 268 -- -- -- B -- -- 1 -- 02 -- --
511-5 0038 268 2 -- -- B -- -- 1 -- 02 -- --511 50099 268 2 -- -- B -- -- 1 -- 02 -- --
511-4 0037 268 -- -- -- B -- -- 1 -- 02 -- --511-3 0007 268 P -- -- B -- -- 1 -- 01 -- --
511 20002 268 -- -- -- B -- -- 1 -- 00 -- --
511-20017 268 P -- -- B -- -- 1 -- 00 -- --
511 10001 268 P -- -- B -- -- 1 -- 00 -- --
511-10062 268 P -- -- B -- -- 1 -- 00 -- --
32T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
Battery
Dehumidificatio
n
ControlB
ox
Temperature
Readout
Pressure
Readout
USDA/PROBE
Interrogator
Rem
ote
Monito
ring
Communications
Compressor
CondenserCoil
Autotransform
er
Temperature
Recorder
Gutters
Handles
Thermometer
Port
Water
Cooling
BackPanels
Controlled Atmosphere Units489-105 0834 305 R X C -- -- D 2 -- P 1R 3 -- -- -- 1 -- P 4489-104 0858 305 R X C -- -- D 2 -- 1 1R 3 -- -- -- 1 -- P 4489-103 0733 305 R X C -- -- D 2 -- 1 1R 3 1 -- -- 1 -- P 4
0431 305 R X A -- -- V 2 -- 3 1R 4 -- -- -- 1 -- P 60479 305 R X A -- -- D 2 -- P 1R 4 -- -- -- 1 -- P 4
489-101 0545 305 R X A -- -- D 2 -- P 1R 3 -- -- -- 1 -- P 4489 1010590 305 R X C -- -- D 1 -- 1 1R 3 1 -- -- 4 -- P 40653 305 R X C -- -- D 1 -- 1 1R 3 1 -- -- 4 -- P 4
489 1000412 305 R X AL -- G V/2 4 -- 1 1R 4 -- -- -- 1 -- F 4
489-1000671 305 R X CL -- G V/2 4 -- 1 1R 3 1 -- -- 4 -- F 4
33 T-300 Rev B
OPTION TABLE
MODEL(69NT40--)
PID(NT--)
ManualNumber
(T--)
460Vo
ltCable
230Vo
ltCable
CableRestraint
Upper
Air
Lower
Air
Controlled
Atm
osphere
Arctic
Mode
CondenserGrille
Humidificatio
n
Power
Correctio
n
Evaporator
EvaporatorFan
Labels
PlateSet(Refer
toPara1.3.31)
PlateSet
--CA
79--01698--
Controller
Stepper
Drive
Emergency
Bypass
Controlled Atmosphere Units489-105 0834 305 1 -- P 2 1 E -- H X -- 2 1 6 014 64 57 X --489-104 0858 305 1 -- P 2 1 E -- H X -- 2 1 2 014 64 57 X --489-103 0733 305 1 -- P 2 1 E -- H -- -- 2 1 2 192 56 57 X --
0431 305 2 -- 3 2 1 E -- H X -- 2 1 2 391 36 57 X --0479 305 1 -- P 2 1 E -- H X -- 2 1 2 391 36 57 X --
489-101 0545 305 1 -- P 2 1 E -- H X -- 2 1 2 391 56 57 X --489 1010590 305 1 -- P 2 1 E -- H X -- 2 1 2 621 56 57 X --0653 305 1 -- P 2 1 E -- H X -- 2 1 2 052 56 57 X --
489 1000412 305 2 -- 3 1 1 E -- H -- -- 2 1 2 311 36 56 X --
489-1000671 305 2 -- P 2 1 E -- H X -- 2 1 2 042 56 56 X --